BPOL2018-0051 Geotechnical Update24
73i
Sudden Engineering
45090 Golf Center Parkway, Suite F, Indio, CA 92201 (760) 863-0713 Fax (760) 863-0847
6782 Stanton Avenue, Suite A, Buena Park, CA 90621 (714) 523-0952 Fax (714) 523-1369
450 Egan Avenue, Beaumont, CA 92223 (951) 845-7743 Fax (951) 845-8863
800 E. Florida Avenue; Hemet, CA. 92543 (951) 766-8777 Fax (951) 766-8778
May 26, 2016 Project No. 544-16138
16-05-212
Mr. Bob Safai
c/o Hayer Architecture, Inc.
445 Marine View Avenue, Suite 280
Del Mar, California 92014
Subject: Geotechnical Update
Project: Proposed Custom Residence
81-454 Amundson Avenue
The Madison Club — Lot 19B
La Quinta, California
Ref: Geotechnical Investigation Report prepared by Sladden Engineering dated January
28, 2005; Project No. 544-4810, Report No. 05-01-101
Report of Testing and Observation During Rough Grading prepared by Sladden
Engineering dated March 2, 2006; Project No. 522-4810; Report No. 06-02-120
As requested, we have reviewed the above referenced geotechnical reports as they relate to the
design and construction of the proposed custom residence to be constructed on the site located at
81-454 Amundson Avenue within the Madison Club development in the City of La Quinta,
California. It is our understanding that the proposed residential structure will be of relatively
lightweight wood -frame construction and will be supported by conventional shallow spread
footings and concrete slabs on grade.
The subject lot was previously graded during the rough grading of the Madison Club project site.
The rough grading included over -excavation and recompaction of the native surface soil along
with the placement of engineered fill material to construct the building pads. The site grading is
summarized in the referenced report of Testing and Observation During Rough Grading along
with the compaction test results.
Because the lot has been previously rough graded, the remedial grading required at this time
should be minimal provided that the building area that falls within the previously assumed
building envelope. The building areas should be cleared of surface vegetation, scarified and
moisture conditioned prior to precise grading. The exposed surface should be compacted to a
minimum of 90 percent relative compaction prior to fill placement. The previously removed soil
and any fill material should be placed in thin lifts at near optimum moisture content and
compacted to at least 90 percent relative compaction.
Sladden Engineering
wlvw.Sladdenengineering.conr
1 1.
May 26, 2016
-2- Project No. 544-16138
16-05-212
The referenced reports include recommendations pertaining to the construction of residential
structure foundations. The previous reports also address the potential for liquefaction,
subsidence and differential settlement. Based upon our review of the referenced reports, it is our
opinion that the structural values included in these reports remain applicable for the design and
construction of the proposed residential structure foundations.
The allowable bearing pressures recommended in the referenced Geotechnical Investigation
report remain applicable. Conventional shallow spread footings should be bottomed into
properly compacted fill material a minimum of 12 inches below Iowest adjacent grade.
Continuous footings should be at least 12 inches wide and isolated pad footings should be at least
2 feet wide. Continuous footings and isolated pad footings should be designed utilizing
allowable bearing pressures of 1500 psf and 2000 psf, respectively. Allowable increases of 300 psf
for each additional I foot of width and 300 psf for each additional 6 inches of depth may be
utilized, if desired. The maximum allowable bearing pressure should be 3000 psf. The
recommended allowable bearing pressures may be increased by one-third for wind and seismic
loading.
Lateral forces may be resisted by friction along the base of the foundations and passive resistance
along the sides of the footings. A friction coefficient of 0.48 times the normal dead load forces is
recommended for use in design. Passive resistance may be estimated using an equivalent fluid
weight of 300 pcf. If used in combination with the passive resistance, the frictional resistance
should be reduced by one third to 0.33 times the normal dead load forces.
The bearing soil is generally non -expansive and falls within the "very low" expansion category in
accordance with the 2013 (CBC) classification criteria. Pertinent 2013 CBC Seismic Design
parameters are summarized on the following page.
Sladden has reviewed the 2013 California Building Code (CBC) and summarized the current
seismic design parameters for the proposed structure. The seismic design category for a structure
may be determined in accordance with Section 1613 of the 2013 CBC or ASCE7. According to the
2013 CBC, Site Class D may be used to estimate design seismic loading for the proposed
structures. The 2013 CBC Seismic Design Parameters are summarized below.
Risk Category (Table 1.5-1): I/II/111
Site Class (Table 1613.32): D
Ss (Figure 1613.3.1):1.516g
S1 (Figure 1613.3.1): 0.711g
Fa (Table 1613.3.3(1)): I.0
Fv (Table 1613.5.3(2)):1.5
Sms (Equation 16-37 fFa X Ss)): I.516g
Smi (Equation 16-38 1FV X S21): 3.066g
SDS (Equation 16-39 f2/3 X Sms)): 1.011g
SDI (Equation 16-40 12/3 X Sm7)): 0.711g
Seismic Design Category: D
Sladden Engineering
ivww.Sladdenengineering.com
May 26, 2016 -3- Project No. 544-16138
16-05-212
We appreciate the opportunity to provide service to you on this project If you have any
questions regarding this letter or the referenced reports, please contact the undersigned.
Respectfully submitted,
SLADDEN ENGINEERING
Brett L. Anderson
Principal Engineer
SER/clb
Aft ^.cOjV
No. C45389
�C
c�
ESP. sisoris
CIVIL
Copies: Q Mr. Bob Safai
��� ENGINEERING
='
0,
CAL
ItS
Sladden Engineering
fvww.Sladdenengineeringcom
La Quinta 14-763
06/17/14
Syll- 16 /3
/$-0S=Z/
1773j
continuity between the investigation/reporting stage and the
Please verify that soils reports contain all of the above information, In addition, to ass
execution siege, please us(
the following checklist to verify that the conclusions and recommendations in the report
cover all the required elements. Only then can we be assured that the constructions
documents address all of the site soil conditions.
La Quinta Geotechnical Report Checklist
Does the "Conclusions and Recommendations" section of the report address each of the
following criteria?
"Address" means:
(a) the criterion is considered significant and mitigation easu
mr�e(s) no
or, (b) the criterion is considered Insignificant. and explici#iyy slated,
Yes No Criterion
-Ef D Foundation criteria based
LVj
9r,
El
upon bearing capacity of natural or compacted soil.
D Foundation criteria to mitigate the effects of expansive soils.
❑ Foundation criteria based upon bearing capacity of natural or compacted soil.
D Foundation criteria to mitigate the effects of liquefaction.
❑ Foundation criteria to mitigate the effects of seismically inducted differentia!
settlement.
L7 Foundation criteria to mitigate the effects of long-term differential settlement
❑ Foundation criteria to mitigate the effects of varying soil strength.
❑ Foundation criteria to mitigate expected total and differential settlement.
Any "No" answers to the above checklist should be noted as specific required
corrections.
(W
Sudden Engineering
45090 Golf Center Parkway, Suite F, Indio, CA. 92201 (760) 863-0713 Fa.� (760) 863-0847-
6782 Stanton Avenue, Suite C, Buena Park, CA 90621 (734) 523-0952 Fax (714) 523-I369
450 Egan Avenue, Beaumont, CA 92223 (951) 845-7743 Fax (951) 845-8863
800 E. Florida Avenue, Hemet, CA 92543 (951) 766-8777 Fax (951) 766-8778
June 6, 2016
Mr. Bob Safai
c/o Hayer Architecture, Inc.
445 Marine View Avenue, Suite 280
Del Mar, California 92014
Project: Proposed Custom Residence
81-454 Amundson Avenue
The Madison Club — Lot 19B
La Quinta, California
Subject: Soluble Sulfate Content
Project No. 544-16138
16-06-223
Ref: Geotechnical Investigation Report prepared by Sladden Engineering dated January
28, 2005; Project No. 544-4810, Report No. 05-01-101
Report of Testing and Observation During Rough Grading prepared by Sladden
Engineering dated March 2, 2006; Project No. 522-4810; Report No. 06-02-120
As requested, we have reviewed the geotechnical update report prepared for the subject property
located at 81-454 Amundson Avenue, Lot 19B located within the Madison Club residential
development with respect to soluble sulfate content as it relates to selecting appropriate concrete
mix designs. Laboratory testing indicated soluble sulfate content of 2400 ppm (024 percent) that
corresponds with the "severe" exposure category in accordance with Table 3 of ACi 318-08
Chapter 9. In accordance with ACI 3I8-08, special sulfate resistant concrete mix designs wiU be
required for structural concrete on this project. Structural concrete in contact with soil should
have a minimum compressive strength of 4500 psi and maximum water/cement content of 0.45. A
copy of the laboratory test results is attached.
If you have questions regarding this letter or the referenced report, please contact the
undersigned.
Respectfully submitted,
SLADDEN ENGINEERIN
Brett L. Anderson -
Principal Engineer
Letter/clb
ES
V( No. Ca5339
j Exp.9/30i16 r
- CIVIL
*\ ENGINEERING11r
Copies: 4 / Mr. Bob Safai C_ ,AZ
Sladden Engineering
6782 Stanton Ave., Suite A. Buena Park, CA 90621 (714) 523-0952 Fax (714) 523-1369
45090 Goff Center Pkwy, Suite F, Indio, CA 92201 (760) 863-0713 Fax (760) 863-0847
450 Egan Avenue, Beaumont, CA 92223 (951) 845-7743 Fax (951) 84&8863
Date: June 6, 2016
Account No.: 544-16138
Customer: Mr. Bob Safai c/o Hayer Architecture, Inc
Location: Amundson Way, Lot 19B, La Quinta
Sulfate Series
Analytical Report
Soluble Sulfates
per CA 417
ppm
2400
Soluble Chloride
per CA 422
ppm
•11
2�1
Sulfate 544-16138 060616
-TA13LE 19--A-2—REOUIREMEfFI-S FOR SPECIAL EXPOSURE CQNDM0hjS'
HOA7dAL II AAiM
1.tAX11.tUM - .
WATER-Z0.16P7Ti jOtrS ; �HT. -
' bi{1TFJitA'�'^' RA�7o-','8Y- ,.- AGGflEG111'EEORCA�
-
-•
EXPOSURE CONDITION �GhEGAT =
AGGREGATE CORCREIE •
..tAL'-YtREM -
intended to have low perrneibility when
Ebrmackiih
x •1'crliPa
_
o water QSQ1000
;
exposed to'fizccing and thawing in a moist
or to deicing chemicals Q_d5
-
ion prolecdon for reinforced concrete
4500
-
chlorides from deicing chernica.ls, salts or
i+atcr, or•sprayfrom th='zcunxs
0_40
SAG
TABLE 19-A-3--REMAREME &FOR COPICl3ETE
EXPOSED TO TO SULFATE COALTAINWG-SOLUTIONS
, - AGGREGATE
: Cxi31CRETE _
.
Maxi lmlwatnr-
WATER- SOLUBLE Camu[tttlosu '
M tiarmat-
.1am-and
_
SULFATE r,[atnrIatc'Rattart :.
SULFATE SOIL,W
PROMSOIL,
ffdr - �0a'
SUA( H
(So.,)
ggmgeteEXP7SUAE WDGy_, ^t�CEREA7TYPE
Coate
- +:P
x TarldPs
'
Negligible 0_00-0.I(y
Mod rat 4.10-Q2Q ISO-1.500 ir.H,(MS),IS -050•
4.000
CMS}
5cvcre Q 20-Z00 1500-iD,Q00 - iV 0 4i
4,50Q
Very Seven Over2.00 Over IQ,00Q Yplus 4.45
4,g{l0
- - pozxolart3
_
t lower Water-ccr= tious macr[Ws ratio orhighcr sq=gt ma b�qn� for tDw Pcrnara
a g Lmsc rorrosion'of cmbcddcd items or firing and rhswii�g (-able 24-�12}. M ��m
Scaw =-
1FoaoLart tftat has boon detrsmiaed by rest or_ suvjce rccord to oe
-
V ecmertL improve sulfate resister when nsgd is eto con-
_
2 264
REINFORCEMENT— REFER
TO FOUNDATION PLAN
TURN DOWN SLAB REINF.
01" INTO FOOTING
4" CONCRETE 5LA5
2 SAND OVER 10 MIL II VAPOR RETARDER \ ,�\
o
i
2—#5 TOP AND 50TTOM
U.N.O. REFER TO CONT. FTC.
SCHEDULE 6 FND. PLAN
0 O
WEEP SCREEP LOCATION. REFER
TO ARCHITECTURALS FOR
COMPLIANCE. WITH:
2015 C5C 2512.12
2015 CRC R'705.6.2.1
5H=ARYVALL
PER PLAN
t- I SILL PLATE WITH
5/8"cP AB AT 4'—O" o% U.N.O.
REFER TO FOUNDATION PLAN
AND SHEAR WALL SCHEDULE
"X" = 6" FOR RESIDENTIAL.
AS PER IRC R51i.1
"X" = 5" FOR COMMERCIAL
E.N. AS PER 15C 2504.112.2
FOUNDATION DETAIL
4B-3,2
4" CONCRETE SLAB
REINFORCEMENT— REFER
TO FOUNDATION PLAN
TURN DOWN SLAB REINF.
ct" INTO FOOTING
2" 5AN12 OVER 10 MIL
VAPOR RETARDER
ADDITIONA
GREATERI
"D" = A5 P:
FIN15H A5 F
REINFORCE
TO FOUNDA
TURN DOWN
9" INTO FOc
4" GONGRE
2° SAND
VAPOR'
2—#5 TC
U.N.O. K
5CHEDU