10-1171 (SFD) RevisionP:O. BOX 1504 4
78-495 CALLE TAMPICO
LA QUINTA, .CALIFORNIA 92253 BUILDING & SAFETY DEPARTMENT
BUILDING PERMIT
Application Number: 10-00001171 Owner:
Property Address: 52903 ROSS AVE LOTHENBACH ROBERT J
APN: 767-670-018- -330761- 1000 VALLEY PARK DR
Application description: DWELLING - SINGLE FAMILY DETACHED SHAKOPEE, MN 55379
Property Zoning: LOW DENSITY RESIDENTIAL
Application valuation: 997816
Applicant:
Architect or Engineer-
------------------------------------ --------------
LICENSED
ngineer:
-----------------------------------=--------------
LICENSED CONTRACTOR'S DECLARATION
. I hereby affirm under penalty of perjury that I. am licensed under provisions of Chapter 9 (commencing with
Section 7000) of Division 3 of the Business and Professionals Code, and my License is in full force and effect.
License Class: B License No.: 671203
Date: Contractor:
OWNER -BUILDER DECLARATION
I hereby affirm under penalty of perjury that I 'am exempt from the Contractor's State License Law for the
following reason (Sec. 7031.5, Business and Professions Code: Any city or county that requires a permit to .
construct, alter, improve, demolish, or repair any structure, prior to its issuance, also requires the applicant for the
permit to file a signed statement that he or she is licensed pursuant to the provisions of the Contractor's State
License Law (Chapter 9 (commencing with Section 7000) of Division 3 of the Business and Professions Code) or
that he or she is exempt therefrom and the basis for the alleged exemption. Any violation of Section 7031.5 by
any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500).:
(_ 1 I, as owner of the property, or my employees with wages as their sole compensation, will do the work, and
the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The
Contractors' State License Law does not apply to an owner of property who builds or improves thereon,
and who does the work himself or herself through his or her own employees, provided that the
improvements are not intended or offered for sale. If, however; the building or improvement is sold within
- one year of completion, the owner -builder will have the burden of proving the he or she did not build or
improve for the purpose of sale.).
(_ 1 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec.
7044, Business and Professions Code: The Contractors' State License Law does not apply to an owner of
property who builds or improves thereon, and who contracts for the projects with a contractor(s) licensed
pursuant to the Contractors' State License Law.).
I_) I am exempt under Sec. , B.&P.C. for this reason
Date:
Owner:
CONSTRUCTION.LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for the performance of the
work for which this permit is issued (Sec. 3097, Civ. C.).
Lender's Name:
Lender's Address:
LQPERMIT
Contractor:
PIERCE CORPORATION, ANDREW
P.O. BOX 3420
PALM DESERT, CA 92261-3420
,-..(760)346-3228
`Lic. No.: 671203
VOICE (760) 777-7012
FAX (760) 777-7011
INSPECTIONS (760) 777-7153
Date: 5/14/12
-----------------7-----------------------------
WORKER'S COMPENSATION DECLARATION
1 hereby affirm under penalty of perjury one of the following declarations:
_ I have and will maintain a certificate of consent to self -insure for workers' compensation, as provided
for by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued.
I have and will maintain workers' compensation insurance, as required by Section 3700 of the Labor
Code, for the performance of the work for which this permit is issued. My workers' compensation
insurance carrier and policy number are:
Carrier STATE FUND Policy Number 0006745-2010
_ I certify that, in the performance of the work for which this permit is issued, I shall not employ any
person in any manner so as to become subject to the workers' compensation laws of California,
and agree that, if I should become subject to the workers' compensation provisions of Section
3700 of the Labor Code, I shall forthwith comply with those provisions.
Date: Applicant:
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS UNLAWFUL, AND SHALL
SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO ONE HUNDRED THOUSAND
DOLLARS ($100,000). IN ADDITION TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN
SECTION 3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT Application is hereby made to the Director of Building and Safety for a permit subject to the
conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose request and for
whose benefit work is performed under or pursuant to any permit issued as a result of this application,
the owner, and the applicant, each agrees to, and shall defend, indemnity and hold harmless the City
of La Quinta, its officers, agents and employees for any act or omission related to the work being
performed under or following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is not commenced
within 180 days from date of issuance of such permit, or cessation of work for 180 days will subject
permit to cancellation.
I certify that I have read this application and state that the above information is correct. I agree to comply with all
city and county ordinances and state laws relating to building construction, and hereby authorize representatives
of this county to enter upon the above-mentioned property for. inspection purposes.
Date: Signature (Applicant or Agent):
Application Number. . . . . . 10-00001171
------ ^Structure Information 10,776SF DWELLING/VB/RES-3/CL
A -FR [ENG] -----
Construction Type . .
. . . TYPE V, UNPROTECTED
Occupancy Type
DWELLG/LODGING/CONG <=10
Other struct info
CODE EDITION
2007/2008
# BEDROOMS
8.00
FIRE SPRINKLERS.
NO
GARAGE SQ FTG
1651.00
PATIO SQ FTG
6204.00.
NUMBER OF UNITS
1.00
1ST FLOOR SQUARE FOOTAGE
8394.00
--------------------------------
2ND FLOOR SQUARE -FOOTAGE
-------------------------------
2012.00
-------------
Permit . . . BUILDING PERMIT
Additional desc .
Permit Fee . . . .
3533.50 Plan Check Fee
.' 2296.78
Issue*Date '. . . .
2/17/11 Valuation
997816
Expiration Date ,.
7/08/12
Qty. Unit Charge
Per
Extension
BASE FEE
2039.50
498.00 3.0000
--------------------------
THOU BLDG.500,001-1,000,000
------------------ - - - - -- - - -- - - - -
1494.00
- - - - - - - - - - - - - - - -
Permit . . . ELEC-NEW RESIDENTIAL
Additional desc .
Permit Fee . . . .
750.58 Plan Check Fee
187.65
Issue Date . .
2/17/11 Valuation
0
Expiration Date
7/08/12
Qty Unit Charge
Per
Extension
BASE FEE
15.00
10776.00 .0350
ELEC NEW RES -1 OR 2 FAMILY 377.16
17171.00 .0200
ELEC GARAGE OR NON-RESIDENTIAL 343.42
•1.00 15.0000
-----------------------------------------------------------------------------
EA ELEC TEMPORARY POWER POLE
15.00
Permit . .... GRADING PERMIT
Additional desc .
Permit Fee . . . .
15.00 Plan Check Fee
.00
Issue Date . . . .
2/17/11 Valuation
0
Expiration Date
7/08/12-
/08/12Qty
QtyUnit Charge
Per
Extension
----------------------------------------------------------------------------
BASE FEE
15.00
Permit .. . . . . . MECHANICAL
LQPERMIT
Application Number .
. . . 10-00001171
Permit
MECHANICAL
Additional desc .
Permit Fee-
355.50 Plan Check Fee
88.88
Issue Date . . . .
2/17/.11 Valuation
0
Expiration Date
7/08/12
Qty Unit Charge
Per
Extension
BASE FEE
15.00
9.00 9.0000
EA MECH FURNACE <=100K
81.00
1.00 4.5000
EA MECH VENT INST/ DUCT ALT
4.50
4.00 9.0000
'EA MECH B/C <=3HP/100K BTU
36:00
5.00 16.5000
EA MECH B/C >3-15HP/>100K-500KBTU
82.50
20.00 6.5000
EA MECH VENT.FAN
130.00
1.00 6.5000
EA MECH EXHAUST HOOD
6.50
Permit . . .
PLUMBING
Additional desc .
Permit Fee . . . .
385.50 Plan Check Fee
96.38
Issue Date
2/17/11 Valuation
0
Expiration Date
7/08/12
Qty Unit Charge
Per
Extension
BASE FEE
15.00
50.00 6.0000
EA PLB.FIXTURE
300.00
1.00 15.0000
EA PLB BUILDING SEWER
15.00
2.00 7.5000.
EA PLB WATER HEATER/VENT
15..00
1.00 3.0000
EA PLB WATER INST/ALT/REP
3.00.
1.00 9.0000
EA PLB LAWN SPRINKLER SYSTEM
9.00
18.00 .7500
EA PLB GAS PIPE >=5
13.50
1.00 15.0000
----------------------------------------------------------------------------
EA PLB GAS METER
15.00
Permit . .
SPECIAL INSPECTION
Additional desc
FOUNDATION INSPECTION SP.
Permit Fee
100.00 Plan Check Fee
00.
Issue Date . . .
2/24/12. Valuation . . . .
997816
Expiration Date
8/22/12
Qty Unit Charge
Per
Extension
BASE FEE.
100.00
----------------------------------------------------------------------------
Special Notes and Comments
10,776SF DWELLING/VB/RES-3/CLASS
A -FR
[ENGINEERED] THIS PERMIT DOES NOT -
INCLUDE POOL, SPA, WATER FEATURES, FIRE
PITS OR BLOCKWALLS. 2007/2008
CALIFORNIA
BUILDING CODES.
LQPERMIT
Application Number . . . . . 10-00001171
--------------------------------------
Notes and Comments
February 11, 2011 9:33:41 AM AORTEGA
PERMIT EXTENSION GRANTED ON DECEMBER
30,2011: iNSPECTION MUST BE APPROVED BY
02/13/2012.December 30, 2011 8:37:37 AM
bhanada.
STRUCTURAL REVISION APPROVED PER REVISED
PLANS. HIGHLIGHTED FOUNDATION SHEETS
SHALL BE AVAILABLE DURING INSPECTION.
ENGINEER: DANNY MATSUMOTO C33307..
February 23, 2012 11:22:52 AM bhanada.
REVISION TO RESIDENCE UNDER
CONSTRUCTION. 10,406 SF LIVING AREA.
1651 SF GARAGE W/STORAGE. 6204 SF
COVERED PATIO W/BALCONIES. AREAS REFLECT
FOUNDATION REVISION PREVIOUSLY
APPROVED.May 14, 2012 Bhanada.
----------------------------------------------------------------------------
Other Fees . . . . . . ART IN PUBLIC PLACES -RES
1994.54
BLDG STDS ADMIN (SB1473)
40.00
DIF COMMUNITY CENTERS -RES
74.00.
DIF CIVIC CENTER - RES
995:00
ENERGY REVIEW FEE
229.68
DIF FIRE PROTECTION -RES
140.00
' GRADING PLAN CHECK FEE
15.00
HOURLY PLAN CHECK
455.00
DIF LIBRARIES - RES
355.00
MULTI -SPECIES (MSHCP) FEE
1284.00
DIF PARK MAINT FAC - RES
22.00
DIF PARKS/REC - RES
892.00
STRONG MOTION (SMI) - RES
99.78
DIF STREET MAINT FAC -RES
- 67.00
DIF TRANSPORTATION.= RES
1930.00
Fee summary Charged Paid Credited
- ------- -- ---------- ----------
Due
----------------- ----------
Permit Fee Total 5140.08 5140.08 .00
.00
Plan Check -Total 2669.69 2669.'69 .00
.00
Other Fee Total 8593.00 8348.00 .00
245.00
Grand Total 16402.77 16157.77 .00
245.00
LQPERMIT
A MA 1. STA2& C,7-. � Aeh- &Izo
Bin
Permit #P.O.
� ..
B
City of >a Qu(n tQ
Building 8t Safety Division
Box 1504, 78-495 Calle Tampico
La. Quints, CA 92253 - (760) 777-7012
Building Permit Application and Tracking Sheet.
•io •� '
Project Address: `j Z 410ap
Owner's Name:
A. P. Number:
Address:
Legal Description:
Contractor�J1Nt
;City; ST, Zip:
Telephone:.:
Address:
Project Description:
City, ST, Zip:
�`� v�%�••
Telephone:
State Lie. # :
Arch., Engr., Designer:
City Lie.
Address:
City, ST, Zip:
Telephoner.
.ABaa, ,.:,�}•Construction
TYPe. Occupancy:
Project type (circle one): New Add'n Alter Repair Demo
Sq. Ft: # Stories: # Units:
State Lie. #::�
Name of Contact Person: 60AL40
Telephone # of Contact Person:"7&0
Estimated Value of Project:
APPLICANT: DO NOT WRITE BELOW THIS UNE
#
Submittal
Req'd
Recd
TRACKING PERMIT FEES
Plan Sets
Plan Check submitted afi
Amount
Structural Calcs.
Reviewed, ready focorrections Z�j Plan Check Deposit
Truss Calcs.
Called Contact Person j Check Balance •
Tide 24 Calcs.
Plans picked up ctioo
Flood plain plan
Plans resubmitted it Mechanical
Grading plan
2"" Review, ready for corr Electrical
Subcontactor List
Called Contact Person Plumbing
Grant Deed
Plans picked up S.M.I.
H.O.A. Approval
Plans resubmitted Grading
IN HOUSE:-
''' Review, ready for correctionsfissue Developer Impact Fee
Planning Approval
Called Contact Person A.I.P.P.
Pub. Wks. Appr
Date of permit issue
School Fees
Total Permit Fees
M
FEB 10 2012
�r OAIL •
Bin- #
City of La Quintal •
BufldIng &r Safety DMsion
Permit # P.O. Box 1504,79-495 Calle Tampico
U-Quinta, CA 92253 - (760) 777-7012
Building Permit Application and Tracking Sheet
jProject Address: �►'� �T11 - Owner's Name:
i A. P. Number: Address:
Legal Description: City, ST, Zip:
Contractor
Telephone: AMM
Address:poop dk14- Project Description:
City, ST, Zip: FPAJ Awl ram►
State Lie. #: City Lic. #,
Arch.; Engr., Designer:
Address:
City., ST. Zip:
Telephone: Construction Type: Occupancy:
State Lie. #: Project type (circle one): New Add'n Alter Repair Demo
Name of Contact Person• _ I.okt,.r a 4 - I Sq, Ft,: 1 # Stories: I # units:
Telephone # of Contact Person-XC fP'6Q --Esti ated V
m alue of F'rejest,
APPLICANT:
DO NOT WRITE BELOW THIS LINE
#
I Submittal Rcq'd Rt 'd
TRACMG PERMITFEES
Plan Sets
JMA Check submitted Item Amount
Structural Calm
Reviewed, ready for corrections Plan Check Deposit
Truss Calcs.
Called Contact Person Plan Check Balance
Title 24 Calcs.
Plans picked up Construction
Flood plain plan I
Plans resubmitted Mechanical
Grading plan
2`i Review, ready for correetio vsue M cal
Subcontactor List
Called Contact Person �umbing
Grant Deed
Plans picked up 'S.M.L
H.O A Approval
Plans resubmitted Grading
M HOUSE..'
'^` Review, ready for cormetlons/issue
Developer Impact Fee
Planning Approval
Called Contact Person
A.I.P.P.
Pub. Wks. Appr
Date of permit issue
School Fees
Total Permit Fees
�- aux- a1112
BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Lothenbach Residence
Lot #22, The Madison Club
La Quinta, CA 92253
Project Designer:
Design Mind Studios
75-175 Merle Drive, Suite 200
Palm Desert, Ca 92211
(760) 773-4488
Report Prepared by:
Jon Scott
Scott Design and Title 24, Inc,
77-085 Michigan Drive
Palm Desert, Ca 92211
P
(760) 200-4780 CITY OF LA QUI NTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
DATEZ; �Z BY
-T"=
Job Number:
p11
Date: FE810 �'
2/7/2012
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2012-02-07709:04:12 ID:
7
I*
IN
I TABLE OF CONTENTS I
Cover Page
Table of Contents
Form CF -1 R Certificate of Compliance
Form MF -1 R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
a
EnergyPro 5.1 by Energysoft Job Number: ID: User Number: 6712
1
2
3
17
20
27
34
41
•
•
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Lothenbach Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/7/2012
Project Address
Lot #22, The Madison Club La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
10,406
Addition
n/a
# of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity Features see Part 2 of 5 Status
Roof Wood Framed Attic R-38 6,923 Radiant Barrier New
Wall Wood Framed R-21 6,898 New
Door Opaque Door None 48 New
Slab Unheated Slab -on -Grade None 8,142 Perim = 658' New
Floor Wood Framed w/Crawl Space R-19 142 New
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades Status
Right (N) 155.7 0.330
0.38 none none Bug Screen New
Front (SE) 40.5 0.330
0.38 none none Bug Screen New
Left (S) 242.5 0.330
0.38 none none Bug Screen New
Left (S) 452.3 0.390
0.38 none none Bug Screen New
Left (S) 13.5 0.330
0.38 10.0 none Bug Screen New
Right (N) 175.2 0.390
0.38 none none Bug Screen New
Left (S) 72.0 0.510
0.38 none none Bug Screen New
Rear (W 150.0 0.510
0.38 none none Bug Screen New
Right (N) 90.0 0.510
0.38 none none Bug Screen New
Front (E) 97.5 0.330
0.38 none none Bug Screen New
Front (E) 189.0 0.330
0.38 10.0 none Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff
Cooling Min. Eff Thermostat Status
1 Split Heat Pump 8.00 HSPF
Split Heat Pump 14.0 SEER Setback
New
1 Split Heat Pump 8.00 HSPF
Split Heat Pump 14.0 SEER Setback
New
3 Split Heat Pump 8.00 HSPF
Split Heat Pump 14.0 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
HVAC 1 Ducted
Ducted Attic, Ceiling Ins, vented 8.0
New
HVAC 2 Ducted
Ducted Attic, Ceiling Ins, vented 8.0
New
HVAC 3, 5 & 5A Ducted
Ducted Attic, Ceiling Ins, vented 8.0
New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
2 Large Gas 100
0.99 All Pipes Ins New
Ene Pro 5:1 by EnergySoft User Number: 6712
RunCode: 2012-02-07709:04:12 ID:
Page 3 of 52
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Lothenbach Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
217/2012
Project Address
Lot #22, The Madison Club
La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
10,406
Addition
n/a
# of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity Features see Part 2 of 5 Status
FENESTRATION
Orientation Area
U- Exterior
Factor SHGC Overhang Sidefins Shades Status
Front (E) 108.0
0.390 0.38 10.0 none Bug Screen New
Front (E) 6.0
0.510 0.38 none none Bug Screen New
Rear (lAq 59.0
0.330 0.38 none none Bug Screen New
Rear (tq 576.0
0.510 0.38 18.0 none Bug Screen New
Rear (l9 6.0
0.390 0.38 8.0 none Bug Screen New
Right (N) 99.0
0.390 0.38 8.0 none Bug Screen New
Rear (t1) 12.5
0.390 0.38 none none Bug Screen New
HVAC SYSTEMS
Ot . Heating
Min. Eff Cooling Min. Eff Thermostat Status
1 Split Heat Pump
8.00 HSPF Split Heat Pump 14.0 SEER Setback
New
1 Split Heat Pump
8.00 HSPF Split Heat Pump 14.0 SEER Setback
New
1 Split Heat Pump
8.00 HSPF Split Heat Pump 14.0 SEER Setback
New
HVAC DISTRIBUTION Duct
Location 'Heating Cooling Duct Location R -Value Status
HVAC 6 Ducted
Ducted Attic, Ceiling Ins, vented 8.0
New
HVAC 7 Ducted
Ducted Attic, Ceiling Ins, vented 8.0
New
HVAC 4 Ducted
Ducted Attic, Ceiling Ins, vented 8.0
New
WATER HEATING
Ot . Type
Gallons Min. Eff Distribution Status
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2012-02-07To9:04:12 to:
Pa e 4 of 52
•
U
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Lothenbach Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
217/2012
Project Address
Lot #22, The Madison Club La Quinta
California Energy Climate Zone
CA Climate Zone 15
I Total Cond. Floor Area
10,406
Addition
n/a
# of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
IZI Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
'Construction Type CavityFeatures see Part 2 of 5 Status
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades Status
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
1 Split Heat Pump 8.00 HSPF Split Heat Pump 14.0 SEER Setback
New
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
HVAC 8 Ducted Ducted Attic, Ceiling Ins, vented 8.0
New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2012-02-07709:04:12 ID:
Page 5 of 52
•
•
•
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name
Lothenbach Residence
Building Type ® Single Family ❑ Addition Alone
1 ❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/712012
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
The DHW System Bradford -White #MN-1-100T6BN is a non-NAECA large storage gas water heater. Verify DHW details.
The HVAC System HVAC 1 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Verify Thermal Mass: 320.0 ft' Covered Slab Floor, 3.500" thick at Office/Hall/Stairs
HIGH MASS Design - Verify Thermal Mass: 482.0 ft' Exposed Slab Floor, 3.500" thick at Office/Hall/Stairs
HIGH MASS Design - Verify Thermal Mass: 936.0 ft' Covered Slab Floor, 3.500" thick at Master Suite
HIGH MASS Design - Verify Thermal Mass: 663.0 ft2 Exposed Slab Floor, 3.500" thick at Master Suite
The HVAC System HVAC 3, 5 & 5A must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must
have a separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Verify Thermal Mass: 386.0 ft2 Covered Slab Floor, 3.500" thick at GreatBar/Foyer/Dining/Kitchen
HIGH MASS Design - Verify Thermal Mass: 2,871.0 ft2 Exposed Slab Floor, 3.500" thick at Great/Bar/Foyer/Dining/Kitchen
The HVAC System HVAC 6 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Verify Thermal Mass: 634.0 ft' Covered Slab Floor, 3.500" thick at Game/Theater/Hall
HIGH MASS Design - Verify Thermal Mass: 934.0 ft2 Exposed Slab Floor, 3.500" thick at Game/Theater/Hall
The HVAC System HVAC 7 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
The Cooling System Carrier 25HHB448/FV4BNF048 includes credit for a 12.0 EER Condenser A certified HERS rater must field verity the installation
of the correct Condenser.
The HVAC System HVAC 1 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 1 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verity that duct
leakage meets the specified criteria.
The Cooling System Carrier 25HHB4601 FV4BNF060 includes credit for a 12.0 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System HVAC 2 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 2 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verity that duct
leakage meets the specified criteria.
The Cooling System Carrier 14 SEER/Equipment includes credit for a 12.0 EER Condenser A certified HERS rater must field verity the installation of
the correct Condenser.
The HVAC System HVAC 3, 5 & 5A incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 3, 5 & 5A incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that
duct leakage meets the specified criteria.
The Cooling System Carrier 25HHB460/ FV4BNF060 includes credit for a 12.0 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System HVAC 6 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 6 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
EnerqyPro 5.1 by Enem ySoft User Number.' 6712 RunCode: 2012-02-07709:04:12 ID: Page 6 of 52
r �
U
•
•
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name
Lothenbach Residence
Building Type ® Single Family ❑ Addition Alone
1 ❑ Multi Family ❑ Existing+ Addition/Alteration
Date
217/2012
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the s ecial 'ustification and documentation submitted.
HIGH MASS Design - Verify Thermal Mass: 707.0 ft2 Covered Slab Floor, 3.500" thick at Bedroom 1 & 2
HIGH MASS Design - Verify Thermal Mass: 209.0 ft2 Exposed Slab Floor, 3.500" thick at Bedroom 1 & 2
The HVAC System HVAC 4 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
The HVAC System HVAC 8 must serve'only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met. -
The Roof R-38 Roof(R.38.2x 14.16) includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in
Residential Appendix RA4.2.2.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -411 form for each of the measures listed below for final to be given.
The Cooling System Carrier 25HHB4361FV4BNF036 includes credit for a 12.0 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System HVAC 7 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 7 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Carrier 25HHB4301FV4BNF030 includes credit for a 12.0 EER Condenser. A certified HERS rater must field verify the installation
of the correct Condenser.
The HVAC System HVAC 4 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 4 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Carrier 25HHB4361FV4BNF036 includes credit for a 12.0 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System HVAC 8 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 8 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
EnergyPro 5.1 by EnerqySoft User Number: 6712 RunCode: 2012-02-07709:04:12 ID: Pae 7 of 52
•
•
PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF -1 R
Project Name
Building Type m Single Family ❑ Addition Alone
Date
Lothenbach Residence
❑ Multi Family ❑ Existing+ Addition/Alteration
21712012,
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV kBtu/ft2- r
Space Heating 3.52 4.44 -0.92
Space Cooling 53.35 49.71 3.64
Fans 10.61 13.85 -3.24
Domestic Hot Water 3.30 1.75 1.55
Pumps 0.00 0.00 0.00
Totals 70.78 69.75 1.03
Percent Better Than Standard: 1.4%
BUILDING COMPLIES - HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (E) 90 deg Ext. Walls/Roof Wall Area Area
Number of Dwelling Units: 1.00 (E) 1,705 441
Fuel Available at Site: Natural Gas (S) 2,747 780
Raised Floor Area: 142 (w) 2,090 804
Slab on Grade Area: 8,142 (N) 2,949 520
Average Ceiling Height: 11.1 Roof 6,923 0
Fenestration Average U -Factor: 0.41 TOTAL: 2.545
Average SHGC: 0.38 Fenestration/CFA Ratio: 24.5%
REMARKS
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
Company Scott Design and Title 24, Inc,-
Address 77-085 Michigan Drive Name Jon Scott 1�f /2012
City/State/ZiD Palm Desert, Ca 92211 Phone (760) 200-4780 Signed Date
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and
with any other calculations submitted with this permit application, and recognizes that compliance using duct design,
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company Design Mind Studios
Address 75-175 Merle Drive, Suite 200 Name Gordon Stein
City/State/Zip Palm Desert, Ca 92211 Phone (760) 773-4488 Signed Ucense # Date
EnerqvPro 5.1 by Ene Soft User Number: 6712 RunCode: 2012-02-07709:04:12 ID: Page 8 of 52
•
•
•
CERTIFICATE OF COMPLIANCE: Residential
Part 4 of 5 CF -1 R
Project Name
Lothenbach Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/712012
OPAQUE SURFACE DETAILS
Surface
Type Area
U Insulation Joint Appendix
Factor Cavity7Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Roof
274
0.026 R-38
0
20 New 4.2.1-A9 Zone 1
Wall
523
0.069 R-21
0
90 New 4.3.1-A6 Zone 1
Wall
336
0.069 R-21
135
90 New .4.3. I -A6 Zone 1
Door
24
0.500 None
135
90 New 4.5.1-A4 Zone 1
Wall
272
0.069 R-21
180
90 New 4.3.1-A6 Zone 1
Wall
60
0.069 R-21
270
90 New 4.3.1-A6 Zone 1
Slab
320
0.730 None
0
180 New 4.4.7-A1 Zone 1
Slab
482
0.730 None
0
180 New 4.4.7-A1 Zone 1
Roof
1,128
0.026 R-38
0
20 1 New 4.2.1-A9 Zone 2
Wall
643
0.069 R-21
0
90 New 4.3.1-A6 Zone 2
Wall
45
0.069 R-21
90
90 New 4.3.1-A6 Zone 2
Wall
214
0.069 R-21
180
90 New 4.3.1-A6 Zone 2
Wall
87
0.069 R-21
270
90 New 4.3.1-A6 Zone 2
Slab
936
0.730 None
0
180 New 4.4.7-A1 Zone 2
Slab
6631
0.730 None
0
180 New 4.4.7-A 1 Zone 2
Roof
3,2571
0.026 R-38
01
20 1 New 14.2.1-A9 lZone 3 8 5
FENESTRATION SURFACE DETAILS
ID
Type
Area U -Factor
SHGC
Azm Status
Glazing Type Location/Comments-
1
Window
8.0 0.330 NFRC
0.38 NFRC 0 New
Architectural Madison Club Win Zone 1
2
Window
25.0 0.330 NFRC
0.38 NFRC 0 New
Architectural Madison Club Winc Zone 1
3
Window
8.0 0.330 NFRC
0.38 NFRC 0 New
Architectural Madison Club Winc Zone 1
4
Window
8.0 0.330 NFRC
0.38 NFRC 0 New
Architectural Madison Club Winc Zone 1
5
Window
8.0 0.330 NFRC
0.38 NFRC 0 New
Architectural Madison Club Winc Zone 1
6
Window
13.5 0.330 NFRC
0.38 NFRC 135 New
Architectural Madison Club Winc Zone 1
7
Window
13.5 0.330 NFRC
0.38 NFRC 135 New
Architectural Madison Club Winc Zone 1
8
Window
13.5 0.330 NFRC
0.38 NFRC 135 New
Architectural Madison Club Wnc Zone 1
9
Window
13.5 0.330 NFRC
0.38 NFRC 180 New
Architectural Madison Club Wnc Zone 1
10
Window
9.1 0.390 NFRC
0.38 NFRC 180 New
Architectural Madison Fr Door Zone 1
11
Window
60.0 0.390 NFRC
0.38 NFRC 180 New
Architectural Madison Fr Door Zone 1
12
Window
9.1 0.390 NFRC
0.38 NFRC 180 New
Architectural Madison Fr Door Zone 1
13
Window
49.5 0.390 NFRC
0.38 NFRC 180 New
Architectural Madison Fr Door Zone 1
14
Window
49.5 0.330 NFRC
0.38 NFRC 180 New
Architectural Madison Club Winc Zone 1
15
Window
49.5 0.330 NFRC
0.38 1 NFRC 1801 New
Architectural Madison Club Winc Zone 1
16
Window
24.0 0.330 NFRC
0.38 1 NFRC 180 New
Architectural Madison Club Winc Zone 1
(1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
Hot Wd
Ove hang Left Fin Right Fin
Len Hot LExt RExt Dist Len Hot Dist Len Hot
1
Bug Screen
0.76
2
Bug Screen
0.76
3
Bug Screen
0.76
4
Bug Screen
0.76
5
Bug Screen
0.76
6
Bug Screen
0.76
7
Bug Screen
0.76
8
Bug Screen
0.76
9
Bug Screen
0.76
10
Bug Screen
0.76
11
Bug Screen
0.76
12
Bug Screen
0.76
13
Bug Screen
0.76
14
Bug Screen
0.76
15
iBug Screen
0.76
16
JBug Screen
0.76
EnemvPro
5.1 bv EnemvSoft User Number: 6712
RunCode: 2012-02-07709:04:12 ID: Page 9 of 52
r �
•
•
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Lothenbach Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/712012
OPAQUE SURFACE DETAILS
Surface
Type Area
U- Insulation Joint Appendix
Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Wall
98
0.069 R-21
0 90 New 4.3.1-A6 Zone 3 & 5
Wall
460
0.069 R-21
90 90 New 4.3.1-A6 Zone 3 & 5
Wall
57
0.069 R-21
180 90 New 4.3.1-A6 Zone 3 & 5
Wall
745
0.069 R-21
270 90 New 4.3.1-A6 Zone 3 & 5
Slab
386
0.730 None
0 180 New 4.4.7-A1 Zone 3 & 5
Slab
2871
0.730 None
0 180 New 4.4.7-A1 Zone 3 & 5
Roof
442
0.026 R-38
6 20 New 4.2.1-A9 Zone 6
Wall
215
0.069 R-21
0 90 New 4.3.1-A6 Zone 6
Wall
123
0.069 R-21
90 90 New 4.3.1-A6 Zone 6
Door
24
0.500 None
90 90 New 4.5.1-A4 Zone 6
Wall
390
0.069 R-21
180 90 New 4.3.1-A6 Zone 6
Wall
120
0.069 R-21
270 90 New 4.3.1-A6 Zone 6
Slab
634
0.730 None
0 180 New 4.4.7-A1 Zone 6
Slab
934
0.730 None
0 180 New 4.4.7-A1 lZone 6
Wall
50
0.069 R-21
0 90 New 4.3.1-A6 lZone 7
Wall
130
0.069 R-21
1 901 90 1 New 14.3.1-A6 JZone 7
FENESTRATION SURFACE DETAILS
ID
Type
Area U -Factor
SHGC
Azm Status Glazing Type Location/Comment;-
17
Window
13.5 0.330 NFRC
0.38 NFRC 180 New Architectural Madison Club Wnc Zone 1
18
Window
8.0 0.390 NFRC
0.38 NFRC 0 New Architectural Madison Fr Door Zone 2
19
Window
8.0 0.390 NFRC
0.38 NFRC 0 New Architectural Madison Fr Door Zone 2
20
Window
33.6 0.330 NFRC
0.38 NFRC 0 New Architectural Madison Club Wnc Zone 2
21
Window
8.0 0.330 NFRC
0.38 NFRC 0 New Architectural Madison Club Wnc Zone 2
22
Window
72.0 0.510 NFRC
0.38 NFRC 180 New Architectural Madison SI door Zone 2
23
Window
150.0 0.510 NFRC
0.38 NFRC 270 New Architectural Madison SI door Zone 2
24
Window
90.0 0.510 NFRC
0.38 NFRC 0 New Architectural Madison Si door Zone 3 & 5
25
Window
19.5 0.330 NFRC
0.38 NFRC 90 New Architectural Madison Club Wnc Zone 3 & 5
26
Window
19.5 0.330 NFRC
0.38 NFRC 90 New Architectural Madison Club Wnc Zone 3 & 5
27
Window
189.0 0.330 NFRC
0.38 NFRC 90 New Architectural Madison Club Wnc Zone 3 & 5
28
Window
108.0 0.390 NFRC
0.38 NFRC 90 New Architectural Madison Fr Door Zone 3 & 5
29
Window
6.0 0.330 NFRC
0.38 NFRC 90 New Architectural Madison Club Win Zone 3 & 5
30
Window
6.0 0.510 NFRC
0.38 NFRC 90 New Architectural Madison SI door Zone 3 & 5
31
Window
6.0 0.330 NFRC
0.38 NFRC 90 New Architectural Madison Club Winc Zone 3 & 5
32
Window
6.0 0.330 NFRC
0.38 NFRC 90 New Architectural Madison Club Wnc Zone 3 & 5
(1) Ll -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
H t Wd
Ove hang Left Fin Right Fin
Len H t LExt RExt Dist Len I Hot Dist Len Hat
17
Bug Screen
0.76
3.5 4.0 10.0 0.1 10.0 10.0
18
Bug Screen
0.76
19
Bug Screen
0.76
20
Bug Screen
0.76
21
Bug Screen
0.76
22
Bug Screen
0.76
23
Bug Screen
0.76
24
Bug Screen
0.76
25
Bug Screen
0.76
26
Buo Screen
0.76
27
Bug Screen
0.76
13.5 14.0 10.0 0.1 10.0 10.0
28
Bug Screen
0.76
12.0 9.0 10.0 0.1 10.0 10.0
29
Bug Screen
0.76
30
Bug Screen
0.76
31
JBug Screen
0.76
32
JBug Screen
0.76
EnergyPro,
5.1 by EnemvSoft User Number: 6712
RunCode: 2012-02-07709:04:12 ID: Pae 10 of 52
•
•
. . t
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Lothenbach Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2!712012
OPAQUE SURFACE DETAILS
Surface-
Type Area
U- Insulation
Factor Cavity Exterior Frame Interior Frame Azm
Joint Appendix
Tilt Status 4 Location/Comments
Wall
127
0.069 R-21
180
90 New 4.3.1-A6 Zone 7
Slab
707
0.730 None
0
180 New 4.4.7-A 1 Zone 7
Slab
209
0.730 None
0
180 New 4.4.7-A1 Zone 7
Roof
700
0.026 R-38
0
20 New 4.2.1-A9 Zone 4
Wall
349
0.069 R-21
0
90 New 4.3.1-A6 Zone 4
Wall
350
0.069 R-21
.180,
90 New 4.3.1-A6 Zone 4
Wall
125
0.069 R-21
270
90 New 4.3.1-A6 Zone 4
Floor
142
0.037 R-19
0
180 New 4.4.1-A4 Zone 4
Roof
1,122
0.026 R-38
0
20 New 4.2.1-A9 Zone 8
Wall
550
0.069 R-21
0
90 1 New 4.3.1-A6 Zone 8
Wall
123
0.069 R-21
901
90 New ' 4.3.1-A6 Zone 8
Wall
556
0.069 R-21
180
90 New 4.3.1-A6 Zone 8
Wall
150
0.069 R-21
270
90 New 4.3.1-A6 Zone 8
FENESTRATION SURFACE DETAILS
ID
Type
Area U -Factor
SHGC
Azm Status
Glazing Type -+ Location/Comments
33
Window
24.0 0.330 NFRC
0.38 NFRC 180 New
Architectural Madison Club Winc Zone 3 & 5
34
Window
10.0 0.330 NFRC
0.38 NFRC 270 New
Architectural Madison Club Winc Zone 3 & 5
35
Window
12.5 0.330 NFRC
0.38 NFRC 270 New
Architectural Madison Club Winc Zone 3 & 5
36
Window
576.0 0.510 NFRC
0.38 NFRC 270 New
Architectural Madison Sl door Zone 3 & 5
•37
Window
6.0 0.330 NFRC
0.36 NFRC 270 New
Architectural Madison Club Wnc Zone 3 & 5
38
Window
6.0 0.330 NFRC
0.38 NFRC 270 New
Architectural Madison Club Wnc Zone 3 & 5
39
Window
6.0 0.330 NFRC
0.38 NFRC 270 New
Architectural Madison Club Wnc Zone 3 & 5
40
Window
6.0 0.330 NFRC
0.38 NFRC 270 New
Architectural Madison Club Wnc Zone 3 & 5
41
Window
6.0 0.390 NFRC
0.38 NFRC 270 New
Architectural Madison Fr Door Zone 3 & 5
42
Window
49.5 0.390 NFRC
0.38 NFRC 0 New
Architectural Madison Fr Door Zone 6
43
Window
49.5 0.390 NFRC
0.38 NFRC 0 New
Architectural Madison Fr Door Zone 6
44
Window
9.1 0.390 NFRC
0.38 NFRC 0 New
Architectural Madison Fr Door Zone 6
45
Window
24.0 0.390 NFRC
0.38 NFRC 0 New
Architectural Madison Fr Door Zone 6
46
Window
9.1 0.330 NFRC
0.38 NFRC 0 New
Architectural Madison Club Wnc Zone 6
47
Window
13.5 0.390 NFRC
0.38 NFRC 0 New
Architectural Madison Fr Door 1Zone6 .
48
Window
13.5 0.330 NFRC
0.38 1 NFRC 90 New
Architectural Madison Club WM4 Zone 6
(1) Ll -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
H t Wd
Ove hanq Left Fin Right Fin
Len 'H t LExt RExt Dist Len I H t Dist Len H t
33
Bug Screen
0.76
34
Bug Screen
0.76
35
Bug Screen
0.76
36
Bug Screen
0.76
12.0 48.0 18.0 0.1 18.0 18.0
37
Bug Screen
0.76
38
Bug Screen
0.76
39
Bug Screen
0.76
40
Bug Screen
0.76
41
Bug Screen
0.76
8.0 6.0 8.0 0.1
8.0 8.0
42
Bug Screen
0.76
9.0 5.5 8.0 0.1
8.0 8.0
43
Bug Screen
0.76
9.0 5.5 8.0 0.1
8.0 .- 8.0
44
Bug Screen
0.76
45
Bug Screen
0.76
46
Bug Screen
0.761
1
47
IBug Screen
1 0.761
1
48
[Bug Screen
1 0.76
1-
EnergyPro
5.1 by EnemySoft User Number: 6712
RunCode: 2012-02-07709:04:12 ID: Pae 11 of 52
•
•
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Lothenbach Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/712012
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor CavityTExterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID
Type Area
U -Factor
SHGC
Azm Status Glazing Type Location/Comments
49
Window 8.0
0.330 NFRC
0.38 NFRC 180 New Architectural Madison Club Wnc Zone 7
50
Window 8.0
0.330 NFRC
0.38 NFRC 180 New Architectural Madison Club Wnc Zone 7
51
Window 13.6
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
52
Window 42.4
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
53
Window 13.6
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
54
Window 13.6
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
55
Window 42.4
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
56
Window 13.6
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
57
Window 13.6
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
58
Window 42.6
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
59
Window 13.6
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
60
Window 8.0
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 7
61
Window 8.0
0.390 NFRC
0.38 NFRC 180 New I Architectural Madison Fr Door Zone 7
62
Window 12.0
0.390 NFRC
0.38 NFRC 1801 New I Architectural Madison Fr Door Zone 7
63
Window 8.0
0.330 NFRC
0.38 NFRC 0 New I Architectural Madison Club Wnc Zone 4
64
Window 8.0
0.330 NFRC
0.38 NFRC 0 New I Architectural Madison Club Wnc Zone 4
(1) Ll -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
Hot I Wd
Ove hang Left Fin Right Fin
Len H t LExt RExt Dist Len H t Dist Len H t
49
Bug Screen
0.76
50
Bug Screen
0.76
51
Bug Screen
0.76
52
Bug Screen
0.76
53
Bug Screen
0.76
54
Bug Screen
0.76
55
Bug Screen
0.76
56
Bug Screen
0.76
57
Bug Screen
0.76
58
Bua Screen
0.76
59
Bug Screen
0.76
60
Bug Screen
0.76
61
Bug Screen
0.76
62
Bug Screen
0.76
63
JBug Screen
0.76
64
JBug Screen
0.76
EnerqyPro
5.1 by EnergySoft
User Number: 6712
RunCode: 2012-02-07709:04:12 ID: Pae 12 of 52
•
•
•
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Lothenbach Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/712012
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID
Type Area
U -Factor
SHGCz
Azm Status Glazing Type Location/Comments
65
Window 8.0
0.330 NFRC
0.38 NFRC 0 New Architectural Madison Club Win Zone 4
66
Window 8.0
0.330 NFRC
0.38 NFRC 0 New Architectural Madison Club Win Zone 4
67
Window 8.0
0.330 NFRC
0.38 NFRC 0 New Architectural Madison Club Win Zone 4
68
Window 8.0
0.330 NFRC
0.38 NFRC 0 New Architectural Madison Club Win Zone 4
69
Window 8.0
0.390 NFRC
0.38 NFRC 0 New Architectural Madison Fr Door Zone 4
70
Window 12.5
0.390 NFRC
0.38 NFRC 0 New Architectural Madison Fr Door Zone 4
71
Window 12.5
0.390 NFRC
0.38 NFRC 0 New Architeciural Madison Fr Door Zone 4
72
Window 39.8
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 4
73
Window 39.8
0.390 NFRC
0.38 NFRC 180 New Architectural Madison Fr Door Zone 4
74
Window 12.5
0.330 NFRC
0.38 NFRC 270 New Architectural Madison Club Win Zone 4
75
Window 12.5
0.390 NFRC
0.38 NFRC 270 New Architectural Madison Fr Door Zone 4
76
Window 39.8
0.390 NFRC
0.38 NFRC 0 New Architectural Madison Fr Door Zone 8
77
Window 39.8
0.390 NFRC
0.38 NFRC 0 New Architectural Madison Fr Door Zone 8
78
Window 13.5
0.330 NFRC
0.38 NFRC 90 New Architectural Madison Club Wric Zone 8
79
Window 13.5
0.330 NFRC
0.38 NFRC 90 New Architectural Madison Club Wric Zone 8
80
Window 8.0
0.330 NFRC
0.38 NFRC 180 New Architectural Madison Club Win Zone 8
(1) Ll -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-13 = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
Hat I Wd
Ove hang Left Fin Right Fin
Len H t LExt RExt Dist Len I Hat Dist Len Hat
65
Bug Screen
0.76
66
Bug Screen
0.76
67
Bug Screen
0.76
68
Bug Screen
0.76
69
Bug Screen
0.76
70
Bug Screen
0.76
71
Bug Screen
0.76
72
Bug Screen
0.76
73
Bug Screen
0.76
74
Bug Screen
0.76
75
Bug Screen
0.76
76
Buj Screen
0.76
77
Bug Screen
0.76
78
Bug Screen
0.76
79
Bug Screen
0.76
80
JBug Screen
0.76
EnergyPro
5.1 by EnergySoft
User Number.- 6712
RunCode: 2012-02-07709:04:12 ID: Pae 13 of 52
•
•
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Lothenbach Residence
Building Type m Single Family O Addition Alone
o Multi Family O Existing+ Addition/Alteration
Date
121712012
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID Type Area U -Factor SHGC
Azm Status Glazing Type Location/Comments
81 Window 12.5 0.330 1 NFRC 0.38 NFRC 180 New Architectural Madison Club WinZone 8
82 Window 12.5 0.330 NFRC 0.38 NFRC 180 New Architectural Madison Club Win Zone 8
83 Window 8.0 0.330 NFRC 0.38 NFRC 180 New Architectural Madison Club Win Zone 8
84 Window 12.5 0.330 NFRC 0.38 NFRC 180 New Architectural Madison Club Win Zone 8
85 Window 12.5 0.330 NFRC 0.38 NFRC 180 New Architectural Madison Club Win Zone 8
86 Window 8.0 0.390 NFRC 0.38 NFRC 180 New Architectural Madison Fr Door Zone 8
(1) Ll -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
Window
ID Exterior Shade Type SHGC H t I Wd
Ove hanq Left Fin Right Fin
Len H t LExt RExt Dist Len H t Dist Len H t
81 Bug Screen 0.76
82 Bug Screen 0.76
83 Bug Screen 0.76
84 Bug Screen 0.76
85 Bug Screen 0.76
86 Bug Screen 0.76
EnergyPro 5.1 by EnergySoft User Number: 6712
RunCode: 2012-02-07709:04:12 ID: Pae 14 of 52
•
•
0
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5
CF -1 R
Project Name
Lothenbach Residence
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/712012
BUILDING ZONE INFORMATION
System Name
Zone Name
Floor Area
New Existino I Altered Removed Volume
Year Built
HVAC 1 OfFcelHall/Stairs
1,241
14,892
HVAC 2 Master Suite
1,599
17,269
HVAC 3, 5 & 5A Great/Bar/Foyer/Dining/Kitchen 3,257
39,735
HVAC 6 Game/Theater/Hall
1,571
15,710
HVAC 7 Bedroom 1 & 2
916
91160
HVAC 4 2nd Floor North
700.
7,000
HVAC 8 2nd Floor South
1,122
11,220
Totals 1 10,4061 0 0 0
HVAC SYSTEMS
System Name Qty. Heating Type_
Min. Eff. Cooling Type Min. Eff. Thermostat Type
Status
HVAC 1
1 Split Heat Pump
8.00 HSPF Split Heat Pump 14.0 SEER Setback
New
HVAC 2
1 Split Heat Pump
8.00 HSPF Split Heat Pump 14.0 SEER Setback
New
HVAC 3, 5 & 5A
3 S lit Heat Pump
8.00 HSPF Split Heat Pump 14.0 SEER Setback
New
HVAC 6
1 Split Heat Pump
8.00 HSPF splitHeatPurnp 14.0 SEER Setback
New
HVAC 7
1 Split Heat Pump 18.00
HSPF I Split Heat Pump 114.0 SEER I Setback
New
HVAC DISTRIBUTION
System Name
Heating
Duct
Cooling Duct Location R -Value -
Ducts
Tested? Status
HVAC 1 Ducted Ducted Attic, Ceiling Ins, vented 8.0
m
New
HVAC 2 Ducted Ducted Attic, Ceiling Ins, vented 8.0
m
New
HVAC 3, 5 & 5A Ducted Ducted Attic, Ceiling Ins, vented 8.0
El
New
HVAC 6 1 Ducted I Ducted I Attic, Ceiling Ins, vented 8.0
INew
HVAC 7 1 Ducted I Ducted JAttic, Ceiling Ins, vented 8.0
m
New
WATER HEATING SYSTEMS
S stem Name
Oty.
Type
Distribution
Rated
Input
(Btu h)
Tank
Cap.
al
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
Bradford -White #MN -1-100
2
Large Gas
All Pipes Ins
85,000
100
0.99
0.00%
0.0
New
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
Control
Hot Water Piping Length
ff
c
z o
m
N
a
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
Oty. HP
Plenum Outside Buried
EnergyPro 5.1 by EnergySoft
User Number: 6712
RunCode: 2012-02-07709:04:12 ID:
Pae 15 of 52
•
U
0
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5
CF -1 R
Project Name
Lothenbach Residence
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/7/2012
BUILDING ZONE INFORMATION
System Name Zone Name
Floor Area
New Existing Altered Removed Volume
Year Built
Totals 10,4061 01 01 0
HVAC SYSTEMS
System Name QtY. Heating Type
Min. Eff. Cooling Type Min. Eff. Thermostat Type
Status
HVAC 4 1 Split Heat Pump
8.00 HSPF Split Heat Pump 14.0 SEER Setback
New
HVAC 8 1 Split Heat Pump
8.00 HSPF Split Heat Pump 14.0 SEER Setback
New
HVAC DISTRIBUTION
System Name Heating
Duct
Cooling Duct Location R -Value
Ducts
Tested? Status
HVAC 4 Ducted Ducted Attic, Ceiling Ins, vented 8.0
m
New
HVAC 8 Ducted Ducted Attic, Ceiling Ins, vented 8.0
m
New
❑
WATER HEATING SYSTEMS
S stem Name
O
T e
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy Standby
Factor Loss or
or RE Pilot
Ext.
Tank
Insul. R-
Value
Status
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
Control
Hot Water Piping Length
(ft)c
N
a
System Name
Pipe
Len th
Pipe
Diameter
Insul.
Thick.
Oty. HP
Plenum Outside Buried
❑
EnergyPro 5.1 by EnemvSoft User Number: 6712
RunCode: 2012-02-07709:04:12 ID:
Pae 16 of 52
r:
•
•
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R
Project Name
Lothenbach Residence
Date
1 217/2012
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
116(a)1: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form.
§118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§150(a): Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor.
§150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
*§150(c): Minimum R-13 insulation in wood -frame wall orequivalent U -factor.
*§150(d): Minimum R-13 insulation in raised wood -frame floor orequivalent LI -factor.
§150(f): Air retarding wrap is tested labeled and installed according to ASTM E1677-95(2000) when specified on the CF -1 R Form.
§150(g): Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor•permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 e 1 A: M asonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
§150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
§150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§150(j)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§1500)113: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have' R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
§1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculating sections of hot water pipes are insulated per Standards Table 150-13.
§1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot
water tank shall be insulated to Table 150-B and Equation 150-A.
§1500)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
123-A.
§150(')3A: Insulation is protected from dama a including that due to sunlight, moisture equipment maintenance and wind.
§1500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
150(j)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
EnergyPro5.1 by EnergySoR User Number: 6712 RunCode: 2012-02-07709:04:12 ID: Page 17 of 52
•
•
C
MANDATORY MEASURES SUMMARY: Residential Pae 2 of 3 MF -1 R
Project Name
Date
Lothenbach Residence
1 2/7/2012
§150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150(m)7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150 m 10: Flexible ducts cannot have porous inner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
required in Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
§150(p): Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of 150
Residential Lighting Measures:
§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low eff icacy luminaire asspecified by §150(k)2.
§150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage, lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k).
150(k)7: All switching devices and controls shall meet the requirements of §150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet,. and utility rooms are high efficacy and controlled by a
manual -on occupant sensor.
§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
EnergyPro5.1 by EnergySoft User Number: 6712 RunCode: 2012-02-07709:04:12 ID: Page 18 of 52
C._ J
r�
0
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
Lothenbach Residence
1 277/2012
§150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)l1: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with §150 k 11.
§150(k)l2: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)l3: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptionl to §150(k)l3 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)l4: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)l5: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130, 131, 134, and 146.
§150(k)l6: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2012-02-07709:04:12 ID: Page 19 of 52
•
•
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lothenbach Residence
Date
2/7/2012
System Name
HVAC 1
Floor Area
1,241
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING PEAK
CFM Sensible
Total Room Loads 887 17,603
Return Vented Lighting 6
Return Air Ducts 829
Return Fan 01
Ventilation o 0
Supply Fan 0
Supply Air Ducts 829
TOTAL SYSTEM LOAD 1 19,262
COIL HTG.
Latent CFM
2,946 1,161
0 0
2,946
PEAK
Heating System
Sensible
Output per System 47,500
20,616
Total Output Btuh 47,500
Output Btuh/s ft 38.3
624
Cooling System
0
Output per System 47,5001
0
Total Output Btuh 47,500
0
Total Output ons 4.0
624
Total Output Btuh/s ft 38.3
Total Output s ft/Ton 313.5
1 21,864
Air System
CFM per System
1,600
HVAC EQUIPMENT SELECTION
Airflow cfm
1,600
Carrier 25HHB448/FV4BNF048 33,426
4,698
29,667
Airflow cfm/s ft
1.29
Airflow cfm/Ton
404.2
Outside Air %
0.0%
Total Adjusted System Output 1 33,426
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
4,698 1 29,667
Aug 3 PM Jan 1 AM
Outside Alr cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
72 OF
72 OF 89 OF 89 OF
fC+7 r+ G
Heating Coil Supply Fan 89 OF
1,600 cfm
ROOM ",-",m
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
70 / 58 OF
70/59°F 51/50°F 51/50°F
_ ra.)
Cooling Coil Supply Fan
1,600 cfm
49.7%
51 / 50 OF
ROOM MW
70 ! 58 OF
EnergyPro 5.1 by EnergySoft
User Number.' 6712 RunCode: 2012-02-07709:04:12 ID:
Page 20 of 52
0
1�
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lothenbach Residence
Date
2/7/2012
System Name
HVAC 2
Floor Area
1,599
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING
CFM Sensible
Total Room Loads 1,255 20,814
Return Vented Lighting 0
Return Air Ducts 981
Return Fan 0
Ventilation 0 0
Supply Fan 2,978
Supply Air Ducts 981
TOTAL SYSTEM LOAD 1 25,753
PEAK COIL HTG.
PEAK
Heating System
Latent I CFM
Sensible
Output perSystem 58,500
3,565 1,055
20,207
Total Output Btuh 58,500
Output Btuh/ ft 36.6
612
Cooling System
0
Output perSystem 57,500
0 0
0
Total Output Btuh 57,500
3,565
-2,978
Total Output ons 4.8
612
Total Output Btuh/s ft 36.0
Total Output s ft/Ton 333.7
18,452
Air System
CFM perSystem
2,000
HVAC EOUIPMENT SELECTION
Airflow cfm
2,000
Carrier 25HHB460/ FV4BNF060 38,112
8,653
36,538
Airflow cfm/s ft
1.25
Total Adjusted System Output 38,112
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
8,653 36,538
Aug 3P MJan 1 AM
Airflow cfm/Ton 417.4
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
72 OF
72 OF 89 OF 90 OF
Heating Coil Supply Fan g0 °F
2,000 cfm
[ROOM J1
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air Arc
0 cfm
70 / 59 OF
70/59°F 53/52°F 54/52°F
i�
Cooling Coil Supply Fan 54 / 52 OF
2,000 cfm_........ ........ .... ............
53.1 % ROOM
70 / 59 OF
Energy 5.1 by EnergySoff
User Number: 6712 RunCode: 2012-02-07T09:04:12 /D:
Page 21 of 52
0
1�
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lothenbach Residence
Date
2/7/2012
System Name
HVAC 3, 5 & 5A
Floor Area
3,257
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
3
COIL COOLING PEAK
CFM Sensible
Total Room Loads 2,505 50,825
Return Vented Lighting 0
Return Air Ducts 2,395
Return Fan 0
Ventilation 0 0
Supply Fan 0
Supply Air Ducts 2,395
TOTAL SYSTEM LOAD 55,615
COIL HTG.
Latent I CFM
6,4331 2,761
0 0
6,433
PEAK
Heating System
Sensible
Output per System 47,500
49,476
Total Output Btuh 142,500
Output Btuh/s ft 43.8
1,498
Cooling System
0
Output per System 47,500
0
Total Output Btuh 142,500
0
Total Output ons 11.9
1,498
Total Output Btuh/s ft 43.8
Total Output s ft/Ton 274.3
52,471
Air System
CFM per System
1,600
HVAC EQUIPMENT SELECTION
Airflow cfm
4,800
Carrier 14 SEER/Equipment 102,180
Total Adjusted System Output 102,180
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
11,498 89,002
11,498 89;002
Aug 3P ml Jan 1 AM
Airflow cfm/s ft 1.47
Airflow cfm/Ton 404.2
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
10�0-
Outside Air
0 cfm
72 OF
72 OF 89 OF 89 OF
i;
Heating Coil Supply Fan 89 OF
4,800 cfm _
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside AirAr
0 cfm
70158 OF
70/58°F 50/50°F 50/50°F
c
Cooling Coil Supply Fan
4,800 cfm 48.2%
51 / 50 OF
�......�.,.,.�........_.........................
�'(
� OOM
70 ! 58 OF
PE,—e;7y—P,o5 I by EnergySoR
User Number: 6712 RunCode: 2012-02-07709:04:12 ID:
Page 22 of 52
FJ
•
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lothenbach Residence
Date
2/7/2012
System Name
HVAC 6
Floor Area
1,571
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING PEAK
CFM Sensible
Total Room Loads 828 13,977
Return Vented Lighting 0
Return Air Ducts 659
Return Fan 0
Ventilation 0 0
Supply Fan 2,978
Supply Air Ducts 659
TOTAL SYSTEM LOAD 1 18,272
COIL HTG.
Latent CFM
3,517 819
0 0
3,517
PEAK
Heating S ystem
Sensible
Output per System 58,500
15,783
Total Output Btuh 58,500
Output Btuh/s ft 37.2
478
Cooling System
0
Output per System 57,500
0
Total Output Btuh 57,500
-2,978
Total Output ons 4.8
478
Total Output Btuh/s ft 36.6
Total Output s ft/Ton 327.9
13,760
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 25HHB460/ FV4BNF060 38,075
8,599
36,538
Airflow cfm/s ft
1.27
Total Adjusted System Output 38,075
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
8,599 36,538
Aug 3P M1 F Jan 1 AM
Airflowcfmfron 417.4
Outside Air % 0.0%
Outside Air cfm/ ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
72 OF
4 pop -
72 OF 89 OF 90 °F
Heating Coil Supply Fan 90 OF
2,000 cfm
ROOM In
72 OF
14
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112 / 78 OF
Outside Air Ar
0 cfm
70 / 59 OF
70 / 59 OF 52 / 52 OF 54 / 52 OF
Cooling Coil Supply Fan
2,000 cfm
52.8%
54 / 52 OF
..._.
ROOM
70/ 59 OF
EnergyPro 5.1 by EnergySoft
User Number: 6712 RunCode: 2012-02-07709:04:12 ID:
Page 23 of 52
•
•
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lothenbach Residence
Date
2/7/2012
System Name
HVAC 7
Floor Area
916
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING PEAK
CFM Sensible
Total Room Loads 752 14,620
Return Vented Lighting 0
Return Air Ducts 689
Return Fan 01
Ventilation E 0 0
Supply Fan 0
Supply Air Ducts 689
TOTAL SYSTEM LOAD 1 15,9971
COIL HTG.
Latent CFM
2,384 589
0 0
2,3841
PEAK
Heating System
Sensible
Output per System 35,500
10,574
Total Output Btuh 35,500
Output Btuh/ ft 38.8
320
Cooling System
0
Output per System 35,5001
0
Total Output Btuh 35,500
0
Total Output ons 3.0
320
Total Output Btuh/s ft 38.8
Total Output s ft/Ton 309.6
1 11,214
Air System
CFM per System
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Carrier 25HHB436/FV4BNF036 24,693
3,910
22,172
1 22,172
Jan 1 AM
Airflow cfm/s ft 1.31
Airflow cfm/Ton 405.6
Outside Air % 0.0%
Total Adjusted System Output 1 24,693
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
3,910
Aug 3P M
Outside Air (cfm/ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air Ar
0 cfm
72 OF
72 OF 69 °F 89 °F
-
10 N
WA
Heating Coil Supply Fan 89 OF
1,200 cfm
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
71 /59°F
71/59°F 51/50°F 51/50°F
Cooling Coil Supply Fan
1,200 cfm
50.6 %
52 / 51 OF
.................. .... ,
ROOM
70/59°F
EnergyPro5.1 by EnergySoR
User Number., 6712 RunCode: 2012-02-07709:04:12 ID:
Page 24 of 52
0
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lothenbach Residence
Pate
2/7/2012
System Name
HVAC 4
Floor Area
700
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING PEAK
CFM Sensible
Total Room Loads 1,482 14,869
Return Vented Lighting 0
Return Air Ducts 701
Return Fan 0
Ventilation 0 0
Supply Fan 0
Supply Air Ducts 701
TOTAL SYSTEM LOAD 1 16,2701
COIL HTG.
LatentCFM
2,011 626
0 0
2.0111
PEAK
Heating System
Sensible
Output erSys tem 29,500
9,322
Total Output Btuh 29,500
Output Btuh/s ft 42.1
282
Cooling System
0
Output perSystem 29,600
0
Total Output Btuh 29,600
0
Total Output ons 2.5
282
Total Output Btuh/s ft 42.3
Total Output s ft/Ton 283.8
1 9,887
Air System
CFM perSystem
1,200
HVAC EQUIPMENT SELECTION
Airflow (cfm)
1,200
Carrier 25HHB430/FV4BNF030 13,439
Total Adjusted System Output 1 13,439
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
12,367 18,425
12,367 1 18,425
Aug 3 PM Jan 1 AM
Airflow cfm/s ft 1.71
Airflow cfm/Ton 486.5
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of. Heating Peak
26 OF
Outside Air
0 cfm
72 OF
72 OF 86 OF 86 OF
Heating Coil Supply Fan 86 OF
1,200 ch
""-.M
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112178 OF
Outside Air
Ar 0 Cfrrr
71 / 64 OF
71 / 64 OF 60 / 60 OF 60 / 60 OF
Cooling Coil Supply Fan
1,200 cfm
70.7%
3
61 160 °F
II ROOM
70 ! 64 OF
EnergyPro 5.1 by EnergySoff
User Number: 6712 RunCode: 2012-02-07709:04:12 ID:
Page 25 of 52
•
C
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lothenbach Residence
Date
2/7/2012
System Name
HVAC 8
Floor Area
1,122
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING PEAK
CFM Sensible
Total Room Loads 759 14,578
Return Vented Lighting 0
Return Air Ducts 687
Return Fan 01
Ventilation 0 0
Supply Fan 0
Supply Air Ducts 687
TOTAL SYSTEM LOAD 1 15,952
COIL HTG.
Latent CFM
2,7401 709
0 0
2.7401
PEAK
Heating System
Sensible
Output per System 35,500
12,653
Total Output Btuh 35,500
Output Btuh/s ft 31.6
383
Cooling System
0
Output per System 35,500
0
Total Output Btuh 35,500
0
Total "Out ut ons 3.0
383
Total Output Btuh/s ft 31.6
Total Output s ft/Ton 379.3
1 13,419
Air System
CFM per System
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Carrier 25HHB436/FV4BNF036 24,410
4,292
22,172
Airflow cfm/s ft 1.07
Airflow cfm/Ton
405.6
22,172
Jan 1 AM
Outside Air°/, 0.0%
Total Adjusted System Output 24,410
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
4,292
Aug 3P ml
Outside Alr cfm/s ft 0.00
Note: values above given at ARI conditions I
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
0
Outside Air Ar-
0 cfm
72 OF
72 OF 89 °F89 OF
LA ^^
WA
Heating Coil Supply Fan 89 OF
1,200 cfm
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air Ar
0 cfm
71 159 OF
71/59°F 51/51°F 51/51°F
Cooling Coil Supply Fan
1,200 cfm
51.5%
52 / 51 OF
_._.........„�.
ROOM
70 / 59 OF
EnergyPro 5.1 by EnergySoft
User Number.' 6712 RunCode: 2012-02-07T09:04:12 ID:
Page 26 of 52
9
•
•
ROOM LOAD SUMMARY
Project Name Date
Lothenbach Residence 2/7/2012
HVAC 1 1 1,241
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name I Room Name Mult. I CFM Sensible Latent CFM I Sensible Latent CFM I Sensible
Zone 1 I Office/Hall/Stairs 1 1 8871 17,6031 2,946 8871 17,6031 2,946 1,1611 20,616
PAGE TOTAL
TOTAL'
887
17,603
2,946
1,161
20,616
887
17,603
2,946
1,161
20,616
EN
•
r
•
ROOM LOAD SUMMARY
Project Name Date
Lothenbach Residence 2/7/2012
System Name Floor Area
HVAC 2 1,599
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name Room Name Mult. I CFM TSensible I Latent CFM I Sensible Latent CFM I Sensible
Zone 1 Master Suite I 1 1 12-551 20,8141 3,565 1,2551 20,8141 3,5651 1,0551 20,207
PAGE TOTAL
TOTAL"
1,255
20,814
3,565
1,055
20,207
1,255
20,8141
3, 565
1,055
20,207
0
•
is
•
ROOM LOAD SUMMARY
Project Name Date
Lothenbach Residence 2/7/2012
System Name Floor Area
HVAC 3, 5 & 5A 3,257
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name I Room Name I 4''Z5051
FM Sensible Latent CFM Sensible Latent CFM Sensible
Zone 3 & 5 Great0arlFoyer/DininglJo 50,8251 6,433 Z5051 50,825 6,433 2,7 . 611 49,476
Total includes ventilation load for
PAGE TOTAL
TOTAL '
2,505
50,8251
6,433
2,7611
49,476
2,505
50,8251
6,433
2,7611
49,476
•
•
•
ROOM LOAD SUMMARY
Project Name Date
Lothenbach Residence 2/7/2012
System Name Floor Area
HVAC 6 1,571
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible Latent CFM Sensible Latent I CFM Sensible
Zone 6 Game/TheaterlHall 1 1 8281 13,9771 3,517 8281 13,9771 3,5171 81,91 15,783
PAGE TOTAL
TOTAL'
828
13,9771
3,5171
819 15,783
828
13,9771
3,5171
819 15, 783
Total includes ventilation load for zonal systems.
EnemyPro 5.1 by Enem
ySoft User Number: 6712 RunCode: 2012-02-07709:04:12 ID: Page 30 of 52
7
•
ROOM LOAD SUMMARY
Project Name Date
Lothenbach Residence 2/7/2012
System Name Floor Area
HVAC 7 916
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible Latent CFM Sensible I Latent I CFM I Sensible
Zone 7 Bedroom 1 & 2 1 1 1 7521 14,6201 2, 384 752 . 14,6201 2,3841 5891 10,574
• ' Total includes ventilation load for
EnerovPro 5.1 by EnerovSoR L
PAGE TOTAL
TOTAL*
>012-02-07709:04:12
752 14,620
2,384
589
10,574
7.521 14,620
2,384
589
10,574
•
0
I ROOM LOAD SUMMARY
Lothenbach Residence
2/7/2012
HVAC 4 1 700
ROOM LOAD SUMMARY
Zone Name I Room Name I Mult. I CFM I Sensible I Latent I CFM I Sensible I Latent I CFM I Sensible
Zone 4 12nd Floor North 1 1 1,4821 14,8691 2,011 1 1,4821 14,8691 Z0111 6261 9,322
PAGE TOTAL
TOTAL'
1,482 14,869
2011
626
9,322
1,482 14,869
2,011
626
9,322
•
•
•
ROOM LOAD SUMMARY
Project Name Date
Lothenbach Residence 2/7/2012
System Name Floor Area
HVAC 8 1,122
ROOM LOAD SUMMARY
Zone Name I Room Name I Mult. I CFM I Sensible I Latent I CFM I Sensible I Latent I CFM I Sensible
Zone 8 2nd Floor South 1 759 14,578 2,740 759 14,578 2,740 709 12,653
PAGE TOTAL
TOTAL•
759
14,5781
2,740
709 12,653
759
14,5781
2,7401
7091 1Z6
Total includes ventilation load for zonal systems.
EnemyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2012-02-07709:04:12 ID: Page 33 of 52
C]
•
•
ROOM HEATING PEAK LOADS
Project Name
Date
Lothenbach Residence
2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name OfficeMall/Stairs
Time of Peak
Jan 1 AM
Floor Area 1,241.0 ft'
Outdoor Dry Bulb Temperature
26 OF
Indoor Dry Bulb Temperature 72 OF
Conduction Area
U -Value
AT OF
Btu/hr
R-38 Roof(R. 38.2x 14.16) 274.0
X
0.0260 X
46
c
328
R-21 Wall (W. 19.2x6.16) 1,190.8
X
0.0690 X
46
c
3,780
Architectural Madison Club Windows 247.5
X
0.3300 X
46
=
3,757
Wood Door 24.0
X
0.5000 X
46
c
552
Architectural Madison Fr Door 127.7
X
0.3900 X
46
c
2,291
Slab -On -Grade perim = 165.0
X
0.7300 X
46
=
5,541
X
X
=
X
X
=
X
X
X
X
X
X
X
X
X
X
=
X
X
X
X
X
X
X
X
=
X
X
X
X
X
X
X
X
X
X
X
X
X
X
=
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Items shown with an asterisk (') denote conduction through an interior surface to another room
Page Total
16,248
Infiltration:[ 1.00 )( 1.064 X 1,241 X 12.00
X 0.360
/60] X
46
= 4,368
Schedule Air Sensible Area
Ceiling Height
ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
20,616
EnergyPro 5.1 by Energ Soft User Number: 6712 RunCode: 2012-02-07709:04:12 ID:
Page 34 of 52
•
•
ROOM HEATING PEAK LOADS
Project Name
Lothenbach Residence
Date
2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Floor Area
Indoor Dry Bulb Temperature
Master Suite
1, 599.0 ft'
72 OF
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 OF
Conduction
Area U -Value
1,128.0 X 0.0260 X
989.4 X 0.0690 X
16.0 X 0.3900 X
41.6 X 0.3300 X
222.0 X 0.5100 X
perim = 118.0 X 0.7300 X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
through an interior surface to another room
X 1,599 X 10.80 X 0.399
Area Ceiling Height ACH
AT OF
46 =
46 =
46 =
46 =
46 =
46 =
=
=
=
=
=
=
=
=
=
-
=
=
=
=
=
=
=
=
=
=
=
=
Page Total
/60] X 46
AT
Btu/hr
R-38 Roof(R. 38.2x 14.16)
1,349
R-21 Wall (W.19.2x6.16)
3,140
Architectural Madison Fr Door
287
Architectural Madison Club Windows
631
Architectural Madison Sl door
5,208
Slab -On -Grade
3,962
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X F 1.064
Schedule Air Sensible
Fraction
1 14,579
= 5,628
TOTAL HOURLY HEAT LOSS FOR ROOM
20,207
Energ Pro 5.1 by Energ Soft User Number: 6712
RunCode: 2012-02-07709:04:12
ID:
Page 35 of 52
•
•
•
ROOM HEATING PEAK LOADS
Project Name72/7/2012
ate
Lothenbach Residence
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great/Bar/Foyer/Dining/Kitchen
Time of Peak
Jan 1 AM
Floor Area 3,257.0 ft'
Outdoor Dry Bulb Temperature
26 OF
Indoor Dry Bulb Temperature 72 OF
Conduction Area
U -Value
AT OF
Btu/hr
R-38 Roof(R.38.2x14.16) 3,257.0
X
0.0260 X
46 =
3,895
R-21 Wall (W.19.2x6.16) 1,359.5
X
0.0690 X
46 =
4,315
Architectural Madison S/ door 672.0
X
0.5100 X
46 =
15,765
Architectural Madison Club Windows 316.5
X
0.3300 X
46 =
4,804
Architectural Madison Fr Door 114.0
X
0.3900 X
46 =
2,045
Slab -On -Grade perim = 214.0
X
0.7300 X
46 =
7,186
X
X
=
X
X
,-
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
•X
=
X
X
-
X
X
=
X
X
=
X
X
=
Items shown with an asterisk (') denote conduction through an interior surface
to another room
Page Total
38,011
Infiltration:[ 1.00 X 1.064 X 3,257 X
12.20
X 0.354
/60] X 46 =
11,465
Schedule Air Sensible Area
Ceiling Height
ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
49,476
EnergyPro 5.1 by Energ Soft User Number: 6712 RunCode: 2012-02-07T09:04:12 ID:
Page 36 of 52
•
•
•
ROOM HEATING PEAK LOADS
Project Name
Date
Lothenbach Residence
2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Game/Theater/Hay
Time of Peak
Jan 1 AM
Floor Area
1,571.0 ft'
Outdoor Dry Bulb Temperature
26 OF
Indoor Dry Bulb Temperature
72 OF
Conduction
Area
U -Value
AT °F
Btu/hr
R-38 Roof(R. 38.2x 14.16)
442.0
X
0.0260
X
46 =
529
R-21 Wall (W.19.2x6.16)
847.8
X
0.0690
X
46 =
2,691
Architectural Madison Fr Door
145.6
X
0.3900
X
46 =
2,612
Architectural Madison Club Windows
22.6
X
0.3300
X
46 =
343
Wood Door
24.0
X
0.5000
X
46 =
552
Slab -On -Grade
perim = 105.0
X
0.7300
X
46 =
3,526
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Items shown with an asterisk (') denote conduction through an interior surface to another room
Page Total
10,253
Infiltration:[ 1.00 X 1.064 X
1,571 X 10.00
X 0.431
/60] X 46
= 5,530
Schedule Air Sensible
Area
Ceiling Height
ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
15,783
Energ Pro 5.1 by Energ Soft User Number: 6712
RunCode: 2012-02-07709:04:12 ID:
Page 37 of 52
•
C7
•
ROOM HEATING PEAK LOADS
Project Name
Lothenbach Residence
Date
2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Bedroom 1 & 2
Floor Area 916.0 ft'
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area U -Value
307.0 X 0.0690
16.0 X 0.3300
237.0 X 0.3900
perm = 56.0 X 0.7300
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
through an interior surface to another room
X 916 X 10.00 X 0.431
Area Ceiling Height ACH
AT OF
X 46
X 46
X 46
X 46
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Page Total
/60] X
AT
Btu/hr
c 974
= 243
= 4,252
= 1,880
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
7,350
46 = 3,224
R-21 Wall (W. 19.2x6.16)
Architectural Madison Club Windows
Architectural Madison Fr Door
Slab -On -Grade
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 10,574
Energ Pro 5.1 by Energ Soft User Number: 6712 RunCode: 2012-02-07709:04:12 ID: Page 38 of 52
•
•
•
ROOM HEATING PEAK LOADS
Project Name
Lothenbach Residence
Date
217/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name 2nd Floor North
Floor Area 700.0 ft'
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U -Value AT °F Btu/hr
X 0.0260 X 46 = 837
X 0.0690 X 46 = 2,617
X 0.3300 X 46 = 918
X 0.3900 X 46 c Z244
X 0.0370 X 46 c 242
X X -
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X
X X =
to another room Page Total 6,858
10.00 X 0.431 /60] X 46 = 2,464
Ceiling Height ACH AT
R-38 Roof(R. 38.2x 14.16)
700.0
R-21 Wall (W.19.2x6.16)
824.4
Architectural Madison Club Windows
60.5
Architectural Madison Fr Door
125.1
R-19 Floor (F. 19.2x8.16)
142.0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 )( 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 700 X
Area
TOTAL HOURLY HEAT LOSS FOR ROOM 9,322
Energ Pro 5.1 by Energ Soft User Number: 6712 RunCode: 2012-02-07709:04:12 ID: Page 39 of 52
0
•
0
ROOM HEATING -PEAK LOADS
Project Name
Lothenbach Residence
Date
2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name 2nd Floor South
Floor Area 1,122.0 ft'
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area U -Value AT OF
1,122.0 X 0.0260 X 46
1,379.4 X 0.0690 X 46
87.6 X 0.3900 X 46
93.0 X 0.3300 X 46
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X, X
X X
X X
X X
X X
X X
X X.
X X
X X
X X
X X
X X
X X
X X
X X
X X
through an interior surface to another room. Page Total
X 1,122 X 10.00 X 0.431 / 60 ] X
Area Ceiling Height ACH AT
Btu/hr
= 1,342
= 4,378
= 1,572
= 1,412
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
8,703.
46 = 3,949
R-38 Roof(R.38.2x 14.16)
R-21 Wall (W. 19.2x6.16)
Architectural Madison Fr Door
Architectural Madison Club Windows
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 12,653
Energ Pro 5.1 by Energ Soft User Number. 6712 RunCode: 2012-02-07709:04:12 ID: Page 40 of 52
0
•
0
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Lothenbach Residence
2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name OfficeMall/Stairs
Floor Area 1,241.0 ft'
Indoor Dry Bulb Temperature 70 OF
Outdoor Dry Bulb Temperature 112 OF
Outdoor Wet Bulb Temperature 78 OF
Outdoor Daily Range: 34 OF
Opaque Surfaces Orientation
R-38 Roof(R. 38.2x 14.16) (N)
R-21 Wall (W. 19.2x6.16) (N)
R-21 Wall (W. 19.2x6.16) (SE)
Wood Door (SE)
R-21 Wall (W. 19.2x6.16) (S)
R-21 Wall (W.19.2x6.16)
Area
X
X
X
X
X
X
X
X
X
U -Factor CLTD'
0.0260 X 56.0 =
0.0690 X 23.0 =
0.0690 X 31.0 =
0.5000 X 31.0 =
0.0690 X 26.0 =
0.0690 X 33.0 =
X =
X =
X =
Page Total
Btu/hr
274.0
399
523.0
830
335.5
718
24.0
372
272.3
489
60.0
137
398
281
1 2,653
2,94a
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Windowl-D
Window2-J
Window3-DTEMP
Window4-D
WndowS-D
Wndow6-B
Window7-B
Window8-B
Window9-B
Internal Gain
Orientation
(N)
(N)
(N)
(N)
(N)
(SE)
(SE)
(SE)
Shaded
Area
0.0 X
0.0 X
0.0 X
0.0 X
0.0 X
0.0 X
0.0 X
0.0 X
0.01 X
GLF
20.7
20.7
20.7
20.7
20.7
20.7
20.7
20.7
20.7
Unshaded
Area
+ 8.0
+ 25.0
+ 8.0
+ 8.0
+ 8.0
+ 13.5
+ 13.5
+ 13.5
+ 13.5
GLF
X 20.7 =
Btu/hr
166
X
20.7
=
518
X
X
X
X
X
20.7
=
=
=
=
=
166
20.7
166
20.7
166
29.4
398
29.4
398
X 29.4 =
X1 20.8 =1
Page Total
398
281
1 2,653
4.0 Occupants X 230 Btuh/occ. = 920
1.0 Dwelling Unit X 1,600 Btu = 1,600
Infiltration: 1.064 X 1.27 X 67.91 X 42 = 3,841
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 17,6031
Latent Gain Btu/hr
Occupants 4.0 Occupants X 200 Btuh/occ. = 800
Infiltration: 4,771 X 1.27 X 67.91 X 0.00523 = 2,146
Air Sensible CFM ELA AW
v , I 1
•
•
LJ
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lothenbach Residence
1 2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
OfficeMall/Stairs
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,241.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OFI
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X J
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
Windowl0-A
(S) 0.0 X 21.9 +
9.1
X 22.0
= 200
Windowll-101
(S) 0.0 X 21.9 +
60.0
X 22.0
= 1,319
Window12-A
(S) 0.0 X 21.9 +
9.1
X 22.0
= 200
Window13-113
(S) 0.0 X 21.9 +
49.5
X 22.0
= 1,089
Windowl4-113
(S) 0.0 X 20.7 +
49.5
X 20.8
= 1,029
Windowl5-113
(S) 0.0 X 20.7 +
49.5
X 20.8
= 1,029
Windowl6-118
(S) 0.0 X 20.7 +.
24.0
X 20.8
= 499
wndow17-B
(S) 13.5 X 20.7 +
0.0
X 20.8
= 279
X +
XI
-
Page Total
5,645
Internal Gain
Btu/hr
Occupants
4.0 Occupants X 230
Btuh/occ.
=
820
Equipment
1.0 Dwelling Unit X 1,600
Btu
Infiltration: 1.064
X 1.27 X 67.91 X 42 =
3,841
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
17,603
Latent Gain
Btu/hr
Occupants
4.0 Occupants X 200
Btuh/occ.
=
800
Infiltration: 4,771
X 1.27 X 67.91 X 0.00523 =
2,146
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
2,946
E,,emvPro 5.1 7v EnemySoft
User Number: 6712 RunCode: 2012-02-07709:04:12 ID:
Pace 42 of 52
•
C7
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lothenbach Residence
1 2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Master Suite
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,599.0 tt2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OFI
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x 14.16)
(N) 1,128.0 X 0.0260
X
56.0 =
1,642
R-21 Wall (W. 19.2x6.16)
(N) 643.4 X 0.0690
X
23.0 =
1,021
R-21 Wall (W. 19.2x6.16)
(E) 45.0 X 0.0690
X
33.0 =
102
R-21 Wall (W.19.2x6.16)
(S) 214.0 X 0.0690
X
26.0 =
384
R-21 Wall (W. 19.2x6.16)
(W) 87.0 X 0.0690
X
33.0 =
198
X
X
=
X
X
=
X
X
=
X J
X
=
Page Total
3,348
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
Windowl8-D
(N) 0.0 X 21.9 +
8.0
X 21.9 =
175
Wndow19-D
(N) 0.0 X 21.9 +
8.0
X 21.9 =
175
Window20-M
(N) 0.0 X 20.7 +
33.6
X 20.7 =
696
Wndow2l-D
(N) 0.0 X 20.7 +
8.0
X 20.7 =
166
Window22-108
(S) 0.0 X 24.3 +
72.0
X 24.4 =
1,756
Window23-107
(t9 0.0 X 24.3 +
150.0
X 46.9 =
7,029
X +
X -
X +
X -
X +1
X -
Page Total
9,997
Internal Gain
Btu/hr-
tu/hrOccu
Occupants
ants
4.0 Occupants X 230
Btuh/occ.
=
920
Equipment
1.0 Dwelling Unit X 1,600
Btu
=
1,600
Infiltration: 1.064
X 1.27 X 87.50 X 42 =
4,949
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
20,814
Latent Gain
Btu/hr
Occupants
4.0 Occupants X 200
Btuh/occ.
=
800
Infiltration: 4.771
X 1.27 X 87.50 X 0.00523 =
2,765
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
3,565
EnemvPro 5.1 bv EnerovSoft
User Number: 6712 RunCode: 2012-02-07709:04:12 ID:
Page 43 of 52
, � t
0
•
a
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Lothenbach Residence
1 2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great/BarlFoyer/Dining/Kitchen
Floor Area 3,257.0 ftz
Indoor Dry Bulb Temperature 70 OF
Outdoor Dry Bulb Temperature 112 OF
Outdoor Wet Bulb Temperature 78 OF
Outdoor Daily Range: 34 OF
Opaque Surfaces
Orientation Area
(N) 3,257.0
(N) 98.0
(E) 460.0
(S) 57.0
(W) 744.5
X
X
X
X
X
X
X
X
X
U -Factor CLTD'
0.0260 X 56.0 =
0.0690 X 23.0 =
0.0690 X 33.0 =
0.0690 X 26.0 =
0.0690 X 33.0 =
X =
X
X =
X =
Page Total
Btu/hr
R-38 Roof(R. 38.2x 14.16)
Equipment
4,742
R-21 Wall (W.19.2x6.16) .
90.0
156
R-21 Wall (1..19.2x6.16)
24.3
1,047
R-21 Wall (W. 19.2x6.16)
X
102
R-21 Wall (W. 19.2x6.16)
+
1,695
X
Air Sensible
43.3
=
0.0
X
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
20.7
+
19.5
X
43.3
7,743
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Window24-115
Window25-K
Window26-K
Window27-116
Window28-114
Window29-L
Window30-L
Window3l -L
Window32-L
Orientation
Shaded
Unshaded
Btu/hr
Area
GLF
Area
230
GLF
0.0
X
Equipment
24.3
+
90.0
X
Btu
24.3
=
0.0
X
Infiltration:
20.7
+
19.5
X
Air Sensible
43.3
=
0.0
X
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
20.7
+
19.5
X
43.3
=
110.6
X
4.0 Occupants X 200 Btuh/occ.
20.7
+
78.4
X
4,771
43.3
=
71.1
X
CFM ELA AW
21.9
+
36.9
X
44.5
=
0.0
X
20.7
+
6.0
X
43.3
=
0.0
X
24.3
+
6.0
X
46.9
=
0.0
X
20.7
+
6.0
X
43.3
=
0.0
X
20.7
+
6.0
X1
43.3
=
Page Total
Btu/hr
2,187
844
844
5,661
3,198
260
281
260
260
13,8131
Internal Gain
Btu/hr
Occupants
4.0
Occupants X
230
Btuh/occ.
=
920
Equipment
1.0
Dwelling Unit X
1,600
Btu
=
1,600
Infiltration:
1.064
)( 1.27 X 178.22 X 42 =
10,081
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
50,825
Latent Gain
Btu/hr
Occupants
4.0 Occupants X 200 Btuh/occ.
= 800
Infiltration:
4,771
X 1.27 X 178.22 X 0.00523 =
5,633
Air Sensible
CFM ELA AW
, % I
•
•
•
I RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Lothenbach Residence 1 2/7/2012
ROOM INFORMATION DESIGN CONDITIONS
Room Name Great/Bar/Foyer/Dining/Kitchen Outdoor Dry Bulb Temperature 112 OF
Floor Area 3,257.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Daily Range: 34 OF
Surfaces
Orientation
Area U -Factor CLTD' Btu/hr
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X J X =
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestration
Window33-110
Window34-G
Window35-H
Window36-109
Window37-L
Wndow38-L
Wndow39-L
Window40-L
Window4l -L
Orientation
(S)
(tM
01
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
Btu/hr
0.0
20.7
24.0
20.8
499
0.0
20.7
10.0
43.3
433
0.0
20.7
12.5
43.3
541
576.0
24.3
0.0
46.9
13,997
0.0
20.7
6.0
43.3
260
0.0
20.7
6.0
43.3
260
0.0
20.7
6.0
43.3
260
0.0
20.7
6.0
43.3
260
4.7
21.9
1.3
44.5
160
Page Total
16,668
Internal Gain Btu/hr-
Occupants
tu/hrOccu ants 4.0 Occupants X 230 Btuh/occ. = 920
Equipment 1.0 Dwelling Unit X 1,600 Btu = 1,600
I Infiltration: 1.064 X 1.27 X 178.22 X 42 = 10,081
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 50.8251
Latent Gain Btu/hr
Occupants 4.0 Occupants X 2001 Btuh/occ. = 800
Infiltration: 4.771 X 1.27 X 178.22 X 0.00523 = 5,633
Air Sensible CFM ELA AW
I
1 1
•
•
PJ
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lothenbach Residence
1 2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
GamelTheaterlHa//
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,571.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces.
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x 14.16)
(N) 442.0 X 0.0260
X
56.0 =
644
R-21 Wall (W. 19.2x6.16)
(N) 215.3 X 0.0690
X
23.0 =
342
R-21 Wall (W. 19.2x6.16)
(E) 122.5 X 0.0690
X
33.0 =
279
Wood Door
(E) 24.0 X 0.5000
X
33.0 =
396
R-21 Wall (W. 19.2x6.16)
(S) 3.90.01 X 0.0690
X
26.0 =
700
R-21 Wall (W. 19.2x6.16)
(W) 120.0 X 0.0690
X
33.0 =
273
X
X
=
X
X
=
X J
X I=
Page Total
2,s33
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
Window42-113
(N) 0.0 X 21.9 +
49.5
X 21.9
= 1,084
Window43-113
(N) 0.0 X 21.9 +
49.5
X 21.9
= 1,084
Window44-A
(N) 0.0 X 21.9 +
9.1
X 21.9
= 199
Window45-101
(N) 0.0 X 21.9 +
24.0
X 21.9
= 526
Window46-A
(N) 0.0 X 20.7 +
9.1
X 20.7
= 188
Window47-B
(N) 0.0 X 21.9 +
13.5
X 21.9
= 296
Window48-B
(E) 0.0 X 20.7 +
13.5
X 43.3
c 584
X +
X
-
X +1
X
-
Page Total
3,961
Internal Gain
Btu/hr
Occupants
4.0 Occupants X 230
Btuh/occ.
=
820
Equipment
1.0 Dwelling Unit X 1,600
Btu
=
1,600
Infiltration: 1.064
X 1.27 X 85.97 X 42 =
4,863
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
13,977
Latent Gain
Btu/hr
Occupants
4.0 Occupants X 200
Btuh/occ.
=
800
Infiltration: 4.771
X 1.27 X 85.97 X 0.00523 =
2,717
Air Sensible
CFM Et.A AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
3,517
EnemvPro 5.1 by EnemySoft
User Number- 6712 RunCode: 2012-02-07709:04:12 ID:
Pa a 46 of 52
I v
0
•
:7
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Lothenbach Residence 2/7/2012
ROOM INFORMATION DESIGN CONDITIONS
Room Name Bedroom 1 & 2 Outdoor Dry Bulb Temperature 112 OF
Floor Area 916.0 R2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Daily Range: 34 OF
Opaque Surfaces
R-21 Wall (W. 19.2x6.16)
R-21 Wall (W. 19.2x6.16)
R-21 Wall (W. 19.2x6.16)'
Orientation
(N)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
Btu/hr
50.0
0.0690
31.0
8.0
130.0
0.0690
44.0
8.0
127.0
0.0690
38.0
13.6
35.0
0.0
26.6
42.4
35.0
0.0
26.6
13.6
35.0
0.0
26.6
13.6
35.0
0.0
26.6
42.4
35.0
0.0
26.6
13.6
35.0
0.0
26.6
13.6
35.0
Page Total
I
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestration
Window49-D
WindoW50-D
Window5l -E
Wndow52-112
WindowW-E
Window54-E
Window55.112
Window56-E
Window57-E
Orientation
(S)
(S)
(S)
(S)
(S)
(S)
(S)
(S)
(S)
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
25.4
8.0
33.8
0.0
25.4
8.0
33.8
0.0
26.6
13.6
35.0
0.0
26.6
42.4
35.0
0.0
26.6
13.6
35.0
0.0
26.6
13.6
35.0
0.0
26.6
42.4
35.0
0.0
26.6
13.6
35.0
0.0
26.6
13.6
35.0
Page Total
Btu/hr
270
270
476
1,483
476
476
1,483
476
476
Internal Gain Btu/hr
Occupants 4.0 Occupants X 230 Btuh/occ. = 920
Equipment 1.0 Dwelling Unit X 1,200 Btu = 1,200
I Infiltration: 1.064 )( 1.27 X 50.12 X 42 = 2,835
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 14,6201
Latent Gain Btu/hr
Occupants 4.0 Occupants X 2001 Btuh/occ. = 800
Infiltration: 4,771 X 1.27 X 50.12 X 0.00523 = 1,584
Air Sensible CFM ELA DW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2,3841
U
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name721712012
ate
Lothenbach Residence
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Bedroom 1 & 2
Outdoor Dry Bulb Temperature
112 OF
Floor Area
916.0 (t2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
Window58-112
(S) 0.0 X 26.6 4
42.6
X 35.0
= 1,490
Wndow59-E
(S) 0.0 X 26.6 +
13.6
X 35.0
= 476
Window60-D
(S) 0.0 X 26.6 +
8.0
X 35.0
= 280
Wnd6w6l-D
(S) 0.0 X 26.6 +
8.0
X 35.0
= 280
Window62-F
(S) 0.0 X 26.6 +
12.0
X 35.0
= 420
ix +
X
-
X +
X
-
X +
X
=
X +
X
-
Page Total
2,945
Internal Gain
Btu/hr
Occupants
4.0 Occupants X 230
Btuh/occ.
=
920
Equipment
1.0 Dwelling Unit X 1,200
Btu
=
1,200
Infiltration: 1.064
.X 1.27 X 50.12 X 42 =
2,835
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
14,620
Latent Gain
Btu/hr
Occupants
4.0 Occupants X 200
Btuh/occ.
=
800
Infiltration: 4.771
X 1.27 X 50.12 X 0.00523 =
1,584
Air Sensible
CFM ELA OW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
2,384
EnemvPro 5.1 bv EnerovSoft
User Number.' 6712 RunCode: 2012-02-07T09:04:12 ID:
Page 48 of 52
' , 1
0
•
0
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Lothenbach Residence 1
Date
2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name 2nd Floor North
Floor Area 700.0 112
Indoor Dry Bulb Temperature 70 OF
Outdoor Dry Bulb Temperature 112 OF
Outdoor Wet Bulb Temperature r 78 OF
I Outdoor Daily Range: 34 OF
Opaque Surfaces Orientation
R-38 Roof(R. 38.2x 14.16) (N)
R-21 Wall (W. 19.2x6.16) (N)
R-21 Wall (W. 19.2x6.16) (S)
R-21 Wall (W. 19.2x6.16) (1M
R-19 Floor (F. 19.2x8.16)
Area U -Factor
700.0 X 0.0260
349.0 X 0.0690
350.4 X 0.0690
125.0 X 0.0690
142.0 X 0.0370
X
X
X
X
CLTD'
X 77.0
X 31.0
X 38.0
X 55.0
X 19.0
X
X
X
X I=
=
=
=
=
=
=
=
=
Btu/hr
1,401
747
919
474
100
25.4
8.0
25.4
0.0
Page Total
Items shown with an asterisk (•) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestratinn
Window63-D
Window64-D
Window65-D
Window66-D
Window67-D
Window68-D
Window69-D
Window70-H
Window7l-H
(N)
(N)
(N)
11V
(N)
1 3,6411
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
25.4
8.0
25.4
0.0
25.4
8.0
25.4
0.0
25.4
8.0
25.4
0.0
25.4
8.0
25.4
0.0
25.4
8.0
25.4
0.0
25.4
8.0
25.4
0.0
26.6
8.0
26.6
0.0
26.6
12.5
26.6
0.0
26.6
12.51
26.6
Page Total
203
203
203
203
203
203
213
333
333
Internal Gain
Btu/hr
Occupants
4.0 Occupants X
230 Btuh/occ.
= 920
Equipment
1.0 Dwelling Unit X
1,200 Btu
Infiltration: 1.064
X 1.27 X 38.30
X 42 =
2,167
Air Sensible
CFM ELA
AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
14,869
Latent Gain
Btu/hr
Occupants
4.0 Occupants X 200Btuh/occ.
= 800
Infiltration: 4,771
X 1.27 X 38.30
X 0.00523 =
1,211
Air Sensible
CFM ELA
AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2.0111
I
. I
•
0
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lothenbach Residence
1 2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
2nd Floor North
Outdoor Dry Bulb Temperature
112 OF
Floor Area
700.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
.
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
Window72-104
(S) 0.0 X 26.6 +
39.8
X 35.0
= 1,392
Window73-104
(S) 0.0 X 26.6 +
39.8
X 35.0
= 1,392
Window74-H
(W) 0.0 X 25.4 +
12.5
X 81.8
= 1,023
Window75-H
0.0 X 26.6 +
12.5
X 63.0
= 1,038
X +
X
-
X +
X
-
X +
X
-
X +
X
=
X 1 +1
X
=
Page Total
4,644
Internal Gain
Btu/hr
Occupants
4.0 Occupants X 230
Btuh/occ.
=
920
Equipment
1.0 Dwelling Unit X 1,200
Btu
=
1.200
Infiltration: 1.064
X 1.27 X 38.30 X 42 =
2,167
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
14,869
Latent Gain
Btu/hr
Occupants
4.0 Occupants X 200
Btuh/occ.
=
800
Infiltration: 4,771
X 1.27 X 38.30 X 0.00523 =
1,211
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
2,011
Ene Pro 5.1 by EnerqvSoft
User Number. 6712 RunCode: 2012-02-07T09:04:12 ID:
Page 50 of.
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Lothenbach Residence 217/2012
ROOM INFORMATION DESIGN CONDITIONS
Room Name 2nd Floor South Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,122.0 ft' Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranae: 34 OF
ODaaue Surfaces
R-38 Roof(R.38.2x 14.16)
R-21 Wall (W. 19.2x6.16)
R-21 Wall (W. 19.2x6.16)
R-21 Wall (W. 19.2x6.16)
R-21 Wall (W. 19.2x6.16)
Orientation
(E) I
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,122.0
0.0260
56.0
550.4
0.0690
23.0
123.0
0.0690
33.0
556.0
0.0690
26.0
150.0
0.0690
33.0
20.7
260
20.7
166
20.71+
260
1 4,024
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestratinn
Window76-104
wndow77-104
Window78-B
Window79-B
Window80-D
Window81-H
Window82-H
Wndow83-D
Window84-H
(E)
(S)
(S)
Btu/hr
1, 634
873
280
1 3421
1 4,1261
Shaded
Area
0.0 X
0.0 X
0.0 X
GLF
+
+
+
+
+
+
+
+
Unshaded
Area
39.8
39.8
13.5
13.5
8.0
12.5
12.5
8.0
12.5
GLF
X 21.9 =
X 21.9 =
X 43.3 =
X 43.3 =
X 20.8 =
X 20.8 =
X 20.8 =
X 20.8 =
X1 20.8 =1
Page Total
Btu/hr
21.9
872
21.9
872
20.7
584
0.0
X
20.7
584
0.0 X
0.0 X
0.0 X
0.0 X
0.0 X
20.7
166
20.7
260
20.7
260
20.7
166
20.71+
260
1 4,024
d Gain
Btu/hr
nts
4.0
Occupants
X
230
Btuh/occ.
= 920
ent
1.0
Dwelling Unit
X
1,600
Btu
Infiltration: 1.064 )( 1.27 X 61.40 X 42 = 3,473
Air Sensible CFM ELA AT
TOTAL HOURLY
Latent Gain Btu/hr
Occupants 4.0 Occupants X 200 Btuh/occ. = 800
Infiltration: 4,771 X 1.27 X 61.40 X 0.00523 = 1,940
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR
,, , "
C11
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lothenbach Residence
2/7/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
2nd Floor South
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,122.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X J
X I=
Page Total
o
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF - Area GLF
Btu/hr
Window85-H
(S) 0.0 X 20.7 +
12.5 X 20.8
= 260
Window86-D
(S) 0.0 X 21.9 +
8.0 X 22.0
= 176
X +
X
=
X +
X
=
X +
X
=
X +
X
X +
X
=
X +
X
=
X +1
X
=
Page Total
436
Internal Gain -
Btu/hr
Occupants
4.0 Occupants X 230
Btuh/occ. =
920
Equipment
1.0 Dwelling Unit X 1,600
Btu =
1,600
Infiltration: 1.064
X 1.27 X 61.40 X 42 =
3,473
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
14,578
Latent Gain
Btu/hr
Occupants
4.0 Occupants X 200
Btuh/occ. =
800
Infiltration: 4,771
X 1.27 X 61.40 X 0.00523 =
1,940
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
2,740
EnemvPro 5.1 by EnerqvSoft
User Number., 6712 Runcode: 2012-02-07709:04:12 /D: