BPOL2018-0047 Geotechnical UpdateI I � V S 31
Sladden Engineering
45090 Golf Center Parkway, Suite F, Indio, CA 92201 (760) 8634M3 Fax (760) 863-0847
6782 Stanton Avenue, Suite A, Buena Park, CA 90621 (714) 523-0952 Fax (714) 523-1369
450 Egan Avenue, Beaumont, CA 92223 (951) 845-7743 Fax (951) 845-8863
800 E. Florida Avenue, Hemet, CA. 92543 (951) 766-8777 Fax (951) 766-8778
May 26, 2016 Project No. 544-16138
16-05 212
Mr. Bob Safai
c/o Hayer Architecture, Inc.
445 Marine View Avenue, Suite 280
Del Mar, California 92014
Subject: Geotechnical Update
Project: Proposed Custom Residence
81-454 Amundson Avenue
The Madison Club -- Lot 19B
La Quinta, California
Ref: Geotechnical Investigation Report prepared by Sladden Engineering dated January
28, 2005; Project No. 544-4810, Report No. 05-01-101
Report of Testing and Observation During Rough Grading prepared by Sudden
Engineering dated March 2, 2006; Project No. 522-4810; Report No. 05-M-120
As requested, we have reviewed the above referenced geotechnical reports as they relate to the
design and construction of the proposed custom residence to be constructed on the site located at
81-454 Amundson Avenue within the Madison Club development in the City of La Quinta,
California. It is our understanding that the proposed residential structure will be of relatively
lightweight wood -frame construction and will be supported by conventional shallow spread
footings and concrete slabs on grade.
The subject lot was previously graded during the rough grading of the Madison Club project site.
The rough grading included over -excavation and recompaction of the native surface soil along
with the placement of engineered Fill material to construct the building pads. The site grading is
summarized in the referenced report of Testing and Observation During Rough Grading along
with the compaction test results.
Because the lot has been previously rough graded, the remedial grading required at this tin,_e
should be minimal provided that the building area that falls within the previously assumed
building envelope. Tne building areas should be cleared of surface vegetation, scari$ed a —a
moisture conditioned prior to precise grading. The exposed surface should be compacted to a
minimum of 90 percent relative compaction prior to fill placement. The previously removed soil
and any fill material should be placed in thin lifts at near optimum moisture content and
compacted to at Ieast 90 percent relative compaction.
Sladden Engineering
wwty. Sladdenengineering. com
*31
May 26, 2016 2- Project No. 544-16138
16-05-212
The referenced reports include recommendations pertaining to the construction of residential
structure foundations. The previous reports also address the potential for liquefaction,
subsidence and differential settlement. Based upon our review of the referenced reports, it is our
opinion that the structural values included in these reports remain applicable for the design and
construction of the proposed residential structure foundations.
The allowable bearing pressures recommended in the referenced Geotechnical Investigation
report remain applicable. Conventional shallow spread footings should be bottomed into
properly compacted fill material a minimum of 12 inches below lowest adjacent grade.
Continuous footings should be at least 12 inches wide and isolated pad footings should be at least
2 feet wide. Continuous footings and isolated pad footings should be designed utilizing
allowable bearing pressures of 1500 psf and 2000 psf, respectively. Allowable increases of 300 psf
for each additional I foot of width and 300 psf for each additional 6 inches of depth may be
utilized, if desired. The maximum allowable bearing pressure should be 3000 psf. The
recommended allowable bearing pressures may be increased by one-third for wind and seismic
loading.
Lateral forces may be resisted by friction along the base of the foundations and passive resistance
along the sides of the footings. A friction coefficient of 0.48 times the normal dead load forces is
recommended for use in design. Passive resistance may be estimated using an equivalent fluid
weight of 300 pcf. If used in combination with the passive resistance, the frictional resistance
should be reduced by one third to 033 times the normal dead load forces.
The bearing soil is generally non -expansive and falls within the "very low" expansion category in
accordance with the 2013 (CBC) classification criteria. Pertinent 2013 CBC Seismic Design
parameters are summarized on the following page.
Sladden has reviewed the 2013 California Building Code (CBC) and summarized the current
seismic design parameters for the proposed structure. The seismic design category for a structure
may be determined in accordance with Section 1613 of the 2013 CBC or ASCEf. According to the
2013 CBC, Site Class D may be used to estimate design seismic loading for the proposed
structures. The 2013 CBC Seismic Design Parameters are summarized below.
Risk Category (Table 1.5-1):1/11/11I
Site Class (Table 1613.32):D
Ss (Figure 1613.3.1):1.516g
Si (Figure 1613.3.1): 0.711g
Fa (Table 16133.3(1)):1.0
Fv (Table 1613.5.3(2)):1.5
Sms (Equation 16-37 tFa X 5s)): 1.516g
Smi (Equation 16-38 (Fv X S1]):1.066g
SDs (Equation 16-39 f2/3 X Sms)):1.011g
SDI (Equation 16-40 f 2/3 X Sm7 j): 0.711g
Seismic Design Category: D
Sladden Engineering
www.Sladdeneugineering. com
May 26, 2016
-3-
Project No. 544-16138
16-05-212
We appreciate the opportunity to provide service to you on this project. If you have any
questions regarding this Ietter or the referenced reports, please contact the undersigned.
Respectfully submitted,
SLADDEN ENGINEERING
Brett L. Anderson J a�r"C��
'�
Principal Engineer pe—IrL "E
s 1;
C4 ;
SERfc)b N°� � `s;:s
EYp.9/�0116 I9
C1VIL t'ft
Copies: Q Mr. Bob Safai �� ENGtN RI 1
CAL
Sladden Engineering
www.Sladdenengineering.cofn
1. 1 ► C
La Quinta 14.763
06/17/Z¢
Please verify that soils reports contain all of the above information. In addition, to assur,
continuity between the investigation/reporting stage and the execution stage, please use
the following checklist to verify that the conclusions and recommendations in the report
cover all the required elements. Only then can we be assured that the construction
documents address all of the site soil conditions.
La Quinta Geotechrdeal Report Checklist
Does the "Conclusions and Recommendations" section of the report address each of the
following criteria?
"Address" means:
(a) the criterion is considered significant and mitigation measure(s) noted, or-
b) the criterion is considered Insignificant.and
explicitly so stated.
Yes
No Criterion
❑
Foundation criteria based upon bearing capacity of natural or compacted soft_
❑
Foundation criteria to mitigate the effects of expansive soils.
❑
Foundation criteria based upon bearingCapacity PacitY of natural or compacted soil.
❑
Foundation criteria to mitigate the effects of liquefaction.
❑
Foundation criteria to mitigate the effects of seismical! induced dential
y
settlement.
❑
Foundation criteria to mitigate the
9 effects of song -team differential went.
❑
Foundation criteria to mitigate the effects of varying soil strength.
❑
Foundation criteria to mitigate expected total and differential settlement.
Any "No" answers to the above checklist should be noted as speck required
corrections.
Sladden Engineering
45090 Golf Center Parkway, Suite F, Indio, CA. 92201 (760) 863-0713 Fax (760) 863-0847
6782 Stanton Avenue, Suite C, Buena Park, CA 90621 (714) 523-0952 Fax (7I4) 523-1369
450 Egan Avenue, Beaumont, CA 92223 (951) 845-7743 Fax (951) 845-8863
800 E. Florida Avenue, Hemet, CA 92543 (951) 766-8777 Fax (951) 766-8778
June 6, 2016 Project No. 544-16138
16-06-223
Mr. Bob Safai
c/o Hayer Architecture, Inc.
445 Marine View Avenue, Suite 280
Del Mar, California 92014
Project: Proposed Custom Residence
81-454 Amundson Avenue
The Madison Club — Lot 19B
La Quinta, California
Subject: Soluble Sulfate Content
Ref: Geotechnical Investigation Report prepared by Sladden Engineering dated January
28, 2005; Project No. 544-4810, Report No. 05-01-101
Report of Testing and Observation During Rough Grading prepared by Sladden
Engineering dated March 2, 2006; Project No. 522-4810; Report No. 06-02-120
As requested, we have reviewed the geotechnical update report prepared for the subject property
located at 81-454 Amundson Avenue, Lot 19B located within the Madison Club residential
development with respect to soluble sulfate content as it relates to selecting appropriate concrete
mix designs. Laboratory testing indicated soluble sulfate content of 2400 ppm (024 percent) that
corresponds with the "severe" exposure category in accordance with Table 3 of ACI 318-08
Chapter 9. In accordance with ACI 3I8-08, special sulfate resistant concrete nix designs will be
required for structural concrete on this project Structural concrete in contact with soil should
have a minimum compressive strength of 4500 psi and maximum water/cement content of 0.45_ A
copy of the laboratory test results is attached.
If you have questions regarding this letter or the referenced report, please contact the
undersigned.
Respectfully submitted,
SLADDEN ENGINEERIN
Brett L. Anderson
1 AMID S s
Principal Engineer No. Cup=J9 rT
U ExR• 9/30116 h
ctvu-
Letter/clb "
\-;r ENG111rGP1NG o-£,
Copies: 4 / Mr. Bob Safaip-
, d V
Sladden Engineering
6782 Stanton Ave., Suite A. Buena Park, CA 90621 (714) 523-0952 Fax (714) 523-1369
45090 Golf Center Pkwy, Suite F, Indio, CA 92201 (760) 863-0713 Fax (760) 863-0847
450 Egan Avenue, Beaumont, CA 92223 (951) 845-7743 Fax (951) 845-8863
Date: June 6, 2016
Account No.: 544-16138
Customer: Mr. Bob Safai c/o Hayer Architecture, Inc
Location: Amundson Way, Lot 19B, La Quinta
Analytical Report
Sulfate Series
Soluble Sulfates Soluble Chloride
per CA 417 per CA 422
ppm ppm
2400
•tl
Sulfate 544-16138 060616
-TABLE I q-A-2—RE0ilIREMEfM FOR SPEC1kL EXPOSlJRE CONDCi10f4S-
-
MA7�ZMUhi • -
f'n
,HOR�� AHL) .
WATER-t0AE IiTi ?iG i
MtLT[7iLALS' RAk -RY= ;
:t2G7t�}Vc�Gff� -
kmfiew+'tl4MHCRETE6
EXPOSURE COHOMOH
AGGREGATE COR
= x 0 nogs4ar UPS
Con4retc intended to have low permeability when
exposed to water
0 -50 J
Concrete exposed to'frrczing and thawing in a moist
condition or to deicing chemicals
0-45
4,500
For corrosion projection for reinfacred concrete
exposed to chlorides fmm deicing ch&rnirals, salts or
brackish wares, orsprayfmm thesc"soumes
0-40
5,OM
TABLE TB-A-3•—REQUIREMEKiS:FC)14 CONCf3ETE
EXFOSEO TO SULFATE-00WrAJNIHd-SOUM0NS _
r ORMAL-W 3GNl
=AGGRSGATE
ActMEGATE
= CONCRETE
n;lYatcf-
- CatsrstGttauz
_ f" ttm;nst-
��
• -
- -•
WATER- SOLUBLE
htataaiets-_Rat3a; bq=.
SULFATE
( tI'
g&IH
ttc4rsut d r
pJt
SULFATE
E
P AGE BY
SULFATE [SO4)IN
t¢yrcgEta
x a --S9TaritPa
EXPOSURE
WEIGHT ,
WATER, ppft
CEMERTTYPE
Corrtetes
Ilegligibie
0 00-0.1Q
0-150
- —
—.
—
Modcratc2•
0-10-Q20
L50-1S00
If.IP(MS7,7S
W-0-
S,£rMJ
CMS)
_
Sevcre
0.20-7-00
E,50040,000
-V
0.45 _
41%0
troy severe
Over 200
Over 10,000
V plus
A45
4.5
pozaolan3
IA Iowcr water-ccmrntitious marcriaLs ratio orhighcrs4=gth rssa7-� benquimd for law permca-b igroriarpcatsea�
against eocrorion'of cmbcddcd items or fre�rtg and rhawiag [i'abl-
2Scawater_ _
?Fozsotan that has been dctcrrniocd by test orservice romrd to impmvesulfate rmdsbnce whca rid inconmcm coo -
ram ring TI epc V rcmcnL