11-0695 (AC)P.O. BOX 1504
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
Application Number:
11-00000695
Property -Address:---
60750 -TRILOGY PKWY
APN:
764-270-999-135 -300231-
Application description:_
ADDITION - COMMERCIAL ,
Property Zoning:
MEDIUM HIGH DENSITY RES
Application valuation:
39896
_
for by Section 3700 of the Labor Code, for the performance of the work for which this permit is
Applicant:
Arr'c'hityct or Engineer -
issued.
Date: Contract
_ I have and will maintain workers' compensation insurance, as required by Section 3700 of the Labor
-4
BUILDING & SAFETY DEPARTMENT -
BUILDING PERMIT
Owner:
SHEA LA QUINTA
60800 TRILOGY PARKWAY
LA QUINTA, CA 92253
e ..
��,_JALM
R BUILDERS
SEP 02 011 301 BADGER, SUITE #300'
4 it DESERT, CA 922i1
nrO�o. 60)360-6632
1. A �Qi11Ny�c. No..: 693077
VOICE (760) 777-7012
FAX (760) 777-7011
INSPECTIONS (760) 777-7153
Date: 8/30/11
Date:
Owner:
CONSTRUCTION LENDING AGENCY
1 hereby affirm under penalty of perjury that there is a construction lending agency for the performance of the
work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's Name: _
Lender's Address:
LQPERA11T
of La Quinta, its officers, agents and employees for any act or omission related to the work being
performed under or following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is not commenced
within 180 days from date of issuance of such permit, or cessation of work for 180 days will subject
permit to cancellation.
I certify that I have read this application and state that the above information is correct. 1 agree to comply with all
city and county ordinances and state laws rel g to buil in tru 'on-ar♦d,>ereby authorize representatives
of this county
tttooenter/'ppon the above-mentioned property for ins purposes
Date: -` Signature (Applicant or Agent):
- LICENSED CONTRACTOR'S DECLARATION
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter 9 (commencing with
I hereby affirm under penalty of perjury one of the following declarations:
Section 7000) of Division 3 t e usin d P fest' als Code, and my License is in full force and effect.
I have and will maintain a certificate of consent to self -insure for workers' compensation, as provided
License Class; B ' ense No.: 693077
_
for by Section 3700 of the Labor Code, for the performance of the work for which this permit is
/.
issued.
Date: Contract
_ I have and will maintain workers' compensation insurance, as required by Section 3700 of the Labor
-.-
- Code, for the performance of the work for which this permit is issued. My workers' compensation
DECLARATION
insurance carrier and policy number are:
a Contractor's State License Law for the
I hereby affirm under penalty of perjury that I�Dior
Carrier STATE FUND Policy Number 1960920-2011'
following reason (Sec. 7031 .5, Business 'andAny city or county that requires a permit to
_ I certify that, in the performance of the work for which this permit is issued, I shall not employ any
' construct, alter, improve, demolish, or repair anyo its issuance, also requires the applicant for the
person in any manner so as to become subject to the workers' compensation laws of California,
permit to file a signed statement that he or she is licensed pursuant to the provisions of the Cohtractor's State
and agree , at, if I s o ecome subject to the workers' compensation provisions of Section
License Law (Chapter 9 (commencing with Section 7000) of Division 3 of the Business and Professions Code) �or
3700 of the Labor Cade , I fort .comply with those provisions.
that he or she'is exempt therefrom and the basis for the alleged exemption. Any violation of Section 7031.5 by
any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500).:
Date:�v ApplicanLL
1 _ 1 I, as owner of the property, or my employees with wages as their sole compensation, will do the work, and
the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The
WARNING: FAILURE TO SECURE WORKERS' C PENSA COVERAGE IS UNLAWFUL, AND SHALL
Contractors' State License Law does not apply to an owner of property who builds or improves thereon,
�N
SUBJECT AN EMPLOYER TO CRIMINAL PENAL IES AND Cl FINES UP TO ONE HUNDRED THOUSAND
and who does the work himself or herself through his or her own employees, provided that the
DOLLARS ($100,000). IN ADDITION TO THE ST OF COMP SATION, DAMAGES AS PROVIDED FOR IN
improvements are not intended or offered for sale. If, however, the building or improvement is sold within
SECTION 3706 OF THE LABOR CODE, INTERES , ND ATTOR Y'S FEES.
one year of completion, the owner -builder will have the burden of proving that he or she did not build or
improve for thepurpose of sale.).
APPLICANT ACK WLEDGEMENT
(_) 1, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec.
IMPORTANT Application is hereby made to the Director of Building and Safety for a permit subject to the
7044, Business and Professions The Contractors' State License Law does not apply to ar`owner of
conditionsand restrictions set forth on this application.
_Code:
property who builds or improves thereon, and who contracts for the projects with a contractor(s) licensed
1 . Each person upon whose behalf this application is made, each person at whose request and for
_
pursuant to the Contractors' State License Law.)..
whose benefit work is performed under or pursuant to any permit issued as a result of this application,
(_) I am exempt under Sec. , BAP.C. for this reason
the owner, and the applicant, each agrees to, and shall defend, indemnify and hold harmless the City
Date:
Owner:
CONSTRUCTION LENDING AGENCY
1 hereby affirm under penalty of perjury that there is a construction lending agency for the performance of the
work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's Name: _
Lender's Address:
LQPERA11T
of La Quinta, its officers, agents and employees for any act or omission related to the work being
performed under or following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is not commenced
within 180 days from date of issuance of such permit, or cessation of work for 180 days will subject
permit to cancellation.
I certify that I have read this application and state that the above information is correct. 1 agree to comply with all
city and county ordinances and state laws rel g to buil in tru 'on-ar♦d,>ereby authorize representatives
of this county
tttooenter/'ppon the above-mentioned property for ins purposes
Date: -` Signature (Applicant or Agent):
Application.Number 11-00000695
LQPERiIMIT
Structure Information
Construction Type . .
. . . TYPE V, UNPROTECTED
Occupancy Type . :
. . . LOW HAZARD STORAGE
Other struct info . .
. . . CODE EDITION 2010
FIRE SPRINKLERS YES
OCCUPANT LOAD
3.00
----------------------------------------------------------------------------
1ST FLOOR SQUARE FOOTAGE
505.00
Permit . . .
BUILDING PERMIT
Additional desc .
Permit Fee . . . .
336.50 Plan Check Fee
218.73
Issue Date
Valuation . . . .
37269
Expiration Date
2/26/12
Qty Unit Charge
Per
Extension
BASE FEE
252;.00 <,
13.00 6.5000
----------------------------------------------------------------------------
THOU BLDG 25,001-50,000
84.50
Permit . . .
ELECT - ADD/ALT/REM
Additional desc .
Permit Fee . . . .
25.10 Plan Check Fee
6.28
Issue Date . . .
Valuation . .
0
Expiration Date
2/26/12
Qty Unit Charge
Per
Extension
BASE FEE
15.00
505.00 .0200
-----------------------------------------------------------------------------
ELEC GARAGE OR NON-RESIDENTIAL
10.10
Permit . . . MECHANICAL
Additional desc .
Permit Fee . . . .
30.50 Plan Check Fee
7.63
Issue Date
Valuation . . . .
0
Expiration Date
2/26/12
Qty Unit Charge
Per
Extension•
BASE FEE
15.00
1.00 9.0000
EA MECH B/C <=3HP/100K BTU
9.00
1.00 6.5000
EA MECH AH <=10K CFM
6.50
Special Notes.and Comments
487 SF STORAGE ROOM AND 87 SF HALL
ADDITION TO EXISTING
SANTA ROSA CLUB. -
2010 CODES.
-----------------------------------------------------------------------------
Other Fees . . . . .
. . . . ACCESSIBILITY PLAN REVIEW
21.87
LQPERiIMIT
Application Number
11-00000695
----------------------------------------------------------------------------
Other Fees .
. . . . . .
BLDG.STDS ADMIN (SB1473)
2.00
ENERGY.REVIEW FEE
21.87.
STRONG.MOTION (SMI) - COM
7.83
Fee summary
Charged
Paid Credited
Due
-----------------
Permit Fee Total
----------
392.10
------------------------------
.00 .00
392:10
Plan Check Total
232.64
.00 .00
232_.64
Other Fee Total
53.57
.00 00
53.57
Grand Total
678.31,
.00 .00
678.31
LQPERMIT
0
In, k - 7 �ra 19 �7-5
Qty of La Quinta
Building &I Safety Division
P.O. Box 1504, 78-495 Calle Tampico
La Quinta, CA 92253 - (760) 777-7012
Building Permit Application and Tracking Sheet
Permit #
Project Address: (DC) --10Do
Owner's Name:
A. P. Number:
Address:
Legal Description:
Contractor:
City, ST, Zip:
Telephone:
Address:
Project Description: <5r ..4eN-
City, ST, Zip:
Telephone:
. ..........
........ ..........
.......
Par—
State Lic. #
City Lie. #.-.
C -0 ro\
Arch., Engr., Designer:
Address:4—e;1--,30 501") 9�—�L AAJE22V-)
City., ST, Zip: Cl#—
..... X -X. X
Telephone:ei
IX..... . ......... . .
State Lic. #: C,— lot ezLr) M:
.............
Construction Type: V-13 Occupancy:
Project type (circle one): New Alter. Repair Demo
Name of Contact Person:
Sq. Fu
I # Stories:
# Units:
Telephone # of Contact Person: -7(oo --45
Estimated Value of Prqje&
APPLICANT: DO NOT. WRITE BELOW Tft"k
Submittal
Reqld
Rec!d
-J�,J V
PERMIT FEES
Plan Sets
Plan Check submitted
Item Amount
Structural Cafes.U11
a
Reviewed, ready for correctioW
. Deposit
Plan Check
Truss Cafes..
Called Contact Person
61D!lan
Check Balance
Title 24 Cafes.
a
Plans picked up 13Y
Construction
Flood plain plan
Plans resubmittedMech
anical
Grading plan
2'd Review, ready for correctio/-issue)
Ift)
Electrical
Subcontactor List
Called Contact Person
Plumbing
Grant Deed
Plans picked up
S.M.I.
H.O.A. Approval
Plans resubmitted
Grading
IN HOUSE:-
3rd Review, ready for corrections/issue
Developer Impact Fee
Planning Approval
Called Contact Person
A.I.P.P. •
Pub. Wks. Appr
Date of permit issue
-A-
School Fees
Total Permit Fees L
J
Coachella Valley Unified School District
83-733 Avenue 55, Thermal, CA 92274
(760) 398-5909 — Fax (760) 398-1224
This Box For District Use Only
DEVELOPER FEES PAID
AREA: _
AMOUNT
LEVEL ONE AMOUNT:
LEVELTWO AMOUNT:
MITIGATION AMOUNT:
COMM/IND. AMOUNT':
DATE:
RECEIPT:
CHECK #:
INITIALS:
CERTIFICATE OF COMPLIANCE
(California Education Code 17620)
Project Name: Date: September 2, 2011
Owner's Name: Trilogy at La Quinta Maintenance Phone No. 760 360-6632
Project Address: 60-750 Trilogy Parkway, La Quinta, Ca
Project Description: Addition to Commercial Building — Storage Rm and Hall Addition at Santa Rosa
APN: 764 390 021 Tract #: Lot #'s:
Type of Development: Residential ommercial Industrial
Total Square Feet of Building Area: 505
Certification of Applicant/Owners: The person signing certifies that the above information is correct and makes this statement under
penalty of perjury and further represents that he/she is authorized to sign on behalf of the owner/developer.
Dated: Signature:
******************************
SCHOOL DISTRICT'S REQUIREMENTS FOR T1 -
ACCORDANCE WITH ONE OF THE FOLLOWING: (CIRCLE ONE)
Education Code Gov. Code Project Agreement Existing Not Subject to Fee
17620 65995 Approval Prior to 1/1/87 Requirement
Not
Number of Sq.Ft. 505
Amount per Sq.Ft. $.47
Amount Collected $237.35
Building Permit Application Completed: Yes/No
By:. Jamie T. Brown, Asst. Supt., Business Services
Certificate issued by: Marcela Valdez, Construction Analyst Signature:
NOTICE.OF 90 DAY PERIOD. FOR PROTEST OF FEES AND STATEMENT OF FEES
Section 66020 of the Government Code asserted by Assembly Bill 3081, effective January 1, 1997, requires that this District provide (1) a written notice to the
project appellant, at the time of payment of school fees, mitigation payment or other exactions ("Fees"), of the 90 -day period to protest the imposition of these
Fees and (2) the amount of the fees., Therefore, in accordance with section 66020 of the Government code and other applicable law, this Notice shall 'serve to
advise you that the 90 -day protest period in regard to such Fees or the validity thereof, commences with the payment of the fees or performance of any other
requirements as described in section 66020 of the Government code. Additionally, the amount of the fees imposed is as herein set forth, whether payable at thi:
time or in whole or in part prior to issuance of a Certificate of Occupancy. As in the latter, the 90 days starts on ;the date hereof. This Certificate o•'
Compliance is valid for thirty (30) days from the date of issuance. Extension will be granted only for good cause, as determined by the School District, and up
to -three (3) such extensions may be granted.
:f.!%:c:'r�<fucs:�i::+.ler,-cexti.li�::tie ;�t c�:n�.psi:f3lcc; f«rt: nl3cl,teci :+-"ili)'
11/2010
P.O. BOX 1504 BUILDING & SAFETY DEPARTMENT
78-495 CALLS TAMPICO (760) 777-7012
LA QUINTA, CALIFORNIA 92253 FAX (760) 777-7011
To: Greg Butler, Building & Safety Director To PD: August 11, 2011
From: Les Johnson, Planning -Director Due Date: 'August 17, 2011
Permit #: 11-694-695 Status:. 2nd
Building Plans Approval.
(This is an approval to issue a Building Permit)
The Planning Department has reviewed the Building Plans for the following
project:
Description: Storage (Trilogy)
Address or General Location: 60-750 Trilogy Parkway
Applicant Contact: Frank Rodriquez (760)779-5393
The Planning Department finds that:
❑ ...these Building Plans do not require Planning Department approval.
...these Building Plans are approved by the Planning Department.
❑ ...these Building Plans require corrections. Please forward a copy of the
attached corrections to the applicant. When the corrections are made
please return them to the Planning Department for review.
Les Johnso , Director -Planning Date
I" Ned
AUG 12 2011
City of La Quinta
Planning Department,
BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Trilogy Golf Club -Aerobics & Storage
60 -Trilogy Parkway
Laauuinta,-CA 92253 • r
Project ,Designer:
Prest Vuksic Architects
44-530 San Pablo Ave. Suite200
Palm Desert, Ca 92260 -
(760) 779-5393
{
Report Prepared by:
` Tim Scott -
Scott Design'. and Title 24, Inc,
,* q 77-085 Michigan Drive
Palm Desert, Ca 92211
(760) 200-4780
CITY�OF LA QUINTA
} t BUILDING- & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
Job Number:' PATE .30� BY
Date:
AUG.I 1 2011
7/28%2011
By
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
Energ Pro 5.1 by EnergySoft User Number: 6712 Run Code: 2011-07-28T12:59:38 ID
4
4
r
PLRFORMANCE CERTIFICATE OF COMPLIANCE (Part 1 of 3) PERF -1 C
Project Name
Date
rilogy Golf Club -Aerobics & Storage
7/28/2011
Project Address
Climate Zone
Total Cond. Floor Area
Addition Floor Area
60800 Trilogy Parkway La Quinta
CA Climate Zone 15
1,405
n/a
GENERAL INFORMATION
Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Relocatable - indicate ❑ specific climate zone ❑ all climates
Phase of Construction: ❑ New Construction ❑ Addition ❑ Alteration
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed to
comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This
certificate applies only to a Building using the performance compliance approach.
The documentation author hereby certifies that the documentation is accurate and co
tete.
Documentation Author
Name Tim Scott
Signature
Company
p Scott Design and Title 24, Inc,
Date 728/1011
Address 77-085 Michigan Drive
Phoned (760) 200-4780
�Y
City/State/Zip Palm Desert, Ca 92211 l' Ok v43 -� ':5— 7CG
am
The Principal Designer hereby certifies that the proposed building design represented in this set of
construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with
any other calculations submitted with this permit application. The proposed building has been designed to meet the energy
efficiency requirements contained in sections 110, 116 through 118, and 140 through 149 of Title 24, Part 6. Please
check one:
ENV. LTG. MECH.
I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
❑ ❑ ❑ sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section
❑ ❑ ❑ 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
❑ ❑ ❑ because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538 and 6737.1.
Principal Envelope Designer
[Signature
Name Prost Vuksic Architects
Company Prost Vuksic Architects Date
Address 44-530 San Pablo Ave. Suite200 License #
City/State/Zip Palm Desert Ca 92260 Phone 60) 779-5393
Principal Mechanical Designer
Name Tim Scott
Signature
Company Scott Design and Title 24, Inc. Date I I" l(
Address 77-085 Michigan Drive License #
City/State/Zip Palm Desert, Ca 92211 Phone (760) 200-4780
Principal Lighting Designer
Name Prest Vuksic Architects
Signature
Company Prost Vuksic Architects Date
Address 44-530 San Pablo Ave. Suite200 License #
City/State/Zip Palm Desert, Ca 92260 Phone (760) 779-5393
INSTRUCTIONS TO APPLICANT COMPLIANCE & WORKSHEETS (check box if worksheets are included)
m ENV -1C Certificate of Compliance. Required on plans. m MECH-1C Certificate of Compliance. Required on plans.
m LTG -1C Certificate of Compliance. Required on plans. m MECH-2C Air/Water Side/Service Hot Water & Pool Requirements.
m LTG -2C Lighting Controls Credit Worksheet. m MECH-3C Mechanical Ventilation and Reheat.
❑ LTG -3C Indoor Lighting Power Allowance.. m MECH-5C Mechanical Equipment Details.
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2011-07-28T12:59:38 ID: Page 3 of 27
1 '
rroTn
RFORMANCE CERTIFICATE OF COMPLIANCE (Part 2 of 3) 'PERF -1 C
ect NameDate
o Golf Club -Aerobics & Storage 7/28/2011
ANNUAL TDV ENERGY USE SUMMARY kBtu/s ft- r 4
Standard, Proposed Compliance
Energy Component Design Design Margin'--
Space Heating
'Space Cooling
Indoor Fans
Heat Rejection
Pumps & Misc. ,
Domestic Hot Water
Lighting
Receptacle
Process
Process Lighting
TOTALS
- 0.49
1.45
-0.96
175.85
153.80
22.05
57.15
76.78
-19.63
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
59:90
51.99
7.91
43.57
43.57
0.00
0.00
0.00
0.00
0.00
- 0.00
0.00
336.96
327.59
9.37
Heating
Cooling14;
Fans . C .
V.Heat Ref SFV•
Pumps !
DH W b
Lighting
x
Receptacle 4,4 x }` &
' f
a°
Process 1 $
k
Process Ltg t #.
Percent better than Standard F 2.8%1 2.8 % excludinprocess)
BUILDING COMPLIES
GENERAL INFORMATION '
Building Orientation (E) 90 deg Conditioned. Floor Area 1,405 sqft
Number of Stories 1 Unconditioned Floor Area 0 sqft.
Number of Systems 2 Conditioned Footprint Area 1.405 sqft.
Number of Zones 2 Natural Gas Available On Site Yes
Orientation Gross Area Glazinq Area Glazino Ratio
Front Elevation
Left Elevation
Rear Elevation
Right Elevation
Total
Roof
(E)
145
(S)
.548
(1M
221
(N)
780
1,694
906
sqft.
sqft.
sqft.
sqft..
sqft. '
sqft.
sqft.
sqft.
sqft.
sqft.
sqft.
sqft.
0.0%
17.4%
11.5%
3.8%
8.9%
0.0%
Standard Proposed Prescriptive Values for
Prescriptive Lighting Power Density 0.856 W/sgft. 0.743 W/sgft• Comparison only. See
Prescriptive Envelope TDV Energy 65,969 103,716 LTG -1C for allowed LRD..
Remarks: A
EnemyPro6lbyEnemySoft User Number: 6712 RunCode: 2011-07-28712:59:38 ID: - Page 4 of 27
0
96
26
30
151
0
sqft.
sqft.
sqft.
sqft.
sqft.
sqft.
0.0%
17.4%
11.5%
3.8%
8.9%
0.0%
Standard Proposed Prescriptive Values for
Prescriptive Lighting Power Density 0.856 W/sgft. 0.743 W/sgft• Comparison only. See
Prescriptive Envelope TDV Energy 65,969 103,716 LTG -1C for allowed LRD..
Remarks: A
EnemyPro6lbyEnemySoft User Number: 6712 RunCode: 2011-07-28712:59:38 ID: - Page 4 of 27
i
4
4
PtRFORMANCE CERTIFICATE OF COMPLIANCE (Part 3 of 3) PERF-1 C
Project Name
Trilogy Golf Club-Aerobics & Storage
Date
7/28/2011
ZONE INFORMATION
System Name
Zone Name
Floor Inst.
Area LPD
Occupancy Type s ft. W/sf'
Ctrl Allowed LPD Proc.
Credits Area Tailored Loads
W/Sf 2 W/Sf 3 W/Sf ° W/Sf
HVAC - 1
Aerobics
Exercise, Gymnasium 900 0.920
HVAC -2
Storage
All Others 505 0.535
0.107
Notes: 1. See LTG-1 C 2. See LTG-2C 3. See LTG-3C 4. See LTG-4C
items marked with asterisk, see LTG-1-C by others) (by others
Items above require special documentation
;EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
-The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The local enforcement agency
determines the adequacy of the justifications, and may reject a building or design that otherwise complies based on the adequacy of the
special justification and documentation submitted.
The HVAC System HVAC - 1 incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-4A.
The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Signature or Stamp
Energ Pro 5.1 by Energ Soft User Number: 6712 RunCode: 2011-07-28T12:59:38 ID: Page 5 of 27
C
C
9
ERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C
AND FIELD INSPECTION ENERGY CHECKLIST
Project Name
Trilogy Golf Club -Aerobics & Storage
Date
7/28/2011
Project Address
60800 Trilogy Parkway La Quinta
Climate Zone
15
Total Cond. Floor Area
1,405
Addition Floor Area
n/a
GENERAL INFORMATION
Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Schools (Public School) ❑ Bledlocatable g. Public School m Conditioned Spaces ❑ Unconditioned Spaces
❑ Skylight Area for Large Enclosed Space z 8000 ft2 (If checked include the ENV -4C with submittal)
Phase of Construction: ❑ New Construction ❑ Addition ❑ Alteration
Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit)
Front Orientation: N, E, S, W or in Degrees:
90 deg
FIELD INSPECTION ENERGY CHECKLIST
OPAQUE SURFACE DETAILS
INSULATION
Ta /ID
AssemblyType
y
a`
c3
;a
c N
m W
62
°`o
u
U.
:5v¢
>>
c d
w>
0 of
c
w�i
° m
S>
a
° c
��.
x
'Cc
a
•$a
v
c
L)ra
uyi
a
U.
1
Roof
900
(N)
0.025
R-38
4.2.1-A21
New
❑
❑
2
Wall
460
(NE)
0.178
R-21
4.3.3-A6
New
❑
❑
3
Wall
210
(S)
0.178
R-21
4.3.3-A6
New
❑
❑
4
Wall
146
(NIA
0.178
R-21
4.3.3-A6
New
❑
❑
5
Slab
900
(N)
0.730
None
4.4.7-A1
New
❑
❑
6
Roof
6
(N)
0.025
R-38
4.2.1-A21
New
❑
❑
7
Wall
290
(N)
0.178
R-21
4.3.3-A6
New
❑
❑
8
Wall
145
(E)
0.178
R-21
4.3.3-A6
New
❑
❑
❑
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance.
FENESTRATION SURFACE DETAILS
Tag/ID
Fenestration
Type
A
Q
CC
r
y W
c
O Z
r
K lC
ALL
n
r
t0
4 o
M cn
U
k w
:i' 7
x o
N N
c
d
>
O
g N
C
o
0 cn
y
a
a
1
Window
30
(NE)
0.510
NFRC
0,4601
NFRC
❑
New
❑
❑
2
Window
96
(S)
0.510
NFRC
0.460
NFRC
❑
New
❑
❑
3
Window
26
(NM
0.510
NFRC
0.460
NFRC
❑
New
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
EnergyPro 5.1 by EnergySoft User Number., 6712 Run Code: 2011-07-28712:59:38 ID: Pae 6 of 27
•
•
CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C
AND FIELD INSPECTION ENERGY CHECKLIST
Project Name
Trilogy Golf Club -Aerobics & Storage
Date
1 7/28/2011
Project Address
60800 Trilogy Parkway La Quinta
Climate Zone
15
Total Cond. Floor Area
1,405
Addition Floor Area
n/a
GENERAL INFORMATION
Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Schools (Public School) ❑ RRlellocatable Public School to Conditioned Spaces ❑ Unconditioned Spaces
❑ Skylight Area for Large Enclosed Space z 8000 ft2 (If checked include the ENV -4C with submittal)
Phase of Construction: ❑ New Construction ❑ Addition ❑ Alteration
Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit)
Front Orientation: N, E, S, W or in Degrees:
90 deg
FIELD INSPECTION ENERGY CHECKLIST
OPAQUE SURFACE DETAILS
INSULATION
Ta /ID
Assembly Type
,F •C
Q
Ems:O
N
y If
OZ
U
li
n
.T.' �
'� ;
UM
L
61
W
0
� C
d
W {L
y 7y
Ci
-LL
x
C d
-7Q
�_
C
UN
y
IL
LL
9
Wall
242
(S)
0.178
R-21
4.3.3-A6
New
❑
❑
10
Wall
50
(W)
0.178
R-21
4.3.3-A6
New
❑
❑
11
Slab
505
(N)
0.730
None
4.4.7-A1
New
❑
❑
❑
❑
❑
❑
❑
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance.
FENESTRATION SURFACE DETAILS
Tag/ID
Fenestration
Type
d
a`
C
cN
N W
2
$
x {L
>
c
2
IL
> N
V
x=
x Cn
2 0
y O
m
> >
N
O .�.
Urn
U)
a
.
U.
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
1 ❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
LE3
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2011-07-28712:59:38 /D: Page 7 of 27
1�
0
•
CERTIFICATE OF COMPLIANCE (Part 2 of 3)
AND FIELD INSPECTION ENERGY CHECKLIST
ENV -1 C
Project Name
Trilogy Golf Club -Aerobics & Storage
Date
7/28/2011
ROOFING PRODUCT COOL ROOFS
(Note if the roofing product is not CRRC certified, this compliance approach cannot be used). Go to Overall Envelope Approach or
Performance Approach.
CHECK APPLICABLE BOX BELOW IF EXEMPT FROM THE ROOFING PRODUCT "COOL ROOF" REQUIREMENTS:
Pass
Fail'
N/A
❑ Roofing compliance not required in Climate Zones 1 andl6 with a Low -Sloped. 2:12 pitch or less.
❑
❑
❑
❑ Roofing compliance not required in Climate Zone 1 with a Steep -Sloped with less than 5 Ib/ft2. Greater than 2:12 pitch.
❑
❑
❑
Wood framed roofs in Climate Zones 3 and 5 are exempted, solar reflectance and thermal emittance or
[3SRI
SRI that have a LI -factor of 0.039 or lower. See Opaque Surface Details roof assembly, Column H of ENV -2C.
13
13
[3
❑ Low -sloped Metal building roofs in Climate Zone 3 and 5 are exempted, solar relectance and thermal emittance or SRI
that have a U -factor of 0.048 or lower. See Opaque Surface Details roof assembly below, Column H of ENV -2C.
❑
❑
❑
❑ The roof area covered by building integrated photovoltaic panels and building integrated solar thermal panels are
exempted. Solar reflectance and thermal emittance or SRI, seespreadsheet calculator at www.ener .ca. ov/title24/
❑
❑
❑
13 Roof constructions that have thermal mass over the roof membrane with a weight of at least 25 Ib/ft are exempt from
the Cool Roof criteria below.
❑
❑
❑
❑ High-rise residential buildings and hotels and motels with low -sloped roofs in Climate Zones 1 through 9, 12 and 16 are
exempted from the low -sloped roofing criteria.
❑
❑
❑
1. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
CRRC Product ID
Number'
Roof Slope
s 2:12 > 2:12
Product Weight
< 51b/ft2 a 51b/ft2
Product
Type 2
Aged Solar
Reflectance
Thermal
Emmitance
SR 15
Pass
Fail6
❑ ❑
❑ ❑
❑ 4
❑
❑
❑ ❑
❑ ❑
❑ 4
❑
❑
❑ ❑
❑ ❑
❑ 4
❑
❑
❑ ❑
❑ ❑
❑° 1❑
❑
❑ ❑
❑ ❑
❑ °
❑
❑
❑ ❑
❑ 1 ❑
❑4
❑
❑
1. The CRRC Product ID Number can be obtained from the Cool Roof Rating Council's Rated Product Directory at
www.coolroofs.org/r)roducts/search.phi)
2. Indicate the type of product is being used for the roof top, i.e. single -ply roof, asphalt roof, metal roof, etc.
3. If the Aged Reflectance is not available in the Cool Roof Rating Council's Rated Product Directory then use the Initial Reflectance value from the
same directory and use the equation (0.2+0.7(p;niva,— 0.2) to obtain a calculated aged value. Where p is the Initial Solar Reflectance from the Cool
Roof Rating Council's Rated Product Directory.
4. Check box if the Aged Reflectance is a calculated value using the equation above.
5. The SRI value needs to be calculated from a spreadsheet calculator at htto://www.energv.ca.00v/title24/
6. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
To apply Liquid Field Applied Coatings, the coating must be applied across the entire roof surface and meet the dry mil thickness or coverage
recommended by the coatings manufacturer and meet minimum performance requirements listed in §118(i)4. Select the applicable coating:
❑ Aluminum -Pigmented Asphalt Roof Coating
❑ Cement -Based Roof Coating
❑ Other
Discrepancies:
I
EnemyPro 5.1 by EnemySoft User Number: 6712 Run Code: 2011-07-28T12:59:38 ID:
Page 8 of 27
•
dERTIFICATE OF COMPLIANCE (Part 3 of 3) ENV -1 C
AND FIELD INSPECTION ENERGY CHECKLIST
Project Name
Trilogy Golf Club -Aerobics & Storage
Date
7/28/2011
Required Acceptance Tests
Designer:
This form is to be used by the designer and attached to the plans. Listed below is the acceptance test for Envelope
Fenestrations system. The designer is required to check the acceptance tests and list all the fenestration products that
require an acceptance test. If all the site -built fenestration of a certain type requires a test, list the different fenestration
products and the number of systems. The NA7 Section in the Appendix of the Nonresidential Reference Appendices
Manual describes the test. Since this form will be part of the plans, completion of this section will allow the responsible
party to budget for the scope of work appropriately.
Enforcement Agency:
Systems Acceptance. Before Occupancy Permit is granted for a newly constructed building or space or whenever new
fenestration is installed in the building or space shall be certified as meeting the Acceptance Requirements.
The ENV -2A form is not considered a complete form and is not to be accepted by the enforcement agency unless the
boxes are checked and/or filled and signed. In addition, a Certificate of Acceptance forms shall be submitted to the
enforcement agency that certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of §10-103(b) of Title 24 Part 6. The field inspector must receive the properly filled
out and signed forms before the building can receive final occupancy. A copy of the ENV -2A for each different
fenestration product line must be provided to the owner of the building for their records.
Test Description ENV -2A Test Performed By:
Fenestration Products Name or ID Area of like Building Envelope
Requiring Testing or Verification Products Acceptance Test
Double Metal Tinted 151
13
13
13
13
13
13
13
13
13
13
13
13
13
11
EnemyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2011-07-28T12:59:38 ID: Page 9 of 27
ERTIFICATE OF COMPLIANCE, (Part 1 of 3) LTG -1 C
—77
oject Name
V�n'!
ate
lgy Golf Club -Aerobics & Storage7/28/2011
DOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST
Installation Certificate, LTG -1- INST (Retain a copy and verify form is completed and signed.)' 4
Field -Inspector ❑
r
ERTIFICATE OF COMPLIANCE, (Part 1 of 3) LTG -1 C
—77
oject Name
V�n'!
ate
lgy Golf Club -Aerobics & Storage7/28/2011
DOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST
Installation Certificate, LTG -1- INST (Retain a copy and verify form is completed and signed.)' 4
Field -Inspector ❑
Certificate of Acceptance, LTG -2A and LTG -3A (Retain a copy and verify form is completed and signed.)
Field Inspector ❑ -
A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces Installed Lighting Power listed on
this Lighting Schedule is only for:
0 CONDITIONED SPACE ❑ UNCONDITIONED SPACE
The actual indoor lighting power listed below includes all installed permanent and portable lighting systems in accordance
®
with §146(a).
Only for offices: Up to the first 0.2 watts per square foot of portable lighting shall not be required to be included in the
0 calculation of actual indoor lighting power density in accordance with the Exception to §146(a). All portable lighting in excess of
0.2 watts per square foot is totaled below.
Luminaire (Type, Lamps, Ballasts
Installed Watts -
A
f B
C
D
E
F
G
H
_ .
How wattage"
r Field
Was determined
klns °ector.
None
r
N ,_
a m
CEC
C O.
:O r�
N
;, .c.
� o
�
or
Complete Luminaire Description'
E
E
Default •
m
a N � �w
Item
'. • (i.e, 3 lamp fluorescent troffer,'
J
From
NAS
o • o r
Q ~
> >
Z
c
`� ku
Ta
F32T8, one dimmable electronic ballasts
(2) 13W
(2) 13w Compact Fluorescent
36.0
0
❑
231
828
❑ D>
(2) 2X4
(2) 4 ft Fluorescent T8
54.0
®
❑
5
270
❑ ; A ❑
❑
❑❑>a
❑
❑
x El d❑,a
'
❑
❑
❑ ;❑ ".
❑
❑
❑
❑❑
❑ d
❑
❑
`❑ ffiR ❑ ;,;g;
El
❑p❑�,
'
❑
❑
f❑,'.
{y❑
Installed Watts Page Total:
1,098
<.
Installed Watts Building Total
Building total number of pages:
{
Sum of all a es
r<
Enter LTG -1C Page 4 of 4
1.098
1. Wattage shall be determined according to Section 130 (d and e). Wattage shall be rating of light fixture, not rating of bulb.`
2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2011-07-28712:59:38 ID: Pae 10 of 27
�• Y
t,
CERTIFICATE OF COMPLIANCE (Part 2 of 3)
LTG.1 C
Project Name
Date .
Trilogy Golf Club -Aerobics & Storage
7/28/2011
INDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST
Fill in controls for all spaces: a) area controls, b) multi-level controls, c) manual daylighting controls for daylit areas > 250 ft2,
automatic daylighting controls for daylit areas > 2,500 ft2, d) shut-off controls, e) display lighting controls, f) tailored lighting controls —
general lighting controlled separately from display, ornamental and display case lighting and g) demand responsive automatic
controls for.retail stores > 50,000 ft2, in accordance with Section 131.
ld
MANDATORY -LIGHTING CONTROLS — FIELD INSPECTION ENERGY CHECKLIST In`s
ecto`r`
Number Special
Type/ Description of Units Location in Building Features PasseFait
❑. g❑R
❑
„ ❑ ❑p
❑ ❑ ❑`'^.
❑ ❑: ❑;.
❑ El EQ
❑ ae ❑ �"` a Dr;.'.:
' ❑ "�uD x? ❑t
r ❑a'D,
A ❑
•st �: i ❑aaE`...
D �,❑. ❑ '
t
' ❑
k C ❑ �'x [ ❑?t`',�
r
❑
❑,.aD' s
SPECIAL FEATURES INSPECTION CHECKLIST See Page 2 of 4 of LTG -1C
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification. The local enforcement agency determines the adequacy of the
justification,
and may reject a building or design that otherwise. complies based on the adequacy of the special justification and documentation
submitted.
Field Inspector's Notes or Discrepancies:
EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2011-07-28712:59:38 ID:
Pae 11 of 27
1
• a M
1
1�
ERTIFICATE OF COMPLIANCE Part 3 of 3 LTG -1 C
Project Name
Date
Trilogy Golf Club -Aerobics & Storage 1
7/28/2011
CONDITIONED AND UNCONDITIONED SPACE LIGHTING MUST
NOT BE COMBINED FOR COMPLIANCE
Indoor Lighting Power for Conditioned S aces
Indoor Lighting Power for Unconditioned Spaces
Watts
Watts
Installed Lighting
1,098
Installed Lighting
0
from Conditioned LTG -1C, Page 2
from Unconditioned LTG -1C, Page 2
Lighting Control Credit _
54
Lighting Control Credit _
0
Conditioned Spaces from LTG -2C
Unconditioned Spaces from LTG -2C
Adjusted Installed
1044
Adjusted Installed =
0
Lighting Power
Lighting Power
Complies if Installed:5 Allowed
Complies if Installed:5 Allowed
Allowed Lighting Power
1'044
Allowed Lighting Power
Conditioned Spaces from LTG -3C or PERF -1
Unconditioned Spaces from LTG -3C)0
Required Acceptance Tests
Designer:
This form is to be used by the designer and attached to the plans. Listed below is the acceptance test for the Lighting system,
LTG -2A and LTG -3A. The designer is required to check the acceptance tests and list all control devices serving the building or space
shall be certified as meeting the Acceptance Requirements for Code Compliance. If all the lighting system or control of a certain type
requires a test, list the different lighting and the number of systems. The NA7 Section in the Appendix of the Nonresidential
Reference Appendices Manual describes the test. Since this form will be part of the plans, completion of this section will allow the
responsible party to budget for the scope of work appropriately. Forms can be grouped by type of Luminaire controlled.
Enforcement Agency:
Systems Acceptance. Before Occupancy Permit is granted for a newly constructed building or space or when ever new lighting
system with controls is installed in the building or space shall be certified as meeting the Acceptance Requirements.
The LTG -2A and LTG -3A forms are not considered complete forms and are not to be accepted by the enforcement agency unless
the boxes are checked and/or filled and signed. In addition, a Certificate of Acceptance forms shall be submitted to the enforcement
agency that certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements
of §10-103(b) of Title 24 Part 6. The field inspector must receive the properly filled out and signed forms before the building can
receive final occupancy. A copy of the LTG -2A and LTG -3A for each different lighting luminaire control(s) must be provided to the
owner of the building for their records.
LTG -2A and
Luminaires Controlled
LTG -3A
Controls and
Sensors and
Number of
Automatic
Luminaires
Daylighting Controls
Equipment Re uirin Testing
Description
controlled
Location
Acceptance
Occ Sensor- Multi -Level
(2) 4 ft Fluorescent T8
5
Storage/Hall
m
❑
❑
EnergyPro 5.1 by EnergySoh User Number., 6712 Run Code: 2011-07-28T12:59:38 ID: Pae 12 of 27
r:
i
ERTIFICATE OF COMPLIANCE and (Part 1 of 4) MECH-1 C
FIELD INSPECTION ENERGY CHECKLIST
Project Name
Trilogy Golf Club -Aerobics & Storage
Date
7/28/2011
Project Address
60800 Trilogy Parkway La Quinta
Climate Zone
15
Total Cond. Floor Area
1,405
Addition Floor Area
n/a
GENERAL INFORMATION
Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Schools (Public School) ❑ Relocatable Public School Bldg. m Conditioned Spaces ❑ Unconditioned Spaces
affidavit
Phase of Construction: ❑ New Construction ❑ Addition ❑ Alteration
Approach of Compliance: ❑ Component ❑ Overall Envelope TDV ❑ Unconditioned (file affidavit)
Energy
Front Orientation: N, E, S, W or in Degrees:
90 deg
HVAC SYSTEM DETAILS
FIELD INSPECTION ENERGY CHECKLIST
E ui ment2
Inspection Criteria
Meets Criteria
or Requirements
Pass
Fail — Describe Reason
Item or System Tags
i.e. AC -1, RTU -1, HP -1
HVAC - 1
❑
❑
Equipment T e3:
Split DX
❑
❑
Number of Systems
1
❑
❑
Max Allowed Heating Capacity'
57,500 Btu/hr
❑
❑
Minimum Heating Efficiency'
7.70 HSPF
❑
❑
Max Allowed Cooling Capacity'
59,000 Btu/hr
❑
❑
Cooling Efficiency'
13.5 SEER / 11.2 EER
❑
❑
Duct Location/ R -Value
Attic, Ceiling Ins, vented/ 8.0
❑
❑
When duct testing is required, submit
MECH-4A & MECH-4-HERS
Yes
❑
❑
Economizer
No Economizer
❑
❑
Thermostat
Setback Required
❑
❑
Fan Control
Constant Volume
❑
❑
E ui ment2
Inspection Criteria
FIELD INSPECTION ENERGY CHECKLIST
Pass
Fail — Describe Reason
Item or System Tags
i.e. AC -1, RTU -1, HP -1
HVAC -2
❑
❑
Equipment T e3:
Split DX
❑
❑
Number of Systems
1
❑
❑
Max Allowed Heating Capacity'
21,600 Btu/hr
❑
❑
Minimum Hea . ting Efficiency'
10.00 HSPF
❑
❑
Max Allowed Coolinq Capacity'
18,000 Btu/hr
❑
❑
Cooling Efficiency'
19.0 SEER / 14.0 EER
❑
❑
Duct Location/ R -Value
n/a
❑
❑
When duct testing is required, submit
MECH-4A & MECH-4-HERS
No
❑
❑
Economizer
No Economizer
❑
❑
Thermostat
Setback Required
❑
❑
Fan Control
Constant Volume
❑
❑
1. If the Actual installed equipment performance efficiency and capacity is less than the Proposed (from the energy compliance submittal or from
the building plans) the responsible party shall resubmit energy compliance to include the new changes.
2. For additional detailed discrepancy use Page 2 of the Inspection Checklist Form. Compliance fails if a Fail box is checked.
3. Indicate Equipment Type: Gas (Pkg or, Split), VAV, HP (Pkg or split), Hydronic, PTAC, or other.
JEnergyPro5.1byEnergySoft User Number: 6712 Run Code: 2011-07-28712:59:38 ID: Pae 13 of 27
CJ
CERTIFICATE OF COMPLIANCE and FIELD INSPECTION ENERGY CHECKLIST (Part 3 of 4) MECH-1 C
Project Name
Date
Trilogy Golf Club -Aerobics & Storage
7/28/2011
Required Acceptance Tests
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the applicable
boxes by all acceptance tests that apply and listed all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and
the number of systems. The NA number designates the Section in the Appendix of the Nonresidential Reference Appendices Manual that describes the test. Since this form will be
part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately.
Building Departments:
Systems Acceptance: Before occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated for
normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
Systems Acceptance: Before occupancy permit is granted. All newly installed HVAC equipment must be tested using the Acceptance Requirements.
The MECH-1 C form is not considered a completed form and is not to be accepted by the building department unless the correct boxes are checked. The equipment requiring testing,
person performing the test (Example: HVAC installer, TAB contractor, controls contractor, PE in charge of project) and what Acceptance test must be conducted. The following $!
checked -off forms are required for ALL newly installed equipment. In addition a Certificate of Acceptance forms shall be submitted to the building department that certifies plans,
specifications, installation, certificates, and operating and maintenance information meet the requirements of §10-103(b) and Title -24 Part 6. The building inspector must receive the
properly filled out and signed forms before the building can receive final occupancy.
TEST DESCRIPTION
MECH-2A
MECH-3A
MECH-4A
MECH-5A
MECH-6A
MECH-7A
MECH-8A
MECH-9A
MECH-10A
MECH-11A
Hydronic
Outdoor
Constant
Demand
Supply
System
Automatic
Ventilation
Volume &
Air
Control
Supply
Valve
Water
Variable
Demand
For
Single -Zone
Distribution
Economizer
Ventilation
Fan
Leakage
Temp.
Flow
Shed
Equipment Re uirin Testing or Verification QtY.
VAV & CAV
Unitary
Ducts
Controls
DCV
VAV
Test
Reset
Control
Control
Carrier 25HBC360/FX4BNC060 1
❑
®
m
❑
❑
❑
❑
❑
❑
❑
Fujitsu 18RLQ 1
❑
®
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑ .
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑-
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
EnergyPro 5.1 by EnergrySoft User Number. 6712 Run
Code: 2011-07-28T12:59:38
ID: Pae 15 of 27
0 •
CERTIFICATE OF COMPLIANCE and FIELD INSPECTION ENERGY CHECKLIST
(Part 4 of 4) MECH-1 C
Project Name
Trilogy Golf Club -Aerobics & Storage
Date
7/28/2011
TEST DESCRIPTION MECH-12A
MECH-13A
MECH-14A
MECH-15A
Fault
Detection &
Diagnostics
Equipment Re uirin Testing Qty.for DX Units
Automatic Fault
Detection &
Diagnostics for
Air & Zone
Distributed
Energy Storage
DX AC
Systems
Thermal Energy
Storage (TES)
S stems
Test Performed By:
Carrier 25HBC360/FX4BNC060 1 ❑
❑
❑
❑
Fujitsu 18RLQ 1 ❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
EnergyPro 5. 1 by Ene Soft User Number. 6712
RunCode: 2011-07-28T12:59:38 ID:
Pae 16 of 27
0
L' IGHTING CONTROLS CREDIT WORKSHEET Part 1 of 2) LTG -2C
Project Name
Trilogy Golf Club -Aerobics & Storage
Date
1 7/28/2011
POWER ADJUSTMENT FACTORS PAF FOR NON -DAYLIGHT CONTROLS
A Separate PAF Worksheet Must Be Filled Out for Conditioned and Unconditioned Spaces. Control Credits listed on this
schedule are only for:
m CONDITIONED SPACES ❑ UNCONDITIONED SPACES
A B C D E F
G
Watts of Power
Room # Zone ID Plan Room Area Control Adjustments
Areas Lighting Control Description' Reference(ft) Lighting Factor
Control
Credit Watts
E x F
Storage/Hall Occ Sensor - Multi -Level (2) 2X4 505 270 0.20
54
PAGE TOTAL
54
Note:
Building total of non -daylight control credit watts for all pages of LTG -2C Pa e 1 of 2
Conditioned and
Enter building total of all daylight controls credit watts from LTG -2C Page 2 of 2
0
Unconditioned
Space shall be
separately
totaled
BUILDING TOTAL OF ALL CONTROL CREDIT WATTS
(FOR BOTH NON -DAYLIGHT AND DAYLIGHT CONTROL CREDITS)
Enter in LTG -1C; Page 4: Lighting Control Credit as appropriate for CONDITIONED
or UNCONDITIONED Spaces
54
1. Description shall be consistent with Type of Control defined in Table 146-C
2. Power Adjustment Factor taken from Table 146-C
EnergyPro5.1byEnergySoft User Number., 6712 RunCode: 2011-07-28712:59:38 ID: Pae 17 of 27
•
•
IR SYSTEM REQUIREMENTS
Project Name
Trilogy Golf Club -Aerobics & Storage
Indicate Air Systems T
Item or System Tags h F
i.e. AC -1, RTU -1, HP -1 HVAC- 1.
Number of Systems 1
MANDATORY MEASURES
Heating Equipment Efficiency
Cooling Equipment Efficiency
HVAC Heat Pump Thermostat
Furnace Controls/Thermostat
Natural Ventilation
Mechanical Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Location/ R -value
Indicate P
T-24 Sections
112 a
112 a
112(b), 112(c)
112(c), 115 a
121 b
121 b
121 c
121 c
122(e)
122(e)
122(f)
122
123
124
PRESCRIPTIVE MEASURES
Calculated Design Heating Load
Proposed Heating Capacity
Calculated Design Cooling Load
Proposed Cooling Capacity .
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heat Air Supply Reset
Cool Air Supply Reset
Electric Resistance Heating'
Air Cooled Chiller Limitation
Duct Leakage Sealing. If Yes, a
MECH-4-A must be submitted
144(a &
144(a &
144(a &
144(a &
144(c)
144(c)
144(c)
144(d)
144(e)
144(f)
144(f)
144
144(i)
144(k)
Reference on PI
7.70 HSPF
13.5 SEER/ 11.2 EER
Yes
n/a
Yes
208 cfm
No
No
Programmable Switch
Setback Required
Auto
n/a
Attic, Ceiling Ins, vented /8.0
n/a
35,913 Btu/hr
n/a
45,249 Btu/hr
Constant Volume
Yes
No
No Economizer
Constant Temp
Constant Temp
Yes
Part 1 of 2
Single Zone, Packac
HVAC -2
1
lule and indicate the
10.00 HSPF
19.0 SEER / 14.0 EER
Yes
n/a
Yes
76 cfm
No
No
Programmable Switch
Setback Required
Auto
n/a
n/a
n/a
13,491 Btu/hr
n/a
15,924 Btu/hr
Constant Volume
Yes
No
No Economizer
Constant Temp
Constant Temp
No
► MECH-2C
Date
7/28/2011
VAV. or etc...)
01, Total installed capacity (MBtu/hr) of all electric heat on this project exclusive of electric auxiliary heat for heat pumps. If electric heat is used
explain which exception(s) to §144(g) apply.
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2011-07-28712:59:38 /D: Pae 18 of 27
MECHANICAL VENTILATION AND REHEAT MECH-3C
Project Name
Trilogy Golf Club -Aerobics & Storage
Date
7/28/2011
MECHANICAL VENTILATION §121 b 2
REHEAT LIMITATION (§144(d))
AREA BASIS
OCCUPANCY BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
Zone/System
Condition
Area
(ft2)
CFM
per
ftz
Min CFM
By Area
B X C
Number
Of
People
CFM
per
Person
Min CFM
by
Occupant
E X F
REQ'D
V.A.
Max of
D or G
Design
Ventilation
Air
CFM
50% of
Design Zone
Supply
CFM
B X 0.4
CFM / ftz
Max. of
Columns
H, J, K,
300 CFM
Design
Minimum
Air
Setpoint
Transfer
Air
Aerobics
900
0.15
135
13
208
HVAC - 1
Total
135
208
Storage
505
0.15
76
76
76
HVAC -2
Total
76
76
Totals Column I Total Design Ventilation Air
C Minimum ventilation rate per Section 121, Table 121-A.
E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seating.
H Required Ventilation Air REQ'D V.A. is the larger of the ventilation rates calculated on an AREA BASIS or OCCUPANCY BASIS Column D or G).
I Must be greater than orequal to H, or use Transfer Air column N to make up the difference.
J Design fan supply CFM Fan CFM x 50%; or the design zone outdoor airflow rate per 121.
K Condition area(ft) x 0.4 CFM / ft2; or
L Maximum of Columns H, J, K, or 300 CFM
M This must be less than orequal to Column L and greater than orequal to the sum of Columns H plus N.
N Transfer Air must be provided where the Required Ventilation Air (Column H) is greater than the Design Minimum Air (Column M). Where required, transfer air must be greater than or
equal to the difference between the Required Ventilation Air Column H and the Design Minimum Air Column M), Column H minus M.
EnergyPro 5. 1 by EnergySoft User Number. 6712 Run Code: 2011-07-28T12:59:38 ID: Pae 19 of 27
• ! i
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-5C
Project Name
Trilogy Golf Club -Aerobics & Storage
Date
7/28/2011
CHILLER AND TOWER SUMMARY
PUMPS
Equipment Name Type
Qty. Efficiency
Pump
Tons Ot . GPM BHP Control
DHW / BOILER SUMMARY
System Name Type
Distribution Qty. Rated Input
Vol. Energy Factor Standby Loss Tank Ext.
(Gals). or RE or Pilot R -Value Status
MULTI -FAMILY CENTRAL WATER HEATING DETAILS
Hot Water Pump
Hot Water Piping Length(ft)
Control Ot HP
Type
In Plenum Outside Buried Add 1/2" Insulation
CENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name Type
aty. Output Aux. kW
Eff iciency Output Eff iciency Status
Carrier25HBC360/FX4BNC060 . Split DX
1 57,500 0.0
7.70 HSPF 59,000 13.5 SEER/ 11.2 EER New
Fujitsu 18RLQ Split DX
1 21,600 0.0
10.00 HSPF 18,000 19.0 SEER/ 14.0 EER New
CENTRAL SYSTEM FAN SUMMARY
SUPPLY FAN RETURN FAN
System Name Fan Type
Economizer Type
CFM BHP CFM BHP
Carrier 25HBC360/1-X4BNC060 Constant Volume
No Economizer
2,000 1.00 none
Fujitsu 18RLQ Constant Volume
No Economizer
412 0.12 none
EnerqyPro5l by EnemySoft User Number. 6712
RunCode: 2011-07-28712:59:38 ID: Page 20 of 27
C
•
NVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV -MM
Project Name
Date
Trilogy Golf Club -Aerobics & Storage
7/26/2011
DESCRIPTION
Building Envelope Measures: -
§118(a): Installed insulating material shall have been certified by the manufacturer to comply with the California Quality
Standards for insulating material, Title 20 Chapter 4, Article 3.
§118(c): All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of
Sections 2602 and 707 of Title 24, Part 2.
§118(f): The opaque portion's of framed demising walls in nonresidential buildings shall have insulation with an installed R -value
of no less than R-13 between framing members.
All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed,
§117(a):
weatherstripped or otherwise sealed.
Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.2 of
§116(a) 1: window area, 0.3 cfm/ft.2 of door area for residential doors, 0.3 cfm/ft.2 of door area for nonresidential single doors
(swingingand sliding), and 1.0 cfm/ft.2 for nonresidential double doors (swinging).
§116(a) 2: Fenestration U -factor shall be rated in accordance with NFRC 100, or the applicable default U -factor.
Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the
§116(a) 3:
applicable default SHGC.
Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be
§116(b):
weatherstripped (except for unframed glass doors and fire doors).
EnergyPro 5.1 by EnemySoft User Number., 6712 RunCode: 2011-07-28712:59:38 ID: Page 21 of 27
l I1
C
•
LIGHTING MANDATORY MEASURES: NONRESIDENTIAL LTG -MM
Project Name
Date
Trilogy Golf Club -Aerobics & Storage
7/28/2011
Indoor Lighting
Measures:
§131(d): Shut-off Controls
For every floor, all interior lighting systems shall be equipped with a separate automatic control to shut off the lighting.
1.
This automatic control shall meet the requirements of Section 119 and may be an occupancy sensor, automatic time
switch, or other device capable of automatically shutting off the lighting.
2
Override for Building Lighting Shut-off: The automatic building shut-off system is provided with a manual, accessible
override switch in sight of the lights. The area of override is not to exceed 5,000 square feet.
§119(h):
Automatic Control Devices Certified: All automatic control devices specified are certified, all alternate equipment shall
be certified and installed as directed by the manufacturer.
§111:
Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for the project are certified and listed in the
Directory. All installed fixtures shall be certified.
§131(a):
Individual Room/Area Controls: Each room and area in this building is equipped with a separate switch'or occupancy
sensor device for each area with floor -to -ceiling walls.
Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 square feet and more than 0.8 watts
§131(b):
per square foot of lighting load shall be controlled with bi-level switching for uniform reduction of lighting within the
room.
Daylight Area Control: All rooms with windows and skylights that are greater than 250 square feet and that allow for
the effective use of daylight in the area shall have 50% of the lamps in each daylit area controlled by a separate switch;
§131(c):
or the effective use of daylight cannot be accomplished because the windows are continuously shaded by a building on
the ad'acent lot. Diagram of shading during different times of the year is included on plans.
§131(c):
Display Lighting. Display lighting shall be separately switched on circuits that are 20 amps or less.6.
Outdoor Lighting Measures:
§130(c)1:
Mandatory lighting power determination for medium base sockets without permanently installed ballasts
All permanently installed luminaires with lamps rated over 100 Watts either have a lamp efficacy of at least 60 lumens
§132(a):
per Watt or are controlled by a motion sensor.
All Luminaires with lamps rated greater than 175 Watts in hardscape area, including parking lots, building entrances,
§132(b):
canopies, and all outdoor sales areas meet the Cutoff Requirements. .
§132(c)1:
All permanently installed outdoor lighting meets the control requirements listed.
Building facades, parking lots, garages, canopies, and outdoor sales areas meet the Multi -Level Lighting Requirements
c
§1 32 O'
listed.
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2011-07-28712:59:38 ID: Page, 22 of 27
t
•
1�
MECHANICAL MANDATORY MEASURES: NONRESIDENTIAL MECH-MM
Project Name
Date
Trilogy Golf Club -Aerobics & Storage
7/28/2011
Equipment and System Efficiencies
§111:
Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply
with the applicable standard.
§115(a):
Fan type central furnaces shall not have a pilot light.
§123:
Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC
equipment, shall be insulated in accordance with Standards Section 123.
§124:
Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of
the CMC Standards.
Controls
§122(e):
Each space conditioning system shall be installed with one of the following:
1A.
Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not
explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an
accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch
shall be capable of programming different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or
1 B.
An occupancy sensor to control the operating period of the system; or
1 C.
A 4 -hour timer that can be manually operated to control the operating period of the system.
Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the
2
system as required to maintain a setback heating and/or a setup cooling thermostat setpoint.
Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000
square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided
§122(g).
with isolation devices, such as valves or dampers that allow the supply of heating or cooling to be setback or shut off
independently of other isolation areas; and shall be controlled by a time control device as described above.
Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to
§122(c):
authorized personnel.
Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the
§122(b):
heating load can be met by the heat pump alone
Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the
zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the
§122(a&b):
control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be
capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
Ventilation
Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified
§121(e):
on these plans.
All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all
22 f
§1 ()'
openings to the outside, except for combustion air openings.
Ventilation System Acceptance. Before an occupancy permit is granted for a newly constructed building or space, or a
§121(f):
new ventilating system serving a building or space is operated for normal use, all ventilation systems serving the
building ors ace shall be certified as meeting the Acceptance Requirements for Code Compliance
Service Water Heating Systems
§113(c)
Installation
3.
Temperature controls for public lavatories. The controls shall limit the outlet Temperature to 110° F.
Circulating service water -heating systems shall have a control capable of automatically turning off the circulating pump
2
when hot water is not required.
l
EnergyPro 5.1 by EnergySoft User Number 6712 Run Code: 2011-07-28712:59:38 ID: Page 23 of 27
4
4
VAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Date
rilogy Golf Club -Aerobics & Storage
7/28/2011
System Name
Floor Area
HVAC - 1
900
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING
CFM Sensible
Total Room Loads 1,198 19,186
Return Vented Lighting 0
Return Air Ducts 1,439
Return Fan 0
Ventilation 208 7,366
Supply Fan 2,978
Supply Air Ducts 1,439
PEAK COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output perSystem 57,500
4,154 922
12,620
Total Output Btuh 57,500
Output Btuh/s ft 63.9
946
Cooling System
0
Output perSystem 59,000
1,808 208
9,627
Total Output Btuh 59,000
-2,978
Total Output Tons 4.9
946
Total Output Btuh/s ft
65.6
TOTAL SYSTEM LOAD 32,407
5,961
Total Output s ft/Ton 183.1
21,162
Air System
CFM perSystem
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 25HBC360/FX4BNC060 45,249
9,513
35,913
Airflow cfm/s ft
2.22
Total Adjusted System Output 45,249
(Adjusted for Peak Design conditions)
9,513 35,913
Airflow cfm/Ton 406.8
Outside Air % 10.4%
0.23
Outside Air cfm/s ft
TIME OF SYSTEM PEAK
Aug 3 PM Jan 1 AM
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
65 OF 82 OF 83 OF
PAR- 10
i C�) •`Y
Outside Air
208 cfm
Heating Coil Supply Fan
83 OF
2,000 cfm
Roos .
70 OF
70 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
82/68°F 61/60°F 62/60°F
Outside Air Ar
Supply Fan
63 / 60 OF
208 cfm
Cooling Coil
_......
2,000 cfm........................._..._....
53.8% I ROOM
78/66°F
79/66°F
t
EnergyPro 5.1 by EnergySoR
User Number: 6712 Run Code: 2011-07-28712:59:38 ID:
Page 24 of 27
i
4
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
rilogy Golf Club -Aerobics & Storage
Date
7/28/2011
System Name
HVAC -2
Floor Area
505
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 364
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 76
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK
Sensible
10,385
0
779
0
2,598
0
779
14,540
COIL HTG.
Latent CFM
1,515 463
1,9941 76
3,509
PEAK
Heating System
Sensible
Output perSystem 21,600
9,697
Total Output Btuh 21,600
Output Btuh/s ft 42.8
727
Cooling System
0
Output perSystem 18,000
3,413
Total Output Btuh 18,000
0
Total Output Tons 1.5
727
Total Output Btuh/s ft 35.6
Total Output s ft/Ton 336.7
14,565
Air System
CFM perSystem
412
HVAC EOUIPMENT SELECTION
Airflow cfm
412
Fujitsu 18RLQ
15,924
0
13,491
Airflow cfm/s ft
0.82
13,491
F Jan 1 AM
Airflow cfm/Ton 274.7
Outside Air % 18.4%
Total Adjusted System Output 15,924
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
0
Aug 3P ml
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
jAirstream Temperatures at Time of Heating
Peak
26 OF 61 OF
Outside Air
76 cfm Supply Fan
412 cfm:
68 OF
61 OF 91 OF
Heating Coil
90 OF
:..:.
ROOM
70 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112 / 78 OF 86165 OF 86 / 65 OF 49 / 48 OF
Outside Air
76 cfm Supply Fan Cooling Coil
412 cfm
80/61 OF
51 / 49 OF
36.2% �. ROOM
flow
78/61 OF
EnergyPro 5.1 by EnergySoft
User Number: 6712 Run Code: 2011-07-28T12:59:38
ID:
Page 25 of 27
ZONE •A, SUMMARY
• .
Trilogy Goff Club -Aerobics & Storage
Date
to
712812011
System Name
HVAC- 1
•0i
ZONE LOAD
COOLINGFIRM
.. ..26.
a
ZONE LOAD SUMMARY
Project Name
Qoff Club -Aerobics & Storage
Date
712812011
System Name
HVAC -2
FloorTrilogy -.
505
ZONE LOAD SUMMARY
COOLING PEAK
.LOAD)
.•. ..,,