BUILDING PERMIT
J Date: 2/28/06
Application Number: 05-00005176. _ Owner:
Property Address: 80637 VIA PESSARO Harry Bederhan
APN: 772-500-'059- - - 44910 Yucca Avenue
Application description: `DWELLING SINGLE FAMILY DETACHED - LANCASTER, CA 93534
Property Zoning: LOW DENSITY RESIDENTIAL o
t Application valuation: 449259
.- Contractor:
Applicant: Architect or Engineer: -BLECHEN CONSTRUCTION pI ,
P.O. BOX 60 p%gR.O
LA QUINTA, CA 92247 g
(7 60.)-238-6986 �o�.
Lic. No.: OOR SQUARE FOOT Lic. No.:.*811182
'LICENSED CONTRACTOR'S DECLARATION - WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury -that I amlicensed under provisions of Chapter 9 (commencing with " I hereby affirm under penalty of perjury one of the following declarations: _
- Section 7000) of Division 3 of the Business and Professionals Code, and my License is in full force and effect." _ I have and will maintain a certificate of consent to self -insure for workers' compensation, as provided
License Class: B - License N .: 811182 - for by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued.
Contractor: _ I have and will maintain workers' compensation insurance, as required by Section 3700 of the Labor
`... -•J �' - i - Code, for the performance of the work for which this permit is issued. My workerscompensation • ' : -
•
OWNEFIBUILDER DECLARATION r-•--•- • insurance carrier and policy number are:
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State License Law for the��C_arrier EXEMPT .,! Policy Number EXEMPT
following reason (Sec. 7031 .5, Business and Professions Code: Any city or county that requires a permit to - - _ I certify that, in the performance of the work for which this permit is issued, i shall not employ any 'r
construct, alter, improve, demolish, or repair any structure, prior to its issuance, also requires the applicant for the - -person in any manner so as to become subject to the workers' compensation laws of California,
permit to file a signed statement that he or she is licensed pursuant to the provisions of the Contractor's State and agree that, if Ishould become subject to the workers' compensation provisions of Section 1 '•
License Law (Chapter 9 (commencing with Section 7000) ofDivision 3 of the Business and Professions Code) or 700 of the Labor Code `I s a I forthwith c ply 'F those rovisions.
that he or she is exempt therefrom and the basis for the alleged exemption. Any violation of Section 7031.5 by i '
any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500).: -Date- � � Applicant:-
(_ 1 I, as owner of the property, or my employees with wages as their sole compensation, will do the work, and ✓
the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The ' WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS UNLAWFUL, AND SHALL
'Contractors' State License Law does not apply to an owner of property who builds or improves thereon, .SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO ONE HUNDRED THOUSAND
and who does the work himself or herself through his or her own employees, provided that the DOLLARS ($100,000). IN ADDITION TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN '
improvements are not intended or offered for sale. If, however, the building orimprovement is sold within SECTION 3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY'S FEES..
one year of completion, the owner -builder will have the burden of proving that he or she did not build or _
improve for the purpose of sale.). -APPLICANT ACKNOWLEDGEMENT
1 1 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. IMPORTANT Application is hereby made to the Director of Building and Safety for a.permit subject to the
7044, Business and Professions Code: The Contractors' State License Law does not apply to an owner of . conditions and restrictions set forth on this application.
property who builds or improves thereon, and who contracts for the projects with a contractor(s) licensed 1 . Each person upon whose behalf this application is made, each person at whose request and for
pursuant to the Contractors' State License Law.). whose benefit work is performed under or pursuant to any permit issued as a result of this application,
( _') I am exempt under Sec. , B.&P.C. for this reason the owner, and the applicant, each agrees to, and shall defend, indemnify and hold harmless the City
of La Quinta, its officers, agents and employees for any act or omission related to the work being
performed'under or following issuance of this permit.
Date: Owner: 2. Any permit issued as a result of this application becomes null and void if work is not commenced
within 180 days from date of issuance of such permit, or cessation of work for 180 days will subject
CONSTRUCTION LENDING AGENCY permit to cancellation. I _
I hereby affirm under penalty of perjury that there is a construction lending agency for the performance of the I certify that I have read this application and state that the above information is correct. I agree to comply with all "
work for which this permit is issued (Sec. 3097, Civ. C.). -- city and county ordinances and state laws relating to building construction, and hereby aut orize representatives
of this cou ty to enter. upon the, above-mentioned propert fo LQ ion pu ses.
Lender's Name:
�� Y
Date: � r Signature (Applicant or Agent):
Lender's Address:
LQPERAIIT
Application -Number .
. . . . 05-00005176 '
Permit . . BUILDING PERMIT
Additional desc .
Permit Fee
1864.50
Plan Check Fee
1211.93
Issue Date
Valuation . .
449259
Expiration Date..
8/27/06
Qty Unit Charge
Per
Extension
BASE
FEE
639.50
350.00 3.5000
THOU BLDG
100,001-500,000
1225,.00
Permit MECHANICAL'
Additional.desc
,
Permit Fee
157.00
Plan Check Fee
15.00
Issue Date
Valuation . .
.0
Expiration Date
8/27/06.:`
e
Qty Unit Charge
Per_'.
.,
Extension
BASE
FEE..
15.00
5.00 9. 00.00,
EA MECH
FURNACE <=100K
45.00
5.00 9.0000
EA MECH
B/C <=3HP/100K BTU
45.00
7.00. < 6.5000
EA MECH
`VENT FAN �, _
45.50
1.00 6.5000
EA MECH
EXHAUST HOOD
6.50
Permit ELEC-NEW RESIDENTIAL
nal desc
a Permit�Fee
228.76
Plan Check Fee.
57.19.
Issue Date
Valuation
.
0
Expiration Date `.a
8/27/06
r
~Charge
Qty, Unit
Per
Extension •_
BASE
FEE15.00
,OR
5244.00 .0350"
ELEC
NEW RES -"1 2 FAMILY
183.54
761.00• .0200
ELEC
GARAGE OR NON-RESIDENTIAL
15.22
1.00 15.0'000
EA ELEC
TEMPORARY POWER POLE.
--------------------------
15.00
Permit . . PLUMBING
Additional desc
Permit Fee . .
230.25
Plan Check Fee
61.31
;Issue Date . . . .
Valuation
0
Expiration Date
8/27/06
Qty Unit Charge
Per
Extension
BASE
FEE
15.00-
25.00 6.0000
EA PLB
FIXTURE
150.00
LQPERDiIT,
LQPERMIT
Application Number
05-00005176
Permit . .
PLUMBING
Qty Unit Charge.
Per
Extension
.00 15.0000
EA PLB BUILDING SEWER
.00.
2.00 6.0000
EA PLB. ROOF DRAIN
12.00
2.00 7.5000
EA PLB WATER HEATER/VENT
15.00
1.00 3.0000
EA PLB WATER INST/ALT/REP
3.00
1.00 9.0000
EA PLB LAWN SPRINKLER SYSTEM
9.00
15.00 .7500"EA-
PLB GAS PIPE >=5
11.25
1-.00 15.0000
------------------------------------------------------------------------------
EA- PLB GAS METER
15.00
Permit . . . . . .
GRADING PERMIT
l
Additional desc ....
Permit Fee"
15.00- Plan Check Fee
.00
Issue Date
Valuation
0
Expiration bate
8/27/06.
' Qty. Unit Charge
Per
Extens.ion`. •:
-
:BASE _FEE :_ •
15.00
Permit .. . . ..` . . •
PLUMBING
Additional desc .
Permit Fee
15.00.. Plan Check Fee ..
.00
-Issue'Date
Valuation
0 ,
Expiration Date ..
8/27/06
Qty. Unit Charge
Per,.
Extension _
BASE FEE
6.00
00 -6.0000
EA,.: PLB FIXTURE
00
` :00• 15.0000'
EA, PLB BUILDING -'SEWER
.00•
..,"00 6.0000
-EA PLB ROOF DRAIN
00
.00 7.5000
EA PLB WATER HEATER/VENT
`.00
.00 3.0000
EA PLB WATER INST/ALT/REP
.00 .
_ 1.00. 9.0000
EA PLB-LAWN SPRINKLER SYSTEM
9.00
.00 .71500
EA PLB GAS PIPE >=5
.00
.00 15.0000
EA PLB GAS'METER
.00
Special Notes and Comments
5244SF. SFD PERMIT DOES NOT INCLUDE
BLOCK WALLS, POOL/SPA'OR
DRIVEWAY
APPROACH.
Other Fees . . .
. . . . ART IN PUBLIC PLACES -RES
623.14
DIF COMMUNITY CENTERS -RES
74.00
DIF CIVIC CENTER - RES
480.00
ENERGY REVIEW FEE
121.19
LQPERMIT
" ,T •
_
_ ,
Application Number
. . . .
05-00005176
----------------------------------------------------------------------------
Other Fees . . .
. . . .
DIF FIRE PROTECTION -RES
140.00
GRADING PLAN CHECK,FEE
00
DIF LIBRARIES•- RES
355.00
DIF PARK MAINT FAC = RES
22.00
DIF PARKS/REC.- RES —
892.00
STRONG MOTION (SMI) - RES
44.92
DIF.STREET MAINT FAC -RES
67.00
DIF TRANSPORTATION,- RES
1666.00
Fee summary
Charged
Paid Credited
Due
Permit Fee Total
2510.51
.00 00
2510.51
Plan Check Total
1345.43
750.00 .AO
595.43
Other Fee Total_
4485.25
QO .00,
4485.25
Grand Total
8341.19
750.0.0; 00
7591.19
E
LQPERnIIT
-
Building Q
Address 61
?wner,
Mailing
Address
State Lic. City
& Classif. ¢� rD Lic. #
Arch., Engr., O
Designer
Address
Lic. #/' _.
014 " ossa 7K
P.O. BOX 1504 APPLICATION ONLY
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm that I am licensed under provisions of Chapter 9 (commencing with Section
7000) of DiYyI/'sign 3 he Business nd Profe sions de, and my license is)n full f ce and
effect. ✓J, / / - - t _ ,�f i1�_ /. / _ Ow
OWNEWBUILDER DECLARATION -
I hereby affirm that I am exempt from the Contractor's License Law for the following
reason: (Sec. 7031.5, Business and Professions Code: Any city or county which requires a
permit to construct, alter, improve, demolish, or repair any structure, prior to its issuance also
requires the applicant for such permit to We a signed statement that he is licensed pursuant to
the provisions of the Contractor's License Law, Chapter 9 (commencing with Section 7000) of
Division 3 of the Business and Professions Code, or that he is exempt therefrom, and the basis
for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects
the applicant to a civil penalty of not more than five hundred dollars ($500).
❑ I, as owner of the property, or my employees with wages as their sole compensation, will do
the work, and the structure is not intended or offered for sale. (Sec. 7044, Business and Profes-
sions Code: The Contractor's License Law does not apply to an owner of property who builds
ort mproves thereon and who does such work himself or through his own employees, provided
that such improvements are not intended or offered for sale. If, however, the building or im-
provement is sold within one year of completion, the owner -builder will have the burden of
proving that he did not build or improve for the purpose of sale).
❑ I, as owner of the property, am exclusively contracting with licensed contractors to construct
the project. (Sec. 7044, Business and Professions Code: The Contractor's License Law does
not apply to an owner of property who builds or improves thereon, and who contracts for such
projects with a contractor(s) licensed pursuant to the Contractor's License Law.)
❑ 1 am exempt under Sec. B. & P.C. for this reason
Date Owner
WORKER'S COMPENSATION DECLARATION
I hereby affirm that I have a certificate of consent to self -insure, or a certificate of Worker's
Compensation Insurance, or a certified copy thereof. (Sec. 3800, Labor Code.)
Policy No. Company
❑ Copy is filed with the city. ❑ Certified copy is hereby furnished.
CERTIFICATE OF EXEMPTION FROM
WORKERS' COMPENSATION INSURANCE
(This section need not be completed if the permit is for one hundred dollars ($100) valuation
or less).
I certify that in the performance of the work for which this Permit is issued, I shall not
employ any person in any manner so as to become subject to Workers' Compensation Laws of
California.
Date Owner
NOTICE TO APPLICANT If, after making this Certificate of Exemption you should become
subject to the Workers' Compensation Provisions of the Labor Code, you must forthwith
comply with such provisions or this permit shall be deemed revoked.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance of the work
for which this permit is issued. (Sec. 3097, Civil Code.)
Lender's Name
Lender's Address
This is a building permit when properly filled out, signed and validated, and is subject to
expiration if work thereunder is suspended for 180 days.
I certify that I have read this application and state that the above information is correct.
I agree to comply with all city and county ordinances and state laws relating to building
construction, and hereby authorize representatives of this city to enter the above-mentioned
property for inspection purposes.
Signature of applicant Date
Mailing Address
City, State, Zip
WHITE = BUILDING DEPARTMENT
BUILDING: TYPE CONST. �/" OCC. GRP.
A.P. Number 77,2- a;525
Legal Description39?,,
Project Description
Sq. Ft�
Size
No. No. Dw.
Stories Units
NevW Add ❑
Alter ❑ Repair ❑ Demolition ❑
Estimated Valuation
PERMIT
AMOUNT
Plan Chk. Dep.
Plan Chk. Bal.
Const.
Mech.
Electrical
Plumbing
S.M.I.
Grading
Driveway Enc.
Infrastructure
t A InIl
TOTAL
REMARKS
UPI I I
III I mny HBO ` L: -,I
N I I
I
ZONE:
Minimum Setback Distances:
Front Setback from Center Line
Rear Setback from Rear Prop. Line
Side Street Setback from Center Line
Side Setback from Property Line
FINAL DATE INSPECTOR
Issued by: Date Permit
Validated by:
Validation:
YELLOW = APPLICANT
PINK = FINANCE
a
Coachella Valley .Unif ed' School District This Box For District use only t
83-733 Avenue 55, Thermal, CA. 92274 DEVELOPER FEES PAID
(760) 398-5909 — Fax (760) 39871224 .
AREA:
AMOUNT r
- LEVEL ONE AMOUNT:,' - -
LEVEL TWO AMOUNT:
MITIGATION AMOUNT:
COMM/MD. AMOUNT:
DATE: -
RECEIPT: -
CHECK #:
INITIALS:
CERTIFICATE OF COMPLIANCE
'
(CaliforniaEducationCode 17620)
Project Name:Harry ariResidence@ Aldeaway, - Date: February 21, 2006
Owner's Name: Harry Beder an Phone No. (760) 238-6986
Project Address: 80637 Via Pessaro
Project Description: 1 Single Family Dwelling
Tract
-APN: • 772-500-059 #: Lot #'s:
s _.
Type of Development: Residential XR "Commercial Industrial
Total Square Feet of Building'Area: "5244 ,sq: Ft.
Certification of Applicant/Owners: The person signing certifies that the above information is correct and makes this statement under
penalty of perjury and further represents that he/she is authorized to sign on behalf of the owner/developer.
Dated: 02/21./06 Signature: n `
SCHOOL DISTRICT'S REQUIREMENTS FOR THE ABOVE PROJECT HAVE BEEN OR WILL BE SATISFIED IN
ACCORDANCE WITH ONE OF THE FOLLOWING: (CIRCLE ONE)
Education Code Gov. Code Project Agreement Existing Not Subject to Fee '
17620 65995 Approval -'Prior to 1/1/87 Requirement ,
Number of Sq.Ft. 5, 244
Amount per Sq.Ft. $ 2.88 ,
Amount Collected - $ 15,102.72-
'Building
5,102.72Building Permit Application Completed: Yes/No
By: Carey M. Carlson, Asst. Supt:, Business Services
Certificate issued by:, Leticia C. Torres Facilities Clerk Si natur
g.
NOTICE OF 90 DAY PERIOD FOR PROTEST OFF SAND STATEMr�T FEES
Section 66020 of the Government Code asserted by Assembly Bill 3081, effective January 1,1997, requires that this District provide (1) a written notice to the
project appellant, at the time of payment of school fees; mitigation payment or other exactions ("Fees"), of the 90 -day period to protest the imposition of these
Fees and (2) the amount of the fees. Therefore, in accordance with section 66020 of the Government code and other applicable law, this Notice shall serve to
advise you that the 90 -day protest period in regard to such Fees or the validity thereof, commences with the payment of the fees or performance of any other
requirements as described in section 66020 of the Government code. Additionally, the amount of the fees imposed is as herein set forth, whether payable at this
time or. in whole or in 1part prior to issuance of a Certificate of Occupancy. As in the latter, the 90 days starts on the date hereof: , This Certificate of
Compliance is valid for thirty (30) days from the date of issuance. Extension will be granted only, for good cause, as determined by the School District, and up
to.three (3) such extensions may be granted. At such time as this Certificate expires, if a building permit has not been issued for the project that is the subject
of this Certificate, the owner will be reimbursed all fees that were paid to obtain this Certificate of Compliance.
rt u)nl il6.nc:: ?mn I bicSt <'
I I'.} 1/16/03T
° DOC a 2005-0152835•
~ 03/10/2605 08:00A Eee:36.00,
RECORDING -REQUESTED BY: _ Page 1 of 4 Doc T Tax Paid
q w enturyTitle,Company;- Riverside Title Recorded in Official Records
ORDER NO.' 2352600 °" <, , County of Riverside
Larry W. Ward
ESCROW NO.:• 33050096-SVO.. Assessor, County Clerk 8 Recorder
AND WHEN RECORDED MAIL TO;
Hairy Bederian 4 IIIIIIIIIIIIIIIII'IIIIIIIIIIIIIIIIIIIIIIII IIII IIIIIII
Nancy Bederian
'49910 N. Yucca Ave. -
Lancaster, CA 93534' .
A.P.. ,
772-500-059-1
M.,
$
U
PAGE
I SIZE ' DA - I ICOR' I NOCOR
7 I `• i I - -. .I
A'
R
}L
--i
COPY I loNuN„ IC ,..
{ -
GRANT'DEED r
THE UNDERSIGNED GRANTOR(S) DECLARE(S) that documentary transfer tax is $1',045.00 -(County) $.00 (City)
( X ) computed on full value of property conveyed, or
( ) computed on full value less liens or encumbrances remaining at time of sale
( X ) City of La Quinta '
FOR A VALUABLE CONSIDERATION,V.receipt of which is hereby acknowledged, Randall James Blackwood and
Eve Lynn Blackwood, husband and wife as joint tenants ,
hereby GRANT(S) to Harry Bederian and Nancy Bederian ;, Husband and Wife as Joint Tenants
the following described real property in the City of La Quinta; County of Riverside, State of California:
Please see attached Exhibit`"A
Dated: January 26, 2005 TM - • ,,
STATE OF CALIFORNIA
COU OF / Ste' cS,�)y r/ C �c� '� •rr
On l uti 2D before me 4 ,,�Randall James Blac ood
Pefsonally appRared G % �.
` Eve Lynn BI wood
'Personally to me (or proved to me on the. basis of satisfactory ' ,• :
evidence) to be the person(s).whose name(s) is/are'subscribed to the.'
within instrument and'acknowledged tome that'he/she/they executed the
sarrie`in his/her/their authorized capacity(ies), and .that -by his/her/their = ;
signature(s) on the instrument the.person(s) or the entity upon behalf of.,
which the person(s)'a�ed; executed the instrument. '
l/ITNESS my hand and official seal
Signature d I CGMih
NOIARI'i'116,IC Lr, i=r^:.:i:• '%
(This area ier eif ua ;ctar•, sea';
'Grant Deed- Individual (290) 10-04 MAIL TAX STATEMENTS AS DIRECTED ABOVE
11/lb/'LMM IW OJ bbl-J4UU4b0 )LANCASTER FLOORING PAGE01/03
Nov ^.5 05 0226a
r - .
Ow-NERS ASSOCIATION
November 15, 2005
' Mr. Harry Bederian..
44910 Yucca Avenue
Lancaster, CA 93534
Fax#661-940-8450.
RE: • Dederisn-YhillipslFiaal Working DrawbW #Z • .
Lot 307 at $0637 Via Pessaeu
Dear Mr. Bederiara►: _ ..
The. Hideaway Design Review Committee meet to discuss the. Revised Final v1;oc it
Dmwimp subwitted for Lot 307. The DRC is providing You with a 'Cooditia"91;
approval of the Final Working Draw6P .so your Plans may be submitted to the City n:'
La Quiint& for plan check. _
MM DRC will also accommodate tits scbe4Ww8 of a Pre-CORS=dw meeting at tile: 10'
however, construction way NOT cammemce unto the remaining issues are m0lve11 �r.i
Final pleas we given complete DRC aMfOval.
Note: Pleam have therlrekiket of Record MMPthe Plaits at the,Jlnal review level. _
2.7 Grading and Drainage
a.. Slopes at the pool area are indicated at 21 which is not allowable per t"r:
Guidelines.
b. Proposed contours must be labeled on the grading Plan for a thorou & rOvilv".
c. ne lower.basin elevation must be indicated on tate plans for mvicw-
d: The pool soon details (grades) do not match im- radin8 plm
e. Any grading in the NaMW Area and/or golf course must be approved, by snc:
Golf Club prior to the iss;uaace,of'a DRC approval.
f. The patio and driveway cannot extend all the wW to the property lines rs
minimum of 3' - 5' of space must be dedicated for.the purposes of
trees, vises, etcto soften and screen the orc hitectmr- "
2.11 - Walls, Yenew and Gate9i
IL Wall tett=uses must be designed where wall ends are visible to the str-2t.ts,
golf course or adjacent.lots ,
L131 Pools and Water Features
a. A variance for'the pool tocation at 6' ftem the rear pr OM line is aplrn`cr.
as there does not appear to be a negative impact to the golf ealuse. -
b. All exterior materials , exposed to . the golf course must be . submittod .,
review. • Man tt$ORT MANAGCMENT �
POST Orrtrr BOK 4?72 I PALM DG5151M CALIEORain 9-M,61-4772.
r, In -350 ALB9SAN78O, SUITII i I PALM DzssaT. CALIFORNIA 93160
PY.ONH 760.346.116i f FAX 760.346.9918 I E -MNL: ASSOCIATIO144PNIDRAWAYGO1FCLl18.CL14{
CITY OF LA QUINTA '.
PLAN CHECK CORRECTIONLIST
CITY.OF LA QUINTA - PUBLIC WORKS/ENGINEERING DEPARTMENT
GREEN SHEET (PUBLIC WORKS CLEARANCE) FOR BUILDING PERMITS
Form updated & effective 8/25/2005
Please .DO NOT submit the Green Sheet (Public Works Clearance) Packetto. the Public
Works/Engineering .Department until ALL requirements listed below: are. complete. Incomplete
applications or applications which cannot be processed will be returned to Applicant: . Green Sheet
approvals will be forwarded to the Building Department directly by Public Works.
Date: Developer: A.ZSCLG7D
Tract No.: Tract Name: fj�J fL j/ Lot No. (s) O
Address(s): E755 6
The following are the requirements for Public Works Clearance to authorize: issuance of a building
permit from the Building/Safety Department.
CUSTOM HOMES: PROVIDE ITEMS #2,'#3, #4 AND #5` BELOW.
TRACT HOMES: PROVIDE ITEMS #1, #2, #3,44 (AS APPLICABLE) AND #6 BELOW:
COMMERCIAL BUILDINGS/OTHER: PROVIDE ITEMS 01, #2, #3 AND #5 BELOW.
1. Attach Pad Elevation Certificates in compliance with .the approved design elevation for
building pad (maximum allowable deviation of +/- 0.1 foot). Pad Elevation Certificates must
be current (within 6 months of current date). If a precise grading plan creates the .pad for
approval, please withhold green sheet submittal until a Pad Elevation Certificate :. canbe
rovided.
Attach geotechnical certification of grading plan compliance. + %If✓6 I)JAa.
Attach recorded final map showing proposed building locations are legal lots:
4 Attach a completed <1 acre per lot or infill project Fugitive Dust Control project information
form', PM10.plan & agreement or provide alternative & valid City approved PM10 plan set
reference.number.or hard copy plan. PM10 plans for commerciall and residential developments
(be; c d it lot arc submitted separately with aradine nlw-s a-nd are su1,JC..t uddition"al
requirements.
5. Attach an approved precise grading plan for the building location(s). AO flood zone
developments will require an approved flood plain development plan.
6. Attach an approved rough grading plan for the building location(s).
I have reviewed and confirmed the requirements listed above as presented and find the improvements..
to be sufficiently. complete for construction of the proposed building(s)/structure(s).on the subject
lot(s). Pursuant t%4Rg,1fimdin s the Bove roject may be released for building permit issuance.
Recommended by: Dated:
Declined for approval for reason(s) as follow(s), please correct and resubmit:
TAPWDEPT,STAFF\Goble\Green Sheet PW Release\050824GREEN SHEET COVERdoc
L
City -of La Quinta - PM .10 Project Information (<1 acre per Lot or Infill Project)* Page 1 of 3
Form updated & effective 8/25/2005. '
:Project Information Project Contractor: '
Project Phase
Project Phase
(Check• One):
Project -Name:
Project Tract
Number: `
,Construction
..
Q Demolition.
Lot Number(s):
Anticipated Start Date:'..
Project Street
Address:
C p
. � �: Q/,V C__ F}-.
Anticipated Completion:
Tot 1 acres in•ac ive
construction (<1" acre.pe'r
dip
Project Contact
Information
Please Note: Dust control is required 24 hours a day, 7 days a week,
regardless of construction status. Person listed below is responsible for
dust control during business and.non- business hours. '
Name: Ji
Title:
Com any Name:;
Mailing Address: t
oyla;m ..
State:
Zi :Code:7.
Primary.
Telephone .
Number:
Fax:
7(0 3 -
24 Hour
Access/Emergency
Phone:
7&0-2-38_ t
Cell Phone:
PM 10 Certificate
Number:
* Expanded PM10 plans for commercial'and residential developments > 1 acre are required -by the
City of La Quinta.
1:\PWDEPT1STAFRG0b1e\Green Sheet PW Re1ease\050824M1N1 PM 10 PACKET GREEN SHEET.doc .
PM 10 (Q acre per Lot or Infill Project) Fugitive Dust Control Plan Pa�e.2 of 3
Plan.updated & effective 8/25/2005
This plan shall take into account applicable SCAQMD Rule 403 regulations. ' . Training may obtained by
contacting SCAQMD (Sharon Zamora (909) 396=2183). This plan shall consist.of the following action items:
• . WATERING: Continuous watering is required to prevent dust. and must occur a minimum of,4".,
times daily.
Water shall be applied to dry soils to stop:.
• ' .Visible dust emissions over 20% opacity
• Visible dust emissions that travel over 100 feet._
• Water source. 3/< inch water meter at front (south) side of pad.
• EDUCATION: Responsible Dust Control Individual .arid key personnel shall attend SCAQMD
PM 10 class and obtain PM 10 certificate number prior to construction activity.,
• WEATHER MONITORING: Wind predictions shall be. monitored.
• SIGNAGE: Use Coachella Valley Fugitive Dust Control Plan Handbook ConstructionSite Signage
Guidelines.:
•' TRAFFIC:.. Construction traffic.: shall. not, be allowed. on the pad, unless absolutely:necessary.• if-
-vehicles operate on pad, pad shall. be -kept, firm and moist through hose watering or sprinklers
Fugitive Dust shall be prevented by fencing off site to prevent unauthorized, traffic on pad. (15 mph
maximum traffic speed): F
• PARKING: Parking is not allowed on the pad: All vehicles must =park on street (at designated areas..
only).: .
• TRACK OUT: Provide 24 hour street cleaning and track out system as. approved. by .City Public
Works Inspector. (No dirt on public or private. roads). Track out shall. be. cleaned'up within one hour
of _incident. .:
• DIRT PILES: Dirt piles shall be limited to 50 cubic yards and built per California Building -Code'
grading requirements. Piles shall be kept,moist. or covered with tarp' material: Larger dirt.piles will
require stockpile or grading permit.
• FENCING: ,Provide. PM 10 fencing at perimeter of public roads and where applicable:' Wood'slat
fencing can be installed at rear. of property and' return 20 feet on either side. if HOA restrictions apply. .
Block walls can replace PM 10 fencing during the construction phase.
• EOUIPMENT-' Extra hoses and sprinklers shall be maintained on site.
• . EXCAVATION MEASURES: All areas to be excavated or graded shall be .pre -watered. Water shall;
be applied during excavation. or grading operations also.
• DUMP TRUCKS: Open top dump trucks to be wet down, moist andtarped,.phor to weaving site.
• INACTIVE SITE: Within 10 days. of ceasing of activities, "re -vegetate or permanently stabilize as
required.
4 City of La Quints - Site Specific Construction Phase PM 10 Agreement Pate 3 of 3
Agreement updated & effective 8/25/2005
, The signature of the property owner (or authorized representative):
•Shall .act as his/her acknowledgement of dust control requirements and their enforceability, '
pursuant to AQMD Rules 403 and 403.1; .
• Shall constitute: and agreement to comply with , all project. conditions as identified in the
approved dust:control:plan;
The•propertYowner (or authorized representative):
• Acknowledges that dust- control is required 24 .hours. a. day, 7 days a week, throughout.the
Period of project:performance, regardless of project size or',status;
• Shall ensure that. each and every contractor/subcontractor and all. other persons associated
with the project shall be in continuous compliance with all requirements of the approved dust
control plan; ;
Shall take all. necessary precautions to minimize, dust, even if additional measures beyond
those listed in the dust .control -plan are necessary;
• Shal"1'authonze representative of the City/County to enter upon the above mentioned,property
'for inspection and/or abatement purposes; and .
• Shall .hold harmless the City/County` and its representatives from liability for any actions
related to this dust control plan.or any:City/County initiated abatement activities.
Signature of Property wrier or Authorized Representative .
L
Printed Name t
Title 6ate,
Company
er.tinca.te of ®cc'ypancy�0
41
DOC
OF Building'.A*Safetv,De 6itinent=-
This Certificate is issued pur's'uant to the requirements of Section 109 yof the California Building: ;
-Code, certifying,.. that, ,at the tune of issuance, `.this;:structure,.was in",compliance with the'.
rovisions of the 'Buildirt Code and the various ordinances of the Cit re ulatin buiidin
p g r.. , Y g g...,.9
construction anal/or use..
BUILDING ADDRESS: 80-637VIAPESSAR0
Use classification: SINGLE FAMILY-=DWELLING v,�., "Building' Permit No: 05-5176,
Occupancy.Group: R3 �1. ,' Typeof Construction:,VN- ,Land -.Zone: RL_.
—
—
f
Owner Building: HARRY BEDERIAN` - Address: 80-637 VIA PESSARO
•-. City, ST, ZIP: LA QUINTA, Ck92253i.
_ i ,
F ,By: EDDIE MUIR,.
Date: MARCH 26 2007
Building Official ...',
` • POST IN ASCONSPICUOUS .PLACE
La Quinta, CA 922
(760) 564-4707
t 5018 .. r
Date: FEB 01 2006'
1/9/2006 B:
The EnergyPro computer program, has been used to perform the calculations summarized in this compliance report. This.program has approval and is
authorized by -the California Energy Commission for use with.both the Residential and. Nonresidential 2005 Building Energy Efficiency Standards.'
This program developed by EnergySoft, LLC = www.energysoft.com.
EnergyPro 4.0 by Energysoft., Job N6mber:,5018 User Number: 5970
f:
Certificate Of Compliance:
Residential
(Part 1 of 3) CF -1 R
Bederian Residence
Project Title
11A19006
Date
80637 Via Pessaro l a
Q,linta
Project Address
Building Permit #
South Wp-,t Concepts
(760) 564-4707
Documentation Author
Telephone
Plan Check/Date
_EneraVPro
Compli nce Method
15
Climate Zone
Field Check/Date
TDV Ener Use
Standard
Proposed
Compliance
(kBtu/sf-yr�
Design
Design
Margin
Space Heating
1.50
1.12
0.38.
Space Cooling
53.56
51.67
1.88
Fans
8.07
7.77
0.30
Domestic Hot Water
4.89
5.86
-0.97
Pumps
0.00
0.00
0.00
Totals
68.02
66.42
1.60
Percent better than Standard:
2.3%
Building Type: [ Single Family ❑ Addition Total Conditioned Floor Area: 5,244 ft2
'E] Multi Family ❑ Existing + Add/Alt Existing Floor Area: n/a ft2
Building Front Orientation: (N) 0 deg Raised Floor Area: 606 ft2
Fuel Type: Natural Gas Slab on Grade Area: 4,638 ft2
Fenestration: Average Ceiling Height: 10.0 ft
Area: 1,321 ft 2 Avg. U: 0.39 Number of Dwelling Units: 1.00
Ratio: 25.2% Avg. SHGC: 0.37 Number of Stories: 1
BUILDING ZONE INFORMATION # of Thermostat Vent
Zone Name Floor Area Volume Units Zone Type Type Hgt. Area
HVAC System 1x516 15 16 9A_ CnnditinnPd SPthnnk n/a
HVAC System 611 611 0.12 Conditioned Sethack _2 n/a
HVAC System 1 140 114f) 099 Conditioned Setback n/a
MVAC System 1,371 13 710 0.26 Conditioned Setback _2 n/a
OPAQUE SURFACES Insulation Act. Gains Condition
Type Frame Area U -Fac. Cay. Cont. Azm. Tilt Y / N Status JA IV Reference Location / Comments
Roof Wood 1516 0-025 R-38 X0_0 0 18 New 01-A18 Zone1
Wall Wood 121 0.069 R_21 R-0.0 0 90 New 09-A6 Zone1
Wall Wood 49 0 069 R_21 R-0 0 270 9 New 09-A6 7one1
Wall Wood 49 0.069 R_21 R-0.0 90 New MAR Zone1
Wall Wood 53 0.069 R_21 RR -0.0 180_90 New 09-A6 Zone1
Roof Wood 611 0 025 R_3g R-0.0 - 1g • New 01-A18 Zone 2
Wall Wnnd 314 0069 R-21 R-0.0 270 90 New 09-A6 Zone 2
Wall Wood 178 0 069 R_21 R-0.0 _ ---N PNew 09-A6 Zone 2
Wall Wood 242 0 069 R_21 R-0.0 9f) go r� New 09-A6 Zone 2
Roof Wand 1,140 0.025 R_38 R-0.0 --0- 18 icy ®New 01-AlA Zone 3
Wall Wood 183 0 069 ® _$_21 R 0.0 270 _9Q New n9 -A6 Zone 3
Wall Wnnd 616 0.069 R-21 R-0.0 90 gQ New nq-A6 Zone 3
Wall Wood 92 0.069 R-21 R-0.0 180 9Q New 09-A6 Zone 3
Roof Wood 289 0.025 R_38 R0.0 x_18 New 01-A18 Zone 4
Wall Wood 448 0.069 R_21 R-0.0 270 9Q New 09-A6 - Zone 4
Wall Wood 125 0.069 R_21 R-0.0 180 9 New 09-A6 Zone 4
Rnnf Wnnd 606 n 025_ X38 -0 0 n 1B PNpw W -A18 Zone 5
Wall Wnnd 350 0.069 R_21 R-0.0 270 �Q New nq-A6 Zone 5
Wall Wood 177 0.069 R_21 R 0.0 180 _ 90. New 09-A6 Zone 5
Floor Wood 606 0.048 R_19 R-0 1A0 New 21-A4 Zone 5
❑ ❑
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number: 5018 Page: 3 of 23
Certificate Of Compliance :
Residential
(Part 1 of 3) CF -1 R
Bederian Residence
Project Title
11919006
Date
80637 Via Pessarn I a
Q, lints
Project Address
Building Permit #
South West Concepts
(760) 564-4707
Documentation Author
Telephone
Plan Check/Date
FneroyPro
Compli nce Method
15
Climate Zone
Field Check/Date
TDV Ener Use
Standard
. Proposed
Compliance
(kBtu/sf-yr
Design
Design
Margin
Space Heating
1.50
1.12
0.38
Space Cooling
53.56
51.67
1.88
Fans
8.07
7.77
0.30
.Domestic Hot Water
4.89
5.86
-0.97
Pumps
0.00
0.00
0.00 -
Totals
68.02
" 66.42
1:60
Percent better than Standard:.
2.3%
Building Type: (50 Single Family ❑ Addition
❑ Multi Family ❑ Existing + Add/Alt
Building Front Orientation: (N) 0 deg
Fuel Type: Natural Gas
Fenestration:
Area: 1,321 ft 2 Avg. U:
Ratio: 25.2% Avg. SHGC:
BUILDING ZONE INFORMATION
Zone Name Floor Area
HVAC System ROB
0.39
0.37
Total Conditioned. Floor Area:
Existing ,Floor Area:
Raised Floor Area:
Slab on Grade Area:
Average Ceiling Height:
Number of Dwelling Units:.
Number of Stories:
5,244 ft
n/a ft
606 ft
4,638 ft
10.0 ft
1.00
. 1
# of Thermostat Vent
Volume Units Zone Type Type Hgt' Area
R ns 017 CnnditinnPd SPthark n1
OPAQUE SURFACES' Insulation Act. Gains Condition
Type Frame Area U -Fac. Cay. Cont. Azm. Tilt Y / N Status JA IV Reference Location / Comments
❑ ❑
❑ ❑
❑ ❑
❑ ❑
❑ ❑
❑❑'
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number: 5018 Page: 4 of 23
Certificate Of Compliance : Residential (Part 2 of 3) CF -1 R
Bederian Residence 1/9/2006
Project Title Date
FENESTRATION SURFACES
True Cond. Location/
# Tvoe Area U -Factors SHGC2 Azm. Tilt Stat. Glazino TVDe Comments
4
Window
Front
(N)
54 6 039 NFRC 0_37 NFRC -_ qQ_ New Fleetwood Window & Doors
7nne1
2
Window
Front
(N)
60.0 0.390 NFRC 0.37 NFRC 0 90 New Fleetwood Window & Doors
Zone1
3
Window
Front
(N)
104.0 0.390 NFRC 0.37 NFRC 0 90 New Fleetwood Window & Doors
Zone1
4
Window
Right
(W)
56.0 0.390 NFRC 0_37 NFRC 270 90 New Fleetwood Window & Doors
Zone1
5
Window
Left
(E)
56.0 0.390 NFRC 0.37 NFRC 90 90 New Fleetwood Window & Doors
Zone1
6
Window
Rear
(S)
220.0 0.390 NFRC 0_37 NFRC 180 90 New Fleetwood Window & Doors
Zone1
L
Window
Right
(gyp()
24.0 0.390 NFRC 0_37 NERC 270 90 New Fleetwood Window & Doors
Zone 2
8
Window
Front
(N)
27.5 0.390 NFRC 0.37 NFRC 0 90 New Fleetwood Window & Doors
Zone 2
.9_
Window
Left
(E)
48.0 0.390 NFRC 0_37 NFRC 90_ 90 New Fleetwood Window & Doors
Zone 2
1Q
Window.
Left
(E)
48.0 0.390 NFRC 0_37 NFRC 90 90 New Fleetwood Window & Doors
Zone 2
11
Window
Right
(W)
25.0 0.390 NFRC 0_37 NFRC 270 90 New Fleetwood Window & Doors
Zone 3
12
Window
Left
(E)
7.5 0.390 NFRC 0.37 NFRC 90 90 New Fleetwood Window & Doors
Zone 3
Aa
Window
Left
(Fa
48.0 0-39ONFRC SL3Z NFRC 90 _91 New Fleetwood Window & Doors
Zone 3
14
Window
Left
(E)
12.5 0.390 NFRC 0.37 NFRC 90 90 New Fleetwood Window & Doors
Zone 3
15
Window
Left
(E)
12.5 0.390 NFRC 0.37 NFRC 90 90 New Fleetwood Window & Doors
Zone 3
16
Window
Left
(E)
12.5 0.390 NFRC 0.37 NFRC 90 90 New Fleetwood Window & Doors
Zone 3
17
Window
Left
(E)
6.2 0.390 NFRC 0_37 NFRC 90 90 New Fleetwood Window & Doors
Zone 3
18
Window
Rear
(S)
108.0 0.390 NFRC 0.37 NFRC 180 90 New Fleetwood Window & Doors
Zone 3
1Q
Window
Right
(W)
20.0 0.390 NFRC 0_37 NFRC270 90 New Fleetwood Window & Doors
Zone 4
1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 11613.
INTERIOR AND EXTERIOR SHADING
Area Thick. Heat
Inside
Condition
Location/
Type
(sf)
(in.)
Cap. Cond. R -Val.
window
Status
Overhang
Left Fin Right Fin
#
Exterior
Shade Type
SHGC
Hgt.
Wd.
Len.
Hgt. LExt.
REA Dist. Len. Hgt. Dist. Len. Hgt.
1
Bug
Screen
0.76
10.0
6.7
8.0
0.1 8.0
8.0
2
Bug
Screen
0.76
10.0
6.0
2.0
0.1 2.0
2.0
3
Bug
Screen
0.76
10.0
13.5
8.0
0.1 8.0
8.0
4
Bug
Screen
0.76
10.0
5.5
8.0
0. A.0
8.0
5
Bug
Screen
0.76
10.0
5.5
8.0
0.1 8.0
8.0
6
Bug
Screen
0.76
10.0
22.0
2.
0,_ 2.
2.0
7
Bug
Screen
0.76
8.0
3.0
2.0
0.1 2.0
2.0
8
Bug
Screen
0.76
5.5
5.0
2.0
0.1 2.0
2.0
9
Bug
Screen
0.76
8.0
6.0
2.0
0.1 2.0
2.0
10
Bug
Screen
0.76
8.0
6.0
2.0
0.1 2.0
2.0
11
Bug
Screen
0.76
5.0
5.0
2.0
0.1 2.0
2.0
12
Bug
Screen
0.76
2.5
3.0
2.0
0.1 2.0
2.0
13
Bug
Screen
0.76
8.0
6.0
2.0
0.1 2.0
2.0
14
Bug
Screen
0.76
5.0
2.5
2.0
0.1 2.0
2.0
15
Bug
Screen
0.76
5.0
2.5
2.0
0.1 2.0
2.0
16
Bug
Screen
0.76
5.0
2.5
2.0
0.1 2.0
2.0
17
Bug
Screen
0.76
2.5
2.5
2.0
0.1 2.0
2.0
18
Bug
Screen
0.76
9.0
12.0
8.0
0.1 8.0
8.0
19
Bug
Screen
0.76
5.0
4.0
2.0
0.1 2.0
2.0
THERMAL MASS FOR HIGH MASS DESIGN
Run Initiation Time: 01/09/06 13:40:25 Run Code: 1136842825
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number: 5018 Page:5 of 23
Area Thick. Heat
Inside
Condition
Location/
Type
(sf)
(in.)
Cap. Cond. R -Val.
JA IV Reference
Status
Comments
Frame Wall, Stucco
121
7.00
21
0.47 2
09-A6
New
Zone1 / Exterior Mass
Frame Wall, Stucco
49
7.00
21
0.47 2
09-A6
New
Zone1 / Exterior Mass
Frame Wall, Stucco
49
7.00
21
0.47 2
09-A6
New
Zone1 / Exterior Mass
Frame Wall, Stucco
53
7.00
21
0_47 2
09-A6
New
Zone1 / Exterior Mass
Frame Wall, Stucco
7.00
21
0_47 2
09-A6
New
Zone 2 /Exterior Mass
PERIMETER LOSSES
Insulation
Condition
Location/
Type
Length
R -Val.
Location
JA IV Reference
Status
Comments
Run Initiation Time: 01/09/06 13:40:25 Run Code: 1136842825
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number: 5018 Page:5 of 23
Certificate Of Compliance : Residential (Part 2 Of 3) CF -1 R
Bederian Residence 1/9/2006
Project Title Date
FENESTRATION SURFACES
# Type Area U -Factors SHGCZ
True
Azm. Tilt
Cond.
Stat. Glazing Type
Location/
Comments
20.
Window
Right
(ZI)
225_ n Sao NFRC -O-U NERC 270 9p New Fleetwood Window & Doors
Zone 4
21
Window
Right
(W)
24.0 0.390 NFRC 0_37 NFRC
270 90 New
Fleetwood Window & Doors
Zone 4
22
Window
Rear
(S)
180.0 0.390 NFRC 0.37 NFRC
180 90 New
Fleetwood Window & Doors
Zone 4
23
Window
Right
(W)
18.0 0.390 NFRC 0_37 NFRC
270 90 New
Fleetwood Window & Doors
Zone 5
24
Window
Right
(W)
22.5 0.390 NFRC 0_37 NFRC .270
90 New
Fleetwood Window & Doors
Zone 5
25
Window
Right
(W)
15.8 0.390 NFRC 0_37 NFRC
270 90 New
Fleetwood Window & Doors
Zone 5
2f)
Window
Rear
(SL
24.0 0.390 NFRC 0.37 NFRC 180 90 New Fleetwood Window & Doors
Zone 5
27
Window
Rear
(S)
64.0 0.390 NFRC 0.37 NFRC
180 90 New
Fleetwood Window & Doors
Zone 5
1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 11613.
INTERIOR AND EXTERIOR SHADING
Window'
Overhang
Left Fin Right Fin
# Exterior Shade Type
SHGC
Hgt.
Wd.
Len. Hgt. LExt.
RExt. Dist. Len.. Hgt. Dist. Len. Hgt.
20 Bug Screen
0.76
4.5
6.0
2.0 0.1 2.0
2.0
Ti Bug Screen
0.76
8.0
3.0
2.0 0.1 2.0
2.0
22 Bug Screen
0.76
9.0
20.0
8.0 0.1 8.0.
8.0
23 Bug Screen
0.76
4.5
4.0
2.0 0- 2.0
2.0
24 Bug Screen
0.76
4.5
5.0
2.0 0.1 - 2.0
2.0
25 Bug Screen
0.76
4.5
3.5
2.0 0. 2.
2.0
26 Bug Screen
0.76
8.0
3.0
2.0 0.1 2.0
2.0
27 Bug Screen
0.76
8.0
8.0
2.0 0.1 2.0
2.0
THERMAL MASS FOR HIGH MASS DESIGN
Run Initiation Time: 01/09/06 13:40:25 Run Code: 1136842825
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number: 5018 Page:6 of 23
Area Thick. Heat
Inside
Condition
Location/
Type
(sf)
(in.)
Cap.
Cond. R -Val.
JA IV Reference
Status
Comments
Frame Wall, Stucco
178
7.00
21
• 0_47 2
09-A6
New
Zone 2 / Exterior Mass
Frame Wall, Stucco
242
7.00
21
0.47 2
09-A6
New
Zone 2 / Exterior Mass
Frame Wall. -Stucco
183
7.00
21
0.47 2
09-A6
New
Zone 3 / Exterior Mass
Frame Wall, Stucco
616
7.00
21
0_47 2
09-A6
New
Zone 3 / Exterior Mass
Frame Wall, Stucco
7.00
21
0_47 2
09-A6
New
Zone 3 / Exterior Mass
PERIMETER LOSSES
Insulation
Condition
Location/
Type
Length
R -Val.
Location
JA IV Reference
Status
Comments
Run Initiation Time: 01/09/06 13:40:25 Run Code: 1136842825
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number: 5018 Page:6 of 23
Certificate Of Compliance : Residential (Part -2 of 3) CF -1R
Bederian Residence 1/9/2006
Project Title bate
FENESTRATION SURFACES
True Cond. � Location/
# Type Area U-Factorl SHGCz Azm. Tilt Stat. Glazing Type Comments
1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 11613.
INTERIOR AND EXTERIOR SHADING Window Overhang Left Fin Right Fin
# Exterior Shade Type SHGC Hgt. Wd. Len.. Hgt. LExt. RExt. Dist. Len. Hgt. Dist. Len. Hgt.
THERMAL MASS FOR HIGH MASS DESIGN
Run. Initiation Time: 01/09/06 13:40:25 Run Code: 1136842825
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number:5018 Page:7 of 23
r
Area Thick. Heat
Inside
.
Condition
Location/
Type
(sf)
(in.)
Cap. Cond. R -Val.
JA IV Reference.
Status
Comments
Frame Wall, Stucco
448
7.00
21
0.47 2
09-A6
New
Zone 4 / Exterior Mass
Frame Wall, Stucco
125
7.00
21
0.47 .2
09-A6
New
Zone 4 / Exterior Mass
Frame Wall, Stucco
350
7.00
21
0.47 2
09-A6
New
Zone 5 / Exterior Mass
Frame Wall, Stucco
177
7.00
21
0.47 2
09-A6
New
Zone 5 / Exterior Mass -
PERIMETER LOSSES
Insulation
Condition
Location/
Type
Length
R -Val.
Location
JA IV Reference
Status
Comments
Run. Initiation Time: 01/09/06 13:40:25 Run Code: 1136842825
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number:5018 Page:7 of 23
r
Certificate Of Compliance Residential _' (Part 3 of 3) _ CF -1 R
Bederian Residence
1/9/2006
Project Title
Date
HVAC SYSTEMS
Heating
Minimum
Cooling
Minimum Condition
Thermostat
Location
Type
Eff
Type
Eff . Status
Type
HVAC System
Central Furnace
80% AFUE
Split Air Conditioner
13.0 SEER New
Setback
HVAC System
Central Furnace
80% AFUE
No Cooling
13.0 SEER New
Setback
HVAC System
Central Furnace
80% AFUE
Split Air Conditioner
13.0 SEER New
Setback
HVAC DISTRIBUTION
Ducts
Duct Condition
Ducts
Location
Heating
Cooling
'Location
R -Value Status
Tested?
HVAC System
Ducted
Ducted
Attic
4.2 New
Yes
HVAC System
Ducted
Ducted
Attic -
4.2 New
Yes
HVAC System
Ducted
Ducted
Attic
4.2 New
Yes
Hydronic Piping
Pipe Pipe
Insul.
System Name
Length Diameter
Thick.
WATER HEATING SYSTEMS
Rated 1, Tank
Energy
Standbyl Tank Insul,
Water Heater 1# in Input Cap. Condition Factor Loss R -Value
System Name Type Distribution Syst. (Btu/hr) (gal) Status or RE 1 (%) Ext.
American Water Heater Co. PVG82-Small Gas No Pipe Insulation 2 t 50,000 40 New 0.62 n/a n/a
Multi -Family Central Water Heating Details
Hot Water Pump Hot Water Piping Length (ft) Add 1/2"
Control # HP Tvpe In Plenum Outside Buried Insulation
1 For small gas storage (rated input <= 75000 Btu/hr), electric resistance and heat pump water heaters, list energy factor.
For large gas storage water heaters (rated input > 75000 Btu/hr), list Rated Input, Recovery Efficiency and Standby Loss
For instantaneous gas water heaters, list Rated Input, and Recovery Efficiency..
REMARKS
COMPLIANCE STATEMENT
This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California` Code of
Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall design responsibility.
The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insulation installation quality,
and building envelope sealing require installer testing and certification and field verification by an approved HERS rater.
Designer or Owner, (per Business • & Professions Code) Documentation Author
Name: Name: Monica A. Rose
Title/Firm:. Blechen Construction Title/Firm: South West Concepts
Address: Address: -78120 Calle Estado, Suite 206
Telephone: 7 0 238-6986
Lic. #:
(s t F&T(date)
Enforcement Agency
Name:
Title/Firm:
Address:
Telephone:
User Number: 5970
La Quinta, CA 92253
Telephone: (760) 564-4707
(signature) (date)
(signature/stamp). _ (date)
= Certificate Of Compliance : Residential
(Part 3 of 3)
CF -1 R
Bederian Residence
1/9/2006
Project Title
Date
HVAC SYSTEMS
, •ra . .
Heating
Minimum
Cooling
Minimum Condition
Thermostat
Location Type
;Eff
Type
Eff . Status
Type
HVAC System Central Furnace
80% AFUE
Split Air Conditioner 13.0 SEER New
Setback
HVAC System Central Furnace
80% AFUE
No Cooling
13.0 SEER New
Setback
HVAC DISTRIBUTION
Duct
Duct Condition
Ducts
Location Heating
Cooling
Location
R -Value Status
Tested?
HVAC System Ducted
Ducted
Outdoors
4.2. New
Yes
HVAC System Ducted
Ducted
Outdoors .
4.2 New
Yes
Hydronic Piping Pipe Pipe
Insul.
System Name Length Diameter
Thick. '
WATER HEATING SYSTEMS
Rated
Tank Energy
Standbyl Tank Insul.
Water Heater
# in Input
Cap. Condition
Loss R -Value
System Name Type
Distribution
Syst. (Btu/hr)
.Factor
(gal) Status or RE 1
(%) Ext:
Multi -Family Central Water Heating Details
Hot Water Pump Hot Water Piping Length (ft) Add 1/2"
Control # HP Type In Plenum Outside Buried Insulation
1 For small gas storage (rated input <= 75000'Btu/hr), electric resistance and heat pump water heaters, list energy factor.
For large gas storage water heaters (rated input > 75000 Btu/hr), list Rated Input, Recovery Efficiency and Standby Loss.
For instantaneous gas water heaters, list Rated Input, and Recovery Efficiency.
RFMAPWA
COMPLIANCE STATEMENT ,
This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of
Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall'design responsibility.
The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insulation installation quality,
and building envelope sealing require installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code) Documentation Author
Name: Name: Monica A. Rose
Title/Firm: Blechen Construction Title/Firm: South West Concepts
Address: Address: 78120 Calle Estado, Suite 206
La Quinta, CA 92253
Telephone: (760) 238-6986 Telephone: (760) 564-4707
Lic. #:
(signature) (date)
Enforcement Agency
Name:
Title/Firm:
Address:
Telephone:
(signature) (date)
(signature/stamp) (date)
EnergyPro 4.0 by EnergySoft User Number 5970 Job Number.,5018 Page:9 of 23 I
0
Certificate Of Compliance :.Residential . (Addendum) CF -1 R,
Bederian Residence 1/9/2006
Project Title Date
Special Features and Modeling Assumptions
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special
written justification and documentation, and special verification to be used with the performance approach. The local enforcement
ananr_v dPtarminPs the adeauacv of the iustification. and may reiect a buildina or desian that otherwise complies based on the
adequacy of the special justification and documentation submitted. Plan Field
The Roof "R-38 Roof Attic" includes credit for a Radiant Barrier, instaIliad per Section 3.3.3 of the Residential Manual
HERS Required Verification
Items in this section require field testing and/or verification by a certified home energy rater under the supervision of a CEC-
approved HERS provider using CEC approved testing and/or verification methods and must be reported on the CF -4R Plan I Field
inctallatinn rartifiratP_
The HVAC System "HVAC System" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the
CF -4R.
The HVAC System "HVAC System" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion
Valve.
This building has credit for Insulation Quality Installation. A certified HERS rater must visually verify the installation of all Insulation.
The HVAC System "HVAC System" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the
CF -4R.
This building has credit for Insulation Quality Installation. A certified HERS rater must visually verify the installation of all. Insulation.
The HVAC System "HVAC System" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the
CF -4R.
The HVAC System "HVAC System" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion
Valve.
This building has credit for Insulation Quality Installation. A certified HERS rater must visually verify the installation of all Insulation.
The HVAC System "HVAC System" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the
CF -4R.
This building has credit for Insulation Quality Installation. A certified HERS rater must visually verify the installation of all Insulation.
The HVAC System. "HVAC System" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the
CF -4R.
This building has credit for Insulation Quality Installation. A certified HERS rater must visually verify the installation of all Insulation.
EnergyPro 4.0 by Energysoh User Number: 5970 Job Number: 5018 Page: 10 of 23
Mandatory Measures Summary:: Residential : (Page 1 of 2) MF -1 R
NOTE`. Lowrise residential buildings subject to the Standards'must contain these measures regardless of the compliance approach used. More stringent
compliance requirements from the Certificate of Compliance supercede the items marked with an asterisk (') below. When this checklist is incorporated
into the permit documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory
measures whether thev are shown elsewhere in the documents or on this checklist only.
DESCRIPTION Instructions: Check or initial applicable boxes when completed.or check N/A if not
applicable. • °,
NIA
DESIGNER
ENFORCE -
MENT
Building Envelope Measures'
e§ 150(.): Minimum R-19 in wood ceilinginsulation or equivalent U -factor in metal frame ceiling.'*
�.
ElOR-
❑X
❑
§ 150(b): 'Loose fill insulation manufacturer's labeled R -Value:+ `
❑X
❑
❑
§ '150(c): Minimum R-13 wall insulation in wood framed walls or.equivalent LI -factor -in metal frame walls (does not
❑
❑X
❑
apply to. exterior mass walls).
❑
0
❑
§ 150(d): Minimum R-13 raised floor insulation in framed floors or equivalent U -factor �- 1
❑ `
❑
❑
§ 1500): Water system pipe and tank insulation and cooling systems line insulation. > "
§ 150(e): Installation of Fireplaces, Decorative Gas Appliances and Gas Logs.-
ogs.1.
Q.
❑
1:1,
1.Masonry and factory -built fireplaces have: }. '•
'
a. closable metal or glass door covering the entire opening of the firebox.
❑
❑X
❑
b. outside air intake -with damper and control, flue damper and _control,
El.
EK
Elt.
2. No continuous burning gas pilot lights allowed. "
❑
EK
❑
§ 150(f): Air retarding wrap installed to comply witt§ 151 meets + requirements specified in the ACM Residential Manual
❑X
❑
❑
§ 150(g): Vapor barriers mandatory in Climate Zones 1.4 and 16 only. -
..E
❑
❑
§ 150(1): Slab edge insulation - water absorption rate for the insulation alone without facings no greater than 0.3%, water vapor '
❑X
❑
permeance rateno greater than 2.0 perm/inch.
§ 118: Insulation specified or installed meets insulation installation quality•standards. Indicate type and
El..
EK
El,
include CF -6R Form: t
❑X
❑
❑
§ 116-17: Fenestration Products, Exterior Doors, and Infiltration/Exfiltration Controls
1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage.
❑
CK '
❑ .
2 Fenestration roducts (except field fabricated) have label with certified U -Factor -certified Solar Heat Gain
Coefficient (SHGC), and-infiltration.certification.
❑
. ❑,
,:
3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed.
❑
❑X
❑
Space Conditioning, WaterrHeating and Plumbing System Measures
§ 110-13: HVAC equipment, water heaters, showerheads-and faucets certified by the Energy Commission.
❑.
Q
❑
§ 150(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA orACCA.
❑
0
❑
§ 150(i): Setback thermostat on all applicable heating and/or 6o6lin6 systems:'
❑ `
❑X
❑
§ 1500): Water system pipe and tank insulation and cooling systems line insulation. > "
.j 1. Storage gas water heaters rated with an Energy Factor less than 0.58,must be externally wrapped with
Q.
❑
1:1,
insulation having an installed thermal resistance of R-12 or greater.
'
2. Back-up tanks for solar systems, unfired storage tanks, or other indirect hot water tanks' have R-12 external
❑X
El:
El
insulation or R-16 internal insulation and. indicated on the exterior of the tank showing the R -value.
3. The,following piping is insulated according to Table 150-A/B or Equation,150-A Insulation Thickness: -
i
1. First 5 feet of hot and cold water pipes closest to water heater tank,.non-recirculating systems, and entire
Q
❑
❑
length of recirculating sections of hot water pipes shall be insulated to Table 150B. -
❑X
1:1.
❑
2. Cooling system piping (suction, chilled water, or brine lines), piping insulated between heating source
and indirect hof water tank shall be insulated to Table'150-13 and Equation 150-A.-
4. Steam hydronic heating systems or hot water systems > 15 psi, meet requirements of Table 123-A.
Q
❑
❑
5. Insulation must be protected from damage; including that due to sunlight, moisture, equipment,
❑X
❑
❑
maintenance, and wind.
6: Insulation for chilled water piping and refrigerant suction piping includes a vapor retardant or is enclosed
0
❑
❑
entirely in conditioned space.
7.Solar water -heating systems/collectors are certified by the Solar. Rating and Certification Corporation.
❑X
❑
❑
EnergyPro.4.0 by EnergySoft. E. .. User'Number: 5970 ' - Job Number: 5018
Page: 11 of 23
Mandatory Measures Summarv: Residential (Page 2 of 2) MF -1 R
NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent
compliance requirements from the Certificate of Compliance supercede the items marked with an asterisk (') below. When this checklist is incorporated
into the permit documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory
measures whether they are shown elsewhere in the documents or on this checklist only.
DESCRIPTION Instructions: Check or initial applicable boxes when completed or check N/A if not ENFORCE -
applicable. N/A DESIGNER MENT
Space Conditioning, Water Heating and Plumbing System Measures: (continued)
§ 150(m): Ducts and Fans
1. All ducts and plenums installed, sealed and insulated to meet the requirements of the CMC Sections 601, 602, 603, 604, ❑ Q ❑
605, and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minumum installed level of
R-4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system
that meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol'sealant that meets the requirements
of UL 723. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh
or tape shall be used.
2. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than
❑X
❑
❑
sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air: Building cavities and
support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause
reductions in the cross-sectional area of the ducts.
❑
❑
3. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive
❑
®
❑
duct tapes unless such tape is used in combination with mastic and draw bands.
❑X
❑
❑
dwelling units shall be high efficacy luminaires OR are controlled by occupant sensor(s) certified to comply with Section
❑
®
❑
4. Exhaust fan systems have back draft or automatic dampers.
5. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operating
®
❑
❑
dampers.
6. Protection of Insulation. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment
®
❑
❑
maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water
retardant and provides shielding from solar radiation that can cause degradation of the material.
®
❑
❑
7. Flexible ducts cannot have porous inner cores.
§ 114: Pool and Spa Heating Systems and Equipment
1. A thermal efficiency that complies with the Appliance Efficiency Regulations, on-off switch mounted outside of the
❑
❑X
❑
heater, weatherproof operating instructions, no electric resistance heating and no pilot light.
2. System is installed with:
a. At least 36" of pipe between filter and heater for future solar heating.
®
❑
❑
.b. Cover for outdoor pools or outdoor spas.
❑X
❑
❑
3. Pool system has directional inlets and a circulation pump time switch.
❑X
❑
❑
§ 115: Gas fired fan -type central furnaces, pool heaters, spa heaters or household cooking appliances have no continuously
❑
®
❑
burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr)
§ 118 (i): Cool Roof material meets specified criteria
0
❑
❑
Lighting Measures
§ 150(k)1: HIGH EFFICACY LUMINAIRES OTHER THAN OUTDOOR HID: contain only high efficacy lamps as outlined in Table
❑.
®
❑
150-C, and do not contain a medium screw base socket (E24/E26). Ballasts for lamps 13 Watts or greater are
electric and have an output frequency no less than 20 kHz.
§ 150(k)1: HIGH EFFICACY LUMINAIRES - OUTDOOR HID: contain only high efficacy lamps as outlined in Table 150-C,
Q
❑
❑
luminaire has factory installed HID ballast.
§ 150(k)2: Permanently installed luminaires in kitchens shall be high efficacy luminaires. Up to 50% of the Wattage, as determined
❑
Q
❑
in Section 130(c), of permanently installed luminaires in kitchens may be in luminaires that are not high efficacy luminaires,
provided that these luminaires are controlled by switches separate from those controlling the high efficacy luminaires.
§ 150(k)3: Permanently installed luminaires in bathrooms, garages, laundry rooms, utility rooms shall be high efficacy luminaires.
❑
Q
❑
OR are controlled by an occupant sensors) ceritfied to comply with Section 119(d).
§ 150(k)4: Permanently installed luminaires located other than in kichens, bathrooms, garages, laundry rooms, and utility rooms
shall be high efficacy luminaires (except closets less than 70 ft) OR are controlled by a dimmer switch OR are
❑
X❑
controlled by an occupant sensor that complies with Section 1) 9(d) that does not turn on automatically or have an
always on option.
§ 150(k)5: Luminaires that are recessed into insulated ceilings are approved for zero clearance insulation cover (IC) and are
❑
X❑
❑
certified to ASTM E283 and labeled as air tight (AT) to less than 2.0 CFM at 75 Pascals.
§ 150(k)6: Luminaires providing outdoor lighting and permanently mounted to a residential building or to other buildings on the
X❑
❑
❑
same lot shall be high efficacy luminaires (not including lighting around swimming poolstwater features or other Article
680 locations) OR are controlled by occupant sensors with integral photo control certified to comply with Section 119(d).
§ 150(k)7: Lighting for parking lots for 8 or more vehicles shall have lighting that complies with Sections 130, 132, and 147.
❑
❑
Lighting for parking garages for 8 or more vehicles shall have lighting that complies with Section 130, 131, and 146.
§ 150(k)8: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
❑X
❑
❑
dwelling units shall be high efficacy luminaires OR are controlled by occupant sensor(s) certified to comply with Section
119(d).
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number: 5018
Page:12 of 23
-5R
Residential Kitchen:Lighting. Worksheet WS
Bederian Residence 1/9/2006
Project Title Date
At least 50% of the total rated wattage of permanently installed luminaires in kitchens must be In luminaires that are high efficacy luminaires
as defined in Tattle 150-C. Luminaires that are not high efficacy must be switched separately.
Kitchen Lighting Schedule. Provide the following information for all luminaires to be installed.in kitchens.
High Efficacy .
Luminaire Type High Efficacy. * Watts Quantity Watts Other Watts
(1) 22w Fluorescent Circline Rapid Start Yes 'X . No 27.0 x 10 = 270 or
100w Surface Mount Incandescent Yes No X 100.0 x " .1 or 100
60w Recessed Incandescent Yes No X 60.0 x 2 or 120
Yes No . x _ or
Yes No x or
Yes No x or .
Yes No x - or
Yes No X; or
Yes No .x a or
Yes' No x - - or
Yes No x or
Yes No X = or
Yes Nox - or
Yes No x _ ! or
Yes No ix or
Yes No x - or
Yes No x or
Yes No X = or
Yes No x = or
Yes No x r.. = or L,
j
a 'Total A: .270 B: 220
COMPLIES IF A z B YES ® NO ❑
F-EnergyPro 4.0 by EnergySoft User'Number: 5970 Job Number: 5018 Page: 13 0f 23
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Bederian Residence 1/9/2006
SYSTEM NAME FLOOR AREA
HVAC System 1,516
Number of Systems
1
Heating System
Output per System
71,000
Total Output (Btuh)
71,000
Output (Btuh/sgft)
46.8
Cooling System
Output per System
46,500
Total Output (Btuh)
46,500
Total Output (Tons)
3.9
Total Output (Btuh/sgft)
30.7
Total Output (sgft/Ton)
391.2
Air System
CFM per System
1,720
Airflow (cfm)
1,720
Airflow (cfm/sgft)
1.13
Airflow (cfm/Ton)
443.9
Outside Air (%)
0.0
Outside Air (cfm/sgft)
0.00
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
I COIL HTG. PEAK
CFM
Sensible
Latent
I I CFM
I Sensible
1,545
21,307
2,202
435
17,171
0
2,209
1,585
0
0
0
0
0
0
0
0
0
2,209
1,585
25,726 2,202 20 341
nt 550AN048-E/311JAV048090 28,143 15,679 71,000
Total Adjusted System Output28,143 15,679 71,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK - I Aug 2 pm I i Jan 12 am
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS (Airstream Tel
26.0 OF 69.1 OF ray 107.9 OF
Outside Air
0 cfm
Heating Coil
Supply Fan
1720 cfm
107.9 of
—� Supply Air Ducts
107.1 of
ROOMS
70.0 of
69.1 OFI � I
��; Return Air Ducts
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
111.0 / 77.6 of 79.2 / 68.3 of 63.8 / 62.9 of 63.8 62.9 of
4 Supply Air Ducts
Outside Air O'
0 cfm 65.0 / 63.3 of
Cooling Coil Supply Fan
1720 cfm 59.9% R.H: ROOMS
79.2/68.2 of 78.0 / 67.8 of
Return Air Ducts
EnergyPro 4.0 by EnergySoft User Number: 5970 Job Number: 5018 Page: 14 of 23
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE'
Bederian Residence 1/9/2006
SYSTEM NAME FLOOR AREA
HVAC System 611
Number of Systems
1
Heating System
Output per System
53,000
Total Output (Btuh)
53,000
Output (Btuh/sgft)
86.7
Cooling System
Output per System
0
Total Output (Btuh)
0
Total Output (Tons)
0.0
Total Output (Btuh/sgft)
0.0
Total Output (sgft/Ton)
0.0
Air System
CFM per System
900
Airflow (cfm)
900
Airflow (cfm/sgft)
1.47
Airflow (cfm/Ton)
0.0
Outside Air (%)
0.0
Outside Air (cfm/sgft)
0.00
Note: values above given at ARI conditions
EATING SYSTEM PSYCHROME'
26.0 of 69.3 of
Outside Air
0 cfm )( w
Supply Fan
900 cfm
69.3 of
69.3 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts'
TOTAL SYSTEM.LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
Latent
CFM
Sensible
502
11,605
1,365
131
7,537
0
79.3 / 63.1 of 79.3 / 63.2 of
55.0 53.7 of
1,203
696
0
0
0
0
0
0
0
Outside Air
0
0
1,2031
1 696
14,012 1,365 8 929
Bryant Heating & Cool 311JAV024070 0 0 53,000
Total Adjusted System Output 0 0 53,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 pm C_ Jan 12 am
ream Temneratures at Time of Heatina Peak)
124.6 of
Heating Coil
Supply Air Ducts
123.9 of
ROOMS
70.0 of
Return Air Ducts I
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures
at Time of Cooling -Peak
111.0 / 77.6 of
79.3 / 63.1 of 79.3 / 63.2 of
55.0 53.7 of
Supply Air Ducts
O F
Outside Air
0 cfm
Supply Fan Cooling Coil
56.3 / 54.2 of
900 cfm
ROOMS
42.7% R.H.
of
78.0 / 62.7 of
79.3163.1
Return Air" Ducts
EnergvPro 4.0 by EnergySoft
User Number: 5970
Job Number: 5018
Page: 15 of 23
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Bederian Residence 1/9/2006
SYSTEM NAME FLOOR AREA
HVAC System 1,140
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems
1
Heating System
Output per System
54,000
Total Output (Btuh)
54,000
Output (Btuh/sqft)
47.4
Cooling System
Output per System
35,000
Total Output (Btuh)
35,000
Total Output (Tons)
2.9
Total Output (Btuh/sqft)
30.7
Total Output (sgft/Ton)
390.9
Air System
CFM per System
1,200
Airflow (cfm)
1,200
Airflow (cfm/sqft)
1.05
Airflow (cfm/Ton)
411.4
Outside Air (%)
0.0
Outside Air (cfm/sgft)
0.00
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
Latent
CFM
I Sensible
943
15,585
1,854
275
11,875
0
1,616
1,096
0
0
0
0
0
0
0
0
0
1,616
1,096
18,8171 1,854 F 14 067
Bryant 550AN036=E/311JAV036070 23,067 9,075 54,000
Total Adjusted System Output 067 9,075 5a,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK i Aug 2 pm I Jan 12 am
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0°F 69.1,01F 69.10F 111.4°F
Supply Air Ducts
Outside Air 0�
0 cfm 110.6 OF
Supply Fan Heating Coil
1200 cfm ROOMS
70.0 OF
69.1 OF I
Return Air Ducts
DOLING SYSTEM PSYCHROMETRICS Airstream Temiperatures at Time of Cooling Peak
111.0/77.6°F 79.3166.6°F 79.3/66.7°F 61.2/60.2°F
Supply Air Ducts
)
Outside Air 0
0 cfm Supply Fan Cooling Coil 62.5! 60.6 OF
1200 cfm 54.4% R.H. ROOMS
78.0 / 66.2 OF
79.3/66.6 °F �
4.0 by EnergySoft User Number: 5970
Return Air Ducts
Job Number: 5018
16 of 23
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Bederian Residence 1/9/2006
SYSTEM NAME FLOOR AREA
HVAC System 1,371
FNr;INFFRINr; r:HFCKS . SYSTEM LOAD
Number of Systems
1
Heating System
Output per System
89,000
Total Output (Btuh)
89,000
Output (Btuh/sqft)
64.9
Cooling System
Output per System
46,500
Total Output (Btuh)
46,500
Total Output (Tons)
3.9
Total Output (Btuh/sgft)
33.9
Total Output (sgft/Ton)
353.8
Air.S stem
CFM per System
1,680
Airflow (cfm)
1,680
Airflow (cfmisgft)
1.23
Airflow (cfm/Ton)
433.5
Outside Air (%)
0.0
Outside Air (cfm/sgft)
0.00
Note: values above given at ARI conditions
iATING SYSTEM PSYCHROME'
26.0 of 69.4 of
Outside Air
0 cfm
Supply Fan
1680 cfm
69.4 of
11.0 177.6 of
Outside ��
0 cfm
79.2/68.0 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Retu rn ' Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
I COIL HTG. PEAK
CFM
Sensible
Latent
CFM
Sensible
1,465
21,079
2,868
213
11,017
0
2,186
1,017
0
0
0
0
0
0
0
0
0
2,186
1,017
25 45 . 2 868 13 051
Bryant 550AN048-E/31lJAV048110 28,545 , 15,107 89,000
Total Adjusted System Output 28,545 15,107 89,000
(Adjusted for Peak Design Conditions)
.TIME OF SYSTEM PEAK Aug 2m Jan 12 am
Cream Temoeratures at Time of Heating Peak)
69.4 of W 119.20F
Heating Coil
IReturn_Air Ducts
'STEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooli
79.2 68.0 of 79.2 / 68.0 of 63.3 / 62.3 of
Supply Fan Cooling Coil
1680 cfm
Return Air Ducts
4.0 by EnergySoft User Number: 5970 Job Number: 5018
Supply Air Ducts
118.6 of
ROOMS
70.0 of
I
Supply Air Ducts
64.5/62.8OF
59.0% R.H. ROOMS
78.0 / 67.6 of
I
17 of 23
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Bederian Residence 1/9/2006
SYSTEM NAME FLOOR AREA
HVAC System 606
Number of S stems
1
Heating System
Output per System
53,000
Total Output (Btuh)
53,000
Output (Btuh/sgft)
87.5
Cooling System
Output per System
0
Total Output (Btuh)
0
Total Output (Tons)
0.0
Total Output (Btuh/sgft)
0.0
Total Output (sgft/Ton)
0.0
Air System .
CFM per System
900
Airflow (cfm)
900
Airflow (cfm/sgft)
1.49
Airflow (cfm/Ton)
0.0
Outside Air (°/,)
0.0
Outside Air (cfm/sgft)
0.00
Note: values above given at ARI conditions
26.0 OF
Outside
—�—�
0 cfm
69.2 OF
SYCHROMETRICS
69.2 OF 69.2 OF
Supply Fan
900 cfm
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
11COIL TG.PEAK
CFM
Sensiblel
Latent
CFM'
Sensible
552
12,711
1,360
142
8,111
55.0 / 53.7 OF
0
O'
1,318
749
0
0
0
0
0
0
0
0
0
1,318
749
15,34T871 360 =:j:608
Bryant Heating & Cool 311JAV024070 0 0 53,000
Total Adjusted System Output--� 53,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 pm I Jan 12 am
Cream Temperatures at Time of Heating Peak)
124.60F r
Supply Air Ducts
123.8 OF
Heating Coil
ROOMS
70.0 OF
Return Air Ducts I
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures
at Time of Cooling -Peak
111.0 / 77.6 OF
79.4 ! 63.2 OF 79.4 / 63.2 OF
`
55.0 / 53.7 OF
Supply Air Ducts
O'
Outside Air
0 cfm
Supply Fan Cooling Coil
56.4 / 54.2 of
900 cfm
ROOMS
42.6% R.H.
OF
78.0 / 62.7 OF
79.4/63.2
Return Air Ducts
EnergyPro 4.0 by EnergySoft User Number: 5970 ' Job Number: 5018 Page: 18 of 23
ROOM LOAD SUMMARY
PROJECT NAME
Bederian Residence
DATE
1/9/2006
SYSTEM NAME
HVAC System
FLOOR AREA
1,516
ROOM LOAD SUMMARY '
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone1
1 st Floor
1
1,545
21-,307
2,202
1,545
21,307
2,202
435
17,171
'
t
PAGE TOTAL 1,545 21,307 2,202 435 17,171
TOTAL 1 1,545 21,307 2,202 435 17,171
EnergyPro By EnergySoftUser Number: User Job Number: 5018 Page: 19 of 23
ROOM LOAD SUMMARY
PROJECT NAME
Bederian Residence
DATE
1/9/2006
SYSTEM NAME
HVAC System
FLOOR AREA
611
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone
Guest
'1
502
11,605
1,365
502
11,605
1,365
131
7,537
f.
PAGE TOTAL 502 11,605 1,365 131 7,537
TOTAL 1 502 11,605 1,365 131 7,537
EnergyPro By EnergySoft User Number: User Job Number: 5018 Page:20 of23
RnnM U nAn Cl rnnnnnRY
IVIAL I I uaI ii,vraI
EnergyPro By EnergySoft User Number: User Job Number: 5018 ' Page:21 of 23
ROOM LOAD SUMMARY
EnergyPro By EnergySoft User Number• User Job Number: 5018 r Page:22 of 23
ROOM LOAD SUMMARY
PROJECT NAME
Bederian Residence -
DATE
1/9/2006
SYSTEM NAME
HVAC System
FLOOR AREA
606
[ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 5
2nd Floor
1
552
12,711
1,360
552
12,711
1,360
142
8,111
PAGE TOTAL 1 5521 12,711 1,360 142 8,111
TOTAL 1 552 12,711 1,360 142 8,111
EnergyPro By EnergySoft User Number: User Job Number: 5018 Page: 23 of 23