CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG— 1—A
PROJECT NAME CIRCLE K 0457
DATE
_1
PROJECT ADDRESS
78110 CAME TAMPICo, LA OUIHTA, CA 92253
Checkedtry/Date
Enforcement Agen Use
BUILDING TYPE ® NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑. HOTEL/MOTEL GUEST ROOM
TESTING AUTHORITY
TELEPHONE
GENERAL INFORMATION
DATE OF BLDG. PERMIT
PERMIT # '
BLDG. CONDITIONED FLOOR AREA
3190
CLIMATE ZONE
BUILDING TYPE ® NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑. HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION NEW CONSTRUCTION ❑ ADDITION ® ALTERATION ❑ UNCONDITIONED SPACES
STATEMENT OF COMPLIANCE I
This Certificate of Acceptance summarizes the results of the acceptance tests related to building mechanical requirements
.per Title 24, Part 6. (Section 10-103.b, 121.f, 122.h, 125.a, 125.b, 125.c, 125.0.5, 125.d)
Please check one:
I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this
document as the person responsible for its preparation; and that I am licensed in the State of California as a civil
engineer or electrical engineer, or I am a licensed architect.
® I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or
6737.3 to sign this document as the person responsible for its ,preparation; and that I am a licensed. contractor
performing this work.
❑ I affirm that I am eligible under Div' ion 3 of the Business and Professions Code to sign this document because it
pertains to a structure or type of wo described as exempt pursuant to Business and Professions Code Sections
5537, 5538 and 6737.1.
(These sections of the Business and P fessions Code are printed in full in the Nonresidential Manual)
TESTING AUTHORITY — NAME SIGMA E DATE UC.
06 t,
INSTRUCTIONS TO APPLICANT I
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please• refer to the
Nonresidential Manual published by the California Energy Commission.
Part 1 of 3 — Statement of Acceptance
Part 2 of 3 — Summary of Acceptance Tests
Part 3 of 3 — Summary -of Acceptance Testing Results
D
L
CERTIFICATE OF ACCEPTANCE (Part 2 of 3) LTG -1 —A
PROJECT NAME •
CIRCLE K #457
STATEMENT OF COMPLIANCE
SYSTEM ACCEPTANCE DOCUMENT
(From of )
TESTING AUTHORRY
DATE OF TEST
PASS / FAIL
NOTES Bldg.
Dept. Use
NOTE. • Use additional sheets as necessary
Certified
N/A
CERTIFICATE OF ACCEPTANCE (Part 3 of 3) LTG -1 —A
Q
PROJECT NAME
CIRCLE K. {457
The occupant sensors with ultrasonic radiation. as a signal for
sensing occupants shall
The occupant sensors with microwave- radiation as a signal. for
sensing occupants shall
Automatic Daylighting Controls
SUMMARY OF ACCEPTANCE TESTING RESULTS
The continuous dimming control systems meet the requirements
of Section 119(e)
13
stepped dimming control systems meet the requirements ' '
of
of Section 119(e)
�.
,p(
YAl
The stepped switching control systems meet the requirements
of Section 119(e)
Automatic Time Switch Controls
E:]
The automatic time switch control devices meet the requirements .
of 119(e)
Manual Daylighting Controls
�
The manual daylighting controls meet the requirements of:..
Certified
N/A
Q
Certified
N/A
Occupant & Motion Sensors
Q
�
The occupant sensors with ultrasonic radiation. as a signal for
sensing occupants shall
The occupant sensors with microwave- radiation as a signal. for
sensing occupants shall
Automatic Daylighting Controls
�
The continuous dimming control systems meet the requirements
of Section 119(e)
13
stepped dimming control systems meet the requirements ' '
of
of Section 119(e)
�.
,p(
YAl
The stepped switching control systems meet the requirements
of Section 119(e)
Automatic Time Switch Controls
E:]
The automatic time switch control devices meet the requirements .
of 119(e)
Manual Daylighting Controls
�
The manual daylighting controls meet the requirements of:..
CERTIFICATE OF COMPLIANCE
(Part 1 of
4) LTG— 1—C
PROJECT NAME
CIRCLE K 0457
Certificate of compliance. Part 3 of 4 submittals are required only if Control Credits are claimed.
E3 LTG -1-C, Parts 4 of 4
DATE
9-08-6
PROJECT ADDRESS
78110 CALLS TAMPICO, LA QUINTA, CA 92253
Interior Lighting Schedule.
❑ LTG -3-C
Building Permit d
Checked by/Date
Enforcement Ageney Use
PRINCIPAL DESIGNER-uGHnNG
WALTER D. CAMP
TI]FPHONE
619-934-1815
E3 LTG -5-C
DOCUMENTATION AUTHOR
WALTER D. CAMP
TELEPHONE
619-934-1815
Tailored Method Worksheet.
GENERAL INFORMATION
Room Cavity Ratio Worksheet.
❑ LTG -8-C
DATE OF PLANS 6-23-6 BUILDING CONDITIONED FLOOR AREA 1590
CLIMATE ZONE -
BUILDING TYPE ® NONRESIDENTIAL
❑ HIGH RISE RESIDENTIAL
❑ HOTEL/MOTEL GUEST ROOM
CONDITIONED SPACES
❑ UNCONDITIONED SPACES
❑ INDOOR/OUTDOOR SIGNS
PHASE OF CONSTRUCTION ❑ NEW
❑ ADDITION ® ALTERATION
METHOD OF COMPLIANCE
❑ PERFORMANCE ❑ COMPLETE BLDG. ® AREA CATEGORY ❑ TAILORED ❑ COMMON LIGHTING
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and pertormance speclrlcauons neeaea to compry wlm 11UC I.,, rulw
and 6 of the California Code of Regulations. This certificate applies only to building lighting requirements.
The documentation preparer hereby certifies that the clcumentation is acc rate and complete.
DOCUMENTATION AUTHOR SIGNATURE DATE
WALTER D. CAMP - 9-08-06
The Principal Lighting Designer hereby certifies that the proposed building design represented in this set of construction documents
is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations
submitted with this permit application. The proposed building has been designed to meet the lighting requirements
contained in the applicable parts of Sections 110, 119, 130 through 132, 146, 148, and 149 of Title 24, Part 6.
® The plans & specifications meet the requirements of Part 6 (Sections 10-1030).0 The installation certificates meet
the requirements of Part 6 (Sections 10-103a 3).
❑ The operation & maintenance information meet the requirements of Part 6 (10-103c).
Please check one: (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual).
® 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this
document as the person responsible for its preparation; and that I am licensed in the State of California as a civil
engineer or electrical engineer, or I am a licensed architect.
❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or
6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor
performing this work.
❑ I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it
pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections
5537, 5538 and 6737.1.
PRINCIPAL— SIGNATURE DAAC'
WALTER D. CAMP 9-08-06 E07061
LIGHTING MANDATORY MEASURES
177Y Indirnte location on alans of Note Block for Mandatory Measures SHEET T-24
LIGHTING COMPLIANCE FORMS & WORKSHEETS (check box if worksheet is included)
E3 LTG -1-C, Parts 1 of 4 and 2 of
4 Certificate of compliance. Part 1 of 4 and 2 of 4 are required for all submittals.
❑ LTG -1-C, Parts 3 of 4
Certificate of compliance. Part 3 of 4 submittals are required only if Control Credits are claimed.
E3 LTG -1-C, Parts 4 of 4
Certificate of compliance. Part 4 of 4 submittals are required when lighting controls are installed.
E3 LTG -2-C
Interior Lighting Schedule.
❑ LTG -3-C
Portable Lighting Worksheet.
❑ LTG -4-C
Lighting Control Credit Worksheet.
E3 LTG -5-C
Interior Lighting Power Allowance.
❑ LTG -6-C
Tailored Method Worksheet.
❑ LTG -7-C
Room Cavity Ratio Worksheet.
❑ LTG -8-C
Common Lighting Systems Method Worksheet.
❑ LTG -9-C
Line Voltage Track Lighting Worksheet.
E3 OLTG-4-C
Signs (See 0LTG-4-C Sign Worksheet in Chapter 6, Outdoor lighting and Signs Chapter).
2005 Nonresidential Compliance Forms APR/L 2005
CERTIFICATE OF COMPLIANCE (Part 2 of 4) LTG— 1—C
PRQIECT NAME CIRCLE K #457 SATE 9-08-06
INSTALLED INTERIOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES
INSTALLED LIGTHING, CONDITIONED SPACES
PORTABLE LIGHTING
LIGHTING CONTROL CREDIT, CONDITIONED SPACES
CONDITIONED SPACE ADJUSTED INSTALLED
INSTALLED LIGTHING, UNCONDITIONED SPACES
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES
UNCONDITIONED SPACE ADJUSTED INSTALLED
(From LTG -2—C)
(From LTG -3—C)
(From LTG -4—C)
LIGHTING POWER.
(From LTG -2—C)
(From LTG --:4—C)
LIGHTING POWER
INSTALLED
WATTS
2448
+ —
— —
= 2448
TS 0
—
— —
= —
ALLOWED INTERIOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -5—C)
E3 AREA CATEGORY METHOD (From LTG -5—C) ALLOWED
WATTS
❑ TAILORED METHOD (From LTG -5—C)
ALLOWED, LIGHTING POWER 2703
ALTERNATE COMPLIANCE
❑ PERFORMANCE METHOD
❑, COMMON LIGHTING SYSTEM (From LTG -8—C)
ALLOWED INTERIOR LIGHTING POWER -FOR UNCONDITIONED SPACES (From LTG -5—C) watts
MANDATORY LIGHTING MEASURES FOR INTERIOR LIGHTING AND 'DAYLIT AREAS
MANDATORY INTERIOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION
(Room #, Area #, or
Description)
CONTROL
IDENTIFICATION
CONTROL TYPE
(Auto Time Switch,
Dimming
Photosensor, etc.)
SPACE CONTROLLED
. Lists the Location of
Controlled Lights
If Control is
for
Daylighting
NOTE TO
FIELD
BACK STORAGE
TS 0
AUTO TIME
ENTIRE
ROOM
S
SWITCH
STORE
/
ROOF
PE
PHOTO CELL
EXTERIOR
LIGHTING
& SIGNS
__APRIL 2005
2005 Nonresidential Compliance Forms
CERTIFICATE OF COMPLIANCE (Part a of a) LTG -1 —C
2005
APRIL
2005 Nonresidential Compliance Forms
PROJECT NAME I DATE
CLE K #4579-08-06
Designer:
This form is to be used by the designer and attached to the plans. listed below are all the acceptance tests for lighting systems. The
designer is required to check the boxes by all acceptance tests that apply and list all equipment that require an acceptance test. If all
. equipment ofa certain type requires a test, list the equipoment description and the number of. systems to be tested in parentheses. The
NJ number designates the Section in the Appendix of .the Nonresidential ACM Manual that describes the test. Also indicate the
person reasponsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner).
Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building, Departments:
Systems acceptance. Before an occupancy permit is granted for a newly constructed building or space, or a new . space—conditioning
systems serving a building or space is operated for normal. use, all control devices. serving the building or space shall be certified as
meeting the Acceptance Requirements for. Code Compliance. in additon a- Certificate of Acceptance, MECH—I—A, Forms shall be
submitted .to the building department that:
A. Certifies plans, specifications, installation certificates; and operating and maintenance information meet the requirements of
paragraph 10-103(b) and Title 24 Part 6.
Test Description
Test Performedd by:
LTG -2—A: Lighting Control Acceptance Document
Occupancy Sensor Acceptance
[� Manual Daylight Controls Accceptance
• Automatic Time _Switch Control Acceptance
Equipment requiring acceptance testing by installing Contractor Manual Daylight. Controls
•
�i ❑ LTG -3—A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing by installing Contractor
2005 ACCEPTANCE REQUIREMENTS .FOR CODE COMPLIANCE
Lighting. Control Acceptance Document LTG -2—A
Form 1 of 2
PROJECT NAME DATE
gRgF K /457 � i g-
A. Select Acceptance Test (Indicate lighting control systems Names / Designations by the applicable test below)
❑
1
Occupancy Sensor
❑
2
Manual. Daylighting Controls
❑
3
Automatic Time Switch Controls
Alnfu• Qhnrfoff nrens do not DDDiv for DORIDWar rest pro auuic
C. PASS / FAIL Evaluation (Check one) .
Applicable Lighting
Control Systems
B. Equipment Testing Requirements
Check and verify those items applicable to selected systems
1
2
3
Occupancy Sensor — Step 1: Simulate an unoccupied condition
response in any applicable equipment testing requirements section. Provide explanation below. Use and attach
additional pages if necessary.
a.
Lights controlled by occupancy sensors tum off within a maximum of 30 minutes
from start of an occupied condition per Standard Section 119(d).
b.
The occupant sensor does not trigger a false "on" from movement in an area
adjacent to the controlled space or from HVAC operation
C.
Signal sensitivity is adequate to achieve desired control
Step 2: Simulate on occupied condition
a.
Status indicator or annunciator operates correctly
b.
Lights controlled by occupancy sensors tum on when immediate upon an occupie
condition OR (this requirement is mutually exclusive with Step 2.c)
C.
Sensor indicates space is. "occupied" and lights turn on manually
Step 3: System returned to initial operating conditions
Manual Daylighting Controls — Step 1: Manual Switching Control
a.
At least 50% of lighting power in daylit areas is separately controlled from other
lights
b.
The amount of light delivered to the space is uniformly reduced
Step 2: System returned to initial operating conditions
Automatic Time Switch Controls -- Step 1: Manual Switching Control
a.
All lights can be turned on and off by their, respective area control switch
b.
Verify the switch only operates lighting in the ceiling—height partitioned area in
which the switch is located
Step 2: Simulate an unoccupied condition
a.
All non—exempt lighting turns off per Section 131(d)l
b.
IManual 'override switch allows only the lights in the selected ceiling height
partitioned space where the override switch is located, to turn on or remain on
until the next scheduled shut off occurs
c.
I All non—exempt lighting turns off
Step 3: System returned to initial operating conditions
Alnfu• Qhnrfoff nrens do not DDDiv for DORIDWar rest pro auuic
C. PASS / FAIL Evaluation (Check one) .
PASS: All applicable construction inspection responses are complete and all applicable equipment testing requirements
❑
responses are positive (Y = yes).
FAIL: Any applicable construction inspection responses are incomplete OR there is one or more negative (N = no)
❑
response in any applicable equipment testing requirements section. Provide explanation below. Use and attach
additional pages if necessary.
2005' ACCEPTANCE REQUIREMENTS FOR CODE COMPLIANCE
Lighting Control Acceptance Document LTG -2—A
From 2 of •2 ,
PROJECT NAME
DATE '
. CIRCLE K #457
V ,
PROJECT. ADDRESS
49594 29 PALMS HYYY, MORONGO VALLEY.. CA 92256 ,
TESTING AUTHORITY
LIGHTING CONTROL SYSTEM NAME / DESIGNATION
Check by Date ❑ Enforcement Agency Use
'
Intent I Lights are turned off when not needed per 119(d) 6 131(d)
Construction Insoection
1. Instruction to perform test includes, but limited to:
a. Light meter
b. Hand-held amperage and voltage meter
C. Power meter
2. Occupancy Sensor Construction Inspection
Cl -Occupancy sensor has been located to minimize false signals
❑ Occupancy sensors do not encounter any obstructions that could• adversely affect desired performance
❑ Ultrasonic occupancy sensors do not emit audible sound (119a) 5 feet from source
3. Manual Daylighting Controls Construction Inspection
❑ If dimming ballasts are specified for light fixtures within the daylit area, make sure they
meet. all Standards requirements, including "reduced flicker operation" for -manual
dimming control systems
4. Automatic Time Switch Controls Construction Inspection
a: Automatic time switch control is programmed for (Check all)
❑ Weekdays
❑ ' Weekend
❑ Holidays
b.' Document for the owner automatic time switch programming (Check all)
❑ Weekdays settings '
❑ Weekend settings
❑ Holidays setting
❑ Set—up settings '
❑ Preference program setting `
❑ Verify the correct time and date is properly set in the time switch
❑ Verify the battery is installed and energized
❑ Override time limit is no more than 2 hours
Certification 'Statement: I certify that all statements,are.true on this LTG -2—A form including the
PASS/FAIL Evaluation
I affirm I am, eligible to sign this form under the provisions described in the Statement of Acceptance on form . LTG -1-A
Name:
Company:
Signature: Date:
License: Expires:
0
INTERIOR LIGHTING SCHEDULE (Part 1 of 2). LTG -2—C
PRO CT NAM DATE e_na_nr
UM;LL K
INSTALLED LIGHTING POWER FOR CONDITIONED SPACES
Luminaire
Lampsj Ballasts
Installed Watts
A
B
C
D
E
F
G
H
I
J
Name
Type Description
�07
7
J a z
c r
3 3 3
3
N
D
°
r
00 ��
B c O
m
r g �
3, �_�
p 6 -
��
3 rt
O
�✓
C�_
c 0
_
c c
�.�
�•CD
'
�
^ to
x
C -
.. a
A
FLUORESCENT 2 X 4
T8
3
22
1
72
./
34
2448
PAGE TOTAL 2448
BUILDING TOTAL (sum of all pages) +
PORTABLE LIGHTING (From LTG -3—C) +
CONTROL CREDIT (From LTG -4—C) —
ADJUSTED ACTUAL WATTS + 2448
2005 Nonresidential Compliance Forms APRIL 2005
INTERIOR LIGHTING POWER ALLOWANCE LTG -5-C
PROJECT NAME CIRCLE K #457 DATE 9-08-06
ALLOWED LIGHTING POWER (Choose One Method)
COMPLETE BUILDING METHOD — CONDITIONED SPACES
BUILDING CATAGORY (From § 146 Table 146-8WATTS COMPLETE ALLOWED
PER (ft BLDG. AREA WATTS
AREA CATAGORY METHOD — CONDITIONED SPACES
AREA CATAGORY (From §146 Table 146—C)
I RETAIL SALES/MERCHANDISE I
B
C
D
WATTS
PER (ft
AR
(ft
ALLOWED
WATTS
1.7
1540
2703
1590 2703
TOTALS AREA WATTS
TAILORED METHOD — CONDITIONED SPACES
TOTAL ALLOWED WATTS
(From LTG -6—C)
UNCONDITIONED SPACES
A
Complete Building and Area Category Methods
CATAGORY (From § 146 Table 146—B & C)
B C D
WATTS AR ALLOWED
PER (ft (ft� WATTS
TOTALS AREA WATTS
TAILORED METHOD — UNCONDITIONED SPACES
TOTAL UNCONDITIONED SPACES ALLOWED WATTS
(From LTG -5—C and LTG -6—C)
2005 Nonresidential Compliance Forms APRIL 2005
MANDATORY MEASURES
Building Lighting Shut—Off
The building lighting shut—off system consists of an' automatic time switch, with a zone for each floor
or the building is separately metered and exempt from the shut—off requirement.
Override for Building Lighting shut—Off
The automatic building shut—off system is provided with a manual accessible override switch in sight
of the lights. The area of override is not to exceed 5,000 square feet.
Automatic Control Devices Certified
All automatic control devices specified are certified, all alternated equipment shall be certified and
installed as directed by the manufacturer.
Fluorescent Ballast and Luminaries Certified
All fluorescent fixtures subject to certification and specified for the projects are certified.
Individual Room/Area Controls
Each room and area in this building is equipped with a separate switch or. occupancy sensor device
for each area with floor—to—ceiling walls.
Uniform reduction for Individual Rooms
All rooms and areas greater than 100 square feet and more. than 0.8 watts per square foot of
lighting load shall be controlled with multi—level switching for uniform reduction of lighting within
the room.
Daylit Area Control
All rooms that are greater than 250 square feet and contain windows and skylights, that allow for
the effective use of daylight, in the area shall have 50% of the lighting power in each daylit area
controlled by a separate switch or
The effective use of daylight throughout cannot be accomplished because the windows are
continuously shaded by a building on the adjacent lot. Diagram of shading during. different times
of year is included on plans.
The above notes are only examples of wording. Each mandatory measure that requires a separate
note should be listed on the plans.