BELC2018-000278-495 CALLE TAMPICO
LA QUINTA; CALIFORNIA 92253
Permit Type/Subtype: , ELECTRICAL/
c&ht 4 4 Q"
DESIGN & DEVELOPMENT DEPARTMENT
BUILDING PERMIT
Application Number:
BELC2018-0002
Property Address:
79190 LAURIE CT CT
APN:
604343006
Application Description:
ZYSK / TESLA POWER WALL
Property Zoning:
Application Valuation:
$4,000.00
Applicant:
HOSOPO CORPORATION DBA HORIZON SOLAR POW
7100 WEST FLORIDA AVENUE
HEMET, CA 92253
JAN 1.6 2018
CITY OF LA QUINTA
COMMUNITY DEVELOPMENT DEPARTMENT
LICENSED CONTRACTOR'S DECLARATION
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter 9
(commencing with Section 7000) of Division 3 of the Business and Professions Code, and
my License is in full force and effect.
License Class: B. C46 License No.: 1004/23/3
,D to e: 'Ile, 4 it Contr:
OWNER -BUILDER DECLARATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State
License Law for the following reason (Sec. 7031.5, Business and Professions Code: Any
city or county that requires a permit to construct, alter, improve, demolish, or repair any
structure, prior to its issuance, also requires the applicant for the permit to file a signed
statement that he or she is licensed pursuant to the provisions of the Contractor's State .
License Law (Chapter 9 (commencing with Section 7000) of Division 3 of the Business
and Professions Code) or that he or she is exempt therefrom and the basis for the
alleged exemption. Any violation of Section 7031.5 by any applicant for a permit
subjects the applicant to a civil penalty of not more than five hundred dollars ($500).:
(_) I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for sale.
(Sec. 7044, Business and Professions Code: The Contractors' State License Law does not
apply to an owner of property who builds or improves thereon, arid who does the work
himself or herself through his or her own employees; provided that the improvements
are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner -builder will have the burden of proving that he
or she did not build or improve for the purpose of sale.).
(_) I, as owner of the property, am exclusively contracting with licensed contractors to
construct the project. (Sec. 7044, Business and Professions Code: The Contractors' State
License Law does not apply to an owner of property who builds or improves thereon,
and who contracts for the projects with a contractor(s) licensed pursuant to the
Contractors' State License Law.).
(� I am exempt under Sec. B.&P.C. for this reason
Date
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for
the performance of the work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's Name:
Lender's Address:
VOICE (760) 777-7125
FAX (760) 777-7011
INSPECTIONS (760) 777-7153
Date: ' 1/16/2018
Owner:
ZYSK
79190 LAURIE COURT
LA QUINTA, CA 92253
Contractor:
HOSOPO CORPORATION DBA HORIZON SOLAR POW
7100 WEST FLORIDA AVENUE
HEMET, CA 92253
(951)537-6859
Llc. No.: 1004233
WORKER'S COMPENSATION DECLARATION
I hereby'affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided for by Section 3700 of the Labor Code, for the performance
of the wo for which this permit is issued.
9 -Vv I have and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My workers' compensation insurance carrier and policy number are:
Carrier: HDI GLOBAL INSURANCE COMPANY Policy Number: EWGCR000228616
I certify that in the performance of the work for which this permit is issued, I
shall not employ any person in any manner so as to become subject to the workers'
compensation laws of California, and agree that, if I should become,subject to the
workers' compensation provisions of Section 3700 of the Labor Code, I shall forthwith
comply with those provisions.
D a t e: 1/ C Applicant-.'Y'� 1 d
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS UNLAWFUL,
AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO
ONE HUNDRED THOUSAND DOLLARS ($100,000). IN ADDITION TO THE COST OF
COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE,
INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT: Application is hereby made to the Building Official for a permit subject to
the conditions and restrictions set forth on this application.
1. Each person upon whose behalfthis application is made, each person at whose.
request and for whose benefit work is performed under or pursuant to any permit issued
as a result of this application , the owner, and the applicant, each agrees to, and shall
defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and
employees for any act or omission related to the work being performed under or .
following issuance of this permit. (
2. Any permit issued as a result of this application becomes null and void if work is not
commenced within 180 days from date of issuance of such permit, or cessation of work
for 180 days will subject permit to cancellation.
I certify that I have read this application and state that the above information is correct.
I agree to comply with all city and county ordinances and state.laws relating to building
construction, and hereby authorize representatives of this city to en -upon the above-
mentioned property for inspection purposes. 1
Da� t� r 111 Z 1I � Sign�e.(Applicant or gen ): ��J
Date: 1/16/2018
Applicant: Contractor:
HOSOPO CORPORATION DBA HORIZON SOLAR POW HOSOPO CORPORATION DBA HORIZON SOLAR POW
7100 WEST FLORIDA AVENUE 7100 WEST FLORIDA AVENUE
HEMET, CA 92253 HEMET, CA 92253
(951)537-6859
Llc. No.: 1004233
--------------------------------------------------------------------------------------------
Detail: INSTALL TESLA POWERWALL BACKUP BATTERY AND GATEWAY TRANSFER SWITCH TO SUPPLY PROTECTED LOAD PANEL. 2016 CALIFORNIA
BUILDING CODES.
Application Number:
BELC2018-0002
Owner:
Property Address:
79190 LAURIE CT CT
ZYSK
APN:
604343006
79190 LAURIE COURT
Application Description:
ZYSK / TESLA POWER WALL
LA QUINTA, CA 92253
Property Zoning:
Application Valuation:
$4,000.00
Date: 1/16/2018
Applicant: Contractor:
HOSOPO CORPORATION DBA HORIZON SOLAR POW HOSOPO CORPORATION DBA HORIZON SOLAR POW
7100 WEST FLORIDA AVENUE 7100 WEST FLORIDA AVENUE
HEMET, CA 92253 HEMET, CA 92253
(951)537-6859
Llc. No.: 1004233
--------------------------------------------------------------------------------------------
Detail: INSTALL TESLA POWERWALL BACKUP BATTERY AND GATEWAY TRANSFER SWITCH TO SUPPLY PROTECTED LOAD PANEL. 2016 CALIFORNIA
BUILDING CODES.
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT
BSAS SB1473 FEE 101-0000-20306 0 $1.00
Total Paid for BUILDING STANDARDS ADMINISTRATION BSA: $1.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
POWER APPARATUS
101-0000-42403
0
$25.33
DESCRIPTION
ACCOUNT
QTY
AMOUNT
POWER APPARATUS PC
101-0000-42600
0
$25.33
Total Paid for ELECTRICAL: $50.66
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PERMIT ISSUANCE
101-0000-42404
0
$98.83
Total Paid for PERMIT ISSUANCE: $98.83
DESCRIPTION
ACCOUNT
QTY
AMOUNT
RECORDS MANAGEMENT FEE
101-0000-42416
0
$10.00
Total Paid for RECORDS MANAGEMENT FEE: $10.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
TECHNOLOGY ENHANCEMENT FEE
502-0000-43611
0
$5.00
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00
.
i
,
i
Project Address: 79190 Laurie Court .
1
ii
.
s
,
i
Project Address: 79190 Laurie Court .
• 1
ii
79190 Laurie Court '
Legal Description:
city, sT, zip: La Quinta,,CA 92253
Contractor: HOSOPO•CORP DBA" t :' `
ITelephone:
Address:`
7100 W Florida Ave,... �
Pro�ect`Description: BatteCy, .
Ity, ST, Zi
`.. C P Hemet CA 92545
-
Telephone: 951 537 6859 y
"•
..State Lia # A 004233 ` ...._ City;Lic. #, 762822
c
i
Arch., Bngr., Designer
Address
City., ST, Zip: • ,i
c `
l Telephone: _ _ _
"�',
.''
.._Construction Type , Occupancy *' .
State Lic. #: - '.�
Project type (circle one): New Add'n Alter Repair Demo
Name of Contact Person: Holly Thompson
Sq Ft.:
# Stories: -
#Unit;:
Tali phone # of Contact Person: 951 5376859
Esttmatcd Value of 1'roject: $ 4600 _ Y
{ . •_....,- -- .- APPLICANT: DO NOT_WRITE BELOW _THIS UNE
#
Submlttal
Req'd _'
Ree'd
TRACKDVG..�
_,., = PERMIT FEES
Plan Sets
Plan Check submitted
.
Item Amount
Structural Cafes.
'-
Reviewed, ready for corrections
Plan Check Deposit ,
Truss Cala.
Called Contact Person .
Plan Check Balance
Tide 24 Cala.
I
I
Plans picked up
Construction' '
Flood plain plan
(
Plans resubmitted
Mechatilcal _
Grading plan
2id Review, ready for correctionsressue
Electrical
SubcontactorList
Called Contact Person
[Plumbing -
Grant Deed
( Plans picked up . -
I
, S.M.I. "
H.O.A. Approval
Plans resubmitted
Grading
I'M HOUSE:-
I
Rcview, ready for corrections/Issue
Developer Impact Fee
Planning Approval.
Called Contact Person
-
A.I.P.P•
Pub. Wks. Appr t
Date of permit Issue
r
School Fees
(
,
e
Total Permit Fees
D O x T m m cn 0 m O m 0 -i z m 0� m n D m O cn D M m T�
c O D m � Z 0 0 z m z O m m D 0 m m c 0 x 0 -i x x 0 0=
O O 2:00 C r0 D O O� m Z 0 m O F Z m Z p O O m m C Z m
0 >C/)zZym0 nmDz�Ocmn >-;�-40OC�O��my�
zmn-1 0
r`_'c D�mrn �O�C=O-�0zO{ m c) r mD�mZcm'>
0r m� z�Z �ocDi)�cci�DD=Dm�00cnOZ�ZnOn--i
OiO�c>-icn7mmzmcZj- rncnzcnX-Orno0m0�
cn�AOOmcn��c-)nG7cmD 00A �Tn mOcmw0
z O c:5 Z U) Z m 0 0 R -A n -G 0 _ 7 m p m 0 m y c mr
ocm m m D=n D Z W D > m m000m�-mi
M
O Z Z D T m � O -i - D 0 0 0�� m 0 Z m
c MMz0 rrmc7= � W OOmo
�=pD�=;� D&5D?p0 -i0p�DF zcnO000ZZ0
m-i00z� Zco Z�m mcn mm ��-z-imc�m m
v?OOAm CD CD (n�000(n mO�zcn D
zcznc- �Wmm� > 0=00 r=c7r�Oczi��XO
rr Oxz>mm�OZmmo co> U) -i yO,�mD70
��70
ccn(nG M0� I m0 MO�pO -'O. c� 0z
Z D< m D rn CO OO Z D O z m A O G p
z - O�Ornmmm 0 poG� m mmz�z
D �OzoDG) C-) 0 O-icm�m mm OO�cn>m
cnm W nMX 0C) 2ZmNcmi --j m�cc��O�
OOO�cnOrzC) c/) mDomO m� W xCnzcn
D mm��cnr2T 0 00mmD �O 0mzm�0
M 0 Z y m N y z f Z r cn � O O m� z
0�0���0DZ11) 07Dz Xm �0 m �--j C)
c� m D� m r 0 D 0 � _ G 0 m m
D O O j m i 0 � m D
z = 0 --A +
o m
p 7 m
X= --A O 0 0 0> - Z= m 5
F 0 Z C Z C/) r M M� 0 0 m
cvizz� d
0>M--
mGmcm Azz zvc �� TI
o
oopc—ZioZmpzM> >v'--1ooc O -I
z
o=C)-icmc'mrzz�m=00
M O
-��OmZMm--i=iM =: x O L
O�2
m�zmD�m00mvOr0-
ic)OmmC�zr�c��mzc
m�0m0o00VOmcnM x>0 1��
M 0 A 0 m? m cn 0 0r x 0 D
U T m Z c m m z c
=ZmN mv) --I XO -C)OmZ r
m0x�cn�m0 c� nmmc�cmi� STI
m �
- M� 00ifX--I(n 'D
-iimmm�m0 az
O D m m m m O m 0=
cn -v m
-DimzomA000 mmz�m�
0 m � E
z
C-) I C)z c m O 0 D zf -om -i
m
j m 0 m 0 m 70 z z� m 0m 70 No
�Sm oCSz m=OTT
imz� 00m� cci)m=m m
O� m r m D m o D
v � -
i Z c7 Z x O OC -< O`
+ m
0 m n D
m -i �
1
Z
S
I �
C
�0
m
m
D
m
O XO �a �
tc
U
Om
M m
az
Z
x 'v�iaO
Z
m
T nOm
O
D
D
z
m-+� r
r— m C
n m
z m
XD
C- m -o
C
m
0
n
�
>
C =
(f)
X
O
iv r m �17
y
z m
O m
z-<
y o
rm—z
m
D
L2 �2 C2 O
T
r
T
p 7 m
X= --A O 0 0 0> - Z= m 5
F 0 Z C Z C/) r M M� 0 0 m
cvizz� d
0>M--
mGmcm Azz zvc �� TI
o
oopc—ZioZmpzM> >v'--1ooc O -I
z
o=C)-icmc'mrzz�m=00
M O
-��OmZMm--i=iM =: x O L
O�2
m�zmD�m00mvOr0-
ic)OmmC�zr�c��mzc
m�0m0o00VOmcnM x>0 1��
M 0 A 0 m? m cn 0 0r x 0 D
U T m Z c m m z c
=ZmN mv) --I XO -C)OmZ r
m0x�cn�m0 c� nmmc�cmi� STI
m �
- M� 00ifX--I(n 'D
-iimmm�m0 az
O D m m m m O m 0=
cn -v m
-DimzomA000 mmz�m�
0 m � E
z
C-) I C)z c m O 0 D zf -om -i
m
j m 0 m 0 m 70 z z� m 0m 70 No
�Sm oCSz m=OTT
imz� 00m� cci)m=m m
O� m r m D m o D
v � -
i Z c7 Z x O OC -< O`
+ m
0 m n D
m -i �
II
O
pi
Z►
h u I ZU I I
SLC
S 0 L A R P 0 W E R
yg.: �4�
10SOP0 CORP. OWNER
100 W. Florida Ave. ZYSK
emet, Ca 92545 79190 LAURIE COURT
)51) 926-1176 LA QUINTA, CA 92253
SLB- C-46 #1004233 PHONE: (760) 610-5626
JOB#:16651
p
m
z
n
m JAN 0 5 2011b
CITY OF lA QUINTA
W N Cf)
1
Z
S
I �
,
�0
m
m
D
m
O XO �a �
U
Om
az
Z
x 'v�iaO
m
T nOm
O
II
O
pi
Z►
h u I ZU I I
SLC
S 0 L A R P 0 W E R
yg.: �4�
10SOP0 CORP. OWNER
100 W. Florida Ave. ZYSK
emet, Ca 92545 79190 LAURIE COURT
)51) 926-1176 LA QUINTA, CA 92253
SLB- C-46 #1004233 PHONE: (760) 610-5626
JOB#:16651
p
m
z
n
m JAN 0 5 2011b
CITY OF lA QUINTA
W N Cf)
� Z Z Z
S
m
m
z ,
> M
>
Z n
m-+� r
r— m C
C- m -o
m
0
m
N p D
X
O
iv r m �17
y
m
T
L2 �2 C2 O
r
zGz�m �
n
m
m
D nj
z
0
�0
GD') m
cci>
�
S
mzz
-�-i
m 9- o
o z z
� o
G) m
rn
cn
TESLA POWER WALL
DATE: 1/3/18 REVISIONS:
DESIGNER: J.F. _
CHECKED BY: X.X
SITE PLAN &
GENERAL NOTES
SHEET 1
2a6 coc"*$
TrSLA SPECIFIC NOTES
1. THERE WILL BE A TEMPORARY DISCONNECTION OF SOLAR DURING
THIS RELOCATION. CUSTOMER IS RESPONSIBLE TO CONFIRM WITH
THE ORIGINAL SOLAR INSTALLER AND/OR SYSTEM OWNER THAT THIS
RELOCATION OF THE MAIN POINT OF INTERCONNECTION WILL NOT
VOID ANY APPLICABLE WARRANTIES OR VIOLATE ANY APPLICABLE
CONTRACTUAL OBLIGATIONS.
2.INSTALLATION OF A CATS HARDWIRED CONNECTION OR POWERLINE
CONNECTION FROM ENERGY STORAGE SYSTEM MONITORING HUB TO
CUSTOMER'S INTERNET ROUTER. NO WIRELESS CONNECTIONS
PERMITTED.
3.COMMISSIONING AND TESTING OF SYSTEM TO INCLUDE A
SIMULATION OF GRID OUTAGE WHILE CUSTOMER IS HOME TO
SIMULATE PROPER OPERATING EXPERIENCE DURING GRID OUTAGE.
REVIEW OF MONITORING PLATFORM WITH CUSTOMER TO SHOW
VISIBILITY INTO SYSTEM OPERATIONS VIA COMPUTER AND SMART
DEVICES.
4.D000MENTATION AND PERMANENT LABELING OF ALL NEW CIRCUIT
BREAKERS INSTALLED IN PROTECTED LOADS PANEL TO IDENTIFY
THE CIRCUIT AND APPLIANCES CONNECTED.
RELOCATE CIRCUITS TO THE NEW
PROTECTED LOAD SUB PANEL WITH
INSTALLATION OF ALL NEW CONDUIT, WIRE
AND OTHER COMPONENTS AS NECESSARY
WITHIN 25' OF EXISTING LOCATION.
BRANCH CIRCUIT WIRING MODIFIED,
REPLACED, OR EXTENDED MORE THAN 6
FT. SHALL BE REQUIRED TO HAVE AFCI
PROTECTION. ART. 210.12(B)
ALL WORK SHALL COMPLY WITH NEC
(480.1-480.10) AND (690.71-690.85)
(E) PV SYSTEM:
(18) CS6K 280M MODULES W/
(1) SOLAREDGE SE380OH-US INVERTER
CEC RATING: 257.8 X 18 X 0.99 = 4594
BATTERY STORAGE SYSTEM NOTES
ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL
COMPLY WITH THE FOLLOWING APPLICABLE CODES:
2016 CA BUILDING CODE, PART 2
2016 CA RESIDENTIAL CODE PART, 2.5
2016 CA MECHANICAL CODE, PART 4
2016 CA ELECTRICAL CODE, PART 3
2016 CA PLUMBING CODE, PART 5
2016 CA EXISTING BUILDING CODE, PART 10
2016 CA GREEN BUILDING STANDARDS CODE, PART 11
2016 CA REFERENCE STANDARDS CODE, PART 12
2016 CA FIRE CODE
BACKFED BREAKERS MUST BE LOCATED @ OPPOSITE END OF BUS
BAR FROM MAIN BREAKER OR MAIN LUG ON GRID SIDE. WHEN A
BACKFED BREAKER IS THE METHOD OF UNTILITY INTERCONNECTION,
BREAKER SHALL NOT READ'LINE OR LOAD'.
PER CEC 250.64(C): CONDUCTOR SPLICES ONLY ALLOWED WITH
COMPRESSION CONNECTORS OR EXOTHERMIC WELDING
VERIFY (E) LIFER GROUND NEAR MSP. IF (E) LIFER IS NOT ACCESSIBLE
OR VERIFIABLE, INSTALL A NEW 5/8"0 X 8' LONG GROUNDING ROD
AND BOND SOLAR SYSTEM EQUIPMENT GROUNDING ACCORDINGLY.
2 f
TESLA
POWER WALL 2
CT
CT
T
r3
3
L_-
0.75" I E MT 10.0844 I 169/.
CAT 5 HARDWIRED
INTO ROUTER NO
WIRELESS
CONNECTION
PERMITTED
INCOMING
UTILITY
SERVICE
7
MAIN
--BREARER-
M
CITY F LA QIJONTA
�UILDING &
SAFETY DEPT.
J ORS ONSTR CTI®
I
DATE � BY.
Conductors
OEXISTING RUN
O 3 #lOAWGTHWN-2
1 #10 AWG THWN-2 EGC
O 3
4
1.00" I EMT 10.3285 I 38%
120/240V
1 -PH, 3W
TESLA WALL 2 EQUIPMENT
QPV BREAKER 20A -2P, 240V- 1
2Q SUB 200A BUS W/ 100A MAIN 1
PANEL BREAKER 240V
SUB
APANELBREAKER 100A 2P BREAKER 1
TESLA
POWERWALL 2 AC SKW, 240V, 13.5 KWH 1
TESLA
Q POWERWALL 30A 2P BREAKER 1
BREAKER
BACKUP TESLA 200A ATS /METER 1
6 GATEWAY
(N) MAIN SERVICE PANEL & �
QMAIN SERVICE METER: 225 MAIN BUSBAR
PANEL W/ 200 TOP FED MAIN
BREAKER.
QMONITORING TESLA MONITORING UNIT 1
CIRCUITS 30A OR LESS
Q9 (E) LOADS RELOCATED TO SUB PANEL, e
TOTAL LOAD NOT TO
EXCEED SUB PANEL RATING
GATEWAY 100A 2P BREAKER 1
BREAKERI
MAIN SERVICE BACKFEED CALC:
1 X 5000W / 240V = 20.83A
PER NEC A. 705.12(D)
20.83A X 1.25 = 26.04A
MSP BUS BAR = 225A
TOTAL POWERWALL BACKFEED = 26.04A
225A x 1.2 = 270A
LARGEST OCPD : 270A - 200A = 70A
3 AWG THWN-2
46.04A < 70A
1
#8 AWG THWN-2 EGC
OCURRENT
PER NEC A. 705.12(D)
TRANSFORMER
1.00" I EMT 10.3285 I 38%
120/240V
1 -PH, 3W
TESLA WALL 2 EQUIPMENT
QPV BREAKER 20A -2P, 240V- 1
2Q SUB 200A BUS W/ 100A MAIN 1
PANEL BREAKER 240V
SUB
APANELBREAKER 100A 2P BREAKER 1
TESLA
POWERWALL 2 AC SKW, 240V, 13.5 KWH 1
TESLA
Q POWERWALL 30A 2P BREAKER 1
BREAKER
BACKUP TESLA 200A ATS /METER 1
6 GATEWAY
(N) MAIN SERVICE PANEL & �
QMAIN SERVICE METER: 225 MAIN BUSBAR
PANEL W/ 200 TOP FED MAIN
BREAKER.
QMONITORING TESLA MONITORING UNIT 1
CIRCUITS 30A OR LESS
Q9 (E) LOADS RELOCATED TO SUB PANEL, e
TOTAL LOAD NOT TO
EXCEED SUB PANEL RATING
GATEWAY 100A 2P BREAKER 1
BREAKERI
TESLA POWERWALL BACKFEED:
AMPACITY CALCULATIONS ,
BATTERY TO BACK UP SUB PANEL
WIRE AMPACITY 2016 CEC THERMAL DERATE FACTOR NUMBER OF
TABLE 310.15(8)(16) 2016 CEC TABLE 310.15(B)(2)(a) CONDUCTORS
THWN•2 - 75° C 2016 CEC 310.15 (B)(3)(a )
10 AWG 30 0-3
35 AMPS X 1 X 1
MAXIMUM ALLOWABLE AMPACITY = 35
DESIGN AMPACITY = 30.00
BACK UP SUB PANEL TO MSP
NUMBER OF
WIRE AMPACITY 2016 CEC
THERMAL DERATE FACTOR CONDUCTORS
TABLE 310.15(8)(16)
2016 CEC TABLE 310.15(B)(2)(a)(C°) 2016 CEC 310.15
THWN-2 - 75° C
16113!(a)
MAIN SERVICE BACKFEED CALC:
1 X 5000W / 240V = 20.83A
PER NEC A. 705.12(D)
20.83A X 1.25 = 26.04A
MSP BUS BAR = 225A
TOTAL POWERWALL BACKFEED = 26.04A
225A x 1.2 = 270A
LARGEST OCPD : 270A - 200A = 70A
SOLAR BACKFEED CALC:
46.04A < 70A
16A X 1.25 = 20A
SUB PANEL BACKFEED CALC:
TOTAL (E) PV BACKFEED = 20A
PER NEC A. 705.12(D)
SUB PANEL BUS BAR = 200A
TOTAL SYSTEM BACKFEED CALC:
200A X 1.2 = 240A
26.04A + 20A = 46.04A
LARGEST OCPD :240 -100A = 140A
46.04 < 140A
UofLU
3 AWG
30
0-3
100 AMPS X 1 X 1
MAXIMUM ALLOWABLE AMPACITY = 100
DESIGN AMPACITY = 100
TESLA POWERWALL BACKFEED:
AMPACITY CALCULATIONS ,
BATTERY TO BACK UP SUB PANEL
WIRE AMPACITY 2016 CEC THERMAL DERATE FACTOR NUMBER OF
TABLE 310.15(8)(16) 2016 CEC TABLE 310.15(B)(2)(a) CONDUCTORS
THWN•2 - 75° C 2016 CEC 310.15 (B)(3)(a )
10 AWG 30 0-3
35 AMPS X 1 X 1
MAXIMUM ALLOWABLE AMPACITY = 35
DESIGN AMPACITY = 30.00
BACK UP SUB PANEL TO MSP
NUMBER OF
WIRE AMPACITY 2016 CEC
THERMAL DERATE FACTOR CONDUCTORS
TABLE 310.15(8)(16)
2016 CEC TABLE 310.15(B)(2)(a)(C°) 2016 CEC 310.15
THWN-2 - 75° C
16113!(a)
MAIN SERVICE BACKFEED CALC:
1 X 5000W / 240V = 20.83A
PER NEC A. 705.12(D)
20.83A X 1.25 = 26.04A
MSP BUS BAR = 225A
TOTAL POWERWALL BACKFEED = 26.04A
225A x 1.2 = 270A
LARGEST OCPD : 270A - 200A = 70A
SOLAR BACKFEED CALC:
46.04A < 70A
16A X 1.25 = 20A
SUB PANEL BACKFEED CALC:
TOTAL (E) PV BACKFEED = 20A
PER NEC A. 705.12(D)
SUB PANEL BUS BAR = 200A
TOTAL SYSTEM BACKFEED CALC:
200A X 1.2 = 240A
26.04A + 20A = 46.04A
LARGEST OCPD :240 -100A = 140A
46.04 < 140A
w
Z :�ii CV
� Q
J � W
Q =
U)
Z 0
C/)
UofLU
3 AWG
30
0-3
100 AMPS X 1 X 1
MAXIMUM ALLOWABLE AMPACITY = 100
DESIGN AMPACITY = 100
J
J
� I
W _o
OLL,
� x
Q LL X
W LC
U,
_Z
iu 2 U
- O in
Q � O
U cn
Q
W U o
Z �z 6j
Y o =) Z
cn�2Qocn
N
�
U QLr) o
� v _
0 = N � #
a. 0);: (0
UofLU
4
A
U)
z
W o
LL X
uj LJ.I
Z Y
-' wOU
QW 2
0 0 U
CNO
[D':
CN 17
O s O
U Q cn
w U
o
� cn�
eco
Z g Z w
Y o Z
w 00 m
o NSad
O cn
U >
Q- Lo o '
Zr
^O^ :2N r i it
a. _O O O
� U N U
0 �.E:�m
OJ
TT N Lo U)
r
Lu
N >.
® Q.
_ - bx6.. I YF
.. - GtC 705 10
_i r Ln
NOTES
1. CEC ARTICLES 690 AND 705 AND CRC SECTION R331 MARKINGS SHOWN HEREON,
•. .. � � ...
ALL MARKINGS S HALL CONSIST OF THE FOLLOWING: -
-
`
. A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR MACHINE PRINTED LETTERS OR ELECTRO -PLATING
W
M
B. RED BACKGROUND COLOR WITH WHITE TEXT AND LINE WORK
,.
C. ARIAL FONT
` Q
W
*'
3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN THE LOCATIONS SPECIFIED: -
Z
LLJ
4. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT USING POP -RIVETS OR SCREWS.
(�
2
5.- THE LABEL SHALL BE SUITABLE FOR THE ENVIRONMENT WHERE IT IS INSTALLED •
c/)�
*
4
6. WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL FIELD APPLIED LABELS, WARNINGS, AND MARKINGS'
O
�*'
MARKING].
SHOULD COMPLY WITH ANSI Z535.4 [NEC 110.21(B) FIELD MARKING].
",
- L
• „ HERED VINYL'SIGN S SHALL BE
7. ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IFPROPERLYAD
-.
..
A 1
WEATHER RESISTANT [IFC 605 -
4
A
U)
z
W o
LL X
uj LJ.I
Z Y
-' wOU
QW 2
0 0 U
CNO
[D':
CN 17
O s O
U Q cn
w U
o
� cn�
eco
Z g Z w
Y o Z
w 00 m
o NSad
O cn
U >
Q- Lo o '
Zr
^O^ :2N r i it
a. _O O O
� U N U
0 �.E:�m
OJ
TT N Lo U)
r
Lu
N >.
® Q.
_ - bx6.. I YF
.. - GtC 705 10
_i r Ln
POWERWALL {
- TYPICAL SYSTEM UAYOUTS
Tesla Powerwall is a fully -integrated AC battery system for WHOLE HOME BACKUP
residential or light commercial use. Its rechargeable lithium -ion` s..� L
battery pack provides energy storage for solar self -consumption, optional:
load shifting, and backup. ' . - _/�r�//}�/�/�//��/] -
• • +`Fk- • r lam!
Powerwall's electrical interface provides a simple connection to �;,t r 4 Solar
any home or building. Its revolutionary compact design achieves `< .S'- , ,•-I
market -leading energy density and is easy to install, enabling 4.'FR -- • ". t
owners to quickly realize the benefits of reliable. clean power.
oar inverter
1
S I ity
____ _________________ Main panel Backup Gateway` = Utility meter Grid
including
service disconnect
k
PERFORMANCE SPECIFICATIONS' MECHANICAL SPECIFICATIONS•- , _ - - • 'V w ,
AC Voltage (Nominal) 120/240 V Dimensions 1150 mm x 755 mm x 155 mm 'r
(45.3 in x 29.7 in x 6.1 in)
Feed -In Type Split Phase .................. ... ............ _....--........ _....... _....................... ....... --- .......... - ------- __.............. _-..... _.__....... _..................
.
.... _.... _........ _.......... _...... -............... ..... ................._....._....--_..... _...... _..__... .._..__............ ..._..__........__.................._...._.........................
_. ti....._ Weight 125 kg (2761bs) + - Grid Frequency - 60 Hz z............._.._.......__..._..._._....._..._........_.......__......._.............._...._...__............._............. _............. ,
AL
....."............_...._.._................................._........._. Powerwall 3 e
f _ ............ ...... .......... _.'......... _................ _................................................................................. ". Mounting options Floor or wall mount •
Total Energy 14 kWh ................ •• Whole hom
•---_.._....------......----.._..........-----........------....__......---._..............._..__....---..__....__._.............---..:_...._..__..__.._..__ _ __ _ __ _-
backup
u
Usable Energy' 13.5 kWh 755 mm 155 mm ? df
- .17q 7 int (6 1 in)
' Real Power, max continuous
5 kW (charge and discharge)
L Real Power, peak (10s)
7 kW (discharge only)
Apparent Power, max continuous-
5.8 kVA (charge and discharge)
...... _...........
................................................. _.... _................................. ........ ................. ....._......
Apparent Power, peak (10 s)
_--..................... ................... ..................... ._-...................
7.2 kVA (discharge only)
--......__.._..._..--............... _... __._....--...........
' Maximum Supply Fault Current
---......... -............. ..... --._...... -----.......................... .............
10 kA
- - - ----- ..__..—_.._...--- - ...._..--.._..
Maximum Output Fault Current
-._........__..__._......--- --...._..__-. --__........... - -
32A
Overcurrent Protection Device •
..
30 A^�-
......... _.........
.......................................... ............................................. ........ ........... ..................
Imbalance for Split -Phase Loads
.._.._._............ ........_........................ ............... -...__........._._-
100%
__ ............................ ............. _........... ......
Power Factor Output Range
---- ... -- -.... - ---...._._._.._...__.._.....__....._._...-
__.......__.........._.._........................... .__..._......... ....... _ -...
+/- 1.0 adjustable
...__._......... .._............ ---.....__.....- ...... --........... _
Power Factor Range (full -rated power)
+/-0.85
._....... --_- ........ ---..... -- ...._—._._.....--- - _
Internal Battery DC Voltage
.................. ........ ... ......... _........... _-._._.........._.__....---
1
_ .._..... __._._._...- ....... - ... _..... _..... __ _...... _
50V
-._..__...... ._...---....-— ..... .... ............ _....... - _
Round Trip Efficiency 90%
• ................. __............................. _._....... _..... _............ _. __.... __....._..._._.._.--'................................... ............ ........ - ...... --
Warranty • , 10 years
•
ENVIRONMENTAL SPECIFICATIONS
'
_.�..___
_-
-
-_ I
.
+ PARTIAL HOME BACKUP
_...._ _.._ . __......._._...---_......___......._...._...
_..._..._._._ .._._..__...._.�....._...__ _...`
1150 mm Optional
.Solar inverter
(45.3 in) I
`' `• Solar
_
' 2 A to battery to AC. at beginning of life. •
Round Trip Efficiency 90%
• ................. __............................. _._....... _..... _............ _. __.... __....._..._._.._.--'................................... ............ ........ - ...... --
Warranty • , 10 years
•
ENVIRONMENTAL SPECIFICATIONS
'
_.�..___
_-
-
-_ I
.
- 'Values provided for 25`C (77°F). 3.3 kW charge/discharge power. -
_...._ _.._ . __......._._...---_......___......._...._...
_..._..._._._ .._._..__...._.�....._...__ _...`
•
.
.Solar inverter
_
' 2 A to battery to AC. at beginning of life. •
Operating Temperature
-20°C to 50°C (-4°F to 122°F)
"""'""- """" """'
Sub panel
Backup Gateway
Main panel
Utility meter -
Grid
•
'
s
,.
Operating Humidity (RH)
Up to 100%, condensing
i
Storage Conditions
-20°C to 30°C (-4°F to 86°F)
COMPLIANCE .INFORMATION �
up to 95% RH, non -condensing
� t
State of Energy (SoE) 25% initial
_
(
fl)
t Certifications ; • UL 1642, UL 1741, UL 1973,
. w UL 9540, UN 38.3
_ ._. ...
Maximum Elevation
Environment
3000 m (9843
Indoor-and outdoor rated
•
+ Grid Connection Worldwide Compatibility
Enclosure Type
NEMA 3R
Powerwall
Backup loads
Home loads
Emissions ±' FCC Part 15 Class B, ICES 003
Ingress Rating
IP67 (Battery & Power Electronics)
-
_
Environmental i 1 RoHS Directive 2011/65/EU
IP56 (Wiring Compartment)
Seismic ". AC156, IEEE 693-2005 (high)
Wet Location Rating
Yes
•'
Pollution Degree Rating
PD3 .
-
Noise level @ 1 m
"10 dBA at 30' C (86"Fi
`
T = S L n
-
ESL n.CO f/et . GY
T = S L n
NA - BACKUP - 2017-07-17
7e5tA.COM/c cRGv
POWERWALL
Backup Gateway
The Backup Gateway for Tesla Powerwall provides energy management
and monitoring for solar self -consumption, load shifting, and whole -
home or partial -home backup.
The Backup Gateway controls connection to the grid, automatically
detecting outages and providing a seamless transition to backup
power. When equipped with a circuit breaker, the Backup Gateway can
be installed at the service entrance.
The Backup Gateway communicates directly with Powerwall, allowing
you to monitor home energy use and manage backup energy reserves
from any mobile device with the Tesla app.
PERFORMANCE SPECIFICATIONS
AC Voltage (Nominal)
..................... _... ......... .... - ............. -_............... - -- ...._._...._..-.__....----
230 V, 120/240 V
-....... - - -.. _..
Feed -In Type
Single & Split Phase
Grid Frequency — -
- 50 and 60 Hz
.................................. .._.... _.............. ---...... ............. _.._........................................................................
Disconnect Current
_.................... _........... .............. __._............................... _...... _... _._
200 A
--.....__-...... -... -......... _--...................... __....... .-
Maximum Input Short Circuit Current
--- ------- --.....__... ._..._.... — - .-_._......-
10 kA
Overcurrent Protection Device'
100-200 A; Service Entrance Rated
Overvoltage Category
Category III
AC Meter
Revenue grade (+/- 1 %)
----------------------._....--_....-- - — --
Connectivity
..... _.... _............................................... _._.._... _..._............................ .
----- --- -..
Ethernet, Cellular (3G), Wi-Fi
_.......
.............
User Interface
......... _.._._.._.................._.._.__.......................... _........ _._...__--..........
Tesla App
............. _.... _._. .---...._...........__._.....__.........._.................._...................................._.................................._....................__.........................-
Operating Modes
Support for solar self -consumption,
... .... .... _._..... _........ ........................................ .......... . ........
FCC Part 15 Class B, ICES 003
load shifting, and backup
Backup Operation
Automatic disconnect for seamless
WEEE Directive 2012/19/EU,
backup transition
Modularity Supports up to 10 AC -coupled
Powerwalls
-................ -...................... --............ ................... .... -.... --._........................ _..... _....... .............. _......... ... _........... ..
Warranty 10 years
._.... _........ -.... _._._....... ............................... --.... -..__._._......................
'Circuit breaker required for installation at service entrance.
COMPLIANCE INFORMATION
__._._.__..---.._.__....-----.----___..._.._._......._____......_.
Certifications
_._._.... _..................... _.... _..... _.._..__....---------- --- ---
UL 1642, UL 1741, IEC 61000-6-3,
IEC 62109-1; CSA C22.2.107.1,
EN 55024, EN 301 489-1,
__._ .... _...........,
EN 301 489-7, EN 301 489-17
_...._ ... _....... .... ._......... .... _._....._.-.._... ..._......._._._ _..
Grid Connection
Worldwide Compatibility
-._.._ ............... __ ............... ...._.............. _ ......
Emissions
... .... .... _._..... _........ ........................................ .......... . ........
FCC Part 15 Class B, ICES 003
Environmental
RoHS Directive 2011/65/EU,
WEEE Directive 2012/19/EU,
Battery Directive 2006/66/EC
Seismic
AC 156, IEEE 693-2005 (high)
T=SLn
MECHANICAL SPECIFICATIONS
_...__.-.— ....... _............ ---...__........ --.._._.__._...._._._..--_..._._._.. -- -- —---._..__.._
Dimensions 740 mm x 378 mm x 129 mm
(29.1 in x 14.9 in x 5.1 in)
-- ............. - - ------....__...._.._..._...---...__......_..._._..........._......_............----..... -_..._..._- ......... _.... _.......
Weight 16.4 kg (36 lbs)
Mounting options Wall mount
740 mm
(29.1 in)
378 mm
(14.9 in)
129 mm
(5.1 in)
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature -20°C to 50°C (-4°F to 122°F)
... _._............... .............................. ................ _.......... _.......... ----.... ............................ .,..... _...... o._.._ .... _.......... _._................ _.... _... _................. _._... _........ __....
Operating Humidity (RH) Up to 100%, condensing
.......... ............... ............ ........_ ...... _ ...... ......... _............. _ _....... _.................
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
............ ...... -... ........... .... _... ... _........... .... _.__....__..._..__ .....__........_,...... _..__.......... ......_....... __....... _.... _... ... ..........
Enclosure Type NEMA 3R
Ingress Rating IP44
Pollution Degree Rating PD3
2017-07-17
TESLA.CON/ENERGv
■
Step 10: Make AC Power Connections
1. Determine whether the installation requires that neutral be bonded to ground in the Backup
Gateway. In most cases, if the Backup Gateway is to be located between the electrical service
entrance and the main electrical panel, neutral should be bonded to ground. Otherwise,
bonding should be removed.
The Backup Gateway ships with neutral bonded to ground. To remove bonding, disconnect
the green wire between the ground bar and the neutral terminals.
Figure 39: Backup Gateway Ground Bar (top left) Bonded to Neutral (bottom right)
2. Connect the electrical service from the service inlet or from the main panel (depending on
the backup configuration) to the Backup Gateway source connection terminals according to
the following table and diagram (Fig 40). Strip the ends of the wires and insert them in the
corresponding Backup Gateway terminal lugs. Tighten the lugs to 30 Nm (22 Ib -ft).
NOTE: For electrical service connections to the Backup Gateway, use 16-120 mm2 (6 AWG to
250 kcmil), 90 deg C minimum copper (Cu) wire.
36 Powerwall Installation Manual
O
n
[gill
Backup Gateway AC Wiring
Service Connection
Backup Gateway Terminal Wire Gauge
Line 1 =
Sl 16-120 mm2 (6 AWG - 250 kcmil)
Line 2
S2 16-120 mm2 (6 AWG - 250 kcmil)
Neutral
N 16-120 mm2 (6 AWG - 250 kcmil)
36 Powerwall Installation Manual
O
n
[gill
Main/Sub Panel Breaker Terminal
Powerwall Terminal
Wire Gauge
0
o .O . O
Fu_mm
It
EO
O
Source Connection
S1 S2
L1 L1 L2 L2 N N
Load Connections
Figure 40: Backup Gateway Power Connectors (shown with breaker installed)
3. Connect Powerwall to the main or sub electrical panel of the installation (depending on the
backup configuration) according to the following tables, for your electrical service type.
NOTE: For AC power connections to Powerwall, use 6-10 mm2 (10-8 AWG) 90 deg C
minimum copper (Cu) wire.
100 V, 120 V, 200 V, 220 V, 230 V, 240 V Single -Phase Service
Main/Sub Panel Breaker Terminal
Powerwall Terminal
Wire Gauge
Line 1
Ll
6-10 mm2 (10-8 AWG)
Neutral
L2
6-10 mm2 (10-8 AWG)
AN\\ CAUTION: For single-phase service, Neutral is not connected to the Powerwall N
terminal. It is instead connected to the Powerwall L2 terminal.
120/240 V Split -Phase Service
Main/Sub Panel Breaker Terminal
Powerwall Terminal
Wire Gauge
Line 1
Ll
6-10 mm2 (10-8 AWG)
Neutral
N
6-10 mm2 (10-8 AWG)
Line 2
L2
6-10 mm2 (10-8 AWG)
208 V Service
Main/Sub Panel Breaker Terminal
Powerwall Terminal
Wire Gauge
Line 1
Ll
6-10 mm2 (10-8 AWG)
Line 2
L2
6-10 mm2 (10-8 AWG)
4. On the Powerwall side, strip the ends of the wires and attach them to the corresponding
leads on the AC power harness using the provided wirenuts.
S. Plug the AC power harness into the AC connector in the Powerwall wiring compartment.
Ensure that the connector clicks into place.
Figure 41: Powerwall 2 AC Power Harness Connection
NOTE: The Powerwall connection to the main electrical panel requires a 30 A circuit breaker
with a short circuit current rating of 10 kA. This breaker serves as the disconnect for the
Powerwall, and must be wired .in accordance with local wiring codes and regulations.
38 Powerwall Installation Manual