BCOM2017-0028BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Desert Vein & Vascular Institute TI
79440 Corporate Center Way, Suite 1.19 +
La Quinta,• CA 92253
Project Designer:
Lawrence C.Reeves, L.P.
49-850 Jefferson St., Suite 130
Indio, CA 92201
(818) 425-0830
Report Prepared by:
Tim Scott
Scott Design and Title 24, Inc,
74-818 Velie Way, Suite #8
Palm Desert, CA 92260
(760) 200-4780
CITY OF"iA QUINTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
R "'DVED
Job Number: AU6 0 3 2917
� .J .: ,.. UINTA
0�'Ii�1)Nf iY 64-VELOPMENT
Date:
7/25/2017
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2016 Building Energy Efficiency Standards.
This program developed by EnergySoft Software — www.energysoft.com.
TABLE OF CONTENTS' '
Cover Page
Table of Contents
Form PRF -01-E Certificate of Compliance ,
Form ENV -MM Envelope Mandatory Measures: j
Form ELC-01-E Electrical Power Distribution - - I
HVAC System Heating and Cooling Loads Summary
Zone Load Summary
1
2
3
22
23
29
30
�a..mnc.rcmm,.
10 113
Js -31C Y11RA8 A aOWa , JIUS
r
r y ;r",t'
i
EnergyPro 7.1 by EnergySoft Job Number. ID: User Number. 6712
t
r
,
�a..mnc.rcmm,.
10 113
Js -31C Y11RA8 A aOWa , JIUS
r
r y ;r",t'
i
EnergyPro 7.1 by EnergySoft Job Number. ID: User Number. 6712
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 1 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
A. PROJECT GENERAL INFORMATION
_ _ _ __ _
4140.1.,
1.
Project Location (city)
La Quinta
S.
Standards Version
Compliance2016
2.
CA Zip Code
92253
9.
Compliance Software (version)
EnergyPro 7.1
3.
Climate Zone
15
10.
Weather File
PALM-SPRINGS-INTL_722868_CZ2010.epw
4.
Total Conditioned Floor Area in Scope
3,221 ft2
11.
Building Orientation (deg)
(S) 180 deg
S.
Total Unconditioned Floor Area
0 ft2
12.
Permitted Scope of Work
ExistingAlteration
6.
Total # of Stories (Habitable Above Grade)
1
13
Building Type(s)
Nonresidential
7.
Total 4 of dwelling units
0
14
Gas Type
NaturalGas
B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft 2 -yr). _...
_ _ _ __ _
4140.1.,
BUILDING COMPLIES --
- - -
- - -
1. Energy Component
2. Standard Design (TDV)
3. Proposed Design (TDV)
4. Compliance Margin (TDV)
S. Percent Better than Standard
Space Heating „
0.32
0.35
-0.03
-9.4%
Space Cooling
213.04
202.91
10.13
4.8%
Indoor Fans ' '
160.80
159.38
1.42
0.9%
Heat Rejection 1 -
Pumps & Misc.
Domestic Hot Water
+ 5.11
15.49
-10.38
-203.1%
Indoor Lighting
78.27
41.49
36.78
47.0%
COMPLIANCETOTAL - -
457.54
419.62
37.92
8.3%
Receptacle - _
- ' " - 110.83
110.83
0.0
0.0%
Process.-
Oth'ar I'tg--
TOTAL' , ' '
568.37
530.45
37.9
6.7%
��.� '• _`+-`Y.� -._; - � r. ._.-.: -�._ •� ,, .. ti+-�-!' _.._.,»�_.-�.- ..ate. �..... .._ r�--^r r ._. �.. .. .w ..(__. t.. _ _ _'r _ _��..� F .. ... ...' � .....f
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
� F '
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 2 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlteration
input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
C. PRIORITY PLAN CHECK/ INSPECTION ITEMS (in order of highest to lowest TDV energy savings)
1st
Indoor Lighting: Check lighting
Compliance Margin By
Energy Component (from Table B column 4)
Indoor Lighting
Space Cooling
1 I
2nd
Space Cooling: Check envelope and mechanical
3rd -
Indoor Fans: Check envelope and mechanicals
�. �
—
- Indoor Fans
"4th"
Heat Rejection: Check envelope and mechanical
" "
Heat Rejection_
_ _ _ • -
�+
5th _
Pumps &'Misc.: Check mechanical'
_ Pumps & Misc. _
!
'6th
Space Heating: Check -envelope
and mechanical
t'
Space Heating-
Domestic Hot Water
-
,7th'
.
Domestic Hot Water: Check mechanical-
D. EXCEPTIONAL CONDITIONS
This project includes Domestic Hot Water in the analysis. Please verify that Domestic Hot Water is included in the design for the permitted scope of work. _
E. HERS VERIFICATION
This Section Does Not Apply , r n
F. ADDITIONAL REMARKS
None Provided �---• _ .' . - _ _ _ .
�. s t R -
.. .. .+. w � ._ _ w. •+rt ..n - . .. .- _ _ y.y.- ._ . _.+ w i. r+s• �r _. r+. ....i: - _.moi.. . .. �c.I .r - .. i.� - i..+.iElr�-..�-..rM s.— w • .w.r._ � ..A � ..r._� wa.►r -. �.�.w �
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 3 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
Identify which building components use the performance or prescriptive path for compliance. "NA "= not in project
For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans.
Building Component
Compliance Path
Compliance Forms (required for submittal)
Location of Mandatory Notes on
Plans
Envelope
❑ Performance
NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-ENV-01 / 02 / 03 / 04 / 05 / 06-E
® NA
Mechanical
® Performance
NRCC-PRF-MCH-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
INA
NRCC-MCH-01 / 02 / 03 / 04 / 05 / 06 / 07-E
❑
Domestic Hot Water
® Performance
NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-PLB-01-E
❑ NA
- - -
Lighting (Indoor Conditioned)
.
® Performance --
NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-01-E) - - - -
- - -
r
❑ Prescriptive
NRCC-LTI-01 / 02 / 03 / 04 / 05-E y w
❑ NA
Covered Process:
Commercial Kitchens -�
1.
❑ 'Performance
52 (section of the NRCC-PRF-01-E) '
_
,
❑ Prescriptive
NRCC PRC Ol/ 03-E
® NA
{
Covered Process:
Computer Rooms. .o
❑ Performance
S3 (section of the NRCC-PRF-OS-E)
,
❑ Prescriptive
NRCC-PRC-01/ 04-E i
® NA
' _ . a' "`
Covered Process: _ _ `_ _.. _
Laboratory Exhaust
❑ Performance '
S4 (section of the NRCC-PRF-01-E)-
❑ Prescriptive
CC-PRC-01/09-E-
NRCC-PRC-01/0!)-E-
NA
E t
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 4 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
The following building components are only eligible for prescriptive compliance. Indicate which ore
The following building components may have mandatory requirements per Part 6. Indicate
' relevant to"the project. "' - " _ "` `
- "" " " which are relevdntfto the project.
Yes NA
Prescriptive Requirement
Compliance Forms `
Yes NA'
" Mandatory Requirement
Compliance Forms
El®
Lighting (Indoor
NRCC-LTI-01 / 02 / 03 / 04 / 05-E
❑ -. ®.
Commissioning §120.8'
_ ._ Simple Systems
NRCC-CXR-01 / 02 / 03 / 05-E
Unconditioned) §140.6
❑ ®
Complex Systems
NRCC-CXR-01 / 02 / 04 / 05-E
❑ ®
Lighting (Outdoor) §140.7
NRCC-LTO-01 / 02 / 03-E - :
® ❑
Electrical: §130.5
NRCC-ELC-01-E
❑ ®
Lighting (Sign) §140.8
NRCC-LTS-01-E
❑ ®
Solar Ready: §110.10
NRCC-SRA-01 / 02-E
Covered Process: §120.6
NRCC-PRC-01-E
-
❑ ®
Parking Garage
NRCC PRC 02 E
-Solar
❑ . ®
Thermal Water f
i
NRCC STH OSE
❑ - ®
— - Commercial Refrigeration- -
NRCC-PRC-05-E _
1. .. _ Z '�
Heating: §140.5
❑ ®
Warehouse Refrigeration
NRCC-PRC-06/07/08-E
z
r -'
❑ ' ®
Compressed Air
NRCC-PRC-10-E
-
❑ ®
Process Boilers - -
NRCC-PRC-11-E
T
•,�� .. '.. ., >
1. .. _ Z '�
._ - '
s»i,
y..._ .r—,F. «.� -.�- _.. ,.. _ �....._...... rr.•..
•-• _ -" r'.'�`.`r - .r
,TWt.`,�ri...wt.,
. _.
�
. r r r .Y. r .. r .
_ _-•••',+. iw. .i. a..w �5. ....;y.,�,y..._'�.t,..'�.- i =+. r—
�•...._ .� �w ✓ _y.♦t:er _4r.r r..trr . w,.
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance
Report Version: NRCC-PRF-01-E-07122017-4377
Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 5 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253 `
Calculation Date/Time: '
16:45, Tue; Jul 25, 2017- '
Compliance Scope:-.
ExistingAlteration - -
Input File Name: -� •
Desert Vein Tl -La Quinta-TCZ-17.cibdl6x. - -
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) -
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance ~,
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections,for,Acceptance Tests and forms by equipment.
Confirmed w
Building Component _
Compliance, Forms (required for submittal) _ ,. _ _ _ _- _.
Pass,
Fail
'Envelope
El - For all buildings , _ .. _ ..
El
1:1_ .
,
❑ NRCA-ENV-02-F- NFRC label verification for fenestration _ ._ . _ _ _ _ - _. _ _ . -
❑
❑
'
Mechanical
+
'
-
' {
® NRCI-MCH-01-E - For all buildings with Mechanical Systems. _ _ _ _ _ _ _
_ ❑
❑ _
❑ NRCA-MCH=027A-,Outdoor. Air _ _ _ _ . ._ _ _ .. _
__ .❑
. ❑
❑ NRCA-MCH-03-A-Constant Volume Single Zone HVAC _ _ __ .. _ ._. _ _ _
_ ❑
❑ .
❑ NRCA-MCH-04-H- Air Distribution Duct Leakage _ _ __ _ _ _ _
❑
❑ .
❑ NRCA-MCH-05-A- Air Economizer Controls . t
❑
❑
❑ NRCA-MCH-06-A- Demand Control Ventilation - -
❑
❑
❑ NRCA-MCH-07-A-Supply Fan Variable Flow Controls
❑
❑-
❑} NRCA-MCH-08-A- Valve Leakage Test '
❑ '
❑
❑ NRCA-MCH-09-A-Supply WaterTemp'ResetControls -^
❑
❑
❑ NRCA-MCH-10-A- Hydronic System Variable Flow Controls'" _ `" -
❑
❑ -
❑ NRCA-MCH-1I-A-Auto Demand Shed Controls`
❑
ElNRCA-MCH 12-A- Packaged Direct Expansion Units -
❑
El
❑ NRCA-MCH-13-A- Air Handling Units and'Zone Terminal Units ' "" ' ' _ _ _ _..
_ ❑..
_ ._❑ _ _
❑ NRCA-MCH-14-A- Distributed Energy St6 age -
13
❑ -
0-NRCA-MCH-15-A- Thermal Energy Storage - _ _ _
❑.
❑ _
❑ 'NKA;MGH-16-A-'5uouWAir Temp -Reset Controls' _
❑
❑ NRCA-MCH-17-A = Condensate Water Temp Reset Controls i ' -" - _ . . _
❑
❑
❑ .NRCA-MCH-18-A- Energy Management Controls Systems
❑
❑
❑ NRCV-MCH-04-H- Duct Leakage Test T
❑
❑
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 6 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) --
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance -Tests and forms by equipment.
• .
- Confirmed -
Building Component
Compliance Forms (required for submittal)
"Pass
Fail
Plumbing
® NRCI-PLB-01-E:,For all buildings with Plumbing Systems - _
❑
❑
❑ NRCI-PLB-02-E - required on central systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-PLB-03-E - Single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-PLB-21-E :HERS verified central systems in high-rise residential; hotel/motel application. -,
❑
❑- "
❑ NRCI:PLB-22-E -HERS verified single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCV-PLB-21-H- HERS verified central systems in high-rise residential,`hotel/motel application.
❑
❑
❑ NRCV-PLB-22-H - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application. -
❑
❑
❑ NRCI-5TH-01-E - Any solar water heating - - -
❑
❑
Indoor Lighting
-
® NRCI-LTI-01-E - For all buildings ; % . - - - -
❑ "
-
❑ NRCI-LTI-02-E = Lighting control system, or for an Energy Management Control System (EMCS) -
❑
❑ `
❑ NRCI-LTI-03-E - Line -voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to
energize only.line-voltage track lighting
❑ NRCI-LTI-04-E - Two interlocked systems serving an auditorium, a convention center, a conference room, or a theater _
❑ _
❑ -
❑ NRCI-LTI-05-E - Lighting Control Credit Power Adjustment Factor. (PAF) _
❑
❑
❑ NRCI-LTI-06 E - Additional wattage installed in a video conferencing studio _ .. _ _
❑
❑
❑. NRCA-LTI-02-A -Occupancy sensors and automatic time switch controls.
❑
❑ -
❑ NRCA-LTI-03-A - Automatic daylighting controls - _ _
❑
❑
❑ NRCA-LTI-04-A - Demand responsive lighting controls _
. ❑.
_ ❑ .
_. _.
4
Outdoor Lighting . '
❑ NRCI-LTO-01-E- Outdoor. Lighting _ _. _ _ -. _
❑
❑
❑ 'NRCI-LTO-02-E- EMCS Lighting Control System
❑
❑
❑ NRCA-LTO-02-A -Outdoor Lighting Controls
❑
❑
Sign Lighting =
❑ NRCI-LTS-01-E -Sign Lighting • - ; 4- . ` h - )
❑
❑
Electrical' - - -
® NRCI-ELC-01-E - Electrical Power Distribution' — -
❑ -
❑
Photovoltaic
❑ NRCI-SPV-01-E Photovoltaic Systems - `"' • -
❑
-
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 7 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlte ration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment. J , - y
Confirmed
s- • �i -
Building Component
Compliance Forms (required for submittal) , r�
Pass
Fail
_• _ , , __ •_ _ -
_ -- , -_
`
Covered Process ,,-
T '
•
❑ NRCI-PRC-01-E Refrigerated Warehouse_ r {
❑
❑
❑ NRCA-PRC-01-F- Compressed Air Systems _-, - • , _ _ _ -, _ . , _ _ . _ -. _ _ _ -
❑
❑ _ -
❑ NRCA-PRC-02-F- Kitchen Exhaust _ _ _
❑
0 ftz -
❑ NRCA-PRC-03-F- Garage Exhaust
❑
❑
❑ NRCA-PRC-04-F- Refrigerated Warehouse- Evaporator Fan Motor Controls
❑
❑
❑: NRCA-PRC-05-F- Refrigerated Warehouse- Evaporative Condenser Controls
❑
❑
❑ NRCA-PRC-06-F- Refrigerated Warehouse- Air Cooled Condenser Controls
❑
❑
❑ NRCA-PRC-07F- Refrigerated Warehouse- Variable Speed Compressor
❑
❑
❑ NRCA-PRC-08-F- Electrical Resistance Underslab Heating System i" t
❑
❑
I. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more information):
1;
Total Conditioned Floor Area _
3,221 ft?
S. Number of Floors Above Grade
1
Confirmed
2.
Total Unconditioned Floor Area -
0 ftz -
-6. Number of Floors Below Grade
0 - -- - -
- --
d
d
-
3.
Addition Conditioned Floor Area 0 ftz 'ut
4.
Addition Unconditioned Floor Area 0 ftz
,7. Opaque Surfaces & Orientation - - - S. Total Gross Surface Area 9. Total Fenestration Area 30. Window to Wall Ratio
North Wall `
468 ftz
75 ftz,
f 16.0%
❑
❑
East Wall
i 738 ft'
i 0 ftz
t 00.0%
❑
El
South Wall
468 ftz a rt- , a4
105 ft?
! _ ° r 22.4%
❑
❑
West Wall-- _ __
_
` 738 ft' - _ — _ _ . _ - • _
165 ft'
.22.4%
Q
; ❑
—Total
_ _
- - - 2,412 ftz
345 ftz
_ . _ _ ` ..- - - 14.3%
❑ �
❑
Roof , ,' _ . _ .
..
- - - - * - 3,220 ftz _. _ . _.. - - — -
0 ftz
- — . _ 00.0%
❑
❑
-
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 8 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
.ompliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
J. FENESTRATION ASSEMBLY SUMMARY - - - - - . - - - --- --+ - - -
§ 110.6
Confirmed
L
2. -
3.
- 4.
^5i
6. -
7.
8.
_'9.
_
-
Surface Type
Area (ft2 )
--.Framing -
Type
Cavity -
R -Value
-Continuous
R -Value
U-Factor/F-Factor
/ C -Factor
,- iu'
N'
N
°'
-
R-30 Roof9
Roof
Fenestration Assembly Name/•-
Fenestration Type ProductType
Method"
Assembly Method
;. Area ft2
Overall
Overall
OverallCertifcation
R-19 Wall (W.19.2x6.16)11
ExteriorWail
OT
1
Tag or I.D.
/ Frame Type
NA
U -Factor: 0.072
E ,
U -factor
SHGC
VT
v,
738
Wood
11
VerticalFenestration
U -Factor: 0.110
E
❑
❑
Slab On Grade28
UndergroundFloor
3220
1
0
Existing Window - ^
' FixedWindow
Default Performance
Manufactured
345
0.71
0.73
0.77
E
�❑
❑
-•. -
..--.- MetalFraming
` Newly installed fenestration shall have a certified NFRC Label Certificate or use the CEC default tables found in Table 110.6-A and Table 110.6-8. Cinter of Glass (COG) values are for the glass -only, determined by the manufacturer, and are shown for ease
of verification. Site -built fenestration values are calculated per Nonresidential Appendix NA6 and are used in the analysis. - - -
2 Status: N- New, A -Altered, E- Existing
f v -
Taking compliance credit for fenestration shading devices? (if "Yes'; see NRCC-PRF-ENV-DETAILS for,more information) - - No
K. OPAQUE SURFACE ASSEMBLY SUMMARY
§ 120.7/ § 140.3
Confirmed
L
2. ' ^
_
• 3_.
4.
S.
6.
7.
8.
_
- - --
Surface Name - •
Surface Type
Area (ft2 )
--.Framing -
Type
Cavity -
R -Value
-Continuous
R -Value
U-Factor/F-Factor
/ C -Factor
,- iu'
N'
N
°'
-
R-30 Roof9
Roof
3220
NA
0
30
U -Factor: 0.030,
E
❑
❑
R-19 Wall (W.19.2x6.16)11
ExteriorWail
1674
Wood
19
NA
U -Factor: 0.072
E ,
❑
❑
R-11 Wall Partition18
ExteriorWall
738
Wood
11
NA
U -Factor: 0.110
E
❑
❑
Slab On Grade28
UndergroundFloor
3220
NA
0
NA
F Factor: 0.730
E
❑
El
' Status: N -New, A - Altered, E - Existing - -
L. ROOFING PRODUCT SUMMARY _ _ _ _ . _ _- _
§ 140.3
Confirmed
L
2.
3.
4.
5.
6.
7.
_
Product Density
Aged Solar
Thermal
Cool Roof
Roofing Product f
�
N
T
°-t
-- - - Product Type - -
„L . • _
(Ib/ft2 (
-
Reflectance
Emittance
SRI .
Credit
Description
-.
R-30 Roof9
5.32333
0.08
0.75
NA
NO
NA
❑
❑
-l- +• C '
a
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 9 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlte ration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information)
I § 110.1 / § 110.2
Dry System Equipment 1(Fan & Economizer info included below in Table N)
Confirmed
1.
2.
3.
4.
S.
6.
7.
S.
9.
10.
11.
23.
24.
1
System Type
Equip Type
Total Heating
Supp Heat
Supp Heat
Total Cooling
Efciency
Acceptance
Testingzor
�
0''
d=n
EquipName
Equip Type
(Simple
Qty
Output
Source (Y/N)
Output
Output
(k6t6/h)
Required? (Y/N)
Nm
TSP
Complex 3)
N
(kBtu/h)
(katuh)
(kBtu/h)
°
4,
v,
CFM
Cooling
Heating
- AC 1- 4
521-10'(SpIit3Phase)
,^ Simple _
4
, 54'-_
No-
..0, - ,
53
SEER -12.0 /
HSPF-7J
No
` E
❑
ET
NA _
NA
NA
NA
No .1
: �
❑
❑
EER -10.0
AC 1- 4
121
3 Dry System Equipment includes fumnces, air handling units, heat pumps, etc.
2 Simple Systems must complete NRCC-CXR-03-E commissioning design review form
3 Complex Systems must complete NRCC-CXR-04-E commissioning design review form
4 A summary of which acceptance tests are applicable is provided in NRCC PRF -MCH -DETAILS
5 Status: N - New, A=Altered, E- Existing
Wet System Equipment 1
-' Pumps- •
Contirmed
Confirmed
- 12.
-13.
14.
15.
' 16."
17 "-
`18:
19.
20.
21.
22.
23.
24.
1
- - Equip Name
Equip Type
Qty
Vol (gal)
Rated Capacity
Efficiency _
•.
Standby Loss
Tank
Ext. R
Qty
GPM
HP
VSD
d
N
Economizer Type
N
01
(k6t6/h)
TSP
(Y/N)
N
TSP
Equip Name
(If present)
CFM
- CFM -
Value
BHP
(inch ..
Control
-CFM -
-HP
BHP
(inch
AO SMITH EUF-06*2
Storage
3-1
6 -
1_ 5 _._.
EF: 0.950._
NA
NA _
NA
NA
NA
No .1
N
❑
❑
1 Wet System Equipment includes boilers, chillers, cooling towers, water heaters, etc.
? Status: N - New, A - Altered, E - Existing
Discrepancy between modeled and designed equipment sizing? (if "Yes", see Table F. "Additional Remarks" for an explanation) No t
N. ECONOMIZER & FAN SYSTEMS SUMMARY' _< ' .
g 14CIA
Contirmed
1.
2.
f 3.
4.
5.
Outside
`
._.. Supply Fan_
Return Fan
'Air
_.. _ _. - - - -
--- - - -
- -
V
T
Economizer Type
N
01
TSP
TSP
Equip Name
(If present)
CFM
- CFM -
-- HP.
BHP
(inch ..
Control
-CFM -
-HP
BHP
(inch
-Control-
WC)
WC)
AC 1- 4
121
1800
1.000
1:000
1.76
'ConstantVolume
NA
NA
NA
NA
NA
NoEconomizer
❑
❑
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-OS-E
Page 10 of 19
Project Address: ,
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017 "
Compliance Scope:
ExistingAlteration r
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
1 Mechanical ventilation calculations and exhaust fans are included in the NRCC-PRF-MCH-DETAILS section 4 ,
O. EQUIPMENT CONTROLS
§ 120.2
Confirmed
1.
2.
3.
o,
r
d
—
Equip Name
Equip Type
Controls
,V,
-n
No DCV Controls
-
Equip Type _.
Dud Leakage and Sealing
Required per 140.4(1)
<
Duds _
No Economizer
Location
AC 1- 4
- AC 1- 4
SZHP
No Supply Air Temp. Control'
❑
❑
❑
❑
No Optimum Start
No Evaporative Cooler
Res DHWS - SHW _
Service Hot Water, Primary Only
Fixed Temperature Control, No DDC _ . _ _
❑
❑
P. SYSTEM DISTRIBUTION SUMMARY
§ 120.4/ § 140.4(1)
Dry System Distribution
Confirmed
,V,
-n
J
Equip.Name _ _. , .
-
Equip Type _.
Dud Leakage and Sealing
Required per 140.4(1)
"Duct Leakage will be
verified per. NAl and
NA2
Duds _
Insulation R -Value_
Location
AC 1- 4
SZHP .
No
No
8
Unconditioned
❑
❑
Does the Project Include Zonal Systems? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) No
Does the Project Include a Solar Hot Water System? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) No
Multifamily or Hotel/ Motel Occupancy? (if "Yes", see NRCC-PRF-MCH-DETAILS for DHW system information) +, No
I.y
_..elL_
.. _ .. .... _.. _. •-ter_....'. ... _ .{ _ _ � - � _.....�. .. .-_.. .. _ .r i .. .. -"_ - is _.� ._ -.... __•• _..; , _ _` 1:�
.. .. . . • _ _ r _�. ,_, .. � _ .. ori _, - - _r... --._ _ .. n - r • �_ --
lit Y1• r •. . .jr �_ _.. .. r_ ter- .. .-w. w - .p i:.e, 141 + 'r .�� •,<-P . ". .. ,.r _- ...
+r... �. r. arm. -... -� �L,_s+� ar.... �...1 _ �.ti. .rte. ._ .. i..ta ��. titi-v ....1�. ..r. _s ..Y.�.- . .. r j-..�_+w.. .. ., ...--.r- .�. _ •yF�-�.c..�..._....•. ... .-i ..,N....+ti......a.....�.w �.. ... �.i..�. ..r .. ..�_
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Iject Name:
Tenant Improvement
NRCC-PRF-01-E
Page 11 of 19
Iject Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
mpliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info)'
§ 140.6
Luminaire Schedule (includes all permanent installed lighting in
conditioned space, and portable lighting over 0.3 w/ft' in
offices) _
Confirmed
1.
2.
3.
4.
5.
-
Total Number
Luminaires
R -
Installed Watts
Pass
Fail
CEC Default '
from NAB
According to
§130.0(c)
A
- - W-13.2 W Can
-13
1,4
Occupancy Type
Conditioned Floor Area Z
Installed Lighting Power
Lighting Control Credits
Additional (Custom) Allowance
N
°-T'
(3) 4 ft Fluorescent T8
(ftl)
(Watts)
• (Watts)
6
474
❑
❑
_ Y
E -Cove -3 W/F
3
Area Category Footnotes
Tailored Method (Watts)
❑
❑
1 ❑
❑
(Watts)
Medical and Clinical Care
3,221
2,049
0
0
0
❑
❑
Building Totals:
• , 3,221
2,049
.. 0
0
0
1 See Table 140.6-C
1 See NRCC-LTI-01 -Efor unconditioned spares — - -
3Lighting information for existing spaces modeled is not included in the table
4Multiple entries for an Occupancy Type may be listed in the table as these have been aggregated for Building Stories that have the some floor multiplier.
R. INDOOR CONDITIONED LIGHTING SCHEDULE.(Adapted from NRCC-LTI-01-E)1 _
§ 130.0
Luminaire Schedule (includes all permanent installed lighting in
conditioned space, and portable lighting over 0.3 w/ft' in
offices) _
_
Installed Watts (Conditioned)
- -
Confirmed
_
Name or Item Tag
Complete Luminaire Description (i.e.,
3 -lamp fluorescent troffer, F32T8,
one dimmable electronic ballast)
Watts per luminaire
How Wattage is Determined
-
Total Number
Luminaires
R -
Installed Watts
Pass
Fail
CEC Default '
from NAB
According to
§130.0(c)
A
- - W-13.2 W Can
-13
- Yes
No
- 85
-1,121
❑
❑
C
(3) 4 ft Fluorescent T8
79
Yes
No
6
474
❑
❑
E
E -Cove -3 W/F
3
Yes
No
151
453
1 ❑
❑
'if lighting power densities were used in the compliance model Building Departments will need to check prescriptive forms for Luminaire Schedule details.
61, COVERED°PROCESS SUMMARY - ENCLOSED PARKIN! GARAGES § 140.9
This Section Does Not Apply - - -
S2: COVERED PROCESS SUMMARY - COMMERCIAL KITCHENS - - - §140.9 -
This Section Does Not Apply
i
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 12 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
S3. COVERED PROCESS SUMMARY - COMPUTER ROOMS - - ' ' § 140.9-
This
40.9-This Section Does Not Apply - - - - - - - - - -
54. COVERED PROCESS SUMMARY - LABORATORY EXHAUSTS - - _ - - - - - -` `-- § 140.9
This Section Does Not Apply-
T.
pply
T. UNMET LOAD HOURS '
This Section Does Not Apply i »
U. ENERGY USE SUMMARY -
Energy'Component
Standard Design Site
(MWh)
Proposed Design Site
(MWh)
Margin'
(MWh)
Standard Design Site
(MBtu)
Proposed Design Site
(MBtu)
Margin
(MBtu)
Space Heating
0.1
0.1
0.0
Space Cooling
24.0
22.7
1.3:
Indoor Fans
._ 24.1
23.8
0.3
Heat Rejection
--
--
--
Pumps & Misc.
--
-
-
-
--
Domestic Hot Water
--
2.2
--
11.4
--
Indoor lighting
10.8
5.7
5.1
--
--
COMPLIANCE TOTAL
59.0
54.5
4.5
11.4
0.0
--
Receptacle
14.7
14.7
0.0
10.0
10.0
0.0
Process
-
--
--
--
--
Other Ltg
-
--
--
TOTAL
73.7
69.2
4.5
21.4.,
j . ,10.0
11.4
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 13 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
§ 10-103
1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Tim Scott
Signature•
Company: ScottDesign and Title 24, Inc, ' J� ; "' -''
Address: 74-818 Velie Way, Suite.#8 I Signature Date:
City/State/Zip: Palm Desert CA 92260 CEA Identification (If applicable): r, • i
Phone: (760)200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following undei peniltyof perjury, undenthe laws of the State of California:
-
I hereby affirm that I am eligible under the provisions of,Division 3 of,the Business and Professions Code to sign this.document as the.person responsible for.its preparation; and that I am
1
licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
I affirm that -I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3 to sign this document as the person responsible for its `
2
preparation; and that I am a licensed contractor,performing this work..
I affirm that I am eligible under Division 3 of the' Business and Professions Code to sign this document because it pertains to a structure`or type of work described as:exempt pursuant to
3
Business and.Professions Code Sections 5537, 5538 and 6737.1.
Responsible Envelope Designer Name: Lawrence C.Reeves �'
` -- - - - -ignature: NOT 1N SCOPE f_ _ V
Company: Lawrence C.Reeves, L.P. I
Address: 49-850 Jefferson St., Suite 130 ' `- ,, bate Signed:
City/State/Zip: Indio CA 92201 I Declaration Statement Type:
Phone: (818) 425-0830 �. ` Title:
License #:
Responsible Lighting Designer Name: Lawrence C.Reeves . •c , t I
ignature:
Company: Lawrence C.Reeves, L.P.
Address: 49-850'Jefferson St., Suite 130 • _` Al - Date Signed:
City/State/Zip: Indio CA 92201 { Declaration Statement Type: t
1. J-
Phone:(818)425-0830 Title: =License '
Responsible Mechanical Designer Name: Tim Scott
.. ... .: _. . _ _ ,. ,._ Signature:
Company: Scott Design and Title 24, Inc.
Address: 77085 Michigan Drive --- - - - - -- -- »- - -- - Date Signed: - - - --- - -- --- .-,,- - - •- -- - - -
City/State/Zip: Palm Desert CA 92211 - Declaration Statement Type:
Phone:(760)200-4780 - — _._ _ .__. _. _ _.- _ - - - - -- �• Title: __. �._. _ ._ License#: -.. �_ _ _ w.
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name: - Tenant Improvement -- - t NRCC-PRF-01-E Page 14 of 19 - - - -
Project Address: 79440 Corporate Center Way, Suite 119 La Quinta 92253 - Calculation Date/Time: 16:45;-Tue, Jul 25, 2017 — - - - - -
Compliance Scope: - ExistingAlteration - - - Input File Name: - - Desert Vein•TI-La-Quinta-TCZ-17.cibdl6x
NRCC=PRF=ENV-DETAILS =SECTION START
A. OPAQUE SURFACE ASSEMBLY DETAILS
Confirmed
1.
2.
3. -
4.
v
N
n
—
Surface Name
Surface Type
Description of Assembly Layers
Notes
_
_ _ .
.• Plywood, -,S/8 in.
- Area
U -factor
Statusl
R-30 Roof9
Roof
Glass fiber batt - 10 in. R30 (CEC Default)
Metal UninsulatedSingleLayerpoor
❑
❑
20,
0.079
Air - Cavity - Wall Roof Ceiling - 4 in. or more
❑
❑
HB Part. Brd - 3/4 in.
r
Stucco' -.7/8 in.
R-19 Wall (W.19.2x6.16)11
y ExteriorWall
Vapor permeable felt - 1/8 in. " -
`wall,
-"" �- -
11
El
-
- -
- Wood framed 16in. OC, 5.5in., R-19
Gypsum Board - 1/2 in.
"
Stucco - 7/8 in.
R-11 Wall Partition18 T
ExteriorWall ,•
Vapor permeable felt - 1/8 in.
❑
❑
Wood framed wall, 16in. OC, 3.5in., R-11
Gypsum Board - 1/2 in.
Slab Type = UnheatedSlabOnGrade
Slab On Grade28 ..
Underground Floor
_ _ _ " _ - Irisulation Orientation = None Y _ _ .'_ : _ - _;
' '
_ :.❑
w ❑ _
%_
_ Insulation R -Value = RO
B. OVERHANG DETAILS (Adapted from NRCC-ENV-02-E)
This Section Does Not Apply
C. OPAQUE DOOR SUMMARY w -
Confirmed
1.
2.
3.
4.
S.
6.
7.
Opaque Door Assembly NameOverall
/ Tag or I.D.
Door Type
--•- - -
Certification Method
-
Operation
- Area
U -factor
Statusl
Pass
Fail
Insulated Metal Door16
Metal UninsulatedSingleLayerpoor
DefaultPerformance
Swinging
20,
0.079
E
❑
❑
{ 3 Status: N -New, A —Altered, E— Existing
- . i . • 1.. oaf. - -r ,r ._- .
�-pG: j ' r .. - � � i= Y•.-,.1 ' ,- ../t+`.{ • - .., - _ - _ _ _ .. � - .... �:;,.F-ter • ' � t J , ti� T J _ _ '� _ _ �• •-- • ..
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 15 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:'
• ExistingAlteration "' "``
Input File Name:
Desert Vein TI -La Quinta-TCZ47.cibd16x
i
NRCC-PRF-MCH-DETAILS -SECTION START
A. MECHANICAL VENTILATION AND REHEAT (Adapted from 2016-NRCC-MCH-03-E) f_
Confirmed
' 1. DESIGN AIR FLOWS
2. VENTILATION
(§ 120.1)
4.
5.
6
7
8.
Confirmed
H
3
Rated Capacity
_
p
9
m
System ID
System Type
Qty
(kBtuh)
Economizer
Zone Name
°a,'
4
G1
O
Z
Design
_
_ Min.
O
0
a
y Z
3
N
G1
Z
O
N
Z
'^
a
Z.
G1
Z
y
D z
.�v
OCr
�
�3
,
O�
n
m
I C
1
Z
Z
TT
<
^'
G1
2
T
m
NA, _
f. to
AG
__._} _.NA
1 -Tenant Improvement
^CONDITIONED
NA:. _
NA_
O
,._.NA �
3
_ 3
-❑
Improvement-Trm
('
.3
3
D
D-
<
- iE
IU
T
m
G
Or '.
T 3
D
��
v
��
�
�m
Z
<
m
$ Z...
i
p•
- .Z
r
<
�a
--o
N
ZONE NAME
Z
3�
n
3
n=
3 !'
1
A
Or
3
O
v
^'
rO,D'y
M m
3-�
O
Z
E
G1
D
r3
OD
--Z
02
m0
�r
3
Z<
G1
ZOZ
O
A
N
_n
,Or 4
t7
m
c
C.
a
_.�
a
A_
a
_
N
v
r
Z
T
„
$
o
/ n
51 -Tenant
AC 1- 4
-1,800
NA
NA
NA
NA
N
AC 1--4 _
' 3,221
NA_
16l
30.0
483
483
NA-
N
NA
❑
ClImprovement
_
i
TOTAL
3,221
NA
NA
NA
NA
❑
E]
r ..
B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY., • . -
§ 140.4
1.
2.
3.
4.
5.
6
7
8.
Confirmed
Rated Capacity
_
Airflow (cfm)
- Fan
System ID
System Type
Qty
(kBtuh)
Economizer
Zone Name
°a,'
T
d
Heating
Cooling
Design
_
_ Min.
Min.
BHP
Cycles
ECM
_
.. _ _ . _
_
_ _
'^
Ratio
Motor .
1 -Tenant
_Uncontrolled
4 _
NA, _
:NA -
__._} _.NA
1 -Tenant Improvement
.1800,.
NA:. _
NA_
- NA_.
,._.NA �
❑
.11
-❑
Improvement-Trm
C. EXHAUST FAN SUMMARY
This Section Does Not Apply - - + - -i-
i
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 16 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
D. DHW EQUIPMENT SUMMARY — (Adapted from NRCC-PLB-01)
§ 110.3
Confirmed
- 1. -
-- 2.
3. -
4.
-5. -
-6.-
7.-
- B. -
-9.
•10.
11.
12.
-
Heater
Test Description
- Tank -
-
n
x;
n
x-
Tank
n
x
n
=
DHW Name
_ Element
_Tank Type
Qty
Tank Vol
_
Rated Input
Efficiency
Insulation
Pilot Energy
Standby Loss
Heat Pump
location or
N
°_
pp'
A-
b
Vf
o
T
C
-4
(gal)
(kBtu/h)
O
R -value
(Btu/h)'
Type
Ambient
4
v
_
Type
;
a
a
•'
(Int/Ext)
A
a
- '
Condition'
A
A
AO SMITH
Electricity
Storage -.
- .3
- 17'
15 -
EF: 0.950,
NA '
_
0.027
NA } �
NA
❑
❑
EUF-06
�
_
.0
r
A
v
n
,
E. MULTI -FAMILY CENTRAL'DHW SYSTEM DETAILS
This Section Does Not Apply_
F. SOLAR HOT WATER HEATING SUMMARY (Adapted from NRCC-STH-03)
This Section Does Not Apply__
G. MECHANICAL HVAC ACCEPTANCE TESTS & FORMS (Adapted from 2016-NRCC-MCH-01-E)
§ RA4
Declaration of.Required Acceptance Certificates (NRCA) -Acceptance Certificates that maybe submitted. (Retain copies and verify forms -are completed and signed to post in field for Field
Inspector to verify).
Test Description
n
x'
n
x
n
x;
n
x-
n
x
n
x
n
=
n
x
n
x
n
x
n
x
n
x
n
x
n,
x.
n
x
n
x
n
x
Confirmed
0
o
W
pp'
A-
b
Vf
o
T
C
-4
p
00
0
l0
O
it
��
4.
4
v
a
a
A
A
A
a
to
A
A
A
A�
a
D
A
A
N.
C
_
.0
r
A
v
n
Equipment
N
3
s
v
<
T
3
'm
v
D
'
Requiring
# of
o-
o
v
<
n ,<,
o
n o,
o
o
0
r, o
v
�„
o
m
Testing or
units
"' '°
C
O '
<
;
M
cu
o
o
x
. ii _
n v+
_ 3
Verification
D
o
n
<
w
(D
-a
„
a
2
o
3
o_
_
,,,
_
. _a
-
2o
vam
ResDHW1
El
SHW
AC1-4
4
-
-
_
�.
- _.
...
-
-
-
-
_-
... r _.L. _ .. - _ .- � , _ � . i .-.rw .�. -- ti .. +.nw-.w - - - _ • �� � ni. w r.... 4 - w i.sr.i. r .�+. . ... _-•_ w .. r.._.. .r - -- w r+_.- -.r -. -
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
t Name:
Tenant Improvement
NRCC-PRF-01-E
Page 17 of 19
t Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
iance Scope:
ExistingAlte ration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
H. EVAPORATIVE COOLER SUMMARY,
This Section Does Not Apply .
NRCC-PRF-LTI-DETALLS -SECTION START
L
A. INDOOR CONDITIONED LIGHTING CONTROL'CREDITS (Adapted from NRCC-LTI-02-E) - -
§ 140.6
Lighting Control Credits Schedule (includes all lighting controls installed in conditioned space for
Control Credit Calculation
Confirmed .
r, compliance credit per §140.6(a)2 and Table 140.6-A)
J If Acceptance
Test Required
q
Location in.
-
Occupancy Type (must meet
Type/Description of Lighting -
- "'
Watts of ' '
-Power
Control Credit :
_
_
Building
requirements of Table 140.6-A)
Control (i.e.; partial on occupancy
# of Units
Controlled `
Adjustment
Watts
sensor, manual dimming, etc.) _
_. -. - _
_ _ _ Lighting _
Factor
:
Pass
Fail
S-1-Tenanti
Medical and Clinical Care
- none specified =
_ 1
0.00
0
❑
.Improvement
S -1 -Tenant
Medical and Clinical Care
-none specified -
1
0.00
0
` ❑
'❑
Improvement
t•
:.
S -1 -Tenant
Medical and Clinical Care
none specified -
1
0.00
0
❑
❑
Improvement
B. INDOOR CONDITIONED LIGHTING MANDATORY LIGHTING CONTROLS (Adapted from NRCC-LTI-02-E) § 130.1
This Section Does Not Apply
§130.1(0) = Manual area controls; §130.0(6) = Multi Level; §130.1(c) =Auto Shut -Off; §130.1(d) =Mandatory Daylight; §130.1(e) =Demand Responsive
C. TAILORED METHOD CONDITIONED LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST,(Adapted from NRCC-LTI-04-E). § 140.6
General lighting power. (see Table D) . _ _ . _ _ _ _ _ _ _ - _ .0
General lighting power from special function areas (see Table E) - _ _ _ _ _ _ NA _
Additional "use it or lose it" (See Table G) 0
' Total watts -0
D. GENERAL LIGHTING POWER (Adapted fr6m'NRCC-LTI-04-E) "' § 140.6-D
This Section Does Not Apply -
f;
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 18 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
16:45, Tue, Jul 25, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E)
§ 140.6(c) 3H
Room Number
< .,
Primary Function Area
- - -
Illuminance Value
(LUX) _
Room Cavity Ratio
- (Table G) -
+ - -
Allowed LPD
-
Floor Area (ft')
Allowed Watts
' -
Confirmed
`Pass—
Fail '
NA
NA
NA
NA
NA
NA
NA
❑
❑
[!ore: ianorea mernoo jor .�peaa! runaion.vrem is nor currency impiemenrea
F. ROOM CAVITY RATIO (Adapted from NRCC-LTI-04-E)
Rectangular Spaces
Room Number
Task/Activity Description
_
Room Length (ft)
-
Room Width (ft)
Room Cavity Height (ft)
RCR
Confirmed
"
Pass
Fail
NA
NA
NA
NA
NA
NA
❑
❑
Non -Rectangular. Spaces F _� • ; .
This Section Does Not Apply
rvore: Au appncame spaces ore urea unaer me mon-necrangmar 3poces male
i i
G. ADDITIONAL "USE IT OR LOSE IT" (Adapted from NRCC-LTI-04-E) ,
2. ..
_ - _ 3.
4.
Allowed Watts.
Confirmed
Wall Display
Combined Floor Display and Task
_ Lighting . _
Combined Ornamental and Special
_. Effects Lighting;
Very Valuable Merchandise
0
/ 0
0
i 0
0
❑
❑
S. Wall Display
This Section Does Not Apply
6. Floor Display and Task Lighting - -
This Section Does Not Apply
7. Combined Ornamental and Special Effects lighting.
This -Section Does Not Apply
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
S. Very Valuable Merchandise .•I
This Section Does Not Apply
H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-LTO-01-E) '
§:130.41
Declaration of Required Acceptance Certificates (NRCA) —Acceptance Certificates that -must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for
Field Inspector to verify). - F
'
Indoor
Outdoor
Confirmed �•
Test Description
NRCA-LTI-02-A
NRCA-LTI-03-A
NRCA-LTI-04-A
NRCA-LTO-02-AV.
Equipment Requiring
+ -
# of units •
Occ Sensors-/ Auto Time
-Switch
Auto Daylight
Demand Responsive
Outdoor Controls
N ,
"•
Testing or Verification
' + Occupant Sensors
0
❑
❑
❑
❑
❑
❑, ,
Automatic Time Switch
0
❑
❑
❑
❑
❑
❑
Automatic Daylighting
0
r• ❑ _
❑
❑
❑
❑ '
❑l
Demand Responsive
0
❑
❑ .
❑
❑
❑
❑'
Outdoor Controls
0
❑ 1
❑
❑
❑
IT
❑
Lighting Controls, shown on plan's, -comply with the requirements of Title 24, California Energy Code.
to
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-07122017-4377 Report Generated at: 2017-07-25 16:45:27
ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV -MM
Project Name
Date
Desert Vein & Vascular Institute T/
7/25/2017
DESCRIPTION
Building Envelope Measures: -
§110.8(a):
Installed insulating material shall have been certified by the manufacturer to comply with the California Quality
Standards for insulating material, Title 20 Chapter 4, Article 3.
§110.8(c):
All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of
Sections 2602 and 707 of Title 24, Part 2.
§110.8(g):
Heated slab floors shall be insulated according to the requirements in Table 110.8-A.
§110.7(a):
All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed,
weatherstripped or otherwise sealed.
Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.2 of
§110.6(a):
window area, 0.3 cfm/ft.2 of door area for residential doors, 0.3 cfm/ft.2 of door area for nonresidential single doors
(swinging and sliding), and 1.0 cfm/ft.2 for nonresidential double doors (swinging).
§110.6(a):
Fenestration U -factor shall be rated in accordance with NFRC 100, or the applicable default U -factor. '
§110.6(a) :
Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the
applicable default SHGC.
§110.6(b):
Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be
weatherstripped (except for unframed glass doors and fire doors).
The opaque portions of the roof/ceiling that separates conditioned spaces from unconditioned spaces or ambient air
shall meet the applicable U -Factor requirements as follows:
§120.7(a):
Metal Building- The weighted average U -factor of the roof assembly shall not exceed 0.098.
Wood Framed and Others- The weighted average U -factor of the roof assembly shall not exceed 0.075.
The opaque portions of walls that separate conditioned spaces from unconditioned spaces or ambient air shall meet the
applicable U -factor as follows:
Metal Building- The weighted average U -factor of the wall assembly shall not exceed 0.113.
Metal Framed- The weighted average U -factor of the wall assembly shall not exceed 0.151.
Light Mass Walls- A 6 inch or greater Hollow Core Concrete Masonry Unit shall have a U -factor not to exceed 0.440.
§120.7(b):
Heavy Mass Walls- An 8 inch or greater Hollow Core Concrete Masonry Unit shall have a U -factor not to exceed
0.690.
Wood Framed and Others- The weighted average U -factor of the wall assembly shall not exceed 0.110.
Spandrel Panels and Opaque Curtain Wall- The weighted average U -factor of the spandrel panels and opaque
curtain wall assembly shall not exceed 0.280.
Demising Walls-. The opaque portions of framed demising walls shall meet the requirements of Item A or B below:
A. Wood framed walls shall be insulated to meet a U -factor not greater than 0.099. -
B. Metal Framed walls shall be insulated to meet a U -factor not greater than 0.151.
The opaque portions of floors and soffits that separate conditioned spaces from unconditioned spaces or ambient air
shall meet the applicable U -Factor requirements as follows:
§120.7(c):
Raised Mass Floors- Shall have a minimum of 3 inches of lightweight concrete over a metal deck or the weighted
average U -factor of the floor assembly shall not exceed 0.269.
Other Floors -The weighted average U -factor of the floor assembly shall not exceed 0.071.
'STATE OF CALIFORNIA
Electrical Power Distribution
CEC-NRCC-ELC-01-E (Revised 01/16)
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E
Electrical Power Distribution (Page 1 of 6)
Project Name: Desert Vein & Vascular Institute TI Dace Prepared: .7/25/2017 �.
General Information
Document Number
- - �-
_
Document Title / Descriptions
(include description information for Table or
Schedule if it contains compliance information)
Project Address:
79440 Corporate Center Way, Suite 119
Indicate which
subsection of
Section 130.5 is
related to the
document (e.g.
130.5(a) for
service electrical
metering)
Climate Zone:
15
Conditioned Floor Area:
3,221
Unconditioned Floor Area:
0
Building Type:• 0 Nonresidential
❑ Schools
❑ High -Rise Residential ❑
❑ Relocatable Public Schools
Hotel/Motel
Phase of Construction: - ❑ New Construction
❑ Addition ®
Alteration
In the table below identify all applicable construction documents that specify the requirements for the scope of responsibility
reported by this certificate. Use additional pages as needed to list all construction documents related to compliance of Section 130.5.
Document Number
- - �-
_
Document Title / Descriptions
(include description information for Table or
Schedule if it contains compliance information)
Document Sheet #
or Page #
Indicate which
subsection of
Section 130.5 is
related to the
document (e.g.
130.5(a) for
service electrical
metering)
E1, E2 & E3
Lighting, Power, Panel for the TI-
,
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
STATE OF CALIFORNIA
Electrical Power Distribution
EC-NRCC-ELC-ui-t (Revised D'v16) CALIFORNIA ENERGY COMMISSION iii'
CERTIFICATE OF COMPLIANCE NRCC-ELC-017E
Electrical Power Distribution (Page"2 of 6)
Project Name: - - Date Prepared: -
Desert Vein & Vascular Institute TI 7/25/2017
Document Number
'.
Document Title / Descriptions
(include description information for Table or
Schedule if it contains compliance information)
Document Sheet #
or Page #
Applicable '
subsection of`:^
Section 130.5 ;..
t
,
t
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance y sJanuary 2016
STATE OF' CALIFORNIA +
Electrical Power Distribution " =
CEC-NRCC-ELC-01-E (Revised 01/16) CALIFORNIA ENERGY COMMISSION ''iei'
CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E
Electrical Power Distribution (Page 3 of 6)
``°je`Name: Desert•Vein & Vascular Institute TI na=er.e�red: 7/25/2017
A. Service Electrical Metering
Check one of the three'boxes below if the electrical power distribution system is in compliance with Section 130.5(0).
❑ For newly installed electrical service in newly constructed buildings, Service Electrical Metering is required according to Section 130.5(a). Fill out
Column 1 thru 6 of table below. '
f�7 For new or replacement electrical service equipment in existing buildings, Service Electrical Metering is required according to Section 141.0(b)2Pi.
Fill out Column 1 thru 6 of tattle below.' - - I ' ' - l" 1'
❑ EXCEPTION to Electrical Service Metering: Service or feeder for which the utility company provides a metering system that indicates instantaneous
kW demand and kWh for a utility -defined period. Fill out Column 1, 2 and 6 of table below with the compliance information.
Fill out a separate line for each electrical service that is connected to the building. If additional table space is needed for electrical service information,
submit additional page with the information.'
Electrical
Electrical Service Schedule
Service
Metering Capabilities
Exception to
-
Field Inspector
`
(check all that are present)
130.5(0) -
Rating
01
02
03
04
05
06
07
08
O/
bo
e,
v E
3
n
;6 3-
v d
ba m o
'�°
y o
}v+ E
v
;. Check -that the.
vY
Y
uY
v
c c:c
w
a C
E y
A
r,
metering complies
Electrical Service
N
N
° a
3 a
—
Designation/Location/Description
kVA
—
D
200 Amp Panel
61.97
R
❑
R
❑
i
❑
1
❑
❑
❑
❑
❑
❑
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance _ January 2016
j
Z
O
co
O
U
>-
X
LL,
z
W
Q`
Z
0'
0
J
U
W
O
U
J
i W
u
Z`r
O
�
GJ
coo
a
�.
N
In
N.
9
d
a
v
O
7
.N
C
f0
7
v
U)
I
N
p
M r
d
aL+ —O.
S
O
W
N
'L
Z
O
H
Q
J
o
0
a
Y u
„,A
❑
L N
0
N
C1 ;
u
p
a3�L
z O w
O
3
oa'�
o
a wQ
a
U �%
V
w:
O
O
U-
E
w V
~
�
u
Z
hWZ
LLI Qi
W
U
0)
W
a`
CO L)
m E
U
I
N
p
M r
d
aL+ —O.
" E
oa
r
d
C
Y u
„,A
❑
C
_
w:
O
O
Y
m E
U
to
U
t
y
?
To
41
7 u
E w
r
a
d
d ens
s
c
fn
C
��
Ctw
CO
u
Z
�O L
C
d
~
O
E O
D
Gl
W
C
O
C
N
E
a, w
E
w
v
C CQ) m
W
C hCU
O
O u An
M
(v
C
Y
Cr
~ aui
p o
N
(U
m
E
C
1
p
V4ij d
p
L N
m
N
C
= n E
.••
w e
C
O
E
A
OD
...
3 u
E o
y .n
A
� E
E
Nv
0
o� E
20 o
°
c°
CL
c
°
c
O
a t; 0
E
E o
y
d
Y
E
o
.
° aui .L
U d
o
N a
N
a:+ E
�
T
C O •D
I
N
H E
O
An 0
u
u
- (n ..
- ..
OD
'E c0 m
m w
n
O
cy
3 _L
0
LU
m y%
a
a E
_
HCL
•'E
e
o
r
v
e
C
y0
LA
O
1
L
v E o
VI
v
o
C
J•+
00
E
u
fA
-0c
N
n>
ao a o
n
°1
°1
O
L
o cD
.
An "
E
u.
o
(v
1
V
o y
3
o3
0
r
co
MIv
3
COL
J
o
m
m C. u,._..
u
Aw
C
a
3
C
(8
o��v��
:.a
N
r
E
zs
�6
a
•a n L
V N w
N
p
N N O
°
e
e
o
o°
Z
CL
O
io
w An
n in
°
u p
E
a
a
CL
c a, o
a u o
m w
m
v°
w m
Q
m
n
m ;
Q
c
c
i2
0
N
ii
STATE OF CALIFORNIA
' Electrical Power Distribution
CEC-NRCC-ELC-01-E (Revised 01/16)
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE 1 NRCC-ELC-01-E
Electrical Power Distribution (Page 5 of 6)
Project Name: - Date Prepared:
Desert Vein & Vascular Institute TI 7/25/2017
C. Voltage Drop Enforcement Agency
Check all boxes below if the electrical power distribution system is in compliance with Section 130.5(c). �i i, Check that the system
complies
�l The electrical power distribution system meets the voltage drop requirement of Section 130.5(c). The maximum ,
combined voltage drop on feeder conductors and branch circuit conductors to the farthest connected load or ❑
outlet, do not exceed 5%.
$1 Voltage drop calculation documents showing compliance to Section 130.5(c) are submitted as part of the - ❑
compliance document submittal. `
D. Circuit Controls for 120 -Volt Receptacles and Controlled Receptacles , . •
Field Inspector
Check one or more boxes below for applicable requirements of Section 130.5(d) for the electrical power distribution
Cehck that the system
system.
; complies
91 The control is capable of automatically shutting OFF the controlled receptacles when the space is typically I
- •
unoccupied, either at the receptacle or circuit level. For the automatic time switch control, it incorporates an -
I
override control that allows the controlled receptacle to remain ON for no more than 2 hours when an override
_
is initiated and an automatic holiday "shut -OFF" feature that turns OFFall loads for at least 24 hours and then
1 .-
resumes the normally scheduled operation. Countdown timer switches are not be used to comply with the
,
automatic time switch control requirements. The controls meet the requirement of Section 130.5(d)1.
,
❑ There is at least one controlled receptacle within 6 ft from each uncontrolled receptacle. Where receptacles are
installed in modular furniture in open office area, at least one controlled receptacle is installed at each ,
❑. �,_
workstation. The receptacles meet the requirement of Section 130.5(d)2.
❑ There are installed split wired receptacles with at least one controlled and one uncontrolled receptacle. Where
receptacles are installed in modular furniture in open office area, at least one controlled receptacle is installed
❑
at each workstation. The receptacles meet the requirement of Section 130.5(d)2.
'
91 Permanent and durable marking for controlled receptacles or circuits to differentiate them from uncontrolled
receptacles or circuits is provided. The markings meet the requirement of Section 130.5(d)3.
❑
❑ For hotel and motel guest rooms, there are controlled receptacles for at least one-half of the 120 -volt
receptacles in each guest room. Electric circuits serving controlled receptacles in guestrooms are installed to
have captive key controls, occupancy sensing controls, or automatic controls so the power is switched off no
❑
longer than 30 minutes after the guest room has been vacated. The receptacles meet the requirement of
Section 130.5(d)4.
❑ Receptacles that are only for the following purposes are excepted from Section 130.5(d):
-Receptacles specifically for refrigerators and water dispensers in kitchen areas.
-Receptacles located a minimum of six ft above the floor that are specifically for clocks.
-Receptacles for network copiers, fax machines, A/V and data equipment other than personal computers in
copy rooms.
p
-Receptacles on circuits rated more than 20 amperes.
-Receptacles connected to an uninterruptible power supply (UPS) that are intended to be in continuous use, 24
hours per day/365 days per year, and are marked to differentiate them from other uncontrolled
receptacles or circuits.
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance 'January 2016
STATE OF CALIFORNIA +
Electrical Power Distribution . • , I.
CEC-NRCC-ELC-01-E (Revised.01/16) CALIFORNIA ENERGY COMMISSION 'qQW-
CERTIFICATE OF COMPLIANCE -NRCC-ELC-01-E
Electrical Power Distribution (Pap 6 of 6)
Project Name: Date Prepared: -
Desert Vein & Vascular Institute TI 7/25/2017
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Tim Scott
Documentation Author Signature:
Company: Scott Design and Title 24, Inc,
Signature Date: 7/25/2017~
Address: 74-818 Velie Way, Suite #8
CEA/ HERS Certification Identification (if applicable):
City/State/Zip: Palm Desert, CA 92260
phone:' (760) 200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design
identified on this Certificate of Compliance (responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system ,
design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations. , i - . , . , : • - , ,
4. The building design features or system design features identified on this Certificate -of Compliance are consistent with the information
provided on other applicable compliance documents; worksheets, calculations, plans and specifications submitted to the enforcement
agency for approval with this building permit application. i . I +. .
5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this
Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name: Lawrence C. Reeves
Responsible Designer Signature: • , ^
Company:
Lawrence C.Reeves, L.P.
Date Signed: -
Address: 49-850 Jefferson St., Suite 130
License:
City/state/zip: Indio, CA 92201
Phone: (818) 425-0830
'r �.. .. i
M1
s _ 1
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Desert Vein & Vascular Institute TI
Date
7/25/2017
System Name
AC 1 -4
Floor Area
3,221
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
4
COIL
CFM
Total Room Loads 6,286
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 483
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
;Latent CFM
Sensible
Output perSystem 54,000
113,368
12,153 2,098
31,823
Total Output Btuh 216,000
0
Output Btuhls ft 67.1
5,668
1,591
Cooling System
01
0
Output per System 53,000
17,606
6,574 483
22,517
Total Output Btuh 212,000
0
5,668
1 142,311
18,727
0
Total Output (Tons) 17.7
1,591
Total Output Btuhls ft 65.8
Total Output s ft/Ton 182.3
F 57,522
Air System
CFM per System
1,800
HVAC EQUIPMENT SELECTION
Airflow cfm
7,200
Existing York HVAC 158,790
31,444
134,908
Airflow cfm/s
2.24
t
Airflow cfm/Ton
407.5
Total Adjusted System Output 158,790
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
31,444 134,908
4ug 4 PM Jan 1 AM
Outside Air % 6_7%
Outside Air cfmis ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
483 cfm
70 OF
-d -&=
67 OF 84 OF 84 OF
ICE
Heating Coil Supply Fan 84 OF
7,200 cfm
ROOM
70 OF
4 U-1— A 4
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
111 178 OF
Outside Air Ar
483 cfm
77 / 64 OF
79 ! 65 OF 58 / 57 OF 58 157 OF
�-- ---1� - –�
Cooling Coil Supply Fan 59 / 57 OF
7,200 cfm
52.3% ROOM
76164 OF
EnergyPro 7.1 by EnergySoff
User Number. 6712 ID:
Page 29 of 30
ZONE / • , SUMMARY
Project
Vein & Vascular Institute T/
Date
712512017
System Name
1
FloorDesert
zoNE LoWwmMARY
ZONAL SYSTEM COOLING
NAME
Tenant ImprovementSYSTEM
. ..,
EnergyPro 7.1 by EnergySoft User Number: 6712
ID:
:Page 30 ,
12
Contractor Name: Ike
k:r ........ .........
'
Address:
PERMIT #.!
PLAN LOCATION: 3
Project Address: 6r o�c�e C
r
Project Description: Pool, Remodel, Add't, Elect, Plumb, Mech
APN #:
Su
State Lic: City Bus Lic:
State Lic: City Bus Lic:
�Q �d slreea's. -)v f'e-AecL` -
Applicant Name:
Address:
City, ST, Zip:
%wa ter° SG��S Z�� CG.ICS,
Telephone:
60_ '5b-7 —.$-?%%
Email:
Valuation of Project $ 2D Ola • Q 0
Contractor Name: Ike
New SFD Construction:
Address:
Conditioned Space SF
City, St, Zip
Garage SF.
Telephone:
Patio/Porch SF
Email:
Fire Sprinklers SF
State Lic: City Bus Lic:
Arch/Eng Name:
Construction Type: Occupancy:
Address:
Grading:
City, St, Zip
Construction Type: Occupancy:
Telephone:
Bedrooms:
Stories:
# Units:
Email:
State Lic: City Bus Lic:
Property Owner's Name:
New Commercial / Tenant Improvements:
Address:
Total Building SF
City, ST, Zip
Construction Type: Occupancy:
Telephone:RE C-Enign
Email:
DEC 08 2011
CITY :OF LA QUINTA
COMMUNITY DRELOPMENT
78495 CALLE TAMPICO
LA QUINTA, CA 92253
760-777-7000
a
a
OFFICE USE ONLY .
� . � '> • � .
#
Submittal
Re q'd
Rec'd
Plan Sets
Structural Calcs
Truss Calcs
-
Title 24 Calcs
Soils Report
Grading Plan (PM 10)
Landscape Plan
Subcontractor List
Grant Deed
HOA Approval
y
School Fees
Buniec Debris Plan
Planning approval
t
Public Works approval
Fire approval
City Business License
c
M
I
r
BUILDING ENERGY ANALYSIS. REPORT
Report Prepared by.
Jon d. Scott
Scott Design and Title 24,
74818 Velie Way Suite
Palm Desert, CA 9226
760-200-4780
RECEIVED
DEC 0 8 2017
CITY OF LA QUINTA
COMMUNITY DEVELOPMENT
Job Number:
Date:
c12/5j2Q 1`7
Revi-slohl A I
CITY OF LA QUINTA
c, BUILDING & SAFv�®PT.
APPR®
FOR CONSTRUCTION
> DATE �i7 BY
L 14 Wrr t -j4
Ar UL"wesl
I AtJV Pio �E 4001
D�
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2016 Building Energy Efficiency Standards.
This program developed by EnergySoft Software — www.energysoft.com.
PROJECT:
Desert Vein & Vascular Institute TI
79440 Corporate Center Way, Suite 119
La Quinta, CA 92253
Project Designer: "`f
"'• =` `� ��iuti
Lawrence C.Reeves, L.P.
49-850 Jefferson St., Suite 130
Indio, CA 92201
(818) 425-0830
Report Prepared by.
Jon d. Scott
Scott Design and Title 24,
74818 Velie Way Suite
Palm Desert, CA 9226
760-200-4780
RECEIVED
DEC 0 8 2017
CITY OF LA QUINTA
COMMUNITY DEVELOPMENT
Job Number:
Date:
c12/5j2Q 1`7
Revi-slohl A I
CITY OF LA QUINTA
c, BUILDING & SAFv�®PT.
APPR®
FOR CONSTRUCTION
> DATE �i7 BY
L 14 Wrr t -j4
Ar UL"wesl
I AtJV Pio �E 4001
D�
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2016 Building Energy Efficiency Standards.
This program developed by EnergySoft Software — www.energysoft.com.
I TABLE OF CONTENTS I
Cover Page 1
Table of Contents 2
Form PRF -01-E Certificate of Compliance 3
Form ENV -MM Envelope Mandatory Measures 22
Form ELC-01-E Electrical Power Distribution 23
HVAC System Heating and Cooling Loads Summary 29
Zone Load Summary 30
Tc Ow ` •_
r
j
EnergyPro 7.2 by EnergySofft Job Number: IU: User Number: 6712
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 1 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
A. PROJECT GENERAL INFORMATION
1.
Project Location (city)
La Quinta
S.
Standards Version
Compliance2016
2.
CA Zip Code
92253
9.
Compliance Software (version)
EnergyPro 7.2
3.
Climate Zone
15
30.
Weather File
PALM-SPRINGS-INTL_722868_CZ2010.epw
4.
Total Conditioned Floor Area in Scope
3,221 ft'
11.
Building Orientation (deg)
(S) 180 deg
S.
Total Unconditioned Floor Area
0 ft,
12.
Permitted Scope of Work
ExistingAlteration
6.
Total # of Stories (Habitable Above Grade)
1
13
Building Type(s)
Nonresidential
7.
Total # of dwelling units
0
14
Gas Type
NaturalGas
B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft 2 -yr)
§ 140.1
BUILDING COMPLIES
1. Energy Component
2. Standard Design (TDV)
3. Proposed Design (TDV)
4. Compliance Margin (TDV)
S. Percent Better than Standard
Space Heating
0.32
0.34
-0.02
-6.3%
Space Cooling
208.95
206.02
2.93
1.4%
Indoor Fans
160.65
160.22
0.43
0.3%
Heat Rejection
--
--
--
Pumps & Misc.
--
--
--
Domestic Hot Water
5.11
16.97
-11.86
-232.1%
Indoor Lighting
78.27
67.02
11.25
14.4%
COMPLIANCE TOTAL
453.30
450.57
2.73
0.6%
Receptacle
110.83
-110.83 110.83
0.0
0.0%
Process
--
--
--
--
Other ltg
_
Process Motors
-
TOTAL
564.13
561.40
2.7
0.5%
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 2 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
C. PRIORITY PLAN CHECK/ INSPECTION ITEMS (in order of highest to lowest TDV energy savings)
1st
Indoor Lighting: Check lighting
Compliance Margin By Energy
] Indoor Lighting'��-oo
j Space Cooling
Indoor Fans �
Heat Rejection .
Pumps & Misc.
Space Heating
f Domestic Hot Water
Component
- -
(from Table B column 4)
-
Energy Credit
2nd -;
Space Cooling: Check envelope and mechanical
3rd
Indoor Fans: Check envelope and mechanical
4th
Heat Rejection: Check envelope and mechanical
5th
Pumps & Misc.: Check mechanical
6th
Space Heating: Check envelope and mechanical
7th
Domestic Hot Water: Check mechanical
Penalty
D. EXCEPTIONAL CONDITIONS
This project uses the Simplified Geometry Performance Modeling Approach which is not capable of modeling daylighting controls and assumes the prescriptive Secondary Daylit Control
requirements are met. PRESCRIPTIVE COMPLIANCE documentation (form NRCC-LTI-02-E) for the requirements of section 140.6(d) Automatic Daylighting Controls in Secondary Daylit Zones is
required.
This project includes Domestic Hot Water in the analysis. Please verify that Domestic Hot Water is included in the design for the permitted scope of work.
E. HERS VERIFICATION
This Section Does Not Apply
F. ADDITIONAL REMARKS
None Provided
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Iroject Name:
Tenant Improvement
NRCC-PRF-01-E
Page 3 of 19
Iroject Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
:ompliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
Identify which building components use the performance or prescriptive path for compliance. "NA "= not in project
For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans.
Building Component
Compliance Path
Compliance Forms (required for submittal)
Location of Mandatory Notes on
Plans
Envelope
❑ Performance
NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-01-E)
® Prescriptive
NRCC-ENV-01 / 02 / 03 / 04 / 05 / 06-E
❑ NA
Mechanical
® Performance
NRCC-PRF-MCH-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-MCH-01 / 02 / 03 / 04 / 05 / 06 / 07-E
❑ NA
Domestic Hot Water
Performance
NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-PLB-01-E
❑ NA
Lighting (Indoor Conditioned)
..
® Performance
NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-LTI-01 / 02 / 03 / 04 / 05-E
❑ NA
Covered Process:
Commercial Kitchens
❑ Performance
52 (section of the NRCC-PRF-01-E)
ElPrescriptive
NRCC PRC O1/ 03-E _
® NA
Covered Process:
Computer Rooms
❑ Performance
S3 (section of the NRCC-PRF-01-E)
- Y
❑ Prescriptive
NRCC PRC Ol/ 04-E
® NA
- -
Covered Process: - - - -
Laboratory Exhaust
❑' Performance
S4 (section of the NRCC-PRF-OI-E)
- - - - -
❑ "Prescriptive
-
NRCC PRC Ol/ 09-E
® NA
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 4 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
The following building components are only eligible for prescriptive compliance. Indicate which are
The following building components may have mandatory requirements per Part 6. Indicate
relevant to the project.
which are relevant to the project.
Yes NA
Prescriptive Requirement
Compliance Forms
Yes NA
Mandatory Requirement
Compliance Forms
Lighting (Indoor
Commissioning: §120.8
❑ ®
Unconditioned) §140.6
NRCC-LTI-01 / 02 / 03 / 04 / 05-E
❑ ®
Simple Systems
NRCC-CXR-01 / 02 / 03 / 05-E
❑ ®
Complex Systems
NRCC-CXR-01 / 02 / 04 / 05-E
❑ ®
Lighting (Outdoor) §140.7
NRCC-LTO-01 / 02 / 03-E
® ❑
Electrical: §130.5
NRCC-ELC-01-E
❑ ®
Lighting (Sign) §140.8
NRCC-LTS-01-E
❑ ®
Solar Ready: §110.10
NRCC-SRA-01 / 02-E
Covered Process: §120.6
NRCC-PRC-01-E
❑ ®�
Parking Garage
NRCC-PRC-02-E
❑ ®
Solar Thermal Water
NRCC STH Ol E
❑ ®
Commercial Refrigeration
NRCC-PRC-05-E
Heatin g: §140.5
❑ ®
Warehouse Refrigeration
NRCC-PRC-06/07/08-E
❑ ®
Compressed Air
NRCC-PRC-10-E
❑ ®
Process Boilers - -
NRCC-PRC-11-E
I
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Iroject Name:
Tenant Improvement
NRCC-PRF-01-E
Page 5 of 19
'roject Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:-
14:56, Tue, Dec 05, 2017
:ompliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
- -
Building Component
Compliance Forms (required for submittal)
Pass
Fail
Envelope
❑ NRCI-ENV-01-E - For all buildings
❑
❑
❑ NRCA-ENV-02-F- NFRC label verification for fenestration
❑
❑
Mechanical
® NRCI-MCH-01-E - For all buildings with Mechanical Systems
❑
❑
❑ NRCA-MCH-02-A- Outdoor Air
❑
❑
❑ NRCA-MCH-03-A—Constant Volume Single Zone HVAC
❑
❑
❑ NRCA-MCH-04-H- Air Distribution Duct Leakage
❑
❑
❑ NRCA-MCH-05-A- Air Economizer Controls
❑
❑
❑ NRCA-MCH-06-A- Demand Control Ventilation
❑
❑
❑ NRCA-MCH-07-A — Supply Fan Variable Flow Controls
❑
❑
❑ NRCA-MCH-08-A- Valve Leakage Test
❑
❑
❑ NRCA-MCH-09-A — Supply Water Temp Reset Controls
❑
❑
❑ NRCA-MCH-10-A- Hydronic System Variable Flow Controls
❑
❑
❑ NRCA-MCH-11-A —Auto Demand Shed Controls
❑
❑
❑ NRCA7-MCH-12-A- Packaged Direct Expansion Units
❑
❑
❑ NRCA-MCH-13-A- Air Handling Units and Zone Terminal Units
❑
❑
❑ NRCA-MCH-14-A- Distributed Energy Storage
❑
❑
❑ NRCA-MCH-15-A—Thermal Energy Storage
❑
❑
❑ NRCA-MCH-16-A- Supply Air Temp Reset Controls
❑
❑
❑ NRCA-MCH-17-A — Condensate Water Temp Reset Controls
❑
❑
❑ NRCA-MCH-18-A- Energy Management Controls Systems
❑
❑
❑ NRCV-MCH-04-H- Duct Leakage Test
❑
❑
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 6 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
-ompliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment. "
Confirmed
Building Component
Compliance Forms (required for submittal)
Pass
Fail
Plumbing
® NRCI-PLB-01-E - For all buildings with Plumbing Systems
❑
❑
❑ NRCI-PLB-02-E - required on central systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-PLB-03-E - Single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
ElNRCI-PLB-21-E - HERS verified central systems in high-rise residential, hotel/motel application.
1:1
1:1
❑ NRCI-PLB-22-E - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCV-PLB-21-H- HERS verified central systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCV-PLB-22-H - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-STH-01-E - Any solar water heating
❑
❑
Indoor Lighting
® NRCI-LTI-01-E - For all buildings
❑
❑
❑ NRCI-LTI-02-E - Lighting control system, or for an Energy Management Control System (EMCS)
❑
❑
❑ NRCI-LTI-03-E - Line -voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to
only line -voltage track lighting - _ .
1:1
1:1energize
❑ NRCI-LTI-04-E - Two interlocked systems serving an auditorium, a convention center, a conference room, or a theater
❑
❑
❑ NRCI-LTI-05-E - Lighting Control Credit Power Adjustment Factor (PAF)
❑
❑
❑ NRCI-LTI-06-E - Additional wattage installed in a video conferencing studio
❑
❑
® NRCA-LTI-02-A - Occupancy sensors and automatic time switch controls.
❑
❑
® NRCA-LTI-03-A - Automatic daylighting controls
❑
_ ❑
❑ NRCA-LTI-04-A - Demand responsive lighting controls
❑
❑
Outdoor Lighting
❑ NRCI-LTO-01-E — Outdoor Lighting
❑
❑
❑ NRCI-LTO-02-E- EMCS Lighting Control System
❑
❑
❑ NRCA-LTO-02-A - Outdoor Lighting Control
❑
❑
Sign Lighting
❑ NRCI-LTS-01-E = Sign Lighting
❑
❑
Electrical
® NRCI-ELC-01=E - Electrical Power Distribution -
❑
❑
Photovoltaic
❑ NRCI-SPV-01-E Photovoltaic Systems - -
❑
❑
2.
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
)roject Name:
Tenant Improvement
NRCC-PRF-01-E
Page 7 of 19
)roject Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
'-ompliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component
Compliance Forms (required for submittal)
Pass
Fail
_
Covered Process
❑ NRCI-PRC-01-E Covered Processes
❑
❑
❑ NRCA-PRC-01-F- Compressed Air Systems
❑
❑
❑ NRCA-PRC-02-F- Kitchen Exhaust
❑
❑
❑ NRCA-PRC-03-F- Garage Exhaust
❑
❑
❑ NRCA-PRC-04-F- Refrigerated Warehouse- Evaporator Fan Motor Controls
❑
❑
❑ NRCA-PRC-05-F- Refrigerated Warehouse- Evaporative Condenser Controls
❑
❑
❑ NRCA-PRC-06-F- Refrigerated Warehouse- Air Cooled Condenser Controls
❑
❑
❑ NRCA-PRC-07F- Refrigerated Warehouse- Variable Speed Compressor
❑
❑
❑ NRCA-PRC-08-F- Electrical Resistance Underslab Heating System
❑
❑
I. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more information)
CA-
1.._
Total Conditioned Floor Area
3,221 ft2
S. Number of Floors Above Grade
1
Confirmed
2.
Total Unconditioned Floor Area
0 ft2
6. Number of Floors Below Grade
0
3.
Addition Conditioned Floor Area 0 ft2
4.
Addition Unconditioned Floor Area 0 ft2
7. Opaque Surfaces & Orientation S. Total Gross Surface Area 9. Total Fenestration Area 10. Window to Wall Ratio
North Wall
468 ft2
75 ft2
16.0%
❑
❑
East Wall
738 ft2
p ft2
00.0%
❑
❑
South Wall
468 ft2
105 ft2
22.4%
❑
❑
West Wall
738 ft2
165 ft2
22.4%
❑
❑
Total
2,412 ft2
345 ft2
14.3%
❑
❑
Roof
3,220 ft2
0 ft2
00.0%
❑
0 -
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 8 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
:ompliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Qu1nta-TCZ-17.cibd16x
J. FENESTRATION ASSEMBLY SUMMARY
§ 110.6
Confirmed
1.
2.
3.
4.
S.
6.
7.
8.
9.
Surface Name
Surface Type
Area (ft')
Framing
Type
Cavity
R -Value
Continuous
R -Value
U -Factor / F -Factor
/ C -Factor
VN
N
Product Type
O1
-
R-30 Roof 10
Roof
Fenestration Assembly Name /
Fenestration Type / Product TypeOverall
0
30
U -Factor: 0.030
E
Overall
Overall
R-19 Wall (W.19.2x6.16)12
ExteriorWall
CU
Tag or I.D.
/ Frame Type
Certification Methods
Assembly Method
Area ft'
U -factor
SHGC
VT
H
738
Wood
11
Vertical Fenestration
U -Factor: 0.110E
❑
❑
Slab On Grade29
UndergroundFloor
3220
NA
0
Existing Window
FixedWindow
Default Performance
Manufactured
345
0.71
0.73
0.77
E
❑
❑
MetalFraming
-Newly installed fenestration shall have a certified NERC Label Certificate or use the CEC defoult tables found in Table 110.6-A and Table 110.6-9. Center of Glass (COG) values are for the gloss -only, determined by the manufacturer, and are shown for ease
of verification. Site -built fenestration values are calculated per Nonresidential Appendix NA6 and are used in the analysis.
2 Status: N - New, A -Altered, E - Existing
Taking compliance credit for fenestration shading devices? (if "Yes", see NRCC-PRF-ENV-DETAILS for more information) No
K. OPAQUE SURFACE ASSEMBLY SUMMARY
§ 120.7/ § 140.3
Confirmed
1.
2.
3.
4.
S.
6.
7.
8.
Surface Name
Surface Type
Area (ft')
Framing
Type
Cavity
R -Value
Continuous
R -Value
U -Factor / F -Factor
/ C -Factor
VN
N
Product Type
O1
-
R-30 Roof 10
Roof
3220
NA
0
30
U -Factor: 0.030
E
❑
❑
R-19 Wall (W.19.2x6.16)12
ExteriorWall
1674
Wood
19
NA
U -Factor: 0.072
E
❑
❑
R-11 Wall Partition19
ExteriorWall
738
Wood
11
NA
U -Factor: 0.110E
❑
❑
Slab On Grade29
UndergroundFloor
3220
NA
0
NA
F -Factor: 0.730
E
❑
❑
`Status: N- New, A -Altered, E -Existing
L. ROOFING PRODUCT SUMMARY
§ 140.3
Confirmed
1.
2.
3.
4.
5.
6.
7.
Product Type
Product Density
Aged Solar
Thermal
SRI
Cool Roof
Roofing Product
(Ib/ft2)
Reflectance
Emittance
Credit
Description
R-30 Roof 10
5.323
0.08
0.75
NA
No
NA
❑
❑
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
)roject Name:
Tenant Improvement
NRCC-PRF-01-E
Page 9 of 19
)roject Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
:ompliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information)
§ 110.1 / § 110.2
Dry System Equipment 1(Fan & Economizer info included below in Table N)
Confirmed
1.
2.
3.
4.
S.
6.
7.
8.
9.
10.
11.
23.
24.
Air
System Type
Equip Type
Total Heating
Supp Heat
Supp Heat
Total Cooling
Efficiency
Acceptance
Testing
,��,
v
fu
T
°'
Equip Name
Equip Type
(Simple or
Qty
Output
Source (Y/N)Required?
Output
Output
(kBtu/h)
(Y/N)
*
N
'^
HP
BHP
.
Complex 3)
N_
(kBtu/h)
BHP
(kBtuh)
(kBtu/h)
4
N
5
EF: 0.95
Cooling
Heating
AC 1-4'
SZHP Split Phase)
Simple
4
S4
No
0
- 53
SEER 12.00
EER -10.00
HSPF-7.70
No
E
-❑
121
1 Dry System Equipment includes furnaces, air handling units, heat pumps, etc.
2 Simple Systems must complete NRCC-CXR-03-E commissioning design review form
3 Complex Systems must complete NRCC-CXR-04-E commissioning design review form
4 A summary of which acceptance tests are applicable is provided in NRCC-PRF-MCH-DETAILS
s Status: N - New, A - Altered, E- Existing
Wet System Equipment
Pumps
COfifiPmed
Confirmed
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
Air
Equip Name
Equip Type
Qty
Vol (gal)
Rated Capacity
Efficiency -
Standby Loss
Tank
Ext. R
Qty
GPM
HP
VSD •
(y/N)
N
T
--
(if present)
(kBtu/h)
CFM
Value
HP
BHP
(inch
Control
N_
HP
BHP
AO SMITH EUF-06*2
Storage
3
5.70
5
EF: 0.95
SBLF: NA
I NA
NA
WC)_
No
N
El
El
1 Wet System Equipment includes boilers, chillers, cooling towers, water heaters, etc. ti
2 Status: N - New, A - Altered, E - Existing
Discrepancy between modeled and designed equipment sizing? (if "Yes", see Table F. "Additional Remarks" for an explanation) No
N. Er.ONnMl7FR A FON SYSTEMS SUMMARY!
§ 14u.4
COfifiPmed
1.
2.
3.
4.
S.
Outside
Supply Fan . - •
- --- - Return Fan
Air
Economizer Type
V
H
=
TSP
TSP
Equip Name
(if present)
CFM
CFM
HP
BHP
(inch
Control
CFM
HP
BHP
(inch
Control
-
_
WC)_
- _
-
WC)
AC 1- 4
121
1800
1.000
1.000
1.76
ConstantVolume
NA
NA-
NA
NA
NA
NoEconomizer
❑ -
❑
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
)roject Name:
Tenant Improvement
NRCC-PRF-01-E
Page 10 of 19 _
)roject Address: . _
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
-ompliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
' Mechanical ventilation calculations and exhaust fans are included in the NRCC-PRF-MCH-DETAILS section a
0. EQUIPMENT CONTROLS
I § 120.2
Confirmed
1.
2.
3.
V
—
Equip Name
Equip Type
Controls
-
- —
No DCV Controls
Equip Name.
Equip Type
Dud Leakage and
Sealing Required per
140.4(1)
Dud Leakage will be
verified per NA1 and
NA2
No Economizer
Status'
Insulation
R -Value
AC 1- 4
SZHP
No Supply Air Temp. Control
❑
Q
8
Unconditioned
No Optimum Start
❑
❑
No Evaporative Cooler
No Heat Recovery
Res DHW1- SHW
Service Hot Water, Primary Only
Fixed Temperature Control, No DDC
- l
❑
❑
No Heat Recovery
P; SYSTEM DISTRIBUTION SUMMARY
§ 120.4/ § 140.4(1)
Dry System Distribution
Confirmed
1.
2.
3.
4.
S.
6.
Equip Name.
Equip Type
Dud Leakage and
Sealing Required per
140.4(1)
Dud Leakage will be
verified per NA1 and
NA2
Duds
Status'
Insulation
R -Value
Location
AC 1- 4
SZHP
No
No
8
Unconditioned
E
❑
❑
tatus: N - New, E— Existing
loes the Project Include Zonal Systems? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) No
toes the Project Include a Solar Hot Water System? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) - No
Aultifamily or Hotel/ Motel Occupancy? (if "Yes", see NRCC-PRF-MCH-DETAILS for DHW system information) No
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 11 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein Tf-La Quinta-TCZ-17.cibdl6x
Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info)3
§ 140.6
Luminaire Schedule (includes all permanent installed lighting in
conditioned space, and portable lighting over 0.3 w/ftZ in
offices)
Confirmed
Confirmed
2.- --
- 3.
4.-
How Wattage is Determined
Total Number
Luminaires
Installed Watts
Pass
Fail
CEC Default
from NAB
According to
§130.0(c)
A
A-13.2 W Can
13
1
Occupancy Type
Conditioned Floor Area Z
Installed Lighting Power
lighting Control Credits
Additional (Custom) Allowance
9
T
(3) 4 ft Fluorescent T8
(ftZ)
(Watts)
(Watts)
6
474
❑
❑
E
E -Cove -3 W/F
3
Area Category Footnotes
Tailored Method (Watts)
❑
❑
❑
❑
H
6" LED Task Lighting
(Watts)
Yes
No
20
Medical and Clinical Care
3,221
3,309
0
0
0
❑
❑
Building Totals:
3,221
3,309
0
0
0
` See Table 140.6•C
2 See NRCCATI-01-E for unconditioned spares
3Lighting information for existing spaces modeled is not included in the table
.t
R. INDOOR CONDITIONED LIGHTING SCHEDULE (Adapted from NRCC-LTI-01-E),
§ 130.0
Luminaire Schedule (includes all permanent installed lighting in
conditioned space, and portable lighting over 0.3 w/ftZ in
offices)
Installed Watts (Conditioned) -
Confirmed
Name or Item Ta
Tag
Complete Luminaire Description (i.e.,
3 -lam fluorescent troffer, F32T8,
P
one dimmable electronic ballast)
Watts per luminaire
P
How Wattage is Determined
Total Number
Luminaires
Installed Watts
Pass
Fail
CEC Default
from NAB
According to
§130.0(c)
A
A-13.2 W Can
13
Yes
No
82
1,082
❑
❑
C
(3) 4 ft Fluorescent T8
79
Yes
- No
6
474
❑
❑
E
E -Cove -3 W/F
3
Yes
No
151
453
❑
❑
H
6" LED Task Lighting
65
Yes
No
20
1,300
❑
❑
llf lighting power densities were used in the compliance model Building Departments will need to check prescriptive forms for Luminaire Schedule details.
S1. COVEREb PROCESS SUMMARY - ENCLOSED PARKING GARAGES § 140.9
This Section Does Not Apply
S2. COVERED PROCESS SUMMARY - COMMERCIAL KITCHENS § 140.9
This Section Does Not Apply _
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 12 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
S3. COVERED PROCESS SUMMARY - COMPUTER ROOMS § 140.9
This Section Does Not Apply
S4. COVERED PROCESS SUMMARY - LABORATORY EXHAUSTS § 140.9
This Section Does Not Apply
T. UNMET LOAD HOURS
This Section Does Not Apply
U. ENERGY USE SUMMARY
Energy Component
Standard Design Site
(MWh)
Proposed Design Site
(MWh)
Margin
(MWh)
Standard Design Site
(MBtu)
Proposed Design Site
(MBtu)
Margin
(MBtu)
Space Heating
0.1
0.1
0.0
Space Cooling
23.0
22.7
0.3
--
Indoor Fans
24.1
24.0
0.1
-
Heat Rejection
--
--
--
Pumps & Misc.
--
-
--
Domestic Hot Water
--
2.4
--
11.4
Indoor Lighting
10.8
9.3
1.5
--
--
COMPLIANCE TOTAL
58.0
58.5
-0.5
11.4
0.0
--
Receptacle
14.7
14.7
0.0
10.0
10.0
0.0
Process
--
--
--
--
--
--
Other Ltg
--
Process Motors
--
--
--
--
--
TOTAL
72.7
73.2
-0.5
21.4
10.0
11.4
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160
Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 13 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
§ 10-103
I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:-lon d. Scott-
-
Company: Scott Design and Title 24, Inc, `'" r A''
Signature: • „•r _t
'C ,• , • _"�ri1 S'
Address: 74818 Velie Way Suite 8
Signature Date:
City/State/Zip: Palm Desert CA 92260
CEA Identification (If applicable): f ,
Phone: 760-200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1
I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am
licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
2
_
1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3 to sign this document as the person responsible for its
preparation; and that I am a licensed contractor, performing this work. _
3
I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to
Business and Professions Code Sections 5537, 5538 and 6737.1.
Responsible Envelope Designer Name: Lawrence C.Reeves
-Signature:
Company: Lawrence C.Reeves, L.P.
_
NOT IN SCOPE# -
Address: 49-850 Jefferson St., Suite 130
Date Signed: i
City/State/Zip: Indio CA 92201
Declaration Statement Type:
Phone: (818) 425-0830
Title: - License #: j
Responsible Lighting Designer Name: Lawrence C.Reeves
Company: Lawrence C.Reeves, L.P.
Signature:
Address: 49-850 Jefferson St., Suite 130 -
Date Signed: '
City/State/Zip: Indio CA 92201
Declaration Statement Type: '
Phone: (818) 425-0830
Title: License #: '
Responsible Mechanical Designer Name: Tim Scott
Company: Scott Design and Title 24, Inc.
Signature:
C- p
Address: 77085 Michigan Drive • - - j _ _ __ _, __ _. _ _ _ - . - . -
Date Signed:
City/State/Zip: Palm Desert CA 92211 - r-
Declaration Statement Type:-------- - - - - - - -- -- --- --
Phone: (760) 200-4780 - - - - - - --- - - - -
- Title: - r - - - License #: - -
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-03-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 14 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name: -
Desert Vein TI -La Quinta-TCZ-17.cibdl6x -
NRCC-PRF-ENV-DETAILS -SECTION START
A. OPAQUE SURFACE ASSEMBLY DETAILS
Confirmed
1.
2.
3.
4.
v
N
N
T
d
—
Surface Name
Surface Type
Description of Assembly Layers
Notes
_ Door Type
Certification Method
Plywood - 5/8 in.
t
Area
Overall "
U -factor
Status'
R-30 Roof10
Roof
Glass fiber batt - 10 in. R30 (CEC Default)
MetalUninsulated5ingleLayerpoor
❑
❑
20.
0.079
Air - Cavity - Wall Roof Ceiling - 4 in. or more
❑
❑
HB Part. Brd - 3/4 in.
Stucco - 7/8 in.
R-19 Wall (W.19.2x6.16)12
ExteriorWall
Vapor permeable felt - 1/8 in.
❑
❑
Wood framed wall, 16in. OC, 5.5in., R-19
Gypsum Board - 1/2 in.
Stucco - 7/8 in.
R-11 Wall Partition19
ExteriorWall
Vapor permeable felt - 1/8 in.Wood
❑
❑
framed wall, 16in. OC, 3.5in., R-11
Gypsum Board -1/2 in.
Slab Type = UnheatedSlabOnGrade
Slab On Grade29
UndergroundFloor
Insulation Orientation = None
❑
❑
Insulation R -Value = RO
B. OVERHANG DETAILS (Adapted from NRCC-ENV-02-E)
This Section Does Not Apply
C. OPAQUE DOOR SUMMARY
Confirmed
1.
2.
3.
4.
S.
6.
7.
Opaque Door Assembly Name
/ Tag or I.D.
_ Door Type
Certification Method
Operation
t
Area
Overall "
U -factor
Status'
Pass
Fail
-
Insulated Metal Door17
MetalUninsulated5ingleLayerpoor
DefaultPerformance
Swinging
20.
0.079
E
❑
❑
' Status: N -New, A—Altered, E—Existing
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance
Report Version: NRCC-PRF-01-E-11092017-5160
Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 15 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:--'
k• ExistingAlteration" - + " " "", I
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x ' --
NRCC-PRF-MCH-DETAILS -SECTION START
A. MECHANICAL VENTILATION AND REHEAT (Adapted from 2016-NRCC-MCH-03-E) i = i
Confirmed
1. DESIGN AIR FLOWS +
2. VENTILATION
(§ 1204)
4.
5.
6.
7.
S
p
m
+
'
_
0
Fan
m
3
m
A
v
m
_I
�"
(kBtuh)
10
,M
G1
Z
Qty
Economizer
v
N
z
+ 3
Z
o
v+
Z
C
+
+ Z
Z
V.
D Z
03
-n
0�
n
n
m
Z
O
Z
Z
Tm
<
m
G1
Z
T
m
Cycles
�• m
A
F
-
- A
- 00
' ,3,.
-NA-
.�.
•OC
3
�C
3
O
_-�.
0 .nM
NA
Z
$ Z
-1
m-
D
_v
r
CONDITIONED
+
T
0 D
T
"
1
<
+ m
3
3
v
D
r Z
3, alu
ZONE NAME
'Z
3
n<
r
1
O
m
D
N M
0
c A
"n
3 D
o
Z
70
3Z
2<
VGZ1
2�
56
A
'^
:EC
t
?�
r
D
D
i7
D
Z
v
H
O
n
�'
T
o
m
Z
n
$
n
1 -Tenant
AC 1- 4
1,800
NA
NA
NA
NA '
N
AC 1- 4
3,221
NA
16.11
30.00
483
483
NA
N
NA
Cl
1:1Improvement
-
TOTAL
3,221
NA
NA
I NA
NA
❑
❑
B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY .
§ 140.4
1.
2.
3.
4.
5.
6.
7.
8.
Confirmed
Rated Capacity
_
Airflow (cfm)
Fan
(kBtuh)
System ID
Sfu
ystem Type
Qty
Economizer
_Y Zone Name �.
N
d
.._ .
..
_
-
Min.
ECM
-
_ -
Heating
Cooling
_ _ _ _
Design
Min.
Ratio
BHP
Cycles
Motor
F
1 -Tenant
Uncontrolled
4 _
-NA-
NA . -
NA - -
-1-Tenant Improvement
1800
NA-.
- NA
NA
NA
El-
❑•
ElImprovement-Tim
t
,
+
C. EXHAUST FAN SUMMARY
This Section Does Not Apply - -- -- - - - - - - - - - -
ad Vit. ,. h° b. I[. I �1 ,• _ � � 1
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 16 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
D. DHW EQUIPMENT SUMMARY — (Adapted from NRCC-PLB-01)
§ 110.3
Confirmed
1.
2.
3.
4.
S.
6.
7.
8.
9.
10.
11.
HeaterTank
Vol
Rated Input
Tank
Insulation
Standby Loss
Heat Pump
Tank Location
x
x
DHW Name
Element Type
yp
Tank Type
Qty
(gal)
(k8tu/h)
Efficiency
R -value
Fraction
Type
or Ambient
x
—
0
N
0
W
0
W
0
O�
0
V
(Int/Ext)
o
t0
4
O
Condition
�
N
�+
W
AO SMITH
EUF-06*2
Electricity
Storage
3
5.70 -
5
EF: 0.95
NA
SBLF: NA
NA
NA
❑
❑
E. MULTI -FAMILY CENTRAL DHW SYSTEM DETAILS
This Section Does Not Apply
F. SOLAR HOT WATER HEATING SUMMARY (Adapted from NRCC-STH-01)
This Section Does Not Apply . -
G. MECHANICAL HVAC ACCEPTANCE TESTS & FORMS (Adopted from 2016-NRCC-MCH-01-E)
§ RA4
Declaration of Required Acceptance Certificates (NBCA) — Acceptance Certificates that may be submitted. (Retain copies and verify forms are completed and signed to post in field for Field
Inspector to verify).
Test Description
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Confirmed
0
N
0
W
0
W
0
O�
0
V
o
t0
4
O
►+
N
�
N
�+
W
�.
�.
W
�.
01
► •
V
�
00
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
ao
D
n
3
c
<
c
x
o
C
0
T
0
D
—
�+
'�
v
l'1
p°
Equipment
0
°
°
c
o
°�
m
m
D
M a
Requiring
# of
n
°o
o
3
0
<
fo
o
o m
N 0
0
x rn
�^
�v
"� '
n
o
�,
Testing or
units
m
c�
<
a
f D
^ ':
`„° r�o
^ O1
0)i
o 'a
0
x
M o
0°
n L,
M
m
o o
°'
d
_
Verification
D
—
C
°v
o
°
oo
o f
T
D
°
3
o
Ln
.^.
rho
N
or
2
F
a
Q°
CFQ
fD
Res DHW1-
SHW
AC1-4
4
❑
❑
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 17 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
H. EVAPORATIVE COOLER SUMMARY
This Section Does Not Apply
NRCC-PRF-LTI-DETAILS -SECTION START
A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E)
§ 140.6
Lighting Control Credits Schedule (includes all lighting controls installed in conditioned space for
Control Credit Calculation
General lighting power from special function areas (see Table E)
Confirmed
compliance credit per §140.6(a)2 and Table 140.6-A)
0
J If Acceptance
Test Required
4
0
Location in
Occupancy Type (must meet
Type/Description of Lighting
Watts of
Power
Control Credit
_
Building
requirements of Table 140.6-A)
Control (i.e., partial on occupancy
# of Units
Controlled
Adjustment
Watts
sensor, manual dimming, etc.)
Lighting
Factor
Pass
Fail
S -1 -Tenant
Medical and Clinical Care
none specified -
1
0.00
0
El
❑
Improvement
S -1 -Tenant
Medical and Clinical Care
none specified
1
0.00
0
❑
❑
Improvement
S -1 -Tenant
Medical and Clinical Care
none specified
1
0.00
0
❑
❑
Improvement
S -1 -Tenant
-
Medical and Clinical Care
-none specified -
1
0.00
0
❑
El
Improvement
B. INDOOR CONDITIONED LIGHTING MANDATORY LIGHTING CONTROLS (Adapted from NRCC-LTI-02-E) § 130.1
This Section Does Not Apply
§130.1(x) =manual area controls; §130.0(6) = Multi Level; §130.1(c) =Auto Shut -Off; §130.1(d) =Mandatory Daylight; §130.1(e) = Demand Responsive
C. TAILORED METHOD CONDITIONED LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-LTI-04-E)
§ 140.6
General lighting power (see Table D)
0
General lighting power from special function areas (see Table E)
NA
Additional "use it or lose it" (See Table G)
0
Total watts
0
D. GENERAL LIGHTING POWER (Adapted from NRCC-LTI-04-E) _ _ § 140.6-D.'
This Section Does Not Apply
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 18 of 19
project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
:ompliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E)
§ 140.6(c) 3H
Room Number
Primary Function Area
Illuminance Value
(LUX)
Room Cavity Ratio
(Table G)
_ Allowed LPD
Floor Area (ft'
_ All_owed Watts
`
Confirmed
Pass
-Fail -
NA
NA
NA
NA
NA
NA
NA
❑
❑
pore: ianorea memo? Jor 3pectaf runcoon Areas is nor currenoy impiemenrea
F. ROOM CAVITY RATIO (Adapted from NRCC-LTI-04-E)
Rectangular Spaces
Room Number
Task/Activity Description _
Room Length (ft)
Room Width (ft)
Room Cavity Height (ft)
RCR
Confirmed
Pass
Fail
NA
NA
NA
NA
NA
NA
❑
❑
Non -Rectangular Spaces
This Section Does Not Apply
pore: An appcoore spaces are nsrea unaer me rvon-necrongmar Spaces mole
G. ADDITIONAL "USE IT OR LOSE IT" (Adapted from NRCC-LTI-04-E)
1.
2.
3.
4.
Allowed Watts
Confirmed
Wall Display
Combined Floor Display and Task
Lighting
Combined Ornamental and Special
Effects Lighting
Very Valuable Merchandise
W
1
_
—
0
0
0
0
0
❑
❑
i. Wall Display
chis Section Does Not Apply
i. Floor Display and Task Lighting
chis Section Does Not Apply
7. Combined Ornamental and Special Effects Lighting _
chis Section Does Not Apply -
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
Project Name:
Tenant Improvement
NRCC-PRF-01-E
Page 19 of 19
Project Address:
79440 Corporate Center Way, Suite 119 La Quinta 92253 -
Calculation Date/Time:
14:56, Tue, Dec 05, 2017
Compliance Scope:
ExistingAlteration
Input File Name:
Desert Vein TI -La Quinta-TCZ-17.cibdl6x
S. Very Valuable Merchandise -
This Section Does Not Apply ?
H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-LTO-01-E)
§ 130.4
Declaration of Required Acceptance Certificates (NRCA) —Acceptance Certificates that must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for
' Field Inspector to verify). - a
Test Description
Indoor
Outdoor
Confirmed
NRCA-LTI-02-A
NRCA-LTI-03-A
NRCA-LTI-04-A
NRCA-LTO-02-A
"n
Equipment Requiring
Testing or Verification
# of units
Occ Sensors / Auto Time
Switch
Auto Daylight
Demand Responsive
Outdoor Controls
N
Occupant Sensors
0
®
❑
❑
❑
❑
❑
Automatic Time Switch
0
®
❑
❑
❑
❑
❑,
Automatic Daylighting
0
❑
®
❑
❑
❑
❑
Demand Responsive
0
❑
❑
❑
❑
❑
❑
' Outdoor Controls
0
❑
❑
❑
❑
❑
❑
J
1
i
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11092017-5160 Report Generated at: 2017-12-05 14:57:01
s
t
{
ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV -MM
Project Name
Date
Desert Vein & Vascular Institute T/
12/5/2017
DESCRIPTION
Building Envelope Measures:
§110.8(a):
Installed insulating material shall have been certified by the manufacturer to comply with the California Quality
Standards for insulating material, Title 20 Chapter 4, Article 3.
§110.8(c):
All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of
Sections 2602 and 707 of Title 24, Part 2.
§110.8(g):
Heated slab floors shall be insulated according to the requirements in Table 110.8-A.
§110.7(a):
All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed,
weatherstripped or otherwise sealed.
Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.2 of
§110.6(a):
window area, 0.3 cfm/ft.2 of door area for residential doors, 0.3 cfm/ft.2 of door area for nonresidential single doors
(swinging and sliding), and 1.0 cfm/ft.2 for nonresidential double doors (swinging).
§110.6(a):
Fenestration U -factor shall be rated in accordance with NFRC 100, or the applicable default U -factor.
§110.6(a) :
Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the
applicable default SHGC.
§110.6(b):
Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be
weatherstripped (except for unframed glass doors and fire doors).
The opaque portions of the roof/ceiling that separates conditioned spaces from unconditioned spaces or ambient air
shall meet the applicable U -Factor requirements as follows:
§120.7(a):
Metal Building- The weighted average U -factor of the roof assembly shall not exceed 0.098.
Wood Framed and Others- The weighted average U -factor of the roof assembly shall not exceed 0.075.
The opaque portions of walls that separate conditioned spaces from unconditioned spaces or ambient air shall meet the
applicable U -factor as follows:
Metal Building- The weighted average U -factor of the wall assembly shall not exceed 0.113.
Metal Framed- The weighted average U -factor of the wall assembly shall not exceed 0.151.
Light Mass Walls- A 6 inch or greater Hollow Core Concrete Masonry Unit shall have a U -factor not to exceed 0.440.
§120.7(b):
Heavy Mass Walls- An 8 inch or greater Hollow Core Concrete Masonry Unit shall have a U -factor not to exceed
0.690.
Wood Framed and Others- The weighted average U -factor of the wall assembly shall not exceed 0.110.
Spandrel Panels and Opaque Curtain Wall- The weighted average U -factor of the spandrel panels and opaque
curtain wall assembly shall not exceed 0.280.
Demising Walls-. The opaque portions of framed demising walls shall meet the requirements of Item A or B below:
A. Wood framed walls shall be insulated to meet a U -factor not greater than 0.099.
B. Metal Framed walls shall be insulated to meet a U -factor not greater than 0.151.
The opaque portions of floors and soffits that separate conditioned spaces from unconditioned spaces or ambient air
shall meet the applicable U -Factor requirements as follows:
§120.7(c):
]Raised Mass Floors- Shall have a minimum of 3 inches of lightweight concrete over a metal deck or the weighted
average U -factor of the floor assembly shall not exceed 0.269.
Other Floors -The weighted average U -factor of the floor assembly shall not exceed 0.071.
STATE OF CALIFORNIA
Electrical Power Distribution
CEC-NRCC-ELC-01-E (Revised 01/16) GALIFURNIA ENERGY GUMMISSIUN `itrrr
CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E
Electrical Power Distribution (Page 1 of 6)
Project Name: Date Prepared:
DesertVein 8 Vascular Institute TI 12/5/2017 -
General Information -
Document Number
t
Document Title / Descriptions
(include description information for Table or
Schedule if it contains compliance information)
Project Address:
. .% _
79440 Corporate Center Way, Suite 119
Indicate which
subsection of
Section 130.5 is
related,to the
document (e.g.
130.5(a)for
service electrical
metering)
Climate Zone:
1
15
Conditioned Floor Area:
3,221
Unconditioned Floor Area:
0
Building Type: 0 Nonresidential
❑ Schools
❑ High -Rise Residential ❑
❑ Relocatable Public Schools
Hotel/Motel
Phase of Construction: ❑ New Construction
❑ Addition ®
Alteration
In the table below identify all applicable construction documents that specify the requirements for the scope of responsibility .
reported by this certificate. Use additional pages as needed to list all construction documents related to compliance of Section 130.5.
Document Number
t
Document Title / Descriptions
(include description information for Table or
Schedule if it contains compliance information)
Document Sheet #
or Page #
Indicate which
subsection of
Section 130.5 is
related,to the
document (e.g.
130.5(a)for
service electrical
metering)
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
STATE OF CALIFORNIA
Electrical Power Distribution
GEC-NRCG-ELG-01-E (Revised 01/16) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E
Electrical Power Distribution (Page 2 of 6)
Project Name: Date Prepared:
Desert Vein & Vascular Institute TI 12/5/2017
Document Title / Descriptions Applicable
Document Sheet #
Document Number (include description information for Table or subsection of,"
or Page #
Schedule if it contains compliance information) Section 130.5
r
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
n F D
z n m
0 ' O
n. 0
M C9
cri 41 F
o m
0
A D
<. M
m
M
ov
I; Cr
O
7
i
•
p
In C
Pr x
TT
=
n
a
O
D p
3
m
pe>>
M
M
m
a
(D --i.
i
i
g m
�i
j
(D
- p O
Cu
O °
I.a
�. ?
M
M
°+
2
y o
a?
e m
s;
m
iD
m
7 n i
�c1�
Qr '
O f
a o
> T
3 a
7 N
:3
.�
1
F
o
m
G CO`
d o
'r
H N
�
1
I
a w
o
�,
a p
3
.,
ro o
d
1
Dpi
,.
to
I•+
M
O
b rp
a
C j
O
O
n k
,
7 N
fD
M O
t` ?
O!n
..
M
ti.'
�0
H:•
M
n
S
�'
+
�•
2
N
.
Cr
m
d m
A
Z
r
'�
Z
C^
= `D
o
a-
o
m°
Z F
7
:
ro
do
o
' o
CL
`0
`D s
M
0
0
�
M M
0 2
m
�D
d
o ^
a in
n
- a'
�_
0
3
S
CD
M
v
C
EV
.
I
f
v+ ^'
v
n rD
` m
o
D
opo A n
m
°e n
X
n n
_
!
n.Cr
r
°
o
c °
°
QQ
c
;
Instantaneous
❑
❑
(at the time)
LOU
s
T
�,
°,°Q
kW
0 g
M- M,
a
a
s
^' T
m
a•
o'o
N N
Z m
-
Historical peak
o
❑
❑(kW)
p
m
+
c
m
o
Ip
ti
<
n'
n n
-�
Tracking kWh
n F D
z n m
0 ' O
n. 0
M C9
cri 41 F
o m
0
A D
<. M
m
M
ov
I; Cr
O
7
i
•
p
In C
Pr x
TT
=
n
(D
OR
O
D p
3
m
pe>>
M
�?
m
a
(D --i.
i
3
g m
�i
j
(D
- p O
Cu
O °
I.a
�. ?
M
°+
2
y o
a?
e m
s;
m
iD
m
7 n i
�c1�
Qr '
O f
a o
> T
3 a
7 N
n, s
.�
1
o
m
G CO`
d o
'r
H N
01
�°
1
d MA
a w
o
�,
a p
3
.,
ro o
d
,.
to
I•+
M
O
b rp
S ri
D!
C j
O
O
n k
3
7 N
fD
M O
t` ?
O!n
..
M
ti.'
�0
H:•
M
n
S
�'
+
�•
2
N
.
Cr
m
d m
A
M
c
'�
Z
C^
= `D
o
a-
°
m°
Z F
7
�;
do
o
' o
a `.D
`0
`D s
0
0
�
M M
0 2
m
�D
o ^
a in
n
- a'
�_
3
S
CD
M
C
v+ ^'
v
n rD
` m
o
D
opo A n
m
°e n
X
n n
_
n.Cr
°
o
c °
°
QQ
c
;
Instantaneous
❑
❑
(at the time)
LOU
s
T
�,
°,°Q
kW
0 g
M- M,
a
a
s
^' T
m
a•
o'o
N N
Z m
-
Historical peak
o
❑
❑(kW)
p
m
+
c
m
d aQ
Ip
ti
<
n'
n n
-�
Tracking kWh
..
M
o
for a user-
o
oM,
°o,
a
p 3
a s
❑
❑
definable
`f'Cr
o
o d
3
period
Nii
• p
'D O
M n
p
o
m
kWh per rate
❑
❑
period
m
:; v
a d
M
m
m
O
ry d
3
QpQ
;;- n
^'
°
_m
M
L.
a m
_ �.
CL wo
-
Utility metering
c
o fDo�
a
n
a'
o
❑
system
M K
fl
c
m
..
{
0 3
0
Q
°
+
..
04
? Q
0
°
o
3
•. r
fD *
2r.
.y'
CA
M
°
w
S
. (D
M
n'
ry M
°
O
a
mCD
°
in
o
❑
g fu
3
fD
3
:3.
c
_
=r
C
p
Q
4
..
`vDi
..
p
- -0
C
_
n F D
z n m
0 ' O
n. 0
M C9
cri 41 F
o m
0
A D
<. M
m
M
ov
I; Cr
O
7
i
STATE OF CALIFORNIA
Electrical Power Distribution
CEC-NRCC-ELC-01-E (Revised 01/16)
t
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E
Electrical Power Distribution (Page 4 of 6)
Project Name: - Date Prepared:
Desert Vein & Vascular Institute TI 12/5/2017
B. Separation of Electrical Circuits for Electrical Energy Monitoring
Check all boxes below if the electrical power distribution system is in compliance with Section 130.5(b).
CK The electrical power distribution system meets the separation of electrical circuits for electrical energy monitoring requirement of Section
130.5(b). The electrical power distribution systems is designed so that measurement devices can monitor the electrical energy usage of load
types according to TABLE 130.5-B.
I$ Describe the electrical power distribution system installed and the compliance method chosen in meeting the requirement of Section
130.5(b). Use the space below to include the information. Examples of compliance methods are detailed in Nonresidential Compliance r
Manual Chapter 8.
rl
Fill out Column 1 thru 3 with the compliance information.
General information
Electrical Power Distribution System information and Method of
Electrical Service
Enforcement
compliance
Rating
Agency
01
02
03
04
Electrical Service
Designation/Location/Descrip
Describe the electrical power distribution system installed and the _
kVA ` -
Check that the.-
tion
compliance method used.
system complies„
0
Field Inspector Notes:
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance I January 2016
STATE OF CALIFORNIA
Electrical Power Distribution
CEC-NRCC-ELC-01-E (Revised 01/16)
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E
Electrical Power Distribution (Page 5 of 6)
Project Name: Date Prepared:
Desert Vein & Vascular Institute TI 12'5/2017
C. Voltage Drop Enforcement Agency
Check all boxes below if the electrical power distribution system is in compliance with Section 130.5(c). Check that the system
complies
91 The -electrical power distribution system meets the voltage drop requirement of Section 130.5(c). The maximum
combined voltage drop on feeder conductors and branch circuit conductors to the farthest connected load or ❑
outlet, do not exceed 5%.
$1 Voltage drop calculation documents showing compliance to Section 130.5(c) are submitted as part of the I ❑
compliance document submittal.
D. Circuit Controls for 120 -Volt Receptacles and Controlled Receptacles
Field Inspector
Check one or more boxes below for applicable requirements of Section 130.5(d) for the electrical power distribution
Cehck that the system
system.
complies.
91 The control is capable of automatically shutting OFF the controlled receptacles when the space is typically
unoccupied, either at the receptacle or circuit level. For the automatic time switch control, it incorporates an
override control that allows the controlled receptacle to remain ON for no more than 2 hours when an override
❑
is initiated and an automatic holiday "shut -OFF" feature that turns OFF all loads for at least 24 hours and then
resumes the normally scheduled operation. Countdown timer switches are not be used to comply with the
automatic time switch control requirements. The controls meet the requirement of Section 130.5(d)1.
❑ There is at least one controlled receptacle within 6 ft from each uncontrolled receptacle. Where receptacles are
installed in modular furniture in open office area, at least one controlled receptacle is installed at each
❑
workstation. The receptacles meet the requirement of Section 130.5(d)2.
❑ There are installed split wired receptacles with at least one controlled and one uncontrolled receptacle. Where
receptacles are installed in modular furniture in open office area, at least one controlled receptacle is installed
' ❑
at each workstation. The receptacles meet the requirement of Section 130.5(d)2.
91 Permanent and durable marking for controlled receptacles or circuits to differentiate them from uncontrolled
❑
receptacles or circuits is provided. The markings meet the requirement of Section 130.5(d)3.
❑ For hotel and motel guest rooms, there are controlled receptacles for at least one-half of the 120 -volt
receptacles in each guest room. Electric circuits serving controlled receptacles in guestrooms are installed to
have captive key controls, occupancy sensing controls, or automatic controls so the power is switched off no
❑
longer than 30 minutes after the guest room has been vacated. The receptacles meet the requirement of
Section 130.5(d)4.
❑ Receptacles that are only for the following purposes are excepted from Section 130.5(d):
-Receptacles specifically for refrigerators and water dispensers in kitchen areas.
-Receptacles located a minimum of six ft above the floor that are specifically for clocks.
-Receptacles for network copiers, fax machines, A/V and data equipment other than personal computers in
copy rooms.
❑
-Receptacles on circuits rated more than 20 amperes.
-Receptacles connected to an uninterruptible power supply (UPS) that are intended to be in continuous use, 24
hours per day/365 days per year, and are marked to differentiate them from other uncontrolled
receptacles or circuits.
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
STATE OF CALIFORNIA
Electrical Power Distribution
CEC-NRCC-ELC-01-E (Revised 01/16) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E
Electrical Power Distribution (Page 6 of 6)
Project Name: Date Prepared:
Desert Vein &Vascular Institute TI 12/5/2017
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Jon d. Scott
Documentation Author Signature:
Company:
Scott Design and Title 24, Inc,
Signature Date:
12/5/2017
Address: 74818 Velie Way Suite 8
CEA/ HERS Certification Identification (if applicable):
City/state/zip: Palm Desert, CA 92260
Phone: 760-200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design
identified on this Certificate of Compliance (responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system
design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information
provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement
agency for approval with this building permit application.
5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this
Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name: Lawrence C. Reeves
Responsible Designer Signature:
company:
Lawrence C.Reeves, L.P.
Date Signed:
Address: 49-850 Jefferson St., Suite 130
License:
City/State/Zip: Indio, CA 92201
Phone: (818) 425-0830
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
NWA
ad
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Desert Vein & Vascular Institute TI
Date
12/5/2017
System Name
AC 1 -4
Floor Area
3,221
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
4
COIL COOLING PEAK
CFM Sensible
Total Room Loads 6,542 117,665
Return Vented Lighting 0
Return Air Ducts 5,883
Return Fan 0
Ventilation 483 17,591
Supply Fan 0
Supply Air Ducts 5,883
TOTAL SYSTEM LOAD 1 147,023
COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output per System 54,000
12,153 2,098
31,823
Total Output Btuh 216,000
Output Btuh/s ft 67.1
1,591
Cooling System
0
Output per System 53,000
6,560 483
22,517
Total Output Btuh 212,000
18,713
0
Total Output Tons 17.7
1,591
Total Output Btuhls ft 65.8
Total Output s ftfTon 182.3
1 57,522
Air System
CFM per System
1,800
HVAC EQUIPMENT SELECTION
Airflow cfm
7,200
Existing York HVAC 158,852
31,432
134,908
Airflow cfm/s ft2.24
Airflow cfm/Ton
407.5
Outside Air %
6.7%
Total Adjusted System Output 158,852
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
31,432 134,908
Aug 4 PM Jan 1 AM
Outside Air cfmis ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
483 cfm
70 OF
14
67 OF 84 OF 84 OF
Heating Coil Supply Fan 84 OF
7,200 cfm
ROOM
70 OF
4ATr-iOE14
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
111 / 78 OF
Outside Air
483 cfm
77 / 64 OF
79 / 65 OF 58 / 57 OF 58 / 57 OF
Cooling Coil Supply Fan 59 / 58 OF
7,200 cfm
52.3% ROOM
II 76 / 64 OF
EnergyPro 7.2 by EnergySoft
User Number. 6712 ID:
Page 29 of 30
ZONE •AD SUMMARY
ProjectDate
Desert -IM12017
Name
FloorSystem
ZONE LOAD SUMMARY
ZONAL SYSTEM COOLING PEAK
SYSTEM NAME
Tenant Improvement
. ..,
..
30 of ,