Loading...
RPL (14-0123) (Structural Calculations)CLIENT: Desert Outdoors (760)-275-7359 MJECT= wKBSHNEIZ WATER FEATURE 40 7 Mesa ADDFREZ: - Gi-95 W Court La Qu nta" Trilogy Country club 1 JOB �1�' V o _ A DATE:, 05 March 2ol(fl-. STRUCTURAL-AND CIVIL, ENGINEERING ' n DENISE R. POELTLER, INC. 7,7725 ENFIELD -LANE, STE. #130, PALM' DESERT, CA 92211 TEL. (760) 772-4411 FAX (760) 772-4409 drpfly@ao[.COM ty1 l jqyVVtW buttY'ew 77725 Enfield Lane, #130 Palm Desert, CA 92211 (760) 772-4411 FAX (760) 772-4409 drpfly@aol.com PROJECT: BY D DATE REVISED KIRS14NER 61"185 Masa Court La Qulnta Trilogy G.G. DESERT OUTDOORS '19405 Highway 111, Suite 9, . #42'1 La Quinta, GA 92253 (160) 215--059, 060) 399-9600 STRUCTURAL GALGULATIONS 0I -I?. PAGE_ OF 2012 Int'I Building Godo Ej�1GtNEERING SERVICES: 2013 California Building Code 1. Design steel in 3.5 -ft. high x 13 -ft. long concrete water feature. 2. Design 3' x 3' CMU pedestal, 4 -ft. high. 3. DETAIL "A": 3.5 -ft. high concrete water feature. 4. DETAIL "B 4 -ft. high, 3' square CMU pedestal I Il` a & 5 '1 NO SOILS REPORT PROVIDED. USE CBC TABLE 18062 FOR MINIMUM VALUES. Soil Classification = Silty sand Soil Bearing Pressure. = 2000 PSF Continuous Footing Equivalent Fluid Pressure = 35 PGF (Cantilever Wall, Level Backfill) Equivalent Fluid Pressure = 55 PGF (Restrained Wall, Level Backfill) Sliding Coefficient = 0?5 Passive Pressure = 150 PSF/FT OWNER/GONTRAGTOR ACCEPTS ALL LIABILITY FOR COMPACTION AND SUBSIDENCE OF UNDERLYING SOILS. C.ONGRET'E (GU IE) STRENGTH f c = 2500 PSI 28 -Day Compressive Strength No 33446 . WT = 150 PGF REINFORCING STEEL * Exp. 6-30-14- 4 F y = 40 KSI, Grade 40, ASTM A615, #3 BARS OR GREATER ��-`--I�-�.�� 9 CIV1- � IT 15 THE FULL INTENTION OF THE ENGINEER THAT THESE CALCULATIONS CONFORM TO THE CALIF. BUILDING CODE, 2013 EDITION. THESE CALCULATIONS SHALL GOVERN THE STRUCTURAL PORTION OF THE WORKING DRAWIN65. WHERE ANY DISCREPANCIES OCCUR BETWEEN THESE CALCULATIONS AND THE WORKING DRAWINGS, THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY 50 PROPER ACTION MAY BE TAKEN. THE STRUCTURAL CALCULATIONS INCLUDED ARE FOR THE ANALY515 AND DESIGN OF THE PRIMARY STRUCTURAL SYSTEM. THE ATTACHMENT OF VENEER AND NON-STRUCTURAL ELEMENTS 15 THE RESPONSIBILITY OF THE ARCHITECT, UNLE55 SPECIFICALLY 5HOWN OTHERWISE. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR WORK NOT A PART OF THESE CALCULATIONS NOR FOR INSPECTION TO ENSURE CONSTRUCTION 15 PERFORMED IN ACCORDANCE WITH THESE CALCULATIONS. 5TRUCTURAL OBSERVATION OR FIELD INVESTIGATION SERVICES ARE RETAINED UNDER A SEPARATE CONTRACT. 1 &c& flyC+i* but ew BY DATE KIR.S+INER 77725 Enfield Lone, #130 REVISED 61185 Mesa Court PAGE a. Palm Desert, CA 92211, Lo Quints (760) 772-4411 FAX (760) 772-4409 TNlogy G.G. OFA@_ drpfly@noL.com PROJECT: DESERT OUTDOORS ?9405 Highway III, Sults 9, #42'1 La Quints, GA 92253 (160) 215.1559, ("160) 599-9600 BASI5 OF 2E51GN CODE INTERNATIONAL BUILDING GODS (IBC), 2012 EDITION CALIFORNIA BUILDING CODE (GBG), 2013 EDITION INTERNATIONAL CONFERENCE OF BUILDING OFFICIALS ASCE 1-10 MINIMUM DESIGN LOADS FOR BUILDINGS STEEL MANUAL OF STEEL CONSTRUCTION, ALLOWABLE STRESS DESIGN (A156 341-10) FOURTEENTH EDITION, AMERICAN INSTITUTE OF STEEL CONSTRUCTION CONCRETE BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (AGI), AGI 518-11 AMERICAN CONCRETE INSTITUTE WOOD NATIONAL DESIGN OF SPECIFICATIONS FOR WOOD CONSTRUCTION (NDS -2012) AN51/NFOPA, 2012 EDITION, NATIONAL FOREST PRODUCTS ASSOCIATION. MASONRY TM5 402-11, AGI 530-11, A5CE 5-11 and IBC 20121-' r t < "• "`.' f ytin* but e*k BY PO DATE 91/14r KIRSHNER s •12 77725 Enfield Lane, #130 REVISED 61,785 Masa Court PAGE_ Palm Desert, CA 92211 (760) 772-4411 FAX (760) 772-4409 L a Quinto • ?.450 'drpRy@aol.com Trilogy Co.C. OF PROJECT: Dr:5ERT OUTDOORS 19405 Highway III, Suite Q, #42'1 La Ovinta, CA 92255 , 060)-215-T-5501, (760) 54q -g600 MA50NRY DEMON '(Working Stress Design) NO SPECIAL INSPECTION, USE HALF 5TRE55E5 . TM5 402-11, AGI 550-11, ASCE 5-11 and IBC 2012 WT. = 65 P5F, w CMU, &ROUT CELLS WITH STEEL. f Wi = 1500 P51 COMPRE551NE 5T1?EN&TH fb = 250 P51 COMPRESSION - FLEXURAL + fv = 20 P51 MA50NRY TAKES SHEAR ' fv = 29 P51 REINFORCIN& TAKES ALL SHEAR fs = 20 K51 STEEL STREN&TH (Fy = 40 KSI) Em = 1.125 X 10 '. P51 n = 25.5 MODULAR RATIO Es/Em CONCRETE 5TREN&TH r f'r, = 2500 P51 2.6 -Day Compressive Strength 5L EL f F y ='40 K51, Grade 40, ASTM A615 , &ROUT STRENGTH f'c = 2500 P51 26 -Day Compressive Strength Olin. r !i•,,,j.�,i, ,r.,;�i,.nry;.�ul.,iq:'i ^iu:•ia;: q: ui-ir�,�.J ONE Nil I X 1 GLASS MOSAIC TILE ' AT SIDES AND TOP OF UPPER BASIN, TILE TO BE SELECTED BY OWNER. ' BEY COLUMN ND WITH O BULLNOSED PAVER CAP AND RIVER ROCK VENEER (SOLID ROCK, NOT FLAT VENEER) RIVER 16 ROCK TO BE SELECTED BY ' OWNER, SIZE TO BE APPROX. 6' ANGLE GUNITE FOR a' LEDGESTONE STACK ' 3ll (APPROX. T' OFFSET) GirR a ° ' STUCCO FACE AT REAR ° b l —1 ,4l�D.G• (TYP.) LEDGE STONE VENEER, TO BE SELECTED BY OWNER ' a1' C'�YP•) :° . I ATERLJNE ° - # 3 VP -A T. —I Qr G _ alt' (�"O•G. C��P.) II III III a •° . 8 =— u • ' A PEBBLE MIN. 2 - 3" EQUALIZER a LINES TO POOL NOTCH GUNITE BACK TO CREATE DRIP EFFECT tA FROM LEDGESTONE ' (�•• O11.0 Co1 X 1 GLASS WATERLINE M IN . Mime, TILE TO MATCH TILE AT I IPPFR RAMN 2'• Co'' MIN ' . , WATER FS.AT0VITZ. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 "• "& fbYtMLY butt e*r 77725 Enfield Lane, #130 Palm Desert, CA 92211 (760) 772-4411 FAX (760) 772-4409 BY OAF DATE REVISED IGRSHNER 61785 Mega Court La Qulnto Trilogy G.G., $ PAGE OF_�j@ CLIENT: 46" 90- PAD FOOTING #5 VERT. BARS AT #5 HORIZ. TIE 4" O.G. AT 16" O.G. (TYPIAO (`TYPJ a ` •�•�,• ��? � 0 PLAN 1/IEWTROUGH��A.' or — , 8-#4 VERT. BARS (TYPJ 6" STONE VENEER --,, . 4 8" GMU PEDEST SOLID &ROUT SECTION #3 HORIZ. TIE AT 16" O.G. (TYPJ #5 VERT. BARS AT b" D.G. (TYP) #3 VERT. BARS AT 4" O.C. d (TYP) `KATER SURFACE ----#3 HORIZ. BARS AT 12" O.G. (TYP) #3 44_BARSFM AT AT 3°GLR.r 6" O.G. GONGRETE (&UNITE) STREN&TH (TYP) V c = 2500 P51 28 -Day Compressive Strength MASON= Fon = 1500 P51 STEEL F y = 40 KSI, &rade 40, ASTM A615 &ROUT: Pc. = 2500 P51 AT 2&-DAY5 #5 BAR MIN. LAP = 18" #4 BAR MIN. LAP = 24 1/2"=1'-0" 48" H I GH - PEDESTAL AT WATER FEATURE E3 � • . Iii , .. .'. .r. _. . 4 '19405 Highway III, Suite 9, #42"1 4, La Quinta, GA 92253 (160) 215-1359, (160) 399-9600 LATERAL LOADS 2013 GBG and ASCE 1-10 4. SEISMIC 00EFFIGIENT5 GBG 5ECT,40N 1613 ASCE 1-10 Chapter 15 Seismic Design Req,. for Non-5vilding Structures . EQUIVALENT LATERAL FORGE ASCE 1-10; SECTION 15.4 V= Gs x Wdl q SEISMIC BASE SHEAR (EQ. 12.8-1) Cs = (0.8) 5 - 0,13 (0-40 - - • o:1 l „ •, MO. 15.4-2) (R/1) x (1.4) (Cs = NOT LE -55 THAN 0.03) V= p x Cs x YVdl = (,o n 0,1-7 x cep,, 0,11 WbLo WHERE p= 1.0 ASCE SECTION VALUE • FACTOR ' SEG. 15.4.1.1 11 = I.O Importance Factor SEG. I1b-1 D Seismic Design Category TABLE 15.4-2 R = 2 Response Modification Factor SEG. 11.4.4 51= 0.6 g Design Spectral Response Acceleration ADDRESS = 61185 Mesa Court, La 'Quints , ZIPCOM = 92253 -' LATITUDE = 33599695 + LONGITUDE _ -116.234361 ALTERNATIVE BASK LOAD COMBINATION FOR ALLOWABLE 5T Z-55 DESIGN PER ASCE 1-10, SEG. 12.4.2 SEISMIC LOAD EFFECT E= Eh + Ev (EG. 12.4-1) YVERE Eh= pOe YV!-IERE Ev = 02 Sds D = O WHERE p= .13 D + w (ObYV or (6.1EJ (EQ. 2.4.1) , ) WHERE w 1.3 MERE D DEAD LOAD ' WHERE W _ WIND FORGE WERE E = EARTHQUAKE ` "' "`� 1 �' i�tA��"• '�aa BY b " DATE Ylt ' ° :�- IUR514NER 77725 Enfield Lane, #130 REVISED 61185 Mesa Court_ PAGE_ Palm Desert, CA 92211 (760) 772-4411 FAX (760) 772-4409 La Quints # OF, drpfly@aol.com Trilogy C.G. PROJECT: OUTDOORS DESERT ,. '19405 Highway III, Suite 9, #42"1 4, La Quinta, GA 92253 (160) 215-1359, (160) 399-9600 LATERAL LOADS 2013 GBG and ASCE 1-10 4. SEISMIC 00EFFIGIENT5 GBG 5ECT,40N 1613 ASCE 1-10 Chapter 15 Seismic Design Req,. for Non-5vilding Structures . EQUIVALENT LATERAL FORGE ASCE 1-10; SECTION 15.4 V= Gs x Wdl q SEISMIC BASE SHEAR (EQ. 12.8-1) Cs = (0.8) 5 - 0,13 (0-40 - - • o:1 l „ •, MO. 15.4-2) (R/1) x (1.4) (Cs = NOT LE -55 THAN 0.03) V= p x Cs x YVdl = (,o n 0,1-7 x cep,, 0,11 WbLo WHERE p= 1.0 ASCE SECTION VALUE • FACTOR ' SEG. 15.4.1.1 11 = I.O Importance Factor SEG. I1b-1 D Seismic Design Category TABLE 15.4-2 R = 2 Response Modification Factor SEG. 11.4.4 51= 0.6 g Design Spectral Response Acceleration ADDRESS = 61185 Mesa Court, La 'Quints , ZIPCOM = 92253 -' LATITUDE = 33599695 + LONGITUDE _ -116.234361 ALTERNATIVE BASK LOAD COMBINATION FOR ALLOWABLE 5T Z-55 DESIGN PER ASCE 1-10, SEG. 12.4.2 SEISMIC LOAD EFFECT E= Eh + Ev (EG. 12.4-1) YVERE Eh= pOe YV!-IERE Ev = 02 Sds D = O WHERE p= .13 D + w (ObYV or (6.1EJ (EQ. 2.4.1) , ) WHERE w 1.3 MERE D DEAD LOAD ' WHERE W _ WIND FORGE WERE E = EARTHQUAKE ` Convert Address to Lat Long Geocode ` . ` Page 1 of I Aldd Pres UIMst P�o�s 011111111111" Ust YIflsNa Am h / *ATL0NG,m.7-.1 Ad�ss -+ c«io UI! tag -o All#ftea t w L" -* WA t it UmO.-.trill) ' Convert Address to Lot Lon To convert address to lat long type the address with city name, street name to get more accurate tat long value. Address l 161785 MESA COURT, LA QUINTA, CA 92253 f; Find Lat Long j ' Llks114 OgJ}a� ar :. rn o`ra'yf rnj �'i i e k i ,,.��{ �a4 :rr,,. Fs hid i 't• 31 swimmtn9 cr Go/ x P v� a r ool Aquasafe den Tnlal�a'Qumta .' Latitude 3 33.599695 µ I ��* t Mesquite Real!a xSaZia a T l} ;4ffi,%oh Estate For Sale- _ ^ �� m r' ',. �`• �y r ,, [ ' t. T� t A + Longitude, -116.234361` 1�$ 3r 14/e,P�' "� dYro r. r fyc In s ✓� r r ' tt� tr - _1vr La Pat Ys.SamF. e `� } 1 Database 4` ,I f`i+ InSUra11�� ` . Fuianaal Se es i HM Insurance r .�Chnstopher Conversion Tool �WaftAPLC� n rwgg www.altova.com/MapForce &` r N'S k .3 n ru..w L;_4 k} fr din s Easy Tool to Convert, Migrate, , 62nd Ave — 62nd Ave = 62nd Ave ' or Transform Data for All k Databases. , ' r .. I,CD l vi �riCi i • <ti i t = w hlap �ortEffifia�eIIofe Share this location: , http://www.latlong.net/c/?Iat=33.599695&long=-116.234361 ' You can hold and move marker to anywhere you want to get the lat long of near places of your address. This geo process Is also known as geocode address. J 1 1 02012- 2014 wvn•: latlong net I Privacy I Contact We do not guarantee the accuracy of the coordinate places. Please use latlong.net at your mm risk.. h4://www.latlong.net/convert-address-to-lat-lo-ng.html 3/1/2014 11 I. 1 L- Design Maps Summary Keport s Yage;l'Ot l Design Maps Summary Report User—Specified Input Report Title KIRSHNER Sat March 1, 2014 21 35:47.UTC Building Code Reference Document ASCE 7-10 Standard iry ; { rY , �" �St 3 j � r• ,. (which utilizes USGS hazard'data available in -2008) ` t Site Coordinates 33.5997°N, 116.23436-k,, r , .-Site Soil Classification Site Class, D "Stiff Soil r 'k Qtt Risk Category I/II/III f ,• �f+ `�" i `..•'Y c�sk rctYS4t�a,. Y i L Y 1 r ur1...r,� s : t •� .,' �t rr�xS .a'r t� , rNi,.. :. - .�1 'v}F,..+•r`+i t k 1,. _ ,".,�t.r�•k s/ ,[ Y•rss�"�`C� C"Z�.,. 'fin' X11T'y,,,rsvf�+ NMI m s z" % I (� ^'. Q' E ^ �","y `C"X` yFi. ,[ 1� ��r`rfi .c5+.¢.- y%4`i.'.s`,rrg- �' Lgv �r r ,,. -.. I. Wdra:i�- z' T _` I f �a,y5.".,�y�.k.�17Mfr-y�t•"M--r SIt,.'SI.S[O iR �2F A�yt ^"r��• A•�-.�[, $•t }`' R ,5s [�� "'z .J� f �- � -h". i zri.E � •c1•,+* Y �.�:'�7-c.'lrzii.�,-;l^Fyr4f.,t�`y�Fry�e SN•.s'T,ci. [p /s :':,3�ry.r-1�e.ZnR N d 3 w -%?4 S1 %� x �1 � � . ;� .i fr,.� �¢z� i„ 1 s� � •r�M•.y� * " I ^J t aka F=s t s .} ,� .s 2r rd. Yry4. K s'f^'rr-'.;�t pryer �_.eY ��`�.r-�..i's 7<i�rc,[t,,vx"n :.."v fir#' ,•'. , ev4: se '1 s'(' '• �• s psi , •x' q t . �+ r ax ,F >••G'. ..-� .t° t "� � ax r 1'3•'� a �'.�'iN a� s r. >�, a � rs� Y 3fm� `Y. , , ro " .', �' _s-4. t.,,37a � wf� '-. a -A +fi t'X... O y,,.. a- �a �, r i't ,y_•l SlH 3"! 'rJ'4'f '- .a'"t }',t 6-"R., ., .pit" 1 .��s,,YNr• .F. rti lt1a>,r- �R '� zw- 7 a�. y i, v tlr7 7 3r� r y_ afi R rx t h r i 4' q1& 'u t•f 7�` � x x.r 'k 1.- tcR 1L ...1' F' J• ..Y 'i'..' ^' .T.�_— �"'=�y C^.7ar L � � ,t/ �•4 .iN �> , c ;j <., .�. �sr , -r ..� 9 ' •{ AN -NE -0 y N -NE- nA„r� �rs�,.��M•�==��v�K�,•�b�r�s �,�i 6x5 ,;,,� a��ti��?``r.�� � Lret�r���r�:�v ', °r 1 �, ..•.+�n .,�'..$�.. _ .-r ;�. .'�r��; .-�p.�.y �yVrd,���?�}.�.r'�i�� �i`ary"'��r�y N7o�R�y.�' H = �,� _ . J � .1� �,pd% zw 'F v :3.r"'N�F•� •"'` �'&:Ca.s�`,.�.t} d't�' a� .r i.• e = , t wvl., a�a-°r,v7s"z an5nez:MoreniamARM`r r I ME MA k�.•.+.;, u i:.+',��•'tiJ- ,,3"•--�5 yt_r"x-Lx 0 a a fF2 3J� Ns3'..�,1,>,Y.c� �iy,•y.r- 5 L --'r1 ,. v-ty-` +rr ss e'r+7^ . a eii" rc,• „F''" SYa '3e r &,,.rls�sy� . Com. a a y,„ai, -` Yr •+ n7y+_ 3 , y 1i1>gpQliBSt'+ g� u�3 xY�}v� z'a I'LL.. rr r3 �s-.cre�,• ,...w ,. ?.r �r.:fi' �t f �'.!.c`.i�r,� ..'.ecr^�E�„ A.�".�<:� 7'�:.,��,;®2614, i .... � ' "'. �`.r',r,� �® I�dP�sty . ' i USGS—Provided Output x _ + SS`= 1.500 9 Ss = 1.500 g 1., » SDS = 1.000 g r, z• S. = 0.600 g S„1'= 0.900 g .,1 SDI 0.600 9`✓ �. 4 f For information on how the SS and S1 values above have been calculated from probabilistEc"(risk targeted) and.. " , deterministic ground motions in the direction of maximum horizontal response, please return .to the applicatrion and select the "2009 NEHRP" building code reference document r'- 4 MCEa Response Spectrum �' Design Response%Spectrum L65 + t �.. a �- 10 ., #' f t, ♦+r' r t . 1.75 � • . � �' a.99 _ «* '� 1.20.- 1.05 .20 1.05 �' • r 6.77 ..� . L P 0:90 • Y a +; OE 0.66 r, , t i ^7 -k . _ 0.60 < y , ,"•1 , 0.15 4 0.00 �� : 0:00' K k 4.00 0.20 0.40 0.60 0.80 1.00: 1.20 1.40, 1.60 1.80 2.00 0.00 0 20 0.40 0 60,`0.80 1.00-1.20 1.40 160 1.89, 2.00,; Period, T se l cl;,rt P Per . ` .' ,`h'• 1, * � �•/ » � •; +�f+#, t ?ro' tr r � r f � t ,' - a i For PGAM, TL, CRs, and CR, values,. please view the'detailed report: " * jr '� ••, '' 1>-M; Although this information is a product of the U.S. Geological Survey, we provide no warranty; expressed or implied as to the,, accuracy of the data contained therein. This tool is not a substitute for -technical subject -,matter knowledge http://geohazards.usgs.gov/desigmnaps/us/summaryphp' template--minimal&amp;latitude=33.5996... 3/1/2014 �°2{A Table 15.42 Seismic Coefficients for Nonbuilding Structures not Similar to Buildings Structural System and Structural Height, h," — Limits (ft)" J . Nonbuilding Structure Type Detailing Requirements` R L1, Ce A& B C D E F Elevated tanks, vessels, bins or hoppers On symmetrically braced legs (not similar to buildings) 15.7.10 3 2° 2.5 NL NL 160 100 100 ' On unbmced legs or asymmetrically braced legs (not similar buildings) 15.7.10 2 2° 2.5 NL NL 100 60 60 Horizontal, saddle -supported welded steel vessels 15.7.14- 3 2" 2.5 NL NL NL NL NL Tanks or vessels supported on structural towers similar to 15.5.5 Use values for the appropriate structure type in the categories for buildings building frame systems and moment resisting frame systems listed in.Table 12.2-1 or Table 15.4-1. Flat -bottom ground -supported tanks: 15.7 Steel or fiber -reinforced plastic: ' Mechanically anchored 3 2° 2.5 NL NL NL NL NL Self -anchored 2.5 2° 2 NL NL NL NL NL Reinforced or prestressed concrete: ' Reinforced nonsliding base 2 26 2 NL NL NL NL NL Anchored flexible base 3.25 2° 2 NL NL NL NL NL Unanchored and unconstrained flexible base 1.5 1.5° 1.5 NL NL NL NL NL ' All other 1.5 1.5° 1.5, NL NL NL NL NL Cast -in-place concrete silos having walls continuous to the 15.6.2 .3 1.75 3 NL NL NL NL NL ' foundation Al) - other reinforced masonry structures not similar to 14.4. If 3 2 2.5 NL NL 50 50 50 buildings detailed as intermediate reinforced masonry shear walls c144) PEOESTaI. All other reinforced masonry structures not similar to 14.4.1 2 2.5 1.75 NL 160 NP NP NP buildings detailed as ordinary reinforced masonry shear walls All other nonreinforced masonry structures not similar to 14.4.1 1.25 2 1:5 NL NP NP NP NP buildings Concrete chimneys and stacks 15.6.2 and ACI 307 2 1.5 2.0 NL NL NL NL NL - All steel and reinforced concrete distributed mass cantilever 15.6.2 structures not otherwise covered herein including stacks, chimneys, silos, skirt -supported vertical -vessels; single pedestal or skirt supported Welded steel 15.7.10 2 2° 2 NL NL NL NL NL Welded steel with special detailing` 15.7.10 & 15.7.10.5 3 2° 2 NL NL NL NL NL a and b Prestressed or reinforced concrete 15.7.10 2 2° 2 NL NL NL NL NL Prestressed or reinforced concrete with special detailing 15.7. 10 and 3 2" 2 NL NL NL NL NL 14.2.3.6 ' Trussed towers (freestanding or guyed), guyed stacks, and 15.6.2 3 2 2.5 NL NL NL NL NL chimneys Cooling towers Concrete or steel 3.5 1.75 3 NL NL NL NL NL Wood frames 3.5 3 3. NL NL NL 50 50 Telecommunication towers 15.6.6 Truss: Steel 3 1.5 3 NL NL NL NL NL ' 108 STANDARDS 7-10 ' 1533 Architectural, Mechanical, and Electrical Components. Architectural, mechanical, and electrical components supported by nonbuilding structures shall be designed in accordance with Chapter 13 of this standard. 15.4 STRUCTURAL DESIGN REQUIREMENTS 15.4.1 Design Basis. Nonbuilding structures having specific seismic design criteria established in reference documents shall be designed using the standards as amended herein. Where refer- ence documents are not cited herein, nonbuilding structures shall be designed in compliance with Sections 15.5 and 15.6 to resist ' minimum seismic lateral forces that are not less than the require- ments of Section 12.8 with the following additions and exceptions: 1 1 1 1 1 f 1 1 1 1 The seismic force -resisting system shall be selected as follows: a. For nonbuilding structures similar to buildings, a system shall be selected from among the types indicated in Table 12.2-1 or Table 15.4-1 subject to the system limi- tations and limits on structural height, h,,, based on the seismic design category indicated in the table. The appropriate values of R, Do, and Ca indicated in the selected table shall be used in determining the base shear, element design forces, and design story drift as indicated in this standard. Design and detailing require- ments shall comply with the sections referenced in the selected table. b. For nonbuilding structures not similar to buildings, a system shall be selected from among the types indicated in Table 15.4-2 subject to the system limitations and limits on structural height, h,,, based on seismic design category indicated in the table. The appropriate values of R, Q., and C, indicated in Table 15.4-2 shall be used in determining the base shear, element design forces, and design story drift as indicated in this standard. Design and detailing requirements shall comply with the sections referenced in Table 15.4-2. c. Where neither Table 15.4-1 nor Table 15.4-2 contains an appropriate entry, applicable strength and other design criteria shall be obtained from a reference docu- ment that is applicable to the specific type of nonbuild- ing structure. Design and detailing requirements shall comply with the reference document. For nonbuilding systems that have an R value provided in Table 15.4-2, the minimum specified value in Eq. 12.8-5 shall be replaced by C, = 0.044SoS1� (15.4-1) The value of C, shall not be taken as less than 0.03. And for nonbuilding structures located where S, >_ 0.6g, the minimum specified value in Eq. 12.8-6 shall be replaced by C, = 0.8S11(R/1') (15.4-2) EXCEPTION: Tanks and vessels that are designed to AWWA D100, AWWA D103, API 650 Appendix E, and API 620 Appendix L as modified by this standard, and stacks and chimneys that are designed to ACI 307 as modi- fied by this standard, shall be subject to the larger of the minimum base shear value defined by the reference docu- ment or the value determined by replacing Eq. 12.8-5 with the following: C, = 0.044SoS 1, (15.4-3) The value of C, shall not be taken as less than 0.01 106 And for nonbuilding structures located where S, >_ 0.6g, the minimum specified value in Eq. 12.8-6 shall be replaced by C, = 0.5S,/(R/1,) (15.4-4) Minimum base shear requirements need not apply to the convective (sloshing) component of liquid in tanks. 3. The importance factor, I,, shall be as set forth in Section 15.4.1.1. 4. The vertical distribution of the lateral seismic forces in nonbuilding structures covered by this section shall be determined: a. Using the requirements of Section 12.8.3, or b. Using the procedures of Section 12.9, or c. In accordance with the reference document applicable to the specific nonbuilding structure. 5. For nonbuilding structural systems containing liquids, gases, and granular solids supported at the base as defined in Section 15.7.1, the minimum seismic design force shall not be less than that required by the reference document for the specific system. 6. Where a reference document provides a basis for the earth- quake resistant design of a particular type of nonbuilding structure covered by Chapter 15, such a standard shall not be used unless the following limitations are met: a. The seismic ground accelerations and seismic coefficients shall be in conformance with the require- ments of Section 11.4. b. The values for total lateral force and total base overturning moment used in design shall not be less than 80% of the base shear value and overturning moment, each adjusted for the effects of soil -structure interaction that is obtained using this standard. 7. The base shear is permitted to be reduced in accordance with Section 19.2.1 to account for the effects of soil - structure interaction. In no case shall the reduced base shear be less than 03V. 8. Unless otherwise noted in Chapter 15, the effects on the nonbuilding structure due to gravity loads and seismic forces shall be combined in accordance with the factored load combinations as presented in Section 2.3. 9. Where specifically required by Chapter 15, the design seismic force on nonbuilding structures shall be as defined in Section 12.4.3. 15.4.1.1 Importance Factor. The importance factor, Ie, and risk category for nonbuilding structures are based on the relative hazard of the contents and the function. The value of 1, shall be the largest value determined by the following: a. Applicable reference document listed in Chapter 23, b. The largest value as selected from Table 1.5-2, or c. As specified elsewhere in Chapter 15. 15.4.2 Rigid Nonbuilding Structures. Nonbuilding structures that have a fundamental period, T, less than 0.06 s, including their anchorages, shall be designed for the lateral force obtained from the following: V = 0.30SoSW1, (15.4-5) where V = the total design lateral seismic base shear force applied to a nonbuilding structure SDs = the site design response acceleration as determined from Section 11.4.4 W = nonbuilding structure operating weight STANDARDS 7-10 rl� 1 1 1 1 1 1 th& fJ -"n O ut t ew BYQit—P DATE � �14 KIR-c*ReR 77725 'Enfield Lane, #130 . REVISED 61785 Mesa Court Palm Desert, CA 92211 La aulnto PAGE_ (760) 772-4411 FAX (760) 772-4409 OF drpflyeaoi.com Trilogy G.G. PROJECT: , s DESERT OuTnooRs 741405 Highway III, Suite 41, #427 ' La Quinta, GA 412253 (760) 275-73541, (760) 3419-41600 + . WIND DE516N ASCE 7-10, CHAPTER 241 SOLID FREE-STANDING WALLS ASCE 7-10, Fig. 241.4-1 Qh= 0.00256 (Kz) x (Kzt) x (Kd) x (V)2 x I.3 x w = 32 P4,f (Ea. 2CIZ-1) ZFi>✓ P.O�rrol� 1 S Fold W i N IO o►J ° Ftt� � STaJD I N {. - W - p= QhxGxGfxwx0.6= i ASCE SECTION VALUE FACTOR SEG. 65.4 V= 110 MPH BASIC WIND SPEED SEG. 65.4.4 Kd - OX6 DIRECTIONALITY SEG. 655 1 = 1.0 . IMPORTANCE FACTOR, CATEGORY II G EXPOSURE CATEGORY SEG. 65.6 Kz = 0.85 VELOCITY PRESSURE EXPOSURE COEFFICIENT SEG. 65.7.2 Kzt= 1.00 TOPOGRAPHIC FACTOR (FIS. 6-4) -SEG. 65.8 6= 0.85 GUST FACTOR' ALTERNATIVE BASIC LOAD COMBINATION FOR ALLOWABLE STRESS DE516N PER ASCE 7-10, CHAPTER 241 WIND LOAD EFFECT ; PER GBG 2013, SEG. 16055.2 D + w (0.6100 or (o.7E) (Ea. 2.4.1), MERE w= 1.3 1 1 1 �i 1 1 1 1 1 1 1 1 1 1 II 1 1 2.3.6 Load Combinations for Nonspecified Loads. Where approved by the authority having jurisdiction, the registered design professional is permitted to determine the combined load effect for strength design using a method that is consistent with the method on which the load combination requirements in Section 2.3.2 are based. Such a method must be probability based and must be accompanied by documentation regarding the analysis and collection of supporting data that is acceptable to the authority having jurisdiction. 2.4 COMBINING NOMINAL LOADS USING ALLOWABLE STRESS DESIGN 2.4.1 Basic Combinations. Loads listed herein shall be consid- ered to act in the following combinations; whichever produces the most unfavorable effect in the building, foundation, or struc- tural member shall be considered. Effects of one or more loads not acting shall be considered. 1. D 2. D + L 3. D+(L,orSorR) 4. D + 0.75L + 0.75(L, or S or R) 5. D + 0.6W or 0.7E) 6a. D + 0.75L + .75(0-.-W + 0.75(L, or S or R) 6b. D + 0.75L + 0.75(0.7E) + 0.75S 7. 0.6D + 0.6W 8. 0.6D + 0.7E EXCEPTIONS: 1. In combinations 4 and 6, the companion load S shall be taken as either the flat roof snow load (pf) or the sloped roof snow load (p,). 2. For nonbuilding structures, in which the wind load is deter- mined from force coefficients, Cf, identified in Figures 29.5-1, 29.5-2 and 29.5-3 and the projected area contribut- ing wind force to a foundation element exceeds 1,000 square feet on either a vertical or a horizontal plane, it shall be permitted to replace W with 0.9W in combination 7 for design of the foundation, excluding anchorage of the struc- ture to the foundation. 3. It shall be permitted to replace 0.6D with 0.9D in combina- tion 8 for the design of special reinforced masonry shear walls, where the walls satisfy the requirement of Section 14.4.2. Where fluid loads F are present, they shall be included in combinations 1 through 6 and 8 with the same factor as that used for dead load D. Where loads H are present, they shall be included as follows: 1. where the effect of H adds to the primary variable load effect, include H with a load factor of 1.0; 2. where the effect of H resists the primary variable load effect, include H with a load factor of 0.6 where the load is permanent or a load factor of 0 for all other conditions. The most unfavorable effects from both wind and earthquake loads shall be considered, where appropriate, but they need not be assumed to act simultaneously. Refer to Sections 1.4 and 12.4 for the specific definition of the earthquake load effect E.2 1 'The same E from Section 12.4 is used for both Sections 2.3.2 and 2.4.1 Refer to the Chapter 11 Commentary for the seismic provisions. Increases in allowable stress shall not be used with the loads or load combinations given in this standard unless it can be demonstrated that such an increase is justified by structural behavior caused by rate or duration of load. 2.4.2 Load Combinations Including Flood Load. When a structure is located in a flood zone, the following load combina- tions shall be considered in addition to the basic combinations in Section 2.4.1: 1. In V -Zones or Coastal A -Zones (Section 5.3.1), 1.5F, shall be added to other loads in combinations 5, 6, and 7, and E shall be set equal to zero in 5 and 6. 2. In noncoastal A -Zones, 0.75F, shall be added to combina- tions 5, 6, and 7, and E shall be set equal to zero in 5and 6. 2.43 Load Combinations Including Atmospheric Ice Loads. When a structure is subjected to atmospheric ice and wind -on -ice loads, the following load combinations shall be considered: 1. 0.7D; shall be added to combination 2. 2. (L, or S or R) in combination 3 shall be replaced by 0.7D; +0.7W+S. 3. 0.6W in combination 7 shall be replaced by 0.7D; + 0.7W. 2.4.4 Load Combinations Including Self -Straining Loads. Where applicable, the structural effects of load T shall be con- sidered in combination with other loads. Where the maximum effect of load T is unlikely to occur simultaneously with the maximum effects of other variable loads, it shall be permitted to reduce the magnitude of T considered in combination with these other loads. The fraction of T considered in combination with other loads shall not be less than 0.75. 2.5 LOAD COMBINATIONS FOR EXTRAORDINARY EVENTS 2.5.1 Applicability. Where required by the owner or applicable code, strength and stability shall be checked to ensure that struc- tures are capable of withstanding the effects of extraordinary (i.e., low -probability) events, such as fires, explosions, and vehicular impact without disproportionate collapse. 2.5.2 Load Combinations. 2.5.2.1 Capacity. For checking the capacity of a structure or structural element to withstand the effect of an extraordinary event, the following gravity load, combination shall be considered: (0.9 or 1.2)D + Ak + 0.5L + 0.2S (2.5-1) in which Ak = the load or load effect resulting from extraordinary event A. 2.5.2.2 Residual Capacity. For checking the residual load - carrying capacity of a structure or structural element following the occurrence of a damaging event, selected load-bearing ele- ments identified by the registered design professional shall be notionally removed, and the capacity of the damaged structure shall be evaluated using the following gravity load combination: (0.9 or 1.2)D + 0.5L + 0.2(L, or S or R) (2.5-2) 2.53 Stability Requirements. Stability shall be provided for the structure as a whole and for each of its elements. Any method that considers the influence of second -order effects is permitted. STANDARDS 7-10 i 1. 'I 11 STRUCTURAL DESIGN f2 = 0.7 for roof configurations (such as saw tooth) that do not shed snow off the structure, and 0.2 for other roof configurations. Exceptions: I. Where other factored load combinations are specifi- cally required by other provisions of this code, such combinations shall take precedence. 2. Where the effect of H resists the primary variable load effect, a load - factor of 0.9 shall be included with H where H is permanent and H shall be set to zero for all other conditions. 1605.2.1 Other loads. Where flood loads, F,, are to be considered in the design, the load combinations of Section 2.3.3 of ASCE 7 shall be used. Where self -straining loads, T, are considered in design, their structural effects in com- bination with other loads shall be determined in accor- dance with Section 2.3.5 of ASCE 7. Where an ice - sensitive structure is subjected to loads due to atmospheric icing, the load combinations of Section 2.3.4 of ASCE 7 shall be considered.. 1605A.3 Load combinations using allowable stress design 1605A.3.1 Basic load combinations. Where allowable stress design (working stress design), as permitted by this code, is used, structures and portions thereof shall resist the most critical effects resulting from the following com- binations of loads: D + F (Equation 16A=8) D + H + F + L (Equation 16A-9) D + H + F + (L, or S or R) (Equation 16A-10) D +H+ F+ 0.75(L) + 0.75(L,or S or R) (Equation 16A-11) D + H + F + (0.6W or 0.7E) (Equation 16A-12) D + H + F + 0.75(0.6W) + 0.75L + 0.75(L, or S or R) (Equation 16A-13) D + H + F + 0.75 (0.7 E)+0.75L+0.755 (Equation 16A-14) 0.6D + 0.6W+H (Equation 16A-15) 0.6(D + F) + 0.7E+H (Equation 16A-16) Exceptions: 1. Crane hook loads need not be combined with roof ' live load or with more than three-fourths of the snow load or one-half of the wind load. 2. Flat roof snow loads of 30 psf (1.44 kN/m2) or ' less and roof live loads of 30 psf or less need not be combined with seismic loads. Where flat roof snow loads exceed 30 psf (1.44 Mtn), 20 per- cent shall be combined with seismic loads. ' 3. Where the effect of H resists the primary variable load effect, a load factor of 0.6 shall be included with H where H is permanent and H shall be set I I to zero for all other conditions. 4. In Equation 16-15, the wind load, W, is permitted to be reduced in accordance with Exception 2 of Section 2.4.1 of ASCE 7. 5. In Equation 16-16, 0.6 D is permitted to be increased to 0.9 D for the design of special rein- forced masonry shear walls complying with Chapter 21. 1605A.3.1.1 Stress increases. Increases in allowable stresses specified in the appropriate material chapter or the referenced standards shall not be used with the load combinations of Section 1605A.3.1, except that increases shall be permitted in accordance with Chapter 23. 16053.1.2 Other loads. Where flood loads, Fe, are to be considered in design, the load combinations of Sec- tion 2.4.2 of ASCE 7 shall be used. Where self -strain- ing loads, T, are considered in design, their structural effects in combination with other loads shall be deter- mined in accordance with Section 2.4.4 of ASCE 7. Where an ice -sensitive structure is subjected to loads due to atmospheric icing, the load combinations of Sec- tion 2.4.3 of ASCE 7 shall be considered. 16053.2 Alternative basic load combinations. In lieu of the basic load combinations specified in Section 1605.3.1, structures and portions thereof shall be permitted to be designed for the most critical effects resulting from the following combinations. When using these alternative basic load combinations that include wind or seismic loads, allowable stresses are permitted to be increased or load combinations reduced where permitted by the mate- rial chapter of this code or the referenced standards. For load combinations that include the counteracting effects of dead and wind loads, only two-thirds of the minimum dead load likely to be in place during a design wind event shall be used. When using allowable stresses which have been increased or load combinations which have been reduced as permitted by the material chapter of this code or the referenced standards, where wind loads are calcu- lated in accordance with Chanters 26 through 31 of ASCE 7 the coefficient (m) in the following equations shall " taken as 1.3. For other wind loads, ((o) shall be taken as 1. When allowable stresses have not been increased or load combinations have not been reduced as permitted by the material chapter of this code or the referenced standards, (a)) shall be taken as 1. When using these alternative load combinations to evaluate sliding, overturning and soil bearing at the soil -structure interface, the reduction of foundation overturning from Section 12.13.4 in ASCE 7 shall not be used. When using these alternative basic load combinations for proportioning foundations for loadings, which include seismic loads, the .vertical seismic load effect, E, in Equation 12.4-4 of ASCE 7 is permitted to be taken equal to zero. D + L + (L, or S or R) (Equation 16A-17) D + L + 0.6 mW (Equation 16A-18 D + L + 0.6 wW + S/2 (Equation 16A-19) D + L + S + 0.6 coW/2 (Equation 16A-20) 2013 CALIFORNIA BUILDING CODE r402� 1�4w THE FLYING BUTTRESS f� PROJECT ICIRSJNEG� '° ���" PAGE 77725 ENFIELD LN STF 130 CLIENT '� h r fDf r� s^� A DESIGN BY PALM DESERT, CA 92211 JOB NO.. WWI � DATE : .03J01/t4 REVIEW BY : INPUT DATA Exposure category (e, C or D) Importance factor, 1.0 only, (rade 1.5-2) Basic wind speed (ASCE 7 -to 26.5.1) Topographic factor (26.6 & Table 28.6-1) Height of top Vertical dimension (for wall, s = h) Horizontal dimension Dimension of return comer IW = 1.00 v J V = „,x1:td mph K,- zr Flat Fees\ond'm9 Wo\\ hp4 ft Soad s,9^ a r S4 " ft B Lr = a T Ground Su,loce M DESIGN SUMMARY -'-,F Max horizontal wind pressure p = 41 psf X I, 3 X O, io r 3 Z pg r Max total horizontal force at centroid of base F = 1.44 kips Max bending moment at centroid of base M = 3.16 ft -kips Max torsion at centroid of base T = 3.52 ft4dps ANALYSIS Velocity pressure qh = 0.00256 Kh K.t Kd V2 = 22.38 psf where: qh = velocity pressure at mean roof height, h. (Eq. 29.3-1 page 307 & Eq. 30.3-1 page 316) Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 29.31, pg 310) = 0.85 Kd = wind directionality factor. (Tab. 26.6-1, for building, page 250) = 0.85 h = height of top M, = 4.00 ft Wind Force Case A: resultant force though the geometric center (Sec. 29.4.1 & Fig. 29.1-1) (psf) p=qt. GG= = 26 psf (ft4dps) F = p As = 1.35 kips 2.140 M = F (h - 0.5s) for sign, F (0.55h) for wall = 2.98 ft -kips 0.65 T = = 0.00 ft4dps 8.0 where: G = gust effect factor. (Sec. 26.9) 27 R Cr = net force coefficient. (Fig. 29.4-1, page 311) 0.94 1.37 Ag=Bs 0.950 = 52.0 ft2 VVind Force Case B: resultant force at 0.2 B offset of the goometric center (Sec. 29.4.1 & Fig. 29.1-1) . 0.64 p = Case A = 26 psf 0.910 F = Case A = 1.35 kips 0.07 M = Case A = 2.98 ft4dps E T=0.2 F B = 3.52 ft -kips Wind Force Case Q resultant force different at each region (Sec. 29.4.1 & Fig. 29.4-1) 1.72 p= qh G Cr Balance s s s s F=EpAe M = E [ F (h - 0.5s) for sign, F (0.55h) for wall ] T=ETe t�L] 4w,..a Distance Cr P, Ad, F, M, T, (ft) (Fg.6-20) (psf) (f2) (kips) (ft4dps) (ft-Wps) 4.0 2.140 41 16 0.65 1.43 2.93 8.0 1.400 27 16 0.43 0.94 0.21 12.0 0.950 18 16 0.29 . 0.64 -1.01 13.0 0.910 17 4 0.07 0.15 -0.42 E 1.44 3.16 1.72 � ,a Design Wind Loads All Heights Figure 29.41 Force Coefficients, Cr Solid Freestanding Walls other structures & Solid Freestanding Signs F so3msIGNaR a meLm�xaamw�tl CASE A n .. Mmy F F F F w1m i aRora a SURFACE CASE C ELEVATION VIEW } F RANGE CASE B e _ F F wwe h art IVt F ,�, oAsn qF _ i F r < t GROUO awckE BRi -1 0.28'�iRANGE stn 'Vd1a21 21130 hemWfipOeE tryae tc(kWng raEueaan fader whet a relwn caner is weaem Lis Ram Faaw tt }} vUW VIEW OF WALL OR SIGN Wm` 'W I ARMRN CORNER 0.90 7.0 0.75 Aspect Ratio, B/s WM Ir..rw Aspect Ratio, B/S dWenm nam nam whft.d 0W 2 3 4 5 6 7 8 9 10 wb dna Q*) 13 2 45 0 to s 2.25 2.60 2.90 3.10' 3.30' 3.40' 3.55• 3.65' 3.75' 0 to s 4.00' 4.30' s to 2s 1.50 1.70 1.90 2.00 2.15 2.25 2.30 2.35 2.45 s to 2s 2.60 2.55 2s to 3s 1.15 1.30 1.45 1.55 1.65 1.70 1.75 1.85 26 to 3s 2.00 1.95 3s to 10s 1.10 1.05 1.05 1.05 1.05 1.00 0.95 3s to 4s 1.50 1.85 'Vd1a21 21130 hemWfipOeE tryae tc(kWng raEueaan fader whet a relwn caner is weaem Lis Ram Faaw tt }} vUW VIEW OF WALL OR SIGN Wm` 'W I ARMRN CORNER 0.90 7.0 0.75 22 0.60 WM Notes: 1. The term 'signs' in notes below also applies to "freestanding walls'. 2. Signs with openings comprising lose than 30% of the gross area are classed as solid signs. Force coefficients for solid signs with openings shall be permitted to be multiplied by the reduction factor (1 - (1 - ¢),.) 3. To allow for both normal and oblique wind directions, the following cases shall be considered: For s/h < 1: 1. - CASE A: resultant force acts normal to the face of the sign through the geometric center. CASE B: resultant force acts normal to the face of the sign at a distance from the geometric center toward the windward edge equal to 0.2 times the average width of the sign. For B/s 2 2, CASE C must also be considered: CASE C: resultant forces act normal to the face of the sign through the geometric centers of each region. For s/h = 1: The same cases as above except that the vertical locations of the resultant forces occur at a distance above the geometric center equal to 0.05 times the average height of the sign. 4. For CASE C where s/h > 0.8, force coefficients shall be multiplied by the reduction factor (1.8 - s/h). 5. Linear interpolation is permitted for values of a/h, We and L,/s other than shown. 6. Notation: B: horizontal dimension of sign, in feet (meters); h: height of the sign, in feet (meters); s: vertical dimension of the sign, In feet (meters); E: ratio of solid area to gross area; 4 ' L,: horizontal dimension of return comer, In feet (meters) STANDARDS 7-10 F STANDARDS 7-10 STRUCTURAL 8. CIVIL ENGINEERING ---77o-7 77•-7?SrtnfieidfLane�4 -Unit #k130! : Paltr Desert Callfomta 922;11 t # #(T60)�772-44141 �� FAX (760)772=4409 { 4 _drp-,,- aolEcom BY -bRP DATEi_ i { I -- i ��• a 9 , + 2 PREPARED FOR #`- j Al ..� _ _'� _l� f%Sl Ca_N _A3,_5.N'! l► H �C� I�,N_l_�_�. y �.--.._i � tt.si'�t � (� 5 G� �-%:� �� � r �"—_v # F _-�r!'_v�.►�-i�_t� P.1__::�i_� ; _ _:�_ �L:..r? _ 1 _-� i .�_�—�_.._...` _ .5 -- J 'St�Ifah61 �i-t7�a.l�aPl '-1 �_K -w-La �.F/_U� lel��.f��+ ST�t� ��V��'��—! I _ t• "� -'! � •F� � # t t� (. i t- Cyt , ``. l 4 �/7 6 ( t� # { F i ; . # t EE � j _t-._... #-�...� g• C"�id� ! -.-1--- �� ._X O!. t_ -.l•_ W ��: L-_ 1X _POI (7 .'X# 25 , t t a 1 /�lp ._ _Go t3.o Ge1GI a ®13 t j • C 1 1-t/,-_� 1 I f ! S. (,` t S 4', -S I' � � - •! t 5 i� i LU �%' 1 PG' x�i Cy i 12rj_ f�G �? S{Ti:•l t i fM J ' f ' _�.SD + _�4 __ K _t �----i-=-tk--� {--�-. �--^f--- e----r----t.__-__j- ,..;�.1 '� (� �. ter..,-.�.._�_ •j___�.� i '. i'. � i _'."--A-.-i.^ CA- { 77to c_H bl i __ t__!�=��_PbF 1 ; T- � -_i_ � _ �_._.r s G�Ce�7.01��_��I � "�� %�'� C_O���J_, � CFi�• ��,.�•._ ' ; � 1 �' � { 1 i j_�___�_ if 3 t if • � ► # ! { , ! i � ,•`� i ice. SI S# -.�1 :� _{ t A '-t7 64 BYt DRP 'DATE�' yL OT I .+..--..S:tRU&TUiAL4�'.CIVI.L-ENGINEERIN J 7i4(25 *E�, fieO L6n6 O'Unit. # I P(; . Paim-DL-se'rt,!-C-alifoinii3-9-22- 7 6 (760) 77!�-44i I Ai FAX (7.60) 717 2-4409 0 OpTly"o aol.com 1. 7 1,' T A I PREPARED FOR : M. -QA. _.... !77 I Z. _ __----:_` %A 15: Ora, t7 rlo co _' __-__._.-__. i 13LJL' all 4 42 ;r'.jjti,4si�� A .: t_� j4i; _ --l- ''.T,_..!,�;. 14 i IM f 01 Sal It C. A '-t7 i 6 S .. i .i � i-. �' s 1 , �� i { 1' � � { - 5 { 1 1 4•.. -t. L f • /3tA!L�! ' BY DRf� rDATEJ ; �os� ---' ++f1I�t,{4jt Ll& CIV -EI fild Nm 77T En #130 �Uit iL#t`t�ie.t't ane °-- R.10— -S�I;s,'i'7L,�.!>fIIT-._ E2-, U1�-i-d-tti'.fJfii'`')�1,tS:,idf�i; - ' CDAE --__-- Il P.' _ Desert;C 1 FAX -_�`._-1 a_ i _ __,_•.- �_ __. (7607411 (760) 772-40 ry®oalcom OF, — – - . -"•a ,_ . _ m - fs?��.#F��('i{E1�+ =,,_'.:_� - PREPARED FOR:Y �41Es;tf�1d' ^G It W ( N w_:lG 1�—%•. 37t!t;tE�S!�;irS!� w.. ��Y-' -y �. 1_-V��_-!,'-i16�7'1�;iIa{i�! `-ING -._--_R.'U•---_a---,_(C;Li�f+Y�riifE-T_ 10, 77-7 ` i g F ole _= _ �j..� . �:_:_ — —! �__�4_�., ►_"--, 1.i�1j)i!{i11f!y;,j1 L: �-1�I<}i1t;t�i�t{'tiI_ _. '_.i. _—.�—� _... -•.._.._.. __ _". . ' _- "T»I��!ii{EjjtE1,- .•- _.-..:iy'j(1t1i!1i)tfiI -.-- -�N•! �__.�._ . - :• •�-• - "Et`�1����j{(jYa2'11EEE�ft! -- am •?rr_ � tP ;- ..L!;i•.?E?Etjii't'i'-. �.`i��.i .'�rj�#jt1ff�1}E : - - •_.r;�!Fi�r-iF�i+ .,s - � -' ti -.. -i =-I___� ._�l- --i-.. --'__"-'� ''_ �_, -_;(. ` +3, '._.__..- _-- � _._�-•:(1tisaf{s{�Jifi�j�Fj T+1t(,st�fE1I; ..,.t_�,,{c1iFiI1jij� _, , '_'_-.._..•_� �. �. ..•_ ..��T-• -• f f ._" T 7- •, E t i ! j ` f ! 1 s � ( ; 1 t � i• j i t E. #• Hri �. { i. ¢ - _} i —t ,. ; .�"_" 4'__—� i i_"- j _•._!` j ,� j ( 3 ; t _,.__ y _._. -� ., ' `. � ' --#''_'-7 '�-'-' .t._..s•_— ! , e': 't .li i 3. .��.-.•. } t;_:� j _.. ..-_..; �... { "'-Y-'_."'1i -; �r _:'_' itE I a ( # l i i `--'r- t i 6 S .. i .i � i-. �' s 1 , �� i { 1' � � { - 5 { 1 1 4•.. -t. L f • Surcharge Loads Lateral Load Applied to Stem y Adjacent Footing Load Building Code Surcharge Over Heel = The Flying Buttress , Title KIRSHNER WATER FEATURE Page: 'Job .: 2 Structural and Civil Engineering Used To Resist Sliding & Overtuming # 14-125 Dsgnr. DRP Date: 5 MAR 2 4 77725 Enfield Lane #130 0.00 ft Descr: DESIGN 3.5 -FT. HIGH GUNITE WATER FEATURE Palm Desert, CA 92211 ...Height to Bottom = 0.00 ft , (760) 772-4411 email: drpfly@aol.com Used for Sliding & Overturning Wall in File: c:\usersldeniseldesktopldocuments\retainpro 10 project f RetalnPro 10 (c)1987-2012, Build 10.13.8.31 Wall to Ftg CL Dist _ 0.00 ft License: Kw416063110 Cantilevered Retaining Wall Design ;ode: CBC 2010,ACI 318-08,ACI 530-08 License To: FLYING BUTTRESS Base Above/Below Soil - 0.0 ft Axial Dead Load = 0.0 lbs „ Criteria Soil Data Retained Height = 2.50 ft Allow Soil Bearing = 1,995.0 psf Poisson's Ratio = Wall height above soil = 3.50 ft ti Equivalent Fluid, Pressure _ Method Heel Active Pressure - 35.0 psf/ft Slope Behind Wall = 0.00:1 _ Height of Soil over Toe 0.00 in 'Passive Pressure _ '150.0 psf/ft Wall Stability Ratios Water height over heel = 0.0 ft Soil Density, Heel 110.00 pd Overturning = Soil Density, Toe = 1,100.00 pcf Slab Resists All Sliding I FootingllSoil Friction = - 0.250 ' Soil height to ignore Rebar Size = u # 4 for passive pressure = 12.00 in Rebar Spacing = Surcharge Loads Lateral Load Applied to Stem y Adjacent Footing Load Building Code Surcharge Over Heel = 0.0 psf Lateral Load = 0.0 #/R Adjacent Footing Load = 0.0 Itis Used To Resist Sliding & Overtuming ...Height to Top = 0.00 ft Footing Width = 0.00 ft Surcharge Over Toe = 0.0 psf ...Height to Bottom = 0.00 ft Eccentricity = 0.00 in Used for Sliding & Overturning Concrete Data The above lateral load Wall to Ftg CL Dist _ 0.00 ft Axial Load Applied to Stem by been c increased 1.00 Footing Type Line Load Base Above/Below Soil - 0.0 ft Axial Dead Load = 0.0 lbs Wind on Exposed Stem = 32.0 psf ✓ at Bads of Wall Axial Live Load = Axial Load Eccentricity = 0.0 lbs 0.0 in Poisson's Ratio = 0.300 Design Summary Stem Construction Top stem Stem OK Wall Stability Ratios Design Height Above F% it = 0.00 , Overturning = 2.71 OK Wall Material Above "Ht" ` = 'Concrete Slab Resists All Sliding I Thickness = 12,00 l Rebar Size = u # 4 Total Bearing Load = 1,275 lbs Rebar Spacing = 8.00 ... resultant ecc. = 1.54 in Rebar Placed at _ Edge 6166, *3 v&4T, Ct`+Up,L, Soil Pressure @ Toe= 667 psf OK Design Data fb�g + falFa = 0.082 fad � Ca •`�3 r l'T Soil Pressure @ Hal = 353 psf OK Total Force Section lbs = 297.9 Allowable = Soil Pressure Less Than Allowable 1 995 Moment ... Actual ft-#= 630. 9 • ACI Factored @ Toe= 933 psf � Moment.... Allowable = 7,716.6 r ACI Factored @ Heel = 495 psf Shear..... Actual psi = 3.6 Footing Shear @ Toe = 5.1 psi OK Shear..... Allowable psi= 75.0 ` Footing Shear @ Heel = . 0.0 psi OK Wall Weight = .150.0 Allowable = ' 75.0 psi Rebar Depth 'd' in = 8.81 Sliding Calcs Slab Resists All Sliding I LAP SPLICE IF ABOVE in= 12.48 Lateral Sliding Force = 326.4 Itis LAP SPLICE IF BELOW in= HOOK EMBED INTO FTG in = 6.00 Masonry Data Load Factors psi = Building Code CBC 2010,ACI Dad Load 1.400 Live Load 1.700 Earth, H 1.700 Wind, W 1.000 Seismic, E 1.000 Masonry Data I'm psi = Fs psi = . Solid Grouting Use Half Stresses = Modular Ration' Short Term Factor = Equiv. Solid Thick. _ Masonry Block Type = Medium Weight Masonry Design Method = ASD Concrete Data fc - psi = 2,500.0 s Fy psi = 40,000.0 The Flying Buttress- structural and Civil Engineering Idle : KIRSHNER WATER FEATURE , Page: '.21 " ' Job # : 14-125 Dsgnr, DRP Date: 5 MAR 20 T7725 Enfield Lane 6130 DESIGN 3.5 -FT. HIGH GUNITE WATER FEATURE Palm Desert, CA 92211 772.4411 email: drpfly@aol.com '(760) Wallin File: c:\userskleniseldesktopldocumentsXretainpro 10 project f RetalnPro 10 (c)1987-2012, Build 10.13.8.31 License: KW416)W826 Cantilevered Retaining Wall Design :ode: CBC 2010,ACI 318-08,ACI'530-08 License To: FLYING BUTTRESS - Footing Dimensions & Strengths Footing Design Results Toe Width = 1.50 ft Toe Heel ' Heel Width 1.00 ✓ Factored Pressure = 933 495 psf Total Footing Width 2.50 Mu': Upward = 951 0 ftp# Footing Thickness = 12.00 in Mu': Downward = 236 0 ft-# Mu: Design = 715 0 ft-# ' Key Width = , 0.00 in - Key Depth 0.00 in Actual 1 -Way Shear = 5.07 0.00 psi,. - Allow 1 -Way Shear = 75.00 0.00 Key Distance from Toe 0.00 ft psi Toe Reinforcing = # 4 @ 8.00 in Pc = 2,500 psi Fy = 40,000 psi Heel Reinforcing = None Spedd ' Footing Concrete Density = . 150.00 pcf Min. As % 0.0018 Key Reinforcing = None Speo'd Other Acceptable Sizes & Spacings ` Cover @ Top 2.00 @ Btm= 3.00 in Toe: Not req'd, Mu < S • Fr Heel: Not req'd, Mu < S ' Fr ' Key: No key defined Summary of Overturnina & Resistina Forces & Moments .....OVERTURNING..... .....RESISTING..... Force Distance Moment Force Distance Moment ' Item lbs ft ft•# lbs ft ft-# Heel Active Pressure = 214.4 1.17 250.1 Soil Over Heel = 2_.50 ' Surcharge over Heel = Surcharge Over Toe _ Sloped Soil Over Heel = Surcharge Over Heel Adjacent Footing Load Adjacent Footing Load ' Added Lateral Load = Axial Dead Load on Stem = Load @ Stem Above Soil = 112.0 5.25 588.0 • Axial Live Load on Stem = ' = Soil Over Toe Surcharge Over Toe Total 326.4 O.T.M. 838.1 Stem Weight(s) = 900.0 • 2.00 1,800.0 Earth @ Stem Transitions - - Footing Weight 375.0 1.25 468.8 - Resisting/Overtuming Ratio - 2.71 Key Weight - Vertical Loads used for Soil Pressure = 1,275.0 lbs Vert. Component = Total m 1,275.0 lbs R.M = 2,268.8 ' Axial live load NOT included in total displayed or used for overturning resistance, but is included for soil pressure calculation. DESIGNER NOTES: . r 7 1 1 1 1 1 1 1 1 1 1 1 1 . ► J'� .. .- .� � y s i + i ' -' • . I • � _. • , r , � .. .. ' w_ , r ._ 1 i 4�. • � •{ r+f as ' . ,1� 32.psf a t ,HqF to � Wing Restraint ' ' *u r1 ` rr k' F� ssi'� pppp- 326.37# 4 - ' 353.42psf ' 666.58psf i ! _+ —.� —' • '— ! � ' ,—! , _ � s ';' � ! BY P'; DATE 3�W 1 � } � 3 !^ A J0,(LI is _� . ,_ ! # - - STRIICTURAI-B'C-IVIL-ENGINEERING - t i 1 77 725 Enfield Lane 0! Un..1# 130 —= (-- CKD i� DATE i i , PG - - -i-- r ` � , -�' 7 �� I--- ! , j._ { ;.__Palm Desert; Califomia92211� { 77,2•=44'11 FAX i ! ! ' i OF— I (760) • (760) 772-4409 1 drpfiy@aol:com . .. _.__....__ .. PREPARED FOR jam Ll I j !.. •ice - 3 J-.{� � <_:, ` t �:_-.. I i !,(o/ s di A. i J. I /� — —— of , I� i -L—A, 17 71, MI - 00 1 4i � l �' fir_ J �6, � � _•_� �-'_�' ' ' _.:. I � /�, ,off S �. �i{. ��M+ S i 7 M, _ /�!� 2. i 211 L !`'a €• _ `� ,�.,p y �, u 3 �_i P r i'� IV iI• �V�'_'% f✓�+ : �Z a lr ..;/�_—T+ ' ��--- —..—._.__-•! —•W;�• "�. _,;� i• -- -� :gam � f a 1� t a i- t i #.._� i j �" i ) ��_-� (—� -- j f , 1 1 1 THE FLYING BUTTRESS PROJECT KiRSHNER'�' � `Er', PAGE {"5 77725 ENFIELD LN STE 130-x CLIENT �DE$E_RTOtITDDQ_Ei.SzL DESIGN BY �� PALM DESERT CA 92211 JOB NO..DATE: r3l52U1._ REVIEW BY INPUT DATA & DESIGN SUMMARY d P SPECIAL INSPECTION( O=NO, 1=YES)"' , No, (reduced fm' by 0.5) TYP E OF MASONRY (1�MU, 2--BRICK)'1 CMU M MASONRY STRENGTH m' _1'm ksi r> REBAR YIELD STRESS f =400 " ksi a v, �fiz-, ALLOWABLE INCREASING? (Il3GCBC 1605.3.2)[Y Yesy mg!' SEISMIC DESIGN CATEGORY (5 -Gravity) �St ; Gravity Only �.' P/a - M/5. P/k + M/S. SERVICE AXIAL LOAD P = -0ma 0, k Fc SERVICE SHEAR LOAD V 0"Y ,. k ° MOMENT AT MIDHEIGHT M = ft -k EFFECTIVE WIDTH b = `�in EFFECTIVE DEPTH d = ry 24� 4 �'`.� in DISTANCE BETWEEN COL. REINF. a = ;;8;;; �m EFFECTIVE HEIGHT h 4� .ft (TMS 402, 1.16.4.1) VERTICAL REINF. (EACH SIDE) HORIZ. TIES leg, 0 8 8 In o.a (THE COLUMN DESIGN IS ADEQUATE.] ANALYSIS TOTAL REINFORCEMENT AREA As = 1.60 tr? MODULAR RATIO n = 21.48 EFFECTIVE COLUMN AREA An 576 k? REINFORCEMENT RATIO p = 0.003 NET EFFECTIVE MOMENT OF INERTIA In = 27648 Irl' ALLOWABLE STRESS FACTOR SF = 0.667 RADIUS OF GYRATION r 6.93 in MAX TIES SPACING (210aA.5.3.2) S_ - 16 in MASONRY ELASTICITY MODULUS Em = 1350 ksi TRANSFORMED COLUMN AREA STEEL ELASTICITY MODULUS . Es = 29000 ksi Ar c (1 +(2n —1) p) = 643 rnz CHECK VERTICAL REINFORCEMENT LIMITATION (ACI 530, 2.1.6.4) As = 1.60 W? > 0.0025An = 1.44 slz ]Satlsfattoryl 0.04An = 23.04 0 (Satlsfaet-A ALLOWABLE STRESS DUE TO AXIAL LOAD ONLY- AXIAL STRESS AT MIDHEIGHT OF THE COLUMN A—)2)= z _ P +( half col. g = F° _ (SF)(0.25 f'ozas ksi f = weiht) 0.002 W ) 1.0 — (140r)) ° Ar [for h/r < 99] < Fa. MatisfattoM ALLOWABLE STRESS DUE TO FLEXURE ALLOWABLE REINF. STRESS DUE TO FLEXURE Fb='(SF)(0.33f= 0.330 Ii Fs=(133 or 1.0)(20) or 32= 26.7 ksi TOTAL MOMENT ACTING AT MIDHEIGHT TRANSFORMED MOMENT OF INERTIA _ / l Mr=M+(0.1)r 2d1= 0.3 ft4dps Ir=I„+(2n—l)A,i 2 Iz 26252 In' STRESS IN THE EXTREME FIB)JER DUE TO MT MAX -STRESS COMBINED AXIAL & FLEXURE f b = Md = 0.001 ksi .f m = f ° +•.f b = 0.003 ksi 2I, < fa, Matisfaetory. the section Is untracked] < Fb, rYl MAX REINF. STRESS COMBINED AXIAL & FLEXURE AXIAL LOAD AT BASE OF THE COLUMN f s = 2n f ° + afb l = 0.1 ksi P, = P +( full col. weight) = 2.160 k d J < Fc, MatistsctoM ALLOWABLE AXIAL LOAD FOR AXIAL COMPRESSION ONLY P,=((SF)0.25f�A„+0.65FsAs) 1.0-171.31 k >P%MadsfatwrA (h140r)2)= [for h/r <991 SHEAR DESIGN DETERMINED FROM THE FOLLOWING EXPRESSION f�= d 0 FdF„=MVV (SF)1.125 Ff. A -Fd (SF)2 f. (TSM 402-112.3.6) ll 36.68626 psi [5attafattory] Technical References: 1. 'MasonryDesigners' Guide. Third Edrtial' (MDG3), The MasonrySociety. 2001. ' i 41 _ "' .^� 1�/%BY DATE 3 I 1 i JOB iLiRS� S7RUCTURAI4-CIVIL-ENGINEERING _.__� CKD 1 ; 77.725 Enfield Lane �: Unit!# 130 ; ! t DATE !_� (760) 7Z2-4411 FAX (760) 772-4409; t ? t a �- i ! IdrPfly®aol.com s1 PREPARED FOR: , _07— hI;T, o F P9' t + 1 71- f ! P A i rja®�-_ I y �. f.-5r�� !��—._:!_....;fir � ' —'-', ���_—� /i� •_ `S v—.�ei►T✓ ._ ! ._! —�_3-_ -r r __ _ – — - .177