BSOL2015-022278-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
c&t1t 4 ZP Qu&A
COMMUNITY. DEVELOPMENT DEPARTMENT
BUILDING PERMIT
65
VOICE (760) 777-7125
FAX (760) 777-7011
INSPECTIONS (760)'777-7153
Application Number:
BSOL2015-0222
Owner:
Property Address:
54200 AFFIRMED CT CT
STUART HELLERBRAND
AP N:
767780077
54200 AFFIRMED CT
Application Description:
HELLERBRAN D/16.2kW PV SYSTEM - (58) 28OW PANELS/(2) INVERTER
LA QUINTA, CA 92253
Property Zoning:
Application Valuation:
$56,000.00
Applicant: LDEC
Contractor:
HIRAM CONSTRUCTION HIRAM CONSTRUCTION
20240 EAST ARROW HWY O 4 2015U 20240 EAST ARROW HWY
COVINA, CA 91724 COVINA, CA 91724
OF LAOUINTA
EVELOPMENTDEPARTMENT (626)6.73-7704
LIC. No.: 977138
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter
9 (commencing with Section 7000) of Division 3 of the Business and Professions Code,
and my License is in full force and effect.
License Class: B C10�?,/,��'ontractor:
cense No.: 977 38
tDate: rof`M�4 1i ll
OWNER -BUILDER DECLARATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State
License Law for the following reason (Sec. 7031.5, Business and Professions Code: Any
city or county that requires a permit to construct, alter, improve,. demolish, or repair
any structure, prior to its issuance, also requires the applicant for the permit to file a
signed statement that he or she is.licensed pursuant to the provisions of the
Contractor's State License Law (Chapter 9 (commencing with Section 7000) of Division
3 of the Business and Professions Code) or that he or she is exempt therefrom and the
basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a
permit subjects the applicant to a civil penalty of not more than five hundred dollars
($500).:
(1 I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for sale.
(Sec. 7044, Business and Professions Code: The Contractors' State License Law does not
apply to an owner of property who builds or improves thereon, and who does the work
himself or herself through his or her own employees, provided that the improvements
are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner -builder will have the burden of proving that
he or she did not build or improve for the purpose of sale.).
(� 1, as owner of the property, am exclusively contracting with licensed contractors
to construct the project. (Sec. 7044, Business and Professions Code: The Contractors'
State License Law does not apply to an owner of property who builds or improves
thereon, and who contracts for the projects with a contractor(s) licensed pursuant to
the Contractors' State License Law.).
( I I am exempt under Sec. . B.&P.C. for this reason
Date:
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for
the performance of the work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's
Lender's
Date: 12/4/2015
WORKER'S COMPENSATION DECLARATION -
I hereby affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self -insure for workers'
comp ns n, as provided for by Section 3700 of the Labor Code, for the performance
of t for which this permit is issued.
I
and will maintain workers' compensation insurance, as required by
Secti 3700 of the Labor Code, for the performance of the work for which this permit
is issued. My workers'.compensation insurance carrier and policy number are:
Carrier: _ Policy Number:
I certify that in the performance of the work for which this permit is issued, I
shall not employ any, person in any manner so as to become subject to the workers'
compensation laws of California, and agree that, if I should become subject to the
workers' compensation rovisions of Section 3700 of the Labor Code, I shall forthwith
comply with th ae pro isions.e/
Date: (u "( Applicant: ��
WARNING: FAILU E TO SECURE WORKERS' COMPENSATIO OVERAGE IS WFUL,
AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO
ONE HUNDRED THOUSAND DOLLARS ($100,000). IN ADDITION TO THE COST OF
COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE,
INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT: Application is hereby made to the Building Official for a permit subject to
the conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose
request and for whose benefit work is performed under or pursuant to any permit
issued as a result of this application , the owner, and the applicant, each agrees to, and
shall defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and
employees for any act or omission related to the work being performed under or
following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is
not commenced within 180 days from date of issuance of such permit, or cessation of
work for 180 days will subject permit to cancellation.
I certify that I have read this application and state that the above information is correct.
I agree to comply with all city and county ordinances and state laws relating to building
construction, and hereby authorize representatives of this city to enter upon the
above -mention d pr ertyPr inspection purposes.
Date: �� �I Signature (Appy ant or Agent): �L/
FINANCIAL e• e
4s YES l 4 }' . { Y-:dY. '.t R.. Y X 's"°'.;u✓' `Y:X'Hp?�g..Ylr`"Si $$'iT'^::✓,Ti
u�y Y 5 `;:DESCRIPTION u TY AMOUNT Y r
f A04. D',?AID:DATE
> .11, 3 F _SPA x
d>�.S.i..�.>x-,-.,..ti r,P�1':�..':t%. Et:w�, :�-.:"v.:'�b s;`a>. wf�, d. 3.ktF a•,> .�`.a. �{'� �,{n
BSAS SB1479 FEE 10170000-20306
0.' $3.00. $0.00
ry ,N vYS:, v q y R4 "'.k. T 8F' ' : S3 ifi'AC'>AyX-.i.x.:—✓:'".-Y%ei "3- &
PAIUBY� ` ' METHOD H
.... "M"Y:f4rc
RECEIPT #b *�' CHECK #CLTD BY
•.. '�4 .�-.: r .. �,.._s .. u.SX� es _v<,a., .., 7e,, m� xa�.., .3..._.."...,... ,..,: `.CaS'fN,r.rS°ik..�i. i.n..
X%'.�c.r .>"u w_"v.,,,.,.:...«:.e..'S. nxk'ES,wJ:s.:t'....r.j.�'J�flF... :.Yi>,LiS.,,...�.'K...... :Y. <.,. fir'-.t*6' �_.&_w.,
Total Paid for BUILDING STANDARDS ADMINISTRATION BSA: $3.00 $0.00
<:1,Y�. 'K-4, d&i
r
'.yr+ -�Yd` q"°.^ y rc5 `v"big4E t.5%Zawe.T >
`QNAMOUNTDPAIQXDATE
{.'"a..:.
i'E S ..�Tis�" fi5-
DESCRIrPTIONyih �r��ACCOUNT��
'"
PV SYSTEM - ARRAY, FIRST 20
101-0000-42403
0 $24.17
$0.00
'?:."4.''X3
a y;r PAID BY
'y�. METHODaa
��RECEIPT#jCLTD
BY
gg
�. +`I;y:.Y.��.T.E:.IO
$."'f
O¢UNTbPAIDY%
iY:
wi
AUA
4TY�'AM
PAID`DATE,
PV SYSTEM -ARRAY, FIRST 20 PC
101-0000-42600
0
$24.17
$0.00
1 : E '.. a} > %
�2 PAID BY h?
F"'{,4•'.1'ce '�' #-<:2avy 'C>
>METIiOD,RECEIPT#y
t :y'
CHECK,#up
x p-.,
CLTUBYk
: .r zi
�.a:Ha3r•,..�., .�fr1�i.{E�'aw>.,,..w,.
.r....,','•`�ruSBz>5:...:.r«:cA,.m..c."ie..3,w.-.,-.'R,_�sa,
5;:�,�zF-u��.'�k;,,,,.:
n.a, `Y,r�.r...zt6:
M�:fi. H�':e:
D
k`iwl!i�I 'P
_U
Ll—
PhAksI-,DJ� vDs.AT34EE
PV SYSTEM - MISCEQUIPMENT
101-0000-42403
0
$48.34
$0:00
p5.uk„`R`>s^SE'.Y:
RECEIPT #
CHECK # =E'CLTD
BY
SEMETHOD'�
'
i,f'.:
DESCRIPTION :, �
h . .aYdT .-SvS'k"° Y >'
ACCOUNTS` a €
QTY'
�x$ ANIIOUNT�
f � PAID
,; .{
�i.-'.`=�2".4ia.n'xa"�'a'sSS
,AID,DATEA
PV. SYSTEM - MISC EQUIPMENT PC
'101-0000-42600 >
0,
$4834 ""
$0.00
(
N,q3,..2`E}uCi^EhI.'SPi :;'t,.'bY4tSkIY':^r
--------------
Eh..ia.'
:e'*,�id�
£.
o'CKBY
Total Paid for ELECTRICAL: $145.02 $0.00
y
DE
b
CAC
AMOUNT
:)•
RATPAIDPAIODSCR"IPTON;k
... -'r".,•. F k','k.:l 9'%a...?., .T•:4 .rFdk
y'
..... r9 't rkd^.. $-.
.'irS4
xYD.. Y..;T'.... ,.. ,A:t-�'-si :
s.d�i;c.r'(d m�.,^.:.R.'A4'�? s, «}?..Ghzi
PERMIT ISSUANCE
101-000042404
0
$91.85
$0.00
x:. arRE'
} METHOD
CEIPT
HEC #`
LTD B
,. a �MPAID.BY N ;z riz
:, ..wt
rs
Total Paid for PERMIT ISSUANCE: $91.85 $0.00
Description: HELLERBRAND/16.2kW PV SYSTEM - (58) 280W PANELS/(2) INVERTER
Type: SOLAR Subtype: Status: APPROVED
Applied: 11/6/2015 SGU
Approved:
Parcel No: 767780077 Site Address: 54200 AFFIRMED CT CT LA QUINTA,CA 92253
Subdivision: TR 32879 Block: Lot: 300
Issued:
Lot Sq Ft: 0 Building Scl Ft: 0 Zoning:
Finaled:
Valuation: $56,000.00 Occupancy Type: Construction Type:
Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
NOTES
Details: 16.2kW SOLAR ARRAY - (58) 280W SOLARWORLD+SOLAREDGE P300 OPTIMIZERS W/ (1) SOLAREDGE SESOOOA-US-ZB-U-AFCI
INVERTER & (1) SOLAREDGE SE10000A-US-ZB-U-AFCI [870SF].100AMP LOAD CENTER & 175AMP MAIN BREAKER DERATE. 2013
CALIFORNIA ELECTRICAL CODE.
Printed: Friday, December 04, 2015 1:20:21 PM 1 of 3 J
UFIV SYSTEMS
ADDITIONAL
CHRONOLOGY
CHRONOLOGY TYPE,
STAFF. NAME
ACTION DATE COMPLETION DATE`
NOTES
PLAN CHECK PICKED UP
STEPHANIE GUMPERT
11/17/2015
11/17/2015
PLAN CHECK SUBMITTAL
STEPHANIE GUMPERT
12/4/2015
12/4/2015
RECEIVED
TELEPHONE CALL
LUIS URIBE
11/16/2015
11/16/2015
LEFT HAL A MESSAGE. 1ST REVIEW IS COMPLETD AND
CORRECTIONS ARE REQUIERD
SPOKE WITH DIL, DILL SENT ME A SET OF REVISED PLANS VIA
EMAIL, SHE ASKED IF I COULD LOOK THEM OVER BEFORE THE
HARD COPY ARE SENT. ADJUSTMENT FACTOR NEEDS TO BE
TELEPHONE CALL
LUIS URIBE
11/30/2015
11/30/2015
CORRECTED FOR #4 WIRE( CURRENT EXCEEDS WIRE RATING
AFTER TEMP CORRECTION FACTOR). ALSO LOAD CALCS ARE
MISSING FOR BREAKER DOWNGRADE. DIL SAID TO GIVE HER
SOME TIME AND SHE WILL SEND IN A NEW REVISED PLAN
SET.
CONDITIONS
Printed: Friday, December 04, 2015 1:20:21 PM 1 of 3 J
UFIV SYSTEMS
NAME TYPE
NAME
FINANCIAL
INFORMATION
DESCRIPTION
ACCOUNT_ QTY
AMOUNT
PAID
ADDRESSI
CONTACTS
CITY
STATE
ZIP
PHONE
FAX
EMAIL
APPLICANT
HIRAM CONSTRUCTION
20240 EAST ARROW
HWY
COVINA
CA
91724
$0.00
BSA:
CONTRACTOR
HIRAM CONSTRUCTION
20240 EAST ARROW
HWY
COVINA
CA
91724
$0.00
OWNER
STUART HELLERBRAND
54200 AFFIRMED CT
LA QUINTA
CA
92253
PARENT PROJECTS
Printed: Friday, December 04, 2015 1:20:21 PM 2 of 3 CI?
SYSTEMS
FINANCIAL
INFORMATION
DESCRIPTION
ACCOUNT_ QTY
AMOUNT
PAID
CLTD
PAID DATE RECEIPT# CHECK 4 METHOD PAID BY
BY
BSAS SB1473 FEE
101-0000-20306 0
$3.00
$0.00
Total Paid for BUILDING STANDARDS ADMINISTRATION
$3.00
$0.00
BSA:
PV SYSTEM - ARRAY,
101-0000-42403
0
$24.17
$0.00
FIRST 20
PV SYSTEM - ARRAY,
101-0000-42600
0
$24.17
$0.00
FIRST 20 PC
PV SYSTEM - MISC
101-0000-42403
0
$48.34
$0.00
EQUIPMENT.
PV SYSTEM - MISC
101-0000-42600
0
$48.34
$0.00
EQUIPMENT PC
Total Paid for ELECTRICAL:
$145.02 •
$0.00
PERMIT ISSUANCE
101-0000-42404
0
$91.85
$0.00
Total Paid for PERMIT ISSUANCE:
$91.85
$0.00
TOTALS:
PARENT PROJECTS
Printed: Friday, December 04, 2015 1:20:21 PM 2 of 3 CI?
SYSTEMS
REVIEW TYPE
REVIEWER
SENT DATE
DUE DATE
RETURNED
"STATUS
REMARKS
NOTES
DATE
NON-STRUCTURAL -
LUIS URIBE
11/6/2015
11/16/2015
11/16/2015
REVISIONS REQUIRED
1 WK
1ST BLDG NS (1 WK)
LUIS URIBE
12/4/2015
12/11/2015
12/4/2015
APPROVED
Printed: Friday, December 04, 2015 1:20:21 PM 3 of 3
CRWSYSTEMS
Bin #
Permit #f
0222.
Prgject Address:
Qty of La Quinto
Building u Safety Division
. _ 78-495 Calle Tampico
La Quinta, CA 92253 - (760) 777-7012
Building Permit Application and Tracking Sheet
v/ .0wner's Name: r 6 e al'_
A. P. Number:
Address: ��►�
cJ
Legal Description:City,
�ST, Zip: (w
Contract r /r
o. U u
c
T h
ele one:
P
Address:
��
Project Desc iption: r d r
�.
/1
City, ST, Zip: ut(AO\ 0 p / � 7 P/%
G
h ne n
Telephone:
P /
v Cf � N�
� S
State Lic.# :
_
City Lie.• #;
(/1 (A�o/
Arch., Engr., Designer: c t
Address: D a
, J
City, ST, Zip: .447
r�
c •Construction TYPe:TelePhone: l
Occupancy:
Lic.
n NAddn Alter Re air
ProJect Pe�cir le
tY
oState
De m
Name of Contact Person:
A (,
Sq. Ft.:
# Stories:
# Units:
Telephone # of Contact Person:"
( 7
Estimated Value of Project:
APPLICANT: DO NOT WRITE BELOW THIS LINE
tl
Submittal
Req'd
Rec'd
TRACKING
PERMIT FEES
Plan Sets
Plan Check submitted
Item
Amount
Structural Calcs.
Reviewed, ready for corrections
Plan Check Deposit
Truss Cates.
Called Contact Person
Plan Check Balance
Title 24 Calcs.
Plans picked up
Construction
Flood plain plan
Plans resubmitted
Mechanical
Grading' plan
2°' Review, ready for corrections/issue
Electrical
Subcontactor.List
Called Contact Person
Plumbing
Grant Deed
Plans picked up
S.M.I.
II.O.A. Approval
Plans resubmitted
Grading
IN ROUSE:-
'"' Review, ready for corrections/issue
Developer Impact Fee
Planning Approval
Called Contact Person
A.I.P.P.
Pub. Wks. Appr
Date of permit issue
School Fees,
Total Permit Fees
PV SYSTEM: 58 X 280 W = 16.24 KW (DC)
1 AERIAL VIEW
SCALE:N.T.S.
CITY OF LA QUINTA
BUILDING & SAF��®PT.
A,PPRO
FOR CONSTRUCTION
-/- BY �-
DATE
SHEET INDEX:
A-1 GENERAL NOTES, SHEET INDEX,
BUILDING DATA, PROJECT DATA,
A-2 EXISTING SITE CONDITION
A-3 ROOF PLAN - SOLAR PANEL LAYOUT
E-1 SINGLE LINE DIAGRAM
E-2 WARNING NOTES
E-3 EQUIPMENTS: PV MODULE
SPECIFICATION` SHEET
E-4 EQUIPMENTS: INVERTER
SPECIFICATION SHEET
S-1 EQUIPMENTS: UNIRAC
SPECIFICATION SHEET
Ai
CODE AUTHORITY:
1111.1111111-1
2 VICINITY PLAN
SCALE: N.T.S
2013 CALIFORNIA RESIDENCIAL BUILDING CODE
2013 CALIFORNIA ELECTRICAL CODE
2013 CALIFORNIA MECHANICAL CODE
2013 CALIFORNIA PLUMBING CODE
2013 CALIFORNIA FIRE CODE
2013 CALIFORNIA ENERGY CODE
2013 CALIFORNIA GREEN BUILDING CODE
2013 LA QUINTA MUNICIPAL CODE
16.24 KW (DC) PV SYSTEM
54200 AFFIRMED CT
LA QUINTA, CA 92253
PHOTOVOLTAIC NOTES:
1. AN INVERTER OR AN AC MODULE IN AN INTERACTIVE PHOTOVOLTAIC
SYSTEM SHALL AUTOMATIC CALL DE -ENERGIZE ITS OUTPUT TO THE
CONNECTED ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON
LOSS OF VOLTAGE IN THAT SYSTEM AND SHALL REMAIN IN THAT STATE
UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE
HAS BEEN RESTORED (NEC 690361)
2. ALL EXTERIOR ELECTRICAL METALLIC TUBING(EMT) CONDUIT FITTING
SHALL BE RAINTIGHT THREADLESS COMPRESSION TYPE.
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED
4. NAMEPLATES SHALL BE PROVIDED FOR ALL CIRCUITS IN THE SERVICE
DISTRIBUTION AND POWER DISTRIBUTION SWITCH BOARDS, PANEL BOARDS,
DISCONNECTING SWITCHES, TERMINAL CABINETS, ETC. ALL NAMEPLATES
SHALL BE PERMANENTLY ATTACHED AND BE OF SUFFICIENT CAPACITY TO
WITHSTAND THE WEATHER.
5. JUNCTION BOX/COMBINER BOX HAVE TO USE COMPRESSION TYPE STRAIN
RELIEF POSITIONED FOR APPROPRIATE WATER RUN OFF.
6. CONDUIT RUNS SHALL BE PROVIDED WITH SUFFICIENT WEATHERPROOF
PULL BOXES OF JUNCTION BOX/COMBINER BOXES PER APPROPRIATE NEC
REQUIREMENTS.
7. SEE PROVIDED CUT SHEETS FOR ADDITIONAL EQUIPMENT SPECIFICATIONS
8. WIRING MATERIALS SHALL BE SUITABLE FOR THE SUN EXPOSURE AND WET
LOCATIONS. FIELD APPLIED PROTECTIVE COATINGS ARE NOT ACCEPTABLE.
9. JUNCTION, PULL AND OUTLET BOXES LOCATED BEHIND MODULES SHALL BE
SO INSTALLED THAT THE WIRING CONTAINED IN THEM CAN BE RENDERED
ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF MODULE(S) SECURED BY
REMOVABLE FASTENERS AND CONNECTED BY A FLEXIBLE WIRING SYSTEM.
(NEC 690.34)
10. IN AN UNDERGROUND PHOTOVOLTAIC SYSTEM, THE POWER SOURCE
SHALL BE LABELED WITH THE FOLLOWNIG WARNING AT EACH JUNCTION
BOX, COMBINER BOX, DISCONNECT AND DEVICE WHERE THE UNGROUNDED
CIRCUITS MAY BE EXPOSED DURING SERVICE: " WARNING - ELECTRIC SHOCK
HAZARD. THE CURRENT CIRCUIT CONDUCTORS OF THIS PHOTOVOLTAIC
POWER SYSTEM ARE UNGROUNDED BUT MAY BE ENERGIZED WITH THE
RESPECT TO GROUND DUE TO LEAKAGE PATHS AND/OR GROUND FAULTS."
(NECE 690.35(F))
11. ALL PHOTOVOLTAIC MODULES AND ASSOCIATED EQUIPMENT AND WIRING
MATERIAL SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE.
12. ALL ELECTRICAL DEVICES AND UTILIZATION EQUIPMENT SHALL BE LISTED
BY AN APPROVED TESTING AGENCY. �
13. NOTIFY SERVING UTILITY BEFORE ACTIVATION OF
fpfo
14. WHEN A BACKFED BREAKER IS THE METHOD OF UT
INTERCONNECTION, BREAKER SHALL NOT READ LINE AND V* .0
�IJ1
15. ALL WORK TO COMPLY WITH THE LATEST EDITION OF THE CAW_ ��MEi�
CODE AS AMENDED AND ADOPTED BY THE CITY. CION i7�""W
�o
REVISION
DATE NO
11/18/2m5 ,
Q
Lu
a
J w�
U
I-- Q In
_ f— W J
CL >
Q a =
0o U 0 p
o Z
Z Q
Q J
U In
0
0 0
N
to
0
z
n U L0
m p N
W 01
LLJ J � U
Lu „` a
= Qz
� o C33
s
a
z "'
o�
v�
w
zwQ�
w ¢
w W A w
Lu
O
Lu
Lu
Lu
W (n U N
o� (31
_ � a
a
a a z
W
J Y ON CS
s
Z N Ln Q
U)
Dale:
10/11/2015
Scale:
AS NOTED
Drawn:
Y W KERING
sneer
Al
SOLAR PANEL INSTALLATION
(VIATATVf TTnkT TIT; T A TT
SUPPORT RAIL
Mid -Clamp
PANEL CONNECTOR SOLAR PANEL
UNIRAC ATTACHMENT HARDWARE O 48'
O.C. MAX SPANISH TILE ROOF
ROOF SHEATHING
ROOF 2 X 4 TRUSS AT 24'
O.C.
STAINLESS STEEL 5/16' OIA. x 3 1/2' LONG
TIE -DOWN LAG BOLT MIN 2 1/2' EMBED
AT 48' O.C. MAX
ARRAY INFORMATION
DATE
MODULE WEIGHT
39.5
LBS
MODULE LENGTH
I
I
Q/
I
I
I
I
I
I
I I
I I
I \1/
I I
I I
I I
I I
I I
I I
I
I
I d
I
I
I
I
I
I
I
I
Ed/
I
I
I
I
I
I
SOLAR PANEL
39.41'X65.94'
SUPPORT RAILS ROOF 2 X 4 TRUSS
OAT 24' O.C.
Mid -Clamp PANEL CONNECTOR O 40' O.C.,
X UNIRAC ATTACHMENT HARDWARE O 48' O.C. MAX. SEE
SHEET S-1
SUPPORT RAIL
Mid -Clamp
PANEL CONNECTOR SOLAR PANEL
UNIRAC ATTACHMENT HARDWARE O 48'
O.C. MAX SPANISH TILE ROOF
ROOF SHEATHING
ROOF 2 X 4 TRUSS AT 24'
O.C.
STAINLESS STEEL 5/16' OIA. x 3 1/2' LONG
TIE -DOWN LAG BOLT MIN 2 1/2' EMBED
AT 48' O.C. MAX
ARRAY INFORMATION
DATE
MODULE WEIGHT
39.5
LBS
MODULE LENGTH
65.94
INCHES
MODULE WIDTH
39.41
INCHES
MODULE DEPTH
1.22
INCHES
TOTAL MODULES
58
E.A
TOTAL MODULE WT.
2291
LBS
TOTAL RAIL WT.
290
LBS
TOTAL INSTALLED WT.
2581
LBS
INSTALLATION AREA
1046.70
SQ.FT
DISTRIBUTED LOAD
2.47
LBS/SQ.FT
# OF CONNECT POINTS
116
E.A
POINT LOAD
22
LBS/POINT
SLOPE
9DEGREES
TRUSS SIZE
2 x 4 @ 24" O.0
C) O
M �
NOTE:
Z
* THE SOLAR SYSTEM HAS A DISTRIBUTED WEIGHT
LESS THAN 4PSF
* THE CONCENTRATED LOAD FOR EACH VERTICAL
SUPPORT IS LESS THAN 40 LBS
AFFIRMED CT
c
G
z
n
PL PL PL PL PL PL
e
�ZJI
REVISION
DATE
NO
11/18/2015 1
12/10/2015
Q
ch
w
C:) r,
Q
J
Lu 01
O
� Q
Cn J
5 O
Q
In
S I—
Lu
Q
m u
Q S
�, o
Z
O
ZQ
O O
C) O
M �
Z
Q
Of
u ' A
m
of
o Nt.
0 0\
LLJ
LIJ
J
of V
W
Q(
=
Q Z_
F__
o =)
x
N O
a
Z
� Q.
J a
3 �
o U)
Liz
7-
7-
z
x 0
xo
r W U
W
N
E
Lu
F �
N }
� N
0 N
LLJ U
O >
1: Q
} IL
(if U
Q
a
a z
LLLu
O
N
J Y
a
z �
Ln Q
� N
Date:
10/11/2015
Scale:
AS NOTED.
Drawn:
YW RISING
Sheet:
A2
GENERAL NOTES:
I. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED
2. ALL SPECIFIED WIRING IS BASED ON THE USE OF COPPER.
3. CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS AND SHALL
COORDINATE ALL INSPECTION, COMMISSIONING AND ACCEPTANCE WITH
THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED.
4. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL
BE AT THE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND
SHALL BE COORDINATED WITH OTHER TRADES.
5. IF DISTANCES OF CABLE RUNS ARE DIFFERENT THAN SHOWN, THE
CONTRACTOR SHALL NOTIFY ELECTRICAL ENGINEER TO VALIDATE THE
WIRE SIZE. FINAL DRAWINGS WILL BE RED -LINED AND UPDATED AS
APPROPRIATE.
6. WHENEVER A DISCREPANCY IN QUANTITY OF EQUIPMENT, ARISES ON
THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND
SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE
DRAWINGS OR IN THE SPECIFICATIONS TO ENDURE COMPLETE
COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY
THE ARCHITECT/ENGINEER.
7. ALL BROCHURES, OPERATION MANUALS, CATALOGS, SHOP DRAWINGS,
ETC. SHALL BE HANDED OVER TO THE OWNER'S REPRESENTATIVE AT THE
COMPLETION OR WORK.
8. ALL WIRING CONCEALED IN WALL AND CEILING SPACES SHALL BE IN
METAL CONDUIT.
9. THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS
SHALL BE IN ACCORDANCE WITH THE "SMACNA"-GUIDLINES FOR SEISMIC
RESTRAINS OF MECHANICAL SYSTEMS AND PLUMING PIPING SYSTEMS'
10. ALL OF THE LISTED SYSTEMS REQUIRED THAT THE SEISMIC LATERAL
FORCE F INCLUDING CONSIDERATION OF a^P AND r^P BE DETERMINED AT
EACH LEVEL OF THE BUILDING SO THAT BRACE SPACING CAN BE
CALCULATED. THE DISTRICT STRUCTURAL ENGINEER CAN APPROVE THE
SEISMIC LATERAL FORCE DETERMINATION.
11. A COPY OF THE CHOSEN BRACING SYSTEM(S) INSTALLATION
GUIDE/MANUAL SHALL BE ON THE JOB SITE PRIOR TO STARTING THE
INSTALLING OF HANGERS AND/OR BRACES.
12.WHEN INSTALLING DRILLED -IN ANCHORS AND/OR POWDER DRIVEN
PINS IN EXISTING NON -PRESTRESSED REINFORCED CONCRETE, USE CARE
AND CAUTION TO AVOID CUTTING OR DAMAGING THE REINFORCED BARS.
WHEN INSTALLING THEM INTO EXISTING PRESTRESSED CONCRETE
TENDONS BY USING A NON-DESTRUCTIVE METHOD PRIOR TO
INSTALLATION. EXERCISE EXTREME CARE AND CAUTION TO AVOID
CUTTING OR DAMAGING THE TENDONS DURING INSTALLATION. MAINTAIN
A MINIMUM CLEARANCE OF ONE INCH BETWEEN THE REINFORCEMENT
AND THE DRILLED -IN ANCHOR.
13. THE WORKING CLEARANCES AROUND THE EXISTING ELECTRICAL
EQUIPMENT AS WELL AS THE NEW ELECTRICAL EQUIPMENT WILL BE
MAINTAINED IN ACCORDANCE WITH NEC 110.26.
14. SPACING MUST BE MAINTAINED BETWEEN ANY PLUMBING SEWER
VENTS EXTENDING THROUGH THE ROOF AND THE UNDERSIDE OF THE
PHOTOVOLTAIC PANELS (6" MINIMUM RECOMMENDED).
15. SMOKE ALARMS AND CARBON MONOXIDE DETECTORS SHALL BE
LOCATED AS REQUIRED PER SECTIONS R314 & R315 WITHIN THE
CALIFORNIA RESIDENTIAL CODE (CRC).
16. SMOKE ALARMS SOLELY BATTERY OPERATED FOR THE
PHOTOVOLTAIC SYSTEM DOES NOT INVOLVE THE REMOVAL OF INTERIOR
WALL AND CEILING FINISHES INSIDE THE HOME.
17. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT
RESISTANT. (NEC 300.6 01, 310.8 D)
18. GROUNDING BUSHINGS ARE REQUIRED AROUND PRE -PUNCHED
CONCENTRIC KNOCKOUTS ON THE DC SIDE OF THE SYSTEM. (NEC 250.97)
19.THE GROUNDING ELECTRODE CONDUCTOR MUST BE PROTECTED FROM
PHYSICAL DAMAGE IF SMALLER THAN #6 COPPER WIRE. (NEC 250.64 B)
20. GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT
FOR SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT. (NEC
250.64 C)
21. RACEWAY FOR GROUNDING ELECTRODE CONDUCTOR SHALL BE
BONDED AT EACH END. (CEC 250.64 (E)
22. EQUIPMENT GROUNDING SHALL BE INSTALL AT EACH INDIVIDUAL
MODULE AT THE MANUFACTURES RECOMMENDED POINT OF
ATTACHMENT USING A LISTED LUG SUITABLE FOR THAT PURPOSE. (WITH
OR WITHOUT WEEB OR SHUCO CLIPS)
23. SOLAR ARRAY (TYPICAL) 4' ON CENTER ATTACHED TO ROOF W/ 5/16" LAGS.
MIN. 2 1/2" EMBED.
24. ALL CONDUIT THAT IS EXPOSED MUST BE PAINTED THE SAME COLOR
AS THE. HOUSE.
m
(n
r-
0
FIREPLACE
m
m
0
a
m
(E) SLOPE
EMT CONDUIT
TO BE RUN
INSIDE THE
ATTIC
COMBINER BOX TYP
J -BOX
O
m
N
r
O
a
m
SPANISH TILE ROOF
I EM CONDUIT
Y-0" MIN TOB RUN
INSIDE
TTIC
.J .J .J "'I "I .J .J J
11111111
EMT CONDUIT
TO BE RUN
INSIDE THE
ATTIC
NOTE: S1=STIRNG 1
AZIMUTH: 180 DEGREES S2=STIRNG 2
SLOP: 9 DEGREES
(E) BUILDING 3450 SQ. FT. S3=STIRNG 3
S4=STIRNG 4
S5=STIRNG 5
S6=STIRNG 6
PV SYSTEM: 58 X 280 W = 16.24 KW (DC)
MODEL: SOLARWORLD SW 280 MONO BLACK MODULES
PV PANEL, SEE SHEET E-3
INVERTER: (1) SOLAR EDGE SE5000A-US
(1) SOLAR EDGE SE1000OA-US (240V)
(58) SOLAR EDGE OPTIMIZER P300
SEE SHEET E-4
js
LEGEN D
/ t(S T
��/L SIS ►J
(E) SLOPE Ci -y OF L, OUINTA
BI JILDING & SAFETY DEPT.
APPR®u F-1)
FOR COINS
:::S]6
S6NOTE:
'AZIMUTH: 90
SLOP: 9`
(E) BUILDING 3450 SQ. FT.
N
(E) SLOPE
PV MODULE LAYOUT
1
SCALE: 3/32" = V-0"
SOLARWORLD SW 280 MONO BLACK
(65.94"X39.41 "X1.22")
®
DC DISCONNECT
0
INVERTER
®
LOAD CENTER
FAM
AC DISCONNECT
RACKING: UNIRAC RACKING, SEE S-1 ® MAIN SERVICE ELEC. PANEL
INSTALLATION GUIDE, SEE SHEET S-1 (E) EXISTING TO BE REMAIN
TRUSS: 2x4 @ 24" O.C.
REVISION
DATE
NO
11/18/2015
12/10/2015
a
F
N
O_
Lu
o
po 'o
Q
1011)
w 01o
�Q
QU)U
2 I-
C.7 E
w U)
�
Cl� Q
_J
Q 2
CO u
�7
oz
Q
Z
Q J
U
oO
0
Z
Q"0
UN
00
Of
N
a,
Lu
J
W
-
LL Q
_
az
�
o �
N C3
z =D
L0 Q
o U)
F
a
O
J
zz
�a
J
r tr. Q
O 1
�O
N
w
Lu V)UN
N >_
.o V)
o 01
CL
Ch U
u
K
LL Q
a z
LU
N C5
J L
�
Q
z
Z
Lr)
N
V)
Date:
10/11/2015
Scale:
AS NOTED
Drawn:
YW RISING
Sheet: .
A3_
PHOTOVOLTAIC SINGLE LINE DIAGRAM
(4)#10(USE-2) 3/4' EMT CONDUIT
(1)06 BARE COPPER GROUND
#10(USE-2) RATE 90 -F -40A (4)#1G(THWN-2)
TEMPERATURE DE -RATING 0104'F+3OF=0.71 (1)#8 COPPER GROUND
AMP - 9.71 X 1258 X 1252 -15.17 A #10(THWN-2) RATE 9OF-4OA
40AXO.71-28.4A > 15.17A TEMPERATURE DE -RATING 0104'F+3OF-0.71
OK TO INSTALL #10 (USE -2) AMP a 9.71 X 1257E X 125X - 15.17 A
40AXO.71-28.4A > 15.17A
OK TO INSTALL #10 (THWN-2)
9 -PC. STRING01
SOLARWORLD SW 280 MONO BLACK INVERTER
®• 'YARNING: PHOTOVOLTAIC (SESOOOA-US)
POWER SOURCE.* DC DISCONNECT
(AFCI) BY SOLAR EDGE
DC=/
9 -PC. STRING02
-
SOLARWORLD SW 280 MONO B
10 -PC. SIRING#5
®
J -BO%
GROUND
(18) SOLAR EDGE OPTIMIZER P300
BUSHING
(8)#10(USE-2)
(1)08 BARE COPPER GROUND
10 -PC. STRING03 #10(USE-2) RATE 90'F -40A
SOLARWORLD SW 280 MONO BLACK TEMPERATURE DE -RATING 0IOVF+30'F-O.71
AMP -9.71 X 125X 1258- 15.17A
40AXO.71=28.4A > 15.17A
• OK TO INSTALL #10 (USE -2)
10 -PC. STRING04
SOLARWORLD SW 280
MONO BLACK Q
®. .L.49�H I COMBINER 1
BOX WITH
(2) ES WEERVARNIS: PHOTOVOLTAIC (A DISC01
FUSES OWER SOURCE.' (AFCI) BY
3/4' EMT CONDOR
(3)18(THWN-2)
(1)08 COPPER GROUND
010 RATE 9OC - SSA
TEMPERATURE DE -RATING 0104'F a 0.91
MIP - 21 X125X- 26.25A
55A % 0.91 - 50.05 A > 26.25A
QOK TO INSTALL #8 THWN-2
'YARNING: PHOTOVOLTAIC
SOU
FUSIBLE l_ PAC
GROUND
BUSHING
GEC GROUND -7
'YARNING: PHOTOVOLTAICIl
POWER SOURCE.'
INVERTER
(SEt0000A-US)
MODULE INFORMATION PV STRING INFORMATION
MFR: SOLARWORLD SW 280 MONO BLACK NO. OF MODULES PER SERIES STRING 1,2 = 9
-
DC=
10 -PC. SIRING#5
Voc 39.5 V
i
SOLARWORLD SW 280 MONO SLAC
MAX.- 9.71 X 125% X 125% = 15.17 A
AC
®•
Imp = 9.07 A
MAX Voc FOR SYSTEM AT 32 'F = 39.5x9x1.14 = 405.27 V
BREAKER
GROUND
GROUND
DC TEMPERATURE derating = 0.71 (0 104 'F + 30 'F)
BUSHING
BUSHING
10 -PC. STRING#6
PV STRING INFORMATION
DC DISCONNECT RATING
SOLARWORLD SW 280 MONO BLACK
L1
NO. OF MODULES PER SERIES STRING 3.4.5.6 = 10
DISE SW RATING= 25A
3/4- EMT CONDUIT
MAX DISC VOLT= 600V
Vmp PER STRING= 36.59 X 9 = 329.31 V
(4)#10(THWN-2)
GEC GROUND
(1)#8 COPPER GROUND
00 U
(40) SOLAR EDGE OPTIMIZER P300
#10(THWN-2) RATE 9OF=404
DC TEMPERATURE derating = 0.71 (0 104 'F + 30 'F)
AC TEMPERATURE derating = 0.91 (0 104 'F)
MAX. 10' FROM MAIN
NOTE: OP - OPTIMIZER EACH SOLAR
70.71
Q AMP - 9.71 X 2 X 125X = 24.27 A
PANEL INSTALL WITH ONE OPTIMIZER
40AXO.71-28.4A > 24.27A_
.
MODULE INFORMATION PV STRING INFORMATION
MFR: SOLARWORLD SW 280 MONO BLACK NO. OF MODULES PER SERIES STRING 1,2 = 9
NOtE:
- 1OrOMT/ SYSTEM CDNDL ORS SHALL BE
WenVUO arm GJOIM1FD. THE MENS OF
O]ENTOD'ATON SH BE PEVUTTM BY SEPN TE
O]Lpt COODO, MWI GTAPE, TAGGMG OR
011R:xR APPROVED MEANS. THE P OF GROUPM
SHNl BE WBtE TB OR SOmAR WAS AT LEAST
ON CF ANA THEN AT OnERV NOT TO EXOEED SIX
(6) TEE (OEC 6SO.4(B))
NOTE:
-RQTOVOLTA EQUUMENT AND SSTD6 AND ALL
ASMATED WOIDWG AND Ol1ERl'OIMETfONS
S BE IN6TAllFD MY SY QUAUUF® PERSONS. -
(ON 690.1(m)
1-1/2' EMT CONDUIT
(3)03(THWN-2)
(1)08 COPPER GROUND
13 RATE 90'C - 1104
TEMPERATURE DE -RATING 0IOWF - 0.82
1104 % 0.82 = 80.2 A > 78.754 EXISTING 2254
MAIN SERVICE PANEL
UK TU lmbi� 13 imigim
IOGA LOADCENIER
Voc PER STRING= 39.5 X 9 - 355.5 V
ELECTRICAL DATA PER PANEL
Vmp PER STRING= 36.59 X 9 = 329.31 V
Voc 39.5 V
P 31.2 V
MAX.- 9.71 X 125% X 125% = 15.17 A
Isc 9.71 A
k1 -2P, 60A
Imp = 9.07 A
MAX Voc FOR SYSTEM AT 32 'F = 39.5x9x1.14 = 405.27 V
BREAKER
HEIGHT OF CONDUIT = 8', TEMPERATURE ADDER = 30 'F
F
a
N
DC TEMPERATURE derating = 0.71 (0 104 'F + 30 'F)
DISCONNECT'WARNING:
AC TEMPERATURE derating - 0.91 (0 104 'F)
Q
PV STRING INFORMATION
DC DISCONNECT RATING
W (T
L1
NO. OF MODULES PER SERIES STRING 3.4.5.6 = 10
DISE SW RATING= 25A
Voc PER STRING= 39.5 X 9 = 355.5 V
MAX DISC VOLT= 600V
Vmp PER STRING= 36.59 X 9 = 329.31 V
S H
MAX.= 9.71 X 125% X 125% = 15.17 A
MAX Voc FOR SYSTEM AT 32 'F = 39.5x9x1.14 = 405.27 V
00 U
HEIGHT OF CONDUIT = 8', TEMPERATURE ADDER 30 'F
DC TEMPERATURE derating = 0.71 (0 104 'F + 30 'F)
AC TEMPERATURE derating = 0.91 (0 104 'F)
MAX. 10' FROM MAIN
PER SECTION 690.53 #1
QAC
1 MODEL• DV 22 1R13
(A) RATED MAXIMUM POWER -POINT CURRENT (mppA)
Imax X # OF STRINGS = 9.07A X 2 = 18.14A
(8) RATED MAXIMUM POWER -POINT VOLTAGE (mppV)
C)
Vmax X # OF MODULES = 31.2V X 9 =280.8V
z
(C) MAXIMUM SYSTEM VOLTAGE
Q
39.5V X 9 X 1.14 = 405.27V
m
(D) SHORT CIRCUIT CURRENT
(
Isc X 1.25 = 12.13A
NOtE:
- 1OrOMT/ SYSTEM CDNDL ORS SHALL BE
WenVUO arm GJOIM1FD. THE MENS OF
O]ENTOD'ATON SH BE PEVUTTM BY SEPN TE
O]Lpt COODO, MWI GTAPE, TAGGMG OR
011R:xR APPROVED MEANS. THE P OF GROUPM
SHNl BE WBtE TB OR SOmAR WAS AT LEAST
ON CF ANA THEN AT OnERV NOT TO EXOEED SIX
(6) TEE (OEC 6SO.4(B))
NOTE:
-RQTOVOLTA EQUUMENT AND SSTD6 AND ALL
ASMATED WOIDWG AND Ol1ERl'OIMETfONS
S BE IN6TAllFD MY SY QUAUUF® PERSONS. -
(ON 690.1(m)
1-1/2' EMT CONDUIT
(3)03(THWN-2)
(1)08 COPPER GROUND
13 RATE 90'C - 1104
TEMPERATURE DE -RATING 0IOWF - 0.82
1104 % 0.82 = 80.2 A > 78.754 EXISTING 2254
MAIN SERVICE PANEL
UK TU lmbi� 13 imigim
IOGA LOADCENIER
DATE
NO
Y
OUT DOOR
W/1/1 -2P, 304
LOCKABLE
1
Q
k1 -2P, 60A
BREAKER
AC
F
a
N
DISCONNECT'WARNING:
PHOTOVOLTAI
Q
'o to
SOURCE.'
W (T
L1
I- Q
JQ
L2
1
S H
w U)
N
00 U
®
DISCONNECT WITHIN
SOl1ARE D
MAX. 10' FROM MAIN
Q O
QAC
1 MODEL• DV 22 1R13
SERVICE PANEL
1004 FUSIBLE
3/4' EMT CONDUIT
(3)#6(T4WN-2)
(1)#8 COPPER GROUND
#6 RATE 90'C - 75A
TEMPERATURE DE -RATING 0104'F a 0.91
AMP ; 42 X12570 52.SA
75A % 0.91 - 68.25 A > 52.5A
OK TO INSTALL #6 THWN-2
INVERTER RATING #1
SOLAR EDGE SE5000A-US INVERTER
• WITH INTEGRATED DC DISCONNECT (AFCI)
MAX DC VOLT RATING = 500V
DC MAX. INPUT CURRENT = 15.5A
AC MAX. OUTPUT APPARENT POWER = 5 KW
AC MAX. OUTPUT CURRENT = 21A
FREQUENCY OP. RANGE = 60 HZ
INVERTER EFFICIENCY - 98 %
MAX AC OCPD = 21 X125%= 26.25A
OCPD USED = 30 A BREAKER
INVERTER RATING #2
SOLAR EDGE SE1000OA-US INVERTER
WITH INTEGRATED DC DISCONNECT (AFCI)
MAX DC VOLT RATING = 500V
OC MAX. INPUT CURRENT = 30.5
AC MAX. OUTPUT APPARENT POWER =10KW
AC MAX. OUTPUT CURRENT = 42A
FREQUENCY OP. RANGE = 60 HZ
INVERTER EFFICIENCY = 97.5 %
MAX AC OCPD - 42 X125%- 52.5A
OCPD USED = 60 A BREAKER
PER SECTION 690.53 #2
(A) RATED MAXIMUM POWER -POINT CURRENT (mppA)
Imox X # OF STRINGS = 9.07A X 4 = 36.28A
(B) RATED MAXIMUM POWER -POINT VOLTAGE (mppV)
Vmax X # OF MODULES = 31.2V X 10 =312V
(C) MAXIMUM SYSTEM VOLTAGE
39.5V X 10 X 1.14 = 450.3V
(D) SHORT CIRCUIT CURRENT
Isc X 1.25 = 12.13A
(E) AC GROUNDING J
ELECTRODE
M IMPERIAL IRRIGATION
DEPARTMENT (IID)
SERVICE
120/240V
DOWNGRADE
EXISTING 225A
STa MAIN SERVICE
PANEL TO
175A MAIN
CIRCUIT
BREAKER
NEW
90A 2P
BREAKER
TO BE
INSTALLED
AT END OF
BUSBAR
SUPPLY POWER
175A+SOA-265A
225A x 1.2-270A QK
CITY OF
LA
BUILDING & SAFETY
FOR CONSTRUCTION
DATE --,-.-By
OUTPUT CALCULATIONS
PV SYS .MAX DC OUTPUT: 28OW X 58 = 16.24 KW
PV SYS MAX AC CALCULATION PER INVERTER #1
USING PTC PMAX:
Pmox PER MODULE = 251 W
251W X 18 MODULES= 4.52 KW
4.52 KW X 98%= 4.43 KW
PV SYS MAX AC CALCULATION PER INVERTER #2
USING PTC PMAX:
Pmax PER MODULE = 251 W
251W X 40 MODULES= 10.04 KW
10.04 KW X 97.5%= 9.79 KW
PV SYS MAX AC = 4.43KW + 9.79KW = 14.22KW
REVISION
DATE
NO
11/18/2015 1
F
a
N
W
r7 'O
Q
'o to
J
W (T
O
I- Q
JQ
U
N
S H
w U)
> J
00 U
Q
C7 O
Z
O
a
Z
J
Q O
4110N
U
CD O
n
C)
z
Q
V N
m
N
(
W 01
JU
Lu
LL Q
=
Q Z_
O �
N O
LU
-.1 Q
?
Z
oO
Cn
C
v
Q
w
_z
w -�
J w
N
)-
0
w z
LU
W
rn
Lu
N
U N
o_ N
01
Lu
r CL
o U
a
a
z
Lr_
J
o
ON CS
]C
Q
Z N
Lr)
N
Date:
10/11/2015
Scale
AS NOTED
Drawn:
YW FMI[NG
Sheet
E1
FDP REQUIREMENTS:
SEC. 5. MARKING, LABELS, AND WARNING SIGNS. SOLAR PI SOLAR PV
i� PANELS �� PANELS
A. Purpose: Provides emergency responders with appropriate warning and
guidance with respect to isolating the solar electrical system. this can
facilitate identifying energized electrical lines that connect the solar panels
to the inverter, as these should no be cut when venting for smoke
removal.
B. Main Service Disconnect:
1. Residential buildings - the marking may be placed within the main
service disconnect. The marking shall be placed on the outside over if the
main service disconnect is operable with the service panel closed.
2. Commercial buildings - the marking shall be placed adjacent to the
main service disconnect clearly visible from the locatin where the lever is
operated.
"WARNING. ELECTRICAL SHOCK HAZARD. IF A
GROUND FAULT IS INDICATED, NORMALLY
GROUNDED CONDUCTORS MAY BE ENERGIZED AND
UNGROUNDED." NEC 690.5(C)
"DO NOT DISCONNECT UNDER LOAD"
CAUTION: SOLAR CIRCUIT
RATED MAXIMUM POWER -POINT CURRENT = 36.28A
RATED MAXIMUM POWER -POINT VOLTAGE = 312V
MAXIMUM SYSTEM VOLTAGE = 450.3V
SHORT CIRCUIT CURRENT = 12.13A
CEC 690.53
]-BOX
"WARNING. ELECTRICAL SHOCK HAZARD. IF A
GROUND FAULT IS INDICATED, NORMALLY
GROUNDED CONDUCTORS MAY BE ENERGIZED AND
UNGROUNDED." NEC 690.5(C)
"DO NOT DISCONNECT UNDER LOAD"
CAUTION: SOLAR CIRCUIT
RATED MAXIMUM POWER -POINT CURRENT = 18.14A
RATED MAXIMUM POWER -POINT VOLTAGE = 280.8V
MAXIMUM SYSTEM VOLTAGE = 405.27V
SHORT CIRCUIT CURRENT = 12.13A
CEC 690.53
3. Markings: Verbiage, Fomat, and Type of Material. O1 **WARNING**��� SE10000A-US SE 5000A -US **WARNING**
a. Verbiage: WARNING: PHOTOVOLTAIC POWER SOURCE." ELECTRIC SHOCK HAZARD DC DISCONNECT DC DISCONNECT \ \ ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS DO NOT TOUCH TERMINALS
TERMINALS ON BOTH THE LINEQ TERMINALS ON BOTH THE LINE
b. Format: AND LOAD SIDES MAY BE ENERGIZED AND LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION. NEC 690.17 IN THE OPEN POSITION. NEC 690.17
(1) White letter on a red background. I I INVERTER
W/ DC DISCONNECT
(2) Minimun 3/8 inches letter height. **WARNING** D INTEGRATED D **WARNING**
IF A GROUND FAULT IS INDICATED, n n IF A GROUND FAULT IS INDICATED,
(3) All letters shall be capitalized. THE NORMALLY GROUNDED CONDUCTORS THE NORMALLY GROUNDED CONDUCTORS
MAYBE ENERGIZED AND UNGROUNDED. MAYBE ENERGIZED AND UNGROUNDED.
(4) Arial or similar font, non -bold. (NEC 690.5 C) (NEC 690.5 C)
c. Material: I ETIft
(1) Reflective, weather resistant material suitable for the
environment (use UL - 969 as standard for weather rating). Durable
adhesive materials meet this requirements.
C. Marking Requirements on DC Conduit, Raceways, Enclosures, Cable
Assemblies, DC Combiners, and ]unction Boxes:
1. Marking: Placements, Verbiage, Format, and Type of Material.
a. Placement: Markings shall be placed every 10 feet on all interior a
exterior DC conduits, raceways, enclosures, and cable assemblies, at
turns above and/or below penetrations, all DC combiners, and juncti(
boxes.
b. Verbiage: CAUTION: SOLAR CIRCUIT
Note: The Format and Type_ of Material shall adhere to "SEC. 5. B -3b &
c" of this Requirement.
D. Inverter - A warning label shall appear on the utility-ineractive inverter or
be applied by the installer near the ground -fault indicator at visible
location.
CITY OF LA QUI NTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
DATE BY
AC DISCONNECT
""WARNING" 2 SOURCES OF POWER PV/AC
DISCONNECT @ AD]CENT LOCATION" CEC 705.10
"PHOTOVOLTAIC AC DISCONNECT FOR UTILITY
OPERATIONS" NEC 690.14 C
THE MAXIMUM AC OUTPUT OPERTIVING CURRENT = 63A. NEC 690.54
THE NOMINAL OPERATIVE AC VOLTAGE = 240V. NEC 690.54
MAIN SERVICE
"THIS SERVICE ALSO SERVED BY A
PHOTOVALTAIC SYSTEM" NEC 690.64
M
"WARNING - PHOTOVOLTAIC CONNECTION. DO NOT
RELOCATE THIS OVER CURRENT DEVICE" 690.64 B
REVISION
DATE
NO
11/18/2015 1
E
a
0
N
w
CD
Q
'0 to
J
LLI rn
O
F- Q
JQ
N U
_ F_W
J
L
_J
CCQ
G z
z
O
za
J
Q 0
U O
o O
N
Z
<F_
P0
Of
U N
CD
11 N
Cl!�
w rn
J
- U
LU
L Q
=
Qz
F_
oo
a
N
Z
s
") Q
oco
V)
LLJ
0
Z
0
z
Lij
LU3
x
N
LU
U >- U
N
O 0,
o >
� Q
r D_
O_ U
U
LL d
F-
a
a
L
LU Y
oZ
oN O
s
Q
z N
L0
N
Date:
10/11/2015
Scale:
AS NOTED
Drawn:
YW
RISING
Sheer.
E2
REVISION
DATE
NO
11/18/2015 1
Sunmodule;/' PI u s . .
Sunmodule% PI u s. •
LD
%D
d:
a
En
280 MONO BLACK REALVALUE
w
EO r-
<
SW 280 MONO BLACK REALVALUE
J
Lu rn
O
F- Q
Cn J
PERFORMANCE UNDER STANDARD TEST CONDITIONS (STC)' PERFORMANCE AT 800 W/mz, NOCT, AM 1.5
Q
N
= H
w �
CJ
Q
Maximum power Pm„ 280 Wp Maximum power p- 207.2 Wp
Q =
U p
�,0.t///u��kv-oo
`` -1
Z
Q J
0
Open circuit voltage V« 39.5 V Open circuit voltage V. 35.8 V
U
TUV Power Controlled:
- -
TovRhelNteod =
0
Maximum point voltage V 28.3 V
Maximum power point voltage V_ 31.2 V Power P 9 °m
Z
Lowest measuring tolerance in industry
Q
Of
N
Short circuit current IY 9.71 A Short circuit current Ix 7.85 A
U
N
000002°•
LU
J
- U
Maximum power point current 1.. 9.07 A Maximum power point current I, 7.33 A
� Q
=
Q Z_
�
>
Module efficiency nm 16.7% Minor reduction in efficiency under partial load conditions at 256C: at 200 W/m•. 100%
N O
Q
w
�a
3
(+/-2%) of the STC efficiency (1000 W/mE) is achieved.
J F
LU w
'STC: 1000 W/mr. 25'C, AM 1.5
Q _
II�� Every component is tested to meet
a
1) Measuring tolerance(P,) traceable to TUV Rheinland: +/- 2% (TUV Power Controlled). COMPONENT MATERIALS
d O
3 times IEC requirements
THERMAL CHARACTERISTICS Cells per module 60
U
�
Cell type Mono crystalline
F_ U
F_ w
U.1 a�
NOCT 48 °C
Cell dimensions 6.17 in x 6.17 in (156.75 x 1S6.75 mm)
W
rn
TC Iu 0.044 %/'C
ZD to
w 0,
CL
v
Front Tempered glass (EN 12150)
LL a
a
z
J
oa
oN O
TC_ -0.31 %/°C
Q
Z N
Designed to withstand heavy
N
Frame Black anodized aluminum
10/11/2015
Scale:
AS NOTED
Tic P_ -0.43 %/°C
YW RISING
accumulations of snow and ice
'
E3
Weight 39.5 lbs (17.9 kg)
J
Operating temperature -40°C to 85°C
SYSTEM INTEGRATION PARAMETERS
Ix 1000 W/m' Maximum system voltage SC 11 /NEC 1000 V
$unmodule Plus:
O
--- Maximum reverse current 25A
Positiveerformance tolerance
P
800 W/m' Number of bypass diodes 3
J
= 600 W/ms Design Loads' Two rail system 113 psf downward
64 psf upward
170 psf downward
Design Loads' Three rail system
400 W/m2 71 psf upward
year • 25 -year linear performance warranty
- _ Design Loads' Edge mounting 30 psf downward
and 10 -year product warranty
200 w/m2 30 psf upward
J100
W/m' Please refer to the Sunmodule installation instructions for the details associated with
these load cases.
1 I 1
V. ADDITIONAL DATA
Module voltage IV)
Glass with anti -reflective coating
Powersorting' -O Wp/+S wp
1 x 4, 37.44 (951) !-Box I P65
J
- Module leads PV wire per UL4703 with H4 connectors
Module type (UL 1703) 1
World-class quality ay.en.ano„:„ a .�mmanl.n.i.lm.
'� °
1133 (288) Glass Low iron tempered with ARC
Fully -automated production lines and seamless monitoring ofthe process and mate-�•
ate
rial ensure the quality that the company sets as its benchmark for its sites worldwide. ' •••.•r''
rial
0.6 15.3
39.37 (1000)
SolarWorld Plus -Sorting �� ®
VERSION 2.5 FRAME
cEmoaEUN x Es Eo A@
Plus-Sortingguarantees highest system efficiency. SolarWorld only delivers modules -� .-or=1�SS.N
rNoroxE.tvomaulcl US
version Compatible with both "Top -Down"
` ,
g g y y y v
2.5 frame and 'Bottom"mounting methods
that have greater than or equal to the nameplate rated power. UL 1703
65.94 (1675) bottom ♦Grounding Locations:
DVE • EE
25 -year linear performance guarantee and extension of product warranty to 10 years E 1
mountingD 4corners oftheframe
holes 4locations along the length of the
SolarWorld guarantees a maximum performance digression of 0.7% p.a. in the course FF51 Gp
module in the extended flanges
of 25 years, a significant added value compared to the two-phase warranties com-
mon in the industry. In addition, SolarWorld is offering a product warranty, which has L".
been extended to 10 years.'
Homelnnovation
GEFFN CEEIIIiFe.
NGEE
'in accordance with the applicable SolarWorld Limited Warranty at purchase.
www.solarworld.com/warranty
' x4
4.20(107)t
1.22 (31) Fes- 39.41(1001)-1
MADE IN USA OF Us
solarworld.cOm AND IMPORTED PARTS
All units provided are imperial. S1 units provided in parentheses.
SolarWorld AG reserves the right to make specification changes without notice. SW-01-6026US 12-2014
NOTE: SOLAR PANELS LISTED ON CEC, CALIFORNIA CERTIFIED
REVISION
DATE
NO
11/18/2015 1
d:
a
En
w
EO r-
<
.p 17
J
Lu rn
O
F- Q
Cn J
5 U
Q
N
= H
w �
CJ
Q
CL'
CD U
Q =
U p
OZ
Q
Z
Q J
0
U
N O
3
0
Z
Q
Of
N
co
U
N
W
LU
J
- U
LU
� Q
=
Q Z_
�
>
N O
Q
w
�a
3
O cn
J F
LU w
LLI
Q _
a
>z
d O
U
�
F_ U
F_ w
U.1 a�
N
W
rn
N } UN
ZD to
w 0,
CL
v
U
LL a
a
z
J
oa
oN O
Y
Q
Z N
N
Date:
10/11/2015
Scale:
AS NOTED
Drawn:
YW RISING
Sheet
E3
I'
^ _" 3 a" R ai o� 0 O
d O^' 3 {a5�--5m o Z OY
ia.1 7 S c c � O.
0 3 n 0 W D d - I; � q- F b, O ` N
CD co)
i d C d i0
I 3 3 ". c S r► 1 G o z D N
mCID
CD
CD
INVERTERS
A 5 y
Z r' A 1 l 3N 3 m
g c �
� N
k
i a '
1 ,
F E '
E F 1
£ j E
O
ma
I:c Q P ?4.2 3 '6 3 -1g.C';^Ia ri°1s a q s� s s s.a. - N yl i' 6' o R F
�j 6 lYYS �: q s 3 13':E F.y^ .8. .3:"'I--
J,
�'�FF si 3 � T^c3�S $ .d'�^.ate I O 1�� �5 yl� � �g@ Fill
y�� �....:::tljjj
i31G�,�!lla oR �.�� S A��gl= � O
3 3 ��a3 33:8q g 3 {�{ S' $ SS�� S /��
3=3 ; 3�qF 3fi E' Bal ° 3 FPa�3fisx$3R I /�+ lii2`� i 3g, b z k ii/
genii a �plp
o��geP3y."� s C�:
3. "- � _. ! �S F'_ _. _• E �1 � �g�� _ _ � 1 M V M a � N , � 15 '�I �1
7 1• - If� h� �;I •Cns v 3 Vfi '� gm N_
O
le
e 1 B
It a g—;$ ai I -
T'
� - o � e N i � 151 '� a �s ' i I +"ig •�' � ++=—++++� � H �
P_ g •.. � 1 3
r
Cn
H
LT1
d
O
z
r)
n
n
r
O
z
n
H
'TJ
l�
0
V
o
D
o
SINGLE FAMILY HOUSE
SHEET TITLE:
OWNER:
BRIGHTSOLAR
STAM :
c
0
16.24 KW (DC) PV SYSTEM
EQUIPMENT: INVERTER
STUART HELLERBRAND
=:_ - CAPITAL
\
00
z
SPECIFICATION SHEET
g
N
�,
0
54200 AFFIRMED CT
54200 AFFIRMED CT
6320 CANOGA AVE SUITE 630E
OZ
co
LA QUINTA, CA 92253
LA QUINTA, CA 92253
WOODLAND HILLS, CA 91367
V
�r
rnr
P tw
gx x
�} 2-
—1- g -
Q m
p 7w
a o
n> ( v
N_ ,
y 9 5'g fit r�
I
8 fa o
9
Hal,
( IT
s
I
�a
fill
i PH
r ti
ls� �
o
v
SHEET TITLE:
OWNER:
STAMP:
w
;
'
SINGLE FAMILY HOUSE
STUART HELLERBRAND
BRIGHTSOLAR
-,
V J)
D
16.24 KW (DC) PV SYSTEM
RACKING
, CAPITAL
N
F
Z
INSTALLATION GUIDE
'
il
g
Ln
°
54200 AFFIRMED CT
54200 AFFIRMED CT
6320 CANOGA AVE SUITE 630E
0
LA
°
LA QUINTA, CA 92253
QUINTA, CA 92253
WOODLAND HILLS, CA 91367
O
I
I
I
I
1>1
54200 Afirrmed ct.
L' t CA 92253
6sd� �S-D22�
a Quin
Date Prepared: 11/20/ � / r
STANDARD SERVICE/FEEDER LOAD CALCULATION - One Family Dwelling
NEC Article 310
General Lighting
4000
Sq. Feet
x 3
VA =
12000
VA
Small Appliance ..
3
Circuits
x 1500
VA =
4500
VA
Laundry .........:
1
Circuits
x 1500
VA =
1500
VA
Total General Light
& Small Appliance ......
18000
VA
The First 3000
VA @
100% =
3000
VA
VA
Remaininct 15000
VA @
35% =
5250
VA
.......E
119 5 VA
GENERAL LIGHTING, SMALL APPLIANCE & LAUNDRY DEMAND LOAD (NEC 220.42) : 8250 VA
Heating Demand 1200 VA @ 100% = 1200 VA
Cooling Demand 45552 VA @ 100% = 45552 VA
LARGER OF HEATING OR COOLING DEMAND LOADS (Cooling) (NEC 220.60) ... 45552 VA
Wall Oven: 3000 VA
COOKING EQUIPMENT DEMAND LOAD (NEC 220.55) ......................... 2400 VA
Dryer: 3400 VA
DRYER DEMAND LOAD (NEC 220.54) ..................................... 3400 VA
Water Heater:
4500
VA
Attic Fan
350
VA
!'SOT/
I
Dishwasher
1200
VA
ii�� �� ii ®F A Ql.l����
Disposal
450
VA
BUILDING & SAFETY DEPT.
Other App. #1
6000
VA [ Pool Equip.
] A P P ®®��
Other App. #2
3400
VA [ Ref ridge l
DEC 0 4 2015
FORB—COdN�S CONSTRUCTION
Fixed Appliance
Total: 15900
VA
15900 VA @ 75%
FIXED APPLIANCE
Demand: 11925 VA
DEMAND LOAD 220.53)
DATZ2
y�,f
(NEC
.......E
119 5 VA
Largest Motor:
Pool Equip. @
6000 VA
25% OF LARGEST
MOTOR LOAD (220.14)
.................................
. 1500 VA
Other Lighting
Load 2239 VA
[ Misc. Lighting
Continuous Load: 125% Demand
OTHER LIGHTING
DEMAND LOAD (NEC 220.14) ............................
: 2799 VA
NET COMPUTED LOAD .................................................. . 75826 VA
120/240 VOLT SERVICE/FEEDER LOAD ................................... . 316 AMP
NEUTRAL LOAD (NEC 220.61):
General Lighting .........
8250
VA
Appliances ...............
5729
VA
Cooking ..................
1680
VA
Dryer ....................
Largest Motor ............
2380
1500
VA
VA
Heating/Cooling
0
VA
RECEIVED
Total Neutral Demand Load
19539
VA
DEC 0 4 2015
81 AMP
CITY or. LA QUINTA
COMMUNITY DEVELOPMENT