13-0395 (CONR)P.O. BOX 1504
78-495 CALLE TAMPICO 44
LA QUINTA, CALIFORNIA 92253 BUILDING & SAFETY DEPARTMENT
BUILDING PERMIT
Application Number: 13-00000395
Property Address: 53962 GRAY AVE
APN: 767-200-998-S -330762-
Application description: NEW COMML - OTHER NON-RESIDENTIAL
Property Zoning: LOW DENSITY RESIDENTIAL
Application valuation: 200000
Applicant: Architect or Engineer:
/V_
LICENSED
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that ' I am ensed under provisions of Chapter 9 (commencing with
Section 7000) of Division 3 of the Business an ofessi Is Code, and my License is in full force and effect.
License class: B Li se No.: 915336
tD3e: !�/ /7/3 Contactor
NER-BUILDER DECLARATION
I hereby affirm under penalty of perjury that Ixempt from the Contractor's State License Law for the
following reason (Sec. 7031.5, Business and essions Code: Any city or county that requires a permit to
construct, alter, improve, demolish, or repair an structure, prior to its issuance, also requires the applicant for the
permit to file a signed statement that he or she is licensed pursuant to the provisions of the Contractor's State
License Law (Chapter 9 (commencing with Section 7000) of Division 3 of the Business and Professions Code) or
that he or she is exempt therefrom and the basis for the alleged exemption. Any violation of Section 7031.5 by
any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars IS500)•:
(_ 1 I, as owner of the property, or my employees with wages as their sole compensation, will do the work, and
the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The
Contractors' State License Law does not apply to an owner of property who builds or improves thereon,
and who does the work himself or herself through his or her own employees, provided that the
improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner -builder will have the burden of proving that he or she did not build or
improve for the purpose of sale.).
(_ 1 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec.
7044, Business and Professions Code: The Contractors' State License Law does not apply to an owner of
property who builds or improves thereon, and who contracts for the projects with a contractor(s) licensed
pursuant to the Contractors' State License Law.).
(_ 1 I am exempt under Sec. , B.&P.C. for this reason
Date: Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for the performance of the
work for which this permit is issued (Sec. 3097, Civ. C.)•
Lender's Name: _
Lender's Address:
LQPERMIT
Owner:
EAST OF MADISON LLC
PO BOX 1482
LA QUINTA, CA 92247
Contractor:
DBCA INC
P.O. BOX 1482
LA QUINTA, CA 92247
(760)393-5271
Lic. No.: 915336
VOICE (760) 777-7012
FAX (760) 777-7011
INSPECTIONS (760) 777-7153
Date: 12/17/13
tDEtC71 2013
D
CITY OF LA QU NTNT
F1NANCF:!]F_tpT.
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
_ I have and will maintain a certificate of consent to self -insure for workers' compensation, as provided
for by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued.
1 have and will maintain workers' compensation insurance, as required by Section 3700 of the Labor
Code, for the performance of the work for which this permit is issued. My workers' compensation
insurance carrier and policy number are:
Carrier TRAVELERS Policy Number Y7UB282D7797-12
I certify that, in the performance of the work for which this permit is issued, I shall not employ any
person in any manner. so as to bWsubt to the workers' compensation laws of California,
and agree that, if I should becom t workers' compensation provisions of Section
vn� 3700 of the or Code, I shall fmply 'th those provisions.
D (G ��� A plicant:
WARNING: FAILURE TO SECURE WORKERS' C01 I NSATION COVERAGE IS UNLAWFUL, AND SHALL
SUBJECT AN EMPLOYER TO CRIMINAL PENALTI S NO CIVIL FINES UP TO ONE HUNDRED THOUSAND
DOLLARS 15100,0001. IN ADDITION TO THE CO OF COMPENSATION, DAMAGES AS PROVIDED FOR IN
SECTION 3706 OF THE LABOR CODE, INTERES NO
ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT Application is hereby made to the Director of Building and Safety for a permit subject to the
conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose request and for
whose benefit work is performed under or pursuant to any permit issued as a result of this application,
the owner, and the applicant, each agrees to, and shall defend, indemnify and hold harmless the City
of La Quinta, its officers, agents and employees for any act or omission related to the work being
performed under or following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is not commenced
within 180 days from date of issuance of such permit, or cessation of work for 180 days will subject
permit to cancellation.
I certify that I have readthis application and state that the abo i forma correct. I agree to comply with all
city and county ordinances and state laws relating to building c ructio , and by authorize representatives
of this Yung y 'ol �er upon t above-mentioned property for i cti purposes.
Date: I Signature (Applicant or Agent):
Application Number . . . . . 13-00000395
------ Structure Information 114 SQ. FT. GUARD HOUSE -----
Other struct info . . . . . CODE EDITION 2010
FIRE SPRINKLERS 13D
MIXED-USE OCCUPANCY B
OCCUPANT LOAD 1.00
PATIO SQ FTG 63.00
1ST FLOOR SQUARE FOOTAGE 114.00
----------------------------------------------------------------------------
Permit . . . BUILDING PERMIT
Additional desc .
Permit Fee . . . . 989.50
Issue Date . . . .
Expiration Date . . 6/15/14
Plan Check Fee . . 643.18
Valuation . . . . 200000
Qty Unit Charge Per Extension
BASE FEE 639.50
100.00 3.5000 THOU BLDG 100,001-500,000 350.00
----------------------------------------------------------------------------
Permit ELEC-NEW COMMERCIAL
Additional desc .
Permit Fee . . 17.28 Plan Check Fee 4.32
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 6/15/14
Qty Unit Charge Per Extension
BASE FEE 15.00
114.00 .0200 ELEC GARAGE OR NON-RESIDENTIAL 2.28
----------------------------------------------------------------------------
Permit GRADING PERMIT
Additional desc .
Permit Fee 33.00 Plan Check Fee .00
Issue Date . . . . Valuation . . . . 0
Expiration Date 6/15/14
Qty Unit Charge Per Extension
BASE FEE 22.50
1.00 10.5000 HND GRADING 101-1000 10.50
-----------------------------------------------------------------=----------
Permit
Additional desc .
Permit Fee . . . .
Issue Date . . . .
Expiration Date . .
LQPERMIT
MECHANICAL
39.50 Plan Check Fee . . 9.88
Valuation . . . . 0
6/15/14
Application Number . . . . . 13-00000395
Permit . . . . . . MECHANICAL
Qty Unit Charge
Per
Extension
BASE FEE
15.00
1.00 9.0000
EA MECH FURNACE <=100K
9.00
1.00 9.0000
EA MECH B/C <=3HP/100K BTU
9.00
1.00 6.5000
----------------------------------------------------------------------------
EA MECH VENT FAN
6.50
Permit
PLUMBING
Additional desc .
Permit Fee . . . .
76.50 Plan Check Fee
19.13
Issue Date . . . .
Valuation . . .
. 0
Expiration Date
6/15/14
Qty Unit Charge
Per
Extension
BASE FEE
15.00
3.00 6.0000
EA PLB FIXTURE
18.00
1.00 15.0000
EA PLB BUILDING SEWER
15.00
1.00 7.5000
EA PLB WATER HEATER/VENT
7.50
1.00 3.0000
EA PLB WATER INST/ALT/REP
3.00
1.00 3.0000
EA PLB GAS PIPE 1-4 OUTLETS
3.00
1.00 15.0000
EA PLB GAS METER
15.00
----------------------------------------------------------------------------
Special Notes and Comments
114 SQ. FT. GUARD HOUSE
WITH 63 SQ. FT.
PATIO COVER.PER 2010
CALIFORNIR CODES.
June 25, 2013 9:57:43
AM JJOHNSON.
----------------------------
Other Fees .. . . . .
-----------------------------------------------
. . . . ART IN PUBLIC PLACES -COM
1000.00
BLDG STDS ADMIN (SB1473)
8.00
DIF CIVIC CENTER - COMM
7.2.85
DIF FIRE PROTECTION -COMM
41.04
HOURLY PLAN CHECK
122.50
STRONG MOTION (SMI) - COM
42.00
DIF STREET MAINT FAC -COMM
28.73
DIF TRANSPORTATION - COMM
643.87
Fee summary Charged
----------------- ----------
Paid Credited
---------- --- - ------ ----------
Due
Permit Fee Total
1155.78 .00 .00
1155.78
Plan Check Total
676.51 .00 .00
676.51
Other Fee Total
1958.99 .00 .00
1958.99
Grand Total
3791.28 .00 .00
3791.28
LQPEPMIT
Bin #
RECEIVED
CIty Of, %d Quilltd MAR 2 7 201
�'� U ✓ Building8t Safe Division
P.O. Box 1504 "78-4 5 Calle Tampico CI -[Y OF LA QUI TA
Permit # COMMUNITY DEVEL PMENT
Ja.Quinta, CA 92253 - (760) 777-701213' Building Permit Application' and Tracking Sheet
Project Address: 3 62 � Owner's Name:. , $%Q,Fdl�fll LL'C
A. P. Number. Address: �,L�
Legal Description: �1 �'' City, ST, Zip; U/N //F ell* -44
Contractor•
Telephone z- k' 18': -
Address: qff' �j / , �2. Project Description: -917=1
City, ST, Zip: 0/&7
ex `%ZZ5 3 �f A/ �-01
Telephone t1 !� 7�0� ?j. ;:�� �.: •. -',mow'
State Lic. #:
Arch., Engr., Designer: PA t
Address: 7.4 Z�7—
City, ST, Zip: �/( a. '� a
Telephone 60 rf., 7 Construction Type:. Y A3 Occupancy:
State Lic. #: 2 �.�.4;f; Project type (circle one Ne Add'n. Alter Repair Demo
Name of Contact Person: \/�r� 1 /Cr�T Sq. Ft.: l4 # Stories: #Units:
Telephone # of Contact Person: (0o ' 7�8 3 Estimated Value of Project: O Q.O
APPLICANT: DO NOT WRITE BELOW THIS LINE
# Submittal Req'd Recd TRACKING PERMIT FEES
Plan Sets Plan Check submitted yJ vt Irl ltem Amount
Structural Calcs. Reviewed, ready for corrections Plan Check Deposit. .
Truss Calcs. Called Contact Person Z Plan Check Balance -
Title 24 Cslcs. Plans picked up Construction
Flood plain plan Plans resubmitted Mechanical
Grading plan r' Review, ready for correctionsfissue Electrical
Subcontactor List Called Contact Person Plumbing
Grant Deed Plans picked up S.M.I.
H.O.A. Approval Plans resubmitted Grading
IN HOUSE:- '"' Review', ready for correctionsAssue Developer Impact Fee
Planning Approval. Called Contact Person A.I.P.P.
Pub. Wks. Appr " Date of permit issue
School Fees
Total Permit Fees
(? - 6 R 1 C, OfVot,a 6u� 5/z3113
/l9 S �w 5 �Ra ( To tsst, &
z
Coachella Valley Unified School District
83-733 Avenue 55, Thermal, CA 92274
(760) 398-5909 — Fax (760) 398-1224
Project Name:
Owner's Name:
This Box For District Use Oniy
DEVELOPER FEES PAID
AREA:
AMOUNT
LEVEL ONE AMOUNT:
LEVEL TWO AMOUNT:
' MITIGATION AMOUNT:
COMM/IND. AMOUNT:
DATE:
RECEIPT:
CHECK #:
INITIALS:
CERTIFICATE OF COMPLIANCE
(California Education Code 17620)
East of Madison (Madison Club) Date: 06/12/08
East of Madison, LLC Phone No. (760) 391-2593
Project Address: 53-962 Gray Avenue, La Quinta, CA 92253
Project Description: Guard House No. 2
APN: 767-200-998 Tract #:
Type of Development: Residential
Lot #'s:
Commercial XXi Industrial ,,..;_
Total Square Feet of Building Area: 114 sq. Ft.
Certification of Applicant/Owners: The person signing certifies that the above, information is correct and makes this statement under
penalty of perjury and further represents that he/she is authorized to sign on behalf of the owner/developer.
Dated: 06/12/08 Signature: i
sssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssssss
SCHOOL DISTRICT'S REQUIREMENTS FOR THE ABOVE PROJECT HAVE BEEN ORWILLZE SATISFIED IN
ACCORDANCE WITH ONE OF THE FOLLOWING: (CIRCLE ONE)
Education Code Gov. Code Project Agreement Existing Not Subject to Fee
17620 65995 Approval Prior to 1/1/87 Requirement
Number of Sq.Ft. 114 sq. ft.
Amount per Sq.Ft. $ .47
Amount Collected $ 53.58
Building Permit Application Completed: Yes/No
By: Carey M. Carlson, Asst. Supt., Support Services
Certificate issued by: Leticia C. Torres, Facilities Analyst
Section 66020 of the Government Code asserted by Assembly Bill 3081, effective January 1, 1997, requires that thi�iLs' ti'(ct provide (1) a written notice to the
project appellant, at the time of payment of school fees, mitigation payment or other exactions ("Fees"), of the 90 -day period to protest the imposition of these
Fees and (2) the amount of the fees. Therefore, in accordance with section 66020 of the Government code and other applicable law, this Notice shall serve to
advise you that the 90 -day protest period in regard to such Fees or the validity thereof, commences with the payment of the fees or performance of any other
requirements as described in section 66020 of the Government code. Additionally, the amount of the fees imposed is as herein set forth, whether payable at this
time or in whole or in part prior to issuance of a Certificate of Occupancy. As in the latter, the 90 days starts on the date hereof. This Certificate of
Compliance is valid for thirty (30) days from the date of issuance. Extension will be granted only for good cause, as determined by the School District, and up
to three (3) such extensions may be granted. At such time as this Certificate expires, if a building permit has not been issued for the project that is the subject
of this Certificate, the owner will be reimbursed all fees that were paid,to obtain this Certificate of Compliance.
Ll':c/mydocs/devfees/certificate of compliance form tablesTO USE.doc 1/16103 T
CITY OF LA QUINTA - PUBLIC WORKS DEPARTMENT GREEN SHEET
PUBLIC WORKS CLEARANCE FOR RELEASE OF BUILDING PERMIT
Form updated & effective 9/25/2009
Green Sheet approvals are forwarded to the Buildinq & Safety Department directiv by Public Works. Please DO NOT
submit the Green Sheet (Public Works Clearance) Packet to the Public Works Department until ALL requirements listed
below are complete. Incomplete applications or arpp�lications which cannot
be processed will be returned to applicant.
Date: 7/ /? Developer:
Tract No.: ??'��" � Tract Name: Lot No.(s): � �e�K�A''��► ��
Address(s)- �' �z ,r l /� Phone Number: (e;�09) `7`8 7 \✓
The following are the requirements for Public Works Clearance to authorize issuance of REicarE
IVED
from the
Building & Safety Department:
4
4.
2.
3.
4.
5.
6.
7.
JUL 31 2013
CITY OF LA QUINT
Attach Pad Elevation Certificates in' compliance with the approved design elevati i r
allowable deviation of +/- 0.1 foot). Pad Elevation Certificates must be current (within 6 months of curren1ie1'
If a precise grading plan creates the pad for approval, please withhold green sheet submittal until a Pad Elevation
Certificate can be provided.
Attach geotechnical certification of grading plan compliance including compaction reports from a licensed Soils
Engineer. Recently rough graded residential developments which .have a previously approved geotechnical
certification are exempt from this requirement.
Attach recorded final map or title information/grant deed showing proposed building locations are legal lots.
Complete the attached <1 acre per lot or infill project Fugitive Dust Control project information form, PM10 plan &
agreement or provide alternative & valid City approved PM10 plan set reference number or hard copy plan.
PM10,plans for commercial & residential developments (beyond 1 lot) are submitted separately with grading plans
& are subject to additional requirements. A current PM10 certification number is required.
Attach a copy of the rough or precise grading plan to the Public Works Department showing building location(s)
for pad elevation verification. AO flood zone developments will require an approved flood plain development plan.
Attach supporting documentation for wall plan, monument sign, grease trap or special facility installations.
Complete and sign the attached water quality management plan (WQMP) exemption form, if applicable. PW
approved building construction projects require either a WQMP or a completed WQMP exemption form.
Approved maps/plans may be viewed at the following link: http://www.la-guinta.org/PlanCheck/m search.aspx
I have reviewed and confirmed the requirements listed above as presented ana find the improvements to be sufficiently
complete for construction of the proposed buildings/structures/walls/signs on the subject lot(s). Pursuant to my findings,
the above project may be released for building permit issuance.
This section completed by City staff.
Recommended by: Date:
Public Works Distribution: ( C/) GrUn Sheet to Building & Safety
( ) Green Sheet to Planning Department
Declined for approval for reason(s) as follow(s); please correct and resubmit:
TACheddists - Forms & ApplicationslFonns & Applications\GREEN SHEET cover & PM10less than 1 Acre Revised 9-25-09.doc
City of La Quinta - PM10 Fugitive Dust Control Project Information
Construction Phase PM10 Agreement (<1 acre/lot or Infill Project)
Project Information
Project Contractor:
Project Phase
(check one)
Construction
Demolition
�'l
Project Name: % ��_0wy 7 Awn;i—'
Project Tract/Lot Numbers: �7����'
Project Street Address:
Total Acres in Active
Construction (<1 acre per2
Lot):
Anticipated Start Date: 8 / / 13 Anticipated Completion Date:
PM10 Contact
Information
Please note: Dust control is required 24 hours a day, 7 days a week, regardless of
construction status. Person listed below is responsible for dust control during business and
non -business hours.
Name:
1�Pizk�
Title:
v,,d
Company Name:
AF%r%
Mailing Address:
�7 AVV: 15�_Z
City, State ZIP Code:
P-� ¢U�NT / % 3
Primary Phone M
_1;�C .7/6 3
Fax #:
24 Hour Emergency
Phone#:
Cell Phone #:
Lla0�' 9z� 7153
Email Address:
PM10 Certificate #:
The above stated property owner (or authorized representative):
❖ Shall act as his/her acknowledgement of dust control requirements and their enforceability, pursuant to SCAQMD
Rules 403, 403.1, 401, 402, 201, 203 and PERP;
❖ Shall constitute an Agreement to comply with all project conditions as identified in the approved dust control plan.
❖ Acknowledges that dust control is required twenty-four (24) hours a day, seven (7) days a week, throughout the
period of project performance, regardless of project size or status;
❖ Shall ensure that each and every contractor, subcontractor and all other persons associated with the project shall
be in continuous compliance with all requirements of the approved dust control plan;
❖ Shall take all necessary precautions to minimize dust, even if additional measures beyond those listed in the dust
control plan are necessary;
❖ Shall authorize r p esentatives of City/County to enter the property for inspection and/or abatement purposes;
4 -Shall hold harm) the ity/County and its representatives from liability for any actions related to this dust control
plan or any City/ untA inMated abatement activities.
Signature of
Owner or Authorized Representative
TAChecldists - Forms & ApplicationsTortnilMApplications\GREEN SHEET cover & PM10 less than 1 Acre Revised 9-25-09.doc
Dat
0
i "N
Engineering
77-725 Enfield Lane, Suite 100, Palm Desert, CA 92211 (760) 772-3893 Fax (760) 772-3895
6782 Stanton Ave., Suite A, Buena Park, CA 90621 (714) 523-0952 Fax (714) 523-1369
450 Egan Avenue, Bcaumont, CA 92223 (951) 845-7743 Fax (951) 845-8863
November 14, 2007
East of Madison, LLC
81-100 Avenue 53
La Quinta, California 92253
Subject: Geoteclunical Update.
Project: Madison Club—Secondary Entrance
Avenue 54
La Quinta, California
Project No. 544-4810
07-11-785
Ref: Geotechnical Investigation Report prepared by Sladden Engineering dated January
28, 2005; Project No. 544-4810, Report No. 05-01-101.
As requested, we have reviewed the above referenced geotechnical report as it relates to the
design and construction of the proposed secondary entrance to the Madison Club development
located on the north side of Avenue 54 between Monroe Street and Madison Street in the City of
La Quinta, California.
The referenced geotechnical report includes recommendations for the design and construction of
structures. Based upon our review of the referenced report and our recent site observations, it is
our opinion that the recommendations included in the above referenced reports remain
applicable for the proposed secondary entrance.
Footings should extend at least 12 inches beneath lowest adjacent grade. Isolated square or
rectangular footings should be at least two feet square and continuous footings should be at least
12 inches wide. Continuous footings may be designed using an allowable bearing value of 1500
pounds per square foot (psf) and isolated pad footings may be designed using an allowable
bearing pressure of 1800 psf. Allowable increases of 250 psf for each additional 1 foot of width
and 250 psf for each additional 6 inches of depth may be utilized if desired. The maximum
allowable bearing pressure should -be 2500 psf. The allowable bearing pressures are applicable to
dead and frequently applied live loads. The allowable -bearing pressures may be increased by 1/3
to resist wind and seismic loading.
r -
November 14, 2007 -2- Project No. 544-4810
07-11-785
The recommendations made in the preceding paragraph are based on the assumption that all
footings will be supported by properly compacted soils. Prior to the placement of the reinforcing
steel and concrete, we recommend that the footing excavations be inspected in order to verify
that they extend into the firm compacted soils and are free of loose and disturbed materials.
Settlements may result from the anticipated foundation loads. These estimated ultimate
settlements are calculated to be a maximum of 1 inch when using the recommended bearing
values. As a practical matter, differential settlements between footings can be assumed as one-
half of the total settlement. These elastic settlements are expected to occur during construction.
Resistance to lateral loads may be provided by a combination of friction acting at the base of the
slabs or foundations and passive earth pressure along the sides of the foundations. A coefficient
of friction of 0.40 between soil and concrete may be used for dead load forces. only. A passive
earth pressure of 250 pounds per square foot, per foot of depth, may be used along the sides of
footings which are poured against properly compacted native or approved import soils.
Retaining walls may be required to accomplish the proposed construction. Cantilever retaining
walls may be designed using "active" pressures. Active pressures may be estimated using an
equivalent fluid weight of 35 pcf for native backfill soils with level free -draining backfill
conditions. For walls that are restrained, "at rest" pressures should be utilized in design. At rest
pressures may be estimated using an equivalent fluid weight of 55 pcf. Walls should be provided
with adequate drainage.
The site was previously graded during the rough grading of the Madison Club project site and
was recently regraded. The rough grading included overexcavation of the native surface soil
along with the placement of engineered fill material to construct the building pads. Because the
subject lot has been previously rough graded, the remedial grading necessary at this time should
be miuumal.
It should be noted that the site is located within a seismically active area of Southern California
and it is likely that the proposed structures will experience strong ground. shaking as a result of
an earthquake event along one of the faults in the region during the expected life of the
development. As a minimum, structures should be designed based upon Seismic Zone 4 design
criteria included in the Uniform Building Code (UBC). The potential for liquefaction or other
geologic/seismic hazards occurring at the site is considered to be negligible.
Sladden Engineering
November 14, 2007
Qc3I
Project No. 544-4810
07-11-785
We appreciate the opportunity to provide service to you on this project, if you have any
questions regarding this letter or the referenced reports please contact the undersigned.
Respectfully subn-dtted,
SLADDEN ENGINEERING
Brett L. Anderson)
Principal Engineer
SER/gl
CC
\,
Exp 9-.30-2008
Copies: 4/East of Madison,
Sladden Engineering
November 14, 2007 -4- Project No. 544-4810
07-11-785
2001 CALIFORNIA BUILDING CODE SEISMIC DESIGN INFORMATION
The California Code of Regulations, Title 24 (2001 California Building Code) and 1997 Uniform
Building Code, Chapter 16 of this code, contain substantial revisions and additions to earthquake
engineering design criteria. Concepts contained in the code that will be relevant to construction
of the proposed structures are summarized below.
Ground shaking is expected to be the primary hazard most likely to affect the site, based upon
proximity to significant faults capable of generating large earthquakes. Major fault zones
considered to be most likely to create strong ground shaking at the site are listed below.
Fault Zone
Approximate Distance
From Site
Fault Type
(1997 UBC)
San Andreas
8.9 km
A
San Jacinto
30.9 km
A
Based on our field observations and understanding of local geologic conditions, the soil profile
type judged applicable to this site is So, generally described as stiff or dense .soil. The site is
located within UBC Seismic Zone 4. The following table presents additional coefficients and
factors relevant to seismic mitigation for new construction upon adoption of the 1997 code.
Sladden Engineering
Near -Source
Near -Source
Seismic
Seismic
Seismic
Acceleration
Velocity
Coefficient
Coefficient
Source
Factor, Na
Factor, N..
Ca
Cv
San Andreas
1.04
1.29
0.44 Na
0.64 N,•
San Jacinto
1.0
1.0
0.44 N.,
0.64 Nv
Sladden Engineering
r '
WEDDLE
SURVEYING MAPPING, INC.
Boundary • Construction • Topographic -Aerial Surveys • ALTA Surveys- GPS • Consulting
December 16, 2013
Mr. Timothy R. Jonasson
Public Works Director/ City Engineer
City of La Quinta
78-495 Calle Tampico
La Quinta, CA 92253-1504
Re: Pad Grade Verification
City of La Quinta
SECONDARY GUARD GATE ENTRY
Por. Lot "S" Tract No. 33076-2 MB 393/61-80
53-962 Gray Avenue
MADISON CLUB
APN Por. 767-890-004
Dear Mr. Jonasson:
1 '31V d O73/13G'� I
nb , owwo3
a''1IJ
E10Z L J3o
We have performed a field survey to determine the vertical location of the Building Pad for the
above referenced project. The elevation observed is as follows:
PAD (DESIGN)
968.0'
PAD (AS -BUILT)
968.1'
This field observation. is in substantial conformance with the Precise Grading Plan prepared by
RCE CONSULTANTS, INC., dated 11/8/13, approved by the City of La Quinta Public
Works Department 11/21/13 and the building Pad horizontal location substantially conforms to
the required setbacks and site layout as shown on the approved site plan.
Sincerely,
WEDDLE SURVEYING MAPPING, INC.
David L. Weddle, President
L.S. 5570, exp 09/30/15
P.O. Box 10418'- Palm Desert, CA 92255-0418
77-725 EnJield Lane, Ste. 140 • Palm Desert, CA 92211 • 760.360.5570
E -Mail: 171edSury uaol. com • Fax 760.360.55 73
BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Madison Guard House
The Madison Club
La Quinta, CA 92253
Project Designer:
Pearson Architects
74-260 Highway 111, Suite 8
Palm Desert, CA 92260
(760) 779-1937
Report Prepared by:
Tim Scott
Scott Design and Title 24, Inc,
r 77-085 Michigan Drive
Palm Desert, Ca 92211
(760) 200-4780
RECEIVI:D
MAR 2 7 2013
Job Number: CITY OF LA QUINTq
COMMUNITY DEVELOPMENT
Date:.I ;ry OF LA QUINTA
3/18/2013BLJ)I LING & SAFETY DEPT,
"OP OVED
The EnergyPro computer program has been used to perform the calculations summari ed iin�t i coomplia c T r rogram as approval and is
authorized by the California Energy Commission for use with both the Resi ential and N r side tial 2 B ilding Energy Effi ency Standards.
1-01,
'�. DATE
This program developed by EnergyS ft LLC — �d
EnerovPro 5.1 by EnerovSoft User Number: 6712 RunCode: 2013-03-18721:12:20 ID:
AS
x
•
r
17,
•
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1 C
Project Name
Date
Madison Guard House
3/18/2013
Project Address
Climate Zone
Total Cond. Floor Area
Addition Floor Area
The Madison Club La Quinta
CA Climate Zone 15
149
n/a
GENERAL INFORMATION
Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Relocatable - indicate ❑ specific climate zone ❑ all climates
Phase of Construction: ® New Construction ❑ Addition ❑ Alteration
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed to
comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This
certificate applies only to a Building using the performance compliance approach.
The documentation author hereby certifies that the documentation is accurate and com
I te.
Documentation Author
Name Tim Scott
Signature
Company Scott Design and Title 24, Inc,
Date 3118/2013
Address 77-085 Michigan Drive
Phone (760) 200-4780
City/State2ip Palm Desert, Ca 92211 #J 20 —OC{ — -7m
The Principal Designer hereby certifies that the proposed building design represented in this set of
construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with
-any other calculations submitted with this permit application. The proposed building has been designed to meet the energy
efficiency requirements contained in sections 110, 116 through 118, and 140 through 149 of Title 24, Part 6. Please
check one:
ENV. LTG. MECH.
I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
❑ ❑ ❑ . sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section
❑ ❑ ❑ 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
❑ ❑ ❑ because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538 and 6737.1.
Principal Envelope Designer
Name
Signature
Company Pearson Architects Date
Address 74-260 Highway 111, Suite 8 License #
City/State/Zip palm Desert, CA 92260 Ph ne (760)
779-1937
Principal Mechanical Designer
Name Tim Scott
Signature
Company Scott Design and Title 24, Inc. Date
l $ 13
Address 77-085 Michigan Drive License #
City/State/Zip palm Desert, Ca 92211 Phone (760) 200-4780
Principal Lighting Designer
Name
Signature -.—. ilk 1n
CompanyLighting Compliance Not /n The Scope Of This Submittal�Da o
ETY
Address L''ice e`#^ E
City/State/Zip PliorieA 1 f
INSTRUCTIONS TO APPLICANT COMPLIANCE & WORKSHEETS (check box if worksheets° d'r dI6dVd
m ENV -1 C Certificate of Compliance. Required on plans. m MECH-1 C Certificate of C n'Pre n ns.
❑ LTG -1C Certificate of Compliance. Required on plans. m MECH-2C Air/Water Sid ' er of Requirem nts.
❑ LTG -2C Lighting Controls Credit Worksheet. m MECH-3C Mechanical Ve il, lion a
❑ LTG -3C Indoor Lighting Power Allowance. m MECH-5C Mechanical EquipmentVe`f@ls.
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-03-18721:12:20 ID: Page 3 of 24
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 ERF -IC
isProject Name Date
Madison Guard House 3/18/2013
ANNUAL TDV ENERGY USE SUMMARY kBtu/s ft- r
Standard Proposed Compliance
Energy Component Design Design Margin --T ----�-
Space Heating
'Space Cooling
Indoor Fans
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Lighting
Receptacle
Process
Process Lighting
TOTALS
3.56
1.96
. 1.59
294.96
215.25
79.71
35.34
98.17
-62.83
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
41.98
41.98
0.00
12.82
12.82
0.00
0.00
0.00
0.00
0.00
0.00
0.00
388.66
370.18
18.47
Heating --,-
Cooling L -
Fans
Heat Rej j t
Pumps
D H W
Lighting t --
Receptacle
Process -- - ---� -
Process Ltg j
Percent better than Standard 4.8% 4.8 % excluding process)
BUILDING COMPLIES
GENERAL INFORMATION
Building Orientation (N) 0 deg Conditioned Floor Area 149 sqft.
Number of Stories 1 Unconditioned Floor Area 0 sqft.
Number of Systems 1 Conditioned Footprint Area 149 sqft.
Number of Zones 1 Natural Gas Available On Site Yes
Orientation Gross Area Glazing Area Glazing Ratio
Front Elevation
Left Elevation
Rear Elevation
-Right Elevation
Total
Roof
(N)
64
(E)
143
(S)
64
(VV)
143
414
149
sqft.
sqft.
sqft.
sqft.
sqft. .
sqft.
0
42
18
21
81
0
sqft.
sqft.
sqft.
sqft.
sqft.
sqft.
0.0%
29.4%
28.1%
14.7%
19.6
L0.0
Standard Proposed Prescriptive Values for
Prescriptive Lighting Power Density 0.600 W/sqft. 0.600 W/sgft. Comparison only. See
Prescriptive Envelope TDV Energy 23,710 1 21,382 LTG -1 C for allowed LPD.
Remarks:
CITY OF LA QUINTA
9WILDING & SAFETY DEPT.
PPROVED
F:ili? COYRUCTIO.
EnemvPro5.1byEnerqySoft User Number: 6712 RunCode: 2013-03-18721:12:20 /D: Pa e 4 of 24
•
n
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1 C
Project Name
Madison Guard House
Date
3/18/2013
ZONE INFORMATION
Floor Inst. Ctrl. Allowed LPD Proc.
Area LPD Credits Area Tailored Loads
System Name Zone Name Occupancy Type s ft. W/sf' W/sf 2 W/sf 3 W/sf a (W/St)
HVAC 1 Guard House Corridor/Restroom/Support 149 '0.600
Notes: 1. See LTG -1C 2. See LTG -2C 3. See LTG -3C 4. See LTG -4C Items above require special documentation
items marked with asterisk, see LTG -1 -C by others) (by others
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
..The local enforcement agency should pay special attention to the items specified in this checklist. These Items require special written
justification and documentation, and special verification to be used with the performance approach. The local enforcement agency
determines the adequacy of the justifications, and may reject a building or design that otherwise complies based on the adequacy of the
special justification and documentation submitted.
The HVAC System HVAC 1 incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-4-A.
0
t
A"�I All
A U BFIN ;S
i
> PPROVED
r -v L UCTION
The exceptional features listed in this performance approach application have specifically been reviewed A�uate ritte justific tion and
documentation for their use have been provided by the applicant.r`�J
DATE � � . Y
Authorized Signature or Stamp
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-03-18721:12:20 ID: Page 5 of 24
L-
•
•
CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C
AND FIELD INSPECTION ENERGY CHECKLIST
Project Name
Madison Guard House
Date
3/18/2013
Project Address
The Madison Club La Quinta
Climate Zone
15
Total Cond. Floor Area
149
Addition Floor Area
n/a
GENERAL INFORMATION
Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Schools (Public School) ❑ RRlellocatable Public School m Conditioned Spaces ❑ Unconditioned Spaces
❑ Skylight Area for Large Enclosed Space z 8000 ftz (If checked include the ENV -4C with submittal)
Phase of Construction: ® New Construction ❑ Addition ❑ Alteration
Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit)
Front Orientation: N, E, S, W or in Degrees: 1 0 deg
FIELD INSPECTION ENERGY CHECKLIST
OPAQUE SURFACE DETAILS
INSULATION
Ta /ID
Assembly Type
y
Q
0 3
cy
d LL!
OZ
v
LL
D
>q j
3cc
ac
m
::
W>
WU,
0W
a`� ?
C>
IM
°0
a`�
U.
x
d
C a
�Q
c
o
v7
c
UN
vyi
a.
U.
1
Roof
149
(M
1 0.022
R-381
7.0
None
14.2.1-A9
New
❑ 1
❑
2
Wall
64
(N)
0.074
R-19
4.3.1-A5
New
❑
❑
3
Wall
101
(E)
0.074
R-19
4.3.1-A5
New
❑
❑
4
Wall
46
(S)
0.074
R-19
4.3.1-A5
New
❑
❑
5
Wall
122
(W)
0.074
R-19
4.3.1-A5
New
❑
❑
6
Slab
149
(N)
0.730
None
4.4.7-A1
New
❑ 1
❑
❑
❑
❑
❑
❑
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance.
FENESTRATION SURFACE DETAILS
Tag/ID
Fenestration
Type
a
d w
O Z
V
RLL
2>
V
4 o'
> U)
N
�¢
= o
u) N
W
> 0 :' a
O v w a
is
a
1
Window
42
(E)
0.400
NFRC
0.2901
NFRC
❑ New ❑
❑
2
Window
18
(S)
0.400
NFRC
0.290
NFRC
❑ New ❑
❑
3
Window
21
(MM
0.400
NFRC
0.290
NFRC
❑ New ❑
❑
r.-�--.
DO—
,
i t3 ii_UIIN
L
I FOR
C0NPT,13LXT10P1
❑
[3\ 1
DATE
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96. ---
2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify buildij Ia if necessary.
EnergyPro 5.10 EnergySoft User Number.- 6712 RunCode: 2013-03-18721:12:20 ID: Page 6 of 24
•
0
CERTIFICATE OF COMPLIANCE (Part 2 of 3)
AND FIELD INSPECTION ENERGY CHECKLIST
ENV -1 C
Project Name
Madison Guard House
Date
3/18/2013
ROOFING PRODUCT COOL ROOFS
(Note if the roofing product is not CRRC certified, this compliance approach cannot be used). Go to Overall Envelope Approach or
Performance Approach.
CHECK APPLICABLE BOX BELOW IF EXEMPT FROM THE ROOFING PRODUCT "COOL ROOF" REQUIREMENTS:
Pass
Fall'
N/A
❑ Roofing compliance not required in Climate Zones 1 andl6 with a Low -Sloped. 2:12 pitch or less.
❑
❑
❑
❑ Roofing compliance not required in Climate Zone 1 with a Steep -Sloped with less than 5 Ib/ft2. Greater than 2:12 pitch.
❑
❑
❑
❑ Low -sloped Wood framed roofs in Climate Zones 3 and 5 are exempted, solar reflectance and thermal emittance or
SRI that have a U -factor of 0.039 or lower. See Opaque Surface Details roof assembly, Column H of ENV -2C.
❑
❑
❑
❑ Low -sloped Metal building roofs in Climate Zone 3 and 5 are exempted, solar relectance and thermal emittance or SRI
that have a U -factor of 0.048 or lower. See Opaque Surface Details roof assembly below, Column H of ENV -2C.
❑
❑
❑
❑ The roof area covered by building integrated photovoltaic panels and building integrated solar thermal panels are
exempted. Solar reflectance and thermal emittance or SRI, seespreadsheet calculator at www.energy.22.qov/tiitlie;2e4/
❑
❑
❑
❑ Roof constructions that have thermal mass over the roof membrane with a weight of at least 25 Ib/ft are exempt from
the Cool Roof criteria below.
❑
❑
❑
❑ High-rise residential buildings and hotels and motels with low -sloped roofs in Climate Zones 1 through 9, 12 and 16 are
exempted from the low -sloped roofing criteria.
❑
❑
❑
1. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
CRRC Product ID Roof Slope Product Weight Product Aged Solar Thermal
Number' s 2:12 > 2:12 < 51b/ft' a 51b/ft2 Type 2 Reflectance Emmitance SRI5
Pass Faile
❑ ❑ ❑ ❑ ❑ °
❑ ❑
❑ ❑ ❑ ❑ (3 °
❑ ❑
❑ ❑ ❑. ❑ ❑°
❑ ❑
❑ ❑ ❑ ❑ ❑°
❑ ❑
❑ ❑ ❑ ❑ ❑°
❑ ❑
13 13 13 ❑ °
❑ ❑
1. The CRRC Product ID Number can be obtained from the Cool Roof Rating Council's Rated Product Directory at
www.coolroots.org/r)roducts/search.r)hp
2. Indicate the type of product is being used for the roof top, i.e. single -ply roof, asphalt roof, metal roof, etc.
3. If the Aged Reflectance is not available in the Cool Roof Rating Council's Rated Product Directory then use the Initial Reflectance value from the
same directory and use the equation (0.2+0.7(p,,dtlal — 0.2) to obtain a calculated aged value. Where p is the Initial Solar Reflectance from the Cool
Roof Rating Council's Rated Product Directory.
4. Check box if the Aged Reflectance is a calculated value using the equation above.
5. The SRI value needs to be calculated from a spreadsheet calculator at h_ni3://www.enerov.ca.gov/title24/
6. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
To apply Liquid Field Applied Coatings, the coating must be applied across the entire roof surface and meet the dry mil thickness or coverage
recommended by the coatings manufacturer and meet minimum performance requirements listed in §118(i)4. Select the applicable coating:
❑ Aluminum -Pigmented Asphalt Roof Coating
❑ Cement -Based Roof Coating
❑ Other
Discrepancies:
7 (�,1 T V
r llLDING & SAFETY DEPT.
Er�r� �` nl tit
a v.
CA; #t.
EnergyPro 5.1 by EnerqvSoft User Number: 6712 RunCode: 2013-03-18721:12:20 ID:
Page 7 of 24
10
•
•
CERTIFICATE OF COMPLIANCE (Part 3 of 3) ENV -1 C
AND FIELD INSPECTION ENERGY CHECKLIST
Project NameDate
Madison Guard House
3 118/2013
Required Acceptance Tests
Designer:
This form is to be used by the designer and attached to the plans. Listed below is the acceptance test for Envelope
Fenestrations system. The designer is required to check the acceptance tests and list all the fenestration products that
require an acceptance test. If all the site -built fenestration of a certain type requires a test, list the different fenestration
products and the number of systems. The NA7 Section in the Appendix of the Nonresidential Reference Appendices
Manual describes the test. Since this form will be part of the plans, completion of this section will allow the responsible
party to budget for the scope of work appropriately.
Enforcement Agency:
Systems Acceptance. Before Occupancy Permit is granted for a newly constructed building or space or whenever new
fenestration is installed in the building or space shall be certified as meeting the Acceptance Requirements.
The ENV -2A form is not considered a complete form and is not to be accepted by the enforcement agency unless the
boxes are checked and/or filled and signed. In addition, a Certificate of Acceptance forms shall be submitted to the
enforcement agency that certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of §10-103(b) of Title 24 Part 6. The field inspector must receive the properly filled
out and signed forms before the building can receive final occupancy. A copy of the ENV -2A for each different
fenestration product line must be provided to the owner of the building for their records.
Test Description ENV -2A Test Performed By:
Fenestration Products Name or ID Area of like Building Envelope
Requiring Testing or Verification Products Acceptance Test
Double Non -Metal 81 m
13
13
13
13
13
13
13
13
13
13
Ot'l-,-,11 OF i
' ka Y 9 Y
"13
❑r.. e•i — n'n A CCT/DEPT,
❑C.,. ri�li i erw ax
. a -v r-„
❑ P ill r/ EB
o
❑ ,
❑��
❑
13
EnergyPro 5. 1 by EnergySoft User Number., 6712 RunCode: 2013-03-18721:12:20 /D: Page 8 of 24
•
•
•
CERTIFICATE OF COMPLIANCE and
FIELD INSPECTION ENERGY CHECKLIST
(Part 1 of 4)
MECH-1 C
Project Name
Madison Guard House
Date
3/18/2013
Project Address
The Madison Club La Quinta
Climate Zone
15
Total Cond. Floor Area
149
Addition Floor Area
n/a
GENERAL INFORMATION
Building Type: ®
Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
E3Schools (Public School) ❑
Relocatable Public School Bldg. m Conditioned Spaces ❑
Unconditioned Spaces
affidavit
Phase of Construction: ®
New Construction ❑ Addition
❑ Alteration
Approach of Compliance: ❑
Component 13Overall Envelope TDVEner13 Unconditioned (file affidavit)
Front Orientation: N, E, S, W or in Degrees: 1 0 deg
HVAC SYSTEM DETAILS
FIELD INSPECTION ENERGY CHECKLIST
E ui ment2
Inspection Criteria
Meets Criteria or Requirements
Pass Fail – Describe Reason
Item or System Tags
i.e. AC -1, RTU -1, HP -1
DHW Heater
❑
❑
Equipment T e3:
Electric Res DHW Boiler
❑
❑
Number of Systems
1
❑
❑
Max Allowed Heating Capacity'
5,120 Btu/hr
❑
❑
Minimum Heating Efficiency'
0.95 EF
❑
❑
Max Allowed Cooling Capacity'
n/a
❑
❑
Cooling Efficiency'
n/a
❑
❑
Duct Location/ R -Value
n/a
❑
❑
When duct testing is required, submit
MECH-4A & MECH-4-HERS
n/a
❑
❑
Economizer
n/a
❑
❑
Thermostat
n/a
❑
❑
Fan Control
n/a
❑
❑
E ui ment2
Inspection Criteria
FIELD INSPECTION ENERGY CHECKLIST
Pass Fail — Describe Reason
Item or System Tags
i.e. AC -1, RTU -1, HP -1
HVAC 1
❑
❑
Equipment T e3:
Split DX
❑
❑
Number of Systems
1
❑
❑
Max Allowed Heating Capacity'
18,000 Btu/hr
❑
❑
Minimum Heatinq Efficiency'
8.00 HSPF
❑
❑
Max Allowed Cooling Capacity'
17,500 Btu/hr
❑
❑
Cooling Efficiency'
15.0 SEER / 12.5 EER
❑
❑
Duct Location/ R -Value
Attic, Ceiling Ins, vented /8.0
O —_
,
II
When duct testing is required, submit
MECH-4A & MECH-4-HERS
Yes
,' NTA
. 1„ o G
Economizer
No Economizer
t7u"❑"'��"
Thermostat
Setback Required
, =� �
LP 116.011,
Fan Control
Constant Volume
I � �
1. If the Actual installed equipment performance efficiency and capacity is less than the Proposed (from the e Ii c bmi dor from
the building plans) the responsible party shall resubmit energy compliance to include the new changesTE �l
2. For additional detailed discrepancy use Page 2 of the Inspection Checklist Form. Compliance fails if-a=Fall,box,ls9dhec
3. Indicate Equipment Type: Gas (Pkg or, Split), VAV, HP (Pkg or split), Hydronic, PTAC, or other.
JEnergyPro5.1byEnergySoft User Number: 6712 RunCode: 2013-03-18721:12:20
ID:
Page 9 of 24
0
0
•
CERTIFICATE OF COMPLIANCE and (Part 2 of 4) MECH-1 C
FIELD INSPECTION ENERGY CHECKLIST
Madison Guard House
3/18/2013
EnemyPro 5.1 by EnemySoR User Number. 6712 RunCode: 2013.03-18721:12:20 ID: IPage 10 of 24
9 0 0
CERTIFICATE OF COMPLIANCE and FIELD INSPECTION ENERGY CHECKLIST (Part 3 of 4) MECH-1 C
Project Name
Date
Madison Guard House
3/18/2013
Required Acceptance Tests
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the applicable
boxes by all acceptance tests that apply and listed all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and
the number of systems. The NA number designates the Section in the Appendix of the Nonresidential Reference Appendices Manual that describes the test. Since this form will be
part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately.
Building Departments:
Systems Acceptance: Before occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated for
normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
Systems Acceptance: Before occupancy permit is granted. All newly installed HVAC equipment must be tested using the Acceptance Requirements.
The MECH-1 C form is not considered a completed form and is not to be accepted by the building department unless the correct boxes are checked. The equipment requiring testing,
person performing the test (Example: HVAC installer, TAB contractor, controls contractor, PE in charge of project) and what Acceptance test must be conducted. The following
checked -off forms are required for ALL newly installed equipment. In addition a Certificate of Acceptance forms shall be submitted to the building department that certifies plans,
specifications, installation, certificates, and operating and maintenance information meet the requirements of §10-103(b) and Title -24 Part 6. The building inspector must receive the
properly filled out and signed forms before the building can receive final occupancy.
TEST DESCRIPTION
MECH-2A
MECH-3A
MECH-4A
MECH-5A
MECH-6A
MECH-7A
MECH-8A
MECH-9A
MECH-10A
MECH-11A
Hydronic
Outdoor
Constant
Demand
Supply
System
Automatic
Ventilation
Volume &
Air
Control
Supply
Valve
Water
Variable
Demand
For
Single -Zone
Distribution
Economizer
Ventilation
Fan
Leakage
Temp.
Flow
Shed
Equipment Re uirin Testing or Verification Qty.
VAV & CAV
Unitary
Ducts
Controls
DCV
VAV
Test
Reset
Control
Control
Carrier 25AHB618/FE4BNF018 1
❑
®
®
❑
❑
❑
1 ❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
_.
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
kn n"11
I `-- r. r; ��
❑
El
❑
❑
13
❑
11
13
�^ o17
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
.1
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
t' U
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
<l_
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
Il �m Z
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
Ene Fero 15.1 b Ene Soft User Number. 6712 RunCode:
2013-03-18721:12:20
ID: Pae 11 of 24
0 0 0
CERTIFICATE OF COMPLIANCE and FIELD INSPECTION ENERGY CHECKLIST
(Part 4 of 4) MECH-1 C
Project Name
Madison Guard House
Date
3/18/2013
TEST DESCRIPTION
MECH-12A
MECH-13A
MECH-14A
MECH-15A
Equipment Re uirin Testing
Fault
Detection &
Diagnostics
Qtv. for DX Units
Automatic Fault
Detection &
Diagnostics for
Air & Zone
Distributed
Energy Storage
DX AC
Systems
Thermal Energy
Storage (TES)
Systems
Test Performed By:
Carrier 25AHB618/FE4BNF018
1 ❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
-g
❑
❑
❑
❑
t
❑
❑
❑
❑
16
13
13
0
14-
❑
❑
❑
❑
I c3
❑
❑
❑
❑
I I� z ->i go
❑
❑
❑
❑
❑
❑
❑
❑
-n❑
❑
❑
❑
n
❑
❑
❑
Cl
0—
❑
❑
❑
❑
z m -411❑
❑
13:4
y
1 ❑
❑
❑
❑
EnergyPro 5.1 by EnergySoft
User Number. 6712
RunCode: 2013-03-18721:12:20 ID:
Page 12 of 24
•
•
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2C
Project Name
Date
Madison Guard House
1 3/18/2013
Indicate
Air S stems Tvpe Central, single Zone, Package,
VAV, or etc...
Item or System Tags
i.e. AC -1, RTU -1, HP -1
HVAC 1
Number of Systems
1
Indicate Pape Reference on Plans or Schedule and indicate the applicable exception(s)
MANDATORY MEASURES
T-24 Sections
Heating Equipment Efficiency
112(a)
8.00 HSPF
Cooling Equipment Efficiency
112(a)
15.0 SEER/ 12.5 EER
HVAC Heat Pump Thermostat
112(b), 112(c)
Yes
Furnace Controls/Thermostat
112(c), 115(a)
n/a
Natural Ventilation
121 b
Yes
Mechanical Ventilation
121 b
15 cfm
VAV Minimum Position Control
121 c
No
Demand Control Ventilation
121 c
No
Time Control
122(e)
Programmable Switch
Setback and Setup Control
122(e)
Setback Required
Outdoor Damper Control
122(f)
Auto
Isolation Zones
122
n/a
Pipe Insulation
123
Duct Location/ R -value
124
Attic, Ceiling Ins, vented /8.0
PRESCRIPTIVE MEASURES
Calculated Design Heating Load
144(a & b
n/a
Proposed Heating Capacity
144(a & b
11,242 Btu/hr
Calculated Design Cooling Load
144(a & b
n/a
Proposed Cooling Capacity
144(a & b
12,405 Btu/hr
Fan Control
144(c)
Constant Volume
DP Sensor Location
144(c)
Supply Pressure Reset (DDC only)
144(c)
Yes
Simultaneous Heat/Cool
144(d)
No
Economizer
144(e)
No Economizer
Heat Air Supply Reset
144(f)
Constant Temp
Cool Air Supply Reset
144(f)
Constant Temp
Electric Resistance Heating'
144
U-1 I
Air Cooled Chiller Limitation
144(i)
Duct Leakage Sealing. If Yes, a
I L :J, I_Q N S
.
MECH-4-A must be submitted
144(k)
Yes
;APPROVED
FOR CONS
RUCTION
1. Total installed capacity (MBtu/hr) of all electric heat
on this project exclusive of electric uxiliary heat or h t um ,
I electric heat is use
explain which exception(s) to §144(g) apply.
(�,
GAl-E 25�1L
EnePro 5.1 by EnergySoft User Number: 6712
RunCode: 2013-03-18T21:12:20-1 : 41
-Pae
3 of 24
•
•
•
WATER SIDE SYSTEM REQUIREMENTS Part 2 of 2 MECH-2C
Project Name
Date
Madison Guard House
3/18/2013
WATER SIDE SYSTEMS: Chillers, Towers, Boilers, H dronic Loops
Item or System Tags
(i.e. AC -1, RTU -1, HP -1)'
Number of Systems
Indicate Page Reference on Plans or Specification 2
MANDATORY MEASURES T-24 Sections
Equipment Efficiency 112 a
Pipe Insulation 123
PRESCRIPTIVE MEASURES
Cooling Tower Fan Controls 144(a & b
Cooling Tower Flow Controls 144(h)
Variable Flow System Design 144(h)
Chiller and Boiler Isolation 144
CHW and HHW Reset Controls 144
WLHP Isolation Valves 144'
VSD on CHW, CW & WLHP Pumps>5HP 144
DP Sensor Location 144
1. The proposed equipment need to match the building plans schedule or specifications. If a requirement is not applicable, put "N/A" in the column
next to applicable section.
2. For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification
section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column next to
applicable section.
Service Hot Water Pool Heating
Item or System Tags
DHWHeater
(i.e. WH -1, WHP, DHW, etc...)'
Number of Systems 1
Indicate Page Reference on Plans or Schedule
MANDATORY MEASURES T-24 Sections
SERVICE HOT WATER
Certified Water Heater 111, 113 a AO SMITH ELJF-06'
Water Heater Efficiency 113 b 0.95 EF"
Service Water Heating Installation 113(c) Controls Req.
Pipe Insulation 123 Required
POOL AND SPA ----- t
Pool and Spa Efficiency and Control 114(a) n1a
Pool and Spa Installation 114(b) n1a
n1a
Pool Heater - No Pilot Light 115 c
n1a
Spa Heater - No Pilot Light 115(d)
Pipe Insulation 123 n1a _
t. The Proposed equipment needs to match the building plans schedule or specifications. If a requi ent ii _not-appI ' I ,- rUTA"in the colu n
next to applicable section.
2. For each water heater, pool heater and domestic water loop (or groups of similar equipment) fill in the reference to t number and/or
specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "WA" in the
column.
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-03-18721:12:20 ID: Pae 14 of 24
0 0 0
MECHANICAL VENTILATION AND REHEAT
MECH-3C
Project Name
Madison Guard House
Date
3/18/2013
MECHANICAL VENTILATION 121 b 2
REHEAT LIMITATION (§144(d))
AREA BASIS
OCCUPANCY BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M N
Zone/System
Condition
Area
(ft2)
CFM
per
ft2
Min CFM
By Area
B X C
Number
Of
People
CFM
per
Person
Min CFM
by
Occupant
E X F
REQ'D
V.A.
Max of
D or G
Design
Ventilation
Air
CFM
50% of
Design Zone
Supply
CFM
B X 0.4
CFM / ftz
Max. of
Columns
H, J, K,
300 CFM
Design
Minimum
Air Transfer
Setpoint Air
Guard House
149
0.15
22
22
15
7
HVAC 1
Total
22
15
Totals
rn
Column I Total Design Ventilation Air
C i imum:ventil`ationratJ! per Section 121, Table 121-A.
E 1-11: sed -on fixed _4eat-or, tAe greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes
fors aces without fixed seating.
H '� �entilation'rAir (REQ'D V.A. is the larger of the ventilation rates calculated on an AREA BASIS or OCCUPANCY BASIS Column D or G).
I � � pp
st be3 eler th or ual to H or use Transfer Air column N to make u the difference.
t s L an CFM x 50%• or the design zone outdoor airflow rate per 121.
K l o d t ar a Col CFM / ft2; or
L MaxinfGt!o,'_' o Cs -H, J K, or 300 CFM
M This m Ist le hM equal to Column L and greater than orequal to the sum of Columns H plus N.
N ITransfer Air musrbep ` ided where the Required Ventilation Air (Column H) is greater than the Design Minimum Air (Column M). Where required, transfer air must be greater than or
e ual to the differ nib tween the Required Ventilation Air Column H and the Design Minimum Air Column M), Column H minus M.
Energypro5.1 by EnerqySoft ser Number., 6712 Run Code: 2013-03-18T21:12:20
ID:
Pae 15 of 24
0 0 0
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-5C
Project Name
Madison Guard House
Date
3/18/2013
CHILLER AND TOWER SUMMARY
PUMPS
Equipment Name Type
oty, Efficiency Tons
Pump
Ot . GPM BHP Control
DHW / BOILER SUMMARY
System Name Type
Vol.
Distribution City. Rated Input (Gals).
Energy Factor Standby Loss Tank Ext.
or RE or Pilot R -Value Status
AO SMITH ELJF-06' Small Elec.
Point of Use 1 5,120 6
0.95 n/a n/a New
MULTI -FAMILY CENTRAL WATER HEATING DETAILS
Hot Water Pump
Hot Water Piping Length ft
Control Ot . HP
Type
In Plenum Outside Buried Add 1/2" Insulation
CENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name Type
City. Out ut Aux. kW Efficiency
Output Efficiency Status
Carrier 25AHB618/FE4BNF018 Split DX
1 18,000 0.0 8.00 HSPF 17,500 15.0 SEER / 12.5 EER New
ii
r-. 1
�z.
CENTRAL TEM FAN -$UM „ARY
J� I
SUPPLY FAN RETURN FAN
S st ' Namea Fan Type
Economizer Type
CFM BHP CFM BHP
Carrier 2 E4d1 F:1B T Constant Volume
No Economizer
600 0.10 none
n
z
�
EnergyPro 5.1 by EnemySoft User Number: 6712
RunCode: 2013-03-18721:12:20
ID: Pae 16 of 24
174
•
ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV -MM
Project Name
Date
Madison Guard House
3/18/2013
DESCRIPTION
Building Envelope Measures:
§118(a): Installed insulating material shall have been certified by the manufacturer to comply with the California Quality
Standards for insulating material, Title 20 Chapter 4, Article 3.
§118(c): All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of
Sections 2602 and 707 of Title 24, Part 2.
§118(f): The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value
of no less than R-13 between framing members.
§117(a): All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed,
weatherstripped or otherwise sealed.
Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.2 of
§116(a) 1: window area,'0.3 cfm/ft.2 of door area for residential doors, 0.3 cfm/ft.2 of door area for nonresidential single doors
(swingingand sliding),and 1.0 cfm/ft.? for nonresidential double doors (swinging).
§116(a) 2: Fenestration U -factor shall be rated in accordance with NFRC 100, or the applicable default U -factor.
§116(a) 3: Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the
applicable default SHGC.
§116(b): Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be
weatherstripped (except for unframed glass doors and fire doors).
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONS UCTION
i
DATE r
EnemyPro 5.1 by Enem ySoft User Number., 6712 RunCode: 2013-03-18721:12:20 ID: Pae 17 of 24
•
C7
a
MECHANICAL MANDATORY MEASURES: NONRESIDENTIAL MECH-MM
Project Name
Date
Madison Guard House
3/18/2613
Equipment and System Efficiencies
§111:
Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply
with the applicable standard.
§115(a):
Fan type central furnaces shall not have a pilot light.
§123:
Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC
equipment, shall be insulated in accordance with Standards Section 123.
§124:
Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of
the CMC Standards.
Controls
-
§122(e):
Each space conditioning system shall be installed with one of the following:
1A.
Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not
explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an
accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch
shall be capable of programming different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or
1 B.
An occupancy sensor to control the operating period of the system; or
IC.
A 4 -hour timer that can be manually operated to control the operating period of the system.
2
Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the
system as required to maintain a setback heating and/or a setup cooling thermostat setpoint.
Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000
§122(8)'
square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided
with isolation devices, such as valves or dampers that allow the supply of heating or cooling to be setback or shut off
independently of other isolation areas; and shall be controlled by a time control device as described above.
§122(c):
Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to
authorized personnel.
§122(b):
Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the
heating load can be met by the heat pump alone
Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the
zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the
§122(a&b):
control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be
capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
Ventilation
§121(e):
Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified
on these plans.
§122(f):
All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all
openings to the outside, except for combustion air openings.
Ventilation System Acceptance. Before an occupancy permit is granted for a newly constructed building or space, or a
§121(f):
new ventilating system serving a building or space is operated for normal use, all ventilation systems serving the
building ors ace shall be certified as meeting the Acceptance Requirements for Code Compliance
Service Water Heating Systems
§113(c)
Installation
3.
Temperature controls for public lavatories. The controls shall limit the ou IettTempe at re fb AOQF
2
Circulating service water -heating systems shall have a control capable o _ dyfnaattiealutgrn�n�cAgff i `,e �`ir�u� r� pu p
when hot water is not required. U __
I
FOR CONST CTION
I
DATE _B
Ene Pro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-03-18T21:12:20 ID: Pae 18 of 24
a
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Madison Guard House
Date
3/18/2013
System Name
HVAC 1
Floor Area
149
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 147
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 15
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
Sensible Latent CFMSensible
2,813 231 269
0
141
0
662 369 15
0
141
3,756F 600
PEAK
Heating System
Output per System 18,000
4,521
Total Output Btuh 18,000
Output Btuh/s n 120.8
226
Cooling System
0
Output per System 17,500
724
Total Output Stuh 17,500
0
Total Output ons 1.5
226
Total Output Btuh/s ft 117.4
Total Output s ft/Ton 102.2
5,697
Air System
CFM per System
600
HVAC EQUIPMENT SELECTION
Airflow cfm
600
Carrier 25AHB618/FE413NF018
12,405 1,732
11,242
Airflow cfm/s ft 4.03
Airflow cfm/Ton
411.4
Total Adjusted System Output
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
12,405 1,732 1 11,242
F Jul 3 PM F Jan 1 AM
Outside Air % 2.5%
Outside Air cfm/s ft 0.10
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
260F 71 OF
Outside Air
15 cfm Supply Fan
600 cfm
72 OF
71 OF 88 OF
Heating Coil
880F
ROOM
720F
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Coolin`'PeEA t
TA
j
112178°F 71159 OF 71 /59°F 52/51 °F
j
Outside Air i
15 cfm Supply Fan Cooling Coil/
600 cfm
70158 OF
r
�l,.tl T Vt
BUILDING & SAFETY DEPT.
�;� '� 1-
`�' N TRAr U 10
51 OF
Z ........... :..............
C ",TEC.5- MM
70/ 58 °F
EnergyPro 5.1 by EnergySoR User Number: 6712 RunCode: 2013-03-18721:12:20
ID: Page 19 of 24
ZONE •AD SUMMARY
• .
Madison. -
..
311812013
System Name
�HV
Roor Area
•, •.D SUMMARY
COOLING
ZONAL SYSTEM
MW
TOTALS ���® ��
•
EM V.-iWIffly .;
2013-03-18T21:12:20
20.
r�
L
•
ROOM LOAD SUMMARY
Project Name Date
Madison Guard House 3/18/2013
System Name Floor Area
HVAC 1 149
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible I Latent CFM I Sensible Latent CFM I Sensible
Guard House Guard House 1 .1 1 1471 Z8131 231 1471 2,813 2311 2691 4,521
PAGE TOTAL
TOTAL'
147
2,813
231
269
4,521
147
2,813
231
269
4,521
' Total includes ventilation load for zonal systems.
EnergyPro 5.1 by EnemySoft User Number: 6712 RunCode: 2013-03-18721:12:20 ID: Page 21 of ZU
I 1 1 a
•
ROOM HEATING PEAK LOADS
Project Name
Madison Guard House
Date
3/18/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guard House
Floor Area 149.0 R2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U -Value
AT °F Btu/hr
46 = 151
46 = 1,134
46 = 1,490
46 = 1,746
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
-
bot J
~ -
P U
OR CO =
ge 4,5 1
B
46 = 0
OT
R-38 Roof(R.30.2x 14.16)
149.0
X
0.0220 X
R-19 Wall (W. 19.2x 6.16)
333.0
X
0.0740 X
Double Non -Metal
81.0
X
0.4000 X
Slab -On -Grade
perm = 52.0
X
0.7300 X
X
X
x
X
X
X
X
X
X
X
X
X
X
x
X
X
X
X
X
x
X
X
X
X
X
x
x
X
X
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
I , %XT -
X
x
�.Xa �
x
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 149 X
Area
x
xF
to another room 1
.
8.00 x 0.0.00.
Ceiling Height ACH
TOTAL HOURLY HEAT LOSS FOR ROOM 4,521
Energ Pro 5.1 by Energ Soft User Number.- 6712 RunCode: 2013-03-18721:1220 ID: Page 22 of 24
i4 I , 4
C]
0
ROOM COOLING PEAK LOADS
Project Name
Date
Madison Guard House
3/18/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guard House
Time of Peak
Jul 3 PM
Floor Area 149.0 ft'
Outdoor Dry Bulb Temperature
112 OF
Indoor D Bulb Temperature 70 OF
Outdoor Wet Bulb Temperature
78 OF
Conduction Area U -Value DETD'
Btu/hr
R-38 Roof(R,30.2x14.16) .149.0 X 0.0220 X
32.8 =
107
R-19 Wall (W, 19.2x6.16) 64.0 X 0.0740 X
35.6 =
169
R-19 Wall (W, 19.2x6.16) 101.0 X 0.0740 X
35.5 =
266
Double Non -Metal 63.0 X 0.4000 X
32.7 =
825
R-19 Wall (W. 19.2x 6.16) 46.0 X 0.0740 X
35.5 =
121
Double Non -Metal 18.0 X 0.4000 X
32.7 =
236
R-19 Wall (W, 19.2x6.16) 122.0 X 0.0740 X
36.3 =
327
X X
=
X X
=
Page Total
2,051
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Weighting
Solar Gain Orientation Area SGF SC
Factor
Btu/hr
Window (E) 42.0 X 0 X 0.323 X
0.000 =
25
Window (S) 9.0 X 0 X 0.323 X
0.000 =
5
Window (S) 9.0 X 0 X 0.323 X
0.000 =
5
Window (K9 21.0 X 0 X 0.323 X
0.000 =
107
X X X
=
X X X
=
X X X
=
X X X
=
X X X
=
Page Total
143
Sched.
Weighting
Internal Gain Frac. Area Heat Gain
Factor
Btu/hr
Lights 1.00 X 149 X 0.000 Watts/Sgft X 3.413 Btu/Watt
X 0.000 =
0
Occu ants 1.00 X 149 X 245 Btu/occ. / 100 Sqft/OCC.
X 1.000 =
365
Receptacle 1.00 X 149 X 0.500 Watts/Sgft X 3.413 Btu/Watt
X 1.000 =
254
Process 1.00 X 149 X 0.000 Watts/Sgft X 3.413 Btu/Watt
X 1.000 =
0
Process htin 1.00 X 149 X 0.000 Watts/Sgtt X 3.413 mBtuMlatt-"X
Li
0
0
lay OF L
Infiltration: 1.00 X 1.064 X 149 X X /
�0 0 0 001
c3(i
0
Height 1ACH'O
Schedule Air Sensible Area Ceiling Height 'ACFi' J
p
Fraction t'\
f -1O
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM ;`,-;
STNn72
8 3
Sched.
Latent Gain Frac. Area Heat Gain
Btu/h
Occupants 1.00 X 149 X 155 Btuh/oC� .U�/T
Receptacle 1.00 X 149 X 0.000 Watts/S ft
u tt =
0
Process 1.00 X 149 X 0.000 Watts/Sgft X 3.413
u aft =
0
Infiltration:[ 1.00 X 4,771 X 149 X 8.00 X 0.00 /60]
X 0.00000 =
0
Schedule Air Sensible Area Ceiling Height ACH
AW
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
231
EnergyPro 5.1 by EnemySoft User Number: 6712 RunCode: 2013-03-18721:12:20 ID:
Page 23 of 24
e , .
•
s
ROOM COOLING COIL LOADS
Project Name
Date
Madison Guard House
3/18/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guard House
Time of Peak
I
Jul 3 PM
Floor Area
149.0 ft'
Outdoor Dry Bulb Temperature
112 OF
Indoor Dry Bulb Temperature
70 OF
Outdoor Wet Bulb Temperature
78 OF
Conduction
Area U -Value DETD'
Btu/hr
R-38 Roof(R.30.2x 14.16)
149.0 X 0.0220 X
32.8 =
107
R-19 Wall (W. 19.2x6.16)
64.0 X 0.0740 X
35.6 =
169
R-19 Wall (W. 19.2x6.16)
101.0 X 0.0740 X
35.5 =
266
Double Non -Metal
63.0 X 0.4000 X
32.7 =
825
R-19 Wall (W. 19.2x6.16)
46.0 X 0.0740 X
35.5 =
121
Double Non -Metal
18.0 X 0.4000 X
32.7 =
236
R-19 Wall (W. 19.2x6.16)
122.0 X 0.0740 X
36.3 =
327
X X
=
X X
=
Page Total
2,051
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Weighting
Solar Gain Orientation
Area SGF SC
Factor
Btu/hr
Window (E)
42.0 X 0 X 0.323 X
0.000 =
25
Window (S)
9.0 X 0 X 0.323 X
0.000 =
5
Window (S)
9.0 X 0 X 0.323 X
0.000 =
5
Window (W)
21.0 X 0 X 0.323 X
0.000 =
107
X X X
=
X X X
=
X X X
=
X X X
=
X X X
=
Page Total
143
Sched.
Weighting
Internal Gain Frac. Area
Heat Gain
Factor
Btu/hr
Lights 1.00 X 149
X 0.000 Watts/Sgft X 3.413 Btu/Watt
X 0.000 =
0
Occupants 1.00 X 149
X 245 Btu/occ. / 100 Sgft/occ.
X 1.000 =
365
Receptacle 1.00 X 149
X 0.500 Watts/Sgft X 3.413 Btu/Watt
X 1.000 =
254
Process 1.00 X 149
X 0.000 Watts/Sgft X 3.413 Btu/Watt
X 1.000 =
0
Process Lighting 1.00 X 1 149
X 1 0.000 Watts/Sgft X 3.413 Btu/Watt
X1 0.000 =
0
�•
T
[OOC�O��
Infiltration: 1.00 X 1.064
X 149 X 8.00 X �' (0.00 %'6D�
ig
0
Schedule Air Sensible
Area Ceiling Height ; SACH j GJJL
Fraction
.A
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM (_
813
Sched.
FOR CO
S
Latent Gain Frac.
Occupants 1.00 X
Area Heat Gain /'
149 X 155 Btuh/OCC. �'/
CC. =
B u/hr
231
B
Receptacle 1.00 X 149 X 0.000 Watts/Sgft= - -34t
=
0
Process 1.00 X
149 X 0.000 Watts/Sgft X 3.413
Btu/Watt =
0
Infiltration:[ 1.00 X 4,771
X 149 X 8.00 X 0.00 /60]
X 0.00000 =
0
Schedule Air Sensible
Area Ceiling Height ACH
pW
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
231
EnergyPro 5.1 by EnemySoft User Number; 6712
RunCode: 2013-03-18721:12:20 /D:
Page 24 of 24