RC (06-2675)51025 Avenida Mendoza Ste 102
06-2675
P.O. BOX 1504
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
Application Number: 06-000026751
Property Address: `51025 AVENIDA MENDOZA
APN: 773-073-012- -
Application description: REMODEL - COMMERCIAL
Property Zoning: VILLAGE COMMERCIAL
Application valuation: 10000
• VINW
BUILDING & SAFETY DEPARTMENT
BUILDING PERMIT
Owner:
STE 102 PATRICK & MONICA ADAMS
- 45795 PUEBLO ROAD
LA QUINTA, CA 92253
Applicant: Architect or Engineerr'
kl ur G4;7z!s rr l
c //"/ '
Contractor:
Owner 00,
VOICE (760) 777-7012
FAX (760) 777-7011
INSPECTIONS (760) 777-7153
Date: 8/31/06
SEP 2 0 1006 D
CITY OF (q QUI
F/MA1e^e ___ NrA
------------------------------------------------------------------------------------------
LICENSED CONTRACTOR'S DECLARATION WORKER'S COMPENSATION DECLARATION CLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter 9 (commencing with I hereby affirm under penalty of perjury one of the following declarations:
Section 7000) of Division 3 of the Business and Professionals Code, and my License is in full force and effect. - _ I have and will maintain -a certificate of consent to self -insure for workers' compensation, as provided
License Class: License No.: for by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued.
Date:' Contractor: _ 1. have and will maintain workers' compensation insurance, as required by Section 3700 of the Labor
Code, for the performance of the work for which this permit is issued. My workers' compensation
OWNER -BUILDER DECLARATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State License Law for the
following reason (Sec. 7031.5, Business and Professions Code: Any city or county that requires a permit to
construct, alter, improve, demolish, or repair any structure, prior to its issuance, also requires the applicant for the
permit to file a signed statement that he or she is licensed pursuant to the provisions of the Contractor's State
License Law (Chapter 9 (commencing with Section 7000) of Division 3 of the Business and Professions Code) or
that he or she is exempt therefrom and the basis for the alleged exemption. Any violation of Section 7031.5 by
any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500).:
(_) I, as owner of the property, or my employees with wages as their sole compensation, will do the work, and
the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The
Contractors' State License Law does not apply to an owner of property who builds or improves thereon,
and who does the work himself or herself through his or her own employees, provided that the
improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner -builder will have the burden of proving that he or she did not build or
improve for the purpose of sale.). '
(_) I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec.
7044, Business and Professions Code: The Contractors' State License Law does not apply to an owner of
property who builds or improves thereon, and who contracts for the projects with a contractor(s) licensed
pursuant to the Contractors' State License Law.).
I _ 1 I am exempt under Sec. , B.&P.C. for this reason
Date: / —/'1'06 Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for the performance of the
work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's Name:
Lender's Address:
LQPERAIIT
insurance carrier and policy number are:
Carrier Policy Number
I certify that, in the performance of the work for which this permit is issued, I shall not employ any
person in any manner so as to become subject to the workers' compensation laws of California,
and agree that, if I should become subject to the workers' compensation provisions of Section
3700 of the Labor Code, 1 II f rthw h co Iy v ith those provisions.
Nater `Applicant:
y WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS UNLAWFUL, AND SHALL
SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO ONE HUNDRED THOUSAND
DOLLARS 15100,000). IN ADDITION TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN
SECTION 3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT Application is hereby made to the Director of Building and Safety for a permit subject to the
conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose request and for
whose benefit work is performed under or pursuant to any permit issued as a result of this application,
the owner, and the applicant, each agrees to, and shall defend, indemnify and hold harmless the City
of La Quinta, its officers, agents and employees for any act or omission related to the work being
performed under or following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is not commenced
within 180 days from date of issuance of such permit, or cessation of work for 180 days will subject
permit to cancellation.
I certify that I have read this application and state that the above information is correct. I agree to comply with all
city and county ordinances and state laws relating to building construction, and hereby autone, presentatives
of this c o%unty to a/n'ter upon the above-mentioned property for iryg 'on purpose .
Date: / ' " C.Signature (Applicant or Agent): ( 4 I
Application Number . . . . 06-00002675
Structure Information T.I. IN EXISTING SHELL BLDG.SUITE 102
Other struct info . . . . . CODE EDITION
01/04/05
FIRE SPRINKLERS
YES
MIXED-USE OCCUPANCY
B
OCCUPANT LOAD
10.00
1ST FLOOR SQUARE FOOTAGE
----------------------------------------------------------------------------
924,00
Permit BUILDING PERMIT - ADA INV.FEE
Additional desc .
Permit Fee . . . . 234.00 Plan Check Fee
76.05
Issue Date . . . . Valuation . .
. . 10000
Expiration Date 2/27/07
Qty Unit Charge Per „
Extension
BASE FEE
90.00
8.00 18.0000 THOU 'BLDG 2,001-25,000
----------------------------------------------------------------------------
144.00
Permit ELEC-MISCELLANEOUS INV FEE
Additional desc*.'.
Permit Fee . . . . 64.50 Plan Check Fee
8.06
Issue Date . . . Valuation
0
Expiration Date 2/27/07
Qty Unit Charge Per
Extension
BASE FEE
30.00
20.00 1.5000 PER ELEC DEVICE/FIXTURE 1ST 20•
30.00
5.00 .9000 EA ELEC DEVICE/FIXTURE >20
- ----------------------------------------------------------------------------
4.50
Permit . . . MECHANICAL INV FEE
Additional desc .
Permit Fee 102.00 Plan Check Fee
12.75
Issue Date . . . . Valuation . .
0
Expiration Date 2/27/07
Qty Unit Charge Per
Extension
BASE FEE
30.00
8.00 9..0000 EA MECH VENT INST/ DUCT ALT
72.00
q ----------------------------------------------------------------------------
Special Notes and Comments
924 SF. TENANT IMPROVEMENT "SUITE 2B -
`' LAWYER'S OFFICE", "B"OCCUPANCY, TYPE
V-N.CONSTRUCTION, 10 OCCUPANT LOAD.
2001 CBC,CMC,2004 CEC.,2005 ENERGY
CODES. **NOTE:WORK DONE WITHOUT
LQPERi%HT
Application Number . . . . . 06-00002675
-----------------------
Special Notes and
--------------------
Comments
-------
------------
--------------
PERMIT -A.. MORENO CODE
OFF.
INVESTIGATION FEES
ASSESSED PER CBC
107.5.2**
August 30, 2006 2:29:00
----------------------------------------------------------------------------
PM bhanada
Other Fees .. . .
. . . . . ACCESSIBILITY
PLAN REVIEW
7.61
ENERGY
REVIEW
FEE
7.61
r
STRONG
MOTION
(SMI) - COM
2.10
Fee summary
Charged Paid
Credited
Due
-----------------
- - - - - - - - - - - - - - - - -
- - - - -
- - - - - - - - ----------
---------Permit
Permit Fee Total
400.50
.00
.00
400.50
Plan Check Total
96.86
.00
.00
96.86
Other Fee Total
17.32
.00
.00
17.32
Grand Total
514.68
.00
.00
514.68
04
LQPERDIIT
C1,9,gc Do Nf %fie riS MW T %c A,-1 /VWrL UA."I..1
0
City. of La Quints
Building 81 Safety Division
P.O. Box 1504, 78-495 Calle Tampico
La Quinta, CA 92253 - (760) 777-7012
Building Permit Application and Tracking Sheet
:'er mit #
G Z
Project Address: t—.J U r Tie p-R
Owner's Name: Cll
A. P. Number:
Address: L
Legal Description:
City, ST, Zip: aA&C) ►vL
Contractor: t Y
Telephone:
Address:
Project Description:
City, ST, Zip:
`"01 r,
Telephone:
State Lic. # :
City Lic. #:
b
Arch., Engr., Designer:
Address:
City, ST, Zip:
Telephone:
State Lic. #:
Name of Contact Person: L, j, r
Construction ipg1o" Occu anc
P Y-
Project type Acle one): New Add'n Alter Repair Demo
Sq. Ft.: # Stories: # Units:
Telephone # of Contact Person: Cj Z' L4 8 Q
Estimated Value of Project:
APPLICANT: DO NOT WRITE BELOW THIS LINE
#
Submittal
Req'd
Rec'd
TRACKING.
PERMIT FEES
. Plan Sets
Plan Check submitted 7/y
Item
Amount
Structural Calcs.
Reviewed, ready for corrections
Plan Check Deposit
Truss Calcs.
Called Contact Person
Plan Check Balance
Energy Calcs.
l l
Plans picked up
Construction
Flood plain plan
Plans resubmitted
Mechanical
Grading plan
2nd Review, ready fo correction issueElectrical
Subcontactor List
Called Contact Person 'i
'Plumbing
Grant Deed
Plans picked up
S.M.I.
H.O.A. Approval
Plans resubmitted
Grading
IN HOUSE:-
'"' Review, ready for corrections/ ssueq'
Developer Impact Fee
Planning Approval
Called Contact Person `
A.I.P.P.
Pub. Wks. Appr
Date of permit issue
School Fees
Total Permit Fees
0s '4
G✓ovod
OD >P
John R. Hawkins
Fire Chief
Proudly serving the
Unincorporated
Areas of Riverside
County and the
Cities of:
Banning
Beaumont
Calimesa
Canyon Lake
e•
Coachella
Desert Hot Springs
Indian Wells
Indio
Lake Elsinore
La Quinta
Moreno Valley
Pam Desert
Perris
Rancho Mirage
4 -
San Jacinto
.;.
Temecula
Board of Supervisors
Bob Buster,
District 1
John Tavaglione,
District 2
Jim Venable,
District 3
Roy Wilson,
District 4
Marion Ashley,
District 5
RIVERSIDE COUNTY FIRE DEPARTMENT
In cooperation with the
California Department of Forestry and Fire Protection
210 West San Jacinto Avenue • Perris, California 92570 •"(909) 940-6900 • Fax (909) 940-6910
August 30, 2006
Patrick & Monica Adams
51025 Avenida Mendoza
La Quinta, CA 92253
RE: TENANT IMPROVEMENT PLAN CHECK
LAQ-06-TI-069 / Patrick & Monica Adams at 51025 Avenida Mendoza,
La Quinta, CA
You have been issued a release for a'tenant improvement on an existing building. THIS IS
NOT AN OCCUPANCY PERMIT.
It is prohibited to use/process or store any materials in this occupancy that would classify it
as an "H" occupancy per Sec. 307 of the 2000 UBC.
THE FOLLOWING CONDITIONS MUST BE MET PRIOR TO INSPECTION:
Install door hardware and exit signs as per Chapter 10 of the 2000 UBC.
Install Knox Lock Boxes, Models 4400, 3200 or 1300, mounted per recommended standard
of the Knox Company. Plans must be submitted to the Fire Department for approval of
mounting location/position and operating standards. Special forms are available from this
office for the ordering of the Key Lock Boxes. This form must be authorized and signed by
this office for the correctly coded system to be purchased. If the building/facility is protected
with a fire alarm system or burglar alarm system, the lock boxes will require "tamper'
monitoring.
A minimum 2A10BC Fire Extinguisher, (State Fire Marshal Approved) must be mounted in a
visible location within 75' walking distance from any point in your building or suite. Fire
extinguishers can be installed by a licensed extinguisher company with a State Fire Marshal
service tag attached to the extinguisher, or purchased from a retail store with a sales receipt
attached. A licensed fire extinguisher company must service extinguisher yearly.
ELECTRICAL PANEL BOX:
All breakers must be labeled and a clearance of 36 inches must be maintained around the
panel at all times.
OTHER REQUIREMENTS.
Approved building address shall be placed in such a position a to be plainly visible and
legible from the street. Said numbers shall contrast with their background.
A durable sign stating 'This door to remain unlocked during business hours" shall be placed
on or adjacent to the front exit door. The sign shall be in letters not less than one inch high
on a contrasting background.
EMERGENCY SERVICES DIVISION • PLANNING SECTION • INDIO OFFICE
82-675 Highway 111, 2nd FI., Indio, CA 92201 • (760) 863-8886 • Fax (760) 863-7072
Applicantlinstaller shall be responsible to contact the Fire Department to schedule
inspections. A re -inspection fee will be required if more than one (1) inspection is necessary.
Requests for inspections are to be made at least 72 hours in advance and may be arranged
by calling (760) 863-8886.
All questions regarding the meaning of these conditions should be referred to the Fire
Department Planning & Engineering Staff at (760) 863-8886.
Sincerely,
Tracy Hobday
Chief Fire Department Planner
BY:
Sonia Cooley
Cc: City of La Quinta Fire Safety Specialist __..
Certificate of Occu anocY
oF9ti5 Building & Safety Department
i ..
This Certificate is issued pursuant to the requirements of Section 109 of the California Building
Y
Code, certifying that, at the time of issuance, this structure was in compliance with the
provisions of the Building Code and the various ordinances of the City regulating building
construction and/or use.
BUILDING ADDRESS: 51-025 AVENIDA MENDOZA, STE. 102
Use classification: OFFICE Building Permit No.: 06-2675
Occupancy Group: B Type of Construction: V-N Land Use Zone: VC
t
Owner of Building: PATRICK & MONICA ADAMS Address: 45795 PUEBLO ROAD
City, ST, ZIP: INDIAN WELLS, CA 92210
By: KIRK KIRKLAND
f
Date: NOVEMBER 1, 2006
Building Official
POST IN A CONSPICUOUS PLACE
TITLE 24 REPORT
Title 24 Report for:
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg.
51-025 Avenida Mendoza;
La Quinta, CA
Project Designer:
U
Report Prepared By:
Marc Farmer `
Energy and Duct Systems
40492 Clark Drive
Hemet, CA 92544
(951) 925-0100 - - -
A RE• INSPECTI(M FEg OF 3U
WILL. 6E CHARGED IF THE APPROM
PLANS AND 108 CARD ARE NOT ON
THE SITE FOR A SCHEDL%d Epi
INSPECTION,
Job Number:- NOMWON0,
03-135 CITY OF LA QUINTA
BUILDING & SAFEIY DEPT.
FOR Date. R CONSTRUCTION
8/14/2006 oA
O(o -ZG7S-
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.2 by EnergySoft Job Number: 03135 User Number: 1268
TABLE OF CONTENTS
Cover Page 1
Table of Contents 2.
Nonresidential Performance Title 24 Forms _ 3
Form ENV -MM Envelope Mandatory Measures ", • _ . 15
Form LTG -MM Lighting Mandatory Measures 16
Form MECH-MM Mechanical Mandatory Measures 17
HVAC System Heating and Cooling Loads Summary 19
EnergyPro 4.2 by EnergySoft Job Number: 03135 User Number: 1268
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1
PROJECT NAME
DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg.
8/14/2006
PROJECT ADDRESS
DATE OF PLANS
51-025 Avenida Mendoza La Quinta
' >.
a
PRINCIPAL DESIGNER - ENVELOPE
TELEPHONE
Budding permit # -
DOCUMENTATION AUTHOR
Energy and Duct Systems
TELEPHONE
(951) 925-0100
Checked by/Date
E forcerri'entAgenovUse
GENERAL INFORMATION
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
DATE OF PLANS
DATE
Marc Farmer
BUILDING CONDITIONED FLOOR AREA
924 Sq.Ft.
he Principal Designer hereby certifys that the proposed building desi n represented In this set of construction documents is
CLIMATE ZONE
15
BUILDING TYPE
®
NONRESIDENTIAL HIGH RISE RESIDENTIAL
E]
HOTELIMOTEL GUEST ROOM
PHASE OF CONSTRUCTION
E]
NEW CONSTRUCTION ADDITION
®
EXISTING + ADDITION/ALTERATION
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
SIGNATURE
DATE
Marc Farmer
—
he Principal Designer hereby certifys that the proposed building desi n represented In this set of construction documents is
consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with thi
permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
0 ❑ ❑ 1.1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, or I am a licensed architect.
❑ El El 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
7 F-1 0 3.1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in
full in the Nonresidential Manual.)
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
ENVA
Required Forms
PR CIPAL ENVELOPE DESIGNER - NAME
7
SIGNA
LIC. NO.
DATE
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
LTG -1,- LTG -2
Required Forms
PRINCIPAL LIGHTING DESIGNER - NAME --TSIGNATURE
LIC. NO.
DATE
MECHANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
MECH-1 MECH-2 MECH-3 MECH-5
Required Form's
PRINCIPAL MECHANICAL DESIGNER - NAME
SIGNATURE
LIC. NO.
DATE
I Run Initiation Time• 08114/06 5.16.6 Run Code; 1155593806
EnergyPro 4.2 by EnergySoft User Number: 1268 Job Number: 03135 Page:3 of 19
j
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF
PROJECT NAME DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg. 8/14/2006
ANNUAL TDV ENERGY USE SUMMARY
kBtuls ft- r
Conditioned Floor Area
Unconditioned Floor Area
Conditioned Footprint Area
Fuel Type
924
sgft.
sgft.
sgft.
Standard
Proposed
Compliance
924
ENERGY COMPONENT
Design
Design
Margin
[N stsndsro _._-_ Proposed - .. _
Space Heating
0.18
sgft.
78
0.18
0.00
Rear Elevation S
400
Space Cooling
254.48
sgft.
18.0%
254.45
0.03
SDM C-"
sqft.
481
sgft.
Indoor Fans
38.47
Total
1,om
38.47
0.00
sgft.
Heat Rejection
0.00
sqn.
0
0.00
0.00
Pumps & Misc.
0.00
0.00
0.00
""'s`""`
Domestic Hot Water
18.07
18.07
0.00
Lighting
79.61
79.54
0.07
`
Receptacle
91.54
91.54
0.00
Process
o.o0
0.00
0 20 40 60 80 100120140160180 200 220240
TOTALS: 482.35
Percent better than Standard:
Aflh ' LC
0.0% ( 0.0%
0.10
Building Orientation
Number of Stories
Number of Systems
Number of Zones
N 0 deg
Conditioned Floor Area
Unconditioned Floor Area
Conditioned Footprint Area
Fuel Type
924
sgft.
sgft.
sgft.
1
0
1
924
11
Natural Gas
sgft.
0.0%
Orientation
Gross Area
Glazing Area
Glazing
Ratio
Front Elevation N
o
sgft.
0
sgft.
0.0%
Left Elevation E
312
sgft.
78
sgft.
25.0%
Rear Elevation S
400
sgft.
72
sgft.
18.0%
Right Elevation (W)l
310
sqft.
481
sgft.
15.5%
Total
1,om
sgft.
198
sgft.
Roof
0
sqn.
0
sgft.
o.o%
Standard Proposed
Lighting Power Density 1.200 W/sgft. 1.199 W/sgft.
Prescriptive Env. Heat Loss 177 Btu/h 233 Btu/h
Prescriptive Env. Heat Gain 19,717 Btu/h-F 21,671 Btum-F
Remarks:
I EnergyPro 4.2 by EnergySoft User Number: 1268 Job Number: 03135 Page:4 of 19
`e
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1
(PROJECT NAME DATE
924 Sq. Ft. 1 I. Avenida Mendoza Commercial Bldq. 8/14/2006
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Signature or
EnergyPro 4.2 by EnergySoft User Number. 1268 Job Number: 03-135 Paae:5 of 19 1
CERTIFICATE OF COMPLIANCE ENV -1-C
PROJECT NAME DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg. 8/14/2006
OPAQUE SURFACES
aEMORM,
IType
M
Area U -Fac'
Kq-TW6=lIIIEM
Act.
Azm.
Cond.
Stat.
Glazing Type
Location/
Comments
I Comments
Window
Left E
42 0.720 NFRC
0.40 NFRC
90
Existing
Double Mtl Low E(2)
1st Floor 924 Sq. Ft.
2
Window
1 st Floor 924 Sq. Ft.,Location
36 0.720 NFRC
0.40 NFRC
90
Existing
Double Mtl Low E(2)
1 st Floor 924 Sq. Ft.
3
Window
Rear S
72 0.720 NFRC
I st Floor,424 Sq.
180
Existing
Double Mtl Low E(2)
1 st Floor 924 Sq. Ft.
4
Window
Right
48 0.720 NFRC
0.40 NFRC
270
1 st Floor 924 Sq. Ft.
Double MN Low E(2)
1st Floor 924 Sq. Ft.
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
N. E, A, R (New, Existing, Altered, Removed)
FENESTRATION SURFACES
FMore than or equal to 10,000 sq.fL of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U -factors from
Jf Standards Table 116-A and B. Certificate shall be filed in the contractors project office during construction and in the building managers office after construction
#
IType
Area U -Fac'
SHGC2
Act.
Azm.
Cond.
Stat.
Glazing Type
Location/
Comments
1
Window
Left E
42 0.720 NFRC
0.40 NFRC
90
Existing
Double Mtl Low E(2)
1st Floor 924 Sq. Ft.
2
Window
Left E
36 0.720 NFRC
0.40 NFRC
90
Existing
Double Mtl Low E(2)
1 st Floor 924 Sq. Ft.
3
Window
Rear S
72 0.720 NFRC
0.40 NFRC
180
Existing
Double Mtl Low E(2)
1 st Floor 924 Sq. Ft.
4
Window
Right
48 0.720 NFRC
0.40 NFRC
270
Existing
Double MN Low E(2)
1st Floor 924 Sq. Ft.
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
1 U -tactor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
## Exterior Shade Type
SHGC
Window
Hgt. Wd.
Overhang Left Fin Right Fin
Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
1 None
0.76
7.0 6.0
6.0 0.1 6.0 6.0
2 None
0.76
6.0 6.0
6.0 0.1 6.0 6.0
3 None
0.76
4 None
0.76
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
1:1The proposed building contains an enclosed space with flow area greater than 25,000 s%f% a ceiling height greater than 15 feet and a LPD for general lighting of at least 0.5 Wlsq.ft. If this
box Is checked, ENV- -C must be filled out when submitting under the Prescriptive Compliance Approach.
EnergyPro 4.2 by EnergySoft User Number: 1268 Job Number: 03-135 Paae:6 of 19 1
CERTIFICATE OF COMPLIANCE (Part 1 of 3) LTG -1-C
1
PROJECT NAME DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg. 8/14/2006
INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -5-C) ALLOWED
❑ AREA CATEGORY METHOD (From LTG -6-C) WATTS
❑ TAILORED METHOD (From LTG -6-C) ALLOWED LIGHTING POWER F 1,108
ALTERNATE COMPLIANCE
❑X PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION
(Room #)
CONTROL
IDENTIFICATION
CONTROL TYPE
(Auto Time Switch, Dimming, etc.)
SPACE CONTROLLED
Check if
NOTE .TO:
FIELD
INSTALLED
WATTS
INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C)
1,108
PORTABLE LIGHTING (From LTG -3-C)
0
LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG4-C)
0
CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER
1 1,108
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -5-C) ALLOWED
❑ AREA CATEGORY METHOD (From LTG -6-C) WATTS
❑ TAILORED METHOD (From LTG -6-C) ALLOWED LIGHTING POWER F 1,108
ALTERNATE COMPLIANCE
❑X PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION
(Room #)
CONTROL
IDENTIFICATION
CONTROL TYPE
(Auto Time Switch, Dimming, etc.)
SPACE CONTROLLED
Check if
NOTE .TO:
FIELD
ERTIFICATE OF COMPLIANCE (Part 3 of 3) LTG-1 -C
PROJECT NAME
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg.
DATE
8/14/2006
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance
tests for lighting systems. The designer is required to check the boxes by all acceptance tests that
apply and list all equipment that require an acceptance test. If all equipment of a certain type requires
a test, list the equipment description and the number of systems to be tested in parentheses. The NJ
number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the
test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design
professional or an agent selected by the owner). Since this form will be part of the plans, completion
of this section will allow the responsible party to budget for the scope of work appropriately.
Building Departments:
Before an occupancy permit is granted for a newly constructed building or space, or a new lighting
system system serving a building or space is operated for normal use, all control devices serving the
building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building department
that: '
A. Certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of §10-103(b) and Title 24 Part 6.
Test Description
Test Performed By:
❑ LTG-2-A: Lighting Control Acceptance Document
- Occupancy Sensor Acceptance
- Manual Daylight Controls Acceptance
- Automatic Time Switch Control Acceptance
Equipment requiring acceptance testing
❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing
EnergyPro 4.2 by EnergySoft User Number: 1268 Job Number: 03135 Page:8 of 19 1
I
CERTIFICATE OF COMPLIANCE MECH-1-C
NAME
924 Sa. Ft. T. I. Avenida Mendoza Commercial Blda.
DATE
Designer:
This form is to be used by the designer and attached to the plans. listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates. and ooeratina and maintenance information meet the requirements of Section 10-103(b) and Title 24 Part 6.
STATEMENT OF COMPLIANCE
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Relrofit.
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on a// New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do require construction Inspection.
❑ MECH5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required N the unit serves 4000112 of space or lass and 25% or more of the ducts are In nonconditioned or semkonditloned space like an
attic. New systems that meet the above requirements. Rett systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VAV fan volume controls installed on new or existing systems must be tested
❑ MECH-8-A:-Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new toilers and chillers and the pilmary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500, 000 Btu/hr.
-Water-loop Heat Pump Controls
Applies to all new waterfoop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilkec( hydronic heat pump
or condenser water systems where the primps motors are greater than 5 hp.
Equipment requiring acceptance testing
EnergyPro 4.2 by EnergySoft User Number: 1268 Job Number: 03-135 Page:9 of 19
INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG -2-C
PROJECT NAME DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg. 8/14/2006
INSTALLED LIGHTING POWER FOR CONDITIONED SPACES
Luminaire
Lamps/Ballasts
Installed Watts
C
D
E
F
G
H
I
J
Name
Type Description
d
N'3
cdc
3.33
FNM
m
0)
3
cW
3w3
Of~
fD '
c
3
5
01
`e
O
m5.0
C0
r
Z
'o-
Q
L)` y►
vViN
a
(1) 2 ft Fluorescent T8 Elec
1
17
1.0
22.0
X
1
22
(1) 22w Compact Fluorescent Quad 2 Pin
2
1.0
0
X
31
81
(1) 9w Compact Fluorescent Quad 2 Pin
-21
1
9
1.0
13.0
X
1
13
(4) 4 ft Fluorescent T8 Elec
328
4
32
1.0
114.0X
8
912
40w Wall Mount Incandescent
00
8
PAGE TOTAL 1 108
BUILDING TOTAL (sum of all pages) 1 ,108
PORTABLE LIGHTING (From LTG -3-C) O
CONTROL CREDIT (From LTGd-C) Q
ADJUSTED ACTUAL WATTS 1 108
Run Initiation Time: 08/14/0615:16:46 Run Code: 1155593806
EnergyPro 4.2 by EnergySoft User Number: 1268 Job Number: 03.135 Page: 10 of 19
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
r
PROJECT NAME DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg. 8/14/2006
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
AIR SYSTEMS, Central or Single Zone
924 Sq.ft. Office HVAC
Sy tem
Reference on Plans or Specification 1
112(a)
80% AFUE
112(a)
12.0 SEER / 11.2 EER
112(b)
n/a
112(c), 115(a)
n/a
121(b)
Yes
121(b)
139 cfm
121 c
No
121(c)
No
121 c 122(el
Programmable Switch
122(e)
Heating & Cooling Required
122
Auto
122(8)
n/a
123
124
R-4.2
144 a & b
n/a
144 a & b
51,000 btuh
144 a & b
n/a
144 a & b
18,930 btuh
144 c
Constant Volume
144 (c)
144 c
Yes
144 d
No
144 a
No Economizer
144
Constant Tem
144 (f)
Constant Temp
144 (k)
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. if a requirement is not applicable, put "NIN' in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method dud sealing requirements.
WATER SIDE SYSTEM REQUIREMENTS Part 2 of 2 MECH-2-C
PROJECT NAME DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg. 8/14/2006
[SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section Reference on Plans or Specification'
Equipment Efficiency 112(a)
Pipe Insulation 123
PRESCRIPTIVE MEASURES
Calculated Capacity
Proposed Capacity
Tower Fan Controls
Tower Flow Controls
Variable Flow System Design
Chiller and Boiler Isolation
CHW and HHW Reset Controls
WLHP Isolation Valves
VSD on CHW, CW & WI -HP Pumps > 6
HP
DP Sensor Location
1: For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph
number where the required features are documented. 11 a requirement is not applicable, put -NIA- in the column.
2: Water side systems include wet side system using other liquids such as glycol or brine.
Service Hot Water, Pool Heating
ITEM OR SYSTEM TAG(S) DHW Heater
Number of Systems 1
MANDATORY MEASURES Reference on Plans or Specification'
Water Heater Certification
Water Heater Efficiency
Service Water Heating Installation
Pool and Spa Efficiency and Control
Pool and Spa Installation
Pool Heater - No Pilot Light
Spa Heater - No Pilot Light
113 (a
113 b
113 c)
114(a)
114(b)
115 (c)
115 d
CHRONOMITE LABS MF -
200C W40VAC
n/a
n/a
n/a
n/a
1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and
paragraph number where the required features are documented. If a requirement is not applicable, put'N/A7 ins the column.
Run Initiation Time: 08/14/0615:16:46 Run Code: 1155593806
EnergyPro 4.2 by EnergySoft User Number: 1268 Job Number: 03-135 Page: 12 of 19
MECHANICAL VENTILATION MECH-3-C
PROJECT NAME DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldq. I
8/14/2006
PRESCRIPTIVE REHEAT
LIMITATION Section 144(d))
MECHANICAL VENTILATION Section
121 (b)2)
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
ZONEISYSTEM
A
Z;>:3
Amo
3
.0
o`iyA
a1o
c 3
»
W,5
xD
Ami
Z
m3
oQ
mo
m-aA
inm
Cr
mp3
x
-
_ ;
Omp
oxp
Q»<
D
<
Aim
-1 .. v+
3DB
Oe
nm o,
-60
m
c
T
3X
in
ap
OS
w3m
3x
0. 0_+
C_
V)w
v
w'3
D
ui
D
1 st Floor 924 Sq. Ft.
924
0.15
139
139
139
924 Sq.ft. Office HVAC System
Total
139
139
C Minimum ventilationte rar Section 121 Table 121-A
E Based on Pored seat or the greater of the expected number of occupants and 50% of the CBC occupant load for egress purposes for spaces without fixed seating.
H Required Ventilation Air REO'D V.A. Is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G).
I Must be greater than or equal to H or use Transfer Air column N to make up the difference.
J Design fan supply cfm (Fan CFM) x 30%; or
K Condition area ft s x 04 cfm/ft sq.; or
L Maximum of Columns H, J, K, or 300 dm
M This must be less than or equal to Column L and greater that or equal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column H) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or
equal to the difference between the Required Ventilation Air (column H) and the Design Minimum Alr (column M), column H - M.
Ener Pro 4.2 by Ener ft User Number: 1268 Job Number: 03-135 Page: 13 of 19
MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-5-C
", PROJECT NAME DATE
924 So. Ft. T. I. Avenida Mendoza Commercial_BIdQ. _ 8/14/2006
CHILLER AND TOWER SUMMARY
Efficiency
Tons
PUMPS
Equipment Name
Equipment Type
Qty.
Tot.
Qty
GPM
BHP
Motor
Eff.
Drive
Eff.
Pump
Control
1
1DHW I BOILER SUMMARY
Energy Standby IIANKINbUL.
Rated Vol. Condition Factor Loss or I Ext.
System Name System Type Distribution Type Qty Input (Gals.) Status or RE I Pilot R -Val.
CHRONOMITE LABS MF- Instant Elec No Pi Insulation 1 31,400 0 Existing 0.98 n/a n/a
00C 220-240VAC nsug
Hot Water
r=
Hot Water Piping I
In Plenum I Outside
Add 1/2"
Buried Insulation
CENTRAL SYSTEM RATINGS
HEATING COOLING
Aux. Condition
System Name System Type Qtf Output kW Eff. Qu ut Efficiency Status Economizer Type
80%
n S E 12.0 SEEER 2-
1 t Split DX 1 51,000 0. 80% AFUE 29,40012.0 SEER/ 11.2 EER Existing No Economizer
ENVELOPE MANDATORY MEASURES ENV -MM
PROJECT NAME DATE
924 Sa. Ft. T. I. Avenida Mendoza Commercial Blda. 1 8/14/2006
DESCRIPTION
Designer
Enforcement
0 § 118(a) Installed Insulating Material shall have been certified by the manufacturer to comply
with the California Quality Standards for insulating material, Title 20, Chapter 4, Article
3.
§118(c) All Insulating Materials shall be installed in compliance with the flame spread rating
and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2.
X] § 117(a) All Exterior Joints and openings in the building that are observable sources of air
leakage shall be caulked, gasketed, weatherstripped or otherwise sealed.
§116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit
and the building, and shall be weatherstripped (except for unframed glass doors and
fire doors).
X❑ § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not
exceeding those shown in Table Number 1-E. of the Standards. Manufactured
fenestration products must be labeled for U -value according to NFRC procedures.'
FX §118(e) Demising Walls in Nonresidential Buildings;
The opaque portions of framed demising walls in nonresidential buildings shall have
insulation with an installed R -value of no less than R-13 between framing members.
EnergyPro By EnergySoft User Number: User Job Number: 03-135 Page: 15 of 19
LIGHTING MANDATORY MEASURES LTG -MM
PROJECT NAME DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg. 8/14/2006
DESCRIPTION
Designer
Enforcement
§131(d)1 For every floor, all interior lighting systems shall be equipped with a separate automatic
control to shut off the lighting. This automatic control shall meet the requirements of
Section 119 and may be an occupancy sensor, automatic time switch, or other device
capable of automatically shutting off the lighting.
§131(d)2 Override for Building Lighting Shutoff: The automatic building shutoff system is
provided with a manual, accessible override switch in sight of the lights. The area
of override is not to exceed 6,000 square feet.
§119(h) Automatic Control Devices Certified: All automatic control devices specified are
certified, all alternate equipment shall be certified and installed as directed by the
manufacturer.
§111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for
the project are certified and listed in the Directory. All installed fixtures shall be
certified.
§132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three
lamp fluorescent fixtures are tandem wired with two lamp ballasts where required
by Standards Section 132; or all one and three lamp fluorescent fixtures are
specified with electronic high -frequency ballasts and are exempt from tandem
wiring requirements.
XJ §131(a) Individual Room/Area Controls: Each room and area in this building is equipped
with a separate switch or occupancy sensor device for each area with floor -to -
ceiling walls.
0 §131(b) Uniform Reduction for Individual Roans: All rooms and areas greater than 100
square feet and more than 0.8 watts per square foot of lighting load shall be
controlled with bi-level switching for uniform reduction of lighting within the room.
§131(c) Daylight Area Control: All rooms with windows and skylights that are greater than
260 square feet and that allow for the effective use of daylight in the area shall
have 60% of the lamps in each daylit area controlled by a separate switch; or the
effective use of daylight cannot be accomplished because the windows are
continuously shaded by a building on the adjacent lot. Diagram of shading during
different times of the year is included on plans.
® §131(e) Display Lighting. Display lighting shall be separately switched on circuits that
are 20 amps or less.
EnergyPro 4.2 by EnergySoH User Number: 1268 Job Number: 03-135 Page: 16 of 19
MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
PROJECT NAME DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg. 8/14/2006
DESCRIPTION
Designer
Enforcement
Equipment and Systems Efficiencies
0 §111 Any appliance for which there is a California standard established in the Appliance
Efficiency Regulations will comply with the applicable standard.
n§ 115(a) Fan type central furnaces shall not have a pilot light.
a§ 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
a§ 124 Air handling duct systems shall be installed and insulated in compliance with
Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards.
Controls
§ 122(e) Each space conditioning system shall be installed with one of the following:
§ 122(e)1A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the requirements
of Section 112 (d)) shall be installed with an automatic time switch with an
accessible manual override that allows operation of the system during off -hours for +
up to 4 hours. The time switch shall be capable of programming different
schedules for weekdays and weekends and have program backup capabilities that
prevent the loss of the device's program and time setting for at least 10 hours if
power is interrupted; or
§ 122(e)1g An occupancy sensor to control the operating period of the system; or
F] § 122(e)1C A 4 -hour timer that can be manually operated to control the operating period of the
system.
a§ 122(e)2 Each space conditioning system shall be installed with controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint.
§ 122(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with isolation
zones. Each zone: shall not exceed 25,000 square feet; shall be provided with
isolation devices, such as valves or dampers, that allow the supply of heating or
cooling to be setback or shut off independently of other isolation areas; and shall
be controlled by a time control device as described above.
® § 122(a&b) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the control
shall be adjustable up to 85 degrees F or higher. Where used for both heating and
cooling, the control shall be capable of providing a deadband of at least 5 degrees
F within which the supply of heating and cooling is shut off or reduced to a
minimum.
§ 122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable
setpoint stops accessible only to authorized personnel.
§ 112(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
EnergyPro By EnergySoft User Number: User Job Number: 03135 Page: 17 of 19
MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM
PROJECT NAME DATE
924 Sa. Ft. T. I. Avenida Mendoza Commercial Bldq. I
8/14/2006
Descri
tion
Designer
Enforcement
Ventilation
❑X
§ 121(e)
Controls shall be provided to allow outside air dampers or devices to be operated at
the ventilation rates as specified on these plans.
§ 1220
Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air intakes and discharges of all space conditioning and
exhaust systems.
§ 14 0
All gravity ventilating systems shall be provided with automatic or readily accessible
manually operated dampers in all openings to the outside, except for combustion air
openings.
§ 121(f)1
Air Balancing: The system shall be balanced in accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
Associated Air Balance Council (AABC) National Standards (1989); or
FXJ
§ 121(f)2
Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the
installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the
person with overall responsibility for the design of the ventilation system; or
§ 121(f)3
Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
§ 121(f)4
Another method approved by the Commission.
Service Water Heating Systems
§ 113(b)2 if a circulating hot water system is installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water is not required.
§ 113(c)
Lavatories in restrooms of public facilities shall be equipped with controls to limit the
outlet temperature to 110 degrees F.
EnergyPro
By EnergySoft User Number: User Job Number: 03135 Page:18 of 19
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME
DATE
924 Sq. Ft. T. I. Avenida Mendoza Commercial Bldg.
8/14/2006
SYSTEM NAME
FLOOR AREA
924 S .ft. Office HVAC System
924
NGINEERING CHECKS
Number of Systems
0
Heating System
Output per System
51,000
Total Output (Btuh)
51,000
Output (Btuh/sgft)
55.2
Cooling System
Output per System
29,400
Total Output (Btuh)
29,400
Total Output (Tons)
2.5
Total Output (Btuh/sgft)
31.8
Total Output (sgft/Ton)
377.1
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
CFM
I Sensible
3,367
29,496
3,777
618
20,716
0
80%AFUE 12.0 SEEER 2-1/2 ton Sys 18,930 10,118 51,000
Total Adjusted System Output 18 930 10,118 51,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug3pml Jan 12 am
1,475
1,036
0
0
139
4,854
-835
139
6,377
10.9
0
0.15
0
1,475
1,036
37,301 2,94 29 165
Air System
HVAC EQUIPMENT SELECTION
80%AFUE 12.0 SEEER 2-1/2 ton Sys 18,930 10,118 51,000
Total Adjusted System Output 18 930 10,118 51,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug3pml Jan 12 am
CFM per System
1,270
Airflow (cfm)
1,270
Airtlow (cfm/sqft)
1.37
Airtlow (cfm/Ton)
518.4
Outside Air (01.)
10.9
Outside Air (cfm/sgft)
0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
(Airstream Temperatures at Time of Heating
Peak)
26.0°F 64.5°F
Outside Air
102.2 OF 102.2°F
O
Supply Air Ducts
139 cfm
Heating Coil Supply Fan
1270 cfm
101.50F
ROOMS
70.0 OF
69.2 OF
1114
-S Retum Air Ducts
I
:DOLING S
12.0 / 77.9 OF
out li
side Air
139 cfm
79.1/70.5 0 F
4stream Temperatures at Time o
82.7/71.4°F 68.7/66.5°F
Cooling Coil Supply Fa
1270 cfm
68.7/66.5°F
Supply Air Ducts
Fan
69.8 / 66.9+°F
68.3% R.H. ROOMS
78.0/70.2°F
K Retum Air Ducts `I
EnergyPro 4.2 by EnergySoft User Number: 1268 Job Number: 03-135 Page: 19 of 19