BRES2014-1081Applicant: Contractor:
MONARCH HOMES MONARCH HOMES
49950 JEFFERSON STREET 49950 JEFFERSON STREET
LA QUINTA, CA 92264 LA QUINTA, CA 92264
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that I am I' d under provisions of Chapter
9 (commencing with Section 7000) of Division a siness and Professions Code,
and my License is in full force and effect.
License Class: License No.: C28860
Date: V Contractor:
I 4r
rJLIsT %Aca
OWNER -BUILDER CLARA
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State
License Law for the following reason (Sec. 7031.5, Business and Professions Code: Any
city or county that requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for the permit to file a
signed statement that he or she is licensed pursuant to the provisions of the
Contractor's State License Law (Chapter 9 (commencing with Section 7000) of Division ?
of the Business and Professions Code) or that he or she is exempt therefrom and the
basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a
permit subjects the applicant to a civil penalty of not more than five hundred dollars
($500).:
(_) I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for sale.
(Sec. 7044, Business and Professions Code: The Contractors' State License Law does not
apply to an owner of property who builds or improves thereon, and who does the work
himself or herself through his or her own employees, provided that the improvements'
are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner -builder will have the burden of proving that
he or she did not build or improve for the purpose of sale.).
(_) I, as owner of the property, am exclusively contracting with licensed contractors
to construct the project. (Sec. 7044, Business and Professions Code: The Contractors'
State License Law does not apply to an owner of property who builds or improves
thereon, and who contracts for the projects with a contractor(s) licensed pursuant to
the Contractors' State License Law.).
(_) I am exempt under Sec: , B.&P.C. for this reason
Date
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that.there is a construction lending agency for
the performance of the work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's
Lender's
(760)413-8863
Llc. No.: C28860
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided for by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
I have and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which this permit
is issued. My workers' compensation insurance carrier and policy number are:
Carrier: _ Policy Number:
I certify that in the performance of the work for which this permit is issued,
shall not employ any person in any manner come subject to the workers'.
compensation laws of California, and agr th , if I sh Ld become subject to the .
workers' compensation provisions of S ction 3 0 o e L bor Code, I shall forthwith
comply with those provisions.Date. 21 p
WARNING: FAILURE TO SECURE WORKERS' CCOMPC1VSATION COVERAGE IS UNLAWFUL,
AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO
ONE HUNDRED THOUSAND DOLLARS ($100,000). IN ADDITION TO THE COST OF
COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE,
INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT: Application is hereby made to the Building Official for a permit subject to
the conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose
request and for whose benefit work is performed under or pursuant to any permit
issued as a result of this application , the owner, and the applicant, each agrees to, and
shall defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and
employees for any act or omission related to the work being performed under or
following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is
notcommenced within 180 days from date of issuance of such permit, or cessation of
work for 180 days will subject permit to cancellation.
I certify that I have read this application and state thatMins correct.
I agree to comply with all city and county ordinances ao building
construction, and hereby authorize representatives of he above-
mentioned property for inspection purposes.
Dat/2�Signature (Applicant or Agen
0 Nvw.rr D
✓ .,.- - - '^ fry, ; J..�
f
VOICE (760) 777-7125
78-495 CALCE TAMPICO
0
D
LA QUINTA, CALIFORNIA 92253
COMMUNI I DEVFRPMEN
FAX (760) 777-7011
NT INSPECTIONS (760) 777-7153
8
W"D T
-
,1AIV� F �r,5
Date: 1/21/2015
Application Number: BRES2014-1081
Owner:
Property Address: 80110 VIA CAPRI .
p y
ROBERT MCDONALD
APN: 777100065 �
COMMUNITY
11 L mEENT DEPARTMENT
2110 A BOCA RATON NO 206 .
Application Description: MC DONALD RESIDENCE
NEW SFD
AUSTIN, TX 0
Property Zoning:
Application Valuation: $586,195.50
Applicant: Contractor:
MONARCH HOMES MONARCH HOMES
49950 JEFFERSON STREET 49950 JEFFERSON STREET
LA QUINTA, CA 92264 LA QUINTA, CA 92264
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that I am I' d under provisions of Chapter
9 (commencing with Section 7000) of Division a siness and Professions Code,
and my License is in full force and effect.
License Class: License No.: C28860
Date: V Contractor:
I 4r
rJLIsT %Aca
OWNER -BUILDER CLARA
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State
License Law for the following reason (Sec. 7031.5, Business and Professions Code: Any
city or county that requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for the permit to file a
signed statement that he or she is licensed pursuant to the provisions of the
Contractor's State License Law (Chapter 9 (commencing with Section 7000) of Division ?
of the Business and Professions Code) or that he or she is exempt therefrom and the
basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a
permit subjects the applicant to a civil penalty of not more than five hundred dollars
($500).:
(_) I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for sale.
(Sec. 7044, Business and Professions Code: The Contractors' State License Law does not
apply to an owner of property who builds or improves thereon, and who does the work
himself or herself through his or her own employees, provided that the improvements'
are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner -builder will have the burden of proving that
he or she did not build or improve for the purpose of sale.).
(_) I, as owner of the property, am exclusively contracting with licensed contractors
to construct the project. (Sec. 7044, Business and Professions Code: The Contractors'
State License Law does not apply to an owner of property who builds or improves
thereon, and who contracts for the projects with a contractor(s) licensed pursuant to
the Contractors' State License Law.).
(_) I am exempt under Sec: , B.&P.C. for this reason
Date
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that.there is a construction lending agency for
the performance of the work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's
Lender's
(760)413-8863
Llc. No.: C28860
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided for by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
I have and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which this permit
is issued. My workers' compensation insurance carrier and policy number are:
Carrier: _ Policy Number:
I certify that in the performance of the work for which this permit is issued,
shall not employ any person in any manner come subject to the workers'.
compensation laws of California, and agr th , if I sh Ld become subject to the .
workers' compensation provisions of S ction 3 0 o e L bor Code, I shall forthwith
comply with those provisions.Date. 21 p
WARNING: FAILURE TO SECURE WORKERS' CCOMPC1VSATION COVERAGE IS UNLAWFUL,
AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO
ONE HUNDRED THOUSAND DOLLARS ($100,000). IN ADDITION TO THE COST OF
COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE,
INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT: Application is hereby made to the Building Official for a permit subject to
the conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose
request and for whose benefit work is performed under or pursuant to any permit
issued as a result of this application , the owner, and the applicant, each agrees to, and
shall defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and
employees for any act or omission related to the work being performed under or
following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is
notcommenced within 180 days from date of issuance of such permit, or cessation of
work for 180 days will subject permit to cancellation.
I certify that I have read this application and state thatMins correct.
I agree to comply with all city and county ordinances ao building
construction, and hereby authorize representatives of he above-
mentioned property for inspection purposes.
Dat/2�Signature (Applicant or Agen
0 Nvw.rr D
t
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT'' PAID PAID DATE
ART IN PUBLIC PLACES - RESIDENTIAL 270-0000-43201 0 $965.49
$965.49 1/21/15
PAID BY METHOD RECEIPT #
CHECK # CLTD BY
MONARCH HOMES CHECK R3454
6003 MFA
Total Paid'forART IN PUBLIC PLACES - AIPP: $965.49 $965.49
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
BSAS S131473 FEE
101-0000-20306
0
$24.00
$24.00
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
Total Paid for BUILDING STANDARDS ADMINISTRATION BSA $24.00 $24.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT"
PAID
PAID DATE
DIF - CIVIC CENTER
252.0000-43200
0
$942.00
$942.00 •
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
DIF - COMMUNITY CENTERS
254-0000-43200
0
$129.00
$129.00
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
DIF - FIRE PROTECTION
257-0000-43200
0
$433.00
$433.00
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
DIF - LIBRARIES
253-0000-43200
0
$344.00
$344.00
1/21/15
PAID BY
METHOD
RECEIPT #
' CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
DIF _ PARK MAINTENANCE
256-0000-43200
0
$40.00
$40.00
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
DIF - PARKS/REC
251-0000-43200
0
$2,048.00
$2,048.00
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
„ DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
DIF - STREET MAINTENANCE
255-0000-43200
0
$116.00.
$116.00
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #"
CLTD BY'
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
DIF - TRANSPORTATION
250-0000-43200
0
$2,842.00
$2,842.00
1/21/15
PAID BY
METHOD
- RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
Total Paid for DIF - SINGLE FAMILY DWELLING: $6,894.00 $6,894.00
DESCRIPTION r
ACCOUNT.
QTY
AMOUNT
PAID "
PAIDMATE
TEMP POWER SERVICE
101-0000-42403
0
$23.83
$23.83
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
' CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
TEMP POWER SERVICE PC
101-0000-42403
0
$16.68
$16.68
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
Total Paid for ELECTRICAL: $40.51 $40.51
DESCRIPTION
ACCOUNT �
QTY
AMOUNT
PAID
PAID DATE
RESIDENTIAL, EA ADDITION 1,000SF
101-0000-42403
0
$85.12
$85.12
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RESIDENTIAL, EA ADDITION 1,000SF, PC
101-0000-42600
0
$35.07
$35.07
1/21/15
PAID BY.
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION •
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RESIDENTIAL, FIRST 1,000SF
101-0000-42403
0
$143.00
$143.00
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
• 6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RESIDENTIAL, FIRST 1,000SF, PC
101-0000-42600
0
$47.19
$47.19
1/21/15
PAID BY
METHOD
RECEIPT #;
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
Total Paid for ELECTRICAL - NEW CONSTRUCTION: i $310.38 $310.38
DESCRIPTION '
ACCOUNT
QTY
AMOUNT
PAID
'PAID DATE
RESIDENTIAL FINISH GRADING PC
101-0000-42600 I.
0
$143.00
$143.00
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
Total Paid forGRADING: $143.00 $143.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
AIR HANDLER
101-0000-42402
0
$71.50
$71.50
1/21/15
PAID BY
METHOD
RECEIPT#-
CHECK #
CLTD"BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
AIR HANDLER PC
101-0000-42600
0
$23.84
$23.84
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCR PTION
ACCOUNT
Q
AMOUNT
PAID
PAID E
CONDENSER/COMPRESSOR
101-0000-42402
0/
$214.50
$214.50
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID • "
-PAID DATE
CONDENSER/COMPRESSOR PC
101-0000-42600
0
$142.98
$142.98
1/21/15 '
PAID BY,.
METHOD
RECEIPT #
CHECK #
CLTD BY .
MONARCH HOMES
CHECK
R34S4
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT-
PAID
PAID,DATE
EXHAUST HOOD
101-0000-42402
0
$11.92
$11.92
1/21/15
PAID BY
a METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R34S4
6003
MFA
DESCRIPTION ,
ACCOUNT
QTY'
AMOUNT
-PAID
PAID DATE
EXHAUST HOOD PC
101-0000-42600
0
$4.77
$4.77
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID'DATE.
FURNACE
101-0000-42402
0
$214.50
$214.50
1/21/15
PAID BY
METHOD
RECEIPT .#
CHECK #
CLTD BY,
MONARCH HOMES
CHECK
R34S4
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
FURNACE PC
101-0000-42600
0
$142.98
$142.98
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK # ,
CLTD BY
MONARCH HOMES
CHECK
R34S4
6003
MFA .
DESCRIPTION
ACCOUNT
QTY
AMOUNT-
, PAID
PAID DATE
VENT FAN'
101-000042402
0
$143.04
$143.04
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID .•
,PAID DATE
VENT FAN PC
101-0000-42600
0
$57.24
$57.24
1/21/15
PAID BY
METHOD '
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK `
R34S4
6003
MFA
Total Paid for MECHANICAL: $1,027.27 $1,027.27
DESCRIPTION -
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
NEW CONSTRUCTION PERMIT
101-0000-42400
0
$790.15
$790.15
1/21/15
PAID BY
METHOD
RECEIPT,#
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA'
Total Paid forNEW CONSTRUCTION PERMIT: $790.15 $790.15
DESCRIPTION
b. ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
NEW CONSTRUCTION PLAN CHECK
101-0000-42600
0
$206.99
$206.99
1/21/15
PAID BY'- '
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
'6003
MFA
DESCRIPTION
ACCOUNT..
QTY
AMOUNT
PAID
PAID DATE
NEW CONSTRUCTION PLAN CHECK
101-0000-42600
0
$1,500.00
$1,500.00
8/5/14
PAID BY
METHOD
RECEIPT # ',
CHECK #' "'
CLTD BY
MONARCH HOMES
CHECK
R616
1652
SKH ,
Total Paid for NEW CONSTRUCTION PLAN CHECK: $1,706.99 $1,706.99
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
BACKFLOW DEVICE
101-0000-42401
0
$11.92 '
$11.92
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
BACKFLOW DEVICE PC
101-0000-42600
0
$4.77
$4.77
1/21/15
PAID BY
METHOD ,
-RECEIPT #
CHECK #
CLTD BY.
MONARCH HOMES
CHECK-
R3454
6003
MFA
DESCRIPTION
ACCOUNT i,
CITY'
AMOUNT 4
PAID
PAID DATE.
BUILDING SEWER
101-0000-42401
0
$11.92
$11.92
1/21/15
PAID BY =
METHOD
RECEIPT #
CHECK #
CLTD BY.
MONARCH HOMES
CHECK
R3454
6003
MFA
',DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
BUILDING SEWER PC
101-0000-42600
0
$11.92
$11.92
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY.
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
FIXTURE/TRAP
101-0000-42401
0
$357.60
$357.60
1/21/15
PAID BY
METHOD -
RECEIPT #"
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT -
.'PAID
PAID DATE
FIXTURE/TRAP PC
101-0000-42600
0
$357.60
$357.60
1/21/15
PAID BY
;METHOD
RECEIPT #,
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA'
DESCRIPTION
ACCOUNT
QTY"
AMOUNT
PAID
PAID DATE
GAS SYSTEM, S+ OUTLETS
101-0000-42401
0
$35.75
$35.75
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
GAS SYSTEM, 5+ OUTLETS PC
101-0000-42600
0
$23.83
$23.83
1/21/15
PAID BY
METHOD.
RECEIPT•# ,
CHECK #
CLTD BY.
MONARCH HOMES
CHECK `
113454
6003 _
MFA
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
WATER HEATER/VENT
101-0000-42401
0
$23.84
$23.84
1/21/15
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION
ACCOUNTQTY
AMOUNT
PAID
PAID DATE
+ WATER HEATER/VENT PC
101-0000-42600
U
$14.3014.30
1/21/15
PAID. BY �, �
METHOD
RECEIPT #�� <,
.% CHECK # ,_'"
:CLTD, BY.
' MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION',. : ' •'
ACCOUNT.:_
QTY
AMOUNT
PAID ` x
PAID DATE
WATER SYSTEM INST/ALT/REP
101-0000-42401
0
$11.92
$11.92
1/21/15
t.. PAID BYti
METHOD, '
RECEIPT #
CHECK #
CCTD BY -
MONARCH HOMES
CHECK
R3454
6003
MFA
DESCRIPTION ` _, .�
-, ACCOUNT;
3
,QTY':
='_ AMOUNT
PAID'
PAID.DATE
WATER SYSTEM INST/ALT/REP PC
101-0000-42600
0
$11.92
$11.92
.1/21/1S
PAID BY _ .. ':
METHOD
RECEIPT #,!
CHECK #_
CLTD BY
MONARCH HOMES
CHECK
R3454
6003
MFA
Total Paid for PLUMBING FEES: $877.29 $877.29
DESCRIPTION •'
ACCOUNT �:,a"
QTYF
AMOUNT `'
PAID:
PAID DATE.
SMI - RESIDENTIAL
101-0000-20308
0
$76.21
$76.21
1/21/15 ,
PAID BY *'
METHOD -
RECEIPT # :
CHECK # _
CLTD BY
MONARCH HOMES +
CHECK
R3454
6003
MFA
Total Paid forSTRONG MOTION INSTRUMENTATION SMI: .$76.21 $76.21
ES
DCRIPTION
ACCOUNT ,
'QTY
AMOUNT r,
PAID
PAID DATE
SINGLE FAMILY DETACHED
224-0000-20320
0
$1,837.44
$1,837.44
1/21/15
PAIDBY
METHOD •
'RECEIPT#
!CHECK #
CLTD.BY'.
MONARCH HOMES
CHECK
R3454
.6003
MFA
Total Paid forTUMF - RESIDENTIAL: $1,837.44 $1,837.44
TOTALS: $14,692.73 $14,02.73
i
• J
CALLED ALBERS CONST. @760-774-8787 PLANS READY TO
ISSUE. ITEMS NEEDED P.M. 10, SCHOOL FEES, GRAND DEED,
TELEPHONE CALL JIM JOHNSON. 1/13/2015 1/13/2015 HOA LETTER,GRADING PLAN NOT SIGNED, CONTRACTORS LIC.-
NEED
IC:NEED 5 TO BE UPDATED.
NAMETYPE
NAME
"ADDRESSI
CONTACTS
CITY
STATE
ZIP'
PHONE ::FAX EMAIL
APPLICANT-
ALBERS CONSTRUCTION CO INC
P 0 BOX 238
LA QUINTA
CA
92247
(760)771-9954
$15.00
CONTRACTOR
ALBERS CONSTRUCTION CO INC
P 0 BOX 238
LA QUINTA
CA
92247
(760)771-9954
Total Paid for BUILDING STANDARDS ADMINISTRATION
$15.00 $15.00
OWNER
JACLIN C. SMITH
302 E. WEDGEWOOD
SPOKANE
WA
99208
(760)771-9954
R3425
•
•
'DESCRIPTION"' "ACCOUNT ` QTY AMOUNT PAID =
PAID DATE RECEIPT #+ CHECK # METHOD:. 4=� PAID BY, r . CLTD
14
ART IN PUBLIC PLACES - 270-0000-43201 0 $382.17 $382.17
1/15/15 R3425 7021 CHECK JACLIN C. SMITH AZA
RESIDENTIAL
Total Paid forART IN PUBLIC PLACES - AIPP: $382.17 $382.17
BSAS SB1473 FEE
101-0000-20306
0
$15.00
$15.00
.1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
Total Paid for BUILDING STANDARDS ADMINISTRATION
$15.00 $15.00
BSA:
DIF - CIVIC CENTER
252-0000-43200
0
$942.00
$942.00
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
DIF -COMMUNITY
254-0000-43200
0
$129.00
$129.00
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
CENTERS
DIF - FIRE PROTECTION
257-0000-43200
0
$433.00
$433.00
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
DIF - LIBRARIES
253-0000-43200
0
$344.00
$344.00
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
DIF - PARK
256-0000-43200
0
$40.00
$40.00
1/15/15
R3425
7021.
CHECK
JACLIN C. SMITH
AZA
MAINTENANCE
DIF - PARKS/REC
251-0000-43200
0
$2,048.00'
$2,048.00
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA'
DIF - STREET
255-0000-432000
$116.00
$116.00
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
MAINTENANCE
Printed: Wednesday,.January 21, 2015 4:01:16 PM 2 of 6 C
SYS7Eh1S
Printed: Wednesday, January 21, 2015 4:01:16 PM 3 of 6
SYSTEMS
-.- ,----w-
---�-------------
JRECEIPT
"CHECK
. _
"PAID
DESCRIPTION
r :=ACCOUNT
QTY
AMOUNT
PAID
PAID
#
# '
METHOD
BY
{CBY
DIF - TRANSPORTATION
250-0000-43200
0
$2,842.00
$2,842.00
1/15/15
113425
7021
CHECK
JACLIN C. SMITH
AZA
Total Paid for DIF - SINGLE FAMILY DWELLING: $6,894.00 $6,894.00
TEMP POWER SERVICE
101-0000-42403
0
$24.17
$24.17
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
TEMP POWER SERVICE
101-0000-42403
0
$16.92
$16.92
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
PC
Total Paid forELECTRICAL: $41.09 $41.09
RESIDENTIAL, EA
101-0000-42403
0
$73.98
$73.98
1/15/15
R3425
7.021
CHECK
JACLIN C. SMITH
AZA
ADDITION 1,000SF
RESIDENTIAL, EA
101-0000-42600
0
$30.48
$30.48
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
ADDITION 1,000SF, PC
RESIDENTIAL, FIRST
101-0000-42403
0
$145.03
$145.03
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
1,000SF
RESIDENTIAL, FIRST
101-0000-42600
0
$47.86
$47.86
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
1,000SF, PC
Total Paid for ELECTRICAL- NEW CONSTRUCTION: $297.35 $297.35
RESIDENTIAL FINISH
101-0000-42600
0
$143.00
$143.00
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
GRADING PC
Total Paid forGRADING: $143.00 $143.00
CONDENSER/COMPRES
101-0000-42402
0
$181.30
$181.30
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
SOR
CONDENSER/COMPRES
101-0000-42600
0
$120.85
$120.85
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
SOR PC
EXHAUST HOOD
101-0000-42402
0
$24.18
$24.18
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
EXHAUST HOOD PC
101-0000-42600
0
$9.66
$9.66
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
FURNACE
101-0000-42402
0
$181.30
$181.30
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
FURNACE PC
101-0000-42600
0
$120.85
$120.85
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH,
AZA
VENT FAN
101-0000-42402
0
$72.54
$72.54
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
Printed: Wednesday, January 21, 2015 4:01:16 PM 3 of 6
SYSTEMS
DESCRIPTION
"-ACCOUNT
QTY'
AMOUNT
PAID t"
'
.PAID DATE
-RECEIPT
CHECK
METHOD
,PAID BY'w
CLTD
BY
x J
_-
r _.
�• 4
_.�
m
az „s
VENT FAN PC
101-0000-42600
0
$28.98
$28.98
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
Total Paid for MECHANICAL: $739.66 $739.66
MULTI -SPECIES
101-0000-20310
0
$1,292.00
$1,292.00
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
RESIDENTIAL 0-8 UNITS
Total Paid forMULTI-SPECIES RESIDENTIAL $1,292.00 $1,292.00
NEW CONSTRUCTION
101-0000-42400
0
$667.25
$667.25
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
PERMIT
Total Paid for NEW CONSTRUCTION PERMIT: $667.25 $667.25
NEW CONSTRUCTION
101-0000-42600
0
$1,428.60
$1,428.60
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
PLAN CHECK
ALBERS
NEW CONSTRUCTION',
101-0000-42600
0
$1,400.00
$1,400.00
10/22/14
R2311
3839
CHECK
CONSTRUCTION CO
SKH
PLAN CHECK
INC
NEW CONSTRUCTION
101-0000-42600
0
$28.60
$28.60
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
PLAN CHECK
"
Total Paid forNEW CONSTRUCTION PLAN CHECK: $2,857.20 $2,857.20
BACKFLOW DEVICE
101-0000-42401
0
$12.09
$12.09
'1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
BACKFLOW DEVICE PC
101-0000-42600
0
$4.83
$4.83
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
BUILDING SEWER
101-0000-42401
0
$12.09
$12.09
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
BUILDING SEWER PC
101-0000-42600
0
$12.09
$12.09
1/15/15
R3425
7021
CHECK,
JACLIN C. SMITH
AZA
FIXTURE/TRAP
101-0000-42401
0
$278.07
$278.07
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
FIXTURE/TRAP PC
101-0000-42600
0
$278.07
$278.07
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
GAS SYSTEM, 5+
101-0000-42401
0
$36.26
$36.26
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA '
OUTLETS
GAS SYSTEM, 5+
101-0000-42600
0
$24.17
$24.17
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
OUTLETS PC
WATER HEATER/VENT
101-0000-42401
0
$36.27
$36.27
1/15/15
R3425
7021
CHECK
JACLIN C. SMITH
AZA
Printed: Wednesday, January 21, 2015 4:01:16 PM A of 6
CRWIYSTEMS
I(/�� �I4^ "PO
�
Cv
P.O. BOX 1504 APPLICATION ONLY
Building i 78-495 CALLE TAMPICO
Address / Q LA QUINTA, CALIFORNIA 92253
Owner
L
Sfdcill(x= BUILDING: TYPE CONST. OCC. GRP.
Mailing o/v/4tpnl/}e. t! r�tt f 7 7 % - .' DO — o (,PS
Address.�js0 Sr -)O,/.?D A.P. Number
City 40 Zip ZZa ' qs) to 3 � -� 3 8 i Legal Description
.l
�I'D�
Contractor 8 � IME s Project Description
Addres
7 - q -a e11sa,J s -T 3
City Zip Tel.
__Pdf o tzo i) (03 s1-�o3$i
State Lic. City Sq. Ft. No. No. Dw.
& Classif. Lic. # Size Stories Units
Arch., Engr., New ❑ Add ❑ Alter ❑ Repair ❑ Demolition ❑
Designer
Address Tel.
lilt /_IP Jtatu
Lic. #
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm that I am licensed under provisions of Chapter 9 (commencing with Section 7000)
Of Division 3 of the Business and Professions Code, and my license is in full force and effect.
SIGNATURE DATE
OWNER -BUILDER DECLARATION
I hereby affirm that I am exempt from the Contractor's License Law for the following reason:
(Sec. 7031.5, Business and Professions Code: Any city or county which requires a permit to construct,
alter, improve, demolish, or repair any structure, prior to its issuance also requires the applicant for
such permit to file a signed statement that he is licensed pursuant to the provisions of the Contrac-
tor's License Law, Chapter 9 (commencing with Section 7000) of Division 3 of the Business and
Professions Code, or that he is exempt therefrom, and the basis for the alleged exemption. Any
violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of
not more than rive hundred dollars (S500).
O1, as owner of the property, or my employees with wages as their sole compensation, will do
the work, and the structure is not intended or offered for sale. (Sec. 7044, Business and Profes-
sions Code: The Contractor's License Law does not apply to an owner of property who builds or
improves thereon and who does such work himself or through his own employees, provided that
such improvements are not intended or offered for sale. If, however, the building or improvement
is sold within one year of completion, the owner -builder will have the burden of proving that he did
not build or improve for the purpose of sale).
❑ 1, as owner of the property, am exclusively contracting with licensed contractors to construct the
project. (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply
to an owner of property who builds or improves thereon, and who contracts for such projects with
a contractor(s) licensed pursuant to the Contractor's License Law)
❑ 1 am exempt under Sec. B. & P.C. for this reason
Date Owner
WORKER'S COMPENSATION DECLARATION.
I hereby affirm that I have a certificate of consent to self -insure, or a certificate of Worker's
Compensation Insurance, or a certified copy thereof. (Sec. 3800, Labor Code.)
Policy No. Company
❑ Copy is filed with the city. ❑ Certified copy is hereby furnished.
CERTIFICATE OF EXEMPTION FROM
WORKERS' COMPENSATION INSURANCE
(This section need not be completed if the permit is for one hundred dollars ($100) valuation
or less).
I certify that in the performance of the work for which this permit is issued, I shall not em
any person In any manner so as to become subject to Workers' Compensation laws of California.
Date Owner
NOTICE TO APPLICANT..- If, after making this Certificate of Exemption you should become
subject to the Workers' Compensation provisions of the Labor Code, you must forthwith
comply with such provisions or this permit shall be deemed revoked.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance of the work for
which this permit is issued. (Sec. 3097, Civil Code.)
Lender's Name
Lender's Address
This is a building permit when properly filled out, signed and validated, and is subject to
expiration if work thereunder is suspended for 180 days.
I certify that I have read this application and state that the above information is correct.
I agree to comply with all city and county ordinances and state laws relating to building
construction, and hereby authorize representatives of this city to enter the above-mentioned
property for inspection purposes.
Signature of applicant Date
Mailing Address
City, State, Zip
WHITE = BUILDING DEPARTMENT
Estimated Valuation
PERMIT
Plan Chk. Dep.
Plan Chk. Bal.
Const.
Mech.
Electrical
S.M.I.
Grading
Driveway Enc.
Infrastructure
TOTAL
INFORMATION
NAME:
PHONE:
AMOUNT
Sao • 0Z)
ZONE: BY:
Minimum Setback Distances:
Front Setback from Center Line
Rear Setback from Rear Prop. Line
Side Street Setback from Center Line
Side Setback from Property Line
FINAL DATE INSPECTOR
Issued by:
Validated by: —
Validation:
YELLOW = APPLICANT
Date Permit
PINK = FINANCE
Coachella Valley Unified School District
83-733 Avenue 55, Thermal, CA 92274
(760) 398-5909 — Fax (760) 398-1224
This Box For District Use Only
DEVELOPER FEES PAID
AREA:
AMOUNT ,
LEVEL ONE AMOUNT:
LEVEL TWO AMOUNT:
MITIGATION AMOUNT:
I COMMAND.AMOUNT:
DATE:
RECEIPT:
- CHECK #:
INITIALS
CERTIFICATE OF COMPLIANCE
California Education Code 17620)
Project Name: cDonald (The Hideaway) Date: January 21, 2015
Owner's Name: Phone No. 5l LP 3y- o3w/
Project Address: 80-110 Via Capri, La Quinta, CA 92253
Project Description:
APN: 777-100-065
Family Dwelling Unit
Tract #:
Lot #'s:
Type of Development: Residential iIXXI Commercial Industrial
Total Square Feet of Building Area: 6,613 Sq. Ft.
Certification of Applicant/Owners: The person signing certifies t e aFehal
information is correct and makes this statement under
penalty of perjury and further represents that he/she is authorized to t f of the owner/developer.
Dated: / Z/ _ l� Signature:
SCHOOL DISTRICT'S REQUIREMENTS FOR THE ABOVE PROJECT HAVE BEEN OR WILL BE SATISFIED IN
ACCORDANCE WITH ONE OF THE FOLLOWING: (CIRCLE ONE)
Education Code Gov. Code Project Agreement Existing Not Subject to Fee
17620 65995 Approval Prior to 1/1/87 Requirement
Number of Sq.Ft. 6,613 Sq. Ft.
Amount per Sq.Ft. $ 3.36
Amount Collected $ 22,219.68
Building Permit Application Completed: Yes/No
By: Elsa F. Esqueda, Director of Facilities and Maintenance
Certificate issued by: Leticia Torres, Facilities Analyst Signatur�:
Section 66020 of the Government Code asserted by Assembly Bill 3081, effective January 1, 1997, requires tha this I'strict provide (1) a written notice to the
project appellant, at the time of payment of school fees, mitigation payment or other exactions ("Fees"), of the 9 -day period to protest the imposition of these
Fees and (2) the amount of the fees. Therefore, in accordance with section 66020 of the Government code and other applicable law, this Notice shall serve to
advise you that the 90 -day protest period in regard to such Fees or the validity thereof, commences with the payment of the fees or performance of any other
requirements as described in section 66020 of the Government code. Additionally, the amount of the fees imposed is as herein set forth, whether payable at this
time or in whole or in part prior to issuance of a Certificate of Occupancy. As in the latter, the 90 days starts on the date hereof. This Certificate of
Compliance is valid for thirty (30) days from the date of issuance. Extension will be granted only for good cause, as determined by the School District, and up
to three (3) such extensions may be granted.
MV:c/Inydocs/de\•Iees/certilicate ul'compliance form updated 3-2007 11/2010
Ar
I
Recording Requested By
First American Title NHS
144-.11kHFP�`t ` U� ? f=i-)- ) I
Robert W. McDonald III
2110—A Boca Raton Dr. #20.6
Austin, Texas 78747
AVN: 777-100-065-5
TRA: 020=160
DOC # 2007-0450314
07/11/2007 08:00A Fee:10.00
.Page 1 of .2
Recorded in Official Records
County of Riverside
Larry W. Ward
Assessor, County Clerk 8 Recorder
I (VIII IIIIIII III.III
_ II IIII 1111111 111111 III VIII IIII IIII
S R U PAGE -SIZE DA MISC LONG RFD COPY
M A L 465 426 CO NCOR SMFNCHG EXAM
T: CTY UNI V
tihaCc \bore this line' is for IYiC n'ders (.!se.
TI K` UN t);?!(S;C;NI:P) GRAN't�R(S) 1: I:C•LARh:(S).
tJOCUMI-ATARY't`A\ IS S none tv o "pot sw)iIr,
_ (innilxilcd 011 R111 slue ur twolicrt!' conveyed, or
_ (:otiiIMVc l .,n bill \;duc I ss liin anel cnci"nhrancds rc•mainin!s :n 611w of
sale.
t
Unincorporncd arca __ Cit!- of La O.p? 1,-4
GRANT DEED
f'or valuable coils ider111IJ0n, receipI- of which is herebNr acknowledged,
L:SLIE P. MCDONALD
hercby GR N':['(S) to ROBERT W. NICDONALD III
the real propeny sitbated in the ( Curry of.Rivcrside, State of Califori .ia; more partaculad), ilCscribed as 17611>��s:
All of"Grantor's itit:erest in.and to:
.PARCEL 1:
I.vf 38/39 (the "Lot") of .Arnended 7'racf iNo. 29894-2, as Shciwrl on SUbdivision Map the "Map")
recorded on T.3cceniber 121 2002 in 13ook 327, Pages 56 to 88,.inclusive, of [flaps; in the office of IIIc
Riverside County Recorder of. Said country and shown on Grant Deed recorded as Instrument No.
2003.26092: of Official Recoals.
Grant .0cced reflects 1Pare I NI:crger.No- 2003 `113, as approved by the cit), of La C)Uulla.
PARCEL 2:
Non-cxdusivi (ascnu:nt for :access, ingress, cgreSs, drainage, rnaintcnancc, repairs aild For. Tither
purposes, all as described in (i) the Amended and Restated Declatatiiin of Coven nrs; Conditions and
Rcst.1,10,1crtls and Reservation of F"asenlents for. The Hideaway Owners .AssOciation (as amended or
supplemented, the "Declarat.ion"), recorded on Dccember 13,. 2002, as lnsrrument No. 2002-745939
of Official Records of 16,crside Cor. niy, California; and (i.i) "F'hc Supplementary Declaration of
tincxation of Property rccord6d on (March 21, 2003, as lstrurnent No. ?0037201647 of Official
Records of_Rivcrside County; Cali foruia.
r7CEIVED
I)aICd: )uric r U ?007.
Le re P. *McDonald NOV 212014
CITY OF to QUINTA
COMMUNITY DEVELOPMENT
SI'Al' S.S.
C DUIN]"N' W. FRAVIS-
10-
2'�s �Ie eve
-2,007, bef Ine m
orem sunhily appeired
per,
LESLIE P. MCDONALD,lj.cts'oi,411.kii(j,wiI to ffie. (6r'- proved to n!c;*o6-.the b4si of sacisfact' r evidence) to be
.0 S o.y I
whose ii/ ice- to the within iiistrurnertr stud ickno,\xleciged.i:(:).,ti.ic.tI.i,,it he/shc/ti.le\
sccirrcd the sine; in his/her./ti-icir.authof zed and chat :b?
-L menu.
on die ins.tpl
d-w-porson(I acted, executed. the instrOmbir.
)�.or Ihe ctluuv
wrl"N h -SS inv hAnd,*,and 4fidal seal.
M6irin D. ReeVey
Notary P6blic
State of Texas
My Commissibn Expires
AUGUST 13, 2009
2
777620.0
CITY OF LA QUINTA -.PUBLIC WORKS DEPARTMENT GREEN SHEET
PUBLIC WORKS CLEARANCE FOR RELEASE OF BUILDING PERMIT
Form updated & effective 9/25/2009
Green Sheet approvals are forwarded to the Building & Safety Department directly by Public Works. Please DO
NOT submit the Green Sheet (Public Works Clearance) Packet to the Public Works Department until ALL
requirements listed below are complete. Incomplete applications or applications which cannot be processed will be
returned to applicant. ,
Date: / % � /J Ju Developer: [ (�/J/a LZ G1� ` J 10 FS
Tract No.: Z % 99 7 ZTract Name: Lot No. (s): A 13
Address(s): G.j' - % -D LA L' �2 ( Phone Number: (�)
The following are the requirements for Public Works Clearance to authorize issuance --from the
R�Ctiv�D Building & Safety Department:
❑ CUSTOM HOMES: PROVIDE ITEMS #2, #3, #4, #5 & #7 BELOW
❑ TRACT HOMES: PROVIDE ITEMS #1, #2, #3 & #5 BELOW AUG 12 2014
❑ COMMERCIAL BUILDINGS/OTHER: PROVIDE ITEMS #1, #2, #3, #5 & #7 BELOW
❑ WALLS, SIGNS, OTHER: PROVIDE ITEM #6 BELOW CITY OF LA QUINTA
COMMUNITY DEVELOPMENT
1. Attach Pad Elevation Certificates in compliance with the approved design elevation for building pad
(maximum allowable deviation of +/- 0.1 foot). Pad Elevation Certificates must be current (within 6
months of current date). If a precise grading plan creates the pad for approval, please withhold green sheet
submittal until a Pad Elevation Certificate can be provided.
2. Attach geotechnical certification of grading plan compliance including compaction reports from a licensed
Soils Engineer. Recently rough graded residential developments which have a previously approved
geotechnical certification are exempt from this requirement.
3. Attach recorded final map or title information/grant deed showing proposed building locations.are legal lots.
4. Complete the attached <1 acre per lot or infill project Fugitive Dust Control project information form, PM10
plan & agreement or provide alternative & valid City approved PM10 plan set reference number or hard copy
plan. PM10 plans for commercial & residential developments (beyond 1 lot) are submitted separately with
grading plans & are subject to additional requirements. A current PM10 certification number is required.
5. Attach a copy of the rough or precise grading plan to the Public Works Department showing building
location(s) for pad elevation verification. AO flood zone developments will require an approved flood plain
development plan.
6. Attach supporting documentation for wall plan, monument sign, grease trap or special facility installations.
7. Complete and sign the attached water -quality management plan (WQMP) exemption form, if applicable. PW
approved building construction projects require either a WQMP or a completed WQMP exemption form.
Approved maps/plans may be viewed at the following link: http://www.la-guinta.org/PlanCheck/m search.aspx
I have reviewed and confirmed the requirements listed above as presented and find the improvements to be
sufficiently complete for construction of the proposed buildings/structures/walls/signs on the subject lot(s).
Pursuant to my findings, the above project may be released for building permit issuance.
This section completed by City staff.
Recommended by: Date:
Public Works Distribution: ( (/) Green Sheet to Building & Safety
( ) Green Sheet to Planning Department
Declined for approval for reason(s) as follow(s), please correct and resubmit: ,
TAChecklists - Forms & Applications\Forms & Applications\GREEN SHEET cover & PM10 less than 1 Acre Revised 10-02-12.doc
1
City of La Quinta - PM10 Fugitive Dust Control Project Information
Construction Phase PM10 Aareement (< 1 acre/lot or Infill Proiect)
Project Information
Project Contractor:
Project Phase
(check one)
Construction
.0 Demolition
Project Name: � { 1100 L-0' U`"rS I cte'J LE
qr�
Project Tract/Lot Numbers: l 9 �' Z �� .3g 3
„ _ 1 0
Project Street Address: _��l V
Total Acres in Active
Construction (< 1 ae per
Lot): J9r l 2(O 9
r"
Anticipated Start Date: 3_1A_/_f4 Anticipated Completion Date: 4-/ 1�l
PM10 Contact Information
Please note: Dust control is required 24 hours a day, 7 days a week, regardless of
construction status. Person listed _ below is responsible for dust control during
business and non -business hours.
Name:
A -0(5j S T 1 ,
Title:
P41 3rc Y " 1 '
Company Name:
Ari AUT �C►MIL S
Mailing Address:
.� 1��0^+ �-D
City, State, ZIP Code:
(Nw � 7710
Primary Phone #:
s i
Fax #:
—7 W)
24 Hour Emergency
Phone#:
`
Cell Phone #:
• f I ,, r'
Email Address:
G S T- co to deJ(-1oo1oF,,j7-_ 0- f
PM10 Certificate #:
V .J " ` 9' j_00
The above stated property owner (or authorized representative):
❖ Shall act as his/her acknowledgement of dust control requirements and their enforceability, pursuant to
SCAQMD Rules 403, 403.1, 401, 402, 201, 203 and PERP; -
❖ Shall constitute an Agreement to comply with all project conditions as identified in the approved dust
control plan.
Acknowledges that dust control is required twenty-four _ (24) hours a day, seven (7) days a week,
throughout the period of project performance, regardless of project size or status;
❖ Shall ensure that each and every contractor, subcontractor and. all other persons associated with the project
shall be in continuous compliance with all requirements of the approved dust control plan;
Shall take all necessary precautions to minimize dust, even if additional measures beyond those listed in the
dust control plan are necessary;
Shall authorize representatives of City/County to enter the property .for inspection and/or abatement
purposes;
❖ Shall hold Slessthe County and its representatives from•liability for any actions related to this dust
control platy initiated abatement activities.
Signature or Authorized Representative Date
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD OFFIC*t Ccf%f CF1R-PRF-01
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014 Page 1 of 14
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xml
GENERAL INFORMATION
01
Project Name McDonald Residence
02
Calculation Description Title 24 Analysis
03 This building incorporates one or more SpeclaI Feature§'shown below. '.
«i
03
Project Location 80110 Via Capri
04
A City La Quinta
05
Standards Version Compliance 2014
06
Zip code 92253
07
Compliance Manager Version BEMCmpMgr 2013-3 (651)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.3
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 135
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (FTZ) 6613
15
Number of Zones 6
16
Slab Area (FTZ) 5529
17
Number of Stories 2
18
Addition Cond. Floor Area N/A
19
Natural Gas Available Yes
20
Addition Slab Area (FTZ) N/A'`
21
Glazing Percentage (%) 22.5%
COMPLIANCE RESULTS
01 Building Complies with`Computer Performance"
02 This building incorporates atu�res that�equlre fiend testing and/oar, �e tlfication�by a cenified�HERS�rai�;t/undenthe supervision of a CEC-approved HERS provider.
03 This building incorporates one or more SpeclaI Feature§'shown below. '.
«i
ENERGY USE SUMMARY
04 "' } 05
06
07
08
Energy Use Standard
(kTDV/ft) Design
Proposed
Design
Compliance
Margin
Percent
Improvement
Space Heating 3.14
3.52
-0.38
-12.1%
Space Cooling 115.68
107.74
7.94
6.9%
IAQ Ventilation 1.41
1.41
_
0.0%
Water Heating 4.10
3.97 CITY OF
LA UU11N I A 1
3.2%
Photovoltaic Offset ----0.00
1ILDIJG & SAFbi D �' 1.
Compliance Energy Total 124.33
116.64 P rn
07,69
6.2%
L
ONSTFiUU I IUIN
ATE /LBY
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance' Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:32
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian=14.xml
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Ducts with high level of insulation
• Window overhangs and/or fins
CF1 R -PRF -01
Page 2 of 14
HERS FEATURE SUMMARY _
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
• IAQ mechanical ventilation
Cooling System Verifications: -
• Minimum Airflow
• Verified SEER
•
Refrigerant Charge
• Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:
• Duct Sealing
• Verified low -leakage ducts located entirely in conditioned. space
Domestic Hot Water System Verifications: ■+
None v;'a;: �E�
.t sa r' _,W Jr r rtr 4 i__ ► � i c
ENERGY DESIGN RATING /!+ 'jj /j )% A jj '' ' tt `
. �F�� � �4:.�-..«.���� .�i. 't.. j:�'.''i',1�.ik o .
This is the sum of the annual TDV energy consumption for energy use components included in the performance compliance approach_fof the Standard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and component§'not'�r'-egulated by Title 24, -Part 6 (sucn'as dorimestio appliances and'consdmer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system.
Reference Energy Use Energy Design Rating-.� MarginPercent Improvement
Total Energy (kTDV/f2)• `.. 7 159.63 ''. .151.94 .. 7.69 4.8%
includes calculated Appliances and Miscellaneous Energy Use (AMEU)
BUILDING - FEATURES INFORMATION ;
" 01
02
03
04
05
06
07
Project Name
Conditioned Floor Area (sft)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water .
Heating Systems
McDonald Residence
6613
1
18
6
0
2
Registration Numbe1r: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:36:21
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651
HERS Provider: CaICERTS inc.
Report Generated at: 2014-11-19 10:24:32
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CFIR-PRF-01
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014 Page 3 of 14
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-1.4.xml
ZONE INFORMATION
01
02
03
04
05
06 t 07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1 Water Heating System 2
Master
Conditioned
HVAC Master1
1003
15.8
DHW Sys 1
Great Sitting Room
Conditioned
HVAC great sitting2
1717
16.3
DHW Sys 1
Snug and Dining Room
Conditioned
HVAC snug dining3
882
16.3
DHW Sys 1
Kitchen Breakfast and Med
Conditioned
HVAC kitchen media4
1511
16.3
DHW Sys 1
Guest
Conditioned
HVAC guest5
416
14
DHW Sys 1 '
2nd Floor
Conditioned
HVAC 2nd6
1084
16.3
DHW Sys 1
Registration'Number: 214-N009759313-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:32
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CFI R -PRF -01
Page 4 of 14
OPAQUE SURFACES
01
02
03
04
05
06
07
08
Name
Zone
Construction
Azimuth
Orientation'
Gross Area (ft2)
Window Area (ft2)
Tilt(deg)
10d Wall
Master
R-21 Wall (W.21.2x6.16)
10
specify -
438
18
90
100d Wall
Master
R-21 Wall (W.21.2x6.16)
100
specify -
284
16
90
190d Wall
Master
R-21 Wall (W.21.2x6.16)
190
- specify - .
802
125.2
90
280d Wall
Master
R-21 Wall (W.21.2x6.16)
280
- specify -
784
117.4
90
_ . Roof
_ Master
R-38 Roof(R.38.2x14.16)
1003
NE Wall
Great Sifting Room
R-21 Wali (W.21.2x6.16)
45
Right
80
0
90
SE Wall
Great Sifting Room
R-21 Wali (W.21.2x6.16)
135
Front
482
152.5
90
SW Wall
Great Sitting Room
R-21 Wall (W.21.2x6.16)
225
Left
290
0
90
NW Wail
Great Sifting Room
R-21 Wall (W.21.2x6.16)
315
Back
976
275
90
Roof 2
Great Sitting Room
R-38 Roof(R.38.2x14.16)
1717
SE Wall 2
Snug and Dining Room
R-21 Wali (W.21.2x6.16)
135
Front
224
72
90
SW Wall 2
Snug`and Dining Roomr"" , <R-21Wa11 (W:21*2x6:16]-,225
.. «
Left
112
0
90
NW Wall 2
Snug and Dining Room ''.
_�_...
v ,pR-2 Wall (W.212x6 16) .:' h"' 315 -
-� .. Back .
224
54
90
Roof 3
Snug and'Dlning Room R-38 Roof(R.38;2x14 16)``
ImA04
882
NE Wall 2
Kitchen Breakfast and Med'
"'�R=2TWa11 (W 21.226 16) ;r
' X45,,, '-V'= Right
1120
38.3
90
SE Wall 3
Kitchen. Breakfast and Med
R-21 Wall (W.21.2x6.16)
135
Front
608
43.8
90
SW -Wall 3'
Kitchen Breakfast and Med
R-21 Wall (W.21.2x6.16)
225
Left
304
72
90
NW Wall 3
Kitchen Breakfast and Med
R-21 Wall (W.21.2x6.16)
315
Back
528
156
90
Roof 4
Kitchen Breakfast and Med
R-38 Roof(R.38.2x14.16)
1511 ,
NE Wall 3
Guest
R721 Wall (W.21.2x6.16)
45
Right
224
42.4
90
SE Wall 4
Guest
R-21 Wall (W.21.2x6.16)
135
Front
308
53.6
90
SW Wall 4
Guest
R-21 Wall (W.21.2x6.16)
225
Left
266'
0
90
Roof 5
Guest
R-38 Roof(R.38.2x14.16)
_
416
NE Wall 4
2nd Floor
R-21 Wall (W.21.2x6.16)
45
Right
350
22.8
90
SE Wall 5
2nd Floor
R-21 Wall (W.21.2x6.16)
135
Front
410
11.4
90
SW Wall 5
2nd Floor
R-21 Wall (W.21.2x6.16)
225
Left
192
30
90
NW Wall 4
2nd Floor
R-21 Wall (W.2.1.2x6.16)
315
Back
410
188
90
Roof 6
2nd Floor
R-38 Roof(R.38.2x14.16)
1084
a
Registration Number: 214-1400975938-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:32
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xmi
CF1 R -PRF -01
Page 5 of 14
ATTIC
01 02 03 04 05 06 07
Name Construction Roof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic Attic Roof Cons 4.36764 0.1 0.85 No No
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:32
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence
Calculation Description: Title 24 Analysis
Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CFI R -PRF -01
Page 6 of 14
WINDOWS
01
02
03
04
05 06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Width(ft)
Height
(ft) Multiplier
Area
(ftZ)
U -factor
SHGC
Exterior Shading
Window
Window
10d Wall (- specify --10)
----
--- 1
18.0
0.39
0.28
Insect Screen (default)
Window 2
Window
100d Wall (- specify --100)
- 1
8.0
0.39
0.28
Insect Screen (default)
Window 3
Window
100d Wall (- specify --100)
----
- 1
8.0
0.39
0.28
Insect Screen (default)
Window 4
Window
190d Wall (- specify --190)
----
---- 1
8.0
0.39
0.28
Insect Screen (default)
Window 5
Window
190d Wall (- specify --190)
----
--- 1
21.6
0.39
0.28
Insect Screen (default)
Window 6
Window
190d Wall (- specify --190)
----
- 1
16.0
0.39
0.28
Insect Screen (default)
Window 7
Window
190d Wall (- specify --190)
----
- 1
16.0
0.39
0.28
Insect Screen (default)
Window 8
Window
190d.Wall (- specify --190)
- -
-- 1
8.0
0.39
0.28
Insect Screen (default)
Window 9
Window
190d Wall (- specify --190)
----
-- 1
8.0
0.39
0.28
Insect Screen (default)
Window 10
Window
190d Wall (- specify --190)
----
-- 1
21.6
0.39
0.28
Insect Screen (default)
Window 11
Window
190d Wall (--specify --190)„
r. -
1
8.0
0.39
0.28
Insect Screen (default)
Window 12
Window
► 190.6.Wall (-,specify -x1190)
1
18.0
0.39
0.28
Insect Screen (default)
Window 13
Window
280d Wall (- specify -280)`
--
'.- - v 1
3.8
0.39
0.28
Insect Screen (default)
Window 14
Window
280d Wall ( specify -280) '
f --- �'=--
l ;' 1\- {
3.8
0.39
0.28
Insect Screen (default)
Window 15
Window
280d Wall (- specify --280)
----
- 1
3:8
0.39
0.28
Insect Screen (default)
Window 16
Window
280d Wall (- specify --280)
----
--- 1
18.0
0.39
0.28
Insect Screen (default)
Window 17
Window
_ 280d Wall (- specify --280)
----
--- 1
54.0
0.39
0.28
Insect Screen (default)
Window 18
Window
280d Wall (=specify --280)
----
---- 1
18.0
0.39
0.28
Insect Screen (default)
Window 19
Window
280d Wall (- specify --280)
-
--- 1
8.0
0.39.
0.28
Insect Screen (default)
Window 20
Window
280d Wall (- specify --280)
----
--- 1
8.0
0.39
0.28
Insect Screen (default)
Window 21
Window
SE Wall (Front -135)
4.0
10.0 1
40.0
0.39
0.28
Insect Screen (default)
Window 22
Window
SE Wall (Front -135)
9.0
12.5 1
112.5
0.39
0.28
Insect Screen (default)
Window 23
Window
NW Wall (Back -315)
8.0
8.0 1
64.0
0.39
0.28
Insect Screen (default)
Window 24
Window
NW Wall (Back -315)
24.0
8.0 1
192.0
0.39
0.28
Insect Screen (default)
Window 25
Window
NW Wall (Back -315)
---
--- 1
3.8
0.39
0.28
Insect Screen (default)
Window 26
Window
NW Wall (Back -315)
- 1
3.8
0.39
0.28
Insect Screen (default)
Window 27
Window
NW Wall (Back -315)
----
- 1
3.8
0.39
0.28
Insect Screen (default)
Window 28
Window
NW Wall (Back -315)
--
-- 1
3.8
0.39
0.28
Insect Screen (default)
Window 29
Window
NW Wall (Back -315)
----
- 1
3.8
0.39
0.28
Insect Screen (default)
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance. Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:32
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence
Calculation Description: Title 24 Analysis
Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Input File Name: McDonald Res-Cornerstone-Brian-14.xmi
CF1R-PRF-01
Page 7 of 14
Window 30
Window
SE Wall 2 (Front -135)
- ---
1
72.0
0.39
0.28
Insect Screen (default)
.Window 31
Window
NW Wall 2 (Back -315)
---- ----
1
18.0
0.39
0.28
Insect Screen (default)
Window 32
Window
NW Wall 2 (Back -315)
---- ---
1
18.0
0.39
0.28
Insect Screen (default)
Window 33
Window
NW Wall 2 (Back -315)
--- ---
1
18.0
0.39.
0.28
Insect Screen (default)
Window 34
Window
NE Wall 2 (Right -45)
---- ---
1
8.0
0.39-
0.28
Insect Screen (default)
Window 35
Window
NE Wall 2 (Right -45)
---
1
8.0
0.39
0.28
Insect Screen (default)
Window 36
Window
NE Wall 2 (Right45)
---- ---
1
2.3
0.39
0.28
Insect Screen (default)
Window 37.
Window
NE Wall 2 (Right -45)
---- ---
1
20.0
0.39
0.28
Insect Screen (default)
Window 38
Window
SE Wall 3 (Front -135)
---- ---
1
3:8
0.39
0.28
Insect Screen (default)
Window 39
Window
SE Wall 3 (Front -135)
---
1
8.0
0.39
0.28
Insect Screen (default)
Window 40
Window
SE Wall 3 (Front -135) •
- ---
1
8.0
0.39
0.28
Insect Screen (default)
Window 41
Window
SE Wall 3 (Front -135)
---- ---
1
8.0
0.39
0.28
Insect Screen (default)
Window 42
Window
SE Wall 3 (Front -135)
---- ---
1
8.0
0.39.
0.28
Insect Screen (default) '
Window 43
Window
SE Wall 3 (Front -135)
---- ---
1
8.0
0.39
0.28
Insect Screen (default)
Window 44
Window
,.. SW Walh3,(Left-225)x,,,, ,,
;�--. ,r
1
72.0
0.39
0.28
Insect Screen (default)
Window 45
Window
NW.WaII 3 (Back -3.15
1 .
96.0
0.39
0.28
Insect Screen (default)
Window 46
Window
NW Walla Back 315
`} ( )
1' .i; ^e :1,
1 -
15.0
0.39
0.28
Insect Screen (default)
Window 47
Window!['`NW.WaII'--�1
30.0
0.39
0.28
Insect Screen (default)
Window 48
Window
- NGV Wall 3 (Back -315)
- ---
1
15.0
0.39
0.28
Insect Screen (default)
Window 49
Window
NE Wall 3 (Right -45)
---
1
42.4
0.39
0.28
Insect Screen (default)
Window 50
Window
t SE Wall 4 (Front -135)
---- ---
1
5.3
0.39
0.28
Insect Screen (default)
Window 51
Window
SE Wall 4 (Front -135)
---- ---
1
16.1
0.39.
0.28
Insect Screen (default)
Window 52
Window
SE Wall 4 (Front -135)
---
1
16.1
0.39
0.28
Insect Screen (default)
Window 53
Window
SE Wall 4 (Front -135)
--- ---
1
16.1
0.39
0.28
Insect Screen (default)
Window 54
Window
NE Wall 4 (Right -45)
---- ---
1
3.8
0.39
0.28
Insect Screen (default)
Window 55
Window
NE Wall 4 (Right -45)
---- ---
1
3.8
0.39
0.28
Insect Screen (default)
Window 56
Window
NE Wall 4 (Right -45)
---
1
3.8
0.39
0.28
Insect Screen (default)
Window 57
Window
NE Wall 4 (Right -45)
---- ---
1
3.8
0.39
0.28
Insect Screen (default)
Window 58
Window
NE Wall 4 (Right -45)
---- ---
1
3.8
0.39
0.28
Insect Screen (default)
Window 59
Window
NE Wall 4 (Right -45)
---- ---
1
3.8
0.39
0.28
Insect Screen- (default)
Window 60
Window
SE Wall 5 (Front -135)
---- ---
1
3.8
0.39'
0.28
Insect Screen (default)
Window 61
Window
SE Wall 5 (Front -135)
---
1
3.8
0.39
0.28
Insect Screen (default)
Window 62
Window
SE Wall 5 (Front -135)
---- ---
1
3.8
0.39
0.28
Insect Screen (default)
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19'10:24:32
v
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF1 R -PRF -01
Page 8 of 14
Window 63
Window
SW Wall 5 (Left -225)
- 1
15.0
0.39
0.28
Insect Screen (default)
Window 64
Window
SW Wall 5 (Left -225)
---- - - 1
15.0
0.39
0.28
Insect Screen (default)
Window 65
Window
NW Wall 4 (Back -315)
---- --- 1
15.0
0.39.
0.28
Insect Screen (default) -
Window 66
Window
NW Wall 4 (Back -315)
--- --- 1
15.0
0.39
0.28
Insect Screen (default)
Window 67
Window
NW Wall 4 (Back -315)
---- --- 1
15.0
0.39
0.28
Insect Screen (default)
Window 68
Window
NW Wall 4 (Back -315)
---- --- 1
15.0
0.39
0.28
Insect Screen (default)
Window 69
Window
NW Wall 4 (Back -315)
---- --- 1
15.0
0.39
0.28
Insect Screen (default)
Window 70
Window
NW Wall 4 (Back -315)
---- --- 1
63.0
0.39
0.28
Insect Screen (default)
Window 71
Window
NW Wall 4 (Back -315)
---- --- 1
12.5
0.39
0.28
Insect Screen (default)
Window 72
Window
NW Wall 4 (Back -315)
---- --- 1
25.0
0.39
0.28
Insect Screen (default)
Window 73
Window
NW Wall 4 (Back -315)
- --- 1
12.5
0.39
0.28
Insect Screen (default)
DOORS
01 03 .1'1 04 OS 06 07 08 09 10 11 12 13 14
01 4 ,.
02 03 04
Name ) :...
�r Side of Building Area (ft2) U -factor
Door t4;
iSE Walli3 t' ,sr' 21.6 0.50
Door 2,r'SSE
Wall 3 24.0 0.50,
% .i -If ke! tF��,'d_s:l* IfaJ 4* < .�!� f". .1: i Jf 'A,". IValCii)f If -
OVERHANGS AND FINS
01 03 .1'1 04 OS 06 07 08 09 10 11 12 13 14
Overhang Left Fin Right Fin
Window Depth
1
Dist Up
Left
Extent
Right
Extent
Flap Ht. Depth
Top Up
DIstL
Bot Up Depth
Top Up
Dist R
Bot Up
Window 21 10
0.1
10
10
0 0
0
0
0 0
0
0
0
Window 22 10
0.1
10
10
0 0
0'
0
0 0
0
0
0
Window 23 10
0.1
10
10
0 0
0
0
0 0
0
0
0
Window 24 10
1 0.1
10
10
0 0
0
1 0
0 0
1 0
0 1
0
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFIR-10172014-651
HERS Provider: CaICERTS inc.
Report Generated at: 2014-11-19 10:24:32
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov"19, 2014
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xm1
CF1 R -PRF -01
Page 9 of 14
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
Construction Name
Surface Type
Construction Type
Framing
Total Cavity R -value
Assembly Layers
07
Name
Zone
2x4 Top Chord of
Perimeter (ft) Edge Insul. R -value& Depth
Cavity/ Frame: no insul. / 2x4 Top Chrd
Heated
Covered Slab
Master * = �. 355 f32
Roof Truss @ 24 in.
0.8
Roof Deck: Wood Siding/sheathing/decking
Attic Roof Cons
Attic Roofs
Wood Framed Ceiling
O.C.
none
Roofing: Light Roof (Asphalt Shingle)
Covered Slab 2
Great;Sittii-- Room
.. k f . g .
' 435 :' ..
- s i �t i.
_'28 h
_ ar•-�kwS s"•• sit
None
• Inside Finish: Gypsum Board
No
Hard surface Slab 2
'a, Great Sltting "Room,
;%'1282 -y R• x.,
28>`
• Cavity / Frame: R-9.1 / 2x4
R-38 Roof(R.38.2xl4.16)
Ceilings (below attic) .
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R38
Over Floor Joists: R-28.9 insul. .
None
0.8
No.
Hard surface Slab 3
Snug and Dining Room
• Inside Finish: Gypsum Board
26
None
0.8
No
Covered Slali 4
• Cavity/ Frame: R-21 / 2x6
R-21 Wall (W.21.2x6.16)
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
Exterior Finish: Wood Siding/sheathing/decking
SLAB FLOORS
01
02
03
04
05
06
07
Name
Zone
Area (ft2)
Perimeter (ft) Edge Insul. R -value& Depth
Carpeted Fraction
Heated
Covered Slab
Master * = �. 355 f32
None
0.8
No
Hard surface Slab'
/ .'fir ; ` Master '" i'rR.Y-: 648 .bJ ?.
°rt= 72r r
-
None
0.8
No
Covered Slab 2
Great;Sittii-- Room
.. k f . g .
' 435 :' ..
- s i �t i.
_'28 h
_ ar•-�kwS s"•• sit
None
0.8
No
Hard surface Slab 2
'a, Great Sltting "Room,
;%'1282 -y R• x.,
28>`
None
0.8
No
Covered Slab 3
Snug and Dining Room ` '"
126
10
None
0.8
No.
Hard surface Slab 3
Snug and Dining Room
756
26
None
0.8
No
Covered Slali 4
Kitchen Breakfast and Med
585
150
None
0.8
No
Hard surface Slab 4
Kitchen Breakfast and Med
926
10
None
0.8
No
Covered Slab 5
Guest
312
56
None
0.8
No
Hard surface Slab 5
Guest
104
0.1
None
0.8
No
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa
Not Required Not Required Not Required ---
Registration Number: 214-N00975938-000000000-0000 Registration DateMme: 2014-11-19 10:38:21
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-6S1
HERS Provider: CaICERTS inc.
Report Generated at: 2014-11-19 10:24:32
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence
Calculation Description: Title 24 Analysis
Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF1 R -PRF -01
Page 10 of 14
WATER HEATING SYSTEMS
01
02
03
04
05
01
02
03
04
05
06
Name
System Type
Distribution Type
Water Heater
Number of Heaters
Solar Fraction (%)
DHW Sys 1
DHW
Standard
DHW Heater 1
1
.0%
DHW Sys 1
DHW
Standard
DHW Heater 1
2
.0%
WATER HEATERS
01
02
03
04
05
06
07
08
Name
Heater Element Type
Tank Type
Tank Volume
(gal)
Energy Factor or
Efficiency
Input Rating
Tank Exterior
Insulation
R -value
Standby Loss
(Fraction)
DHW Heater 1
Natural Gas
Large Storage
75
0.8
85000-Btu/hr
0
0.0085
DHW Heater 1
Natural Gas
Large Storage
75
0.8
85000-Btu/hr
0
0.0085
WATER HEATING - HERS VERIFICATION
01
X02;,,
03 7
art 04„�
05
06
07
Heating System
/Compact
Distribution
Recirculation
Central DHW
Name
Pipe IInsulat on rf
Parallel Piping-.
Distribution
Point -of Use
Control
Distribution
DHW Sys 1 - 1/1
i�l N/A ri'r y ..
/�,. ;N/A° ...
: `IF : N/A i JA
�r
js N/A
N/A
N/A
DHW Sys 1 - 1/2
N/A
- . N/A
N/A
N/A
N/A
N/A
HVAC SYSTEMS
01
02
03
_ 04
05
06
07
Heating System
Cooling System
Distribution
Floor Area
Name
System Type
Name Ducted
Name Ducted
System
Fan System
Served
HVAC Masterl
Heat Pump
Heat Pump System 1
Yes
Heat Pump System 1
Yes
Air Distribution
System 1
1003
HVAC great sitting2
Heat Pump
Heat Pump System 2
Yes
Heat Pump System 2
Yes
Air Distribution
System 2
1717
HVAC snug dining3
Heat Pump
Heat Pump System 3
Yes
Heat Pump System 3
Yes
Air Distribution
System 3
882
HVAC kitchen media4
Heat Pump
Heat Pump System 4
Yes
Heat Pump System 4
Yes
Air Distribution
System 4
1511
HVAC guest5
Heat Pump
Heat Pump System 5
Yes
Heat Pump System 5
Yes
Air Distribution
System 5
416
HVAC 2nd6
Heat Pump
Heat Pump System 6
Yes
Heat Pump System 6
Yes
Air Distribution
System 6
1084
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:32
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF1 R -PRF -01
Page 11 of 14
HVAC - HEATING SYSTEMS: Heat Pumps
01
02
03 04 05
06 07
08
09
10
03 :
r r /.
Heating
Cooling
Zonally
Muitispeed
HERS
Name
Type
HSPF/COP Cap 47 Cap 17
SEER EER
Controlled
Compressor
Verification
Heat Pump System•1
SplitHeatPump
8.7 HSPF
46500
46500
15
12.5
No
No
Heat Pump System
Required
Verified
HVAC kitchen media4 SCSysRpt 1
350
Not Required
Required
Verified
1 -hers -cool
Heat Pump System 2
SplitHeatPump
8.5 HSPF
57000
57000
15
12.5
No
No
Heat Pump System
Verified
1 -hers -cool
Heat Pump System 3
SplitHeatPump
8.7 HSPF
35200
35200
15
12.5
No
No
Heat Pump System
1 -hers -cool
Heat Pump System 4
SplitHeatPump
8.5 HSPF
57000
57000
15
12.5
No
No
Heat Pump System
1 -hers -cool
Heat Pump System 5
SplitHeatPump
8.7 HSPF
35200
35200
15
12.5
No
No
Heat Pump System
1 -hers -cool
Heat Pump System 6
SplitHeatPump
8.7 HSPF
46500
46500
15
12.5
No
No
Heat Pump System
1 -hers -cool
HVAC HEAT PUMP.COOLING - HERS VERIFICATION
01 ,
%� `'. i f. `
02
k ..�
03 :
r r /.
04
05
Name" "'• :' Verified Airflow _ ,
h"` __Verified EER,
Verified SEER
Verified Refrigerant Charge
HVAC Master1 SCSysRpt 1 .,^� �`
350
Not Required
Required
Verified
HVAC great sitting2 SCSysRpt 1 ;
350
Not Required
Required
Verified
HVAC snug dining3 SCSysRpt 1
350
Not Required
Required
Verified
HVAC kitchen media4 SCSysRpt 1
350
Not Required
Required
Verified
HVAC guest5 SCSysRpt 1
350
Not Required
Required
Verified
HVAC 2nd6 SCSysRpt 1
350
Not Required
Required
Verified
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - &IR -10172014-651 Report Generated at: 2014-11-19 10:24:32
-CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF1 R -PRF -01
Page 12 of 14
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
08
1 `" i9
:IIA , A Y _.� r
Supply Duct
Duct Leakage'% -"✓V
01�'
Name
Type
Duct Leakage
Insulation R -value
Location
Return Duct
Bypass Duct
HERS Verification
Air Distribution System 1
Ducts located entirely in
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
s
conditioned space
Required"
Not Required
Not Required
1 -hers -dist
System 1 -hers -dist
Air Distribution System 2
Ducts located entirely in
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
Required
conditioned space
Not Required
2 -hers -dist
System 2 -hers -dist
Air Distribution System 3
Ducts located entirely in
Sealed and tested
` 8
Conditioned Zone
Conditioned Zone
None
Air Distribution
_
conditioned space
3 -hers -dist
- -
_
System 3 -hers -dist
Air Distribution System 4
Ducts located entirely in
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
4 -hers -dist
conditioned space
-
System 4 -hers -dist
Air Distribution System 5
Ducts located entirely in
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
conditioned space
Air Distribution System
Required
System 5 -hers -dist
Air Distribution System 6
Ducts located entirely in+.
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
conditioned space
System 6 -hers -dist
• �Me. r !.+w�..,rw.wrti'.-»e+.!r. xf..w.-�+-..�r! wP"�l.e
HVAC DISTRIBUTION - HERS VERIFICATION
01
yyk �r,.wJ'#
02 1
„
"' j_A_1 z
"p" 04p ::
05 06
07
1 `" i9
:IIA , A Y _.� r
Duct Leakage'% -"✓V
01�'
-9
Verified Duct Design
Low -leakage
9
+a. Y.t ...nw ',
.3si.. "'max :a:r�l.,> " ,.-•-. '��
Name
Verification
Duct Leakage Target (%)
Verified Duct Location
Return Supply
Air Handier
Air Distribution SystemTRequired.
s
6.0
Required"
Not Required
Not Required
1 -hers -dist
'i
Air Distribution System
Required
'.
6.0
Required
Not Required
Not Required
2 -hers -dist
Air. Distribution System
Required
6.0
Required
Not Required
Not Required
- -
3 -hers -dist
Air Distribution System
Required
6.0
Required
Not Required
Not Required .
4 -hers -dist
-
Air Distribution System
Required
6.0
Required
Not Required
Not Required
---
5-hers-dist
Air Distribution System
Required
6.0
Required
Not Required
Not Required
6 -hers -dist
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:32
-CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014 Page 13 of 14
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xml
HVAC -FAN SYSTEMS
01
02 t-
01
01
02
03
04
Name
Type
Fan Power (Watts/CFM)'
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
HVAC Fan 1 -hers -fan
HVAC Fan 2
Single Speed PSC Furnace Fan
0.58
HVAC Fan 2 -hers -fan
HVAC Fan 3
Single Speed PSC Furnace Fan
0.58
HVAC Fan 3 -hers -fan
HVAC Fan 4
Single Speed PSC Furnace Fan
0.58•
HVAC Fan 4 -hers -fan
HVAC Fan 5
Single Speed PSC Furnace Fan
0.58
HVAC Fan 5 -hers -fan
HVAC Fan 6
Single Speed PSC Furnace Fan
0.58
HVAC Fan 6 -hers -fan
HVAC FAN SYSTEMS - HERS VERIFICATION
01
02 t-
01
02
03
Name
_N; • . VerifiedFanWatt Draw
Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan _`;,
Required
0.58
HVAC Fan 2 -hers -fan
ix. T Required _ - '
0.58
HVAC Fan 3-hers-fari` f;�t;
�€' � w F` p: �f J 'zR6; uired` '- *t II n#
0.58
HVAC Fan 4 -hers fan g- d
rJ x}3 / ?KV `Required [±w -
0.58
.€ ✓
HVAC Fan 5 -hers fan='; ;w, �^ Required• � ,ArL,A
0.58
HVAC Fan 6-hers-fan"7'
, .'."'- '"'Required �'`•••
0.58
IAQ (Indoor Air Quality) FANS = �w
01
02 t-
03 t
04
05
06
Name.
IAQ CFM
IAQ WattsICFM
IAQ Fan Type
IAQ Recovery
Effectiveness(%)
HERS Verification
DwellingUnit
208.63
0.25
Default
0
. Required
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21
CA Building Energy Efficiency Standards - 2013 Residential ComplianceReport Version - CF1R-10172014-651
HERS Provider: CaICERTS inc.
Report Generated at: 2014-11-19 10:24:32
• • • CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF1 R -PRF -01
Page 14 of 14
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Tim Scott
Company:
Signature Date:
Scott Design and Title 24, Inc.
2014-11-1910:38:21
Address:
CEA/HERS Certification Identification (If applicable):
77085 Michigan Drive
City/State/Zip: •
Phone:
Palm Desert, CA 92211
(760) 200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify thafthe energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.'
3. The building design features or system design features identified.on-this Certificate of...Compliance.are.consistent.with the information provided on other applicable compliance documents,
worksheets, calculations, plans and°specifications submitted -,to the enforcementagency forapproval wdh this building permit application.
Responsible Designer Name: ` ;,^
AD
Responsible Designer Signature:'..,-
Tim Scott
Company: �, . "' ";_ -r:,.
Date Signed:
'Scott Design and Title 24, Incy .,
2014-11-19 10:38:21 - -
Address:
License:
77085 Michigan Drive 'k
na
City/State/Zip:
Phone:
Palm Desert, CA 92211
(760) 200-4780
C1 i Y OF LA CSU I'"TA
- BUILDH Ju & SAFE DEPT.
- IV `D
FOR CONSTRUCTION
Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document n din ?o=way implies Regbt(ation Provider respon ibility for the accuracy of the
information.
Registration Number: 214-N0097593B-000000000-0000 Registration Date/Time: 2014-11-19 10:38:21 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:32
0
BUILDING ENERGY ANALYSIS REPORT
PROJECT:
McDonald Residence
80110 Via Capri
La Quinta, CA.92253
Project Designer:
Cornerstone Architects
700 Bee Cave Road STE 200
Austin, TX 78746
(512) 329-0007
.Report Prepared by:
Jon Scott
Scott Design and Title 24, Inc,
77-085 Michigan Drive
Palm_ Desert, CA 9221.1
(760) 200-4780
Job Number:
Date:
11/19/2014
CITY OF
BUILDING & 8A � IQUIE P�
APPROVED T.
FOR CONSTRUCTION
DATE,BY
-X-
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC—www.energysoft.com.
EnergyPro 6.3 by EnergySoft User Number: 6712 ID:
"r
►+ ;.
., -
• - .. R.
CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE NOOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF1*F-01
Page 1 of 14
GENERAL INFORMATION
01
. Project Name McDonald Residence
02
Calculation Description Title 24 Analysis
03 This building incorporates one or more Special Features showri�below.
03
Project Location 80110 Via Capri
04
A City La Quinta
05
Standards Version Compliance 2014
06
Zip code 92253
07.
Compliance Manager Version BEMCmpMgr 2013-3 (651)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.3
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 135
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (FTZ) 6613
15 A�
Number of Zones 6
16
Slab Area (FTZ) 5529
17
Number of Stories 2
18
Addition Cond. Floor Area N/A
X1+91,
Natural Gas Available Yes
20
Addition Slab Area (FTZ) N/A
RC2
Glazing Percentage (%) 22.5%
A'W
COMPLIANCE RESULTS $� v
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features showri�below.
ENERGY USE SUMMARY
04
05�e`r
06
07
08
Energy Use
(kTDVlft)
Standard
,Design
Proposed
Design
Compliance
Margin
Percent
Improvement
Space Heating
3.14
3.52
-0.38
-12.1%
Space Cooling
115.68
107.74
7.94
6.9%
IAQ Ventilation
1.41
1.41
0.00
0.0%
Water Heating
I4A 4.10
3.97
0.13
3.2%
Photovoltaic Offset
—
0.00
0.00
—
Compliance Energy Total
124.33
116.64
7.69
6.2%
Registration Number: 0� Registration Date/Time: HERS Provider:
CA Building Energy Efficiency StanUa ds - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
CERTIOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Ducts with high level of insulation
• Window overhangs and/or fins
CF*F-01
Page 2of14
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
IAQ mechanical ventilation
Cooling System Verifications:
• Minimum Airflow
• Verified SEER
• Refrigerant Charge
• Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:
• Duct Sealing
• Verified low -leakage ducts located entirely in conditioned space
Domestic Hot Water System Verifications:
— None —I
ENERGY DESIGN RATING
This is the sum of the annual TDV energy consumption for energy use components include' in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and components not regulated by Title 24, Part %(;such as domestic appliances and consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy systema
Reference Energy<Use Energy.Design Rating Margin Percent Improvement
Total Energy (kTDVH2)• 159.631 151.94 7.69 4.8%
includes calculated Appliances and Miscellaneous Energy Use (AMEU)' IQ
BUILDING . FEATURES INFORMATION
01
02
03
04
05
06
07
Project Name
Conditioned Floor A%(sft)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water.
Heating Systems
McDonald Residence
6613
1
18
6
0
2
.O00
'e
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE h*OD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CFOF-01
Page 3 of 14
ZONE INFORMATION
01
02
03
04
65
06 07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1 Water Heating System 2
Master
Conditioned
HVAC Masterl
1003
15.8
DHW Sys 1
Great Sitting Room
Conditioned
HVAC great sitting2
1717
16.3
DHW Sys 1
Snug and Dining Room
Conditioned
HVAC snug dining3
882
16.3
DHW Sys 1
Kitchen Breakfast and Med
Conditioned
HVAC kitchen media4
1511
16.3
DHW Sys 1
Guest
Conditioned
HVAC guests
416
14
DHW Sys 1
2nd Floor
Conditioned
HVAC 2nd6
1
16.3
DHW Sys 1
e ®dVI
4
e
e V�
.e
C�
Registration Number: �® Registration Date/Time:
CA Building Energy Efficiency Stands - 2013 Residential Compliance Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at: 2014-11-19 10:24:21
CERTIFOF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE rfOD
Project Name: McDonald Residence Ca culation Daie/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF*F-01
Page 4 of 14
OPAQUE SURFACES
01
02
03
04
05
06
07
08
Name
Zone
Construction
Azimuth
Orientation
Gross Area (ft2)
Window Area (W)
Tilt(deg)
10d Wall
Master
R-21 Wall (W.21.2x6.16)
10
- specify -
438
18
90
100d Wall
Master
R-21 Wall (W21.2x6.16)
100
- specify -
284
16
90
190d Wall
Master
R-21 Wall (W.21.2x6.16)
190
- specify -
802
125.2
90
280d Wall
Master
R-21 Wall (W.21.2x6.16)
280
- specify -
784
117.4
90
Roof
Master
R-38 Roof(R.38.2x14.16)
1003
NE Wall
Great Sitting Room
R-21 Wall (W21.2x6.16)
b 45
Right
80
0
90
SE Wall
Great Sifting Room
R-21 Wall (W.21.2x6.16)
4� 135
Front
482
152.5
90
SW Wall
Great Sifting Room
R-21 Wall.(W.21.2x6.16) M� 225
Left
290
0
90
NW Wall
Great Sifting Room
R-21 Wall (W21.2x6.16)�`
315
Back
976
275
90
Roof 2
Great Sifting Room
R-38 Roof(R.38.2x14.;16-1*
1717
SE Wall 2
Snug and Dining Room
R-21 Wall (W.21.2xx6�16)
135
Front
224
72
90
SW Wall 2
Snug and Dining Room
R-21 Wall (W.2 zi x6.16)
225
Left
112
0
90
NW Wall 2
Snug and Dining Room
R-21 Wall (t21?24.16)
315
Back
224
54
90
Roof 3
Snug and Dining Room
R-38 Roo
,f(R`38.2x14.16)
882
NE Wall 2
Kitchen Breakfast and Med
R-21 M71r(W.21.2x6.16)
45
Right
1120
38.3
90
SE Wall 3
Kitchen Breakfast and Med
R-31�Wall (W.21.2x6.16)
135
Front
608
43.8
90
SW Wall 3
Kitchen Breakfast and Med
�RlfWall (W21.2x6.16)
225
Left
304
72
90
NW Wall 3
Kitchen Breakfast and Med
�:16-21 Wall (W.21.2x6.16)
315
Back
528
156
90
Roof 4
Kitchen Breakfast and Med
R-38 Roof(R.38.2x14.16)
1511
NE Wall 3
Guest
R-21 Wall (W21.2x6.16)
45
Right
224
42.4
90
SE Wall 4
Guest ., �v R-21 Wall (W21.2x6.16)
135
Front
308
53.6
90
SW Wall 4
Roof 5
Guest A *%
Guest '1
R-21 Wall (W21.2x6.16)
R-38 Roof(R.38.2x14.16)
225
Left
266
416
0
90
NE Wall 4
2nd Floo�� _
R-21 Wall (W.21.2x6.16)
45
Right
350
22.8
90
SE Wall 5
2nd Floor
R-21 Wall (W21.2x6.16)
135
Front
410
11.4
90
SW Wall 5
2ndwFJoor
R-21 Wall (W21.2x6.16)
225
Left
192
30
90
NW Wall
�P2nd"'FIoor
R-21 Wall (W.21.2x6.16)
315
Back
410
188
90
Roof 6
P2nd Floor
R-38 Roof(R.38.2x14.16)
1084
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
CERTIF&_ OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OOD
Project Name: McDonald -Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis . Input File Name: McDonald Res-Cornerstone-Brian-14.xmi
CFOF-01
Page 5 of 14
ATTIC
01 02 03 04 05 06 07
Name Construction Roof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic Attic Roof Cons 4:36764 0.1 0.85 No No
�0
• V�
�0
4&
Registration
Registration Number:��t�O Registration Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at: 2014-11-19 10:24:21
0
CERTIFW OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF*F-01
Page 6 of 14
WINDOWS
01
02
03
04 05
06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Height
Width(ft) (ft)
Multiplier
Area
(W)
U -factor
SHGC
Exterior Shading
Window
Window
10d Wall (- specify -10)
- -
1
18.0
0.39
0.28
Insect Screen (default)
Window 2
Window
100d Wall (- specify -100)
- -
1
8.0
0.39
0.28
Insect Screen (default)
Window 3
Window
100d Wall (- specify -100)
- -
1
8.0
0.39
0.28
Insect Screen (default)
Window 4
Window
190d Wall (- specify -190)
- -
1
8.0
0.39
0.28
Insect Screen (default)
Window 5
Window
190d Wall (- specify -190)
- e, --
1
21.6
0.39
0.28
Insect Screen (default)
Window 6
Window
190d Wall (- specify --190)
- -
1
16.0
0.39
0.28
Insect Screen (default)
Window 7
Window
190d Wall (- specify -190),`
--
1
16.0
0.39
0.28
Insect Screen (default)
Window 8
Window
190d Wall (- specify -190)
-
1
8.0
0.39
0.28
Insect Screen (default)
Window 9
Window
190d Wall (- specify -190)0`-
-
1
8.0
0.39
0.28
Insect Screen (default)
Window 10
Window
190d Wall (- specify -190) my - -
1
21.6
0.39
0.28
Insect Screen (default)
Window 11
Window
190d Wall (- specify -190) w
- --
1
8.0
0.39
0.28
Insect Screen (default)
Window 12
Window
190d Wall (- specify -190) �
-- -
1
18.0
0.39
0.28
Insect Screen (default)
Window 13
Window
280d Wall (- specify -280)
- -
1
3.8
0.39
0.28
Insect Screen (default)
Window 14
Window
280d Wall (- specify -280) �a�
- --
1
3.8
0.39
0.28
Insect Screen (default)
Window 15
Window
280d Wall (- specify -280)
- -
1
3.8
0.39
0.28
Insect Screen (default)
Window 16
Window
280d Wall (- specify -280)
- --
1
18.0
0.39
0.28
Insect Screen (default)
Window 17
Window
280d Wall (- specify---'��280)
- -
1
54.0
0.39
0.28
Insect Screen (default)
Window 18
Window
280d Wall (- spe„c fyy -280)
- -
1
18.0
0.39
0.28
Insect Screen (default)
Window 19
Window
280d Wall (- specify -280)
- -
1
8.0
0.39
0.28
Insect Screen (default)
Window 20
Window
2 8 0 d Wal�(specify --280)
-- -
1
8.0
0.39
0.28
Insect Screen (default)
Window 21
Window
SECWaII(Front-135)
4.0 10.0
1
40.0
0.39
0.28
Insect Screen (default)
Window 22
Window
SE.Wall (Front -135)
9.0 12.5
1
112.5
0.39
0.28
Insect Screen (default)
Window 23
Window
1M Wall (Back -315)
8.0 8.0
1
64.0
0.39
0.28
Insect Screen (default)
Window 24
Window
*VNW Wall (Back -315)
24.0 8.0
1
192.0
0.39
0.28
Insect Screen (default)
Window 25
Window
NW Wall (Back -315)
- --
1
3.8
0.39
0.28
Insect Screen (default)
Window 26
Windows
NW Wall (Back -315)
- --
1
3.8
0.39
0.28
Insect Screen (default)
Window 27
Windows
NW Wall (Back -315)
- -
1
3.8
0.39
0.28
Insect Screen (default)
Window 28
Window
NW Wall (Back -315)
- --
1
3.8
0.39
0.28
Insect Screen (default)
Window 29
Window
NW Wall (Back -315)
- --
1
3.8
0.39
0.28
Insect Screen (default)
♦ 0
Registration Number: ® Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
CERTIFIOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CFIWF-01
Page 7 of 14
Window 30
Window
SE Wall 2 (Front -135)
- -
1
72.0
0.39
0.28
Insect Screen (default)
Window 31
Window
NW Wall 2 (Back -315)
- -
1
18.0
0.39
0.28
Insect Screen (default)
window 32
Window
NW Wall 2 (Back -315)
- -
1
18.0
0.39
0.28
Insect Screen (default)
Window 33
Window
NW Wall 2 (Back -315)
- -
1
18.0
0.39
0.28
Insect Screen (default)
Window 34
Window
NE Wall 2 (Right -45)
--
1
8.0
0.39
0.28
1 Insect Screen (default)
Window 35
Window
NE Wall 2 (Right -45)
- -
1
8.0
0.39
0.28
Insect Screen (default)
Window 36
Window
NE Wall 2 (Right -45)
- --
1
2.3
0.39
0.28
Insect Screen (default)
Window 37
Window
NE Wall 2 (Right -45)
-- -
1
20.0
0.39
0.28
Insect Screen (default)
Window 38
Wndow
SE Wall 3 (Front -135)
- -
1
3.8
0.39
0.28
Insect Screen (default)
Window 39
Window
SE Wall 3 (Front -135)
- ^� -
1
8.0
0.39
0.28
Insect Screen (default)
Window 40
Window
SE Wall 3 (Front -1 35)-
1
8.0
0.39
0.28
Insect Screen (default)
Window 41
Window
SE Wall 3 (Front -135)
G -
1
8.0
0.39
0.28
Insect Screen (default)
Window 42
Window
SE Wall 3 (Front -135)
-- -
1
8.0
0.39
0.28
Insect Screen (default)
Window 43
Window
SE Wall 3 (Front -135) ��
'r - -
1
8.0
0.39
0.28
Insect Screen (default)
Window 44
Window
SW Wall 3 (Left -225)`
- -
1
72.0
0.39
0.28
Insect Screen (default)
Wndow 45
Wndow
NW Wall 3 (Back -315) Ov
-- -
1
96.0
0.39
0.28
Insect Screen (default)
Window 46
Window
NW Wall 3 (Back -315) �`
- -
1
15.0
0.39
0.28
Insect Screen (default)
Window, 47
Window
NW Wall 3 (Back -315) �V
- -
1
30.0
0.39
0.28
Insect Screen (default)
Window 48
Window
NW Wall 3 (Back -315) 0
-- -
1
15.0
0.39
0.28
Insect Screen (default)
Window 49
Window
NE Wall 3 (Right -45Y
- -
1
42.4
0.39
0.28
Insect Screen (default)
Window 50
Window
SE Wall 4 (Front;1A.8)
- -
1
5.3
0.39
0.28
Insect Screen (default)
Window 51
Window
SE Wall 4 (Frb&�135)
- -
1
16.1
0.39
0.28
Insect Screen (default)
Window 52
Window
SE Wall 4s.� (Front -135)
- -
1
16.1
0.39
0.28
Insect Screen (default)
Window 53
Window
SE WaI .t(Front-135)
- -
1
16.1
0.39
0.28
Insect Screen (default)
Window 54
Window
NE ,Wall 4 (Right -45)
- --
1
3.8
0.39
0.28
Insect Screen (default)
Window 55
WindowNEyWall
4 (Right 45)
- -
1
3.8
0.39
0.28
Insect Screen (default)
Window 56
Window
�.NE Wall 4 (Right -45)
- -
1
3.8
0.39
0.28
Insect Screen (default)
Window 57
Window
%SNE Wall 4 (Right -45)
- --
1
3.8
0.39
0.28
Insect Screen (default)
Window 58
Window
NE Wall 4 (Right -45)
-- -
1
3.8
0.39
0.28
Insect Screen (default)
Window 59
Window`
NE Wall 4 (Right -45)
- --
1
3.8
0.39
0.28
Insect Screen (default)
Window 60
Window`s
SE Wall 5 (Front -135)
-- -
1
3.8
0.39
0.28
Insect Screen (default)
Window 61
Window
. �`" SE Wall 5 (Front -135)
- --
1
3.8
0.39
0.28
Insect Screen (default)
Window 62
Window
SE Wall 5 (Front -135)
-- -
1
3.8
0.39
0.28
Insect Screen (default)
• to
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Stand ds - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
CERTIF*E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OD
Project Name: McDonald Residence Ca culation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File.Name: McDonald Res-Cornerstone-Brian-14.xml
CFO' F-01
Page 8of14
Window 63
Window
SW Wall 5 (Left -225)
- -
1
15.0
0.39
0.28
Insect Screen (default)
Window 64
Window
SW Wall.5 (Left -225)
_ -
1
15.0
0.39
0.28
Insect Screen (default)
Window 65
Window
NW Wall 4 (Back -315)
- -
1
15.0.
0.39
0.28
Insect Screen (default)
Window 66
Window
NW Wall 4 (Back -315)
- -
1
15.0
0.39
0.28
Insect Screen (default)
Window 67
Window
NW Wall 4 (Back -315)
- -
1
15.0
0.39
0.28
Insect Screen (default)
Window 68
Window
NW Wall 4 (Back -315)
-- -
1
15.0
0.39
0.28
Insect Screen (default)
Window 69
Window
NW Wall 4 (Back -315)
-- -
1
15.0
0.39
0.28
Insect Screen (default)
Window 70
Window
NW Wall 4 (Back -315)
-- -
1
63.0
0.39
0.28
Insect Screen (default)
Window 71
Window
NW Wall 4 (Back -315)
--. -
1
12.5
0.39
0.28
Insect Screen (default)
Window 72
Window
NW Wall 4 (Back -315)
-- �� y -
1
25.0
0.39
0.28
Insect Screen (default).
Window 73
Window
NW Wall 4 (Back -315)
-�`� -
1
12.5 1
0.39
0.28
Insect Screen (default)
DOORS
V .
A�
01
03
04
Name
Side of Building
Area (ft2)
U -factor
Door
Q SE Wall 3
21.6
0.50
Door 2
4V SE Wall 3
24.0
0.50
*A S
OVERHANGS AND FINS
V .
A�
01
02
03 04 _CO -5
06
07
08
09
10
11
12
13
1 14
Overhang ��
Left Fin
Right Fin
Window
Depth
Left Right
Dist Up Extejt) Extent
Flap Ht.
Depth
Top Up
DistL
Bot Up
Depth
Top Up
Dist R
Bot Up
Window 21
10
0.1 41 .* v 10
0
0
0
0
0
0
0
0
0
Window 22
10
0.1 , d10 10
0
0
0
0
0
0
0
0
0
Window 23
10
0.1 10 10
0
0
0
0
0
0
0
0
0
Window 24
10
0.1 �`� 10 10
0
0
0
0
0
0
0
0
0
Registration Number: i� Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
CERTIFW OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE IOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF&F-01
Page 9of14
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
Construction Name
Surface Type
Construction Type
Framing
Total Cavity R -value
Assembly Layers
07
Name
Zone Area (ft2)
2x4 Top Chord of
Perimeter (ft)
Cavity/Frame: no insul. /2x4 Top Chrd
Carpeted Fraction
Heated
Covered Slab
Roof Truss @ 24 in.
`'�
Roof Deck: Wood Siding/sheathing/decking
Attic Roof Cons
Attic Roofs
Wood Framed Ceiling
O.C.
none
Roofing: Light Roof (Asphalt Shingle)
72
None
0.8
No
Covered Slab 2
• Inside Finish: Gypsum Board
28
None
0.8
No
• Cavity/Frame: R-9.1 /2x4
R-38 Roof(R.38.2xl4.16)
Ceilings (below attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 38
Over Floor Joists: R-28.9 insul.
Covered Slab 3
Snug and Dining Room 126
10
None
• Inside Finish: Gypsum Board
No
Hard surface Slab 3
Snug and Dining Room �� 756
26
• Cavity/Frame: R-21 /2x6
R-21 Wall (W 21.2x6.16)
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.��
R 21
Exterior Finish: Wood Siding/sheathing/decking
ov
SLAB FLOORS
� w
02 03 04
Quality Insulation Installation (QII)
Quality Installation of Spray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa
Not Required
01
02 03
04
05
06
07
Name
Zone Area (ft2)
�i
Perimeter (ft)
Edge Insul. R -value& Depth
Carpeted Fraction
Heated
Covered Slab
Master 355
`'�
32
None
0.8
No
Hard surface Slab
Master 648v
72
None
0.8
No
Covered Slab 2
Great Sitting Room 435'
28
None
0.8
No
Hard surface Slab 2
Great Sitting Room "a1�282
28
None
0.8
No
Covered Slab 3
Snug and Dining Room 126
10
None
0.8
No
Hard surface Slab 3
Snug and Dining Room �� 756
26
None
0.8
No
Covered Slab 4
Kitchen Breakfast and Med A �`� 585
150
None
0.8
No
Hard surface Slab 4
Kitchen Breakfast and Med ! 926
10
None
0.8
No
Covered Slab 5
Guest � 312
56
None
0.8
No
Hard surface Slab 5
Guest �_ 104
0.1
None
0.8
No
BUILDING ENVELOPE - HERS VERIFICATIONv
01
02 03 04
Quality Insulation Installation (QII)
Quality Installation of Spray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa
Not Required
.,f �► Not Required Not Required —
♦f%
Registration Number: , Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards�`- 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xm1
CFOF-01
Page 10 of 14
WATER HEATING SYSTEMS
01
02
03
04
05
01
02
03
04
05
06•
Name
System Type
Distribution Type
Water Heater
Number of Heaters
Solar Fraction (%)
DHW Sys 1
DHW
Standard
DHW Heater 1
1
.0%
DHW Sys 1
DHW
Standard
DHW Heater 1
2
.0%
WATER HEATERS
01
02
03
04
05
06
07
08
Name
Heater Element Type
Tank Type
Tank Volume
(gal)
�,
EEhergy Factor or
Efficiency
Input Rating
Tank Exterior
Insulation
R -value
Standby Loss
(Fraction)
DHW Heater 1
Natural Gas
Large Storage
75 '.
0.8
85000-Btu/hr
0
0.0085
DHW Heater 1
Natural Gas
Large Storage
75 �~
0.8
85000-Btu/hr
0
T 0.0085
AZO
WATER HEATING - HERS VERIFICATION~�
•
01
02
03`
04
05
06
07
Name
Pipe Insulation
Parallel Piping
Compact Distribution
Point -of Use
Recirculation
Control
Central DHW
Distribution
DHW Sys 1.- 1/1
N/A
N/Ap
N/A
N/A
N/A
N/A
DHW Sys 1 - 1/2
N/A
Heat Pump System 1
N/A
N/A
N/A
N/A
r`
HVAC SYSTEMS �w
01
02
A V 03
04
05
06
07
Heating System
4a
Cooling System
Distribution
Floor Area
Name
System Type
Name Ducted
Name Ducted
System
Fan System
Served
HVAC Masterl
Heat Pump
Heat Pump System 1
Yes
Heat Pump System 1
Yes
Air Distribution
System 1
1003
HVAC great sitting2
Heat Pump
®
Heat Pump System 2
Yes
Heat Pump System 2
Yes
Air Distribution
System 2
1717
HVAC snug.dining3
Heat Pump ��
Heat Pump System 3
Yes
Heat Pump System 3
Yes
AirSystemDistribution
882
HVAC kitchen media4
Heat Pump
Heat Pump System 4
Yes
Heat Pump System 4
Yes
Air Distribution
System 4
1511
HVAC guest5
�t`e
Heat"Pump
Heat Pump System 5
Yes
Heat Pump System 5
Yes
Air Distribution
System 5
416
�.�
HVAC 2nd6
Heat Pump
w_
Heat Pump System 6
Yes
Heat Pump System 6
Yes
Air Distribution
System 6
1084
I�y
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE IOD
Project Name: McDonald Residence Ca culation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF*F-01
Page 11 of 14
HVAC - HEATING SYSTEMS: Heat Pumps
01
02
03 04 05
06 07
08
09
10
04
05
Heating
Cooling
Zonally
Multispeed
HERS
Name
Type
HSPF/COP Cap 47 Cap 17
SEER EER
Controlled
Compressor
Verification
Heat Pump System 1
SplitHeatPump
8.7 HSPF
46500
46500
15
12.5
No
No
Heat Pump System
1 -hers -cool
Heat Pump System 2
SplitHeatPump
8.5 HSPF
57000
57000
15
12.5
No
No
Heat Pump System
1 -hers -cool
Heat Pump System 3
SplitHeatPump
8.7 HSPF
35200
35200
15
12.5
No
No
Heat Pump System
1 -hers -cool
Heat Pump System
Heat Pump System 4
SplitHeatPump
8.5 HSPF
57000
570
�
15
12.5
No
No
1 -hers -cool
Heat Pump System
Heat Pump System 5
SplitHeatPump
8.7 HSPF
35200 <
5200
15
12.5
No
No
1 -hers -cool
Heat Pump System 6
SplitHeatPump
8.7 HSPF
�`
465007)
46500
15
12.5
No
No
Heat Pump System
1 -hers -cool
%4►
HVAC HEAT PUMP COOLING - HERS VERIFICATION
01
02 v
03
04
05
Name
Verified Airflow `�
Verified EER
Verified SEER
Verified Refrigerant Charge
HVAC Masterl SCSysRpt 1
350 �.
Not Required
Required
Verified
HVAC great sitting2 SCSysRpt 1
350
Not Required
Required
Verified
HVAC snug dining3 SCSysRpt 1
3550��7'
Not Required
Required
Verified
HVAC kitchen media4 SCSysRpt 1
350'.1
Not Required
Required
Verified
HVAC guests SCSysRpt 1
350
Not Required
Required
Verified
HVAC 2nd6 SCSysRpt 1
O, J 350
Not Required
Required
Verified
VWV
®�
.y
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCEOD
Project Name: McDonald Residence Ca culation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF F-01
Page 2 of 14
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
08
*44;;�
Verified Duct Design
Low -leakage
Supply Duct
Verification
Duct Leakage Target (%)
Verified Duct Location
Name
Type
Duct Leakage
Insulation R -value
Location
Return Duct
Bypass Duct
HERS Verification
Air Distribution System 1
Ducts located entirely in
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
System 1
Air Distribution System
conditioned space
W
6.0
Required
Not Required
Not Required
--
-hers -dist
Air Distribution System 2
Ducts located entirely in
conditioned space
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
System 2 -hers -dist
Air Distribution System 3
Ducts located entirely in
conditioned space
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
System 3 -hers -dist
A
Required
6.0
Required
Air Distribution System 4
Ducts located entirely in
Sealed and tested
8
Cod itioned Zone
Conditioned Zone
None
Air Distribution
conditioned space
Air Distribution System
Required��
�
Required
Not Required
System 4 -hers -dist
Air Distribution System 5
Ducts located entirely in
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
Air Distribution System
conditioned space
y
6.0
Required
Not Required
Not Required
_
System 5 -hers -dist
Air Distribution System 6
Ducts located entirely in
conditioned space
Sealed and tested
8
�A
Conditioned Zone
Conditioned Zone
None
Air Distribution
System 6 -hers -dist
4t–
HVAC DISTRIBUTION - HERS VERIFICATION
01
02
03 `'�
04
05 06
07
Duct Leakage
*44;;�
Verified Duct Design
Low -leakage
Name
Verification
Duct Leakage Target (%)
Verified Duct Location
Return Supply
Air Handler
Air Distribution System
Required
,�i6.0
Required
Not Required
Not Required
—
1 -hers -dist
�►
Air Distribution System
Required
W
6.0
Required
Not Required
Not Required
--
2 -hers -dist
��,
Air Distribution System
Required
6.0
Required
Not Required
Not Required
—
3 -hers -dist
Of
Air Distribution System
Required
6.0
Required
Not Required
Not Required
—
4 -hers -dist
Air Distribution System
Required��
6.0
Required
Not Required
Not Required
--
5 -hers -dist
Air Distribution System
°i
Required
y
6.0
Required
Not Required
Not Required
_
6 -hers -dist
ASA
eke
®y
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at: 2014-11-19 10:24:21
CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE I1OD .
Project Name: McDonald Residence Ca culation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xml
CF*F-01 -
Page 13 of 14
HVAC -FAN SYSTEMS
01
02
01
01
02
03
04
Name
Type
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
HVAC Fan 1 -hers -fan
HVAC Fan 2
Single Speed PSC Furnace Fan
0.58
HVAC Fan 2 -hers -fan
HVAC Fan 3
Single Speed PSC Furnace Fan
0.58
HVAC Fan 3 -hers -fan
HVAC Fan 4
Single Speed PSC Furnace Fan
0.58
HVAC Fan 4 -hers -fan
HVAC Fan 5
Single Speed PSC Furnace Fan
0.58
HVAC Fan 5 -hers -fan
HVAC Fan 6
Single Speed PSC Furnace Fan
0.58
HVAC Fan 6 -hers -fan
Ai
HVAC FAN SYSTEMS - HERS VERIFICATION
01
02
01
02Zi
03
Name
Verified Draw
Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan
6kequired
0.58
HVAC Fan 2 -hers -fan
44* Required
0.58
HVAC Fan 3 -hers -fan
Qv Required
0.58
HVAC Fan 4 -hers -fan
4V Required
0.58
HVAC Fan 5 -hers -fan
��� Required
0.58
HVAC Fan 6 -hers -fan
Required
0.58
rf]
IAQ (Indoor Air Quality) FANS
01
02
03
04
05
06
Name
IAQ CFM
IAQ Watts/CFM
IAQ Fan Type
IAQ Recovery
Effectiveness(%)
HERS Verification
DwellingUnit
208.63 �v
0.25
Default
0
Required
. *Z0
4
O
14P
V�
#J1
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at: 2014-11-19 10:24:21
CERTIFOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE IOD
Project Name: McDonald Residence Calculation Date/Time: 10:20, Wed, Nov 19, 2014
Calculation Description: Title 24 Analysis
Input File Name: McDonald Res-Cornerstone-Brian-14.xm1
CF*F-01
Page 14 of 14
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Jon Scott
Jon d. Scott
Signature Date:
Company:
Scott Design and Title 24, Inc,
11/19/2014
Address:
CEA/HERS Certification Identification (If applicable):
77-085 Michigan Drive
City/State ip:
Palm Desert, CA 92211
Phone: 11�11-
(76,0) 200-4780
RESPONSIBLE PERSON'S.DECLARATION STATEMENT
I certify the following under penalty of pedury, under the laws of the State of California: ,�%
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for�the building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of;C-ompliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.W
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agencyfor approval with this building permit application.
Responsible Designer Name:
Responsible Designer Signature:
Brian McLaury
Company: A v
Date Signed:
Cornerstone Architects ^�
Address:
License:
700 Bee Cave Road STE 200
City/State/Zip:
Phone:
Austin, TX 78746 ,��
(512) 329-0007
V
0�
Registration Number: ►, Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Stanch ds - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-11-19 10:24:21
r
4
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 WAR
R
Project Name
Date
McDonald Residence
11111912014
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form.with plans.
Building Envelope Measures:
110.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§110.6(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC and infiltration that meets the requirements of 10-111 (a).
110.7: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
110.8(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -2R Form.
§110.8(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §110.8(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§1 50.0 a : Minimum R-30 R-19 for Alterations insulation in wood -frame ceiling orequivalent U -factor.
§150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
*§1 50.0 c : Minimum R-13 insulation in 2x4 wood -frame wall R-19 in 2x6 orequivalent U -factor.
*§1 50.0 d : Minimum R-19 insulation in raised wood -frame floor orequivalent U -factor.
150.0 : Air retarding wrap is tested, labeled and installed according to ASTM E1677-95(2000) when specified on the CF -1R Form.
150.0 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150.0(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
§150.0(q) Fenestration Products. Fenestration separating conditioned space from unconditioned space or outdoors shall meet the
requirements of either Item 1 or 2 below:
1. Fenestration, including skylight products, must have a maximum. U -factor of 0.58.
2. The weighted average U -factor of all fenestration, including skylight products, shall not exceed 0.58.
EXCEPTION to Section 150.0(q)1: Up to 10 square feet of fenestration area or 0.5 percent of the Conditioned Floor Area, whichever is
reater, is exempt from the maximum U -factor requirement.
150.0 r Solar Ready Buildings. Shall meet the requirements of Section 110.10 applicable to the building project.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150.0 a 1A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible operable, and tight-fifting tight-fittingdamper and or a combustion -air control device.
§150.0(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§110.3(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §110.3(c)5.
§110.5: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150.0(h): Heating and/or cooling loads are calculated in accordance with ASHRAE SMACNA or ACCA.
§150.0(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 110.2(c).
§150.00)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally
wrapped with insulation having an installed thermal resistance of R-12 or greater.
§150.00)113: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
EnergyPro 6.3 by EnergySoft User Number: 6712 ID: Page 17 of 48
4
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 WAR
Project Name
Date
McDonald Residence
11111912014
§150.00)2A: All domestic hot water system piping conditions listed below, whether buried or unburied, must be insulated per TABLE
120.3-A.
i. The first 5 feet (1.5 meters) of hot and cold water pipes from the storage tank.
ii. All piping with a nominal diameter of 3/4 inch (19 millimeter) or larger.
iii. All piping associated with a domestic hot water recirculation system regardless of the pipe diameter.
iv. Piping from the heating source to storage tank or between tanks.
v. Piping buried below grade.
vi. All hot water pipes from the heating source to the kitchen fixtures.
§150.00)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards
Table 120.3-A.
§150.0(j)3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§150.00)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
§150.0(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC
Sections 601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed
level of R-6 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that
meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic
or tape is used to seal openings reater than 1/4 inch the combination of mastic and either mesh or tape shall be used
§150.0(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150.0(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150.0(m)7: Exhaust fans stems have back draft or automatic dampers.
§150.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150.0(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150.0(m)10: Flexible ducts cannot have porous inner cores.
§150.0(n)1: Systems using gas or propane water heaters, whether tank or on -demand, to serve individual dwelling units shall include
all the following components :
A. A 120V electrical receptacle that is within 3 feet from the water heater and accessible to the water heater with no obstructions;
B. A Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the space where the water
heater is installed;
C. A condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining
without pump assist,
D. A gas supply line with a capacity of at least 200,000 Btu/hr.
§150.0(0): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2 Ventilation and Acceptable Indoor Air Quality
in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in
Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§110.4(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines or built-up connections for future solar heating.
110.4(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150.0 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of 150.0
Residential Lighting Measures:
§150.0(k)1A: Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with Section 150.0(k) in accordance
with TABLE 150.0-A or TABLE 150.0-B as applicable.
150.0 k 1C: The wattage of permanently installed luminaires shall be determined asspecified by §130.0(c).
150.0 k 1 D: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency - 20 kHz.
§150.0(k)1E: Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume
no more than five watts of power per luminaire or exhaust fan as determined in accordance with Section 130.0(c). Night lights shall not
be required to be controlled by vacancy sensors.
EnergyPro 6.3 by EnergySoff User Number., 6712 ID: Page 18 of 48
4
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 WAR
Project Name
Date
McDonald Residence
11111912014
150.0 k 1 F: Lighting integral to exhaust fans in rooms other than kitchens, shall meet the applicable requirements of §150.0(k).
150.0(k)2: All switching devices and controls shall meet the requirements of §150.0(k)2.
§150.0(k)3: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts
for dwelling units larger than 2,500 ft2 may be exempt from the 50 percent high efficacy requirement when all
lighting in the kitchen is controlled in accordance with the applicable provisions in Section 150.0(k)2, and is also
controlled by vacancy sensors or dimmers.
§150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
§150.0(k)5: Lighting installed in bathrooms shall meet the following requirements:
A. A minimum of one high efficacy luminaire shall be installed in each bathroom; and
B. All other lighting installed in each bathroom shall be high efficacy or controlled by vacancy sensors.
§150.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be
high efficacy, or shall be controlled by either dimmers or vacancy sensors.
EXCEPTION 1: Luminaires in closets less than 70 square feet.
EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site.
§150.0(k)8: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the luminaire is airtight with air
leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150.0(k)9A: For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on
the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of items
ii or iii below; and
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and
automatically reactivates the motion sensor within 6 hours
iii. Controlled by one of the following methods:
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and
which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements:
At a minimum provides the functionality of an astronomical time clock in accordance with Section 110.9;
meets the Installation Certification requirements in Section 130.4; meets the requirements for an EMCS in
Section 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
§150.0(k)9A: For low-rise multi -family residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and
outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
following requirements:
i. Shall comply with Section 150.0(k)9A; or
ii. Shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by Section 150.0(k)9B or
Section 150.0(k)9D shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall
comply with the applicable requirements in Sections 110.9 130.0, 130.2 130.4, 140.7, and 141.0.
§150.0(k)10: Internally illuminated address signs shall comply with Section 140.8; OR not contain a screw -base socket, and consume
no more than five watts of power as determined according to §130.0(d).
§150.0(k)11: Lighting for residential parking garages for eight or more
vehicles shall comply with the applicable requirements for nonresidential garages in Sections 110.9, 130.0, 130.1,
130.4, 140.6, and 141.0.
§150.0(k)12A. In a low-rise multi -family residential building where the total interior common area in a single building equals 20 percent
or less of the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
§150.0(k)l2B. In a low-rise multi -family residential building where the total interior common area in a single building equals more than
20 percent of the floor area, permanently installed lighting in that building shall:
i. Comply with the applicable requirements in Sections 110.9, 130.0, 130.1, 140.6, and 141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
ingress and egress.
EnergyPro 6.3 by EnergySoft User Number: 6712 /D: Page 19 of 48
C.
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
McDonald Residence
System Name
HVAC Master
Date
11/19/2014
Floor Area
1,003
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 950
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 46,500
19,415
2,802 1,170
20,856
Total Output Btuh 46,500
0
Output Btuh/s ft 46.4
367
265
Cooling System
0
0
Output per System 47,500
0
0 0
0
Total Output Btuh 47,500
0
367
1 20,149
2,802
0
Total Output Tons 4.0
265
Total Output Btuh/s ft 47.4
Total Output s ft/Ton 253.4
21,386
Air System
CFM per System
1,600
HVAC EQUIPMENT SELECTION
Airflow cfm
1,600
Carrier 25HCC548A/FXDNF049 33,448
4,522
29,043
Airflow cfm/s ft
1.60
Airflow cfm/Ton
404.2
29,043
Jan 1 AM
Outside Air °i° 0.0%
Total Adjusted System.Output 33,448
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
4,522
Aug 3 PM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions I
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
72 OF
4 194
72 OF 89 OF 89 OF
f n .� ►
Heating Coil Supply Fan
1,600 cfm
89 OF
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
70/58°F
70/58°F 51/50°F 51/50°F
O
Cooling Coil Supply Fan 51 / 50 OF
1,600 cfm • - -- --
49.1 % om,m
70/58°F
Energ Pro 6.3 by Energ Soft
User Number: 6712 RunCode: 201411-19T10:27:27 /D:
Page 20 of 48
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
McDonald Residence
Date
11/19/2014
System Name
HVAC great sitting
Floor Area
1,717
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,543
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output perSystem 57,000
27,049
4,797 1,383
24,188
Total Output Btuh 57,000
0
Output Btuh/s ft 33.2
511
307
Cooling System
0
0
Output perSystem 57,000
0
0 0
0
Total Output Btuh 57,000
0
1 4,797
0
Total Output Tons 4.8
511
307
Total Output Btuh/s ft 33.2
Total Output s ft/Ton 361.5
28,071
24,802
Air System
CFM perSystem
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 25HCC560A/FXDNF061 36,083
10,682
35,601
Airflow cfm/s ft
1.16
Total Adjusted System Output 36,083
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
10,682 35,601
Aug 3 PM Jan 1 AM
Airflow cfm/Ton 421.1
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
72 OF
72 OF 89 OF 89 OF
ni
s
45"
Heating Coil Supply Fan o
2,000 cfm 88 F
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
70/60°F
70/60°F 53/53°F 53/53°F
c
Cooling Coil. Supply Fan 54 / 53 OF
2,000 cfm - --- ••-
55.5 % ROOM
70/60°F
J
Energ Pro 6.3 by Energ Soft
User Number: 6712 Run Code: 201411-19T10:27:27 /D:
Page 21 of 48
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Il
ct Name
PonaldResidence
System Name
HVAC snug dining
Date
11/19/2014
Floor Area
882
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems 1
COIL
CFM
Total ROOM Loads 1 596
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
PEAK
Heating S stem
Sensible
Latent CFM
Sensible
Output per System 35,200
11,275
2,464 557
10,083
Total Output Btuh 35,200
0
Output Btuh/s ft 39.9
213
128
Cooling System
0
0
Output per System 34,800
0
0 0
0
Total Output Btuh 34,800
0
213
11,702 2,464
0
Total Output Tons 2.9
128
Total Output Btuh/s ft 39.5
Total Output s ft/Ton 304.1
10,339
Air System
CFM per System 1,200
HVAC EQUIPMENT SELECTION
Airflow cfm 1,200
copy of Carrier 25HCC536A/FXDNF037 23,129 5,065
21,985
Airflow cfm/s ft 1.36
Airflow cfm/Ton 413.8
Outside Air °i° 0.0%
Total Adjusted System.Output 23,129 5,065
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK Aug 3 PM
21,985
Jan 1 AM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 72 OF 89 OF 89 OF
Outside Air
0 cfm Heating Coil Supply Fan
1,200 cfm 89 OF
ROOM ;
72 OF 72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 70/59°F 52/51 OF 52/51 OF
Outside Air c
0 cfmCooling Coil Supply Fan 52 / 51 OF
1,200 cfm ----
52.5% I ROOM
70/59°F 70/59°F
Energ Pro 6.3 by Energ Soft User Number: 6712 RunCode: 201411-19T10:27:27 /D: Page 22 of 48
4
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
McDonald Residence
Date
11/19/2014
System Name
HVAC kitchen media
Floor Area
1,511
ENGINEERING CHECKS
SYSTEM LOAD
Number of S stems
1
COIL
CFM
Total Room Loads 1,439
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation. 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK .
Heating System
Sensible
Latent CFM
Sensible
Output per System 57,000
25,577
4,222 1,602
27,951
Total Output Btuh 57,000
0
Output Btuh/s ft 37.7
484
355
Cooling System
01
0
Output per System 57,000
0
0 0
0
Total Output Btuh 57,000
0
4,222
0
Total Output ons 4.8
484
355
Total Output Btuh/s ft 37.7
Total Output s ft/Ton 318.1
26,544
28,661
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 25HCC560A/FXDNF061 36,511
10,089
35,601
Airflow cfm/s ft 1.32
Airflow cfmfTon
421.1
35,601
Jan 1 AM
Outside Air % 0.0 %
Total Adjusted System Output 36,511
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
10,089
Aug 3 PM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
72 OF
72 OF 89 OF 89 OF
f Cil � i
Heating Coil Supply Fan °
2,000 cfm 88 F
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
70/60°F
70/60°F 53/52°F 53/52°F
c
c
Cooling Coil Supply Fan 53 / 52 OF
2,000 cfm - - -
54.7 % ROOM
70/60°F
Energ Pro 6.3 by Energ Sof
User Number: 6712 RunCode: 2014-11-19T10:27:27 /D:
Page 23 of 48
4
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
McDonald Residence
Date
11/19/2014
System Name
HVAC guest
Floor Area
416
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems.
COIL COOLING
CFM Sensible
Total Room Loads 481 9,536
Return Vented Lighting 0
Return Air Ducts 180
Return Fan 0
Ventilation 0 0
Supply Fan 0
Supply Air Ducts 180
'TOTAL SYSTEM LOAD 9,897
PEAK COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output per System 35,200
1,162 457
8,300
Total Output Btuh 35,200
Output Btuh/s ft 84.6
105
Cooling System
0
Output per System 34,8001
0 0
0
Total Output Btuh 34,800
1,1621'
0
Total Output Tons 2.9
105
Total Output Btuh/s ft 83.7
Total Output s ftrron 143.4
8,511
Air System
CFM per System
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
copy of Carrier. 25HCC536A/FXDNF037 24,134
3,694
21,985
21,985
Jan 1 AM
Airflow cfm/s ft 2.88
Airflow cfm/Ton 413.8
Outside Air % 0.0 %
Total Adjusted System Output 24,134
1 (Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
3,694
Aug 3 PM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
72 OF
72 OF 89 OF 89 OF
Heating Coil Supply Fan
1,200 cfm
JU
o
89 F
ROOM ,
72 OF
I
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air Ar
0 cfm
70 / 58 OF
70/58°F 51/50°F 51/50°F
Cooling Coil Supply Fan 51 / 50 OF
1,200 cfm -- -
' 49.3% ROOM
70/58 OF
Energ Pro 6.3 by EnergySoft
User Number: 6712 RunCode: 201411-19710:27:27 ID:
Page 24 of 48
4
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
McDonald Residence
System Name
HVAC 2nd
Date
11/19/2014
Floor Area
1,084
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 875
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating S stem
Sensible
Latent CFM
Sensible
Output per System 46,500
17,813
3,029 808
14,482
Total Output Btuh 46,500
0
Output Btuh/s ft 42.9
337
184
Cooling System
0
0
output per System 47,500
0
0 0
0
Total Output Btuh 47,500
0
3,029
0
Total Output(Tons)'4.0
337
184
Total Output Btuh/s ft 43.8
Total Output s ft/Ton 273.9
18,4861
14,850
Air System
CFM per System
1,600
HVAC EQUIPMENT SELECTION
Airflow cfm
1,600
Carrier 25HCC548A/FXDNF049 33,261
4,765
29,043
Airflow cfm/s ft
1.48
Airflow cfmfTon
404.2
Outside Air %
0.0%
Total Adjusted System Output 33,261
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
4,765
Aug 3 PM
29,043
Jan 1 AM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
72 OF
72 OF 89 OF 89 OF
i
Heating Coil Supply Fan o
1,600 cfm 89 F
ROOM
72 OF
� 3 I
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
70/58°F
70/58°F 51/50°F 51/50°F
c
Cooling Coil Supply Fan 51 / 50 OF
1,600 cfm - �-- — –
49.5 % ROOM
70/58°F
1
EnergyPro 6.3 by Energ Soft
User Number: 6712 Run Code: 201411-19T10:27:27 /D:
Page 25 of 48
•
•
ROOM LOAD SUMMARY
Project Name Date
McDonald Residence 11/19/2014
System Name Floor Area
HVAC snug dining 882
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name I Room Name I Mult. I CFM I Sensible Latent CFM I Sensible Latent CFM Sensible
Snug and Dining Room Snug and Dining Room 1 596 11,275 2,464 596 11,275 2,464 5571 10,083
PAGE TOTAL
TOTAL*
596
11,275
2,464
557
10,083
596
11,275
2,464
557
10,083
Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnergySoft User Number: 6712 RunCode: 201411-19710:27:27 /D: Page 28 of 48
L�
C]
C7
ROOM LOAD SUMMARY
Project Name Date
McDonald Residence 11/19/2014
System Name Floor Area
HVAC kitchen media 1,511
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible I Latent CFM I Sensible I Latent CFM Sensible
Kitchen Breakfast and Medii Kitchen Breakfast and Me 1 1,4391 2.5,5771 4,222 1,4391 25,5771 4,2221 1,6021 27,951
PAGE TOTAL
TOTAL '
1,439 25,577
4,222
1,602
27,951
1,439 25,577
4,222
1,602
27,951
Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnemySoft User Number: 6712 Run Code: 2014-11-19710:27:27 /D: Page 29 of 48
•
ROOM LOAD SUMMARY
Project Name Date
McDonald Residence 11/19/2014
System Name Floor Area
HVAC guest 416
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. I CFM I Sensible I Latent CFM I Sensible Latent CFM I Sensible
Guest Guest 1 1 4811 9,5361 1,162 4811 9,5361 1,162 457 8,300
PAGE TOTAL
TOTAL•
481
9,5361
1,162
457 8,300
481
9,536
1,162
457 8,300
Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnerpySoft User Number: 6712 Run Code: 2014-11-19T10:27:27 /D: Page 30 of 48
•
lJ
•
ROOM LOAD SUMMARY
Project Name Date
McDonald Residence 11/19/2014
System Name Floor Area
HVAC 2nd 1,084
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. I CFM I Sensible I Latent CFM I Sensible Latent CFM I Sensible
2nd Floor 12nd Floor 1 1 8751 17,8131 3,029 8751 17,8131 3,029 8081 14,482
PAGE TOTAL
TOTAL '
875
17,8131 3,0291
808
14, 482
875
17,813 3,029
808
14,482
Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnemySoft User Number: 6712 Run Code: 2014-11-19710:27:27 /D: Page 31 of 48
•
•
ROOM HEATING PEAK LOADS
Project Name
McDonald Residence
Date
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master
Floor Area 1,003.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area U -Value
1,003.0 X 0.0260
2,031.4 X 0.0690
276.6 X 0.3900
pen .m = 104.0 X 0.7300
803.0 X 0.1020
X
X
X
X
X
X
X
X
X
X
X
X.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
through an interior surface to another room
X 1,003 X 15.80 X 0.368
Area Ceiling Height ACH
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT °F
Btu/hr
= 1,200
= 6,448
= 4,962
= 3,492
= 0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
16,102
46 = 4,754
R-38 Roof(R.38.2x14.16)
46
R-21 Wall (W.21.2x6.16)
46
Dual Metal Tint
46
Slab -On -Grade
46
'R-13 Wall
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
Page Total
/60] X
AT
TOTAL HOURLY HEAT LOSS FOR ROOM 20,856
EnergyPro 6.3 by EnergySoft User Number: 6712 RunCode: 201411-19710:27:27 ID: Page 32 of 48
ROOM HEATING PEAK LOADS
Project Name
McDonald Residence
Date
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great Sitting ROOM
Floor Area 1, 717.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
_
=
=
=
c
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof(R.38.2x14.16)
11717.0
0.0260
46
2,054
R-21 Wall (W.21.2x6.16)
1,400.5
0.0690
46
4,445
Dual Metal Tint
427.5
0.3900
46
7,669
Slab -On -Grade
perim = 56.0
0.7300
46
1,880
'R-13 Wall
1,462.0
0.1020
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,717 X
Area
another room
16.30 X 0.356
Height ACH
Page Total
/60] X
AT
16,049
= 8,139
TOTAL HOURLY HEAT LOSS FOR ROOM 24,188
EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 2014-11-19710:27:27 ID: Page 33 of 48
•
r�
U
ROOM HEATING PEAK LOADS
Project Name
McDonald Residence
Date
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Snug and Dining Room
Floor Area 882.0 ftZ
Indoor Dry Bulb Temperature 72 OF11
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
=
=
c
=
c
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
-
=
=
46
Btu/hr
R-38 Roof(R.38.2x14.16)
882.0
0.0260
46
1,055
R-21 Wall (W.21.2x6.16)
434.0
0.0690
46
1,378
Dual Metal Tint
126.0
0.3900
46
2,260
Slab -On -Grade
perim = 36.0
0.7300
46
1,209
"R-13 Wall
682.0
0.1020
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 882 X
Area
another room
16.30 X 0.356
Height ACH
Page Total
/60] X
AT
5,902
= 4,181
TOTAL HOURLY HEAT LOSS FOR. ROOM 10,083
EnergyPro 6.3 by EnergySoft User Number: 6712 RunCode: 2014-11-19710:27:27 ID: Page 34 of 48
•
1�
ROOM HEATING PEAK LOADS
Project Name
McDonald Residence
Date
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Kitchen Breakfast and Media
Floor Area 1,511.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U -Value
X 0.0260
X 0.0690
X 0.3900
X 0.5000
X 0.7300
X 0.1020
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to another room
16.30 X 0.356
Ceiling Height ACH
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
OT'F
46 =
46 _
Btu/hr
R-38 Roof(R.38.2x14.16)
1,511.0
1,807
R-21 Wall (W.21.2x6.16)
2,204.3
6,996
Dual Metal Tint
310.1
46
=
5,563
Wood Door
45.6
46
_
1,049
Slab -On -Grade
perim = 160.0
46
=
5,373
'R-13 Wall
1,211.0
0
=
0
=
=
=
_
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Page Total
/60] X 46
AT
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an interior surface
1.064 X 1,511 X
Area
20,788
_ 7,162
TOTAL HOURLY HEAT LOSS FOR ROOM 27,951
EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 201411-19710:27:27 ID: Page 35 of 48
•
C
ROOM HEATING PEAK LOADS
Project Name
McDonald Residence
Date
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest
Floor Area 416.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
1.064
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT `F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
c
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof(R.38.2x14.16)
416.0
0.0260
46
498
R-21 Wall (W.21.2x6.16)
702.0
0.0690
46
2,228
Dual Metal Tint
96.0
0.3900
46
1,722
Slab -On -Grade
perim = 56.0
0.7300
46
1,886
'R-13 Wall
216.0
0.1020
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an interior surface
X 416 X
Area
another room
14.00 X 0.415
Height ACH
Page Total
/60] X
AT
6,328
= 1,972
TOTAL HOURLY HEAT LOSS FOR ROOM 8,300
EnergyPro 6.3 by EnergySoR User Number: 6712 RunCode: 2014-11-19710:27:27 /D: Page 36 of 48
C7
•
ROOM HEATING PEAK LOADS.
Project Name
McDonald Residence
Date
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name 2nd Floor
Floor Area 1,084.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
Btu/hr
= 1,296
= 3,523
= 4,524
c 0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
9,343
46 = 5,138
R-38 Roof(R.38.2x14.16)
1,084.0
0.0260
46
R-21 Wall (W.21.2x6.16)
1,109.8
0.0690
46
Dual Metal Tint
252.2
0.3900
46
'R-13 Wall
884.0
0.1020
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,084 X
Area
another room
16.30 X 0.356
Height ACH
Page Total
/60] X
AT
TOTAL HOURLY HEAT LOSS FOR ROOM 14,482
Energ Pro 6.3 by EnergySoft User Number: 6712 RunCode: 2014-11-19T10:27:27 /D: Page 37 of 48
I , I
•
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
McDonald Residence 11/19/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Master Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,003.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor D Bulb Temperature 70 OF Outdoor Daily Range: 34 OF
Opaque Surfaces
R-38 Roof(R.38.2x14.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
"R-13 Wall
Orientation
(N)
(N)
(E)
(S)
(M
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,003.01
0.0260
56.0
420.0
0.0690
24.3
268.0
0.0690
32.6
676.8
0.0690
27.1
666.6
0.0690
32.4
803.0
0.1020
0.0
0.0
18.2
21.6
19.7
0.0
18.2
16.0
19.7
0.0
18.2
16.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fpnpstratinn
Window
Window
Window
Window
Window
Window
Window
Window
Window
Orientation
(N)
(E)
(E)
(S).
(S)
(S)
(S)
(S)
(S)
Shaded Unshaded
Btu/hr
1.460
01
1 5,5231
Area
.X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
. X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
0.0
18.2.
18.0
20.2
0.0
18.2
8.0
34.2
0.0
18.2
8.0
34.2
0.0
18.2
8.0
19.7
0.0
18.2
21.6
19.7
0.0
18.2
16.0
19.7
0.0
18.2
16.0
19.7
0.0
18.2
8.0
19.7
0.0
18.2
8.0
Page Total
363
274
274
157
425
315
315
157
1 2,4371
Internal Gain
Btulhr
Occupants
13.0 1 Occupants X
245 Btuh/occ.
= 73
Equipment
1,003 Floor Area X
0.50 w/sgft
Infiltration: 1.064 X 1.27 X 73.91 X 42 = 4,1
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,4151
Latent Gain Btu/hr
Occupants 3 0 Occupants X 155 Btuh/occ. = 466
Infiltration: 4,771 X 1.27 X 73.91 X 0.00523 = 2,336
Air Sensible CFM ELA AW
EnergyPro 6.3 by EnergySoft User Number: 6712 RunCode: 201411-19710:27:27 /D: Page 38 of 48 1
•
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
McDonald Residence 11/19/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Master Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,003.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranqe: 34 OF
ue Surfaces
Orientation
Area U -Factor CLTD'
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
Page Total
Items shown with an asterisk (•) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
FP_nPStratinn
Window
Window
Window
Window
Window
Window
Window
Window
Window
Orientatinn
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
c
-
=
=
=
=
=
=
=
0.0
18.2
21.6
19.7
0.0
18.2
8.0
19.7
0.0
18.2
18.0
19.7
0.0
18.2
3.8
33.1
0.0
18.2
3.8
33.1
0.0
18.2
3.8
33.1
0.0
18.2
18.0
33.1
0.0
18.2
54.0
33.1
0.0
18.2
18.01
33.1
Page Total
Btu/hr
425
157
354
126
126
126
596
1,789
596
Internal Gain Btu/hr
Occupants 3.0 Occupants X 245 Btuh/occ. = 737
Equipment 1,003 Floor Area X 0.50 w/sgft = 1.712
Infiltration: 1.064 X 1.27 X 73.91 X 42 = 4,181
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,415
Latent Gain Btu/hr
Occupants 3 0 Occupants X 155 Btuh/occ. = 466
Infiltration: 4,771 X 1.27 X 73.91 X 0.00523 = 2,336
Air Sensible CFM ELA OW
4
I EnergyPro 6.3 by EnemySoR User Number: 6712 Run Code: 201411-19T10:27:27 ID: Page 39 of 48 1
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
McDonald Residence
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Master
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,003.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
Window
W 0.0 X 18.2 +
8.0
X 33.1
= 265
Window
(lM 0.0 X 18.2 +
8.0
X 33.1
= 265
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
—
X +
X
=
X +
X
=
Page Total
530
Internal Gain
Btu/hr
Occupants
3.0 Occupants X 245
Btuh/occ.
=
737
Equipment
1,003 Floor Area X 0.50
w/sqft
=
1,712
Infiltration: 1.064
X 1.27 X 73.91 X 42 =
4,181
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
19,415
Latent Gain
Btu/hr
Occupants
3 0 Occupants X 155
Btuh/occ.
=
466
Infiltration: 4,771
X 1.27 X 73.91 X 0.00523 =
2,336
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
466
EnemyPro 6.3 by EnemySoft
User Number: 6712 Run Code: 2014-11-19710:27:27 ID:
Page 40 of 48
•
IA
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
McDonald Residence 11/19/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Great Sitting Room Outdoor Dry Bulb Temperature 112 OF
Floor Area 1, 717.0 ft-' Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranae: 34 OF
Opaque Surfaces
R-38 Roof(R.38.2x14.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
"R-13 Wall
Orientation
(N)
(NE)
(SE)
(SW)
(NM
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X.
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,717.01
0.0260
56.0
80.0
0.0690
29.0
329.5
0.0690
31.0
290.0
0.0690
31.0
701.0
0.0690
30.2
1,462.0
0.1020
0.0
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Window
Window
Window
Window
Window
Window
Window
Window
Window
Oriantatinn
(SE)
(SE)
(NM
(NM
(NM
(N W)
(NW)
(NW)
(NM
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
-
40.0
18.2
0.0
24.6
112.5
18.2
0.0
24.6
0.0
18.2
64.0
27.2
0.0
18.2
192.0
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
Page Total
Btu/hr
2,500
160
705
620
1,462
0
5,447
Btu/hr
728
2,046
1,740
5,221
103
103
103
103
103
10,2531
Internal Gain Btu/hr
Occupants 5 2 Occupants X 245 Btuh/occ. = 1,2
Equipment 1,717 Floor Area X 0.50 w/sqn = 2,9
Infiltration: 1.064 X 1:27 X 126.52 X 42 = 7,1
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 27.046
Latent Gain Btu/hr
Occupants 5 2 Occupants X 155 Btuh/occ. = 798
Infiltration: 4,771 X 1.27 X 126.52 X 0.00523 = 3,999
Air Sensible CFM ELA AW
I EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 2014.11-19T10:27:27 /D: Page 41 of 48
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
McDonald Residence
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Snug and Dining Room
Outdoor Dry Bulb Temperature
112 OF
Floor Area
882.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x14.16)
(N) 882.01 X 0.0260 .
X 56.0 =
1,284
R-21 Wall (W.21.2x6.16)
(SE) 152.0 X 0.0690
X 31.0 =
325
R-21 Wall (W.21.2x6.16)
(S 149 112.0 X 0.0690
X 31.0 =
240
R-21 Wall (W.21.2x6.16)
(NtM 170.0 X 0.0690
X 30.2 =
355
"R-13 Wall
682.0 X 0.1020
X 0.0 =
0
X
X =
X
X =
X
X =
X
X =
Page Total
2,203
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
Window
(SE) 0.0 X 18.2 +
72.0 X 24.6 =
1,774
Window
(NtM 0.0 X 18.2 +
18.0 X 27.2 =
490
Window
(NM 0.0 X 18.2 +
18.0 X 27.2 =
490
Window
(NK9 0.0 X 18.2 +
18.0 X 27.2 =
490
X +
X =
X +
X =
X +
X =
X +
X =
X +
X =
Page Total
3,242
Internal Gain
Btu/hr
Occupants .
2 6 Occupants X 245
Btuh/occ. =
648
Equipment
882 Floor Area X 0.50
W/sgft =
1,505
Infiltration: 1.064
X 1.27 X 64.99 X 42 =
3,676
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
11,275
Latent Gain
Btu/hr
Occupants
2 6 Occupants X 155
Btuh/occ. =
410
Infiltration: 4.771
X 1.27 X 64.99 X 0.00523 =
2,054
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
410
F-
EnemvPro 6.3 by EnemySoft
User Number: 6712 RunCode: 201411-19T10:27:27 /D:
Pa a 42 of 48
RESIDENTIAL ROOM COOLING LOAD SUMMARY
0 Project Name Date
McDonald Residence 7 11/19/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Kitchen Breakfast and Media Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,511.0 ft-- Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Daily Range:. 34 OF
•
Oaaaue Surfaces
R-38 Roof(R.38.2x14.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
Wood Door
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
•R-13 Wall
Orientation
(N)
(NE)
(SE)
(SE)
(SK0
(NIA9
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,511.0
0.0260
56.0
1,081.7
0.0690
29.0
518.6
0.0690
31.0
45.6
0.5000
31.0
232.0
0.0690
31.0
372.0
0.0690
30.2
1,211.0
0.1020
0.0
24.6
0.0
18.2
8.0
24.6
0.0
18.2
8.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
I Fenestration
Window
Window
Window
Window
Window
Window
Window
Window
Window
Oripntatinn
(NE)
(NE)
(NE)
(NE)
(SE)
(SE)
(SE)
(SE)
(SE)
Shaded Unshaded
1 4961
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
0.0
18.2
8.0
27.2
0.0
18.2
8.0
27.2
0.0
18.2
2.3
27.2
0.0
18.2
20.0
27.2
0.0
18.2
3.8
24.6
0.0
18.2
8.0
24.6
0.0
18.2
8.0
24.6
0.0
18.2
8.0
24.6
0.0
18.2
8.0
Page Total
7
Btulhr
218
218
63
544
1
94
197
197
197
Internal Gain Btu/hr
Occupants 4 5 Occupants X 245 Btuh/occ. = 1,111
Equipment 1,511 Floor Area X 0.50 w/sgft = 2,579
Infiltration: 1.064 X 1.27 X 111.34 X 42 = 6,298
Air Sensible . CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 25x77
Latent Gain Btu/hr
Occupants 4 5 Occupants X 155 Btuh/occ. = 703
Infiltration: 4,771 X 1.27 X 111.34 X 0.00523 = 3,519
Air Sensible CFM ELA pW
I EnergyPro 6.3 by EnemySoft User Number: 6712 Run Code: 201411-19T10:27:27 ID: Page 43 of 48
1 1,
•
e
L
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
McDonald Residence
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Kitchen Breakfast and Media
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,511.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 °F
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
X
X
X
X
=
X
X
=
X
X
=
Page Total
o
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area GLF
Btu/hr
Window
(SE) 0.0 X 18.2 +
8.0 X
24.6 =
197
Window
(SlM 0.0 X 18.2 +
72.0 X
24.6 =
1,774
Window
(NM 0.0 X 18.2 +
96.0 X
27.2 =
2,611
Window
(NIAq 0.0 X 18.2 +
15.0 X
27.2 =
408
Window
(NIA 0.0 X 18.2 +
30.0 X
27.2 =
816
Window
(NM 0.0 X 18.2 +
15.0 X
27.2 =
408
X +
X
=
X +
X
=
X +
X
=
Page Total
6,213
Internal Gain
Btu/hr
Occupants
4 5 Occupants X 245
Btuh/occ.
Equipment
1,511 Floor Area X 0.50 w/gq ft
Infiltration: 1.064
X 1.27 X 111.34 X 42 =
6,298
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
25,577
Latent Gain
Btulhr
Occupants
4 5 Occupants X 155
Btuh/occ.
=
703
Infiltration: 4,771
X 1.27 X 111.34 X 0.00523 =
3,519
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM703
Ene Pro 6.3 6 Ene Soft
User Number: 6712 Run Code: 2014-11-19T10:27:27 ID:
Page 44 of 48
•
•
C
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name711/19/2014
ate
McDonald Residence
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest
Outdoor Dry Bulb Temperature
112 OF
Floor Area
416.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x14.16)
(N) 416.0 X 0.0260
X
77.0 =
833
R-21 Wall (W.21.2x6.16)
(NE) 181.6 X 0.0690
X
34.0 =
426
R-21 Wall (W.21.2x6.16)
(SE) 254.4 X 0.0690
X
43.0 =
755
R-21 Wall (W.21.2x6.16)
(SM 266.0 X 0.0690
X
52.0 =.
954
"R-13 Wall
216.0 X 0.1020
X
0.0 =
0
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
2,968
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
Window
(NE) 0.0 X 21.7 +
42.4
X 32.0 =
1,359
Window
(SE) 0.0 X 21.7 +
5.3
X 45.9 =
243
Window
(SE) 0.0 X 21.7 +
16.1
X 45.9 =
739
Window
(SE) 0.0 X 21.7 +
16.1
X 45.9 =
739
Window
(SE) 0.0 X 21.7 +
16.1
X 45.9 =
739
X +
X =
X +
X =
X +
X =
X +
X =
Page Total
3,819
Internal Gain
Btu/hr
Occupants
1.2 Occupants X 245
Btuh/occ.
=
306
Equipment
416 Floor Area X 0.50
w/sgft
=
710
Infiltration: 1.064
X 1.27 X 30.65 X 42 =
1,734
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
9,536
Latent Gain
Btu/hr
Occupants
12 Occupants X 155
Btuh/occ.
=
193
Infiltration: 4,771
X 1.27 X 30.65 X 0.00523 =
969
Air Sensible
CFM ELA AIN
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
193
EnergyPro 6.3 by EneMySoft
User Number: 6712 Run Code: 201411-19710:27:27 /D:
Page 45 of 48
•
E
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
McDonald Residence 11/19/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name 2nd Floor Outdoor Dry Bulb Temperature 112 °F
Floor Area 1,084.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranae: 34 OF
Oaaaue Surfaces
R-38 Roof(R.38.2x14.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
"R-13 Wall
Orientation
(N)
(NE)
(SE)
(SVt9
(NVV9
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,084.0
0.0260
56.0
327.2
0.0690
29.0
398.6
0.0690
31.0
162.0
0.0690
31.0
222.0
0.0690
30.2
884.0
0.1020
0.0
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
Page Total
FP_nP_Stratinn
Window
Window
Window
Window
Window
Window
Window
Window
Window
Orientatinn
(NE)
(NE)
(NE)
(NE)
(NE)
(NE)
(SE)
(SE)
(SE)
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
27.2
0.0
18.2
3.8
24.6
0.0
18.2
3.8
24.6
0.0
18.2
3.8
24.6
Page Total
Btu/hr
1,578
655
853
347
463
0
3, 895
Btu/hr
103
103
103
103
103
103
94
1 941
1 9011
Internal Gain Btu/hr
Occupants 3 3 Occupants X 245 Btuh/occ. = 7
Equipment 1,084 Floor Area X 0.50 w/s4 ft
Infiltration: 1.064 X 1.27 X 79.88 X 42 =
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 17.813
Latent Gain Btu/hr
Occupants 3 3 Occupants X 155 Btuh/occ. = 504
Infiltration: 4,771 X 1.27 X 79.88 X 0.00523 = 2,525
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 504
EnerqvPro 6.3 by EnemySoft User Number: 6712 Run Code: 2014-11-19710:27:27 /D: Pa - e 46 of 48
0
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project NameDate
McDonald Residence 11/19/2014
ROOM INFORMATION' DESIGN CONDITIONS
Room Name
2nd Floor
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,084.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
70 OF
Outdoor Daily Range:
34 OF
Surfaces
rientation
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
GLF
=
=
=
=
=
=
=
0.0
18.2
15.0
24.6
0.0
18.2
15.0
24.6
0.0
18.2
15.0
27.2
0.0
18.2
15.0
27.2
0.0X
18.2+
15.0X
27.2=
0.0
18.2
15.0
27.2
0.0
18.2
15.0
Page Total
Fenestration
Window
Window .
Window
Window
Window
Window
Window
Window
Window
Orientation
(S K9
SM
(NIA
(NIA9
(NM
(NIAO
(NM
(NM
(NIA9
Shaded Unshaded
Area
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
0.0
18.2
15.0
24.6
0.0
18.2
15.0
24.6
0.0
18.2
15.0
27.2
0.0
18.2
15.0
27.2
0.0X
18.2+
15.0X
27.2=
0.0
18.2
15.0
27.2
0.0
18.2
15.0
27.2
0.0X
18.2+
63.0X
27.2=
0.0
1 18.2
1 12.5
27.2
Page Total
Btu/hr
Btu/hr
370
370
408
408
408
408
408
1,713
340
Internal Gain Btulhr
Occupants 3.3 Occupants X 245 Btuh/occ. = 797
Equipment 1,084 Floor Area X 0.50 w/sqn = 1,850
Infiltration: 1.084 X 1.27 X 79.88 X 42 = 4,518
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 17,813
Latent Gain Btu/hr
Occupants 3.3 Occupants X 155 Btuh/occ. = 504
Infiltration: 4,771 X 1.27 X 79.88 X 0.00523 = 2,525
Air Sensible CFM ELA AW
5041
I EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 2014-11-19T10:27:27 /D• Page 47 of 48
,q r, 1
•
r:
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
McDonald Residence
11/19/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
2nd Floor
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,084:0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
1 Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor.
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
-
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
Window
(NIM 0.0 X 18.2_ +
25.0
X 27.2 =
680
Window
(NKK 0.0 X 18.2 +
12.5
X 27.2 =
340
X +
X =
X +
X =
X +
X =
X +
X =
X +
X =
X +
X =
X +
X =
Page Total
1,020
Internal Gain
Btu/hr
Occupants
3 3 Occupants . X 245
Btuh/occ.
=
797
Equipment
1,084 Floor Area X 0.50
w/ggft
=
1,850
Infiltration: 1.064
X 1.27 X 79.88 X 42 =
4,518
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
17,813
Latent Gain
Btu/hr
Occupants
3 3 Occupants X :77155
Btuh/occ.
=
504
Infiltration: 4,771
X 1.27 X 79.88 X 0.00523 =
2,525
Air Sensible
i
CFM ELA OW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
504
EnemyPro 6.3 by EnemySoft
User Number: 6712 Run Code: 201411-19T10:27:27 /D: