BCOM2018-001078-495.CALLE TAMPICO D
haw
LA QUINTA, CALIFORNIA 92253 DESIGN & DEVELOPMENT DEPARTMENT
BUILDING PERMIT
Permit Type/Subtype: . BUILDING COMMERCIAL/REMODEL
Application Number:
BCOM2018-0010
Property Address:
4610.0 WASHINGTON ST
APN:
604050038
Application Description:
DESERT NEUROLOGY & SLEEP / 4,560SF TI/V6/B-OCC/46-OL/SPRINK
Property Zoning:
Application Valuation:
$190,000.00
Applicant:
GABRIEL LUJAN & ASSOCIATES
77530 ENFIELD LN BLDG I STE 101
PALM DESERT, CA 92211
LICENSED CONTRACTOR'S' DECLARATION
I hereby affirm under penalty of perjury that l am licensed under provisions of Chapter 9
{commencing with Section 7000) of Division 3 of the Business and Professions Code, and
my License is in full force and effect.
License Class: B A License No.: 693077
(Da e: 3 /S Contracto7:
OW= DECLARATION
I hereby affirm under penalty of perjury that I am exempt from the Contractor's State
License -Law for the following reason (Sec. 7031.5, Business and Professions Code: Any
city or county that requires a permit to construct, alter, improve, demolish, or repair any
structure, prior to its issuance, also requires the applicant for the permit to file a signed
statement that he or she is licensed pursuant to the provisions of the Contractor's State
:License Law (Chapter 9 (commencing with Section 7000) of Division 3 of the Business
and Professions Code) or that he or she is exempt therefrom and the basis for the
alleged exemption. Any violation of Section 7031.5 by any applicant for a permit
subjects the applicant to a civil penalty of not more than five hundred dollars ($500).:
(_) 1, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for sale.
(Sec. 7044, Business and Professions Code: The Contractors' State License Law does not
apply to an owner of property who builds or improves thereon, and who does the work
himself or herself through his or her own employees, provided that the improvements
are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner -builder will have the burden of proving that he
or she did not build or improve for the purpose of sale.).
( 11, as owner of the property, am exclusively contracting with licensed contractors to
constructthe project. (Sec. 7044, Business and Professions Code: The Contractors' State
License Law does not apply to an owner of property who builds or improves thereon,
and who contracts for the projects with a contractor(s) licensed pursuant to the
Contractors' State License Law.).
(� I am exempt under Sec. B.&P.C. for this reason
Date:
Owner:
CONSTRUCTION LENDING AGENCY
I hereby affirm under penalty of perjury that there is a construction lending agency for
the performance of the work for which this permit is issued (Sec. 3097, Civ. C.)'.
Lender's Name:
Lender's Address:
VOICE (760) 777-7125
FAX (760) 777-7011
INSPECTIONS (760) 777-7153
Date: 3/15/2018
Owner:
AJE DESERT VENTURES LLC
46100 WASHINGTON ST
LA QUINTA, CA 92253
Contractor:
ORR BUILDERS
39-301 BADGER STREET STE 300
PALM DESERT, CA 92211
(760)360-6632
Llc. No.: 693077
WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self -insure for workers'
compensation, as provided for by Section 3700 of the Labor Code, for the performance
of thew k for which this permit is issued.
ave and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My workers' compensation insurance carrier and policy number are:
Carrier: STATE COMPENSATION INSURANCE FUND Policy Number: 9213286
1 certify that in the performance of the work for which this permit is issued, I
shall not employ any person in any manner so as to become subject to the workers'
compensation laws of California, and agree that, if I should become subject to the
workers' compensation provisions of Section 3700 of the Labor Code, I shall forthwith
comply with those provisions.
Datesly/�Applica
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS UNLAWFUL,
AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO
ONE HUNDRED THOUSAND DOLLARS ($100,000). IN ADDITION TO THE COST OF
COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE,
INTEREST, AND ATTORNEY'S FEES.
APPLICANT ACKNOWLEDGEMENT
IMPORTANT: Application is hereby made to the Building Official for a permit subject to
the conditions and restrictions set forth on this application.
1. Each person upon whose behalf this application is made, each person at whose
request and for whose benefit work is performed under or pursuant to any permit issued
as a result of this application , the owner, and the applicant, each agrees to, and shall
defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and
employees for any act or omission related to the work being performed under or
following issuance of this permit.
2. Any permit issued as a result of this application becomes null and void if work is not
commenced within 180 days from date of issuance of such permit, or cessation of work
for 180 days will subject permit to cancellation.
I certify that I have read this application and state that the above information is correct.
I agree to comply with all city and county ordinances and state laws relating to building
construction, and hereby authorize representatives of this city to enter upon the above-
mentioned property for inspection purposes.
Da� 3 / Ste/ ` Signatu�(AppIican
Date: 3/15/2018
Application Number: - BCOM2018-0010 Owner:
Propertq'Adttresr- 46100 WASHINGTON ST AJE DESERT VENTURES LLC
APN: 604050038 46100 WASHINGTON ST
Application Description: DESERT NEUROLOGY & SLEEP / 4,5605F TI/VB/B-OCC/46-OL/SPRINK LA QUINTA, CA 92253
Property Zoning:
Application Valuation: $190,000.00
Applicant: Contractor:
GABRIEL LUJAN & ASSOCIATES ORR BUILDERS
77530 ENFIELD LN BLDG I STE 101 39-301 BADGER STREET STE 300
PALM DESERT, CA 92211 PALM DESERT, CA 92211
(760)360-6632
Llc. No.: 693077
--------------------------------------------------------------------------------------------
Detail: 4,560SF OFFICE TI/VB/B-OCC/46-OL/SPRINKLED [DESERT NEUROLOGY & SLEEP] THIS PERMIT DOES NOT INCLUDE ALTERATION TO EXISTING LOAD
BEARING AND LATERAL RESISTING CONSTRUCTION OR EXISTING SITE, OSPHD REVIEW OR APPROVAL, OR BUILDING SIGNAGE: TUMF FEE NOT ASSESSED
DUE TO REDUCED TRIP GENERATION RATE. 2016 CALIFORNIA BUILDING CODES.
DESCRIPTION
ACCOUNTQTY AMOUNT'
ART IN PUBLIC PLACES - COMMERCIAL REMOD
270-0000-43201 1 0 $450.00
Total Paid for ART IN PUBLIC PLACES - AIPP: $450.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
BSAS SB1473 FEE
101-0000-20306
0
$8.00
Total Paid for BUILDING STANDARDS ADMINISTRATION BSA: $8.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
NON-RESIDENTIAL, EA ADDITION 2,0005F
101-0000-42403.
0
$78.02
DESCRIPTION
ACCOUNT
QTY
AMOUNT
NON-RESIDENTIAL, EA ADDITION 2,000SF, PC
101-0000-42600
0
$20.80
DESCRIPTION
ACCOUNT
QTY
AMOUNT
NON-RESIDENTIAL, FIRST 2,000SF
101-0000-42403
0
$117.03
DESCRIPTION
ACCOUNT
QTY
AMOUNT
NON-RESIDENTIAL, FIRST 2,000SF, PC
101-0000-42600
0
$90.50
Total Paid for ELECTRICAL - NEW CONSTRUCTION: $306.35
DESCRIPTION
ACCOUNT
QTY
AMOUNT
FIRE COMMERCIALTI PC
101-0000-42420
0
$234.00
Total Paid for FIRE FEES: $234.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
VENT FAN
101-0000-42402
0
$52.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
VENT FAN PC
101-0000-42600
0
$20.80
Total Paid for MECHANICAL: $72.80
DESCRIPTION ACCOUNT QTY AMOUNT
PLAN CHECK DEPOSIT - ADDITION/REMODEL 101-0000-42600 1 $125.00
Total Paid for PLAN CHECK DEPOSIT - ADDITION/REMODEL: $125.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
FIXTURE/TRAP
101-0000-42401
0
$130.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
FIXTURE/TRAP PC
101-0000-42660
0
$130.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
WATER HEATER/VENT
101-0000-42401
0
$13.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
WATER HEATER/VENT PC
101-0000-42600
0
.$7.80
DESCRIPTION
ACCOUNT
QTY
AMOUNT
WATER SYSTEM INST/ALT/REP
101-0000-42401
0
$13.00 .
DESCRIPTION
ACCOUNT
QTY
AMOUNT
WATER SYSTEM INST/ALT/REP PC
101-0000-42600
0
$13.00
Total Paid for PLUMBING FEES: $306.80
DESCRIPTION ACCOUNT I QTY AMOUNT
RECORDS MANAGEMENT FEE-- MAJOR
I101-0000-42416 0 ) $20.00
Total Paid for RECORDS MANAGEMENT FEE - MAJOR: $20.00
DESCRIPTION
ACCOUNT
QTY
AMOUNT
REMODEL, EA ADDITIONAL 500 SF
101-0000-42400
0
$210.69
DESCRIPTION
ACCOUNT
QTY
AMOUNT
REMODEL, EA ADDITIONAL 500 SF PC
101-0000-42600
0
$168.48
DESCRIPTION
ACCOUNT
QTY
AMOUNT
REMODEL, FIRST 100 SF
101-0000-42400
0.
$53.05
DESCRIPTION
ACCOUNT
QTY
AMOUNT
REMODEL, FIRST 500 SF PC
101-0000-42600
0
$145.12
Total Paid for REMODEL: $577.34
DESCRIPTION ACCOUNT QTY AMOUNT
SMI - COMMERCIAL 101-0000-20308 0 $53.20
Total Paid for STRONG MOTION INSTRUMENTATION SMI: $53.20
DESCRIPTION
ACCOUNT
QTY
'AMOUNT
TECHNOLOGY ENHANCEMENT FEE
502-0000-43611
0
$5.00
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00
Bin #
City of La Quina-
Building 8r Safety Division
P.O. Box 1504,78-495 Calle Tampico
La .Quints, CA 92253 -:(760) 777-7012
Building Permit Application and Tracking Sheet
Permit #
G
P,a
Project Address: 46-100
Washington St.
Owner's Name:. Dr. Elhajjar
A. P. Number.
Address: 46-100 Washington St.
Legal Description:
Contractor: To'Be Determined`'°'~'
City, ST, Zip: La Quinta, Ca. 92253
Telephone:
Address:
Project Description: A tenant improvement for a
City, ST, Zip:
Medical Sleep Clinic of approximately
Telephone:
4,546 Sq. Ft. consisting of electrical, mechanical
State Lic. # :City
Lia #;
plumbing and faming work
Arch., Engr., Designer. Gabriel Lujan & Associates. .
Address: 77-530 Enfield Ln. Bldg. I-Ste. 101
City, ST, zip: palm Desert, CA.
Telephone: 760.578.8545 Construction Type:. VB Occupancy: B
State Lic. #: Project type (circle one): New Add'n Alter Repair Demo
Name of contact person: Gabriel LujanSq. Ft.: 4,546 # Stories: 1 #Units:
Telephone # of Contact Person: 760.578.8545
Estimated value of Project: 190,000.00
APPLICANT: DO NOT WRITE BELOW THIS LINE
#
Submittal
Req'd
Recd
TRAgMG
PERMIT FEES
Plan Sets
Plan Cheek submitted
Item Amount
Structural Calcs.
Reviewed, ready for corrections
Plan Check Deposit. .
Truss Cales.
Called Contact Person
Plan Check Balance •
Title 24 Calm.
Plans picked up
Construction '
Flood plain plan
Plans resubmitted
Mecharikal
Grading plan
2i8 Review, ready for corrections/issue
Electrical
Subcontactor List
Called Contact Person
Plumbing
Grant Deed
Plans picked up
S bLL
H.O.A. Approval
Plans resubmitted
Grading
IN ROUSE:-
'^' Review; ready for correetionsAssue
Developer 3mpaet Fee
Planning Approval
Called Contact Person
AA.P.P.
Pub. Wks. Appr
Date of permit issue
School Fees
Total Permit Fees
•
BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Desert Neurology & SleepTl
46-100 Washington Street
La Quinta, CA 92253
Project Designer:
Gabriel Lujan & Associates
77-530 Enfield Lane, Suite 101
Palm Desert, CA 92211
(760) 578-8545
Report Prepared by:
Tim Scott
Scott Design and Title 24, Inc,
74-818 Velie Way, Suite #8
Palm Desert, CA 92260
(760) 200-4780
CITY OF LA QUINT,
BUILDING & SAFETY DEP'
,APPROVED
¢.
FOR CONSTRUCTION
DAT61 %BYE_
Job Number: RECEIVED
MAR 0 i 2018
Date: CITY OF LA QUINTA
COMMUNITY DEVELOPMENT
3/6/2018
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2016 Building Energy Efficiency Standards.
This program developed by EnergySoft Software — www.energysoft.com.
9J
0
Project Name:
Dr. Elhajar TI
NRCC-PRF-01-E
Page 1 of 16
Project Address:
46-100 Washington Street La Quinta 92253
Calculation Date/Time:
12:18, Tue, Mar 06, 2018
Compliance Scope:
ExistingAlteration
Input File Name:
Elhajar DR. TI-LQ-GLA-17.cibdl6x
A. PROJECT GENERAL INFORMATION
§ 140.1
1.
Project Location (city)
La Quinta
8.
Standards Version
Compliance2016
2.
CA Zip Code
92253
9.
Compliance Software (version)
EnergyPro 7.2
3.
Climate Zone
15
10.
Weather File
PALM-SPRINGS-INTL_722868_CZ2010.epw
4.
Total Conditioned Floor Area in Scope
4,667 ftz
11.
Building Orientation (deg)
(E) 135 deg
S.
Total Unconditioned Floor Area
0 ft2
12.
Permitted Scope of Work
ExistingAlteration
6.
Total # of Stories (Habitable Above Grade)
1
13
Building Type(s)
Nonresidential
7.
Total # of dwelling units
0
14
Gas Type
NaturalGas
B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft 2 -yr)
§ 140.1
BUILDING COMPLIES
1. Energy Component
2. Standard Design (TDV)
3. Proposed Design (TDV)
4. Compliance Margin (TDV)
S. Percent Better than Standard
Space Heating
0.63
0.85
-0.22
-34.9%
Space Cooling
187.64
178.16
9.48
5.1%
Indoor Fans
134.00
122.83
11.17
8.3%
Heat Rejection
--
--
--
--
Pumps & Misc.
--
--
--
Domestic Hot Water
7.27
7.27
--
0.0%
Indoor Lighting
78.30
35.37
42.93
54.8%
COMPLIANCE TOTAL
407.84
344.48
63.36
15.5%
Receptacle
110.86
110.86
0.0
0.0%
Process
--
--
--
--
Other Ltg
.Process Motors
TOTAL
518.70
455.34
63.4
12.2`Yo
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
Project Name:
Dr. Elhajar TI
NRCC-PRF-01-E
Page 2 of 16
Project Address:
46-100 Washington Street La Quinta 92253
Calculation Date/Time:
12:18, Tue, Mar 06, 2018
Compliance Scope:
ExistingAlteration
Input File Name:
Elhajar DR. TI-LQ-GLA-17.cibdl6x
C. PRIORITY PLAN CHECK/ INSPECTION ITEMS (in order of highest to lowest TDV energy savings)
1st
Indoor Lighting: Check lighting
Compliance Margin By Energy
Component
(from Table B column
4)
Cnedrt
2nd
Indoor Fans: Check envelope and mechanical
Indoor Lighting
Indoor Fans
Space Cooling
Heat RejectionPumps & Misc.
Domestic Hot Water
Space Heating
Energy
3rd
Space Cooling: Check envelope and mechanical
4th
Heat Rejection: Check envelope and mechanical
5th
Pumps & Misc.: Check mechanical
6th
Domestic Hot Water: Check mechanical
7th
Space Heating: Check envelope and mechanical
_
Penalty
D. EXCEPTIONAL CONDITIONS
The building does not include service water heating. Verify that service water heating is not required and is not included in the design.
This project uses the Simplified Geometry Performance Modeling Approach which is not capable of modeling daylighting controls and assumes the prescriptive Secondary Daylit Control
requirements are met. PRESCRIPTIVE COMPLIANCE documentation (form NRCC-LTI-02-E) for the requirements of section 140.6(d) Automatic Daylighting Controls in Secondary Daylit Zones is
required.
The proposed building includes space(s) that are modeled with unknown HVAC system(s). Verify that the spaces modeled with unknown HVAC system(s) are either part of core and shell analysis
which will be permitted for mechanical compliance in the future, or the spaces have an existing HVAC system not modeled for compliance, or the compliance scope does not include mechanical.
E. HERS VERIFICATION
This Section Does Not Apply
F. ADDITIONAL REMARKS
None Provided
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
Project Name:
Dr. Elhajar TI
NRCC-PRF-01-E
Page 3 of 16
Project Address:
46-100 Washington Street La Quinta 92253
Calculation Date/Time:
12:18, Tue, Mar 06, 2018
Compliance Scope:
ExistingAlteration
Input File Name:
Elhajar DR. TI-LQ-GLA-17.cibdl6x
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
Identify which building components use the performance or prescriptive path for compliance. "NA"= not in project
For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans.
Building Component
Compliance Path
Compliance Forms (required for submittal)
Location of Mandatory Notes on
Plans
Envelope
® Performance
NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-ENV-01 / 02 / 03 / 04 / 05 / 06-E
❑ NA
Mechanical
❑ Performance
NRCC-PRF-MCH-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-MCH-01 / 02 / 03 / 04 / 05 / 06 / 07-E
® NA
Domestic Hot Water
❑ Performance
NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-PLB-01-E
❑ NA
Lighting (Indoor Conditioned)
® Performance
NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-LTI-01 / 02 / 03 / 04 / 05-E
❑ NA
Covered Process:
Commercial Kitchens
❑ Performance
S2 (section of the NRCC-PRF-01-E)
ElPrescriptive
NRCC-PRC Ol/03-E
® NA
Covered Process:
Computer Rooms
❑ Performance
S3 (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-PRC-01/ 04E
® NA
Covered Process:
Laboratory Exhaust
❑ Performance
S4 (section of the NRCC-PRF-01-E)
❑ Prescriptive
NRCC-PRC Ol/ 09-E
® NA
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
Project Name:
I Dr. Elhajar TI
NRCC-PRF-01-E
Page 4 of 16
Project Address:
46-100 Washington Street La Quinta 92253
Calculation Date/Time:
12:18, Tue, Mar 06, 2018
Compliance Scope:
ExistingAlteration
Input File Name:
Elhajar DR. TI-LQ-GLA-17.cibd16x
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
The following building components are only eligible for prescriptive compliance. Indicate which are
The following building components may have mandatory requirements per Part 6. Indicate
relevant to the project.
which are relevant to the project..
Yes NA
Prescriptive Requirement
Compliance Forms '
Yes NA
Mandatory Requirement
Compliance Forms
Lighting (Indoor
Commissioning: §120.8
❑ ®
Unconditioned) §140.6
NRCC-LTI-01 / 02 / 03 / 04 / 05-E
❑ ®
Simple Systems
NRCC-CXR-01 / 02 / 03 / 05-E
❑ ®
Complex Systems
NRCC-CXR-01 / 02 / 04 / 05-E
❑ ®
Lighting (Outdoor) §140.7
NRCC-LTO-01 / 02 / 03-E
❑ ®
Electrical: §130.5
NRCC-ELC-01-E
❑ ®
Lighting (Sign) §140.8
NRCC-LTS-01-E
❑ ®
Solar Ready: §110.10
NRCC-SRA-01 / 02-E
Covered Process: §120.6
NRCC-PRC-01-E
❑ ®
Parking Garage
NRCC-PRC-02-E
❑ ®
Solar Thermal Water
Ol E
❑ ®
Commercial Refrigeration
NRCC-PRC-05-E
Heating:NRCC-STH
§140.5
❑ ®
Warehouse Refrigeration
NRCC-PRC-06/07/08-E
❑ ®
Compressed Air
NRCC-PRC-10-E
❑ ®
Process Boilers
NRCC-PRC-11-E
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance
Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
•
Project Name:
Dr. Elhajar TI
NRCC-PRF-01-E
Page 5 of 16
Project Address:
46-100 Washington Street La Quinta 92253
Calculation Date/Time:12:18,
Tue, Mar 06, 2018
Compliance Scope:
ExistingAlteration
Input File Name:
I Elhajar DR. TI-LQ-GLA-17.cibdl6x
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component
Compliance Forms (required for submittal)
Pass
Fail
Envelope
® NRCI-ENV-01-E - For all buildings
E]
El
® NRCA-ENV-02-F- NFRC label verification for fenestration
❑
❑
Mechanical
❑ NRCI-MCH-01-E - For all buildings with Mechanical Systems
❑
❑
❑ NRCA-MCH-02-A- Outdoor Air
❑
❑
❑ NRCA-MCH-03-A — Constant Volume Single Zone HVAC
❑
❑
❑ NRCA-MCH-04-H- Air Distribution Dud Leakage
❑
❑
❑ NRCA-MCH-05-A- Air Economizer Controls
❑
❑
❑ NRCA-MCH-06-A- Demand Control Ventilation
❑
❑
❑ NRCA-MCH-07-A — Supply Fan Variable Flow Controls
❑
❑
❑ NRCA-MCH-08-A- Valve Leakage Test
❑
❑
❑ NRCA-MCH-09-A —Supply Water Temp Reset Controls
❑
❑
❑ NRCA-MCH-10-A- Hydronic System Variable Flow Controls
❑
❑
❑ NRCA-MCH-1I-A—Auto Demand Shed Controls
❑
❑
❑ NRCA-MCH-12-A- Packaged Direct Expansion Units
❑
❑
❑ NRCA-MCH-13-A- Air Handling Units and Zone Terminal Units
❑
❑
❑ NRCA-MCH-14-A- Distributed Energy Storage
❑
❑
❑ NRCA-MCH-15-A —Thermal Energy Storage
❑
❑
❑ NRCA-MCH-16-A- Supply Air Temp Reset Controls
❑
❑
❑ NRCA-MCH-17-A — Condensate Water Temp Reset Controls
❑
❑
❑ NRCA-MCH-18-A- Energy Management Controls Systems -
❑
❑
❑ NRCV-MCH-04-H- Duct Leakage Test
❑
❑
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component
Compliance Forms (required for submittal)
Pass
Fail
Plumbing
❑ NRCI-PLB-01-E - For all buildings with Plumbing Systems
❑
❑
❑ NRCI-PLB-02-E - required on central systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-PLB-03-E - Single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
ElNRCI-PLB-21-E - HERS verified central systems in high-rise residential, hotel/motel application.
❑
El
❑ NRCI-PLB-22-E - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCV-PLB-21-H- HERS verified central systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCV-PLB-22-H - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-STH-01-E - Any solar water heating
❑
❑
Indoor Lighting
® NRCI-LTI-01-E - For all buildings
❑
❑
❑ NRCI-LTI-02-E - Lighting control system, or for an Energy Management Control System (EMCS)
❑
❑
❑ NRCI-LTI-03-E - Line -voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to
energize only line -voltage track lighting
❑
❑
❑ NRCI-LTI-04-E - Two interlocked systems serving an auditorium, a convention center, a conference room, or a theater
❑
❑
❑ NRCI-LTI-05-E -Lighting Control Credit Power Adjustment Factor (PAF)
❑
❑
❑ NRCI-LTI-06-E - Additional wattage installed in a video conferencing studio
❑
❑
® NRCA-LTI-02-A - Occupancy sensors and automatic time switch controls.
❑
❑
® NRCA-LTI-03-A - Automatic daylighting controls
❑
❑
❑ NRCA-LTI-04-A - Demand responsive lighting controls
❑
❑
Outdoor Lighting
❑ N RCI -LTO -01-E —Outdoor Lighting
❑
❑
❑ NRCI-LTO-02-E- EMCS Lighting Control System
❑
❑
❑ NRCA-LTO-02-A -Outdoor Lighting Control
❑
❑
Sign Lighting
❑ NRCI-LTS-01-E—Sign Lighting
❑
❑
Electrical
❑ NRCI-ELC-01-E - Electrical Power Distribution
❑
❑
Photovoltaic
❑ NRCI-SPV-01-E Photovoltaic Systems
❑
❑
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
Project Name: Dr. Elhajar TI NRCC-PRF-01-E Page 7 of 16
Project Address: 46-100 Washington Street La Quinta 92253 Calculation Date/Time: 12:18, Tue, Mar 06, 2018
Compliance Scope: ExistingAlteration Input File Name: Elhajar DR. TI-LQ-GLA-17.cibdl6x
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component
Compliance Forms (required for submittal)
Pass
Fail
Covered Process
❑ NRCI-PRC-01-E Covered Processes
❑
❑ .
❑ NRCA-PRC-01-F- Compressed Air Systems
❑
❑
❑ NRCA-PRC-02-F- Kitchen Exhaust
❑
❑
❑ NRCA-PRC-03-F-Garage Exhaust
❑
❑
❑ NRCA-PRC-04-F- Refrigerated Warehouse- Evaporator Fan Motor Controls
❑
❑
❑ NRCA-PRC-05-F- Refrigerated Warehouse- Evaporative Condenser Controls
❑
❑
❑ NRCA-PRC-06-F- Refrigerated Warehouse- Air Cooled Condenser Controls
❑
❑
❑ NRCA-PRC-07F- Refrigerated Warehouse- Variable Speed Compressor
❑
❑
❑ NRCA-PRC-08-F- Electrical Resistance Underslab Heating System
❑
❑
t. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more information)
1.
Total Conditioned Floor Area
4,667 ft2
S.
Number of Floors Above Grade 1
Confirmed
2.
Total Unconditioned Floor Area
0 ft2
6.
Number of Floors Below Grade 0
V
N
=
3.
Addition Conditioned Floor Area 0 ft2
4.
Addition Unconditioned Floor Area 0 ft2
7. Opaque Surfaces & Orientation 8. Total Gross Surface Area 9. Total Fenestration Area 10. Window to Wall Ratio
North Wall
570 ft2
175 ft2
30.7%
❑
❑
East Wall
590 ft2
187 ft2
31.7%
❑
❑
South Wall
858 ft2
220 ft2
25.6%
❑
❑
West Wall
525 ft2
136 ft2
25.9%
❑
❑
Total
2,543 ft2
718 ft2
28.2%
❑
❑
Roof
4,667 ft2
0 ft2
00.0%
❑
❑
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
-0
Project Name
Project Address:
Compliance Scope
Dr. Elhajar TI
46-100 Washington Street La Quinta 92253
ExistingAlteration
NRCC-PRF-01-E Page 8 of 16
Calculation Date/Time: 12:18, Tue, Mar 06, 2018
Input File Name: Elhajar DR. TI-LQ-GLA-17.cibdl6x
•
J. FENESTRATION ASSEMBLY SUMMARY
§ 110.6
Confirmed
1.
2.
3.
4.
S.
6.
7.
8.
9.
Surface Name
Surface Type
Area (ft')
Framing
Type
Cavity
R -Value
Continuous
R -Value
U -Factor / F -Factor
/ C -Factor
d
C
N
�
N
T
R-19 Roof rafter6
Roof
Fenestration Assembly Name /
Fenestration Type / Product Type1
19
NA
U -Factor: 0.052
Overall
Overall
Overall
d
ExteriorWall
2543
Wood
11
Certification Method'
Assembly Method
Area ft
❑
❑
Slab On Grade34
Underground Floor
4667
NA
Tag or I.D.
/ Frame Type
F -Factor: 0.730
E
❑
U-factor
SHGC
VT
N
Vertical Fenestration
Single Metal Tinted
Fixed Window
Default Performance
SiteBuilt
605
1.04
0.63
0.77
E
❑
❑
NonMetalFraming
Vertical Fenestration
Dual Metal Tinted
OperableWindow
NFRC Rated
Manufactured
113
0.52
0.39
0.50
A
❑
❑
N/A
' Newly installed fenestration shall hove a certified NFRC Label Certificate or use the CEC default tables found in Toble 110.6-A and Table 110.6.8. Center of Gloss (COG) values are for the gloss -only, determined by the manufacturer, and are shown for ease
of verification. Site -built fenestration values are calculated per Nonresidential Appendix NA6 and are used in the analysis.
1 Status: N - New, A -Altered, E- Existing '
Taking compliance credit for fenestration shading devices? (if "Yes", see NRCC-PRF-ENV-DETAILS for more information) No
K. OPAQUE SURFACE ASSEMBLY SUMMARY
§ 120.7/ § 140.3
Confirmed
1.
2.
3.
4.
S.
6.
7.
8.
Surface Name
Surface Type
Area (ft')
Framing
Type
Cavity
R -Value
Continuous
R -Value
U -Factor / F -Factor
/ C -Factor
d
C
N
�
N
T
R-19 Roof rafter6
Roof
4667
Wood
19
NA
U -Factor: 0.052
E
❑
❑
Default Wa118
ExteriorWall
2543
Wood
11
NA
U -Factor: 0.110
E
❑
❑
Slab On Grade34
Underground Floor
4667
NA
0
NA
F -Factor: 0.730
E
❑
❑
' Status: N -New, A -Altered, E -Existing
L. ROOFING PRODUCT SUMMARY
§ 140.3
Confirmed
1.
2.
3.
4.
5.
6.
7.
ProductType
Product Density
Aged Solar
Thermal
SRI
Cool Roof
Roofing Product
�
T
-
1
(Ib/ft)
Reflectance
Emittance
Credit
Description
R-19 Roof rafter6
5.895
0.08
0.75
NA
No
NA
❑
❑
M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information) § 110.1 / § 110.2
Dry System Equipment Section Does Not Apply
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
Project Name: Dr. ElhajarTl NRCC-PRF-01-E Page 9 of 16
Project Address: 46-100 Washington Street La Quinta 92253 Calculation Date/Time: 12:18, Tue, Mar 06, 2018
Compliance Scope: ExistingAlteration Input File Name: Elhajar DR. TI-LQ-GLA-17.cibdl6x
Wet System Equipment Section Does Not Apply
V. ECONOMIZER & FAN SYSTEMS SUMMARY' § 140.4
'his Section Does Not Apply
0. EQUIPMENT CONTROLS § 120.2
Fhis Section Does Not Apply
3. SYSTEM DISTRIBUTION SUMMARY § 120.4/ § 140.4(i)
rhis Section Does Not Apply
Multifamily or Hotel/ Motel Occupancy? (if "Yes", see NRCC-PRF-MCH-DETAILS for DHW system information) No
Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info)'
§ 140.6
Confirmed
1.
2.
3.
4.
S.
1
Occupancy Type
Conditioned Floor Area 2
Installed Lighting Power
Lighting Control Credits
Additional (Custom) Allowance
V
Nfu
T
(ft2)
(Watts)
(Watts)
Area Category Footnotes
Tailored Method (Watts)
❑
❑
(Watts)
Medical and Clinical Care
4,667
2,530
0
0
0
❑
❑
Building Totals:
4,667
2,530
0
0
0
'See Table 140.6-C
2 See NRCC-LTI-01-E for unconditioned spaces
3Lighting information for existing spaces modeled is not included in the table
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
Project Name: Dr. Elhajar TI NRCC-PRF-01-E Page 10 of 16
Project Address: 46-100 Washington Street La Quinta 92253 Calculation Date/Time: 12:18, Tue, Mar 06, 2018
Compliance Scope: ExistingAlteration Input File Name: Elhajar DR. TI-LQ-GLA-17.cibdl6x
R. INDOOR CONDITIONED LIGHTING SCHEDULE (Adapted from NRCC-LTI-01-E)t
§ 130.0
Luminaire Schedule (includes all permanent installed lighting in
Proposed Design Site
(MWh)
Margin
(MWh)
conditioned space, and portable lighting over 0.3 w/ftz in
Installed Watts (Conditioned)
Confirmed
offices)
--
--
--
Complete Luminaire Description (i.e.,
2.5
How Wattage is Determined
Space Cooling
28.3
26.7
1.6
Name or Item Ta
Tag
3 -lam fluorescent troffer, F32T8,
P
Watts per luminaire
P
Total Number
Luminaires
Installed Watts
Pass
Fail
CEC Default
According to
-- d
one dimmable electronic ballast)
from NAB
§130.0(c)
2X4 LED
34 W LED
34
Yes
No
58
1,972
❑
❑
Can LED
18 W LED
18
Yes
No
31
558
❑
❑
'If lighting power densities were used in the compliance model Building Departments will need to check prescriptive forms for Luminaire Schedule details.
Sl. COVERED PROCESS SUMMARY — ENCLOSED PARKING GARAGES § 140.9
This Section Does Not Apply
S2. COVERED PROCESS SUMMARY — COMMERCIAL KITCHENS § 140.9
This Section Does Not Apply
S3. COVERED PROCESS SUMMARY— COMPUTER ROOMS § 140.9
This Section Does Not Apply
S4. COVERED PROCESS SUMMARY — LABORATORY EXHAUSTS § 140.9
This Section Does Not Apply
r. UNMET LOAD HOURS
This Section Does Not Apply
U. ENERGY USE SUMMARY
Energy Component
Standard Design Site
(MWh)
Proposed Design Site
(MWh)
Margin
(MWh)
Standard Design Site
(MBtu)
Proposed Design Site
(MBtu)
Margin
(MBtu)
Space Heating
--
--
--
1.9
2.5
-0.6
Space Cooling
28.3
26.7
1.6
--
--
--
Indoor Fans
29.2
26.7
2.5
--
-- d
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
L -I
Project Name: -
Dr. Elhajar TI
NRCC-PRF-01-E
Page 11 of 16
Project Address:
46-100 Washington Street La Quinta 92253
Calculation Date/Time:
12:18, Tue, Mar 06, 2018
Compliance Scope:
ExistingAlteration
Input File Name:
I Elhajar DR. TI-LQ-GLA-17.cibdl6x
U. ENERGY USE SUMMARY
Energy Component
Standard Design Site
(MWh)
Proposed Design Site
(MWh)
Margin
(MWh)
Standard Design Site
(MBtu)
Proposed Design Site
(MBtu)
Margin
(MBtu)
Heat Rejection
Pumps & Misc.
-_
--
--
Domestic Hot Water
--
--
--
23.6
23.6
0.0
Indoor Lighting
15.7
7.1
8.6
--
--
--
COMPLIANCE TOTAL
73.2
60.5
12.7
25.5
26.1
-0.6
Receptacle
21.3
21.3
0.0
14.5
14.5
0.0
Process
--
--
--
--
--
Other Ltg
Process Motors
--
--
--
--
--
--
TOTAL
94.5
81.8
12.7
40.0
40.6
-0.6
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
§ 10-103
1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Tim Scott
Signature:
Company: Scott Design and Title 24, Inc,
Address: 74-818 Velie Way, Suite #8
Signature Date:
City/State/Zip: Palm Desert CA 92260
CEA Identification (If applicable):
Phone: (760) 200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1
I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am
licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
2
1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3 to sign this document as the person responsible for its
preparation; and that I am a licensed contractor performing this work.
3
'affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document becaus ains to a structure or type of work described as exempt pursuant to
Business and Professions Code Sections 5537, 5538 and 6737.1.
Responsible Envelope Designer Name: Gabriel Lujan
Company: Gabriel Lujan & Associates
ignature:
Address: 77-530 Enfield Lane, Suite 101
Date Signed:
City/State/Zip: Palm Desert CA 92211
Declaration Statement Type:
Phone: (760) 578-8545
Title: License #:
Responsible Lighting Designer Name: Gabriel Lujan
Company: Gabriel Lujan & Associates
ignature:
Address: 77-530 Enfield Lane, Suite 101
Date Signed:
City/State/Zip: Palm Desert CA 92211
Declaration Statement Type:
Phone: (760) 578-8545
Title: License #:
Responsible Mechanical Designer Name: Tim Scott
Company: Scott Design and Title 24, Inc.
Signature: NOT IN SCOPE
Address: 74-818 Velie Way, Suite #8
Date Signed:
City/State/Zip: Palm Desert CA 92260
Declaration Statement Type:
Phone: (760) 200-4780
Title: License #:
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
Project Name: Dr. Elhajar TI NRCC-PRF-01-E Page 13 of 16
Project Address: 46-100 Washington Street La Quinta 92253 Calculation Date/Time: 12:18, Tue, Mar 06, 2018
Compliance Scope: ExistingAlteration Input File Name: Elhajar DR. TI-LQ-GLA-17.cibdl6x
NRCC-PRF-ENV-DETAILS -SECTION START
A. OPAQUE SURFACE ASSEMBLY DETAILS
Confirmed
1.
2.
3.
4.
d
—
Surface Name
Surface Type
Description of Assembly Layers
Notes
Door Type
Certification Method
Asphalt shingles - 1/4 in.
Area
Overall
LI -factor
status'
Pass
Fail
Vapor permeable felt - 1/8 in.
WoodGreaterThanOrEqualTol.75inThickDoor
DefauItPerformance
Swinging
R-19 Roof rafter6
Roof
Plywood - 1/2 in.
❑
❑
❑
Air - Cavity - Wall Roof Ceiling - 4 in. or more
Wood framed roof, 16in. OC, 5.5in., R-19
Gypsum Board -1/2 in.
Stucco - 7/8 in.
Default Wall8
ExteriorWall
Vapor permeable felt - 1/8 in.
❑
❑
Wood framed wall, 16in. OC, 3.5in., R-11
Gypsum Board - 1/2 in.
Slab Type = UnheatedSlabOnGrade
Slab On Grade34
UndergroundFloor
Insulation Orientation = None
❑
❑
Insulation R -Value = RO
B. OVERHANG DETAILS (Adapted from NRCC-ENV-02-E)
This Section Does Not Apply
C. OPAQUE DOOR SUMMARY
Confirmed
1.
2.
3.
4.
S.
6.
7.
Opaque Door Assembly Name
/ Tag or I.D.
Door Type
Certification Method
Operation
Area
Overall
LI -factor
status'
Pass
Fail
Wood Door13
WoodGreaterThanOrEqualTol.75inThickDoor
DefauItPerformance
Swinging
61
0.500
E
❑
❑
I Status: N -New, A—Altered, E— Existing
NRCC-PRF-MCH-DETAILS -SECTION START
A. MECHANICAL VENTILATION AND REHEAT (Adapted from 2016-NRCC-MCH-03-E)
This Section Does Not Apply
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
Project Name: Dr. Elhajar TI NRCC-PRF-01-E Page 14 of 16
Project Address: 46-100 Washington Street La Quinta 92253 Calculation Date/Time: 12:18, Tue, Mar 06, 2018
Compliance Scope: ExistingAlteration Input File Name: Elhajar DR. TI-LQ-GLA-17.cibdl6x
B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY
This Section Does Not Apply
C. EXHAUST FAN SUMMARY
This Section Does Not Apply
D. DHW EQUIPMENT SUMMARY — (Adapted from NRCC-PLB-01)
This Section Does Not Apply
E. MULTI -FAMILY CENTRAL DHW SYSTEM DETAILS
This Section Does Not Apply
F. SOLAR HOT WATER HEATING SUMMARY (Adapted from NRCC-STH-03)
This Section Does Not Apply
G. MECHANICAL HVAC ACCEPTANCE TESTS & FORMS (Adapted from 2016-NRCC-MCH-01-E) § RA4
This Section Does Not Apply
H. EVAPORATIVE COOLER SUMMARY
This Section Does Not Apply
NRCC-PRF-LTI-DETAILS -SECTION START-
A.
TART
A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E)
§ 140.6
Lighting Control Credits Schedule (includes all lighting controls installed in conditioned space for
Control Credit Calculation
Confirmed
compliance credit per §140.6(a)2 and Table 140.6-A)
V If Acceptance
Test Required
q
Location in
Occupancy Type (must meet
Type/Description of Lighting
Watts of
Power
Control Credit
Building
requirements of Table 140.6-A)
Control (i.e., partial on occupancy
# of Units
Controlled
Adjustment
Watts
sensor, manual dimming, etc.)
Lighting
Factor
Pass
Fail
S -1 -Tenant
Medical and Clinical Care
-none specified
1
0.00
0
❑
El
Improvement
S -1 -Tenant
Medical and Clinical Care
none specified
1
0.00
0
❑
❑
Improvement
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-06 12:18:28
Project Name:
Dr. Elhajar TI
NRC&PRF-01-E
Page 15 of 16
Project Address:
46-100 Washington Street La Quinta 92253
Calculation Date/Time:
12:18, Tue, Mar 06, 2018
Compliance Scope:
ExistingAkeration
Input File Name:
Elhajar DR. TI-LQ-GLA-17.cibdi6x
B. INDOOR CONDITIONED LIGHTING MANDATORY LIGHTING CONTROLS (Adapted from NRCC-LTI-02-E) § 130.1
This Section 1%QPL11940
w
130.1(0) =Manual area controls; §13�lulti Levet §130.1jc% =Auto Shut -Off, §130.1%d% = Mondotoryi)?Anr.• §130.1jej =Demand Responsive
C. TAILORED METHOD CONDITIONED LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-LTI-04-E) § 140.6
General lighting power (see Table D) 0
General lighting power from special function areas (see Table E)
NA
Additional "use it or lose it" (See Table G) 0
Total watts 0
D. GENERAL LIGHTING POWER (Adapted from NRCC-LTI-04-E) § 140.6-D
This Section ' A PP L r ES . "1.k
E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E)
§ 140.6(c) 3H
Room Number
Primary Function Area
Illuminance Value
(LUX)
Room Cavity Ratio
(Table G)
Allowed LPD
Floor Area (ft')
Allowed Watts
Confirmed
Pass Fail
NA
Nnf-• T -:l-.-.1 AA -.AM f .
NA
f --.:..I L....Nlw- ....... .. --. _..__-_v., r�-r____._�
NA
NA
NA
NA
NA
❑ ❑
F. ROOM CAVITY RATIO (Adapted from NRCC-LTI-04-E)
Rectangular Spaces
Room Number
Task/Activity Description
Room length (ft) Room Width (ft)
Room Cavity Height (ft)
RCR Confirmed
Pass Fail
NA
NA
NA NA
NA
NA ❑
❑
Non -Rectangular Spaces
This Section Does Not Apply
At- .11 --- 1:...4.1.. A- AI -.._o-..---..1-_ ��--- .-Ar-
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-0612:18:28
Project Name:
Dr. Elhajar TI
NRCC PRF -01-E
Page 16 of 16
Project Address:
46-100 Washington Street La Quinta 92253
Calculation Date/Time:
12:18, Tue, Mar 06, 2018
Compliance Scope:
ExistingAlteration
Input File Name:
Elhajar DR. TI-LCI-GLA-17.cibd16,x
G. ADDITIONAL"USE IT OR LOSE.IT" (Adapted from NRCC-LTI-04-E)
1.
2.
3.
4.
Allowed Watts
Confirmed
Wall Display
p y
Combined Floor Display and Task
LightingEffects
Combined Ornamental and Spedal
Lighting
Very Valuable Merchandise
v T
N d
0
0.
0
0
0
Outdoor Controls
5. Wall Display
This Section Does Not Apply
6. Floor Display and Task Lighting
This Section Does Not Apply
7. Combined Ornamental and Special Effects Lighting
This Section Does Not Apply
B. Very Valuable Merchandise
This Section Does Not Apply
H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-LTO-01-E)
§ 130.4
Declaration of Required Acceptance Certificates (NRCA) —Acceptance Certificates that must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for
Field Inspector to verify).
Test Description
Indoor .
Outdoor
Confirmed
NRCA-LTI-02-A
NRCA-LTI-03-A
NRCA-LTI-04-A
NRCA-LTO-02-A
Equipment. Requiring # of units
Testing or Verification
Occ Sensors / Auto Time
Switch
Auto Daylight
Demand Responsive
Outdoor Controls
N
N
Occupant Sensors 0
®
❑
El
0
Automatic Time Switch 0
®
0
El
Automatic Daylighting 0
❑
E
Demand Responsive 0
C1
El
1
Outdoor Controls 0
1
11
1
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-122020178-5302 Report Generated at: 2018-03-0612:18:28
AL
•
0
ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV -MM
Project Name
Date
Desert Neurology & Sleep TI
3/6/2018
DESCRIPTION
Building Envelope Measures:
§110.8(a):
Installed insulating material shall have been certified by the manufacturer to comply with the California Quality
Standards for insulating material, Title 20 Chapter 4, Article 3.
§110.8(c):
All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of
Sections 2602 and 707 of Title 24, Part 2.
§110.8(g):
Heated slab floors shall be insulated according to the requirements in Table 110.8-A.
§110.7(a):
All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed,
weatherstripped or otherwise sealed.
Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.2 of
§110.6(a):
window area, 0.3 cfm/ft.2 of door area for residential doors, 0.3 cfm/ft.2 of door area for nonresidential single doors
(swingingand sliding), and 1.0 cfm/ft.2 for nonresidential double doors (swinging).
§110.6(a):
Fenestration U -factor shall be rated in accordance with NFRC 100, or the applicable default U -factor.
§110.6(a) :
Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the
applicable default SHGC.
§110.6(b):
Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be
weatherstripped (except for unframed glass doors and fire doors).
The opaque portions of the roof/ceiling that separates conditioned spaces from unconditioned spaces or ambient air
shall meet the applicable U -Factor requirements as follows:
§120.7(a):
Metal Building- The weighted average U -factor of the roof assembly shall not exceed 0.098.
Wood Framed and Others- The weighted average U -factor of the roof assembly shall not exceed 0.075.
The opaque portions of walls that separate conditioned spaces from unconditioned spaces or ambient air shall meet the
applicable U -factor as follows:
Metal Building- The weighted average U -factor of the wall assembly shall not exceed 0.113.
Metal Framed- The weighted average U -factor of the wall assembly shall not exceed 0.151.
Light Mass Walls- A 6 inch or greater Hollow Core Concrete Masonry Unit shall have a U -factor not to exceed 0.440.
§120.7(b):
Heavy Mass Walls- An 8 inch or greater Hollow Core Concrete Masonry Unit shall have a U -factor not to exceed
0.690.
Wood Framed and Others- The weighted average U -factor of the wall assembly shall not exceed 0.110.
Spandrel Panels and Opaque Curtain Wall- The weighted average U -factor of the spandrel panels and opaque
curtain wall assembly shall not exceed 0.280.
Demising Walls-. The opaque portions of framed demising walls shall meet the requirements of Item A or B below:
A. Wood framed walls shall be insulated to meet a U -factor not greater than 0.099.
B. Metal Framed walls shall be insulated to meet a U -factor not greater than 0.151.
The opaque portions of floors and soffits that separate conditioned spaces from unconditioned spaces or ambient air
shall meet the applicable U -Factor requirements as follows:
§120.7(c):
Raised Mass Floors- Shall have a minimum of 3 inches of lightweight concrete over a metal deck or the weighted
average U -factor of the floor assembly shall not exceed 0.269.
Other Floors -The weighted average U -factor of the floor assembly shall not exceed 0.071.
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Desert Neurology & SleepTl
Date
3/6/2018
System Name
HVAC
Floor Area
4,667
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
3
COIL
CFM
Total Room Loads 6,844
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 700
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 69,000
101,080
7,234 5,121
63,298
Total Out utBtuh 207,000
0
Output Btuh/s ft 44.4
5,054
3,165
Cooling System
0
0
Output per System 71,000
26,329
5,749 700
33,963
Total Output Btuh 213,000
0
5,054
1 137,516 12,983
0
Total Output Tons 17.8
3,165
Total Output Btuh/s ft 45.6
Total Output s ftrron 262.9
103,590
Air System
CFM per System
2,400
HVAC EQUIPMENT SELECTION
Airflow cfm
7,200
Existing Package units 142,781 53,263
129,287
Airflow cfm/s ft
1.54
Airflow cfmrron
405.6
Outside Air %
9.7%
Total Adjusted System Output 142,781 53,263
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK Aug 3 PM
129,287
Outside Air cfm/s ft 0.15
Jan 1 AM
Note: values above given at ARI conditions I
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 67 OF
Outside Air
700 cfm Supply Fan
7,200 cfm
72 OF
67 OF 84 OF
Heating Coil 84 OF
ROOM
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 80/67°F 80/67°F 61/60°F
0
Outside Air
700 cfm Supply Fan Cooling Coil 62 / 61 OF
7,200 cfm
58.0% ROOM IN
77/66°F 76/66°F
U -T- 1
EnergyPro7.2 by EnergySoff User Number: 6712 ID: Page 20 of 21
ZONE •SUMMARY
Project..-
Neurology & SleepTl
31612018
System Name
FloorDesert
..
ZONE LOAD
ZONAL••
ILI SYSTEM NAME
Tenant Improvement
. -. •
•