PP 93-497Titit 4 Q9 M - - CITY OF LA QUINTA 78-095 CALLE TAMPICO — LA - QUINTA, CALIFORNIA 92253 - (619) 777-7000 FAX (619) 777-7101 August 23, 1993 Mr. Michael Allen Indian Wells Joint Venture 45-025 Manitou Drive . Indian Wells, CA 92210 SUBJECT: PLOT PLAN 93-497 (RED ROBIN RESTAURANT) Dear Mr.' Allen: The Planning and Development Department has reviewed your initial set of working drawings for the Red Robin Restaurant in the One Eleven La Quinta Center. We have found that a number of corrections are needed. These revisions are as follows: 1. Roof lighting fixtures shall be in compliance with the City's "Dark Sky" Ordinance. If light fixtures are not in compliance they will be required to be removed (Condition #4). 2. The handicap ramp between the handicap parking stalls on the north side of the building is required to be widened to 8 -feet and relocated so that the landscape planter at the top of the ramp (south end) does not interfere with persons utilizing the ramp (Condition #12). 3. Trash enclosure specifications are not in compliance with Waste Management design standards. Please contact Waste Management of the Desert for proper standards and include them as a part of the working drawings (Condition #15). 4. Submit final landscaping and irrigation working drawings, incorporating Conditions #16, 17, 18, and 19. 5. Along the east side of the building, a trellis similar to that utilized on the west side of the building is required to be provided. The site plan on CS -1 indicates a small trellis on the east side of the building. However, no additional details are shown for this trellis on either a detail sheet or the east elevation -of the building. Include appropriate specifications and plans for the trellis. Additionally, the trellis should span at least of ten feet of the east side of the wall over the doorway (Condition #20). 6. The window glass _on the building is required to be either recessed or provided with overhangs so that a minimum of two feet protection is provided. Plans show two foot overhangs in some areas. However,- not all section views and details indicate the two foot protection. The plans should be revised to insure that this is provided (Condition #21). LTRSS.389MAILING ADDRESS - P.O. BOX 1504 - LA OUINTA, CALIFORNIA 92253 • F 7. All signs shall require separate sign permits and be in compliance with approved sign program (Condition #22). r 8. The roof trellis members are required to be placed close enough to provide shade with all wood members a minimum of 3" X 6" and lag bolted. There are no details on the trellis to determine that this condition is being complied with. The plans must be revised to comply with the condition (Condition #23). 9. Condition #25 requires that the following items be studied and revisions implemented if it is determined to be necessary by the City: A. The vertical treatment along the upper parapet roof. B. The applicant shall study the possibility to provide additional horizontal members on the windows. There is no indication that this item has been dealt with. 10. Sheet, CS -2 indicates a screen wall detail. It is not clear where this screen wall is being utilized. The plans should be revised to show where this screen wall is to be used. 11. The landscaping and irrigation plans are required to be reviewed and approved by both the Riverside County Agricultural Commissioner and the Coachella Valley Water District. These clearances must be received prior to a building permit being issued. Please make the necessary changes or clarifications to the working drawings. Once they are made please see that we receive a copy in order to recheck the plans. Should you have any questions regarding this matter, please feel free to contact the undersigned. Very truly yours, JERRY HERMAN PLANNING & DEVELOPMENT DIRECTOR STAN B. SAWA Principal Planner SBS:bja cc: Mr. Chris .Cooper, Archnet :Buil ding and `Safety Department LTRSS.389 OF RIVEggJDE - PART(NIEE�T pF� HEALTH PLAN REJECTION NOTICE TO: tU��+ l�;�l CG: 0 RE: DATE: PHONE :�}) l 1 ila% / CCD ESTALLISFL'fENT NAME —LIcC (L-Qv, ADDRESS— 2A 7 � (.,� The plans for your food establishment have been reviewed and rejected for the reasons: ' following allure o provide an adequate finish s he ul - s����- , V, •h.e, l a c �r .�R 6 e .-es 4�`jV.-C..1, n cS Ir0.l WQ t t r +� Q UJ iii/. Failure to rov dean P (,J1d �•( c ec.v,• Aas� b'�v��e.�binQ.. .o��i ., , P KCL P�;r quate eqbip en sched ale u2 o� f�a.�. -� S p �( kn�tit� �2.2v_itw� f Failure to provide a plumb^ img s �}eduleyrr`e w.acl��k2E.s ��� e��au� f orr e d tnA � � h CQ �:t Ot�er Y�fl��oc� foo a r ks �ikia�t�e � L.e*'( (X TO xi" Please retrieve your plans and add the above indicated information prior to resub- mittal. Plans rerejectionwill not be submitted within sixty (60) days of + plan check fee, charged another Plans are available at V7`? 2_ ' as and will be discarded ►s A if not picked up within sixty (60) days of. thin s otice date, NO INSPECTION OF YOUR ESTABLISHMENT WILL BErCONDUCTED, OR APPROVAL GRANTED TO 0 UNTIL ALL PROPER INFORMATION REQUESTED HAS BEEN RECEIVED AND YOUR PLANS RETURNED TO YOU. PLANS MUST BE REVIEWED, APPROVED, FINALED, AND RETURNED TO YOU BY THISPETE, MENT PRIOR TO ANY CONSTRUCTION WORK BEGINNING. UPON COMPLETION, TWO SETS OF FINALT PLANS ARE TO BE TAKEN TO THE BUILDING DEPARTMENT FOR THEIR•REVIEW AND APPROVAL. ED DOH SAN 030 - (New 5/87) Reply lo: MARVIN A. HORNSTEIN STRUCTURAL ENGINEER CALCULATION SHEET NO. 18340 VENTURA BLVD., SUITE 202 1 Z I I Q - TARZANA, CALIFORNIA 91356 ------_..------------------------ PFOJECT kM 'OFFICE (818) 708-1860 FAX 818 708-9524 �`�� � P• H 0;j �`, No. 875 z J-ExP. 12-31;96 LP s�* UCT\N�P��Q ��'' nr�ac.►�F��/e is mill number (000 shown), and the perAl )rms to APA's performance standard PRP - >des in NER-108 (Ref. 15.1). )anels account for much of the wood es. These materials are assumed to 'lywood and panels with directional are normally used in the strong ierpendicular to the supports). How- !) the panels are often turned in the ,his latter case, a thicker panel may on results in a savings in labor. In be carried with the increased panel appears in the grade -trademark d erformance-rated sheathing. Recall :tural wood panels may be performs, to determine the sheathing require- �ction under typical roof live loading lual span agrees with the roof spas can be used indirectly to determine 8.13. For example, if the span is 24 ie required span rating of 40/20 can roof span in the span rating (40 in.l 4 in.). ,g. 8.13 are recognized by the three 5.1), which contains a similar table. it performance -rated panels, and the sum load capacities. Consequently apacities that are greater than thou applies to plywood only, and it cons, exceed the loads in Fig. 8.13. 1 list the maximum allowable span' (port (the UBC table refers to 11edgla the panel edges parallel to the span Example 8.10. Generally support to (ming can be provided by blocking. ?l clips. mit differential movement between �► some form of edge support is not ;lacing of supports will be required. ALLOWABLE UNIFORM ROOF LIVE LOADS FOR APA RATED SHEATHING AND APA RATED STURD•1•FLOOR WITH LONG DIMENSION PERPENDICULAR TO SUPPORTS I, 6 N WTO SHEATHING ROOF FLOOR i� 0X SHMINGICEILINO DECK s^ i f•.�%fir. I MAXIMUM SPAR Peon) ALLOWABLE LIVE L040S Ipd) Jn A rMS fMNFI THICKNESS With Eepe Without Edge Spuing of Supports Comer -to -Center 9nchec) MAXIMUM SPAN Qnehul _ rhe 48 54 60 bse Onch) 3uppon Support 1 12 16 20 24 32 40 511 6 12 12 30 0 YO 5118^ 3/8 16 16 70 30 0 300 5116.3/8 20 20 120 50 30 0 MO 318.711 1/2 24 203 190 100 60 30 0 i WS 7/16, 1/2 24 24 190 100 65 40 16 165 F 11116 15132. 1/2, 518 32 28 325 180 120 70 30 204' 5 all" 9/16. 19!32, 518, 314, 718 40 32 305 205 130 60 30 1 rYJ4 23132, 314, 7/8 48 36 — — 280 175 95 45 35 24 W32 7/8.1 54 40 245 130 75 50 35 32 ij 4" 718.1, 1-1/8 60 1 48 305 165 100 70 50 35 1 48 I N PAD STURD-1-FLOOR ROOF FLOOR 4 ^— MAXIMUM SWILL unchu) ALLOWABLE LIVE LOADS (p!n I MAXIMUM Spacing m supports Centerdo-to 9nchu) MEL THICKNESS SPUN gifts Ed Withom Edge (Inches) gSM (inch) Support Support 12 16 20 24 32 40 48 51 gp Y o c 19132, 518, 21132 24 24 185 100 65 '40 165 204.5 A e c 19132, 5/8, 314 32 32 270 150 100 60 30 M c c 11116, 23132, 3/4 48 36 240 160 100 50 30 25 24 (` ( Sl o c 718, 1 48 40 — 295 185 100 60 40 32 Igoe 1-3132, 1.1/8 60 48 — — — 290 160 100 65 50 40 1 48 --0 W*W* spans were determined using a dead load of 10 psf. If the dead load exceeds 10 psf then the live load should be reduced f%"&iagroove edges, panel edge clips (one midway between each support^ except two equally Spaced between supports 48 inches P wol. lumber blocking, or other. Only lumber blocking will satisfy blocked diaphragm requirements of Table No. If. except as noted in l+me83. %rgbw inches for 112 -Inch panels. %it to YM over framing spaced 24 inches on center for floors where 1-1/2 inches of cellular or lightweight concrete is applied over • go"% 4%w mud Over framing of 24 inches on center where 3/4 -inch wood strip flooring is installed at right angles to joist. 1Vsw to panels 24 inches or wider. Allowable roof live loads on APA Rated Sheathing. (APA.) A point about the support of panel edges should be emphasized. The use dT&G edges or panel clips is accepted as an alternative to lumber blocking br sheathing loads only. If blocking is required for diaphragm action (Chap. 11, panel clips or T&G edges (except 11/8 -in. -thick 2-4-1 plywood with stapled T{G edges) cannot be substituted for lumber blocking. QAMPLE 8.10 Roof Sheathing Edge Support Requirements Alternative forms of support for panel edge that is perpendicular to roof framing (Fig. 114). Unsupported edge. In most cases Fig. 8.13 and UBC Table 25-S-1 require closer roof joist spacing than given by the span rating when the 8 -ft panel edges are not supported. Note that panel thickness may be increased as an alternative to providing support to all edges (or reducing the roof beam spacing). S. Lumber blocking. Cut and fitted between roof joists. r. Tongue -and -groove (T&G) edges. d. Panel clips. Metal H-shaped clips placed between plywood edges. For the number of panel clips refer to Fig. 8.13, footnote 2. s^ i f•.�%fir. Jn A . y DESCRIOtION WATts OtA 0 &t)LIP6 r -A LT ALLbWEb VWATft rz a r, r, 4 c 2'K 4.' rLUOIZ L4 F1; T�2. A a V- LT 11 q e A 0 V, k. Vze-" 14 lwr-A'No P6057"I r-3 ,it 16T F -i P FL v 0 R STJZI fl r -L UDIZ [Fit tte"l ride SYSITSM I I it Abi U&4 #4 bkc tsaiiui vow. p4ea" i4wo iuppodN dowftwnWoh- Awdsitij AMAL WAtft AMA cAtEoollv (t, zok) WATts OtA 0 AREA (SF) ALLbWEb VWATft toths AREA DEscgll>tioN F ice ctas. I o e.*wo Fla &V.IT L16N FK} wkLt 'MTV µp5 sy-r9'K.IOR F1911W14 15OW gKtgK10It U FI(o 614040. STN WAY tri 7 2 6Y otHDA ax d►tioa SIDO 06 F.18 IVal.t W614 Fil t m'JT VO,9 W O It FVJ 2)<4' Fcv49Tz I eWUP r-LuoR �N� �� t'�6t b�AI rillM, pt�A�t+ �rovld+ lt�pparlM�j doaxn�n6�ffntl. WAtT$ Otil LUMMIAIpE Owkm p 13 ao CEc Lw -FAULT, Y N. ❑ U 0 E ❑❑ _❑ ❑ El El ❑❑ ❑❑ '•Z °O sa �v — 3 7 2 72 ❑ ❑ tULtit & FROM 1tIM PAGN PLUS susTotAL rAoM CoNTINUAtION PAcdE NA LOS CoNthoL Cqt ult WAtft NSA+ (FROM LTO -31... • AUJU9TE3 ACTUAL. WAtit I q 4 $� 1681 �4�! i 4s 1 1.5/7-9 1-) E--� — wlol yNiallne i I _ nifin Q 9 lel .. • AeldslQ IIeM °u►lBej Iie(eS AeIdsIQ pq j ?u4pe4 fops �(eldslp s� .ads IE' sue4 woad Q4114011 A!lgslq 4of spffi 'E s�16M �G °l �i cc (Z Neo t-UNI)1-4 §91401418Q poueuN.t ool P'l so@m " ►�taunN ' 4 7-i7�'� ` V'1Nn� d7 /�Il�✓02/ G`a/la�rok i lg�tol rfN3N2A1' 1 1s-7io.l 5H-el1 =h ► Y1709 /15.8N 96 - rorl -q23?)- i a1/ 0 7-J n wadi/ 9Hd4P �V V V.-1 /71 9nnA7 1/b'' ga zl8.s �� �N/Nla r•7� o °� Tel /�r >n/N a 0. Mu�µuYM>}11 _ nifin Q 9 lel .. • AeldslQ IIeM °u►lBej Iie(eS AeIdsIQ pq j ?u4pe4 fops �(eldslp s� .ads IE' sue4 woad Q4114011 A!lgslq 4of spffi 'E s�16M �G °l �i cc (Z Neo t-UNI)1-4 §91401418Q poueuN.t ool P'l so@m " ►�taunN ' 4 7-i7�'� ` V'1Nn� d7 /�Il�✓02/ G`a/la�rok DRED LPI 9 Wk tAcfiWtV .106;" OAR pA df IP 7 $441449Y #0 4 , 'IPA Ilium Cat. RCR (d ti (DOTES` —ALLOMbWAttS tA§kALLOTTED AREA ALLOWED WATTS (E x F) a 0 so t000 V1 4 - 5 109 IA 0 &,,yj a i,;,011 P: DESIGN WAus LUMIN. CODE D� oty. —ALLOMbWAttS tA§kALLOTTED AREA ALLOWED WATTS (E x F) a 0 so t000 V1 4 - 5 109 IA 0 +t 7 P: -7 !;o FS 45 3L. c DESIGN WAus LUMIN. CODE D� oty. %4AjTS1 ., LUMIN. WATTS J) r a 0 so t000 F+ 5 109 523 P: -7 !;o FS 45 3L. c PAGE TOTAL Enbi' � N1 of throw SOUANGtOtAL TAILORED LPD - Public Atea Ulspla s LJ G [jig [tq lJ LJ n ALLb"M WATTS OTY. TASKALLOWEDALLOTTED L AREA Lpb wAtf§ bts oN WATTS LUMiN.WATTS/ cobg OTY. L um, I N. DESIGN WATTS, 3 ALLb"b WAtti -(Min. d or k) 10,00 523. 324. �7O ALLbW'E'b WATTS (mirl. F or J)- T6fA7L AREA PUBLIC DISPLAYS TOTAL WATTS PUBLIC bISOLAY AREA MAXIMUM AREA PUBLIC DISPLAYS (so) jMone 4*J? Clain -Aft" 78495 CALLE TAMPICO - LA QUINTA, CALIFORNIA 92253 - (619) 777-7000 FAX (619) 777-7101 August 23, 1993 Mr. Michael Allen Indian Wells Joint Venture 45-025 Manitou Drive Indian Wells, CA 92210 SUBJECT: PLOT PLAN 93-497 (RED ROBIN RESTAURANT) Dear Mr. Allen: The Planning and Development Department has reviewed your initial set of working drawings for the Red Robin Restaurant in the One Eleven La Quinta Center. We- have found that a number of corrections are needed: Thesejevisions are as i IMS: Roof lighting fixtures shall be in compliance with the City's "Dark Sky" Ordinance. If light fixtures are not in compliance they will be required to be removed (Condition #4). 2. The handicap ramp between the handicap parking stalls on the north side of the building is required to be widened to 8 -feet and relocated so that the landscape planter at the top of the ramp (south end) does not interfere with persons utilizing the ramp (Condition #12). 3. Trash enclosure specifications are not in compliance with Waste Management design standards. Please contact Waste Management of the Desert for proper standards and include them as a part of the working drawings (Condition #15). Submit final landscaping and irrigation working drawings, incorporating Conditions #16, 17, 18, and 19. ,L . Along theeast side of the building, a trellis similar to that utilized on the west side of the building is required to be provided. The site plan on CS -1 indicates a small trellis on the east side of the building. However, no additional details are shown for this trellis on either a detail sheet or the east elevation of the building. Include appropriate specifications and plans for the trellis. Additionally, the trellis should span. at least of ten feet of the east side of the wall over the doorway (Condition #20). 6. The window glass on. the building is required to be either recessed or provided with overhangs so that a minimum of two feet protection is provided. Plans show two foot overhangs in some areas. However, not all section views and details indicate the two foot protection. The plans should be revised to insure that this is provided (Condition #21). ' LTRSS.389MAILING ADDRESS - P.O. BOX 1504 - LA QUINTA, CALIFORNIA 92253 11 All signs shall require separate sign permits and be in compliance with approved sign program (Condition #22). S8. The roof trellis members are required to be.placed close enough to provide shade with all wood members a minimum of 3" X 6" and lag bolted. There are no details on the trellis to determine that this condition is being complied with. The plans must be revised to comply with the condition (Condition #23). r. 9. Condition #25 requires that the following items be studied and revisions implemented if it is determined to be necessary by the City: A. The vertical treatment along the upper parapet roof. B The applicant shall study the possibility to provide additional horizontal members on the windows. There is no indication that this item has been dealt with. 10. Sheet CS -2 indicates a screen wall detail. It is not clear where this screen wall is being utilized. The plans should be revised to show where this screen wall is to be used. fl l The landscaping and irrigation plans are required to be reviewed and approved by both the Riverside County Agricultural Commissioner and the, Coachella Valley Water District. These clearances must be received prior to a building permit being issued. Please make the necessary changes or clarifications to the working drawings. Once they are made please see that we receive a copy in order to .recheck the plans. Should you have any questions regarding this matter, please feel free to contact the undersigned. Very truly yours, JERRY HERMAN PLANNING & DEVELOPMENT DIRECTOR STAN B. SAWA Principal Planner .SBS:bja cc: {Mr, `Chris Cooper, Aichnet - . Building and Safety Department LTRSS.389 t it �. 1:�r+6YNnv9vk+@1'fatatGy II'�LH11D TR�J'� cihJC . T` fti� . r 14-:455 ur2l �• 27,93 15:3'� No . 01S P . 0� `� _ ,.. , _ �.w___ f_at'tat_ra rl`CI i»J71(fryn(!!•sJ?l)233^ r 5 Inc. 1 14 4 Ta Qw-nta Building t7ej-hArt<lte-rit i i Attn: Kim Harold Ref v ie ni k-we?i tali c_ i i.nt a z la (:njinta, CA In the evaluatic,n and design of roof trusses, on the forejiez-nUoneed- project, Inland Truss, Inc., follcmed Pres ribud icxads. The Struc- tural, sheets, in particular 5--2 plans dated July 13, 1993 vre fol- lmAed and adhered to. All information in plans provided were cun- si.derxi and follryaen. t If there are any further questions, please do not hesttat.e to r Very truly Yom's, ikiniel W. I'rwin President C .. - Al -S ,N,. 4tiw, r ` k batt�►�Y R� C .. - Al -S ,N,. 4tiw, r ` k batt�►�Y