BRES2015-022978-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
Application Number:
Property Address:
APN:
Application Description:
Property Zoning:
Application Valuation:
Applicant:
ROB PITCHFORD
77622 COUNTRY CLUB DR
PALM DESERT, CA 92211
-1/
�"�'O%rwQulnrw
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING PERMIT
BRES2015-0229
49981 CALLE ESTRELLA
658260032
SMITH / ADDITION AND REMODEL
$23,698.00
p Q �
AUG 17 2015
CITY OF LA QUINTA
COMMUNITY DEVELOPMENT DEPARTMENT
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter
9 (commencing with Section 70001 of Division 3 of the Business and Professions Code,
and my License is in full force and effect.
License ��:� / � se No.: 997936
Date Con
OWNER -BUILDER DECLARATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State
License Law for the following reason (Sec. 7031.5, Business and Professions Code: Any
city or county that requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for the permit to file a
signed statement that he or she is licensed pursuant to the provisions of the
Contractor's State License Law (Chapter 9 (commencing with Section 7000) of Divisio
of the Business and Professions Code) or that he or she is exempt therefrom and the
basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for
permit subjects the applicant to a civil penalty of not more than five hundred dolls
($500).:
(_) I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for sale.
(Sec. 7044, Business and Professions Code: The Contractors' State License Law does not
apply to A owner of property who builds or improves thereon, and who does the work
himself or herself through his or her own employees, provided that the improvements
are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner -builder will have the burden of proving that
he or she did not build or improve for the purpose of sale.).
(1 1, as owner of the property, am exclusively contracting with licensed contractors
to construct the project. (Sec. 7044, Business and Professions Code: The Contractors'
State License Law does not apply to an owner of property who builds or improves
thereon, and who contracts for the projects with a contractor(s) licensed pursuant to
the Contractors' State License Law.).
( I I am exempt under Sec. . B.&P.C. for this reason
Date:
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for
the performance of the work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's
Lender's
VOICE (760) 777-7125
FAX (760) 777-7011
INSPECTIONS (760) 777-7153
Date: 8/17/2015
Owner:
JOHN LELAND
28 GARDEN PL
BROOKLYN, NY 92253
Contractor:
D & T REMODELING INC
44630 FRANKLIN COURT
LA QUINTA, CA 92253
(760)218-6414
Llc. No.: 997936
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided for by Section 3700 of the Labor Code, for the performance
of the wor hich this permit is issued.
I have and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which this permit
is issued. My workers' compensation insurance carrier and policy number are:
Carrier: _ Polity Number: _
I certify that in the performance of the work for which this permit is issued, I
shall not employ any person in any manner so as to become subject to the workers'.
compensation laws of California, and agree that, if I should become subject to the
workers' compensation provisions of Section 00 of the Labor Code, I sh
ompl it those pr isio .
1
Date / Applica
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS UNLAWFUL,
AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO
ONE HUNDRED THOUSAND DOLLARS ($100,000). IN ADDITION TO THE COST OF
COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE,
INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT: Application is hereby made to the Building Official for a permit subject to
the conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose
request and for whose benefit work is performed under or pursuant to any permit
issued as a result of this application , the owner, and the applicant, each agrees to, and
shall defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and
employees for any act or omission related to the work being performed under or
following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is
not commenced within 180 days from date of issuance of such permit, or cessation of
work for 180 days will subject permit to cancellation.
I certify that I have read this application and state that the above information is correct.
I agree to comply with all city and county ordinances and state laws relating to building
construction, and hereby authorize representativesf this city to enter upon the ab
menti
on d prope y J�pection purposes.
Dat J Signature (Applicant or A
FINANCIAL INFORMATION
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
ADDITION, EA ADDITIONAL 500 SF
101-0000-42400
0
$62.36
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
ADDITION, EA ADDITIONAL 500 SF PC
101-0000-42600
0
$17.40
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
ADDITION, FIRST 100 SF
101-0000-42400
0
$120.83
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
ADDITION, FIRST 100 SF PC
101-0000-42600
0
$171.14
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid forADDITION: $371.73 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
HOURLY PLAN CHECK - YES
101-0000-42600
1.5
$105.00
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
HOURLY PLAN CHECK - YES
101-0000-42600
0.75
$52.50
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid for BLDG CITY STAFF - PER HOUR: $157.50 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
BSAS SB1473 FEE
101-0000-20306
0
$1.00
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid forBU1LDING STANDARDS ADMINISTRATION BSA: $1.00 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RESIDENTIAL, EA ADDITION 1,000SF
101-0000-42403
0
$24.66
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RESIDENTIAL, EA ADDITION 1,000SF, PC
101-0000-42600
0
$10.16
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RESIDENTIAL, FIRST 1,000SF
101-0000-42403
0
$145.03
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RESIDENTIAL, FIRST 1,000SF, PC
101-0000-42600
0
$47.86
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid for ELECTRICAL.- NEW CONSTRUCTION: $227.71 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT _
PAID
PAID DATE
APPLIANCE REPAIR/ALTERATION
101-0000-42402
0
$12.09
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
APPLIANCE REPAIR/ALTERATION PC
101-0000-42600
0
$4.83
$0.00
PAID BY
METHOD
RECEIPT # .
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT'
QTY
AMOUNT
PAID
PAID DATE
CONDENSER/COMPRESSOR
101-0000-42402
0
$36.26
$0.00
PAID BY
METHOD.
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
CONDENSER/COMPRESSOR PC
101-0000-42600
0
$24.17
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
EXHAUST HOOD
101-0000-42402
0
$12.09
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
EXHAUST HOOD PC
101-0000-42600
0
$4.83
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
FURNACE
101-0000-42402
0
$36.26
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID,
PAID DATE
FURNACE PC
101-0000-42600
0
$24.17
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT .
QTY
AMOUNT,
PAID
PAID DATE
VENT FAN
101-0000-42402
0
$36.27
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
VENT FAN PC
101-0000-42600
0
$14.49
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid for MECHANICAL: $205.46 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
FIXTURE/TRAP
101-0000-42401
0
$72.54
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
FIXTURE/TRAP PC
101-0000-42600
0
$72.54
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
-ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
GAS SYSTEM, 1-4 OUTLETS
101-0000-42401
0
$12.09
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
GAS SYSTEM, 1-4 OUTLETS PC
101-0000-42600
0
$24.17
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
WATER SYSTEM INST/ALT/REP
101-0000-42401
0
$12.09
$0.00
PAID BY
METHOD.
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
WATER SYSTEM INST/ALT/REP PC
101-0000-42600
0
$12.09
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
Total Paid for PLUMBING FEES: $205.52 $0.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
REMODEL, EA ADDITIONAL 500 SF
101-0000-42400
0
$87.00
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
REMODEL, EA ADDITIONAL 500 SF PC
101-0000-42600
0
$69.60
$0.00
PAID BY
METHOD
RECEIPT #
CHECK #
CLTD BY
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
REMODEL, FIRST 100 SF
101-0000-42400
0
$49.31
$0.00
Al $ eta
,}..:� `•��,..%-�.`p�� ".CJ�
Y
r + "� ' METHODS �+
- JEt.V.4u:i�..v. .ak:safi �
�• RECEIPT # ' `
�a�Yr' ._A ....�i �. ���
^_ 1' CHECK # �•
f "CLTD BY'
DESCRIPTION"° Fst s
r�#h,��gA000UNTY`�i r
QTY`
r,�r AMOUNTF
��PAID, '�`��•'PAID6ATE
REMODEL, FIRST 500 SF PC
101-0000-42600
0
$134.88
$0.00
}h Sn,Y z
dor, n t, PAIDBY�. Y�,METHOD
i fi Sh
<<� '
�..
%
�sRECEIPT-#kr�
CHECK#k ,e,
..
GLTDBY•,
Total Paid for REMODEL: $340.79 $0.00
�.. :�DESCRIPTIONY a= a� ; r'' t
,.". N aACCOUNT"r t
QTY
;z y'AMOUNTz , fs�µ
, PAID}*>
PAID'DATE
SMI - RESIDENTIAL
101-0000-20308
0
$3.08
$0.00
a: PAID BY
10,
METHOD`§�..r�i�3frCHECK#
i%i�d
>G
-
-CLTDBY.;
Total Paid for STRONG MOTION INSTRUMENTATION SMI: $3.08 $0.00
TOTALS:$0.00
• r
I
�r
• r
I
a" T�•�
�3 0�
C�OF'Ft�'�6
Description: SMITH / ADDITION AND REMODEL
Type: BUILDING, RESIDENTIAL Subtype: ADDITION Status: APPROVED
Applied: 6/9/2015 SKH
Approved: 8/11/2015 JJO
Parcel No: 658260032 Site Address: 49981 CALLE ESTRELLA LA QUINTA,CA 92253
Subdivision: TR 14496-1 & INT IN COMMON AREAS Block: Lot: 98
Issued:
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning:
Finaled:
Valuation: $23,698.00 Occupancy Type: Construction Type:
Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: 506 SQ. FT. ADDITION AND INTERIOR REMODEL 1660 SQ. FT. ELEC, PLUMBING, AND MECH. WILL BE REVISED PER 2013 CRC CODES.
Printed: Monday, August 17, 2015 2:42:40 PM 1 of 5
RWYS TEMS
CHRONOLOGY
CHRONOLOGY TYPE
STAFF NAME
ACTION DATE COMPLETION DATE
NOTES
PLAN CHECK COMMENTS
FROM CONSULTANT
JIM JOHNSON
6/24/2015
6/23/2015
RECEIVED
PLAN CHECK COMMENTS
FROM CONSULTANT
MARY FASANO
7/20/2015
7/21/2015
RETURNED FROM YOUNG STRUCTUAL NOT APPROVED
RECEIVED
REVISIONS REQUIRED
PLAN CHECK PICKED UP
PHILIP JUAREZ
7/22/2015
7/22/2015
ROB PITCHFORD PICKED UP.
PLAN CHECK PICKED UP
STEPHANIE KHATAMI
6/25/2015
6/25/2015
PICKED UP BY MR ROB PITCHFORD
PLAN CHECK SENT TO
KAY HENSEL
7/15/2015
7/15/2015
OUTSIDE PC
PLAN CHECK SUBMITTAL
STEPHANIE KHATAMI
6/9/2015
6/11/2015
RECEIVED
RESUBMITTAL
PHILIP JUAREZ
7/15/2015
7/15/2015
PLANS RESUBMITTED GIVEN TO KAY.
Printed: Monday, August 17, 2015 2:42:40 PM 1 of 5
RWYS TEMS
RESUBMITTAL
STEPHANIE KHATAMI
8/5/2015
8/5/2015
TELEPHONE CALL
JIM JOHNSON
6/25/2015
6/25/2015
FINANCIAL
CALLED ROB PITCHFORD TO IMFORM HIM PLANS ARE READY
FOR CORRECTIONS.
TELEPHONE CALL
JIM JOHNSON
7/21/2015
7/21/2015
CALLED ROB PITCHFORD TO INFORM HIM OF CORRECTIONS
TELEPHONE CALL
JIM JOHNSON
7/22/2015
7/22/2015
DESCRIPTION
CALLED ROB PITCHFORD TO PICK UP CORRECTIONS
TELEPHONE CALL
AMOUNT
JIM JOHNSON
8/11/2015
RECEIPT #
CHECK #
8/11/2015
PAID BY
CALLED ROB PITCHFORD TO INFORM HIM PLANS ARE READY
TO ISSUE
ADDITION, EA
101-0000-42400
0
CONDITIONS
$0.00
ADDITIONAL 500 SF
CONTACTS
ADDITION, EA
NAME TYPE
0
NAME
ADDRESSI
CITY
STATE
ZIP
PHONE .
FAX :
EMAIL
APPLICANT
ROB PITCHFORD
77622 COUNTRY CLUB
DR
PALM DESERT
CA
92211
(
Printed: Monday, August 17, 2015 2:42:40 PM 2 of 5
RWYSTEMS
FINANCIAL
INFORMATION
CL
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
BY
ADDITION, EA
101-0000-42400
0
$62.36
$0.00
ADDITIONAL 500 SF
ADDITION, EA
101-0000-42600
0
$17.40
$0.00
ADDITIONAL 500 SF PC
ADDITION, FIRST 100 SF
101-0000-42400
0
$120.83
$0.00
ADDITION, FIRST 100 SF
101-0000-42600
0
$171.14
$0.00
PC
Total Paid forADDITION: $371.73 $0.00
HOURLY PLAN CHECK -
101-0000-42600
1.5
$105.00
1
$0.00
YES
Printed: Monday, August 17, 2015 2:42:40 PM 2 of 5
RWYSTEMS
Printed: Monday, August 17, 2015 2:42:40 PM 3 of 5
RWY57EM5
CLTD
DESCRIPTION
ACCOUNT
CITY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #,
METHOD
PAID BY
BY
HOURLY PLAN CHECK -
101-0000-42600
0.75
$52.50
$0.00
YES
Total Paid forBLDG CITY STAFF - PER HOUR: $157.50 $0.00
BSAS SB1473 FEE
I 101-0000-20306
1 0
1 $1.00
1 $0.00
Total Paid forBUILDING STANDARDS ADMINISTRATION $1.00 $0.00
BSA:
RESIDENTIAL, EA
101-0000-42403
0
$24.66
$0.00
ADDITION 1,000SF
RESIDENTIAL, EA
101-0000-42600
0
$10.16
$0.00
ADDITION 1,000SF, PC
RESIDENTIAL, FIRST
101-0000-42403
0
$145.03
$0.00
1,000SF
RESIDENTIAL, FIRST
101-0000-426000
$47.86
$0.00
1,000SF, PC
Total Paid for ELECTRICAL - NEW CONSTRUCTION: $227.71 $0.00
APPLIANCE
101-0000-42402
0
$12.09
$0.00
REPAIR/ALTERATION
APPLIANCE
101-0000-42600
0
$4.83
$0.00
REPAIR/ALTERATION PC
CONDENSER/COMPRES
101-0000-42402
0
$36.26
$0.00
SOR
CONDENSER/COMPRES
101-0000-42600
0
$24.17
$0.00
SOR PC
EXHAUST HOOD
101-0000-42402
0
$12.09
$0.00
EXHAUST HOOD PC
101-0000-42600
0
$4.83
$0.00
FURNACE
101-0000-42402
0
$36.26
$0.00
FURNACE PC
101-0000-42600
0
$24.17
$0.00
VENT FAN
101-0000-42402
0
$36.27
$0.00
Printed: Monday, August 17, 2015 2:42:40 PM 3 of 5
RWY57EM5
DESCRIPTION
ACCOUNT
QTY
T AMOUNT
PAID
PAID DATE
'RECEIPT #
CHECK #
METHOD
PAID BY
CLTD
BY
VENT FAN PC
101-0000-42600
0
$14.49
$0.00
Total Paid forMECHANICAL: $205.46 $0.00
FIXTURE/TRAP
101-0000-42401
0
$72.54
$0.00
FIXTURE/TRAP PC
101-0000-42600
0
$72.54
$0.00
GAS SYSTEM, 1-4
101-0000-42401
0
$12.09
$0.00
OUTLETS
GAS SYSTEM, 1-4
101-0000-42600
0
$24.17
$0.00
OUTLETS PC
WATER SYSTEM
101-0000-42401
0
$12.09
$0.00
INST/ALT/REP
WATER SYSTEM
101-0000-42600
0
$12.09
$0.00
INST/ALT/REP PC
Total Paid for PLUMBING FEES: $205.52 $0.00
REMODEL,EA
101-0000-42400
0
$87.00
$0.00
ADDITIONAL 5000 SF
REMODEL, EA
101-0000-42600
0
$69.60
$0.00
ADDITIONAL 500 SF PC
REMODEL, FIRST 100 SF
101-0000-42400
0
$49.31
$0.00
REMODEL, FIRST 500 SF
101-0000-426000
$134.88
$0.00
PC
Total Paid for REMODEL: $340.79 $0.00
SMI - RESIDENTIAL
101-0000-20308
0
$3.08
$0.00
Total Paid forSTRONG MOTION INSTRUMENTATION SMI: $3.08 $0.00
TOTALS:00
Printed: Monday, August 17, 2015 2:42:40 PM 4 of 5
RWSYS7EMS
FINAL" I BLD I I I I I
Printed: Monday, August 17, 2015 2:42:40 PM 5 of 5
RWSYSTEMS
PARENT PROJECTS
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
DOC
REVIEWS
ANGELICA ZARCO
STRUCTURAL CALCS.pdf
REVIEW TYPE
REVIEWER
SENT DATE
DUE DATE
RETURNED
DATE
STATUS
REMARKS
NOTES
NON-STRUCTURAL -
JIM JOHNSON
6/11/2015
6/23/2015
6/25/2015
REVISIONS REQUIRED
ESTRELLA.docx
2 WK
DOC
7/21/2015
JIM JOHNSON
49-981 CALLE
49-981 CALLE
0
STRUCTURAL - 2 WK
KATHRYN
SAMUELS
6/11/2015
6/23/2015
6/23/2015
REVISIONS REQUIRED
DOC
NON-STRUCTURAL -
1 WK
JIM JOHNSON
7/16/2015
7/23/2015
7/21/2015
REVISIONS REQUIRED
TITLE -24 NEEDS TO BE CLARIFIED
STRUCTURAL -1 WK
KATHRYN
SAMUELS
7/21/2015
7/28/2015
7/21/2015
APPROVED
NON-STRUCTURAL-
JIM JOHNSON
8/5/2015
8/12/2015
8/11/2015
APPROVED
KATHRYN SAMUELS
STRUCTURAL
1 WK
0
TRANSMITTAL
(2nd).pdf
Printed: Monday, August 17, 2015 2:42:40 PM 5 of 5
RWSYSTEMS
ATTACHMENTS
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
DOC
6/22/2015
ANGELICA ZARCO
STRUCTURAL CALCS.pdf
STRUCTURAL CALCS.pdf
0
DOC
6/25/2015
JIM JOHNSON
49-981 CALLE
49-981 CALLE
0
ESTRELLA.docx
ESTRELLA.docx
DOC
7/21/2015
JIM JOHNSON
49-981 CALLE
49-981 CALLE
0
ESTRELLA.docx
ESTRELLA l.docx
DOC
8/11/2015
JIM JOHNSON
SCHOOL FEES BRES2015-
SCHOOL FEES BRES201S-
0
0229.pdf
0229.pdf
2ND REVIEW -
NEW CITY TRANSMITTAL
DOC
7/20/2015
KATHRYN SAMUELS
STRUCTURAL
BRES 2015-0229
0
TRANSMITTAL
(2nd).pdf
Printed: Monday, August 17, 2015 2:42:40 PM 5 of 5
RWSYSTEMS
Bin #, 0�
Qty of La Quinta
Building 8z Safety Division
P.O. Box 1504, 78-495 Calle Tampico
La Quinta, CA 92253 - (760) 777-7012.
Building Permit Application an Tracking Sheet
Permit #
w5W5-,M
Iq
Project Address: 49n- �O f (-A,(,LC t22r,��
Owner's Name: Tm— (TY4
A. P. Number: 6se -Xco
Address: 4q-96 I t5p4LE VELLA.
Legal Description:
City, ST-; Zip: LA- GE) (&CT%
Contractor: 374 7
Telephone:
Address:
Project Description:
City, ST, Zip:
Tele phone:—r6o 726 6.4 4�
......................
CXJ f��r—�Lq OML
State Lic. #
City Linc. #.-.
Designer:
Address:777Z (r0U0r0)K&,--"5
City, ST, Zip:
Telephone
.....
............ . ........ ........... .
........ ..
X,
---struction Type: Occupancy:
State Lic.
Project type (circle one): New Add'n Alter Repair Demo
Name of Contact Person: Rr7
Sq. Ft.Zp AR>It� Stories:
#Units:
Telephone # of Contact Person: ;�
Estimated Value of Project: Q 0(:: %
APPLICANT: DO NOT WRITE BELOW THIS LINE
9
'Submittal
Req'd
Rec1d
TRACKING
PERMIT FEES
Plan Sets
Plan Check submitted
Item
Amount
Structural Calcs.
Reviewed, ready for corrections
Plan Check Deposit
Truss Calcs.
Called Contact Person
Plan Check Balance.
Title 24 Calcs.
Plans picked up
Construction
Flood plain plan
Plans resubmitted
Mechanical
Grading plan
21' Review, ready for corrections/issue
Electrical
Subcontactor List
Called Contact Person
Plumbing
Grant Deed
Plans picked up
S.M.I.
H.O.A. Approval
Plans resubmitted
Grading
IN HOUSE:-
Review, ready for corrections/issue
Developer Impact Fee
Planning Approval
Called Contact Person
A.I.P.P.
Pub. Wks. Appr
Date of permit issue
School Fees
0%
KLUCIV I M.U--
A A eIA4&
Total Permit Fees
��Z� s {-ru �i PAO V -p -
J.0 I I V 41 w1.+
1.0
CITY OF LA QUINTA
;OMMUNITY DEVELOPMEV
4-
CERTIFICATE OF COMPLIANCE
s
Desert Sands Unified School District
47950 Dune Palms Road
< 6ERMUDAOUNES r
Date
8/17/15
La Quinta,.CA 92253
1A RANCHO MIRAGE d
�— INDIANWELLS ti
31899
(760) 771-8515
PALM DIDESERT
d
IIO y
Owner
Stephen Smith
APN #
658-260-032
Address
49981 Calle Estrella
Jurisdiction
La Quinta
City
La Quinta Zip
Permit #
Tract #
No. of Units
1
Type
Residential Addition - Street No. Correction
Lot # No. Street
S.F. Lot # No.
Street S.F.
Unit 1
49981 Calle Estrella
221 Unit 6
Unit 2 Unit 7
Unit 3 Unit 8
Unit 4 Unit 9
Unit 5 Unit 10
CommentOriginal COC recorded as 49081 which did not exist in school site locator. I searched apn after D. Norblom left & found it was linked to 49981
vs 49081. Philip Juarez from city called later in day regarding error on their Cert. of Sq. Footage form.
Emailinq this corrected COC to Divarez(Dla-quinta.orq on 8/18/15 Der his reauest.
At the present time, the Desert Sands Unified School District does not coltectiees on garages carports, covered patios/walkways, ressidential additions un er
500 square feet, detached accessory structures (spaces that do not contain facilities for living, sleeping, cooking, eating or sanitation) or replacement mobile
homes. It has been determined that the above-named owner is exempt from paying school fees at this time due to the following reason:
Residential Addition 500 Sq Feet or Less
EXEMPT
This certifies that school facility fees imposed pursuant to
Education Code Section 17620 and Government Code 65995 Et Seq.
in the amount of $0.00 X 221 S.F. or $0.00 have been paid for the property listed above and that
building permits and/or Certificates of Occupancy for this square footage in this proposed project may now be issued.
Fees Paid By Exempt - Dennis Norblom Check No.
Bank Name/Recipient of Certificate Telephone
Funding Exempt
BY Dr. Gary Rutherford
Superintendent
Fee collected lexemp�ed,tty S ar n -M bilvrey Payment Recd
/f /v Over/Under
NOTICE: Pursuant to Government Code Section 66020(d)(1),thi will serve to notify you that the 90 -day approval period in which you may protest the fees
or other payment identified above will begin to run from the da n which the building or installation permit for this project is issued, or from the date on
which those amounts are paid to the District(s) or to another public entity authorized to collect them on the District('s) behalf, whichever is earlier.
NOTICE: This Document NOT VALID without embossed seal
Embossed Original - Building Department Applicant Copy - Applicant/Receipt Copy - Accounting
Comments
At the present time, the Desert Sands Unified School District does not collect fees on garages/carports, covered patios/walkways, residential additions under
500 square feet, detached accessory structures (spaces that do not contain facilities for living, sleeping, cooking, eating or sanitation) or replacement mobile
homes. It has been determined that the above-named owner is exempt from paying school fees at this time due to the following reason:
Residential Addition 500 Sq Feet or Less
EXEMPT
This certifies that school facility fees imposed pursuant to
Education Code Section 17620 and Government Code 65995 Et Seq.
in the amount of $0.00 X 221 S.F. or $0.00 have been paid for the property listed above and that
building permits and/or Certificates of Occupancy for this square footage in this proposed project may now be issued.
Fees Paid By Exempt - Dennis Norblom Check No.
Bank Name/Recipient of Certificate Telephone
Funding Exempt
BY Dr. Gary Rutherford
Superintendent
Fee collected /exempte by haro Mc Ivre fN- -- Payment Recd I$0.00
!°Over/Under
Signature
NOTICE: Pursuan to Government Code Section 66020(d)(1), thi will s rve to notify you that the 90 -day approval period in which you may protest the fees
or other payment identified above will begin to run from the date o wh' h the building or installation permit for this project is issued, or from the date on
which those amounts are paid to the District(s) or to another public entity authorized to collect them on the District('s) behalf, whichever is earlier.
NOTICE: This Document NOT VALID without embossed seal
Embossed Original - Building Department Applicant Copy - Applicant/Receipt Copy - Accounting
I
BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Stephen Smith Residence
49-981 Calle Estrella
La Quinta, CA 92253
Project Designer:
Robert A. Pitchford Design and Drafting
77-622 Country Club STE O
Palm Desert, CA 92211
(760) 346-2856
Report Prepared by:
Tim Scott
Scott Design and Title 24, Inc,.
77085 Michigan Drive
Palm Desert, CA 92211
(760) 200-4780
Job Number: CITY OF LA QUINTA
BUILDING & SAFETY DEPT
APPR VED
Date: FOR CONST CTION
7/30/2015 DATE a /
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
0 authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC—www.energysoft.com.
1
EneravPro 6.6 by EneravSoft User Number: 6712 ID:
CERTIFJOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE r#OD
Project me: Remodeled Residence C ulation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CF F-01
PaJF1 of 11
GENERAL INFORMATION
01
Building Complies with Computer Performance
01
Project Name Remodeled Residence
03
This building incorporates one or more Special Features shown' below
02
Calculation Description Title 24 Analysis
08
Energy Use (kTDVIftZ-yr)
03
Project Location 49-981 Calle Estrella
Compliance Margin
Percent Improvement
04
City La Quinta
05
Standards Version Compliance 2015
06
Zip Code 92253
07
Compliance Manager Version BEMCmpMgr 2013-4 (744)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.6
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 20
12
Project Scope Addition and/or Alteration
13 21�*
Number of Dwelling Units 1
14
Total Cond. Floor Area (ft2) 2175
15 A�
Number of Zones 3
16
Slab Area (ft2) 2175
17W(v
Number of Stories 1
18
Addition Cond. Floor Area 221
e165
Natural Gas Available Yes
20
Addition Slab Area (ft) 221
C21
Glazing Percentage (%) 23.6%
AW
COMPLIANCE RESULTS
01
Building Complies with Computer Performance
02
This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03
This building incorporates one or more Special Features shown' below
06
A��
Registration Number: �►�
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-07082015-744
HERS Provider:
Report Generated at: 2015-07-30 08:23:28
ENERGY USE SUMMARY
045j
06
07
08
Energy Use (kTDVIftZ-yr)
Sta d d Design
Proposed Design
Compliance Margin
Percent Improvement
Space Heating
12.70
12.59
0.11
0.9%
Space Cooling
^11� 332.88
328.20
4.68
1.4%
IAQ Ventilation
0.00
0.00
0.00
0.0%
Water Heatingtv
10.97
10.79
0.18
1.6%
Photovoltaic Offset
�,' —
0.00
0.00
--
Compliance Energy Total
�^�� 356.55
351.58
4.97
1.4%
Registration Number: �►�
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-07082015-744
HERS Provider:
Report Generated at: 2015-07-30 08:23:28
CERTIFJOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE IVOD CFF -01
Project Name: Remodeled Residence IC
ulation Date/Time: 08:22, Thu, Jul 30, 2015 PaW2 of 11
Calculation Description: Title 24 Analysis Input File Name: Smith-Pitchford-15.xm1
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Cool roof
• Cathedral Ceiling
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
• -- None —
o
Coling System Verifications:
• -- None —
HVAC Distribution System Verifications:
• Duct Sealing
Domestic Hot Water System Verifications:
• -- None —
ENERGY DESIGN RATING 4r
This is the sum of the annual TDV energy consumption for energy use components included in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and components not regulated by Title 24, Part 6 (such as'domestic appliances and consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system. V
Reference Energy Use ♦.1 Energy Design Rating Margin Percent Improvement
Total Energy (kTDV/f2-yr)* 402.84 397.87 4.97 1.2%
includes calculated Appliances and Miscellaneous Energy Use (AMEU) e�
4LV
BUILDING - FEATURES INFORMATION
01
02
03
04
05
06
07
d'
Number of Dwelling
Number of Ventilation
Number of Water
Project Name
Conditioned Floor Area (ft2)
Units
Number of Bedrooms
Number of Zones
Cooling Systems
Heating Systems
Remodeled Residence
2175 v
1
3
3
3
1
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-07082015-744
HERS Provider:
Report Generated at: 2015-07-30 08:23:28
CERTIFJPE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project ame: Remodeled Residence C ulation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CFF -01
Pa'X3 of 11
ZONE INFORMATION
01
02
03
04
05
06
07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1
Water Heating System 2
residence
Conditioned
HVAC1
1660
9
DHW Sys 1
addition
Conditioned
HVAC2
221
9
DHW Sys 1
casita
Conditioned
HVAC new3
294
9
DHW Sys 1
OPAQUE SURFACES
01
02
03
04
jh,05
06
07
08
09
10
Name
Zone
Construction
Azimuth�Orientation Gross Area (ft)
Window & Door
Area (ft)
Tilt
(deg)
Status
Verified
Existing
Condition
70d Wall ex
residence
R-13 Wall
7S0'4:0
50
682
78
90
Existing
No
160d Wall ex
residence
R-13 Wall
162)
140
1386
122.5
90
Existing
No
250d Wall ex
residence
R-13 Wall
W.
230
882
98
90
Existing
No
NW Wall ex
residence
R-13 Wall
315
295
250
15
90
Existing
No
340d Wall ex
residence
R-13 Wall 340
320
1386
90
Existing
No
Roof 3
residence
Defaul: 1978 to present
1623.6
Existing
No
70d Wall
addition
R-21 Wall (W.21.2Z,A)
70
50
200
90
New
N/A
160d Wall
addition
R-21 Wall (W21 -.2z6.16)
160
140
200
46.9
90
New
N/A
S Wall
addition
R-21 Wall (W 2x6.16)
180
160
150
26.8
90
New
N/A
250d Wall
addition
R-21 Wall;(W'21.2x6.16)
250
230
252
40
90
New
N/A
340d Wall
addition
R-21 Waa11T(W21.2x6.16)
340
320
352
90
New
N/A
Roof 4
addition
AT38 Roof Attic
221
New
N/A
70d Wall ex 2
casita
R-13 Wall
70
50
200
15
90
Existing
No
160d Wall ex 2
casita 4
R-13 Wall
160
140
200
90
Existing
No
250d Wall ex 2
casita R-13 Wall
250
230
252
25
90
Existing
No
W Wall ex
casita
R-13 Wall
270
250
150
48
90
Existing
No
340d Wall ex 2
casita
R-13 Wall
340
320
352
90
Existing
No
Roof 5
casita �^�`
Default prior To 1978
285.2
Existing
No
♦0
Registration Number: ,P'% Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:28
CERTIFIOe: Remodeled Residence C ulE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE #OD
Project mation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CFF -01
Pa'X4 of 11
OPAQUE SURFACES — Cathedral Ceilings
01
02
03
04
05
06
06
07
08
09
10
11
1 12
13
Radiant
Statu
Verified Existing
Name
Construction
Type
Roof
Reflectance
Framin
Barrier
Verified
s
Condition
Orientatio
Area
Skylight
Roof Rise
Roof
Roof
Reflectan
Roof
g
Statu
Existing
Name
Zone
Type
n
(ft)
Area (ft2)
(x in 12)
Pitch
Tilt(deg)
ce
Emittance
Factor
s
Condifion
Roof
residence
Defaul: 1978 to
_ specify -
36.5
1.2
3
0.25
14.04
0.1
0.85
0.1
Existin
No
Attic addition
Attic Roofaddition
presentl
3%
0.3
0.75
No
Yes
New
No
Attic casita
Attic Roofcasita
g
�
Roof 2
casita
Default prior To
specify -
8.9
8.8
3
0.25
14.04
0.1
0.85
0.1
Existin
No
ng_
19781
g
ATTIC
01
02
03
04
05
06
07
08
09
10
Radiant
Statu
Verified Existing
Name
Construction
Type
Roof Rise,Roof
Reflectance
Roof Emittance
Barrier
Cool Roof
s
Condition
Existi
Attic residence
Attic Roofresidence
Ventilated
3
0.1
0.85
No
No
No
�)
ng
Attic addition
Attic Roofaddition
Ventilated
3%
0.3
0.75
No
Yes
New
No
Attic casita
Attic Roofcasita
Ventilated
�
0.1
0.85
No
No
Existi
No
��3
ng_
e®�
AP
♦ V�
♦r
Registration Number- Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:28
CERTIFJPE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE I#OD
Project ame: Remodeled Residence C culation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CFSRF-01
Pa7'5 of 11
WINDOWS
01
02
03
04 05
06
07
08
09
10
11
Name
Surface (Orientation -Azimuth)
Width(ft)
Multiplie
Height (ft) r
Area (ft)
U -factor
SHGC
Exterior Shading
Status
Verified
Existing
Condition
ex 3x5
70d Wall ex (- specify -70)
--
-- 1
15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 3x5 2
70d Wall ex (- specify -70)
-
-- 1
15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 5x5
160d Wall ex (- specify -160)
-
-- 1
25.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 5x5 2
160d Wall ex (- specify -160)
-
-- 1
25.0
0.71
0.60
Insect Screen (default)
Existing
No .
ex 3x5 3
160d Wall ex (- specify -160)
--
-- 1
15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 3x5 4
160d Wall ex (- specify -160)
--
-- 1 15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 7.5x5
160d Wall ex (- specify -160)
-
-- �J{!P
10.0
0.71
0.60
Insect Screen (default)
Existing
No
alt 5x6.5
160d Wall ex (- specify -160)
--
-- "Al
32.5
0.46
0.24
Insect Screen (default)
Altered
N/A
all 5x8
250d Wall ex (- specify -250)
-
-- 1
40.0
0.46
0.24
Insect Screen (default)
Altered
N/A
alt 5x8 2
250d Wall ex (- specify -250)-
-- 1
40.0
0.46
0.24
Insect Screen (default)
Altered
N/A
all 3x6
250d Wall ex (- specify -250)
--
,5- , 1
18.0
0.46
0.24
Insect Screen (default)
Altered
N/A
alt 2.5x6
NW Wall ex (- specify -315)--
1
15.0
0.46
0.24
Insect Screen (default)
Altered
N/A
Skylight ex
Roof (- specify --270)
--
-- 1
1.2
0.55
0.55
None
Existing
No
Skylight ex 2
Roof (- specify --270)
- -- 1
8.8
0.55
0.55
None
Existing
No
Skylight ex 3
Roof (- specify --270)
-- �,
-- 1
8.8
0.55
0.55
None
Existing
No
Skylight ex 4
Roof (- specify --270)
�'�
-- 1
8.8
0.55
0.55
None
Existing
No
Skylight ex 5
Roof (- specify --270)
�!w
-- 1
8.8
0.55
0.55
None
Existing
No
new 3x6.7
160d Wall (- specify -160)
1
20.1
0.46
0.24
Insect Screen (default)
New
N/A
new 4x67
160d Wall (- specify --160) j v --
-- 1
26.8
0.46
0.24
Insect Screen (default)
New
N/A
new 4x6.7
S Wall (- specify -180) ,e
--
-- 1
26.8
0.46
0.24
Insect Screen (default)
New
N/A
new 8x5
250d Wall (- specify -256)'30'--
-- 1
40.0
0.46
0.24
Insect Screen (default)
New
N/A
ex 3x5 5
70d Wall ex 2 (- specify-
--
-- 1
15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 5x5 3
250d Wall ex 2 (- specify --250)
--
-- 1
25.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 6x8
W Wall ex (- specify -270)
-
-- 1
48.0
0.71
0.60
Insect Screen (default)
Existing
No
Skylight ex 6
Roof 2 (,specify -270)
--
-- 1
8.8
0.55
0.55
None
Existing
No
Registration Number: t�
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - MR -07082015-744
HERS Provider:
Report Generated at: 2015-07-30 08:23:28
CERTIFJW OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE Cr
Project ame: Remodeled Residence C ulation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis Input File Name: Smith-Pitchford-15.xml
CFF -01
PaW6 of 11
DOORS
01 02 03 04 05 06
Name Side of Building Area (ft2) U -factor Status Verified Existing Condition
Door 70d Wall ex 48.0 0.50 Existing No
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:28
CERTIFjPE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE I#OD
Project ame: Remodeled Residence C culation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CFSRF-01
Pa of 11
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
Total Cavity
Winter Design
Construction Name
Surface Type
Construction Type
Framing
R -value
U -value
Assembly Layers
• Cavity / Frame: no insul. 12x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofresidence
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-9.1 /2x4
Defaul: 1978 to present
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 11
0.083
Over Floor Joists: R-1.9 insul.
>
Inside Finish: Gypsum Board
• Cavity / Frame: R-11 / 2x4
• Roof Deck: Wood Siding/sheathing/decking
Defaul: 1978 to presentl
Cathedral Ceilings
Wood Framed Ceiling
2x4 @ 16 in. D.C.
R 11
0.088
Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
• Cavity/Frame: R -13/2x4
• Exterior Finish: Wood
R-13 Wall
R-13
Exterior Walls
Wood Framed Wall
2x4 @ 16
R 13
0.095
Siding/sheathing/decking
• Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord o�f RRoof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofaddition
Attic Roofs
Wood Framed Ceiling
IV. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
�®
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-9.1 /2x4
R-38 Roof Attic
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 38
0.025
Over Floor Joists: R-28.9 insul.
Inside Finish: Gypsum Board
• Cavity/Frame: R-21 /2x6
Exterior Finish: Wood
R-21 Wall (W.21.2x6.16)
Exterior Walls
Wood Framed Wall''
2x6 @ 16 in. O.C.
R 21
0.066
Siding/sheathing/decking
Cavity/ Frame: no insul. / 2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofcasita
Attic Roofs
Wood Framedeiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-9.1 /2x4
Default prior To 1978
attic)
Wood Famed Ceiling
2x4 @ 16 in. O.C.
R 11
0.083
Over Floor Joists: R-1.9 insul.
P
Inside Finish: Gypsum Board
Cavity / Frame: R-11 / 2x4
• Roof Deck: Wood Siding/sheathing/decking
Default prior To 19781
Cathedral Ceilings,
Clood Framed Ceiling
2x4 @ 16 in. O.C.
R 11
0.088
Roofing: Light Roof (Asphalt Shingle)
'00
Registration Number:
CA Building Energy Efficiency Stands - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-07082015-744
HERS Provider:
Report Generated at: 2015-07-30 08:23:28
CERTIFPE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE COD
Project
'PE
Remodeled Residence C culation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CFSRF-01
Pa 8 of 11
SLAB FLOORS
01
02
03
04
05
06
07
08
09
Name
Zone
Area (ft)
Perimeter
(ft)
Edge Insul. R -value
Carpeted
Fraction
Heated
Status
Verified
Existing
Condition
Covered Slab
residence
1660
175
None
0.8
No
Existing
No
Covered Slab 2
addition
221
62
None
0.8
No
New
No
Covered Slab 3
casita
294
72
None
0.8
No
Existing
No
BUILDING ENVELOPE - HERS VERIFICATION b
01 02 zo 03 04
Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa
Not Required Not Required �� Not Required --
pA_
WATER HEATING SYSTEMS ���
w
01
02
03K�'
04
05
06
07
08
Name
Heater Element Type
®v
Tank Volume
(gal)
Energy Factor or
Efficiency
Solar
Tank Exterior
Insulation R -value
Standby Loss
(Fraction)
DHW Heater 1
Natural Gas
�t§mall Storage
50
Number of
Fraction
0
Verified Existing
Name
System Type
Distribution Type
Water Heater
Heaters
N
Status
Condition
DHW Sys 1
DHW
Pipe Insulation, All Lin "S*'
DHW Heater 1
1
Annual
Existing
No
M
WATER HEATERS �V
01
02
s 0`
04
05
06
07
08
Name
Heater Element Type
wank Type
Tank Volume
(gal)
Energy Factor or
Efficiency
Input Rating
Tank Exterior
Insulation R -value
Standby Loss
(Fraction)
DHW Heater 1
Natural Gas
�t§mall Storage
50
0.61 EF
40000-Btu/hr
0
0
Ifto,
WATER HEATING - HERS VERIFICATION .01,
01
02 0v
03
04
05
06
07
Recirculation with
Recirculation with
Name
Pipe Insulation
Parallel Piping
Compact Distribution
Point -of Use
Manual Control
Sensor Control
DHW Sys 1^
n
n/a
n/a
n/a
n/a
n/a
.0
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-07082015-744
HERS Provider:
Report Generated at: 2015-07-30 08:23:28
CERTIE OF COMPLIANCE -RESIDENTIAL PERFORMANCE COMPLIANCE OD
Project ame: Remodeled Residence C culation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CF ARF -01
Pa 9of11
SPACE CONDITIONING SYSTEMS
01
02
03
04
05
06
07
08
09
CntrlFurnace Fuel -fired central furnace
80 AFUE
Heating System
Cooling System
80 AFUE
Heating Component 3
Cntrl Fa nr ace - Fuel -fired central furnace
80 AFUE
HERS Verification
Cooling Component 1
SplitAirCond - Split air conditioning
10
12
Distribution
Fan
Floor Area
Verified Existing
Name
System Type
Name Ducted
Name Ducted
System
System
Served
Status
Condition
HVAC1
Other Heating and
Heating
Yes
Cooling
Yes
Air Distribution
HVAC Fan
1660
Existing
No
Cooling System
Component 1
Component 1
System 1
1
10
12
No
HVAC2
Other Heating and
Heating
Yes
Cooling
No
Air Distribution
HVAC Fan
221
Existing
No
Cooling System
Component 2
Component 2
System 2
2
HVAC new3
Other Heating and
Cooling System
Heating
Component 3
Yes
Cooling
Component 3
No
'Air Distribution
3
HVAC Fan
3
294
Existing
No
��System
4k�
HVAC - HEATING SYSTEMS
01
02
01
♦w02�
03
Name
pQType
Efficiency
Heating Component 1
CntrlFurnace Fuel -fired central furnace
80 AFUE
Heating Component 2
CntrlFurnraace - Fuel -fired central furnace
80 AFUE
Heating Component 3
Cntrl Fa nr ace - Fuel -fired central furnace
80 AFUE
HVAC - COOLING SYSTEMS ♦411;�'
01
02
X69 04
05
06
07
Efficiency
Multi -speed
Name
System Type
♦.� EER SEER
Zonally Controlled
Compressor
HERS Verification
Cooling Component 1
SplitAirCond - Split air conditioning
10
12
No
No
N/A
system
Cooling Component 2
DuctlessSplitAirCond - Ductless '
10
12
No
No
N/A
mini -split and multi -split heat A/;C i
Cooling Component 3
DuctlessSplitAirCond Duc�ssY
mini -split and multi -split heatawc
10
12
No
No
N/A
♦®4/
Registration Number: "
CA Building Energy Efficiency Stan ds - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-07082015-744
HERS Provider:
Report Generated at: 2015-07-30 08:23:28
CERTIFJOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE I OD
Project
'JOE
Remodeled Residence Ca culation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xmi
CF9RF-01
Pag 0 of 11
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
08
09
10
Duct Leakage f
Target (%) ��
Verified Duct Location
Verified Duct Design
Return Supply
Insulation
Supply Duct
Return Duct
61
0.52459
Verified Existing
HERS
Name
Type
Duct Leakage
R -value
Location
Location
Bypass Duct
Status
Condition
Verification
Air Distribution
Ducts located in attic
Existing (not
4.2
Attic
Attic
None
Existing
No
N/A
System 1
specified)
Air Distribution
Ducts located in attic
Existing (not
4.2
Attic
Attic
None
Existing
No
N/A
System 2
specified)
Air Distribution
Air Distribution
Ducts located in attic
Sealed and tested
4.2
AtticF,��Attic
None
New
No
System
System 3
3 -hers -dist
ow
HVAC DISTRIBUTION - HERS VERIFICATION
�w
M
01
02
03
�� 04
05 06
Name
Duct Leakage
Verification
Duct Leakage f
Target (%) ��
Verified Duct Location
Verified Duct Design
Return Supply
Air Distribution System 1 -hers -dist
N/A
WH Fan 2
61
0.52459
1
Air Distribution System 2 -hers -dist
N/A
—
–
—
–
Iv
IAQ (Indoor Air Quality) FANS #AZ
01 02 03 04 05
Name IAQ CFM �� IAQ Fan Type IAQ Recovery Effectiveness(%) HERS Verification
SFam IAQVentRpt 0`Default 0 Not Required
O%N
COOLING VENTILATION
01
�� 02
03
04
Name
Cooling Vent CFM
Cooling Vent Watts/CFM
Number of Fans
WH Fan 1
�S►v 61
0.52459
1
WH Fan 2
61
0.52459
1
WH Fan 3
��/ 61
0.52459
1
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-07082015-744
HERS Provider:
Report Generated at: 2015-07-30 08:23:28
CERTIF* OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE I#OD
Project ame: Remodeled Residence Ca ulation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xm1
CFVF-01
Page CFV
of 11
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Tim Scott
Company:
Signature Date:
Scott Design and Title 24, Inc,
7/30/2015
Address:
CEA/HERS Certification Identification (If applicable):
77085 Michigan Drive
City/State ip:
Palm Desert, CA 92211
Phone: �
(7 0) 200-4780
lito
RESPONSIBLE PERSON'S DECLARATION STATEMENT w(_
I certify the following under penalty of perjury, under the laws of the State of California: oma%
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility forr"Re building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this CertificateCompliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
3. The building design features or system design features identified on this Certificate of Comp it ance are consistent with the information rovided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency�or b ' approval with this permit a
Responsible Designer Name: 4t�
igner Sign
Robert A. Pitchford
Company: � v
v /�Robert
Fev
A. Pitchford Design and Drafting C1I
Address: ��
License:
77-622 Country Club STE.O �®
City/State/Zip: `� -
Phone:
Palm Desert, CA 92211 A
_
(760) 346-2856 - -
Registration Number: t�
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-07082015-744
HERS Provider:
Report Generated at: 2015-07-30 08:23:28
•
1�
L.
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Stephen Smith Residence
Building Type 10 Single Family ❑ Addition Alone
❑ Multi Family 12 Existing+ Addition/Alteration
Date
7/30/2015
Project Address
49-981 Calle Estrella La Quinta
California Energy Climate Zone I
CA Climate Zone 15 i
Total Cond. Floor Area
2,175
Addition
221
# of Units
1
INSULATION
Construction Type
Area
Cavity (ft)
Special Features Status
Roof Wood Framed Attic
R 11 1,624
Existing
Wall Wood Framed
R 13 5,633
Existing
Door Opaque Door
no insulation 48
Existing
Slab Unheated Slab -on -Grade
no insulation 1,954
Perim = 247'
Existing
Demising Wood Framed
R 13 723
New
Roof Wood Framed Attic
R38 221
Cool Roof
New
Wall Wood Framed
R 21 1,040
New
Slab Unheated Slab -on -Grade
- no insulation 221
Perim = 62'
New
FENESTRATION
Orientation Area(ft)
I Total Area: 512 Glazing Percentage: 23.6
U -Fac SHGC Overhang Sidefins
New/Altered Average U -Factor: 0.46
Exterior Shades Status
Skylight 1.2
0.550
0.55 none
none
None Existing
Skylight 8.8
0.550
0.55 none
none
None Existing
Skylight 8.8
0.550
0.55 none
none
None Existing
Skylight 8.8
0.550
0.55 none
none
None Existing
Skylight 8.8
0.550
0.55 none
none
None Existing
Left (E) 45.0
0.710
0.60 none
none
Bug Screen Existing
Rear (S) 90.0
0.710
0.60 none
none
Bug Screen
Existing
Rear (S) 32.5
0.460
0.24 none
none
Bug Screen Altered
Right (W) 98.0
0.460
0.24 none
none
Bug Screen Altered
Right (NIM 15.0
0.460
0.24 none
none
Bug Screen Altered
Rear (S) 46.9
0.460
0.24 none
none
Bug Screen
New
Rear (S) 26.8
0.460
0.24 none
none
Bug Screen New
Right (W) 40.0
0.460
0.24 none
none
Bug Screen New
Skylight 8.8
0.550
0.55 none
none
None
Existing
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling
Min. Eff
Thermostat Status
2 Central Furnace
80% AFUE
Split Air Conditioner
12.0 SEER
Setback
Existing
1 Central Furnace
80% AFUE
Split Air Conditioner
12.0 SEER
Setback
Existing
1 Central Furnace
80% AFUE
Split Air Conditioner
12.0 SEER
Setback
Existing
HVAC DISTRIBUTION
Location Heating
Cooling Duct Location
Duct
R -Value Status
HVAC Ducted
Ducted Attic
4.2
Existing
HVAC Ductless/ with Fan
Ductless n/a
n/a
Existing
HVAC new Ductless/ with Fan
Ductless n/a
n/a
New
WATER HEATING
Qty. Type
Gallons Min. Eff
Distribution Status
Ene Pro 6.6 by EnemySoft User Number. 6712
RunCode: 2015-07-30708:23:46
/D:
Pae 14 of 32
•
C
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Stephen Smith Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Addition/Alteration
Date
7/30/2015
Project Address
49-981 Calle Estrella La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
2,175
Addition
221
# of Units
1
INSULATION
Construction Type
Area
Cavity (ft) Special Features Status
Roof Wood Framed Attic R11 285 Existing
FENESTRATION T Total Area: 512 Glazing Percentage: 23.6 % I New/Altered Average U -Factor: 0.46
Orientation Area(ft) U -Fac SHGC Overhang Sidefins Exterior Shades Status
Right (tM 25.0 0.710
0.60 none none Bug Screen Existing
Right (tq 48.0 0.710
0.60 none none Bug Screen Existing
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
EnemyPro 6.6 by EnemySoft User Number: 6712
RunCode: 2015-07-30708:23:46 /D:
Pae 15 of 32
4
2013 Low -Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the
com /lance
approach used. Exceptions may apply, Review the respective code section or more information.
Building Envelope Measures:
§110.6(a)1:
Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§1 10.6(a)5:
Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of §10-11 I (a).
§110.7:
Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed.
§I 10.8(a):
Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the C172R.
§110.8(1):
The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of § 1 10.8(i) when the
installation of a cool roof is specified on the CFIR.
§ 110.80):
A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CFI R.
Minimum R-30 insulation in wood -frame ceiling; or the weighted average U -factor shall not exceed 0.031. Minimum R-19 in a
§I50.0(a):
rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The
attic access shall be gasketed to prevent air leakage.
§I50.0(b):
Loose fill insulation shall conform with manufacturer's installed design labeled R -value.
§150.0(c):
Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U -
factor).
§I50.0(d):
Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U -factor.
In Climate Zones 14 and 16 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior
§I50.0(g)1:
walls, vented attics and unvented attics with air -permeable insulation.
In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class 11
§ 150.0(g)2:
vapor retarder.
In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of
§I50.0(g)3:
the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section
150.0(d).
§150.0(1):
Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%;
have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration;
and when installed as part of a heated slab floor meets the requirements of § 110.8
150.0 (q)'
Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U -
factor of 0.58; or the weighted average U -factor of all fenestration shall not exceed 0.58.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
§ 150.0(e) I A:
Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§I50.0(e)1B:
Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a readily accessible, operable, and tight -fitting damper or a combustion -air control device.
§I50.0(e)1C:
Masonry or factory -built fireplaces have a flue damper with a readily accessible control.
§I50.0(e)2:
Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside
of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§ 110.3:
HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission.
§I 10.3(c)5:
Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation
valve, and recirculation loop connection requirements of § 110.3(c)5.
Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli-
§110.5:
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool
ands a heaters.
§I50.0(h)1:
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified
in§150.Oh2.
§ 150.0(h)3A:
Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any
dryer vent.
§I50.0(i):
Heating systems are equipped with thermostats that meet the setback requirements of §I 10.2(c).
§150.00)1A:
Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§ 150.00)1 B:
Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R-12 external
insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank.
For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage
tank, all piping with a nominal diameter of 3/4 inch or larger, all piping associated with a domestic hot water recirculation system
§ I50.00)2A:
regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and
all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3-
A,
§I50.00)2B:
All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable casing or sleeve
that allows for installation, removal, and replacement of the enclosed pipe and insulation.
2013 Low -Rise Residential Mandatory Measures Summary
§I50.00)2C: Pipe for cooling system lines shall be insulated as specified in §I50.00)2A. Piping insulation for steam and hydronic heating
systems or hot waters stems with pressure > 15 psig shall meet the requirements in TABLE 120.3-A.
§150.00)3: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For
§150.00)3A: example, protected by aluminum, sheet metal, painted.canvas, or plastic cover. Cellular foam insulation protected as specified or
painted with coating that is water retardant and provides shielding from solar radiation that degrades the material.
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I
§150.00)3B: or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class Il vapor
retarder.
Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3
feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the
§ I50.0(n)l : space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000
Btu/hr.
§I50.0(n)2: Recirculating loops serving multiple dwelling units shall meet the requirements of §I 10.3(c)5.
§150.0(n)3: Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC)
or by a testing agency approved by the Executive Director.
Ducts and Fans Measures:
All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0,
§603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition.
Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC
§605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed
§150.0(m)1: with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B or
aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than ''A inch, the
combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums
defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying
conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms
shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints
§ 150.0(m)2: and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is
used in combination with mastic and draw bands.
§15 0.0(m)3-6: Field -Fabricated Duct Systems shall comply with requirements for: pressure -sensitive tapes, mastics, sealants, and other
requirements specified for duct construction; duct insulation R -value ratings; duct insulation thickness; and duct labeling.
§I50.0(m)7: All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic
dampers.
§I50.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers
except combustion inlet and outlet air openings and elevator shaft vents.
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not
§ I50.0(m)9: limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum,
sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is
water retardant and provides shielding from solar radiation.
§I50.0(m)10: Flexible ducts cannot have porous inner cores.
When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be
§I50.0(m)11: sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference
Residential Appendix RA3.
Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§ 150.0(m)12: conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of
§150.0 m 12.
Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the
placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The
§150.0(m)13: space conditioning system must also demonstrate airflow> 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy < 0.58 W/CFM as confirmed by field verification and diagnostic testing, in
accordance with Reference Residential Appendix RA3.
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode,
§I50.0(m)15: an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of> 350 CFM per ton of nominal cooling
capacity, and operating at an air -handling unit fan efficacy of < 0.58 W/CFM as confirmed by field verification and diagnostic
testing, in accordance with Reference Residential Appendix RA3.
All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of
§150.0(0): central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the
Whole Building Ventilation.
§I50.0(o)IA: Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.
Pool and Spa Heating Systems and Equipment Measures:
Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
§110.4(a): Regulations; an on switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat
setting; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating.
r
2013 Low -Rise Residential Mandatory Measures Summary
§ 110.4(b)1:
Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction
and return lines, or built-up connections for future solar heating.
§1 10.4(b)2:
Outdoor pools or spas that have a heat pump or gas heater shall have a cover.
§1 10.4(b)3:
Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro -
rammed to run only during off-peak electric demand periods.
§110.5:
Natural gas pool and spa heaters shall not have a continuous burning pilot light.
§I50.0(p):
Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements.
Lighting Measures:
§ 110.9:
All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of § 110.9.
§I50.0(k)IA:
Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with §I50.0(k) in accordance with TABLE
150.0-A or TABLE 150.0-B, as applicable.
§ I50.0(k)I B:
When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply
'
with the applicable provisions of 150.0(k).
The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with
§I50.0(k)IC:
§130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has
been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180
watts of low efficacy lighting er electrical box.
§150.0(k)1D:
Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kliz.
Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no
§I50.0(k)IE:
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with §I30.0(c). Night lights do not need to
be controlled by vacancy sensors.
§ 150.0(k) I F:
Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable
requirements of § 150.0(k).
§I50.0(k)2A:
High efficacy luminaires must be switched separately from low efficacy luminaires.
§I50.0(k)2B:
Exhaust fans shall be switched separately from lighting systems.
§I50.0(k)2C:
Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF.
§150.0(k)2D:
Controls and equipment are installed in accordance with manufacturer's instructions.
§ 150.0(k)2E:
No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with § 150.0(k).
§I50.0(k)2F:
Lighting controls comply with applicable requirements of §110.9.
An Energy Management Control System (EMCS) may be used to comply with dimmer requirements if: it functions as a dimmer
§I50.0(k)2G:
according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other
requirements in §150.0(k)2.
An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of § I50.0(k) if: it
§ 150.0(k)2H:
functions as a vacancy sensor according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements
of § 130.5; and all other requirements in ' 150.0(k)2.
§I50.0(k)2I:
A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the
functionality of a dimmer according to §1 10.9, and complies with all other applicable requirements in §150.0(k)2.
§I50.0(k)3A:
A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only
§I50.0(k)3B:
the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are
considered kitchen lighting if they are not separately switched from kitchen lighting.
§I50.0(k)4:
Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.
§I50.0(k)5:
A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom
shall be high efficacy or controlled by vacancy sensors.
§150.0(k)6:
Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§I50.0(k)7:
Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high
efficacy, or shall be controlled by either dimmers or vacancy sensors.
Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other
nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0
CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing
§ I50.0(k)8:
and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and
allow ballast maintenance and replacement without requiring cutting holes in the ceiling.
For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with §I50.0(k), the ballasts
shall be certified to the Energy Commission to comply with the applicable requirements in § 110.9.
For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the
same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and
§I50.0(k)9A:
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically
reactivates the motion sensor within 6 hours; and
iii. Controlled by one of the following methods:
4
2013 Low -Rise Residential Mandatory Measures Summary
0
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is
programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of
an astronomical time clock in accordance with §110.9; meets the Installation Certification requirements in §130.4; meets the
requirements for an EMCS in §130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor
lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
§ I50.0(k)9B:
following requirements:
i. Shall comply with § I50.0(k)9A; or
ii. Shall comply with the applicabie requirements in §110.9, $130.0, §130.2, §130.4, §140.7 and §141.0.
§I50.0(k)9C:
For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by §I50.0(k)9B or 150.0(k)9D
'110.9, '130.0,
shall comply with the applicable requirements in §130.2, §130.4, §140.7 and §141.0.
§ 150.0(k)9D:
Outdoor lighting for residential parking lots and.residential carports with a total of eight or more vehicles per site shall comply
'130.4,
with the applicable requirements in §110.9, §130.0, $130.2, §140.7 and §141.0.
§I50.0(k)10:
Internally illuminated address signs shall comply with §140.8; or shall consume no more than 5 watts of power as determined
'
according to 130.0(c).
§I50.0(k)11:
Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for
'
nonresidential garages in § 110.9 § 130.0, § 130. 1, § 130.4, 140.6, and § 141.0.
In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of
§ I 50.0(k) I 2A:
the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20
percent of the floor area, permanently installed lighting in that building shall:
§I50.0(k)12B:
i. Comply with the applicable requirements in §110.9, §130.0, §130.1, §140.6 and §141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
ingress and egress.
Solar Ready Buildings:
Single family residences located in subdivisions with ten or more single family residences and where the application for a
§1 10.10(a)1:
tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014,
shall comply with the requirements of § 110.10 b through § 110.1D(e).
§110.10(a)2:
Low-rise multi -family buildings shall comply with the requirements of §1 10.10(b) through §I 10.10(d).
The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a
local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than
80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for
§1 10.10(b)1:
buildings with roof areas greater than 10,000 square feet.
For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less
than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or
on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the
building project and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area.
§ 110.10(b)2:
All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north.
§I 10.10(b)3A:
No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be
located in the solar zone.
Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice
§ 110.10(b)3B:
the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the
horizontal projection of the nearest point of the solar zone, measured in the vertical plane.
§ 110.10(b)4:
For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly
indicated on the construction documents.
The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit
§I 10.10(c):
from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating
system.
§ 110.10(d):
A copy of the construction documents or a comparable document indicating the information from § l 10.10(b) through § 110.10(c)
shall be provided to the occupant.
§ 110.10(e)1:
The main electrical service panel shall have a minimum busbar rating of 200 amps.
The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a
§ 110.10(e)2:
future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or
main circuit location, and permanently marked as "For Future Solar Electric".
0
4
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Date
tephen Smith Residence
7/30/2015
System Name
Floor Area
HVAC
1,660
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
COIL
CFM
Total Room Loads 4,908
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 249
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output perSystem 89,000
40,071
2,371 730
41,744
Total Output Btuh 178,000
0
Output Btuh/s ft 107.2
3,398
2,966
Cooling System
0
0
Output perSystem 35,500
10,827
1,920 249
11,926
Total Output Btuh 71,000
0
4,291
0
Total Output Tons 5.9
3,398
2,966
Total Output Btuh/s ft 42.8
Total Output s ft/Ton 280.6
1 57,695
59,601
Air System
CFM perSystem
1,400
HVAC EQUIPMENT SELECTION
Airflow cfm
2,800
Existing HVAC
40,482
23,230
178,000
Airflow cfm/s ft
1.69
Airflow cfm/Ton
473.2
178,000
Jan 1 AM
Outside Air % 8-9%
Total Adjusted System Output 40,482
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
23,230
Aug 3 PM
Outside Air cfm/s ft 0.15
ote: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF 67 OF
67 OF 127 OF
Q.'
Outside Air
249 cfm Supply Fan
Heating Coil
126 OF
2,800 cfm
ROOM
71 OF Return Fan
71 of
72 OF
2,800 cfm
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 75/66°F 75/66°F 61/60°F
O. c
Outside Air
c
249 cfm
Supply I Fan
Cooling Coil
62 / 61 OF
2,800 cfm
71.6%
r7 7 -J
( ROOM
Return Fan
71 /64°F 71 /64°F
70/I64°F
2,800 cfm
Energ Pro 6.6 by Energ Soft User Number: 6712 RunCode: 2015-07-30708:23:46
/D:
Page 20 of 32
4
if
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Date
'tephen Smith Residence
7/30/2015
System Name
Floor Area
HVAC
221
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING
CFM Sensible
Total Room Loads 482 6,071
Return Vented Lighting 0
Return Air Ducts 0
Return Fan 0
Ventilation F 33 1,482
Supply Fan 0
Supply Air Ducts 0
TOTAL SYSTEM LOAD 7,553
PEAK COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output perSystem 89,000
316 136
8,486
Total Output Btuh 89,000
Output Btuh/s ft 402.7
0
Cooling System
0
Output perSystem 35,500
460 33
1,623
Total Output Btuh 35,500
F 775
0
Total Output Tons 3.0
0
Total Output Btuh/s ft 160.6
Total Output s ft/Ton 74.7
110,109
Air System
CFM perSystem
1,400
HVAC EQUIPMENT SELECTION
Airflow cfm
1,400
Existing HVAC 19,100
11,143
89,000
Airflow cfm/s ft
6.33
Total Adjusted System Output 19,100
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
11,143 89,000
Aug 3 PM Jan 1 AM
Airflow cfm/Ton 473.2
Outside Air % 2.4%
Outside Air cfm/s ft 0.15
ote: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 71 OF
71 OF 131 OF
Outside Air
33 cfm Supply Fan
Heating Coil
131 ,F
1,400 cfm
ROOM
72 OF Return Fan
72 OF
72 OF
O
1,400 cfm
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 71/62°F 71/62°F 58/58°F
Outside Air
c
33 cfm
Supply Fan Cooling Coil
58 / 58 OF
1,400 cfm
63.6%
( ROOM kW
Return
Fan
110 4
70/62°F 70/62°F
0
70/62°F
1,400 cfm 3
Energ Pro 6.6 by Energ Soft User Number: 6712 Run Code: 2015-07-30708:23:46 /D:
Page 21 of 32
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Date
tephen Smith Residence
7/30/2015
System Name
Floor Area
HVAC new
294
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,020
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 44
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output perSystem 89,000
12,500
420 186
11,542
Total Output Btuh 89,000
0
Output Btuh/s ft 302.7
0
0
Cooling System
0
0
Output perSystem 35,500
1,971
583 44
2,159
Total Output Btuh 35,500
0
1,003
0
Total Output Tons 3.0
0
0
Total Output Btuh/s ft 120.7
Total Output s ftlTon 99.4
1 14,471
113,700
Air System
CFM perSystem
1,400
HVAC EQUIPMENT SELECTION
Airflow cfm
1,400
Existing HVAC 19,121
11,287
89,000
Airflow cfm/s ft
4.76
Airflow cfm/Ton
473.2
Outside Air %
3-2%
Total Adjusted System Output 1 19,121
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
11,287 89,000
Aug 3P ml Jan 1 AM
Outside Air cfm/s ft 0,15
ote: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 71 OF
71 OF 130 OF
Outside Air
44 cfm Supply Fan
Heating Coil
130 OF
1,400 cfm
ROOM
72 OF Return Fan
72 of
72 OF
1,400 cfm
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 71/63°F 71/63°F 58/58°F
;0
Outside Air Arc
44 cfm
Supply Fan Cooling Coil
58 / 58 OF
1,400 cfm
64.5%
I ROOM i�►
Return Fan
-
70/62°F 70/62°F T
;�D
70/62°F
1,400 cfm
EnergyPro 6.6 by EnergySoft User Number: 6712 RunCode: 2015-07-30708:23:46 /D:
Page 22 of 32
•
ROOM HEATING PEAK LOADS
Project Name
Stephen Smith Residence
Date
7/30/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name altered residence
Floor Area 1,660.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
c
=
_
=
=
=
=
a
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
Defaut 1978 to present
1,623.6
0.0790
46
5,900
Skylight
36.4
0.5500
46
921
R-13 Wall
4,272.5
0.0901
46
17,700
Wood Door
48.0
0.5000
46
1,104
Existing Window
120.0
0.7100
46
3,919
LowE METAL .46.24
145.5
0.4600
46
3,079
Slab -On -Grade
perim = 175.0
0.7300
46
5,877
'R-13 Wall
511.0
0.0901
0
0
Items shown with an asterisk (') denote conduction
Infiltration: 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,660 X
Area
another room
9.00 X 0.266
Height ACH
Page Total
/60] X
AT
38,499
_ 3,244
TOTAL HOURLY HEAT LOSS FOR ROOM 41,744
EnergyPro 6.6 by EnergySoft User Number: 6712 RunCode: 2015-07-30708:23:46 /D: Page 26 of 32
•
L-,
ROOM HEATING PEAK LOADS
Project Name
Stephen Smith Residence
Date
7/30/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name new addition
Floor Area 221.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
OT *F
=
=
=
=
c
=
=
=
=
=
=
=
=
-
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
221.0
0.0260
46
264
R-21 Wall (W.21.2x6.16)
1,040.3
0.0690
46
3,302
LowE METAL .46.24
113.7
0.4600
46
2,406
Slab -On -Grade
perim = 62.0
0.7300
46
2,082
`R-13 Wall
212.0
0.0901
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 221 X
Area
another room
9.00 X 0.266
Height ACH
Page Total
/60] X
AT
8,054
_ 432
TOTAL HOURLY HEAT LOSS FOR ROOM 8,486
EnergyPro 6.6 by EnergySoft User Number: 6712 RunCode: 2015-07-30708:23:46 /D: Page 27 of 32
C
•
ROOM HEATING PEAK LOADS
Project Name
Stephen Smith Residence
Date
7/30/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name exist casita
Floor Area 294.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT 'F
=
=
_
=
_
_
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
Default prior To 1978
285.2
0.0790
46
1,036
Skylight
8.8
0.5500
46
223
R-13 Wall
1,066.0
0.0901
46
4,416
Existing Window
88.0
0.7100
46
2,874
Slab -On -Grade
perim = 72.0
0.7300
46
2,418
'R-13 Wall
294.0
0.0901
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.0o X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 294 X
Area
another room
9.0o X o.2ss
Height ACH
Page Total
/60] X
AT
1 10,967
= 575
TOTAL HOURLY HEAT LOSS FOR ROOM 11,542
EnergyPro 6.6 by EnergySoft User Number: 6712 RunCode: 2015-07-30708:23:46 /D: Page 28 of 32
ME
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Stephen Smith Residence 7/30/2015
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
Indoor Dry Bu
Opaque Surfaces
Default 1978 to present
R-13 Wall
Wood Door
R-13 Wall
R-13 Wall
R-13 Wall
R-13 Wall
'R-13 Wall
altered residence Outdoor Dry Bulb Temperature
1,660.0 ft2 Outdoor Wet Bulb Temperature
70 °F Outdoor Dailv Ranae:
Orientation
(tM
(E)
(E)
(S)
(tM
(NtM
(N)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,623.6
0.0790
56.0
604.0
0.0901
31.2
48.0
0.5000
31.2
1,263.5
0.0901
28.2
784.0
0.0901
32.1
235.0
0.0901
30.2
1,386.0
0.0901
29.0
511.0
0.0901
0.0
15.0
64.8
0.0
36.5
15.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fanactratinn
Skylight ex
Skylight ex
Skylight ex
Skylight ex
Skylight ex
ex 3x5
ex 3x5
ex 5x5
ex 5x5
Oriantatinn
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
0.0
32.1
1.2
106.5
0.0
32.1
8.8
106.5
0.0
32.1
8.8
106.5
0.0
32.1
8.8
106.5
0.0
32.1
8.8
106.5
0.0
36.5
15.0
64.8
0.0
36.5
15.0
64.8
0.0
36.5
25.0
42.7
0.01
36.5
25.0
42.7
Page Total
112 OF
78 OF
34 OF
Btu/hr
7,183
1,698
749
3,211
2,267
640
3,620
0
19,369
btumr
128
937
937
937
937
972
972
1,067
1,067
7.95
Internal Gain Btulhr
Occupants 5.0 Occupants X 245 Btuh/occ.
Equipment 1,660 Floor Area X 0.50 w/sgft 2,!
Infiltration: 1.064 X 0.94 X 68.47 X 42 =
Air Sensible CFM ELA AT
TOTAL'HOURLY SENSIBLE HEAT GAIN FOR ROOM 40,071
Latent Gain Btu/hr
Occupants -7�15.0 Occupants X 155 Btuh/occ. = 772
Infiltration: 4,771 X 0.94 X 68.47 X 0.00523 = 1,599
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
EnerovPro 6.6 by EneravSoft User Number: 6712 RunCode: 2015-07-30708:23:46 ID: Paae 29 of 32
No
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Stephen Smith Residence
ROOM INFORMATION DESIGN CONDITIONS
Room Name altered residence Outdoor Dry Bulb Temperature
Floor Area 1, 660.0 ftz Outdoor Wet Bulb Temperature
Indoor Dry Bulb Temperature 70 OF Outdoor Daily Range:
ue Surfaces Orientation
7/30/2015
Area U -Factor CLTD'
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
Page Total
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestration
ex 3x5
ex 3x5
ex 7.5x5
alt 5x6.5
alt 5x8
alt 5x8
alt 3x6
alt 2.5x6
Orientation
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
0.0
36.5
15.0
42.7
0.0
36.5
15.0
42.7
0.0
36.5
10.0
42.7
0.0
18.1
32.5
20.6
0.0
18.1
40.0
31.3
0.0
18.1
40.0
31.3
0.0
18.1
18.0
31.3
0.0
18.1
15.0
25.8
I=
Page Total
112 OF
78 OF
34 OF
Btu/hr
0
Btu/hr
640
640
427
669
1,252
1,252
563
387
5,
Internal Gain Btulhr
Occupants 5 0 Occupants X 245 Btuh/occ.
Equipment 1,660 Floor Area X 0.50 w/sgft 2,!
Infiltration: 1.064 X 0.94 X 68.47 X 42 = C
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 40,071
Latent Gain Btu/hr
Occupants 5 0 Occupants X 155 Btuh/occ. = 772
Infiltration: 4,771 X 0.94 X 68.47 X 0.00523 = 1,599
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name77/30/2015
ate
Stephen Smith Residence
ROOM INFORMATION
DESIGN CONDITIONS
Room Name new addition
Outdoor Dry Bulb Temperature
112 OF
Floor Area 221.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD�
Btu/hr
R-38 Roof Attic (W) 221.0 X 0.0260
X
56.0 =
322
R-21 Wall (W.21.2x6.16) (E) 200.0 X 0.0690
X
31.2 =
431
R-21 Wall (W.21.2x6.16) (S) 153.1 X 0.0690
X
28.2 =
298
R-21 Wall (W.21.2x6.16) (S) 123.2 X 0.0690
X
26.0 =
221
R-21 Wall (W.21.2x6.16) (tM 212.0 X 0.0690
X
32.1 =
470
R-21 Wall (W.21.2x6.16) (N) 352.0 X 0.0690
X
29.0 =
704
'R-13 Wall 212.0 X 0.0901
X
0.0 =
0
XX
=
X
X
=
Page Total
2,446
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
new 3x6.7 (S) 0.01 X 18.1 +
20.1
X 20.6 =
414
new 067 (S) 0.0 X 18.1 +
26.8
X 20.6 =
552
new 06.7 (S) 0.0 X 18.1 +
26.8
X 18.2 =
487
new 8x5 (W) 0.0 X 18.1 +
40.0
X 31.3 =
1,252
X +
X =
X +
X =
X +
X =
X +
X =
X + I
X =
Page Total
2,70
Internal Gain
Btu/hr
Occupants 0 7 Occupants X 245
Btuh/occ.=L
162
Equipment 221 Floor Area X 0.50
w/sgft
=
377
Infiltration: 1.064 X 0.94 X 9.12 X 42 =
381
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
6,071
Latent Gain
Btu/hr
Occupants 0 7 Occupants X 155
Btuh/occ.
=
103
Infiltration: 4,771 X 0.94 X 9.12 X 0.00523 =
213
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
103
EnemyFro 6.6 by EnerqySoft User Number: 6712 RunCode: 2015-07-30T08:23:46 /D:
Page 31 of 32
0
I- 7
C
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Stephen Smith Residence
1 7/30/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
exist casita
Outdoor Dry Bulb Temperature
112 OF
Floor Area
294.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF,
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
Default prior To 1978
(W) 285.2 X 0.0790
X
56.0 =
1,262
R-13 Wall
(E) 185.0 X 0.0901
X
31.2 =
520
R-13 Wall
(S) 200.0 X 0.0901
X
28.2 =
508
R-13 Wall
(W) 227.0 X 0.0901
X
32.1 =
656
R-13 Wall
(tM 102.0 X 0.0901
X
33.0 =
303
R-13 Wall
(N) 352.0 X 0.0901
X
29.0 =
919
'R-13 Wall
294.0 X 0.0901
X
0.0 =
0
X
X
=
X I J
X I=
Page Total 1
4,169
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
Skylight ex
(tom 0.0 X 32.1 +
8.8
X 106.5 =
937
ex 3x5
(E) 0.0 X 36.5 +
15.0
X 64.8 =
972
ex 5x5
(W) 0.0 X 36.5 +
25.0
X 69.4 =
1,736
ex 6x8
(W) 0.0 X 36.5 +
48.0
X 72.1 =
3,460
X +
X =
X +
X =
X +
X =
X +
X =
X + I
X =
Page Total
7,106
Internal Gain
Btu/hr
Occupants
0 9 Occupants X 245
Btuh/occ.
=
216
Equipment
294 Floor Area X 0.50
w/sgft
=
502
Infiltration: 1.064
X 0.94 X 12.13 X 42 =
507
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
12,500
Latent Gain
Btu/hr
Occupants
0 9 Occupants X 155
Btuh/occ.
=
137
Infiltration: 4,771
X 0.94 X 12.13 X 0.00523 =
283
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
.137
Ene Pro 6.6 by EnerqySoft
User Number: 6712 Run Code: 2015-07-30708:23:46 ID:
Pace 32 of 12
CERTIF* OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE COD
Project ame: Remodeled Residence C Cation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CF3WF-01
Pa of 11
GENERAL INFORMATION
01 Building Complies with Computer Performance
01
Project Name Remodeled Residence
03 This building incorporates one or. more Special Features shown below
04
02
Calculation Description Title 24 Analysis
06
07
03
Project Location 49-981 Calle Estrella
Standard Design
04
City La Quinta
05
Standards Version Compliance 2015
06
Zip Code 92253
07
Compliance Manager Version BEMCmpMgr 2013-4 (744)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.6
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 20
12
Project Scope Addition and/or Alteration
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (ft) 2175
15
Number of Zones 3
16
Slab Area (ft2) 2175
17
Number of Stories 1
18
Addition Cond. Floor Area 221
19
Natural Gas Available Yes
20
Addition Slab Area (ft2) 221
21
Glazing Percentage (%) 23.6%
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
ENERGY USE SUMMARY
02 This building incorporates features that require field testing �and/or verification by a certified;HERS rater under the supervision of a CECapproved HERS provider.
i.. 1A _. -4L[ ti s, Vz i. u u IX rr w ae t�
03 This building incorporates one or. more Special Features shown below
04
t N i` t Is %-'r V il
t-./ L- i
Registration Number:
CA Building Energy Ef
n M
-1m:�c
ZOm Z
1513918-000000-�
Registration Date/Time:
I Compliance Report Version - CF1R-07082015-744
HERS Provider: CaICERTS inc.
Report Generated at: 2015-07-30 08:23:36
ENERGY USE SUMMARY
04
05
06
07
08
Energy Use ( D -yr
Standard Design
Proposed Design
Compliance Margin
Percent Improvement
Spac$ Hi4ting
00 C)
12.70
12.59
0.11
0.9%
Spac' ooling -n
—
332.88
328.20
4.68
1.4%
IAO V ilation
0.00
0.00
0.00
0.0%
Wate eating
10.97
10.79
0.18
1.6%
Photov It dc Offset
go
--
0.00
0.00
--
Complian qergy
D
356.55
351.58
4.97
_1.4%
Registration Number:
CA Building Energy Ef
n M
-1m:�c
ZOm Z
1513918-000000-�
Registration Date/Time:
I Compliance Report Version - CF1R-07082015-744
HERS Provider: CaICERTS inc.
Report Generated at: 2015-07-30 08:23:36
CERTIFY OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD CFF -01
Project me: Remodeled Residence C ulation Date/Time: 08:22, Thu, Jul 30, 2015 PaIjin of 11
Calculation Description: Title 24 Analysis Input File Name: Smith-Pitchford-15.xml
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Cool roof
• Cathedral Ceiling
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
• — None —
Cooling System Verifications:
• -- None —
HVAC Distribution System Verifications:
• Duct Sealing
Domestic Hot Water System Verifications:
• —None —
ENERGY DESIGN RATING
This is the sum of the annual TDV energy consumption for energy use components included in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and components not regulated`by'Title 24, Part 6 (such as -domestic consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system. A It '� 11 � � ( �;,
02
Reference, -Energy Use
Energy Design Rating
Margin Percent Improvement
Total Energy (kTDV/f2-yr)*
0,1 2.84 f
397.87
4.97 1.2%
includes calculated Appliances and Miscellaneous Energy Use (AMEU)
BUILDING - FEATURES INFORMATION
01
02
03
04
05
06
07
Project Name
Conditioned Floor Area (ft2)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Remodeled Residence
2175
1
3
3
3
1
Registration Number: 215-AO1513918-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:36
CERTIF* OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE POD
Project ame: Remodeled Residence C lation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CFF -01
Pa of 11
ZONE INFORMATION
01
02
03
04
05
06
07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1
Water Heating System 2
residence
Conditioned
HVAC1
1660
9
DHW Sys.1
addition
Conditioned
HVAC2
221
9
DHW Sys 1
casita
Conditioned
HVAC new3
294
9
DHW Sys 1
OPAQUE SURFACES
01
02
03
04
05
06
07
08
09
10
Name
Zone
Construction
Azimuth
Orientation Gross Area (ft)
Window & Door
Area (ft)
Tilt
(deg)
Status
Verified
Existing
Condition
70d Wall ex
residence
R-13 Wall
70
50
682
78
90
Existing
No
160d Wall ex
residence
R-13 Wall
160
140
1386
122.5
90
Existing
No
250d Wall ex
residence
R-13 Wall
250
230
882
98
90
Existing
No
NW Wall ex
residence
R-13 Wall
315
295
250
15
90
Existing
No
340d Wall ex
residence
`"` R-13 Wall' I L340 -, —X320
_ 1386
90
Existing
No
Roof
residence`
IkDefaul:c1978 6a6resent
"—
0 t[1623.6(
-'"""
Existing
No
70d Wall
addition A
'R-`21'Wall'(W.2_1.2z6r16)— '° «70-
"-50 At
"� " 260 "`
90
New
N/A
160d Wall
addition N
R'21 W611 (W.-2f.2x6 16)
t' 1601
It ,►1 -140 t
L..,4 200 M
46.9
90
New
N/A
S Wall
addition
R-21 Wall (W21.2x6.16)
180
160
150
26.8
90
New
N/A
250d Wall
addition
R-21 Wall (W21.2x6.16)
250
230
252
40
90
New
N/A
340d Wall
addition
R-21 Wall (W.21.2x6.16)
340
320
352
90
New
N/A
Roof 4
addition
R-38 Roof Attic
221
New
N/A
70d Wall ex 2
casita
R-13 Wall
70
50
200
15
90
Existing
No
160d Wall ex 2
casita
R-13 Wall
160
140
200
90
Existing
No
250d Wall ex 2
casita
R-13 Wall
250
230
252
25
90
Existing
No
W Wall ex
casita
R-13 Wall
270
250
150
48
90
Existing
No
340d Wall ex 2
casita
R-13 Wall
340
320
352
90
Existing
No
Roof 5
casita
Default prior To 1978
285.2
Existing
No
Registration Number: 215-A0151391B-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:36
CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCEOD
Project Name: Remodeled Residence Ca culation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis Input File Name: Smith-Pitchford-15.xml
CFF -01
Pa 4of11
OPAQUE SURFACES — Cathedral Ceilings
01
02
03
04
05
06
06
07
08
09
10
11
1 12
13
Roof Reflectance
Roof Emittance
Radiant
Barrier
Cool Roof
Statu
s
Verified Existing
Condition
Attic residence
Attic Roofresidence
Ventilated
Roof
0.1
Framin
No
Verified
Existi
ng
No
Attic addition
Orientatio
Area
Skylight
Roof Rise
Roof
Roof
Reflectan
Roof
g
Statu
Existing
Name
Zone
Type
n
(ft2)
Area (ft2)
(x in 12)
Pitch
Tilt(deg)
ce
Emittance
Factor
s
Condifion
Roof
residence
Defaul: 1978 to
specify -
36.5
1.2
3
0.25
14.04
0.1
0.85
0.1
Existin
No
presentl
g
Roof 2
casita
Default prior To
_ specify -
8.9
8.8
3
0.25
14.04
0.1
0.85
0.1
Existin
No
19781
g
ATTIC
01
02
03
04
05
06
07
08
09
10
Name
Construction
Type
Roof Rise
Roof Reflectance
Roof Emittance
Radiant
Barrier
Cool Roof
Statu
s
Verified Existing
Condition
Attic residence
Attic Roofresidence
Ventilated
3
0.1
0.85
No
No
Existi
ng
No
Attic addition
Attic Roofaddition
Ventilated
3
0.3
0.75
No
Yes
New
No
Attic casita
Attic Roofcasita
Ventilated/~
" -370:,1
0.85
No
No
Exi ti
No
,sx iso
HERS P'RC3VID1EER
Registration Number: 215-AO151391B-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:36
CERTIFI0 OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE h&OD
Project Name: Remodeled Residence Ca lation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xmi
CF1F-01
P 3 of 11
WINDOWS
01
02
03
04 05
06
07
08
09
10
11
Name
Surface (Orientation -Azimuth)
Width(ft)
Multiplie
Height (ft) r
Area (ft)
U -factor
SHGC
Exterior Shading
Status
Verified
Existing
Condition
ex 3x5
70d Wall ex (- specify -70)
--
-- 1
15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 3x5 2
70d Wall ex ( specify -70)
--
-- 1
15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 5x5
160d Wall ex (- specify -160)
-
-- 1
25.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 5x5 2
160d Wall ex (- specify -160)
--
-- 1
25.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 3x5 3
160d Wall ex (- specify -160)
--
-- 1
15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 3x5 4
160d Wall ex (- specify -160)
--
-- 1
15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 7.5x5
160d Wall ex (- specify -160)
--
-- 1
10.0
0.71
0.60
Insect Screen (default)
Existing
No
alt 5x6.5
160d Wall ex (- specify -160)
--
-- 1
32.5
0.46
0.24
Insect Screen (default)
Altered
N/A
alt 5x8
250d Wall ex (- specify -250)
--
-- 1
40.0
0.46
0.24
Insect Screen (default)
Altered
N/A
alt 5x8 2
250d Wall ex (- specify -250)
--
-- 1
40.0
0.46
0.24
Insect Screen (default)
Altered
N/A
alt 3x6
250d Wall ex (- specify -250)
--
-- 1
18.0
0.46
0.24
Insect Screen (default)
Altered
N/A
all 2.5x6
NW Wall ex (-specify -315)'
-
� - 1_JF
15.0
0.46
0244
Insect Screen (default)
Altered
N/A
Skylight ex
Roof (- specify -270)
- J if 'W 1 0
12
0.55
'0.55
None
Existing
No
Skylight ex 2
Roof (- specify - 70) '"
""" = `_
_ -- _ " 1 `
-8j8 IV
`0.55 _
' 0:55'
None
Existing
No
Skylight ex 3
Roof (- specify a270) f-1
C-'"iE
-- ri 1
`8:8 1
10:55 C
0'55
None
Existing
No
Skylight ex 4
Roof (- specify --270)
--
-- 1
8.8
0.55
0.55
None
Existing
No
Skylight ex 5
Roof (- specify --270)
--
-- 1
8.8
0.55
0.55
None
Existing
No
new 3x6.7
160d Wall (- specify -160)
--
-- 1
20.1
0.46
0.24
Insect Screen (default)
New
N/A
new 4x67
160d Wall (- specify -160)
--
-- 1
26.8
0.46
0.24
Insect Screen (default)
New
N/A
new 4x6.7
S Wall (- specify -180)
--
-- 1
26.8
0.46
0.24
Insect Screen (default)
New
N/A
new 8x5
250d Wall (- specify -250)
--
-- 1
40.0
0.46
0.24
Insect Screen (default)
New
N/A
ex 3x5 5
70d Wall ex 2 (- specify --70)
--
-- 1
15.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 5x5 3
250d Wall ex 2 (- specify --250)
--
- - 1
25.0
0.71
0.60
Insect Screen (default)
Existing
No
ex 6x8
W Wall ex (- specify -270)
-
-- 1
48.0
0.71
0.60
Insect Screen (default)
Existing
No
Skylight ex 6
Roof 2 (- specify -270)
--
-- 1
8.8
0.55
0.55
None
Existing
No
Registration Number: 215-A0151391B-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:36
CERTIF10 OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE POOD
Project Name: Remodeled Residence C ulation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis Input File Name: Smith-Pitchford-15.xmi
CFF -01
Pa of 11
DOORS
01 02 03 04 05 06
Name Side of Building Area (ft2) U -factor Status Verified Existing Condition
Door 70d Wall ex 48.0 0.50 Existing No
eInc
�.
,;.two
H E RS PROVIDER
Registration Number: 215-A0151391B-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:36
CERTIF OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE FOOD
Project Name: Remodeled Residence C FOOD
Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CFF -01
PaIJ97 of 11
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
Total Cavity
Winter Design
Construction Name
Surface Type
Construction Type
Framing
R -value
U -value
Assembly Layers
• Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofresidence
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-9.1 /2x4
Defaul: 1978 to present
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 11
0.083
Over Floor Joists: R-1.9 insul.
• Inside Finish: Gypsum Board
• Cavity/Frame: R-11 /2x4
• Roof Deck: Wood Siding/sheathing/decking
Defaul: 1978 to presentl
Cathedral Ceilings
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 11
0.088
Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
• Cavity/Frame: R -13/2x4
• Exterior Finish: Wood
R-13 Wall
Exterior Walls
Wood Framed Wall
2x4 @ 16 in. O.C.
R 13
0.095
Siding/sheathing/decking
• Cavity/Frame: no insul. /2x4 Top Chrd
r��
294 Top'Chord of.Roof,Truss.@ 24#;
Roof Deck. Wood Siding/sheathing/decking
Attic Roofaddition
Attic Roofs
Wood Framed Ceiling-
11 �� # in. O.C.W�r L
,1 none r• r0.644
Roofing: Light Roof (Asphalt Shingle)
<
1 /
€1:
Inside Finish: Gypsum Board
Ceilings (below
1�.1�
Cavity/Frame: R-9.1 /2x4
R-38 Roof Attic
attic)
Wood Framed Ceiliri4>
42x4 @ 16 in. O.C. n
d ',R 38'-1
x:0.025
Over Floor Joists: R-28.9 insul.
• Inside Finish: Gypsum Board
• Cavity / Frame: R-21 / 2x6
• Exterior Finish: Wood
R-21 Wall (W.21.2x6.16)
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.066
Siding/sheathing/decking
• Cavity/ Frame: no insul. / 2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofcasita
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing. Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-9.1 /2x4
Default prior To 1978
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 11
0.083
Over Floor Joists: R-1.9 insul.
• Inside Finish: Gypsum Board
• Cavity / Frame: R-11 / 2x4
• Roof Deck: Wood Siding/sheathing/decking
Default prior To 19781
Cathedral Ceilings
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 11
0.088
Roofing: Light Roof (Asphalt Shingle)
Registration Number: 215-A0151391B-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - MR -07082015-744 Report Generated at: 2015-07-30 08:23:36
CERTIFIO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Remodeled Residence ation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis Input File Name: Smith-Pitchford-15.xml
CF&F-01
PaW8 of 11
SLAB FLOORS
01
02
03
04
05
06
07
08
09
Name
Zone
Area (ft2)
Perimeter
(ft)
Edge Insul. R -value
Carpeted
Fraction
Heated
Status
Verified
Existing
Condition
Covered Slab
residence
1660
175
None
0.8
No
Existing
No
Covered Slab 2
addition
221
62
None
0.8
No
New
No
Covered Slab 3
casita
294
72
None
0.8
No
Existing
No
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa
Not Required Not Required Not Required —
WATER HEATING SYSTEMS
01
02
03
04
05
06
07
08
Name
System Type
(rq'istrib� utionTypex (
i ¢
Ill !w.e Heater f
Number of
t( Heaters
Solar
Fraction
M
Status
Verified Existing
Condition
DHW Sys 1
DHW
PipeInsulation; All Lines"' `
" aDHW Heatef 1
0.61 EF
Annual
Existing
No
"N 8"-! F-- 11K "+. iMr 011t t P 1r E f ) t - M
WATER HEATERS
01
02
03
04
05
06
07
08
Name
Heater Element Type
Tank Type
Tank Volume
(gal)
Energy Factor or
Efficiency
Input Rating
Tank Exterior
Insulation R -value
Standby Loss
(Fraction)
DHW Heater 1
Natural Gas
Small Storage
50
0.61 EF
40000-Btu/hr
0
0
WATER HEATING - HERS VERIFICATION
01
02
03
04
05
06
07
Name
Pipe Insulation
Parallel Piping
Compact Distribution
Point -of Use
Recirculation with
Manual Control
Recirculation with
Sensor Control
DHW Sys 1
n/a
n/a
n/a
n/a
n/a
n/a
Registration Number: 215-A01513918-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:36
CERTIFI* OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE h OD
Project ame: Remodeled Residence C ulation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis Input File Name: Smith-Pitchford-15.xm1
CFF -01
Pa of 11
SPACE CONDITIONING SYSTEMS
01
02
03
04
05
06
07
08
09
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating System
Cooling System
80 AFUE
Heating Component 3
CntrlFurnace; `Fuel-fred, centfal furnace
80 AFUE
HERS Verification
Cooling Component 1
SplitAirCond - Split air conditioning
10
12
Distribution
Fan
Floor Area
Verified Existing
Name
System Type
Name Ducted
Name Ducted
System
System
Served
Status
Condition
HVAC1
Other Heating and
Heating
Yes
Cooling
Yes
Air Distribution
HVAC Fan
1660
Existing
No
DuctlessSplitAirCond - Ductless
Cooling System
Component 1
No
Component 1
N/A
System 1
1
HVAC2
Other Heating and
Heating
Yes
Cooling
N0
Air Distribution
HVAC Fan
221
Existing
No
Cooling System
Component 2
Component 2
System 2
2
HVAC new3
Other Heating and
Heating
Yes
Cooling
N0
Air Distribution
HVAC Fan
294
Existing
No
Cooling System
Component 3
Component 3
System 3
3
HVAC - HEATING SYSTEMS
01
02 ""
01
02
03
Name
Type
Efficiency
Heating Component 1
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 2
_ CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 3
CntrlFurnace; `Fuel-fred, centfal furnace
80 AFUE
9t I I--�I #; i; If 1rNN 11 -1 11 11 tE it
HVAC - COOLING SYSTEMS `. 4 t: 'z=" I rt U U U c� ' u v u 1;
01
02 ""
,� ~ 03'�r {� �, 04 V,?
OS
06
07
Efficiency
Multi -speed
Name
System Type
EER SEER
Zonally Controlled
Compressor
HERS Verification
Cooling Component 1
SplitAirCond - Split air conditioning
10
12
No
No
N/A
system
Cooling Component 2
DuctlessSplitAirCond - Ductless
10
12
No
No
N/A
mini -split and multi -split heat A/C
Cooling Component 3
DuctlessSplitAirCond - Ductless
10
12
No
No
N/A
mini -split and multi -split heat A/C
Registration Number: 215•A0151391B-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:36
CERTIFI* OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE P#OD
Project Name: Remodeled Residence Ca ulation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis Input File Name: Smith-Pitchford-15.xmi
CF1.*F-01
Pag of 11
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
08
09
10
Name
Duct Leakage
Verification
Duct Leakage
Target (%)
Insulation
Supply Duct
Return Duct
N/A
I—
Verified Existing
HERS
Name
Type
Duct Leakage
R -value
Location
Location
Bypass Duct
Status
Condition
Verification
Air Distribution
Ducts located in attic
Existing (not
4.2
Attic
Attic
None
Existing
No
N/A
System 1
specified)
Air Distribution
Ducts located in attic
Existing (not
4.2
Attic
Attic
None
Existing
No
N/A
System 2
specified)
Air Distribution
Air Distribution
System 3
Ducts located in attic
Sealed and tested
4.2
Attic
Attic
None
New
No
System
3 -hers -dist
HVAC DISTRIBUTION - HERS VERIFICATION
�; } o
01
Q r03 +� - �; 04 05
Name IAQ CFM
01
02
03
04
05
06
Name
Duct Leakage
Verification
Duct Leakage
Target (%)
Verified Duct Location
Verified Duct Design
Return Supply
Air Distribution System 1 -hers -dist
N/A
I—
--
I— --
Air Distribution System 2 -hers -dist
N/A
p ="� r -r-
r = �^� n --
— --
10 . Ill ii ii 3 ice`_/ 11 saw 1! it -)% f% -
IAQ (Indoor Air Quality) FANS �� `"tij
�; } o
01
Q r03 +� - �; 04 05
Name IAQ CFM
IAQ Fan Type IAQ Recovery Effectiveness(%) HERS Verification
SFam IAQVentRpt 0
Default 0 Not Required
COOLING VENTILATION
01
02
03
04
Name
Cooling Vent CFM
Cooling Vent Watts/CFM
Number of Fans
WH Fan 1
61
0.52459
1
WH Fan 2
61
0.52459
1
WH Fan 3
61
0.52459
1
Registration Number: 215-A0151391B-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-07082015-744 Report Generated at: 2015-07-30 08:23:36
CERTIFI OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OD
Project Name: Remodeled Residence Ca ulation Date/Time: 08:22, Thu, Jul 30, 2015
Calculation Description: Title 24 Analysis
Input File Name: Smith-Pitchford-15.xml
CFIWF-01
Pagel of 11
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
T"`v''Z0Z2:-
Tim Scott
Company:
Signature Date:
Scott Design and Title 24, Inc.
Address:
CEA/HERS Certification Identification (If applicable):
77085 Michigan Drive
City/State/Zip:
Phone:
Palm Desert, CA 92211
(760) 200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to -the enforcement agency, for approval with this.building permit application.
Responsible Designer Name: ��
�:
L
Responsible Designer Signature:
Turv.�ce'i
Tim Scott1;.
,
�:•-.��--
t
" r� n# tli i
Company: H E S P
Dtte(Signed-
Scott Design and Title 24, Inc.
Address:
License:
77085 Michigan Drive
na
City/State/Zip:
Phone:
Palm Desert, CA 92211
(760) 200-4780
Digitally signed by Ca10ERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy of the
information.
Registration Number: 215-A0151391B-000000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-07082015-744 Report Generated at: 2015-07-30 08:23:36