RIVERSIDE COUNTY FIRE DEPARTMENT
In cooperation'with-the
\ , . California Department of Forestry and Fire Protection
ciu vvesr man, iacinro Avenue • rerns, %,anwrnia ycvru.• 1z?w/ tFw,P-&,P• rax tmm) yyLrwiu
November 28, 2001
6?
BBG Architects
20371 Irvine Ave, Suite 120,
Santa Ana Heights, CA 92707-5651 ry
Re: Non -Structural Building4Plan,Review- +�
LAQ-01-BLDG-088 /Sales Pavrllon D_esign,Centec
Fire Department personnel have. reviewed and' approved the plans you submitted for the above
referenced project. Please be advised'the following conditions apply as a part of the conditions for the
issuance of a building permit:
1) The Fire Department is required to set a minimum fire flow for the remodel.or construction of all
commercial buildings using the procedu're�established in the 1998 CFC. A fire flow of 2,250 gpm for
a 2 -hour duration at 20 psi residual operating pressure. must be available before any combustible
material is placed on the job site:
2) The required fire flow shall be available from a Standard hydrant (6"x 4" x 21/2') located not less • .
than 165' from the lot frontage.
3) Provide written certification from the appropriate water company that hydrants will be installed and
will produce the required fire flow.
The following conditions must be met prior to occupancy:
4) Egress doors for Design Center and the Sales Pavilion shall comply with `CBC Sec. 1003.3.1.8 for
proper door hardware.
5) Install portable fire extinguishers per NFPA, Pamphlet #10, but not less than 2A1 OBC in rating.
Contact certified extinguisher company for proper placement of equipment.
6) Approved -building address shall be placed in such a position as to be plainly visible and legible from
the street.. Said numbers shall contrast with their background.
Please contact the Fire Department Planning & Engineering staff for final inspection prior to occupancy.
All questionsregarding the meaning of these conditions should.be referred to the Fire Department
Planning & Engineering staff at (760) 863-8886.
Sincerely,
FRANK KAWASAKI
Chief Fire Department Planner
By
Walter-Brandes
Fire Safety Specialist
H:%PE21wPDATAUAW INTAIPROJECrSBLD(3_PCUAa01-BLDG-M.doc