0207-175 (SFD)LICENSED CONTRACTOR DECLARATION
I hereby affirm under penalty of perjury thai l'am licensed under provisions of
Chapter 9 (commencing with Section 7000) of Division 3 of the Business and
Professionals Code, and my License is in full force and effect.
License # Lic. Class Exp. Date
XIA 2,128/04
/Date°% _ 4- Signature of Contractor { �'• �'
OWNER -BUILDER DECLARATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's
License Law for the following reason:
( ) I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for
sale (Sec. 7044, Business & Professionals Code).
( ) I, as owner of the property, am exclusively contracting with licensed
#
contractors to construct the project (Sec. 7044, Business &,Professionals"
Code). 1.
,( ) I am exempt under Section B&P.C. for this reason
Date Signature of Owner
WORKER'S COMPENSATION DECLARATION.
/
I hereby affirm under penalty of perjury one of the following declarations:
() I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided for by Section 3700 of the Labor Code, for the
performance of the work for which this permit is issued.
( ) I have and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which this
permit is issued. My workers' compensation insurance carrier & policy no. are:
Cartier EYa'e1" PT Policy No.
(This section need not be completed if the permit valuation is for $100.00 or less).
( ) I certify that in the performance of the work for which this permit is issued,
I shall not employ any person in any manner so as to become subject to the
workers' compensation laws of California, and agree that if I should become
subject to the workers' compensation provisiops of Section 3700 of the Labor
Code, I,shall forthwith comply with t ose provisions.
Date:&' 7/ -- 0 2.• Applicant �-r,�i I /
i %�.� _�—
Warning: Failure to secure Workers' Compensation coverage is unlawful and
shall subject an employer to criminal penalties and civil fines up to $100,000, in
addition to the cost of compensation, damages as provided for in Section 3706
of the Labor Code, interest and attorney's fees.
A
IMPORTANT Application is hereby made to the Director of Building and Safety
for a permit subject to the conditions and restrictions set -forth on his
application.
1. Each person upon whose behalf thit application is made &'each person at
whose request and for whose benefit work is performed under or pu rsu nt to
any permit issued as a result of this applicaton agrees to, & shall, In{ n'fy _.
& hold harmless the City of La Quinta, its officers, agents and empl , es.
2. Any permit issued as a result of this application becomes null anay of if k.
work is not commenced within 180 days from date of issuance o su h
permit, or cessation of work for 180 days will subject permit to cancel atio .
I certify that I have read this application and state that the above informion is
correct. I agree to comply with all City, and State laws relating -to the b 'Idinn
construction, and hereby author) g -representatives of this City; to.e'nter upon
the above-mentioned property/foinspecilon purposes.
Si. n •
g„,lure (Owner/Agent)'•
_BUILDING PERMIT PERMIT#
DATE VALUATIONt7'S LOT
TRACT
;raC�� yrs
JOB SITE ADDRESS iE -5T5 AVVM,1 , �Tt�TLFt10 .
OWNER CONTRACTOR/DESIGNER/ENGINEER
IvM & k,ARB BUIVMAS if. - )109 F11.1:1: ERS
8.2-137 ti1qMkA�, PO.G•'OX 11335
INI3I0 CA 92201 P A111i 3yM1 1R- * CA, 92255
(760,W5-76571 CKA 4360
USE OF PERMIT :
9Ti+YC�F,� :�.A,2vI[I..�#' 33�F�..i?�iCY •
2312 S.F. uta. PARS IT TOE SNOT IINCLUDL BLOCK W,d LLWPOOL OR
13RIV'i' MVA Y APP ROACH
H
TRACT CONSTRUCTION OF
PORCWPATIC 137.0039
111ARACIWC•Ai"PORT 320.00 SP
"01IM73D COST OF C'QN�r"`MUarA01V
iPI U.r FEE alib lfIz9 'y
CONS'sRUCTIONFRRE
101.•ON0418-M,
PLAN CHECK FE,
101-000-439-318
FEE DEPOSIT
301.000.439-318
M.EC tANICAL FrE
101-000-421-.000
t10.tY0
1<UC:TIUCA1.: F9F.
101.000-420-000
$139.a2
PLUMB1140 =
101.000 i 419_000
$128.'7,
IVRONO MOT.1ON RES)ID
101 *000-X42.000
S13.76
•t RA.N:) NG 1iF,X
201-000-423--000
$15.60
IDEVF.:1,.OPI R IMPACT V99
'S,405.00
PRECISE PLAN
101.000-441-:145
$100.00
44
C01,3a`�.h17C3'1MT AND PLAN CtMr-'K,
LESV PIZ$-PA1D T -'V-.9
VTa-VAL Illy–NMT YET.S.VUE WOW
0 �`a111NTA �
iY 0Epq. �..
FINANCE
RECEIPT DATE BY DAT F AL D
INSPECTOR
J
44,:30o.81
425910
INSPECTION RECORD
OPERATION
DATE
INSPECTOR
OPERATION
DATE
INSPECTOR
BUILDING
APPROVALS
MECHANICAL APPROVALS
Set Backs
Underground Ducts
Forms & Footings
Ducts
Slab Grade
Return Air
Steel
Combustion Air
Roof Deck
Q- - G
Exhaust Fans
O.K. to Wrap
F.A.U.
Framing
tz4
Compressor
Insulation
-
Vents
Fireplace P.L.
Grills
Fireplace T.O.
Fans & Controls
Party Wall Insulation
Condensate Lines
Party Wall Firewall
Exterior Lath
Drywall - Int. Lath��.�'
Final
Final _ O
BLOCKWALL P ROVALS
POOLS - SPAS
Steel
Set Backs
Electric Bond
Footings
Main Drain
Bond Beam
Approval to Cover
Equipment Location
Underground Electric
Underground Plbg. Test
Final
Gas Piping
PLUMBING APPROVALS
Gas Test
Electric Final
Waste Lines_
O _
Heater Final
Water Piping
Plumbing Final
Plumbing Top Out
Equipment Enclosure
Shower Pans
O.K. for Finish Plaster
Sewer Lateral
Pool Cover
Sewer Connection
_
_ /Q —G_
Encapsulation
Gas Piping
Gas Test
=�� �-
Appliances
Final
Final
Utility Notice (Gas)
ELECTRICAL APPROVALS
Temp. Power Pole
Underground Conduit
Rough Wiring
Low Voltage Wiring
Fixtures
Main Service
Sub Panels
Exterior Receptacles
G.F.I.
Smoke Detectors
Temp. Use of Power 6
Final J/
Utility Notice (Perm)
COMMENTS:
a~--
bao-7 - C75 Of / 4P (049WAIJ
uL %�/�Q P.O. BOX 1504 APPLICATION ONLY
Building�'n, , 78-495 CALLE TAMPICO
Address 79-& 7 %�j ` Aa i'
F<-l/Y"f� L/ LA QUINTA, CALIFORNIA 92253
Mailing it ,^
Address ( � /�•CJL>
Cit . C�
Zip
Mel / -0
ity lZip
State Lic.I City
& Classif. YXg i 1�� Lic. #
Arch., Engr., [�
Designer
Address Tel.
CityI Zip I State
#
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm that I am licensed under provisions of Chapter 9 (commencing with Section
7000) of Division 3 of the Business and Professions Code, and my license Is In full force and
effect.
SIGNATURE DATE
OWNER -BUILDER DECLARATION
I hereby affirm that I am exempt from the Contractors License Law for the following
reason: (Sec. 7031.5,Business and Professions Code: Any city or county which requires a
permit to construct, alter, improve, demolish, or repair any structure, prior to'Its issuance also
requires the applicant for such permit to file a signed statement that he is licensed pursuant to
the provisions of rhe Contractor's License Law, Chapter 9 (commencing with Section 7000) of
Division 3 of the Business and Professions Code, or that. he is exempt therefrom, and the basis
for rhe alleged exemption. Any violation of Section 7031.5 by 'any applicant for a permit
subjects the applicant to a civil penalty of not more than five hundred dollars ($500).
I: I, as owner of the property, or my employees with wages as their sole compensation, will
do the work, and the structure is not intended or offered for sale. (Sec. 7044, Buisness and
Professions Code: The Contractor's License Law does not apply to an owner of property who
builds or improves thereon and who does such work himself or through his own employees,
provided that such Improvements are not intended or offered for sale. If, however, the building
or improvement is sold within one year of completion, the owner -builder will have the burden
of proving that he did not build or improve for the purpose of sale.)
I1
I, as owner of the property, am exclusively contracting with licensed contractors to con-
struct the project. (Sec. 7044, Business and Professions Code: The Contractor's License Law
does not apply to an owner of property who builds or improves thereon, and who contracts for
such projects with a contractof(s) licensed pursuant to the Contractor's License Law.)
I'! I am exempt under Sec. B. & P.C. for this reason
Date Owner
WORKERS' COMPENSATION DECLARATION
I hereby affirm that I have a certificate of consent to sell -insure, or a certificate of
Worker's Compensation Insurance, or a certified copy thereof. (Sec. 3800, Labor Code.)
Policy No. Company
(l Copy is filed with the city. CI Certified copy is hereby furnished.
CERTIFICATE OF EXEMPTION FROM
WORKERS' COMPENSATION INSURANCE
(This section need not be completed it the permit is for one hundred dollars ($100) valuation
Of less.)
I cattily that in the performance of thg work for which this permit is issued, 1 shall not
employ any person in any manner so as to become subject to the Workers' Compensation
Laws of California.
Date_ Owner
NOTICE TO APPLICANT: Il, after making this Certificate of Exemption you should become
subject to the Workers' Compensation provisions of the Labor Code, you must forthwith
comply with such provisions or this permit shall be deemed revoked.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance of the
work for which this permit is issued. (Sec. 3097, Civil Code.)
Lender's Name-
Lender's
ame
Lender's Address
This is a building permit when properly filled out, signed and validated, and is subject to
expiration if work thereunder is suspended for 180 days.
I certify that I have read this application and state that the above information is correct.
1 agree to comply with all city and county ordinances and state laws relating to building
construction, and hereby authorize representatives sof this city to enter the above.
mentioned property for inspection purposes.
Signature of applicant Date
Mailing Address
City, State, Zip
BUILDING: TYPE'CONNjST. /- OCC. GRP.
A.P. Number `76 / —Q �& l — 00
Legal Description 1.07- "�iD C -T UVJ r,�—
Project Description SF1�
a -�?I - ss-
Sq.
sSq. Ft.�A/ No. No. Dw.
Size Stories f Units
New 0 Add 0 Alter 0 Repair 0 Demolition 0
Estimated Valuation
PERMIT I I AMOUNT
Plan Chk. Dep. — U
Plan Chk. Bal.
Const.
Mech.
Electrical
Plumbing
S.M.I.
Grading
Driveway Enc.
Infrastructure
TOTAL
REMARKS
ZONE: BY:
Minimum Setback Distances:
Front Setback from Center Line
Rear Setback from Rear Prop. Line
Side Street Setback from Center Line
Side Setback from Property Line
FINAL DATE INSPECTOR
Issued by: Date Permit
Validated by:
Validation:
WHITE = FINANCE YELLOW = APPLICANT PINK = BUILDING DIVISION
Comments
At the present time, the Desert Sands Unified School District does not collect fees on garages/carports, covered patios/walkways, residential additions under
500 square feet, detached accessory structures (spaces that do not contain facilities for living, sleeping, cooking, eating or sanitation) or replacement mobile
homes. It has been determined that the above-named owner is exempt from paying school fees at this time due to the following reason:
EXEMPTION NOT APPLICABLE ,
This certifies that school facility fees imposed pursuant to
Education Code Section 17620 and Government Code 65995 Et Seq.
in the amount of $2.14 X 2,312 S.F. or $4,947.68 have been paid for the property listed above and that
building permits and/or Certificates of Occupancy for this square footage in this proposed project may now be issued.
Fees Paid By CC Downey Savings - Vince D'Ambra Check No. 05510078143
Name on the check Telephone 760/485-7657
Funding Residential
By Dr. Doris Wilson
Superintendent
Fee collected /exempted by C /stal Scott $4,947.68 1$0.00-
Payment
$0.00-Payment Recd OvedUnder
Signature ,
NOTICE: Pursuant to Government Code Section 66020(d)(1), this will serve to notify you that the 90 -day approval period in which you may protest the fees or
other payment identified above will begin to run from the date on which the building or installation permit for this project is issued, or from the date on which
those amounts are paid to the District(s) or to another public entity authorized to collect them on the District('s) behalf, whichever is earlier.
NOTICE: This Document NOT VALID if Duplicated
Embossed Original - Building Department/Applicant Copy - Applicant/Receipt Copy - Accounting
CERTIFICATE OF COMPLIANCE
vsc
Desert Sands Unified School District .
Dune Palms Road
;�a 3c>47950
Q BERMUDA DUNES
Date
8/26/02
La Quinta, CA 92253
U) RANCHO MIRAGE d
No.
23521
(760) 771-8515
{� INDIAN WELLS ti
�, PALM Q°„NT
INDIO
�O v
Owner
Mike & Barb Butvidas
APN #
769-061-006
Address
78575 Avenida Ultimo
Jurisdiction
La Quinta
City
La Quinta . Zip 92253
Permit #
0207-175
Tract #
DCTU5
Study Area
Type
Single Family Residence
No. of Units
' 1
Lot # No. Street
S.F. Lot # No.
Street S.F.
Unit 1 8
78575 Avenida Ultimo
2312 Unit 6
Unit 2
Unit 7
Unit 3
Unit 8
Unit 4
Unit 9
Unit 5
Unit 10
Comments
At the present time, the Desert Sands Unified School District does not collect fees on garages/carports, covered patios/walkways, residential additions under
500 square feet, detached accessory structures (spaces that do not contain facilities for living, sleeping, cooking, eating or sanitation) or replacement mobile
homes. It has been determined that the above-named owner is exempt from paying school fees at this time due to the following reason:
EXEMPTION NOT APPLICABLE ,
This certifies that school facility fees imposed pursuant to
Education Code Section 17620 and Government Code 65995 Et Seq.
in the amount of $2.14 X 2,312 S.F. or $4,947.68 have been paid for the property listed above and that
building permits and/or Certificates of Occupancy for this square footage in this proposed project may now be issued.
Fees Paid By CC Downey Savings - Vince D'Ambra Check No. 05510078143
Name on the check Telephone 760/485-7657
Funding Residential
By Dr. Doris Wilson
Superintendent
Fee collected /exempted by C /stal Scott $4,947.68 1$0.00-
Payment
$0.00-Payment Recd OvedUnder
Signature ,
NOTICE: Pursuant to Government Code Section 66020(d)(1), this will serve to notify you that the 90 -day approval period in which you may protest the fees or
other payment identified above will begin to run from the date on which the building or installation permit for this project is issued, or from the date on which
those amounts are paid to the District(s) or to another public entity authorized to collect them on the District('s) behalf, whichever is earlier.
NOTICE: This Document NOT VALID if Duplicated
Embossed Original - Building Department/Applicant Copy - Applicant/Receipt Copy - Accounting
i M� %;' CQAST TITLE CO,
RECORDING REQUESTED BY:
ORANGE COAST TITLE CCMPACOMPANY
99.87530T R-176975-1 D
NL L -T R %� &I.
MICHAEL S. BUTVIDAS
and BARBARA B. BUTVIDAS
82137 SIERRA AVE.
INDIO, CA 92201
DOC w 1000-204766
37F31/1064 03:640 040:3.64
Page 1 of I Oao T Tan Paid
Raaardad !n off74161.Mo.rds
County of Rlvaroldo
Wry L. Oros
Assessor, County Clark 3 Reaarder
IIIIIIIIIIIII IIIIIIIIII)IIIIIIIIIIIInIIIIVIIIIIIINII i
9 V w[ MQ M KM .IYM W yy
'x%64 - C6 -1 -Cot, 3 R t - w.r wro re.vw cw I U
GRT
az C;G ib ANDEED T
The undersigned grantor(s) declare(s):
Documentary transfer cox !a S15.30 Y S
(Xxx) Computed on full value of property conveyed, or _
( ) Computed on full value lee
a liens and encumbrances remaining at time of sale.
{ ! Unincorporated area: ( ) City of , and
\ FOR A VALUABLE CONSIDERATION, receipt of whi-.h 1s hereby acknowledged,
+, THOMAS L. KANNGIESSER, a single man a
hereby GRANT(S) to
\n MICHAEL S. BUTVIDAS and BARBARA B. BUNIDAS, Husband and Wife as Joint Tenants
the real property in the City of LA pUINTA• County of RIVERSIDE, State of California,
\ \ described as:
V\ LOT 8 OF DESERT CLUB TRACT UNIT 5 AS PER MAP RECORDED IN BOOK 21, PAGES
61 AND 62 OF MAPS, RECORDS CF RIVERSIDE COUNTY, CALIFORNIA
Dated April 21. 1999
iCtrr��C 41 (/
State of.-
Cuunt of? A y��• c.Ml tc��.L
On L ---_I S.S. THOMAS L. KANNrl SER
before me,-
personallo appeared
personally known to me (or proved to me on
the basis of satisfactory evldence)'.to be
the person(s) whose name(s) is/are subscribed
to the within instrument and 'acknowledged to
me that he/she/they executed the same in
his/her/their authorized capacity(ies), and
that by his/signature(s) on the
instrument the person(s), or the entity upon
behalf of which the person(s) acted, executed
the instrument.
WITNESS m a d and ff ic1r' 1
Siyunt \�)1 �\ �Jri- �I -•
I'�./ `(?Itis.az'ba for official notarial scall
MAIL TAX STATEM TS T0: °- •NUC
i'n_•r� IL'bli Slalc sl,Lar e
A1yr�m:nusioncs irrs � �' <:••........•;. :•;' -
Description: Riverside,CA Document-Year.DocID 1999.29478.8 Page: 1 of I
Order: 362 Comment:
D
.1TUID�� CITY OF LA QUINTA SUB -CONTRACTOR LIST
JO ADDRESS '7 ? - X75 A1/��LTjM� PERMIT NUMBER OWNER BUILDER 43c-1'
This form shall be posted on the job with the Building Inspection Card at all times in a consRicuous place. Only persons appearing on this list or'their employees are authorized to work
on this job. Any changes to this list must be approved by the Building Division prior to commencement of work. Failure to comply'Will result in a stoppage of work and/or the voidance
of building permit. For each applicable trade, all information requested below must be completed by applicant. "On File" is not an acceptable response.
Trade / Classification
Contractor
State Contractor's License Workers Compensation Insurance
City Business License
Company Name
Classification
(e.g. A, B, C-8)
License Number
(xxxxxx)
i
Exp. Date Carrier Name Policy Number
(xx/xx/xx) (e.g. State Fund, CalComp) (Format Varies)
Exp. Date
(xx/xx/xx)
License Number
(xxxx)
Exp. Date
(xx/xx/xx)
EARTHWORK (C-12)
r^''tA �� P�
5 �glo9.�
P4/ 04 �Xe,"P"t
v43t.c�
I�S�o3
CONCRETE (C-8)
//vim nn
%t vl 7� d I;l;/1D$
C 8
766 I v2
3131103 She Nr1 i 1402 000 q�
lll�0 3
!� 6 �
X01 // o
FRAMING IC -51
Q i t C& 6N tvoe.
R
77 7 .1, TO_'q
I Of 577 r� r=U/v -43 S!6 -GI qJ 59 -0 /
10/34o2_
0S 751
Sl7 .D3
STRUCT. STEEL (C-51)
MASONRY (C-29)
/V,
PLUMBING (C-36)(1ki0cfW_
C34 NIL
(b3-2-3
►J3,1o3 54qcF::�A,4J I(p-74i-o•2
4497
'5/13.02
LATH, PLASTER (C-35)
sGJ✓h /' cleln Lo.
13
766,46/
'7131103 3�tc F(_104 /9767001
/011/02
47.78
313103
DRYWALL (C-9)
Sq vn Y11/u.,i n L." .
t c
/ c
HVAC (C-20)
PaL4/ "5
C:20/C'3S3
577'ISa
9/3,l03 STA'Ti= FuIvO /(P/ s$'73.
///b3
'0 nM
ELECTRICAL (C-10)
I���
G !D
/ Oct
7/3,*'J 03 �T��e F=und 2-29ozoo !'f3ym
111103
0/984
9��502
ROOFING (C-39)
pQ�'C�/)r1e✓1
]0710'
sc OWL
30 6 ��rfc Farn�t zi3•5"a64jDcr7c17
1111,03
0 323-a
(-/30
SHEET METAL (C-43)
A
FLOORING IC -15)
11,10 ,a
8
80 hof �
a9l0� gXeMP7-
D� 3('pO
1181'03
GLAZING (C-171
(:�� w %v ar
l-7 — G0 1
%3.7 8BX4
-713 i o �4k •Fit,nr.P 04 (01 15-3
W1103
X 30
'2-13//0-2-
Z/ 3i/o
INSULATION (C-2)
/�C( 14
C -'Z
C,
O
'7130/13 • G 1:.T ' . '/ Z2pd `
= :. .: �:.
o32- 9/
SEWAGE DISP. (C-42)
PAINTING (C-33)
CERAMIC TILE (C-54)
lei -`
CABINETS (C-6)
NImJaov_ 13 t�, t e".,5
FENCING (C-13)
SG�y► ITIa,/i.') CO,
LANDSCAPING (C-27)
M o j ct ve- (3 Li', (eA ef5
POOL IC -53)
Pf .
a
Certificate of Occupancy
City of La Quintal
Building and Safety Department
This Certificate issued pursuant to the requirements of Section 109 of the Uniform Building Code,
certifying that, at the time of issuance, this structure was in compliance with the various ordinances
of the City regulating building construction or -use. For the following:
BUILDING ADDRESS: 78-575 AVENIDA ULTIMO
Use Classification: SINGLE FAMILY DWELLING
Occupancy Group: R-3 Type of Construction:
Owner of Building: MIKE & BARB BUTVIDAS
Building Official
vn�
Bldg. Permit No.: 0207-175
Land Use Zone: RL
Address: 82-137 SIERRA AVE.
City: INDIO, CA 92201
By: STEVE TRAXEL
Date: 12-24-2002
POST IN A CONSPICUOUS PLACE
/pa, 1,
GA
RyW,,4,R
I.
,Lor 9
/zo 00
RROPo 3`.EO 6 "MA50,4/RY 4
IIARRO IIW O Fof?AX R.H/rr/i 1a
,GDT /9
yl, PAD E/_. */ 0
ENSITY AS DETERMINED BY THE UNIFORM BUILDING CODE SECTION 7010 ,OR EQUIVALENT AS
APPROVED BY THE CITY ENGINEER. FIELD DENSITY SHALL BE DETERMINED IN ACCORDANCE
GRADING NOTES
WITH THE UNIFORM BUILDING CODE SECTION 7002, OR EQUIVALENT, AS DETERMINED BY THE
ti
J
1. GRADING SHALL BE IN ACCORDANCE WITH THE ENGINEERED GRADING REQUIREMENTS OF
V
10. ALL STREET SECTIONS ARE TENTATIVE. THE MINIMUM SECTION IS 3" A.C. OVER 4.5"
TH
E UNIFORM BUILDING CODE, LATEST EDITION, AND SOILS REPORT, NO. ,
1
�0
0 DETERMINE EXACT SECTION REQUIREMENTS. 'THE CITY ENGINEER SHALL APPROVE THE FIN
PREPARED BY:
AL STREET SECTION.
V J�Q
11. THE CITY ENGINEER WILL REVIEW FOR APPROVAL THE FINAL STREET SECTIONS AFTER S
"R"
2. THE SOILS ENGINEER AND THE ENGINEERING GEOLOGIST
RyW,,4,R
I.
,Lor 9
/zo 00
RROPo 3`.EO 6 "MA50,4/RY 4
IIARRO IIW O Fof?AX R.H/rr/i 1a
,GDT /9
yl, PAD E/_. */ 0
ENSITY AS DETERMINED BY THE UNIFORM BUILDING CODE SECTION 7010 ,OR EQUIVALENT AS
APPROVED BY THE CITY ENGINEER. FIELD DENSITY SHALL BE DETERMINED IN ACCORDANCE
GRADING NOTES
WITH THE UNIFORM BUILDING CODE SECTION 7002, OR EQUIVALENT, AS DETERMINED BY THE
CITY ENGINEER.
1. GRADING SHALL BE IN ACCORDANCE WITH THE ENGINEERED GRADING REQUIREMENTS OF
10. ALL STREET SECTIONS ARE TENTATIVE. THE MINIMUM SECTION IS 3" A.C. OVER 4.5"
TH
E UNIFORM BUILDING CODE, LATEST EDITION, AND SOILS REPORT, NO. ,
CRUSHED A.B.. ADDITIONAL SOIL TEST(S) SHALL BE REQUIRED AFTER ROUGH GRADING T
DATED:
0 DETERMINE EXACT SECTION REQUIREMENTS. 'THE CITY ENGINEER SHALL APPROVE THE FIN
PREPARED BY:
AL STREET SECTION.
TELEPHONE NO.
11. THE CITY ENGINEER WILL REVIEW FOR APPROVAL THE FINAL STREET SECTIONS AFTER S
"R"
2. THE SOILS ENGINEER AND THE ENGINEERING GEOLOGIST
UBMITTAL OF VALUE TESTS FOR ROADYWAY SUBBASE.
SHALL EXERCISE SUFFICIENT SU
PERVISORY CONTROL DURING GRADING TO INSURE
COMPLIANCE WITH THE PLANS, SPECIFICAT
IONS,•AND CODE WITHIN THEIR PURVIEW.
12. LOCATIONS OF FIELD DENSITY TESTS SHALL .BE DETERMINED BY THE SOIL ENGINEER OR
APPROVED TEST AGENCY AND SHALL BE SUFFICIENT IN BOTH HORIZONTAL AND VERTICAL PL
3. THE DESIGN CIVIL ENGINEER SHALL EXERCISE SUFFICIENT
ACEMENT TO PROVIDE REPRESENTATIVE TESTING OF ALL FILL PALCED. TESTING IN AREAS
CONTROL DURING GRADING AN
D CONSTRUCTION TO INSURE COMPLIANCE
OF A CRITICAL NATURE OF SPECIAL EMPHASIS SHALL BE IN ADDITION TO THE NORMAL REPR "
WITH THE PLANS, SPECIFICATIONS, AND CODE WI
THIN HIS PURVIEW.
ESENTATIVE SAMPLINGS.
13. THE FINAL COMPACTION REPORT AND APPROVAL FROM THE SOILS ENGINEER SHALL CONTA
4. DURING ROUGH GRADING OPERATIONS AND PRIOR TO CONSTRUCTION OF PERMANENT DRAINA
GE STRUCTURES, TEMPORARY
IN THE TYPE OF FIELD TESTING PERFORMED. EACH TEST SHALL BE IDENTIFIED WITH THE
DRAINAGE CONTROL SHALL BE PROVIDED TO PREVENT PONDING W
ATER AND DAMAGE TO ADJACENT
METHOD OF OBTAINING THE IN-PLACE DENSITY, WHETHER SAND CONE OR DRIVE RING AND SH
PROPERTY.
ALL BE SO -NOTED FOR.EACH TEST. SUFFICIENT MAXIMUM DENSITY DETERMINATION SHALL B
5. AFTER CLEARING, EXISTING GROUND SHALL BE SCARIFIED
E PERFORMED TO VERIFY THE ACCURACY OF THE`AAXIMUM DENSITY CURVES USED BY THE FIE
TO A MINIMUM OF 6" ON THE
ENTIRE SITE OR AS RECOMMENDED
LD TECHNICAN.
BY THE SOILS REPORT.
14. ALL UNDERGROUND FACILIITES, WITH LATERALS, SHALL BE IN PLACE AND INSPECTED P
6. THE MAXIMUM CUT AND FILL SLOPES SHALL BE 2:1.
RIOR TO PAVING, INCLUDING BUT NOT LIMITED TO THE FOLLOWING: SEWER, WATER, ELECT
7. PADS SHALL BE COMPACTED TO
RIC, GAS AND DRAINAGE.
A MINIMUM OF 90% RELATIVE DENSITY PER A.S.T.M. SPE
CIFICATIONS AND THE ABOVE MENTIONED SOILS REPORT.
15. THE FINAL UTILITY LINE BACKFILL REPORT FROM THE PROJECT SOIL ENGINEER SHALL
8. MINIMUM BUILDING PAD DRAINAGE SHALL BE 20.
INCLUDE AN APPROVAL STATEMENT THAT THE BACKFILL IS SUITABLE FOR THE INTENDED USE
DRAINAGE SHALL BE A MINIMUM OF 0.
3' DEEP AND BE CONSTRUCTED A MINIMUM OF 2' FROM THE TOP OF CUT OR FILL SLOPES.
THE MINIMUM SLOPE OF SWALES SHALL BE 0.50%.
16. BLOCK WALLS ARE NOT PART OF THE GRADING PERMIT. SUBMIT FOR SEPARATE BUILDIN
9.
G PERMIT(S).
ALL FILLS SHALL BE COMPACTED TO A MINIMUM OF NINETY 90) PERCENT OF MAXIMUM D
17. THE CONTRACTOR IS RESPONSIBLE TO PREVENT SILT CONTAMINATION OF STORMWATER IN
FILTRATION FACILITIES DURING CONSTRUCTION OF SUBSEQUENT IMPROVEMENTSBY THE CONTR
8. ,�J� �, F1 /_ /. M.4 TER//1.L P,G it c,EO UND,�,4� Tip/,E STR!/CTU,PE S'/�•9�1.
ACTOR. IMMEDIATELY PRIOR TO FINAL ACCEPTANCE OF STORM DRAINAGE RETENTION/INFILT�j,E
G OMP�ICT,ED
RATION FACILITIES, THE CONTRACTOR SHALL CONDUCT, IN THE PRESENCE OF THE CITY INS
j oF�E,c ,� rives o��c.�s/rte
PECTOR, A PERFORMANCE TEST DESIGNED TO CLEARLY DEMONSTRATE THE FUNCTIONAL ADEQUA
CY OF THE FACILITIES.
18. THE CONTRACTOR SHALL PROVIDE WIND EROSION AND DUST CONTROL MEASURES AS REQUI
L -EMEND
RED BY THE FUGITIVE. DUST CONTROL PLAN APPROVED FOR THIS PROJECT.
/, `Xx,L! XX) ,E1C/$T/A/G G,94D
2. XXX.Xy F/N/sH 4t;1?.4DE
.3. EX/ST/NG CONTOUR
�i XXX F/NISH CONTOUR
✓r. ---•-- ORM/NAGE Sl�V,�IL..E
6 oP .54 OPE: cOrl"C11- L
o.E
7 r. C. TOP OF CU,9B
8 w /L INE
9. T R Top OF PwilzMEmr
/0. E.P. EDGE OF PA!/�'MENT
//. F.S. F/N/S// SURFACE
/2. f F/N/SH GRADE
,.
/3. .EG. EX/9T/N4 GRADE
PROPER rY G /NE
Fi'/G/•/�ST�1D✓.�1C,�'/' GR/-JD,E - Ifo• o;
H/GN pO/NT
/7. CENTER /_ AIVE
h 1al-14ST .EX/5'T//VG ,E,G,Ev,4 rjoAl o/V .G o T - va. a
/8. -'-'r' CONCRETE
49. T W. T'oP of t-fi,4,G G
R.4,4A1,lV/1V9 e Z'o/V/Nc CO3V7R1_/ANC,6
.E.�1 R Ti5/l�YDRK
.0 Ess r,-/, AI 5o c. Y
PRopER r>' �IO,DR,Ess
7S - 7/O 411,CN/DA 411- T/MD
B/lRB,�IRA B'uT!/lQA5
82 -/37 5/E1FR4 AVZN41,E
/ND/O, CA. 9220/
E3 ENC14 "4- RA` �
OXI T UM ,E#o. Oo rap of
c41Re AT
4 or col?lvER. U $. G. S. 1.,4 QU/NTf!
01MOA7,41VG4E.
Cf9.E'C,ED' R.EcoN/ME1V,0,ED
FOR .�IPPRo!/.�l.G ,BY;
TOM HART161AA ✓h',,?A: K AIERNIAN R/_AI/ ChlCCIfER:
By/,L DING �'' S,�IF.ETY D/FF,ECTOR co*iA4 1iV/rY ACklE.G oPMFi r,01A7ECTOR /` C. Z.
C/ r>,- oF._r! ov/n/r,4. CiTYl3f I.A Qu1Nrel F/RM:
•
,0,4 rc: OA rCZ OA T,E
No. 12571
'A'
IL
F/ Tch� Eit/Gf�/�'ERS /Nc.
f? o.,BOX xlssPA,GM DE SERI
CA. 922 E l i 760 - 3-s'- 70a 7
scl-1 G.E 0,94A, iRED ,BY:
6. W BOTTOM OF W,,44 4
CITY OF LA QUINTA
BUILDING & SAFETY DEPT,
APPROVED
FOR CONSTRUCTION
,AI/ENIDA 0.4 riMo
H
41166MIDA o r41a41,VG,4
o I�
41
O
3 C/7�c•zE I"AM�J'/gyp
///G/N/TY MAP AUG 2 12002
woT ro SCA�c.,E '�
C/T Y OF I. A Q U/NT)41L
I!
GREC/5E 6RA-01NC, P/. AN ,G 4 T 8
aesE.Qr C.0 uB TRAc T /-//v/ 7, Al o .5 5/./T,
/pza z//6/ - az
91WIcWeD
A.R./t/. 769-ord/-006 b��,
r�
I TITLE 24 REPORT I
Title 24 Report for:
MIKE & BARBARA BUTVIDAS
78 -575 AVENIDA ULTIMO
LA QUINTA, CA 92253
Project Designer:
GLS GROUP
74-854 VELIE WAY, Suite # 5
PALM DESERT, CA 92260
760-340-3528
Report Prepared By:
GLS GROUP
GLS Group
74-854 Viele Way, Suite 5
Palm Desert, CA 92260
(760) 340-3528
CITY OF LA QUANTA
BUILDING & SAFETY DEPT.
,APPROVED
Job Number: ; FOR CONSTRUCTION
BU- LQ 2K2 oArE � of BY
Date:
1.3911%
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2001 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC (415) 883-5900.
EnergyPro 3.1 By EnergySoft Job Number: BU- LQ 2K2 User Number: 5553
TABLE OF CONTENTS I
Cover Page
Table of Contents
Form CF -1 R Certificate of Compliance
Form MF -1 R Mandatory Measures Checklist
Form C -2R Computer Method Summary
Form ENV -3 Proposed Construction Assembly
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak.Loads
1
2
3
6
8
13
14
16
18
20
EnergyPro 3.1 By EnergySoft Job Number: BU- LQ 2K2 User Number: 5553 j
Certificate of Compliance: Residential (Part 1 of 2) CF -1 R
MIKE & BARBARA BUTVIDAS 8/3/02
Project Title Date
78 7-575 AVENIDA ULTIMO LA QUINTA
Project Address Building Permit #
GLS Group (760) 340-3528 Plan Check / Date
Documentation Author Telephone
Computer Performance 15 Field Check / Date
Compliance Method (Package or Computer) Climate Zone Enforcement Agency Use Only
GENERAL INFORMATION
Total Conditioned Floor Area: 2,312 ft2 Average Ceiling Height: 11.0 ft
Total Conditioned Slab Area: 2,312 ft2
Building Type:
(check one or more)
X❑ Single Family Detached ❑ Addition
❑ Single Family Attached ❑ Existing Building
❑ MUlti-Family ❑ Existing Plus Addition
Front Orientation: (East) 90 deg
Number of Dwelling Units: 1.00
Number of Stories: 1
Component
R-38 Roof (R.38.2x4.24)
Slab On Grade
R-19 Wall w/1" EPS
R-19 Wall (W.19.2x6.16) 1/2+5/8 GYP
Solid Wood Door
Slab On Grade
FENESTRATION
Floor Construction Type: ® Slab Floor
❑ Raised Floor
Frame
Type
Const.
Assembly
U -Value
Location/Comments
(attic, garage, typical, etc.)
Wood
0.024
Exterior Roof
n/a
0.756
Exposed Slab w/R-0.0 Perimeter Insulation
Wood
0.045
Exterior Wall
Wood
0.060
Exterior Wall
None
0.387
Exterior Door
n/a
0.756
Covered Slab w/R-0.0 Perimeter Insulation
Shading Devices
Type
Orientation
Area
Fenestration
Exterior
Overhang Side Fins
SF
U -Factor
SHGC
Shading
Yes / No
Yes / No
Front
(East)
92.0
0.65
0.40
Bug ScreenX❑
❑
❑ x❑
Front
(East)
116.3
0.65
0.40
Bug Screen
❑
❑ Q
Left
(South)
107.0
0.65
0.40
Bug Screen
❑
❑ Q
Rear
(West)
57.0
0.65
0.40
Bug Screen
X❑
❑
❑ 0
Right
(North)
18.0
0.65
0.40
Bug Screen
❑
X❑
❑ X❑
Right
(North)
2.8
0.65
0.48
Bug Screen
❑
x❑
❑ x❑
Left
(South)
15.5
0.65
0.48
Bug Screen
❑
x❑
❑ FRI
Rear
(West)
42.2
0.65
0.40
Bug Screen
❑
x❑
❑ X❑
❑
❑
❑ ❑
❑
❑
❑ ❑
❑❑
El
Run Initiation Time: 08103/02 11:54:06 Run Code: 1028400846
Ener
Pro 3.1 By Ener Soft
User Number: 5553
Job Number: BU- LQ 2K2
Pa e:3 of 23
Certificate of Compliance: Residential (Part 2 of 2) CF -1 R
MIKE & BARBARA BUTVIDAS 8/3/02
Project Title Date
HVAC SYSTEMS Note: Input Hydronic or Combined Hydronic data under Water Heating Systems, except Design Heating Load.
Distribution
Heating Equipment Minimum Type and Duct or
Type (furnace, heat Efficiency Location Piping Thermostat Location /
pump, etc.) (AFU E/HSPF) (ducts, attic, etc.) R -Value Type Comments
('Pntral Furnace 80% AFUE Ducts in Attic 42 Setback ZONE I HVAC Split Gas/Elec
rentral_F_u.rnace 80% AFUE Ducts in Attic 42 Setback ZONE II HVAC Split Gac/ I . .
Cooling Equipment Minimum Duct
Type (air conditioner, Efficiency Location Duct Thermostat Location /
heat pump, evap. cooling) (SEER) (attic, etc.) R -Value Type Comments
Split Air Conditioner 12.0 SEER Ducts in Attic 42 Setback ZONE I HVA(' Split Gas/El n
Split Air Conditioner 12.0 SEER Ducts in Attic 42 Setback ZONE II HVA(' Split Gas/Eler.
WATER HEATING SYSTEMS Rated 1 Tank Energy Facts 1 External
Water Heater Water Heater Distribution # in Input Cap. or Recovery Standby Tank Insul.
System Name Type Type Syst. Btu/hr (gal) Efficiency Loss (%) R -Value
Standard Gas 50 gal or Less Small Gas Recirc/Time+Temp 1 40,000 50 0.52 n/a 12
1 For small gas storage (rated inputs of less than or equal to 75,000 Btu/hr), electric resistance and heat pump water heaters, list energy factor.
For large gas storage water heaters (rated input of greater than 75,000 Btu/hr), list Rated Input, Recovery Efficiency and Standby Loss.
For instantaneous gas water heaters, list Rated Input and Recovery Efficiency.
REMARKS
COMPLIANCE STATEMENT
This certificate of compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations, and the administrative regulations to implement them. This certificate has been signed by the individual with
overall design res po "bility. The undersigned recognize that compliance using duct sealing and TXV's requires installer testing and certification
and field verif on y a VprovedS r ter.Designer r O ssions Code) Documentation Author
Name: Name: GLS GROUP
Title/Firm: GLS UP Title/Firm: GLS Group
Address: 74-854 VELIE WAY, Suite # 5 Address: 74-854 Viele Way, Suite 5
PALM DESERT, CA 92260 Palm Desert, CA 92260
Telephone: 760-340-3528 Telephone: (760) 340-3528
Lic. #:
(signature)
Enforcement Agency
Name:
Title/Firm:
Address:
Telephone:
(date)
(signature) (date)
IEnergvPro 3.1 By EnergvSoft User Number: 5553 Job Number: BU- LQ 21<2 Page:4 of 23 1
Certificate of Compliance: Residential (Addendum) CF -1 R
MIKE & BARBARA BUTVIDAS 8/3/02
Project Title Date
Special Features and Modeling Assumptions
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special
written justification and documentation, and special verification to be used with the performance approach. The local
enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies
based on the adequacy of the special justification and documentation submitted. I Plan I Field
The DHW System "Standard Gas 50 gal or Less" Energy Factor = 0.525. An EF below 0.58 requires an R-12 External Blanket.
The HVAC System "ZONE I HVAC Split Gas/Elec" includes credit for a Radiant Barrier installed per Section 8.13 of the Residential
Manu 1.
HIGH MASS Design(see C -2R) -Verify Thermal Mass: 1135 sqft Exposed Slab Floor, 3.50" thick at ZONE I
The HVAC System "ZONE II HVAC Split Gas/Elec" includes credit for a Radiant Barrier installed per Section 8.13 of the Residential
Man HIGH MASS Design(see C -2R) - Verify Thermal Mass: 939 sqft Covered Slab Floor, 3.50" thick at ZONE II
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 238 sqft Exposed Slab Floor, 3.50" thick at ZONE II
HERS Required Verification
These features must be confirmed and/or tested by a certified HERS rater under the supervision of a CEC approved HERS
provider. i ne HhK5 rater must aocument the neia vermcation and diagnostic testing or tnese measures on a torm (;F -b R.
Plan
Field
The HVAC System "ZONE I HVAC Split Gas/Elec" is using reduced duct leakage to comply and must have diagnostic site testing of
duct leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
The HVAC System "ZONE II HVAC Split Gas/Elec" is using reduced duct leakage to comply and must have diagnostic site testing of
duct leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
Run Initiation Time: 08/03/02 11:54:06 . Run Code: 1028400846
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page:5 of 23
Mandatory Measures Checklist: Residential (Page 1 of 2) MF -1 R
NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. Items marked with an
asterisk (') may be superseded by more stringent compliance requirements listed on the Certificate of Compliance. When this checklist is incorporated into
the permit documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures
whether they are shown elsewhere in the documents or on this checklist only.
DESCRIPTION Instructions: Check or initial applicable boxes or enter NIA if not applicable.
DESIGNER
ENFORCEMENT
Building Envelope Measures
a 1150(a): Minimum R-19 ceiling insulation. ,
a§ 150(b): Loose fill insulation manufacturer's labeled R -Value.
Minimum R-13 wall insulation in wood framed walls or equivalent U -value in metal frame walls (does
❑*§150(c):
i( not apply to exterior mass walls).
E]'§150(d): Minimum R-13 raised floor insulation in framed floors or equivalent.
§150(1): Slab edge insulation -water absorption rate no greater than 0.3%, water vapor transmission rate no
❑ greater than 2.0 perm/inch.
§118: Insulation specified or installed meets insulation quality standards. Indicate type and form.
®§116-17: Fenestration Products, Exterior Doors and Infiltration/Exfiltration Controls
1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage.
2. Fenestration products (except field fabricated) have label with certified U -Factor, certified Solar Heat Gain
Coefficient (SHGC), and infiltration certification.
3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed.
§150(g): Vapor barriers mandatory in Climate Zones 14 and 16 only.
a§ 150(f): Special infiltration barrier installed to comply with Section 151 meets Commission quality standards.
Gas
§ 150(e): Installation of Fireplaces, Decorative Gas Appliances and Logs.
1. Masonry and factory -built fireplaces have:
a. Closeable metal or glass door
b. Outside air intake with damper and control
c. Flue damper and control
2. No continuous burning gas pilots allowed.
Space Conditioning, Water Heating and Plumbing System Measures
§110-13: HVAC equipment, water heaters, showerheads and faucets certified by the Commission.
§ 150(h): Heating and/or cooling loads calculated in accordance with ASH RAE, SMAC NA or ACCA.
§150(i): Setback thermostat on all applicable heating and/or cooling systems.
§1500): Pipe and Tank Insulation
1. Storage gas water heaters rated with an Energy Factor less than 0.58 must be externally wrapped with
insulation having an installed thermal resistance of R-12 or greater.
2. First 5 feet of pipes closest to water heater tank, non -recirculating systems, insulated (R-4 or greater)
3. Back-up tanks for solar system, unfired storage tanks, or other indirect hot water tanks have R-12 external
insulation or R-16 combined internal/external insulation.
4. All buried or exposed piping insulated in recirculating sections of hot water systems.
5. Cooling system piping below 55 degrees F. insulated.
6. Piping insulating between heating source and indirect hot water tank.
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page:6 of 23
I
Mandatory Measu`r'es Checklist: Residential (Page 2 of 2) MF -1 R
vNOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. Items marked with an
asterisk (") may be superseded by more stringent compliance requirements listed on the Certificate of Compliance.. When this checklist is incorporated into
the permit documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures
whether they are shown elsewhere in the documents or on this checklist only.
DESCRIPTION Instructions:; Check or initial applicable boxes or enter N/A if not applicable.
DESIGNER
ENFORCEMENT
Space Conditioning, Water Heating and Plumbing System Measures: (continued) ` �•
X "� 150(m): Ducts and Fans' •
❑ '
r
Y
1. All ducts and plenums installed, sealed and insulated to meet the requirements of the 1998 CMC Sections 601,
603, 604 and Standard 6-3; ducts insulated to a minimum installed level of R-4.2 or enclosed entirely in
conditioned space. Openings shall be sealed with mastic, tape, aerosol sealant, or other duct -closure system
that meets the applicable requirements of UL181, UL181A, or UL181B. If mastic or tape is used to seal openings
greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used. Building cavities shall not
be used for conveying conditioned air. Joints and seams of duct systems and their components shall not be- ,
sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and -
t�
drawbands.
2. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other
than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building
cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be
compressed to cause reductions in the cross-sectional area of the ducts.
3. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive
duct tapes unless such a tape is used in combination with mastic and drawbands. ,
4. Exhaust fan systems have back draft or automatic dampers.
r
5. Gravity ventilation systems serving conditioned space have eitherautomatic or readily accessible, manually
operated dampers. y
ii
6. Protection of Insulation. Insulation shall be protected from damage, including that due to sunlight, moisture,
equipment maintenance, and wind but'not limited to the following: Insulation exposed to weather shall be suitable
�}
for outdoor service e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam
insulation shall be protected as above or painted with a coating that is water retardant and provides shielding
from solar radiation that can cause degradation of the material.
§114: Pool and Spa Heating Systems and Equipment
u
- 1. Certified with 78% thermal efficiency, on-off switch, weatherproof operating instructions, no electric resistance -.
3
heating, and no pilot.
2. System is installed with at least 36'. of pipe between filter and heater for future solar, cover for outdoor pools or
spas.
a. At least 36" of pipe between filter and heater for future solar heating.
b. Cover for outdoor pools or outdoor spas.
e
3. Pool system has directional inlets and a circulation pump time switch.
❑ • § 115: Gas fired central furnaces, pool heaters, spa heaters or household cooking appliances have no
+ 'continuously burning pilot light. (Exception: Non -electrical cooking appliances with pilot <•150 Btu/hr)
IR1§118 (f): Cool Roof material meet specified criteria
Lighting Measures
t'
X❑ §150(k)1: Luminaires for general lighting in kitchens shall have lamps with an efficacy 40 lumens/watt orb reater for
general lighting in kitchens. This general lighting shall be controlled by a switch on a readily accessible lighting
control panel at an entrance to the kitchen. ' +
a1150(k)2: Rooms with a shower or bathtub must have either at least one luminaire with lamps with an efficacy of
40 lumens/watt or greater switched at the entrance to the room or one of the alternative to this requirement +
;.
allowed in Section 150(k)2.; and recessed ceiling fixtures are IC (insulation cover) approved.
3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 page:? of 23
Comauter Method Summary (Part 1 of 3) C -2R
_M.I_KE_&_BARBA RA_B_U_T_V_I.DAS
1.,1.35_
-0.02.4_
8/_3/_02
Project Title
_7_8-57_5_AVE. NJ.DA_U_L_T_MO LA Q_U_IN_T_A
Wall-
14_
Date
Project Address
9.0_
Wall-
Building Permit #
GLS G[oup
9.0.
(760)340-3528
Check/Date
Documentation Author
0.0_4-5
Telephone
Plan
Comp_uter_P_e.rfum.ance
93
15
90
Field Check/Date
Compliance Method (Package or Computer)
22.
Climate Zone
1.8.0_
Source Energy Use Standard
Proposed
Compliance
0..0.45
(kBtu/sf-yr) Design
Design
Margin
7.0
Space Heating 4.00
3.08
0.92
Wall_
Space Cooling 39.97
38.32
1.65
_90-
Domestic Hot Water 11.93
11.61
0.32
-2.7.0.
. Totals 55.90
53.01
2.88
-0,060-
Percent better than Standard: 5.2%
Total Conditioned Floor Area: 2,312 ft2 Floor Construction Type: ❑ Raised Floor ❑X Slab Floor
Building Type: Single Fam Detached
Building Front Orientation: (East) 90 deg Total Fenestration Area: 19.5%
Number of.Dwelling Units: 1.00 Total Conditioned Volume: 25,432 ft 3
Number of Stories: 1 Total Conditioned Slab Area: 2,312 ft 2
BUILDING ZONE INFORMATION # of Thermostat Vent
Zone Name +: Floor Area Volume 'Units Zone Type Type` Hgt. Area
.ZONE_I_HVAC_Split_Gas/.Elec 1,1.35 -12,4.85 _0.4.9_ Conditioned- -Setback_ 2 _n/a
.ZONE_I1_H_VA_C_Sp.lit_G.as/.Ele.c 1.,1.7_7 1.2,9.4.7. _0...51_ -Conditioned- _S-etback_ 2 _n/a
Solar
OPAQUE SURFACES Act. Gains
Type Area U -Fac. Azm. Tilt Y / N
_Roof
1.,1.35_
-0.02.4_
0-
0
Wall-
14_
-0..0.4.5.
9.0
9.0_
Wall-
1.7.3_
_0.0.4.5.
9.0.
90_
Wall-
55
0.0_4-5
90
90
Wall-
93
0..0_4.5
90
_90
Wall_
22.
-0..0.4.5_
1.8.0_
_90_
Wall-
1.82_
0..0.45
_180_90-
-Wall-
7.0
0,045
_2.7_0
90_
Wall_
1.65_
-0..0.60__27.0.
_90-
-Wall
1_4_
_0..0.4.5_
-2.7.0.
_90-
-Wall-
1.2.4_
-0,060-
0
90_
Door
1.8_
0..38.7_
0
90
Wall-
53_
_0.0.4.5_
0.
90_
Wall-
4.3-
_0 045
0.
9.0_
Wall_
1.37_
_0...0.4.5_
0
9.0_
Wall-
22.
-0.0.4.5_
0.
9.0_
.Roof
1„177_
-0..02.4_
1.8.0_
0_
Wall-
320_
_0.0.4.5.
9.0.
9.0_
Wall-
251.
004-5
_1.80
90
Wall-
516_
00_45
_2.7_0
90
Wall_
110
-00_4.5
- 0
_90
Form 3 Reference
.R_38_Ro0.QR_ ,38..2x4..24)
.R_1.9_Wall_w/_L" E
_R_1.9_W a I I_w/_1_E P_S
_R_1.9_W al l_w/1_E P_S
.R_1.9_Wall_W1-EP_S
.R_19_Wa1l_w/_1!EP_S
R_1.9_W_ _aII_w/1_EP_S
B=1.9_WaII_w/1_EP_S
.R_1.9_Wall_(.W.1.9..2x6.1.6.) 112±5/.8_GYP_
.R_1.9_Wall_w/_1!EP_S
R_1.9_Wall_(W.1.9.2x6._-6.) 1.12±5/_8_GYP_
Solid_Wood_Door
RR=19 Wall w/1" EPS
.R=19_Wal1_w1_1!EP_S
_R_1.9_Wal1_wL1" EP_S
_R_1.9_Wall_w/_11 E
_R_3-8_Roof_(R.3.8..2x4..24.)
.R_1.9_W a l l__w/_1_E P_S
.R_1.9_W a l l__w/_1_E P_S
. R_1_9_W a I I_w/ 1_E P_S
R_1.9_W_ _all_w/_1_EP_S
7 -ONE -1
ZONE -1
.ZONE -1
ZONE
ZO.NE_I
.ZO.NE_I
.ZO.NE_I
ZONE1
ZO.NE_I
ZONE -1
ZONE -1
ZONE -1
ZONE1
.ZONE -1
.ZONE_I
.ZONE -11
.ZONE -11
ZONE -II
ZONE -11
Location / Comments
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page:8 of 23 1
Computer Method Summary . (Part 2 of 3) C -2R
MIKE & BARBARA BUTVIDAS 8/3/02
Project Title Date
FENESTRATION SURFACES
U-
Act.
Glazing Type
Location/
#
Type
Area
Factor
SHGC
Azm.
Tilt
Comments
_-
.WindoErot.n(East)_
w
10 6.
-0..6.5.0_
0._40.
9.0`
_9.0. DEEAU.LT_DBL_P_ANE
-ZONE-1
2
Window Front
East_
3.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE 1
3
Window Front
(East _
48.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE I
4
Window Front
East_
9.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE 1
5
Window FrontEast
_
16.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE 1
6
Window Front
(East)
3.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE I
7
Window Front
(East)_
4.0
0-650_
0.40
90_
90 DEFAULT DBL PANE
ZONE 1
8
Window Front
East)
4.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE I
9Window
Left
(South)
16.0
0.650
0.40
180_
90 DEFAULT DBL PANE
ZONE I
_1.0.
Window Left
(South)
3_0
0.650
0.40
180
90 DEFAULT DBL PANE
ZONE I
11
Window Left
(South
48.0
0.650
0.40
180
90 DEFAULT DBL PANE
ZONE 1
12
Window Left
South
9.0
0.650
0.40
180
90 DEFAULT DBL PANE
ZONE I
13
Window -Left -(.South)
16.0
0.650
0.40
18.0_
_90. DEFAULT DBL_PA-NE
_ZQN_ E_I
14
Window Left
(South)
3.0
0.650
0.40
180
90 DEFAULT DBL PANE
ZONE 1
15
Window Rear
West)
48.0
0.650
0.40
270
90 DEFAULT DBL PANE
ZONE 1
16
Window Rear
(West)
9.0
0.650
0.40
270
90 DEFAULT DBL PANE
ZONE I
17
Window RightNorth
_
12.0
0.650
0.40
0
90 DEFAULT DBL PANE
ZONE 1
18
Window Right
North.
6.0
0.650
0.40
0
90 DEFAULT DBL PANE
ZONE 1
19Window
Right(North)
2.8
0 650
0.48
0_
9ECK, S BLO_CK��x4
0 WC��
ZONE I
20
Window Front
East_
2.3
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE II
21
Window Front
East
8.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE II
22.
Window Front
(East)_
16.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE II
23
Window Front
(East _
3.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE II
24
Window Front
(East)_
48.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE II
25
Window Front
East)
9.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE II
26
Window Front
(East_
16.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE II
27
Window Front
(East)
3.0
0.650
0.40
90
90 DEFAULT DBL PANE
ZONE II
28
Window Left
(South)
4.0
0.650
0.40
180
90 DEFAULT DBL PANE
ZONE II
29
Window Left
(South)
4.0
0.650
0.40
180
90 DEFAULT DBL PANE
ZONE II
INTERIOR AND EXTERIOR SHADING
Window
Overhang Left Fin
Right Fin
#
Exterior Shade Type
SHGC
Hgt.
Wd.
Len. Hgt. LExt. RExt. Dist. Len.
Hgt. Dist. Len. Hgt.
1
Bug Screen
0.76
8.0
20.0
7.0
0.1 2.0 2.0
2
Bug Screen
0.76
3
Bug Screen
0.76
8.0
6.0
7.0
0.1 2.0 2.0
4
Bug Screen
0.76
1.5
6.0
7.0
0.1 2.0 2.0
5
Bug Screen
0.76
8.0
2.0
7.0
0.1 2.0 2.0
6
Bug Screen
0.76
1.5
2.0
7.0 -0-1
2.0 2.0
7
Bug Screen
0.76
8
Bug Screen
0.76
9
Bug Screen
0.76
10
Bug Screen
0.76
11
Bug Screen
0.76
12
Bug Screen
0.76
13
Bug Screen
0.76
14
Bug Screen
0.76
15
Bug Screen
0.76
8.0
6.0
4.0
0.1 4.0 4.0
16
Bug Screen
0.76
1.5
6.0
4.0
0.1 4.0 4.0
17
Bug Screen
0.76
18
Bug Screen
0.76
19
Bug Screen
0.76
20
Bug Screen
0.76
21
Bug Screen
0.76
22
Bug Screen
0.76
23
Bug Screen
0.76
24
Bug Screen
0.76
25
Bug Screen
0.76
26
Bug Screen
0.76
27
Bug Screen
0.76
28
Bug Screen
0.76
29
Bug Screen
0.76
EnergyPro 3.1 Rv FnarnvSnft User Number: 5553 Job Number: BU- LQ 2K2 Page:9 of 23 1
J
Computer Method Summary
' ' (Part 2 of 3) C -2R ..
MIKE & BARBARA BUTVIDAS
8/3/02
'Project Title
Date
' FENESTRATION SURFACES
U-
Act. Glazing Type
Location/
# Type Area"
Factor
SHGC
Azm. Tilt
Comments
_ + > _3.0. Window Left (.S.outh) 4...0-
_0.6.50_
—0.40_
1.8.0_ _9.0. DEEAULT_DBL-P_ANE-ZONELI
•31 Window Left South 15.5
0.650
0.48
180 90 WECK GLASS BLOCK 8x8x4
ZONE II
32 Window Rear West). 2.2
0.650
0.40
270 90 DEFAULT DBL PANE "
ZONE II
33 Window RearWest , 20.0
0.650
0.40
270 90 DEFAULT DBL PANE
ZONE II
34 Window Rear West)- 20.0
0.650
0.40
270 90 DEFAULT DBL PANE
ZONE II
INTERIOR AND EXTERIOR SHADING
Window
Overhang Left Fin
Right Fin
L # Exterior Shade Type SHGC
Hgt.
Wd.
Len. Hgt. LExt. RExt. Dist. Len.
Hgt. Dist. Len. H
30 Bug Screen 0.76
-t.
,. 31 Bug Screen 0.76
!
• 32 Bug Screen 0.76
,
33 Bug Screen 0.76
••
34 Bug Screen 0.76
'
r
• — Y
Run Initiation Time_08/03102 11:54:06 Run Code: 1028400846
EnergyPro 3.1 By EneravSoft User Number: 5553 Job Number: BU- LQ 21<2 Page: 10 of 23
Computer Method Summary
Minimum
(Part 3 of 3) C -2R
Insulation
Type
MIKE & BARBARA BUTVIDAS
Factor
R -Val. Depth
118/3/02
Project Title
128
0.76
Date
THERMAL MASS FOR HIGH MASS DESIGN
Slab P_e.rimete.r
—90
016
Area Thick. Heat
ZONE -1.1
Inside
Location
Type (sf) (in.) - Cap.
Cond. Form 3 Reference
R -Val.
Comments
Concrete Heavyweight 1.,135. _3..5.0 —28.
_0..98. n/a
0_
ZONE_L/_SJab_o.n._Grade
Concrete,Heavyweight 939 3_50 28
0_98 n/a
2
ZONE II /.Slab on Grade
_C_oncrete, Hea_vyweigNt _238 -3A-0 28
0:98 n/a
0
ZONE II / Sleb_on Grade
PERIMETER LOSSES
HVAC SYSTEMS
Heating Equipment
Minimum
F2
Insulation
Type
Length
Factor
R -Val. Depth
Location / Comments
Slab Perimeter
128
0.76
0 Q 0
ZONE I
Slab P_e.rimete.r
—90
016
0.0. 0
ZONE -1.1
Slab Perimeter
35
0 76,
0_0 0
ZONE II
HVAC SYSTEMS
Heating Equipment
Minimum
Distribution Type
Type (furnace, heat
Efficiency
and Location
Duct Thermostat
Location /
pump, etc.) (AFUE/HSPF)(ducts/attic,
etc.)
R -Value Type
Comments
Central Furnace
80%AFUE
DuctsinAttic
4.2 Setback
ZONE I HVAC Split Gas/Elec
Central Furnace
801AFUE
Ducts in Attic
4.2 Setback
ZONE II HVAC Split Gas/Elec
Pipe
Insul.
Hydronic Piping Pipe
System Name Length
Diameter Thick.
Cooling Equipment
Minimum
Duct
Type (air conditioner,
Efficiency
Location
Duct Thermostat
Location /
heat pump, evap. cooling)
(SEER)
(attic, etc,)
R -Value Type
Comments
Split Air Conditioner
12_0 SEER
Ducts inAttic
4.2 SetbeGk
ZONE I HVAC Split GaS/mac
Split Air Conditioner
12.0 SEER
Ducts in Attic
4.2 Setback
ZONE II HVAC Split Gas/Elec
WATER HEATING SYSTEMS
Ratedl Tank
Energy Factl 1 Tank Insul.
Water Heater
Water Heater Distribution
# in Input Cap.
or Recovery Standby R -Value
System Name
Type
Type
Syst. (Btu/hr (gam
Efficiency Loss (%) Ext.
Standard Gas 50 gal or Less
Small Gas
Recirc/Time+Temp
1 40,000 50
0_52 n/a 12
1 For small gas storage (rated input — 75000 Btu/hr), electric resistance and heat pump water heaters, list energy factor.
For large gas storage water heaters (rated input > 75000 Btu/hr), list Rated Input, Recovery Efficiency and Standby Loss.
For instantaneous gas water heaters, list Rated Input, and Recovery Efficiency.
REMARKS
Computer. Method Summary (Addendum) C -2R
MIKE & BARBARA BUTVIDAS 8/3/02
Project Title Date
Special Features and Modeling Assumptions
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special
written justification and documentation, and special verification to be used with the performance approach. The local
enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies
based on the adequacy of the special justification and documentation submitted. I Plan I Field
The DHW System "Standard Gas 50 gal or Less" Energy Factor = 0.525. An EF below 0.58 requires an R-12 External Blanket.
The HVAC System "ZONE I HVAC Split Gas/Elec" includes credit for a Radiant Barrier installed per Section 8.13 of the Residential
Manu 1.
HIGH MASS Design(see C -2R) -Verify Thermal Mass: 1135 sqft Exposed Slab Floor, 3.50" thick at ZONE I
The HVAC System "ZONE II HVAC Split Gas/Elec" includes credit for a Radiant Barrier installed per Section 8.13 of the Residential
Manu 1.
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 939 sqft Covered Slab Floor, 3.50" thick at ZONE II
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 238 sqft Exposed Slab Floor, 3.50" thick at ZONE II
A
HERS Required Verification
These features must be confirmed and/or tested by a certified HERS rater under the supervision of a CEC approved HERS
provider. The HERS rater must document the field verification and diagnostic testing of these measures on a form CF -6R.
Plan
Field
The HVAC System "ZONE I HVAC Split Gas/Elec" is using reduced duct leakage to comply and must have diagnostic site testing of
duct leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
The HVAC System "ZONE II HVAC Split Gas/Elec" is using reduced duct leakage to comply and must have diagnostic site testing of
duct leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
Run Initiation Time: 08/03/02 11:54:06 Run Code: 1028400846
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page: 12 of 23
PROPOSED CONSTRUCTION ASSEMBLY ENV -3
(PROJECT NAME DATE
MIKE & BARBARA BUTVIDAS 8/3/02
DESC
W
D
W
0
Floor
TYPE
(check one)
Z
j
Wall
O
SKETCH OF ASSEMBLY
ASSEMBLY NAME
R-19 Wall W.19.2x6.16 1/2+5/8 GYP
ASSEMBLY
Floor
TYPE
(check one)
Wall
Ceiling
Ceiling I Roof
FRAMING MATERIAL
Wppd
FRAMING %
15 pyo
Framing %
15% (16" o.c. Wall)
12% (24" o.c. Wall)
10% (16" o.c. Floor/Cell.)
7% (24" o.c. Floor/Cell.)
I EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page: 13 of 23 1
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME
DATE
MIKE & BARBARA BUTVIDAS
8/3/02
SYSTEM NAME
FLOOR AREA
ZONE I HVAC Split Gas/Elec
1,135
EERING C
Number of Systems
1
Heating System
Output per System
53,000
Total Output (Btuh)
53,000
Output (Btuh/sqft)
46.7
Cooling System
Output per System
35,200
Total Output (Btuh)
35,200
Total Output (Tons)
2.9
Total Output (Btuh/sqft)
31.0
Total Output (sgft/Ton)
386.9
Air System
CFM per System
11200
Airflow (cfm)
-1,200
Airflow (cfm/sgft)
1.06
Airflow (cfm/Ton)
409.1
Outside Air (%)
0.0
Outside Air (cfm/sgft)
0.00
Vote: values above given at ARI condition's
EATING SYSTEM PSYCHROMETRICS
26.0 of 69.3 of 69.3 of
Outside Air
0 cfm
Supply Fan Heating Coil
1200 cfm
69.3 of
TEM LOAD
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I §ensiblel
Latent
I I CFM
I Sensible
23,997
293,707
175,925
412
17,595
0
14,685
880
0
0
0
0
0
0
0
0
0
14,685
880
323,077 175 925 19,354
York H4DH036S06/P3HUA053 U&H 0 66,395 53,000
Total Adjusted System Output o 66,395 53,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 pm Jan 12 am
:DOLING SYSTEM PSYCHROMETRICS (Ai
11.0 / 77.6 of 89.5 / 109.8 of 8f
Outside Air
0 cfm Supply Fan
1200 cfm
/109.8 of
Return Air Ducts
/ 109.8 of M 55.0 / 84.8 of
Cooling Coil
Supply Air Ducts
110.1oF
ROOMS
70.0 of
I
oling Peak)
—�j Supply Air Ducts '
66.5/87.2OF
288.9% R.H. ROOMS
78.0 / 108.4 of
h Return Air Ducts `S
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page: 14 of 23
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME
DATE
MIKE & BARBARA BUTVIDAS
8/3/02
SYSTEM NAME
FLOOR AREA
ZONE II HVAC Split Gas/Elec
1,177
Number of Systems
1
Heating System
Output per System
53,000
Total Output (Btuh)
53,000
Output (Btuh/sqft)
45.0
Cooling System
Output per System
35,200
Total Output (Btuh)
35,200
Total Output (Tons)
2.9
Total Output (Btuh/sgft)
29.9
Total Output (sgft/Ton)
401.2
Air System
CFM per System
1,200
Airflow (cfm)
1,200
Airflow (cfm/sqft)
1.02
Airflow (cfm/Ton)
409.1
Outside Air (%)
0.0
Outside Air (cfm/sgft)
0.00
Note: values above given at ARI conditions
EATING SYSTEM PSYCHROMETRICS (Airsl
26.0 OF 69.4 OF 69.4 OF =
Outside Air
0 cfm
69.4 OF
111.0 / 77.6 OF
Outside Air
0 cfm
78.6/65.2 °F
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensiblel
Latent
I I CFM
I Sensible
793
14,963
475
330
14,201
0
748
710
0
0
0
0
0
0
0
0
0
748
710
16, 1 15,621
York H4DH036S06/P3HUAO53 U&H 24,136 7,392
Total Adjusted System Output 2x,136 7,392
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK I Aug 2 pm
110.90F
Supply Fan Heating Coil
1200 cfm
78.6 / 65.2 OF
Rcf.irn Air r)i..fc
78.6 / 65.2 OF . 59.7 / 58.6 OF
Supply Fan Cooling Coil
1200 cfm
K Return Air Ducts `S
53,000
53,000
Jan 12 am
Supply Air Ducts
110.4 OF
ROOMS
70.0 OF
Supply Air Ducts
60.3 / 58.8 of
50.1% R.H. ROOMS
78.0 / 65.0 OF
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page:15 of 23
ROOM LOAD SUMMARY
PROJECT NAME
DATE
MIKE & BARBARA BUTVIDAS
8/3/02
SYSTEM NAME
FLOOR AREA
ZONE I HVAC Split Gas/Elec
1,135
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
ZONE[
ZONEI
1
23,997
293,707
175,925
23,997
293,707
175,925
412
17,595
PAGE TOTAL 1 23,997 293,707 175,925 412 17,595
TOTAL 1 23,997 293,707 175,925 412 17,595
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page: 16 of 23
ROOM LOAD SUMMARY
PROJECT NAME
MIKE & BARBARA BUTVIDAS
DATE
8/3/02
SYSTEM NAME
ZONE II HVAC Split Gas/Elec
FLOOR AREA
1,177
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
ZONE II
ZONE II
1
793
14,963
475
793
14,963
475
330
14,201
PAGE TOTAL 1 793 14,963 475 330 14,201
TOTAL 1 793 14,963 475 330 14,201
F77EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page: 17 of 23
ROOM HEATING PEAK LOADS
Project Title Date
MIKE & BARBARA BUTVIDAS 8/3/02
Room Information Design Conditions `
Room Name ZONE I Time of Peak Jan 12 am ,
Floor Area .. 1,135 Outdoor Dry Bulb Temperature 26OF
Indoor Dry Bulb Temperature , 70OF
Conduction Area U -Value LT of Btu/hr
•1035.0
X
X
X
x
x,
x'
X
x
x
X
x
X
x
X
X
x
x
X
x
X
x
x
X•
x
X
X
X
x
x
X
x
x
X
x
X
x
x
x ."
X
0.0241
X
x
X
X .
x
X
X
x
x
X•
x
X
x'
X
X
- x'
x
X
X
X
X
X
aX
x
X
X
X
X
x
X
* x
X
X
x
X
X
X
x
x
44.0
. =
=
=
=
=
=
= .
=
_
_
_
_
=
_
_
=
=
_
=
=
=
_
—
_
_
=
=
—
1,201
.
perimeter = 128.0
44.5
'5,696
877.5
0.0453
44.0
i�. 1,749
273.0
0.6500
44.0
7,808
289.3
0.0597
44.0
760
17.7
0.3872
44.0
302
2.8
0.6500
44.0
79
+
2
.
v
I
i
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 17 595
Infiltration: 1.00 x ,1.064 X1 135 X 11.00 X 0100 / 60] X 44 = 0
—Schedule Air Sensible Area Ceiling Height ACH AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 17,595
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page: 18 of 23
i
Project Title Date
MIKE &BARBARA BUTVIDAS 8/3/02
Room Information Design Conditions {
Room Name ZONE II Time of Peak Jan 12 am
Floor Area 1,177 Outdoor Dry Bulb Temperature 26OF
Indoor Dry Bulb Temperature 70 OF
R-38 Roof (R.38.2x4.24)
Slab -On -Grade
_all_w/-1 EP_S
DEFAULT DBL PANE
WECK, GLAS.S_BLO.CK-8x8x4
1177.0
X
X
X
x
X
x:
X
x
X
xx
x
X
x
x
x
X
x
X
x
x
X
x
X
X
X
x
x
X
x
X
X
x
X
X
x
x
X
x
X
- 0.0241
X
x
x
X
X
x
X
x
X
x
x
x
X
x
x
X
X
x
x
x
x
X
x
X
X'
X
X
X
x
X
X
X
X
x
x
X
x
x
44.0
=
=
=
=
=
=
=
=
=
=
=
_
=
=
=
=
_
=
=
=
=
=
1246
perimeter = 125.0
44.5
5,562
1,197.1
0.0453
44.0
2,386
159.6
0.6500
44.0
4,563
15.5
0.6500
44.0
443
'
Items shown with an asterisk (')denote conduction through an interior surface to another room. Page Total: 14 201
Infiltration: L 1.001 x ensibl x 1 177 x 11.00 x 0.00 / 6] x 0 = 0
Schedule Air Sensible Area Ceiling Height ACH AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 14,201
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2Q Page: 19 of 23
RESIDENTIAL ROOM COOLING LOAD SUMMARY
MIKE & BARBARA BUTVIDAS 8/3/02
Project Title Date
,Room Name ZONE
Design Indoor Dry Bulb Temperature:
Design Outdoor Dry Bulb Temperature:
Design Temperature Difference:
780E
112°F
340F
Conduction Area U -Value DETDBtu/hr
X
X
X
X
X
X
1,135..
X
1,392
877.5
X
34.0
273.0
X
529
289.3
X
34.01
17.7
X
( 33.0
2.8
X
0.445
708
X
0.0
73)
x
60
( 11.0
X
X
X
X
X
X
X
51.0
=
=
=
=
=
=
1,392
30.6
1,217
34.0
6,033
30.6
529
30.6
210
34.01
61
X
X
X
1. Design Equivalent Temperature Difference (DETD) Page Total 9441
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Shaded. Unshaded
Solar Gain Orientation Area SGF Area SGF Sc 'Btu/hr
Wind # 1, 2080 FIX
Wind_#2,201.6_F_IX
_(East)
(East
Wind #3,6080 FR.DR.
_ East
Wind #4,6016 FIX.
(East)
Wind #5,2080 FIX
(East)
Wind #6,2016 FIX "
(East)
Wind #7,2020 FIX
_East
Wind #8,2020 FIX
Wind #9,2080 FIX
Wind #10 2016 FIX
_ East)
(South)
(South
( 11.0
X
X
X
x
X
X
x
x
x
xi
15,+
15 +
15 +
15 +
151+
15 +
15 +
15 +
- 15 +
15 +
5.0
X
X
X
X
X
X
X
X
X
x
73)
X
X
x
X
x
X
X
X
) x
X
0.445
=
=
=
=
=
=
=
=
__
=
236
( 0.0
r-3.0
73)
0.445
98
( 33.0
15.0
73)
0.445
708
( 9.0
0.0
73)
0.445
60
( 11.0
5.0
73)
0.445
236
(' 3.0
0.0
73)
0.445
20
( 0.0
4.0
73)
0.445
130
( 0.0
4.0
73)
0.445
130
( 0.0
16.0
32
0.445
228
( 0.0
3.0
32)
0.445
43
Sched. ;
Page Total1 888
Internal Gain Frac. Area Heat Gain Btu/hr
Lights 1.00"1,135 X 0.000 Watts/sgft x 3.413 Btuh/Watt = 0
Occupants 1.00 X 1,135 X 245 Btuh/occ. / 1 sgft/occ. = 278,075
Receptacle 1.00 x 1,135 x 0.500 Watts/sqft X 3.413 Btuh/Watt = 1,937
Process 1.00 x 1,135 x 0.000 Watts/sgft x 3.4133 Btuh/Watt = 0
Infiltration: [L-1---001 x 1..064 x 1.,1.35 x U_ QO , x O..QO / 60] 1341 = I D I
Schedule Air Sensible Area Ceiling Height ACH nT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 293,7071
Sched. ,
Latent Gain Frac. Area Heat Gain - Btu/hr
Occupants 1.00 X 1 135X' 1551 Btuh/occ. /. 1 sgft/occ. = 175925
Receptacle 1.00 X 1 135 x 0.000 Watts/sqft x 3.413 Btuh/Watt = 0
Process 1.00 X 1,135 X 0.000 Watts/sqft X 3.413 Btuh/Waft = 0
Infiltration: 1 1.00 X 4,7711! X [:::::1-135 X 11.00 X 0.00 / 60] 1 0.00000 =
Schedule Air Latent Area Ceiling Height ACH pyy
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 175,925
EnergyPro 3.1 By EnergySoft . User Number: 5553 Job Number: BU- LQ 21<2 Page: 20 of 23
RESIDENTIAL ROOM COOLING LOAD SUMMARY
MIKE & BARBARA BUTVIDAS 8/3/02
Project Title Date
Room Name
Design Indoor Dry Bulb Temperature:
Design Outdoor Dry Bulb Temperature:
Design Temperature Difference:
Conduction
Area U -Value
X
DETD1
ZONE
78°F
112°F
340F
Btu/hr
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total 0
Shaded Unshaded
Solar Gain Orientation Area SGF Area SGF Sc Btu/hr
Wind #11 6080 FR. DR.
Wind_#1.2-6.01.6_F_D
_(South)
_ SouthL
Wind #13 2080 FIX
(South
Wind #14, 2016 FIX
(South)
Wind #15, 6080 FR.DR.
(West)
Wind #16 6016 FIX.
(West)
Wind #17, 4030 XO.
Wind #18, 4016 FIX.
Wind #19, 66NOV
(North)
(North)
(North)
32)
0.445
( 0.0
X
X
X
x
X
x
x
x
x
X
15 +
15 +
15 +
15 +
15 +
15 +
151+
15 +
15+
+
48.0
X
x
x
x
x
X
X
X
X
X
32)
x
x
X
x
X
X
X
X
x
)X
0.445
=
=
=
=
=
=
=
=
__
=
684
( 0.0
9.0
32)
0.445
128
( 0.0
16.0
32)
0.445
228
( 0.0
3.0
32)
0.445
43
( 18.6
29.4
73)
0.445
1,080
( 9.0
0.0
73)
0.445
60
( 0.0
12.0
15)
0.445
80
( 0.0
6.0
15)
0.445
40
( 0.0
2.8
15)
0.534
22
(
Sched.
Page Total 2 365
Internal Gain Frac. Area Heat Gain Btu/hr
Lights 1.00 x 1,135 X 0.000 Watts/sgft X 3.413 Btuh/Watt = 0
Occupants 1.00 X 1,135 x 245 Btuh/OCC. / 1 sgft/occ. = 278,075
Receptacle 1.00 x 1,135 x 0.500 Watts/sgft X 3.413 Btuh/Waft = 1,937
Process 1.00 X 1,135 x 0.000 Watts/sgft x 3.413 Btu��h/Watt = 0
Infiltration: 1..00 x 1_.06.4 x=:1-1 -35 x 11..0.0 x Q.t)0 / 60] �34J = [:::=o
Schedule Air Sensible Area Celling Height ACH pT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 293,707
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 X 1,135x 1551 Btuh/OCC. / 1 sgftlocc. = 175 925
Receptacle 1.00 X 1 135 x 0.000 Watts/sgft X 3.413 Btuh/VVatt = 0
Process 1.00 x 1,135 x 0.000 Watts/sgft X 3.413 BtuhfWatt = 0
Infiltration: [ 1.00 x 4 Air Latent nArea x 1 135 x Ceiling Height
t x ACH 0.00 60] 0.00000 =
Schedule c�lW
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 175,925
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 2K2 Page: 21 of 23
RESIDENTIAL ROOM COOLING LOAD SUMMARY
MIKE & BARBARA BUTVIDAS 8/3/02
Project Title f Date „
,I
Room Name ZONE II
Design Indoor Dry Bulb Temperature: 78°F
Design Outdoor Dry Bulb Temperature: d_ 112�F
Design Temperature Difference: 340F.
Conduction Area U -Value DETD 1 Btu/hr
X
X
X
X
X
X
X
X
X
1,177.0
X
1,444
1,197.1
X
34.0
159.6
X
343
15.5
,X .
(South)
South)
0.445
X
( 0.0
16.0
X
0.445
520
X
3.0
.73)
x
98
( 0.0
X
X
X
X
X
X
X
X
X
X
51.0
=
=
=
=
=
=
=
=
=
1,444
•30.6
1,660
34.0
" 3.526
34.0
343
-(ELS-9-
EastWind
Wind #28, 2020 FIX.
Wind #29 2020 FIX.
(South)
South)
0.445
260
( 0.0
16.0
73)
0.445
520
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room 1 Page Total 6 972
Shaded Unshaded
Solar Gain Orientation Area SGF Area SGF SC Btu/hr
Wind #20,1616 FIX.
Wind_#_21 4.020_X0.
Wind #22 2080 FIX.'
_(East
(East
(East
Wind #23 2016 FIX.
Wind #24, 6080 FR. DR. f
_(East
(East)
Wind #25.6016 FIX.
(East)
Wind #26, 2080 FIX ,E
_(East).
Wind #27, 2016 FIX
-(ELS-9-
EastWind
Wind #28, 2020 FIX.
Wind #29 2020 FIX.
(South)
South)
( 0.0
X
X
x
x
X
X
X
x
X
15+
15 +
15 +
151+
15 +
15 +
19,+
15 +
11. +
•`'. 15 +
, 2.3
X
X
X
X
X
X
X
X
X
X.
73)
X
X
X
X
X
X
X
X
x
x
0.445
=
=
=
=
=
=
=
=
=
_
75
( 0.0
8.0
73)
0.445
260
( 0.0
16.0
73)
0.445
520
( 0.0
3.0
.73)
0.445
98
( 0.0
48.0
73)
0.445
1,560
( 0.0
. 9.0
73)
0.445
293
( 0.0
16.0
73)
0.445
520
( 0.0x
3.0
73)
0.445
98
( 0.0
4.0
32)
0.445
57
( 0.0
4.0
32)
0.445
57
Sched. Page Total 3 531
Internal Gain Frac. Area Heat Gain Btu/hr
Lights 1.00 x 1,177 X - 0.000 •Watts/sqft X 3.413 Btuh/Watt = 0
Occupants 1.00 X 1,177 X' 245 Btuh/OCC. / 384 sqft/occ. _ { 750
Receptacle 1.00 z 1,177 x 0.500 Watts/Sgft X 3.413 Btuh/Watt = ''2,009
Process 1.00 x 1,177 x 0.000 Watts/sgft x 3.4133 Btuh/Watt = 0
Infiltration: 1...00 x 1..0641+x 1.,1.7.7 x 1.1..00 x 0.00 •/ 60] . - 341 = . p
Schedule Air Sensible Area Ceiling Height ACH pT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 14 963
r
Sched. r
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 x 1,177 X 155 Btuh/OCC. / 384 sgft/oC'C. = 475
Receptacle 1.00 X 1,177 X 0.000 Watts/sqft X 3.413 Btuh/Watt = 0
Process 1.00 X 1,177 X 0.000 Watts/sgft, X 3413 BtuhfWatt = 0
Infiltration: [ 1.00 x 4,771 J x 1,17' x 11.00 x - 0.00 /60 ' 0.00000 = } 0
Schedule Air Latent Area Ceiling Height ACH pyy
Fraction �
TOTAL HOURLYLATENT HEAT GAIN FOR ROOM 475
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 21<2 Page: 22 of 23
RESIDENTIAL ROOM COOLING LOAD SUMMARY
MIKE & BARBARA BUTVIDAS 8/3/02
Project Title Date
Room Name
Design Indoor Dry Bulb Temperature:
Design Outdoor Dry Bulb Temperature:
Design Temperature Difference:
ZONE II
780F
112°F
34°F
Conduction Area U -Value DETD 1 Btu/hr
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Page Total 1 01
Shaded Unshaded
Solar Gain Orientation Area SGF Area SGF SC Btu/hr
Wind #30,2020 FIX. _(South) 0.0 x 1,+ 4.0 x 32) x 0.445 = 57
Wind -#39.,4.83-4 GL.RLK. _ South ( 0.0 x 15,+ 15.5 x 32) x 0.534 = 265
Wind #32,1616 FIX _ West ( 0.0 x 1,+ 2.2 X 73) x 0.445 = 73
Wind #33 5040 XO _((Wes) ( 0.0 x 11+ 20.0 X 73)x 0.445 = 650
Wind #34, 5040 XO (West) ( 0.0 x 15 + 20.0 X 73) x 0.445 = 650
( x + x )x =
( x + x )x =
( x + x )x =
( x + x )X =
11 _J(l x + I x )X =
Sched.
Page Total1 695
Internal Gain Frac. Area Heat Gain Btu/hr
Lights 1.00 x 1,177 X 0.000 Watts/sgft X 3.413 Btuh/Watt = 0
Occupants 1.00 X 1 177 X 245 Btuh/OCc. / 384 Sgft/OCC. = 750
Receptacle 1.00 x 1,177 x 0.500 Wafts/sqft x 3.413 Btuh/Waft = 2,009
Process 1.00 x 1,177 X 0.000 Waw/Sgft x 3.413BtuhhfW1att = 0
Infiltration: [ 1..Q0 x 1_Q6_4 x E:7, 7,7_71 x 11..Q0 x 0..0.0 /6q] E��_341 = l 01
Schedule Air Sensible Area Ceiling Height ACH pT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 14,9631
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 X 1,177 x 155 Btuh/OCC. / 384 sgft/occ. = 475
Receptacle 1.00 X 1 177 X 0.000 Watts/sqft X 3.413 Btuh[Watt = 0
Process 1.00 x 1 177 x 0.000 Watts/Sgft x 3.413 Btuh/Waft = 0
Infiltration: [ 1.00 X L 4,771' X 1 1 X 11.00 X 0.00 / 60] 0.00000 =
Schedule Air Latent Area Ceiling Height ACH pyy
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 475
EnergyPro 3.1 By EnergySoft User Number: 5553 Job Number: BU- LQ 21<2 Page: 23 of 23