BRES2014-115878-495 CALLE TAMPICO
LA QUINTA, CALIFORN!,W2253
Application Number:
Property Address:
APN:
Application Description:
Property Zoning:
Application Valuation:
Applicant:
DESERT BUILDERS INC
0 OUTSIDE CITY LIMITS
LA QUINTA, CA 92253
Twy444umro
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING PERMIT
BRES2014-1158
78400 COYOTE CANYON CT CT
770240010
STERIN RESIDENCE
$10,000.00
A
DEC 18 2014
CITY OF LA QUINTA
COMMUNITY DEVELOPMENT DEPARTMENT
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter
9 (commencing with Section 7000) of Division 3 of the Business and Professions Code,
and my License is in full force and effect.
License Cla s: _ License No.: :LIC -0107616
Date: � Contractor:
JkA,01,.
OWNER -BUILDER DECLARATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State
License Law for the following reason (Sec. 7031.5, Business and Professions Code: Any
city or county that requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for the permit to file a
signed statement that he or she is licensed pursuant to the provisions of the
Contractor's State License Law (Chapter 9 (commencing with Section 7000) of Division 3
of the Business and Professions Code) or that he or she is exempt therefrom and the*[
basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for �`
permit subjects the applicant to a civil penalty of not more than five hundred dollars
($500).:
(_) I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for sale.
(Sec. 7044, Business and Professions Code: The Contractors' State License Law does not
apply to an owner of property who builds or improves thereon, and who does the work
himself or herself through his or her own employees, provided that the improvements
are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner -builder will have the burden of proving that
he or she did not build or improve for the purpose of sale.).
( ) I, as owner of the property, am exclusively contracting with licensed contractors
to construct the project. (Sec. 7044, Business and Professions Code: The Contractors'
State License Law does not apply to an owner of property who builds or improves
thereon, and who contracts for the projects with a contractor(s) licensed pursuant to
the Contractors' State License Law.).
( I I am exempt under Sec. . B.&P.C. for this reason
Date:
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for
the performance of the work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's Name:
Lender's
VOICE (760) 777-7125
FAX (760) 777-7011
INSPECTIONS (760) 777-7153
Date: 12/18/2014
Owner:
JEANNE MIRAGLIA
P 0 BOX 3070
INCLINE VILLAGE, NV 92253
Contractor:
DESERT BUILDERS INC
0 OUTSIDE CITY LIMITS
LA QUINTA, CA 92253
(760)568-1790
Llc. No.: :LIC -0107616
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
_ I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided for by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
I have and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which.this permit
is issued. My workers' compensation insurance carrier and policy number are:
Carrier: _ Policy Number:
I certify that in the performance of the work for which this permit is issued, I
shall not employ any person in any manner so as to become subject to the workers'
compensation laws of California, and agree that, if I should become subject to the
workers' compensation provisions of Section 3700 of the Labor Code, I shall forthwith
comply with those provisions. ►► .. -- nn
Date: 2 M
Applicant: � ltoo�
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS UNLAWFUL,
AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO
ONE HUNDRED THOUSAND DOLLARS ($100,000). IN ADDITION TO THE COST OF
COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE,
INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT: Application is hereby made to the Building Official for a permit subject to
the conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose
request and for whose benefit work is performed under or pursuant to any permit
issued as a result of this application , the owner, and the applicant, each agrees to, and
shall defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and
employees for any act or omission related to the work being performed under or
following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is
not commenced within 180 days from date of issuance of such permit, or cessation of
work for.180 days will subject permit to cancellation.
I certify that I have read this application and state that the above information is correct.
I agree to comply with all city and county ordinances and state laws relating to building
construction, and hereby authorize representatives of this city to enter upon the above-
mentioned property for inspection purposes.
Date:
le' Signature (Applicant or Agent):A..S,�
FINANCIAL INFORMATION
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
ADDITION, EA A,DtFT1OWAL 500 SF
101-0000-42400
0
$62.36
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
ADDITION, EA ADDITIONAL 500 SF PC
101-0000-42600
0
$17.40
$0.00
PAID BY
METHOD
RECEIPT. #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
ADDITION, FIRST 100 SF
101-0000-42400
0
$120.83
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
ADDITION, FIRST 100 SF PC
101-0000-42600
0
$171.14
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid forADDITION: $371.73 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
BSAS SB1473 FEE
101-0000-20306
0
$1.00
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid forBUILDING STANDARDS ADMINISTRATION BSA $1.00 $0.00
DESCRIPTION
ACCOUNT
QTY,
AMOUNT
PAID
PAID DATE
RESIDENTIAL, FIRST 1,000SF
101-0000-42403
0
$145.03
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RESIDENTIAL, FIRST 1,000SF, PC
101-0000-42600
0
$47.86
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid forELECTRICAL - NEW CONSTRUCTION: $192.89 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
APPLIANCE REPAIR/ALTERATION
101-0000-42402
0
$12.09
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
APPLIANCE REPAIR/ALTERATION PC
101-0000-42600
0
$4.83
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
VENT FAN
101-0000-42402
0
$12.09
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION, _
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
VENT FAN PC
101-0000-42600
0
$4.83
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid for MECHANICAL: $33.84 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
FIXTURE/TRAP
101-0000-42401
0
$36.27
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION.
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
FIXTURE/TRAP PC
101-0000-42600
0
$36.27
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid for PLUMBING FEES: $72.54 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
SMI - RESIDENTIAL
101-0000-20308
0
$1.30
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid forSTRONG MOTION INSTRUMENTATION SMt $1.30 $0.00
• • $0.00
Description: STERIN RESIDENCE
Type: BUILDING, RESIDENTIAL
Subtype: REMODEL Status: APPROVED
Applied: 10/31/2014 AZA
Approved:
Parcel No: 770240010 Site Address: 78400 COYOTE CANYON CT CTLA QUINTA,CA 92253
Subdivision: TR 28470-1
Block: Lot: 52
Issued:
Lot Sq Ft: 0
Building Sq Ft: 0 Zoning:
Finaled:
Valuation: $10,000.00
Occupancy Type: Construction Type:
Expired:
No. Buildings: 0
No. Stories: 0 No. Unites: 0 JL
Details: CONVERSION OF A GOLF CART GARAGE TO A BATHROOM. ENCLOSURE OF A BREEZEWAY INTO A GAMEROOM.
Printed: Thursday, December 18, 2014 1:06:34 PM 1 of 4 CRIA1sysTEms
ADDITIONAL
CHRONOLOGY
CHRONOLOGY TYPE
STAFF NAME
ACTION DATE
COMPLETION DATE
NOTES
PLAN CHECK COMMENTS
FROM CONSULTANT
KAY HENSEL
11/10/2014
11/10/2014
STRUC APPROVABLE 11/10/14
RECEIVED
PLAN CHECK PICKED UP
KAY HENSEL
11/12/2014
11/12/2014
PLAN CHECK SUBMITTAL
RECEIVED 1ST PLAN CHECK SUBMITTAL FROM EDUARDO
RECEIVED
ANGELICA ZARCO
10/31/2014
10/31/2014
ESCOBAR.
RESUBMITTAL
KAY HENSEL
11/19/2014
SENT TO PLAN CHECK
KAY HENSEL
11/3/2014
11/3/2014
STRUC TO YOUNG DUE 11/14
CONSULTANT
LEFT MESSAGE FOR EDUARDO ESCOBAR THAT PLANS ARE
TELEPHONE CALL
ARMEN ALTOUNIAN
11/12/2014
11/12/2014
READY TO PICK UP.
TELEPHONE CALL
ARMEN ALTOUNIAN
11/20/2014
11/20/2014
PLANS READY FOR PICK UP.
Printed: Thursday, December 18, 2014 1:06:34 PM 1 of 4 CRIA1sysTEms
Printed: Thursday, December 18, 2014 1:06:34 PM 2 of 4 C82"WsrsTEMS
FINANCIAL
INFORMATION
DESCRIPTION
ACCOUNT
CITY
AMOUNT
PAID
' PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
CLTD
BY
ADDITION, EA
101-0000-42400
0
$62.36
$0.00
ADDITIONAL 500 SF
ADDITION, EA
101-0000-42600
0
$17.40
$0.00
ADDITIONAL 500 SF PC
ADDITION, FIRST 100 SF
101-0000-42400
0
$120.83
$0.00
ADDITION, FIRST 100 SF
101-0000-42600
0
$171.14
$0.00
PC
Total Paid forADDITION: $371.73 $0.00
BSAS S61473 FEE
101-0000-20306
1 0
$1.00
$0.00
Total Paid forBUILDING STANDARDS ADMINISTRATION $1.00 $0.00
BSA:
RESIDENTIAL, FIRST
101-0000-42403
0
$145.03
$0.00
1,000SF
RESIDENTIAL, FIRST
101-0000-42600
0
$47.86
$0.00
1,OOOSF, PC
Total Paid forELECTRICAL - NEW CONSTRUCTION: $192.89 $0.00
APPLIANCE
101-0000-42402
0
$12.09
$0.00
REPAIR/ALTERATION
APPLIANCE
101-0000-42600
0
$4.83
$0.00
REPAIR/ALTERATION PC
VENT FAN
101-0000-42402
0
$12.09
$0.00
Printed: Thursday, December 18, 2014 1:06:34 PM 2 of 4 C82"WsrsTEMS
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
CLTD
DUE DATE
RETURNED
REVIEWS
STATUS
REMARKS
NOTES
DATE
BY
VENT FAN PC
101-0000-42600
0
$4.83
$0.00
11/14/2014
11/12/2014
REVISIONS REQUIRED
1ST PLAN CHECK
NON-STRUCTURAL
Total Paid for MECHANICAL:
$33.84
$0.00
FIXTURE/TRAP
101-0000-02401
0
$36.27
$0.00
BUCKET
FIXTURE/TRAP PC
101-0000-42600
0
$36.27
$0.00
STRUC TO YOUNG, DUE 11/14/14
STRUCTURAL
Total Paid for PLUMBING FEES:
$72.54
$0.00
SMI - RESIDENTIAL
101-0000-20308
0
$1.30
$0.00
Total Paid forSTRONG MOTION INSTRUMENTATION SMI:
$1.30
$0.00
TOTALS:00
2ND PLAN CHECK
RESUBMITTAL AT FRONT COUNTER BY SK.
NON-STRUCTURAL
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR
SCHEDULED
COMPLETED RESULT REMARKS NOTES
APPROVED
DATE
DATE
FINAL*"
ALTOUNIAN
Printed: Thursday, December 18, 20141:06:34 PM 3 of 4 CRWrsren S
PARENT
PROJECTS
REVIEW TYPE
REVIEWER
SENT DATE
DUE DATE
RETURNED
REVIEWS
STATUS
REMARKS
NOTES
DATE
BUILDING
10/31/2014
11/14/2014
11/12/2014
REVISIONS REQUIRED
1ST PLAN CHECK
NON-STRUCTURAL
RFC
BUCKET
BUILDING
STRUC TO YOUNG, DUE 11/14/14
STRUCTURAL
10/31/2014
11/14/2014
11/3/2014
APPROVED
STRUC APPROVED 11/10/14
BUCKET
ARMEN
2ND PLAN CHECK
RESUBMITTAL AT FRONT COUNTER BY SK.
NON-STRUCTURAL
11/19/2014
12/3/2014
11/20/2014
APPROVED
2ND PLAN CHECK APPROVED
ALTOUNIAN
APPROVED
Printed: Thursday, December 18, 20141:06:34 PM 3 of 4 CRWrsren S
Printed: Thursday, December 18, 2014 1:06:34 PM 4 of 4 CRsrsreMs
RF-n.CF/SFO
oty of La Quinta - 3z 2�11
0
-Buikrtpg 8z safety Division visi6n � VVA; OF 14
PeriWt # P.O. Box 1504,"78-495 Calle Tamptco
LR.Quinta, CA 92253 -:(760) 777-7012 Tq
4"ZOPML,
W14-- Building Pennit Application' and Tracking Sheet
M
Project Address: '7Sq00 czNort� CA-"NOAj Owner's Name:. j-j11rAjizj k- sf;er-jio
A. P. Number- o -2-z4 o - 0 1 L-)
Address:
Legal Description: 7-5400-1
City, ST, Zip: t 4oW'r.4- C&.
Contractor.
Contracto
x
teitphone: 111 IN
Pmjer4'Description: F C49 -T- Cj4A*TC;-
Address:
u!4 A
City, ST, Zip:
&4C
Telephone:
Vm, U. -M,
State Lic. # : *712.
ity L
City L
C
Arch, Eng., Designer.
Address: q39z? PC l"F?Avc-
•
City., ST, Zip: a
GF- Q1i2ol
Telephone: -9 .0-Z-0?-jZZjConstruction
State l,ic.#:Project
Type:. V -Al Occupancy:
type (circle one): Now d Ktep Repair Demo'
Sq. Ft.: Stories: t # Units:
Name of Contact Person:
Telephone# of Contact Person:
Estimated Value of Project:
APPLICANT: DO NOT WRITE BELOW THIS LINE
#
"Submittal
Req1d
Rec'd
TRACKNG
PERMIT FEES
-iJ—pl_
Sets
Plan Check submitted.
item Amount
Structural Cales.
Reviewed, ready for corrections
PI.. Check Deposit.
Truss CaIcs.
Called Contact Person
Plan Check Balance -
Title 24 Cald.
Plans picked up
construction
Flood plain plan
Plans resubmitted.*.
Mechniw
Grading plan
V Review, ready for correctionslissue
Electrical
Subcontattor List
Called Contact Person
Plumbing
Grant Deed
Plans picked up
S.NLL
H.O.A. Approval
Plans resubmitted
Grading
M HOUSE-
Review; ready for correctionsirissue
Developer Impact Fee
Planning Approval
Called Contact Person
AXP -P -
Pub. talcs. Appr
Date of permit Issue
School Fees
Total Permit Few'
/4
t �t�c �l�
---------- -
Date
12/17/14
No.
31658
Owner
Sterin
Address
78-400 Coyote Canyon
City
La Quinta Zip
Tract #
Type
Residential Addition
CERTIFICATE OF COMPLIANCE
Desert Sands Unified School District
47950 Dune Palms Road
La Quinta, CA 92253
(760) 771-8515
APN #
Jurisdiction
Permit #
No. of Units
4����Ft�vso�o
Q BERMUDA DUNES
RANCHO MIRAGE t.J
INDIAN WELLS
PALM DESERTLA QU IN
��aINDDIOT
�
770-240-010
La Quinta
1
Lot # No. Street S.F. Lot # No. Street S.F.
Unit 1 78400 Coyote Canyon 371 Unit 6
Unit 2 Unit 7
Unit 3 Unit 8
Unit 4 Unit 9
Unit 5 Unit 10
Comments
At the present time, the Desert Sands Unified School District does not collect fees on garages/carports, covered patios/walkways, residential additions under
500 square feet, detached accessory structures (spaces that do not contain facilities for living, sleeping, cooking, eating or sanitation) or replacement mobile
homes. It has been determined that the above-named owner is exempt from paying school fees at this time due to the following reason:
Residential Addition 500 Sq Feet or Less
EXEMPT
This certifies that school facility fees imposed pursuant to
Education Code Section 17620 and Government Code 65995 Et Seq.
in the amount of $0.00 X 371 S.F. or $0.00 have been paid for the property listed above and that
building permits and/or Certificates of Occupancy for this square footage in this proposed project may now be issued.
Fees Paid By Exempt - Brandon Davis Check No.
Bank Name/Recipient of Certificate Telephone
Funding Exempt
BY Dr. Gary Rutherford
Superintendent
Fee collecte
Payment Recd $0.0 '
;'Over/Urider�
Signature
NOTICE: Pursuant to Government Code Sebtion 66020(d)(1), this bill serve to notify you that the 90 -day approval period in which you may protest the fees
or other payment identified above will begin to run from the date on which the building or installation permit for this project is issued, or from the date on
which those amounts are paid to the District(s) or to another public entity authorized to collect them on the District('s) behalf, whichever is earlier.
NOTICE: This Document NOT VALID without embossed seal
Embossed Original - Building Department Applicant Copy - Applicant/Receipt Copy - Accounting
Tradition . .
December 9, 2014
Mr. Henrik Stcrin, and NfsA4olly Grenfell
78400 Coyote Canyon Court
1. a Quinta, CA 92253
Re: Lot 52, Tract 28471-1, 78400 Coyote Canyon
Architectural Addition -
Dear Mr. Sterin and 1v1s. Grenfell:
')'his correspondence shall serve as notification from the Tradition Architectural .Design Review
Committee ("AI)RC") that your architectural addition %vas .rcviewed at the December 4, 2014 meeting.
The addition., which was completed prior to you purchasing the home, was approved as submitted. The
committee appreciates you taking the time to submit the plans and update the Association's records.
Please contact ,Brook. Marshall at 760-219-8057 or by email at.DR.CFacil.itator r@gmail.com with any
cluestio6s regarding this matter.
Sincerely,
THE.TkADITIOIV4RCf...il.TL,CTUAA.L.DESIGNREIy7EiYCOAfiV]TTI,,E
rl
Title. L.Gi nate:. . l L,
cc: AORC: -File
p:vnforu to Cal. Civil Code arty rrjwfon by the ADRC may N al1maled to the Board of Directors for the ARsacintimt If frni wish to pursue an
a,mmwl. please crmkaix the Association's property marnger,ta thota+o+r nut), bep+>i on the. nt;Tt meeting dj errdri. -
DESERT RESORT MANAGENIENT
llosrr OFFICE Box 14387 • PALhI DESERT, C,;ALIFOlkNIA 92255.4387
42-635 NttLANIE• PLACE, SUITE 103 PALM DESERT, CALIFORNIA 92211.
T3:Lrn [ONE (760) .346.1161 • 1 -AX (760) 346.9918
oFi016E &VJ
I BUILDING ENERGY ANALYSIS REPORT I
PROJECT:
MR. HENRIK STERIN -
78400 Coyote Canyon Ct. - APN. 770-240-010
La Quinta, Ca 92253
CITY OF LA QUINTA
BUILDING & SAFETYDEPT.
APPROVED
FOR CON$TRUCTION
DATE 1 i BY,
Project Designer:
ESCOBAR DESIGN
43927 Pacific Ave.
Indio, Ca 92201
(760) 289-9221
Report Prepared by:
Santiago Lopez-Ocampo
Santiago Lopez-Ocampo
P.O. Box 1018
La Quinta, Ca 92247
1 760.485.8927
Job Number:
LQ102614Corr111614
Date:
11/16/2014
EcEN
R
0 19 2014
CITU OF to QUINTA ENT
COMMUNIS DE\JF- I
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report.This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC —www.energysoft.com.
Won11161.
I TABLE OF CONTENTS I
Cover Page 1
Table of Contents 2
Form CF -1 R Certificate of Compliance 3
Form RMS -1 Residential Measures Summary 13
Form MF -1 R Mandatory Measures Summary 15
HVAC System Heating and Cooling Loads Summary 18
EnergyPro 6.3 by EnergySoft Job Number: ID_ LQ102614Corr111614 User Number: 5732
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MR. STERIN Calculation Date/Time: 05:53, Sun, Nov 16, 2014
Calculation Description: Title 24 Analysis Input File Name: 78400 Coyote Canyon Ct. - T24 Corr1,11614.xml
CF1 R -PRF -01
Page 1 of 10
GENERAL INFORMATION
01
Project Name MR. STERIN
02
Calculation Description Title 24 Analysis
03
Project Location 78400 Coyote Canyon Ct. - APN. 770-240-010
04
CA City La Quinta
05
Standards Version Compliance 2014
06
Zip code 92253
07
Compliance Manager Version BEMCmpMgr 2013-3 (651)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.3
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 180
12
Project Scope Addition and/or Alteration
13
Number of Dwelling Units 1
.14
Total Cond. Floor Area (FT2) 5132
15
Number of Zones 4
16
Slab Area (FT2) 4761
17
Number of Stories 1
18
Addition Cond. Floor Area 371
19
Natural Gas Available Yes
20
Addition Slab Area (FT2) 371
21
Glazing Percentage (%) 120.9%
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building DOES NOT require HERS Verification
03. This building incorporates one or more Special Features shown below
ENERGY USE SUMMARY
. 04 05
06
07
08
Energy Use (kTDV/ft2-yr) Standard Design
Proposed Design
Compliance Margin
Percent Improvement
Space Heating 1.27
1.37
-0.10
-7.9%
Space Cooling 247.81
247.52
0.29
0.1%
IAQ Ventilation 0.00
0.00
0.00
0.0%
Water Heating 9.26.
9.26
0.00
0.0%
Photovoltaic Offset --
0.00
0.00
--
TOTAL 268.34
268.15
0.19
0.1%
Registration Number: Registration Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651
CITY OF LA QlJINTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
HERS Provider:
portGene ated-89 = t � ^gib
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01
Project Name: MR. STERIN Calculation Date/Time: 05:53, Sun, Nov 16, 2014 Page 2 of 10
Calculation Description: Title 24 Analysis Input File Name: 78400 Coyote Canyon Ct. - T24 Corrl11614.xmi
REQUIRED SPECIAL FEATURES
The following are features that must be Installed as condition for meeting the modeled energy performance for this computer analysis.
Exposed slab floor in conditioned zone
PROJECT HERS FEATURES
The following are project -level features that must be field -verified as a -condition for meeting the modeled energy performance for this computer analysis. These, plus any additional HERS features listed
in the building components tables below, reciure field verification by a certified HERS Rater.
Building -level Verifications:
• .-None --
Cooling System Verifications:
• ..None --
HVAC Distribution System Verifications:
• ..None --
Domestic Hot Water System Verifications:
• —None •-
ENERGY DESIGN RATING
This is the sum of the annual TDV energy consumption for energy use components Included in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and components not regulated by Title 24, Part 6 (such as domestic appliances and consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system.
Reference Energy Use Energy Design Rating Margin Percent Improvement
Total Energy (kTDV/f2)" 296.29 295.10 0.19 0.1%
includes calculated Appliances and Miscellaneous Energy Use (AMEU)
BUILDING FEATURE INFORMATION
01
02
03
04
06
06
07
Project Name
Conditioned Floor Area (sft)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of
Ventilation Cooling Systems
Number of Water
Heating Systems
MR. STERIN
5132
1
12
4
0
1
ZONE INFORMATION
01
02
03 04
06
06
07
Zone Name
Zone Type
Zone Floor Area
HVAC System Name (ft2)
Avg. Ceiling
Height
Water Heating System 1
Water.Heating System 2
Mein House
Conditioned
HVAC System - Main Housel 4198
10
DHW Sys 1
Bath-Add'n
'Conditioned
HVAC System - Main Housel 150
10
DHW Sys 1
Guest
Conditioned
HVAC System2 563
10
DHW Sys 1
Registration Number: Registration.Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at 2014-11-16 05:57:36
�t
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MR. STERIN Calculation Date/Time: 05:53, Sun, Nov 16, 2014
Calculation Description: Title 24 Analysis Input File Name: 78400 Coyote Canyon Ct. - T24 Corr111614.xml
CF1R-PRF-01
Page 3 of.10
Seating Area-Add'n
Conditioned
HVAC System2
221
10
DHW Sys 1
OPAQUE SURFACES
01
02
03
04
05
06
07
08
09
10
Name
Zone
Construction
Azimuth
Orientation
Gross Area (Wt
Window and Door
Area (ft2)
Tllt(deg
)
Status
Verified
Existing
Condition
Ri/E (E)
Main House
R-21 Wall,
90
Right
908.3
188.6
90
Existing
No
Re/N (E)
Main House
R-21 Wall
0
Back
1047.5
253.1
90
Existing
No
Le/W (E)
Main House
R-21 Wall
270
Left
908.3
309.8
90
Existing
No
Fr/S
Main House
R-21 Wall
180
Front
1047.5
84
90 .
Existing
No
Roof E
Main House
R730 Roof Attic
1048
Existing
No
Roof W
Main House
R-30 Roof Attic
1050
Existing
No
Roof N
Main House
R-30 Roof Attic
1050
Existing
No
Roof S
Main House
R-30 Roof Attic
1050
Existing
No
Le/W
Bath-Add'n
R-21 Wall
270
Left
116.6
90
Altered .
N/A
Fr/S 2
Bath-Add'n
R-21 Wall
180
Front
116.6
20
90
Altered
N/A
Roof
Bath-Add'n
R-38 Roof Attic
75
New
N/A
Roof 2
Bath-Add'n
R-38 Roof Attic
75
New
N/A
Ri/E (E) 2
Guest
R-21 Wall
90
Right
220.1
19.2
90
Existing
No
Re/N (E) 2
Guest
R-21 Wall
0
Back
240
54.2
90
Existing
No
Le/W (E) 2
Guest
R-21 Wall
270
Left
220.1
29
90
Existing
No
Fr/S (E)
Guest
R-21 Wall
180
Front
120
90
Existing
No
Roof E 2
Guest
R-30 Roof Attic
281
Existing
No
Roof W 2
Guest
R-30 Roof Attic
282
Existing
No
Ri/E
Seating Area-Add'n
R-21 Wall
90
Right
116.6
96
90
New
N/A
Le/W 2
Seating Area-Add'n
R-21 Wall
270
Left
173.3
20
90
New
N/A
Roof 3
Seating Area-Add'n
R-38 Roof Attic
111
New
N/A
Roof 4
Seating Area-Add'n
R-38 Roof Attic
110
New
N/A
Registration Number: Registration Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at 2014-11-16 05:57:36
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MR. STERIN Calculation Date/Time: 05:53, Sun, Nov 16, 2014
Calculation Description: Title 24 Analysis Input File Name: 78400 Coyote Canyon Ct. - T24 Corr111614.xml
CF1R-PRF-01
Page 4 of 10
ATTIC
01
02
03
04
05
06
09
10
11
Name
Construction
Roof Rise
Roof
Reflectance
Roof
Emittance
Radiant
Barrier
Cool Roof
Status
Verified
Existing
Condifion
Attic
Attic Roof Cons
4
0.1
0.85
No
No
Existing
No
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards- 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at 2014-11-16 05:57:36
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MR. STERIN Calculation Date/Time: 05:53, Sun, Nov 16, 2014
Calculation Description: Title 24 Analysis Input File Name: 78400 Coyote Canyon Ct. - T24 Corrl 11614.xml
CF1R-PRF-01
Page 5 of 10
WINDOWS
01
02
03 04
05
06
07
08
09
10
11
Name
Side of Building
Width(ft Height
) (ft)
Multiplie
r
Area (ft2)
U -factor
SHGC
Exterior Shading
Status
Verified
Existing
Condition
(2) 2680 Fr.Dr. [E]
RUE (E)
---- ----
1
40.0
0.55
0.67
Insect Screen (default)
Existing
No
(2) 2680 Fr.Dr. [E) 2
RUE (E)
---- ----
1
40.0 j
0.55
0.67
Insect Screen (default)
Existing
No
2680 Fr.Dr. (E]
Ri/E (E)
---- ----
1
20.0
0.55
0.67
Insect Screen (default)
Existing
No
4030 Wdw [E]r
RUE (E)
---- ----
1
12.0
0.71
0.73
Insect Screen (default)
Existing
No
(2) 2670 Fr.Dr. [E]
RUE (E)
---- ----
1
35.0
0.55
0.67
Insect Screen (default)
Existing
No .
26310 Wdw [E]
RUE (E)
---- ---
1
9.6
0.71
0.73
Insect Screen (default)
Existing
No
30310 Wdw [E]
RUE (E)
---- ----
1
11.5
0.71
0.73
Insect Screen (default)
Existing
No
3036 Wdw [E]
RUE (E)
---- ----
1
10.5
0.71
0.73
Insect Screen (default)
Existing
No
2050 Wdw [E]
RUE (E)
---- ---
1
10.0
0.71
0.73
Insect Screen (default)
Existing
No
3050 Wdw [E]
Re/N (E)
---- ----
1
15.0
0.71
0.73
Insect Screen (default)
Existing
No
(2) 2670 Fr.Dr. [E] 2
Re/N (E)
---- ----
1
35.0
0.55
0.67
Insect Screen (default)
Existing
No
26310 Wdw [E] 2
Re/N (E)
---- ---
1
9.6
0.71
0.73
Insect Screen (default)
Existing
No
26310 Wdw [E] 3
Re/N (E)
---- ----
1
9.6
0.71
0.73
Insect Screen (default)
Existing
No
34410 Wdw [E]
Re/N (E),
---- ----
1
16.1
0.71
0.73
Insect Screen (default)
Existing
No
34410 Wdw [E] 2
Re/N (E)
-- ---
1
16.1
0.71
0.73
Insect Screen (default).
Existing
No
46210 Wdw [E]
Re/N (E)
---- -
1
11.3
0.71
0.73
Insect Screen (default)
Existing
No
40410 Wdw [E]
Re/N (E)
---- ---
1
19.3
0.71
0.73
Insect Screen (default)
Existing
No
46410 Wdw [E]
Re/N (E)
-- ---
1
22.2
0.71
0.73 -
Insect Screen (default)
Existing
No
40410 Wdw [E] 2
Re/N (E)
---- ----
1
19.3
0.71
0.73
Insect Screen (default)
Existing
No
(2) 2670 Fr.Dr. (E) 3
Re/N (E)
---
1
35.0
0.55
0.67
Insect Screen (default)
Existing
No
26310 Wdw [E] 4
Re/N (E)
---- ----
1
9.6
0.71
0.73
Insect Screen (default)
Existing
No .
(2) 2670 Fr.Dr. [E] 4
Re/N (E)
---- ----
1
35.0
0.55
0.67
Insect Screen (default)
Existing
No
110310 Wdw [E]
Le/W (E)
----
1
7.0
0.71
0.73
Insect Screen (default)
Existing
No
110310 Wdw [E] 2
Le/W (E)
---- ----
1
7.0
0.71
0.73
Insect Screen (default)
Existing
No
34410 Wdw [E] 3
Le/W (E)
---- ----
1
16.1
0.71
0.73
Insect Screen (default)
Existing
No
(2) 2670 Fr.Dr. [E] 5
Le/W (E)
---- ----
1
35.0
0.55
0.67
Insect Screen (default)
Existing
No
34410 Wdw [E] 4
Le/W (E)
---- ----
1
16.1
0.71
0.73
Insect Screen (default)
Existing
No
3070 Fr.Dr. [E]
Le/W (E)
---- ----
1
21.0
0.55
0.67
Insect Screen (default)
Existing
No
16410 Wdw [E]
Le/W (E)
---- ----
1
7.2
0.71
0.73
Insect Screen (default)
Existing
No
Registration Number: Registration Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at 2014-11-16 05:57:36
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MR. STERIN Calculation Date/Time: 05:53, Sun, Nov 16, 2014
Calculation Description: Title 24 Analysis Input File Name: 78400 Coyote Canyon Ct. - T24 Corr111614.xml
CF1R-PRF-01
Page 6 of 10
50410 Wdw [E]
Le/W (E) --
--- 1
24.2
0.71
0.73
Insect Screen (default)
Existing
No
16410 Wdw [EJ 2
Le/W (E) --
--- 1
7.2
0.71
0.73
Insect Screen (default)
Existing
No
3016 Wdw [E]
Le/W (E) --
--- 1
4.5
0.71
0.73
Insect Screen (default)
Existing
No
3016 Wdw [E] 2
Le/W (E) --
--- 1
4.5
0.71
0.73
Insect Screen (default)
Existing
No
(2) 2680 Fr.Dr. [E] 3
Le/W (E) --
--- 1
40.0
0.55
0.67
Insect Screen (default)
Existing
No
(2) 2680 Fr.Dr. [E] 4
Le/W (E) --
--- 1
40.0
0.55
0.67
Insect Screen (default)
Existing
No
(2) 2680 Fr.Dr. [E] 5
Le/W (E) --
--- 1
40.0
0.55
0.67
Insect Screen (default)'
Existing
No
(2) 2680 Fr.Dr. [E] 6
Le/W (E) --
--- 1
40.0
0.55
0.67
Insect Screen (default)
Existing
No
46410 Wdw (E) 2
Fr/S --
--- 1
22.2
0.71
0.73
Insect Screen (default)
Existing
No
40410 Wdw [E] 3
Fr/S --
--- 1
19.3
0.71
0.73
Insect Screen (default)
Existing
No
(2) 2680 Fr.Dr. [E] 7
Fr/S --
--- 1
40.0
0.55
0.67
Insect Screen (default)
Existing
No
2.5' Half Circle Wdw [E]
Fr/S --
--- 1
2.5
0.71
0.73
Insect Screen (default)
Existing
No
(B) 4050 Wdw [New)
Fr/S 2 --
--- 1
20.0
0.51
0.26
Insect Screen (default)
New
N/A
26310 Wdw (E] 5
RUE (E) 2 --
--- 1
9.6
0.71
0.73
Insect Screen (default)
Existing
No
26310 Wdw [E] 6
Ri/E (E) 2 --
--- 1
9.6
0.71
0.73
Insect Screen (default)
Existing
No
26310 Wdw [E] 7
Re/N (E) 2 --
--- 1
9.6
0.71
0.73
Insect Screen (default)
Existing
No
26310 Wdw [E] 8
Re/N (E) 2 --
--- 1
9.6
0.71
0.73
Insect Screen (default)
Existing
No
(2) 2670 Fr.Dr. [E] 6
Re/N (E) 2 --
--- 1
35.0
0.55
0.67
Insect Screen (default)
Existing
No
30310 Wdw [E] 2
Le/W (E) 2 --
--- 1
11.5
0.71
0.73
Insect Screen (default)
Existing
No
30310 Wdw [E] 3
Le/W (E) 2 --
--- 1
11.5
0.71
0.73
Insect Screen (default)
Existing
No
2030 Wdw [E]
Le/W (E) 2 --
--- 1
6.0
0.71
0.73
Insect Screen (default)
Existing
No
(2) 3080 Fr.Dr. [New]
RUE --
--- 1
48.0
0.37
0.17
Insect Screen (default)
New
N/A
(2) 3080 Fr.Dr. [New] 2
RUE --
--- 1
48.0
0.37
0.17
Insect Screen (default)
New
N/A
(A) 5040 Wdw [New]
Le/W 2 --
--- 1
20:0
0.51
0.26
Insect Screen (default)
New
N/A
DOORS
01
02
03
04
05
06
Name
Side of Building
Area (ft)
U -factor
Status
Verified Existing Condition
4080
Re/N (E)
32.0
0.50
Existing
No
40802
Fr/S
32.0
0.50
Existing
No
40803
Fr/S
32.0
0.50
j Existing
No
Registration Number: Registration Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at 2014-11-16 05:57:36 -
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MR. STERIN
Calculation Description: Title 24 Analysis
Calculation Date/Time: 05:53, Sun, Nov 16, 2014
Input File Name: 78400 Coyote Canyon Ct. - T24 Corr111614.xmi
CF1 R -PRF -01
Page 7 of 10
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
Construction Name
Surface Type
Framing
Total Cavity R -value
Assembly Layers
Zone
Area (ft2)
2x4 Top Chord of Roof
Edge Insul. R -value
Cavity/Frame: no insul. /2x4 Top Chrd
Attic Roof Cons
Attic Roofs
Truss @ 24 in. O.C.
- no insulation -
Roof Deck: Wood Siding/sheathing/decking
4198
0.1
- none -
0.8
• Roofing: Light Roof (Asphalt Shingle)
Existing
No
Slab -on -Grade 2
Bath-Add'n
• Inside Finish: Gypsum Board
R-21 Wall
Exterior Walls
2x6 @ 16 in. O.C.
R 21
Cavity/Frame: R-211 W
No
Slab -on -Grade 3
Guest
563
• Exterior Finish: Wood Siding/sheathing/decking
- none -
0.8
No
Existing
• Inside Finish: Gypsum Board
R-30 Roof Attic
Ceilings (below attic)
2x4 @ 24 in. O.C.
R 30
Cavity/Frame: R-9.1 /2x4
0
No
New
No
• Over Floor Joists: R-20.9insul.
• Inside Finish: Gypsum Board
R-38 Roof Attic
Ceilings (below attic)
2x4 @ 16 in. O.C.
R38
Cavity/ Frame: R-9.1 /2x4
• Over Floor Joists: R-28.9insut
SLAB FLOORS
01
02
03
04
05
06
07
08
09
Name
Zone
Area (ft2)
Perimeter
(ft)
Edge Insul. R -value
Carpeted
Fraction
Heated
Status
Verified
Existing .
Condition
Slab -on -Grade
Main House
4198
0.1
- none -
0.8
No
Existing
No
Slab -on -Grade 2
Bath-Add'n
150
0.1
- none -
0
No
New
No
Slab -on -Grade 3
Guest
563
0.1
- none -
0.8
No
Existing
No
Slab -on -Grade 4
Seating Area-Add'n
221
0.1
- none -
0
No
New
No
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage ACH @ 60 Pa
Not Required Not Required Not Required --
Registration Number: Registration Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at 2014-11-1605:57:36
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MR. STERIN Calculation Date/Time: 05:53, Sun, Nov 16, 2014
Calculation Description: Title 24 Analysis Input File Name: 78400 Coyote Canyon Ct. - T24 Corr111614.xml
C F1 R -PRF -01
Page 8 of 10
WATER HEATING SYSTEMS
01
02
03
01
02
D3
04
05
06
Name '
Distribution Type
Number of Heaters
Solar Fraction (%)
Status
Verified Existing
Condition
DHW Sys 1
Standard
1
Annual
Existing
No
DHW Sys 1
Standard
2
Annual
Existing
No
DHW Sys 1
Standard
3
Annual
Existing
No
WATER HEATERS
01
02
03
04
01
01
02
03
04
06
06
07
08
Name
Heater Element Type
Tank Type
Tank Volume
(gal)
Energy Factor or
Efficiency
Input Rating
Tank Exterior
Insulation R -value
Standby Loss
(Fraction)
DHW Heater 1
Natural Gas
Small Storage
50
0.575 EF
40000-Btu/hr
0
0
DHW Heater 1
Natural Gas
Small Storage
5D
0.575 EF
40000-Btu/hr
0
0
DHW Heater 1
Natural Gas
Small Storage
50
0.575 EF
40000-Btu/hr
0
0 :d
WATER HEATING - HERS VERIFICATION
01
02
03
04
01
02
03
04
06
06
07
Name
Pipe Insulation
Parallel Piping
Compact Distribution
Point -of Use
Recirculation with
Manual Control
Recirculation with
Sensor Control
DHW Sys 1
n/a
n/a
n/a
n/a
n/a
n/a
DHW Sys 1
n/a
n/a
n/a In/a
Name Ducted
n/a
n/a
DHW Sys 1
n/a
n/a
n/a In/a
HVAC System -
In/a
In/a
HVAC SYSTEMS
01
02
03
04
06
06
07
08
09
Heating System
Cooling System
Distribution
Fan
Floor Area
Verified Existing
Name
System Type
Name Ducted
Name Ducted
System
System
Served
Status
Condition
HVAC System -
Other.Heating and
Heating
Yes
Cooling
Yes
Air Distribution
HVAC Fan
4348
Existing
No
Main Housel
Cooling System
Component 1
Component 1
System 1
1
HVAC System2
Other Heating and
Heating
Yes
Cooling
Yes
Air Distribution
HVAC Fan
784
Existing
No
Cooling System
Component 2
Component 2
System 2
2
Registration Number:" Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at 2014-11.16 05:57:36
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MR. STERIN
Calculation Description: Title 24 Analysis
C F1 R -PRF -01
Calculation Date/Time: 05:53, Sun, Nov 16, 2014 Page 9 of 10
Input File Name: 78400 Coyote Canyon Ct. - T24 Corr111614.xml
HVAC - HEATING SYSTEMS
01
02
01
02
03
Name
Type
Efficiency
Heating Component 1
CntrlFurnace - Fuel -fired central furnace
78 AFUE
Heating Component 2
CntrlFurnace - Fuel -fired central furnace
78 AFUE
HVAC -COOLING SYSTEMS
01
02
03 04
06
06
07
04
06
Efficiency
07
Multi -speed
09
Name
System Type •
EER SEER
Zonally Controlled
Compressor
HERS Verification
Cooling Component '1
SplitAirCond - Split air conditioning
8.488
9.7
No
No
N/A
Duct Leakage
system
Location
Location
Bypass Duct
Status
Condition
Cooling Component 2
SplitAirCond - Split air conditioning
8.488
9.7
No
No
N/A
None
system
No
N/A
System 1
specified)
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
06
06
07
O9
09
09
Insulation
Supply Duct
Return Duct
Verify Existing
HERS
Name
Type
Duct Leakage
R -value
Location
Location
Bypass Duct
Status
Condition
Verification
Air Distribution
Ducts located in attic
Existing (not
6
Attic
Attic
None
Existing
No
N/A
System 1
specified)
Air Distribution
Ducts located in attic
Existing (not
4.2
Attic
Attic
None
Existing
No
N/A
System 2
specified)
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency.Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at 2014-11-16 05:57:36
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01
Project Name: MR. STERIN Calculation Date/Time: 05:53, Sun, Nov 16, 2014 Page 10 of 10
Calculation Description: Title 24 Analysis Input File Name: 78400 Coyote Canyon Ct. - T24 Corr111614.xml
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Santiago Lopez-Ocampo
Company:
Signature Date:
Santiago Lopez-Ocampo
11/16/2014
Address:
CEA/HERS Certification Identification (If applicable):
P.O. Box 1018
City/StateZip:
a Quinta, Ca 92247
Phone:
760.485.8927
RESPONSIBLE PERSON'S DECLARATION STATEMENT
certify the following under penalty of perjury, under the laws of the State of California:
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name:
Responsible Designer Signature:
Eduardo Escobar
Company:
Date Signed:
ESCOBAR DESIGN
Address:
License:
43927 Pacific Ave.
City/State/Zip:
Phone:
Indio, Ca 92201
(760) 289-9221
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at 2014-11-16 05:57:36
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
MR. HENRIK STERN
Building Type m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Addition/Alteration 11111612014
Date
Project Address
78400 Coyote Canyon Ct. - APN. 770-240
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,132
Addition
371
# of Units
1
INSULATION
Construction Type
Area
Cavi (ft) Special Features Status
Slab Unheated Slab -on -Grade
- no insulation 4,761 Perim = 0'
Existing
Wall Wood Framed
R 21 3,678
Existing
Door Opaque Door
- no insulation 96
Existing
Demising Wood Framed
R 19 932
Existing
Roof Wood Framed Attic
R30 4,761
Existing
Demising Wood Framed
R 13 116
Existing
Slab Unheated Slab -on -Grade
- no insulation 371 Perim = 0'
New
Wall Wood Framed
R 21 213
Altered
FENESTRATION
Orientation Area(ft)
I Total Area: 1.074 Glazing Percentage: 20.9 %
U -Fac SHGC Overhang Sidefins
New/Altered Average U -Factor. 0.59
Exterior Shades Status
Right (E) 135.0
0.550
0.67 none none
Bug Screen Existing
Right (E) 72.8
0.710
0.73 none none
Bug Screen Existing
Rear (N) 167.3
0.710
0.73 none none
Bug Screen Existing
Rear (N) 140.0
0.550
0.67 none none
Bug Screen Existing
Left (Kq 122.8
0.710
0.73 none none
Bug Screen Existing
Left (W) 216.0
0.550
0.67 none none
Bug Screen Existing
Front (S) 44.0
0.710
0.73 none none
Bug Screen Existing
Front (S) 40.0
0.550
0.67 none none
Bug Screen Existing
Front (S) 20.0
0.510
0.26 none none
Bug Screen New
Right (E) 96.0
0.370
0.17 none none
Bug Screen New
Left (lN) 20.0
0.510
0.26 none none
Bug Screen New
HVAC SYSTEMS
Heating
Min. Eff
Cooling Min. Eff
Thermostat Status
3 Central Furnace
78% AFUE
Split Air Conditioner 9.7 SEER
Setback
Existing
1 Central Furnace
78% AFUE
Split Air Conditioner 9.7 SEER
Setback
Existing
HVAC DISTRIBUTION
Location Heating
Cooling Duct Location
Duct
R -Value Status
HVAC System - Main Hous Ducted
Ducted Attic
6.0
Existing
HVAC System Ducted
Ducted Attic
4.2
Existing
WATER HEATING
Type
Gallons Min. Eff Distribution Status
Ener Pro 6.3 by Ener Soft User Number. 5732
RunCode: 2014-11-16T05:59:30
ID: LQ 102614Con11161-
Pae 13 of 19
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
MR. HENRIK STERIN
Building Type m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Addition/Alteration 111116)2014
Date
Project Address
78400 Coyote Canyon Ct. - APN. 770-240
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
1 5,132
Addition
371
# of Units
1
INSULATION Area
Construction Type Cavi (ft) Special Features Status
Roof Wood Framed Attic R38 371 New
Wall Wood Framed R 21 174 New
FENESTRATION Total Area: 1.074 Glazi Percentage: 20.9 % New/Altered Average U-Factor. 0.59
Orientation Area ft2 U-Fac SHGC Overhang Sidefins Exterior Shades Status
HVAC SYSTEMS
Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R-Value Status
WATER HEATING
Type Gallons Min. Eff Distribution Status
Ener Pro 6.3 by Ener Soft User Number. 5732 RunCode: 2014-11-16705:59:30 ID: LQ102614Con-11161�
Pae 14 of 19
MANDATORY MEASURES SUMMARY: Residential (Page 1 of 3 MF -IR
Project Name
Date
MR. HENRIK STERIN
11/16/2014
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
110.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§110.6(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
110.7: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
110.8(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -2R Form.
§110.8(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §110.8(1) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§1 50.0 a : Minimum R-30 R-19 for Alterations insulation in wood -frame ceiling orequivalent U -factor.
150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
*§1 50.0 c : Minimum R-13 insulation in 2x4 wood -frame wall R-19 in 2x6 orequivalent U -factor.
*§1 50.0 d : Minimum R-19 insulation in raised wood -frame floor orequivalent U -factor.
150.0 : Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form.
150.0 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150.0(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0 permAnch and shall be protected from physical damage and UV light deterioration.
§150.0(q) Fenestration Products. Fenestration separating conditioned space from unconditioned space or outdoors shall meet the
requirements of either Item 1 or 2 below:
1. Fenestration, including skylight products, must have a maximum U -factor of 0.58.
2. The weighted average U -factor of all fenestration, including skylight products, shall not exceed 0.58.
EXCEPTION to Section 150.0(q)1: Up to 10 square feet of fenestration area or 0.5 percent of the Conditioned Floor Area, whichever is
greater, is exempt from the maximum U -factor requirement
150.0 r Solar Ready Buildings. Shall meet the requirements of Section 110.10 applicable to the building project
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150.0 e 1 A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150.0(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§110.3(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §110.3(c)5.
§110.5: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150.0(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
150.0(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 11 0.2 c .
§150.00)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally
wrapped with insulation having an installed thermal resistance of R-12 or greater.
§150.00)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
EnergyPro 6.3 by EnergySoft User Number. 5732 Q LQ 102614Con-11161- Page 15 of 19
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1R
Project Name
Date
MR. HENRIK STERIN
11/16/2014
§150.00)2A: All domestic hot water system piping conditions listed below, whether buried or unburied, must be insulated per TABLE
120.3-A.
i. The first 5 feet (1.5 meters) of hot and cold water pipes from the storage tank.
ii. All piping with a nominal diameter of 3/4 inch (19 millimeter) or larger.
iii. All piping associated with a domestic hot water recirculation system regardless of the pipe diameter.
iv. Piping from the heating source to storage tank or between tanks.
v. Piping buried below grade.
vi. All hot water pipes from the heating source to the kitchen fixtures.
§150.00)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards
Table 120.3-A.
150.00)3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§150.00)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
§150.0(m)l: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC
Sections 601, 602, 603, 604, 605 and Standard 6-5; supply -air and retum-air ducts and plenums are insulated to a minimum installed
level of R-6 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that
meets the applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic
or tape is used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150.0(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150.0(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150.0(m)7: Exhaust fans stems have back draft or automatic dampers.
§150.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150.0(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150.0 m 10: Flexible ducts cannot have porous inner cores.
§150.0(n)l : Systems using gas or propane water heaters, whether tank or on -demand, to serve individual dwelling units shall include
all the following components:
A. A 120V electrical receptacle that is within 3 feet from the water heater and accessible to the water heater with no obstructions;
B. A Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the space where the water
heater is installed;
C. A condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining
without pump assist,
D. A gas supply line with a capacity of at least 200,000 Btulhr.
§150.0(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2 Ventilation and Acceptable Indoor Air Quality
in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in
Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§110.4(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater, a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
110.4(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off- eak'electric demand periods.
150.0 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150.0
Residential Lighting Measures:
§150.0(k)1A: Installed luminaires shall be classified as -high -efficacy or low -efficacy for compliance with Section 150.0(k) in accordance
with TABLE 150.0-A or TABLE 150.0-B, as applicable.
150.0 k 1 C: The wattage of permanently installed luminaires shall be determined asspecified by §130.0(c).
150.0 k 1 D: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency - 20 kHz.
§150.0(k)l E: Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume
no more than five watts of power per luminaire or exhaust fan as determined in accordance with Section 130.0(c). Night lights shall not
be required to be controlled by vacancy sensors.
EnergyPro 6.3 byEnergySoR User Number. 5732 ID: LQ102614Corr11161z Page 16 of 19
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 WAR
Project Name
Date
MR. HENRIK STERIN 711/16/2014
150.0 k 1 F: Lighting integral to exhaust fans, in rooms other than kitchens shall meet the applicable requirements of 150.0 k).
150.0(k)2: All switching devices and controls shall meet the requirements of §150.0(k)2.
§150.0(k)3: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft' or 100 watts
for dwelling units larger than 2,500 ft' may be exempt from the 50 percent high efficacy requirement when all
lighting in the kitchen is controlled in accordance with the applicable provisions in Section 150.0(k)2, and is also
controlled by vacancy sensors or dimmers.
§150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
§150.0(k)5: Lighting installed in bathrooms shall meet the following requirements:
A. A minimum of one high efficacy luminaire shall be installed in each bathroom; and
B. All other lighting installed in each bathroom shall be high efficacy or controlled by vacancy sensors.
§150.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be
high efficacy, or shall be controlled by either dimmers or vacancy sensors.
EXCEPTION 1: Luminaires in closets less than 70 square feet.
EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site.
§150.0(k)8: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the luminaire is airtight with air
leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150.0(k)9A: For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on
the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of items
ii or iii below; and
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and
automatically reactivates the motion sensor within 6 hours
iii. Controlled by one of the following methods:
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and
which is programmed to automatically tum the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements:
At a minimum provides the functionality of an astronomical time clock in accordance with Section 110.9;
meets the Installation Certification requirements in Section 130.4; meets the requirements for an EMCS in
Section 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically tum the outdoor lighting OFF during daylight hours.
§150.0(k)9A: For low-rise multi -family residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and
outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
following requirements:
i. Shall comply with Section 150.0(k)9A; or
ii. Shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by Section 150.0(k)9B or
Section 150.0(k)9D shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall
comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)10: Internally illuminated address signs shall comply with Section 140.8; OR not contain a screw -base socket, and consume
no more than five watts of power as determined according to §130.0(d).
§150.0(k)11: Lighting for residential parking garages for eight or more
vehicles shall comply with the applicable requirements for nonresidential garages in Sections 110.9, 130.0, 130. 1,
130.4, 140.6, and 141.0.
§150.0(k)12A. In a low-rise multi -family residential building where the total interior common area in a single building equals 20 percent
or less of the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
§150.0(k)12B. In a low-rise multi -family residential building where the total interior common area in a single building equals more than
20 percent of the floor area, permanently installed lighting in that building shall:
i. Comply with the applicable requirements in Sections 110.9, 130.0, 130.1, 140.6, and 141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
in rens and egress.
EnergyPro 6.3 by EnergySoff User Number. 5732 M: LQ 102614Con-11161, Page 17 of 19
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. HENRIK STERIN
Date
11/16/2014
System Name
HVAC System - Main House
Floor Area
4,348
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
3
COIL
CFM
Total Room Loads 4,445
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 1 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK
Sensible
85,156
0
5,811
0
0
0
5,811
1 96,779
COIL HTG.
Latent CFM
5,212 1,239
0 0
57212
PEAK
Heating System
Sensible
Output perSystem 0
47,239
Total Output Btuh 0
Output (Btuh/ ) 0.0
2,725
Cooling System
0
Output per System 1
0
Total Output Btuh 3
0
Total Output (rons) 0.0
2,725
Total Output Btuh/s 0.0
Total output s on 17,392,000.0
1 52,688
Air System
CFM per System
0
HVAC EQUIPMENT SELECTION
Airflow (cfm)
0
Default FAlJ/AC 1992 - 2005
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
3
3
0 0
0 0
Aug 3 PM Jan 1 AM
Airflow (cfm/ ) 0.00
Airflow cfmfTon 0.0
Outside Air %) 0.0%
Outside Air cfm/s 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
Outside Air Ar
0 cfm
67 OF
67 OF 105 OF
Heating Coil
r
104 OF
ROOM
68 °F
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside AirAr
0 cfm
77/63°F
4I
77/63°F 55/54°F
-
Cooling Coil
48.7%
57 / 55 OF
I ROOM
75/62°F
EnergyPro 6.3 by EnergySoft
User Number. 5732 RunCode: 2014-11-16705:59:30
ID: LQ102614Con11161i Page 18 of 19
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. HENRIK STERIN
Date
11/16/2014
System Name
HVAC System
Floor Area
784
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING PEAK
CFM Sensible.
Total Room Loads 804 15,392
Return Vented Lighting 0
Return Air Ducts 1,305
Return Fan 0
Ventilation o 0
Supply Fan 0
Supply Air Ducts 1,305
TOTAL SYSTEM LOAD 18,003
COIL HTG.
Latent CFM
940 259
0 0.
940
PEAK
Heating System
Sensible
Output per System 0
9,741
Total Output Btuh 0
Output (Btu h/ ) 0.0
692
Cooling System
0
Output r System 1
o
Total Output Btuh 1
0
Total Output (Tons) 0.0
692
Total Output Btuh/s 0.0
Total Output on 9,408,000.0
11,125
Air System
CFM per System
0
HVAC EQUIPMENT SELECTION
Airflow (cfm)
0
Default FAU/AC 1992 - 2005 1
Total Adjusted System Output 1
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
0 0
0 0
Aug 3 PM Jan 1 AM
Airflow (cfm/ 0.00
Airflow cfm/Ton 0.0
Outside Air (%) 0.0 °,6
Outside Air cfm/s 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 dm
66 °F
66 OF 105 OF
Heating Coil
103 OF
ROOM 11
68 °F
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 77/63°F 55/54°F
Outside Air Ar
0 cfm Cooling Coil
48.7%
°
t T
Ibk A
BUILDING & SAFETY DEPT.
57 / 55 OF
I ROOM In
75/62°F
I
ergyPro erPJ
se Nu, ber. 5738R
RunCode: 2014-11-1 6 705:59:30 ID: LQ102614Con-11161z Page 19 of 19
FOR CONSTRUCTION