0301-397 (CSCS) Title 24TITLE 24 REPORT oR•�3oIe.-19 Title 24 Report for: The Center At LA Quinta LA Quinta, CA Project Designer: PERKOWITZ+RUTH ARCHITECTS 111 W. OCEAN BLVD, 17th FLOOR LONG BEACH, CA 90802 (562) 628-8000 Report Prepared By: Arthur L. Moore TORABIAN & ASSOCIATES 27016 Langside Avenue Santa Clarita, CA 91351 (661) 252-0400 Job Number: CL2 Date: 2/25/2003 `1a - 406- NU34 11 CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION oA o�eY 6fft CE 5Z-1 EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is orized by the California Energy Commission for use with both the Residential and Nonresidential 2001 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC (415) 883-5900. EnergyPro 3.1 By EnergySoft Job Number: CL2 User Number: 4984 0 CERTIFICATE OF COMPLIANCE Part 1 of 2 ENV-1 0—PROJECT NAME DATE The Center At LA Quinta 2/25/2003 PROJECT ADDRESS LA Quinta PRINCIPAL DESIGNER - ENVELOPE TELEPHONE Building Permit # PERKOWITZ+RUTH ARCHITECTS (562) 628-8000 DOCUMENTATION AUTHOR TELEPHONE Checked by/Date TORABIAN & ASSOCIATES 661 252-0400 1 Enforcement A enc Use GENERAL INFORMATION DATE OF PLANS BUILDING CONDITIONED FLOOR AREA CLIMATE ZONE 19,750 Sq.Ft. 15 BUILDING TYPE [Xj NONRESIDENTIAL HIGH RISE RESIDENTIAL HOTELIMOTEL GUEST ROOM PHASE OF CONSTRUCTION 0 NEW CONSTRUCTION ADDITION [:] ALTERATION EXISTING + ADDITION METHOD OF ENVELOPE ❑ COMPONENT ® OVERALL ENVELOPE PERFORMANCE COMPLIANCE STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building envelope requirements. The documentation preparer hereby certifies that the documenoisl plete. DOCUMENTATION AUTHOR SI A 2 DA E "- Arthur L. Moore ' a 3 The Principal Envelope Designer hereby certifies that the pro s buiwi4WS'ign rented in this set of construction documents is consistent with the other compliance forms and 015% sp ifications, and with any other calculations submitted with this permit application. The propose a Q signed to meet the envelope requirements contained in Sections 110, 116 through 118, and 140, 9 of Title 24, Part 6. Please check one: ❑ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the state of California as a civil engineer or mechanical engineer, or I am a licensed architect. ❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. I affirm that I am eligible under Division 3 of the Business and rofessions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to B 01ness and Professions Code Sections 5537, 5538, and 6737.1. PRINCIPAL ENVELOPE DESIGNER - NAME SIG A DATE LIC. # PERKOWITZ+RUTH ARCHITECTS 102 Q 3 co ENVELOPE MANDATORY MEASURES Indicate location on plans of Note Block for Mandatory Measures IONS TO APPLICANT IN7detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the ntial Manual published by the California Energy Commission. Required on plans for all submittals. Part 2 may be incorporated in schedules on plans. ENV-2: Used for all submittals; choose appropriate version depending on method of envelope compliance. ENV-3: Optional. Use if default U-values are not used. Choose appropriate version for assembly U-value to be calculated. EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page:3 of 38 r Site Assembled Glazing U uneCK Dox IT buiioing is >= 1g0,o0o sqtt of GrA and >= 10,000 sqtt vertical glazing then NFRC Certification is required. Fnllnw NFRC 100 -SR Prnraduras anti suhmit NFRC I ahal Cartifirata Fnrm # Type ENVELOPE COMPLIANCE SUMMARY Part 2 of 2 ENV -1 Glazing Type Location / Comments 1 Window 430 0.570 0 0.55 Double NonMtl Tinted Default Tenant "12" PROJECT NAME The Center At LA Quinta 180 0.570 0 DATE 2/25/2003 Double NonMtl Tinted Default OPA(�UE SURFACES 3 Window 180 0.570 0 0.55 Surface Framing # Type Type Act. Area U -Fac. Azm. Tilt Solar ' Gains WN Form 3 Reference Location / Comments 230 0.570 1 Wall Wood 1.400 0.065 90 90 X R-19 Wall W.19.2x6.16 Tenant "12" 2 JRoof Wood 3.800 0.035 0 0 & R-30 Roof R.30.2x12.16 Tenant "12" 0 3 Wall Wood 864 0.065 180 90 X R-19 Wall W.19.2x6.16 Tenant "12" 0.55 4 Wall Wood 434 0.065 0 90 R-19 Wall W.19.2x6.16 Tenant "12" Double NonMtl Tinted Default 5 Roof Wood 1,600 0.035 0 0 0 R-30 Roof R.30.2x12.16 Tenant "11" Tenant -4 6 Wall Wood 324 0.065 180 90 X R-19 Wall W.19.2x6.16 Tenant "11" 7 Wall Wood 144 1 0.065 0 1 90 X11 IR-19Wall W.19.2x6.16 Tenant "11" 8 Roof Wood 1,600 0.035 0 0 X1 I R-30 Roof R.30.2x12.16 Tenant "10" 13 Window 9 Wall lWood 324 0.065 180 90 X1 I R-19 Wall W.19.2x6.16 Tenant "10" 10 Wall Wood 144 0.065 0 90 X1 JR-19Wall W.19.2x6.16 Tenant "10" 11 Roof Wood 1,920 0.035 0 0 X1 I R-30 Roof R.30.2x12.16 Tenant "9" 12 Wall Wood 430 0.065 180 90 X I JR-19Wall W.19.2x6.16 Tenant "9" 13 Wall Wood 200 0.065 0 90 x I I R-19 Wall W.19.2x6.16 Tenant "9" 1 None 14 Roof Wood 1,920 0.035 0 0 X I I R-30 Roof R.30.2x12.16 Tenant "8" 0.76 15 lWall lWood 430 0.065 180 90 x1l I R-19 Wall W.19.2x6.16 Tenant "8" 10.0 16 Wall Wood 200 0.065 0 90 X11 JR-19Wall W.19.2x6.16 Tenant "8" 23.0 17 Roof Wood 1,920 0.035 0 0 X R-30 Roof R.30.2x12.16 Tenant "7" 2.0 18 Wall Wood 430 0.065 180 90 10.0 R-19 Wall W.19.2x6.16 Tenant "7" 0.1 6.0 6.0 0.1 19 Wall Wood 270 0.065 0 90 16.0 R-19 Wall W.19.2x6.16 Tenant "7" 2.0 0 20 Roof Wood 11,920 0.035 0 0 X R-30. Roof R.30.2x12.16 Tenant "6" 0.1 FENESTRATION SURFACES 9 None 0.76 10.0 32.0 6.0 r Site Assembled Glazing U uneCK Dox IT buiioing is >= 1g0,o0o sqtt of GrA and >= 10,000 sqtt vertical glazing then NFRC Certification is required. Fnllnw NFRC 100 -SR Prnraduras anti suhmit NFRC I ahal Cartifirata Fnrm # Type Area U -Fac. Act. Azm. SHGC Glazing Type Location / Comments 1 Window 430 0.570 0 0.55 Double NonMtl Tinted Default Tenant "12" 2 Window 180 0.570 0 0.55 Double NonMtl Tinted Default Tenant "11" 3 Window 180 0.570 0 0.55 Double NonMtl Tinted Default Tenant "10" 4 Window 230 0.570 0 0.55 Double NonMtl Tinted Default Tenant "9" 5 Window 230 0.570 0 1 0.55 Double NonMtl Tinted Default Tenant "8" 6 Window 160 0.570 0 0.55 Double NonMtl Tinted Default Tenant 7" 7 Window 160 0.570 0 0.55 Double NonMtl Tinted Default Tenant "6" 8 Window 160 0.570 0 0.55 Double NonMtl Tinted Default Tenant "5" 9 Window 320 0.570 0 0.55 Double NonMtl Tinted Default Tenant -4 10 Window 170 0.570 270 0.55 Double NonMtl Tinted Default Tenant -4 11 lWindow 170 0.570 270 0.55 Double NonMtl Tinted Default Tenant -3 12 Window 170 0.570 270 0.55 Double NonMtl Tinted Default Tenant -2 13 Window 200 0.570 270 0.55 Double NonMtl Tinted Default Tenant "1" EXTERIOR SHADING ## Exterior Shade Type SHGC Window Hgt. Wd. Overhang Left Fin Len. H t. LExt.RExt. Dist. Len. H t. Right Fin Dist. Len. H t. 1 None 0.76 10.0 43.0 4.0 0.1 4.0 4.0 0.1 2.0 0 0.0 0.0 0 2 None 0.76 10.0 18.0 4.0 0.1 4.0 4.0 0.1 2.0 0 0.1 2.0 0 3 None 0.76 10.0 18.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 4 None 0.76 10.0 23.0 2.0 0.1 2:0 2.0 0.1 2.0 0 0.1 2.0 0 5 None 0.76 10.0 23.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 6 None 0.76 10.0 16.0 6.0 0.1 6.0 6.0 0.1 2.0 0 0.1 2.0 0 7 None 0.76 10.0 16.0 6.0 0.1 6.0 6.0 0.1 2.0 0 0.1 2.0 0 8 None 0.76 10.0 16.0 6.0 0.1 6.0 6.0 0.1 2.0 0 0.1 2.0 0 9 None 0.76 10.0 32.0 6.0 0.1 6.0 6.0 0.1 2.0 0 0.1 2.0 0 10 None 0.76 10.0 14.0 6.0 0.1. 6.0 6.0 11 None 0.76 10.0 17.0 6.0 0.1 6.0 6.0 12 None 1 0.76 10.0 17.0 6.0 0.1 6.0 6.0 3 None 0.76 10.0 20.0 6.0 0.1 6.0 6.0 EnergyPro 3.1 By EnergySoft . User Number: 4984 Job Number: CL2 Page:4 of 38 Site Assembled Glazing11 ChecK box it Building is >= 100,000 sgft of CFA and >= 10,000 sqft vertical glazing then NFRC Certification is required. Follow NFRC 100 -SB Procedures and suhmit NFRC Lahel Certificate Form AIM ENVELOPE COMPLIANCE SUMMARY Part 2 of 2 ENV -1 SHGC Glazing Type Location / Comments PROJECT NAME The Center At LA Quinta DATE 2/25/2003 OPAQUE SURFACES Surface Framing # Type Type Act. Area U -Fac. Azm. Tilt Solar Gains y/N Form 3 Reference Location / Comments 21 Wall Wood 430 0.065 180 90 X R-19 Wall W.19.2x6.16 Tenant "6" 22 Wall Wood 270 0.065 .0 90 R-19 Wall W.19.2x6.16 Tenant "6" 23 Roof Wood 1,920 0.035 0 0 X R-30 Roof R.30.2x12.16 Tenant "5" 24 Wall Wood 430 0.065 180 90 R-19 Wall W.19.2x6.16 Tenant "5" # Exterior Shade Type 25 Wall Wood 270 0.065 0 90 R-19 Wall W.19.2x6.16 Tenant "5" 26 Wall Wood 400 0.065 0 90 X R-19 Wall W.19.2x6.16 Tenant -4 27 Roof Wood 800 0.035 0 0 X11 I R-30 Roof R.30.2x12.16 Tenant -4 28 Wall Wood ' 230 0.065 270 90 x1l JR-19Wall W.19.2x6.16 Tenant -4 29 Roof Wood 800 0.035 0 0 X11 I R-30 Roof R.30.2x12.16 Tenant -3 30 Wall Wood 190 0.065 270 90 x1l JR-19Wall W.19.2x6.16 Tenant -3 31 Roof Wood 700 0.035 0 0 X11 I R-30 Roof R.30.2x12.16 Tenant -2 32 Wall Wood 190 0.065 270 90 X R-19 Wall (W 19.2x6.16) Tenant -2 33 Roof Wood 850 1 0.035 0 0 R-30 Roof R.30.2x12.16 Tenant "1" 34 Wall Wood 720 0.065 180 1 90 X R-19 Wall W.19.2x6.16 Tenant "1" 35 Wall Wood 196 0.065 270 1 90 R-19 Will W.19.2x6.16 Tenant "1" FENESTRATION SURFACES Site Assembled Glazing11 ChecK box it Building is >= 100,000 sgft of CFA and >= 10,000 sqft vertical glazing then NFRC Certification is required. Follow NFRC 100 -SB Procedures and suhmit NFRC Lahel Certificate Form AIM # Type Area U -Fac. Act. Azm. SHGC Glazing Type Location / Comments EXTERIOR SHADING # Exterior Shade Type Window SHGC Hgt. Wd. Overhang Left Fin Right Fin Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page:5 of 38 OVERALL ENVELOPE METHOD Part 1 of 6 ENV -2 ECT NAMEDATE The Center At LA Quinta I 2/25/2003 WINDOW AREA TEST A. DISPLAY PERIMETER 9161 ft X 6 = 1 5,49 sf DISPLAY AREA B. GROSS EXTERIOR WALL AREA 11,680 sf X 0.40 = I4,67 sf 40% AREA C. GROSS EXTERIOR WALL AREA 11 ,680 Sf X 0.10 = 1 ,16 sf MINIMUM STND. AREA •D. ENTER LARGER OF A or B 5 49 sf MAXIMUM STND. AREA E. ENTER PROPOSED WINDOW AREA 2,76d sf PROPOSED AREA F. WINDOW WALL RATIO = Proposed Window Area Divided by Gross Exterior Wall Area = 1— 23.63% IF E IS GREATER THAN D OR LESS THAN C, PROCEED TO THE NEXT CALCULATION FOR THE WINDOW AREA ADJUSTMENT. IF NOT, GO TO PART 2 OF 6. 1. IF E GREATER THAN D: MAXIMUM PROPOSED WINDOW STANDARD AREA WINDOW AREA ADJUSTMENT FACTOR GO TO PART 6 TO CALCULATE ADJUSTED AREAS. 2. IF LESS THAN C: MINIMUM PROPOSED WINDOW . STANDARD AREA 'AREA ADJUSTMENT FACTOR GO TO PART 6 TO CALCULATE ADJUSTED AREAS. I SKYLIGHT AREA TEST ATRIUM HEIGHT 12 FT IF <= 55 FT IF > 55 FT 0.101 X I= 0.051 X 1 19,7501 =1 9881- STANDARD 88STANDARD % GROSS STANDARD ROOF AREA SKYLIGHT AREA 0 �---� PROPOSED SKYLIGHT AREA IF THE PROPOSED SKYLIGHT AREA IS GREATER THAN THE STANDARD SKYLIGHT AREA, PROCEED TO THE NEXT CALCULATION FOR THE SKYLIGHT AREA ADJUSTMENT. IF NOT, GO TO PART 2 OF 6. 1. IF PROPOSED SKYLIGHT AREA >= STANDARD SKYLIGHT AREA: SKYLIGHT • STANDARD SKYLIGHT AREA PROPOSED SKYLIGHT AREA - ADJUSTMENT FACTOR GO TO PART 6 TO CALCULATE ADJUSTED AREAS. EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page:6 of 38 'JOVERALL ENVELOPE METHOD Part 2 of 6 ENV -2 VE'RALL ENVELOPE METHOD DJECT NAME The Center At LA Quinta 'ERALL HEAT LOSS ASSEMBLY NAME (e.g. Wall -1, Floor -1) S Wall N Wall Window N Wall Window Roof W -wall Window Roof W -wall Window Roof W -wall Window Roof S Wall W -Wall Window B Part 2 of 6 ENV -2 IDATE CI IDI I E I IFI IGI IH PROPOSED AREA HEAT CAPACITY U- FACTOR TABLE VALUES UA (B X D) Y N 430 3.23 0.065 ❑X ❑ 28.1 270 3.231 0.065 ❑X ❑ 17.7 160 45.6 0.570 ❑ © 91.2 400 3.23 0.065 ❑X ❑ 26.2 320 16.0 0.570 ❑ ❑X 182.4 800 2.731 0.035 ❑X ❑ 27.8 230 3.23 0.065 © ❑ 15.1 170 60.5 0.570 ❑ ® 96.9 800 2.73 0.035 ®❑ 27.8 190 3.23 0.065 ®❑ 12.4 170 0.570 ❑ ❑X 96.9 700 2.73 0.035 0 ❑ 24.3 190 3.23 0.065 0 ❑ 12.4 170 0.570 ❑ ❑X 96.9 850 2.731 0.035 ❑X ❑ 29.5 720 3.23 0.065 ❑X ❑ 47.1 196 3.23 0.065 ❑X ❑ 12.8 200 0.570 ❑ ❑X 114.0 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ El El 1:1 El STANDARD AREA* (Adjusted) U -FACTOR UA (F X G) 430 0.084 36.1 2701 0.084 22.7 160 0.49C 78.4 400 0.084 33.6 320 0.490 156.8 8001 0.057 45.6 230 0.084 19.3 170 0.490 83.3 800 0.057 45.6 1901 0.084 16.0 170 0.490 83.3 700 0.057 39.9 190 0.084 16.0 170 0.49C 83.3 8501 0.057 48.5 720 0.084 60.5 196 0.084 16.5 200 0.490 98.0 If Window and/or Skylight Area Adjustment is RequiredColumn E shall be 960 This Page Total 983 use Adjusted Areas from Part 6 of 6. no greater than Column H 1 2,843 Building Total 1 3,227 EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Paoe:8 of 38 IOVE'RALL ENVELOPE METHOD Part 3 of 6 ENV -21 ECT NAME UCTION PROPOSED TABLE HEAT ASSEMBLY NAME (e.g. Wall -1, Floor -1) Wall Roof Wall 14 Wall Window Roof Wall 14 Wall Window Roof Wall Wall Window Roof Wall Wall Window Roof Wall Wall Window Roof Wall Wall Window Roof Wall 14 Wall Window oof AREA TF HEAT CAPACITY U- FACTOR VALUES GAIN O BXCxE Y N 1,400 55 3.23 0.065 11,913 ❑ 5,040 3,8001 55 1 2.73 0.035 a ❑ . 7,258 864 55 3.23 0.065 X❑ ❑ 3,110 434 55 3.23 0.065 ❑X ❑ 1,562 430 55 0.490 0.570 ❑ 1,600 13,480 1,600 55 2.73 0.035 ©❑ 1,497 3,056 324 55 3.23 0.065 0.490 ❑ 1,166 144 55 3.23 0.065 N. 0.084 518 180 55 0.084 0.570 0 ® 5,643 1,600 55 2.73 0.035 ®❑ 6,019 3,056 324 55 3.23 0.065 0.084 ❑ 1,166 144 55 3.23 0.065 ❑X ❑ 518 180 55 0.084 0.570 ❑ 270 5,643 1,920 55 2.73 0.035 ❑X ❑ 3,667 430155 55 3.23 0.065 ❑X ❑ 1,548 200 55 3.23 0.065 ❑X ❑ 720 230 55 0.057 0.570 ❑ ❑X 7,210 1,920 55 2.73 0.035 0 ❑ 3,667 430155, 3.23 0.065 ❑X ❑ 1,548 200 55 3.23 0.065 X ❑ 720 230 55 0.570 ❑ © 7,210 1,920 55 2.73 0.035 ❑X ❑ 3,667 4301 55 3.23 0.0651 1K 11 1,548 270 55 3.23 0.065 © ❑. 972 160 55 0.570 ❑ X 5,016 1,920 55 2.73 0.035 X❑ ❑ 3,667 430 55 3.23 0.065 [91 ❑ 1,548 270 55 3.23 0.065 ®❑ 972 160155 0.570 ❑ ❑X 5,016 1,920 55 2.73 0.035 ❑X ❑ 3,667 • ' If Window and/or Skylight Area Adjustment is Required 103,582 use Adjusted Areas from Part 6 of 6. Subtotal DATE STANDARD AREA* adjusted) U- FACTOR TF HEAT GAIN G Hxl 1,400 0.084 55 6,468 3,800 0.057 551 11,913 864 0.084 55 3,992 434 0.084 55 2,005 430 0.490 55 11,588 1,600 0.057 55 5,016 324 0.084 55 1,497 144 0.084 55 665 180 0.490 55 4,851 1,600 0.057 55 5,016 324 0.084 55 1,497 144 0.084 55 665 180 0.490 55 4,851 1,920 0.057 55 6,019 430 0.084 55 1,987 200 0.084 55 924 230 0.490 55 6,198 1,920 0.057 55 6,019 430 0.084 55 1,987 200 0.084 55 924 230 0.490 55 6,198 1,920 0.057 55 6,019 430 0.084 55 1,987 270 0.084 55 1,247 160 0.490 55 4,312 1,920 0.057 55 6,019 430 0.084 55 1,987 270 0.084 55 1,247 160 0.490 55 4,312 1,920 0.057 55 6,019 123,431 Subtotal EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Paae:9 of 38 1 JOVE'RALL. ENVELOPE METHOD Part 3 of 6 ENV -21 PROJECT NAME The Center At LA uinta DATE 2/25/2003 VERALL HEAT GAIN FROM CONDUCTION 0 oaa a o a a o 0 PROPOSED STANDARD TABLE HEAT HEAT GAIN ASSEMBLY NAME HEAT U- VALUES GAIN AREA• U- O (e.g. Wall -1, Floor -1) AREA TF CAPACITY FACTOR -71 N BxCxE (Adjusted) FACTOR TF GxHxl Wall 430 55 3.23 0.065 X❑ ❑ 1,548 430 0.084 55 1,987 Wall 270 55 1 3.23 0.065 ❑1 .9721 270 0.084 55 1 1,247 Window 160 55 0.570 ❑ ❑X 5,016 160 0.490 55 4,312 14 Wall 400 55 3.23 0.065 ©❑ 1,440 400 0.084 55 1,848 Window 320 55 0.570 ❑ © 10,032 320 0.490 55 8,624 Roof 800 55 2.73 0.035 ®❑ 1,5281 800 0.057 55 2,508 wall 230 55 3.23 0.065 X❑ ❑ 828 230 0.084 55 1 1,063 Window 170 55 0.570 ❑ ® 5,330 170 0.490 55 4,582 Roof 800 55 2.73 0.035 ® ❑ 1,528 800 0.057 55 2,508 wall 190 55 3.23 0.065 ®❑ 684 190 0.084 55 878 Window 170 55 0.570 El FX5,330 170 0.490 55 4,582 oof 7001 55 2.73 0.035 X❑ ❑ 1,337 700 0.057 55 2,194 -wall 190 55 3.23 0.065 ❑ 684 190 0.084 55 878 Window 170 55 0.570 ❑ F 5,330 170 0.490 55 4,582 Roof 850 55 2.73 0.035X❑ ❑ 1,623 850 0.057 55 2,665 Wall 720 55 3.23 0.065 0 ❑ 2,592 720 0.084 55 3,326 Wall 196 55 3.23 0.065 ❑ 706 196 0.084 55 906 Window 2001 55 0.570 ❑ ❑X 6,270 200 0.490 55 5,390 F-1 El D❑ ❑❑ ❑❑ ❑❑ ❑❑ . —If Window and/or Skylight Area Adjustment is Required 52,776 54,078 use Adjusted Areas from Part 6 of 6. Subtotal Subtotal EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page: 10 of 38 41 OVERALL ENVELOPE METHOD Part 4 of 6 ENV -2 ROJECT NAME DATE The Center At LA Quinta 1 2/25/2003 a o 0 0 0 0 o a o 54,328 • SUBTOTAL 89,173 SUBTOTAL EnergyPro 3.1 By EnergyPro User Number: 4984 Job Number: CL2 Page:11 of 38 PROPOSED STANDARD ASSEMBLY NAME e.g. Roof -1) AREA SF WEIGHTING FACTOR U- FACTOR Absorp HEAT GAIN i(BxCxDxExF) AREA• (ADJUSTED) U -Factor Absorp HEAT GAIN (CxDxHxlxJ) Roof 3,800 123 0.92 0.035 0.70 10,453 3,800 0.057 0.70 17,157 Roof 1.60d 1231 0.92 0.035 0.70 4.401 1.600 0.057 0.70 1 7,224 Roof 1,600 123 0.92 0.035 0.70 4,401 1,600 0.057 0.70 7,224 Roof 1,920 123 0.92 0.035 0.70 5,281 1,920 0.057 0.70 8,669 Roof 1.920 123 0.92 0.035 0.70 5,281 1,920 0.057 0.70 8,669 Roof 1.920 123 0.92 0.035 0.70 5,281 1,920 0.057 0.70 8,669 Roof 1,920 1231 0.92 0.035 0.70 5,281 1,920 0.057 0.70 8,669 Roof 1,920 123 0.92 0.035 0.70 5,281 1,920 0.057 0.70 8,669 Roof 800 123 0.92 0.035 0.70 2,201 800 0.057 0.70 3,612 Roof 800 123 0.92 0.035 0.70 2,201 800 0.057 0.70 3.612 Roof 700 1231 0.92 0.035 0.70 1,926 700 0.057 0.70 3161 Roof 85C 123 0.92 0.035 0.70 2,338 850 0.057 0.70 3,838 54,328 • SUBTOTAL 89,173 SUBTOTAL EnergyPro 3.1 By EnergyPro User Number: 4984 Job Number: CL2 Page:11 of 38 )VE'RALL ENVELOPE METHOD Part 5 of 6 ENV -2 NAME DATE The Center At LA Quinta --]-2/25/2003 1 HEAT GAIN FROM RADIATION FENESTRATION SURFACES 0 0 ©a000[7H]n n nnn PROPOSED STANDARD WINDOW/SKYLIGHT NAME e.g. Wind -1, Sky -1) ORIENT. WEIGHTING FACTOR AREA SF SHG OVERHANG HEATOGAIN (BxCxDxExH AREA* (ADJUSTED) ) RSHG (or SHGC") SF HEATOGAIN (BxJxICxL) H V HN OHF Window N 0.61 43 123 0.55 4.0 10.1 0.40 0.87 15,420 430 0.47 123 15,164 Window N 0.61 18 123 0.55 4.0 10.1 0.40 0.87 6.455 180 0.47 123 6,348 Window N 0.61 18 123 0.55 2.0 10.1 0.20 0.93 6,883 180 0.47 1231 6,348 Window N 0.61 23 123 8,795 2301 0.47 123 8,111 Window N 0.61 23 123 0.55 2.0 10.1 0.20 0.93 8,795 230 0.47 123 8,111 Window N 0.61 16 123 0.55 6.0 10.1 0.59 0.83 5,460 160 0.47 123 5,642 Window N 0.61 16C 123 0.55 6.0 10.1 0.59 0.83 5,460 160 0.47 123 5,642 Window N 0.61 16C 123 0.55 6.0 10.1 0.59 0.83 5,460 160 0.47 123 5,642 Window N 0.61 32C 123 0.55 6.0 10.1 0.59 0.83 10,921 3201 0.47 123 11,285 Window W 1.05 17 123 0.55 6.0 10.1 0.59 0.58 6,967 170 0.36 123 7,904 Window W 1.05 170 123 0.55 6.0 10.1 0.59 0.58 6,967 170 0.36 123 7,9041 Window W 1.05 171 123 0.55 6.0 110.1 0.59 0.58 6,967 170 0.36 123 7,904 Window W 1.05 200 123 8.197 200 0.36 123 9,299 " Only SHGC is 156,359 177,509 used for Skylights Part 3 Subtotal Part 3 Subtotal • Part 4 Subtotal 54,328 Part 4 Subtotal 89,173 `If Window and/or Skylight Area Adjustment is Required, use Column I must be less than column M Part 5 Subtotal 102,750 Part 5 Subtotal 105,302 Adjusted Areas from Part 6 of 6. 313,436 Total Heat Gain 371,984 EnergyPro 3.1 By EnergySoft User Number: 4964 Job Number: CL2 Page: 12 of 38 OVERALL ENVELOPE METHOD Part 6 of 6 ENV -2 ECT NAME The Center At LA Quinta DATE 2/25/2003 WINDOW AREA ADJUSTMENT CALCULATIONS ❑X CHECK IF NOT APPLICABLE (See ❑p Part 1 of 6.) ORIENTATION �B GROSS AREA SKYLIGHT AREA E❑ ❑F ❑G WINDOW ADJUST. FACTOR (From Part 1) ADJUSTED WINDOW AREA (D X E) ADJUSTED WALL AREA B --(F + C) WALL NAME (e.g. Wall -1, Wall -2) GROSS AREA DOOR AREA WINDOW AREA N E I S JW I ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Ell ❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ N/A TOTALS N/A ❑X CHECK IF NOT APPLICABLE (See Part 1 of 5.) ❑A ROOFNAME (e.g. Roof -1, Roof -2) TOTALS K E EnergyPro 3.1 By EnergySoff User Number 4984 Job Number: CL2 Page: 13 of 38 SKYLIGHT ADJUST. FACTOR (From Part 1) ADJUSTED SKYLIGHT AREA (C X D) ADJUSTED ROOF AREA (B - E) GROSS AREA SKYLIGHT AREA N/A EnergyPro 3.1 By EnergySoff User Number 4984 Job Number: CL2 Page: 13 of 38 ENVELOPE MANDATORY MEASURES ENV -MM jPROJECT NAME DATE The Center At LA Quinta 1 2/25/2003 DESCRIPTION Designer Enforcement ❑X § 118(a) Installed Insulating Material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20, Chapter 4, Article 3. X❑ § 118(c) All Insulating Materials shall be installed in compliance with the flame'spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. X❑ . § 117(a) All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. FX] § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). X❑ § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards. Manufactured fenestration products must be.labeled for U -value according to NFRC procedures. X❑ §118(e) Demising Walls in Nonresidential Buildings: The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value of no less than R-11 between framing members. EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page: 14 of 38 CERTIFICATE OF COMPLIANCE Part 1 of 2 MECH-1 NAME The Center At LA Quinta ADDRESS LA Quinta 1PAL DESIGNER - MECHANICAL TANDA GROUP, INC. MENTATION AUTHOR TORABIAN & ASSOCIATES DATE 2/25/2003 TELEPHONE Building Permit # 661-252-0400 TELEPHONE Checked by/Date (661) 252-0400 Enforcement Agency Use GENERAL INFORMATION DATE OF PLANS BUILDING CONDITIONED FLOOR AREA CLIMATE ZONE 19,750Sq.Ft. 15 BUILDING TYPE ® NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION ❑ EXISTING + ADDITION METHOD OF MECHANICAL ® PRESCRIPTIVE ❑ PERFORMANCE COMPLIANCE PROOF OF ENVELOPE COMPLIANCE ❑ PREVIOUS ENVELOPE PERMIT ❑ ENVELOPE COMPLIANCE ATTACHED STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to buildi Q ;rejkquirements. The documentation preparer hereby certifies that the documentation is accurate an pIOTHUR DOCUMENTATION AUTHOR SIGNATURE MOORE DATE Arthur L. Moore The Principal Mechanical Designer hereby certifies that the proposed building desige' RM of construction `s documents is consistent with the other compliance forms and worksheets, with the sp any other \ calculations submitted with this permit application. The proposed building has been desig a mechanical requirements contained in Sections 110 through115, 120 through 124, 140 through 142, 144 and 145. Please check one: ❑ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, or mechanical engineer or I am a licensed architect. ❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. ❑ I affirm that I am eligible under the exemption to Division 3 of the Busi S s Code to sign this document because it pertains to a structure or type of work described pursuan iness sions Code sections 5537, 5538, and 6737.1. W ARiHIJ F YMAN a PRINCIPAL MECHANICAL DESIGNER - NAME SI A ATE 185 LIC. # I TANDA GROUP INC. �- 2S 6,9 M19/F,6— MECHANICAL MANDATORY MEASURES 14 Me Q Indicate location on plans of Note Block for Mandatory Measures I INSTRUCTIONS TO APPLICANT For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the Nonresidential Manual published by the California Energy Commission. MECH-1: Required on plans for all submittals. Parts 2 may be incorporated in schedules on plans. MECH-2: Required for all submittals, but may be incorporated in schedules on plans. MECH-3: Required for all submittals unless required outdoor ventilation rates and airflows are shown on plans per Section 4.3.4. MECH-4: Required for Prescriptive submittals. MECH-5: Optional. Performance use only for mechanical distribution summary. EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page:15 of 38 CERTIFICATE OF COMPLIANCE Part 2 of 2 MECH-1 {PROJECT NAME DATE The Center At LA Quinta 2/25/2003 • r SYSTEM NAME TIME CONTROL SETBACK CONTROL ISOLATION ZONES HEAT PUMP THERMOSTAT? . ELECTRIC HEAT? FAN CONTROL VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/COOL? HEATING SUPPLY RESET COOLING SUPPLY RESET HEAT REJECTION CONTROL VENTILATION OUTDOOR DAMPER CONTROL ECONOMIZER TYPE DESIGN O.A. CFM MECH-3 COLUMN I HEATING EQUIPMENT TYPE HEATING EQUIPMENT EFFICIENCY COOLING EQUIPMENT TYPE COOLING EQUIPMENT EFFICIENCY MAKE AND MODEL NUMBER PIPE INSULATION REQUIRED? PIPE/DUCT INSULATION PROTECTED? HEATING DUCT LOCATION R -VALUE COOLING DUCT LOCATION R -VALUE VERIFIED SEALED DUCTS IN CEILING/ROOF SPACE MECHANICAL SYSTEMS DHW Heater 1.1 RTU -12 I RTU -11 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a Electric Res 99% n/a n/a AO SMITH ELJF-06' Yes Yes n/a n/a n/a n/a n/a Programmable Switch Heating & Cooling Required n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto Diff. Enth Non-Inte 950 cfm Gas Furnace 82% AFUE Packaged DX 11.1 EER CARRIER 48HJD007 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No Programmable Switch Heating & Cooling Require n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto Diff. Entli Non-Inte 400 cfm Gas Furnace 82% AFUE Packaged DX 11.1 EER CARRIER 48HJD008 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No NOTE TO FIELD CODE TABLES: Enter code from table below into columns above. HEAT PUMP THERMOSTAT? TIME CONTROL SETBACK CTRL. ISOLATION ZONES FAN CONTROL ELECTRIC HEAT? S: Prog. Switch O: Occupancy Sensor M: Manual Timer H: Heating C: Cooling B: Both Enter Number of Isolation Zones. I: Inlet Vanes P: Variable Pitch V: VFD O: Other C: Curve VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/ COOL? Y: Yes HEAT AND COOL SUPPLY RESET? N: No VENTILATION I OUTDOOR DAMPERI ECONOMIZER O.A. CFM HIGH EFFICIENCY? I B: Air Balance I A: Auto A: Air jEnter Outdoor Air PIPE INSULATION REQUIRED? C: Outside Air Cert. G: Gravity W: Water CFM. M: Out. Air Measure N: Not Required Note: This shall be PIPE/DUCT INSULATION PROTECTED? D: Demand Control EC: Economizer less than Col. H on AI SEALED DUCTS IN CEILING/ROOF SPACE N: Natural Control See Section MECH-3. EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CI -2 Page: 16 of 38 11 CERTIFICATE OF COMPLIANCE Part 2 of 2 MECH-1 PROJECT NAME DATE The Center At LA Quinta 2/25/2003 SYSTEM FEATURES SYSTEM NAME TIME CONTROL SETBACK CONTROL ISOLATION ZONES HEAT PUMP THERMOSTAT? ELECTRIC HEAT? FAN CONTROL VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/COOL? HEATING SUPPLY RESET COOLING SUPPLY RESET HEAT REJECTION CONTROL VENTILATION OUTDOOR DAMPER CONTROL ECONOMIZER TYPE DESIGN O.A. CFM MECH-3, COLUMN I HEATING EQUIPMENT TYPE HEATING EQUIPMENT EFFICIENCY COOLING EQUIPMENT TYPE COOLING EQUIPMENT EFFICIENCY MAKE AND MODEL NUMBER PIPE INSULATION REQUIRED? PIPEIDUCT INSULATION PROTECTED? HEATING DUCT LOCATION R -VALUE COOLING DUCT LOCATIO R -VALUE VERIFIED SEALED DUCTS IN CEILING/ROOF SPACE MECHANICAL SYSTEMS RTU -10 I I RTU -9 I RTU -8 Programmable Switch. Heating & Cooling Required n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto Diff. Enth Non-Inte 400 cfm Gas Furnace 82% AFUE Packaged DX 11.1 EER CARRIER 48HJD008 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No Programmable Switch Heating & Cooling Required n/a n/a n/a . Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto Diff. Enth Non-Inte 500 cfm Gas Furnace 82% AFUE Packaged DX 11.1 EER CARRIER 48HJD012 Yes . Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No Programmable Switch Heating & Cooling Require n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto Diff. Enth Non-Inte 500 cfm Gas Furnace 82% AFUE Packaged DX 11.1 EER CARRIER 48HJD012 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No NOTE TO FIELD CODE TABLES: Enter code from table below into columns above. HEAT PUMP THERMOSTAT? Y: Yes N: NoVENTILATION TIME CONTROL SETBACK CTRL. ISOLATION ZONES FAN CONTROL ELECTRIC HEAT? S: Prog. Switch O: Occupancy Sensor M: Manual Timer H: Heating C: Cooling B: Both Enter Number of Isolation Zones. I: Inlet Vanes P: Variable Pitch V: VFD O: Other C: Curve VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT / COOL? HEAT AND COOL SUPPLY RESET? OUTDOOR DAMPER ECONOMIZER O.A. CFM HIGH EFFICIENCY? B: Air Balance C: Outside Air Cert. M: Out. Air Measure D: Demand Control N: Natural A: Auto G: Gravity A: Air W: Water N: Not Required EC: Economizer Control See Section 144e3 Enter Outdoor Air CFM. Note: This shall be less than Col. H on MECH-3. PIPE INSULATION REQUIRED? PIPE/DUCT INSULATION PROTECTED? SEALED DUCTS IN CEILING/ROOF SPACE ')TFS Tn FIFI Il - Fnr Rialrlinn nannrfmanf [lea nnhi EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CI -2 Page: 17 of 38 C. CERTIFICATE OF COMPLIANCE Part 2 of 2 MECH-1 NAME The Center At LA Quinta SYSTEM NAME TIME CONTROL SETBACK CONTROL ISOLATION ZONES HEAT PUMP THERMOSTAT? ELECTRIC HEAT? FAN CONTROL VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/COOL? HEATING SUPPLY RESET COOLING SUPPLY RESET HEAT REJECTION CONTROL VENTILATION OUTDOOR DAMPER CONTROL ECONOMIZER TYPE DESIGN O.A. CFM MECH-3, COLUMN I HEATING EQUIPMENT TYPE HEATING EQUIPMENT EFFICIENCY COOLING EQUIPMENT TYPE COOLING EQUIPMENT EFFICIENCY MAKE AND MODEL NUMBER PIPE INSULATION REQUIRED? PIPE/DUCT INSULATION PROTECTED? HEATING DUCT LOCATION R -VALUE COOLING DUCT LOCATIO R -VALUE VERIFIED SEALED DUCTS IN CEILING/ROOF SPACE RTU -7 Programmable Switch Heating & Cooling Required n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto Diff. Enth Non-Inte 500 cfm Gas Furnace 82% AFUE Packaged DX 11.1 EER CARRIER 48HJD012 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No RTU -6 Programmable Switch Heating & Cooling Required n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto Diff. Enth Non-Inte 500 cfm Gas Furnace 82% AFUE Packaged DX 11.1 EER CARRIER 48HJD012 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No DATE 2/25/2003 RTU -5 Programmable Switch Heating & Cooling Required n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto Diff. Enth Non-Inte 500 cfm Gas Furnace 82% AFUE Packaged DX 11.1 EER CARRIER 48HJD012 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No NOTE TO FIELD CODE TABLES: Enter code from table below into columns above. HEAT PUMP THERMOSTAT? TIME CONTROL SETBACK CTRL. ISOLATION ZONES FAN CONTROL ELECTRIC HEAT? S: Prog. Switch H: Heating Enter Number of I: Inlet Vanes' O: Occupancy C: Cooling Isolation Zones. P: Variable Pitch VAV MINIMUM POSITION CONTROL? Sensor B: Both V: VFD SIMULTANEOUS HEAT/ COOL? Y: Yes M: Manual Timer O: Other C: Curve N. No Mr -A 1 Ar4U k;UUL 5UrrLY HL5L 1 Y HIGH EFFICIENCY? VENTILATION OUTDOOR DAMPER ECONOMIZER O.A. CFM B: Air Balance C: Outside Air Cert. M: Out. Air Measure D: Demand Control N: Natural A: Auto G: Gravity A: Air W: Water N: Not Required EC: Economizer Control See Section IAA1-1.2 Enter Outdoor Air CFM. Note: This shall be less than Col. H on MECH-3. PIPE INSULATION REQUIRED? PIPE/DUCT INSULATION PROTECTED? SEALED DUCTS IN CEILING/ROOF SPACE EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page: 18 of 38 C1 i CERTIFICATE OF COMPLIANCE Part 2 of 2 MECH-1 PROJECT NAME DATE The Center At LA Quinta 2/25/2003 SYSTEM FEATURES SYSTEM NAME TIME CONTROL SETBACK CONTROL ISOLATION ZONES HEAT PUMP THERMOSTAT? ELECTRIC HEAT? FAN CONTROL VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/COOL? HEATING SUPPLY RESET COOLING. SUPPLY RESET HEAT REJECTION CONTROL VENTILATION OUTDOOR DAMPER CONTROL ECONOMIZER TYPE DESIGN O.A. CFM MECH-3, COLUMN I HEATING EQUIPMENT TYPE HEATING EQUIPMENT EFFICIENCY COOLING EQUIPMENT TYPE COOLING EQUIPMENT EFFICIENCY MAKE AND MODEL NUMBER PIPE INSULATION REQUIRED? PIPEIDUCT INSULATION PROTECTED? HEATING DUCT LOCATION R -VALUE COOLING DUCT LOCATIO R -VALUE VERIFIED SEALED DUCTS IN CEILING/ROOF SPACE MECHANICAL SYSTEMS RTU -4 RTU -3 I I RTU -2 Programmable Switch Heating & Cooling Required n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto Diff. Enth Non-Inte 200 cfm Gas Furnace 82% AFUE Packaged DX 11.1 EER CARRIER 48HJD007 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No Programmable Switch Heating & Cooling Required n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto No Economizer 200 cfm Gas Furnace 83% AFUE Packaged DX 13.0 SEER / 11.1 EER CARRIER 48HJD006 Yes Yes Ducts in Attic 4.2 Ducts in Attic 1 4.2 No Programmable Switch Heating & Cooling Require n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto No Economizer 175 cfm Gas Furnace 83% AFUE Packaged DX 13.0 SEER / 11.1 EER CARRIER 48HJD006 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No NOTE TO FIELD CODE TABLES: Enter code from table below into columns above. HEAT PUMP THERMOSTAT? TIME CONTROL SETBACK CTRL. ISOLATION ZONES FAN CONTROL ELECTRIC HEAT? S: Prog. Switch H: Heating Enter Number of I: Inlet Vanes O: Occupancy C: Cooling Isolation Zones. P: Variable Pitch VAV MINIMUM POSITION CONTROL? Sensor B: Both V: VFD SIMULTANEOUS HEAT / COOL? Y: Yes M: Manual Timer O: Other C: Curve N. No PIPE INSULATION REQUIRED? PIPEIDUCT INSULATION PROTECTED? SEALED DUCTS IN CEILING/ROOF SPA VENTILATION OUTDOOR DAMPER ECONOMIZER O.A. CFM B: Air Balance A: Auto A: Air Enter Outdoor Air C: Outside Air Cert. G: Gravity W: Water CFM. M: Out. Air Measure N: Not Required Note: This shall be no D: Demand Control EC: Economizer less than Col. H on N: Natural Control See Section MECH-3. EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CI -2 Paoe:19 of 38 1 J CERTIFICATE OF COMPLIANCE Part 2 of 2 MECH A rPROJECT NAME DATE The Center At LA Quinta 2/25/2003 SYSTEM FEATURES 0 SYSTEM NAME TIME CONTROL SETBACK CONTROL ISOLATION ZONES HEAT PUMP THERMOSTAT? ELECTRIC HEAT? FAN CONTROL VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/COOL? HEATING SUPPLY RESET COOLING SUPPLY RESET HEAT REJECTION CONTROL VENTILATION OUTDOOR DAMPER CONTROL ECONOMIZER TYPE DESIGN O.A. CFM MECH-3 COLUMN I HEATING EQUIPMENT TYPE HEATING EQUIPMENT EFFICIENCY COOLING EQUIPMENT TYPE COOLING EQUIPMENT EFFICIENCY MAKE AND MODEL NUMBER PIPE INSULATION REQUIRED? PIPE/DUCT INSULATION PROTECTED? HEATING DUCT LOCATION R -VALUE COOLING DUCT LOCATIO R -VALUE VERIFIED SEALED DUCTS IN CEILING/ROOF SPACE MECHANICAL SYSTEMS RTU -1 Programmable Switch Heating & Cooling Required n/a n/a n/a Constant Volume Yes Yes Constant Tem Constant Tem n/a Air Balance Auto No Economizer 212 cfm Gas Fumace 83% AFUE Packaged DX 13.0 SEER / 11.1 EER CARRIER 48HJD006 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No NOTE TO FIELD CODE TABLES: Enter code from table below into columns above. HEAT PUMP THERMOSTAT? Y: Yes N: No TIME CONTROL SETBACK CTRL. ISOLATION ZONES FAN CONTROL ELECTRIC HEAT? S: Prog. Switch O: Occupancy Sensor M: Manual Timer H: Heating C: Cooling B: Both Enter Number of Isolation Zones. I: Inlet Vanes P: Variable Pitch V: VFD O: Other C: Curve VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/ COOL? HEAT AND COOL SUPPLY RESET? VENTILATION OUTDOOR DAMPER ECONOMIZER O.A. CFM HIGH EFFICIENCY? B: Air Balance C: Outside Air Cert. M: Out. Air Measure D: Demand Control N: Natural A: Auto G: Gravity A: Air W: Water N: Not Required EC: Economizer Control See Section Enter Outdoor Air CFM. Note: This shall be no less than Col. H on MECH-3. PIPE INSULATION REOUIRED? PIPE/DUCT INSULATION PROTECTED? SEALED DUCTS IN CEILING/ROOF SPACE EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CI -2 Page:20 of 38 EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page:21 of 38 1 IM5 . CHANICAL EQUIPMENT SUMMARY Part 1 of 2 MECH-2 PROJECT NAME I The Center At LA Quinta DATE 2/25/2003 CHILLER AND TOWER SUMMARY Efficiency Tons PUMPS Equipment Name Equipment Type Oty. Tot.Motor Oty GPM BHP Eff. Drive Eff. Pump Control DHW BOILER MM RY Energy Factor or Recovery Efficiency Standby Loss or Pilot TANK INSUL. System Name System Type Distribution Type OtyInput Rated (Gals.) Vol. Ext. R -Val. O SMITH ELJF-06' Storage Elec. Standard 13 5,120 6 0.95 n/a n/a CENTRAL SYSTEM RATINGS HEATING COOLING System Name System Type Oty. Output Aux. kW Eff. Output Sensible Eff iciency Economizer Type CARRIER 48HJD007 Packaged DX 4 41,000 0.0 82%AFUE 77,300 55,30 11.1 EER Diff. Enth (Non-Integ) CARRI8HJD008 Packaged DX 2 73,800 0.0 82%AFUE 92,900 67,20 11.1 EER Diff. Enth (Non-Integ) CARRIER 48HJD012 Packaged DX 5 98,400 0.0 82%AFUE 121,900 82,00011.1 EER Diff. Enth (Non-Integ) CARRIER 48HJD006 Packaged DX 3 58,000 0.0 83%AFUE 62,500 43,80013.0 SEER / 11.1 EER No Economizer EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page:21 of 38 1 jMtCHANICAL EQUIPMENT SUMMARY Part 2 of 2 MECH-2 1 PROJECT NAME The Center At LA Quinta. DATE.2/25/2003 ZONE TERMINAL SUMMARY Tenant"10" Tenant "9" "15" e e e VAV TERMINAL BOX System Type O. Min. CFM Ratio Reheat Coil Type DeltaT VAV Box 3 100% None 0 VAV Box 1 100% None 0 VAV Box 1 100% None 0 VAV Box 1 100% None 0 VAV.Box 1 100% None 0 VAV Box 1 100% None 0 VAV Box 1 100% None 0 VAV Box 1 100% None 0 VAV Box 1 100% None 0 VAV Box 1 100% None 0 VAV Box 1 100% None 0 VAV Box 1 100% None 0 none n/a none none n/a none none n/a TERMINAL FAN EXHAUSTFAN BASEBOARD CFM • BHP Motor Eff. Drive Eff. Type Output none oty. CFM BHP none n/a none 1 200 0.00 none n/a none 1 50 0.00 none n/a none 1 109 0.00 none n/a none 1 50 0.00 none n/a none 1 10 0.00 none. n/a none 1 500 0.00 none n/a none none n/a none none n/a none none n/a none none n/a none none n/a EXHAUST FAIT-- EXHAUSTFAN Room Name City.CFM BHP Motor Eff. Drive Eff. Room Name oty. CFM BHP Motor Eff. Drive Eff. Tenant "12" 1 200 0.00 40.00/ 97.0% Tenant "9" 1 50 0.00 40.0°/ 97.0% Tenant "11" 1 109 0.00 1 40.00/ 97.0% il Tenant "8" 1 50 0.00 40.0°/ 97.0% Tenant "10" 1 10 0.00 40.0°/ 97.0% Tenant "7" 1 500 0.00 40.00/ 97.09/6 EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page:22 of 38 1 ECHANICAL EQUIPMENT SUMMARY Part 2 of 2 MECH-2 1 PROJECT NAME The Center At LA Quinta DATE 2/25 ZONE TERMINAL SUMMARY in. CFM EXHAU Motor Drive CFM BHP Eff. Eff. BASEBOARD Type Output EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 . Page:23 of 38 Room Name ()ty. CFM BHP Motor Eff. Drive Eff. Room Name Qty. CFM BHP Motor Eff. Drive Eff. Tenant "6" 1 500 0.00 40.0°/ 97.0% Tenant -3 1 100 0.00 40.00/ 97.0% Tenant "5" 1 500 0.00 40.00/ 97.0% Tenant 2 11 1 100 0.00 40.00/ 97.0% Tenant -4 1 1 10 0.00 40.0°/ 97.0% Tenant "1" 1 10 0.25 77.0°/ 97.0% EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 . Page:23 of 38 'MECHANICAL VENTILATION MECH-3 NAME The Center At LA Quinta DATE 2/25/2003 MECHANICAL VENTILATION A a© a a F o a o a a AREA BASIS DESIGN OUTDOOF AIR CFM COND. AREA (SF) CFM PER SF MIN. CFM (B x C) 3,800 0.25 950 950 950 1,600 0.25 400 100% 400 1,600 0.25 400 400 400 100°/ 1,920 0.25 480 4801 1,920 0.25 480 480 500 1,920 0.25 480 100% 480 1,920 0.25 480 480 500 100% 1,920 0.25 480 480 800 0.25 200 4801 500 800 0.25 200 100°/ 480 700 0.25 175 200 200 100% 850 0.25 212 200 200 100% 200 200 175 175 100% 1751 OCCUPANCY BASIS NO. . CFM MIN. OF PER CFM PEOPLE PERSON (ExF) Total Total Total Total Total Total Total Total Total Total Total Total REQ'D O.A. (MAX OF D OR G) DESIGN OUTDOOF AIR CFM VAV MIN. RATIO TRANS. FER AIR 950 950 100% 950 950 400 400 100% 400 400 400 400 100°/ 400 400 4801 500 100% 480 500 480 500 100% 480 500 480 500 100% 480 500 480 500 100% 4801 500 480 500 100°/ 480 500 200 200 100% 2001 200 200 200 100% 200 200 175 175 100% 1751 175 212 212 100% 212 212 C Minimum Ventilation Rate per Section 121, Table 1-F. E Based on Expected Number of Occupants or at least 50% of Chapter 10 1997 UBC Occupant Density. I Must be greater than or equal to H, or use Transfer Air. Design Outdoor Air includes ventilation from Supply Air System & Room Exhaust Fans. K Must be greater than or equal to (H minus 1), and, for VAV, greater than or equal to (H -J). I EnergyPro 3.1 By EnergySoft User Number: 4984 Job Number: CL2 Page:24 of 38 1 IF • MECHANICAL SIZING AND FAN POWER MECH-4 PROJECT NAME DATE The Center At LA Quinta 2/25/2003 SYSTEM NAME RTU -12 FLOOR 3,800 NOTE: Provide one copy of this form for each mechanical system when using the Prescriptive Approach. SIZING AND EQUIPMENT SELECTION 1. DESIGN CONDITIONS: COOLING HEATING - OUTDOOR DRY BULB TEMPERATURE (APPENDIX C) 112 OF 2 OF - OUTDOOR WET BULB TEMPERATURE (APPENDIX C) 78 OF - INDOOR, DRY BULB TEMPERATURE SEE ASHRAE CHAPTER 8, 1993 74 OF 70 OF OR APPENDIX B 2. SIZING: - DESIGN OUTDOOR AIR - ROOM LOADS - RETURN VENTED LIGHTING - RETURN AIR DUCTS - RETURN FAN - SUPPLY FAN - SUPPLY DUCTS 950 CFM (MECH 3; COLUMN 1) TOTALS SAFETY/ WARM-UP FACTOR MAXIMUM ADJUSTED LOAD (TOTALS FROM ABOVE x SAFETY / WARM-UP FACTOR) 3. SELECTION: INSTALLED EQUIPMENT CAPACITY (ADJUSTED FOR DESIGN CONDITIONS) IF INSTALLED CAPACITY EXCEEDS MAXIMUM ADJUSTED LOAD, EXPLAIN _ FA FAN DESCRIPTION Supply Fan Exhaust Fan a DESIGN BRAKE HP 2.400 0.000 a o EFFICIENCY MOTOR DRIVE 84.0% 97.0% 40.0% 97.0% NOTE: Include only fan systems exceeding 25 HP (see Section 144). Total Fan System Power Demand may not exceed 0.8 Watts/cfm for constant volume systems or 1.25 Watts/cfm for VAV systems. 0 NUMBER OF FANS 3 1 37,824 116,351 0 5,818 0 0 5,818 165,821 1.21 200,643 177,309 Btu / Hr a PEAK WATTS BxEx746/(CXD 6,592 44,375 58,128 n/ 2,90 2,90 108,315 1.43 154,891 123,000 Btu / Hr a CFM (Supply Fans) 6,300 TOTALS 592 6 300 TOTAL FAN SYSTEM POWER DEMAND 1 1.046] WATTS / CFM Col. F / Col. G EnergyPro 3.1 By EnergySoft User Number 4984 Job Number: CL2 Paae:25 of 38 1 CHANICAL SIZING AND FAN POWER MECH-4 PROJECT NAME DATE The Center At LA Quinta 2/25/2003 SYSTEM NAME RTU -11 FLOOR AREA 600 s NOTE: Provide one copy of this form for each mechanical system when using the Prescriptive Approach. SIZING AND EQUIPMENT SELECTION 1. DESIGN CONDITIONS: COOLING HEATING - OUTDOOR DRY BULB TEMPERATURE (APPENDIX C) 1 1 °F 2 OF - OUTDOOR WET BULB TEMPERATURE (APPENDIX C) 7 of - INDOOR, DRY BULB TEMPERATURE SEE ASHRAE CHAPTER 8, 1993 74 °F 70 °F OR APPENDIX B 2. SIZING: - DESIGN OUTDOOR AIR 4OO CFM (MECH 3; COLUMN 1) 15,980 18,704 - ROOM LOADS 47,260 24,754 -.RETURN VENTED LIGHTING 0 n/ - RETURN AIR DUCTS 2,363 1,23 - RETURN FAN 0 - SUPPLY FAN 0 -SUPPLY DUCTS 2,3631 1 1,23 TOTALS 67,972 45,933 SAFETY/ WARM-UP FACTOR 1.21 1.43 MAXIMUM ADJUSTED LOAD (TOTALS FROM ABOVE x SAFETY / WARM-UP FACTOR) $2,246 65,685 3. SELECTION: INSTALLED EQUIPMENT CAPACITY (ADJUSTED FOR DESIGN CONDITIONS) 63,143 1 73,800 Btu / Hr Btu / Hr IF INSTALLED CAPACITY EXCEEDS MAXIMUM ADJUSTED LOAD, EXPLAIN FA FAN DESCRIPTION Supply Fan Exhaust Fan DESIGN BRAKE HP 2.900 0.000 FRI EFFICIENCY MOTOR DRIVE 84.0% 97.0% 40.0% 97.0% NOTE: Include only fan systems exceeding 25 HP (see Section 144). Total Fan System Power Demand may not exceed 0.8 Watts/cfm for constant volume systems or 1.25 Watts/cfm for VAV systems. NUMBER OF FANS 1 1 a PEAK WATTS BxEx746/(CXD 2,655 0 CFM (Supply Fans) 3,000 TOTALS 2 655 3 000 TOTAL FAN SYSTEM POWER DEMAND 0.885 WATTS / CFM Col. F / Col. G EnergyPro 3.1 By EnergySoft User Number 4984 Job Number: CL2 Pape:26 of 38 1 'MECHANICAL SIZING AND FAN POWER MECH-4 PROJECT NAME DATE The Center At LA Quinta 2/25/2003 SYSTEM NAME FLOOR AREA RTU -10 1,600 NOTE: Provide one copy of this form for each mechanical system when using the Prescriptive Approach. SIZING AND EQUIPMENT SELECTION 1. DESIGN CONDITIONS: COOLING HEATING - OUTDOOR DRY BULB TEMPERATURE (APPENDIX C) 112 OF 2 OF - OUTDOOR WET BULB TEMPERATURE (APPENDIX C) 7 of - INDOOR, DRY BULB TEMPERATURE SEE ASHRAE CHAPTER 8, 1993 74 °F 7O °F OR APPENDIX B 2. SIZING: - DESIGN OUTDOOR AIR 4OO CFM (MECH 3; COLUMN 1) 15,980 18,704 - ROOM LOADS 47,276 24,754 - RETURN VENTED LIGHTING 0 n/ - RETURN AIR DUCTS 2,364 1,23 - RETURN FAN 0 - SUPPLY FAN 0 • - SUPPLY DUCTS 2,364 1,23 TOTALS 67,989 45,933 SAFETY/ WARM-UP FACTOR 1.21 1.43 MAXIMUM ADJUSTED LOAD (TOTALS FROM ABOVE x SAFETY / WARM-UP FACTOR) $2,26 65,685 3. SELECTION:a INSTALLED EQUIPMENT CAPACITY (ADJUSTED FOR DESIGN CONDITIONS) 63,143 1 73,$00 Btu / Hr Btu / Hr IF INSTALLED CAPACITY EXCEEDS MAXIMUM ADJUSTED LOAD, EXPLAIN 0 FAN DESCRIPTION Supply Fan. Exhaust Fan a DESIGN BRAKE HP 2.900 0.000 © o EFFICIENCY MOTOR DRIVE 84.0% 97.0% 40.0% 97.0% NOTE: Include only fan systems exceeding 25 HP (see Section 144). Total Fan System Power Demand may not exceed 0.8 Watts/cfm for constant volume systems or 1.25 Watts/cfm for VAV systems. 0 NUMBER OF FANS 1 1 a PEAK WATTS BxEx746/(CXD 2,655 a CFM (Supply Fans) 3,000 TOTALS 2 655 3 000 TOTAL FAN SYSTEM POWER DEMAND WATTS/CFM Col. F / Col. G 1. EnergyPro 3.1 By EnergySoft User Number 4984 Job Number: CL2 Paae:27 of 38 1 MECHANICAL SIZING AND FAN POWER MECH-4 PROJECT NAME DATE The Center At LA Quinta 2/25/2003 SYSTEM NAME FLOOR AREA RTU -9 ' 1,920 NOTE: Provide one copy of this form for each mechanical system when using the Prescriptive Approach. SIZING AND EQUIPMENT SELECTION 1. DESIGN CONDITIONS: COOLING HEATING - OUTDOOR DRY BULB TEMPERATURE (APPENDIX C) 1 1 °F 2 OF - OUTDOOR WET BULB TEMPERATURE (APPENDIX C) 78 OF - INDOOR, DRY BULB TEMPERATURE SEE ASHRAE CHAPTER 8, 1993 74 °F 70 °F OR APPENDIX B 2. SIZING: - DESIGN OUTDOOR AIR - ROOM LOADS - RETURN VENTED LIGHTING - RETURN AIR DUCTS - RETURN FAN - SUPPLY FAN -SUPPLY DUCTS SAFETY/ WARM-UP FACTOR J 5OO CFM (MECH 3; COLUMN 1) 19,920 57,420 0 2,871 0 0 2,871 TOTALS $3088 1.21 MAXIMUM ADJUSTED LOAD. (TOTALS FROM ABOVE x SAFETY / WARM-UP FACTOR) 1 00,53 3. SELECTION: INSTALLED EQUIPMENT CAPACITY (ADJUSTED FOR DESIGN CONDITIONS) IF INSTALLED CAPACITY EXCEEDS MAXIMUM ADJUSTED LOAD, EXPLAIN 0 FAN DESCRIPTION Supply Fan Exhaust Fan a DESIGN BRAKE HP 2.900 0.000 a a EFFICIENCY MOTOR DRIVE 84.0% 97.0% 40.0% 97.0% 23,362 28,651 n/ 1,43 1,43 54,878 1.43 78,476 85,78 98,400 Btu / Hr Btu / Hr 0 0 0 NUMBER OF FANS 1 1 CFM (Supply Fans) 3,200 TOTALS 2 655 3 200 NOTE: Include only fan systems exceeding 25 HP (see Section 144). Total Fan System Power Demand may not exceed 0.8 Watts/cfm for TOTAL FAN SYSTEM constant volume systems or 1.25 Watts/cfm for VAV systems. POWER DEMAND 0.830 WATTS / CFM Col. F / Col. G EnergyPro 3.1 By EnergySoft User Number 4984 Job Number: CL2 Page:28 of 38