PLBG (9906-142)LICENSED CONTRACTOR DECLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of
Chapter 9 (commencing with Section 7000) of Division 3 of the Business and
Professionals Code, and my License is in full force and effect.
License # Lic. Class Exp. Date
f '1461,59 C42 - 02i29i20t
Date -9 G.� •.; Signature of Contractor
OWNER -BUILDER DECLARATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's
License Law for the following reason:
( ) I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for
sale (Sec. 7044, Business & Professionals Code).
( ) I, as owner of the property, am exclusively contracting with licensed
contractors to construct the project (Sec. 7044, Business & Professionals
Code).
( ) I am exempt under Section , B&P.C. for this reason
Date Signature of Owner
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
( ) I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided. for by Section 3700 of the Labor Code, for the
performance of the work for which this permit is issued.
( )� I have and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which this
permit is issued. My workers' compensation insurance carrier & policy no. are:
Carrier Policy No.
(This section nedTnoF0e completed if the permit valuation Is for $100.00 or less).
( ) I certify that in the performance of the work for which this permit is issued,
I shall not employ any person in any manner so as to become subject to the
workers' compensation laws of California, and agree that if I should become
subject to the workers' compensation -provisions of Section 3700 of the Labor
Code, I shall forthwith comply with those provisions.
Date: -, A, & — Applicant { • I
F�> G• t------------
�11Varning: Failure to secure Workers' Compensation coverage is unlawful and
shall subject an employer to criminal penalties and civil fines up to $100,000, in
addition to the cost of compensation, damages as provided for in Section 3706
of the Labor Code, interest and attorney's fees.
IMPORTANT Application is hereby made to the Director of Building and Safety
for a permit subject to the conditions and restrictions set. forth on his
application.
1. Each person upon whose behalf this application is made &.each person at
whose request and for whose benefit work is performed under or pursuant to
any permit issued as a result of this applicaton agrees to, & shall, indemnify
& hold harmless the City of La Quinta, its officers, agents and employees.
2. Any permit issued as a result of this application becomes null and void if
work is not commenced within 180 days from date of issuance of such
permit, or cessation of work for 180 days will subject permit to cancellation.
I certify that I have read this application and state that the above information is
correct. I agree to comply with all City, and State laws relating to the building
construction, and hereby authorize representatives of this City to enter upon
the above-mentioned property -for inspection purposes.
Signature (Owner/Agent) ` � � Date .� jr�_•
BUILDING PERMIT PERMIT#
DATE VALUATION LOT "06-142 TRACT
1
JOB'SITE r
APN
ADDRESS
52-995 AVLWIDA iVlfJ(3r D07.A
773-332'021
OWNER
CONTRACTOR / DESIGNER / ENGINEER
MS EVANGELINA VALENCIA
ECONO SENVER SERVICE
$2.885 AVENiDA. IvIENDOZA.
540,35 C,ABAZON PLD, INI -D10, CA 9220.1
LA QUINTA Cil 92253
PALM DESERT CA 92^6'I
0/60)346-2793 CBL#i 34*
USE OF PERMIT
fh 4p Tni s
'"TIC ABANDON - SEZVEt2 CONNECTiON - LOW -MOD PROJECT(99.04)
CONTRA;C T' .AMO NT
PERMIT FEE SUMMARY
� --
NAIMINO VC,0 •-- SEWER 101-000-419-000 $30.00
ja
JUN 2 21999
SUB-TUDA1., CONSTRUMON PIAN CI ECT 4
$30.00
LESS ME -PAW FE
ot3,(3G
TOT A% PE1RIMI`t' FEFLS DIf E NOW
$30.00
r V),
RECEIPT
DATE
BY ' 1 )
D T FI D
INSPECTOR
/ '/
INSPECTION RECORD
OPERATION
DATE
INSPECTOR
OPERATION
DATE
INSPECTOR
BUILDING APPROVALS
MECHANICAL APPROVALS
Set Backs
Underground Ducts
Forms & Footings
Ducts
Slab Grade
Return Air
Steel
Combustion Air
Roof Deck
Exhaust Fans
O.K to Wrap
F.A.U.
Framing
Compressor
Insulation
Vents
Fireplace P.L.
Grills
Fireplace T.O.
Fans & Controls
Party Wall Insulation
Condensate Lines
Party Wall Firewall
Exterior Lath
Drywall - Int. Lath
Final
Final
BLOCKWALL APPROVALS
POOLS - SPAS
Steel
Set Backs
Electric Bond
Footings
Main Drain
Bond Beam
Approval to Cover
Equipment Location
Underground Electric
Underground Plbg. Test
Final
Gas Piping
PLUMBING APPROVALS
Gas Test
Electric Final
Waste Lines
Neater Final
Water Piping
Plumbing Final
Plumbing Top Out
Equipment Enclosure
Shower Pans
O.K. for Finish Plaster
Sewer Lateral
Pool Cover
Sewer Connection
Encapsulation
Gas Piping
Gas Test
Appliances
Final
Final
Utility Notice (Gas) 1
ELECTRICAL APPROVALS
Temp. Power Pole;
Underground Conduit
Rough Wiring
Low Voltage Wiring
Fixtures
Main Service
Sub Panels
Exterior Receptacles
G.F.I.
Smoke Detectors
Temp. Use of Power
Final
Utility Notice (Perm)
COMMENTS:
Project: 2x4truss-gutierrez
Phong Truong, SUN STRONG STRUCTURAL May 08, 2015
F:\SC 15-05052-UnitedField-52885-Gutierrez\
Result Cases Extreme Rows Only)
Result Case Name
Design Group Results
Design Group: Wood -Beam X_G01 per NDS 2012 ASD
Designed As: FS2x4, Material: \NDS Lumber (Visual)\No.1\Douglas Fir -Larch
Members Included (6): BmX005, 13mX001, BmX002, BmX003, BmX004, BmX006
Strona Flexure Check
Checks
Member
Name
Result
Case
Demand fbz
Ksi
Capacity Fbz
Ksi
Code
Ref.
Unity
Check ,
BMX005
D+.6H
-0.008
1.334
3.3-1
0.01 OK
BmX001
D+.6H
0.076
1.334
3.3-1
0.06 OK
BmX002
D+.6H
-0.008
1.334
3.3-1
0.01 OK
BmX003
D+.6H
-0.008
1.334
3.3-1
0.01 OK
BmX004
D+.6H
•-0.008
1.334
3.3-1
0.01 OK
BmX006
D+.6H
0.076
1.334
3.3-1
0.06 OK
Strona Shear Check
Member
Name
Result
Case
Demand fvz
Ksi
Capacity Fvz
Ksi
Code
Ref.
Unity
Check
BmX005
D+.75(L+.6W+Lr) A -Y
-0.001
0.288
3.4-2
0.00 OK
BmX001
D+.75(L+.6W+Lr) n -Y
-0.003
0.288
3.4-2
0.01 OK
BmX002
D+.75(L+.6W+Lr) »-Y
-0.001
0.288
3.4-2
0.00 OK
BmX003
D+.75(L+.6W+Lr) »-Y
-0.001
0.288
3.4-2
0.00 OK
BmX004
D+.75(L+.6W+Lr) p -Y
-0.001
0.288
3.4-2
0.00 OK
BmX006
D+.6H
0.003
0.162
3.4-2
0.02 OK
Design Group: Wood -Column -G02 per NDS 2012 ASD
Designed As: FS2x4, Material: \NDS Lumber (Visual)\No.1\Douglas Fir -Larch
Members Included (5): C01-005, C01-004, C01-003, COL002, COL001
Axial Check
Member
Name
Result
Case
Demand fa
Ksi
Capacity Fa
Ksi
Code
Ref.
Unity
Check
COL005
D+.6H
0.000
1.464
3.6.3
0.00 OK
COL004
D+.6H
0.000
1.080
3.6.3
0.00 OK
COL003
D+.6H
0.000
0.618
3.6.3
0.00 OK
COL002
D+.6H
0.000
0.911
3.8.1
0.00 OK
COL001
D+.6H
0.000
0.911
3.8.1
0.00 OK
Design Group: Wood -Roof X_G03 per NDS 2012 ASD
Designed As: FS2x4, Material: \NDS Lumber (Visual)\No.1 \Douglas Fir -Larch
Members Included (8): RBX001, RBX002, RBX005, RBX004, RBX003, RBX006, RBX007, RBX008
Combined Check
Member Result Code Unity
Name Case Ref. Check
RBX001 D+.6H 3.9 -2 -Strong 0.15 OK
Page 1
VisualAnalysis 11.00.0004 (www.iesweb.com)
Member
Name
Result
Case
Demand fa
Ksi
Project: 2x4truss-gutierrez
Code
Ref.
Unity
Check
Phong Truong, SUN STRONG STRUCTURAL
May 08, 2015
0.003
F:\SC15-05052-UnitedField-52885-Gutierrez\
3.6.3
0.00 OK
RBX002 D+.6H
3.9 -2 -Strong
0.12 OK -
RBX005 .6D+.6W u -Y
3.9 -2 -Strong
0.18 OK
RBX004 D+.6H
3.9 -2 -Strong
0.12 OK
RBX003 D+.6H
3.9 -2 -Strong
0.12 OK
RBX006 D+.6H
3.9 -2 -Strong
0.15 OK
Axial Check
3.6.3 _
0.00 OK
Member
Name
Result
Case
Demand fa
Ksi
Capacity Fa
Ksi
Code
Ref.
Unity
Check
RBX001
D+.6H
0.003
0.606
3.6.3
0.00 OK
RBX002
D+.6H
0.003
0.734
3.6.3
0.00 OK
RBX005
D+.6W N -Y
0.004
0.801
3.6.3
0.01 OK
RBX004
D+.6W »-Y
0.003
0.801
3.6.3 _
0.00 OK
RBX003
D+.6H
0.003
0.734
3.6.3
0.00 OK
RBX006
.6D+.6W ))-Y
0.003
0.644
3.6.3
0.01 OK
RBX007
D+.6H
0.000
0.477
3.6.3
0.00 OK
RBX008
D+.6H
0.000
0.477
3.6.3
0.00 OK
Strona Flexure Check
Member
Name
Result
Case
Demand fbz
Ksi
Capacity Fbz
Ksi
Code
Ref.
Unity
Check
RBX001
D+.6H
-0.196
1.333
3.3-1
0.15 OK
RBX002
D+.6H
-0.156
1.333
3.3-1
0.12 OK
RBX005
.6D+.6W u -Y
0.422
2.335
3.3-1
0.18 OK
RBX004
D+.6H
-0.156
1.333
3.3-1
0.12 OK
RBX003
D+.6H -
-0.156
1.333
3.3-1
0.12 OK
RBX006
.6D+.6W »-Y
-0.224
2.335
3.3-1
0.10 OK
RBX007
D+.6H
0.013
1.333
3.3-1
0.01 OK
RBX008
D+.6H
0.013
1.333
3.3-1
0.01 OK
Strona Shear Check
Member
Name
Result
Case
Demand fvz
Ksi
Capacity Fvz
Ksi
Code
Ref.
Unity
Check
RBX001
D+.75(L+.6W+Lr) ))-Y
-0.017
0.288
3.4-2
0.06 OK
RBX002
D+.75(L+.6W+Lr) »-Y
0.015
0.288
3.4-2
0.05 OK
RBX005
.6D+.6W »-Y
0.042
0.288
3.4-2
0.14 OK
RBX004
.6D+.6W n -Y
0.024
0.288
3.4-2
0.08 OK
RBX003
D+.75(L+.6W+Lr) »-Y
0.015
0.288
3.4-2
0.05 OK
RBX006
.6D+.6W »-Y
-0.018
0.288
3.4-2
0.06 OK
RBX007
D+.75(L+.6W+Lr) »-Y
0.001
0.288
3.4-2
0.00 OK
RBX008
D+.75 L+.6W+Lr »-Y
0.001
0.288
3.4-2
0.00 OK
Design Group: Wood -V Brace -G04 per NDS 2012 ASD
Designed As: FS2x4, Material: \NDS Lumber (Visual)\No.1\Douglas Fir -Larch
Members Included (2): V001, V002
Axial Check
Member
Result
Demand fa
Capacity Fa
Code
Unity
Name
Case
Ksi
Ksi
Ref.
Check
V001
D+.6H
0.000
0.390
3.6.3
0.00 OK
V002
D+.6H
0.000
0.390
3.6.3
0.00 OK
Strona Flexure Check
Member
Result
Demand fbz .
Capacity Fbz
Code
Unity
Name
Case
Ksi
Ksi
Ref.
Check
V001
D+.6H
0.014
1.331
3.3-1
0.01 OK
V002
D+.6H
0.014
1.331
3.3-1
0.01 OK
Page 2
VisualAnalysis 11.00.0004 (www.iesweb.com)
Prbject: 2x4truss-gutierrez
Phong Truong, SUN STRONG STRUCTURAL May 08, 2015
F:\SC 15-05052-UnitedField-52885-Gutierrez\
Strona Shear Check
Member
Result
Demand fvz
Capacity Fvz
Code
Unity
Name
Case
Ksi
Ksi
Ref.
Check
V001
D+.75(L+.6W+Lr) v -Y
-0.001
0.288
3.4-2
0.00 OK
V002
D+.75 L+.6W+Lr ))-Y
-0.001
0.288
3.4-2
0.00 OK
t
Page 3
VisualAnalysis 11.00.0004 (www.iesweb.com)
5/8/2015
SEISMIC WEIGHT COMPARISON / ANALYSIS
(PER CHAPTER 34)
Solar Panel Type = Solar World-250
Total # of Panels = 8 panels
Panel Weight = 46.7 lbs
Total Weight, W = 373.60 lbs
Existina Roof Story Weight Considered in Seismic Design
(Wood Framed Building With Comp. Shingle Roof & Stucco Exterior)
Building Section Considered Dimensions = 30 feet x 40 feet (8 feets wall height)
Roof Area Considered Dimensions = 33 feet x 43 feet (18 inches roof overhang)
Comp. Roofing .12 psf x 1 roof x 33 ft long x 43 ft long = 17,028 lbs
Ext. Walls (Long.) 15 psf x 2 walls x 40 ft long x 4 ft high = 4,800 lbs
Ext. Walls (Trans.) 15 psf x 2 walls x 30 ft long x 4 ft high = 3,600 lbs
Int. Walls (Drywall) 10 psf x 2 walls x 15 ft long x 4 ft high = 1,200 lbs
Total Roof Story Weight, Sw = 26,628 lbs
Total Percentage of Panel Weight vs. Total Exlsting Roof Seismic Weight, AW
Aw = [Pw + Sw] x 100 % _ [ 373.6 lbs + 26,628 lbs ] x 100 = 1 % < 10% [OK]
T ,
-Project: 2x4truss-gutierrez
Phong Truong, SUN STRONG STRUCTURAL May 08, 2015
F:\SC 15-05052-UnitedField-52885-Gutierrez\
Member Extreme Results
Member
Fx Ic
V Ic
Vz Ic
Mx Ic
M Ic
Mz Ic
K
K
K
K -ft
K -ft
K -ft
BMX001
0.000 34
-0.015(37)
-0.000(34)
0.000 34
-0.000(34)
-0.022(37)
BmX001
0.000 37
-0.004(34)
-0.000(34)
0.000 34
4000 34
0.034 37
BmX002
-0.000(37)
-0.004(37)
-0.000(34)
0.000 34
-0.000(34)
-0.004(37)
BmX002
-0.000(34)
0.004 37
-0.000(34)
0.000 34
-0.000(34)
0.002 37
BmX003
0.000 34
-0.004(37)
-0.000(34)
0.000 34
-0.000(34)
-0.004(37)
BmX003
0.000 37
0.004 37
-0.000(34)
0.000 34
-0.000(34)
0.002 37
BMX004
0.000 34
-0.004(37)
-0.000(34)
0.000 34
-0.000(34)
-0.004(37)
BmX004
0.000 37
0.004 37
-0.000(34)
0.000 34
-0.000(34)
0.002 37
BmX005
-0.000(37)
-0.004(37)
-0.000(34)
0.000 34
-0.000(34)
-0.004(37)
BmX005
-0.000(34)
0.004 37
-0.000(34)
0.000 34
-0.000(34)
0.002 37
BmX006
-0.000(34)
-0.013(34)
-0.000(34)
0.000 34
-0.000(34)
-0.036(34)
BmX006
-0.000(37)
-0.001(37)
-0.000(34)
0.000 34
-0.000(34)
0.015 34
COL001
-0.001(37)
0.000 34
-0.000(34)
0.000 34
-0.000(34)
0.000 34
COL001
0.001 37
0.000 37
-0.000(34)
0.000 34
-0.000(34)
0.000 37
COL002
-0.003(37)
0.000 34
-0.000(34)
0.000 34
-0.000(34)
0.000 34
COL002
0.003 37
0.000 37
-0.000(34)
0.000 34
-0.000(34)
0.000 37
COL003
-0.004(37)
0.000 37
-0.000(34)
0.000 34
-0.000(34)
0.000 34
COL003
0.004 37
0.000 34
-0.000(34)
0.000 34
-0.000(34)
0.000 34
COL004
-0.003(37)
-0.000(37)
-0.000(34)
0.000 34
-0.000(34)
-0.000(37)
COL004
0.003 37
-0.000(34)
-0.000(34)
0.000 34
-0.000(34)
0.000 34
COL005
-0.001(37)
0.000 37
-0.000(34)
0.000 34
-0.000(34)
0.000 34
COL005
0.001 37
0.000 34
-0.000(34)
0.000 34
-0.000(34)
0.000 34
RBX001
-0.024(37)
-0.090(37)
-0.000(34)
0.000 34
-0.000(34)
-0.087(37)
RBX001
0.024 37
0.069 37
-0.000(34)
0.000 34
-0.000(34)
0.045 37
RBX002
-0.024(37)
-0.080(37)
-0.000(34)
0.000 34
-0.000(34)
-0.069(37)
RBX002
0.024 37
0.080 37
-0.000(34)
0.000 34
-0.000(34)
0.035 37
RBX003
-0.024(37)
-0.080(37)
-0.000(34)
0.000 34
-0.000(34)
-0.069(37)
RBX003
0.024 37
0.080 37
-0.000(34)
0.000 34
-0.000(34)
0.035 37
RBX004
-0.024(37)
-0.066(37)
-0.000(34)
0.000 34
-0.000(34)
-0.054(37)
RBX004
0.034 34
0.129 34
-0.000(34)
0.000 34
-0.000(34)
0.051 34
RBX005
-0.036(37)
-0.098(37)
-0.000(34)
0.000 34
-0.000(34)
-0.108(34)
RBX005
0.061 34
0.223 34
-0.000(34)
0.000 34
-0.000(34)
0.188 34
RBX006
-0.026(34)
-0.097(34)
-0.000(34)
0.000 34
-0.000(34)
-0.100(34)
RBX006
0.026 37
0.079 37
-0.000(34)
0.000 34
-0.000(34)
0.090 34
RBX007
-0.001(37)
-0.005(37)
-0.000(34)
0.000 34
-0.000(34)
0.000 34
RBX007
0.001 37
0.005 37
-0.000(34)
0.000 34
-0.000(34)
0.006 37
RBX008
-0.001(37)
-0.005(37)
-0.000(34)
0.000 34
-0.000(34)
-0.000(34)
RBX008
0.001 37
0.005 37
-0.000(34)
0.000 34
-0.000(34)
0.006 37
V001
-0.003(37)
-0.004(37)
-0.000(34)
0.000 34
-0.000(34)
-0.000(34)
V001
0.003 37
0.004 37
-0.000(34)
0.000 34
-0.000(34)
0.006 37
V002
-0.003(37)
-0.004(37)
-0.000(34)
0.000 34
-0.000 34
-0.000(34)
V002
0.003 37
0.004 37
-0.000 34
0.000 34 ,
-0.000(34)
0.006 37
Project: 2x4truss-gutierrez
Phong Truong, SUN STRONG STRUCTURAL May 08, 2015
F:\SC 15-05052-UnitedField-52885-Gutierrez\
Model Summary
Structure Type: Space Frame
12 Nodes, and 6 Degrees of Freedom
21 Member Elements
The model is linear.
The model will have 6 unique mode shapes.
The size of the model is:
30 ft, in the X direction
4.500 ft, in the Y direction
0 It, in the Z direction
Load Cases
Load Case Design Checks Seismic Type Results
(34).6D+.6W » -Y Allowable (ASD) -NA- Yes
(37)D+.6W n -Y Allowable (ASD) -NA- Yes
Nodes
Node
X
Y
Z
Fix DX
Fix DY
Fix DZ
Fix RX
Fix RY
Fix RZ
Scissor?
ft
ft
ft
ft
BmX001
FS2x4
N001
0.000
0.000
0.000
Yes
Yes
Yes
No
No
No
No
N002
5.000
1.500
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
N003
10.000
3.000
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
N004
15.000
4.500
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
N005
20.000
3.000
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
N006
25.000
1.500
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
N007
30.000
0.000
0.000
Yes
Yes
Yes
No
No
No
No
N008
5.000
0.000
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
N009
10.000
0.000
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
N010
15.000
0.000
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
N011
20.000
0.000
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
N012
25.000
0.000
0.000
Yes
Yes
Yes
Yes
Yes
Yes
No
Member Elements
Member
Section
Material
(1)Node
(2)Node
Length
Rz1
Rz2
One Way
Framing
ft
BmX001
FS2x4
Douglas Fir -Larch
N001
N008
5.000
Rigid
Rigid
Normal(2-way)
Beam
BmX002
FS2x4
Douglas Fir -Larch
N008
N009
5.000
Rigid
Rigid
Normal(2-way)
Beam
BmX003
FS2x4
Douglas Fir -Larch
N009
N010
5.000
Rigid
Rigid
Normal(2-way)
Beam
BmX004
FS2x4
Douglas Fir -Larch
N010
N011
5.000
Rigid
Rigid
Normal(2-way)
Beam
BmX005
FS2x4
Douglas Fir -Larch
N011
N012
5.000
Rigid
Rigid
Normal(2-way)
Beam
BmX006
FS2x4
Douglas Fir -Larch
N012
N007
5.000
Rigid
Rigid
Normal(2-way)
Beam
COL001
FS2x4
Douglas Fir -Larch
N008
N002
1.500
Free
Free
Normal(2-way)
Column
COL002
FS2x4
Douglas Fir -Larch
N009
N003
3.000
Free
Free
Normal(2-way)
Column
COL003
FS2x4
Douglas Fir -Larch
N010
N004
4.500
Free
Free
Normal(2-way)
Column
COL004
FS2x4
Douglas Fir -Larch
N011
N005
3.000 Free
Free
Normal(2-way)
Column
COL005
FS2x4
Douglas Fir -Larch
N012
N006
1.500
Free
Free
Normal(2-way)
Column
RBX001
FS2x4
Douglas Fir -Larch
N001
N002
5.220
Rigid
Rigid
Normal(2-way)
Beam
RBX002
FS2x4
Douglas Fir -Larch
N002
N003
5.220
Rigid
Rigid
Normal(2-way)
Beam
RBX003
FS2x4
Douglas Fir -Larch
N003
N004
5.220
Rigid
Rigid
Normal(2-way)
Beam
RBX004
FS2x4
Douglas Fir -Larch
N004
N005
5.220
Rigid
Rigid
Normal(2-way)
Beam
RBX005
FS2x4
Douglas Fir -Larch
N005
N006
5.220
Rigid
Rigid
Normal(2-way)
Beam
RBX006
FS2x4
Douglas Fir -Larch
N006
N007
5.220
Rigid
Rigid
Normal(2-way)
Beam
RBX007
FS2x4
Douglas Fir -Larch
N002
N009
5.220
Free
Free
Normal(2-way)
Beam
RBX008
FS2x4
Douglas Fir -Larch
N011
N006
5.220
Free
Free
Normal(2-way)
Beam
V001
FS2x4
Douglas Fir -Larch
N003
N010
5.831
Free
Free
Normal(2-way)
Bracin
V002
FS2x4
Douglas Fir -Larch
N010
N005
5.831
Free
Free
Normal(2-way)
Bracin
Page 1
VisualAnalysis 11.00.0004 (www.iesweb.com)
2x4truss-gutierrez
SUN STRONG STRUCTURAL, Phong Truong
May 08, 2015:01:13 PM
Load Case: D
IES VisualAnalysis 11.00.0004
TRUSS DEAD LOADING
2x4truss-gutierrez
SUN STRONG STRUCTURAL, Phong Truong
May 08, 2015; 01:13 PM
Load Case: W-Y
IES VisualAnalysis 11.00.0004
TRUSS UPLIFT WIND LOADING FROM ANCHORS
S7 KUU i URAL
Structural. Solutions for All Your Solar Needs
Structural Calculations for
SOLAR PANEL SYSTEM CONNECTIONS at:
52885 AVENIDA MENDOZA
LA QUINTA, CA 92253
Job # 15. 05052 (Evangelina Gutierrez)
Prepared For:
UNITED FIELD REMODELING, INC.
17514 Ventura Blvd. # 206
Encino, CA 91316
(818) 748-2300
Design Criteria
1- Code: CALIFORNIA BLDG CODE 2013 / ASCE 7-10
2- Wind: ,110 MPH, Exposure: C
3- Wood Species: Douglas Fir Larch (G = 0.5)
Notice: Use restrictions of these calculations.
The attached Calculations are valid only when bearing original signature hereon, photocopy is void.
Contractor/Client to verify existing dimensions/conditions prior to construction.
The use of these calculations is solely intended for the above mentioned project.
949.254.27511 nwtruong@yahoo.com
21308 PATHFINDER RD. SUITE 220, DIAMOND BAR, CA 91765
5/8/2015
JUN 01 20
CITY Or LA.
`ommut4ITV LbL
7
WIND LOADING ANALYSIS - Roof Components and Cladding
Per ASCE 7-10 Code for Bldgs. of Any Height with Gable Roof 0 <= 45° or Monoslope Roof 9 <= 30
Using Part 1 & 3: Analytical Procedure Section 30.4 & 30.6
Job Name: IGutierrez Residence Subject: I Wind Analysis for 1 -Story Building
Job Number. S15-05052 Originator I I Checker.
Input Data:
r
Wind Speed, V = 110 mph (Wind Map, Figure 26.5 -1A -C)
Bldg. Classification = II (Table 1-1 Occupancy Category)
Exposure Category = C (Sect. 26.7) B
Ridge Height, hr = 12.87 ft. (hr - he)
Eave Height, he = 8.00 ft (he <= hr)
Building Width = 30.00, ft. (Normal to Building Ridge)
Building Length = 40.00 ft. (Parallel to Building Ridge) L
Roof Type = Gable (Gable or Monoslope)
Topo. Factor, Kzt = 1.00 (Sect. 26.8 & Figure 26.8-1) Plan
Direct. Factor, Kd = 0.85 ' (Table 26.6)
Enclosed? (Y/N) Y (Sect. 28.6-1 & Figure 26.11-1)
Hurricane Region? N 8
Component Name = Fastener (Purlin, Joist, Decking, or Fastener) hr
Effective Area, Ae = 141.44 ft.112 (Area Tributary to C&C) h he
Overhangs? (Y/N) N (if used, overhangs on all sides)
L
Resultina Parameters and Coefficients: Elevation
Roof Angle, 0 = 18.00 deg.
Mean Roof Ht., h = 10.44 ft. (h = (hr+he)/2, for roof angle >10 deg.)
Roof External Pressure Coefficients, GCp:
GCp Zone 1-3 los. = 0.30 (Fig. 30.4-2A, 30.4-2B, and 30.4-2C)
GCp Zone 1 Neg. _ -0.80 (Fig. 30.4-2A, 30.4-2B, and 30.4-2C)
GCp Zone 2 Neg. _ -1.20 (Fig. 30.4-2A, 30.4-2B, and 30.4-2C)
GCp Zone 3 Neg. _ -2.00 (Fig. 30.4-2A, 30.4-213, and 30.4-2C)
Positive & Negative Internal Pressure Coefficients, GCpi (Figure 26.11-1): _
+GCpi Coef. = 0.18 (positive internal pressure)
-GCpi Coef. = 0.18 1 (negative internal pressure)
If z <= 15 then: Kz = 2.01 *(1 5/z)^(2/a) , If z > 15 then: Kz = 2.01 *(z/zg)^(2/a) (Table 30.3-1)
Cc =E9L5O(Table 26.9-1)
zg =(Table 26.9-1)
Kh =(Kh = Kz evaluated at z = h)
Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2 (Sect. 30.3.2, Eq. 30.3-1)
qh = 22.35 psf qh = 0.00256*Kh*Kzt*Kd"V^2 (qz evaluated at z = h)
Design Net External Wind Pressures (Sect. 30.4 & 30.6):
For h <= 60 ft.: p = qh*((GCp) - (+/-GCpi)) (psf)
For h > 60 ft.: p = q*(GCp) - qi*(+/-GCpi) (psf)
where: q = qh for roof
qi = qh for roof (conservatively assumed per Sect. 30.6) .
5/8/2015 1:01 PM
��
�,
.
;:
�.
�. �,�
�-
,'
;-
��
�,
.
;:
s.
Roof Components and Cladding:
1a
—-
�+ ! 7 J 3 3 i !
20 43)
� k
t f
3 2 ! ! 2 !
,
0 <= 7 deg. 7 deg. < 0 <= 27 deg. 27 deg. < 0 <= 45 deg.
Roof Zones for Buildinas with h <= 60 ft.
(for Gable Roofs <= 450 and Monoslope Roofs <= 30)
, I
a I
L _
I � �
ROOF PLAN
Roof Zones for Buildings with h > 604L
(for Gable Roofs <=10° and Monoslope Roofs <= 3°)
TYPICAL PROFILE:
E
ADEQUACY CHECK OF LAG SCREWS ALONG
EXISTING FRAMING DUE TO WIND FORCES
(HOUSE)
Wind Pressure, P
Legend:
1 . Existing 2x4 Truss Chord.
2. Solar Panel Track Rail.
3. 5/16 " 9 Lag Screw w/ Min. 2.5" Penetration into Rafter.
Uplift from Solar Panel Wind Forces, U
Design Wind Pressure, P =
-30.84 psf (See Attached Wind Analysis)
Trib. Depth for Each Rail, Td=
2.7 ft (5.4 ft + 2) "
Screw Anchor Spacing, S =
_
4 ft (max.)
Resisting Weight of Panels, D = Td x S x 3 =
32.4 lbs
Uplift force on Each Screw, U = P x Td x S -D _
-300.67 lbs (Upwards)
Check Adequacy of Lag Screw for Pull -Out
Uplift Resistance Provided by 5/16 " 4p Lag Screw w/ Min. 2.5" Penetration into Rafter.
Penetration into Douglas Fir Larch Member Per NDS (Table 11.2A) = 266 lbs/in
Allowable Uplift Load, Ua = 1.6 x 2.5 x266 =
1,064 lbs > U = 300.7 lbs [OK]
Existinq Trusses Member Check
,
Truss Span =
30 ft
Roof Dead Load =
12 psf
Panel Dead Load =
3 psf -
Total Dead Load, DL =
15 psf x 2 feet (Trib.) = 30.0 psf
Screw Uplift Loads, W =
300.67 lbs (Max. 4 Anchors/Stand-offs on Truss)
*See attached Enercalc Output for Analysis Results