08-1234 (AR)P.O. BOX 1504
78-495 CALLE TAMPICO
LA QUINTA; CALIFORNIA 92253
Application Number: 08-00001234
Property Address: 80388 PEBBLE BEACH
APN: 775-131-055- -
Application description: ADDITION' - RESIDENTIAL
Property Zoning: LOW DENSITY, RESIDENTIAL
Application valuation: 8807
Applicant:
T4ht'4 4. Qum
. BUILDING & SAFETY DEPARTMENT
Architect or Engineer:
BUILDING PERMIT
--------------------------------------------------
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter 9 (commencing with
Section 7000) of Division 3 of the Business an ofessionals Code, and my License is in full force and effect.
\ License Class: B ,. / License No�684857
Date: t� I r,y.ontraaor: /
owl
W R -BUILDER DECLARATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State License Law for the
following reason (Sec. 7031.5, Business and Professions Code: Any city or county that requires a permit to
construct, alter, improve, demolish, or repair any structure, prior to its issuance, also requires the applicant for the
permit to file a signed statement that he or she is licensed pursuant to the provisions of the Contractor's State
License Law (Chapter 9 (commencing with Section 7000) of Division 3 of the Business and Professions Code) or
that he or she is exempt therefrom and the basis for the alleged,exemption. Any violation of Section 7031.5 by
any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500).:
(_ 1 I, as owner of the property, or my employees with wages as their sole compensation, will do the work, and
the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The
Contractors' State License Law does not apply to an owner of property who builds or improves thereon,
and who does the work himself or herself through his or her own employees, provided that the
improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner -builder will have the burden of proving that he or she did not build or
improve for the purpose of sale.).
1 _ 1 1, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec.
7044, Business and Professions Code: The Contractors' State License Law does not apply to an owner -of
property who builds or improves thereon, and who contracts for the projects with a contractor(s) licensed
pursuant to the Contractors' State License Law.).
1 _ 1 I am exempt under Sec. , B.&P.C. for this reason
Date:
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for the performance of the
work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's Name: _
Lendtr's Address:
LQPERMIT
Owner:
DAVID CARSON
8-388 PEBBLE BEACH
LA QUINTA, CA 92253
(760)777-8202
VOICE (760) 777-7012
FAX (760) 777-7011
INSPECTIONS (760) 777-7153
8/27/08
Contractor:
EDWARDS CONSTRUCTION INC,
51455 DESERT CLUB DRIVE
LA QUINTA, CA 92253
(760)777-8202
Lic. No.: 684857
-------------------------------------------------
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self -insure for workers' compensation, as provided
for by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued.
I have and will maintain workers' compensation insurance, as required by Section 3700 of the Labor
Code, for the performance of the work for which this permit is issued. My workers' compensation
insurance carrier and policy number are:
Carrier GRANITE STATE Policy Number WC 555-61-55
I certify that, in the performance of the work for which this permit is issued, I shall not employ any
person in any manner so as to become subject to the workers' compensation laws of California,
and agree that, if I sho m
ecoe subject to the workers' compensation provisions of Section
�(
3.700 of the Labor Code, s allf rth it mply rovisions.
Date: -;
Applicant:
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS UNLAWFUL, AND SHALL
SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO ONE HUNDRED THOUSAND
DOLLARS ($100,000). IN ADDITION TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN
SECTION 3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT Application is hereby made to the Director of Building and Safety for a permit subject to the
conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose request and for
whose benefit work is performed under or pursuant to any permit issued as a result of this application,
the owner, and the applicant, each agrees to, and shall defend, indemnify and hold harmless the City
of La Quinta, its officers, agents and employees for any act or omission related to the work being
performed under or following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is not commenced
within 180 days from date of issuance of such permit, or cessation of work for 180 days will subject
permit to cancellation.
I certify that I have read this application and state that the above information is correct. I agree to comply with all
city and county ordinances and state laws relating to building construction, and hereby authorize representatives
of thiscountyto enter upon the above-mentioned propT Mrposes.
Date: O � Signature (Applicant or Agent):
LQPERMIT
Application Number . . . . . 08-00001234
------ Structure Information 109SF ATRIUM ENCLOSURE/V-B/RES-3
-----
Other struct info _.. CODE EDITION 2007CODES
# BEDROOMS
.00
FLOOD ZONE NO
- 1ST FLOOR SQUARE -FOOTAGE
109.00
Permit BUILDING PERMIT
Additional desc .
Permit Fee 108.00 Plan Check Fee-.-.
70.20
Issue Date Valuation,
8807
Expiration Date 2/23/09 �.
Qty Unit Charge Per
Extension
BASE FEE
45.00
7.00 9.0000 THOU BLDG 2;001-25,000
63.00
Permit ELECT.- ADD/ALT/REM
Additional desc .
Permit Fee . . . . 18.82 Plan Check Fee
4.71
Issue Date Valuation
0
Expiration -Date 2/23/09
Qty Unit Charge Per
Extension
BASE FEE
15.00
109.00 .0350 ELEC NEW RES - 1 OR 2 FAMILY
3.82
Permit MECHANICAL
Additional desc
Permit Fee 19.50 Plan Check Fee
4.88
Issue Date . . . . Valuation
0
Expiration Date 2/23/09
Qty . Unit Charge Per
Extension
BASE FEE
15.00
1.00 4.5000 EA MECH VENT INST/ DUCT ALT
4.50
----------------------------------------------------------------------------
Special Notes and Comments
109SF ATRIUM ENCLOSURE/V-B/RES-3/CLASS A
EMERGENCY EGRESS HAS NOT BEEN PROVIDED,
THIS PERMIT DOES NOT ALLOW ADDITION TO
BE USED FOR SLEEPING PURPOSE. 2007
CALIFORNIA BUILDING CODES.
August 27, 2008 10:09:52 AM AORTEGA
----------------------------------------------------------- ----------------
Other Fees . . . . . . . . . ENERGY REVIEW FEE
7.02
LQPERMIT
LQPERMIT
Application Number
. . . . .
08-00001234
-------------------.---
j Other Fees
-------------------------
. . . . .
STRONG MOTION
------_-- -
(SMI) RES
-
:88
Fee summary
Charged
----------
Paid
----------
Credited
----------
Due
-----------------
Permit Fee Total
146.32
----------
.00
.00
146.32
Plan Check Total
79.79
.00
.00
79.79
Other Fee Total
7.90
.00
.00
7.90
Grand Total'
234.01
.00
.00
234.01
LQPERMIT
Coachella Valley Unified School District
83-733 Avenue 55, Thermal, CA 92274
(760) 398-5909 — Fax (760) 398-1224
This Box For District Use Only
DEVELOPER FEES PAID
AREA:
AMOUNT
LEVEL ONE AMOUNT:
LEVEL TWO AMOUNT:
MITIGATION AMOUNT:
COMMAND. AMOUNT:
DATE:
RECEIPT:
CHECK N:
INITIALS:
CERTIFICATE OF COMPLIANCE
(California Education Code 17620)
Project Name: David Carson_(PGA West) Date: August 27, 2008
Owner's Name: _ David Carson Phone No. 760-777-8202
Project Address: 80-388 Pebble Beach, LaQuinta, CA 92253
Project Description: Residential Addition
APN: 775-131-055 Tract #: Lot #'s:
Type of Development: Residential XX Commercial Industrial
Total Square Feet of Building Area: 109 sq. ft.
Certification of Applicant/Owners: The person signing certifies that the above information is correct and makes this statement under
penalty of perjury and further represents that he/she is authorized )G-�ign on behalf of the owner/developer.
Dated: � 9 D Signature:
SCHOOL DISTRICT'S REQUIREMENTS FOR THE ABOVE PROJECT HAVE BEEN OR WILL BE SATISFIED IN
ACCORDANCE WITH ONE OF THE FOLLOWING: (CIRCLE ONE)
Education Code
17620
Number of Sq.Ft.
Amount per Sq.Ft.
Amount Collected
Gov. Code Project
65995 Approval
109 sq. ft.
$ 0.00
$ 0.00
Building Permit Application Completed: Yes/No
Agreement Existing Not Subject to Fee
Prior to 1/1/87 Requirement
Note: Pursuant to AB -181, any room additions of 500 square
feet or less on existing dwelling units are exempt from
developer'fees. Pursuant to AB -181, any mobile home being
relocated or replaced within our school district is exempt
from developer_ fees.
By: Carey M. Carlson, Asst. Supt., Support Services
Certificate issued by: Laurie Howard, Secretary III Signature:��
NOTICE OF 90 DAY PERIOD FOR PROTEST OF FEES AND STATEMENT OF FEES
Section 66020 of the Government Code asserted by Assembly Bill 3081, effective January 1, 1997, requires that this District provide (1) a written notice to the
project appellant, at the time of payment of school fees, mitigation payment or other exactions ("Fees"), of the 90 -day period to protest the imposition of these
Fees and (2) the amount of the fees. Therefore, in accordance with section 66020 of the Government code and other applicable law, this Notice shall serve to
advise you that the 90 -day protest period in regard to such Fees or the validity thereof, commences with the payment of the fees or performance of any other
requirements as described in section 66020 of the Government code. Additionally, the amount of the fees imposed is as herein set forth, whether payable at this
time or in whole or in part prior to issuance of a Certificate of Occupancy. As in the latter, the 90 days starts on the date hereof. This Certificate of
Compliance is valid for thirty (30) days from the date of issuance. Extension will be granted only for good cause, as determined by the School District, and up
to three (3) such extensions may be granted. At such time as this Certificate expires, if a building permit has not been issued for the project that is the subject
of this Certificate, the owner will be reimbursed all fees that were paid to obtain this Certificate of Compliance.
MV:c/mydocs/devlees/certificate ofcompliance form tablesTO USE.doc 1/16/03 T
Bin #
yCity of La Quints t
Building u Safety Division -
P.O. Box 1504 78-495 Calle Tampico
p `
La Quinta, CA 92253 - (760) 777-7012
Building Permit Application and Tracking Sheet
Permit # �
Project Address: 0—
Owner'sName: `� Vf �9(D SOc�L
�A. P. Number: 7 S C
=rt�ZO1
Address:
(%NLegal Description ��City,
Contractor:
ST, Zip:
Telephone: %% � � �� � . •�
l
Address:1 –4
Project Description:
City, ST, Zip: CS-�./(1X-p-_
Telephone:'
State Lic. # : City Lic. #:
., Designer:
Address: ��—� ��Q�� (�Z(a�
&4_ry�!
City, ST,Zip:t�:gLLH�
•
Telephone: �574_'8.5g w r '
State Lic. #: J
Name of Contact Person: j �—�S
Construction Type: Occupancy:
Project type circle one New Add'n Alter Repair Demo
Sq. Ft.: Q� # St00W ories:
# Units:
Telephone # of Contact Person: 'j? a ��
Estimated value of Proje
APPLICANT: DO NOT WRITE BELOW THIS LINE
#
Submittal
Req'd
Rec'd
TRACKING
PERMIT FEES
Plan Sets
Plan Check submitted
Item
Amount
Structural Calcs.
v
Reviewed, ready for corrections
Plan Check Deposit
Truss Calcs.
IF 11
Called Contact Person 3
Plan Check Balance
Energy Cafes.
Plans picked up
Construction
Flood plain plan
Plans resubmitted
Mechanical
Grading plan
2" Review, ready for correct io ass D �
Electrical
Subcontactor List
Called Contact Person
Plumbing
Grant Deed
Plans picked up
S.M.I.
H.O.A. Approval
Plans resubmitted
Grading
IN HOUSE:
3"1 Review, ready for corrections/issue
Developer Impact Fee
Planning Approval
Called Contact PersonA.LP.P.
Pub. Wks. Appr
Date of permit issue
School Fees
F
Total Permit Fees
Title .24, Report, for:
Mr. & Mrs. David Carson (Atrium Enclosure)
80-388 Pebble Beach
La Quinta, CA 92253
Project Designer:
3
Robert A. Pitchford, Design & Drafting
77-622 Country Club Ste.O
Palm Desert, CA 92211
(760) 346-2856
Report Prepared By:
Jon Scott
Scott Design-& Title 24
77085 Michigan Dr.
Palm Desert, CA 92211
(760) 200-4780
Date:
8/27/2008
he EnergyPro computer program has been used to perform the calculations summarised in this compliance report. This program has approval and is
uthorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
— I • EnergyPro 4.4 by EnergySoft Job Number: User Number: 6712
i
TABLE OF CONTENTS
Cover Page
Table of Contents
Form CF -1 R Certificate of Compliance
Form MF -1 R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
1
2
3
6
8
9
10
12
EnergyPro 4.4 by EnergySoft Job Number: User Number: 6712
Certificate Of Compliance : Residential (Part 1 of 3) CF -1 R
Percent better than
Building Type:
[k Single Family
❑ Addition
Total Conditioned Floor Area:
r8/27/2(2
oject Title
[X-1 Existing + Add/Alt
Existing Floor Area:
Building Front Orientation:
Date
Raised Floor Area:
Fuel Type:
Natural Gas
Slab on Grade Area:
Project Address
Average Ceiling Height:
Building Permit #
Sr. n t Dp---.*qn & Title
24
Number of Dwelling Units:
(760) 200-4780
19.0% Avg. SHGC: 0.65
Documentation uthorTelephone
BUILDING ZONE
INFORMATION
Plan Check/Date
Fn�ravPro
Complies c� a Method
CA
.limat . 7one 15
Climate Zone
Field Check/Date
TDV
Standard
Proposed
Compliance
(kBtu/sf-yr)
Design
Design
, Margin
Space Heating
7.77
6.43
1.34
Space Cooling
163.07
155.06
8.01
Fans
22.12
20.99
1.13
Domestic Hot Water
8.10
8.10
0.00
Pumps
0.00
0.00
0.00
Totals
201.06
190.58
10.48
Percent better than
Building Type:
[k Single Family
❑ Addition
Total Conditioned Floor Area:
❑ Multi Family
[X-1 Existing + Add/Alt
Existing Floor Area:
Building Front Orientation:
(E) 90 deg
Raised Floor Area:
Fuel Type:
Natural Gas
Slab on Grade Area:
Fenestration:
Average Ceiling Height:
Area:
618 ft2
Avg. U: 1.25
Number of Dwelling Units:
Ratio:
19.0% Avg. SHGC: 0.65
Number of Stories:
BUILDING ZONE
INFORMATION
# of Thermostat
one Name
Floor Area Volume
3 954 29 2R6
Units Zone Type Type
100 _C onfi ionPri Sethack—
FxistingHVAC
OPAQUE SURFACES Insulation Act.
Type Frame Area U -Fac. Cay. Cont. Azm. Tilt
$ np f Wnnd 1 142 n n49 R-19 R_0 0 n
Wall Wood 227 0.110 R_11 R-0 0 _n 90
Wall Wnnd 34 0.110 R_11 R_0 0 _ago
[all Wnnd 24 n11n R_11 R-00 45 gn
Wall Wnnd 667 0.110 R_11 R-0.0 gn gn
Wall Wood 24 n 110 R_11 R-0.0 135 _gn
Wall Wnnd 5n6 n 110 R-11 R-0 n 1R0 _SQ
nnnr NnnP 19 1 450 NnnP R_n n 1Rn gn
Wall Wnnd 849 0.110 R_11 R-0 0 270 90
Wall Wnnd 35 0110 R-11 R-0.0 270 90
$nnf Wnnd 70 _n 028 R_3R R_n 0 n n
Wall Wnnd 99 0 110 R-11 R -n n 27n q
ME
3,254 ft2
3,142 ft2
0 ft2
3,254 ft2
9.0 ft
1.00
Vent
Hat. Area
—2 n/a
Gains Condition
Y / N Status JA IV Reference Location / Comments
Existing 01-A4 Fxisting Residence
❑Fxisting 09-A2 Existin8 Residence
X ❑Removed 09- 2 Existing Residence
® ❑Existing 09-A2 Fxisting RPsidenre
Existing 09-A2 FAsting$esidenre
Fxisting 09-A2 Fxicting Rec_idenra
❑Fxisting 09-A2 Fxisting RpsidPnrP
❑Fxisting 2R -A1 Fxistino Residenra
Fisting 09-A2 Existing Residence
El Removed 09-A2 Fxisting Residence
® L1 New 02-A2R Atrium Enrinsure
® Fxicting 09-A2 Atrium FnrinsurP
I EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:3 of 14 1
Certificate Of Compliance : Residential (Part 2 of 3) CF -1 R
8/27/2008
Date
FENESTRATION SURFACES
# Type Area U -Factor' SHGC2
True Cond.
Azm. Tilt Stat. Glazing Type
Location/
Comments
1
Window
TRight
(N)
80 0
1 280 116-A 0.67 116-B Q_ ---qa Existing Single Metal Tinted
Exicti g
Residence
2
Window
Right
(N)
80.0
1.280 116-A 0_67 116-B
0 90 Existing Single Metal Tinted
Existing
Residence
3
Window
Right
ZL
72.0
1.280 116-A 0_67 116-B
0 90 Existing Single Metal Tinted
^ Existing
Residence
4
Window
Right
(N)
56.0
1.280 116-A 0_67 116-B
0 90 RemovedSingle Metal Tinted
Existing
Residence
6
Window
Right
(NE)
3.0
1.280 116-A 0.67 116-13
45 90 Existing Sinqle Metal Tinted
Existing
Residence
6
Window
Front
(E)
64.0
1.280 116-A 0.67 116-B
90 90 Existing Single Metal Tinted
Existing
Residence
L
Window
Front
(E)
33.0
1.280 116-A 0.67 116-B 90 90 Existing Single Metal Tinted
Existing
Residence
8
Window
Front
(E)
13.4
1.280 116-A 0_67 116-B
90 90 Existing Single Metal Tinted
Existing
Residence
6
Window
Front
(E)
23.5
1.280 116-A 0.67 116-B 90 90 Existing Single Metal Tinted
Existing
Residence
-M
Window
Front
(E)
13.4
1.280 116-A 0.67 116_B 90 90 Existing_ Single Metal Tinted
Existing
Residence
11
Window
Front
(E)
4.5
1.280 116-A 0_67 116-B
90 90 Existing Single Metal Tinted
Existing
Residence
12
Window
Front
(E)
64.0
1.280 116-A 0_67 116-B
90 90 Existing Single Metal Tinted
Existing
Residence
Ia
Window
Front
(E)
80.0
1.280 116-A J1,6Z 116_B 90 qQ Existing Single Metal Tinted
Existing
Residence
14
Window
Front
(SE)
3.0
1.280 116-A 0_67 116-B
135 90 Existing Single Metal Tinted
Existing
Residence
15
Window
Left
(S)
42.4
1.280 116-A 0_67 116-B
180 90 Existing Single Metal Tinted
Existing
Residence
16
Window
Rear
(W)
64.0
1.280 116-A 0_67 116-B
270 90 RemovedSingle Metal Tinted
Existing
Residence
17
Skylight
Right
(N)
42.3
0.800 NFRC 0_39 NFgC
0 0 New Double Metal Tinted Skylight
Atrium Enclosure
1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 116B.
INTERIOR AND EXTERIOR SHADING Window
# FxtPrinr RhwiP TvnP RHGC Hot. Wd.
2
Bug Screen
0.76
Comments
Bug Screen
0.76
New
Bug Screen
0.76
_
Bug Screen
0:76
6
Bug Screen
0.76
7
Bug Screen
0.76
8
Bug Screen
0.76
9
Bug Screen
0.76
10
Bug Screen
0.76
11
Bug Screen
0.76
12
Bug Screen
0.76
13
Bug Screen
0.76
14
Bug Screen
0.76
15
Bug Screen
0.76
16
Bug Screen
0.76
17
None
1.00
Overhang Left Fin
Len. Hgt. LExt. REA Dist. Len. Hgt.
THERMAL MASS FOR HIGH MASS DESIGN
Area Thick. Heat Inside Condition Location/
Type (sf) (in.) Cap. Cond. R -Val. JA IV Reference Status Comments
PERIMETER LOSSES Insulation
Type Length R -Val. Location JA IV Reference
Slab Perimeter 332 None No Insulation 26-A1
Slab Perimeter 11 None No Insulation 26-A1
Dist. Len.
Condition
Location/
Status
Comments
Existing
Existing Residence
New
Atrium Enclosure
Run Initiation Time: 08/27/08 07:58:51 Run Code: 1219849131
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:4 of 14
Certificate Of Compliance : Residential (Part 3 of 3) CF -1 R
8/27/2008
Date
HVAC SYSTEMS
Heating Minimum Cooling Minimum Condition Thermostat
Location Type Eff Type Eff Status Type
Existing HVAC Central Furnace 78% AFUE Split Air Conditioner 10.0 SEER Existing Setback
HVAC DISTRIBUTION
Duct Duct Condition Ducts
Location Heating Cooling Location R -Value Status Tested?
Existing HVAC Ducted Ducted Attic 4.2_. Existing No
Hydronic Piping Pipe Pipe Insul:
System Name Length Diameter Thick.
WATER HEATING SYSTEMS Rated
Tank
Energy
Tank Insul.
Water Heater # in Input
Cap.
Condition Factor
Standby R -Value
System Name Type Distribution Syst. (Btu/hr)
(gal) -
Status or RE
Loss (%) Ext.
Standard Gas 50 gal or Less Small Gas No Pipe Insulation 1 40,000
50
Existing 0.57
n/a n/a
Multi -Family. Central Water Heating Details T
Hot Water Pump Hot Water Piping Length (ft) Add 1/2"
Control # HP TVDe In Plenum Outside Buried Insulation
REMARKS
COMPLIANCE STATEMENT
This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of
Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall design responsibility.
The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insulation installation quality,
and building envelope sealing require installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Name:
Title/Firm: Robert A. Pitchford. Design & Drafting
Address: 77-622 Country Club Ste.O
Palm Desert, CA 92211
Telephone: (760) 346-2856 Lie. #:
(signature) (date)
Enforcement Agency
Name:
Title/Firm:
Address:
Telephone:
ignature) (date)
Documentation Author
Name: Jon Scott
Title/Firm: Scott Design & Title 24
Address: 77085 Michigan Dr.
Palm Desert, CA 92211
Telephone: 760 200 0
(signature(Aate)
I Eneravloro 4.4 by EneravSoft User Number: 6712 Job Number: Paae:5 of 14 1
Mandatory Measures Summary: Residential (Page 1 of 2) MF -1 R
NOTE: Lownse residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent compliance
• requirements from the Certificate of Compliance supercede the items marked with an asterisk (') below. When this checklist is incorporated into the permit
documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether
they are shown elsewhere in the documents or on this checklist only.
•
•
DESCRIPTION Check or Initial applicable boxes or check NA If not applicable and included with the
❑
❑
ENFORCE -
permit application documentation.
NIA
DESIGNER
MENT
Building Envelope Measures
§ 150(a): Minimum R-19 in wood ceiling insulation or equivalent U -factor in metal frame ceiling.
❑
E
❑
§ 150(b): Loose fill insulation manufacturer's labeled R -Value:
❑
❑
❑
�§ 150(c): Minimum R-13 wall insulation in wood framed walls or equivalent U -factor in metal frame walls (does not
❑
❑X
❑
apply to exterior mass walls).
❑
El
El
�§ 150(d): Minimum R-13 raised floor insulation in framed floors or equivalent U -factor.
❑
❑
❑
§ 150(e): Installation of Fireplaces, Decorative Gas Appliances and Gas Logs.
1. Masonry and factory -built fireplaces have:
a. closable metal or glass door covering the entire opening of the firebox
❑
❑X
❑
b. outside air intake with damper and control, flue damper and control
❑
0
El
2. No continuous burning gas pilot lights allowed. -
❑
❑X
❑
§ 150(0: Air retarding wrap installed to comply with §151 meets requirements specified in the ACM Residential Manual.
❑
El
El
§ 150(g): Vapor barriers mandatory in Climate Zones 14 and 16 only.
❑
❑
❑
§ 150(1): Slab edge insulation - water absorption rate for the insulation alone without facings no greater than 0.3%, water vapor
❑
❑
❑
permeance rate no greater than 2.0 perm/inch.
§ 118: Insulation specified or installed meets insulation installation quality standards. Indicate type and include
❑ .
❑
❑
CF -6R Form:
§ 116-17: Fenestration Products, Exterior Doors, and Infiltration/Exfiltration Controls.
1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage.
❑
0
❑
2. Fenestration products (except field fabricated) have label with certified U -Factor, certified Solar Heat Gain
El
❑
El
(SHGC), and infiltration certification.
3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed.
❑
❑X
❑
Space Conditioning, Water Heating and Plumbing System Measures
§ 110-13: HVAC equipment, water heaters, showerheads and faucets certified by the Energy Commission.
❑
❑
❑
§ 150(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA or ACCA.
❑
❑
❑
§ 150(i): Setback thermostat on all applicable heating and/or cooling systems.
❑
❑
§ 1500): Water system pipe and tank insulation and cooling systems line insulation.
1. Storage gas water heaters rated with an Energy Factor less than 0.58 must be externally wrapped with insulation
❑
❑
❑
having an installed thermal resistance of R-12 or greater.
2. Back-up tanks for solar systems, unfired storage tanks, or other indirect hot water tanks have R-12 external
❑
❑
❑
insulation or R-16 internal insulation and indicated on the exterior.of the tank showing the R -value.
3. The following piping is insulated according to Table 150-A/B or Equation 150-A Insulation Thickness:
1. First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire
❑
❑
❑
length of recirculating sections of hot water pipes shall be insulated to Table 150B.
❑
❑
❑
2. Cooling system piping (suction, chilled water, or brine lines), piping insulated between heating source and
indirect hot water tank shall be insulated to Table 150-B and Equation 150 -A.-
50 -A.4.
4.Steam hydronic heating systems or hot water systems > 15 psi, meet requirements of Table 123-A.
❑
❑
❑
5. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance,
❑
❑
❑
and wind.
6. Insulation for chilled water piping and refrigerant suction piping includes a vapor retardant or is enclosed
❑
❑
❑
entirely in conditioned space.
7. Solar water -heating systems/collectors are certified by the Solar Rating and Certification Corporation.
❑
❑
❑
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number:
Page:6 of 14
Mandatory Measures Summary: Residential (Page 2 of 2) MF -1 R
NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent compliance
• requirements from the Certificate of Compliance supercede the items marked with an asterisk (') below. When this checklist is incorporated into the permit
documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether
they are shown elsewhere in the documents or on this checklist only.
•
DESCRIPTION Instructions: Check 1. or initial applicable boxes when completed or check N/A if not ENFORCE -
applicable. N/A DESIGNER MENT
Space Conditioning, Water Heating and Plumbing System Measures: (continued)
§ 150(m): Ducts and Fans
1. All ducts and plenums installed, sealed and insulated to meet the requirements of the CMC Sections 601, 602, 603, 604, ❑ ❑ ❑
605, and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minumum installed level of
R-4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system
that meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol sealant that meets the requirements
of UL 723. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or
tape shall be used.
2. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed ❑ ❑ ❑
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support
platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions
in the cross-sectional area of the ducts.
3. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive
duct tapes unless such tape is used in combination with mastic and draw bands.
4. Exhaust fan systems have back draft or automatic dampers.
5. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operating
dampers.
6. Protection of Insulation. Insulation shall be protected from damage, including that due to sunlight, moisture; equipment
maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water
retardant and provides shielding from solar radiation that can cause degradation of the material.
7. Flexible ducts cannot have porous inner cores
§ 114: Pool and Spa Heating Systems and Equipment
1. A thermal efficiency that complies with the Appliance Efficiency Regulations, on-off switch mounted outside of the
heater, weatherproof operating instructions, no electric resistance heating and no pilot light.
2. System is installed with:
❑ ❑
❑ ❑
❑ ❑
❑ ❑
K
El
a. At least 36" of pipe between filter and heater for future solar heating.
❑ ❑ ❑
b. Cover for outdoor pools or outdoor spas.
❑ ❑ ❑
3. Pool system has directional inlets and a circulation pump time switch.
❑ ❑ ❑
§ 115: Gas fired fan -type central furnaces, pool heaters, spa heaters or household cooking appliances have no continuously
❑ ❑ ❑
burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr)
§ 118 (i): Cool Roof material meets specified criteria
❑ ❑ ❑
Lighting Measures
§ 150(k)l: HIGH EFFICACY LUMINAIRES OTHER THAN OUTDOOR HID: contain only high efficacy lamps as outlined in Table
❑ ❑ ❑
150-C, and do not contain a medium screw base socket (E24/E26). Ballasts for lamps 13 Watts or greater are electric
and have an output frequency no less than 20 kHz.
§ 150(k)l: HIGH EFFICACY LUMINAIRES - OUTDOOR HID: contain only high efficacy lamps as outlined in Table 150-C,
❑ ❑ ❑
luminaire has factory installed HID ballast.
§ 150(k)2: Permanently installed luminaires in kitchens shall be high efficacy luminaires. Up to 50% of the Wattage, as determined
❑ ❑ ❑
in Section 130(c), of permanently installed luminaires in kitchens may be in luminaires that are not high efficacy luminaires,
provided that these luminaires are controlled by switches separate from those controlling the high efficacy luminaires.
§ 150(k)3: Permanently installed luminaires in bathrooms, garages, laundry rooms, utility rooms shall be high efficacy luminaires.
❑ ❑ ❑
OR are controlled by an occupant sensor(s) certfied to comply with Section 119(d).
§ 150(k)4: Permanently installed luminaires located other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms
shall be high efficacy luminaires (except closets less than 70 ft) OR are controlled by a dimmer switch OR are controlled
❑ ❑ ❑
by an occupant sensor that complies with Section 119(d) that does not tum on automatically or have an always on option.
§ 150(k)5: Luminaires that are recessed into insulated ceilings are approved for zero clearance insulation cover (IC) and are
❑ ❑ ❑
certified to ASTM E283 and labeled as air tight (AT) to less than 2.0 CFM at 75 Pascals.
§ 150(k)6: Luminaires providing outdoor lighting and permanently mounted to a residential building or to other buildings on the
❑ ❑ ❑
same lot shall be high efficacy luminaires (not including lighting around swimming poolstwater features or other Article 680
locations) OR are controlled by occupant sensors with integral photo control certified to comply with Section 119(d).
§ 150(k)7: Lighting for parking lots for 8 or more vehicles shall have lighting that complies with Sections 130, 132, and 147.
❑ ❑ ❑
Lighting for parking garages for 8 or more vehicles shall have lighting that complies with Section 130, 131, and 146.
§ 150(k)8: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
❑ ❑
dwelling units shall be high efficacy luminaires OR are controlled by occupant sensor(s) certified to comply with Section 119(d).
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number:
Page:7 of 14
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Ilk Mr. & Mrs. David Carson Atrium Enclosure 8/27/2008
STEM NAME FLOOR AREA
Existinq MVAC 3.254
Number of
Heatina Sv
Total
Cooling System
Output per System
Total Output (Btuh)
Total Output (Tons)
Total Output (Btuh/sqft)
Total Output (sgft/Ton)
Air System
CFM per System
Airflow (cfm)
Airflow (cfm/sgR)
Airflow (cfmrron)
' Outside Air (%)
Outside Air (cfm/sgft)
Note: values above given at ARI conditions
(EATING SYSTEM PSYCHROMETRI
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
Latent
CFM
I Sensible
89,000
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
3,032 73,259
0
14,725
0
o 0
0
14,725
102 709
-248 4,743 74,818
10,718
0
0 0 0
0
10,718
-248 96 254
178,000
54.7
60,000
120,000
10.0
36.9
325.4
26.0 of 44.8 of 44.8 of
OutsideiA r
0 cfm QV
Supply Fan
400 cfm
44.8 of
LI
cuu
400 Existing HVAC System 83,825 34,711 178,000
0.12
40I0.0
0
Total Adjusted System Output
(Adjusted for Peak Design Conditions) 83,825 34,711 TIME OF SYSTEM PEAK Aug 2 pm Jan 12 am
Heating Coil
>% Return Air Ducts �1
Supply Air Ducts
84.8 of
ROOMS
70.0 of
110.0 172.5 OF 112.5/71.0 OF 112.5/70.8 OF 55.0/51.6 OF
Supply Air
Outside Air
0 Ducts
0 cfm Supply Fan Cooling Coil 89.6 / 64.3 of
400 cfm 35.1% R.H. ROOMS
112.5/71.0 OF 77.9/60.2 OF
Return Air Ducts I
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:8 of 14
4
4
ROOM LOAD SUMMARY
PROJECT NAME
Mr. & Mrs. David Carson Atrium Enclosure
DATE
8/27/2008
STEM NAME
Existing HVAC
FLOOR AREA
3 254
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Existing Residence
Existing Residence
1
2 734
66,931
-629
2,734
66,931
-629
4,568
72,059
Atrium Enclosure
Atrium Enclosure
1
297
6,328
381
297
6,328
381
175
2,759
PAGE TOTAL 1 3,032 73,259 -248 04,743 74,818
TOTAL 1 3,032 73,259 -248 4,743 74,818
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:9 of 14
ROOM HEATING PEAK LOADS
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 10 of 14
roject Title
r. & Mrs. David Carson Atrium Enclosure
Date
8/27/2008
Room Information Desicin Conditions
Room Name Existing Residence
Floor Area 3,142
Indoor Dry Bulb Temperature 70 OF
Time of Peak Jan 12 am
Outdoor Dry Bulb Temperature 26OF
,.�S-inqle
Conduction
surface.
Area
Area
X
X
X
•X
X
X
x
X
X
X
X
X •
X
X
x
X
X
X
X
x
X
x
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
9.00 X
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
x
AT of
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Btu/hr
Default Roof 1978 to Present
3,142.0
0.0490
44
6,774
Default Wall 1978 to 1991
227.0
0.1100
44
1,099
Single Metal Tinted
80.0
1.2800
44
4,506
Single Metal Tinted
80.0
1.2800
44
4,506
72.0
1.2800
44
4,055
Default Wall 1978 to 1991
24.0
0.1100
44
116
Sencile Metal Tented
3.0
1.2800
44
169
Default Wall 1978 to 1991
667.2
0.1100
44
3,229
1,2800
44
3,604
Single Metal Tinted
33.0
1.2800
44
1.859
Single Metal Tanted
13.4
1.2800
44=755
Single Metal Tinted
23.5
1.2800
44
1,324
Sin le Metal Tinted
13.4
1.2800
44
755
Single Metal Tinted
4.5
1.2800
44=
253
Senqlp Metal Tontprl
nef -tit Wall 1978 to 1991
64.0
1.2800
44=3604
80.0
1.2800
44
4,506
24.0
44=116
Metal Tinted
3.0
1.2800
44
169
efault Wall 1978 to 1991
505.7
0.1100
44
2.448
42.4
1.2800
44
2,388
Mid Wnnd Dnnr
18.9
144500
44
1 206
Default Wall 1978 to 1991
842.0
0.1100
44
4,075
Slab -On -Grade
Derimeter=332.0
0.7300
44
10,664
Items shown with an asterisk (`r) denote conduction through an interior
Infiltration: f1 1.001 x 1.064 x
-Schedule Air Sensible
Fraction
to another room.
3142 X
Ceiling Height
0.448 / 6 ]
ACH
Page Total:
44
LT
62 179
g 8g0
TOTAL HOURLY HEAT LOSS FOR ROOM 72,059
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 10 of 14
ROOM HEATING PEAK LOADS
roject Title
r. & Mrs. David Carson Atrium Enclosure)8/27/2008
Date
Room Information Design Conditions
Room Name Atrium Enclosure
Time of Peak Jan 12 am
Floor Area 112
Outdoor Dry Bulb Temperature 26OF
Indoor Dry Bulb Temperature 70 OF
69.7
Conduction
Items shown with an asterisk (•r) denote conduction through an interior surface to another room. Page Total: 2 407
Infiltration: 1.001 x 1.064 x 112 x 9.00 x 6] x &T = 352
chedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 2759
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 11 of 14
Area
X
X
x
X
X
X
xx
x
x
x
x
x
X
x
X
x
x
x
X
X
X
X
x
X
X
X
X
X
X
x
X
x
X
X
X
X
x
x
x
U -Value
X
X
x
x
x
x
x
X
x
x
x
X
x
X
x
X
X
x
x
x
x
x
x
X
x
x
X
X
x
X
x
x
x
x
x
x
x
x
AT of
=
=
=
=
=
=
_
—
=
=
_
_
_
=
_
—
_
=
=
=
_
=
Btu/hr
69.7
0.0280
44
86
42.3
0.8000
44
1,489
99.0
0.1100
44
479
perimeter= 11.0
0:7300
44
353
Items shown with an asterisk (•r) denote conduction through an interior surface to another room. Page Total: 2 407
Infiltration: 1.001 x 1.064 x 112 x 9.00 x 6] x &T = 352
chedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 2759
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 11 of 14
RESIDENTIAL ROOM COOLING LOAD SUMMARY
roject Title Date
r. & Mrs. David Carson Atrium Enclosure 8/27/2008
Room Information Desicin Conditions
Room Name: Existing Residence Outdoor Dry Bulb Temperature: 111oF
Floor Area: 3,142 sf Outdoor Web Bulb Temperature: 730F
Indoor Dry Bulb Temperature: 78OFOutdoor Daily Range: 340F
Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr
•
Default Roof 1978 to Present
Default Wall 1978 to 1991
Default Wall 1978 to 1991
Default Wall 1978 to 1991
Default Wall 1978 to 1991
Default Wall 1978 to 1991
Solid Wood Door
Default Wall 1978 to 1991
N
3142.0
x
X
X
X
X
X
x
X
x
x
X
X
0.0490
X
X
X
X
X
X
X
x
x
X
X
x
56.0
=
=
=
=
=
=
=
=
=
=
N
227.0
0.1100
23.0
NE
24.0
0.1100
29.0
E
667.2
0.1100
33.0
SE
24.0
0.1100
31.0
S
505.71
0.1100
26.0
(S) .
18.9
1.4500
26.0
(W)
842.0
0.1100
33.0
E
0.0
50.1
64.0
89.9
5,752
E
0.0
50.1
33.0
89.9
2,966
E
0.0
50.1
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existin
Window Existing
Window Existing
Window Existing
Window Existing
Nage I otal
Orientation
Shaded
Area
X
X
X
X
x
x
x
x
X
X
GLF
+
+
+
+
+
+
+
+
+
+
Unshaded
Area
x
X
x
X
X
X
x
X
X
x
GLF
=
=
=
=
=
=
=
=
Btu/hr
N
0.0
50.1
80.0
50.1
4,007
N
0.0
50.1
80.0
50.1
4,007
N
0.0
50.1
72.0
50.1
3,607
NE
0.0x
50.1+
3.0X
71.6=
215
E
0.0
50.1
64.0
89.9
5,752
E
0.0
50.1
33.0
89.9
2,966
E
0.0
50.1
13.4
89.9
1,204
E
0.0
50.1
23.5
89.9
2,112
E
0.0
50.1
13.4
89.9
1,204
E
0.0
50.1
4.5
89.9
404
Internal Gain
Occu ants 4 Occupants X 230 Btuh/occ. _
E ui ment Dwelling Units X 1 600 Btuh =
Page Total 1 25,4791
Btulhr
920
1,600
Infiltration: 1.064 x 0.86 x 221.70 x 0 = 6,671
Air Sensible CFM ELA DT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 66,9311
Latent Gain Btu/hr
Occu ants771Occupants X 200 Btuh/occ. = 800
Infiltration: 4 77 X 0.86 X 221.70 X 0.00158 = 1 429
Air Latent CFM ELA pW
• TOTAL HOURLY LATENT HEAT GAIN FOR ROOM -629
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 12 of 14
RESIDENTIAL ROOM COOLING LOAD SUMMARY
)lect Title
r R Mrs navirl Carsnn (Atrium Fnr.InsI1rP_)
/?nnR
Room Information Desicin Conditions
Room Name: Existing Residence
Outdoor Dry Bulb Temperature: 111OF
Floor Area: 3,142 sf
Outdoor Web Bulb Temperature: 730F
Indoor Dry Bulb Temperature: 78OFOutdoor
Daily Range: 340F
•
r�J
J
ue Surraces
Orientation Area U -Factor CLTD 1
Items shown with an asterisk (') denote conduction through an interior, surface to another room. rage I o.tai
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Window Existing
Window Existin
Window Existing
Window Existing
Orientation
x
x
x
x
x
x
x
X
x
xx
x
X
X
X
X
X
x
x
X
x
x
X
x
x
x
x
x
x
x
x
x
x
x
+
+• •
+
+
+
+
+
+
+
+
Unshaded
Area
X•
x
X
x
x
x
x
x
x
X
Page
GLF
=
=
=
=
-
_
E
0.0
50.1
64.0
89.9
E
0.0
50:1
80.0
89.9
SE,
O.Ox
50.1+
3.0x
65.5=
S
0.0
50.1
42.4
50.3
Items shown with an asterisk (') denote conduction through an interior, surface to another room. rage I o.tai
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Window Existing
Window Existin
Window Existing
Window Existing
Orientation
Shaded
Area
X
X
X
X
x
x
X
x
x
X
GLF
+
+• •
+
+
+
+
+
+
+
+
Unshaded
Area
X•
x
X
x
x
x
x
x
x
X
Page
GLF
=
=
=
=
-
_
E
0.0
50.1
64.0
89.9
E
0.0
50:1
80.0
89.9
SE,
O.Ox
50.1+
3.0x
65.5=
S
0.0
50.1
42.4
50.3
Total
Btu/hr
Btu/hr
Internal Gain
• - Btu/hr
Occu ants 4 -Occupants X 230 Btuh/OCC. _ 920
E ui ment Dwelling Units X 1,6001 Btuh 1 600
Infiltration: 1.osa X 0.86 X 221.70 x = 6671
Air Sensible CFM ELA 4nT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 66,931
Latent Gain Btu/hr
Occu ants ® Occupants X 200 Btuh/OCC. = 800
Infiltration: 4 771 X 0.86 X 221.70 X -0.00158 = -1,4291
Air Latent CFM ELA pW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM -629
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 13 of 14
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Title Date
1r. & Mrs. David Carson. Atrium .Enclosure . 8/27/2008
Room Information Desi n Conditions
Room Name: Atrium Enclosure Outdoor Dry Bulb Temperature: 11 1O
Floor Area: 112 sf Outdoor Web Bulb Temperature: 730F
Indoor Dry Bulb Temperature: 75 of Outdoor Daily Range: 340F
Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr
IDefault Wall 1978 to 1991 1
N
69.7
X
X
X
X
X
X
X
X
X
X
X
X
0.0280
X
X
X
X
X
X
X
X
X
X
X
X
56.0
=
=
=
=
X 230 Btuh/occ.
99.0
0.1100
33.0
1welling
Dwelling Units
X 1,6001 Btuh _
1 600
Infiltration: 1.064 X 0.88 X
7.90 ' X =
268
Air Sensible CFM
ELA OT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
6,3281
Gain
Btu/hr
rrLatent
loccupants 0 Occupants
X 200 Btuh/occ. =
400
Infiltration: 4771 X 0.88 X
7.90 X -0.00058 =
-19
Air Latent CFM
ELA pW
Items shown with an asterisk (') denote conduction through an interior surface to another room. ,
rage I vial
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Shaded Unshaded
Orientation Area GLF Area GLF Btu/hr
(Sky) 0.0 X 30.7 + 42.3 X 83.5 = 3,532
X + X —
X +, ., X
X + X
X +, X
X + X
X + X
X. + X.
X + X
X + X
X + X
Page Total 3 532
Internal Gain
'
Btu/hr
Occu ants
2
X 230 Btuh/occ.
460
E ui ment'
1welling
Dwelling Units
X 1,6001 Btuh _
1 600
Infiltration: 1.064 X 0.88 X
7.90 ' X =
268
Air Sensible CFM
ELA OT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
6,3281
Gain
Btu/hr
rrLatent
loccupants 0 Occupants
X 200 Btuh/occ. =
400
Infiltration: 4771 X 0.88 X
7.90 X -0.00058 =
-19
Air Latent CFM
ELA pW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 381
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 14 of 14