BSOL2015-0066LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter
9 (commencing with Section 7000) of Division 3 of the Business and Professions Code,
and my License is in full force and effect.
License Class: _ License No.: 896912
Dte; 1 Contractor
OWNER -BUILDER DEC RATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State
License Law for the following reason (Sec. 7031.5, Business and Professions Code: Any
city or county that requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for the permit to file a
signed statement that he or she is licensed pursuant to the -provisions of the
Contractor's State License Law (Chapter 9 (commencing with Section 7000) of Division 3
of the Business and Professions Code) or that he or she is exempt therefrom and the
basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a
permit subjects the applicant to a civil penalty of not more than five hundred dollars
($500).:
(_) I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure Is not intended or offered for sale.
(Sec. 7044, Business and Professions Code: The Contractors' State License Law does not
apply to an owner of property who builds or improves thereon, and who does the work
himself or herself through his or her own employees, provided that the improvements
are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner -builder will have the burden of proving that
he or she did not build or improve for the purpose of sale.).
(_) 1, as owner of the property, am exclusively contracting with licensed contractors
to construct the project. (Sec. 7044, Business and Professions Code: The Contractors'
State License Law does not apply to an owner of property who builds or improves
thereon, and who contracts for the projects with a contractor(s) licensed pursuant to
the Contractors' State License Law.).
(_) I am exempt under Sec. B.&P.C. for this reason
Date
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for
the performance of the work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's Name:
Lender's Address:
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided for by Section 3700 of the Labor Code, for the performance
of the we for which this permit is issued.
I have and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which this permit
is issued. My workers' compensation insurance carrier and policy number are:
Carrier: _ Policy Number: _
_ I certify that in the performance of the work for which this permit is issued, I
shall not employ any person in any manner so as to become subject to the workers'
compensation laws of California, and agree that, if I should become subject to the
workers' compensation provisions of Section 3700 of the Labor Code, I shall forthwith
comply with those
provisions.
Dat : — J ^ Applicane-OWeJAPIk -
WARNING: FAILURE TO SECURE WORKERS' CO ENSATION COVERAGE IS UNLAWFUL,
AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO
ONE HUNDRED THOUSAND DOLLARS ($100,000). IN ADDITION TO THE COST OF
COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE,
INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT: Application is hereby made to the Building Official for a permit subject to
the conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose
request and for whose benefit work is performed under or pursuant to any permit
issued as a result of this application , the owner,'and the applicant, each agrees to, and
shall defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and
employees for any act or omission related to the work being performed under or
following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is
not commenced within 180 days from date of issuance of such permit, or cessation of
work for 180 days will subject permit to cancellation.
I certify that I have read this application and state that the above information is correct.
I agree to comply with all city and county ordinances and state laws relating to building
construction, and hereby authorize representatives of this city to enter uponthe,above-
mentioned property for inspection purposes. `e
Dat�_:,%!> J Signature (Applicant or Agent) -
X,
78-495 CALLE TAMPICO
D 4P
VOICE (760) 777-7125
LA QUINTA, CALIFORNIA 92253
FAX (760) 777-7011COMMUNITY
DEVELOPMENT DEPARTMENT INSPECTIONS (760) 777-7153
BUILDING PERMIT
Date: 6/15/2015
Application Number:
BSOL2015-0066
Owner:
Property Address:
52885 AVE NIDA MENDOZA
EVANGELINA SALAS
APN:
773332021
52885 AVENIDA MENDOZA
Application Description:
GUTIERREZ / ROOF MOUNTED SOLAR
LA QUINTA, CA 92253
Property Zoning:
Application Valuation:
$13,000.00
z c.
n
Applicant:
Contractor:
�� o r..A
UNITED FIELD REMODELING INC DB
1
UNITED FIELD REMODELING IN Cal
17855 VANOWEN STREET
17855 VANOWEN STREET
Zo r.a r-
RESEDA, CA 91335RESEDA,
CA 91335
D
(818)402-5656
Llc. No.: 896912
- -
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter
9 (commencing with Section 7000) of Division 3 of the Business and Professions Code,
and my License is in full force and effect.
License Class: _ License No.: 896912
Dte; 1 Contractor
OWNER -BUILDER DEC RATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State
License Law for the following reason (Sec. 7031.5, Business and Professions Code: Any
city or county that requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for the permit to file a
signed statement that he or she is licensed pursuant to the -provisions of the
Contractor's State License Law (Chapter 9 (commencing with Section 7000) of Division 3
of the Business and Professions Code) or that he or she is exempt therefrom and the
basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a
permit subjects the applicant to a civil penalty of not more than five hundred dollars
($500).:
(_) I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure Is not intended or offered for sale.
(Sec. 7044, Business and Professions Code: The Contractors' State License Law does not
apply to an owner of property who builds or improves thereon, and who does the work
himself or herself through his or her own employees, provided that the improvements
are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner -builder will have the burden of proving that
he or she did not build or improve for the purpose of sale.).
(_) 1, as owner of the property, am exclusively contracting with licensed contractors
to construct the project. (Sec. 7044, Business and Professions Code: The Contractors'
State License Law does not apply to an owner of property who builds or improves
thereon, and who contracts for the projects with a contractor(s) licensed pursuant to
the Contractors' State License Law.).
(_) I am exempt under Sec. B.&P.C. for this reason
Date
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for
the performance of the work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's Name:
Lender's Address:
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided for by Section 3700 of the Labor Code, for the performance
of the we for which this permit is issued.
I have and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which this permit
is issued. My workers' compensation insurance carrier and policy number are:
Carrier: _ Policy Number: _
_ I certify that in the performance of the work for which this permit is issued, I
shall not employ any person in any manner so as to become subject to the workers'
compensation laws of California, and agree that, if I should become subject to the
workers' compensation provisions of Section 3700 of the Labor Code, I shall forthwith
comply with those
provisions.
Dat : — J ^ Applicane-OWeJAPIk -
WARNING: FAILURE TO SECURE WORKERS' CO ENSATION COVERAGE IS UNLAWFUL,
AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO
ONE HUNDRED THOUSAND DOLLARS ($100,000). IN ADDITION TO THE COST OF
COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE,
INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT: Application is hereby made to the Building Official for a permit subject to
the conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose
request and for whose benefit work is performed under or pursuant to any permit
issued as a result of this application , the owner,'and the applicant, each agrees to, and
shall defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and
employees for any act or omission related to the work being performed under or
following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is
not commenced within 180 days from date of issuance of such permit, or cessation of
work for 180 days will subject permit to cancellation.
I certify that I have read this application and state that the above information is correct.
I agree to comply with all city and county ordinances and state laws relating to building
construction, and hereby authorize representatives of this city to enter uponthe,above-
mentioned property for inspection purposes. `e
Dat�_:,%!> J Signature (Applicant or Agent) -
X,
•
}
1
FINANCIAL INF06AATICIN
ACCOUNT rQTY ; - 'AMOUNT, w' ,PAID'` , ; , PAID'DATE'
BSAS SB1473 FEE
101-0000-20306 0 $1.00 $0.00
METHOD 3K;RECEIP.T # .a • n' ti' CHECK # z# d CLTD BY
Total Paid forBUILDING STANDARDS ADMINISTRATION BSA $1.00 $0.00
.
. DESCRIPTION , _,t
ACCOUNT, ,
CITYPAID
AMOUNT_
GATE
PV SYSTEM - ARRAY, FIRST 20
101-0000-42403
0
$24.17.
$0.00
,PAID BY
_ r:'+ METHOD : ; `
'' RECEIPT:#
CHECK.# r , R
CLTD BY ;
DESCRIPTION ,y
...- ACCOUNT
QTY
„',AMOUNT^;
r ,PAID'
PAID DATE:
PV SYSTEM - ARRAY, FIRST 20 PC
101-0000-42600
0
$24.17
$0.00
N `PAID BY T ";
;« ;METHOD w
RECEIPT ';
.:
" .' CHECK:# "
` .CLTD 8Y
Total Paid for ELECTRICAL: $48.34 $0.00
DESCRIP,TIONACCOUNT..QTY»
F AMOUNTS "'
a`
PAID �` .
,
'PAID DATE
PERMIT ISSUANCE
101-0000-42404
0
$91.85
$0.00
,PAID BY
METHOD
y f -' RECEIP.T # ` 7
`CHECK # .
�CLT.D:BYr
Total Paid for PERMIT ISSUANCE: $91.85 $0.00 .
TOTALS:00
•
}
1
Description: GUTIERREZ / ROOF MOUNTED SOLAR
ADDITIONAL
Type: SOLAR Subtype:
Status: APPROVED
Applied: 6/1/2015 SKH
Approved: 6/8/2015 JFU
Parcel No: 773332021 Site Address: 52885 AVENIDA MENDOZA LA QUINTA CA 92253
Subdivision: SANTA CARMELITA VALE LA QUINTA Block: 146
ti
Lot: 8
Issued:
UNIT 15
C�-m#. -STAFF NAME
Lot Sq Ft: 0 Building Sq Ft: 0
Zoning:
Finaled:
Valuation: $13,000.00 Occupancy Type:
Construction Type.:
Expired:
No. Buildings: 0 No. Stories: 0
No. Unites: 0
Details: 2.0 kW SOLAR ARRAY - (8) 25OW SOLARWORLD SW250 PANELS W/ (1) ABB PVI-3.0-OUTD-US-Z-A INVERTER
[144SF] 2013 CALIFORNIA
ELECTRICAL CODE.
6/1/2015
- i?pplied to Approved
Printed: Monday, June 15, 2015 2:29:05 PM 1 of 3 C
SYSTEMS
ADDITIONAL
CHRONOLOGY
',CHRONOLOGY TYPE
C�-m#. -STAFF NAME
°' ACTION DATE,.
',� -cam =y
-COMPLETION DATE ,NOTES..
;-
PLAN CHECK SUBMITTAL
STEPHANIE KHATAMI
6/1/2015
6/1/2015
RECEIVED
NOTIFIED ENVER W/ UNITED FIELD REMODELING (562 -396 -
TELEPHONE CALL
JAKE FUSON
6/8/2015
6/8/2015
1728) THAT PLANS WERE APPROVED AND PERMIT WAS
READY TO ISSUE.
CONDITIONS
CONTACTS
>:
NAMETY` NAME ., ': ;•- ADDRE551 kw ,, ' CITY :.' ,:STATE : .• ZIPS' Y PHONEw=' , y'EMAILF �.
FAX,::,.
APEc �, e, r�'
�,,.�,m'•-�
_
APPLICANT UNITED FIELD REMODELING INC DB
17855 VANOWEN
RESEDA
CA
91335
(760)835-1026
I
STREET
CONTRACTOR UNITED FIELD REMODELING INC DB
17855 VANOWEN
RESEDA
CA
91335
(760)835-1026 '
STREET
Printed: Monday, June 15, 2015 2:29:05 PM 1 of 3 C
SYSTEMS
•
NAME TYPE } °"uy NAME: C0 ADDRESSl CITY » _ STATE d -;ZIPS },;' J3„` PHONE:4 FAX xy EMAIL ” *.
OWNER EVANGELINA SALAS 52885 AVENIDA LA QUINTA CA 92253 (760)835-1026
MENDOZA
PARCPJT Pnnirf T;
Printed: Monday, June 15, 2015 2:29:05 PM 2 of 3 Or
SYSTEMS
FINANCIAL
INFORMATION
-
CLTD'
DESCRIPTION
t ACCOUNT QTY
AMOUNT _
PAID
PAID DATE RECEIPT # CHECK # METHOD PAID BY
BY
BSAS SB1473 FEE
101-0000-20306 0
$1.00
$0.00
Total Paid for BUILDING STANDARDS ADMINISTRATION
$1.00
$0.00
BSA:
PV SYSTEM - ARRAY,
101-0000-42403
0
$24.17
$0.00
FIRST 20
PV SYSTEM - ARRAY,
101-0000-42600
0
$24.17
$0.00
FIRST 20 PC .
Total Paid for ELECTRICAL:
$48.34
$0.00
PERMIT ISSUANCE
101-0000-42404
0
$91.85
$0.00
Total Paid forPERMIT ISSUANCE:
$91.85
$0.00
TOTALS:•
00
PARCPJT Pnnirf T;
Printed: Monday, June 15, 2015 2:29:05 PM 2 of 3 Or
SYSTEMS
r.
Printed: Monday, June 15, 2015 2:29:05 PM , 3 of 3 J SYSTEMS
BOND
INFORMATION
ATTACHMENTS
r.
Printed: Monday, June 15, 2015 2:29:05 PM , 3 of 3 J SYSTEMS
Bfn.#
CJtjv. of La Qli%rata
Bufidtrtg a Safety Div 0n
P.O. Box 1504,78-495 Calle Tamplw
00La.Qutnta, CA 92253 - (760) 777-7012
Building Permit Application* and Tracking Sheet
Permit #
�—� LIS
Project Address: S2
aS veru %U er's Name:. V)qN d
A. P. Number. Address: - S A -e
Legal Description: V -S' CiZAfz- fzpo City, ST, Zip: p� /`1 v 1V �� Cad D12S"3
Contractor. V �e� tz&io d aA; Telephone:
Address: 12 5 5- P S Project Description:
City, ST, Zip:
C 335 v S<>.2- POoF t1c>JM ,
Telephone: / D 30d S � e �1 .. b
State Lie. #: 9 t� GYty Lic. #; CC 15-0 SP.
Arch, EW,Designer
Address.
City. ST, Zip.
Telephone:
State Lic. #:
Name of Contact Person: IV v&Z p S C
Construction Type: _ Occupancy:
Project type (circle one): New Add'n Alter Repair Demo
• Sq. Ft.: �� # Stories:
# Unitp
Telephone # of Contact Person: 6 - -
Estimated Value of Project: 3 0.0 Q
APPLICANT: DO NOT WRITE BELOW THIS UNE
#
Submittal
Req'd
Ree'd
TRACMG
PERMIT FEES
Plan Sets
Plan Cheek submitted
Item Amount
Structural Cates.
Reviewed, ready for veweadw tSSVE
6
Plan Cheek Deposit. .
Truss rales.
Called Contact Person
�j
Plan heck Balance.
Tule 24 Cates.
Pians picked up
Construction
Flood plain plan
Plans resubmitted. -
Mecharikal
Grading plan
2' Review, ready for correctious/issue
Electrical
Subeoetector List
Called Contact Person
Plumbing
Grant Deed
Pians picked up
S.M.I.
H.O.A. Approval
Plans resubmitted
Grading
IN HOUSE:- '
" Review; ready for eorreetions/issae
Developer Impact Fee
Planning Approval
Called Contact Person
A.IR.P.
Pub. WI®. Appr -
Date of permit issue
School Fees
Total Permit Fees
JUN 01 2015
coMM NOF WNW
< N
2
0
in
m
u
2
O
i
0
�I
Z>.—>
z
Cn0
o ao
WpLnZO
C) n
<
w
0z
m
°'C�5D—I
m
c D
N
oo�m
m0
O
,-
n
D
M
rn
-
C m
0
r
m
z
"
M
xm�
D
U)
<
�n0
K
D
m
O x
C
n
�
?co
D
m
x
m0
� 0 n n 0 0 -u
O
.0
m
—cnI
O
z
@ U
-
� D
ao,_
0�
0 z
rr
Z
U.
Z>.—>
0
c-
m
0
cn
m .
z
Cn0
o ao
WpLnZO
C) n
0
>cn
mN�E.
0z
m
°'C�5D—I
m
c D
N
oo�m
m0
O
,-
cNnz
w0X
N'*z
-
C m
0
D
0
z
"
M
xm�
D
U)
<
�n0
K
D
m
O x
C
z
--I
?co
D
m
x
m0
0
c-
m
0
cn
m .
^^r
z
m
Cn0
o ao
WpLnZO
C) n
z D 0 m
>cn
mN�E.
0
NDZZm- cn
Dm00
O-0
°'C�5D—I
m
c D
N
oo�m
C
Too
cNnz
w0X
N'*z
zX
0'm
N
\\\\\
<
+nNNNNNN
+n -i
0
0
00,
C
Z N N N� N N
00
^^r
z
m
NNNNNNN
oaaaaaa
1'ID
0r -
n n
m
wwwwwww
r
r -r
m(n
Znnnnnn
zX
\\\\\
Z
+nNNNNNN
+n -i
O
m o 0 0 0 0 0
00,
Z N N N� N N
00
mm:,cczAW
m0
� 0 n n 0 0 -u
i
—cnI
O
m -
3'-411
w o
c
00 �NIM
Dv�
0wZ0
d z m Q0
�0�c < TO�
--� M
0�° z
Z M�
-N w N
cnmmcn
Z000m
m
G) ;u
m5Dz
r-
�z<
M r cn n
iim0z
�--
o—�
DDz�
Dm-�
cn
2
m
m
-i
m
Z)
r S. D =
X 8 CZOrCO
n U)
Z sc z � C-.' M m
O
D �0 z Z.� 0
s c
M cn 0
_ nip ►-•�
N
5D
IC4r
DATE: TITLE: PROJECT SITE: CONTRACTOR: SIGNED:
03MAY15 SITE PLAN EVANGELINA GUTIERREZ UNITED FIELD REMODELING INC NIR HAGA
VICINITY MAP 52885 AVENIDA MENDOZA 17855 VANOWEN STREET UNITED FIE L EMODELING INC
HOUSE PHOTO
REV: 00 LA QUINTA, CA 92253 RESEDA CA 91335 818.748.2300
760.835.1026 CSLB: 896912 (B) CSLB: 896912 (B)
bz-Ses
AVeWIDA H&V POZA zaa
cn
0
D
r
m
n
oq
i
cn
O
xZ0000
X
0
.y = o'000
o
O
=mZ.
M
�-C
I
oO z o
-
m ; �
z
G)m�
Z
m�
=Zm
0
m
v
mcm
z
;vW=
o
�Cc
D
m
0
--f --I
O Z
Tpr
-OI
9
DU)m
M Z
r
:E >
c/) m
O M m
_
;oZ
r - X r N
> U)
c0°i��'oc°°i)ci
Z X m
nm0,
n O.p
`
^
I�0)Z 1
0
Z
G)
o
=-
m
0 n OD
T N
< C a
y�y
XZZ
<0000000
cn rrn-
i
c -
CD
0
X
n
DC99K9
cn
O
xZ0000
0 z
.y = o'000
o
cccc
< r-rr-r
X0�
0
M
�-C
m
o*KK
-
m ; �
C:>
Q
(Dj
Z
m�
D
0
m
omp
0 z
z
m
o
�Cc
D
m
0
--f --I
m
-OI
9
90
r
c -
CD
0
X
n
DC99K9
9
xZ0000
O
.y = o'000
o
cccc
< r-rr-r
c
r
55 mmmm
m
o*KK
� ,w�i ---.Z ,��'4� +!..a..i._ . �. �.... �
:c— 0>
om
-n
...:js•M"• �G---:s ^:. .;,,'y:'+.:..--.,�,-.. r
1�
�
m� � •
-n r
o
XOz
m
>vcn
m
0
z
=
cn
9
90
m
z
{ Nw�wcncn
'v _ O
r - X r N
c0°i��'oc°°i)ci
n O.p
P r-
w
m
N
n c -
0>o
Tz
o .� o O
z go
c®mom
Mac
®��
�>
@ 0
z
0 Z
h0
r
m
DATE:
TITLE:
PROJECT SITE:
CONTRACTOR:
SIGNED:
„N
03MAY15
REV: 00
-1
d i � y'
!�.- ..
� ,w�i ---.Z ,��'4� +!..a..i._ . �. �.... �
�r`F' •a+1'^ f--^'-'�'j.
M _ 4' .`� .+ .�iRJ�+/.'�..^ r _.- .se. .'w. ': r..., rL+�t_.-�'7 -:-
...:js•M"• �G---:s ^:. .;,,'y:'+.:..--.,�,-.. r
1�
�
. z ��
. 1
A
00000000
T N
N
<0000000
D
N
A
�-n -p ci) )> -n
. p
p
00
G)C)ZO
p
S
00
��
� C
m'
mmm-oc 9m
rm
p
Z
tea,
�
_
m��
�
o
D
�y = G
O
0
N' X
cn
m
cn Z c
X
D m
D
Z
_I
= Om
0
9
m
0
z
N N
-G) m D
2-0
o
m�
p
0
+)
(n
m
r
0
N -4 K) M r%) 0
OCnUtODv-&x
OCD 0 0
m
o a
D
-DGS
M y
-D
.D
--i-i�
NN
r
-Ico
J
Z
rm-
coco
cn—I
n c -
0>o
Tz
o .� o O
z go
c®mom
Mac
®��
�>
@ 0
z
0 Z
h0
r
m
DATE:
TITLE:
PROJECT SITE:
CONTRACTOR:
SIGNED:
„N
03MAY15
REV: 00
-1
ROOF PLAN
ATTACHMENT
DETAIL
EVANGELINA GUTIERREZ
52885 AVENIDA MENDOZA
LA QUINTA, CA 92253
760.835.1026
UNITED FIELD REMODELING INC
17855 VANOWEN STREET
RESEDA CA 91335
CSLB: 896912 (B)
NIR HAGAG
UNITED FIELD REM ELING INC
818.748.2300
CSLB: 896912 (B).
GENERAL ELECTRICAL NOTES:
1. EQUIPMENT USED SHALL BE NEW, UNLESS OTHERWISE NOTED.
2. EQUIPMENT SHALL BE INSTALLED PROVIDING ADEQUATE PHYSICAL WORKING SPACE AROUND
THE EQUIPMENT AND SHALL COMPLY WITH NEC.
3. COPPER CONDUCTORS SHALL BE USED AND SHALL HAVE INSULATION RATING 600V, 90°C,
UNLESS OTHERWISE NOTED.
4. CONDUCTORS SHALL BE SIZED IN ACCORDANCE TO NEC. CONDUCTORS AMPACITY SHALL BE
DE -RATED FOR TEMPERATURE INCREASE, CONDUIT FILL AND VOLTAGE DROP.
5. ALL CONDUCTORS, EXCEPT USE -2 OR PV WIRE SHALL BE INSTALLED IN APPROVED CONDUITS
OR RACEWAY. CONDUITS SHALL BE ADEQUATELY SUPPORTED AS PER NEC.
6. ALL CONDUIT SHALL BE MOUNTED ON THE EXTERIOR UNLESS OTHERWISE NOTED.
7. RACKING AND MODULES ARE GROUNDED VIA A CONTINUOUS #8 AWG COPPER CONDUCTOR,
GROUNDING CLIPS, GROUNDING LUGS AND/OR BONDING JUMPERS.
8. LOAD SIDE INTER -CONNECTION SHALL COMPLY WITH NEC
9. SMOKE ALARM AND CARBON MONOXIDE DETECTORS SHALL BE LOCATED AS REQD PER SEC.
R314 & R315 OF THE CALIFORNIA RESIDENTIAL CODE (CRC)
10. ALL EQUIPMENT SHALL BE LISTED FOR THE APPLICATION, UL 1703 FOR MODULES, UL 1741 FOR
INVERTERS
11. NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM
12. WHEN A BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, BREAKER SHALL
NOT READ LINE AND LOAD
13. ALL EXTERIOR CONDUIT, FITTINGS AND BOXES SHALL BE RAIN -TIGHT AND APPROVED FOR
USE IN WET LOCATIONS ACCORDING TO NEC 314.15
14. ALL METALLIC RACEWAYS SHALL BE BONDED AND ELECTRICALLY CONTINUOUS ACCORDING
TO NEC 250.90, 250.96
15. GROUNDING BUSHINGS ARE PERMITTED AROUND PRE -PUNCHED CONCENTRIC KNOCKOUTS
ON THE DC SIDE OF THE SYSTEM, NEC 250.97
16. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS EXCEPT FOR SPLICES OR
JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT, NEC 250.64(C)
17. ALL EQUIPMENT SHALL BE INSTALLED ONLY BY QUALIFIED PERSONS. 690.4(E)
WIRE/CONDUIT SCHEDULE
TAG DESCRIPTION CONDUCTOR CONDUIT # CONDUCTORS
1
ARRAY TO jUNCTION BOX
#10 AWG PV WIRE
NA 2
2
JUNCTION BOX TO INVERTER
#10 AWG THWN-2
3/4" EMT 2
3
INVERTER TO PV AC DISCO.
#10 AWG THWN-2
3/4" EMT 2
4
AC DISCONNECT TO MAIN PANEL
#10 AWG THWN-2
3/4" EMT 2
5
BARE COPPER
#6 AWG SOLID
NA 1
6
EQUIPMENT GROUND
#8 AWG THWN-2
3/4" EMT 1
STRING 1 t 1 (N) J -BOX 2
8 PV PANELS
EQUIPMENT GROUND
PV CONDUCTORS UNGROUNDED —
I
NOTES
FREE AIR
,I a
FREE AIR ti
i
41.
(N) INVERTER,
ABB, PVI -3.0-01
DC INTERFACE 3000W, 96% CE
DC DISCONNECT 240VAC, 14.5A
DC+
o MPPT1
DC- JJ
41
DC+
p MPPT2 �/
DC -
t
AC INTERFACE
MODULE
MAKE:
SOLARWORLD
MODEL:
SW250 POLY
MAX POWER:
250W
MAX POWER VOLTAGE (VMP):
30.5V
MAX POWER CURRENT (IMP):
8.27A
OPEN CIRCUIT VOLTAGE (VOC):
37.6V
SHORT CIRCUIT CURRENT (ISC):
8.81A
MAX SERIES FUSE:
16A
INVERTER
MAKE:
ABB
MODEL:
PVI-3.0-OUTD-US
MAX DC VOLTAGE RATING:
600V
MAX AC APPARENT POWER:
3000W
NOMINAL AC VOLTAGE:
240V
MAX AC CURRENT:
14.5A
ARRAY DETAILS
NO. OF MODULE/STRING:
8
NO. OF STRING:
1
ARRAY WATTS STC:
2.000 kW
MAX SYSTEM VOLTAGE:
334.2V
(E) UTILITY
BI-DIRECTIONAL
ENERGY METER
CITY OF LA QUANTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTI N
(E) MAIN S@ATP_ PANE BY
100A, 24
a
(E) MAIN
OCPD
100A
2 POLE
(N) AC DISCONNECT
240VAC, 30A, 2 POLE
NEMA 3R, UL LISTED
KNIFE BLADE TYPE
L1
3
II L2
N
—G —
(N) SOLAR
OCPD
20A, 2 POLE
J_
(E) LIFER OR GROUNDING
ELECTRODE
0
Z
�Wv /M\
iY in
pv
J O �
W o o)
Q W N rn
pOpcooo
Q
Z 2 H r- m
to Z 'o 8
U
Z
0
Z_
J F_
W W
p W
O�
2U)
W Z _M m
0 _3
UJ OQ
Q; U rn
Q 00
F- W Lo W m
Z H u) In J
OZ00W(n
L) iY U
N
Wjr o
p
W_ Z Lo
I —
WN
porn
LuOQQ
Q
~ J W � o
WC7QZL6
.)ZLnp�
�
o co C
> N Q co
iLWU)Jf-
2
UIt
(D
�Q
W U 0
LLI
W
Z
H W
o
Q M
W
p o
fY
PV -3
REQUIRED SIGNAGE
1. LABEL FOR SOLAR DC DISCONNECT
[690.14(C)(2), 690.53]:
SOLAR DC DISCONNECT
OPERATING CURRENT:
8.3 ADC
OPERATING VOLTAGE:
244.0 VDC
MAXIMUM SYSTEM CURRENT:
11.0 ADC
MAXIMUM SYSTEM VOLTAGE:
334.2 VDC
2. LABEL AND MARKINGS. A WARNING LABEL SHALL
APPEAR ON THE UTILITY -INTERACTIVE INVERTER OR
BE APPLIED BY THE INSTALLER NEAR THE GROUND
FAULT INDICATOR AT A VISIBLE LOCATION, STATING
THE FOLLOWING, [690.5(C)]:
WARNING!
ELECTRIC SHOCK HAZARD
IF A GROUND FAULT IS INDICATED, NORMALLY
GROUNDED CONDUCTORS MAY BE UNGROUNDED
AND ENERGIZED
3. PROVIDE A PLACARD WITH THE FOLLOWING
WORDING IN 3/8" HIGH LETTERING
LABEL FOR SOLAR AC DISCONNECT, [690.17(4)]
WARNING!
ELECTRICAL SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH
THE LINE AND LOAD SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
4. LABEL FOR SOLAR AC DISCONNECT [690.14(C)(2)]:
PHOTOVOLTAIC DISCONNECT FOR
UTILITY OPERATIONS
OPERATING CURRENT: 14.5 A
OPERATING VOLTAGE: 240 VAC
5. LABEL FOR INSIDE MAIN SERVICE PANEL ADJACENT
TO SOLAR OCPD, [690.64, 705.12(D)(7)1:
PV BACKFEED OCPD TO BE LOCATED AT OPPOSITE
END FROM INPUT FEEDER OR MAIN CIRCUIT
WARNING: INVERTER OUTPUT CONNECTION
DO NOT RELOCATE THIS OVERCURRENT DEVICE
{
i
FIRE DEPARTMENT REQUIRED SIGNAGE
�r
7. THE FOLLOWING SIGNAGE MUST HAVE A MINIMUM
OF 3/8" HIGH LETTERING, IN ARIAL FONT(NON-BOLD),
WITH CAPITAL LETTERS, WHITE ON `RED BACKGROUND
AND ON A REFLECTIVE, WEATHER RESISTANT MATERIAL.
AT THE MAIN SERVICE DISCONNECT PROVIDE A SIGN
WITH THE FOLLOWING WORDING:
CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED
THE SIGN SHOULD BE PLACED ON THE OUTSIDE COVER
IF THE MAIN SERVICE DISCONNECT IS OPERABLE WITH
THE SERVICE PANEL CLOSED
1
8. ON ALL INTERIOR AND EXTERIOR DC CONDUIT,
RACEWAYS, ENCLOSURES, CABLE ASSEMBLIES,
JUNCTION BOXES AND DISCONNECTS
WARNING: PHOTOVOLTAIC POWER SOURCE
MARKING SHALL BE PLACED EVERY..',10 FEET AT TURNS
AND WITHIN 1 FOOT ABOVE AND/ OR BELOW
PENETRATIONS AND AT ALL PV COMBINER AND
JUNCTION BOXES.
ELECTRICAL CALCULATIONS
OPERATION VOLTAGE = (8)(30.5) = 244.0 V
OPERATING CURRENT = (1)(8.3) = 8.3 A
MAX PV VOLTAGE & CURRENT CALC
RECORD LOW TEMP.(°C): -5°
TEMP.COEFF (%/°C): -0.300
OPEN CIRCUIT VOLTAGE (Voc): 37.6 V
MAX PV SYSTEM VOLTAGE (PER NEC 690.7)
= [(-0.00300)(37.6)(-(25-(-5))(8)] + [(37.6)(8)] = 334.2 V
MAX PV CONTINUOUS CURRENT PER NEC 690.8(A)(1)
(1.25)(Isc)(# STRINGS)
(1.25)(8.81)(1) = 11.0A
DC CONDUCTOR AMPACITY CALC'S ROOF CONDUIT
# OF STRINGS PER INVERTER: 1
EXPECTED MAX AMBIENT TEMP. (°C) 61 °
TEMP. CORRECTION NEC, TABLE 310.15(B)(2)(a): 0.65
CIRCUIT CONDUCTOR SIZE/TYPE: 10AWG, THWN-2, 90°C
# OF CURRENT CARRYING CONDUCTORS: 2
CONDUIT FILL CORR., NEC TABLE 316.15(13)(3)(a): 1.0
CIRCUIT CONDUCTOR AMPACITY, TABLE 310.15(B)(16): 40A
REQUIRED CIRCUIT CONDUCTOR AMPACITY, NEC 690.8(B):
(1.25)(1.25)(Isc)
(1.25)(1.25)(8.81) = 13.8 A
ADJUSTED AMPACITIES FOR CONDUCTORS, NEC 310.15
TEMP. CORRECTION, NEC TABLE 310.15(B)(2)(a) x
CONDUIT FILL CORRECTION, NEC 310.15(B)(3)(a) x
CONDUCTOR AMPACITY, NEC TABLE 10.15(B)(16)
(0.65)(1.0)(40) = 26A > 13.8A OK
10AWG, THWN-2, 90°C WIRE IS OK
AC CONDUCTOR AMPACITY CALC'S WALL CONDUIT
# OF INVERTER: 1
EXPECTED MAX AMBIENT TEMP. (°C): 44
TEMP. CORRECTION, NEC TABLE 310.15(B)(2)(a):.87
CIRCUIT CONDUCTOR SIZE/TYPE: 10 AWG, THWN-2, 90°C
# OF CURRENT CARRYING CONDUCTORS: 2
CONDUIT FILL CORR., NEC TABLE 310.15(B)(3)(a): 1.0
CIRCUIT CONDUCTOR AMPACITY, TABLE 310.15(B)(16): 40A
REQUIRED CIRCUIT CONDUCTOR AMPACITY, NEC 690.8(B):
(1.25)(# OF INVERTERS)(MAX INVERTER OUTPUT CURRENT)
(1.25)(1)(14.5) = 18.2 A
ADJUSTED AMPACITIES FOR CONDUCTORS NEC 310.15:
TEMP. CORRECTION, NEC TABLE 310.15(B)(2)(a) x
CONDUIT FILL CORRECTION, NEC TABLE 310.15(B)(3)(a) x
CONDUCTOR AMPACITY, NEC TABLE 10.15(B)(16)
(.87)(1.0)(40) = 34.8A > 18.2A OK
10 AWG, THWN-2, 90°C WIRE IS OK
20A PV BREAKER WILL BE PROVIDED
POINT OF INTERCONNECTIOIN, NEC 705.12(D)(2):
(1.2)(BUS RATING) >_ MAIN BREAKER + PV BREAKER
(1.2)(100A) >_ 100A + PV BREAKER
PV BREAKER SHALL BE <_ 20A
20A:5 20A OK I CITY OF LA QUIN
SITE PLACARD
CAUTION POWER TO THIS BUILDING IS
ALSO SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS
LOCATED AS SHOWN:
SOLAR
DISCONNECT
MAIN PANE
BUILDING & SAFETY DE
APPROVED
FOR CONSTRUCTION
U
z
pv
J O
0wM0)
QNO
�Qpa000
Z = 1.- n m
OWE U)
V3 5 ao U
U
z
z
J H
ww
pw
O�
2 Lo
Z co m
�
W O Q rn
Q > U rn
o
�
Z H Lp Lo (n m
Oz00wcn
U p I W 0
N
Ap
zo
T. N
Q rn
H pU�
~ woo
U QZL
L p �
co O
co
C14
CL w Lr) J ti
0
gW
�<
Q
J 0
F- U (n
wQ o
0o W
PV 41
Illustrated above is how the Fast./ackl
attachment seamlessly integrates with
the Roof Trac' mounting system.
r
yr �
The Fast jack' attachment
provides a quick and strong
installation solution. Our patented
design places the bolt directly
under the stanchion post where it
'; provides the most support. This fea-
y,, tureallows standard roofJlashings
to lay flat on the roof deck. The
removable post allows flashings to
x
+ be slipped over the base without
damaging surrounding composi-
tion shingles.
All attachment hardware is concealed
within the support rail leaving an
aesthetically pleasing solar array.
Splice Kit ;
The splice kit provides a solution to rigidly lock multiple raid ti's
TMy A " sets together. The splice kit has a feature that allows for then-
" mal expansion/contraction of the rails without damaging
�. the roof -top!
professional (800) 84 -SOLAR
SOLAR(805) 383-0804—fax
4630 Calle Quetzal
products.—,A,Camarillo, CA 93012
For more information you
can visit us on the web at
www.Roo-j'Trac.com
F
TMIntegrated with Tile Trac® attachments
Roof Trac The patented Roof Trac ' Outero installed wah the ?'A, nff eattachment
Alke" #4360,491 method provides an ideal solution for mounting on a lite roof. We
The; Original "Top-Oo tnl' PV Mounting System. Trac reduces the possibility of broken tiles and leaking roofs, allowing
"-`— — the installer to make structural atiachmenfs to The roof rafter,
The hoof Tragi'` installed wish the Tile AraO allows solar support rails
\ to be adjusted to compensate for uneven roofs
r Roof TFwS N Fast Jack- protected under
7 Patent #6,360,491 H Other patent pending.
Tile Trac® protected under Patent #6,646,049.
r
_ F
S L jAl, i
1 The Roof Trac` support rail was designed
to conceal all attachment hardware.
All connections are made inside the support
rail hidden from view.
Illustrated above is how the Tile Trac'
attachment seamlessly integrates with the
Roof Trac" mounting system.
The Tile Trac@ attachment system is
the perfect base for surface mounting on
composition roofs! It has over 10 sq. inches
of base to prevent damaging delicate
composition shingles.
Patented Slide -N -Clamp
r
.........
professional
SOLAR
products,.,,
System
All exposed aluminum is fully anodized to
module manufacturer specifications.
Fully integrated, and patented, clamping system
actually changes the structural properties of the
aluminum channel making it significantly stronger.
This design allows solar modules to be installed at a lower
profile to the roof providing a more aesthetically pleasing
installation.
module clamps are specifically designed, extruded and
engineered for each specific module frame. Our innovative
clamping system provides inward tension on the module
frame securing the laminate in the frame.
Washer, Electrical Equipment Bond
INSTALLATION INSTRUCTIONS
dor Professional Solar only
Please read carefully before installing.
EWA40Y. -LLd recommends that the sufficient details of the
installation be submitted to the AHJ for approval before any work
is started.
o
WEEB-PMC
WEEBLug-6.7 assembly WEEB Bonding Jumper -6.7
Products are tested to UL 467, CAN/CSA-C22.2 No. 41 lnWrtek'
US/Canadian• standards for safety grounding and bonding equipment 3098:177.,
Document Number 104-0404-000008414
2012 BURNDY LLC. y HUBBELL
Page 1 of 13'
FastJacke.2X bracket only to
be used between two rows of
modules to maintain approx.
48°upper to lower RoofTrac®
support rail spacing
FastJack® 2X bracket
Assembly side view ApproX cu max
overhang • fel
i 5/16" Stainless Steel Hex
i" bolt and slit lock washer
r` Aluminum ProSolar,
Inter -Module Clamp.
Aluminum ProSolar
Channel Nut
L V�i
E_
cj i �CIF�l Aluminum ProSolar
Roofrrace Support Rail
3/8" Stainless Steel
Hex Bolts and Flat
Washers
i _ I Aluminum ProSolar
FastJack® 2X Bracket
I (only used between two
-� rows of modules) _
Aluminum ProSolar
Patented 2 pc FastJack®
Roof Attachment
5/16" Stainless Steel Lag
Bolt and Flat Washer
f
,, ab tested structural attachments manufactured by Professional Solar Products
(including FastJacko . Tile rracO, and FoamJacke) can be interchanged with this system.
"Check span suitability with AHJ as necessary
Professional Solar Products RoofTrae Patent# 6,360,491
Photovoltaic mounting system
I1— 48^ ..01
Module
Area
18ft' each
Total module (45 Ib/ea:)
and rail (10 lb/ea.) weight,:
310
lbs
Number of attachments:
9
ea
Weight / attachment point:
35
lbs
Area:
108
ft2
Distributed. weight:°
2.9
Ib/ fe
'RoofTrac°-
Solar Modules
Static load test
Page 3 of 3 RT -4
Module.,
Area*-�
18. ft.2;
AwdxW
m".rmg
T'6 f6i II th o d U I e� 4 S- 1 b si'.e a_ Y;
and: rail., (10 lbs ea) weight
:155
lbs:
.N'u-mbert,ofattachments...
-6
ea,-
Might`attathtent' ih,
P-0t
26,
lbs
Area':;,
54
ft.
- htl
DittfibbtddW`6�z
2:9:•
Ib/ ftz
mT=-7
M
5/16"St6ihiess.k.
Steel,Hextolt
5/16 .Stainless- Steel;
Lock-wjsh&''
1
1C4R t .4rL 54',
...........
. . . ..................... . .......
T60,p Load- Defl dr-tidn: A'.46W.'
I E5"'_Oj
Aluminum. Pr6Sblait
Inter-Moduld'Cl6mp.,
. ............ ... _ . .................... .... . . .... . .....
Aluminum ProSolar
Channel. NU Up: lift. DeflOction 0.31`3"
Aluminum ProSolbr
136off-rad&Support Rail:
3/8?i.Stainless,St6el, Hcik.
B6ltJh'dfljt,Washer'
Aluminum. RoS61at patented,
FasUkk@'1366f AttachmiBnV
5/16v Staihhess,;Stiael; Lag: Mt..
and: Flat: -Washer
tab tested structural attachments manufactured,by Professional Solar Products'
(1, ncl u ding- Fast.JackO . TileTracO, and FoamJackO) can- be interchanged with this.system:
Peofe'ssionab,Solar Products Rooffrado Patent# 6.360,491"
Photovoltaic mounting syst6m..;
Page -2 of 3.
RobfTraC®" i
SbIar Modules\
Static-: load,: test
RT- 4,
VI NCI & ASSOCIATES
Structural Engineers
CU ENT:
Professional Solar Products, Inc.
1551 S. Rose Ave., Oxnard, CA 93033
Tel: 805-486-4700
Subject: Static load test results for the following:
Mountin S stem
g y
Maximum Frame
Maximum Frame
Load
Equivalent Wind Speed
Length* (in.)
Width* (in.)
(lbs/ft2)
(mph)**
RoofTrac 0 ,
65 (77**)
40
55
135 (115* *)
TEST SETUP (as shown in attached drawing detaft Three modules, as specified above, were bolted to 136"x1.5"x1.5"
Professional Solar Products (PSP) patented Roofrrac® support rails using an assembly of 5/16" Stainless Steel (SS) bolts,SS
lock washers and proprietary aluminum clamps and inserts. The RoofTrac® support rail was attached to the PSP RoofTrace
structural attachment device with a 3/8" SS nut and SS washer at six attachment points. The setup.was attached to 2"x6
wooden rafters using 5/16" x 3-1/2" SS lag. bolts. The attachment spans consisted of 48 front to rear with structural
attachments spaced 48" on center.
TEST PROCEDURE (as shown in attached drawing detaiD: The test: set up was top loaded to 55 Ib/ft2. The setup remained..
loaded for an approximate period of 30 minutes: The maximum deflection and any signs of permanent deformation were
recorded. The test setup was then inverted and loaded to simulate the uplift.condition. The test set up was re -loaded to 55
Ib/ft2. The setup remained loaded for an approximate period of 30 minutes. The maximum deflection and any signs of
permanent deformation were recorded.
TEST RESULTS:
The maximum top load deflection was recorded at 0.469 with no permanent deformation.
The maximum uplift deflection was recorded at 0.313", with no permanent deformation.
This document -certifies the RoofTrac® mounting system used with modules; as specified above, withstand the stated static
pressure load, equivalent to the stated wind speeds'*. The mounting system performed as expected.
Sincerely,
Jarnes. R. Vinci, S.E.
This engineering report verifies that Vinci & Associates has provided independent observation for load testing as described in this report. The results of this
load test reflect actual deflection values and are generally accepted as the industry standard for testing module mounting systems. Vinci & Associates does
not field check installations or verify that the mounting system is installed as described in this engineering report.
Structural attachment: Lag bolt attachment should be installed using the proper pilot hole for optimum strength. A 5/16" lag bolt requires a 3/16" pilot hole.
It is the responsibility of the installer to insure a proper attachment is made to the structural member of the roof. Failure to securely attach to the roof
structure in ay result in damage to equipment, personal injury or property damage. The purposed racking system may be installed on any roof up to
maximum of 24 foot above grade without further analysis. Racking can be installed at any location on the roof. Racking shall be installed into a r of ber
or blocking with a 5/16" diameter screw at each Fast -jack location. Screws shall have minimum of 2 Y2 penetration into framing member forzo nd
minimum of 3" penetration into framing member for zone 3. (Zone 3 is defined as the approximately 4'-0" square at each corner of the roof)
This office does not express an opinion as to the load. bearing characteristics of the structure them ounting system/modules are being installe o .
ICC accredited laboratory tested structural attachments manufactured by Professional Solar Products I+
(including FasdackO , TileTracfl, and FoamJackm) can be interchanged with this system.
Check with local building department or AHJ for site specific requirements. C
'Modules measuring within stated specifications and tested to 1.11.1703 -or equivalent, are included in this S
engineering. ti� r
**Wind loading values relative to defined load values using wind load exposure and gust factor coefficient � Z
exposure C" as defined in the 2012(IBC) /2013 (CBC). For 77" x 40" module, equivalentwind speed No 4 1
derated to 115 mph. P. 2/ 1/ 5
*** Module tested: 64.6" x 39.1" x 1.8" (shrp)
IP
***Est. snow load rating of 30 Ib/ft2 based on 1.5 safety factor. (20 Ib/ft' for 77" x 40" module)
333.7 E. Thousand Oaks Blvd, Ste 114 . Thousand Oaks, CA 91136
Page 1 of 3 `".1 'AT -4,
Classic Composition Mount I QMSC
n uo 1- TOWAf
3E
12.00
12.00
ITEM
NO.
DESCRIPTION QTY.
1
FLASHING 12" X 12" X.059'. 5052 MILL 1
2
QBLOCK, CLASSIC A360.1 CAST AL MILL 1
3
HANGER BOLT 5/16" x 6" 18-8 SS 1
4
WASHER, SEALING, 5/16" ID X 3/4" OD, EPDM 1
BONDED SS
.• .p.lumber:
I
i Lag Bolt Specifications
Specific Gravity 5116" shaft per 3" thread depth
5116" shaft per 1" thread depth
Douglas Fir, Larch
i
.50 798
266
Douglas Fir, South
46 705
235
j Engelmann Spruce, Lodgepole Pine (MSR 1650 f & higher)
I .46 705
235
I Hem, Fir
.43 i 636
212
j Hem, Fir (North)
.tis %CS
235
I Southern Pine
55 921
307
Spruce, Pine, Fir
i
.42 615
205
1 Spruce, Pine, Fir (E of 2 million psi and higher grades of MSR and MEL)
1 50 798
266
Sources: American Wood Council, NDS 2005, Table 11.2 A, 11.3.2 A
Notes:
1) Thread must be embedded in a rafter or other structural roof member.
2) See IBC for required edge distances.
IMPORTANT: To maintain waterproofing it is important that the aluminum flashing (item 1) is properly placed under one full course above the mounting blockwith at least 1/2" of the flashing
extending up under an.additional course above (3rd course). The bottom of the flashing should never overhang the shingle drip edge. See instructions on back.
uick Mount P v.
81 7.2.3-7 ' Apr -2013, Rev 4
Additional highlight S:.'
- RS-485 communication interface i
('for connection.to-laptop or data
logger).�g�y,
— Integrated Arc Fault Detection and b
K'
Interruption (-A Version)..'
Technical data and types
Type cod® PVI-3.0-OUTD=US
i PVI 3.6-OUTD-US PVI-3.8-OUTD-US PVI 4.2-OUTD-lJS
-Mechanic'a ly speeificatloo"sus
Nominal output power
f
3000W -
- 3300
360OW - 380OW 4200W
Maximum output power wattage
jj 3000 ...33001 ,•33001
:..................3600 40001 40001 3 00 42001 42001 4200 46001 4600
..
II W W
W W W W W W W W W. W:
Rated grid AC voltage
;..
p,a 208V 240V
.......
2 , V 1208V 240V 277V .:208V 240V '. 277V 206V 240V 277V
�a................
. � a Xi��a I
Number of independent MPPT channels Ii 2
....................................
) . 2' 2 2-.:........:
Maximum usable ower for each charm
p el I ( 2000W
.........................................................................................
.......
p 3000W 3000W 3000W
Absolute maximum voltage.(Vmax) 1•t
..........................................................
...
l l 600V
Start up volta a(Vstart):.......................................... f i ::.::............:........
-Full
...... .. ...:. ....: ......... ..
k_. :200V.(adj.::.120-35OV)...:.
power MPPT voltage range I ] 60 530V
.... .........
I } 120 530V 140-530V "' 140-530V
' Operating. MPPT voltage range 1
p ( 0 7 x,Vstart 580V (> 90V)
.......
liiaximum current (Idcmax) for both MPPT In
......
"
parallel 20A
I 32A 32A 32A
::....
Maximum usable current per channel ► ( 10A
j ( 16A .:...:
16A 16A
Mazimurn short circwt current limit per
'
.....
'.
channel 112.5A
...........................................:...:...............................................................................................
},�: 20 OA 20.OA MOA
Number of Wire landing terminals per channel l .........
.........:.........
{ ( 2 pairs
Arra wirin termination
Y 9
.......................................................
Terminal block, pressure clamp AWG10 AWG4
>`OiJtputisld6 (AC}
Grid connection type ' 10 Spit-
.10 107—Spm: 1� 10 ,.: Spit 10 10/ Spm-: 10/
......_ 2W :..
2W 2W 0/3W ' 2W 2W 0/3W 2W 2W 0/3W,::-2W
2
.......: .,..0/3W
Adjustable voltage range (Vmin Vmax) M 183 :211
.. .
244 183 21 i 244 1$3 211 244 .183 211- 244-
.................................................. 28V ': 264V
- ' ........................................... 2
304V "228V 264V 304V 228V 264V 304V 228V 264V 304V
Grid frequency.......:..
oOHi
Adjustable grid frequency range
.::... ....... ......: ...... .
57'60 5Hz
145`: 1.45:
Maximum current (1.,, )
.....
120 . 172 160 160 .160 160 16.0 '20.0 20.0 20.0
........ ..., ARMs 4bvs........AaMs
......ApM6 Aaws ...ARMs .._SRNs ARMs ARMs .%aws ..:.ARMs ..:.ARMs..._
Power factor
>-0.99
..
Total harmonic distortion at rated ower
p......
•9
:..:..
< 2°/a """
.....-.
YP ...::.
Gnd Winn termination t e
Terminal block Pressure clamp AWG10 AWG4
Reverse polarityprotectionYes'
....:
Over-voltage protection type
..........................
Vanstor, 2 for each channel '
' PV array ground fault detection
.........................................................................................................
Pre start-up Riso and Dynamic GFDI-(requires floating arrays)
-Output�protectlon�devlcesi� :: .-
•�����'� �`��"�`� - =r ;� •
Anti islandmgprotection
.... ......, ......
Meets UL 1741/IEEE1547•requirements
Over voila a rotection t e
g.....P........... Y.P...
..............................................
.... Varistor, 2 (L, . ""
...
' Maximum AC OCPD Rating 20A,20A
....
15A 25A 20A 20A.20A.20A 20A 25A 25A' ` 25A
Efficieney�uP�����a
Maximum efficiency ; 96.9%
........ :..:
97% 97% 97%
CEC efficiency _
9640... ,
Ope�atlig perfor`cancel`s��l�.;^�"���i$„>�=`��`a'��a`���•�`,%�'��, ���"��a��.�'�`j
Night time consumption
< 0.6W 1111
Stand-by consumption
< 8W
Whdh
- User interface °
... ..... .................................... ....... .......
16 characters x 2lines LCD display
....... ....................... . ...
Remote monitoring (1xRS485 Incl.)
..
VSN700 Data Logger (opt.)
EnVironmental,.'�s�1`
Ambient air operatingtemperature ran a
..............P.......................... ......
13. F to.+140°F with derating above 122'F (50 C�
..... .......�
Ambient air storage temperature range :..:..
....... ...... .......
40 F to+176 F ( 40 C to +80°C)
..
Relative humidity...:...............................:..............................:i.......:
.. '.
0.100..'o RH•condensin
.................................... .............................
Acoustic noise emission levet _
.. .........
<50 db (A) @1m
Maximum operating'altitutde without derating
..................... ..... ........ .
6560 ft (2000 m) x .
" 1. Capability enabled at nominal AC voltage and with sufFlclent DC power available
,..
.. ... ..., .....
2 'ABB Solar Inverters l Product flyer for PVI-3.0/3 6/3.8/4:2-TL-OUTD
" , /
v
This family of single-phase string
The high-speed MPPT offers real-
Highlights:
inverters complements the typical
time power tracking and improved
— Single phase and split phase output
number of rooftop solar panels
energy harvesting.
grid connection. .
enabling home -owners to get the most
The flat efficiency curve ensures high
— Wide input range for increased
efficient energy harvesting for the size
efficiency at all output levels allowing
stringing flexibility,
of the property.
a consistent and stable performance
— The high speed and precise MPPT
across the entire input voltage and
algorithm offers real time power
This inverter offers a dual input
output power range.
tracking and improved energy
section that processes two strings
The transformerless operation gives the
harvesting.
with independent Multiple Power Point
highest efficiency of up to 97.0%.
— Outdoor NEMA 4X rated enclosure
Tracking (MPPT).
The wide input voltage range makes
for unrestricted use under any
This is especially useful for rooftop
the inverter suitable to low power
environmental conditions.
installations with two different
installations with reduced string size.
— Integrated DC disconnect switch
orientations from two sub -arrays
This rugged outdoor inverter has been
in compliance with international
oriented in different directions. (For
designed to be a completely sealed
Standards (-S Version).
example: East and West)
unit able to withstand the harshest
The dual input sections with
environmental conditions:
independent MPPT enable a more
optimal energy harvesting condition.
dower and produCfiivity
for a better world "' _p lip 1P
Sunmodule;--/ sw245 - 255 poly/Pro-Series
PERFORMANCE UNDER STANDARD TEST CONDITIONS (STC)'
PERFORMANCE AT 800 W/M2, NOCT, AM 1.5
i
SW 245
SW 250
SW255
Maximum power P'%
245 Wp
250 Wp
25S Wp
Open circuit voltage V
37.3 V
37.6 V +
38.0 V
Maximum power point voltage VmPP
30.1 V
30.5 V i
30.9 V
Short circuit current 1„
8.75 A
8.81 A !<
8.88 A
Maximum power point current I -PP
8.22 A
8.27 A I
8.32 A
Measuring tolerance (P...) traceable to TUV Rheinland: +/-2% (TUV Power controlled)
Maximum power point current
1
'STC:1000W/mr,2S'C.AM1.5
PERFORMANCE AT 800 W/M2, NOCT, AM 1.5
i
PP
Minor reduction inefficiency under partial load conditions at 25' C: at 200 W/m',100%(+/-2%) of the STC efficiency (1000 W/m')isachieved.��
I
.x4 I 37.44(9SI) DIMENSIONS COMPONENT MATERIALS
65.94
SW 245
f SW 250 ,
SW255
Maximum power
P
182.3 Wp
185.4 Wp
188.7 Wp
Open circuit voltage
V
34.0 V
{ 34.2 V
34.5 V
Maximum power point voltage
VmPP
27.4 V
27.8 V
28.1 V
Short circuit current
Ir
7.19 A
I 7.24 A
7.30 A
Maximum power point current
1
6.64 A
6.68 A
6.72 A
PP
Minor reduction inefficiency under partial load conditions at 25' C: at 200 W/m',100%(+/-2%) of the STC efficiency (1000 W/m')isachieved.��
I
.x4 I 37.44(9SI) DIMENSIONS COMPONENT MATERIALS
65.94
Module votrage (v) V.
Operating range -40' C to +85' C
SolarWorld USA reserves the right to make specification changes without notice. This data sheet complies with the requirements of EN 50380.
'All units are imperial. SI units provided in parenthesis. SW-01-6050US 01-2014
Length 65.94 in (1675 mm)
Cells per module
60
1.33 (288)
Width 39.41 in (1001 mm)
Cell type
Poly crystalline
Height 1.22 in (31 mm)
Cell dimensions
156 mm x ISIS mm
Frame Clear anodized aluminum
Front
Tempered glass (EN 12150)
Weight 46.7 lbs (21.2 kg)
Version
2.5 frame
bottom
mounting
THERMAL CHARACTERISTICS
ADDITIONAL DATA
holes
NOCT 46'C
Powersorting
-0 Wp/+S Wp
TCI„ 0.081 %/'C
J -Box
IP65
TCV , -0.37 %/'C
Module leads
PV wire per UL4703 with
TCPmPP -0.45 %/'C
H4 connectors
1x4
4.20 (107)t
PARAMETERS FOR OPTIMAL SYSTEM INTEGRATION
Maximum system voltage SC 11
1000 V
Maximum reverse current
16A
Load/dynamic load
5.4/2.4 kN/m'
Number of bypass diodes
3
Module votrage (v) V.
Operating range -40' C to +85' C
SolarWorld USA reserves the right to make specification changes without notice. This data sheet complies with the requirements of EN 50380.
'All units are imperial. SI units provided in parenthesis. SW-01-6050US 01-2014
Sunmodule;-,"'sw245 - 255 poly/ Pro -Series
44 ITO 01.
TUV Power controlled:
TOVRhainland ` Lowest measuring tolerance in industry
i
,O 000002p�'�1
I' Every component is tested to meet
3 times IEC requirements
J
Designed to withstand heavy
accumulations of snow and ice
J
Q5unmodule Plus:
Positive performance tolerance
a
ZS 25 -year linear performance warranty
and 10 -year product warranty
J
Glass with anti -reflective coating
J
World-class quality
Fully -automated production lines and seamless monitoring of the process and material
ensure the quality that the company sets as its benchmark for its sites worldwide.
SolarWorld Plus -Sorting
Plus -Sorting guarantees highest system efficiency. SolarWorld only delivers modules that
have greater than or equal to the nameplate rated power.
25 years linear performance guarantee and extension of product warranty to 10 years
SolarWorld guarantees a maximum performance degression of 0.7% p.a. in the course of
25 years, a significant added value compared to the two-phase warranties common in the
industry. In addition, SolarWorld is offering a product warranty, which has been extended
to 10 years.'
'in accordance with the applicable SolarWorld Limited Warranty at purchase.
www.solarworld.com/warranty
• QUWR•4.1 61115 =i!^. 3 • �mn,.na n.aanv
s.aya.aa.IECGIM
DyE • P. ratlk ln.we0an
• Riovrir�{i •aatl n.kant
s.r .;:,• S( P.r 1. W—fl n
ii SSS Pewvr C-1kd
— PESIOR4.1 11CSRU
« x
v
C us
Jr
UL 1703
A I
•• .��
SOLARWORLD
solarworld.com We turn sunlight into power.