09-0746 (AR) Revision 1Title 24 Report for:
Mitchell Casita Addition
79-115 Rancho La Quinta Drive
La Quinta, CA
Project Designer:
Curtis R. Shupe, Architect
72880 Fred Waring Drive
Suite A-5
Palm Desert, CA 92260-9374
Report Prepared By: {
Joan D. Hacker
• Insu-form, Inc.
77-810 Las Montanas Road, Suite 201
Palm Desert,. CA 92211
(760) 345-1352
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
-APPROVED
FOR CONSTRUCTION Job Number: JUL .2 9 2009
DATE PJ 8`1 13Y By
Z Date:
7/28/2009
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Ener:.gy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.4 by EnergySoft Job Number: User Number: 2655
i d
It
TR 0 3 S th S J T 17
:Io! !"ioq3R. ihlr2' olifl,
Polf*Ub-A stuJ ligr1olifM
v 1. 1 n .3211 o r-, A, c r i.-) r i pi r v
AJ .61muO
t
:VV beispic' hoq9S
%rlos'ri Cl nr,-()'
orl, rri-tot r,znl
ro'lA-, fj:Tjc'' tsco -3onsl n o I'vi as-)
Monc! rv,lc,9
0 el'—
:01.3c
i tv nr.1 v, r -loq,, ;it,ir f.1 ofj. i U, C, -e e, I plo F,A gifT
'r, Y-IF'r, 11 tol.
w
TABLE OF CONTENTS
Cover Page 1
Table of Contents 2
Form CF -1 R Certificate of Compliance 3
Form MF -1 R Mandatory Measures Summary 6
HVAC System Heating and Cooling Loads Summary g
Room Load Summary 10
EnergyPro 4.4 by EnergySoft Job Number: User Number: 2655
--110 M"JEAT
t -psq IovcJ
alinoirtoO 113 eidsT
gonsil�;mu� to oi,
yi+�7rr'fP�1c�, sou F.y" , ti�olrt7risil>i Fit-9i'A
visirlmiR absoJ pi-ilocC' kits gn sW' mele,�P,
0 f v.Isrrvmuc brc-1 mOOH
�:c. 6.':,1 .t',..,: ...1. `. C[?" , I A -., .,tom•
Certificate Of Compliance: Residential
(Part 1 of 3) CF -1 R
Mitchell C;asita Addition
Project Title
Total Conditioned Floor Area:
770 ft2
7/29 2onA
Date
79-115 Ranchn La nuinta
Drive La
Qjinta
Building Front Orientation:
(N) 0 deg
Project Address
0 ft2
Fuel Type:
Building Permit #
Insu-form, Inc.
770 ft2
Fenestration:
(760) 345-1352
Documentation Author
8.0 ft
Area:
Telephone
Plan Check/Date
FnergyPro
Compfffice, Method
1.00
CA
Climate Zone1S
Climate Zone
Field Check/Date
TDV
Standard
Proposed
Compliance
# of Thermostat
(kBtu/sf-yr)
Design
Design
Margin
Units Zone Type Type
044 Conditioned Setback
_p.5&_ f:onditionad Sathark
Space Heating
6.01
5.85
0.17
Space Cooling
123.85
123.16
0.69
Fans
16.57
17.01
-0.44
Domestic Hot Water
25.63
25.63
0.00
Pumps
0.00
0.00
0.00
Totals
172.07
171.65
0.42
Percent better than Standard:
0.2%
Building Type:
Y Single Family
❑ Addition
Total Conditioned Floor Area:
770 ft2
❑ Multi Family
Q Existing + Add/Alt
Existing Floor Area:
430 ft2
Building Front Orientation:
(N) 0 deg
Raised Floor Area:
0 ft2
Fuel Type:
Natural Gas
Slab on Grade Area:
770 ft2
Fenestration:
Average Ceiling Height:
8.0 ft
Area:
118 ft 2
Avg. U: 0.79
Number of Dwelling Units:
1.00
Ratio:
15.3% Avg. SHGC: 0.70
Number of Stories:
1
BUILDING ZONE
INFORMATION
# of Thermostat
Vent
Zone Name
Addition
Ching lone
Floor Area Volume
340 _979
4300
,44_
Units Zone Type Type
044 Conditioned Setback
_p.5&_ f:onditionad Sathark
Hgt. Area
-2 n/a
_2 n/a
OPAQUE SURFACES Insulation Act.
Type Frame Area U -Fac. Cay. Cont. Azm. Tilt
Wall Wnnd 1nA _0 6F;q R -PL R-0 n 1A0 An
Wall Wnnd ARn 099 R-21 R-0 n _gn gn
Dnnr Nnna 40 0.5on Nona R-n_n _90 An
Wall Wnnd 28 n nAo R-2 R_n 0 135 _90
Wall Wnnd 100 () nAq R21 RR_0"0 -0 Qf)
Wall Wnnd 28 n 069 -R21 R-0.0 225 _90
Wall Wnnd 110 n 069 R_91 84) n An An
Dnnr Nnne 20 0,50n Nona R-0 Q _go gn
Ronf Wnnd 340 A 029 R-38 R-0 An
Wall Wnnd PAP 0.110 R-11 R-0 0 -d-9f1
Wall_ Wnnd 360 0.110 R_1l R-0 0 _qn gn
Wall Wnnd 212 0.110 R-11 R-0 0 1 A0 _ gn
Door Nnne 20 0 Snn Nona R-0.0 1A0 _90
Wall Wnnd 38 0.110 R_11 R-0.0 _225, sn
Wall Wnnd 220 0.110 R_11 R_0.0 270 _gn
Roof Wnnd 4.40 0.049 R_19 R-0.0 _0 0
Gains Condition
Y / N Status JA IV Reference Location / Comments
I EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:3 of 11
Certificate Of Compliance: Residential (Part 2 of 3) CF -1 R
Mitchell Casita Addition 7/28/2009
Project Title Date
FENESTRATION SURFACES
# Type Area U -Factor'
True Cond.
SHGC2 Am. Tilt Stat. Glazing Type
Location/
Comments
L
2
L
4
5
Window
Window
Window
Window
Window
Rear
Left
Left
Front
Rear
(S)
(E)
_(S JE
(N)
(SW)
12 -
22.5
12.5
20.0
12.5
0i79o 11A -A -0-Z0
0.790 116-A 0_70
0.790 116-A 0_70
0.790 116-A 0_70
0.790 116-A 0_70
11 R -B 180 _qa NPw Douhle Metal Clear
116-B 90 90 New Double Metal Clear
116-B 135 90 New Double Metal Clear
116-8 0 90 New Double Metal Clear
116-B 225 90 New Double Metal Clear
�_ ddition
Addition
Addition
Addition
Addition
5
Window
Front
_ (N)
8.0 0_790 116-A 0_70
116-B 0_ 90 Existing Debi le Metal Clear
Existing Casita
L
8
Window
Window
Rear
Rear
(S)
(SW)
17.5
12.0
0_790 116-A 0_D
0.790 116-A 0_70
116-B 180 -_9D_ Existing Double Metal Clear
116-B 225 90 Existing Double Metal Clear
Existing Casita
Existing Casita
2.0 01 2.0
2.0
Bug Screen
0.76 5.0 3.5
2.0 0.1 2.0
2.0
S Bug Screen
0.76 4.0 5.0
2.0 0.1 2.0
2.0
THERMAL MASS FOR HIGH MASS DESIGN
Area Thick. Heat Inside
Condition
LocEtion/
Type
(sf) (in.) Cap. Cond. R -Val.
JA IV Reference
1. Indicate source either from NFRC or Table 116A. 2. Indicate.source either from NFRC or Table 1168.
INTERIOR AND EXTERIOR SHADING Window Overhang Left Fin Right Fin
# FYtarinr Rhnrin Tvnn curnrl u..• uJa I „_ - . �.. _.
2 Bug Screen
0.76 2.5 3.0
2.0 0.1 2.0
2.0
3 Bug Screen
0.76 5.0 2.5
2.0 0.1 2.0
2.0
4 Bug Screen
0.76 5.0 2.5
2.0 0.1 2.0
2.0
5 Bug Screen
6
0.76 5.0 2.5
2.0 0.1 2.0
2.0
Bug Screen
7
0.76 4.0 2.0
2.0 01 2.0
2.0
Bug Screen
0.76 5.0 3.5
2.0 0.1 2.0
2.0
S Bug Screen
0.76 4.0 5.0
2.0 0.1 2.0
2.0
THERMAL MASS FOR HIGH MASS DESIGN
Area Thick. Heat Inside
Condition
LocEtion/
Type
(sf) (in.) Cap. Cond. R -Val.
JA IV Reference
Status
Comments
Insulation
PERIMETER LOSSES
Condition
Location/
Type
Length R -Val. Location
JA IV Reference
Status
Comments
Slab Perimeter
33 None No Insulation
26-A1
New
Addition
Slab Perimeter
90 None No Insulation
26 -Ai
Existing
Existing Casita
Run Initiation Time: 07/28/0912.46.47 Run Code: 1248810407
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:4 of 11
Certificate Of Compliance: Residential (Part 3 of 3) CF -1 R
Mitchell Casita Addition
Rated
Water Heater # in Input
7/28/2009
Project Title
Tank Insul.
Standby R -Value
System Name Type Distribution Syst (Btu/hr)
(al)
Date
Loss (%) Ext
HVAC SYSTEMS
50
Existing 0.53
n/a n/a
Heating
Minimum
Cooling
Minimum
Condition Thermostat
Location
Type
Eff
Type
Eff
S-atus Type
Addition
Room Heat Pump
7.52 HSPF
Room PTAC without Side
10.7 EER
N'3w Setback
Living Zone
Central Furnace
80%AFUE
61�41VWConditioner
12.0 SEER
Naw Setback
HVAC DISTRIBUTION
Duct Duct Condition Ducts
Location Heating Cooling Location R -Value StatLs Tested?
Addition Ductless / with Ductless n/a n/a New No
Living Zone Wted Ducted Attic 4.2 Existirxl No
Hydronic Piping Pipe Pipe Insul.
System Name Length Diameter Thick.
WATER HEATING SYSTEMS
Rated
Water Heater # in Input
Tank
Cap.
Energy
Condition Factor
Tank Insul.
Standby R -Value
System Name Type Distribution Syst (Btu/hr)
(al)
Status or RE
Loss (%) Ext
Standard Gas 50 gal or Less Small Gas No Pipe Insulation 1 40,000
50
Existing 0.53
n/a n/a
Multi -Family Central Water Heating Details
Hot Water Pump
Control # HP Type
Add V2"
Insulation
%.VmrL1ANGC , I A I LIVItNT
This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of
Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall design responsibility.
The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insolation installation quality,
and building envelope sealing require installer testing and certification and field verification by an approved HERS rater.
Designer or Owner 4 Curtis R.: Shupe, ArchiteCt Documentation Author
Name: 72880 Fred Waring Drive Name: Joan D. Hacker
Title/Firm: Suite A-5 !. Title/Firm: Insu-form.lnc.
Address. Palm Desert, CA 92260-9374 Address: 77-810 Las Montanas Road Sute 201
Telephone: ? 0 34(x13 Lic. #6C 13'3 $
45�� w /^�
(signatur / Y/
' /�/O 1(date)
Enforcement Agency
Name:
Title/Firm:
Address:
Telephone:
(signature) (date)
Palm Desert, CA 92211
Telephone: 760 345-1352
(signature) J(date)
Mandatory Measures Summary: Residential (Page 1 of 2) MF -1 R
NOTE:' Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent compliance
requirements from the Certificate of Compliance supersede the items marked with an asterisk (') below. When this checklist is incorporated into the permit
documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether
they are shown elsewhere in the documents or on this checklist only.
DESCRIPTION Check or Initial applicable boxes or check NA If not applicable and included with the
.
ENFORCE -
permit application documentation.
N/A
DESIGNER
MENT
Building Envelope Measures
§ 150(a): Minimum R-19 in wood ceiling insulation or equivalent U -factor in metal frame ceiling.
❑
❑X
❑
§ 150(b): Loose fill insulation manufacturer's labeled R -Value:
❑
❑
❑
§ 150(c): Minimum 8-13 wall insulation in wood framed walls or equivalent U -factor in metal frame walls (does not
❑
❑X
❑
apply to exterior mass walls).
§ 150(d): Minimum R-13 raised floor insulation in framed floors or equivalent U -factor.
❑
❑
❑
§ 150(e): Installation of Fireplaces, Decorative Gas Appliances and Gas Logs.
1. Masonry and factory -built fireplaces have:
a. closable metal or glass door covering the entire opening of the firebox
❑
❑
❑
b. outside air intake with damper and control, flue damper and control
❑
❑
❑
2. No continuous burning gas pilot lights allowed:
❑
❑
❑
§ 150(f): Air retarding wrap installed to comply with §151 meets requirements specified in the ACM Residential Manual.
❑
❑
❑
§ 150(g): Vapor barriers mandatory in Climate Zones 14 and 16 only.
❑
❑
❑
§ 150(1): Slab edge insulation - water absorption rate for the insulation alone without facings no greater than 0.3%, water vapor
❑
❑
❑
permeanoe rate no greater than 2.0 perminch.
§ 118: Insulation specified or installed meets insulation installation quality standards. Indicate type and include
El
ER
ElCF-6R
Form:
§ 116-17: Fenestration Products, Exterior Doors, and Infiltration/Exfiftration Controls.
1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage.
❑
❑X
❑
2. Fenestration products (except field fabricated) have label with certified U -Factor, certified Solar Heat Gain
Coefficient (SHGC), and infithation certification.,
❑
Q
❑
3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed. -
❑
❑X
❑
Space Conditioning, Water Heating and Plumbing System Measures
§ 110-13: HVAC equipment, water heaters, showerheads and faucets certified by the Energy Commission.
❑
Q
❑
§ 150(h): Heating and/or cooling bads calculated in accordance with ASHRAE, SMACNA or ACCA.
❑
Q
❑
§ 150(i): Setback thermostat on all applicable heating and/or cooling systems. r
❑
❑X
❑
§ 1500): Water system pipe and tank insulation and cooling systems line insulation.
1. Storage gas water heaters rated with an Energy Factor less than 0.58 must be externally wrapped with insulation
❑
❑X
❑
having an installed thermal resistance of R-12 or greater.
2. Back-up tanks for solar systems, unfired storage tanks, or other indirect hot water tanks have R-12 external
El
ER
Elinsulation
or R-16 internal insulation and indicated on the exterior of the tank showing the R -value.
3. The following piping is insulated according to Table 150-A/B or Equation 150-A Insulation Thickness:
1. First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire
❑
❑X
❑
length of recirculating sections of hot water pipes shall be insulated to Table 150B.
2. Cooling system piping (suction, chilled water, or brine lines), piping insulated between heating source and
❑
❑X
❑
indirect hot water tank shall be insulated to Table 150-B and Equation 150-A.
4. Steam hydronic heating systems or hot water systems > 15 psi, meet requirements of Table 123-A.
❑
❑
❑
5. Insulation must beprotected from damage, including that due to sunlight, moisture, equipment maintenance,
❑
Q
❑
and wind.
6. Insulation for chilled water piping and refrigerant suction piping includes a vapor retardant or is enclosed
❑
El
11entirely
in conditioned space.
7. Solar water -heating systems/collectors are certified by the Solar Rating and Certification Corporation.
❑
❑
❑
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number:
Page:6 of 11
Mandatory Measures Summary: Residential (Page 2 of 2) MF -1 R
NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent compliance
requirements from the Certificate of Compliance supercede the items marked with an asterisk (') below. When this checklist is incorporated into the permit
documents, the features noted shag be considered by all parties as minimum component performance specifications for the mLndatory measures whether
they are shown elsewhere in the documents.or on this checklist only.
DESCRIPTION Instructions: Check or Initial applicable boxes when completed or check N/A If not ENFORCE -
DESCRIPTION N/A DESIGNER MENT
Space Conditioning, Water Heating and Plumbing System Measures: (continued)
§ 150(m): Ducts and Fans
1. All ducts and plenums installed, sealed and insulated to meet the requirements of the CMC Sections 601, 602, 603, 604,
❑
605, and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minumum installed level of
R-4:2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system
that meets the applicable requirements of UL 181, UL 181 A, or UL 181B or aerosol sealant that meets the requirements
of UL 723. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or
tape shall be. used.
2. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
❑
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support
platforms may contain ducts. Ducts installed In cavities and support platforms shall not be compressed to cause reductions
in the cross-sectional area of the ducts.
3. Joints and seams of duct systems and their components shag not be sealed with'cloth back rubber adhesive
❑
duct tapes unless such tape is used in combination with mastic and draw bands.
4. Exhaust fan systems have back draft or automatic dampers.
❑
5. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operating
❑
dampers.
6. Protection of Insulation. Insulation shag be protected from damage, including that due to sunlight, moisture, equipment
❑
maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water
retardant and provides shielding from solar radiation that can cause degradation of the material.
7. Flexible ducts cannot have porous inner cores.
❑
§ 114: Pool and Spa Heating Systems and Equipment
1. A thermal efficiency.that complies with the Appliance Efficiency Regulations, on-off switch mounted outside of the
❑
heater, weatherproof operating instructions, no electric resistance heating and no pilot light.
2. System is installed with:
a. At least 36" of pipe between filter and heater for future solar heating.
❑
b. Cover for outdoor pools or outdoor spas.
❑
3. Pool system has directional inlets and a circulation pump time switch.
❑
§ 115: Gas fired fan -type central furnaces, pool heaters, spa heaters or household cooking appliances have no continuously.
❑
burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr)
§.118 (1): Cool Roof material meets specified criteria
❑
Lighting Measures
§ 150(k)1: HIGH EFFICACY LUMINAIRES OTHER THAN OUTDOOR HID: contain only high efficacy lamps as outlined in Table
❑
150-C, and do not contain a medium screw base socket (E24/E26). Ballasts for lamps 13 Watts or greater are electric
and have an output frequency no less than 20 kHz.
§ 150(k)I HIGH EFFICACY LUMINAIRES - OUTDOOR HID: contain only high efficacy lamps as outlined in Table'150-C,
❑
luminaire has factory installed HID ballast. -
§ 150(k)2: Permanently installed luminaires in kitchens shag be high efficacy luminaires. Up to 50% of the Wattage, as determined
❑
in Section 130(c), of permanently installed luminaires in kitchens may be in luminaires that are not high efficacy luminaires,
provided that these luminaires are controlled by switches separate from those controlling the high efficacy luminaires.
§ 150(k)3: Permanently installed luminaires in bathrooms, garages, laundry rooms, utility rooms shall be high efficacy luminaires.
❑
OR are controlled by an occupant sensor(s) certfied to comply with Section 119(d).
§ 150(k)4: Permanently installed luminaires located other than in kitchens bathrooms,ggaragges, laundry rooms, and utility rooms
shall be high efficacy luminaires (except closets less than 70 ft) OR are controlled by a dimmer switch OR are controlled
❑
by an occupant sensor that complies with Section 119(d) that does not tum on automatically or have an always on option.
§ 150(k)5: Luminaires that are recessed into insulated ceilings are approved for zero clearance insulation cover (IC) and are
❑
certified to ASTM E283 and labeled as air tight (AT) to less than 2.0 CFM at 75 Pascals.
§ 150(k)6: Luminaires providing outdoor lighting and permanently mounted to a residential building or to other buildings on the
❑
same lot shall be high efficacy luminaires (not including lighting around swimming pools/water features or other Article 680
locations) OR are controlled by occupant sensors with integral photo control certified to comply with Section 119(d).
§ 150(k)7: Lighting for parking lots for 8 or more vehicles shall have lighting that complies with Sections 130, 132, and 147.
❑
Lighting for parking garages.for 8 or more vehicles shall have lighting that complies with.Section 130, 131, and 146.
§ 150(k)8: Permanently installed lighting in the enclosed; non -dwelling spaces of low-rise residential buildings with four or more
❑
dwelling units shall be high efficacy luminaires OR are controlled by occupant sensor(s) certified to comply with Section 11 S(d).
4.4 .by EnergySoft User Number: 2655 Job Number:
RX ❑
N ❑
® ❑
® ❑
® ❑
® ❑
® ❑
�W
0
MENIKEN
❑ ❑
Page:7 of 11
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Mitchell Casita Addition 7/28/2009
SYSTEM NAME FLOOR AREA
Addition 340
Number of Systems
2
Heating System
Output per System
7,800
Total Output (Btuh)
15,600
Output (Btuh/sgft)
45.9
Cooling System
Output per System
8,900
Total Output (Stuh)
17,800
Total Output (Tons)
1.5
Total Output (Btuh/sgft)
52.4
Total Output (sgft/Ton)
229.2
Air System
CFM per System
300
Airflow (cfm)
600
Airflow (cfm/sgft)
1.76
Airflow (cfm/Ton)
404.5
Outside Air (°/6)
0.0
Outside Air (cfm/sgft)
0.00
Note: values above given at ARI conditions
Outside Air
0 cfm
Outside Air
0 cfm
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
ICOIL HTG. PEAK
CFM Sensible Latent
CFM
Sensible
584
11,361
1,002
474
7,700
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11,3611 1.0021
7 700
Carrier 52COA209301AA 11,678 4,357 9,743
Total Adjusted System Output �11 s78 4,357 9,743
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 pm an 12 am
Supply Fan Heating Coil
600 cfm
Supply Fan Cooling Coil
600 cfm
h Return Air Ducts. `i
h Return Air Ducts 4
Supply Air Ducts
ROOMS
Supply Air Ducts
51.7%. R.H. ROOMS
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Paa.8 of 11
W&
��i.:• 9.•' r AArt,&P,f;:.ACiJ:�+:zcti�n;J
C(:U
8- r
c tUt+
3,0 r t tt1C''. 0 fr1913YP, c)c T?ijki)A kJoi 0 �
rr .v „0;.^x(1 p, �'...e,.n•
t:rriS i��jA AA3q t,13TMY210 5MI'T CG.^
msfavE 11A
ma)atr' 1o:, M:I:) ^
()tpo;�tio) :vo4siA
Mol, nl.) WOO IM
(01, lit, 013 OO
(lipe"'Tita) !)A ubWuO
t--- enci)ibzo,, IPA to navitl evodr_ ar ►4ev :gtc'7
)9 pn_i!sgFf to 9m.. i , oauj1sicf mf -T mr,�y}2tt!i 2�1f� i' „il��:t 3; 12g M4
V
21VICI()Ri
L.- -1 -
101A 11A y4qqu"l
LA r"O'T ,CJ
aft. U
ya4 pailcoO to smiT to zotutr-m mgt tr-mfaAA) 20t2��BeAOSHOY"sq W1*i2Y2 0yi1.1Co-,
I
9 _ . ' CIT ,�` e,.
..
YRANiii.AW tSQAO.! DMIJ000 CMA 31.A,frA3H P413T8 L 8 OAV€"ii
A(3
ZIMA41 T;)3 osq
f?(30S��S1r
nofiibbA sties; i I'lodaiiM
F1 �i SOOs?
- 3a1aL; ht3Tc Yu
nciii;bbA
1s.a.....�.+�..._..v...».
....�..� ..�•_
'7A 1'riiT�`.
...�.rw.
.�.+...........�..+.�....�G•�.i
JClI��C.i VAI !i«��:t:1 Yi
AA3q •s1Tl'i .SI(;::),
ff`fi31. tt)r1Ij00,-o .ItG0
c
2frl'Jiu�� tO ;;1L�fZU3/1
:,ICE, nn8 CPO
tnefa-1 r)Icst2nu? +�1�
_
rr+afayc nnib,9H
WA -W.
SUG t .dr t t PO
ebsoJ mcoH IntoT
mwa) a *gq luq)iip
Goi)rtgLJ br+tnaV nuulsq
C'Qd ar
(IiIJ13) lut WO IsloT
$tat;G 7!A muNA!
WgfuO
L`
0
P►6� nlUtA`r�
_
_ RlBt�yc�, �f+ttU(i�
0 G
~
)ugtuO
o
e
r1s:1ytgttu2
t��>:.i:
(fl;r:S))uct)uOletoT
r,
u
2touCl iiA �1lgquc
.r
(ono, ? lutimO tntoT
G�OJ-I'�^3Tr;`12 .TATO i
(.Sr
(ilea fiu)ri) it;q!%-,O )okiT
_.
S.F c
(noTd)�.:) ):Jt;tut3 calci
W&
��i.:• 9.•' r AArt,&P,f;:.ACiJ:�+:zcti�n;J
C(:U
8- r
c tUt+
3,0 r t tt1C''. 0 fr1913YP, c)c T?ijki)A kJoi 0 �
rr .v „0;.^x(1 p, �'...e,.n•
t:rriS i��jA AA3q t,13TMY210 5MI'T CG.^
msfavE 11A
ma)atr' 1o:, M:I:) ^
()tpo;�tio) :vo4siA
Mol, nl.) WOO IM
(01, lit, 013 OO
(lipe"'Tita) !)A ubWuO
t--- enci)ibzo,, IPA to navitl evodr_ ar ►4ev :gtc'7
)9 pn_i!sgFf to 9m.. i , oauj1sicf mf -T mr,�y}2tt!i 2�1f� i' „il��:t 3; 12g M4
V
21VICI()Ri
L.- -1 -
101A 11A y4qqu"l
LA r"O'T ,CJ
aft. U
ya4 pailcoO to smiT to zotutr-m mgt tr-mfaAA) 20t2��BeAOSHOY"sq W1*i2Y2 0yi1.1Co-,
I
9 _ . ' CIT ,�` e,.
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Mitchell Casita Addition 7/28/2009
SYSTEM NAME FLOOR AREA
Living Zone 430
SYSTEM LAAO
NGINEERING CHECKS
Number of Systems
1
Heating System
Output per System
56,000
Total Output (Btuh)
56,000
Output (Btuh/sqft)
130.2
Cooling System
Output per System
36,000
Total Output (Stuh)
36,000
Total Output (Tons)
3.0
Total Output (Btuh/sgft)
63.7
Total Output (sgft/Ton)
143.3
Air System
CFM per System
1,500
Airflow (cfm)
1,500
Alrflow (cfm/sgft)
3.49
Airflow (cfm/Ton)
500.0
Outside Air (%)
0.0
Outside Air (cfm/sgft)
0.00
Note: values above given at ARI conditions
Outside Air
0 cfm
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG.
1,130
Sensible Latent
tPEAKCFM
CFM Se
996
10,704
1,130
299
.10,556
0
2,152
1,512
0
0
0
0
0
0
0
0
0
2,152
1,512
15 00 1 130 13 5i30
Exist 20,419 14,230 56,000
Total Adjusted System Output20,419 14,230 56,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 m an 12 am
Supply Fan Heating Coil
1500 cfm
Supply Air Ducts
ROOMS
h Return Air Ducts
:DOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
Al
Supply Air Ducts
Outside Air =0=—
0cfm
Supply Fan Cooling Coil
1500 cfm 64.3% R.H. ROOMS
Return Air Ducts
I EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Paoe:9 of 11 1
ROOM LOAD SUMMARY
PROJECT NAME
Mitchell Casita Addition
DATE
7/28/2009
SYSTEM NAME
Addition
FLOOR AREA
340
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Addition
Addition
1
584
11,361
1,002
584
11,361
1,002
474
7,700
PAGE TOTAL 1 5841 11,361 1,002 474 7,700
TOTAL 1 584 11,361 1,002 474 7,700
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:10 of 11
ROOM LOAD SUMMARY
PROJECT NAME
Mitchell Casita Addition ,
DATE
7/28/2009
SYSTEM NAME
Living Zone
FLOOR AREA
430
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL G. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Existina Casita
Existing Casita
1
996
10,704
1,130
996
10,704
1,130
299
10,556
PAGE TOTAL 1 996 10,704 1,130
TOTAL L 996 10,704 1,130
299 10,556
299
10,556
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 11 of 11