0312-167 (COMB) Structural Calcsti
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
408 S. Stoddard Ave, San Bernardino, CA 92401
IL Phone: (909) 889-0115 Fax: (909) 889-0455 E-mail: abarajas@knapptang.com
April 1, 2004 Page 3 of 38
Re: A Custom House for:
Mr. & Mrs. Frank Wade
The Quarry
La Quinta, California 92253
Plan- Check -#0312-029 (V check) Revision louds
Address to Interior Design
Plan check corrections -------Description
1 See pages 9 thru 13 of the package submitted.
2 Yes, detail 1 thru 3 sheet S2.0 shows the metal deck.connection and it's
bearing condition to block wall along with the correct dowel requirements.
.3 Yes, see detail '15-S 1.0 .clouded.
4 Retaining wall coordinated with revision.3 dated January 15, 2004.
5 Yes, revised pad .footing schedules sheet S2.0 & S2.1 and see page 14 of
the package submitted.
6 Yes, clouded sheet S2.1 and refer to detail 6 thru 9 sheet.S3.1 ,also clouded
sheet S4.0 and refer to detail 14 thru 18 sheet S5.4.
7 See page,l4 of the package submitted and pages 56 thru 70 of the original
calculations.
8 See page 15 of the package submitted regarding load to post.
9 & 10 Tji / steel K3 joists worst case design included into package see sheets 6
and 7 for all information.
11 Seepage 15 of package for floor design breakdown calculations.
12 See pages 16 & 17 of package for beam reaction.
13 See pages 18 .&'19 of package for beam RB 31 of the original calculations.
14 See pages 20 thru 23 of package regarding frame design at foundation.
15 -See details 3 & 9 sheet S5.4 for beam connection to fireplace.
16 See pages 24 thru 31 of package for design of "rho".
17 See page 32 of -package for moment frame joint connections.
18 See page 32 of package for drift design for frame.
19 See page 33 of package for steel column design.
20 Typical detail 11-S3.1 for foundation and 3=S3.4 for steel beam.
21 Revised sheet S4.0 and added detail 16-S5.0 and 14-S5.1 to the area.
22 Yes, see revised calculation sheet 8 and structural plan sheet S2.1.
23 Yes, new note added #23 to sheet S2.0 clouded.
If you have any question, please.contact us at the above telephone numbers.
Sincerely,
ALB.
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
408 S. Stoddard Ave, San Bernardino, CA 92401
Phone: (909) 889-0115 Fax: (909) 889-0455 E-mail: abarajas@knapptang.com
April 1, 2004 Page 4 of 38
Re: A Custom House for:
Mr. & Mrs. Frank Wade
The Quarry
La Quinta, California 9.225
Interior Design Revision louds
Address to Interior Design
Clarifications and Changes ------- Description
1 Kitchen / Butler area on sheet S2.1 clouded for the clarification to shear
wall / holdown per design change by interiors.
2 See page 34 of the submitted package for new shear wall design.
3 See page 32 & 33 of the submitted package for the B-1 and. B-2 new beam
design for kitchen./ butler area change.
4 Kitchen / Butler area on sheet S4:0 clouded for the clarification to shear
wall relocation and beams locations per design change by interiors.
If you have any question, please contact us at the above telephone numbers.
Sincerely,
AL B.
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
408 S. Stoddard Ave, San Bernardino, CA 92401
Phone: (909) 889-0115 Fax: (909) 889-0455 E-mail: abarajas@knapptang.com
SUBMITTING REVISED
CALCULATIONS .
For
A Custom House for:
Mr. &. Mrs. FRANK. WADE .
The Quarry
79-720 (Lot 64) Tom Fazio Lane
La Quinta, California 92253
ZlqHESS
0 4
d Exp. 3-5 1 "
CMN-
�rF OF C A�
Date:
April 1, 2004
Prepared By:
AL B.
Page 5 of 38
STANDARD LOAD TABLE/OPEN WEB STEEL JOISTS, K -SERIES
Based on a Maximum Allowable Tensile Stress of 30 ksi
41
Joist
Desi nation
18K3
18K4 18K5 18K6
18K7
18K9
18K10
20K3
20K4
20K5 20K6 20K7 20K9 20K10 22K4 22K5
22K6 22K7
22K9 22K10
22K11
Depth In.
18
18
18
18
18
18
18
20
20
20
20
20
20
20
22 22
22 22
Approx. Wt.22
22
22
lbs./ft.
6.6
7.2
7.7
8.5
9
10.2
11.7
6.7
7.6
8.2
8.9
9.3
10.8 12.2 8 8.8 9.2 9.7 11.3
12.6
13.8
Span (ft.)
+18
550
550
550
550
550
550
550
550
550
550
550
550
550
550
19
514
550
550
550
550
550
550
494
523
523
523
523
523
523
20
463
550
550
550
550
550
550
517
550
550
550
550
550
550
423
490
490
490
490
490
490
517
550
550
550
550
550
550
21420
506
550
550
'5'
550
550
468
550
550
550
550
550
550
364
426
460
460
460
460
460
ii 453
520
520
520
520
520
520
22
382
460
518
550
550
550
550
426
514
550
550
550
550
550
550 550 550
550
550
550
23
316
349
370
420
414
438
438
438
438
393
461
490
490
490
490
490
548 548 548
548
548
548
550
548
276
323
473
362
516
393
550
550
550
389
469
529
550
550
550
550
518 550 550
550
550
550
550
24
320
385
434
473
418
526
418
550
418
344
402
451
468
468
468
468
491 518 518
518
518
518
518
242
284
318
345
382
396
550357
396
430
485
528
550
550
550
475 536 550
550
550
550
550
25
294
355
400
435
485
550
550
302
329
353
396
396
430
448
448
448
431 483 495
495
495
495
495
214
250
281
305
337
377
377
266
312
446
350
486
380
541
550
550
438 493 537
550
550
550
550
26
272
328
369
402
448
538
550
304
366
412
449
421
500
426
550
426
550
381 427 464
474
474
474
474
190
222
249
271
299
354
361
236
277
310
337
373
405
405
404 455 496
338 379
550
550
550
550
27
252
303
342
372
415
498
550
281
339
382416
463
550
550
411
454
454
454
454
374 422
169
198
222
241
267
315
347
211
247
277
301
333
389
389
459
301 337 367
512
550
550
550
28
234
282
318
346
385463
548
261
315
355
386
430
517
550
348 392 427
406
432
432
432
151
1 77
199
216
239
282
331
189
221
248
269
296
353
375
270 302 326
475
364
550
550
550
29
218
263
296
322
359
431
511
243
293
330
360
401
482
550
324 365 398
443
413
413
413
f
136
159
179
194
215
254
298
170
199
223
242
268
317
359
242 272 295
327
532
550
550
^(
30
203
245
276
301
335
402
477
227
274
308
3361
3741
450.
533
302 341 371
387
399
399
31
123
190-1
144
161
175
194
229
269
153
179
201 1
218
242
286
336
219 245 266
413
295
497
349
550
385
550
385
111
229
130
258
281
313
376
446
212
256
289
314
350
421
499
283 319 347
387
465
550
550
32
178..
21&%
146
242
158
264
175
207
243
138
162
182
198
219
259
304
198 222 241
267
316
369
369
101'"
118
132
144
294
159
353
188
418 :,
221
199s
240
271
295
326
395
468
265 299 326
363
436
517
549
33
168'..202; :.
228:•,
248
276
332
393
126;'
187
147
226
165
254
179
199
235
276
180 201 219
242
287
337
355
92
106'" 1Z1-
131
145
171
201
11�%
134
150
277
163
309
181
371
214
440
251
249 281 306
341
410
486
532
34
1585 :'
1'9a3 ',
214R
233
260
312
370
176 . 21Zc x239-
261
290
349
414
164 183 199
235> 265 288
221
261
307
334
321
386
458
120
132
156
184
105','
122
137'
149
165
195
229
149P 167 182
516
35
149? _
1Z9 ::202;
;
220a
245
294
349
1661 '
200'-''
2261
246
274
329
390
202
239
280
314
22:T:. 249a 272
303
364
36
7T
141
90 101"' 110x"
169: 191:" 208 ?
121
143
168
98
112" '•- 126':
137
151
179
210
137,"' ' 153?- 167
185
219
432
257
494
292
70.82:
'
_,
92. :=
101".:
232
111
278
330
157', b
189x
'
2.13
; 232
259
311
369
; 209E `' 236»;; 25T .
286
344
408
467
37
132
154
8& 103
11'5
125:"
139
164
193
,
1261 "1'44F v 153x'
169
201
236
269
148;
1791
20zv; ;
'
220.":
245
294
349
198` -223». '. 243x
271
325
386
442
38
81'
95. ' 106,
115•:•
128
151
178
116' 130> 141;
156
185
217
247
141' .
170.
` '
191';'
208`-1'
232
279
331
187: , 211a;., ; 23a+i
256
308
366
419
39
74
87
98 106x`
118
139
164
107+ = 1'19+' 131T#
144
170
200
228
69
161'-1 ?„
81. '
18.1:." ',198.°-
90-`. '
?:220x`
9w" :`1091'
:266,;
314
178. 200 ,` 21Sa
r•
243
292
347
397
40
129TC
151
98." 110' c 12W,'=
133
157
185
211
12T ..:153•
.•.17T.!'
;
188 .
209.'
2513;.
298
169=• 190x.:• 20T •
23t' ,.27
330
377
a1
64
75
84s
94" .101:"
119 �
140
91 102:: 111`'.: 123''s <
148+
171
195
16T. ' 18 I: ; • 197,:,
220. ;, 264:.314
359
42
8S " 95 10341'x.114,
`'135:^.
159
181
153 : 173 '180
209u 25Z;
299
342
43
79 88. `° 96" ` 1061•
126=
148
168
146' 165• 179.-
200? `•.240;
285
326
44
73' 82 89 `
99 °
117
1.1
157
139:- 157. " 171" � 191.1 ;,229=
272
311
68 76 83' } 92, :'
1094
128 146
41
Slope Factors
How to Use These Tables
1. Calculate actual total load in pounds per linear foot (pit).
2. Select appropriate ROOF JOIST HORIZONTAL CLEAR SPAN. For slopes
greater than 2" per foot, approximate the increased dead load by multi -
Plying the joist horizontal clear span by the SLOPE FACTOR above.
3. Scan down the column to find a TJI® joist that meets or exceeds actual
total load. TOTAL LOAD values are limited to deflection of U180. For
stiffer deflection criteria, use the LIVE LOAD U240 values.
12 9 in 12 10
12 1.250 1
General Notes
• Tables are based on:
— Uniform loads.
— No composite action provided by sheathing.
— More restrictive of simple or continuous span.
— Minimum roof surface slope of 1/4" in 12".
• TOTAL LOAD limits joist deflection to U180.
Roof Joist Horizontal Clear Span
Roof Load Tables 21
`
Trus Joist • TJI® Joist Specifier's Guide 2025 • September
�• Roof -115% and 125% Load Duration
(PLF)
20'
_T
.22'
!
24'
7
(2003
a1
30
---
` D.epth
TJI®
—Total Load
Roof Joist Horizontal Clear Span
.Tot_a_I Load
:Defl.
Total Load
Defl. 1 'Total Load
Defl. 1
Total Load
Defl.
Total Load
Deft.
_1062F
6'
`Snow
8'
Live
Load ;:.Snow
10'
Non-
Snow
12'
.Non-
.Snow
'.Live i
Load Snow
14'
"Live
Load :'SnowSnow
'Non-
16'
.
Depth
TJI®
LO
Defl. ! Total Load Defl.
Total Load
Deft. ' Total Load
Deft.
Total Load
Defl.
Total Load
Defl.
125%
L/240
Snow
Non-
Snow
Live
Load, Snow
Non- Live 1
Snow Load
Snow
Non-
Snow
Live
Load Snow
Non-
Snow
Live
Load .
Snow
Non-
Snow
Live
Load
Snow
Non-
Snow
Live
Load
115%
125%
U240 ; 115%
125% '1/240
115%
125%
U240 : 115%
125%
U240 ;
115%
125%
L/240 ;
115%
125%
L/240
_110
289
314
i 218
237 i
175
190
' 146
159155
'.
109
118
101 !
83
91
69
9'/z"
_210
321
349
242
263 i
194
211
162
176
i
131
142
118
100
108
81
82 '•
230
360
392
' 272
295 `
218
237
` 182
198
196
145
158
128
112
118
88
101
^110
289_
314
218
237
175
190
146
159
'
125
136
'
106
115
'
117%
210
321
349
' 242
263
194
211
162
176
'
139
151
'
122
132
'
".11'/e"
230
360
392
; 272
295 j
218
237-182
105
198
'
156
170
i
137
149
146
360
368
400
277
301 "
223
242
" 186
202
135
159
173
1
140
152
'
79
560
449
488338
110
368
272
295
227
246
';
195
212
1
170
185
'
110
289_
314
' 218
237 ` 1175
210
190
_
' 146
159
' 1
125
136
80
110
119
1
210
321
349
j 242
263 ' 1
194
211
162
176
' 1
139
151
"
122
132
'
14"
_230
360
392
! 272
295 1
218
237
- 1 182_
198
- 1
'156
170
' 1
137
149
'
102
360
368
400
' 277
301
223
242
" 1 186
202
' 1
159
173-
i
140
152
--
148
560
449
488
" 338
368 ' ;
272
295
" 227
246
'98
195
212
!
170
185
'
"
210
321 _349
I
"_ _242
263 " I
194
211_'_!
162
176_
!
139
151
122
132
230_
122
230
160
360
368
392
400
i 272 295 218 237
" 1277 301 223 242
182
198_
' 1156
1 85
170
' 1
'
137
149
72
.366
124
135
1
1 186
202
' 1:_9
159
173
!
140
152
'
94'
560
449
488
; 338
368 j
272
295
' i 227
246
' i
196_
212
`
170
185
124
Slope Factors
How to Use These Tables
1. Calculate actual total load in pounds per linear foot (pit).
2. Select appropriate ROOF JOIST HORIZONTAL CLEAR SPAN. For slopes
greater than 2" per foot, approximate the increased dead load by multi -
Plying the joist horizontal clear span by the SLOPE FACTOR above.
3. Scan down the column to find a TJI® joist that meets or exceeds actual
total load. TOTAL LOAD values are limited to deflection of U180. For
stiffer deflection criteria, use the LIVE LOAD U240 values.
12 9 in 12 10
12 1.250 1
General Notes
• Tables are based on:
— Uniform loads.
— No composite action provided by sheathing.
— More restrictive of simple or continuous span.
— Minimum roof surface slope of 1/4" in 12".
• TOTAL LOAD limits joist deflection to U180.
Roof Joist Horizontal Clear Span
18'
?
20'
_T
.22'
!
24'
26'
28'
` D.epth
TJI®
—Total Load
Defl.
.Tot_a_I Load
:Defl.
Total Load
Defl. 1 'Total Load
Defl. 1
Total Load
Defl.
Total Load
Deft.
`Snow
Non-
:Snow
Live
Load ;:.Snow
Non-
Snow
',Live 1
:Load ';Snow
.Non-
.Snow
'.Live i
Load Snow
•Non-
-Snow
"Live
Load :'SnowSnow
'Non-
Live
Load.Snow
"Non-
Live
'115%
125%
L/240 115%
125%
.11240 115%
125%
1/240 j 1.15%
125%
L/240
.1.15%
125%
1/240 115%
:Snow
'.125%
.Load
<IJ240
..
110
[
I .' 11h"
.• .._210
77
77
: 58 !
—
230
`84
84
63
_110
84
91
82 '•
I.
—
I
210
101
109
96 1
82
89
Z-1 !
j
117%
:230
'112
121
105.E jr:91"Iss 98' " 78'"t
.75
.79
59
•360
124
135
112
122
103
'102.
105
78 82
82
61
560
152
165
:'
137
148
'
'124
135
117 '114
122
91 1
97
97
73 1
79
79
59
110
98
106
80
87
210
'108
118
' I
97
105
-103 1
80
87
79 1
1
I
14"
.230
122
132
1
107
117
112 j
89
•96
86 75
'81
67 ;
;
360
124
135
1
.112
122
'.
102
111
1 93
101
88 I
86
94
70
76
76
57
550
152
165
'
137
148
j
124
135
1 114
124
'
105
114
104 i
'98
106
85
210_
108
118
"
97
106
I
89
96
77
83
i
1
16°
230_
122
132
i
110_
:'
100
108
1 85
93
90 •,
79_
72
.366
124
135
1
112
_119
122
_
' 1:_9
102
111
' 3
_
101
j
86
94'
' !
80
87
76
560
152
165
"
137
148
' 1
124
135
; 114
124
1105
114
'
98
106
'
' Indicates TOTAL LOAD value controls.
Slope Factors
How to Use These Tables
1. Calculate actual total load in pounds per linear foot (pit).
2. Select appropriate ROOF JOIST HORIZONTAL CLEAR SPAN. For slopes
greater than 2" per foot, approximate the increased dead load by multi -
Plying the joist horizontal clear span by the SLOPE FACTOR above.
3. Scan down the column to find a TJI® joist that meets or exceeds actual
total load. TOTAL LOAD values are limited to deflection of U180. For
stiffer deflection criteria, use the LIVE LOAD U240 values.
12 9 in 12 10
12 1.250 1
General Notes
• Tables are based on:
— Uniform loads.
— No composite action provided by sheathing.
— More restrictive of simple or continuous span.
— Minimum roof surface slope of 1/4" in 12".
• TOTAL LOAD limits joist deflection to U180.
STRUCTURAL ENGINEERS, INC
408 SOUTH STOODARD, AVENUE
SAN BERNARDINO, CA. 9 4;01
TELE:. -9:09) 8.89-0.1 15.
FAX (909) 8-89-0455
E-MAIL (KNAPPAECAOLCOM)
:2 - 5Al,')':rW11 076S—)
/vo uP/!�
Z�:e Mott/ (L
14 -7L/d =
5p- /
WAP
6t!5;F (�� o ;>)-742.) It
SHT'M of
LS Of
'? tb-r ve �--- : ---) ....
14-3
x1d1617
0
V= 7/
/70W
ROMEVELD
IAQ4 IIALLEY )W o
A" GM. SLAB OVER
COMPOSITE F=R ow'r,
PM M.A* h
TS 2 VW V2xMb OL
SETMENJOV57 PER
1
PLANS
wl Wo x W AB.'s32 of
-94 SLAB Da*Lq��'
0 16" OL. -i�124
2'
2- 85 Caff. o
TOP OF WALL
GLR
87 VERTS a 16" C r
(BASEMENT SM
PROVIOE'NATER PROOFINS:
PER ARCRL
17 WK. 13LOOK NAIL
pit 2- WHORIZ. d '24' Of,.'
salp 6p4w.,
SPECK, DSFEV ON
--'�09 VERTS 0 16"
(Plltr Simi,
5-185 coff.
TOP 4 amom
2' DLR:
uu�
UK
ti\RETAININQ WALL.
' FUDDLE MELD U2'm b•
� 1•'�5 GONi.
GONG. SLAB OVER
GOPPO'SITE RX DEGK
PER FLAlF
S.
a•
TS 2 V23L2 U2x3/W BLK1S. IN
EETMEEN JOISTS PER FLANS
rd 5/6'm x b• AB: I-32' OL
2- 15 GOVT. •
EXT. 4' GONG. SLAB ON 6RADE
12'
a• 1
TOP OF IY HAL
2- 15 DONT. •
TOP OF WAIL
STL. BAR.JOISTS
•-46' OL: PER PLANS
94 SLAB DOMELS 2•'CL
. CLR
•-Ib' Of.. .
x '
rl VEMS • Ib' C
L.
(BASEMENT SIDE)
PROVIDE WATER
INS;' '
PER AWK.
4
n
W CONG. M=
WALL
W 2- 65 NORM. 4
24' OL.
SOLID GROUT;
SPEUAL NWWl
ON
x5 VERTS • Ib' C
4.
(DIRT Saw
4WCONT. PVC F
ERFORATED „
PIPE WITH 2 CA). -I
T. OF•
0MIED'ROM
PERFORATION .
FACE DOHN RUN
TO DATLKW
5- 55 CONT.
TOP'I BOTTOM
2' GLR
4--0"
/T\RETAININ
WALL -
KN PO & TANG STRUCTURAL ENGINEERS, INC.
Title WADE RESIDENCE
Page: .
%30,b 'OUTH STODDARD AVENUE
Allowable =
Job
Dsgnr: HW
Date: NOV 18',2003
SAN,BERNARDINO, CA 92401
ACI.Factored @ Heel =
Description....
Footing Shear @ To =
22.1 psi OK
_.._...__.
PHONE: 909-889-0115- - -
_......_
...__..
1T -RETAINING WALL ...
93.1 psi
FAX: 909-889-0455
792.0 lbs
Reaction at Bottom =
4,219.9 lbs
' 8.72 psi
Allow 1 -Way Shear =
93.11
'This Wall
in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0
Restrained Retaining Wall Design
ft-#
Stem Weight =
- Build Date : 10 -SEP -2001, (c) 1989-2001
2.75 ft
4,092.0ft-#
Soil Over Heel =
990.0 lbs
I Criteria
L
3,588.8 ft-#
' I Soil Data
900.0 lbs
i Footing Strengths & Dimensions
Retained Height = 12.00 ft
Allow Soil Bearing
= 3,000.0 psf
Toe Width
2.25 ft
Wall height above soil ' = 0.00 ft
Equivalent Fluid Pressure Method
Heel Width
= 1.75
Total Wall Height = 12.00 ft
Heel Active Pressure
= 55.0 psf/ft
Total Footing Widt
=0�
Toe Active Pressure
= 55.0 psf/ft
Footing Thickness
= 18.00 in
To Support Height = 12.00 ft
Top pp 9
Passive Pressure
Water height over heel
= 300.0 psf/ft
= 0.0 ft
Key Width
_
- 0.00 in
Slope Behind Wal = 0.00: 1
FootingIlSoil Frictio
= 0.400
Key Depth
Key Distance from Toe
= 0.00 in
= 0.00 ft
Height of Soil over To = 0.00 in
Soil height to ignore
Soil Density = 110.00 pcf
for passive pressure
= 12.00 in
fc = 3,000 psi 'Fy
= 60,000 psi
Footing Concrete Densit
- 150.00 pcf
Wind on Stem = 0.0 psf
Min. As %
= 0.0018
Cover @'Top = 2.00 in
@ Btm.= 3.00 in
n Summary
Total Bearing Loa = 3,378 Ib
...resultant ecc. = 12.83 in
Soil Pressure @ To =
2,419 psf OK
Soil Pressure @ Hee =
0 psf OK
Allowable =
3,000 psf
Soil Pressure Less Than Allowable
ACI Factored @ Toe =
3,387 psf
ACI.Factored @ Heel =
0 psf
Footing Shear @ To =
22.1 psi OK
Footing Shear @ Hee =
8:7 psi OK
Allowable =
93.1 psi
Reaction at Top =
792.0 lbs
Reaction at Bottom =
4,219.9 lbs
Sliding Calcs Slab Resists All Sliding I
Lateral Sliding Forc = 4,219.9 lbs
J Footing Design Results
»> S
Load & Moment Summary For
i Oe
eel
Factored Pressure =
3,387
0 psf
Mu': Upward =
7,426
0 ft-#
Mu': Downward =
984
1,082 ft-#
Mu: Design =
6,441
1,082 ft-#
Actual 1 -Way Shear =
22.08
' 8.72 psi
Allow 1 -Way Shear =
93.11
93.11 psi
onry
Thickness = 12.00 in
Wall Weight = 124.0 pcf
Stem is FIXED to top of footing
Block Type = Medium Weight
Solid Grouted
'.Design height
Rebar Size
Rebar Spacing
Rebar Placed a
Rebar Depth 'd'
.Design Data
on
fm = 1,500 psi
Fs = 24,000 psi
@ Top Support
fb/FB + fa/Fa =
Moment .... Actu =
Moment..... Allowable =
Shear Force @ this height =
Shear..... Actual =
Shear..... Allowable =
Rebar Lap Required =
Rebar embedment into footing
Stem OK
12.00 ft
# 5
16.00 in
Center
5.75 in
0.000
0.0 ft-#
2,371.7 ft-#
0.0 lbs.
0.00 psi
38.73 psi
25.00 in
Other Acceptable Sizes & Spacings:
Toe: None Spec'd -or-
Heel: None Spec'd -or-
Key: No key defined -or-
Short Term Factor = 1.000
Equiv. Solid Thick. = 11.600 in
n Ratio (Es/Em) = 25.778
Use Special Inspection
Mmax Between
Top &. Base @ Base of Wall
Stem OK
6.65 ft,
# 7
16.00 in
Edge
9.00 in
0.437
2,833.5 ft-#
6,477.9 ft-#
35.00 in
Not req'd, Mu < S ' Fr
Not req'd, Mu < S " Fr
No key defined
Summary of Forces on Footing : Slab RESISTS sliding, stem is FIXED at footing
rurces dcang on Tooang Tor sou pressure
»> S
Load & Moment Summary For
Footing : For Soil Pressure Calcs
Moment @ Top of Footing Applied from Stem
=
-6,336.1 ft-#
Surcharge Over Heel =
lbs
ft
ft-#
Adjacent Footing Load =
lbs
ft
ftp#.
Axial Dead Load on Stem =
lbs
ft
ftp#
Soil Over Toe =
lbs
ft
ft-#
Surcharge Over Toe =
lbs
ft
ft-#
Stem Weight =
1,488.0 lbs
2.75 ft
4,092.0ft-#
Soil Over Heel =
990.0 lbs
3.63 ft
3,588.8 ft-#
Footing Weight =
900.0 lbs
2.00 ft
1,800.0 ft-#
Total Vertical Force =
3,378.0 lbs
Base Moment
3,144.6 ft-#
Soil Pressure Resulting Moment = 31611.41:4
Stem OK
0.00 ft
7
16.00 in
Edge
9.00 in
0.978
6,336.1 ft-#
6,477.9 ft-#
3,168.0 lbs
33.28 psi
38.73 psi
13.42 in'
Forces are restrained by the adjacent slab
GY//a!iCl .
A
S- rS CONT.
TOP a BOTTOM
r LCR.
S LLR:
4'-4-
2 \RETAININQ7
'-0'\RETAINING WALL
- r.r-o•
• �oDLe reLD
• b' OL. Vrm
5 Vr Om SLM &AR'
4' GOMG. SLAB ' 0;
MFSRE
LOGFLOOR DECK-
'
PER PLANS
TS 2 V2x2 V2x5M OLKS. IN
BETWIN JOISTS, PER M."
W/ 3/6'm x b' A8. • ar OL.
2. 15 CONT. •
TOP OP HALL
lr LONG: BLOCK MALL
W SLAB DOP65
w 2- .S NORlL 1;24' O
t I6' Of..
SOLID GR=.,
SPELLIL DalwTION
PROVIDE MATER PROOF Wr
PER ARUR..
b
r VA
LCR:
n VERTS • 16' OL.
0000l
(BASE1Eli� 5�PJ
:r
16' LONG. BLOCK MALL
TOP OP 16' Kau
W2- 15 NOM • 24' O
SOLID EROVF,
SPE6AL R6PELTI011
GY//a!iCl .
A
S- rS CONT.
TOP a BOTTOM
r LCR.
S LLR:
4'-4-
2 \RETAININQ7
'-0'\RETAINING WALL
- r.r-o•
KNAPP & TANG STRUCTURAL ENGINEERS, INC. Title ; WADE RESIDENCE
X408
Page:
S-OUTH STODDARD AVENUE
Job Dsgnr:
Date: NOV 18,2003
+ `03AN BERNARDINO, CA 92401
Description....
ft-#
.. _. ..
PHONE: 909-889-0115 ` "'
""" _ --~ -1-3-.V--RETAINING WALL
- - ....
FAX: 909-889-0455
ft
ft #
'
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0 Restrained
Retaining Wall Design
ft
- Build Date: 10 -SEP -2001, (c) 1989-2001
Stem Weight = 1,674.0 lbs
2.75 ft
Criteria'
I Soil Data I Footing Strengths & Dimensions ,
Retained Height = 13.50 ft
Allow Soil Bearing = 3,000.0 psf Toe Width
2.25 ft
Wall height above soil = 0.00ft
Equivalent Fluid Pressure Method Heel Width
= 2.30
Total Wall Height = 13.50 ft
Heel Active Pressure = 55.0 psf/ft Total Footing Widt
Toe Active Pressure = 55.0 psf/ft Footing Thickness
= 18.00 in
To Support Height = 13.50 ft
Top pp 9
Passive Pressure = 300.0 psf/ft
Water height over heel = 0.0 ft Key Width
_
- 0.00 in
Slope Behind Wal = 0.00 : 1
Key Depth
FootingIlSoil Frictio = 0.400 Key Distance from Toe
= 0.00 in
= 0.00 ft
Height of Soil over To = 0.00 in
Soil height to ignore
Soil Density = 110.00 pcf
for passive pressure = 12.00 in fc = 3,000 psi
Fy = 60,000 psi
Footing Concrete Densit
= 150.00 pcf
Wind on Stem = 0.0 psf
Min. As"%
= 0.0018
Cover @ Top = 2.00 in
@ Stm.= 3.00 in
;Design Summary
Masonry Stem Construction
--- ---
'
Total Bearing Loa = 4,628 lbs
Thickness = 12.00 in fm = 1,500 psi Short Term Factor = 1.000
...resultant ecc. = 13.20 in
Wall Weight = 124.0 pcf Fs = 24,000 psi Equiv. Solid Thick. = 11.600 in
Soil Pressure @ To = 2,625 psf OK
Stem is FIXED to top of footing n Ratio (Es/Em) = 25.778
Soil Pressure @ Hee = 0 psf OK
Block Type = Medium Weight Use Special
Inspection
Allowable = 3,000 psf
Solid Grouted Mmax Between
Soil Pressure Less Than Allowable
@'Top Support Top & Base
@ Base of Wall
ACI Factored @ Toe = 3,675 psf
ACI: Factored @ Heel = 0 psf.
Stem OK Stem OK
Shear NG!
Footing Shear @ To = 28.3 psi OK
Design height = 13.50 ft 7.48 ft
Rebar Size #
0.00 ft
Footing Shear @ Hee = 16.5 psi OK
= 7 # 7
Rebar Spacing = 16.00 in 8.00 in
# 7
16.00 in
Allowable = 93.1 psi
Rebar Placed a = Center Edge
Edge
Reaction at Top = 1,002.4 lbs
Reaction at Bottom = 5,185.1 lbs.
Rebar Depth 'd' _ 5.75 in 9.00 in
9.00 in
Design Data
Sliding Calcs Slab Resists All Sliding !
fb/FB + fa/Fa = 0.000 0.503
Moment.... Actu = 0.0 ft-#
1.393
=
Lateral Sliding Forc 5,185.1 lbs
4,034.4 ft-#
9,021.6 ft-#
Moment..... Allowable = 3,047.0 ft-#. 8,014.1 ft-#
6,477.9 ft-#
Shear Force @ this height = 0.0 lbs
4,009.5 lbs
Shear..... Actual = 0.00 psi
42.12 psi
Shear..... Allowable = 38.73 psi
38.73 psi
Footing Design Results ,
Rebar Lap Required = 35.00 in 35.00 in
eel
Rebar embedment into footing =
13.42 in:
Factored Pressure = 3,675 0 psf
Other Acceptable Sizes& Spacings:
Mu': Upward = 7,324 4 ft*
Mu': Downward = 797 2,023 ft-#
Toe: None Spec'd -or- Not req'd, Mu < S ' Fr
Mu: Design = 6,527 2,019 ft-#
Heel: None Spec'd -or- Not req'd, Mu < S " Fr
Actual 1 -Way Shear = 28.29 16.52 psi
Key: No key defined -or- No key defined
Allow 1 -Way Shear = 93.11 93.11 psi
i Summary of Forces on Footing : Slab RESISTS sliding, stem is FIXED at footing
Load &.Moment Summary For Footing : For Soil Pressure Calcs
>>> Sliding Forces are restrained by the adjacent slab
Moment @ Top of Footing Applied from Stem
=9,021.6
ft -#
Surcharge Over Heel = lbs
ft
ft-#
Adjacent Footing Load = lbs
ft
ft-#
Axial Dead Load on Stem = lbs
ft
ft #
Soil Over Toe = lbs
ft
ft.#
Surcharge Over Toe = lbs
ft
ft-#
Stem Weight = 1,674.0 lbs
2.75 ft
4,603.5 ft-#
Soil Over Heel = 1,930.5 lbs
3.90 ft
7,529.0 ft-#
Footing Weight = 1,023.8 lbs
2.28 ft
2,329.0 ft-#
Total Vertical Force = 4,628.3 lbs
Base Moment =
5,439.9 ft-#
Soil Pressure Resulting Moment = 5,089.3t-#
X'NAP P) 8c d AN
STRUCTURAL ENGINEERS, INC,
2105 NORTH ARROWHEAD AVENUE
. . . . . . . . . . SAN BERNARDINO CA 92405
7
BB 4
--MAIL (KNAPPAEOAOL.COf ')
4,M /,lo - 5•
•
-
6
MAX Pae� ad 621 -v
�aj-& d6ae
em
O ��
�6 Od R13
�e
A/67Qrr9/n•P 7o
BY:
D A T =:
SHT.-__O.:7-
14 4 30,
i
� `. KNA P P 8c d"A"N G
-Pl ,—
f_11:: STRUCTURAL ENGINEERS INC, u/ADE 8Y:
21 05 NORTH ARROWHEAD AVENUE
a� 4 ih SAN BERNARDWO CA. 92405 DAi.=:
_..
tars :n - r may- - _1 (909 883-497L
__. _ SAY, (909' 883-784-5
• Y" _-MAIL (KNAPPAE®AOL_COM) ,! � SHI O r_
C. A16 D- 2 -Qd
Alo. GxG Pis f• C Au I05 Rr' morel )
9
Oren oW4 Vii- B �.
pod 4�m /Vp
l
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
' TEL: (909) 889-0115
FAX: (909) 889-0455
MULTI -SPAN TIMBER BEAM DESIGN.
WADE RESIDENCE
Date: 03129104
Page:
16 s v'
LL
Total
ROOF BEAM
0.45
1.15
'
1.09
2.80
GENERAL DATA
o
- 1
2
3 -4
-
4-
All
AII Spans Simple Support ??
0.66'
YES
LL
Total
k :
k :
0.45
1.15
Spans Length
ft :
8.00
11.00
19.50
7.50
End Fixity:
-0.071
Pin:Pin
Pin:Pin
Pin:Pin
Pin:Pin
Beam Width
in :
5.125
5.125
5.125
5.125
Beam Depth
in :
12.00
12.00
12.00
12.00
CALCULATED VALUES
L•U dL h
-OK-
-OK-
-OK-
-OK-
F'b-Modified Allow.
psi :
2400.0
2400.0
2400.0
2400.0
fb - Actual.
psi :
224.0 •
423.5
1330.9
196.9
F'v-Modified Allow.
psi :
165.0
165.0
165.0
165.0 _
fv (actual) " 1.5
psi :
20.9
31.3
61.0
19.2
Moment @ Left
k -in :
0.0
0.0
0.0
0.0
Moment @ Right
k -in :
0.0
0.0
0.0
0.0
Max. Mom. @ Mid -Span
k -in :
27.6
52.1
163.7
24.2 .•
X -Dist
ft :
4.00
5.50
9.75
3.75
Shears: Left
k :
1.15
1.58
2.80
1.08
Right
k :
-1.15
-1.58
-2.80
-1.08
Reaction @ Left DL
k.:
0.70
0.96
1.71
0.66
Page:
16 s v'
LL
Total
k :
k : -
0.45
1.15
0.62
1.58
1.09
2.80
0.42
1.08
o
Reaction @ Right DL
k :
0.70
0.96
1.71
0.66'
psi :„
LL
Total
k :
k :
0.45
1.15
0.62
1.58
1.09
2.80
0.42
1.08 4 �a 9C
�,o ,
J
Max. Defl. @'Mid Span
in :
-0.020
-0.071
-0.703
-0.015 V
1.00
X -Dist
ft :
4.00
5.50
9.75
3.75
DESIGN DATA
Use Live Load on This Span
?
Yes
Yes
Yes
Yes
L•U dL h
plf :
175.0
175.0
175.0
'
LL.
ea nsupporte engt
ft .
2.00
2.00
2.00
2.00
Fb:Basic Allowable
..psi :
2400.0
2400.0
2400.0
2400.0
Fv:Basic Allowable
psi :„
165.0
165.0
165.0
165.0
Elastic Modulus
ksi :.
1800
1800
1800
1800
Load Duration Factor
1.00
1.00
1.00
1.00
APPLIED LOADS
Use Live Load on This Span
?
Yes
Yes
Yes
Yes
Uniform...... OL
plf :
175.0
175.0
175.0
175.0
LL.
plf :
112.0
112.0 `
112.0
112.0 "
QUERY VALUES
Location .....
ft :
0.00
0.00
0.00
0.00
Shear
# :
1.15.
1:58
2.80
1.08
_ Moment
k -in :
0.00
0.00
0.00
0.00
........_..... Deflection
in' :...
0.000.-
0.000
0.000
0.000
V4.413 (c) 1983.95 ENERCALC
(continued on next page....)
Knapp Architectural Engineers, Inc, KwO601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 03129104 Page:
MULTI -SPAN TIMBER BEAM DESIGN
WADE RESIDENCE
(.....continued)
287 11111 111111111287
11111287
8.00 11.00 19.50
T
7.50
J 7�ivr /\/,6 /2
`i
V4.4B (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
-� r= KNAP P
=�: �8c 'TAN
STRUCTURAL ENGINEERS, INC.
2 05 NORTH ARROWHEAD AVENUE
max: SAN BERNARDINO CA. 92405
3-4974
(909 88
FAY (909) 883-7545
-MAIL (KNAPPAE®AOL.COM)
u1�1 D E �PFsio �v'c�
)A * , /vo /3. s p/3 - 3 / SFan
BY:
DATE*
.
Sn I Or_
18x.39
ICNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO'CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
NEW BEAM
SPAN DATA
Center Span
10.50 ft
Left Cantilever
0.00 ft
Right Cantilever =
3.50 ft
UNIFORM LOADS
Center Span #1 =
0.03 klft
Center Span N2 =
0.08 klft
Right Cant #1 =
0.03 klft
Right Cant #2 =
0.08 klft
CONCENTRATED LOADS
N 1 = 12.530k at 14.00ft
Moments
Max. Span Moment
Max. Mom. Location
Min. Span Moment
Min. Mom. Location
Max @ Left Support
Max @ Right Support
MAXIMUM MOMENT
_ 0.00 k4t
0.00 ft
_ -44.54 k -ft
10.50 ft
0.00 k ft
-44.54 k -ft
44.54 k -ft
I:Inertia
E:Elastic Modulus
End Fixity
Date: 03129104
MEMBER DATA
2491.000 in4 All distances for load locations refer
1800000 psi to left support. Neg ('-') distances
Pin/Pin means load is on left cantilever
TRAPEZOIDAL LOADS
SUMMARY
Shears
Left Support = 3.65 k
Right Support 12.92. k
Reactions
APPLIED MOMENTS
Deflections —
Max. @ Span = 0.115 in at 6.10 ft
Right Cant = -0.272 in at 14.00 ft
Left Support = -3.65 k
Right Support = 17.75 k
Query Values
Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = -3.654 k, Defl. = 0.000 in
At Right Cantilever @ X = 0.00 ft, M = 0.00 k -ft, V = 0.000 k, Oefl. = 0.000 in
m
N
N
/f
%3 is Igt/
10.50 3.50
, 4t n,- , , /-, " /. 3
QQPage:
�1 oc 36
I
V4.413(c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567'
RISA -2D (R) Version 3.03
Job
Page
Date
WADE RESIDENCE
RD -35 % 6vq t /
/\l
Units Option : US Standard r
RISC Code Checks : 9th Edition ASD
Shear Deformation: No
M
P -Delta Effects No co/ T5. 17tY 2
Redesign No
$m WioX��
Edge Forces : No
A.S.I.F. : 1.333
------------------------------------
Node Boundary Conditions
No X-Coord Y-Coord' X-dof Y-dof Rotation Temp.
-------- --- (ft) -----:--- (.ft) -- -- (in, K/ in) ---- (in, K/in) --- (r, K-ft/r) ----- (F) -
1 0.00 0.00 R R R 0.00
2 0.00 1.3.00 0.00
3 --5.00 13.00 0.00
------------------------------
Material Elastic Poisson's Thermal Weight Yield Stress
Label Modulus Ratio Coefficient Density (Fy)
----------=--- (Ksi)------------------------(F)--------(K/ft3)------(Ksi)----
STEEL .29000.00 0.30000 0.65000 0.490 36.000
-- - - - - - - - - - - -- - -- - - - -- - - - - - - -
Section Database Matl. Area Moment of As y/y
Label. Shape Set Inertia Coef
---------------------------------------- (in"2)--------- (in"4)----------------
BM W10X22 STEEL 6.49 118'000 1.20
COL TU5X5X8 STEEL 8.36 27.000 1.20
----•--------------
I J I Releases J End Offsets
No Node Node Section x y z x y z Sec Sway I J Length
------------------------ - (in) ---- (in)------�(ft)
--------------------
1 _1 - 2 COL
2 .. 2- 3 B13.00M 5.00
---------------------------------------------------
I J Unbraced Lengths K Factors Bending Coefs
No Node Node Lb -in Lb -out Lc In Out Cm Cb
--------------------(ft)-----(ft)-----(ft)------------
1 1 - 2
2. 2 - 3
RISA -2D (R) Version 3.03
Job
Page
Date
WADE RESIDENCE
RB -35
------------------------------------------------------------------
BLC Basic Load Case Load Totals
No. Description Nodal Point Dist.
----------------------------------------------------------------
1 D+L 1
Nodal Loads, BLC.1: D+L
------------------------------------------------------------
Node
Number Global X Global Y Moment
------------------------(K)------------------(K)------------------(K-,ft)----
3 0.000 -1.255 0.000
-------------------------------------------
Load Combination Self Wt BLC BLC BLC BLC BLC W E
No. Description Dir Fac Fac Fac Fac Fac Fac. DYNA S V
--------------------------------------
1 .D+L Y -1 1 1
Dynamic Analysis.Data
Number of modes (frequencies) 3
Basic Load Case for masses None
BLC mass direction of action X only
Acceleration o.f Gravity 32.20 ft/sec'**2
Load Combination is 1 D+L
Nodal Displacements
Node Global X Global Y Rotation
--------------------=(in)-----------------(in)-----------
----- (rad) ---------
1 -0.00000 -0.00000 0..00000
2 --1.22166 -0.00100 0.01'.566
3 -1..22166 -0.9-68-01 0.01634
Load Combination is 1,: D+L
Reactions
------------------------------------------------------------------------i----
Node Global X Global Y Moment
----------------------(K)------------------(K)---------------(K-ft)---------
1 0.00000 1.73523 -6.55105
Totals 0.00000 1.73523 -6:55105
RISA -21) (R) Version 3.03
WADE RESIDENCE
RB -35
Job
P a g 0Z
Date
Load Combination is 1
D+L
Member End Forces
Nodes =________=
I -End =_=-------
---------------------------------------
--------
J -End =..
-
No I J Axial
Shear
Moment Axial
Shear
Moment
--------------=`('K) --------
(K) ------ (K -f t) -------
(K) -------- (K) ------
(K -ft) --
1 1- 2 1.74
-0.00
-6.55
-1.37
0.00
6.55
2 .2- 3 -0.00
-1.37
-6.55
0.00
1.25
-0.00
Load Combination is 1
D+.L
AISC Code Checks
Nodes
---------------------
Member Quarter
Points
No .I. J Maximum
0
1/4 1/2
------------------------------
3/4
L
Shear
1 1- 2 0.3206
.0.3.206
0.3198 0..3191
0.3183
0.3176
0.0000
2 2- 3 0..1426
0.14.26
0.1058 0.0698
0.0345
0.0000
0.0388
L
0
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
DESIGN OF EMBEDDED POLE FOOTINGS
WADE RESIDENCE
RB -35
Allow Passive
Max Passive
Load Duration Factor
Point Load
Load Height
Dist. Load
Start Height
End Height
Pole Type
WidthlDiameter
Surface Restraint
Date: 03129104 Page:
is 4 _V
DESIGN DATA
1 —
300.0 psf
2000.0 psf
1.000
500.0 #
13.00 ft
0.0 plf
0.00 ft
0.00 ft
Rectangular
36.0 in
? Restrained
SUMMARY
Moments @ Surface...
1 —
Point Load
6500.0 ft-#
Uniform Load
0.0 ft-#
... Total Moment
6500.0 ft-#
Total Lateral Load
500.0 #
- NON -RESTRAINED RESULTS -
Min. Req'd Embedment
All +0 +4.36h IA►".5)12
A=2.34PI(S 1 b)
Press @ 113 Embed
Actual
Allowable
— RESTRAINED RESULTS'—
Min. Req'd Embedment
(4.25'P"hIS3"b)".5'
Pressure @ Bottom
Actual
Allowable
Surface Restraint
Force
2.79 ft
837.7 psf
837.7 psf
3217.7 N .
V4.4B (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
Knapp Architectural Engineers, Inc.
tiG�i n!�
WADE RESIDENCE Date: 3/30/04
2105 N. Arrowhead Ave.
San Bernardino, CA 92405
39
Reliability / Redundancy Factor
Ground floor area A b := 9022•ft2
p shall not be taken less than 1.0 and need not be
greater than 1.5
Total story shear V:=50995 -lb
For Grid Line "a" Moment frame
Maximum horizontal force
component in a single brace element
r i - 1882 -lb
r
r max := V r max = 0.037
p:=2- 20 -ft p=-3.705
r max. A b
Therefore p = 1.0
For Grid Line "b" moment frame
Maximum horizontal force
r i :=1882•lb
component- in a single brace element.
ri
r max : = V r max = 0.037
p:=2- 20 -ft p=-3.705
r max
Therefore P = 1.0
For Grid Line "A" Plywood shear wall
Length of shear wall L W:= 14 -ft
Maximum shear wall force r i :=7771 -lb
r i 10•ft
r max = V • L r max = 0.109
w
20 -ft p�=2- p=0.066
r max'4A b
Therefore P = 1.0
• Knapp Architectural Engineers, Inc.
2105 N. Arrowhead Ave.
San Bernardino, CA 92405
For Grid Line `A.4" Plywood shear wall
Length of shear wall
Maximum shear wall force
ri 10•ft
r max V' —L7— r max = 0.073
W
p:=2— 20 -ft p =-0.883
r max*4A b
Therefore P 1.0
For Grid Line "A. 6" Plvwood shear wall
Length of shear wall
Maximum shear wall force
ri 10•ft
r max V ' L w r max = 0.234
20 -ft
p:=2— p = 1.099
r max'4A b .
Therefore P = 1.0 -
For Grid Line T & 8.1 " Plywood shear wall
Length of shear wall
Maximum shear wall force
ri 10•ft .
rmax :=V' L rmax= 0.066
w
20 -ft
p:=2— p=-1.205
r max'NFA b
Therefore p = 1.0
WADE RESIDENCE Date: 3/30/04
02154
Lam,:=8-ft
ri :=2980•lb
LN,:=6.5•ft
ri := 7743-1b
Lam,:=29.5•ft
ri :=9884•lb
Knapp Architectural Engineers, Inc.
2105 N. Arrowhead Ave.
San Bernardino, CA 92405
For Grid Line "C" Plvwood shear wall
Length of shear wall
Maximum shear wall force
r i 10•ft
r max -V'-C-- r max = 0.086
w
p:=2- 20 -ft p=-0.453
r max'A b
Therefore P = 1.0
WADE RESIDENCE
For Grid Line "C.1 " Plywood shear wall
Length of shear wall
Maximum shear wall force
ri 10•ft
r max V' Lw r max = 0.033
p :=2- 20 -ft p = -4.71
r max• A b
Therefore P = 1.0
For Grid Line "D" Plywood shear wall
Length of shear wall
Maximum shear wall force
ri. 10•ft
rmax,=V L rmax =0.024
W
p:=2- 20 -ft p=-6.73
r max. A b
Therefore P = 1.0
Lam,:=15•ft
ri :=6567 -Ib
L W:= 17 -ft
ri:=2865-Ib
LW:=25•ft
r i := 3075•lb
Date: 3/30/04
�S � 3�--
I
Knapp Architectural Engineers, Inc.
2105 N. Arrowhead Ave.
San Bernardino, CA 92405
WADE RESIDENCE
For Grid Line "D.1 & E.1 " Plvwood shear wall
Length of shear wall L W:= 14 -ft
Maximum shear wall force r i:= 1913 -lb
r i 10•ft
r max V ' L w r max = 0.027
20 -ft
p:=2— p = -5.858
r max' A b
Therefore P = 1.0
For Grid Line "E" Plywood shear wall
Length of shear wall
Maximum shear wall force
r i 10•ft
r max = V ' L r max = 0.017
W
p:=2— 20 -ft p=-10.102
r max.4A b
Therefore P = 1.0
For Grid Line "E.2" Plywood shear wall
Length of shear wall
Maximum shear wall force
r i 10•ft
r max :=V' L r max = 0.044
W
p:=2— 20 -ft p=-2.766
r max'NFA b
Therefore o = 1.0
Lam,:=16.5-ft
r i := 1464 -lb
Lam,:=13•ft
ri :=2929.Ib
Date: 3/30/04
17 CP �'
Knapp Architectural Engineers, Inc. WADE RESIDENCE Date: 3/29/04
2105 N. Arrowhead Ave.
San Bernardino, CA 92405ZO
• Reliability / Redundancy Factor
Ground floor area A b := 9022.112 p shall not be taken less than 1.0 and need not be
Total story shear V:= 45076-lb greater than 1.5
For Grid Line "l " P/vwood shear wall
Length of shear wall
Maximum shear wall force
ri 10•ft
r max V ' Lw r max = 0.028
p :=2— 20.11 p = -5.515
r max' A b
Therefore P =-1.0
For Grid Line "2" Plywood shear wall
Length of shear wall
Maximum shear wall force
r i 1.0 • ft
r max V' L r max = 0.132
w
p:=2— 20.11 p=0.404
r max A b
Therefore P = 1.0
For Grid Line "3" Plywood shear wall
Length of shear wall
Maximum shear wall force
ri 10•ft
r max -V' L r max = 0.173
w
p:=2— 20.11 p=0.786
r max._[A b
Therefore P = 1.0
L W :=40•ft_
ri :=5052•lb
L w :=6.11
ri :=3569•lb
Lam,:=6.5•ft
ri := 5080•lb
A
Knapp Architectural Engineers, Inc.
2105 N. Arrowhead Ave.
San Bernardino, CA 92405
For Grid Line "3.4" Plywood shear wall
Length of shear wall
Maximum shear wall force
ri 10•ft
r max 7'-C— r max = 0.197
w
20 -ft
p:=2– p=0.932
r max' A b
Therefore p = 1.0
For Grid Line "3.8" Plvwood shear wall
Length of shear wall
Maximum shear wall force
ri 10•ft
r max V ' L r Max = 0.024
w
20 -ft
p:=2— p=-6.927
rmaxAb
Therefore P =-1.0 -
For Grid Line "4" Plywood shear wall
Length of shear wall
Maximum shear wall force
--- ..._.._..........._.. ... ri.l0,ft..
r max V ' L w r max = 0.01
20 -ft
p =2— p=-18.133
r max'4A b
Therefore P = 1.0
WADE RESIDENCE
Lam,:=8.5•ft'
ri :=7551•lb
Lam,:=19•ft
ri :=2020•lb
Lam,:=7•ft
ri :=330•lb
R
Date: 3/29/04
t�q 09Der
4
Y
Knapp Architectural Engineers, Inc.
2105 N. Arrowhead Ave.'
San Bernardino, CA 92405
For Grid Line "4.6" Plvwood shear wall
Length of shear wall
Maximum shear wall force
r i 10•ft
r max = V' L r max = 0.154
W
20 -ft
p:=2— p=0.635
r max' '°` b
Therefore P = 1.0
For Grid Line "4.7" Plvwbod shear wall
WADE RESIDENCE
Length of shear wall
Maximum shear wall force
ri 10•ft
rmax:=V L rmax =0.018
w
p :=2— 20 -ft p = -9.56
r max' A b
Therefore t) =• 1.0
For Grid Line "5" Plywood shear wall
Length of shear wall
Maximum shear wall force
__ ._... ... r i 10•ft
r max = V' L r max = 0.033
W
p:=2— 20 -ft p=-4.34
r max' A b
Therefore Q = 1.0
Lam,:=4•ft
r i :=2782•lb
L W:= 19 -ft
r i := 1560 -lb
L W: = 67•ft
r i :_ 10030 -lb
Date: 3/2n9/04
fd�Icr
A
Knapp Architectural Engineers, Inc.
2105 N. Arrowhead Ave.
San Bernardino, CA 92405
For Grid Line "6" Plvwood shear wall
Length of shear wall
Maximum shear wall force
ri 10•ft
r max -V'-C-- r max = 0.049.
W
20•ft
p:=2- p=-2.277
r max'4A b
Therefore P 1.0
WADE RESIDENCE Date
- 3/29/04
L W:= 32•ft
ri :=7102•lb
8
) fw A/0 / 7> )'es
'VIADF-
9 Y:
SHT.----Q F
q2,J 32
vv r)
Are Z;,//
er-15C ad 13 o/
bf
7 4�-
1,44
7 kw 4. o, ei.;s-17 -s
d" o 4- X/6 x /a
�' _ �'�
r J
?-47
T/I,,N
STRUCTURAL ENGINEERS, INC,
05 NORTH ARROWHEAD AVENUE
. . . . . ."y SAN BERNARDINO, CA. 92405
(909)
. ... . FAX (909), 883-754
'E-MAIL (KNAPPAEO AOLCOM)
) fw A/0 / 7> )'es
'VIADF-
9 Y:
SHT.----Q F
q2,J 32
vv r)
Are Z;,//
er-15C ad 13 o/
bf
7 4�-
1,44
7 kw 4. o, ei.;s-17 -s
d" o 4- X/6 x /a
�' _ �'�
r J
?-47
�
If:
WADE RESIDENCE
Alo ��: ala y ?O/c FM4,
Steel Column Design:
F
6" Diameter Ex. Strong Steel Column
P:= 941 -lb L:= 11 -ft
1:= 40.5•in4 S := 12.2•in3
M:= P•L M.= 10.35-kip•ft
M
T. T 7 7), fb = 7.66 -ksi
P•L3
0:=T A=0.61 -in
Hallow := L•.005 Hallow = 0.66 -in
Footiniz: Le := 3 -ft Soil := 200•psf
t
4.25 •M•ft 3
d:= d=3.39ft
Soil. 3•l. el
Use 3'-0" sq. x 4'-0" deep footing
Anchorage: Lp := 8 -in
Tension : _ �p_ Tension = 7.76 -kip
Shear : = p Shear- 0.24 -kip
Use 4-1 1/2" diameter A307 fully thr'd steel rod
with 18" min. embedment.
Base plate: width := 10 in dist := 2 -in
Tension -2 -dist
sx :=• csi •0.75—sx = 1.15 -in3
Fs6th:_ th = 0.83 -in
Base plate: Use 10" sq. x 1 1/2" thk. base plate
3
.k
.15TRUCTURAL ENGINEERS INC,
2105 NORTH ARROWHEAD AVENUE
BERNARDINO ria
05
FAX (909) 883-7543
=-Mat
L (KNAPPAE®AOL_COM)
Gtr CT "'16 a((7 jar
Alf_ &64p'
- ' 7,K - 3�S,'
P
, - -:- -��k 6 �,) A 13 - -4
«KNAPP & TANG STRUCTURAL ENGINEERS INC
' 408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
511UVLt tiPAN Ht:AM ANALYSIS
WADE RESIDENCE
NEW RB -24
SPAN DATA
Center Span = 27.50 ft
Left Cantilever = 0.00 ft
Right Cantilever 0.00 ft
UNIFORM. LOADS
Center Span #1 = 0.34 klft
CONCENTRATED LOADS
# 1 = 1.260k at 2.50ft
# 2 - 9.290k at 14,00ft
Moments
Max. Span Moment
= 97.21 k -ft
Max. Mom. Location
14.02 ft
Min. Span Moment
_ -0.00 k -ft
Min. Mom. Location
= 27.50 ft-
tMax
Max@ Left Support
= 0.00 k -ft
Max @ Right Support
- 0.00 k -ft
MAXIMUM MOMENT
= 97.21 k -ft
O.JJ
Date: 03130104 Page: 2
36 o-� 38,
MEMBER DATA
(:Inertia 11530.000 in4 All distances for load locations refer
E:Elastic Modulus 1800000 psi to left support. Neg ('-') distances
End Fixity Pin/Pin means load is on left cantilever -
TRAPEZOIDAL LOADS
SUMMARY
Shears
Left. Support 10.35 k
Right Support 9.49 k
Reactions
APPLIED MOMENTS
Deflections
Max. @ Span = -0.557 in at 13:75 ft
Left Support 10.351'
Right Support 9.49 k.
Query Values
Between Supports @ X - 0.00 ft, M = 0.00 k -ft, V = 10.353 k, Oefl.. = 0.000 in.
V4.4B (c) 1983.95 ENERCALC Knaoo Architectural Enoineers. Inc. Kw0601987
STRUCTURAL ENGINEE
ti ERS, INC,
2105 NORTH ARROWHEAO AVENUE
• SAN BERNARD INO, CA.
..... . TELE. (909 9240�;
. . . . . . . . . . 88.3-4-97-
x (909
. . . . . . E MAIL (KNAPPAECAOLCOM)
Z /3".
. -3
17W J_k
KNAPP & 'TANG STRUCTURAL ENGINEERS, INC..
408 S. Stoddard Ave, San Bernardino, CA 92401
Phone: (909) 889-0115 Fax: (909) 889-0455 E-mail: abarajas@knapptang.com
April 1, .2004 Page 38 of 38
Re: A Custom House for:
Mr. & Mrs. Frank Wade
The Quarry
La Quinta, California 92253
Plan. Check #0312-029 (Vt plan check)
Structural Sheet Index:
Sheet # Description
S1.0 General Notes and. Typical Details
S2.0 Garage / Basement foundation plan and details
S3.0 Foundation Details
S3.1
S3.2 "
S3.3 "
S3.4.
S4.0 Roof Framing Plan
S5.0 Framing Details
S5.1
S5.2 "
S5.3 cc
S5.4 "
If you have any question, please contact us at the above telephone numbers.
Sincerely,
k
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
408 SOUTH STODDARD AVENUE, SAN BERNARDINO, CA 92401
Phone: (909) 889-0115 Fax: (909) 889-0455 : Email: knappae@aol.com
STRUCTURAL CALCULATIONS
For
MR. AND MRS. FRANK. WADE
RESIDENCE
79-720 ( LOT 64) TOM FAZIO LANE
LA QUINTA, CA. 92253
Prepared By
11/26/03
PREPARED BY
HW
a
KMAP P Sic. MA" G
STRUCTURAL ENGINEERS, INC,
y _ 408 SOUTH STODOARD AVENUE
` SAN BERNAROINO, CA. 92401
TELE. (909) 88.9-0115
FAX (909 889-0455
E-MAIL (KNAPPAE®AOL.COM)
19di�7x
t(2s5 ID'5ii/c_F_
76
i
4r Z
BY:
DATE:
SHT. —OF _
}." STRUCTURAL ENGINEERS, INC.
40.8 SOUTH S.TO.D:QARQ AVENUE
SAN BERNARD.INO, CA. 9:240.1
TELE. (909) 889-0115
"= FAX (909) 889-045.5
E-MAIL (KNAPPAE®AOLCOM)
WAPr-- ,QE-5JD
v
17JW
• e �g �S �� e _ /3 �- _
BY:
DATE:
SHT. / OF
m
/
lob
rlr-)
STRUCTURAL ENGINEERS, INC.
40.8 SOUTH STODDARD -A -EN.UE
SAN BERNARDINO, CA. 9,240.1
TELE. (90.9-) 889-0115
FAX (9 93 8]89-0455
=E-MAIL I (KNAPPAECAOL-COM)
WAPa
��C)zas�
zzsF- 6x/�
�4-
.4 - of 6 t� �' 0 's-
J-6 7*
&z7
9 x /
77.6
7 d 7 Kia =1676,7 161—
�!6
tA
SAA /s
BY:
CA TIE:
SHOF
T. .5
KNAPP 8c T,/\"G
STRUCTURAL ENGINEERS, INC.
40.8 SOUTH S.TO.DDARD AVENU=
SAN BERNARDINO, CA. 9:240.1
TELE. (9:09 889 -0 1 15.
- FAX (909J 889-04-55
E-MAIL (KNAPPAE®AOLCOM)
WAP ,2E -5i0 ECIC,=
BY:
OAT -E:
SHT. 4 OF
3
6797
X le
.,
KNAF' P 8.-- TAN.:G
STRUCTURAL ENGINEERS, INC.
408 SOUTH S.TODDARD AVENUE
-' SAN BERNARDINO, CA. 9:240.1
-' TELE. (909 889-0115
FAX (9093 889-04-55
E-MAIL (KNAPPAE®AOLCOM)
BY:
WADa ,2E -5i0 -E,yc,=- DATE:
SHT. SOF
7.297
117
40. V
,g = D, 032=
a, �• 5�x 162'1
h
.
= a764
/,I= 1'6, �' `k 5/- = 43,44 /39 3
-77
rl
-9 CL= 9'-���
a�
a60ve
=Y7o
4
Kr-A./\P P Sc TAN.<G
STRUCTURAL ENGINEERS, INC.
408 SOUTH STO.DDARD AVENUE
;.
SAN BERNARDINO, CA. 9:24`0.1
f TELE. (909) 8'89-0115
"M FAX (909 589-045.5
E—MAIL (KNAPPAE(OAOLCOM)
WA 0 i=- i2E-Vi0 -Ex1c2=-7
_ 7,�6 649- d,
7c� 7" o ti)(Id'
(L = /q L el )
_ 7K0 x'52 = #
--/= p7 ps 'ok ,�-= ,¢/'r op
ZISZ- t$'/' [3 � X ao ;��j c ---A /; � - 2/
M—/:2 (L= A? 6" )
w = (>t-/- /6 )x 7 = 2g7 4/A-
-7
ld,6 3 187K
UY: F
DATE:
SHT. 6 OF
u
KP,-J,,a,PP 8c T./\"Gl
STRUCTURAL ENGINEERS, INC.
rt 408 SOUTH STODAVENUE
A .ENUE
SAN BERNARDINO, CA. 9-.240-1
TELE. (909� 889-0-11 5.
FAX 90 889-0455
E-MAIL (KNAPPAEIZACLCOM)
m)'Y,
WAPa ?eE-510 -El-lc.=-
Kit)
x 7,
a- a C 1-= �
-71P, PAN
'4A
17e OKI
ay-:
OAT E-
SHT. 7 OF
KrV.Z\PP 8,r- Tl/\"G
STRUCTURAL ENGINEERS, INC.
408 SOUTH STODDARD AVENUE
SAN BERNARDINO, CA. 9..2401
TELE. (9:0.9-) 889-01 1 5.
FAX (909J 889-0455
E-MAIL (KNAPPAECAOLCOM)
3f
M -=�:3/o ""' 5 "</� OA-
MW6) �3
31 ISI /13 C -49d)
WAP,=-- YeE-V1,0'Esk1c.=-
0
6X12 -
b
a -y:
DATE:
SHT 06 OF
C11071w
z4 s- e;' 6. ?, 31� // coy k ? -113
Kr*--J,,in,,PP 8c T/\P-slG
STRUCTURAL ENGINEERS, INC.
y""
408 SOUTH STODDARD AVENUE
SAN BERNARDINO, CA. 9-24:0.1
TELE. (9109) 889-01154-
89-01 1 5
'`1-_'�
FAX -
909) 889 -04-55
E-MAIL (KNAPPAECAOLCOM)
WAPa-, RE -51,0 ExlcF
57,
U
J -76b
)yv-xg
Z
1677
7-o4
-3 K
St-- f" cm 3 1
z tg
16.1 f
--7F
/7J. 31 7A*
^77* 16770
-7 7'
BY:
DATE.
S HT 7 OF
Kr,sJ,4,,PP 8c
STRUCTURAL ENGINEERS, INC.
408 SOUTH STODDARD AVENUE
SAN BERNARDINO, CA. 9,240.1
TELE. (909) 8-89-0-115.
FAX 09) 889-0455
MAIL (KNAPPAEZAOL-COM)
0't
C,>t-*,e6 x 7
IAJ 3 (,d- 4- A) x //
WAPa RE-51,0-Exlc,�
Ria - 4- ( 2 --) 7 � 9'' )
-74 = 74ID5 t!' ok
pat<
5-r = 3g3 14 3 (70-)
.A = , 5�' ce
If A Eni
cW -)qg
l
11,839 q")Ilr
5TY:
DATE:
SHT 10 OF
141
13 7
/,00 -= (d"41- o // 3
KN.A� F' 8� TA1\1:G
STRUCTURAL ENGINEERS, INC.
408 SOUTH STO.D'DARD AVENUE
SAN BERNARDINO, CA. 9:240.1
TELE. (909 889-0115
FAX (909 j 889-0455
E-MAIL (KNAPPAE®AOLCOM)
ox
Gtfa = CT;y6 )X %o =416
usZ 13,
le8 -2 8
ffs-F�- 6'cla elt
3 /o
CG=4
:.: BY:
DATE.
SHT. / /.OF
KNAP P 8c
STRUCTURAL ENGINEERS, INC.
r � 408 SO.U.TH S.TO.DDARD AVENUE
SAN BERNARDINO, CA. 9:2401
TELE. (909) 889-0.1 1 5
.• -i FAX (909) 889 -0455
E-MAIL (KNAPPAEOAOLCOM)
13. .Y` x /32
Db' --b"
("TWOO /2 27-/f-
CIZ crSz- lel 61/s p-
X293-
.A_ 7.)" ( yel) :7e
RY: i
CA TEE:
SHT. OF
STRUCTURAL ENGINEERS, INC,
08 SOUTH STODDARD AVENUE
SAN BERNARDINO, CA. 9-2401
TELE. (9-09) 8'89-0115
FAX '909) 889-0455
E MAIL (KNAPPAECAOLCOM)
lee-
Otf /10 5 = d31
WAPa
OJ
63 P.5 eg- 6/-(F-7 e$,413, x1d
37
3 a
/I-
tsS Ki / o � 2-Z
7,)
t>
BY:
D'A Ti E:
SHT 0F
i
KiVAP P cuc �A1�i:G
STRUCTURAL ENGINEERS, INC, �
408 SOUTH S.100.OARD AVENUE
SAN BERNARDINO, CA. 9:24:0.1
TELE. (909 889-0115
:. FAX (909) 889-0455
E-MAIL (KNAPPAEZAOI_CC)M)
yS/AD r_- ,2E- 5/ D -EA
Re- ( L ='li! d/)
naA
53 3
0
5Y:
O'A c:
SHT. 14OF
KNAPP & TANG STRUCTURAL ENGINEERS INC
r
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
Date: 11120103
WADE RESIDENCE...:......_ _...... _ .__ ...............
RB -3
. SPAN DATA
MEMBER DATA
Center Span =
16.00 ft
(:Inertia
2491.000 in4 All distances for load locations refer
Left Cantilever
0.00 ft
E:Elastic Modulus
= 1800000 psi to left support. Neg ('-') distances
Right Cantilever =
0.00 ft
End Fixity
PinlPin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL LOADS
Center Span #1 =
0.03 klft
# 1:
0.090kift @ Left, 0.090kift @ Right, Start @ 0.00it -> 16.00ft
CONCENTRATED LOADS
APPLIED MOMENTS
# 1 = 10.707k at 8.00ft
SUMMARY
Moments
Shears Deflections —
Max. Span Moment =
46.67 k -ft
Left Support
6.31 k Max. @ Span = -0.392 in at 8.00 ft
Max. Mom. Location =
8.00 ft
Right Support
6.31 k
Min. Span Moment =
0.00 k -ft
Reactions
Min. Mom. Location
0.00 ft
Left Support
= 6.31 k
Max @ Left Support =
0.00 k -ft
Right Support
= 6.31 k '" e
Max @ Right Support
0.00 k -ft
Query Values
MAXIMUM MOMENT
46.67 k -ft
Between Supports. @ X = 0.00 ft, M = 0.00 k -ft, V = 6.313 k, Defl. = 0.000 in
o
h
0
0.091111111111111111111111111111111111111111111111111111111
11ME330MENTM0.09
0.03
1 ,6.00 -
Page: Ir
V4.4B (c) 1983.95 ENERCALC Knapp. Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
RB -5
SPAN DATA
Center Span =
21.00 ft
Left Cantilever =
0.00 ft
Right Cantilever
3.00 ft
UNIFORM LOADS
Center Span #1 =
0.03 klft
Right Cant #1 =
0.03 klft
CONCENTRATED LOADS
# 1 = 5.187k at 24.00ft
Moments
Max. Span Moment
18.39 k -ft
Max. Mom. Location =
8.73 ft
Min. Span Moment =
-17.73 k -ft
Min. Mom. Location =
21.00 ft
Max @ Left Support =
0.00 k -ft
Max @ Right Support
-17.73 k -ft
MAXIMUM MOMENT =
18.39 k -ft
Date: 11120103 Page: /(.
MEMBER DATA
I:Inertia 2491.000 in4 All distances for load locations refer
E:Elastic Modulus = 1800000 psi to left support. Neg ('-') distances
End Fixity Pin/Pin means load is on left cantilever
TRAPEZOIDAL LOADS
1E 1: 0.451 klft @ Left, 0.451 klft @ Right, Start @ 0.00ft - > 24.00ft
APPLIED MOMENTS
SUMMARY
Shears Deflections -
Left Support = 4.21 k Max. @ Span = -0.284 in at 9.64 ft
Right Support 6.61 k
Reactions Right Cant = 0.052 in at 24.00 ft
Left Support = 4.21 k
Right Support 12.52 k
Query Values
Between Supports @ X = 0.00 ft, M - 0.00 k -ft, V = 4.206 k, Defl. = 0.000 in
At Right Cantilever @ X = 0.00 ft, M - 0.00 k -ft, V = 0.000 k, Oefl. = 0.000 in
-7
21.00 1 3.00 1
T
V4.413 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
N
0.45111111111111111111111111111111
0.45
0.03
) 0.03
-7
21.00 1 3.00 1
T
V4.413 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
•
'408 SOUTH STODDARD AVE.
1
16.00
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 11120103
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE. _...
SPAN DATA
MEMBER DATA
Center Span 16.00 ft
(:Inertia
2491.000 in4 All distances for load locations refer
Left Cantilever = 0.00 ft
E:Elastic Modulus
1800000 psi to left support. Neg ('-') distances
Right Cantilever, 0.00 ft
End Fixity
PinlPin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL.LOADS
Center Span #1 0.03 klft
# 1:
0.090kift @ Left, 0.090kift @ Right, Start @ O.00ft -> 16.00ft
CONCENTRATED LOADS
APPLIED MOMENTS
# 1 = 12.520k at 6.00ft
SUMMARY
Moments
Shears Deflections
Max. Span Moment = 50.48 k -ft
Left Support
= 8.78 k . Max. @ Span = -0.418 in at 7.49 ft
Max. Mom. Location 6.02 ft
Right Support
5.65 k
Min. Span Moment = 0.00 k -ft
Reactions..
Min. Mom. Location = 0.00 ft .
Left Support
= 8.78 k
Max @ Left Support = 0.00 k'ft
Right Support
5.65 k
Max @ Right Support = 0.00 k -ft
Query Values
MAXIMUM MOMENT = 50.48 Ot
Between Supports @ X = .0.00 ft, M = 0.00 k -ft, V = 8:785 k, Defl. = 0.000 in
N,
N'
N
0.09
0.09
0.03
V4.48 (c) 1983.95 ENERCALC
Page: /:7
Knapp Architectural Engineers, Inc, Kw0601567
•
1
16.00
V4.48 (c) 1983.95 ENERCALC
Page: /:7
Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC ,
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE. .-..
RB -7
SPAN DATA
Center Span =
7.50 ft
Left Cantilever
2.50 ft
Right Cantilever =
0.00 ft
UNIFORM LOADS
Center Span #1 =
0.03 klft
Center Span #2 =
0.29 klft
Left Cant #1 =
0.03 klft
Left Cant #2
0.29 klft
CONCENTRATED LOADS
# 1 = 1.490k at-2.50ft
Moments
Max. Span Moment
Max. Mom. Location
Min. Span Moment
Min. Mom. Location
Max @ Left Support
Max @ Right Support
MAXIMUM MOMENT
m
a
= 0.49 k -ft
5.74 ft
-4.72 k -ft
= 0.00 ft
-4.72 k -ft
0.00 k -ft
4.72 k -ft
1111111111110.3111 111111111flJ11111 I III I 11111111111110.31
(:Inertia
E:Elastic Modulus
End Fixity
Date: 11120103 Page: d
MEMBER DATA
738.000 in4 All distances for load locations refer
1800000 psi - to left support. Neg ('-') distances
Pin/Pin means load is on left cantilever
TRAPEZOIDAL LOADS
SUMMARY
Shears
Left Support =
Right Support =
Reactions
APPLIED MOMENTS
Deflections —
2.28 k Max. @ Span = 0.007 in at 2.00 ft
0.56 k Left Cant = -0.032 in at-2.50,ft
Left Support 4.10 k
Right Support 0.56 k
Query Values
Between Supports @ X = 0.00 ft, M = -4.72 k -ft, V = 1.817 k, Dell. = 0.000 in
At Left Cantilever @ X = 0.00 ft, M = 0.00 k -ft, V = 0.000 k, Defl. = 0.000 in
1 2.50 1 7.50 l
V4.413 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
1408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date:11120103
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE_..-.._.__.-...
RB -8
SPAN DATA
MEMBER DATA
Center Span =
15.00 ft
I:Inertia
= 738.000 in4 All distances for load locations refer
Left Cantilever =
0.00 ft
E:Elastic Modulus
= 1800000 psi to left support. Neg ('-') distances
Right Cantilever =
0.00 ft
End Fixity
Pin/Pin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL LOADS
Center Span #1 =
0.03 klft
it 1:
O.000klft @ Left, 0.205k/ft @ Right, Start @ 2.50ft 15.00ft - -
Center Span #2. =
0:14 klft
.>
CONCENTRATED
LOADS.
APPLIED MOMENTS
ff 1 = 2.760k at 2.50ft
SUMMARY
Moments .
Shears Deflections
Max. Span Moment =
10.86 k -ft
Left Support
3.96 k Max. @ Span = -0.342 in at ' 7.23 ft
Max. Mom. Location =
6.24 ft
Right Support
2.69 k
Min. Span Moment
-0.00 k -ft
Reactions
Min. Mom. Location =
15.00 ft
Left Support
= 3.96 k b
Max @Left Support
0.00 k•ft
Right Support
2.69 k
Max @ Right Support =
0.00 k -ft
Query Values
MAXIMUM MOMENT =
10.86 k -ft
Between Supports . @ X = 0.00 ft, M = 0.00 k -ft, V = 3.961 k, Defl. = 0.000 in
r
,
N
0.00
0.20
Page: /q
V4.4B (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
RB -10
SPAN DATA
Center Span = 14.00 ft (:Inertia
Left Cantilever = 0.00 ft E:Elastic Modulus
Right Cantilever = 0.00 ft End Fixity
UNIFORM LOADS
Center Span #1 = 0.14 klft # 1:
#2:
CONCENTRATED LOADS -
# 1 = 2.760k at 2.50ft
Date: 11121103
MEMBER DATA
= 738.000 in4 All distances for load locations refer
1800000 psi to left support. Neg ('-') distances
Pin/Pin means load is on left cantilever
TRAPEZOIDAL LOADS
0.000kIft @ Left, 0.2O5kift @ Right, Start @ 2.50ft -> 11.50ft
O.2O5kIft @ Left, 0.2O5kIft @ Right, Start @ 11.50ft -> 14.00ft
APPLIED MOMENTS
- SUMMARY
Moments
Shears
Deflections -
Max. Span Moment
9.70 k -ft
Left Support
3.68 k Max. @ Span = -0.266 in at 6.75 ft
Max. Mom. Location
= 5.63 ft
Right Support
2.53 k
Min. Span Moment
= -0.00 k -ft
Reactions
Min. Mom. Location
14.00 ft
Left Support =
3.68 k s
Max @ Left Support
= 0.00 k -ft
Right Support =
2.53 k
Max @ Right Support
= 0.00 k -ft
Query Values
MAXIMUM MOMENT
= 9.70 k -ft
Between Supports @ X =
0.00 ft, M = 0.00 k -ft, V = 3.683 k, Defl. = 0.000 in
0.14
4:�;' z '3- �- i 5e /�'
14.00
Page:2a
V4.46 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw06O1567
KNAPP & TANG STRUCTURAL ENGINEERS INC
' 408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 11121103
SINGLE SPAN BEAWANALYSIS
y WADE RESIDENCE __._.... _.....
RB -10
SPAN DATA
Shears Deflections —
MEMBER DATA
Center Span
19.50 ft
(:Inertia 5904.000 in4 All distances for load locations refer
Left Cantilever
7.50 ft
E:Elastic Modulus 1800000 psi to left support. Neg ('-') distances
Right Cantilever =
0.00 ft
End Fixity Pin/Pin means load is on left cantilever
UNIFORM LOADS
= 16.63 k
TRAPEZOIDAL LOADS
Center Span 111 =
0.45 klft
= 0.00 k -ft
Center Span #2 =
0.03 klft
t.
Left Cant a1 =
0.45 klft
@ X = 0.00 ft, M = -54.93 k=ft, V = 7.507 k, Defl. = 0.000 in
Left Cant #2 =
0.03 klft
@ X'= 0.00 ft, M = , 0.00 k -ft, V = 0.000 k, Defl. = 0.000 in
CONCENTRATED LOADS
'APPLIED MOMENTS
# 1 = 5.520k at-7.50ft
SUMMARY
Moments
Max. Span Moment
Max. Mom. Location
Min. Span Moment
Min. Mom. Location
Max @ Left Support
Max @ Right Support
MAXIMUM MOMENT
N
N
N
0.48 0.48
Shears Deflections —
= 3.65 k -ft
Left Support
= 9.10 k Max. @ Span = 0.082 in at 5.83 ft
= 15.61 ft
Right Support
= 1.87 k Left Cant = -0.412 in at-7.50,ft
_ -54.93 k -ft
Reactions
0.00 ft
Left Support
= 16.63 k
_-54.93.k-ft
Right Support
= 1.87 k
= 0.00 k -ft
Query Values
= 54.93 k -ft
Between Supports
@ X = 0.00 ft, M = -54.93 k=ft, V = 7.507 k, Defl. = 0.000 in
At Left Cantilever
@ X'= 0.00 ft, M = , 0.00 k -ft, V = 0.000 k, Defl. = 0.000 in
0.48 0.48
V4.413 (c) 1983.95 ENERCALC.
Page: a/
Knapp Architectural Engineers, Inc, Kw0601567
l7.50 1
19.50 l
V4.413 (c) 1983.95 ENERCALC.
Page: a/
Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 11121103 Page: 2-2
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
RB -18
SPAN DATA
0.32
MEMBER DATA
Center Span =
32.50 ft
(:inertia
5904.000 in4 All distances for load locations refer
Left Cantilever =
0.00 ft
E:Elastic Modulus
= 1800000 psi to left support. Neg ('-') distances
Right Cantilever =
0.00 ft
Eod Fixity
Pin/Pin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL LOADS
Center Span #1 =
0.03 klft
# 1:
0.000kIft @ Left, 0.328k/ft @ Right, Start @ 0.00ft -> 8.50ft
li 2:
0.328kift @ Left, 0.328k/ft @ Right, Start @ 8.50ft - > 32.50ft
CONCENTRATED LOADS
APPLIED MOMENTS
SUMMARY
Moments
Max. Span Moment
Max. Mom. Location
Min. Span Moment
Min. Mom. Location
Max @ Left Support
Max @ Right Support
MAXIMUM MOMENT
Shears
Deflections
45.31 k -ft Left Support 4.55 k Max. @ Span - -0.804 in at 16.38 ft
16.57 ft Right Support = 5.70 k
-0.00 k -ft Reactions
32.50 ft Leet Support 4.55 k
0.00 k -ft Right Support = 5.70 k
0.00 k -ft Query Values
= 45.31 k -ft Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V 4.545 k, Defl. = 0.000 in
0.32
0.000.32
0.32
0.03
(c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
• 1 408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401 s
TEL: (909) 889-0115 ,
FAX: (909) 889-0455
Oate:.11121103
SINGLE SPAN BEAM ANALYSIS
- WADE RESIDENCE.__._._.,.._..
RB -19
Page:2.3
SPAN DATA
MEMBER DATA
Center Span =
40.50 ft
(:Inertia
= - 19930.000 in4 All distances for load locations refer
Left Cantilever =
0:00 ft
E:Elastic Modulus
= 1800000 psi to left support. Neg I' '1 distances
Right Cantilever' =
0.00 ft
End Fixity
Pin/Pin means load is on left cantilever
UNIFORM LOADS
i-
TRAPEZOIDAL LOADS
Center Span #1 =
0.03 klft
# 1:
0.533kift @ Left, 0.533k/ft @ Right, Start @ 0.00ft -> 30.50ft
# 2:
0.308k1ft @ Left, 0.308k/ft @ Right, Start @ 30.50ft -> 40.50ft
CONCENTRATED
LOADS
APPLIED MOMENTS
# 1 = 7.530k at 30.50ft
SUMMARY
Moments
Shears Deflections
Max. Span Moment =
149.68 k -ft
Left Support
= 12.98 k Max. @ Span = -1.239 in at 20.82 ft
Max. Mom. Location =
23.08 ft
Right Support
15.10 k
Min. Span Moment
0.00 k -ft
Reactions
Min. Mom. Location
0.00 ft
Left Support
= 12.98 k s
Max @ Left Support
0.00 k -ft
Right Support
= 15.10 k
Max @ Right Support =
0.00 k=ft
Query Values
MAXIMUM MOMENT =
149.68 k -ft
Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 12.982 k, Defl. = 0.000 in
M
Ln
r
0.30®0.30 •
11111111111111111110.031111111111111111111111111111111111111111111111111111111
a
Ile
V4.4B Icl 1983-95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567'
KNAPP & TANG STRUCTURAL ENGINEERS INC ,
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 11121103 Page:
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
RB -20
SPAN DATA
MEMBER DATA
Center Span =
23.00 ft
I:Inertia
= 8406.000 in4 All distances for load locations refer
Left Cantilever =
0.00 ft
E:Elastic Modulus = 1800000 psi to left support. Neg ('-') distances
Right Cantilever
0.00 ft
End Fixity
PinlPin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL LOADS
Center Span #1
0.03 klft
1:
0.246k/ft @ Left, 0-246k/ft @ Right, Start @ 0.00ft -> 23.00ft
CONCENTRATED
LOADS
APPLIED MOMENTS
b 1 = 12.980k at 11.00ft
SUMMARY
Moments
Shears Deflections —
Max. Span Moment
92.67 k -ft
Left Support
= 9.95 k Max. @ Span = -0.490 in at 11.36 ft
Max. Mom. Location =
10.99 ft
Right Support
= 9.38 k
Min. Span Moment
0.00 k -ft
Reactions
Min. Mom. Location =
0.00 ft
Left Support
= 9.95 k
Max @ Left Support =
0.00 k -ft
Right Support
= 9.38 k
Max @ Right Support =
0.00 k -ft
Query Values
MAXIMUM MOMENT =
92.67 k -ft
Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 9.946 k, Defl. = 0.000 in
m
m
N
0.2411111111111
0.24
/3 a7
23.00 1
V4.4B (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: -(909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE-
..........
SPAN DATA
MEMBER DATA
Center Span
22.00 ft
Idnertia
2491.000 in4 All distances for load locations refer
Left Cantilever =
0.00 ft
E:Elastic Modulus
1800000 psi to left support. Neg ('-') distances
Right Cantilever =
0.00 ft
End Fixity
PinlPin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL LOADS
Center Span #1
0.03 klft
N 1:
0.144k/ft @ Left, 0.144k/ft @ Right, Start @'0.00ft > 22.00ft
CONCENTRATED LOADS
APPLIED MOMENTS
# lc= 1.080k at 7.00ft
# 2 = 1.080k at 14.00ft
SUMMARY
Moments
Shears Deflections
Max. Span Moment =
18.63 k -ft
Left Support
3.04 k Max. '@ Span = -0.364 in at 11.00 ft
Max. Mom. Location
11.26 ft,
Right Support
= • 2.94 k
Min. Span Moment
0.00 k -ft
Reactions
Min. Mom. Location =
0.00 ft
Left Support
= 3.04 k s
Max @ Left Support
0.00 k -ft
Right Support
2.94 k
Max @ Right Support
0.00 k -ft
Query Values
MAXIMUM MOMENT =
18.63 k -ft
• Between Supports @ X = 0.00 ft, M - 0.00 k4t, V = 3.043 k, Defl. = 0.000 in
ao
ao
o
�o
0.14
0.14
0.03
22.00 1 -
V4.4U IC► 1t1?JJ-yG tNtK1;ALI:
Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO,:CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 11121103
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE ... .
RB -23
SPAN DATA
MEMBER DATA ' 1
Center Span =
27.00 ft
I:Inertia
5904.000 in4 All distances for load locations refer
Left Cantilever
0.00 ft
E:Elastic Modulus
1800000 psi to left support. Neg ('-') distances
Right Cantilever =
0.00 ft
End Fixity
Pin/Pin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL LOADS
Center Span N1
0.03 klft
# 1:
0.298k/ft @ Left, 0.298klft @ Right, Start @ 0.00ft -> 27.00ft
# 2:
0.451kift @ Left, 0.287kift @ Right, Start @ 2.00ft -> 27.00ft
CONCENTRATED LOADS
APPLIED MOMENTS
N 1 = 3.04Ok at 2.00ft
SUMMARY
Moments
Shears Deflections -
Max. Span Moment =
66.80 k -ft
Left Support
= 11.83 k Max. @ Span = -0.830 in at 13.34 It
Max. Mom. Location
12.96 ft
Right Support
= 9.29 k
Min. Span Moment =
0.00 k -ft
Reactions
Min. Mom. Location
0.00 ft
Left Support
= 11.83 k i
Max @ Left Support
0.00 k -ft
Right Support
= 9.29 k
Max @ Right Support =
0.00 k -ft
Query Values
MAXIMUM MOMENT =
66.80 k -ft
Between Supports @ X = 0.00 ft, M = - 0.00 k -ft, V = 11.830 k, Oefl. = 0.000 in
a
• o
m
0.45
0.28
0.29
0.29
I 27.00 f .
V4.4B (c) 1983.95 ENERCALC
Page: 96
Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 11121103 Page: 27
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
RB -24
SPAN DATA
MEMBER DATA
Center Span
27.50 ft
(:Inertia
= 11530.000 in4 All distances for load locations refer
Left Cantilever
0.00 ft
E:Elastic Modulus = 1800000 psi to left support. Neg ('-') distances
Right Cantilever
0.00 ft
End Fixity
Pin/Pin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL LOADS
Center Span #1 =
0.03 klft
# 1:
0.308kIft @ Left, 0.308kift @ Right, Start @ 0.00ft -> 27.50ft
CONCENTRATED LOADS
APPLIED MOMENTS
N 1 = 9.290k at 14.00ft
SUMMARY
Moments
Shears Deflections —
Max. Span Moment
95.67 k -ft
1 -aft Support
= 9.21 k Max. @ Span = -0.545 in at 13.80 ft
Max. Mom. Location =
14.02 ft
Right Support
= 9.38 k
Min. Span Moment
-0.00 k -ft
Reactions
Min. Mom. Location
27.50 ft
Left Support
9.21 k
Max @ Left Support =
0.00 k -ft
Right Support
9.38 k
Max @ Right Support
0.00 k -ft
Query Values
MAXIMUM MOMENT
95.67 k -ft
Between Supports @X = 0.00 ft, M = 0.00 k -ft, V = 9.208 k, Dell. - 0.000 in
0
N
Ot
0.30
0.30
0.03
! 27.50 1
V4.413 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
T . ,408 SOUTH STODDARD AVE.
Deflections
SAN BERNARDINO, CA 92401
= 0.00 k -ft
Left Support . -i
TEL: (909) 889-0115
Max. @ Span = 0.034 in at 2.48 ft
Max. Mom. Location
FAX: (909) 889-04'5.5: ;.
t. f
Right Support
5.27 k
Left Cant = 0.203 in at 4.00 ft'
Min. Span Moment
Date: 11121103
SINGLE SPAN BEAM ANALYSIS
0.03
Min. Mom. Location
y.
i.
WADE RESIDENCE ..._.,-
e
Max @ Left Support
RB -24
Right Support
-5.27 k
SPAN DATA
Max @ Right Support
MEMBER DATA
Center Span 6.00 ft
(:Inertia
= 2491.000 in4 All distances for load locations refer
Left Cantilever 4.00 ft
E:Elastic Modulus
1800000 psi to left support. Neg ('-') distances
Right Cantilever' = 0.00 ft
End Fixity
PinlPin means load is on left cantilever .
UNIFORM LOADS
At Left Cantilever @ X =
TRAPEZOIDAL LOADS
Center Span #1 = 0.03 klft
# 1:
0.451kIft @ Left, 0.533k/ft @ Right, Start @-4.00ft -> 6.00ft
Left Cant #1 = 0.03 klft
CONCENTRATED LOADS
APPLIED MOMENTS
# 1 = 9.380k at-4.00ft
SUMMARY"
Page: 2$ .
Moments
Shears
Deflections
Max. Span Moment
= 0.00 k -ft
Left Support . -i
11.36 k
Max. @ Span = 0.034 in at 2.48 ft
Max. Mom. Location
= 0.00 ft
Right Support
5.27 k
Left Cant = 0.203 in at 4.00 ft'
Min. Span Moment
= -41.46 k -ft
Reactions
0.03
Min. Mom. Location
0.00 ft
Left Support
19.87 k
e
Max @ Left Support
= -41.46 k -ft
Right Support
-5.27 k
Max @ Right Support
0.00 k -ft
Query Values
MAXIMUM MOMENT
41.46 k -ft
Between Supporits @ X =
0.00 ft, M = .-41.46
k4t, V-= 8.500 k, Defl. = 0.000 in
At Left Cantilever @ X =
0.00 ft, M ='
0.00 Wt, V = 0.000 k, Defl. = 0.000 in
ro
rn
T
,
0.45
0.53
0.03
0.03
V4.46 (c) 1983.95 ENERCALC
Y
C�03. 6 :C 8
Knapp Architectural Engineers, Inc, Kw0601567
T
Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
RB -27
SPAN DATA -
Center Span =
Left Cantilever =
Right Cantilever =
UNIFORM LOADS
Center Span #1 =
21.00 ft (:Inertia
0.00 ft E:Elastic Modulus
0.00 ft End Fixity
0.02 klft # 1:
#2:
#3:
CONCENTRATED LOADS
# 1 = 5.520k at 2.00ft
# 2 = 5.520k at 11.00ft
Moments
Max. Span Moment
= 49.01 k -ft
Max. Mom. Location
- 11.00 ft
Min. Span Moment
-0.00 k -ft
Min. Mom. Location
= 21.00 ft
Max @ Left Support
0.00 k -ft
Max @ Right Support
0.00 k -ft
MAXIMUM MOMENT
= 49.01 k -ft
Date: 11124103
MEMBER DATA
= 118.000 in4 All distances for load locations refer
29000000 psi to left support. Neg ('-') distances
PinlPin means load is on left cantilever
TRAPEZOIDAL LOADS
0.082kift @ Left, 0.082kIft @ Right, Start @ 0.00ft -> 2.00ft
0.082kIft @ Left, 0.082k1ft @ Right, Start @ 11.00ft -> 21.00ft
0.410k1ft @ Left, 0.410k1ft @ Right, Start @ 2.00ft -> 11.00ft
- APPLIED MOMENTS
SUMMARY
Shears Deflections
Left Support 10.75 k Max. @ Span = -1.038 in at 10.25 ft
Right Support 5.42 k
Reactions
Left Support = 10.75 k
Right Support 5.42 k
Query Values
Between Supports @ X - 0.00 ft, M = 0.00 k -ft, V = 10.753 k, Oefl. = 0.000 in
N N
N V7
N Vj
0.41 0.41
0.0811111 MMI0.08
0.08®0.08
EEMEOMMITM5.5
( 21.00 1
V4.413 (c) 1983.95 ENERCALC
W !d )(22
Page:
Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
-
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 11124103
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
RB -30
SPAN DATA
MEMBER DATA
Center Span =
20.00 ft
I:Inertia
= 118.000 in4 All distances for load locations refer. -
Left Cantilever =
0.00 ft
E:Elastic Modulus
29000000 psi. to left support. Neg ('-') distances
Right Cantilever =
0.00 ft
End Fixity
PinlPin means load is on left cantilever
UNIFORM LOADS
' .
TRAPEZOIDAL LOADS
Center Span #1 =
0.02 klft
# 1:
0.082k/ft @ Left, 0.082kIft,@ Right, Start @ 0.00ft -> 15.00ft
# 2:
0.615k/ft @ Left, 0.615kift @ Right, Start @ 15.00ft -> 20.00ft
CONCENTRATED LOADS
APPLIED MOMENTS
# 1 = 9.240k at 15.00ft
SUMMARY
Moments '
Shears Deflections
Max. Span Moment =
43.55 k -ft
Left Support
3.68 k Max. @ Span = -0.733 in at 1 1.04ft
Max. Mom. Location =
15.00 ft
Right Support
10.30 k
Min. Span Moment
0.00 k -ft
Reactions -.
Min. Mom. Location =
0.00 ft
Left Support
, '' = 3.68 k b
Max @ Left Support =
0.00 k -ft
Right Support
10.30 k
Max @ Right Support =
0.00 k -ft
Query Values
MAXIMUM MOMENT =
43.55 k'ft
Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 3.683 k, Defl. _. 0.000 in
#
N
a,
0.61®0.61
0.02
22
I
20.00
a
V4.46 (c) 1983-95 ENERCALC
Page: 3d
Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
RB -34
SPAN DATA
Center Span =
21.00 ft
LInertia
Left Cantilever =
0.00 ft
E:Elastic Modulus
Right Cantilever =
0.00 ft
End Fixity
UNIFORM LOADS
Center Span #1 =
0.02 klft
rr 1:
#2:
CONCENTRATED LOADS
# 1 = 6.649k at 6.O0ft
Date: 11124103
MEMBER DATA
118.000 in4 All distances for load locations refer
29000000 psi to left support. Neg ('-') distances
Pin/Pin means load is on left cantilever
TRAPEZOIDAL LOADS
0.451kIft @ Left, 0.451kIft @ Right, Start @ 0.00ft -> 6.00ft
0.082k/ft @ Left, 0.082k/ft @ Right, Start @ 6.00ft -> 21.00ft
APPLIED MOMENTS
SUMMARY
Moments Shears Deflections
Max. Span Moment = 37.91 k -ft Left Support 7.74 k Max. @ Span = -0.722 in at 9.58 ft
Max. Mom. Location = 6.01 ft Right Support 3.31 k
Min. Span Moment = 0.00 k -ft Reactions
Min. Mom. Location = 0.00 ft Left Support 7.74 k
Max @ Left Support = 0.00 k -ft Right Support 3.31 k
Max @ Right Support 0.00 k -ft Query Values
MAXIMUM MOMENT = 37.91 k -ft Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 7.739 k, Defl. = 0.000 in
l21.00 1
W /OAC 22
Page: 3 /
V4.413 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
RISA -2D (R) Version 3.03
Job
Page 32
Date
WADE RESIDENCE
RB -35
Units Option US Standard
AISC Code Checks 9th Edition ASD
Shear Deformation: No
P -Delta Effects No (3�
Redesign No
Edge Forces No 4- 4
A.S.I.F. 1.333-61 /aaC22
-----------------------------------------------
Node BoundaryConditions
-No- X-Coord Y-Coord X-dof Y-dof Rotation Temp.
------- (ft) -------- (ft) ----- (in, K/in) ---- (in, K/in) --- (r, K-ft/r) ----- (F) -
1 0.-00 0.00 1 1 1 0.00
2 0.00 13.00 0.00
3 -5.00 13.00 0.00
---------------
Material Elastic. Poisson's Thermal Weight Yield Stress
Label Modulus Ratio Coefficient Density (Fy)
--------------- (Ksi)----------------------- (F)---. ----- (K/ft3)------ (Ksi)----
STEEL 29000.00 0.30000 0.65000 0.490 36.000
--------------------------------
--------------
Section Database Matl. Area Moment of As y/y
Label Shape Set Inertia Coef
-------------------------------------- (inA2)--------- (in�4)-----------------
BM W10X22 STEEL 6.49 118. 000 1 . 20'
COL TU6X6X8 STEEL 10.40 50.500 1.20
-----------------------------
I J I Releases J End Offsets
No Node Node Section x y z x y z Sec Sway I J Length
--------------------------------------
1 1 - 2 COL 13.00
2 2 - 3 BM 5.00
------------------------ ___
I J Unbraced Lengths g K Factors Bending Coefs
__..,.. No Node Node Lb -in Lb -out Lc In Out Cm Cb
-------------------- ( 1 t) ----- ( f t) ----- ( f t ) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
--
1 1 - 2
2 2 _ 3
RISA -2D (R) Version 3.03
Job
Page_ 33
Date
WADE RESIDENCE
RB -35
--------------------------------------------7---------
BLC Basic Load Case Load Totals
No. Description Nodal Point Dist.
-------------------------------------------------
1 D+L 1
Nodal Loads, BLC 1: D+L
------------------------------------------
Node
Number Global X Global Y Moment
------------------------(K)------------------(K)------------------(K,-ft)----
3 0.000 -1.255 0.000
— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — b -
- — — — — — — — — — —
Load Combination Self Wt BLC BLC BLC BLC BLC W E
No. Description Dir Fac Fac Fac Fac Fac Fac DYNA S V
-------------------------------------------
1 D+L Y -1 1 1
Dynamic Analysis Data
Number of modes (frequencies) 3
Basic Load Case for masses None
BLC mass direction of action X only
Acceleration of Gravity 32.20 ft/sec**2
Load Combination is 1 D+L
Nodal Displacements
----------------------------------------------
Node Global X
Global Y
Rotation
---------------------(in)-----------------(in)----------------
(rad)---------
1 0.00000
0.00000
0.00000
2 -0.65316
-0.00083
0.00837
3 -0.65316
-0.53054
0.00905
Load Combination is 1 D+L
Member End Forces
----------------------------------
Nodes=________= I-EndJ-End
-------------
No I J Axial Shear
Moment Axial
Shear
Moment
---------------(K)--------(K)------(K-ft)-------(K)--------(K)------(K-ft)--
1 1- 2 1.83 -0.00
-6.55 -1.37 0.00
6.55
2 2- 3 0.00 -1.37
-6.55 0.00 1.25
-0.00
RISA -2D (R) Version 3.03
WADE RESIDENCE
RB -35
------------------
Job
Page 3
Date
Load
Combination is 1 D+L
AISC
Code Checks
-------------------------------------------------------------------------
Nodes
Member
Quarter
Points
No
I J Maximum 0
---------------------------------------------------------------
1/4
1/2
1 3/4 L Shear
1
1- 2 0.2073 0.2073
0.2066
0.2059
0.2053 0.2046 0.0000
2
2- 3 0.1426 0.1426
0.1058
'0.0698
0...0345 0.0000 0.0388
s
AN\
cft WADE
- ---------------- --
m
KIVAP P gc TAPl.G
STRUCTURAL ENGINEERS, INC,
408 SOUTH S:TODDARD AVENUE V/AD RE -510 EX/GE
h SAN BERNARDINO', CA. 9:240.1
1..
TELT. (909) 889-0.115 `
FAX (909 889-0455
—MAIL (KNAPPAE®AOL_COM)
s w
BY:
DATE:
SHT. OF
G ' 'ya
Alvl
G��L-Ja�c�oxidx.g.
i
3a -x X, J -A 16 k\143
7.31
3
KNAP P <8c �AIV:G
STRUCTURAL ENGINEERS, INC,
04- 40.8 SOUTH S:TO.D:DARD AVENUE
- SAN BERNARDINO, CA. 9.2401
;`. TELE. (909 889-0-11 5
FX (9093 _
E-MAIL (KNAPPAE® OLOCOM)
WAPa ,'E- 5/P -E-A /c=-
S#
V 32 x 14 3
LS' i1 -x 64 X' 143...=�3y3
fyo4� �= 919' ��/� c syr -s, iii)
A,0144
4�6
_
01`6
Alo No 4�0
.�
mall V%-
�3a
7'
i°
LY: ,
SHT. 3% OF
STRUCTURAL ENGINEERS, INC,
408 SOUTH STOCIDARD AVENUE
SAN BERNARDINO, CA. 92401
TELE. (9:09-) 889-0115.
889-C4.55
-MAIL (KNAPPAE(ZAOLCOM)
761-)
2 -, Iq /
q-1
's.-'herw I�`all
61-7
14
WA 01 =_ , eE- 51, 0 -Exl c =-
5AI x?
�a#J_W7 sem
Te4
'V== 3d )(�/>(, 1-Y /43 = /Jyc
x 1<)le7
7/6)
BY:
DATE:
!� A
SHT,�l 0 OF
KNAP P 8c
STRUCTURAL ENGINEERS, INC,
40.8 SOUTH S.TOODARD AVENUE
SAN BERNARDINO, CA. 9.2401
TELE. (909 859-0115
FAX (9-093 889-0455
( )
Nlme�lf �ii� 6Q
BY: -
DATE:
SHT. 97
DF _
��-
v. /
RISA -2D (R) Version 3.03
Job
Page
jZ-
Date
WADE RESIDENCE
MOMENT FRAME a@
Units Option : US Standard
AISC Code Checks : 9th Edition ASD
Shear Deformation: No
P -Delta Effects No
Redesign : No
Edge Forces : No
A.S.I.F. : 1.333
----------------------------------------------------------------------------
Node Boundary Conditions
No X-Coord Y-Coord X-dof . Y-dof Rotation Temp.
----------- (ft) -------- (ft) ----- (in,K/in)----(in,K/in)--- (r,K-ft/r)----- (F)-
1 0.00 0.00 R R R 0.00
2 21.50 0.00 R R R 0.00
3 0.00 11.00 0.00
4 21.50 11.00 0.00
-------------------------------------------------------------------------
Material Elastic Poisson's Thermal Weight Yield Stress
Label Modulus Ratio Coefficient Density I (Fy)
--------------- (Ksi)----------------------- (F) -------- (K/ft3)------ (Ksi)----
STEEL 29000.00 0.30000 0.65000 0.490 .36.000
------------------------------------------------------------------------
Section Database Matl. Area Moment of As y/y
Label Shape Set Inertia Coef
--------------------- ----------------- (in^2)--------- (in�4)------ ----
COL PI6X.5 STEEL 8.64 32.938 1.20
BM W14X34 STEEL 10.00 340.000 1.20
----------------------------------------------------------------------------
I J I Releases J End Offsets
No Node Node Section x y z x y z Sec Sway I J Length
----------------------------------------------(in)----(in)------(ft)
1 1- 3 COL 11.00
2 2 - 4. COL 11.00
3 3 - 4 BM 21.50
----------,------------------------------------------------------------------
I J Unbraced Lengths K Factors Bending Coefs .
No Node Node Lb -in Lb -out Lc In Out Cm Cb
-------------------- (ft) ----- ( f t) ----- ( f t ) -----------------------------------
3
----------------------•----------
3
ti
RISA -2D (R) Version 3.03
Job
Page �(
Date
WADE RESIDENCE
MOMENT FRAME aO
-------------
-------------------------------------------------------------------
I J Unbraced Lengths K Factors Bending Coefs
No Node Node Lb -in Lb -out Lc In Out Cm Cb
--------------------(ft)-----(ft)-----(ft)--------------
--------------------
2 2 - 4
3 3 - 4 2.00 2.00 2.00'
---------------------------------------------------------------------
BLC Basic Load Case Load Totals
No. Description Nodal Point Dist.
----------------------------------------------------------------
1 D+L+S 1 3
Nodal Loads, BLC 1: D+L+S
-------------------------------------------------------------
Node
Number Global X Global Y Moment
------------------------(K)------------------(K)------------------(K-ft)----
3 1.882 0.000 0.000
Member Distributed Loads,3LC 1: D+L+S
Memb I J
Start
End
Start
End
No
Node Node
Dir Magnitude
Magnitude
Location
Location
---------------------(K/ft,F)-----(K/ft,F)---------(ft)---------(ft)----
3
3 - 4
Y -0.103
-0.103
0.000
21.500
3
3 - 4
Y 0.000
-0.226
0.000
10.750
3
3 - 4
Y -0.226
0.000
10.750
21.500
Load
-----------------.-------------------------------------------
Combination
Self Wt BLC
BLC BLC BLC
BLC
W E
No.
Description
Dir Fac Fac
----------------------------------------------------------
Fac Fac Fac
Fac
DYNA S V
1 D+L+S
Y -1 1 1
Dynamic Analysis Data
Number of modes (frequencies) 3
Basic Load Case for masses None
BLC mass direction of action X only
Acceleration of Gravity 32.20 ft/sec**2
Load Combination is 1 D+L+S
Nodal Displacements
-----------------------------------------------------------------------
Node Global X Global Y Rotation
---------------------(in)-----------------(in)----------------(rad)---------
1 0.00000 -0.00000 -0.00000
r
RISA -2D (R) Version 3.03
Job
Page 4 -7 -
Date
WADE RESIDENCE
MOMENT. -FRAME. -&.1 -
Node .
Global:X
Global Y
Rotation
------------------
.----(in) -----------------
(in) ---------------- (rad)---------
2
0.00000
-0.00000
-0.00000
3
0.20686
_0.00126
-0.00149
4
0.20567
-0.00175
0.00096
Load Combination is 1 D+L+S
Reactions
----------------------------------------------------------------------------
Node
Global X
Global Y
Moment
----------------------(K)------------------(K)---------------(K-ft)---------
1
-0.54185
2.54457
3.87685
2
-1.34015
3.47779.
6.79304
Totals
-1.88200
6.02235
10.66989
Load Combination is 1
D+L+S
Member End
Forces
----------------------------
Nodes,
_________=
-----------------------------------------------
I -End =_________
_________=
J-End
No I J
Axial
Shear
Moment Axial
Shear
Moment
---------------
(K) --- -
---- (K) ------ (K -ft) ------- (.K) --------
(K) ------
(K -ft) --
1 1- 3
2.54
0.54
3.88 -2.22
-0.54
2.08
2 2- 4
3.48
1.34
6.79 -3.15
-1.34
7.95
3 3- 4
1.34.
2.22
-2.08 -1.34
3.15
-7.95
Load Combination is 1
D+L+S
AISC Code Checks
----------------------------------------------
Nodes
------------------------------
Member Quarter Points
No I J
----------------------------------------------------------------------------
Maximum
0
1/4 1/2 3/4
L
Shear
1 1- 3
0.1960
0.1960
0.1269 0.0578 0.0433
0.1113
0.0044
2 2- 4
0.3875
0.3.366
0.1665 0.0496 0.2186
0..3875
0.0108
3 3- 4
0.1486
0.0281
0.1258 0.1486 0.0737
0.0890
0.0550
RISA -2D (R) Version 3.03
Job
Page_ 43
Date
WADE RESIDENCE
MOMENT FRAME
Units Option US Standard
AISC Code Checks 9th Edition ASD
Shear Deformation: No
P -Delta Effects No
Redesign No
Edge Forces No
A.S.I.F. 1.333
---------------------------------
Node Boundary Conditions
No X-Coord Y-Coord X-dof Y-dof Rotation Temp.
----------- (ft) -------- (f=) ----- (in,K/in)---- (in,K/in)---(r,K-ft/r)----- (F)-
1 0.00 0.00 R R R 0.00
2 21.50 0.00 R R R 0.00
3 0.00 11.00 0.00
4 21.50 11.00 0.00
-------------------------------------
Material Elastic Poisson's Thermal Weight Yield Stress
Label Modulus Ratio Coefficient Density (Fy)
--------------- (Ksi)----------------------- (F) -------- (K/ft3)------ (Ksi)----
STEEL 29000.00 0.30000 0.65000 0.490 36.000
------------------------------
Section Database Matl. Area Moment of As
Label Shape Set Inertia Coef
-------------------------------------- (in A2) --------- (in�4)-----------------
COL' PI6X.5 STEEL 8.64 32.938 1.20
BM W14X34 STEEL 10.00 340.000 1.20
-------------------------------
I J I Releases J End Offsets
No Node Node Section x y z x y z Sec Sway I J Length
------------------------------------------------------(in)----(in)------(ft)
1 1 - 3 COL 11.00
2 2 - 4 COL 11.00
3 3 - 4 BM 21.50
--------------------------------------------
I J Unbraced Lengths K Factors Bending Coefs
No Node Node Lb -in Lb -out Lc In Out Cm Cb
-----------------(ft)-----(ft)-----(ft)----------------------------------
1 1 - 3
RISA -2D (R) Version 3.03
r
Job
Page
Date
WADE RESIDENCE
MOMENT FRAME----------------
---------------------------------------------------------=--
--
I J Unbraced Lengths K Factors Bending Coefs
No Node Node Lb -in Lb -out Lc In Out Cm Cb-
----(----------------
ft)-----(ft)-----(ft)-----------------------
------------
2 2 4
3 3 - 4 2.00 2.00 2.00
--------------------------------------------------=------
BLC Basic Load. Case Load Totals
No. Description Nodal Point Dist.
------------------------------------------------------
1 D+L+S 1 3
Nodal Loads, BLC 1: D+L+S
----------------------------------
Node
Number Global X Global Y Moment
------------------------(K)------------------(K)-------------------(K-ft)----
3 5.270 0.000 1 1 0.000
Member Distributed Loads,BLC 1: D+L+S
Memb I J
Start
End
Start
End
No Node Node
Dir
Magnitude
Magnitude
Location
Location
--------------- --'-
-------
(K/ft', F) -----
(K/ft, F) ---------
(ft) ---------
(ft) ----
3 3 - 4
Y
-0".103
-0.103
0.000
21.500
3 3 - 4
Y
0.000
-0.226
0.000
10.750
3 3 - 4
Y
-0.226
0.000
10.750
21.500
Load Combination
Self
----------------------------
Wt BLC
BLC BLC
BLC BLC
W E
No. Description
Dir
Fac Fac
Fac Fac
Fac Fac
DYNA S V
1 D+L+S
Y -1
-------------------------------
1 1
Dynamic Analysis.Data
Number of modes (frequencies) 3
Basic Load Case for masses None
BLC mass direction of action X only
Acceleration of Gravity 32.20 ft/sec**2
Load Combination is 1 D+L+S
Nodal Displacements
-----------------------------------------------------------------------------
Node Global X Global Y Rotation
---------------------(in)-----------------(in)----------------(rad)---------
1 0.00000 -0.00000 -0.00000
RISA -2D (R) Version 3.03
Job
Page_
Date
WADE RESIDENCE
MOMENT FRAME Oa _ C2 _ c;1 66N,l/. BNG
Node
Global X
Global Y
Rotation
---------------------(in)-----------------(in)----------------(rad)---------
----------------------
2
0.00000
-0.00000
-0.00000
3
0.57894
-0.00081
-0.00197
4
0.57624
-0.00219
0.00048
Load Combination is 1 D+L+S
Reactions
-------------------------------------------------------
Node
Global X
Global Y
Moment
----------------------
(K) ------------------ (K) ---------------
(K=ft)---------
1
-2.23883
1.70457
13.49867
2
-3.03117
4.31778
16.37929
Totals
-5.27000
6.02235
29.87796
Load Combination is 1
D+L+S
Member End
Forces
Nodes
=________=
----------------------------------
I -End =---------
-- =
J -End =-----------
No I J
Axial
Shear
Moment Axial
Shear
Moment
----------------
(K) --------
(K) ------
(K -ft) ------- (K) --------
(K) ------
(K -ft) --
1 1- 3
1.70
2.24
13.50 -1.38
-2.24
11.13
2 2- 4
4.32
3.03
16.38 -3.99
-3.03
16.96
3 3- 4
3.03
1.38
-11.13 -3.03
3.99
-16.96
Load Combination is 1
D+L+S
AISC Code Checks
Nodes
------------------------------------
Member Quarter Points
No I J
Maximum
0
------------------------------------------------
1/4 1/2 3/4
L
Shear
1 1- 3
0.6328
0.6328
0.3490 0.0652 0.2388
0.5215
0.0180
2 2- 4
0.8081
0.7834
0.3994 0.0423 0.4252
0.8081
0.0244
3 3- 4
0.1907
0.1301
0.1810 0.1568 0.0351
0.1907
0.0696
1. 0 RISA -2D (R) Version 3.03
Job
Page
Date
WADE RESIDENCE
MOMENT FRAME b
------------
Units Option US Standard
AISC Code Checks 9th Edition ASD.
Shear Deformation: No
P -Delta Effects No
Redesign No
Edge Forces No
A.S.I.F. 1.333
--------------------------------------------------------
Node Boundary.Conditions
No X-Coord Y-Coord X-dof Y-dof Rotation Temp.
----------- (ft) -------- (ft)-----(in,K/in)---- (in,K/in)--- (r,K-ft/r)----- (F)-
1 0.00 0.00 R R R 0.00
2 21.50 0.00 R R R 0.00
3 0.00 11.00 0.00
4 21.50 11.00 0.00
------------------------------ --
Material Elastic Poisson's Thermal Weight Yield Stress
Label Modulus Ratio Coefficient Density (Fy)
--------------- (Ksi)----------------------- (F) -------- (K/ft3)------ (Ksi)----
STEEL 29000.00 0.30000 0.65000 0.490 36.000
----------------7----------
Section Database Matl. Area Moment of As y/y
Label Shape Set Inertia Coef
------------------------------------ ^ ^
COL PI6X.432 STEEL 7.56 29.461 1.20
BM W16X31 STEEL 9.12 375.000 1.20
---------------------------------------------------
I J I Releases J End Offsets
-No-Node Node Section x y z x y z Sec Sway I J Length
--------------------------------------------------(in)----(in)--.----(ft)
1 1 - 3 COL 11.00
2 2 - 4 COL 11.00
3 3 - 4 BM 21.50
-------------------------------------------------
I J Unbraced Lengths K Factors Bending Coefs
No Node Node Lb -in Lb -out Lc In Out Cm Cb
-------------------- (ft) ----- (.c ----- (ft) ----------------------------------
1 1 - 3
RISA -2D (R) Version 3.03
WADE RESIDENCE
MOMENT FRAME b
Job
Page ¢7
Date
-----------------------------------------------------------
I J Unbraced Lengths K Factors Bending Coefs
No Node Node Lb -in Lb -out Lc In Out Cm Cb
--------------------(ft)-----(ft)-----(ft)----------------------------------
2 2 - 4
3 3 - 4 2.00 2.00 2.00
-------------------------------------------------------
BLC Basic Load Case Load Totals
No. Description Nodal Point Dist.
---------------------------------------------------
1 D+L+S 1 1
Nodal Loads, BLC 1: D+L+S
----------------------------------------------------
Node
Number Global X Global Y Moment
------------------------ (_{)------------------ (K) ------------------ (K -ft) ----
3 1.882 0.000 0.000
Member Distributed Loads,BLC 1: D+L+S
Memb I J Start End Start End
No Node Node Dir Magnitude Magnitude Location Location
------------------------- (K/ft,F)----- (K/ft,F)--------- (ft) --------- (ft) ----
3 3 - 4 Y -0.226 -0.226 0.000 21.500
-------------------------------------------
Load Combination Self Wt BLC BLC BLC BLC BLC W E
No. Description Dir Fac Fac Fac Fac Fac Fac DYNA S V
------------------------------------------------
1 D+L+S Y -1 1 1
Dynamic Analysis Data
Number of modes (frequencies) 3
Basic Load Case for masses None
BLC mass direction of action X only
Acceleration of Gravity 32.20 ft/sec**2
Load Combination is 1 D+L+S
Nodal Displacements
--------------------------------------------------
Node
Global X
Global Y
Rotation
---------------------(in)-----------------(in)----------------(rad)---------
1
0.00000
-0.00000
-0.00000
2
0.03000
-0.00000
-0.00000
3
0.22765
-0.00147
-0.00132
RISA -2D (R) Version 3.03
Job
Page
Date
WADE RESIDENCE
MOMENT FRAME b
---------------------------------
Node Global X Global Y Rotation
---------------------(in)-----------------(in)----------------(rad)---------
4 0.22643 -0.00203 0.00084
Load Combination is 1 D+L+S
Reactions
Node
Global X
Global Y
Moment
----------------------(K)------------------(K)---------------(K-ft)---------
1
-0.62603
2.57664
4.15591
2
-1.25597
3.51528
6.45570
Totals
-1.88200
6.09192
10.61160
Load Combination is 1
D+L+S
Member End
Forces
Nodes
_________=
-------------------------------------
I-EndJ-End
No I J
Axial
Shear
Moment Axial
Shear
Moment
---------------(K)--------(K)------(K-ft)-------(K)--------(K)------(K-ft)--
1 1- 3
'2
2.58
0.63
4.16 -2.29
-0.63
2.73
2- 4
3.52
1.26
6.46 -3.23
-1.26
7.36
3 3- 4
1.26
2.29
-2.73 -1.26
3.23
-7.36
Load Combination is 1
D+L+S
AISC Code Checks
Nodes
-------
------- -----------------
Member Quarter Points
______
No I J
Maximum
0
1/4 1/2 3/4
--------------------
L
Shear
1, 1- 3
0.2341
0.2341
----------------------
0.1450 0.0559 0.0706
0.1585
0.0058
2 2- 4
0.4041
0.3598
0.1816 0.0499 0.2270
0.4041
0.0115
3 3- 4
0.1408
0.0359
0.1280 ' 0.1408 0.0741
0.0854
0.0514
RISA -2D (R) Version 3.03
Job
Page
Date
WADE RESIDENCE
No
Edge Forces No
MOMENT FRAME b
/2- =&1-2
7 -ITA
"AlAl,
Units Option
AISC Code Checks
: US Standard
9th Edition ASD
Shear Deformation: No
P -Delta Effects : No
Redesign
No
Edge Forces No
A.S.I.F.
1.333
Node
Boundary Conditions
No
X-Coord Y-Coord X-dof Y-dof Rotation Temp.
-----------
(ft) -------- (ft)
----- (in, K/in) ---- (in,K/in) --- (r, K-ft/r) ----- (F) -
1
0.00 0.00
R R R 0.00
2
21.50 0.00
R R R 0.00
3
0.00 11.00
0.00
4
21.50 11.00
0.00
Material
Elastic
-------------------------------------
Poisson's Thermal Weight Yield Stress
Label
Modulus
Ratio Coefficient Density (Fy)
---------------
(Ksi)-----------------------
(F) -------- (K/ft3)------ (Ksi)----
STEEL
29000.00
0.:0000 0.65000 0.490 36.000
Section
Database
-------------------------------------------
Matl. Area Moment of As
Label
Shape
Set Inertia Coef
---------------------
^
COL
PIGX.432
STEEL 7.56 29.461 1.20
BM
W16X31
STEEL 9.12 375.000 1.20
I
J
-----------------------------------------
I Releases J End Offsets
No -Node
--------------------------------------------------(in)----(in)------(ft)
Node Section
x y z x y z Sec Sway I J Length
1 1
- 3 COL
2 2
- 4 COL
11.00
3 3 -
4 BM
11.00
21.5 0
I
J Unbraced
------------------------------------------------
Lengths K Factors Bending Coefs
No Node
Node Lb -in
Lb -out Lc In Out Cm Cb
--------------------(ft)-----(ft
-----(ft)----------------------------------
1 1 -
3
RISA -2D (R) Version 3.03
Job
Page s5z�
Date
WADE RESIDENCE
MOMENT FRAME b
-------------------------------------------------------------
I . J Unbraced Lengths K Factors Bending Coefs
No Node Node Lb -in Lb -out Lc In Out Cm Cb
-------------------- (ft) ----- (ft) ----- (ft) ---=------------------------------
2 2 - 4
3 3 - 4 2.00 2.00 2.00
---------------------------------------------------------
BLC Basic Load Case Load Totals
No. Description Nodal Point Dist.
-----------------------------------------------------------
1 D+L+S 1 1
Nodal Loads, BLC 1: D+L+S y
------------------------------------------------------------
Node
Number Global X Global Y Moment
-------------------- -
--(K) ---------- ------ (K) ----
--- ---------------
3 5.270 0.000 0.000
Member Distributed Loads,BLC 1: D+L+S
Memb I J
Start
End
Start
End
No Node Node
Dir Magnitude
Magnitude
Location
Location
-------------------------(K/ft,F)
-----
(K/ft,F)---------
(ft) ---------
(ft) ----
3 3 - 4
Y -0.226
-0.226
0.000
21.500
Load Combination
------------------------------------'
Self Wt BLC
BLC BLC
BLC BLC
W E
No. Description
Dir Fac Fac
---------------------------------------------------
Fac Fac
Fac Fac
DYNA S. V
1 D+L+S
Y -1 1 1
Dynamic Analysis Data
Number of modes (frequencies) 3
Basic Load Case for masses . None
BLC mass direction of action X only
Acceleration of Gravity 32.20 ft/sec**2
Load Combination is 1 D+L+S
Nodal Displacements
--------------------------------------------------
Node
Global X
Global Y
Rotation
---------------------(in)-----------------(in)----------------(rad)---------
1
0.00000
-0.00000
-0.00000
2
0.00000
-0.00000
-0.00000
3
0.63720
-0.00096
-0.00176
RISA -2D (R) Version 3.03
Job
Page
Date
WADE RESIDENCE
MOMENT FRAME b Q,VL
------------------------
Node Global X
-------------------------
Global Y
-------------------
Rotation
--------------------- (in) -----------------
(in) -----------------
(rad)
---------
4
0.63433
-0.00254
0.00041
Load Combination is
1 D+L+S
Reactions
------------------------------------------------------------=
Node Global X
Global Y
Moment
----------------------(K)------------------(K)---------------(K-ft)---------
1
-2.32306
1.73176
.13.72532
2
-2.94694
4.36016
15.98942
Totals
-5.27000
6.09192
29.71474
Load Combination is
1 D+L+S
Member End Forces
Nodes =________-
I -End
-------------------------------------------
=________-
J -End
No I J Axial
Shear
Moment Axial
Shear
Moment
---------------(K)--------(K)------(K-ft)-------(K)--------(K)------(K-ft)--
1 1- 3 1.73
2.32
13.73 -1.45
-2.32
11.83
2 2- 4 4.36
2.95
15.99 -4.08
-2.95
16.43
3 3- 4 2.95
1.45
-11.83 -2.95
4.08
-16.43
Load Combination is
1 D+L+S
AISC Code Checks
Nodes
----------------------------------------------------
Member Quarter Points
No I J Maximum
0
---------------------------------------------------
1/4 1/2 3/4
L
Shear
1 1- 3 0.7196
0.7196
0.3905 0.0613 0.2918
0.6198
0.0213
2 2- 4 0.8770
0.8568
0.4394 0.0446 0.4608
0.8770
0.0271
3 3- 4 0.1914
0.1422
0.1858 0.1499 0.0347
0.1914
0.0648
K MAP P 8c TA1\i G
STRUCTURAL. ENGINEERS, INC,
�408 SOUTH S:TO.DDARD AVENUE
SAN BERNARDINO, CA. 9:2401.
TELE. (909 889-0115
FAX (909 � 889 -045.5
E-MAIL (KNAPPAE®AOL.COM)
BY:
WAP eE- /D. ExIcQATE:
SHT. . OF
.........
..
.
14.3
X/%'x 3v' x /43= 0334
- 777/ #
144 S4
Cs -3
JT-
-32-147 x s 7a-/-, /4 3 7743 -'4
/3/ 64 fflJ /4A
I
Kr,--J./\P P 8c
STRUCTURAL ENGINEERS, INC,
408 SOUTH STODDARD AVENUE
SAN BERNARDINO, CA. 9:24401
TELE. (909 889-0115.
FAX (9093 889-0455
E-MAIL (KNAPPAE®AOLCOM)
WAP a
8'Y:
DATE:
SHT. 53 OF
-)t7
L-i7�tx/¢3=12,147#
STRUCTURAL ENGINEERS, INC,
40.8 SOUTH H S.TCD:DARD AVENUE
SAN BERNARDINO, CA. 9;44:01
TEL-. (909 889-0115.
_ r FAx (909J 889-0455
. E-MAIL (KNAPPAECAOLCOM)
D v-. 13711
6-147
s �
V = 3jx 4bl,:-,x 3d -,K. 14- = _)fa�
BY:
OAT -E:
SHT. , G
i
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
DESIGN OF EMBEDDED POLE FOOTINGS
Date: 12111103
WADE RESIDENCE
DESIGN DATA
1 —
Allow Passive
300.0 psf
Max Passive
2000.0 psf
Load Duration Factor
1.330
Point Load
1391.0 #
Load Height
11.00 ft
Dist. Load
0.0 plf
Start Height
0.00 ft
End Height
0.00 ft
Pole Type
: Rectangular
Width/Diameter
36.0 in
Surface Restraint
? Restrained
SUMMARY
Moments @ Surface...
1 —
Point Load
15301.0 ft-#
Uniform Load
0.0 ft-#
... Total Moment
15301.0 ft-#
Total Lateral Load
1391.0 #
- NON -RESTRAINED RESULTS
-
Min. Req'd Embedment
A0 +0 +4.36h IA)".5)12
A=2.34P1(S 1 b)
Press @ 113 Embed
Actual
Allowable
— RESTRAINED RESULTS —
Min: Req'd Embedment
(4.25`P"h/S3'b)".5
3.38 ft
Pressure @ Bottom
Actual
1347.6 psf
Allowable
1347.6 psf
Surface Restraint
Force
6679.9 #
Page:.
V4.46 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
I I
I I
I
I I
I I
I I
I
1
KNdf%,PP <S.-- Tl/\"G
STRUCTURAL ENGINEERS, INC.
40.8 SOUTH STODAVENUE
A --ENUE
SAN BERNARDINO,' CA. 9..24G-1
T —LE.
(909 8.89-0.1 15.
FAX (909) 889-045.5
MAIL (KNAPPAECAOLCOM)
-XI
yA
1,Z = 46 yw-
a,4
WA) z=- RE -51,0 sk/c,=.-
Vu/GYq,�" /�� � �k JatSfi �r�"�"oc,.
4-
(-�4 x D/ -=
16 3/� 1�
in ) de
0 x
sl-iT.,U C
STRUCTURAL ENGINEERS, INC.
408 SOUTH STODDARD AVENUE
SAN BERNARDINO, CA. 9.2401
TELE.09? 889-0115
FAX (V0 9 389-0455
E-MAIL (KNAPPAEOAOL.COM)
... . ......
14- Jt 71 Sr = -P-6, 3 M
ti
O 96 �r- 44; pi --r
BY:
DATE:
�'SHTSI?
OF
KIVAP P 8c TA1�1<G'
STRUCTURAL ENGINEERS, INC.
40.8 SOUTH STOD:DARD AVENUE
SAN BERNARDINO, CA. 9:240.1
TELE. (909:) 889-0.115.
FAX (9093 889-0455
E-MAIL (KNAPPAE®AOLCOM)
WAPa
0 Az
K
LISA W 14)( �.- &4
o"
5r=z:>"l MP
'e- /J-�t
41-
-7 318 -P'
8Y:
DATE:
SHT. $2, OF
STRUCTURAL ENGINEERS, INC.
40.8 SOUTH STODDARD AVENUE
SAN BE,RNARDINO, CA. 92401
w TELE. (9.09) 889-01 15
FAX (909) 889-0455
E-MAIL (KNAPPAE®AOL.COM)
7._ CZ._ ., _ 6__,, �...._.....:.....
merle
Pot P7
��-r0 CL = . 41 6
Pd 6/,
14 =t212.3"l
hB-// CL = ;12'- 6" 3
-1�4ve-.)
7?K0 CiPf3-.-o,-G
106 #1
1,1
k/ 14 x a,) c?'M
rix �� Cil ?47-
2
47.2
-3 0,', r4
43,
BY:
DATE:
SHT. 40 OF -
Kr,-JAP P sc
STRUCTURAL ENGINEERS, INC,
tier: 408 SOUTH STODDARD AVENUE
` s.. SAN BERNARDINO, CA. 92401
TELE. (909 889-0115
�., FAX (909) 889-0455
X e.rn
E—MAIL (KNAPPAECAOL.COM)
��:• :may;
�/- 6
F&
�.. .
w
pclfCo 4 a 7i?
(,' 37)
Al= ?f o� Sr —?4,t -oh 3 ( 70,A3)
,F13 13 CL = ar )
= 13, f r AFB -/a, 44��)
H= X3,/7 tic <r-ih3
Z/Sl& V/14x43 -�
775-14 (L- /a L6 "' )
(6/4 -7t-.46 ) ,Y' 2=
:pox
W,4 0� 62s510VWcr
le'J7r`
BY: -
DATE:
SHT. 1 -/OF _
e�fl/s p 40(
7oofK
CaiS �-76
97lrX
STRUCTURAL ENGINEERS, INC.
40.8 SOUTH STODDARD AVENUE
VIA0� e'�F510 1FC(Gr
SAN BERNARDINO, CA. 92401
DATE:
,.r
5. TELE. (9 '889-0115
F FAX j 889`-0455
rSHT. OF
E-MAIL (KNAPPAE.®AOL.COM)
_
L
)Xr'4 = 4/�
`7a77
75B-ib CZ(=
jS�= 3 Zjf��--
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
FB -3
SPAN DATA
0
Center Span =
21.50 ft
Left Cantilever =
0.00 ft
Right Cantilever =
0.00 ft
UNIFORM LOADS
0.00 ft
Center Span #1 =
0.09 klft
CONCENTRATED LOADS
# 1 = 4.000k at 3.50ft
MAXIMUM MOMENT
# 2 = 4.000k at 8.00ft
# 3 = 4.000k at 12.50ft
# 4 = 4.000k at 17.00ft
Moments
0
Max. Span Moment
= 55.71 k -ft
Max. Mom. Location
= 12.47 ft
Min. Span Moment
= 0.00 k -ft
Min. Mom. Location
0.00 ft
Max @ Left Support
= 0.00 k -ft
Max @ Right Support
= 0.00 k -ft
MAXIMUM MOMENT
55.71 k -ft
(inertia
E`.Elastic Modulus
End Fixity
Date: 12101103
MEMBER DATA
3620.000 in4 All distances for load locations refer
29000000 psi to left support. Neg I'-') distances
PinlPin means load is on left cantilever
TRAPEZOIDAL LOADS
— SUMMARY
Shears
APPLIED MOMENTS
Deflections —
Left Support = 9.34 k Max. @ Span = -0.044 in at 10.75 ft
Right Support = 8.60 k . .
Reactions
Left Support = 9.34 k
Right Support 8.60 k
Query Values
Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 9.340 k, Defl. = 0.000 in
0 0 0
0
0 0 0
0
T
1111111111111111111111111111311111111111111111111110 -0911111111111111111111111111 ITFFMM
1 21.50 1
k/ 3 4 k qo
Page: O
V4.4B (c) 1983-95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
.408 SOUTH STODDARD AVE.
,
SAN BERNARDINO, CA 92401 .
TEL: (909) 889-0115
FAX:' (909) 889-0455
t
Date: 12101103 Pa
SINGLE SPAN BEAM ANALYSIS
.,
WADE RESIDENCE
`
FB -4
SPAN DATA
MEMBER DATA
Center Span = . 16.50 ft
(:Inertia =
.485.000, in4 All distances for load locations refer
Left Cantilever = 0.00 ft
E:Elastic Modulus
29000000 psi to left support. Neg ('-') distances
Right Cantilever = 0.00 ft
End Fixity
PinlPin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL LOADS
Center Span #1 = 0.05 klft
Center Span #2 = 0.21 klft
CONCENTRATED LOADS
'APPLIED MOMENTS
H 1 12.200k at 2.50ft
SUMMARY '
Moments
Shears
I Deflections
Max. Span Moment 30.36 k -ft '
Left Support
= 12.46 k Max. @ Span = -0.093 in at 7.49 ft
Max. Mom. Location = 2.51 ft
Right Support
_ 3.96-k
Min. Span Moment 0.00 k -ft
Reactions.
Min. Mom. Location = 0.00 ft,
Left Support
= 12.46 k
Max @ Left Support = 0.00 k -ft
Right Support
= 3.96 k
Max @ Right Support = 0.00 k -ft
Query Values
MAXIMUM MOMENT 30.36 k -ft
Between Supports @ X =
0.00 ft, M = 0.00 k -ft, V = 12.464 k, Defl. = 0.000 in
oNJ_
k/ X���
.16.50
V4.413 (c) 1983.95 ENERCALC
Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
FB -6
SPAN DATA
Center Span =
14.50 ft
Left Cantilever =
0.00 ft
Right Cantilever =
4.00 ft
UNIFORM LOADS
Center Span #1 =
0.23 klft
Right Cant N1
0.04 klft
CONCENTRATED LOADS
# 1 = 5.577k at 2.50ft
# 2 = 6.864k at 6.50ft
# 3 = 6.864k at 10.50ft
# 4 = 6.864k at 18.50ft
Moments
Max. Span Moment
Max. Mom. Location
Min. Span Moment
Min. Mom. Location
Max @ Left Support
Max @ Right Support
MAXIMUM MOMENT
38.10 k -ft
6.51 ft
-27.78 k -ft
14.50 ft
= 0.00 k -ft
-27.78 k -ft
= 38.10 k -ft
(:Inertia
E:Elastic Modulus
End Fixity
Date: 12102103
MEMBER DATA
291.000 in4 All distances for load locations refer
29000000 psi to left support. Neg ('-') distances
Pin/Pin means load is on left cantilever
TRAPEZOIDAL LOADS
- SUMMARY
- Shears
Left Support = 10.05 k
Right Support = 12.59 k
APPLIED MOMENTS
Deflections -
Max. @ Span = -0.144 in at 6.77 ft
Reactions Right Cant = 0.049 in at 18.50 ft
Left Support = 10.05 k
Right Support = 19.62 k
Query Values
Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 10.048 k, Defl. = 0.000 in
At Right Cantilever @ X = 0.00 ft, M = 0.00 k -ft, V = 0.000 k, Defl. = 0.000 in
10
1
lull)
ro m
111111111111111111111 0.23 I I I I 1111H1111111 III I I 111111111111111111111111111110.04 111111
W!¢x3o
1 14.50 1 4.00
M
Page: 0
MAB (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 12102103
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
FB -9
SPAN DATA
SUMMARY
MEMBER DATA
Center Span =
14.50 ft
(:Inertia. = 199.000 in4 All distances for load locations refer
Left Cantilever =
1.00 ft
E:Elastic Modulus = 29000000 psi to left support. Neg ('-') distances
Right Cantilever =
0.00 ft
End Fixity PinlPin means load is on left cantilever
UNIFORM LOADS
6.63 k
TRAPEZOIDAL LOADS
Center Span #1 =
0.02 klft
Left Cant #1 =
0.02 klft
Left Support =
CONCENTRATED LOADS
APPLIED MOMENTS
# 1 = 4.160k at -1.00ft
Right Support =
6.63 k
# 2 = 1.870k at 2.50ft
= 0.00 k -ft
# 3 = 4.160k at 3.50ft
Query Values
# 4 = 4.160k at 7.50ft
= 29.31 k -ft
Between Supports @ X =
# 5 = 4.160k at 11.50ft
-4.17 k -ft, V = 8.005 k, Defl. = 0.000 in
At Left Cantilever @ X =
0:00 ft, M =
0.00 k -ft, V = 0.000 k, Defl. = 0.000 in
Moments
Max. Span Moment
Max. Mom. Location
Min. Span Moment
.Min. Mom. Location
Max @ Left Support
Max @ Right Support
MAXIMUM MOMENT
II.ao1 14.0 1
Page: 61.
V4.413 (c) 1983.95 ENERCALC , Knapp Architectural Engineers, Inc, Kw06OI567
SUMMARY
Shears
Deflections -
- 29.31 k -ft
Left Support =
8.00 k
Max. @ Span = -0.183 in at 7.28 f1
- 7.50 ft
Right Support =
6.63 k
Left Cant = 0.038 in at -1.00 ft
_ -4.17 k -ft
Reactions
= 0.00 ft
Left Support =
12.18 k
_ -4.17 k -ft
Right Support =
6.63 k
= 0.00 k -ft
Query Values
= 29.31 k -ft
Between Supports @ X =
0.00 It, M =
-4.17 k -ft, V = 8.005 k, Defl. = 0.000 in
At Left Cantilever @ X =
0:00 ft, M =
0.00 k -ft, V = 0.000 k, Defl. = 0.000 in
II.ao1 14.0 1
Page: 61.
V4.413 (c) 1983.95 ENERCALC , Knapp Architectural Engineers, Inc, Kw06OI567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
FB -10
SPAN DATA
Center Span =
24.50 ft
Left Cantilever =
0.00 ft
Right Cantilever =
0.00 ft
UNIFORM LOADS
0.00 ft
Center Span #1
0.05 kift
CONCENTRATED LOADS
# 1 = 5.340k at 3.50ft
MAXIMUM MOMENT
#2 = 5.340k at 7.50ft
N
# 3 = 5.340k at 11.50ft
N
# 4 = 5.340k at 15.50ft
T
# 5 = 5.340k at 19.50ft
# 6 = 16.630k at 10.O0ft
# 7 = 5.598k at 21.50ft
Moments
Max. Span Moment
= 202.31 k -ft
Max. Mom. Location
= 10.00 ft
Min. Span Moment
= 0.00 k -ft
Min. Mom. Location
0.00 ft
Max @ Left Support
= 0.00 k -ft
Max @ Right Support
= 0.00 k -ft
MAXIMUM MOMENT
202.31 k -ft
LInertia
E:Elastic Modulus
End Fixity
Date: 12102103
MEMBER DATA
= 723.000 in4 All distances for load locations refer
29000000 psi to left support. Neg ('-') distances
PinlPin means load is on left cantilever
TRAPEZOIDAL LOADS
- SUMMARY
Shears
Left Support 25.28 k
Right Support = 24.82 k
Reactions
APPLIED MOMENTS
Deflections -
Max. @ Span = -0.968 in at 12.00 ft
Left Support 25.28 k
Right Support 24.82 k
Query Values
Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 25.283 k, Defl. = 0.000 in
111111111111111111111111 1111111111 Ilo-0411 1111111111 11111111H I 11111111111111111111111111
1 24.50
Page: 4j,
V4.46 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
r ro
ro
ro
In
N
Ill Ill
N
In
N
N
T
111111111111111111111111 1111111111 Ilo-0411 1111111111 11111111H I 11111111111111111111111111
1 24.50
Page: 4j,
V4.46 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
,408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455 .
SINGLE SPAN BEAM ANALYSIS
Date: 12102103 Page:
WADE RESIDENCE -,FB -1 1
'
SPAN DATA MEMBER DATA
Center Span = 24.50 ft (:Inertia = 485.000 in4 All distances for load locations refer
Left Cantilever, 0.00 ft E:Elastic Modulus = 29000000 psi to left support. Neg'('-') distances
Right Cantilever = 0.00 ft End Fixity PinlPin means load is on left cantilever
UNIFORM LOADS TRAPEZOIDAL LOADS
Center Span N1 = 0.05 klft
Center Span H2 = 0.41 klft
CONCENTRATED LOADS. APPLIED MOMENTS
N 1 = 26.560k at '5.50ft
a 2 = 7.360k at 10.00ft
SUMMARY
Moments Shears Deflections
Max. Span Moment = 163.44 k -ft Left Support = 30.54 k, Max. @ Span = -1.163 in at 11.27 ft.
Max. Mom. Location = 8,72 ft Right Support = 14.55 k
Min. Span Moment = 0.00 k -ft Reactions
Min. Mom. Location = 0.00 ft Left Support = 30.54 k
Max @ Left Support = 0.00 k -ft Right Support = 14.55 k
Max @ Right Support = 0.00 k -ft Query Values
MAXIMUM MOMENT = 163.44 k -ft Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 30.539 k, Defl. = 0.000,in
p
N D
,il m
N
r4
0.45
V4.413 (c) 1983-95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC
408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
FB -12
SPAN DATA
Center Span =
24.50 ft
Left Cantilever =
0.00 ft
Right Cantilever =
0.00 ft
UNIFORM LOADS
= 0.00 ft
Center Span #1 =
0.05 klft
Center Span #2 =
0.91 klft
CONCENTRATED LOADS
# 1 = 14.259k at 21.50ft
Moments
Max. Span Moment
= 95.01 k -ft
Max. Mom. Location
14.06 ft
Min. Span Moment
= 0.00 k -ft
Min. Mom. Location
= 0.00 ft
Max @ Left Support
= 0.00 k -ft
Max @ Right Support
0.00 k -ft
MAXIMUM MOMENT
= 95.01 k -ft
0.96
Date: 12102103
MEMBER DATA
I:Inertia = 485.000 in4 All distances for load locations refer
E:Elastic Modulus 29000000 psi to left support. Neg ('-') distances
End Fixity Pin/Pin means load is on left cantilever
TRAPEZOIDAL LOADS
APPLIED MOMENTS
SUMMARY -
Shears Deflections —
Left Support = 13.51 k Max. @ Span = -0.748 in at 12.69 ft
Right Support 24.27 k
Reactions
Left Support = 13.51 k
Right Support 24.27 k
Query Values
Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 13.506 k, Defl. = 0.000 in
N
N
d
1 24.50 f
W/ /4 x 49
Page: 47
V4.413 (c) 1983.95 ENERCALC Knapp Architectural Engineers, Inc, Kw0601567
KNAPP & TANG STRUCTURAL ENGINEERS INC'
• 408 SOUTH STODDARD AVE.
SAN BERNARDINO, CA 92401
TEL: (909) 889-0115
FAX: (909) 889-0455
Date: 12102103
SINGLE SPAN BEAM ANALYSIS
WADE RESIDENCE
FB -13
SPAN DATA
MEMBER DATA
Center Span =
14.00 ft
Hnertia
= 485.000 in4 All distances for load locations refer
Left Cantilever =
0.00 ft .
E:Elastic Modulus
= 29000000 psi to left support. Neg (Y) distances
Right Cantilever =
0.00 ft
End Fixity
Pinipin means load is on left cantilever
UNIFORM LOADS
TRAPEZOIDAL LOADS
Center Span #1 =
0.05 klft
Center Span #2 =
0.24 klft
CONCENTRATED LOADS
APPLIED MOMENTS
# 1 = 13.510k at 8.00ft
SUMMARY
Moments
Shears Deflections
Max. Span Moment =
53.17 k -ft
Left Support
= 7.81 k Max. @ Span = -0.110 in at 7.25 ft
Max. Mom. Location
8.01 ft
Right Support
= 9.74 k
Min. Span Moment =
0.00 k -ft
-
Reactions
Min. Mom. Location =
14.00 ft
Left Support
= 7.81 k e
Max @ Left Support =
0.00 k -ft
Right Support
= 9.74 k
Max @ Right Support =
0.00 k -ft
Query Values
MAXIMUM MOMENT =
. 53.17 k -ft
Between Supports @ X = 0.00 ft, M = 0.00 k -ft, V = 7.806 k, Defl. = 0.000 in
0.2U
V4.413 (c) 1983.95 ENERCALC
1/4X49
a
Page:
Knapp Architectural Engineers, Inc, Kw0601567
.--
5ofid Grout,
all ho=rei"
|
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
Title : WADE RESIDENCE
Page: 7.�
,., 409 SOUTH STODDARD AVENUE
Allowable
Job
Dsgnr: HW
Date: NOV 18,2003
SAN BERNARDINO, CA 92401
ACI Factored @ Heel
Description....
Footing Shear @ To
= 7.7 psi OK
PHONE: 909-889-0115
= 1.7 psi OK
T-9" WALL
= 76.0 psi
Wall Stability Ratios
FAX: 909-889-0455
Overturning
= 1.64 OK
Sliding
= 2.41 OK
Sliding Calcs (Vertical
Component NOT Used)
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0
Cantilevered Retaining Wall Design
- 0.0 lbs
less 100% Friction Force= - 329.7 lbs
Build Date : 10 -SEP -2001, (c) 1989-2001
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK
Footing Design Results , I
_Criteria s
LSoii Data
j
1,912 0 psf
Footing Dimensions & Strengths
Retained Height = 0.50 ft
Allow Soil Bearing
1,800:0 psf
Toe Width
= 0.67 ft -- -
Wall height above soil = 5.75 ft
Equivalent Fluid Pressure
Method
Heel Width
= 1.33
Slope Behind Wal = 0.00: 1
Heel Active Pressure
= 35.0 psf/ft
Total Footing Widt
= ------- ._.._2 -00 -
Height of Soil over To = 0.00 in
Toe Active Pressure
Passive Pressure
= 35.0 psf/ft
= 300.0 psf/ft
Footing Thickness
= 12.00 in
Soil Density 110.00 pcf
Water height over heel
= _ 0.0 ft
Key Width
= 0.00 in
Wind on Stem = 20.0 psf
i Design Summary
Total Bearing Loa = 824 lbs
...resultant ecc. = 7.17 in
Soil Pressure @ To
= 1,365 psf OK
Soil Pressure @ Hee
= 0 psf OK
Allowable
= 1,800 psf
Soil Pressure Less Than Allowable
ACI Factored @ Toe
= 1,912 psf
ACI Factored @ Heel
= 0 psf
Footing Shear @ To
= 7.7 psi OK
Footing Shear @ Hee
= 1.7 psi OK
Allowable
= 76.0 psi
Wall Stability Ratios
Design Data
Overturning
= 1.64 OK
Sliding
= 2.41 OK
Sliding Calcs (Vertical
Component NOT Used)
Lateral Sliding Forc
= 136.9 lbs
less 100% Passive Force=
- 0.0 lbs
less 100% Friction Force= - 329.7 lbs
Added Force Req'd
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK
Footing Design Results , I
3.0
Toe Heel
Factored Pressure =
1,912 0 psf
Mu' : Upward =
511 0 ft-#
Mu': Downward _
73 100 ft-#
Mu: Design =
438 100 ft-#
Actual 1 -Way Shear =
7.67 1.68 psi
Allow 1 -Way Shear =
76.03 76.03 psi
Toe Reinforcing =
# 7 @ 31.75 in
Heel Reinforcing =
# 6 @ 18.00 in
Key Reinforcing =
None Spec'd
FootingIlSoil Frictio = 0.400 Key Depth = 0.00 in
Soil height to ignore Key Distance from Toe = 0.00 ft
for passive pressure = 12.00 in fc = 2,000 psi Fy = 60,000 psi
Footing Concrete Densit = 150.00 pcf
Min. As % = 0.0018
Cover @ Top = 2.00 in @ Btm.= 3.00 in
( Stem Construction ■ Top Stem
Design height
ft=
Bar Lap/Emb
0.00
Wall Material Above "Ht"
=
Masonry
Thickness
=
8.00
Rebar Size
=
# 5
Rebar Spacing
=
24.00
Rebar Placed at
=
Center
Design Data
fb/FB + fa/Fa
=
0.738
Total Force @ Section
lbs =
119.4
Moment.... Actual
ft-#=
388.9
Moment..... Allowable
=
527.1
Shear..... Actual
psi =
3.0
Shear..... Allowable
psi =
19.4
Lap Splice if Above
in=
30.00
Lap Splice if Below
in=
11.74
Wall Weight
=
78.0
Rebar Depth 'd'
in =
3.75
Masonry Data
fm
psi=
1,500
Fs
psi =
24,000
Solid Grouting
=
Yes
Special Inspection
=
No
Modular Ratio 'n'
=
25.78
Short Term Factor
=
1.000
Equiv. Solid Thick.
in=
7.60
Masonry Block Type = Medium
Weight
Concrete Data
fc
Psi=
- - ----
Fy
psi =
Other Acceptable Sizes & Spacings
Toe: Not req'd, Mu < S * Fr
Heel: Not req'd, Mu < S " Fr
Key: No key defined
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
Title ; WADE RESIDENCE Page: 77.
408 SOUTH STODDARD AVENUE
Job
Dsgnr: HW Date: NOV 18,2003
SAN BERNARDINO, CA 92401
Description....
PHONE: 909-889-0115
5'-9" WALL
FAX: 909-889-0455
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0 Cantilevered Retaining Wall Design
Build Date: 10 -SEP -2001, (c) 1989-2001
Summary of Overturning & Resisting Forces & Moments
.....OVERTURNING.....
.....RESISTING.....
Force Distance Moment
Force Distance Moment
Item lbs ft ft-#
lbs ft ft-#
Heel Active Pressure = 39.4 0.50 19.7
Soil Over Hee =
36.7 1.67 61.1
Toe Active Pressure = -17.5 0.33 -5.8
Sloped Soil Over Hee =
Surcharge Over Toe =
Surcharge Over Heel =
Adjacent Footing Load =
Adjacent Footing Load =
Added Lateral Load =
Axial Dead Load on Ste =
0.00
Load @ Stem Above Soi = 115.0 4.38 503.1
Soil Over To _
Surcharge Over Toe
Total = 136.9 O.T.M. = 517.0
Stem Weight(s) -
Earth @ Stem Transition _
487.5 1.00 487.5
Resisting/Overturning Ratio 1.64
Footing Weigh
Vertical Loads used for Soil Pressure = 824.2 lbs
=
Key Weight =
300.0 1.00 300.0
Vert. Component
Vertical component of active pressure NOT used for soil pressure
Total =
824.2 lbs R.M. 848.6
�2e�'ere�ce Al
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
408 SOUTH STODDARD AVENUE
SAN BERNARDINO, CA 92401 I �+
PHONE: 909-889-0115 1
FAX: 909-889-0455
fV�.gl V
RetainPro Version 6.0
Build Date: 10 -SEP -2001, (c) 19E
rl
Retained Height
Wall height above soil
Slope Behind Wal
Height of Soil over To
Soil Density
p+Title WADE RESIDENCE
apits Job Dsgnr: HW
Description....
RETAINING WALL
Page: j.. .
Date: NOV 20,2003
This Wall in File: CARETAIN PRO-61EXAMPLES.RP5
Cantilevered Retaining Wall Design
;Soil Data
= 813 psf OK
A low Soil bearing
=U17
= 1,800.0 psf
= Equivalent Fluid Pressure Method
Heel Active Pressure
= 35.0 psf/ft
Toe Active Pressure
= 35.0 psf/ft
= 0.00 in Passive Pressure
= 300.0 psf/ft
= 110.00 pcf Water height over heel
= 0.0 ft
Wind on Stem = 20.0 psf
_Design Summary II
Total Bearing Loa = 1,617 lbs
...resultant ecc. = 4.12 in
Soil Pressure @ To
= 813 psf OK
Soil Pressure @ Hee
= 182 psf OK
Allowable
= 1,800 psf
Soil Pressure Less
Than Allowable
ACI Factored @ Toe
= 1,138 psf
ACI Factored @ Heel
= 255 psf
Footing Shear @ To
= 7.8 psi OK
Footing Shear @ Hee
= 3.9 psi OK
Allowable
= 76.0 psi
Wall Stability Ratios
Min. As % =
Overturning
= 3.27 OK
Sliding
= 1.62 OK
Sliding Calcs (Vertical
Component NOT Used)
Lateral Sliding Forc
400.3 lbs
less 100% Passive Force=
- 0.0 lbs
less 100% Friction Force= - 646.9 lbs
Added Force Req'd
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK
j Footing Design Results
Shear..... Actual
Toe eel
Factored Pressure =
1,138 255 psf
Mu': Upward =
703 633 ft-#
Mu': Downward =
143 1,147 ft-#
Mu: Design =
560 514 ft-#
Actual 1 -Way Shear =
7.77 3.87'psi
Allow 1 -Way Shear =
76.03 76:03 psi
Toe Reinforcing =
# 7 @ 31.75 in
Heel Reinforcing =
# 6 @ 18.00 in
Key Reinforcing =
None Spec'd
Footing11Soil Frictio
Soil height to ignore
for passive pressure
= 0.400
= 12.00 in
Footing Dimensions 8� Strengths
Toe Width =
1.00 ft
Heel Width =
2.25
Total Footing Widt =
sm-
Footing Thickness =
12.00 in
Key Width =
0.00 in
Key Depth =
0.00 in
Key Distance from Toe =
0.00 ft
Pc = 2,000 psi Fy =
60,000 psi
Footing Concrete Densit =
150.00 pcf
Min. As % =
0.0018
Cover @ Top = 2.00 in @ Btm.= 3.00 in
1 Stem Construction;
Top Stem
Design height
ft=
Bar Lap/Emb - - ----
0.00
Wall Material Above "Ht"
=
Masonry
Thickness
=
8.00
Rebar Size
=
f# 5 e
Rebar Spacing
=
16.00
Rebar Placed at
=
Center
Design Data
fb/FB + fa/Fa
=
0.475
Total Force @ Section
lbs =
277.8
Moment.... Actual
ft-#=
572.5
Moment..... Allowable
=
1,206.1
Shear..... Actual
psi =
7.1
Shear..... Allowable
psi =
38.7'
Lap Splice if Above
in =
30.00
Lap Splice if Below
in =
11,74
Wall Weight
=
78.0
Rebar Depth 'd'
in =
3.75
Masonry Data
Pm
psi=
1,500 - -
Fs
psi =
24,000
Solid Grouting
=
Yes
Special Inspection
=
Yes
Modular Ratio 'n'
=
25.78
Short Term Factor
=
1.000
Equiv. Solid Thick.
in =
7.60
Masonry Block Type = Medium Weight
Concrete Data
fc
psi =
--- -
Fy
psi =
Other Acceptable Sizes & Spacings
Toe: Not req'd, Mu < S ' Fr
Heel: Not req'd, Mu < S " Fr
Key: No key defined
KNAPP 8i TANG STRUCTURAL ENGINEERS, INC.
Title WADE RESIDENCE
Page:
„ 4Q3 SOUTH STODDARD AVENUE
SAN
Job Osgnr: HW
Date: NOV 20,2003
BERNARDINO, CA 92401
Description....
PHONE: 909-889-0115
� RETAINING WALL
FAX: 909-889-0455
This Wall in File: CARETAIN PRO-61EXAMPLES.RP5
RetaBuild
Version 6.0 Cantilevered Retaining Wall Design
Build g
at
Date : 10 -SEP 2001, (c) 1989-2001
9
Summary of Overturning & Resisting Forces & Moments
- -- :::..CVERTURNING:..:.
Force Distance Moment
•-••• RESISTING .....
Force Distance
Moment
Item lbs ft ftp
lbs
ft
ft-#
Heel Active Pressure = 354.4 1.50 531.6
Soil Over Hee = 609.6
2.46
- 1,498.6
Toe Active Pressure = -17.5 0.33 ' -5.8
Sloped Soil Over Hee –
Surcharge Over Toe =
'Surcharae Over Heel =
Adjacent Footing Load =
Adjacent Footing Load.Added
Lateral Load =
Axial Dead Load on Ste =
0.00
Load @Stem Above Soi = -63.4- 6.09 385.8
Soil Over To _
Surcharge Over Toe _
Total = 400.3 O.T.M. = 911.5
Stem Weight(s) 520.3
Earth @ Stem Transition _
1.33
693.7
Resisting/Overturning Ratio 3.27
Footing Weigh =
Vertical Loads used for Soil Pressure- 1,617.3 lbs
487.5
Key Weight =
1.63 •
792.2
Vert. Component
Vertical component of active pressure NOT used for soil pressure
Total = 1,617.3 lbs
R.M. b
— 2,984.4
77
8 -in Mas w/ #G @ I G.in o/c
5olid Grout, 5pc In5p
#7@3 1.751n
@Toe
Designer =elect
#G@ 18.in all honz. reinf.
@ Heel 5ee Appendix A
7,-0
5'-G"
�Jefence 5 r x- 1,2
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
Title WADE RESIDENCE
Page: T05
4G6 SOUTH STODDARD AVENUE
Allowable =
Job
Dsgnr: HW
Date: NOV 24,2003
SAN BERNARDINO, CA 92401
1,576 psf
Description....
362 psf
Footing Shear @ To =
PHONE: 909-889-0115
Footing Shear @ Hee =
RETAINING
WALL
76.0 psi,
FAX: 909-889-0455
7.03 psi
Overturning =
3.63 OK
Sliding =
1.54 OK
Sliding Calcs (Vertical Component
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0
Build
Cantilevered Retaining Wall Design
less 100% Passive Force= -
0.0 lbs
Date : 10 -SEP -2001, (c) 1989-2001
1,155.3 lbs
- Bar
ft=
Lap/Emb
0.00
_Criteria
' Soil Data
Masonry
i Footing Dimensions & Strengths
`i
Retained Height = 5.50 ft
Allow Soil Bearing
= 1,800.0 psf
oe Width
= 0.67 ft -
Wall height above soil = 1.50 ft
Equivalent Fluid Pressure
Method
Heel Width
= 3.50
Slope Behind Wal = 0.00:1
Heel Active Pressure
= 35.0 psf/ft
Total Footing Widt
= 4.1'7-
Height of Soil over To = 0.00 in
Toe Active Pressure
Passive Pressure
= 35.0 psf/ft
= 300.0 psf/ft
Footing Thickness
= 12.00 in
Soil Density = 110.00 pcf
Water height over heel
= 0.0 ft
Key Width
= 0.00 in
Wind on Stem = 20.0 psf
I Design Summary iii
Total Bearing Loa = 2,888 lbs
...resultant ecc. = 5.23 in
Soil Pressure @ To =
1,125 psf OK
Soil Pressure @ Hee =
259 psf OK
Allowable =
1,800 psf
Soil Pressure Less Than
Allowable
ACI Factored @ Toe =
1,576 psf
ACI Factored @ Heel =
362 psf
Footing Shear @ To =
8.3 psi OK
Footing Shear @ Hee =
7.0 psi OK
Allowable =
76.0 psi,
Wall Stability Ratios
7.03 psi
Overturning =
3.63 OK
Sliding =
1.54 OK
Sliding Calcs (Vertical Component
NOT Used)
Lateral Sliding Forc
751.9 lbs
less 100% Passive Force= -
0.0 lbs
less 100% Friction Force= -
1,155.3 lbs
Added Force Req'd = 0.0 lbs OK
....for 1.5 : 1 Stability = 0.0 lbs OK
1 Footing Design Results
0.400
Toe
Heel.
Factored Pressure
= 1,576
362 psf
Mu' : Upward
= 523
2,946 ft-#
Mu': Downward
= 74
4,767 ft-#
Mu: Design
= 450
1,821 ft-#
Actual 1 -Way Shear
= 8.33
7.03 psi
Allow 1 -Way Shear
= 76.03
76.03 psi
Toe Reinforcing
= # 7 @ 31.75 in
Heel Reinforcing
= # 6 @ 18.00 in
Stem Construction■y
Key Reinforcing
= None Spec'd
-
Design height
FootingIlSoil Frictio =
0.400
Key Depth = 0.00 in
Key Distance from Toe = 0.00 ft
Soil height to ignore
for passive pressure =
12.00 in
fc = 2,000 psi Fy = 60,000 psi
Footing Concrete Densit = 150.00 pcf
Min. As % = 0.0018
Cover @ Top = 2.00 in @ Btm.= 3.00 in
Stem Construction■y
Top Stem
-
Design height
- Bar
ft=
Lap/Emb
0.00
Wall Material Above "Ht"
=
Masonry
Thickness
=
8.00
Rebar Size
=
# 6
Rebar Spacing
=
16.00
i
Rebar Placed at
=
Center
Design Data
fb/FB + fa/Fa
=
0.863
Total Force @ Section
lbs =
559.4
Moment.... Actual
ft-#=
1,158.0
Moment..... Allowable
=
1,341.6
Shear..... Actual
psi =
14.5
Shear..... Allowable
psi =
38.7
Lap Splice if Above
in=
36.00
Lap Splice if Below
in=
14.09
Wall Weight
=
78.0
Rebar Depth 'd'
in=
3.75
Masonry Data
fm
psi=
1,500
Fs
psi=
24,000
Solid Grouting
=
Yes
Special Inspection
=
Yes
Modular Ratio 'n'
=
25.78
Short Term Factor
=
1.000
Equiv. Solid Thick.
in =
7.60
Masonry Block Type = Medium Weight
Concrete Data
fc
psi =
---
Fy
psi =
Other Acceptable Sizes & Spacings
Toe: Not req'd, Mu < S " Fr
Heel: Not req'd, Mu < S " Fr
Key: No key,defined
KNAPP'& TANG STRUCTURAL ENGINEERS, INC. Title WADE RESIDENCE Page:%�
408 SOUTH STODDARD AVENUE Job Dsgnr: HW Date: NOV 24,2003
SAN BERNARDINO, CA 92401 Description....
PHONE: 909-889-0115 RETAINING WALL
FAX: 909-889-0455
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0 Cantilevered Retaining Wall Design
Build Date : 10 -SEP -2001, (c) 1989-2001
j Summary of Overturning & Resisting Forces & Moments
Total = 751.9 O.T.M. = 1,813.6
Resisting/Overturning Ratio 3.63
Vertical Loads used for Soil Pressure = 2,888.2 lbs
Vertical component of active pressure NOT used for soil pressure
Force
Distance
Moment
Item
lbs
ft
ft-#
Heel Active Pressure =
739.4
2.17
1,602.0
Toe Active Pressure =
-17.5
0.33
-5.8
Surcharge Over Toe =
Adjacent Footing Load =
Added Lateral Load =
Load @ Stem Above Soi =
30.0
7.25
217.5
Total = 751.9 O.T.M. = 1,813.6
Resisting/Overturning Ratio 3.63
Vertical Loads used for Soil Pressure = 2,888.2 lbs
Vertical component of active pressure NOT used for soil pressure
.....RESISTING.....
Force
Distance
Moment
lbs
ft
ft-#
Soil Over Hee =
1,716.2
2.76
4,728.1
Sloped Soil Over Hee =
Surcharge Over Heel =
Adjacent Footing Load =
Axial Dead Load on Ste =
0.00
Soil Over To _
Surcharge Over Toe
Stem Weight(s) =
546.0
1.00
547.8
Earth @ Stem Transition _
Footing Weigh
=
Key Weight _
626.0
2.09
1,306.3
Vert. Component
Total =
2,888.2
lbs R.M.
s
6,582.2
P ; �6
5.in Mas w/ #G @ I G.in o/cix
_
• solid Grout, 5pc In5p
r
`�—
IN
'j s
a .ri �k'z •�"L�; xeN x\�y� �- a t. --„"rxxT ,x`K. } .., 5 � �'. ��
mal
�7ssf�S?,•w".”,c?,.;`ac;"'szifr�rr.,''>`.:s?i"� .,,n. 3�� ..
"7@31 .75in
@Toe
� Designer select i ,••. • —�•�� 1 �' F• j
,
#G@ 18:in all honz. reinf.
i
@ Heel See Appendix A I x+
P-4"
j —®
2 _g� 2.0"
KNAPP & TANG STRUCTURAL ENGINEERS, INC. Title "' Page: 00-/
408 SOJTH STODDARD AVENUE Job Dsgnr: HW Date: JUN 30,2393
SAN OERNARDINO, CA 92401 Description....
PHONE: 909-889-0115 11' RETAINING WALL
FAX: 909-889-0455
Wind on Stem = 20.0 psf
Design Summary I
Total Bearing Loa = 2,705 lbs
...resultant ecc. = 4.68 in
Soil Pressure @ To
= 850 psf OK
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0
Build Date
Allowable
Cantilevered Retaining Wall Design
Soil Pressure Less Than Allowable
: 10 -SEP -2001, (c) 1989-2001
= 1,190 psf
ACI Factored @ Heel
_Criteria
Footing Shear @ To
oil Data
Footing Dimensions & Strengths
Retained Height
= 7.00 ft
AlJow Soil Bearing = 1,800.0 psi
Toe WT = 2.7 5 rt
Wall height above soil
= 0.00 ft
Equivalent Fluid Pressure Method
Heel Width = 2.00
Slope Behind Wal
= 0.00:1
Heel Active Pressure = 35.0 psf/ft
Total Footing Widt
Height of Soil over To
= 6.00 in
Toe Active Pressure = 35.0sf/ft
P
Passive Pressure = 300.0 psf/ft
Footing Thickness = 14.00 in
Soil Density
= 110.00 pcf
Water height over heel = 0.0 ft
Key Width = 8.00 in
Wind on Stem = 20.0 psf
Design Summary I
Total Bearing Loa = 2,705 lbs
...resultant ecc. = 4.68 in
Soil Pressure @ To
= 850 psf OK
Soil Pressure @ Hee
= 289 psf OK
Allowable
= 1,800 psf
Soil Pressure Less Than Allowable
ACI Factored @ Toe
= 1,190 psf
ACI Factored @ Heel
= 405 psf
Footing Shear @ To
= 14.0 psi OK
Footing Shear @ Hee
= 7.8 psi OK
Allowable
= 76.0 psi
Wall Stability Ratios
fc = 2,000 psi
Overturning
= 2.70 OK
Sliding
= 2.18 OK
Sliding Calcs (Vertical
Component NOT Used)
Lateral Sliding Forc
= 1,118.5 lbs
less 100% Passive Force=
- 1,354.2 lbs
less 100% Friction Force= - 1,082.1 lbs
Added Force Req'd
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK
Footing Design Results
Stem Construction
Toe eel
Factored Pressure =
1,190 405 psf
Mu' : Upward =
4,378 548 ft-#
Mu': Downward =
1,370 1,488 ft-#
Mu: Design =
3,008 940 ft-#
Actual 1 -Way Shear =
13.98 7.81 psi
Allow 1 -Way Shear =
76.03 76.03 psi
Toe Reinforcing =
# 7 @ 31.75 in
Heel Reinforcing =
# 6 @ 18.00 in
Key Reinforcing =
None Spec'd
FootingiiSoil Frictio =
0.400
Key Depth
= 18.00 in
Key Distance from Toe
= 2.75 ft
Soil height to ignore
for passive pressure =
12.00 in
fc = 2,000 psi
Fy = 60,000 psi
Footing Concrete Densit
= 150.00 pcf
Min. As %
= 0.0018
Cover @ Top = 2.00 in
@ Btm.= 3.00 in
Stem Construction
Top Stem
2nd
Design height
ft=
Stem OK Bar Lap/Emb
3.34 0.00
Wall Material Above "Ht" =
Masonry
Masonry
Thickness
=
8.00
8.00
Rebar Size
=
# 6
# 6
Rebar Spacing
=
16.00
16.00
Rebar Placed at
=
Edge
Edge
Design Data
fb/FB + fa/Fa
=
0.120
0.842
Total Force @ Section
Itis =
234.4
853.1
Moment.... Actual
ft-#=
286.0
2,000.1
Moment..... Allowable
ft-#=
2,374.3
2,374.3
Shear..... Actual
psi =
4.3
15.5
Shear..... Allowable
psi =
38.7
38.7
Lap Splice if Above
in=
36.00
36.00
Lap Splice if Below
in =
36.00
14.09
Wall Weight
psf=
78.0
78.0
Rebar Depth 'd'
in =
5.25
5.25
Masonry Data
fm
psi=
1,500
1,500
_
Fs
psi =
24,000
24,000
Solid Grouting
=
Yes
Yes
Special Inspection
=
Yes
Yes
Modular Ratio 'n'
=
25.78
25.78
Short Term Factor
=
1.000
1.000
Equiv. Solid Thick.
in =
7.60
7.60
Masonry Block Type = Medium Weight
Concrete Data
_
fc
psi =
--
Fy
psi =
Other Acce table Sizes & Spacings
Toe: #43 10.75 in, #5@ 16.50 n, #6@ 23.50 in, #7@ 31.75 in, #8@ 42.00 in, #9@ 4
Heel: Not req'd, Mu < S ' Fr
Key: #4@ 22.25 in, #5@ 34.50 in, #6@ 48.25 in, #7@ 48.25 in,
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
TitlePage:
414.
,• 404 SOUTH STODDARD AVENUE
Job
Dsgnr: HW
Date:
JUN 30,2003
SAN'F3ERNARDINO, CA 92401
Description....
PHONE: 909-889-0115
1T RETAINING WALL
FAX: 909-889-0455
This Wall in File:
C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0 , Cantilevered Retaining Wall Design
Build Date : 10-SEP-2001, (c) 1989-2001
Summary of'Overturning & Resisting Forces &. Moments
...OVERTURNING
.....RESISTING.....
Force Distance Moment
Force
Distance
Moment
Item lbs ft ft-#
lbs
ft
ft
Heel Active Pressure = 1,167.2 2.72 3,177.2
Soil Over Hee =
1,026.7
4.08
4,192.2
Toe Active Pressure = -48.6 0.56 -27.0
Sloped Soil Over Hee =
Surcharge Over Toe =
Surcharge Over Heel =
Adjacent Footing Load =
Adjacent Footing Load =
Added Lateral Load =
Axial Dead Load on Ste =
0.00
Load @ Stem Above Soi = 8.17
Soil Over To
=
Surcharge Over Toe
151.3
1.38
208.0
Total = 1,118.5 O.T.M. = 3,150.2
Stem Weight(s) -
Earth @ Stem Transition
546.0
3.08
1,683.5
Resisting/Overturning Ratio 2.70
Footing Weigh
Vertical Loads used for Soil Pressure = 2,705.2 lbs
=
Key Weight =
831.3
150.0
2.38
3.08
1,974.2
462.5
Vert. Component
Vertical component of active pressure NOT used for soil pressure
Total =
2,705.2 lbs
•
R.M.
b
8,520.4
8 -In Mas W/ #G CCD I G.Iri OIC
5olid Grout,
I 2.in Mas wl #G (
5olid Grout, 5
I G.in Mas w/ #G ((
5olid Grout, 5
k7@31 .751n
@Toe
L)C51cjner 5electl
4r-@ 1,5.,n all honz. reini.
@ Heel 5ee Appendix Al
7-3--
je s(ei\ cc �
3'-4"
13'-4-
10.-0.'
2'-4"
2'-4"
KNAPP & TANG STRUCTURAL ENGINEERS, INC. Title WADE RESIDENCE Page:
40.3 SOUTH STODDARD AVENUE Job Dsgnr: HW Date: NOV 20,2003
SAN BERNARDINO, CA 92401 Description....
PHONE: 909-889-0115 RETAINING WALL
FAX: 909-889-0455
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0 Cantilevered Retaining Wall Design
Build Date : 10 -SEP -2001, (c) 1989-2001
Crlterta
Soil Data �. ! Footing Dimensions & Strengths
Retained Height _` 10 -60 -ftp) -'Allow
Soil Bearing = 1,800.0 psf
Toe Width
Wall height above soil =34 h
Equivalent Fluid Pressure Method
Heel Width =
8.25
Slope Behind Wal = 0.00:1
Heel Active Pressure = 35.0 psf/ft
Total Footing Widt =
9.2,
Height of Soil over To = 6.00 in
Toe Active Pressure = 35.0 psf/ft
Passive Pressure = 300.0 psf/ft
Footing Thickness =
18.00 in
Soil Density = 110.00 pcf
Water height over heel = 0.0 ft
Key Width =
12.00 in
FootingIlSoil Frictio = 0.400
Key Depth =
18.00 in
Wind on Stem = 20.0 psf .Soil
height to ignore
Key Distance from Toe =
1.00 ft
for passive pressure = 12.00 in
fc = 2,000 psi Fy =
60,000 psi
Footing Concrete Densit =
150.00 pcf
Min. As % =
0.0018
Cover @ Top = 2.00 in @
Btm.= 3.00 in
Design Summary
+ Stem ConstructionTop Stem
2nd 3rd
Total Bearing Loa = 11,795 lbs
Desi n hei ht Stem OK
9 9 ft = 4.67
Stem OK
2.33 0.00
--
...resultant ecc. = 7.38 in
Wall Material Above "Ht" = Masonry
Masonry Masonry
Soil Pressure @ To = 1,784 psf OK
Thickness = 8.00
12.00 16.00
Soil Pressure @ Hee = 766 psf OK
Rebar Size = # 6
# 6 # 6
=
Allowable 1,800 psf
Rebar Spacing = 16.00
16.00 16.00
Soil Pressure Less Than Allowable
= Edge
Rebar Placed atDgn
Edge Edge
ACI Factored @ Toe = 2,397 psf
esig
Design Data
ACI Factored @ Heel = 1,029 psf
+ fa/Fa = 0.569
0.615 0.850
Footing Shear@To = 11.1 psi OK
Total Force @ Section lbs= 564.0
1,096.3 1,812.4
Footing Shear@ Hee = 11.7 psi OK
Moment.... Actual ft-#= 1,350.9
3,256.0 6,612.2
=
Allowable 76.0 psi
Moment..... Allowable ft-#= 2,374.3
5,294.8 7,778.7
Wall Stability Ratios.
Shear..... Actual psi = 10.3
11.3 12.8 .
Overturning = 5.87 OK
Shear..... Allowable psi = 38.7.
38.7 38.7
Sliding = 2.77 OK
Lap Splice if Above in= 36.00
36.00 36.00
Sliding Calcs (Vertical Component NOT Used)
Lap Splice if Below in= 36.00
36.00 14.09
Lateral Sliding Forc 2,311.2 lbs
Wall Weight psf= 78.0
124.0 164.0
less 100% Passive Force= - 1,687.5 lbs
Rebar Depth 'd' in = 5.25
9.00 13.00
less 100% Friction Force= - 4,717.9 lbs
Masonry Data
Added Force Req'd = 0.0 lbs OK
fm psi= 1,500
1,500 1,500
....for 1.5 : 1 Stability = 0.0 lbs OK
Fs psi = 24,000
24,000 24,000
_
Solid Grouting = Yes
Yes Yes
Footing Design Results �;
Special Inspection = Yes
Yes Yes
Modular Ratio 'n' = 25.78
25.78 25.78
Toe- Heel
Factored Pressure = 2,397 1,029 psf
Short Term Factor = 1.000
Equiv. Solid Thick, in = 7.60
1.000 1.000
Mu': Upward = 2,072 0 ft-#
Masonry Block Type = Medium Weight
11.60 15.60
Mu': Downward = 348 0 ft-#.
Concrete Data
Mu: Design = 1,724 11,241 ft-#
fc psi=
-- --
-----
Actual 1 -Way Shear = 11.10 11.69 psi
Fy psi =
Allow 1 -Way Shear = 76.03 76.03 psi
Toe Reinforcing @
= # 7 31.75 in
Other Acceptable Sizes &Spacings
Toe: Not req'd, Mu < S ' Fr
Heel Reinforcing = # 6 @ 18.00 in
Key Reinforcing = None Spec'd
Heel: #4@ 7.25 in, #5@ 11.25 in, #6@ 16.00 in, #7@ 21.75 in, #8@ 28.50
in, #9@ 36
Key: #4@ 12.50 in, #5@ 19.25 in, #6@ 27.25
in, #7@ 37.25 in,
KNAPP &TANG STRUCTURAL ENGINEERS, INC. Title WADE RESIDENCE Page: W�
408 SOUTH STODDARD AVENUE Job Dsgnr: HW Date: NOV 20,2003
SAN BERNARDINO, CA 92401 Description....
PHONE: 909-889-0115 RETAINING WALL
FAX: 909-889-0455
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0 Cantilevered Retaining Wall Design
Build Date : 10 -SEP -2001, (c) 1989-2001
Summary of Overturning & Resisting Forces & Moments
:....OVERTURNING..... .....RESISTING.....
Force Distance Moment Force Distance Moment
Item lbs ft ft-# lbs ft ft-#
Heel Active Pressure =
2,314.4
3.83
8,871.8
Toe Active Pressure =
-70.0
0.67
-46.7
Surcharge Over Toe =
Adjacent Footing Load =
Added Lateral Load =
0.00
Load @ Stem Above Soi =
66.8
13.17
879.8
Total =
55.0
O.T.M. =
27.5
2,311.2
9,704.9
Resisting/Overturning Ratio
1,973.8
Earth @ Stem Transition
5.87
Vertical Loads used for Soil Pressure = 11,794.8 lbs
Vertical component of active pressure NOT used for soil pressure
Soil Over Hee =
7,608.3
5.79
44,064.9
Sloped Soil Over Hee =
Surcharge Over Heel =
Adjacent Footing Load =
Axial Dead Load on Ste =
0.00
Soil Over To
=
Surcharge Over Toe
55.0
0.50
27.5
Stem Weight(s) =
1,348.5
1.46
1,973.8
Earth @ Stem Transition
=
Footing Weigh
476.7
2.03
967.6
=
Key Weight
2,081.3
4.63
9,625.8
=
Vert. Component
225,0
1.50
337.5
Total=
11,794.8 lbs
R.M. a
56,997.1
6"
#5@18. in
@Toe
#5@18.in
@ Heel
8.in Mas w/ #5 (cD 24 -in nIr
5'-6"
12'-6"
T -O"
Designer select
all horiz. reinf.
See Appendix A i
T -O"
V-011
P e�e C e V\Ct
�(2/ A1,2
rIPTA
E -M
KNAPP & TANG STRUCTURAL ENGINEER INC Title 7' HIGH Page: 0-7 '
408 South Stoddard Ave. Job # Dsgnr: Date: NOV 19,2003
San Bernardino, CA 92401 Description....
Phone: (909) 889-0115
Fax: (909) 889-0455
This Wall in File: D:IPROJECTIHOME1Tessier.RP5
RetaBuild Pro Version 6.0 Cantilevered Retaining Wall Design
Build Date : 10 -SEP -2001, (c) 1989-2001 9 9
Criteria
= 1,797 psf OK
Retained Height =
Wall height
F.�
7:00 IfARKtt
above soil =
5ry/ft
Slope Behind Wal =
0:00: 1
Height of Soil over Toe =
6.00 in
Soil Density =
110.00 pcf
Wind on Stem = 20.0 psf
Design Summary 11
Total Bearing Load = 2,565 lbs
...resultant ecc. = 12.58 in
Soil Pressure @ Toe
= 1,797 psf OK
Soil Pressure @ Heel
= 0 psf OK
Allowable
= 1,800 psf
Soil Pressure Less Than Allowable
ACI Factored @ Toe
= 2,390 psf
ACI Factored @ Heel
= 0 psf
Footing Shear @ Toe
= 12.8 psi OK
Footing Shear @ Heel
= 0.0 psi OK
Allowable
= 76.0 psi
Wall Stability Ratios
=
Overturning
= 1.51 OK
Sliding
= 1.71 OK
Sliding Calcs (Vertical
Component NOT Used)
Lateral Sliding Force
= 1,304.4 lbs
less 100% Passive Force= - 1,200.0 lbs
less 100% Friction Force= - 1,025.9 lbs
Added Force Req'd
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK
i Footing Design Results
1,030.0
Toe Heel
Factored Pressure =
2,390 0 psf
Mu' : Upward =
0 0 ft-#
Mu': Downward =
0 0 ft-#
Mu: Design =
5,223 0 ft-#
Actual 1 -Way Shear =
12.85 0.00 psi
Allow 1 -Way Shear =
76.03 0.00 psi
Toe Reinforcing =
# 5 @ 18.00 in
Heel Reinforcing =
# 5 @ 18.00 in
Key Reinforcing =
# 5 @ 10.25 in
Soil Data
Allow Soil Bearing
= 1,800.0 psf
Equivalent Fluid Pressure Method
Heel Active Pressure
= 35.0 psf/ft
Toe Active Pressure
= 35.0 psf/ft
Passive Pressure
= 300.0 psf/ft
Water height over heel
= 0.0 ft
FootingilSoil Frictior
= 0.400
Soil height to ignore
Rebar Spacing
for passive pressure
= 12.00 in
Stem Construction
I
Top Stem
Design height
ft =
Stem OK
3.50
Wall Material Above "Ht" =
Masonry
Thickness
=
8.00
Rebar Size
=
# 5
Rebar Spacing
=
24.00
Rebar Placed at
=
Center
Design Data
fb/FB + fa/Fa
=
0.910
Total Force @ Section
lbs =
324.4
Moment.... Actual
ft-#=
937.6
Moment..... Allowable
ft-#=
1,030.0
Shear.....Actual
psi =
8.1
Shear..... Allowable
psi =
38.7
Lap Splice if Above
in=
30.00
Lap Splice if Below
in=
30.00
Wall Weight
psf=
84.0
Rebar Depth 'd'
in=
3.75
Masonry Data
fm
psi=
1,500
Fs
psi=
24,000
Solid Grouting
=
Yes
Special Inspection
=
Yes
Modular Ratio 'n'
=
25.78
Short Term Factor
=
1.000
Equiv. Solid Thick.
in =
7.60
Masonry Block Type = Normal
Weight
Concrete Data
fc
psi =
Fy
psi =
Other Acceptable Sizes & Spacings
Toe: Not req'd, Mu < S ' Fr
Heel: Not req'd, Mu < S " Fr
Key: Not req'd, Mu < S " Fr
Footing Dimensions & Strengths
Toe Width
= 3.00 ft
Heel Width
= 1.00
Total Footing Width
= 4.00
Footing Thickness
= 18.00 in
Key Width = 12.00 in
Key Depth = 12.00 in
Key Distance from Toe = 3.00 ft
fc = 2,000 psi Fy = 60,000 psi
Footing Concrete Density = 150.00 pcf
Min. As % = 0.0018
Cover @ Top = 2.00 in @ Btm.= 3.00 in
2nd
Stem OK
0.00
Masonry
12.00
# 5
16.00
Edge
0.973
963.1
3,072.6
3,159.4
9.8
38.7
25.00
7.83
133.0
9.00
1,500
20,000
Yes
Yes
25.78
1.000
11.60
• KNAPP & TANG STRUCTURAL ENGINEER INC
Title • 7' HIGH
Page: O
46 South Stoddard Ave.
Job #Dsgnr:
Date:
NOV 19,2003
San Bernardino, CA 92401
Description....
Phone: (909) 889-0115
Fax: (909) 889-0455
This Wall in File:
D:IPROJECTIHOMEITessier.RP5
RetainPro Version 6.0
Caritilevered- Retaining
`
Wall Design
g g
Build Date : 10 -SEP -2001, (c) 1989-2001
! Summary of Overturning & Resistinq Forces & Moments
.....OVERTURNING.....
.....RESISTING.....
Force Distance oment
M
Force
Distance
Moment
Item lbs ft ft-#
lbs
ft
ft-#
Heel Active Pressure = 1,264.4 2.83 3,582.4
Soil Over Heel =
_
4.00
Toe Active Pressure = -70.0 0.67 -46.7
Sloped Soil Over Heel =
Surcharge Over Toe =
Surcharge Over Heel =
Adjacent Footing Load =
Adjacent Footing Load =
Added Lateral Load =
Axial Dead Load on Stem=
0.00
Load @ Stem Above Soil = 110.0" 11.25 1,237.5
Soil Over Toe
=
Surcharge Over Toe _
165.0
1.50
247.5
Total = 1,304.4 O.T.M. = 4,773.2
Stem Weight(s)
Earth @ Stem Transitions=
1,221.5
3.40
4,149.3
Resisting/Overturning Ratio = 1.51
Footing Weight
128.3
3.83
491.9
Vertical Loads used for Soil Pressure = 2,564.8 lbs
=
Key Weight =
900.0
150.0
2.00
3.50
1,800.0
525.0
Vert. Component
Vertical component of active pressure NOT used for soil pressure
Total =
2,564.8
lbs R.M.= ,
7,213.7
12.1
1 2." Masonry wl 412'(pu JIG."
2.* Masonry w/ #7 @ 116.°
Sliding Restraint
#0@ 16.m
@Toe
;"0@ 15. in
@ Heel
a
12 10-01,
\j,
V
N
\N
N
2"
T
2--3-
4--0"
a
KNiiNP & TANG STRUCTURAL ENGINEERS, INC. Title WADE RESIDENCE Page:
466 ,OUTH STODDARD AVENUE Job Dsonr: HW Date: NOV 18,2003
SAN UERNARDINO, CA 92401 Descriotion....
'PHONE: 909-889-0115 12' RETAINING WALL
FAX: 909-889-0455
0 This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
Build Date : 10 -SEP -2001,
(c) 1989-2001 Restrained Retaining Wall Design
= 3,387 psf
Criteria
= 0 psf
1 Soil Data
= 22.1 psi OK
Footing Strengths & Dimensions
Retained Height
= 12.00 ft -"
Allow Soii Bearing = 3,000.0 psf
Reaction at Top =
Toe Width = 9,25 r
Wall height above soil
= 0.00 ft
Equivalent Fluid Pressure Method
Heel Width = 1.75
Total Wall Height
= 12.00 ft
Heel Active Pressure = 55.0 psf/ft
Total Footing Widt = 4 -60 -
ft
Surcharge Over Toe = lbs
Toe Active Pressure = 55.0 psf/ft
Footing Thickness = 18.00 in
Top Support Height
= 12.00 ft
Passive Pressure = 300.0 psf/ft
Soil Over Heel = 990.0 lbs
3.63 ft
3,588.8 ft-#
Water height over heel = 0.0 ft
Key Width = 0.00 in
Slope Behind Wal
= 0.00 : 1Key
FootingllSoil Frictio = 0.400
Depth = 0.00 in
Height of Soil over To
= 0.00 in
Key Distance from Toe= 0.00 ft
Soil Density
= 110.00 pcf
Soil height to ignore -
for passive pressure - 12.00 in
fc = 3,000 psi Fy = 60,000 psi
Footing Concrete Densit = 150.00 pcf
Wind on Stem
= 0.0 psf
Min. As % = 0.0018
Cover @.Top = 2.00 in @ Btm.= 3.00 in
`Design Summary
, Masonry Stem Construction
--
Total Bearing Loa
...resultant ecc.
= 3,378 lbs
= 12.83 in
Thickness 12.00 in fm =
1,500 psi Short Term Factor = 1.000
Wall Weight = 124.0 pcf Fs =
24,000 psi Equiv. Solid Thick. = 11.600 in
Soil Pressure @ To
= 2,419 psf OK
Stem is FIXED to top of footing
n Ratio (Es/Em) = 25.778
Soil Pressure @ Hee
= 0 psf OK
Block Type = Medium Weight
Use Special Inspection
Allowable
= 3,000 sf
Solid Grouted
Soil Pressure Less Than Allowable
ACI Factored @ Toe
= 3,387 psf
ACI Factored @ Heel
= 0 psf
Footing Shear @ To
= 22.1 psi OK
Footing Shear @ Hee
8.7 psi OK
Allowable =
93.1 psi
Reaction at Top =
792.0 lbs
Reaction at Bottom =
4,219.9 lbs
Sliding Caics Slab Resists All Sliding I
Lateral Sliding Forc = 4,219.9 lbs
i Footing Design Results
Mmax Between
Top & Base
Factored Pressure =
3,387
eel
0 psf
Mu' : Upward =
7,426
0 ft_#
Mu': Downward =
984
1,082 ft-*
Mu: Design =
6,441
1,082 ft-#
Actual 1 -Way Shear =
22.08
8.72 psi
Allow 1 -Way Shear =
93.11
93.11 psi
Design height
Rebar Size
Rebar Spacing
Rebar Placed a
Rebar Depth 'd'
Design Data
fb/FB + fa/Fa
Moment .... Actu
Moment..... Allowable
@ Top Support
Mmax Between
Top & Base
@ Base of Wall
Stem OK •
Stem OK
_ Stem OK
_
12.00 ft
6.65 ft
0.00 ft
- 5
# 7
# 7
= 16.00 in
16.00 in
16.00 in
= Center
Edge
Edge
= 5.75 in
9.00 in
9.00 in
Shear Force @ this height =
Shear..... Actual =
Shear..... Allowable =
Rebar Lap Required =
Rebar embedment into footing
0.000
0.0 ft-#
2,371.7 ft --
0.0
x0.0 lbs
0.00 psi
38.73 psi
25.00 in
0.437
2,833.5 ft --
6,477.9
x6,477.9 ft4
35.00 in
Other Acceptable Sizes & Spacings:
Toe: None Spec'd -or- Not reo'd, Mu < S ' Fr
Heel: None Spec'd -or- Not req'd, Mu < S - Fr
Key: No key defined -or- No key defined
0.978
6,336.1 ft-#
6,477.9 ft-#
3,168.0 lbs
33.28 psi
38.73 psi
13.42 in
Summary of Forces on Footing : Slab [STSsliT1'ng, stem is FIXED at footing - " ----
rorces acting on rooting Tor son pressure
Load & Moment Summary For Footing : For
Soil Pressure Calcs
>>> Sliding Forces are restrained by the adjacent slab
Moment @ Top of Footing Applied from
'Stem=
Surcharge Over Heel = lbs
ft
6,336.1 t
Adjacent Footing Load = lbs
ft
ft
Axial Dead Load on Stem = lbs
ft
ft_
Soil Over Toe = lbs
ft
ft
Surcharge Over Toe = lbs
ft
ft
Stem Weight = 1,488.0 lbs
2.75 ft
ft -f
4,092.Oftx
Soil Over Heel = 990.0 lbs
3.63 ft
3,588.8 ft-#
Footing Weight = 900.0 lbs
2.00 ft
1.800.0 ft-#
Total Vertical Force = 3,378.0 ibs
Base Moment
1.144.6 ft�
Soil Pressure Resulting Moment = 3,611.4t-4
8." K&-j5Dnqj yd # 24
Lateral Restraint
269.5 #
Masonry w/ #!7'@"24.' JI
N I P,
!N
X\1
N
8. Masonry w/ #5 @ 24.
fi
3.
7'-0"
7
7'-0'
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
Title WADE RESIDENCE
Page: 9Z
08 SOUTH STODDARD AVENUE
Allowable
Job
Dsgnr: HW
Date: NOV 18,2003
SAN BERNARDINO, CA 92401
ACI Factored @ Heel
Description....
Footing Shear @ To
= 7.9 psi OK
PHONE: 909-889-0115
= 3.6 psi OK
7'-0' RETAINING WALL
= 76.0 psi
FAX: 909-889-0455
= 269.5 lbs
Reaction at Bottom
= 1,640.2 lbs
Sliding Stability Ratio
= 1.53 OK
Sliding Calcs
This Wall in
File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0
Restrained Retaining Wall Design
less 100% Friction Force=
- 1,034.7 lbs
B,jild Date : 10 -SEP -2001, (c) 1989-2001
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK ,
Footing Design Results �.
Criteria ^
'Soil Data
'
Footing Strengths & Dimensions
Retained Height= 7.00 ft
Allow Soil Bearing
"= 1,800:0 psf
Toe Width
= 1.42 ft
Wall height above soil = <0.00 ft
Equivalent Fluid Pressure
Method
Heel Width
= 2.08
Total Wall Height = 7.00 ft
Heel Active Pressure
= 55.0 psf/ft
Total Footing Widt
= -S.5-9-
.5-Toe
2.79ft
ToeActive Pressure
= 55.0 psf/ft
Footing Thickness
= 16.00 in
To Support Height = 7.00 ft
Top pp g
Passive Pressure
Water height over heel
= 200.0 psf/ft
= 0.0 ft
Key Width
_
- 8.00 in
Slope Behind Wal = 0.00: 1
FootingijSoil Frictio
= 0.400
Key Depth
Key Distance from Toe
= 30.00 in
= 1.42 ft
Height of Soil over To = 0.00 in
Soil height to ignore
Soil Density = 110.00 pcf
for passive pressure
= 0.00 in
psi
_
Fy 650.00 0,000 si
Footing Concrete,000 Densit
psf
Wind on Stem = 0.0 psf
Min. As %
=
0.0018Cover
@ Top = 2.00 in
@ Btm.= 3.00 in
In Summary
oiai bearing Loa = 2,5bf it)
.resultant ecc. = 0.95 in
Soil Pressure @ To
= 839 psf OK
Soil Pressure @ Hee
= 639 psf OK
Allowable
= 1,800 psf
Soil Pressure Less Than Allowable
ACI Factored @ Toe
= 1,175 psf
ACI Factored @ Heel
= 895 psf
Footing Shear @ To
= 7.9 psi OK
Footing Shear @ Hee
= 3.6 psi OK
Allowable
= 76.0 psi
Reaction at Top
= 269.5 lbs
Reaction at Bottom
= 1,640.2 lbs
Sliding Stability Ratio
= 1.53 OK
Sliding Calcs
ft
Lateral Sliding Forc
= 1,640.2 lbs
less 100% Passive Force= - 1,469.4 lbs
less 100% Friction Force=
- 1,034.7 lbs
Added Force Req'd
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK ,
Footing Design Results �.
ft#
loe Meal
Factored Pressure =
1,175 895 psf
Mu': Upward =
1,141 936 ft#
Mu': Downward =
281 1,363 ft-*
Mu: Design =
860 427 ft-#
Actual 1 -Way Shear =
7.92 3.56 psi
Allow 1 -Way Shear =
76.03 76.03 psi
Thickness = 8.00 in frn =
Wall Weight = 78.0 pcf Fs =
Stem is FIXED to top of footing
Block Type = Medium Weight
Solid Grouted
Design height
Rebar Size
Rebar Spacing
Rebar Placed a
Rebar Depth 'd'
Design Data
fb/FB + fa/Fa
Moment .... Actu
Moment..... Allowable
1,500 psi
24,000 psi
@ Top Support
Stem OK
7.00 ft
# 5
= 24.00 in
Edge
5.25 in
Short Term Factor =
1.000
Equiv. Solid Thick. =
7.600 in
n Ratio (Es/Em) =
25.778
Use Special Inspection
Mmax Between
Load & Moment Summary For Footing : For
Top & Base @ Base
of Wall
Stem OK
Stem OK
3.88 ft
0.00 ft
#' 5
# 5
24.00 in
24.00 in
Center
Edge
3.75 in
5.25 in
= 0.000 0.546
0.0 ft-# 562.4 ft-#
_ 1,465.7 ft-# 1,030.0 ft-#
Shear Force @ this height = 0.0 lbs
Shear..... Actual = 0.00 psi
Shear..... Allowable = 38.73 psi
0.858 _
1,257.7 ft-#
1,465.7 ft -#-
1,078.0
#1,078.0 lbs
18.88 psi
38.73 psi
Rebar Lap Required = 25.00 in 25.00 in
Rebar embedment into footing = 11.74 in
Other Acceptable Sizes & Spacings:
Toe: # 5 @ 18.00 in -or- Not req'd, Mu < S ' Fr
Heel:# 5 @ 18.00 in -or- Not req'd, Mu < S " Fr
Key: #4@ 22.25 in, #5@ 34 -or- #4@ 22.25 in, #5@ 34.50 in, #6@ 48.
Summary of Forces on Footing : Slab is NOT providing sliding, stem is FIXED at footing
`Forces
acting on rooting For snaing
& soil pressure....
Sliding Forces
Load & Moment Summary For Footing : For
Soil Pressure Calcs
Stem Shear @ Top of Footin =
-1,078.0 lbs
Moment @ Top of Footing Applied from Stem
-1,257.7ft#
Heel Active Pressure =
-562.2
Sliding Force =
1,640.2 lbs
Surcharge Over Heel = lbs
ft
ft-#
Adjacent Footing Load = lbs
ft
ft-#
Net Moment User For Soil Pressure Calculations
Axial Dead Load on Stem = lbs
ft
ft#
204.4 ft-#
Soil Over Toe = lbs
ft
ft-#
Surcharge Over Toe = lbs
ft
ft-#
Stem Weight = 546.0 lbs
1.75 ft-
955.5ft-#
Soil Over Heel = 1,090.8 lbs
2.79ft
3,045.2ft-#
Footing Weight = 950.0 lbs
1.66 ft
1,579.5ft-#
Total Vertical Force = 2-,-58-68-lbs
Base Moment
4,322.6ft#
#7@3 1.75in
@Toe
5.m Mas wl #5 @ 24.in o/c
5olid Grout, 5pc In!
Designer 5CIeCt
1'-0 112- 1'-5 112*
all horiz. reir,f. Do-
5ce Appendix A
4'- 10"
3'-3-
2-
3"
a
KNAPP & TANG STRUCTURAL ENGINEERS, INC. Title WADE RESIDENCE Page: 9Y
.4:NB SOUTH STODDARD AVENUE Job Dsgnr: HW Date: NOV 18,2003
SAN BERNARDINO, CA 92401 Description....
PHONE: 909-889-0115 3'-3" RETAINING WALL
FAX: 909-889-0455
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0 Cantilevered Retaining Wall Design
Build Date : 10 -SEP -2001, (c) 1989-2001
unterla
�..
Retained Height -
= 34257ft
Wall height above soil
= 4.83 ft
Slope Behind Wal
=. 0%0 : 1
Height of Soil over To
= 0.00 in
Soil Density
= 110.00 pcf
Allow Son hearing , '
= 1,800.0 psf
Equivalent Fluid Pressure Method
Heel Active Pressure
= 35.0 psf/ft
Toe Active Pressure
= 35.0 psf/ft
Passive Pressure
= 300.0 psf/ft
Water height over heel
= 0.0 ft
FootingIlSoil Frictio
Wind on Stem = 20.0 psf Soil height to ignore
for passive pressure
Design Summary iI
Total Bearing Loa = 1,484 lbs
...resultant ecc. = 6.75 in
Soil Pressure @ To
= 1,218 psf OK
Soil Pressure @ Hee
= 0 psf OK
Allowable
= 1,800 psf
Soil Pressure Less Than Allowable
ACI Factored @ Toe
= 1,705 psf
ACI Factored @ Heel
= 0 psf
Footing Shear @ To
= 9.1 psi OK
Footing Shear @ Hee
= 4.3 psi OK
Allowable
= 76.0 psi
Wall Stability Ratios.
Rebar Placed at
Overturning
= 2.05 OK
Sliding
= 1.56 OK
Sliding Calcs (Vertical Component NOT Used)
Lateral Sliding Forc •
= 414.2 lbs
less 100% Passive Force=- - 54.2 lbs
less 100% Friction Force= - 593.6 lbs
Added Force Req'd
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK
Footing Design Results
Moment..... Allowable
Toe Heel
Factored Pressure =
1,705 0 psf
Mu' : Upward =
1,039 84 ft-#
Mu': Downward =
179 544 ft-#
Mu: Design =
860 461 ft-#
Actual 1 -Way Shear =
9.06 4.28 psi
Allow 1 -Way Shear =
76.03 76.03 psi
Toe Reinforcing =
# 7 @ 31.75 in
Heel Reinforcing =
# 6 @ 18.00 in
Key Reinforcing =
None Spec'd
= 0.400
= 12.00 in
Footing Dimensions8� Strengfhs -,
Toe Width
= 1.04 ft
Heel Width
= 1.71
Total Footing Widt
=-----2-75-
Footing Thickness
= 14.00 in
Key Width = 0.00 in
Key Depth = 0.00 in
Key Distance from Toe = 2.00 ft
fc = 2,000 psi Fy = 60,000 psi
Footing Concrete Densit = . 150.00 pcf
Min. As % = 0.0018
Cover @ Top = 2.00 in @ Btm.= 3.00 in
I Stem Construction
Top Stem
Design height
ft=
Bar Lap/Emb - - - - - .-.--
0.00
Wall Material Above "Ht"
=
Masonry
Thickness
=
8.00
Rebar Size
=
# 5
Rebar Spacing
=
24.00
Rebar Placed at
=
Edge
Design Data
--
fb/FB + fa/Fa
=
_
0.510
Total Force @ Section
lbs =
281.4
Moment.... Actual
ft-#
747.5
Moment..... Allowable
=
1,465.7
Shear..... Actual
psi =
4.9
Shear..... Allowable
psi =
38.7
Lap Splice if Above
in=
30.00
Lap Splice if Below
in=
11.74
Wall Weight
=
78.0
Rebar Depth 'd'
in=
- 5.25
Masonry Data
fm
psi=
1,500
Fs
psi =
24,000
Solid Grouting
=
Yes
Special Inspection
=
Yes
Modular Ratio 'n'
=
25.78
Short Term Factor
=
1.000
Equiv. Solid Thick.
in=
7.60
Masonry Block Type = Medium
Weight
Concrete Data
fc
psi =
Fy
psi =
Other Acceptable Sizes & Spacings
Toe: Not req'd, Mu < S " Fr
Heel: Not req'd, Mu < S " Fr
Key: No key defined
KNAPP & TANG STRUCTURAL ENGINEERS, INC. Title WADE RESIDENCE Page: •
408 oOUTH STODDARD AVENUE Job Dsgnr: HW Date: NOV 18,2003
SAN BERNARDINO, CA 92401 Description....
PHONE: 909-989-0115 X-3" RETAINING WALL
FAX*. 909-889-0455
RetaThis Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
Build Date
Version 6.0e : 10 -SEP -2001, (c) 1989-2001 Cantilevered Retaining Wall Design
Build
Summary of Overturning & Resisting Forces & Moments -�
.....OVERTURNING..... .....RESISTING.....
Force Distance Moment Force Distance Moment
Item lbs ft ft-# lbs ft ft-#
neer,Ncuve r-ressure =
Toe Active Pressure =
Surcharge Over Toe =
Adjacent Footing Load =
Added Lateral Load =
Load @ Stem Above Soi =
341.4 1.47 502.6
-23.8 0.39 -9.3
96.6 6.83 659.9
Total = 414.2 O.T.M. = 1,153.3
Resisting/Overturning Ratio 2.05
Vertical Loads used for Soil Pressure = 1,483.9 lbs
Vertical component of active pressure NOT used for soil pressure
Soil Over Hee =
372.4
2.23
830.1
Sloped Soil Over Hee =
Surcharge Over Heel =
Adjacent Footing Load =
Axial Dead Load on Ste =
0.00
Soil Over To _
Surcharge Over Toe
Stem Weight(s)
=
Earth @ Stem Transition _
630.2
1.38
866.6
Footing Weigh
=
Key Weight
481.3
1.38
661.7
=
Vert. Component
2.00
Total =
1,483.9 lbs
R.M.
2,358.4
6n
#7@31 .751
@Toe
5 -in Mas w/ #6 @ 16.in o/c
Designer select I
1
#6@ 18.in ! !
all horiz. reinf.
@ Heel 5ee Appendix A I
Z -a I 8" �u
I i
46 ,
i
KNAPP & TANG STRUCTURAL ENGINEERS, INC.
Title WADE RESIDENCE
Page: 9i
408 S0,07-1 STODDARD AVENUE
Allowable =
Job
Dsgnr: HW
Date: NOV 16,220_3
SAN BERNARDINO, CA 92401
1,922 psf
Description....
0 psf
Footing Shear @ To =
PHONE: 909-889-0115
Footing Shear @ Hee =
8'-8" RETAINING WALL
Allowable =
FAX: 909-889-0455
Wall Stability Ratios
10.98 psi
Overturning =
1.80 OK
Sliding =
1.58 OK
This Wall in File: C:IRETAIN PRO-6lEXAMPLES.RP5
RetainPro Version 6.0
Cantilevered Retaining Wall Design
1,070.1 lbs
less 100% Passive Force -
Build Date : 10 -SEP -2001, (c) 1989-2001
less 100% Friction Force= -
904.8 lbs
Added Force Req'd =
0.0 lbs OK
_Criteria
!Soil Data
=
0.172
Footing Dimensions &Strengths
Retained Height = 6.83 ft
Allow Soil Bearing
= 1,800.0 psf
Toe Width
2.00 ft ---
Wall height above soil = i 1.83 ft
Equivalent Fluid Pressure Method
Heel Width
= 1.75
Slope Behind Wal = 0.00: 1
Heel Active Pressure
= 35.0 psf/ft
Total Footing Widt
= ,_--3775-
Height of Soil over To = 6.00 in
Toe Active Pressure
Passive Pressure
= 35.0 psf/ft
= 300.0 psf/ft
Footing Thickness
= 12.00 in
Soil Density = 110.00 pcf
Water height over heel
= 0.0 ft
Key Width
= 8.00 in
Wind on Stem = 20.0 psf
LDesign Summary 1
Total Bearing Loa = 2,262 lbs
...resultant ecc. = 9.32 in
Soil Pressure @ To =
1,373 psf OK
Soil Pressure @ Hee =
0 psf OK
Allowable =
1,800 psf
Soil Pressure Less Than
Allowable
ACI Factored @ Toe =
1,922 psf
ACI Factored @ Heel =
0 psf
Footing Shear @ To =
20.6 psi OK
Footing Shear @ Hee =
11.0 psi OK
Allowable =
76.0 psi
Wall Stability Ratios
10.98 psi
Overturning =
1.80 OK
Sliding =
1.58 OK
Sliding Calcs (Vertical Component
NOT Used)
Lateral Sliding Forc =
1,070.1 lbs
less 100% Passive Force -
787.5 lbs
less 100% Friction Force= -
904.8 lbs
Added Force Req'd =
0.0 lbs OK
....for 1.5: 1 Stability =
0.0 lbs OK
Footing Design Results
,
/
oe
Heel
Factored Pressure
= 1,922
0 psf
Mu' : Upward
= 3,522
49 ft-#
Mu': Downward
= 674
986 ft-#
Mu: Design
= 2,849
937 ft-#
Actual 1 -Way Shear
= 20.62
10.98 psi
Allow 1 -Way Shear
= 76.03
76.03 psi
Toe Reinforcing
= # 7 @ 31.75 in
16.00
Heel Reinforcing
= # 6 @ 18.00 in
=
Key Reinforcing
= None Spec'd
Design Data
FootingIlSoil Frictio
Soil height to ignore
for passive pressure
= 0.400 Key Depth =
Key Distance from Toe =
12.00 in fc = 2,000 psi
Footing Concrete Densit
Min. As %
Cover @ Top = 2.00 in
Fy
12.00 in
2.00 ft
60,000 psi
150.00 pcf
0.0018
@ Btm.= 3.00 in
i Stem Construction
,
Top Stem
2nd
Stem OK Bar Lap/Emb --
Design height
ft =
3.34
0.00
Wall Material Above "Ht"
=
Masonry
Masonry
Thickness
=
8.00
8.00
Rebar Size
=
# 6
# 6
Rebar Spacing
=
16.00
16.00
Rebar Placed at
=
Edge
Edge
Design Data
fb/FB + fa/Fa
=
0.172
0.902
Total Force @ Section
lbs =
249.8
848.6
Moment.... Actual
ft-#=
409.2
2,141.3
Moment..... Allowable
ft-#=
2,374.3
2,374.3
Shear..... Actual
psi =
4.5
15.4
Shear..... Allowable
psi =
38.7
38.7
Lap Splice if Above
in=
36.00
36.00
Lap Splice if Below
in =
36.00
14.09
Wall Weight
psf=
78.0
78.0
Rebar Depth 'd'
in=
5.25
5.25
Masonry Data
fm
psi=
1,500
1,500
Fs
psi=
24,000
24,000
Solid Grouting
=
Yes
Yes
Special Inspection
=
Yes
Yes
Modular Ratio 'n'
=
25.78
25.78
Short Term Factor
=
1.000
1.000
Equiv. Solid Thick.
in=
7.60
7.60
Masonry Block Type = Medium
Weight
Concrete Data
fc
psi =
---
Fy
psi =
Other Acceptable Sizes & Spacings
Toe: #4@ 13.25 in, #5@ 20.50 in, #6@ 29.00 in, #7@ 39.25 in, #8@ 48.25 in, #9@ 4
Heel: Not req'd, Mu < S ' Fr
Key: #4@ 22.25 in, #5@ 34.50 in, #6@ 48.25 in, #7@ 48.25 in,
K•N',,P-P & TANG STRUCTURAL ENGINEERS, INC. Title WADE RESIDENCE" Page: / 6
498 SOUTH STODDARD AVENUE Job Dsgnr: HW Date: NOV 18,2003
SAN BERNARDINO, CA 92401 Description....
PHONE: 909-889-0115 8%8" RETAINING. WALL
FAX: 909-889-0455
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
RetaBuild at Version 6.0 Cantilevered Retainin Wall Design
Build Date : 10 -SEP -2001, (c) 1989-2001 g. 9
Summary of Overturning & Resisting Forces & Moments
...OVERTURNING"'..---
..... RESISTING.....
Force Distance Moment Force Distance Moment
Item lbs ft ft-# lbs ft ft-#
Heel Active Pressure =
Toe Active Pressure =
Surcharge Over Toe =
Adjacent Footing Load =
Added Lateral Load =
Load @ Stem Above Soi =
1,072.9 2.61 2,800.3
-39.4 0.50 -19.7
36.6 8.75 320.1
Total = 1,070.1 O.T.M. = 3,100.7
Resisting/Overturning Ratio 1.80
Vertical Loads used for Soil Pressure = 2,261.9 lbs
Vertical component of active pressure NOT used for soil pressure
Soil Over Hee =
813.9
3.21
2,611.3
Sloped Soil Over Hee =
Surcharge Over Heel =
Adjacent Footing Load =
Axial Dead Load on Ste =
0.00
Soil Over To
=
Surcharge Over Toe _
110.0
1.00
110.0
Stem Weight(s)
675.5
2.33
1,576.1
Earth @ Stem Transition _
Footing Weigh
=
Key Weight
562.5
1.88
1,054.7
=
Vert. Component _
100.0
2.33
233.3
Total = 2,261.9 lbs R.M. 5,585.4
5.in Mas w/ a5 @ I G.in dr-
5ohd Grout: 5pc Ins
#7@3 1 .75in
@Toe
Designer 5electl i
#6@ 18.m P -O"
all hor¢. re nf. —► .�---►�
@ heel See Appendix A
2'-3"
2"
r
I
A-R/hI,2
2'-2"
r
0
KNAPP & TANG STRUCTURAL ENGINEERS, INC. Title WADE RESIDENCE Page: �ba
x4,08 SOUTH STODDARD AVENUE Job Dsgnr: HW Date: NOV 20,2003
SAN BERNARDINO, CA 92401 Description....
PHONE: 909-889-0115 "'' RETAINING WALL
FAX: 909-889-0455
Reta
g g
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
Build Date
version 6.oe : 10 -SEP -2001, (c) 1989-2001 Cantilevered Retaining Wall Design
Build
_
i-5oil Data
---
Footing Dimensions 8� Strengths
Retained Hei � ht �
g
_ . " 2.16 ft
Allow Soil Bearing
= 1,800.0 psf
Toe Width =
1.U0 ft
Wall height above soil
= . 3 ft
Equivalent Fluid Pressure Method
Heel Width =
1.25
Slope Behind Wal
= 0.00:1
Heel Active Pressure
= 35.0 psf/ft
Total Footing Widt =
2-2-5
Height of Soil over To
= 0.00 in
Toe Active Pressure
Passive Pressure
= 35.0 psf/ft
- P
300.0 psf/ft
Footing Thickness =
12.00 in
Soil Density.
= 110.00 pcf
Water height over heel
= 0.0 ft
Key Width =
0.00 in
16.00
L
FootingIlSoil Frictio
= 0.400
Key Depth =
0.00 in
Wind on Stem
= 20.0 psf
P
Soil height to ignore
Key Distance from Toe =
0.00 ft
0.081
for passive pressure
= 12.00 in
fc = 2,000 psi Fy =
60 000 psi
I Design Summary
Total Bearing Loa = 787 lbs
...resultant ecc. = 2.24 in
Soil Pressure @ To = 524 psf OK
Soil Pressure @ Hee = 176 psf OK
Allowable = 1,800 psf
Soil Pressure Less Than Allowable
ACI Factored @ Toe = 734 psf
ACI Factored @ Heel = 246 psf
Footing Shear @ To = 4.1 psi OK
Footing Shear @ Hee = 1.2 psi OK
Allowable 76.0 psi
Wall Stability Ratios
Overturning = 3.26 OK
Sliding = 1.62 OK
Sliding Calcs (Vertical Component NOT Used)
Lateral Sliding Forc =. 193.8 lbs
less 100% Passive Force= - 0.0 lbs -
less 100% Friction Force= - 314.9 lbs
Added Force Req'd = 0.0 lbs OK
....for 1.5 : 1 Stability = 0.0 lbs OK
Footing Design Results
oe eel
Factored Pressure = 734- 246 psf
Mu'.: Upward = 0 84 -ft-.#
Mu': Downward = 0 153 ft-#
Mu: Design = 291 68 ft-#
Actual 1 -Way Shear = 4.07 1.19 psi
Allow 1=Way Shear = 76.03 76.03 psi
Toe Reinforcing = *7 @ 31.75 in
Heel Reinforcing = # 6 @ 18.00 in
Key Reinforcing = None Spec'd
Other Acceptable Sizes & Spacings
Toe: Not req'd, Mu < S ' Fr
Heel: Not req'd, Mu < S ' Fr
Key: No key defined
Footing Concrete Densit = 150.00 pcf
Min. As % = 0.0018
Cover @ Top = 2.00 in @ Btm.= 3.00 in
Stem Construction
-'
Top Stem
Design height
ft=
Bar Lap/Emb
0.00
Wall Material Above "Ht"
=
Masonry
Thickness
=
8.00
Rebar Size
=
# 5
Rebar Spacing
=
16.00
L
Rebar Placed at
=
Edge
Design Data
fb/FB + fa/Fa
=
0.081
Total Force @ Section
lbs =
118.2
Moment .... Actual
ft-#=
171.3
Moment..... Allowable
=
2,115.9
Shear..... Actual
psi =
2.1
Shear..... Allowable
psi =
38.7
Lap Splice if Above
in =
30.00
Lap Splice if Below.
in =
11.74.
Wall Weight
=
78,0
Rebar Depth 'd'
in=
5.25
Masonry Data
fm
psi=
1,500
Fs
psi=
24,000
Solid Grouting
=
Yes
Special Inspection
=
Yes
Modular Ratio 'n'
=
25,78
Short Term Factor
=
1.000
Equiv. Solid Thick.
in=
7.60'
Masonry Block Type = Medium Weight
Concrete Data
fc
psi=
Fy
osi =
Other Acceptable Sizes & Spacings
Toe: Not req'd, Mu < S ' Fr
Heel: Not req'd, Mu < S ' Fr
Key: No key defined
KNAPP & TANG STRUCTURAL ENGINEERS, INC. Title WADE RESIDENCE
408 SOUTH STODDARD AVENUE Page:'
Job Dsgnr: HW Date: NOV 20,2003
SAN BER`NARDINO, CA 92401 Description....
PHONE: 909-889-0115 RETAINING WALL
FAX: 909-889-0455
This Wall in File: C:IRETAIN PRO-61EXAMPLES.RP5
Build Date
Version 6.0e : 10 -SEP -2001, (c) 1989-2001 Cantilevered Retaining g Wall Design
Build
Summary of Overturning & Resisting Forces & Moments
.....OVERTURNING.....
Force Distance Moment RESISTING.....
Item lbs ft ft-# Force Distance Moment
Heel Active Pressure = 174.7 lbs ft ft-#
1.05 184.1
Toe Active Pressure = -17.5 0.33 -5.8
Surcharge Over Toe =
Adjacent Footing Load =
Added Lateral Load =
Load @ Stem Above Soi = 36.6 4.08 149.1
Total = 193.8 O.T.M. = 327.4
Resisting/Overturning Ratio 3.26
Vertical Loads used for Soil Pressure = 787.3 lbs
Vertical component of active pressure NOT used for soil pressure
Soil Over Hee = 138.6 1.96 271.4
Sloped Soil, Over Hee =
Surcharge Over Heel =
Adjacent Footing Load =
Axial Dead Load on Ste = 0.00
Soil Over To _
Surcharge Over Toe
Stem Weight(s) _
Earth @ Stem Transition = 311'2 1.33 415.0
Footing Weigh _
Key Weight - 337.5 1.13 379.7
Vert. Component _
Total = 787.3 lbs R.M. + 1,066.1 -
8 -in Mas w/ #5 @ 24.in o/c
Solid Grout, Spc Insp
12.in Mas w/ #5 @ 16.in o/c
Solid Grout, Spc Insp
16.in Mas w/ #5 @ 16.in o/c
Solid Grout, Spc Insp
20.in Conc w/ #8 @ 16.in o/c
6'-0" 1 5'-6"
3"
-3"
14'-0"
2 1/2"
5'-6"
6":
#5@9.in v
@Toe
Designer selectl i 2'-10"'
#5@10- in all horiz. reinf.1
(0 Heel See Appendix Al
8'-4" V-8"
8'-4"
-8"
101-01,
KNAPP & TANG STRUCTURAL ENGINEER INC Title 14'H -a
408 South Stoddard Ave. Job # Dsgnr:
San Bernardino, CA 92401 Description....
Phone: (909) 889-0115
Fax: (909) 889-0455
Page: 2e _ , ,
Date: NOV 19,2003
FootingilSoil Frictior
Wind on Stem = 20.0 psf Soil height to ignore
for passive pressure
_Design Summary
Total Bearing Load = 7,281 lbs
...resultant ecc. = 11.63 in
Soil Pressure @ Toe
= 1,152 psf OK
This Wall in File: D:IPROJECTIHOME1Tessier.RP5
RetainPro Version 6.0
Allowable
Cantilevered Retaining Wall Design
Soil Pressure Less Than Allowable
Build Date : 10 -SEP -2001,
(c) 1989-2001
ACI Factored @ Heel
= 399 psf
Criteria
= 24.4 psi OK
LSoil Data
Footing Dimensions & Strengths
Retained Height=
14:00 ft,
Allow Soil Bearing = 1,800.0 psf
Toe Width = 8.33 ft
Wall height above soil
= , , 5.50'ft
Equivalent Fluid Pressure Method
Heel Width = 1.67
Slope Behind Wal =
"0.00 : 1
Heel Active Pressure = 35.0 psf/ft
_
Total Footing Widtt = 10.00
Height of Soil over Toe =
6.00 in
Toe Active Pressure = 35.0 psf/ft
Passive Pressure = 300.0 psf/ft
Footing Thickness = 20.00 in
Soil Density =
110.00 pcf
Water height over heel = 0.0 ft
Key Width = 20.00 in
FootingilSoil Frictior
Wind on Stem = 20.0 psf Soil height to ignore
for passive pressure
_Design Summary
Total Bearing Load = 7,281 lbs
...resultant ecc. = 11.63 in
Soil Pressure @ Toe
= 1,152 psf OK
Soil Pressure @ Heel
= 305 psf OK
Allowable
= 1,800 psf
Soil Pressure Less Than Allowable
ACI Factored @ Toe
= 1,508 psf
ACI Factored @ Heel
= 399 psf
Footing Shear @ Toe
= 24.4 psi OK
Footing Shear @ Heel
= 0.0 psi OK
Allowable
= 76.0 psi
Wall Stability Ratios
# 5
Overturning
= 2.20 OK
Sliding
= 1.51 OK
Sliding Calcs (Vertical
Component NOT Used)
Lateral Sliding Force
= 4,323.1 lbs
less 100% Passive Force=
- 3,600.0 lbs
less 100% Friction Force= - 2,912.5 lbs
Added Force Req'd
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK
Footing Design Results
0.277
Toe Heel
Factored Pressure =
1,508 399 psf
Mu' : Upward =
41,638 0 ft-#
Mu': Downward =
14,815 0 ft-#
Mu: Design =
26,823 0 ft-#
Actual 1 -Way Shear =
24.43 0.03 psi
Allow 1 -Way Shear =
76.03 76.03 psi
Toe Reinforcing =
# 5 @ 9.00 in
Heel Reinforcing =
# 5 @ 10.00 in
Key Reinforcing =
# 5 @ 10.25 in
= 0.400 Key Depth = 34.00 in
Key Distance from Toe = 8.33 ft
= 12.00 in fc = 2,000 psi Fy
Footing Concrete Density
Min. As %
Cover @ Top = 2.00 in
I Stem Construction
in=
Top Stem
2nd__
Design height
ft =
Stem OK
13.50
Stem OK
10.17
Wall Material Above "Ht"
=
Masonry
Masonry
Thickness
=
8.00
12.00
Rebar Size
=
# 5
# 5
Rebar Spacing
=
24.00
16.00
Rebar Placed at
=
Center
Edge
Design Data
25.78
Short Term Factor
=
fb/FB + fa/Fa
=
0.348
0.277
Total Force @ Section
lbs =
114.4
366.7
Moment.... Actual
ft-#=
358.2
1,051.5
Moment..... Allowable
ft-#=
1,030.0
3,791.3
Shear..... Actual
psi =
2.8
3.7
Shear..... Allowable
psi =
38.7
38.7
Lap Splice if Above
in=
30.00
Lap Splice if Below
in=
30.00
Wall Weight
psf=
84.0
Rebar Depth 'd'
in =
3.75
Masonry Data
16.00
Edge
fm
psi=
1,500
Fs
psi=
24,000
Solid Grouting
=
Yes
Special Inspection
=
Yes
ModularRatio'n'
=
25.78
Short Term Factor
=
1.000
Equiv. Solid Thick.
in =
7.60
Masonry Block Type =
Normal Weight
Concrete Data
fc
psi =
Fy
psi =
30.00
30.00
133.0
9.00
60,000 psi
150.00 pcf
= 0.0018
@ Btm.= 3.00 in
3rd
4th
Stem OK
_ _
Bar Lap/Emb
5.50
0.00
Masonry
Concrete
16.00
20.00
# 5
# 8
16.00
16.00
Edge
Edge
0.867
1,374.4
4,819.9
5,558.5
9.6
38.7
30.00
43.60
175.0
13.00
0.684
6,010.6
30,342.3
44,329.2
28.6
76.0
87.21
18.78
250.0
17.50
1,500
1,500
24,000
24,000
Yes
Yes
Yes
Yes
25.78
25.78
1.000
1.000
11.60
15.60
2,000.0
60,000.0
Other Acceptable Sizes & Spacings
Toe: #4@ 5.00 in, #5@ 7.50 in, #6@ 10.75 in, #7@ 14.50 in, #8@ 19.25 in, #9@ 24.
Heel: Not req'd, Mu < S ' Fr
Key: #4@ 6.75 in, #5@ 10.25 in, #6@ 14.50 in, #7@ 19.75 in,
KNAPP & TANG STRUCTURAL ENGINEER INC
Title 14'H-a
Page:
f 403 Sou.h Ctoddard Ave.
Job # -
Dsgnr:
Date:
NOV 19,2003
San Bernardino, CA 92401
Description....
Phone: (909) 889-0115 `
Fax: (909) 889-0455
This Wall in File:. D:IPROJECTIHOME1Tessier.RP5
RetainPro Version 6.0 Cantilevered. Retainin
Build Date
Wall Desi n
g g
: 10-SEP-2001, (c) 1989-2001
Summary of Overturning & Resisting Forces & Moments
OVERTURNING.....'
.....RESISTING.....
Force' Distance oment
M
Force
Distance
Moment
Item lbs ft ft-#
lbs
ft
ft-#
Heel Active Pressure = 4,295.3 5.22 22,430.9
Soil Over Heel =
5.1
10.00
51.3
Toe Active Pressure = -82.2 0.72 -59.3
Sloped Soil Over Heel =
Surcharge Over Toe =
Surcharge Over Heel =
Adjacent Footing Load =
Adjacent Footing Load =
Added Lateral Load =
Axial Dead Load on Stem=
0.00
Load @ Stem Above Soil = 110.0 18.42 2,025.8
Soil Over Toe
=
Surcharge Over Toe =
458.2
4.17
1,908.2
Stem Weight(s)
Total = 4,323.1 O.T.M. = 24,397.4
Earth@ Stem Transitions=
3,139.1
8.99
28,229.1
Resisting/Overturning Ratio = 2,20
Footing Weight
470.4
9.70
4,565.3
Vertical Loads used for Soil Pressure = 7,281.2 lbs
=
Key Weight =
2,500.0
708.3
5.00
9.16
12,500.0
6,490.7
Vert.. Component _
Vertical component of active pressure NOT used for soil pressure.
Total.=
7,281.2
lbs R.M.= ,
53,744.7
8.in Mas w/ #5 @ 24.in o/c
Solid Grout, Spc Insp
12.in Mas w/ #5 @ 16.in o/c
Solid Grout, Spc Insp
16.in Mas w/ #5 @ 16. in o/c
Solid Grout, Spc Insp
20.in Conc w/ #8 @ 16.in o/c
6"
Q
F -O"
3'-4" i
14'-O"l
#5@9.in 3
@Toe
2'-4"
Designer select!
#5@10.in all h oriz. reinf.1
@ Heel See Appendix Al
4 -8" 3--7"
4'-9" 5'-3"
101-01,
e� teAC C 2-���. � � � 2C
KNAPP & TANG STRUCTURAL ENGINEER INC Title 14' high Page: /06
403 South Stoddard Ave. Job # Dsgnr: Date: NOV 19,2003
San Bernardino, CA 92401 Description....
Phone: (909) 889-0115
Fax: (909) 889-0455
This Wall in File: D:IPROJECTIHOME1Tessier.RP5
d version 6.0
BuilCantilevered Retaining Wall Design
Build Date : 10 -SEP -2001, (c) 1989-2001
Criteria
Retained Height
Wall height above soil
Slope Behind Wal .
Height of Soil over Toe
Soil Density
Wind on Stem
Soil Data
= 14.00 ft'
Allow Soil Bearing •
= 11800.0 psf
= ft
Equivalent Fluid Pressure Method
(""55o
Heel Active Pressure
- 35.0 psf/ft
= 0.00 : 1
Toe Active Pressure
= 35.0 psf/ft
= 6.00 in
Passive Pressure
= '300.0 psf/ft
= 110.00 pcf
Water height over heel
= 0.0 ft
FootingIlSoil Frictior
20.0 psf Soil height to ignore
for passive pressure
Surcharge Loads
Design Summary
Total Bearing Load = 12,652 lbs
...resultant ecc. _ 6.25 in
Soil Pressure @ Toe
= 1,661 psf OK
Soil Pressure @ Heel
= 870 psf OK
Allowable
= 1,800 psf
Soil Pressure Less Than Allowable
ACI Factored @ Toe
= 2,238 psf
ACI Factored @ Heel
= 1,172 psf
Footing Shear @ Toe
= 27.8 psi OK
Footing Shear @ Heel
= 20.9 psi OK
Allowable
= 76.0 psi
Wall Stability Ratios
12.00
Overturning
= 3.15 OK
Sliding
= 1.74 OK
Sliding Calcs (Vertical Component NOT Used)
Lateral Sliding Force
= 4,572.4 lbs
less 100% Passive Force= - 2,887.5 lbs
less 100% Friction Force=
- 5,060.7 lbs
Added Force Req'd
= 0.0 lbs OK
....for 1.5 : 1 Stability
= 0.0 lbs OK
! Footing Design Results �-
Edge
Toe Heel
Factored Pressure =
2,238 1,172 psf
Mu' : Upward =
23,348 8,344 ft-#
Mu' : Downward =
4,817 16,538 ft-#
Mu: Design =
18,531 8,195 ft-#
Actual 1 -Way Shear =
27.81 20.95 psi
Allow 1 -Way Shear =
76.03 76.03 psi
Toe Reinforcing =
# 5 @ 9.00 in
Heel Reinforcing =
# 5 @ 10.00 in
Key Reinforcing =
# 5 @ 10.25 in
= 0.400
l Footing Dimensions & Strengths
Toe Width
= 4.75 ft
Heel Width
- 5.25
Total Footing Widtt
_
= 10.00
Footing Thickness
= 20.00 in
Key Width = 20.00 in
Key Depth = 28.00 in
Key Distance from Toe = 4.75 ft
12.00 in fc = 2,000 psi Fy = 60,000 psi
Footing Concrete Density = 150.00 pcf
Min. As % = 0.0018
Cover @ Top = 2.00 in @ Btm.= 3.00 in
Surcharge Over Heel = 50.0 psf Surcharge Over Toe 1 0.0 psf
Used To Resist Sliding & Overturning Used for Sliding & Overturning
Stem Construction
L
j
Top Stem
2nd
3rd
Design height
ft=
Stem OK
13.50.
Stem OK
- 10.17
_
Stem OK
5.50
Wall Material Above "Ht"
=
Masonry
Masonry
Masonry
Thickness
=
8.00
12.00
16.00
Rebar Size
=
# 5
# 5
# 5
Rebar Spacing
=
24.00
16.00 -
16.00
Rebar Placed at
=
Center
Edge
Edge
Design Data
Masonry Block Type =
Normal Weight
Concrete Data
fb/FB + fa/Fa
=
0.350
0.308.
0.971
Total Force @ Section
lbs=
122.3
427.6
1,509.6
Moment.... Actual
ft-#=
360.2
1,168.2
5,394.6
Moment..... Allowable
ft-#=
1,030.0
3,791.3
5,558.5
Shear..... Actual
psi =
3.0
4.4
10.5
Shear..... Allowable
psi =
38.7
38.7
38.7'
Lap Splice if Above
in=
30.00
Lap Splice if Below
in=
30.00
Wall Weight
psf=
84.0
Rebar Depth 'd'
in =
3.75
Masonry Data
15.60
-
fm
psi=
1,500
Fs
psi =
24,000
Solid Grouting
=
Yes
Special Inspection
=
Yes
Modular Ratio 'n'
=
25.78
Short Term Factor
_.
1.000
Equiv. Solid Thick.
in=
7.60
Masonry Block Type =
Normal Weight
Concrete Data
fc
psi=
Fy
psi =
30.00
30.00
133.0
9.00
30.00
43.60
175.0
13.00
4th
Bar Lap/Emb
0.00
Ccncrete
20.00
# 8
16.00
Edge
0.744
6,389.2
32, 992.8
44, 329.2
30.4
76.0
87.21
18.78
250.0
17.50
1,500
1,500
24,000
24,000
Yes
Yes
Yes
Yes
25.78
25.78
1.000
1.000
11.60
15.60
2,000.0
60,000.0
Other Acceptable Sizes & Spacings
Toe: #4@ 6.75 in, #5@ 10.50 in, #6@ 15.00 in, #7@ 20.25 in, #8@ 26.75 in, #9@ 33
Heel: #4@ 6.50 in, #5@ 10.00 in, #6@ 14.00 in, #7@ 19.25 in, #8@ 25.25 in, #9@ 31
Key: #4@ 6.75 in, #5@ 10.25 in, #6@ 14.50 in, #7@ 19.75 in,
KNAPP & TANG STRUCTURAL ENGINEER INC Title 14' high
8.21
Page:/67
408 South Stoddard Ave. Job #
Dsgnr: Date:
NOV 19,23"
San Bernardino, CA 92401 Description....
2.38
620.5
Phone: (909) 889-0115
5.41
16,991.0
Fax: (909) 889-0455
6.12
2,881.2
This Wall in File:
D:IPROJECTIHOME1Tessier.RP5
12,500.0
RetainPro Version 6.0 Cantilevered Retaining Wall Design
Build
5.58
3,256.9
Date : 10 -SEP -2001, (c) 1989-2001
R.M.=
83,016.6
' Summary of Overturning & Resisting Forces & Moments
....OVERTURNING:.. -
'Moment
.....RESISTING.....
Force Distance
Force Distance
Moment
Item lbs ft ft-#
lbs ft
ft-#
Heel Active Pressure = 4,544.5 5.37 24,383.3 Soil Over Heel
= 5,518.3 8.21
45,296.3
Toe Active Pressure = -82.2 0.72 -59.3 Sloped Soil Over Heel
=
Surcharge Over Toe =
Adjacent Footing Load =
Added Lateral Load =
Load @ Stem Above Soil = 110.0 18.42 2,025.8
Total = 4,572.4 O.T.M. = 26,349.8
Resisting/Overturning Ratio = 3.15
Vertical Loads used for Soil Pressure = 12,651.7 lbs
Vertical component of active pressure NOT used for soil pressure
Surcharge Over Heel =
Adjacent Footing Load =
Axial Dead Load on Stem=
Soil Over Toe _
Surcharge Over Toe _
Stem Weight(s)
Earth @ Stem Transitions__
Footing Weight _
Key Weight _
Vert. Component
Total =
179.2
8.21
1,470.7
0.00
261.3
2.38
620.5
3,139.1
5.41
16,991.0
470.4
6.12
2,881.2
2,500.0
5.00
12,500.0
583.3
5.58
3,256.9
12,651.7 lbs
R.M.=
83,016.6
r68
I
FeJ e reA cc 2-- -11, -/- - p, r2.
f
KNAPP & TANG STRUCTURAL ENGINEERS, INC. Title
408 SOUTH STODDARD AVENUE Job Dsgnr: HW
SAN BERNARDINO, CA 92401 Description....
PHONE: 909-889-0115 5'-0" RETAINING WALL
FAX: 909-889-0455
Date: MAY 8,2 03 i
Design Summary
��
Masonry Stem Construction
This Wall in File: CARETAIN PRO-61EXAMPLES.RP5
RetainPro Version 6.0
Restrained Retaining Wall Design
Total Bearing Loa
...resultant ecc.
= 986 lbs
= 0.88 in
Build Date : 10 -SEP -2001,
(c) 1989-2001
Short Term Factor =
1.000
Adjacent Footing Load = lbs
ft
Criteria
Soil Data
7.600 in
Footing Strengths & Dimensions
Retained Height
= 3.67 ft
Allow Soil Bearing
= 1,500.0 psf
Toe Width
U.67 ft
Wall height above soil
= 1.67 ft
Equivalent Fluid Pressure Method
Heel Width
= 1.33
Total Wall Height
= 5.34 ft
Heel Active Pressure
= 55.0 psf/ft
Total Footing Widt
= 2 -00 -
Than Allowable
@
Toe Active Pressure
= 55.0 psf/ft
Footing Thickness
= 12.00 in
Top Support Height
= 5.33 ft
Passive Pressure
Water height over heel
= 300.0 psf/ft
= 0.0 ft
Key Width
= 0.00 in
Slope Behind Wal
= 0.00 :1
Footing��Soil Frictio
_
- 0.400
Ke Depth
y p
Key Distance from Toe
-
- 0.00 in
= 0.00 ft
Height of Soil over To
= 0.00 in
Soil height to ignore
0.00 ft
Footing Shear @ Hee
= 1.1 psi OK
Soil Density
= 110.00 pcf
for passive pressure
= 0.00 in
fc = 2,000 psi
Fy = 60,000 psi
Rebar Spacing =
16.00 in
16.00 in
16.00 in
Footing Concrete Densit
= 150.00 pcf
Wind on Stem =
0.0 psf
Center
Center
Min. As %
= 0.0018
Rebar Depth 'd' =
3.75 in
3.75 in
3.75 in
Cover @ Top = 2.00 in
@ Btm.= 3.00 in
Design Summary
��
Masonry Stem Construction
>>> Sliding Forces are restrained by the adjacent slab
Load & Moment Summary For Footing : For Soil Pressure Calcs
Total Bearing Loa
...resultant ecc.
= 986 lbs
= 0.88 in
Thickness = 8.00 in fm
= 1,500 psi
Short Term Factor =
1.000
Adjacent Footing Load = lbs
ft
Wall Weight = 78.0 pcf Fs
= 24,000 psi
Equiv. Solid Thick. =
7.600 in
Soil Pressure @ To
= 601 psf OK
Stem is FIXED to top of footing
Surcharge Over Toe = lbs
n Ratio (Es/Em) =
25.778
Soil Pressure @ Hee
= 385 psf OK
Block Type = Medium Weight
Soil Over Heel = 269.1 lbs
Use Special Inspection
Allowable
= 1,500 psf
Solid Grouted
300.0 ft-#
Mmax Between
Base Moment
Soil Pressure Less
Than Allowable
@
Top Support
Top & Base @ Base of Wall
ACI Factored @ Toe
= 841 psf
ACI Factored @ Heel
= 539 psf
Stem OK
Stem OK
Stem OK
Footing Shear @ To
= 3.8 psi OK
Design height =
5.33 ft
2.50 ft
0.00 ft
Footing Shear @ Hee
= 1.1 psi OK
Rebar Size =
# 6
# 6
# 6
Allowable
= 76.0 psi
Rebar Spacing =
16.00 in
16.00 in
16.00 in
Reaction at Top
= 37.9 lbs
Rebar Placed a =
Center
Center
Center
Reaction at Bottom
= 561.9 lbs
Rebar Depth 'd' =
3.75 in
3.75 in
3.75 in
Design Data
Sliding Calcs Slab Resists All Sliding !
fb/FB + fa/Fa = -
Moment
0.000
0.069
0.187
Lateral Sliding Forc
= 561.9 lbs
.... Actu =
0.0 ft-#
92.5 ft-#
251.3 ft-#
Moment..... Allowable =
1,341.6 ft-#
1,341.6 ft-# 1,341.6
ft-#
Shear Force @ this height =
0.0 lbs
332.5 lbs
Shear..... Actual =
0.00 psi
8.63 psi
Shear..... Allowable =
38.73 psi
38.73 psi
Footing Design Results
Rebar Lap Required =
30.00 in
30.00 in
I 8T eel
Rebar embedment into footing
=
14.09 in
Factored Pressure =
841 539 psf
Other Acceptable Sizes & Spacings:
Mu': Upward =
Mu': Downward =
179 127 ft-#
47 172 ft-#
Toe: # 5 @ 18.00 in
-or- Not req'd, Mu < S * Fr
Mu: Design =
133 45 ft-#
Heel:# 5 @ 18.00 in
-or- Not req'd, Mu < S * Fr
Actual 1 -Way Shear =
3.80 1.09 psi
Key: No key defined
-or-. No key defined
Allow 1 -Way Shear =
76.03 76.03 psi
Summary of Forces on Footing : Slab RESISTS sliding, stem is FIXED at'footing --
Forces acing on tooting or soi pressure
>>> Sliding Forces are restrained by the adjacent slab
Load & Moment Summary For Footing : For Soil Pressure Calcs
Moment @ Top of Footing Applied from Stem
=
251.3 ft-#
Surcharge Over Heel = lbs
ft
ft-#
Adjacent Footing Load = lbs
ft
ft-#
Axial Dead Load on Stem = lbs
ft
ft-#
Soil Over Toe = lbs
ft
ft-#
Surcharge Over Toe = lbs
ft
ft-#
Stem Weight = 416.51bs
1.00 ft
416.5 ft-#
Soil Over Heel = 269.1 lbs
1.67 ft
448.6 ft-#
Footing Weight = 300.0 lbs
1.00 ft
300.0 ft-#
Total Vertical Force = 985.7 lbs
Base Moment
913.7 ft-#.
Soil Pressure Resulting Moment = 71.9t-#
r