13-0820 (RC)P.O. BOX 1504 VOICE (760)777-7012
78-495 CALLE TAMPICO�FAX (760) 777-7011
LA QUINTA; CALIFORNIA 92253 BUILDING & SAFETY DEPARTMENT INSPECTIONS (760)'777-7153
BUILDING PERMIT
Date: 8/30/13
Application Number: i3-00000820 Owner,
Property Address: 47100 WASHINGTON ST STE 101 MCDERMOTT COLIN J
APN:- 643-200-023- - 75200 CHIPPEWA D 6
Application description: REMODEL - COMMERCIAL INDIAN WELLS, CA 92210
Property Zoning: COMMUNITY COMMERCIAL
Application valuation: 50000 SCP Q 3 2013
Contractor:
Applicant: Architect or Engineer: ORR BUILDERS COO. FLAQ(JINTA
39301 BADGER, SUITE #300 FINANCEDEPT
r V PALM DESERT, CA 92211
(760) 360-6632
Lic. No.: 693077.
LICENSED CONTRACTOR'S DECLARATION WORKER'S COMPENSATION DECLARATION -
I hereby affirm under penatty of perjury that I am licensed under provisions of Chapter 9 (commencing with I hereby affirm under penalty of perjury one of the following declarations:
Section 7000) of Division 3 of the Business and Professionals Code, and my License is in full force and effect. _ I have and will maintain a certificate of consent to self-insure for workers' compensation, as provided
License Class: LB Licensee N{/o..:� 6693 077 - for by Section 3700 of the Labor Code, for the performance of the work for which this permit is "
Date: �w-�" "-'l��`i-1 44— ,(��� issued.
Date_ Contractor• r - ({! LV 1 have and will maintain workers' compensation insurance, as required by Section 3700 of the Labor '
. `tel— Code, for the performance of the work for which this permit is issued. My workers' compensation
OWNER-BUILDER DECLARATION insurance carrier and policy number are: -
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State License Law for the Carrier NTNL UNION Policy Number 1960920-2012
following reason (Sec. 7031.5, Business and Professions Code: Any city or county that requires a permit to _ I certify that, in the performance of the work for which this permit is issued, I shall not employ any
construct, alter, improve, demolish, or repair any structure, prior to its issuance, also requires the applicant for the person in any manner so as to become subject to the workers' compensation laws of California,
,permit to file a signed statement that he or she is licensed pursuant to the provisions of the Contractor's State and agree that, if I should become subject to the workers' compensation provisions of Section
License Law (Chapter 9 (commencing with Section 7000) of Division 3 of the Business and Professions Code) or 3700 of the Labor //e, I shall forthwith comply with those provisi s.
that he or she is exempt therefrom and the basis for the alleged exemption. Any violation of Section 7031.5 by "-�
any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars.($ 500).: Date_: j Applicant:
(_) I, as owner of the property, or my employees with wages as their sole compensation, will do thework, and
the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS UNLAWFUL, AND SHALL
Contractors' State License Law does not apply to an owner of property who builds or improves thereon, SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO ONE HUNDRED THOUSAND
and who does the work himself or herself through his or her own employees, provided that the DOLLARS ($100,000). IN ADDITION TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN y
improvements are not intended or offered for sale. If, however', the building or improvement is sold within SECTION 3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY'S FEES.
one year of completion, the owner-builder will have the burden of proving that he or she did not build or _
improve for the.purpose of sale.). APPLICANT ACKNOWLEDGEMENT
(_ 1 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. IMPORTANT Application is hereby made to the Director of Building and Safety for a permit subject to the -
7044, Business and Professions Code: The Contractors' State License Law does not apply to an owner of conditions and restrictions set forth on this application.
property who builds or improves thereon, and who contracts for the projects with a contractor(s) licensed 1 . Each person upon whose behalf this application is made, each person at whose request and for
pursuant to the Contractors' State License Law.). - whose benefit work is performed under or pursuant to any permit issued as a result of this application,
1 _ 1 I am exempt under Sec. BAP.C. for this reason the owner, and the applicant, each agrees to, and shall defend, indemnify and hold harmless the City .
of La Quinta, its officers, agents and employees for any act or omission related to•the work being
performed under or following issuance of this permit. "
Date: Owner: 2. Any permit issued as a result'of this application becomes null and void if work is not commenced -
within 180 days from date of issuance of such permit, or cessation of work for 180 days will subject
CONSTRUCTION LENDING AGENCY permit to cancellation. ,
I hereby affirm under penalty of perjury that there is a construction lending agency for the performance of the I certify that I have read this application and state that the above information is correct. I. agree to comply with all -
work for which this permit is issued (Sec. 3097, Civ. C.1. city and county ordinances and state laws relating to il i
bung construction, and hereby authorize representatives
of this c my to enter upon the above-mentioned pro rt for inspection purposes.
Lender's Name:
Dat_e_: Signature (ApplicanYorAgen
Lender's Address:
Application Number
. . . 13-00000820
Permit . . .
ELECTRICAL
2013
Additional desc .
Permit Fee
47.66
Check Fee
.00
Issue Date . . . .
,-Plan
Valuation . . . .
0
Expiration Date
2/26/14
Qty Unit Charge
Per
Extension
1.00 23.8300
LS ELEC
FIXTURES, FIRST 20
23.83
1.00 23.8300
----------------------------------------------------------------------------
EA ELEC
SERVICES
.23.83
Permit . . .
MECHANICAL
2013
Additional desc .
Permit Fee . . .
11.92
Plan Check Fee
.00
Issue Date . . . .
Valuation . . .
. 0
Expiration Date ".
2/26/14
Qty Unit Charge
Per
Extension
1.00 11.9200
EA MECH
APPL REP/ALT
11.92
Permit
PLUMBING 2013
Additional desc .
Permit.Fee23.84
Plan Check Fee
.00
Issue Date . . .
Valuation . . .
. 0
Expiration Date
2/26/14
t
Qty Unit Charge
Per
Extension
1.00 11.9200
EA PLBG
FIXTURE/TRAP
11.92
• 1.00 11.9200
EA PLBG
WATER INST/ALT/REP
11.92
Permit . . .
REMODEL 2013
Additional desc .
Permit Fee
484.77
Plan Check Fee
.00
Issue Date . . . .
Valuation
0
Expiration Date
2/26/-14
Qty Unit Charge
Per
Extension
1.00 71.5000
EA MISC
PARTITION
71.50
1.00 48.6200
LS MISC
REMODEL,-1ST 100 SF
48.62
17.00 21.4500
EA MISC
REMODEL, ADDL 500 SF
364.65
Special Notes and Comments
TENANT IMPROVEMENT UPPER
AND LOWER
LEVELS. 8329 SQ. FT.
August •30", 2013 10:30:,07'
AM JJOHNSON.
Application Number
13-00000820
----------------------------------------------------------------------
Other Fees
. . . . . ..
BLDG STDS ADMIN (SB1473)
2.00
PLAN CHECK, ELECTRICAL
35.75
-
PLAN CHECK, REMODEL
424.71
PLAN CHECK, MECHANICAL
4.77
PLAN CHECK, PLUMBING
35.76
STRONG MOTION (SMI) - COM
10.50
Fee summary
Charged
Paid Credited
Due
Permit Fee Total
568.19
.00 .00
568.19
Plan Check Total
.00
.00 .00
.00
Other Fee Total
513.49
.00 .00
513.49
Grand Total
1081-.68
.00 .00
1081.68
r
LQPERMIT
.
hjpa�
Bin #
ZVA a,
rr d ,,,� �A
City of LQuinta e > .
Building 8r Safety Division J(/( ' o.2Z�13
P.O. Box 1504, 78-495 Calle Tampico
WLa Quinta, CA 92253 - (760) 777-7012Cp FJ7-y®��
Building Permit Application and Tracking112 1 ��
Permit #
��
Project Address:
Owner's Name:
A. P. Number: 3 —,P&0
Address: S1r• C ► �� ,
Legal Description:
Contractor: Tg-b
City,ST Zi
<:<:>
Telephone:
Address:
Project Description: 7;wA
City, ST, Zip: ""'""`
lae4coevv%e*&04�
�OGJ� EL
Telephone:
x:><>>.. .....:: ..........
s
State Lic. # :
City Lic. #.:
Arch., Engr., Designer: s y
y
Address: 1 Z Z Q
City, ST, Zip: /V 'F' Qle
�Z
Tele hone:
P 3
::<::>::;:>r<:»<»>:<.;:.::.:;>::;:.;;;;;;;;:.>:;;:::•;;:•:;_
CnttionT e:
osruc YP Occupancy
State Li c. #:
Project tYPa (circle le one :New Add'nRepair Dem 0
Name of Contact Person: ®� �_
Sq. Ft.: ,2 q #
Stories: Z
#Units:
Telephone # of Contact Person:
Estimated Value of Project: a
APPLICANT: DO NOT WRITE BELOW THIS LINE
#
Submittal
Req'd
Recd
TRACKING
PERMIT FEES
Plan Sets
Plan Check submitted71Z,
Item
Amount
Structural Calcs.
Reviewed, ready or correctio s
Plan Check Deposit
Truss Cates.
Called Contact Per
3
Plan Check Balance.
Title 24 Calcs.
Plans picked upi. v •
%
Construction
Flood plain plan
Plans resubmitted
Mechanical
Grading plan
2°" Review, ready for correctio&ue
Electrical
Subcontactor List
Called Contact Person
Plumbing
Grant Deed
Plans picked up
S.M.I.
H.O.A. Approval
Plans resubmitted
Grading
IN HOUSE:-
'' Review, ready for corrections/issue
Developer Impact Fee
Planning Approval
Called Contact Person
A.I.P.P.
Pub. Wks. Appr
Date of permit issue
School Fees
Total Permit Fees
(tiltiS DaPT APP. 7� dil3
23
�C op �,.
2
POST IN A CONSPICUOUS PLACE
30-DAY TEMPORARY
Certificate of Occupancy
Expires: NOVEMBER 22, 2013
Community Development Department
This Certificate is issued pursuant to the requirements of Chapter 1 Section 111 of the California
Building Code, certifying that, at the time of issuance, this structure was in compliance with the
provisions of the Building Code and the various ordinances of the City regulating building
construction and/or use.
BUILDING ADDRESS: 47-100 WASHINGTON ST, STE 101
Use classification: OFFICE – KELLER WILLIAMS REALTY Building Permit No.: 13-0820
Occupancy Group: B Type of Construction: VB Land Use Zone: CC
Code Edition: 2010 Sprinkler Installed: YES Occupant Load: 56
Owner of Building: MCDERMOTT, COLIN J
Address: 75200 CHIPPEWA DR
City, ST, ZIP: INDIAN WELLS, CA 92210
_____________________________________ By: AJ ORTEGA
Building Official Date: OCTOBER 23, 2013
OCT -24-2013 THU 07;16 AM RIVERSIDE COUNTY FIRE FAX NO, 17608637072 P. 01
Riverside County Fire Department Fire protection Planning Section
Rlvepltl6 Office: 2300 M61rt(et St., Ste, 1 n0, Rivarelde, CA 02501 Ph (951) 050-4777 Fax (Pn1) 9564BUG
Pairn DaeortOfllce: 77.933 Las Mon(ajlns Rd , N 201 Palm Dosert, CA 92211.4131 Fh• (760) 863.8986 Fix (760) 863.7072
Fire Department Clearance/Release
Date: 1 x/23/2013
To: LA ❑UINTA B&S
Fax:
Tract/Parcel Map #: HILGENSERG REALTY
Permit/Lot #: LAQ-13-TI-024
Job Site Address: 471t7a 1NA5H1NGTDN AVF
City, state, Zip LA QLIINTA
® Final For Recordation
�j Release For Building Permit(s)
❑ Shell Final only (No Tenant)
® Final for Sprinkler System
❑ Release For Residential Sprinkler Installation
❑ Building Plan Check Fees Paid, Water Requirement Met- if wafer applicable
Building Plan Check Fees Not Paid
❑ Residential Sprinkler Plan Check Fees Paid
f Residential Sprinkler Plan Check Fees Not Paid
Other Fees
Fees Not Required
If you should have any questions, please contact the appropriate Riverside County Fire Protection Planning office for
further assistance, TFZtC
Pont Name of Plan Reviewer/Inspector Approved Release
Sent By: Print Name
Form C - RaOsod 3101 12 01 2
- Building & Safety Department
78495 Calle Tampico ,
�� 9ti5 PO Box 1504
OF "La Quinta, CA 92253
(760) 777-7012 voice - (760) 777-7011 fax
To: Greg Butler,.Building Official To PD: July 18, 2013
From: Les Johnson, CDD Director Due date: ASAP
Permit,# - 13-820 Status: 1 st Review .
Building Plans Approval
(This is an approval to issue a Building Permit)
The Planning Division has reviewed the Building Plans•for the following project:
Description: Shell Improvement
Address or general location: 47100 Washington Street
Applicant Contact: Kim Melrose (760)969-8520
The Planning Division finds that:
...these Building Plans do riot require Planning Division approval.
y� ...these Building Plans are approved by the Planning Division.
❑ ...these Building Plans require corrections. Please forward a copy of the
attached corr tions to the applicant. When the corrections are made
2leask return hem to the Planning Division for review.
22
Les hnson, mmunity Development Director Date,
r
Note: PLEASE RETURN PLANS WITH GREENSHEET TO THE BUILDING.
DIVISION. 1
"IN
PROUDLY SERVING THE
UNINCORPORATED AREAS
OF RIVERSIDE COUNTY
AND THE CITIES OF.
BANNING
BEAUMONT
CALIMESA
CANYON LAKE
GOACHELLA
DESERT HOT SPRINGS
EASTVALE
INDIAN WELLS
INDIO
JURUPA VALLEY
LAKE,ELSINORE
LA QUINTA
MENIFEE
MORENO VALLEY
NORCO
PALM DESERT
PERRIS
RANCHO. MIRAGE
RUBIDOUx CSD
SAN JACINTO
TEMECULA
WILDOMAR
BOARD OF
SUPERVISORS:
KEVIN JEFFRIES
DISTRICT 1
JOHN TAVAGLIONE
DISTRICT 2
JEFF STONE
DISTRICT 3
JOHN BENOIT
DISTRICT 4
MARION ASHLEY
DISTRICT 5
A
RIVERSIDE COUNTY FIRE DEPARTMENT
IN COOPERATION WITH
;?
THE CALIFORNIA DEPARTMENT OF FORESTRY AND FIRE PROTECTION
77-933 Las Montanas Rd., Ste. #201, Palm Desert, CA 92211-4131 • Pho ) 8
• Fax 760 863-7072
www.rvcfire.org.
August 23, 2013 - PVG ti
. QUZN�P NS
RE: TENANT IMPROVEMENT PLAN CHECK -Non Structural NZ -(l OE
LAQ-I3-TI-024'Hilgenberg Reality 47-100 Washington I i iinta, CA'.
You have been issued a release for a tenant improvement on an existing building. THIS IS
NOT AN OCCUPANCY PERMIT. t
It is prohibited to use/process or store any materials in this occupancy that would classify it
as an "H" occupancy per Sec. 307 of the 2010 CBC.
THE FOLLOWING CONDITIONS MUST BE MET PRIOR TO INSPECTION:
Install door hardware and exit signs as per Chapter 10 of the CBC.
A minimum 2AIOBC Fire Extinguisher, (State Fire"Marshal Approved) must be mounted in
a visible location within, 75' walking distance from any point in your building or suite. Fire
extinguishers can be installed by a licensed extinguisher company with a State Fire Marshal
service tag attached to the extinguisher, or purchased from -a retail store with a sales receipt
attached. A licensed fire extinguisher company must service extinguisher yearly.
All breakers must be labeled and a clearance of 36 inches must be maintained around the
panel at all times.
A durable sign stating "This door to remain unlocked during business hours" shall be placed
on or adjacent to the front exit door. The sign shall be in letters not less than one inch high
on a contrasting background.
An approved audible interior notification alarm device shall be provided in approved
location. A C-10 licensed contractor must submit plans, designed in accordance with
NFPA 72 to the Fire Department for review and approval prior to installation
Approved suite addresses shall be placed in such a position to. be plainly visible and. legible
from the street. Said numbers shall contrast with their background.
Provide key(s) to the tenant space for inclusion in the main building Knox Box. Key(s)
shall have durable and legible tags affixed for identification. Key(s) shall be provided at
time of final inspection.
As it may be necessary to maintain proper fire -sprinkler protection due to constructions
changes, fire sprinkler.system plans.for the 'tenant improvement area may be required to be
submitted to the Fire Department for review.
01
BUILDING ENERGY ANALYSIS REPORT
Fit Cropy
PROJECT:
Hilgenberg Realty Tenant Improvement
47-170 Washington Street
La Quinta, CA 92253
Project Designer:
Steven Randel, Architect
1221 Harrison Street. Studio 7
San Francisco, CA 94103
(415) 336-3255
Report Prepared by:
Tim Scott
Scott Design and Title 24, Inc,
77-085 Michigan Drive
Palm Desert, Ca 92211FAPPROVED
F LA QUINTA
(760) 200-4780 & SAFETY DEPT.
FOR CONST CTION
DATE ✓:
Job Number:
Date:
AUG 16 208
8/9/2013
oRRBUILDERS
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2013-08-09712:42:34 ID:
TABLE OF CONTENTS
Cover Page 1
Table of Contents 2
Nonresidential Performance Title 24 Forms 3
Form ENV -MM Envelope Mandatory Measures 9
Form LTG -MM Lighting Mandatory Measures 10
Form MECH-MM Mechanical Mandatory Measures 11
4
CIT`( OF LA QUINTA
BUILDING & SAF
TY
DEPT
a COVED
® UCTION
F
DATE -- BY
EnergyPro 5.1 by EnergySoft Job Number: ID: User Number: 6712
C
C
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1 C
Project Name
Date
Hilgenberg Realty Tenant Improvement
1 8/9/2013
Project Address
Climate Zone
Total Cond. Floor AreaAddition
Floor Area
47-170 Washington Street La Quinta
CA Climate Zone 15
5,554
n/a
GENERAL INFORMATION
Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Relocatable - indicate ❑ specific climate zone ❑ all climates
Phase of Construction: ❑ New Construction ❑ ' Addition ❑ Alteration
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed to
comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This
certificate applies only to a Building using the performance compliance approach.
The documentation author hereby certifies that the documentation is accurate and com ete.
Documentation Author
Name Tim Scott
Signature
Company Scott Design and Title 24, Inc,
Date 8/9/2013
AddressPhone
77-085 Michigan Drive
760 200-4780
( )
City/State/Zip Palm Desert, Ca 92211 CEPE #NR08-09-3706
The Principal Designer hereby certifies that the proposed building design represented in this set of
construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with
.,any other calculations submitted with this permit application. The proposed building has been designed to meet the energy
efficiency requirements contained in sections 110, 116 through 118, and 140 through 149 of Title 24, Part 6. Please
check one:
ENV. LTG. MECH.
hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
❑ ❑ ❑ sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
I I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section
❑ ❑ ❑ 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
❑ ❑ ❑ because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538 and 6737.1.
'Principal Envelope Designer
Name Steven Randel
Signature
Company -i.+ , z �
Steven Randel, Architect Date 4: ' Z � — - � . —
AddressLicense #
1221 Harrison Street. Studio 7 C- O
City/State/Zip San Francisco, CA 94103 Phone (415) 336-3255
Principal Mechanical Designer
Name
Signature
Company Mechanical Compliance Not In the Scope Of This Submittal Date
Zene
Address -W--
City/State/Zip R o
Principal Lighting Designer
B PPRovED
Signature G
Name
KI
ONti
Company Lighting Compliance Not In The Scope Of This Submittal C
Address Lice se #
City/State/Zip nAn.. P
INSTRUCTIONS TO APPLICANT COMPLIANCE & WORKSHEETS (check box if worksh_eets wa4ncktded
m ENV -1C Certificate of Compliance. Required on plans. ❑ MECH-1C Certificate of Compliance. Required on plans.
❑ LTG -1C Certificate of Compliance. Required on plans. ❑ MECH-2C Air/Water Side/Service Hot Water & Pool Requirements.
11 ❑ LTG -2C Lighting Controls Credit Worksheet. ❑ MECH-3C Mechanical Ventilation and Reheat.
❑ LTG -3C Indoor Lighting Power Allowance. ❑ MECH-5C Mechanical Equipment Details.
Energ Pro 5.1 by Energ Soft User Number: 6712 RunCode: 2013-08-09712:42:34 ID: Page 3 of 11
f
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF -1C
Project Name Date
Hilgenberg Realty Tenant Improvement 8/9/2013
ANNUAL TDV ENERGY USE SUMMARY kBtu/s ft- r
Standard Proposed Compliance
Energy Component Design Design Margin............_.._..........__-___...__._......_.__..._...__..........................
Space Heating
Space Cooling
Indoor Fans
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Lighting
Receptacle
Process
Process Lighting
TOTALS
0.31
0.30
0.01
212.67
209.65
3.02
74.20
74.02
0.18
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
59.47
59.47
0.00
85.90
85.90
0.00
0.00
0.00
0.00
0.00
0.00
0.00
432.54
429.33
3.21
Percent better than Standard 0.7% 0.7 % excluding process)
BUILDING COMPLIES
GENERAL INFORMATION
Building Orientation (lM 270 deg Conditioned Floor Area 5,554 sqft.
Number of Stories 1 Unconditioned Floor Area o sqft.
Number of Systems 6 Conditioned Footprint Area 5.554 sqft.
is
Number of Zones 1 Natural Gas Available On Site res
Orientation Gross Area Glazinq Area Glazing Ratio
Front Elevation
Left Elevation
Rear Elevation
,Right Elevation
Total
Roof
(lM
442
(N)
998
(E)
527
(S)
1,164
Proposed
0.850W/sqft.
3,131
4,037
sqft.
sqft.
sgft.
sqft.
sqft.
sqft.
134
382
95
436
1,046
0
sqft.
sqft.
sqft.
sgft.
sqft.
sqft.
30.3%
38.2%
18.0%
37.5%
33.4%
0.0%
Prescriptive Lighting Power Density
Standard
0.850 W/sgft.
Proposed
0.850W/sqft.
Prescriptive Values for
Comparison only. See
Prescriptive Envelope TDV Energy
232,527
439,765
LTG -1 C for allowed LPD.
Remarks:
Existing lights to be relocated.
Existing mechanical ductwork to be relocated and extended.
L!
& SA
BUILDING
VES
o�CoR
uc-f ION
F
X136
DATE
•
Ener Pro 5.1 by Ener Soft User Number: 6712 RunCode: 2013-08-09712:42:34 ID:
Page 4 of 11
C
C
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1 C
Project Name
Hilgenberg Realty Tenant Improvement
Date
8/9/2013
ZONE INFORMATION
Floor Inst. Ctrl. Allowed LPD Proc.
Area LPD Credits Area Tailored Loads
System Name Zone Name Occupancy T ft
Type s . W/sf' W/sf 2 W,,Sf 3 W/sf ° W/sf
AC 1 thru 6 Tenant Improvement Comp Bldg Office 5,554 "0.850
Notes: 1. See LTG -IC 2. See LTG -2C 3. See LTG -3C 4. See LTG -4C Items above require special documentation
items marked with asterisk, see LTG -1 -C b others b others
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
The local enforcement agency should pay special attention to the items specified in this checklist. These Items require special written
-justification and documentation, and special verification to be used with the performance approach. The local enforcement agency
determines the adequacy of the justifications, and may reject a building or design that otherwise complies based on the adequacy of the
special Justification and documentation submitted.
T.
13UILDINU
FOR CO
The exceptional features listed in this performance approach application have specifically 6 en reviewed JAdeqluate writ i justification an
documentation for their use have been provided by the applicant. B
Authorized Signature or Stamp DATE
I -
FnamvPrn .5 1 by FnerovSoft User Number: 6712 RunCode: 2013-08-09712:42:34 ID: Page 5 of 11
•
•
CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C
AND FIELD INSPECTION ENERGY CHECKLIST
Project Name Date
Hilgenberg Realty Tenant Improvement 1 8/9/2013
Project Address
47-170 Washington Street La Quinta
Climate Zone
15
Total Cond. Floor Area
5,554
Addition Floor Area
n/a
GENERAL INFORMATION
Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Schools (Public School) ❑ Bledlocatable g. Public School m Conditioned Spaces [3 Unconditioned Spaces
❑ Skylight Area for Large Enclosed Space Z 8000 ftz (If checked include the ENV -4C with submittal)
Phase of Construction: ❑ New Construction ❑ Addition ❑ Alteration
Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit)
Front Orientation: N, E, S, W or in Degrees:
1270 deg
FIELD INSPECTION ENERGY CHECKLIST
OPAQUE SURFACE DETAILS
INSULATION
Ta /ID
AssemblyType
l0
'.
a
c
oOC
cN
d W
O z
/0
4
:3
'� W
A
0 M
° d
7
% l0
W>
C
rN, �-
% 3
W a
0 3
f0
�>
y
7
� a
v
%
aci
C CL
O d
c
._
a
C
O r
y
y
l0
a
l0
U.
1
Roof
4,037
(N)
0.043
R-22
4.2.1-A6
Existing
❑
❑
2
Wall
616
(N)
1 0.102
R-13
4.3.1-A3
Existing
❑
❑
3
Wall
432
(E)
0.102
R-13
4.3.1-A3
Existing
❑
❑
4
Wall
643
(S)
0.102
R-13
4.3.1-A3
Existing
❑
❑
5
Wall
85
(SW)
0.102
R-131
1
14.3.1-A3
Existing
❑
❑
6
Wall
225
(W)
0.102
R-13
4.3.1-A3
Existing
❑ 1❑
7
Wall
83
(NM
0.102
R-13
4.3.1-A3
Existing
❑
❑
8
Slab
5,554
(N)
0.730
None
4.4.7-A1
Existing
❑
❑
❑
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance.
FENESTRATION SURFACE DETAILS
Tag/ID
Fenestration
Type
:'
a
03
W
O Z
S
LL
>
S rz
U2 -E v`;
LL 'o N Z 'o > o :°
> N 2- u) uJ O 0 1)
w
a
m
a
1
Window
382
(N)
0.710
Default 0.6001 Default ❑ Existing
j ❑
❑
2
Window
95
(E)
0.710
Default 0.600 Default ❑ Existing
❑
❑
3
Window
385
(S)
0.710
Default 0.600 Default ❑ Existing
❑
❑
4
Window
53
(SW
0.710
Default 0.600 u
[35
Window
51
(SIM
0.530
N C f-Wl'
[3
6
Window
81
(VV)
0.710
Def ult 6 (�e?au E ifit 1-s tin g'
❑
7
Window
53
(NM
0.710
Def It ..0. t
❑ ❑
- C
❑ [3-
13 ❑
❑ ❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96. DAT
2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate actiou-tocGffeeti y uildin la ' ecessary.
EnergyPro 5.1 by EnergySoft User Number., 6712 RunCode: 2013-08-09712:42:34 ID: Pa e 6 of 11
•
0
CERTIFICATE OF COMPLIANCE (Part 2 of 3)
AND FIELD INSPECTION ENERGY CHECKLIST
ENV -1 C
Project Name
Hilgenberg Realty Tenant Improvement
Date
8/9/2013
ROOFING PRODUCT COOL ROOFS
(Note if the roofing product is not CRRC certified, this compliance approach cannot be used). Go to Overall Envelope Approach or
Performance Approach.
CHECK APPLICABLE BOX BELOW IF EXEMPT FROM THE ROOFING PRODUCT "COOL ROOF" REQUIREMENTS:
Pass
Fail'
N/A
❑ Roofing compliance not required in Climate Zones 1 andl6 with a Low -Sloped. 2:12 pitch or less.
❑
❑
❑
❑ Roofing compliance not required in Climate Zone 1 with a Steep -Sloped with less than 5 Ib/ft2. Greater than 2:12 pitch.
❑
❑
❑
❑ Low-sIopedi Wood framed roofs in Climate Zones 3 and 5 are exempted, solar reflectance and thermal emittance or
SRI that have a U -factor of 0.039 or lower. See Opaque Surface Details roof assembly, Column H of ENV -2C.
❑
❑
❑
❑ Low -sloped Metal building roofs in Climate Zone 3 and 5 are exempted, solar relectance and thermal emittance or SRI
that have a U -factor of 0.048 or lower. See Opaque Surface Details roof assembly below, Column H of ENV -2C.
❑
❑
❑
❑ The roof area covered by building integrated photovoltaic panels and building integrated solar thermal panels are
exempted. Solar reflectance and thermal emittance or SRI, seespreadsheet calculator at www.energy.ca.govttitle24/
❑
❑
❑
❑ Roof constructions that have thermal mass over the roof membrane with a weight of at least 25 Ib/ft are exempt from
the Cool Roof criteria below.
❑
❑
❑
❑ High-rise residential buildings and hotels and motels with low -sloped roofs in Climate Zones 1 through 9, 12 and 16 are
exempted from the low -sloped roofing criteria.
❑
❑
❑
1. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
CRRC Product ID Roof Slope Product Weight Product Aged Solar Thermal
Number' s 2:12 > 2:12 < NNW 2 5lb/ft2 Type 2 Reflectance Emmitance SRI5 Pass Fai16
❑ ❑ ❑ ❑ ❑ 4
❑ ❑
❑ ❑ ❑ ❑ ❑ 4
❑ ❑
❑ ❑ ❑ ❑ ❑ 4
❑ ❑
❑ ❑ ❑ ❑ ❑ 4
❑ ❑
❑ ❑ ❑ ❑ ❑ 4
❑ ❑
❑ ❑ ❑ ❑ ❑ 4
❑ ❑
1. The CRRC Product ID Number can be obtained from the Cool Roof Rating Council's Rated Product Directory at
www.coolroofs.org/products/search.php
2. Indicate the type of product is being used for the roof top, i.e. single -ply roof, asphalt roof, metal roof, etc.
3. If the Aged Reflectance is not available in the Cool Roof Rating Council's Rated Product Directory then use the Initial Reflectance value from the
same directory and use the equation (0.2+0.7(p;,,;flal — 0.2) to obtain a calculated aged value. Where p is the. Initial Solar Reflectance from the Cool
Roof Rating Council's Rated Product Directory.
4. Check box if the Aged Reflectance is a calculated value using the equation above.
5. The SRI value needs to be calculated from a spreadsheet calculator at http://www.energv.ca.clov/title24/
6. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
To apply Liquid Field Applied Coatings, the coating must be applied across the entire roof surface and meet the dry mil thickness or coverage
recommended by the coatings manufacturer and meet minimum performance requirements listed in §118(i)4. Select the applicable coating:
❑ Aluminum -Pigmented Asphalt Roof Coating
❑ Cement -Based Roof Coating
❑ Other
Discrepancies.
P F10 v ED
APP
FO
ION
I DATE BY
EnemyPro 5.1 by EnemySoft User Number.' 6712 RunCode: 2013-08-09712:42:34 ID:
Page 7 of 11
0
,7
•
CERTIFICATE OF COMPLIANCE (Part 3 of 3) ENV -1 C
AND FIELD INSPECTION ENERGY CHECKLIST
Project Name
Hilgenberg Realty Tenant Improvement
Date
8/9/2013
Required Acceptance Tests
Designer:
This form is to be used by the designer and attached to the plans. Listed below is the acceptance test for Envelope
Fenestrations system. The designer is required to check the acceptance tests and list all the fenestration products that
require an acceptance test. If all the site -built fenestration of a certain type requires a test, list the different fenestration
products and the number of systems. The NA7 Section in the Appendix of the Nonresidential Reference Appendices
Manual describes the test. Since this form will be part of the plans, completion of this section will allow the responsible
party to budget for the scope of work appropriately.
Enforcement Agency:
Systems Acceptance. Before Occupancy Permit is granted for a newly constructed building or space or whenever new
fenestration is installed in the building or space shall be certified as meeting the Acceptance Requirements.
The ENV -2A form is not considered a complete form and is not to be accepted by the enforcement agency unless the
boxes are checked and/or filled and signed. In addition, a Certificate of Acceptance forms shall be submitted to the
enforcement agency that certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of §10-103(b) of Title 24 Part 6. The field inspector must receive the properly filled
out and signed forms before the building can receive final occupancy. A copy of the ENV -2A for each different
fenestration product line must be provided to the owner of the building for their records.
Test Description ENV -2A Test Performed By:
Fenestration Products Name or ID Area of like Building Envelope
Requiring Testing or Verification Products Acceptance Test
New Double Metal Tinted 51 m
11
13
13
13
13
13
13
13
13
13
-P1.
®.JIL
❑ FOR O
EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2013-08-09712:42:34 ID: Page 8 of 11
•
•
•
ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV -MM
Project Name
Date
Hilgenberg Realty Tenant Improvement
8/9/2013
DESCRIPTION
Building Envelope Measures:
§118(a): Installed insulating material shall have been certified by the manufacturer to comply with the California Quality
Standards for insulating material, Title 20 Chapter 4, Article 3.
§118(c): All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of
Sections 2602 and 707 of Title 24, Part 2.
§118(f): The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value
of no less than R-13 between framing members.
All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed,
§117(a):
weatherstripped or otherwise sealed.
Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft:? of
§116(a) 1: window area, 0.3 cfm/ft.z of door area for residential doors, 0.3 cfm/ft.z of door area for nonresidential single doors
(swingingand sliding , and 1.0 cfm/ft.2 for nonresidential double doors (swinging).
§116(a) 2: Fenestration U -factor shall be rated in accordance with NFRC 100, or the applicable default U -factor.
Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the
§116(a) 3:.
applicable default SHGC.
Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be .
116 b
§ ()' weatherstripped (except for unframed glass doors and fire doors).
OF �` (LJINTA
CITY. DEPT.
&SAF
BUILDING
�®
�P
FOR C NST CTION
DATE
Enerqwro 5.1 by Ener Soft User Number 6712 RunCode: 2013-08-09712:42:34 ID: Page 9. of 11
•
L�
•
LIGHTING MANDATORY MEASURES: NONRESIDENTIAL LTG -MM
Project Name
Date
Hilgenberg
Realty Tenant Improvement
8/9/2013
Indoor Lighting
Measures:
§131(d): Shut-off Controls
For every floor, all interior lighting systems shall be equipped with a separate automatic control to shut off the lighting.
1.
This automatic control shall meet the requirements of Section 119 and may be an occupancy sensor, automatic time
switch, or other device capable of automatically shutting off the Ii htin .
2
Override for Building Lighting. Shut-off: The automatic building shut-off system is provided with a manual, accessible
override switch in sight of the lights. The area of override is not to exceed 5,000 square feet.
§119(h):
Automatic Control Devices Certified: All automatic control devices specified are certified, all alternate equipment shall
be certified and installed as directed by the manufacturer.
§111:
Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for the project are certified and listed in the
Directory. All installed fixtures shall be certified.
§131(a):
Individual Room/Area Controls: Each room and area in this building is equipped with a separate switch or occupancy
sensor device for each area with floor -to -ceiling walls.
Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 square feet and more than 0.8 watts
§131(b):
per square foot of lighting load shall be controlled with bi-level switching for uniform reduction of lighting within the
room.
Daylight Area Control: All rooms with windows and skylights that are greater than 250 square feet and that allow for
the effective use of daylight in the area shall have 50% of the lamps in each daylit area controlled by a separate switch;
§131(c):
or the effective use of daylight cannot be accomplished because the windows are continuously shaded by a building on
the adjacent lot. Diagram of shading during different times of the year is included on plans.
§131(c):
Display Lighting. Display lighting shall be separately switched on circuits that are 20 amps or less.6.
Outdoor Lighting Measures:
§130(c)1:
Mandatory lighting power determination for medium base sockets without permanently installed ballasts
§132(a):
All permanently installed luminaires with lamps rated over 100 Watts either have a lamp efficacy of at least 60 lumens
per Watt or are controlled by a motion sensor.
All Luminaires with lamps rated greater than 175 Watts in hardscape area, including parking lots, building entrances,
§132(b):
canopies, and all outdoor sales areas meet the Cutoff Requirements.
§132(c)1:
All permanently installed outdoor lighting meets the control requirements listed.
Building facades, parking lots, garages, canopies, and outdoor sales areas meet the Multi -Level Lighting Requirements
§132(c):
listed.
QU�N�CP
P
GX� G
8�,���N �� G1\0
OP J' 0
F 3�� ,
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-08-09712:42:34 ID: Pae 10 of 11
Ci
s
•
MECHANICAL MANDATORY MEASURES: NONRESIDENTIAL MECH-MM
Project Name
Date
Hilgenberg Realty Tenant Improvement
8/9/2013
Equipment and System Efficiencies
§111:
Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply
with the applicable standard.
§115(a):
Fan type central furnaces shall not have a pilot light.
§123:
Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC
equipment, shall be insulated in accordance with Standards Section 123.
Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of
§124:
the CMC Standards.
Controls
§122(e):
Each space conditioning system shall be installed with one of the following:
1A.
Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not
explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an
accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch
shall be capable of programming different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's prograrn and time setting for at least 10 hours if power is interrupted; or
1 B.
An occupancy sensor to control the operating period of the system; or
1 C.
A 4 -hour timer that can be manually operated to control the operating period of the system.
Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the
2
system as required to maintain a setback heating and/or a setup cooling thermostat setpoint.
Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000
square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided
§122(g).
with isolation devices, such as valves or dampers that allow the supply of heating or cooling to be setback or shut off
independently of other isolation areas; and shall be controlled by a time control device as described above.
Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to
§122(c):
authorized personnel.
Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the
§122(b):
heating load can be met by the heat pump alone
Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the
zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the
§122(a&b):
control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be
capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
Ventilation
Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified
§121(e):
on these plans.
All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all
§122(f):
openings to the outside, except for combustion air openings.
Ventilation System Acceptance. Before an occupancy permit is granted for a newly constructed building or space, or a
§121(f):
new ventilating system serving a building or space is operated, for normal use, all ventilation systems serving the
building ors ace shall be certified as meeting the Acceptance Requirements for Code Compliance
Service Water Heating Systems
§113(c)
Installation
3.
Temperature controls for public lavatories. The controls shall limit the outlet Temperature
2
Circulating service water -heating systems shall have a control capabl of C_TT"Fni'_Aff ti u p
1DEPT,
when hot water is not required.
CON�B
EDATEP�ROVEDN
k-emyPm 5.1 b EnergySoft User Number: 6712 RunCode: 2013-08-09712:42:34 ID: Pae11 of 11
Tddf 4 4 Q"
P.O. Box 1504
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
BUILDING & SAFETY DEPARTMENT
IW10.`I
NON RESIDENTIAL PLAN CHECK CORRECTION LIST (os)
DATE: 7/30/13
STATUS: FIRST REVIEW
PLAN CHECKED BY: JJOHNSON
TELEPHONE NUMBER: (760) 777-7130
ADDRESS: 47-100 WASHINGTON ST.
DESCRIPTION: TENANT
IMPROVEMENT
APPLICANT: HILGENBERG
PLAN CHECK #: 13-820
(760) 777-7012
60) 777-7011
This submittal has been chedced for compliance with the 2010 California Building, Mechanical, Electrical,
Plumbing, and Energy Codes, and the City of La Quinta Municipal Code.
APPLICANT:
The following items are being returned to you for
correction:
2 SETS OF PLANS
THIS CORRECTION LIST
BUILDING DEPARTMENT STAFF:
DO NOT accept any resubmittal unless ALL of the
following items are included:
REDLINED SET
2 NEW REVISED SETS
THIS CORRECTION LIST / WITH RESPONSES.
FIRE DEPT APPROVAL
PLANNING DEPT APPTOVAL
r. c
INSTRUCTIONS TO APPLICANT:
1) Provide a written response to each comment on the following pages, noting specifically whw the correction
can be found. Responses such as, "Sheet N3," or, "Handrails shall be per CBC Section 1003," are not
acceptable. Show or note specifically how compliance with a code requirement is achieved Responses
such as, "Added note 16 on sheet X3" are appropriate and will help expedite your back check.
2) Corrections may not be made by handwriting on existing drawings. Revise originals and reprint Plans and/or
Calculations as necessary.
3) Return all red -marked Plans and/or Calculations with your resubmilhal.
4) Each sheet of resubmitted Plans and/or Calculations shall include the preparer's name and telephone number
and shall be wet -signed by the preparer. If the preparer is a licensed architect or engineer, all documents
prepared by that licensed individualshall also bear his/her stamp as prescribed by California Business and
Professions Code Section 5536. Resubmittals will not be accepted with signatures missing.
5) Return this list, your written responses, and all documents listed above with your resubmittal
Non Residential Plan Check Correction List (os) Page 1 of 3
City of La Quinta
SECTION A - GENERAL
1) Provide written evidence ofPlanning Department approval of this Project. Contact thePlanning Department
directly at (760) 777-7125.
2) Provide written evidence of Riverside County Fire Department approval of this Project. Contact the Fire
Department directly at (760) 863-8886.
SECTION C - ARCHITECTURAL
1) Exit signs are required Please revise plan demonstrating compliance with the following requirements:
a) Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress
travel is not immediately visible to the occupants. In no case shall the exit sign placement exceed the lesser
of, 100 feet or the listed viewing distance for the signkCBC § 1011.1)
b) Exit signs shall be internally or externally illuminated(CBC §1011.2)
c) Each exit access door shall be identified by a tactile exit sign with the words, "EXIT ROUTE" (CBC
§ 10 11.3, Item 4)
d) Exit signs shall be illuminated at all times and be able to remain illuminated for a period of 90 minutes in
the case of primary power failure (CBC § 10 11.5.3)
2) Exit doors must be able to open from the inside without the use of a key, special knowledge or effort. See
exception for allowing keylocking hardware on the main exit of Group B, F, M and S Occupancies. Surface
mounted flush or surface bolts are prohibited. Automatic flush bolts are allowed on pairs of doors, provided the
door with the flush bolt has no knobs or surfacemounted hardware and the unlatching of any leaf requires only
a single operation. (CBC § 1003.3.1.8)
3) Provide accessibility to service counters demonstrating compliance with sdions (CBC §111813.5 and
§ 111813.6) Forward Reach and Side Reach respective ly.Show counter elevations or sections.
4) The bottom 10 inches of all doors except automatic and slidng shall have smooth, uninterrupted surface to
allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.C(BC
§ 1133B.2.5.3) See plans for areas not in compliance.
SECTION D - MECHANICAL
1) Provide Mechanical Plan demonstrating compliance with MECH-I-C Certificate of Compliance When
new or replacement space -conditioning ducts are installed to serve an existing building, the new ducts shall
meet the requirements of Section 124, and if they meet the criteria of Section 144(k) 1, 2, and 3, the duct
system shall be sealed and labeled as confirmed through field✓erification and diagnostic testing in accordance
with procedures for duct sealing of existing duct systems to meet one of the requirements of California Energy
Code § 149(b)1 D, (i) or (ii).
SECTION G — ENERGY EFFICIENCY (2010 California Energy Code)
1) Alterations to existing nonresidential or alterations in conjunction with a change in building occupancy to a
Non Residential Plan Check Correction List Page 2 of 3
City of La Quinta
nonresidential occupancy shall meet the requirements of Subchapter 6 of the 2005 California Energy Code,
Section 149 showing compliance by Prescriptive or Performance approach
2) Provide complete Energy Calculations reflecting thc2010 Standards for this project. Due to lack of
information in this submittal, a comprehensive review will be performed at next submittal.
3) Provide Revised and signed form PERF -1 energy compliance statement.
4) Provide Revised form ENV- 1-C energy compliance statement.
5) Provide Completed and signed form LTGI-C energy compliance statement.8 %" x 11" Format.
6) Provide Completed and signed form OLTGI-C energy compliance statement. 8 V? x 11" Format.
7) Specify the following information from Energy CalculationsDn Lighting Plan:
a) Fixture Legend, Show Wattages, Quantities, Types, Etc.(Provide Track Lighting Cut sheets showing
compliance with Section 130 (c) 3 & 4)
b) Switching Requirements, Show compliance with Mandatory Measure Section 119, 130, and 131.
c) Compliance Areas (Tailored, Area Category) Square footages, Uses and Areas of Proposed Credits.
8) Under the mandatory measures, where an encicsed space is greater han 250 W, the electric lightingwithin
daylit area must be switched so that the lights can be controlled;eparately from the non-daylit areas. It is
acceptable to achieve control in thedaylit area by being able to shut off at least 50% of the lamps witin the
daylit area. (California Energy Code 2005, Section 131 (c) 1)Show compliance with all Mandatory
Measures specified on Calculations. LTGMM.
9) When the Area Category Method is used to calculate the allowed total lighting power for an entire buildigg
main entry lobbies, corridors, restrooms, and support functions shall be treated as separate areaRevise
calculations to reflect the areas and factors specified in Table 146C
10) Enclosed office spaces with areas equal to or less than 250square feet enclosed by floor -to -ceiling permanent
partitions are exempt fromcalculating the portable lighting wattageNote on plans: "Upon installation of the
portable lighting systems the building inspectorjf portable lighting is determined to be used for a primary
lighting source, may require resubmittal of compliance documentation using installed and equipment data."
SECTION K - MISCELLANEOUS COMMENTS
1) Red marks on Plans, even if not specifically mentioned in this list, indicate items needing correction. Revise
Plans as necessary and provide written response, notingwhere correction can be found.
2) Provide one copy each of the Site Plan and Floor Plan for the County Assessor's office. While not required for
resubmittal, this administrative item must be addressed prior to issuance of building permit.
3) Provide contractor information to complete building permit application form.
4) Provide proof of current City business license.
END CORRECTION LIST
As further information is provided and reviewed, additional corrections may be required.
Non Residential Plan Check Correction List Page 3 of 3