0302-011 (RC) Title 24
I TITLE 24 REPORT Title 24 Report for: La Quinta Grill Offices 78-034 Calle Barcelona La Quinta, CA Project Designer: Report Prepared By: Joan D. Hacker Insu-form, Inc. 68-255 Corta Road Cathedral City, CA 92234 (760) 324-2046 CITY OF LA QUINTA Job Number: BUILDING & SAFETY DEPT. APPROVED FOR CONSTRt :s ZWO Date: W ICA 5/22/20036307- a �-/& The"EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2001 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC (415) 883-5900. EnergyPro 3.1 By EnergySoft Job Number. User Number: 2655 1 TABLE OF CONTENTS Cover Page 1 Table of Contents 2 Form ENV -1 Certificate of Compliance 3 Form ENV -2 Overall Envelope Method 5 Form ENV -MM Envelope Mandatory Measures 11 Form LTG -1 Certificate of Compliance 12 Form LTG -2 Lighting Compliance Summary 15 Form LTG -4 Tailored LPD Summary and Worksheet 16 Form LTG -5 Room Cavity Ratio Worksheet 17 Form LTG -MM Lighting Mandatory Measures 18 Form MECH-1 Certificate of Compliance 19 Form MECH-2 Mechanical Equipment Summary 21 Form MECH-3 Mechanical Ventilation 23 Form MECH-4 Mechanical Sizing and Fan Power 24 Form MECH-MM Mechanical Mandatory Measures 26 Room Heating Peak Loads 28 Room Cooling Peak Loads 30 EnergyPro 3.1 By EnergySoft Job Number. User Number. 2655 CERTIFICATE OF COMPLIANCE Part 1 of 2 ENV -1 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 PROJECT ADDRESS 78-034 Calle Barcelona La Quinta PRINCIPAL DESIGNER - ENVELOPE TELEPHONE Building Permit # DOCUMENTATION AUTHOR TELEPHONE Checked by/Date Insu-form, Inc. 760 324-2046 1 Enforcement Agency Use GENERAL INFORMATION DATE OF PLANS BUILDING CONDITIONED FLOOR AREA CLIMATE ZONE 5,954 sq.Ft. 15 BUILDING TYPE NONRESIDENTIAL HIGH RISE RESIDENTIAL HOTELIMOTEL GUEST ROOM PHASE OF CONSTRUCTION NEW CONSTRUCTION ADDITION E] ALTERATION EXISTING + ADDITION METHOD OF ENVELOPE COMPONENT ® OVERALL ENVELOPE PERFORMANCE COMPLIANCE STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building envelope requirements. The documentation preparer hereby certifies that the document is accurate and complete. DOCUMENTATION AUTHOR SIGNA URE DAT Joan D. Hacker The Principal Envelope Designer hereby certifies that the pro se building design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building has been designed to meet the envelope requirements contained in Sections 110, 116 through 118, and 140, 142, 143 or 149 of Title 24, Part 6. Please check one: I hereby affirm that l am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the state of California as a civil engineer or mechanical engineer, or I am a licensed architect. I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538, and 6737.1. PRINCIPAL ENVELOPE D SIGNER - NAME SIGNATURE DA E LIC. # l�%�� �— O� ENVELOPE MANDATORY MEASURES Indicate location on plans of Note Block for Mandatory Measures INSTRUCTIONS TO APPLICANT For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the Nonresidential Manual published by the California Energy Commission. ENV -1: Required on plans for all submittals. Part 2 may be incorporated in schedules on plans. ENV -2: Used for all'submittals; choose appropriate version depending on method of envelope compliance. ENV -3: Optional. Use if default U -values are not used. Choose appropriate version for assembly U -value to be calculated. EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:3 of 31 ENVELOPE COMPLIANCE SUMMARY Part 2 of 2 ENV -1 PROJECT NAME La Quinta Grill Offices Area U -Fac. Act. Azm. SHGC Glazing Type DATE 5/22/2003 OPAQUE SURFACES 100 0.710 0 0.63 Mtl Thermal Brk Unctd Default ffices 2 Window Surface Framing # Type Type Act. Area U -Fac. Azm. Tilt Solar Gains YIN Form 3 Reference Location I Comments 1 Wall Wood 400 0.049 0 90 X11 I Premier Structural Building Panels Offices 2 Door None 40 0.387 0 1 90 X11 I Solid Wood Door Offices 3 Wall Wood 353 0.049 90 1 90 X I I Premier Structural Building Panels Offices 4 Wall Wood 324 0.049 180 1 90 X I I Premier Structural Building Panels Offices 5 Wall Wood 328 0.049 270 90 x I I Premier Structural Building Panels Offices 6 Roof Wood 2,977 0.028 180 0 X I I R-38 Roof R.38.2x14.16 Offices 7 Wall Wood 400 0.049 90 90 X I I Premier Structural Building Panels Offices 8 Door None 40 0.387 90 90 X11 I Solid Wood Door Offices 9 Wall Wood 378 0.049 180 90 X11 I Premier Structural Building Panels Offices 10 Wall Wood 324 0.049 270 90 X I I Premier Structural Building Panels Offices 11 Wall Wood 328 j 0.049 1 0 90 x I I Premier Structural Building Panels Offices 12 Roof Wood 2,977 0.028 180 0 X I I R-38 Roof R.38.2x14.16 Offices Overhang Left Fin Len. H t. LExt.RExt. Dist. Len. H t. Right Fin Dist. Len. H t. 1 None F4 0.76 5.0 5.0 2.0 0.1 2.0 2.0 2 None 0.76 5.0 5.0 2.0 0.1 2.0 2.0 3 None 0.76 4.0 4.0 2.0 0.1 2.0 2.0 None 0.76 5.0 5.0 2.0 0.1 2.0 2.0 5 None 0.76 1 5.0 5.0 2.0 0.1 2.0 2.0 6 None 0.76 4.0 4.0 2.0 0.1 2.0 2.0 7 None 0.76 5.0 5.0 2.0 0.1 2.0 2.0 FENESTRATION SURFACES Site Assembled Glazing Check box if Building is - 100,000 sqft of CFA and - 10,000 sgft vertical glazing then NFRC Certification is required. Follow NFRC 100 -SB Procedures and submit NFRC Label Certificate Form. # Type Area U -Fac. Act. Azm. SHGC Glazing Type Location I Comments 1 Window 100 0.710 0 0.63 Mtl Thermal Brk Unctd Default ffices 2 Window 25 0.710 90 0.63 Mtl Thermal Brk Unctd Default ffices 3 Window 16 0.710 160 0.63 Mtl Thermal Brk Unctd Default Yfices 4 Window 50 0.710 270 0.63 Mtl Thermal Brk Unctd Default ffices 5 lWindow 100 0.710 90 0.63 Mtl Thermal Brk Unctd Default Dffices 6 Window 16 0.710 270 0.63 Mtl Thermal Brk Unctd Default ffices 7 Window 50 0.710 0 0.63 Mtl Thermal Brk Unctd Default Dffices EXTERIOR SHADING ## Exterior Shade Type SHGC Window Hgt. Wd. Overhang Left Fin Len. H t. LExt.RExt. Dist. Len. H t. Right Fin Dist. Len. H t. 1 None F4 0.76 5.0 5.0 2.0 0.1 2.0 2.0 2 None 0.76 5.0 5.0 2.0 0.1 2.0 2.0 3 None 0.76 4.0 4.0 2.0 0.1 2.0 2.0 None 0.76 5.0 5.0 2.0 0.1 2.0 2.0 5 None 0.76 1 5.0 5.0 2.0 0.1 2.0 2.0 6 None 0.76 4.0 4.0 2.0 0.1 2.0 2.0 7 None 0.76 5.0 5.0 2.0 0.1 2.0 2.0 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:4 of 31 OVERALL ENVELOPE METHOD Part 1 of 6 ENV -2 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 WINDOW AREA TEST A. DISPLAY PERIMETER 0 ft X 6 =�Q sf DISPLAY AREA B. GROSS EXTERIOR WALL AREA 3,272 sf X 0.40 = X30 sf 40% AREA C. GROSS EXTERIOR WALL AREA 3,272 sf X 0.10 = 32 sf MINIMUM STND. AREA D. ENTER LARGER OF A or B 1 1 300 sf MAXIMUM STND. AREA E. ENTER PROPOSED WINDOW AREA 35sf PROPOSED AREA F. WINDOW WALL RATIO = Proposed Window Area Divided by Gross Exterior Wall Area = 10.9 % IF E IS GREATER THAN D OR LESS THAN C, PROCEED TO THE NEXT CALCULATION FOR THE WINDOW AREA ADJUSTMENT. IF NOT, GO TO PART 2 OF 6. 1. IF E GREATER THAN D: MAXIMUM PROPOSED WINDOW STANDARD AREA WINDOW AREA ADJUSTMENT FACTOR GO TO PART 6 TO CALCULATE ADJUSTED AREAS. 2. IF LESS THAN C: MINIMUM PROPOSED WINDOW STANDARD AREA AREA ADJUSTMENT FACTOR GO TO PART 6 TO CALCULATE ADJUSTED AREAS. I SKYLIGHT AREA TEST ATRIUM HEIGHT Q FT IF — 55 FT IF > 55 FT J 0.10 X = 6.651 X F 5,9541 = 298 STANDARD % GROSS STANDARD ROOF AREA SKYLIGHT AREA D PROPOSED SKYLIGHT AREA IF THE PROPOSED SKYLIGHT AREA IS GREATER THAN THE STANDARD SKYLIGHT AREA, PROCEED TO THE NEXT CALCULATION FOR THE SKYLIGHT AREA ADJUSTMENT. IF NOT, GO TO PART 2 OF 6, 1. IF PROPOSED SKYLIGHT AREA >= STANDARD SKYLIGHT AREA: SKYLIGHT STANDARD SKYLIGHT AREA PROPOSED SKYLIGHT AREA ADJUSTMENT FACTOR GO TO PART 6 TO CALCULATE ADJUSTED AREAS. EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:5 of 31 DVERALL ENVELOPE METHOD Part 2 of 6 ENV -2 PROJECT NAME ASSEMBLY NAME (e.g. Wall -1, Floor -1) Front Wall Window Left Wall Window Rear Wall Window Right Wall Window Roof Front Wall Window Left Wall Rear Wall Window Right Wall Window Roof PROPOSED AREA* (Adjusted) I AREA HEAT CAPACITY U- FACTORtN](B TABLE VALUES UA X D) 100 0.490 400 3.86 0.049 29.7 25 19.5 100 324 0.710 27.2 16 71.0353 7.8 3.86 0.049 27.6 501 17.2 25 2,977 0.710 ❑ ❑ 17.8 324 3.86 0.049 X ❑ 15.8 16 324 0.710 ❑ ❑X 11.4 328 3.86 0.049 0 ❑ 16.0 50 2,977 0.710 ❑ ® 35.5 2,977 3.00 0.028 ®❑ 84.4 400 3.861 0.049 ®❑ 19.5 100 0.710 ❑ 71.0 378 3.86 0.049 X❑ ❑ 18.4 324 3.86 0.049 ❑ 15.8 16 0.710 ❑ a 11.4 328 3.861 0.049 X ❑ 16.0 50 0.710 ❑ X 35.5 2,977 3.00 0.028 X❑ ❑ 84.4 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ DATE STANDARD AREA* (Adjusted) I U -FACTOR UA (F X G) 400 0.084 33.6 100 0.490 49.0 353 0.084 29.7 25 0.49C 12.2 324 0.084 27.2 16 0.49C 7.8 328 0.084 27.6 501 0.490 24.5 2,977 0.057 169.7 400 0.084 33.6 100 0.490 49.0 3781 0.084 31.8 324 0.084 27.2 16 0.490 7.8 328 0.084 27.6 501 0.490 24.5 2,977 0.057 169.7 If Window and/or Skylight Area Adjustment is Required, Column E shall be 560 This Page Total 752 use Adjusted Areas from Part 6 of 6. no greater than Column H 560 Building Total 752 I EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:6 of 31 1 OVERALL ENVELOPE METHOD Part 3 of 6 ENV -2 PROJECT NAME La Quinta Grill Offices DATE 5/22/2003 VERALL HEAT GAIN FROM CONDUCTION a aao 0 0 © o a a PROPOSED STANDARD TABLE HEAT HEAT ASSEMBLY NAME HEAT U- VALUES GAOIN AREA* U- GAIN (e.g. Wall -1, Floor -1) AREA TF CAPACITY FACTOR Y N BxCxE (Adjusted) FACTOR TF GxHxl Front Wall 400 55 3.86 0.049 0 ❑ 1,072 400 0.084 55 1,848 Window 1001 55 J 0.710 ❑ ❑X 3,905 1001 0.490 551 2,695 Left Wall 353 55 3.86 0.049 X❑ ❑ 946 353 0.084 55 1,631 Window 25 55 0.710 ❑ a 976 25 0.490 55 674 Rear Wall 324 55 3.86 0.049 X❑ ❑ 868 324 0.084 55 1,497 Window 16 55 0.71ol ❑ 0 625 16 0.490 55 431 Right Wall 328 55 3.86 0.049 X❑ ❑ 879 328 0.084 55 1,515 Window 50 55 0.710 ❑ ® 1,952 50 0.490 55 1,348 Roof 2,977 55 3.00 0.028 ®❑ 4,642 2,977 0.057 55 9,333 ront Wall 400 55 3.86 0.049 ®❑ 1,072 400 0.084 55 1,848 Window 100 55 0.710 ❑ N 3,9051 100 0.490 55 2,695 eft Wall 378 55 3.861 0.049 a ❑ 1,013 378 0.084 55 1,746 Rear Wall 324 55 3.86 0.049 FX] ❑ 868 324 0.084 55 1,497 Window 16 55 0.710 -]a625 16 0.490 55 431 Right Wall 328 55 3.86 0.049 X❑ ❑ 879 328 0.084 55 1,515 Window 50 55 0.710 ❑ 1,952 50 0.490 55 1,348 Roof 2,977 55 3.00 0.028 a ❑ 4,642 2,977 0.057 55 9,333 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 30,821 41,385 Subtotal Subtotal • If Window and/or Skylight Area Adjustment is Required, use Adjusted Areas from Part 6 of 6. EnergyPro 3.1 By EnergySoft User Number. 2655 Job Number: Page:7 of 31 OVERALL ENVELOPE METHOD Part 4 of 6 ENV -2 PROJECT NAME La Quinta Grill Offices ❑F DATE 5/22/2003 8,596 26,883 SUBTOTAL SUBTOTAL 1 EnergyPro 3.1 By EnergyPro User Number: 2655 Job Number. Page:8 of 31 PROPOSED STANDARD ASSEMBLY NAME e.g. Roof -1) AREA SF WEIGHTING FACTOR U- FACTOR Absorp HEAT GAIN (BxCxDxExF) AREA` (ADJUSTED) U -Factor Absorp HEAT GAIN (CxDxHxlxJ) Roof 2,977 123 0.92 0.028 0.45 4,298 2,977 0.057 0.70 13,441 Roof 197 1231 0.92 0.028 0.45 4.298 2 77 0.05 0.70 13 441 8,596 26,883 SUBTOTAL SUBTOTAL 1 EnergyPro 3.1 By EnergyPro User Number: 2655 Job Number. Page:8 of 31 OVERALL ENVELOPE METHOD Part 5 of 6 ENV -2 PROJECT NAME DATE La Quinta Grill Offices I 5/22/2003 FENESTRATION SURFACES a ©oao©a o 0 0©E PROPOSED STANDARD WINDOW/SKYLIGHT NAME e.g. Wind -1, Sky -1) ORIENT. WEIGHTING FACTOR AREA SF SHG OVERHANG HEATDGAIN (BxCxDxExH) AREA* (ADJUSTED) RSHG (orSHGC"") SF HEATOGAIN (BxJxKxL) H V H/V I OHF Window N 0.61 10C 123 0.63 2.0 5.1 0.39 0.87 4,112 100 0.51 123 3,827 Window E 1.07 25 123 0.63 2.0 5.1 0.39 0.69 1.437 251 0.36 123 1,184 Window S 1.27 1 123 0.63 2.0 4.1 0.49 0.56 885 16 0.36 123 900 Window W 1.05 50 123 2.819 50 0.36 123 2,325 Window E 1.07 10C 123 0.63 2.0 5.1 0.39 0.69 5,746 100 0.36 123 4,738 Window W 1.05 16 123 0.63 2.0 4.1 0.49 0.63 826 16 0.36 123 744 Window N 0.61 5 123 0.63 2.0 5.1 0.39 0.87 2,056 50 0.51 123 1,913 " Only SHGC is Part 3 Subtotal 30,821 Part 3 Subtotal 41,385 used for Skylights Part 4 Subtotal 8,596 Part 4 Subtotal 26,883 'If Window and/or Skylight Area Column I must be Adjustment is Required, use less than column M Part 5 Subtotal 17,882 Part 5 Subtotal 15,63 Adjusted Areas from Part 6 of 6. 57,299 Total Heat Gain 83,898 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:9 of 31 OVERALL ENVELOPE METHOD Part 6 of 6 ENV -2 PROJECT NAME DATE La Quinta Grill Offices 1 5/22/2003 WINDOW AREA ADJUSTMENT CALCULATIONS n CHECK IF NOT APPLICABLE (See a Part 1 of 6.) ORIENTATION a KWINDOW E❑ F❑ ADJUST. FACTOR (From Part 1) ADJUSTED WINDOW AREA (D X E) ADJUSTED WALL AREA B - (F + C) WALL NAME (e.g. Wall -1, Wall -2) GROSS AREA DOOR AREA WINDOW AREA N I E I S JW ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 1:11:1 ❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ ❑❑❑❑ TOTALS I I I I I N/A EnergyPro 3.1 By EnergySoff User Number 2655 Job Number: Page: 10 of 31 ENVELOPE MANDATORY MEASURES ENV -MM PROJECT NAME La Quinta Grill Offices DATE 5/22/2003 DESCRIPTION Designer Enforcement R§118(a) Installed Insulating Material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20, Chapter 4, Article 3. § 118(c) All Insulating Materials shall be installed In compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. ❑ § 117(a) All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. 0 § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). FX § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards. Manufactured fenestration products must be labeled for U -value according to NFRC procedures. 0 §118(e) Demising Walls in Nonresidential Buildings: The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an Installed R -value of no less than R-11 between framing members. EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page: 11 of 31 CERTIFICATE OF COMPLIANCE Part 1 of 3 LTG -1 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 PROJECT ADDRESS 78-034 Calle Barcelona La Quinta # PRINCIPAL DESIGNER - LIGHTING TELEPHONE Building Permit DOCUMENTATION AUTHOR TELEPHONE Checked by/Date Insu-form, Inc. 760 324-2046 1 Enforcement Agency Use GENERAL INFORMATION DATE OF PLANS BUILDING CONDITIONED FLOOR AREA CLIMATE ZONE 5,954 Sq.Ft. 1 15 BUILDING TYPE [Xj NONRESIDENTIAL HIGH RISE RESIDENTIAL HOTEUMOTEL GUEST ROOM PHASE OF CONSTRUCTION [X NEW CONSTRUCTION ADDITION ❑ ALTERATION EXISTING + ADDITION METHOD OF LIGHTING ® COMPLETE BUILDING AREA CATEGORY 0 TAILORED PERFORMANCE COMPLIANCE STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building lighting requirements. The documentation preparer hereby certifies that the documentation is accurate and complete. DOCUMENTATION AUTHOR SIGNAT E DATE Joan D. Hacker AL ID The Principal Lighting Designer hereby certifies that the proposd building design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building has been designed to meet the lighting requirements contained in Sections 110, 119, 130 through 132, and 146 or 149 of Title 24, Part 6. Please check one: I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer or electrical engineer, or I am a licensed architect. I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. E] I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538 and 6737.1. PRINCIPAL LIGHTING DESIGNER - NAME SIGNATURE DATE LIC. # LIGHTING MANDATORY MEASURES Indicate location on plans of Note Block for Mandatory Measures INSTRUCTIONS TO APPLICANT For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the Nonresidential Manual published by the California Energy Commission. LTG -1: Required on plans for all submittals. Part 2 and 3 may be incorporated in schedules on plans. LTG -2: Required on all submittals. LTG -3: Optional. Use only if lighting control credits are taken. LTG -4: Optional. Use only if Tailored method is used. LTG -5: Optional. Use only if Tailored method is used. EnergyPro 3.1 By Energysoft User Number 2655 Job Number. Page: 12 of 31 LIGHTING COMPLIANCE SUMMARY Part 2 Of 3 LTG -1 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 INSTALLED LIGHTING SCHEDULE LAMPS I BALLASTS IF Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Wafts LaMP DESCRIPTION # Lam + # bauasl Wafts Total Watts 4 4 It Fluorescent T8 Elec F32T8 4 32 Electronic 2.0 40 124,0 4,960 Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page 4,960 Meets Total 4,960 1,191 ❑ Efficacy and Control Requirement of§130(c) Portable Lighting (From LTG -1) Less Control Credit Watts (From LTG -3) ❑ ConVol Requirements of§131(f) Adjusted Actual Watts 6,151 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL IDENTIFICATION CONTROL TYPE (Auto Time Switch, Exterior, etc.) SPACE CONTROLLED NOTE TO FIELD EnergyPro 3.1 By Energysoft User Number: 2655 Job Number. Page: 13 of 31 CONTROL LOCATION I CONTROL 11 CONTROL TYPE (Room # or Dwg. #) IDENTIFICATION I (Occupant. Daylight, Dimmi NOTE TO NOTES TO FIELD - For Building Department Use Only EnergyPro 3.1 By Energysoft User Number: 2655 Job Number. Page: 13 of 31 LIGHTING COMPLIANCE SUMMARY Part 3 of 3 LTG -1 PROJECT NAME DATE La Quinta Grill Offices I 5/22/2003 ROOM # DEFAULT OR ZONE ID /s ft AREA SF TOTAL WATTS B X C Offices 0.2 2,977 595 Offices 0.2 2,977 595 TOTALI 5,954 1,191 FA] a o o a a a LUMIN. TASK # OF TOTAL TOTAL ROOM # TOTAL AREA OR ZONE ID (SF) TOTALI 0 BUILDING SUMMARY - PORTABLE LIGHTING Designer needs to provide detailed documentation that the ligl level provided by the overhead lighting meets the needs of the space. The details include luminaire types, CU, and mounting locations relative to work areas. BUILDING SUMMARY TOTAL AREA (SF (FROM TABLES 1A+1 +1C) TOTAL WATTS (FROM TABLES 1A+1B) BUILDING TOTAL 5,954 1,191 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page: 14 of 31 LIGHTING COMPLIANCE SUMMARY LTG -2 PROJECT NAME DATE La Quinta Grill Offices I 5/22/2003 LUMINAIRE NAME NUMBER OF DESCRIPTION LUMINAIRES 4) 4 ft Fluorescent T8 Elec 40 COMPLETE BUILDING METHOD WATTS PER LUMINAIRE (including Ballast CEC DEFAULT Y N' 124.0 a ❑ El ❑❑ ❑❑ ❑❑ ❑❑ El 1:1 ❑❑ ❑❑ ❑❑ Total Watts 4,960 Subtotal from this Page 4, 960 Building Total 4,960 Portable Lighting (From LTG -1) 1 ,191 Less Control Credit Watts (From LTG -3) Adjusted Actual WaftsE 6=1 BUILDING CATEGORY (From Table 1-M) WATTS COMPLETE ALLOWED PER SF BLDG. AREA WATTS Comp Bldg Office 1.20 5,954 7,145 AREA CATEGORY METHOD AREA CATEGORY (From Table 1-N) WATTS AREA ALLOWED PER SF (SF) WATTS PAGE TOTAL BUILDING TOTAL �❑ TOTAL ALLOWED WATTS D (From LTG -4 or from computer run.) I EnergyPro 3.1 By EnergySoft User Number 2655 Job Number: Paoe:15 of 31 1 TAILORED LPD SUMMARY and WORKSHEET Part 1 of 3 LTG -4 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 1. Watts for Illuminance Categories A -D (from column G) 0 watts 2. Watts for Illuminance Categories E-1 (from LTG -4 Part 2) 0 watts 3. Watts for Display Lighting (from LTG -4 Parts 2 & 3) + F 01 + 0H 0 watts Public Area Display Sales Feature Floor Display Sales Feature Wall Display I4. Total Allowed Watts (lines 1+2+3) 1 ] watts I ® a o a a o a ROOM NAME TASK/ACTIVITY ILLUMINANCE CATEGORY ROOM CAVITY RATIO FLOOR AREA ALLOWED LPD ALLOWED WATTS (E x F) Offices A 0.43 0 0.20 0 Offices A 0.43 0 0.20 0 BUILDING PAGE TOTAL TOTAL 1 I —01 5,9541 Q SF WATTS EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number. Page: 16 of 31 ROOM CAVITY RATIO WORKSHEET (RCR>=3.5) LTG -5 (PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 0 Room Name a © o o a Task/Activity Room Room Room Room Cay. Ratio Description Length (L) Width (W) Cavity 5xHx(L+W) Height (H) /(LxW) LIGHTING MANDATORY MEASURES LTG -MM NAME La Quinta Grill Offices DATE 5/22/2003 DESCRIPTION Designer Enforcement 0 § 131(d)1 For every floor, all Interior lighting systems shall be equipped with a separate automatic control to shut off the lighting. This automatic control shall meet the requirements of Section 119 and may be an occupancy sensor, automatic time switch, or other device capable of automatically shutting off the lighting. X] § 131(d)2 Override for Building Lighting Shut-off: The automatic building shut-off system Is provided with a manual, accessible override switch In sight of the lights. The area of override is not to exceed 5,000 square feet. 0 § 119(h) Automatic Control Devices Certified: All automatic control devices specified are certified, all alternate equipment shall be certified and installed as directed by the manufacturer. F§ 111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for the project are certified and listed In the Directory. All Installed fixtures shall be certified. § 132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three lamp fluorescent fixtures are tandem wired with two lamp ballasts where required by Standards Section 132; or all one and three lamp fluorescent fixtures are specified with electronic high -frequency ballasts and are exempt from tandem wiring requirements. X § 131(a) Individual Room/Area Controls: Each room and area in this building Is equipped with a separate switch or occupancy sensor device for each area with floor -to -ceiling walls. X❑ § 131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 square feet and more than 0.8 watts per square foot of lighting load shall be controlled with bi-level switching for uniform reduction of lighting within the room. § 131(c) Daylight Area Control: All rooms with windows and skylights that are greater than 250 square feet and that allow for the effective use of daylight in the area shall have 50% of the lamps in each daylit area controlled by a separate switch; or the effective use of daylight cannot be accomplished because the windows are continuously shaded by a building on the adjacent lot. Diagram of shading during different times of the year is Included on plans. FX]§ 131(f) Control of Exterior Lights: Exterior mounted fixtures served from the electrical panel inside the building are controlled with a directional photo cell control on the roof and a corresponding relay In the electrical panel, or uses an astronomical time clock. ❑ § 131(e) Display Lighting. Display lighting shall be separately switched on circuits that are 20 amps or less. § 130(c) Efficacy of Exterior Lights: Exterior mounted fixtures with lamps over 100 Watts served from the electrical panel Inside the building have a source efficacy of at least 60 lumens per Watt, or are controlled by a motion sensor. EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number. Page: 18 of 31 CERTIFICATE OF COMPLIANCE Part 1 of 2 MECHA PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 PROJECT ADDRESS PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION ❑ EXISTING + ADDITION 78-034 Calle Barcelona La Quinta PROOF OF ENVELOPE COMPLIANCE ❑ PREVIOUS ENVELOPE PERMIT ENVELOPE COMPLIANCE ATTACHED PRINCIPAL DESIGNER - MECHANICAL TELEPHONE Building Permit # DOCUMENTATION AUTHOR TELEPHONE Checked by/Date I nsu-form, Inc. (760) 324-2046 Enforcement Agency Use GENERAL INFORMATION DATE OF PLANS BUILDING CONDITIONED FLOOR AREA 5,954sq.Ft. �CLIMATEZONE 15 BUILDING TYPE ® NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION ❑ EXISTING + ADDITION METHOD OF MECHANICAL ® PRESCRIPTIVE ❑ PERFORMANCE COMPLIANCE PROOF OF ENVELOPE COMPLIANCE ❑ PREVIOUS ENVELOPE PERMIT ENVELOPE COMPLIANCE ATTACHED STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building mechanical requirements. The documentation preparer hereby certifies that the documentation is accurate and complete. DOCUMENTATION AUTHOR Joan D. Hacker SIGNATU E DATE The Principal Mechanical Designer hereby certifies that the propolsedsbuilding design represented in his set of constructio documents is consistent with the other compliance forms and wort heets, with the specifications, and with any other calculations submitted with this permit application. The proposed building has been designed to meet the mechanical requirements contained in Sections 110 through 115, 120 through 124, 140 through 142, 144 and 145. Please check one: ❑ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, or mechanical engineer or I am a licensed architect. ❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. ❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described pursuant to Business and Professions Code sections 5537, 5538, and 6737.1. PRINCIPAL MECHANICAL DESIGNER - NAME SIGNATURE DATE LIC. # MECHANICAL MANDATORY MEASURES Indicate location on plans of Note Block for Mandatory Measures INSTRUCTIONS TO APPLICANT For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the Nonresidential Manual published by the California Energy Commission. MECH-1: Required on plans for all submittals. Parts 2 may be incorporated in schedules on plans. MECH-2: Required for all submittals, but may be incorporated in schedules on plans. MECH-3: Required for all submittals unless required outdoor ventilation rates and airflows are shown on plans per Section 4.3.4. MECH-4: Required for Prescriptive submittals. MECH-5: Optional. Performance use only for mechanical distribution summa!Y. EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:19 of 31 CERTIFICATE OF COMPLIANCE ' Part 2 of 2 MECH-1 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 SYSTEM FEATURES SYSTEM NAME TIME CONTROL SETBACK CONTROL ISOLATION ZONES HEAT PUMP THERMOSTAT? ELECTRIC HEAT? FAN CONTROL VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/COOL? HEATING SUPPLY RESET COOLING SUPPLY RESET HEAT REJECTION CONTROL VENTILATION OUTDOOR DAMPER CONTROL ECONOMIZER TYPE DESIGN O.A. CFM MECH-3, COLUMN I HEATING EQUIPMENT TYPE HEATING EQUIPMENT EFFICIENCY COOLING EQUIPMENT TYPE COOLING EQUIPMENT EFFICIENCY MAKE AND MODEL NUMBER PIPE INSULATION REQUIRED? PIPEIDUCT INSULATION PROTECTED? HEATING DUCT LOCATION I R -VALUE COOLING DUCT LOCATION R -VALUE VERIFIED SEALED DUCTS IN CEILING/ROOF SPACE MECHANICAL SYSTEMS DHW Heater Building One I Building Two n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a Gas Fired 78% Standard Gas 50 gal or Less n/a n/a Yes Yes n/a n/a n/a n/a n/a Programmable Switch Heating & Cooling Required n/a n/a n/a Constant Volume No No Constant Tem Constant Tem n/a Air Balance Auto No Economizer 496 cfm Gas Furnace 80% AFUE Packaged DX 10.1 EER CARRIER 48HJD009501 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No Programmable Switch Heating & Cooling Require n/a n/a n/a Constant Volume No No Constant Tem Constant Tem n/a Air Balance Auto No Economizer 496 cfm Gas Furnace 80% AFUE Packaged OX 10.1 EER CARRIER 48HJD0095 11 Yes Yes Ducts in Attic 4.2 Ducts in Attic 4.2 No NOTE TO FIELD CODE TABLES: Enter code from table below into columns above. HEAT PUMP THERMOSTAT? TIME CONTROL SETBACK CTRL. ISOLATION ZONES FAN CONTROL ELECTRIC HEAT? S: Prog. Switch O: Occupancy Sensor M: Manual Timer H: Heating C: Cooling B: Both Enter Number of Isolation Zones. I: Inlet Vanes P: Variable Pitch V: VFD O: Other C: Curve VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/ COOL? Y: Yes N: No HEAT AND COOL SUPPLY RESET? VENTILATION OUTDOOR DAMPER ECONOMIZER O.A. CFM HIGH EFFICIENCY? B: Air Balance C: Outside Air Cert. M: Out. Air Measure D: Demand Control N: Natural A: Auto G: Gravity A: Air W: Water N: Not Required EC: Economizer Control See Section 144e3 Enter Outdoor Air CFM. Note: This shall be no less than Col. H on MECH-3. PIPE INSULATION REQUIRED? PIPE/DUCT INSULATION PROTECTED? SEALED DUCTS IN CEILING/ROOF SPACE EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:20 of 31 MECHANICAL EQUIPMENT SUMMARY Part 1 of 2 MECH-2 PROJECT NAME La Quinta Grill Offices DATE 5/22/2003 CHILLER AND TOWER SUMMARY Efficiency Tons PUMPS Equipment Name Equipment Type Qty. Tot. Qty GPM BHP Motor Eff. Drive Eff Co rol BOILER Energy Factor or Recovery Efficiency Standby Loss or Pilot TANK INSUL. System Name System Type Distribution Type Qty Rated Input (Gals.) Vol. Ext. R-Val. Standard Gas 50 gal or Less Small Gas Standard 0 40,000 50 0.53 n/a 12 CENTRAL SYSTEM RATINGS HEATING COOLING System Name S stem Type Qty. Output Aux. kW Eff. Out ut Sensible Efficiency Economizer Type CARRIER 48HJD009501 Packaged DX 2 102,500 0.0 80%AFUE 106,000 75,20010.1 EER No Economizer 1 EnergyPro 3.1 By EnergySoft User Number. 2655 Job Number. Page: 21 of 31 1 MECHANICAL EQUIPMENT SUMMARY Part 2 of 2 MECH-2 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 VAV TERMINAL BOX Min. CFM Reheat Coil System Type Ratio Type IDeltaT Motor Drive Room Name Otv_ I CFM I BHP Eff. Eff. CFM I BHP I MotoEff.l DrivEffe I I Type Output EXHAUSTFAN Room Name Qty. CFM BHP Motor Eff. Drive Eff. EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:22 of 31 1 MECHANICAL VENTILATION MECH-3 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 MECHANICAL VENTILATION R ©© a a o© a 01 0 0 ZONE/SYSTEM Offices Building One Offices Building Two AREA BASIS COND. AREA (SF) CFM PER SF MIN. CFM (B x C) 2,977 0.15 447 2,977 0.15 447 OCCUPANCY BASIS NO. CFM MIN. OF PER CFM PEOPLE PERSON (EXF) Total Total VAV MIN. RAW C Minimum Ventilation Rate per Section 121, Table 1-F. E Based on Expected Number of Occupants or at least 50% of Chapter 10 1997 UBC Occupant Density. I Must be greater than or equal to H, or use Transfer Air. Design Outdoor Air includes ventilation from Supply Air System & Room Exhaust Fans. K Must be greater than or equal to (H minus 1), and, for VAV, greater than or equal to (H -J). I EnergyPro 3.1 By EnergySoft User Number. 2655 Job Number: Page:23 of 31 1 MECHANICAL SIZING AND FAN POWER MECH-4 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 SYSTEM NAME FLOOR AREA Building One 2,977 NOTE: Provide one copy of this form for each mechanical system when using the Prescriptive Approach. SIZING AND EQUIPMENT SELECTION 1. DESIGN CONDITIONS: - OUTDOOR DRY BULB TEMPERATURE - OUTDOOR WET BULB TEMPERATURE - INDOOR, DRY BULB TEMPERATURE 2. SIZING: - DESIGN OUTDOOR AIR - ROOM LOADS - RETURN VENTED LIGHTING - RETURN AIR DUCTS - RETURN FAN - SUPPLY FAN - SUPPLY DUCTS SAFETY/ WARM-UP FACTOR (APPENDIX C) (APPENDIX C) SEE ASHRAE CHAPTER 8, 1993 OR APPENDIX B 496 CFM (MECH 3; COLUMN 1) TOTALS MAXIMUM ADJUSTED LOAD (TOTALS FROM ABOVE x SAFETY / WARM-UP FACTOR) 3. SELECTION: INSTALLED EQUIPMENT CAPACITY (ADJUSTED FOR DESIGN CONDITIONS) IF INSTALLED CAPACITY EXCEEDS MAXIMUM ADJUSTED LOAD, EXPLAIN 0 FAN DESCRIPTION Fan DESIGN BRAKE HP 2.900 K o EFFICIENCY MOTOR DRIVE 84.0%1 97.0% NOTE: Include only fan systems exceeding 25 HP (see Section 144). Total Fan System Power Demand may not exceed 0.8 Watts/cfm for constant volume systems or 1.25 Watts/cfm for VAV systems. COOLING HEATING 112 OF 26 OF 78 OF 74 OF 70 OF 19,881 23,287 45,506 16,177 0 n/ 2,275 809 0 0 0 0 2,2751 809 69,938 41,082 1.21 1.43 84 625 58,747 74,4591 1 102,500 Btu / Hr Btu / Hr 0 NUMBER OF FANS 1 a PEAK WATTS BxEx746/(CXD 2.655 CFM (Supply Fans) 3,400 TOTALS 2 655 3 400 TOTAL FAN SYSTEM POWER DEMAND 0.781 WATTS / CFM Col. F / Col. G EnergyPro 3.1 By EnergySoft User Number 2655 Job Number: Page: 24 of 31 1 MECHANICAL SIZING AND FAN POWER MECH-4 PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 SYSTEM NAME FLOOR AREA Building Two 2,977 NOTE: Provide one copy of this form for each mechanical system when using the Prescriptive Approach. SIZING AND E UIPMENT SELECTION 1. DESIGN CONDITIONS: - OUTDOOR DRY BULB TEMPERATURE - OUTDOOR WET BULB TEMPERATURE - INDOOR, DRY BULB TEMPERATURE 2. SIZING: -DESIGN OUTDOOR AIR - ROOM LOADS -RETURN VENTED LIGHTING - RETURN AIR DUCTS - RETURN FAN - SUPPLY FAN - SUPPLY DUCTS SAFETY / WARM-UP FACTOR (APPENDIX C) (APPENDIX C) SEE ASHRAE CHAPTER 8, 1993 OR APPENDIX B 4961 CFM (MECH 3; COLUMN 1) TOTALS MAXIMUM ADJUSTED LOAD (TOTALS FROM ABOVE x SAFETY / WARM-UP FACTOR) 3. SELECTION: INSTALLED EQUIPMENT CAPACITY (ADJUSTED FOR DESIGN CONDITIONS) IF INSTALLED CAPACITY EXCEEDS MAXIMUM ADJUSTED LOAD, EXPLAIN a FAN DESCRIPTION Supply Fan DESIGN BRAKE HP 2.900 EFFICIENCY MOTOR DRIVE 84.0% 97.0% NOTE: Include only fan systems exceeding 25 HP (see Section 144). Total Fan System Power Demand may not exceed 0.8 Watts/cfm for constant volume systems or 1.25 Watts/cfm for VAV systems. COOLING HEATING 112 OF 26 OF 78 OF 74 OF 70 OF 19,884 23,292 15,450 n/a 77 0 0 77 40,287 1.43 57,610 45,094 0 2,255 0 0 2,255 69,4921 1.21 84 086 74,4531 1 102,500 Btu / Hr Btu / Hr a NUMBER OF FANS 1 U PEAK WATTS BxEx746/(CXD 2,655 a CFM (Supply Fans) 3,400 TOTALS 2 655 3 400 TOTAL FAN SYSTEM POWER DEMAND 0.781 WATTS / CFM Col. F / Col. G I EnergyPro 3.1 By EnergySoft User Number 2655 Job Number: Page: 25 of 31 MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 7] DESCRIPTION Designer Enforcement Equipment and Systems Efficiencies n§111 Any appliance for which there Is a California standard established In the Appliance Efficiency Regulations will comply with the applicable standard. 0 § 115(a) Fan type central furnaces shall not have a pilot light. § 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be Insulated in accordance with Standards Section 123. § 124 Air handling duct systems shall be installed and insulated in compliance with Sections 601, 603 and 604 of the Uniform Mechanical Code. Controls § 122(e) Each space conditioning system shall be Installed with one of the following: § 122(e)1A Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch shall be capable of programming different schedules for weekdays and weekends; incorporate an automatic holiday "shut- off" feature that turns off all loads for at least 24 hours, then resumes the normally scheduled operation; and has program backup capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power Is Interrupted; or § 122(e)1 B An occupancy sensor to control the operating period of the system; or ❑X § 122(e)1C A 4 -hour timer that can be manually operated to control the operating period of the system. X❑ § 122(e)2 Each space conditioning system shall be Installed with controls that temporarily restart and temporarily operate the system as required to maintain a setback heating and/or a setup cooling thermostat setpoint. F] § 122(g) Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000 square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided with Isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be setback or shut off Independently of other isolation areas; and shall be controlled by a time control device as described above. F§ 122(a&b) Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or reduced to a minimum. 0 § 122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to authorized personnel. § 112(b) Heat pumps shall be Installed with controls to prevent electric resistance supplementary heater operation when the heating load can be met by the heat pump alone. EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:26 of 31 MECHANICAL MANDATORY MEASURES Part 2 of'2 MECH-MM PROJECT NAME DATE La Quinta Grill Offices 5/22/2003 Description Designer Enforcement Ventilation R§ 121(e) Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified on these plans. 0 § 122(f) Gravity or automatic dampers Interlocked and closed on fan shutdown shall be provided on the outside air Intakes and discharges of all space conditioning and exhaust systems. § 122(f) All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers In all openings to the outside, except for combustion air openings. § 121(f)1 Air Balancing: The system shall be balanced in accordance with the National Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or Associated Air Balance Council (AABC) National Standards (1989); or a§ 121(f)2 Outside Air Certification: The system shall provide the minimum outside air as shown on the mechanical drawings, and shall be measured and certified by the installing licensed C-20 mechanical contractor and certified by (1) the design mechanical engineer, (2) the Installing licenced C-20 mechanical contractor, or (3) the person with overall responsibility for the design of the ventilation system; or ❑ § 121(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous basis and displaying that quantity on a readily accessible display divice; or § 121(f)4 Another method approved by the Commission. Service Water Heating Systems X❑ § 113(b)2 If a circulating hot water system Is Installed, It shall have a control capable of automatically turning off the circulating pump(s) when hot water is not required. X❑ § 113(b)3B Lavatories In restrooms of public facilities shall be equipped with controls to limit the outlet temperature to 110 degrees F. 0 § 113(b)3C Lavatories In restrooms of public facilities shall be equipped with one of the following: Outlet devices that limit the flow of hot water to a maximum of 0.5 gallons per minute. Foot actuated control valves, and outlet devices that limit the flow of hot water to a maximum of 0.75 gallons per minute. Proximity sensor actuated control valves, and outlet devices that limit the flow of hot water to a maximum of 0.75 gallons per minute. Self-closing valves, and outlet devices that limit the flow of hot water to a maximum of 2.5 gallons per minute, and 0.25 gallons/cycle (circulating system). Self-closing valves, and outlet devices that limit the flow of hot water to a maximum of 2.5 gallons per minute, and 0.50 gallons/cycle (non -circulating system). Self-closing valves, and outlet devices that limit the flow of hot water to a maximum of 2.5 gallons per minute, and 0.75 gallons/cycle (foot switches and proximity sensor controls). EnergyPro 3.1 By EnergySoft User Number. 2655 Job Number. Page:27 of 31 ROOM HEATING PEAK LOADS Project Title Date La Quinta Grill Offices 15/22/2003 71 Room Information Design Conditions Room Name Offices Time of Peak Jan 12 am Floor Area 2,977 Outdoor Dry Bulb Temperature 26OF Indoor Dry Bulb Temperature 70 OF Conduction Area U -Value AT of Btu/hr Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 16 177 Infiltration: r 1.001 X 1.072 X 2 977 x 10.00 X 6] X W _ �0 `schedule Jr Sensible Area Ceiling Height ACH DT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 16,177 EnergyPro 3.1 By EnergySoft User Number. 2655 Job Number. Page: 28 of 31 perimeter = 63.0 x X X X X x X x X X x x x x X X x X X X X X X x X X X X X X x X x X X X X x X x X X X X x X X X X X X X X X X X x X X X X X x X x x x X x x X X X X X X x X 44.5 = = = = = = = = = = 2,804 1,405.0 0.0487 44.0 3,011 40.0 0.3872 44.0 682 191.0 0.7100 44.0 5,967 2,977.0 0.0284 44.0 3,714 Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 16 177 Infiltration: r 1.001 X 1.072 X 2 977 x 10.00 X 6] X W _ �0 `schedule Jr Sensible Area Ceiling Height ACH DT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 16,177 EnergyPro 3.1 By EnergySoft User Number. 2655 Job Number. Page: 28 of 31 ROOM HEATING PEAK LOADS Project Title Date La Quinta Grill Offices 5/22/2003 Room Information Desicin Conditions Room Name Offices Time of Peak Jan 12 am Floor Area 2,977 Outdoor Dry Bulb Temperature 260E Indoor Dry Bulb Temperature 70 OF Conduction Area U -Value AT OF Items shown with an asterisk ('ff) denote conduction through an interior surface to another room. Page Total: 15 450 Infiltration: 1.001 x 1.072 x 2 977 x 10.00 x 6] x &T = 0 chedule Air Sensible Area Ceiling Height ACH DT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 15,450 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number. Page: 29 of 31 perimeter = 63.0 x x x x X x x X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X x x x x X x X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 44.5 = = = = = = = = 2,804 1,430.0 0.0487 44.0 3,065 40.0 0.3872 44.0 682 166.0 0.7100 44.0 5,186 2,977.0 0.0284 44.0 3.714 Items shown with an asterisk ('ff) denote conduction through an interior surface to another room. Page Total: 15 450 Infiltration: 1.001 x 1.072 x 2 977 x 10.00 x 6] x &T = 0 chedule Air Sensible Area Ceiling Height ACH DT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 15,450 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number. Page: 29 of 31 ROOM COOLING PEAK LOADS Project Title Date La Quinta Grill Offices 5/22/2003 ROOM INFORMATION DESIGN CONDITIONS Room Name Offices Time of Peak Jul 3 pm Floor Area 2,977 Outdoor Dry Bulb Temperature 112 `k Indoor Dry Bulb Temperature 74cl= Outdoor Wet Bulb Temperature 78 c� Conduction remier Structural Building Panels olid Wood Door tl Thermal Brk Unctd Default remier Structural Building Panels remier Structural Building Panels tl Thermal Brk Unctd Default remier Structural Building Panels R-38 Roof R.38.2x14.16 Area X X X X X X X X X U -Value X X X X X X X X X 400.0 0.0487 40.0 0.3872 175.0 0.7100 353.0 0.0487 324.0 0.0487 16.0 0.7100 328.0 0.0487 2,977.0 0.0284 16.0 42 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Solar Gain DETD t 37.0 = 37.2 = 27.0 = 39.2 = 40.1 = 27.0 = 57.4 = 64.0 = Page Total Orientation Area X X X X X X X X X X SGF X x X x X x X X X x SC Weighting X x x x X x X X x x Factor = = = = = = 100.0 41 0.701 0.797 _(North) (East) 25.0 41 0.701 1.461 (South) 16.0 42 0.701 0.783 (West) 50.0 169 0.701 0.394 Page Total Btu/hr 721 577 3,357 674 632 307 917 5,399 12 583 Btu/hr 2 293 1 050 369 2.33 6043 Sched. Weighting Btu/hr Internal Gain Frac. Area Heat Gain Factor fights 1.0 x 2,977 x 0.833 Watts/sgft x 3.41 Btuh/Watt x 0.998 = 8,450 ccu ants 1.0 X 2,977 X 250 Btuh/occ. / 9 sgft/OCc. X 1.00 = 8,269 eceptacle 1.0 x 2,977 X 1.000 Wafts/sqft x 3.41 Btuh/Waft x 1.00 = 10,161 recess r1.0 x 2,977 x 0.000 Wafts/sqft X 3.41 Btuh/Watt x 1.00 = 0 Infiltration: I 1.00 x 1.072 x 2 977 x 10.00 x 0.00 /60] x 38 = �0 chedule Air Sensible Area Ceiling Height ACH OT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 45,506 Sched. Btu/hr Latent Gain Frac. Area Heat Gain ccupants 1.00 X 1 2,9771 x 2001 Btuh/occ. / 90 sgft/occ. = 6 616 Receptacle 1 o x x 0,0001 Wafts/sqft x Btuh/Watt = rocess 1.00 x 2,977 x 0.000 Waftslsgft x 3.413 BtuhfWaft = ��o� Infiltration: 1 00 x 4.806 x 2,g x 10.0o x 160] x o ODoo. _ �oJ chedule Air Latent Area Ceiling Height ACH &W ROOM COOLING PEAK LOADS Project Title Date La Quinta Grill Offices I 5/22/2003 ROOM INFORMATION DESIGN CONDITIONS Room Name Offices Time of Peak Jul 2 pm Floor Area 2,977 Outdoor Dry Bulb Temperature 111 '� Indoor Dry Bulb Temperature 74`� Outdoor Wet Bulb Temperature 77 OF Conduction Premier Structural Building Panels 6olid Wood Door Roof Area .01 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Solar Gain Window Window Window U -Value 0.0487 0.3872 1 0.02841 DETD 1 38.8 = 40.4 = 25.8 = 41.3 = 51.4 = 36.3 = 67.5 = Page Total Orientation Area x X x X X X x X X X SGF SC X 0.701 X 0.701 X 0.701 X X X X X x X Weighting x X X X X x X X X X Factor = = = = = (East) 100.0 46 1.353 (West) 16.0 81 0.545 (North) 50.0 46 0.701 Page Total Btu/hr 755 626 3,045 761 811 581 5,696 12 275 Btu/hr 4,365 496 1,130 5 991 Sched. Weighting Btu/hr Internal Gain Frac. Area Heat Gain Factor fights 1.0 x 2,977 x 0.833 Watts/sgft x 3.41 BtuhlWaft x 0.998 = 8,447 ccu ants 1.0c x 2,977 X 250 Btuh/occ. / 9 sqft/occ. x 1.00 = 8,269 eceptacle _ 1.0 X 2,977 x 1.000 Wafts/sqft x 3.41 Btuh/Waft X 1.00 = 10,161 rocess 4 1.0 X 2,977 X 0.000 Wafts/sgft X 3.41 Btuh/Waft X 1.00 = 0 Infiltration: 1.00 x 1.072 x 2977 x 10.00 x 0.00 /601 x 38 = Lhedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 45,143 Sched. Btu/hr Latent Gain Frac. Area Heat Gain Occupants 1.00 x I 2 977 x 2001 Btuh/occ. / 90 sgft/occ. = 6 616 Receptacle 1.00 vl 1 2.9771 x0,000 Wafts/sgft x BtuhlWaft = 0 Process 1.00 x 2,977 x 0.000 Watts/sgft x 3.413 Btuh/Watt = 00 Infiltration: 1.DD x 06 x 2.977 xo_o x [Lo_ffl� / 60] x 0-00.09.0 = E1:::_01 chedule Air la ent Area Ceiling Height ACH pw