10-0915 (SFD) Revision,.. Bin# .. ... .,.... .. . ,. ... ...... ,
City of La Quinta .
Building d Safety Division
Permit #.\� P.O. Box 1504, 78-495 Calle Tampico
La Quints, CA 92253 - (760) 777-7012
� Building Permit Application and Tracking Sheet
Project Address:
Owner's Name:.
A. P. Number: f y- �! '
L �7r Address7509WAtMz5-5"512-
Legal Description:
I > :City, ST, Zipll/:
9�Z'a,sj
Contractor: Dec* IN6 IhTone
f :*
Address:rJ� f �2 ProjectDescription:
VOl -1-AnIv o iF-
City, ST, Zip: (✓� G� i !�G `J 2j �/!% �f�v `.��5 %� � ��
Tele hone: (f— / !.�-'' ��� -•:... ;,.:v:. :' ::::;:.:<• :s;:;.;;
State Lic. # :��� City Lic.
Arch., Engr., Designer: �/�
Address: 7 c pao,460 s �—Kl
City, ST, Zip:
/ L7V " / r ` til:;.„`9>'':%L:z.':;;f�"'A.'.%;E':"':td.•';;::<•' x
Telephone:
Construction Type:Occupancy:
' �•�+: �: w^C�::i r..v`'r� :}.:Cii�:�{:Y:iK:wv'i�
�; Pro'eet circle one): New Add'n Alter Repair Demo
State Lic. #: igy4:s>: ....:.:::.... ,•:.,:,-;s,:;,: ^..4. type
Name of Contact Person: q. qD # Stories: #Units;
Telephone # of Contact Person: OZ. pj
Estimated Value of Project: DOO
APPLICANT: DO NOT WRITE BELOW THIS UNE
#
Submittal
Req'd
Reecnc'd
TRACKING PERMIT FEES
Plan Sets
oG
Plan Check submi
! Item
Plan Check Deposit
plan Check Balance
Construction
Amount
Structural Calcs.
Reviewed, ready fo correctio
Truss Calcs.
Called Contact Person
Title 24 Calcs.
a,
Plans picked up
Flood plain plan
Plans resubmitted
i Mechanical
Grading plan
2' Review, ready for correction issue
Electrical
Subcontactor List
Called Contact Person
lambing
S M I
Grant Deed
Plans picked up
H.P.A. Approval
Plans resubmitted
Grading
IN HOUSE:-
3" Review, ready for corrections/issue
Developer Impact Fee
Planning Approval .
Called Contact Person
A.I.P.P.
Pub. Wks. Appr
Date of permit issue
School Fees
Total Permit Fees
y1111 jum - So -w-4 bvt 41% 41210 , ,alae.
User Number: 3665
EnergyPro 5.Y by EnergySoft Job Number: ID:
r) •
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
"Colonial"
i Building Type- 0 Single Family ❑ Addition Alone
O Multi Family 0' Existing+ Addition/Alteration 1212712012
Date
Project Address
81-681 Baffin Ave. La Quinta
California Energy Climate Zone
CA Climate Zone 15
;Total Cond: Floo
5,42671
Addition
n/a
; # of Stories ,
2
FIELD INSPECTION ENERGY CHECKLIST
El Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes : ❑ No Special Features =- If Yes, see Part 2 of.5 of this.form for details.
INSULATION
Construction Type
Area: Special
Cavity Features see Part 2 of 5 Status
Roof _ _ Wood Framed Rafter R-38 4,478.. New
Wall. Wood Framed R-19 5,428 New
Slab Unheated Slab -on -Grade None 4,484 Perim =499' New
Demising . Wood Framed w/Crawl Space R-13 948 New '
Door -'Opaque Door None 40 New
Door Opaque Door None 24 New
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhand Sidef ins Shades. Status
Left (E) 40.0 0.340
0.28 8.0 none Bug Screen New
Left (E) 40.0 0.340
0.28. 8.0 none • - .. Bug Screen New
Left (E) 8.0 0.340:
0.28 8.0 none Bug Screen New =
Rear (S) 72.0 0.710
0.60 4.0 none : Bug Screen New
Right (W) 4.5 0.340
0.28 2.0 none Bug Screen New
Right (W) 20.0 0.710
0.60 2.0none, Bug Screen New
Right (W) 20.0 0.340
0.28 2.0 none Bug Screen New
Right (W) 4.5 0.340
0.28 2.0' none Bug.Screen New
Left (E) 39.0 0.340
0.28 - 10.0 none, Bug Screen New
Right (W) 40.0 0.340
0.28 2.0 none Bug Screen New
Right (W) 4.5 0.340 0.28 2.0 ' none.. Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff
Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE
Split Air Conditioner 14.5 SEER Setback
New
.1. Central Furnace . 80% AFUE
Split Air Conditioner 15.0 SEER Setback
New
1 Central Furnace 80% AFUE
Split Air Conditioner 14.0 SEER Setback
New
HVAC DISTRIBUTION _
Location Heating
Duct
Cooling Duct Location "R -Value Status
AC #1 Ducted
Ducted Attic, Ceiling Ins, vented 6.0
New.
AC #2 Ducted
Ducted Attic, Ceiling Ins, vented 6.0
New
AC #3 Ducted
Ducted • Attic, Ceiling Ins, vented 6.0. '
New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
1 Large Gas 58
0.76 Recirc/Time+Temp _ New
Ener Pro 5.1 by Ener Soft User Number: 3665
RunCode:.2012-02-27713:56:06 _ ID:
Page 3 of 41.
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
"Colonial"
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/27/2012
Project Address
81-681 Baffin Ave. La Quinta
California Energy Climate Zone
CA Climate Zone 15.
Total Cond. Floor Area
5,426
Addition
ri
# of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
El Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area. Special
Construction Type Cavit Features see Part 2 of 5 Status
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhand Sidefins Shades. Status
Right (lM 4.5 0.340 0.28 2.0 none Bug Screen New
Right (W) 27.0 0.340 0.28. 2.0. none _ Bug Screen New
Front (N) 4.5 0.340. 0.28 10.0 none Bug Screen New
Front (N) 5.5 0.340 0.28 none none Bug Screen New
Front (N) 5.5 0.340 0.28 none none Bug Screen New
Front (N) 6.0 0.340 0.28 none none Bug Screen New
Front (N) 3.0 .. - 0.340. 0.28 none none Bug Screen. New .
Front (N) 3.0 0.340 0.28 . none none _ Bug Screen New
Front (N) 13.5 0.340 0.28 2.0 none Bug Screen New
Left (E) 6.0 0.340 0.28 2.0 none Bug Screen New
Left (E) 6.0 0.340 0.28 2.0 none Bug Screen New ,
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff. Thermostat Status
1 Central Furnace 80% AFUE Split Air Conditioner 15.0 SEER Setback -New
1 Split Heat Pump 3.2 kW Variable Refrigerant Flo 2.4 kW Setback
New
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
AC #4 Ducted Ducted Attic, Ceiling Ins, vented 6.0 New
AC #5 Ducted Ducted Attic, Ceiling Ins, vented " 6.0 New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
Ener Pro 5.1 by Ener Soft User Number: 3665 RunCode: 2012-02-27T13:56:06 ID:
Page 4 of 41
PERFORMANCE CERTIFICATE: Residential . Part 1 of 5
CF -1 R
Project Name
"Colonial"
Building Type ® Single Family ❑ .Addition Alone
❑ Multi Family 0 Existing+ Addition/Alteration
Date
2127/2012
Project Address
81-681 Baffin Ave. La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,426
-. Addition
n/a
'
# of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
El Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features.-- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area. Special
Construction Type Cavit Features see Part 2 of 5
Status
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades
Status
Left (E) 13.5 0.340 0.28' 3.0 none Bug Screen
New
Left (E) 24.0 0.710 0.60 _ 4.0 none . Bug Screen
New
Left (E) 39.0 - 0.340 0.28 • 10.0 none Bug Screen
New
Left (E) 39.0 0.340 0.28 10.0 none Bug Screen -
New
Left (SE) • 6.0 0.340 0.28 . none none Bug Screen
New
Rear (S) 3.8 0.340 0.28: none none. Bug Screen
New .
Rear (S) .. 3.8 0.340, 0.28 none . none Bug Screen,
New
Rear(S) 3.8 0.340 : , 0.28 none none Bug Screen
New
Rear (S) 3.8 0.340 0.28 none none Bug Screen
New
Rear (S) 3.8 0.340. 0.28 none none 'Bug Screen
New
Rear (S) 3.8 0.340 0.28 none none Bug Screen
New
HVAC SYSTEMS
Ot . • Heating Min. Eff Cooling Min. Eff Thermostat
Status
HVAC DISTRIBUTION Duct': .
Location Heating Cooling Duct Location R -Value •
Status
WATER HEATING
Qty. Type Gallons Min. Eff-Distribution
Status
Ener Pro 5.1 by Ener Soft User Number: 3665 RunCode: 2012-02-27T13:56:06 ID:
Page 5 of 41
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
"Colonial"
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/27/2012
Project Address
81-681 Baffin Ave. La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,426
Addition
n/a
# of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
EI Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavity Features see Part 2 of 5 Status
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidef ins Shades Status
Rear (S) 216.0 0.340 0.28 4.0 none Bug Screen New
Rear (S) 72.0 0.340 0.28 10.0 none Bug Screen New
Right (IM 3.8 0.340 0.28 none none Bug Screen New
Right (tM 3.8 0.340 0.28 none none Bug Screen New
Rear (SK9 6.0 0.340 0.28 none none Bug Screen New
Front (N) 14.0 0.340 0.28 none none Bug Screen New
Front (N) 14.0 0.340 0.28 none none Bug Screen New
Front (N) 14.0 0.340 0.28 none none Bug Screen New
Front (N) 14.0 0.340 0.28 none none Bug Screen New
Left (E) 11.3 0.340 0.28 none none Bug Screen New
Left (E) 11.3 0.340 0.28 none none Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
Ener Pro 5.1 by Ener Soft User Number., 3665 RunCode: 2012-02-27713:56:06 ID:
Page 6 of 41
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
"Colonial"
; Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1212712012
Project Address
81-681 Baffin Ave. La Quinta
California Energy Climate Zone
CA Climate Zone 15
' Total Cond. Floor Area
5,426
Addition .
n/a
# of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes • ❑ No Special Features =- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavit Features see Part 2 of 5
Status
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades
Status
Left (E) 10.0 - 0.340 0.28 none none Bug Screen
New
Left (E) 5.0 0.340 - 0.28 none none . Bug Screen New
Rear (S) 20.0 0.340 0.28 none none Bug Screen
New
Rear (S) 48.0 0.340 0.28 none . none Bug Screen
New
Rear (S) 20.0 0.340 0.28 none none Bug Screen
'New
Right 10.0 0.340 0.28 none none Bug Screen
New
Front (N) 15.0 :. - 0.340 - 0.28 2.0 none Bug Screen . , '
New.
Front (N) 95.0 0.340 0.28 2.0 none Bu Screen
Bug
New
Left (E) 8.0 0.340 0.28 none none Bug Screen
'New
Left (E) 39.0 0.340. 0.28 10.0 none Bug Screen
New
Right (149 4.5 0.340 0.28 2.0- none Bug Screen
New
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff • Thermostat
Status
HVAC DISTRIBUTION Duct -
Location Heating Cooling Duct Location R -Value
Status
WATER HEATING
Ot . Type Gallons Min. Eff Distribution
Status
Ener Pro 5.1 by Ener Soft User Number: 3665 RunCode: 2012-02-27T13:56:06 ID:
Page 7 of 41
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name
"Colonial"
Building Type ® Single Family ❑ Addition Alone .
13Multi Family 13Existing+ Addition/Alteration
Date
1212712012
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention tothe items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
The DHW System Rheem RGH PRO -75F is a non-NAECA large storage gas water heater. Verify DHW details.
A hot water recirculation systems has been modeled. Verification of type is required.
The HVAC System AC #1 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
The HVAC System AC #2 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
The HVAC System AC #4 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
The HVAC System AC #5 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
The Cooling System Lennox 14ACXISL280UH110 (4 Ton) includes credit for a 12.0 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System AC #1 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System AC #1 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Lennox 14ACXISL280UH090 (3 Ton) includes credit for a 12.5 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System AC #2 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System AC #2 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Lennox 14ACX/SL280UH110 (5 Ton) includes credit for a 12.0 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System AC #3 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System AC #3 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Lennox 14ACXISL280UH090 (3 Ton) includes credit for a 12.5 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System AC #4 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System AC #4 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
Ener Pro 5.1 by Ener Soft User Number: 3665 RunCode: 2012-02-27T13:56:06 ID: Page 8 of 41
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name%
"Colonial"
Building Type ® Single Family 0 Addition Alone
0 Multi Family O Existing+ Addition/Alteration
Date
2127/2012
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
The HVAC System AC #5 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
Ener Pro 5.1 by Ener Soft User Number: 3665 _ RunCode: 2012-02-27713:56:06 ID: Paq e 9 of 41
PERFORMANCE CERTIFICATE: Residential '.''(Part 3 of R1 CF -1 R
Project Name
Building Type m Single Family OAddition Alone
Date
"Colonial" :.
❑ Multi Family O Existing+. Addition/Alteration
2/27/2012
ANNUAL ENERGY: USE SUMMARY
Standard Proposed Margin
TDV kBtu%ft2- r
Space Heating .. 4.55 -4.85 .. 0.30: .
Space Cooling 67.39' 54.84 12.55
Fans 13.30 15.44 -2.13
Domestic Hot Water 6.33 11.68 -5.35
Pumps 0.00..° 0.10.° 70.10:
Totals 91.57 86.91 -4.67
Percent Better•Than Standard: b.1 i
BUILDING COMPLIES - HERS VERIFICATION REQUIRED
enestratlon
Building Front Orientation: (N) 0 deg Ext. Walls/Roof Wall Area* Area
Number -of Dwelling Units-. 1.00 :' (N) 1,441- 127
Fuel Available at Site: Natural Gas (E) 1,928 345:
Raised Floor Area: o (S) 1,448 477
Slab on Grade Area: 4,484 (IAS 1,772 147
Average'Ceiling Height: ;. 12.0 Roof 4,478 ; 0
Fenestration Average* U -Factor: ' 0.38 TOTAL: 1,096'
Average SHGC: 0.31 Fenestration/CFA Ratio: _ 20.2
REMARKS
STATEMENT OF COMPLIANCE
This certificate of compliance lists the, building features and specifications needed'
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the'documentation is accurate and complete:
Documentation Author
Company ; • BREEZE AIR CONDITIONING
Address 75-145 St. Charles Place Name Scott DeVoe 2/27/2012
City/State/Zip. Palm Desert, CA 92211 Phone (760) 346-0855 Signed Date
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with the specifications,. and ;
with any other calculations submitted with this permit application, and recognizes that compliance using duct design,
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require . .
installer testing and certification and field verification by an approved HERS rater. :.
Designer or Owner (per Business & Pro fessions:Code)';
Company PHX Arch .
(Scott
Address 7507 E McDonald Dr. Suite B Name Carson
City/State/Zip Scottsdale, AZ 85250 Phone (480);477-1111• _.: Signed ::. 'License # Date
Ener Pro 5.1 by Ener Soft User Number.
3665 RunCode: 2012-02-27713:56:06 � . ID: Pa e' 10 of 41 ; ' .
CERTIFICATE OF COMPLIANCE:
Residential Part 4 of 5 CF -1 R
Project Name
"Colonial"
Building Type ❑ Single Family ❑ Addition Alone
❑ Multi Family . ❑ Existing+ Addition/Alteration
f Date
2/27/2012
OPAQUE SURFACE DETAILS
Surface ' U- Insulation ; ' Joint Appendix
Type Area Factor: Cavit ;':Exterior ;Frame Interior1Frame Azm ; Tilt Status 4 Location/Comments
Roof. 992 i
0.029, R-38
270.
0 `New 4.2.2-A18
Zone #1
Wall 72: ;
0.074 R-19
0.
90 New 4.3:1-A5
Zone #1
Wall 230
0.074 R-1990:'
90 New 4.3.1-A5
Zone #1
Wall = 246::
0.074 'R-19
180'.
90 New 4.3.1-A5
Zone #1
Wall 521
0.074 R-19
270.
90 New 4.3.1-A5
Zone #1
Slab 992.:
0.730 None
0.
180; New 4.4.7-A1
Zone #1
Roof 867 `
0.029, R-38
270:
0 New 4.2.2-A 18
Zone #2
Wall 24
0.074 R-19
0
90 New 4.3.1-A5
Zone #2
Wall 153`'
0.074. 'R-19.
90
901 New 4.3.1-A5
Zone#2
Wall 17 '
0.074 R-19180.:
90 New 4.3.1-A5
Zone #2
Wall 440,
0.074,'R-19270;
90 New 4.3.1-A5
Zone #2
Slab 867 '
0.730 None0.:
180: New 4.4.7-A1
Zone #2
Demising 9481;
0.046, R-13
; `
0,
90 New 4.4.1-A3
Zone #3 faces Great Roo
Roof 1,162, ,
0.029''R-38
270, ;
0,New 4.2.2-A18
Zone #3
Wall . 747:
0.074: R-19
0.
90 New 4.3.1-A5
Zone #3. _
Door r 40; ;
1.450: None ` ,
0
901 New 4.5.1-A1
Zone #3
FENESTRATION SURFACE DETAILS
ID " Type Area ;', U -Factor
SHGC.
Azm;:_Status Glazing Type
Location/Comments
1 - Window
40.0; ' 0.340. ;NFRC
0.281 NFRC
90, New
= Loewen Mticlad Low -E(11914)
:.Zone #1
2 Window
40.0 0.340; NFRC
0.28; ,NFRC
90 :New
Loewen Mticlad Low -E(11913) 'Zone #1
3 ; .Window
8.0; 0.340; NFRC
0.26:NFRC90
New
Loewen Mticlad Low -E 119/8
"Zone #1
4 Window
72.0, 0.710 Default
1 0.0 pefault 180 New
Default Dbl Mt/ Tint(1191A)
Zone #1
5 Window
4.5 0.340'NFRC
0.28 NFRC
270 New
Loewen Mticlad Low-E(1201A)
; Zone #1
6 Window
20.0'; 0.710 Default
0.60 Default
270. New
]`Default Dbl Mtl Tint(12012)
Zone #1
7 Window '
20.0;' 0.340 'NFRC
0.28' NFRC
270; New
Loewen Mticlad Low -E(12013)
;Zone #1
8 ; Window
4.5, ° 0.340 NFRC
0.281 NFRC
270 New
Loewen Mticlad Low-E(1201B)
Zone #1
9 Window
39.0' 0.340 NFRC
0.28 NFRC
90 New
Loewen Mticlad Low -E(12911) ''Zone #2
10 .,Window
40.0` 0.340 NFRC ;
. 0.28: NFRC
270 New
..Loewen Mticlad Low -E(12511)
; :Zone #2
11 ` Window
4.5' . 0.340_ NFRC
0.28; NFRC
270, New
Loewen Mticlad Low-E(1261A)
Zone #2
12 'Window
4.5;: 0.340' NFRC
0.28 NFRC
270 New
Loewen Mticlad Low-E(1271A)
,Zone #2
13 Window
27.0.. 0.340: NFRC
0.28; NFRC
270. New
Loewen Mticlad Low-E(1291A)
: Zone #2
14 Window
4.5! 0.340 NFRC
0.28 NFRC
0. New
Loewen Mticlad Low-E(1331A)
Zone #3
15 Window
5.54 0.340, NFRC
0.28''NFRC
0; New
Loewen Mticlad Low-E(117/A)
` Zone #3
16 Window 1
5.5' 0.340 NFRC
0.28 NFRC
0 New
Loewen Mticlad Low-E(117/B)
; Zone #3
(1) Ll -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-13 = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID Exterior Shade Type SHGC
Window
H t ; Wd
Overhanq Left Fin Ri ht Fin
Len H t 1 RExt ' Dist ' Len H t Dist Len H t
1 ug Screen
0.76
8.0; 5.0
8.0 0.1
8.0
2 'Bug Screen
0.76
8.0; 5.0.
8.0 0.1
8.0 .
14.01
3 ', ug Screen
0.76_
4.0: 2.0'
8.0, 0.1;
.
8.01
4 Bug Screen
0.76
6.0: 12.0..
4.0 0.14.01
5 ug Screen0.76.
3.0 1.6
2.0. 0.1.
2.0'.
6 Bug Screen
0.76,
8.0'; 2.6,
2.0. 0.1_
2.0. 2.0..
7 foug Screen
0.76;
8.0' 2.6 .
2.0 0.1
2.0 . 2.0: ,
8 i Bug Screen
0.76
3.0. 1.6;
2.0 0. 1;
2.0 2.0;
9 : Bug Screen
0.76
6.6; _ 6.0_
10.0: 0.1.,
10.0 10.0'
10 . Bug Screen.
0.76
8.01 5.0;
2.0 0.111, .
2.0, 2.0
11 Pug Screen
0.76.
3.0` 1.6'
2.0; 0.1:
2.0 2.0
12 ; Bug Screen
0.76;
3.0t. 1.6 _
2.0 ` 0.1,
2.01 2.0-
113 Buo Screen _.
0. 76
4.51 6.0
2.0, _ 0.1 '
2.0; 2.01.
`
14 fflug Screen
0. 76,
3.01; 1.61
10.0: 0.1;
10.0; 10.0:
15 Bug Screen
0.76
16 ,Bug Screen_ _
: ;_ 0.76,
17
Ener Pro 5.1 6 Ener Soft User Number: 3665 RunCode: 2012-02-27T13:56:06 ID::
Pae 11 of 41
CERTIFICATE OF COMPLIANCE:
Residential Part 4 of 5 CF -1 R
Project Name
"Colonial"
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/27/2012
OPAQUE SURFACE DETAILS
Surface '
Type Area
U- Insulation
Factor 'Cavity 'Exterior 'Frame Interior frame. Azm
Joint Appendix
Tilt Status 4 Location/Comments
Wall
. 647
0.074 R-1990.
90 ;New 4.3.1-A5
Zone #3
Wall
8 `
0.074 'R-19
135
90 New 4.3.1-A5
Zone #3
Wall
493
0.074. 'R-19
1861
90. New 4.3.1-A5
Zone #3
Wall
184..
0.074 R -19-A5
90' New 4.3.1-A5
Zone #3
Wall
8.
0.074,R-19
225 '
90 1 New 4.3.1-A5
Zone #3
Slab
2,110,
0.736 None
6
180 'New 4.4.7-A1
Zone #3
Roof
942
0.029. R-38270.
;
0: 'New 4.2.2-A18
Zone #4
Wall
166.
0.074 R-19
0
90; "New 14.3.1-A5
Zone #4
Wall
352;
0.074 R-19
90
90, New 4.3.1-A5
Zone #4
Wall
152.
0.074 'R-19
180.
90' New 4.3.1-A5
Zone #4
Wall
212,,
0.074 R-19
270,
90'New 4.3.1-A5
Zone #4
Door
24' .
1.450, None
27090;
'New 4.5.1-A1
Zone #4
Roof
515,
0.029''R-38
1611.01
New 4.2.2-A18
Zone #5
Wall
265`
0.074 'R-190.
:
90 New 4.3.1-A5
Zone #5
Wall
193
0.074 R-19
90.
90; New 4.3.1-A5
Zone #5
Wall55
0.074 `R-19
180
90 1New 14.3.1-A5
JZone #5
FENESTRATION SURFACE DETAILS
ID
Type Area ' ; U -Factor
SHGC
Azm :, Status ; Glazing Type
Location/Comments
17
'Window
6.01 0.340[NFRC
0.28; NFRC
0. ;New
Loewen Mtldad Low-E(1031B) ;
Zone #3
18
.Window
3.0 ; 0.340 NFRC
0.28 NFRC
0 New
Loewen Mtldad Low -E(1 17//)
Zone #3
19
Window
3.0' 0.340, NFRC
0.28 NFRC
0. ;New
Loewen Mtldad Low -E 117/H
Zone #3
20
Window
13.6 0.340 NFRC
0.28 NFRC
O'New
Loewen Mtldad Low-E(112/A) '
Zone #3
21
Window 1
6.0,' 0.340 NFRC
0.28 NFRC
901 New
Loewen Mtldad Low-E(114/B)
Zone #3
22
Window
6.0.1 0.340 NFRC
0.28 NFRC
90 New
Loewen Mtldad Low-E(114/A) ;Zone
#3
23
Window
13.5' . 0.340 NFRC
0.28, NFRC
90 New
Loewen Mtldad Low-E(112/B)
Zone #3
24
Window
24.0, 0.710 Default
0.60: ;Default
96 New
Default Dbl Mtl Tint(110/1)
Zone #3
25
Window
39.0 0.340; NFRC
0.28'. NFRC
90 New
-Loewen Mticlad Low -E(13212)
Zone #3 _
26
Window
39.0. 0.340, NFRC
0.28; NFRC
90 New
Loewen Mticlad Low -E(13211)
Zone 1f3
27
Window
6.0 0.340: NFRC
0.28 NFRC
135_ New
Loewen Mt/clad Low-E(1031A)
Zone #3
28
Window
3.8 , 0.340 NFRC
0.28. NFRC
180 New
Loewen Mticlad Low-E(117/C)
', :Zone #3
29
Window
3.8 0.340, NFRC
0.28 NFRC
180 New
Loewen Mt/clad Low -E 117/D
Zone #3
30
Window
3.8., 0.340. NFRC
0.28, NFRC
180 New
Loewen Mt/clad Low-E(117/E
Zone #3
31
Window
3.8 : 0.340 NFRC
0.28; NFRC
180 New
Loewen Mt/clad Low-E(116/A)
Zone #3
32
Window
3.8' : 0.340 NFRC
0.28 NFRC
180 New
Loewen Mt/clad Low-E(116/B) ' Zone #3
(1) LI -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
H t I Wd
Ove hanq Left Fin Ri ht Fin
Len LU2L ' LExt RExt , Dist Len H t Dist .' Len H t
17
: Bug Screen
0.76
18
Bug Screen
0.76
19
; Bug Screen
0.76
20
' Bug Screen
0.76,
4.6' 3.0'.
2.0; 0.1;
2.0. 2.0
21
Bug Screen
0.76
4.0 1.6,
2.01 0.1
2.012.0;
22
Bug Screen
0.76
4.0; 1.6.-
2.0,. 0.1
2.0'. 2.0'
23
Bug Screen
0.76,
4.61 3.0'
3.0 0.1
3.0' 3.0; . .
24
Bug Screen
0.76
- 8.0 3.0
4.0' 0.11 _
4.0. 4.0, _
25
; Bug Screen
0.76
6.6' 6.0
10.0 0. f
10.0 10.0'
26 ;,Bug Screen
0.76
6.6; 6.0J.
10.0, . 0.1
10.0; 10.01
27 ;'Bug Screen
0. 76,'
28
Bug Screen
0.76
29 'Bug Screen
0.76;
.
30
' Bug Screen
0.70;
31
' Bug Screen
0.76.
32
JBug Screen
0.76
Ener Pro 5.1 by Ener Soft User Number: 3665 RunCode: 2012-02-27713:56:06 ID:
Pae 12 of 41
CERTIFICATE OF COMPLIANCE: Residential Part 4 of5 CF -1 R
Project Name
"Colonial"
; Building Type m Single Family ❑' Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/27/2012
OPAQUE SURFACE DETAILS
Surface U-
Type : Area .:Factor
Insulation Joint Appendix
Cavity Exterior 'Frame Interior .Frame `Azm Tilt _ Status - 4 Location/Comments
Wall
r243. 0.074 R-19
270 90 New 4.3.1-A5
Zone #5
Slab
515 0.730 None
0 . 180, :New 4.4.7 -Al
Zone #5
FENESTRATION SURFACE DETAILS
ID
; Type Area '
U -Factor
SHGC
= Azm := Status Glazing Type
Location/Comments
33
Window I3.8
0.340: NFRC
0.28 JNFRC 180 New Loewen Milclad Low-E(116/C)
: Zone #3
34
Window 216.0
0.340. NFRC
0.28 'NFRC 180; New Loewen Mticlad Low -E(1 17/1)
_ Zone #3
35
Window 72.0.
0.340 NFRC
0.28 NFRC 180 :'New Loewen Mticlad Low -E 114/1
Zone #3
36
Window 3.8
0.340 NFRC
0.28 NFRC 270 New Loewen Mticlad Low-E(117/F)
: Zone #3
37
Window 3.8;
0.340' NFRC
0.28 NFRC 270 New Loewen Milclad Low-E(117/G)
Zone #3
38
Window . 6.0
0.340 NFRC
0.28 NFRC 225 New Loewen Mticlad Low-E(1031C)
' ;Zone #3
39
Window 14.0
0.340: NFRC
0.28, NFRC 0, -New Loewen Mticlad Low -E 203/8)
; -Zone #4
40
Window 14.0:.
0.340. NFRC
0.28. NFRC 0 New Loewen Mticlad Low-E(2031C)
_ Zone #4
41
Window 14.0
0.340 NFRC
0.28 NFRC 0 New Loewen Mticlad Low-E(2031D)
Zone #4
42
Window 14.0
0.340 NFRC
0.28' NFRC 0 New Loewen Mticlad Low-E(2031E)
Zone #4
43
11.3.
0.340_ `NFRC
0.28, NFRC 90. New Loewen Mticlad Low-E(2011B)
; Zone #4
44
11.3.
0.340 WFRC
0.28 NFRC 90 New Loewen Mticlad Low-E(2011A)
''Zone #4
45
NWindow
10.0
0.340-.NFRC
0.28 NFRC 90, New Loewen Mticlad Low-E(2031A)
' Zone #4
46
5.0
0.340. NFRC
0.28'NFRC 90, New Loewen Mticlad Low-E(103/D)
; Zone #4
47
20.0
0.340NFRC
0.28 NFRC 180 New Loewen Mticlad Low-E(201/C)
Zone #4
48
48.0"
0.340 'NFRC
0.28 NFRC 180 New Loewen Mticlad Low -E(20112)
Zone #4
(1) Ll -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
H t Wd
Ove Left Fin Right Fin
, Len H t ;: LExt RExt : Dist Len H t Dist Len H t
33
Bug Screen
0.76
34
Bug Screen
0.76
9.0' 24.0 4.0 0.1' 4.0 4.0,
35
Bug Screen
0.76
9.0 8.0' 10.0 0. 1; 10.0: 10.0
36
IlBug Screen
0.76.
37
, Bug Screen
0. 70 _
38
Bug Screen
0.76,
39
Bug Screen
0.76,
40
. Bug Screen
0.76
41
Bug Screen
0.76.
42
, Bug Screen _ .
0.76
43
: Bug Screen
0.76
;
44
Bug Screen
0.76.
45
Bug Screen
0.76;
46
Bug Screen
0.76.
47
Bug Screen
11 0.76
48
` Bug Screen
0.76
Ener Pro 5.1 by EnergySoft
User Number: 3665
RunCode: 2012-02-27T13:56:06 ID:
Pae 13 of 41
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
"Colonial"
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2127/2012
OPAQUE SURFACE DETAILS
Surface Ll-
Type Area 'Factor:Cavity
Insulation Joint Appendix
;Exterior, ;Frame Interior ;Frame Azm ; Tilt =Status .' 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID Type Area
LI -Factor SHGC2
Azm Status Glazing Type Location/Comments
49 Window 20.0.
0.340 NFRC 0.28; NFRC 180 New .Loewen Mticlad Low-E(2011D) ; Zone #4
50 , Window 10.0. ;•
0.340; `NFRC 0.28 NFRC 270 'New Loewen Mticlad Low-E(2031F) Zone #4
51 Window 15.0, :
0.340: NFRC 0.28 NFRC 0 New Loewen Mticlad Low-E(1341A) I Zone #5
52 ` Window 15.0
0.340; NFRC 0.28 NFRC 0 New Loewen Mticlad Low-E(1341B) ; Zone #5
53 IWfndow 8.0
0.340: NFRC 0.28 NFRC 90 New Loewen Mticlad Low-E(1371A) Zone #5
54 Window 39.0
0.340: NFRC 0.28NFRC 90 New Loewen Mticlad Low -E(13411) 'Zone #5
55 Window 4.5 _
0.340; NFRC 0.28 NFRC 270_ New Loewen Mticlad Low-E(1351A) Zone #5
(1) U -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-13 = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID Exterior Shade Type
Window
SHGC H t Wd
Overhanq Left Fin Right Fin
: Len H t LExt : RExt Dist . Len H t Dist Len H t
49 Bug Screen
0.76
50 Bug Screen
0.76 _
51 Bug Screen
0.76 5.0, _ 3.0' 2.0 0.1 2.0,: 2.0
52 1Bug Screen
0.76, 5.0' 3.0; 2.0_ 0.1! 2.0 2.0,
53 Bug Screen
0.76
54 . Bug Screen
0.76 6.6 6.0 _ 10.0: 0.11 10.0; ; 10.0
55 'Bug Screen
0.76 _ 3.0 _ 1.6 2.0 0.1! _ 2.0' 2.0
Ener Pro 5.1 by Ener Soft
User Number: 3665
RunCode: 2012-02-27T13:56:06 ID: Pae 14 of 41
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5
CF -1 R
Project Name
"Colonial"
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
: Date
2/27/2012
BUILDING ZONE INFORMATION
System Name
Zone Name
Floor Area ft
New Existinq Altered Removed Volume
Year Built
AC #1
;Master Suite
992
11,904
AC #2
Beds #1/#2
867.
10,404
AC #3
Great RoomiKitchen
2,110.
25,320
AC #4
Upstairs Casita
942
11,304
AC #5
Guest Casita
515 ;
6,180;
Totals : 5,426 ; 01 0 0
HVAC SYSTEMS
System Name
LO! . Heating Type
Min. Eff. Cooling Type Min. Eff. Thermostat Type
Status
AC #1
1 Central Furnace
80% AFUE Split Air Conditioner 14.5 SEER Setback
New
AC #2
1 Central Furnace
80% AFUE, Split Air Conditioner 15.0 SEER Setback
New
AC #3
1 Central Furnace
80% AFUE; Split Air Conditioner 14.0 SEER Setback
New
AC #4
1 _Central Furnace
80% AFUE Split Air Conditioner 15.0 SEER Setback
New
AC #5
1 Split Heat Pump
3.2 kW Variable Refrigerant Flo 2.4 kW Setback
'New
HVAC DISTRIBUTION
System Name
Heating
Duct
Cooling Duct Location R -Value
Ducts
Tested? Status
AC #1
Ducted Ducted Attic, Ceiling Ins, vented 6.0,
m
New
AC #2
'Ducted Ducted Attic, Ceiling Ins, vented 6.0
m
New
AC #3
Ducted Ducted Attic, Ceiling Ins, vented 6.0
E)
New
AC #4
Ducted Ducted lAttic, Ceiling Ins, vented 6.0
El
New
AC #5
Ducted I Ducted lAttic, Ceiling Ins, vented 6.0
m
New
WATER HEATING SYSTEMS
S stem Name
Qty.
Type
Distribution
qBtuh
Tank
Cap.
al
Energy Standby
Factor Loss or
or RE Pilot
Ext.
Tank
Insul. R-
Value
Status
Rheem RGH PRO -75F
1
Large Gas
Recirc/Time+Temp
58
0.76 3.50%
n/a
New
MULTI -FAMILY WATER
HEATING
DETAILS
I HYDRONIC
HEATING SYSTEM
PIPING
Control
Hot Water Piping Length
ft
C
O
c
—
S stem Name
Pipe
Len th ;
Pipe
Diameter
Insul.
Thick.
Ot . - HP
Plenum , Outside ;
Buried :
13
Ener Pro 5.1 by Ener Soft User Number: 3665
RunCode: 2012-02-27713:56:06 ID:
Pae 15 of 41
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3)'.,'. MF -1 R
Project Name
"Colonial"
Date
1212712012
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are show_ n elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form.
§118(1): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
.*§150(a): Minimum R-19 insulation in wood -frame ceiling orequivalent Ll -factor. _
150 b : Loose fill insulation shall conform with manufacturer's installed design labeled R -Value..
*§1 50 c : Minimum R-13 insulation in wood -frame wall orequivalent U -factor.
*§1 50 d .: Minimum R-13 insulation in raised wood -frame floor orequivalent LI -factor.
150(f): Air retarding wrap is tested labeled and installed according,to ASTM El 677-95 2000. when specified on the CF -1 R Form.
1 50 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0 permAnch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 e 1 A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)l B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible operable, and tight -fitting- damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage"connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
§150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§1506)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped'
with insulation having an installed thermal resistance of R-12 or greater.
§1506)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank. .
§1506)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculating, sections of hot water pipes are insulated.per Standards Table 150-13. '
§1506)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot
water tank shall be. insulated to Table 150-B and Equation 150-A. .
§1506)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
123-A.
1 50 ' 3A: Insulation is protected from damage, including that due to sunli ht moisture equipment maintenance , and wind.
§1506)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned s ace.
1500)4: Solar water -heating systems and/or collectors -are certified by the -Solar Rating and Certification Corporation.
EnergyPro 5.1 by Energysoft User Number. 3665 RunCode: 2012-02-27713:56:06 ID: Page 16 of 41
MANDATORY MEASURES SUMMARY: Residential '"(Page 2 of 3 MF -1 R
Project Name
Date
"Colonial"
; 2/27/2012
§150(m)l : All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums definedor constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts. .:.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed_ With cloth back rubber adhesive duct tapes .
-unless such tape is used in combination with mastic and draw bands.
150,(m)7: Exhaust fans stems have back draft or automatic dampers. -
§150(m)8: Gravity ventilating systemsserving conditionedspace have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that, is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150 m 10: Flexible ducts cannot have porous inner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
required in Section 4 of that Standard.
.Pool and .S a Heating Systems and. Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating or a. pilot light.
§114(b)l : Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and' heater, or dedicated suction
and return lines orbuilt-up connections for future solar heating.
114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a. time switch that will allow all pumps to beset or
programmed to run only during off-peak electric demand periods. .
150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150
Residential Lighting Measures:
§150(k)l : High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2.
150(k)3: The wattage. of permanently installed luminaires shall be determined asspecified by §130.(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz. :... :..
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall'contain
-only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
§150(k)6: Lighting integral to exhaust fans in rooms other than kitchens, shall meet the applicable,requirements of §150(k).
,§150(k)7: All switching devices and controls -shall meet the re uirements of §150(k)7..
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 wafts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS),' or a multi -scene programmable control system; and all permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility. rooms are high efficacy and controlled by a
manual -on occupant sensor.
§150(k)9: Permanently. installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet. •.
EnergyPro 5.1 by EnergySoft:. User Number: 3665 RunCode: 2012-02-27T13:56:06. ID:. Page 17 of 41
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
"Colonial"
2/27/2012
§150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)l 1: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with §150 k 11.
§150(k)l2: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)l3: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptionl to §150(k)l3 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be hi h efficacy luminaires.
§150(k)l4: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)l5: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130.131 134,, and 146.
§150(k)l6: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
EnergyPro 5.1 by EnergySoR User Number: 3665 RunCode: 2012-02-27T13:56:06 ID: Page 18 of 41
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
"Colonial"
Date
2/27/2012
System Name
AC #1
Floor Area
992
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 778
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 60
Supply Fan
Supply Air Ducts
SYSTEM LOAD
COOLING PEAK
Sensible
13,710
0
759 -
01-
2,505
0
7591:
17,733:
COIL HTG.
Latent CFM
1,701 766
1,148 60
2,848
PEAK
Heating System
Sensible
Output per System 88,000
19,967
Total Output Btuh 88,000
Output Btuh/s ft 88.7
886
Cooling System
0
Output per System 47,500
: 3,388
Total Output Btuh 47,500
0
Total Output ons 4.0
886
Total Out ut Btuh/s ft 47.9
Total Output s ft/Ton 250.6TOTAL
25,127
Air S stem
CFM per System
1,600
HVAC EQUIPMENT SELECTION
Airflow cfm
1,600
Lennox 14ACX/SL280UH110 (4 Ton)
36,253 `
3,819
88,000
1 88,000
Jan 1 AM
Airflow cfm/s ft 1.61
Airflow cfm/Ton 404.2
Outside Air°/, 3.7%
Total Adjusted System Output 36,253 r
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
3,819
Aug 3 PM
Outside Air cfm/s ft 0.06
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF 77 OF
Outside Air
60 cfm Supply Fan
1,600 cfm
79 OF
77 OF 105 OF
Heating Coil
104 OF
ROOM
80 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 74/62°F^ 74/62°F 55/54°F
Outside Air c
60 cfm Supply Fan Cooling Coil
1,600 cfm
72/61 °F
52.9%
55 / 54 OF
ROOM
72/61 °F
EnergyPro 5.1 by EnergySoft User Number: 3,665 RunCode: 2012-02-27713:56:06 ..
_ ID:
Page 19 of 41
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
"Colonial"
Date
2/27/2012
System Name
AC #2
Floor Area
867
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 497.
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 52
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 70,400
8,786:
1,712. 527
13,758
Total Output Btuh 70,400
0
=
Output Btuh/s ft 81.2
486
611
Cooling System
0
0
Output per System 34,600
2,193:
983 52
2,963
Total Output Btuh 34,600
0
4861.
11,952.
2,691%
0
Total Output ons 2.9
611
Total Output Btuh/s ft 39.9
Total Output s ftfTon 300.7
17,943
Air System
CFM per System
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Lennox 14ACX/SL280UH090 (3 Ton) 26,135
3,155
70,400
Airflow cfm/s ft
1.38
Airflow cfmfTon
416.2
Outside Air %
4.3%
Total Adjusted System Output 26,135,_
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
3,155-
Aug 3 PM
70,400
Outside Air cfm/s ft 0.06
Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 77 OF
0'
Outside Air
52 cfm Supply Fan
1,200 cfm
80 OF
77 OF 105 OF
Heating Coil
105 OF
ROOM
80 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 74/62°F 74/62°F 55/54°F
Outside Air c
52 cfm Supply Fan Cooling Coil 55 / 54 OF
1,200 cfm
53.3% ROOM
72/61 OF 72/61 OF
I
EnergyPro 5.1 by EnergySoft User Number: 3665 RunCode: 2012-02-27713:56:06 ID:
Page 20 of 41
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
"Colonial"
Date
2/27/2012
System Name
AC #3
Floor Area
2,110
ENGINEERING CHECKS ..
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,477
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 127
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output per System 88,000
25,667
3,592:
1,587
i 40,792
Total Output Btuh 88,000
0
;
Output Btuh/s ft 41.7
1,421
1,810
Cooling System,
0
0
Output per System 56,500
5,299
2,357 ; 1A
7,161
Total Output Btuh 56,500
0
1,421
33,807
5,950
0
Total Output ons 4.7
1,810
Total Output Btuh/s ft 26.8
Total Output s ft/Ton 448.1
51,574
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Lennox 14ACX/SL280UH110 (5 Ton)
34,941
; 13,314
` 88,000
U 88,000
Jan 1 AM
Airflow cfm/s ft 0.95
Airflow cfmrron 424.8
Outside Air % 6.3%
Total Adjusted System Output 34,941
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
13,314
Aug 3 PM
Outside Air cfm/s ft 0.06
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF 76 OF
Outside Air
127 cfm Supply Fan
2,000 cfm
79 OF
76 OF 105 OF
Heating Coil
104 OF
ROOM
80 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 75/62°F 75/63°F 55/54°F
C1c
Outside Air c
127 cfm Supply Fan Cooling Coil
2,000 cfm
73 / 61 OF
56 / 54 OF
--
53.7% ROOM
72 / 61 OF
EnergyPro 5.1 by EnergySoft User Number: 3665 RunCode: 2012-02-27T13:56:06
ID:
Page 21 of 41
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
"Colonial"
Date
2/27/2012
System Name
AC #4
Floor Area
942
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 665.
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 57
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK
Sensible ,
11,674 `
0
646
0
2,376
0,
646
15,342 ,
COIL HTG.
Latent CFM
1,625 ' 559
1,075 57
2,700.
PEAK
Heating System
Sensible
Output per System 70,400
14,563
Total Output Btuh 70,400
Output Btuh/s ft 74.7
646
Cooling System
0
Output per System 34,600
3,218
Total Output Btuh 34,600
0
Total Output (Tons) 2.9
646
Total Output Btuh/s ft 36.7
Total Output s fUTon 326.7
19,074
Air S stem
CFM per System
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Lennox 14ACX/SL280UH090 (3 Ton)
26,345.
2,981
70,400
70,400
Jan 1 AM
Airflow cfm/s ft 1.27
Airflow cfm/ron 416.2
Outside Air % 4.7%
Total Adjusted System Output 1 26,345
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
2,981
Aug 3 PM;
Outside Air cfm/s ft 0.06
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF 77 OF
Outside Air
57 cfm Supply Fan
1,200 cfm
79 °F
77 OF 105 OF
Heating Coil
rn
104 OF
ROOM
80 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 74/62°F 74/62°F 55/54°F
0 1-1
c
Outside Air c
57 cfm Supply Fan Cooling Coil
1,200 cfm
73 / 61 OF
53.2%
56 / 54 OF
ROOM
72 / 61 OF
EnergyPro 5.1 by EnergySoft User Number. 3665 RunCode: 2012-02-27713:56:06
ID:
Page 22 of 41
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
"Colonial"
Date
2/27/2012
System Name
AC #5
Floor Area
515
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
Sensible ' Latent CFM
7,063
1 7,063-1:12,491
PEAK
Heating System
Sensible
Output per System 34,000
12,491
Total Output Btuh 34,000
Output Btuh/s ft 66.0
Cooling System
Output per System 30,000
Total Output Btuh 30,000
Total Output ons 2.5
Total Output Btuh/s ft 58.3
Total Output s ft/Ton 206.0
Air System
CFM per System
0
HVAC EQUIPMENT SELECTION
Airflow cfm
0
Mitsubishi PUMY
25,796: 030,677
30,677
Jan 1 AM
Airflow cfm/s ft 0.00
Airflow cfm/Ton 0.0
Outside Air % 0.0%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
25,796 0
Aug 3 PM.
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
Outside Air
0 cfm
79 OF
72 OF 105 OF
Heating Coil
104 OF
ROOM
80 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling
Peak
112/78°F
Outside Air Ar
0 cfm
73/60°F
78/63°F 52/51 OF
C
Cooling Coil
53 / 51 OF
50.2 % ROOM
72/60°F
EnergyPro 5.1 by EnergySoft
User Number: 3665 RunCode: 2012-02-27713:56:06
ID: Page 23 of 41
I ROOM LOAD SUMMARY
vrolect Name Date
"Colonial" 2/27/2012
System Name Floor Area
AC #1 992
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible . Latent CFM Sensible Latent CFM Sensible
Zone # 1 Master Suite 1 778 13, 710 1, 701 778 13, 710 1, 701 766 19,967
PAGE TOTAL
TOTAL'
778 `
13,710'
1,701
766
19,967
778 =
13,710[
1,701
766 `
19,967
Total includes ventilation load for zonal systems.
Ener Pro 5.1 by Ener Soft User Number: 3665 RunCode: 2012-02-27713:56:06 ID: Pa a 24 of 41
ROOM LOAD SUMMARY
Project Name Date
"Colonial" 2/27/2012
System Name Floor Area
AC #2 867
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult.CFM Sensible Latent CFM ` Sensible Latent CFM Sensible
Zone #2 ..Beds #11#2 1 1 497: 8,786. 1,712 497: 8,7861 1,712 5271 13,758
PAGE TOTAL
TOTAL•
497:
8,786'1
1, 712
527
' 13,758
497:
8,7861
1,7121
527
' 13,7581
' Total includes ventilation load for zonal systems.
Ener Pro 5.1 by Ener Soft User Number. 3665 RunCode: 2012-02-27713:56:06 ID: Page 25 of 41
ROOM LOAD SUMMARY
Project Name
"Colonial"
System Name
A C #3
ROOM LOAD SUMMARY
Zone Name
Zone #3
1 ' Total
for
ROOM COOLING PEAK COIL
loom Name Mult. I CFM I Sensible,[ Latent CFM
Room/Kitchen f 1 1 1,477f 25,667 3,592 1,477
PAGE TOTAL 1,4
TOTAL • 1,4
2/27/2012
Floor Area
2.110
COOLING PEAK COIL HTG. PEAK
Sensible Latent CFM , Sensible
25,6671 3,592 1,5871 40,792
3,5921 1,5871 40,7921
3,5921 1,5871 40,7921
1. EnergyPro 5.1 by EnergySoft User Number: 3665 RunCode: 2012-02-27713:56:06 ID: Page 26 of 411
ROOM LOAD SUMMARY
Project Name Date
"Colonial" 2/27/2012
System Name Floor Area
AC #4 942
ROOM LOAD SUMMARY
ROOM COOLING PEAK I COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible ' Latent I CFM ` Sensible I Latent CFM Sensible
Zone #4 Upstairs Casita I 1 1 665 11,674. 1,6251 665 11,674 1,625 5591 14,563
PAGE TOTAL
TOTAL*
31E
11,6741
1,6251
559,
14,563
11,6741;
1,6251
559
14, 563
Total includes ventilation load for zonal systems.
Ener Pro 5.1 by Ene ySoft User Number: 3665 RunCode: 2012-02-27713:56:06 ID: Page 27 of 41
ROOM LOAD SUMMARY
Project Name Date
"Colonial" 2/27/2012
System Name Floor Area
AC #5 515
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible . Latent CFM Sensible Latent CFM Sensible
Zone #5 Guest Casita1 2871: 5,74 979 287 ' 5,7471 979 4261'10,715
PAGE TOTAL 1 287 s 5,747 9791 426 10,715
TOTAL 1 287,'14 5,747; 979 426 10,715
Total includes ventilation load for zonal systems.
Ener Pro 5.1 by Ener Sok User Number: 3665 RunCode: 2012-02-27T13:56:06 JD: Page 28 of 41
ROOM HEATING PEAK LOADS
Project Name
Date
"Colonial"
2/27/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Master Suite
1 Time of Peak
Jan 1 AM
Floor Area
992.0 ftZ
Outdoor Dry Bulb Temperature
26 OF
Indoor Dry Bulb Temperature
80 OF;.
Conduction
Area U -Value AT
°F
Btu/hr
R-38 Roof- Icynene
992.0 X
0.0290: X
54 =
1,553
R-19 Wall
1,069.0 " X
0.0740: X
54 =
4,272
Loewen Mticlad Low -E(11914)
40.01 X
0.3400 ' X
54- —
734
Loewen Mticlad Low -E(11913)
40.0 X
0.3400 X
54 =
734
Loewen Mticlad Low-E(119/B)
8.0 ' X '
0.3400 X
54 ' =
147
Default Dbl MU Tint(1191A)
72.0 - X
0.71001 X -
54 =
2, 760
Loewen Mticlad Low-E(1201A)
4.5. X :
0.3400 X
54 =
83
Default Dbl Md Tint(12012)
20.0; X
0.7100 X
54 =
767
Loewen Mticlad Low -E(12013)
20.0 X
0.3400 X
54 ! _
367
Loewen Mticlad Low-E(1201B)
4.5 X
0.3400 ' X
54 _
83
Slab -On -Grade
perim = 103.5: X
0.7300 X
54 =
4,080
X
X
—
X
X
-
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
-
X
X
-
X -
X,
_
X
X
-
X
X.
-
X
X
=
X
X
X
X
=
X
X'
_
X
X
=
X
X
=
Items shown with an asterisk (') denote conduction through
an interior surface to another room
Page Total
15,581
Infiltration:[ _ 1.00; X' 1.064
X 992 X 12.00,.
X 0.385 . /60]
X 54
= 4,386
Schedule Air Sensible
Area Ceiling Height
ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
19 967
Energ Pro 5.1 by Energ Soft User Number: 3665
RunCode: 2012-02-27713:56:06 ID:
Page 29 of 41
ROOM HEATING PEAK LOADS
Project Name
Date
"Colonial"
2/27/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Beds #1/#2
Time of Peak
Jan 1 AM
Floor Area
867.0 ft2
Outdoor Dry Bulb
Temperature
26 OF
Indoor Dry Bulb Temperature
80 °F
Conduction
Area
U -Value AT °F
Btu/hr
R-38 Roof- Icynene
867.0.
X
0.0290: X '.
54! =
1,358
R-19 Wall
634.0
' X
0.07401 X
54 c
2, 533
Loewen Mticlad Low -E(12911)
39.0
X _
0.3400: X
54 =
716
Loewen Mticlad Low -E(12511)
40.0
X
0.3400 X
54.' =
734
Loewen Mticlad Low-E(1261A)
4.5
X
0.3400, X
54 =
83
Loewen Mticlad Low-E(1271A)
4.5.
X
0.3400 < X
54 ' =
83
Loewen Mticlad Low-E(1291A)
27.0
X
0.3400 X
54 ` =
496
Slab -On -Grade
perim = 99.5.
X
0.7300 X
54 =
3,922
X
X
—
X
X
—
X
X
=
X
X
=
X
X
—
X
X
=
X
'X
=
X
X
=
X
X
=
X
.. _
X
.
=
X
X
-
X
X
—
X
X'
_
X
X
=
X
X
_
X
X
—
. X _
X
C
X
X
=
X
X
=
X
X
—
X
X
—
X
X
-
X
X
=
Items shown with an asterisk (') denote conduction through an interior surface to another room
Page Total
9,925
Infiltration:[ 1.00 X 1.064 X 867, X 12.00;
X 0.385 ' /60]
X' - 54•
_ 3,834
Schedule Air Sensible
Area
Ceiling Height
ACH'
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
13,7589
EnergyPro 5.1 by Energ Soft User Number: 3665
RunCode: 2012-02-27T13:56:06
ID:
Page 30 of 41
ROOM HEATING PEAK LOADS
Project Name
"Colonial"
ROOM INFORMATION DESIGN CONDITIONS
Room Name Great Room/Kitchen Time of Peak
Floor Area 2;110.0 ft2 Outdoor Dry Bulb Temperature
Indoor Dry Bulb Temperature 80 °F
Conduction Area U -Value AT °F
*R-0 Floor (F.0.2x .16)
R-38 Roof-Icynene
R-19 Wall
Loewen Mticlad Low-E(1331A)
Loewen Mticlad Low-E(117/A)
Loewen Mticlad Low-E(117/B)
Loewen Mticlad Low-E(1031B)
Loewen Mticlad Low -E(1 17/1)
Loewen Mticlad Low-E(117/H)
Loewen Mticlad Low-E(112/A)
SIdWdDr (103/1)
Loewen Mticlad Low-E(114/B)
Loewen Mt/clad Low-E(114/A)
Loewen Mticlad Low-E(112/B)
Default Dbl MU Tint(110/1)
Loewen Mticlad Low -E(13212)
Loewen Mticlad Low -E(13211)
Loewen Mticlad Low-E(1031A)
Loewen Mticlad Low-E(117/C)
Loewen Mticlad Low-E(117/D)
Loewen Mticlad Low-E(117/E)
Loewen Mticlad Low-E(116/A)
Loewen Mticlad Low -E(1 16/8)
Loewen Mticlad Low-E(116/C)
Loewen Mticlad Low -E(1 17/1)
Loewen Mticlad Low -E(11411)
Loewen Mticlad Low-E(117/F)
Loewen Mticlad Low-E(117/G)
Loewen Mticlad Low-E(103/C)
Slab -On -Grade
948.0
1,162.0
2,086.3
4.5
5.5
5.5
6.0
3.0'
3.0
13.5
40.0
6.0
6.0
13.5
24.0:
39.0.
39.0
6.0.
3.8
3.8
3.8
3.8
3.8
3.8
216.0
72.0
3.8z
3.8
6.0:
perim = 216.5.
0.0460
0.0290
0.0740
0.3400
0.3400
0.3400
0.3400
0.3400
0.3400
0.3400
1.4500
0.3400
0.3400:
0.3400
0.7100
0.3400
0.3400
0.3400
0.3400
0.3400
0.3400
0.3400
0.3400
0.3400
0.3400
0.3400;
0.3400
0.3400
0.3400
0.7300
0
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54,
54:
54
54.
54
Items shown with an asterisk (*) denote conduction through an interior surface to another room
Infiltration:[ 1.00 X 1.064 X 2,110 X 12.00 X. 0.385
Schedule Air Sensible Area Ceiling Height ACH
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
2/27/2012
Jan 1 AM
26 OF
Page Total C
/60] X. 54 _
AT
it
0
1,820
8,337
83
101
101
110
55
55
248
3,132
110
110
248
920
716
716
110
70
70
70
70
70
70
3,966
1,322
70
70
110
8,534
31,462
9,330
Energ Pro 5.1 by Energ Soft User Number. 3665 RunCode: 2012-02-27T13:56:06 ID: Page,31 of 41
ROOM HEATING PEAK LOADS
Project Name
Date
"Colonial"
2/27/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Upstairs Casita
Time of Peak
Jan 1 AM
Floor Area
942.0 ft2
Outdoor Dry Bulb Temperature
26 OF
Indoor Dry Bulb Temperature
80 °F
Conduction
Area
U-Value AT °F
Btu/hr
R-38 Roof - Icynene
942.0
X
0.0290 X
54 '' =
1,475
R-19 Wall
882.4
X ` '
0.0740: X
54 ; _ .
3,526
Loewen Mticlad Low-E(2031B) -
14.0:
X
0.3400 X ?
54 _
257
Loewen Mticlad Low-E(2031C) '
14.0
X
0.3400 X ` ;
54
Loewen Mticlad Low-E(2031D)
14.0
X -
0.3400 X
54 _ .
257
Loewen Mticlad Low-E(2031E)
14.0
X
0.3400 X
54 _
257
Loewen Mticlad Low-E(2011B)
11.3
X
0.3400 X
54 ' 0
207
Loewen Mticlad Low-E(2011A)
11.3
X : _
0.3400 X
54. c
207
Loewen Mticlad Low-E(2031A) _
10.0
X ;
0.3400. = X
54
184
Loewen Mticlad Low-E(1031D)
5.0
X
0.3400 X ;
54 _
92
Loewen Mticlad Low-E(2011C)
20.0
X:
0.3400 ' X '
54 ' c
367
Loewen Mt/clad Low-E(26112)
48.0
X -
0.3400 ; X
54' =
881
Loewen Mticlad Low-E(2011D)
20.0
X _
0.3400 X
54 =
367
SIdWdDr (204/1)
24.0
X
1.4500 X
541=
1,879
Loewen Mticlad Low-E(2031F)
10.0.,
X
0.3400- X
54 _
184
X
X
_
X:
X
_ -
X
X
-
X
X
-
X.
X
_
X
X
-
X .'
X
_
X
X
X
X
=
X
X
X .'
X
X
X
-
X
X 1
-
X:
X
-
X
X':
-
X
X:
Items shown with an asterisk (') denote conduction through an interior surface to another room
Page Total .
10,398
Infiltration:[ - 1.00 X. 1.064:
X. 942 X 12.00.
X' 0.385 /60].
X 54
= 4,165
Schedule Air Sensible
- Area.
Ceiling Height
ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR, ROOM
14 563.
Energ Pro 5.1 by Energ Soft User Number: 3665
RunCode: 2012-02-27T13:56:06
ID:
Page.32 of 41
ROOM HEATING PEAK LOADS
Project Name
FD -ate
"Colonial"
2/27/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest Casita
Time of Peak
Jan 1 AM
Floor Area
515.0 ft'
Outdoor Dry Bulb Temperature
26 OF
Indoor Dry Bulb Temperature
80 OF
Conduction
Area
U -Value AT
OF
Btu/hr
R-38 Roof - Icynene
515.0
X
0.0290 X
54- =
806
R-19 Wall
756.0
X
0.0740 ' X
54_ i =
3,021
Loewen Mticlad Low-E(1341A)
15.0
X
0.3400X
54 =
275
Loewen Mticlad Low-E(1341B)
15.0
X ,
0.3400 : X
54 =
275
Loewen Mticlad Low-E(1371A)
8.0
X
0.3400 , X
54: ` =
147
Loewen Mticlad Low -E(13411)
39.0
X
0.3400. ; X
54 =
716
Loewen Mticlad Low-E(1351A)
4.5
X
0.3400 ; X
54 =
83
Slab -On -Grade
perim = 79.0
X
0.7300: X
54 =
3,114
X
X
X
X
-
X
X
-
X
X
=
X
X
-
X
X'
-
X
X
=
X
X
-
X
X
-
X
X
=
X
X
-
X
X
_
X
X
=
X
X
-
X
X
-
X
X
=
X
X
-
X
X
-
X .,
X
=
X 1
X
-
X
X
X
X
-
X:
X
Items shown with an asterisk (') denote conduction through
an interior surface to another room
Page Total !
8,438
Infiltration:[ 1.00 X 1.064
X: 515 X: 12.00
X 0.385 /60]
X
Schedule Air Sensible
Area
Ceiling Height
ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
10 715
Energ Pro 5.1 by Energ Soft User Number: 3665
RunCode: 2012-02-27T13:56:06
IO:
Page 33 of 41
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
"Colonial"
72/27120-12
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master Suite
Outdoor Dry Bulb Temperature
112 OF
Floor Area 992.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 72 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof - Icynene (VV) . 992.0: X 0.0290.
X
56.0 =
1,611
R-19 Wall (N) 72.0 X 0.0740
X
23.0 =
123
R-19 Wall(E) 230.0 X 0.0740
X
33.0 =
562
R-19 Wall (S) 246.0 X 0.0740
X
26.0 =
473
R-19 Wall 521.0 X 0.07401:
X
33.0 =
1,272
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
4,041
Items shown with an asterisk (') denote conduction through an interior surface to another room.
t. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
SwngGlsDr (119/4) (E) 31.5 X . 17.2 +
8.5
X 33.8
= 829
SwngGlsDr (119/3) (E) 31.5 X 17.2 +
8.5
X 33.8
= 829
Operable Wdw (119/8) (E) 8.0. X 17.2 +
0.0
X 33.8
= 138
Operable Wdw (119/A) (S) 72.0 X 36.5 +
0.0
X 36.6
= 2,625
FxdWdw (120/A) (W) 2.2 X 17.2 +
2.3
X 33.8
= 115
SwngGlsDr (120/2) (lM 3.7 . X 36.5 +
16.3
X 72.1
= 1,308
SwngGlsDr (120/3) 3.7 X 17.2 +
16.3
X 33.8
= 614
X 17.2 +
Operable Wdw (120/8) (W) 2JX1
2.3
X 33.8
= 115
+.
X
-
Page Total
6,572
Internal Gain
Btu/hr
Occupants 1.0 Occupants X 230
Btuh/occ.
=
230
Equipment o.o Dwelling Unit X 1,600
Btu
=
0
Infiltration: 1.064. X 1.24 X 54.28 X 40 =
2,867
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
13,710
Latent Gain
Btu/hr
Occupants 1.0 Occupants X 200
Btuh/occ.
=
200
Infiltration: 4,771 X 1.24 X 54.28 X 0.00467 =
1,501
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,701
Ener Pro 5.1 bv Ener Soft User Number: 3665 RunCode: 2012-02-27T13:56:06 ID:
Pa a 34 of 41
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
"Colonial"
2127/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Beds #1/#2
Outdoor Dry Bulb Temperature
112 °F
Floor Area 867.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 72 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof - Icynene(lM 867.0 - X 0.0290:
X 56.0 ' =
1,408
R-19 Wall (N) 24.0', X 0.0740
X 23.0 =
41
R-19 Wall (E) 153.0 X 0.0740
X 33.0: =
374
R-19 Wall (S) 17.0 X 0.0740
X 26.0! =
33
R-19 Wall W 440.0' X 0.0740
X 33.07 =
1,074
X
X
X
X
' X
X =
X
X =
Page Total
2,930
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area GLF
Btu/hr
SwngGlsDr (129/1) (E) 39.0 X` 17.2 +
0.0 X, 33.8 .
= 670
SwngGlsDr (125/1) (119 7.5 X 17.2: +
32.5 X: 33.8 :
c 1,228
FxdWdw (126/A) (149 2.2. 'X . 17.2 +1
2.3 X 33.8;
= i 115
FxdWdw (127/A) (VV) 2.2 X , 17.2 +
2.3: X 33.8
= 115
Operable Wdw (129/A) 9.0 X 17.2 +
18.0, X' : 33.8
= 763
X '.+.
X,
X'' +
X
X' +
X
X, +
X
Page Total
2,891
Internal Gain
Btu/hr
Occupants 2.0 Occupants X 230
Btuh/occ. =
460
Equipment o.0 Dwelling Unit X 1,600
Btu =
0
Infiltration: 1.064, X 1.24 X 47.44; X 40 .: =
2,505
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
8,786
Latent Gain
Btu/hr
Occupants 2.0 Occupants X 200J
Btuh/occ. =
400
Infiltration_ : 4,771 X 1.24. X 47.44 X ; . 0.00467 =
1,312
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,712
Ener Pro 5.1 by Ener Soft User Number: 3665 RunCode: 2012-02-27713:56:06 ID:
Pa a 35 of 41
RESIDENTIAL ROOM COOLING LOAD SUMMARY
"Colonial" 2/27/2012
ROOM INFORMATION DESIGN CONDITIONS
Room Name Great Room/Kitchen Outdoor Dry Bulb Temperature 112 OF
Floor Area 2,110.0 ft2. Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 72 OF Outdoor Dailv Ranae: 34 OF
I Ooaaue Surfaces
'R-0 Floor (F.0.2x .16)
R-38 Roof - Icynene
R-19 Wall
SIdWdDr (103/1)
R-19 Wall
R-19 Wall
R-19 Wall
R-19 Wall
R-19 Wall
Orientation
(N)I
1: (SM I
Area
X
X
X
X
X
X
X
X
X
948.0
1,162.0
747.0
40.0
646.5
7.6'
493.2
184.4
7.6
U -
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
for
X
• X
` X
; X
X
' X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
0.0460
0.0
0.0290
56.0
0.0740
23.0'
1.4500
23.0
0.0740
33.0
0.0740
31.0
0.0740:
26.0
0.0740
33.0
.0740
0.07401:
31.0
Page Total
Shaded Unshaded
Fenestration Orientation Area GLF Area GLF
OperableWdw (133/A)
FxdWdw (117/A)
FxdWdw (117/8)
FxdWdw (103/8)
FxdWdw (117/1)
FxdWdw (117/H)
OperableWdw (112/A)
FxdWdw (114/8)
FxdWdw (114/A)
I Internal Gain
(N)
(N)
(N)
(N)
(N)
(N)
(N)
(E)
(E)
0.0
X
X
X
X
X
X
X
17.2
+
"+
+
+
+
+
+
+
4.5
X,
X
X
X.
X
X
X
X
17.2
=
=
=
=
=
=
0.0
17.2
5.5'X
17.2
0.0
17.2
5.5
17.2
0.0
17.2
6.0
17.2
0.0'X
17.2
3.0
17.2
0.0
17.2
3.0
17.2'-
0.0
17.2
13.5
17.2'=
2.2.X
17.2,`+
3.8
33.8
2.2.
17.2
3.8
Page Total
2.0 Occupants X 230 Btuh/occ.
1.0 Dwelling Unit X 1,600 Btu
I Infiltration: 1.064 X 1.241 ' X 115.46, X 40 =
Air Sensible CFM ELA AT
RLY SENSIBLE HEAT G
Latent Gain
Occupants 2.0 Occupants X 200; Btuh/occ.
Infiltration: 4,771 X - 1.24, X 115.46 X 0.00467
Air Sensible CFM ELA AW
HEAT GAIN FOR
Btu/hr
0
1,887
1,271
1,334
1,579
17
949
450
17
7,505
77
95
95
103
52
52
232
165
165
1,036
Btu/hr
460
1.600
Btu/hr
1 3,1921
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
"Colonial" ' 2/27/2012
ROOM INFORMATION DESIGN CONDITIONS
Room Name Great Room/Kitchen Outdoor Dry Bulb Temperature 112 OF
Floor Area 2,110.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 72 OF I Outdoor Daily Range: 34 OF
Surfaces
Orientation
Area U -Factor CLTD'
X X =
X X =
X X =
X X =
X X =
X X =
X X =
X X _
X X =
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
FP_neStra*inn
OperableWdw (112/8)
SwngGlsDr (110/1)
SwngGlsDr (13212)
SwngGlsDr (132/1)
FxdWdw (103/A)
FxdWdw (117/C)
FxdWdw (117/D)
FxdWdw (117/E)
FxdWdw (116/A)
Orientatinn
(E)
(E)
(E)
(E)
(SE)
(S)
(S) .
(S)
(S)
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+1
Area
X
X
X
X
X
X
X
X
GLF
_
=
=
=
=
=
6.8
17.2
6.7
33.8.:
9.3
36.5
14.7
72.1
39.0
17.2
0.0
33.8
39.0
17.2
0.0
33.8'=
0.0
. 17.2
6.0
23.6
0.0
17.2_+
3.8
17.3
0.0
17.2
3.8'X
17.3
0.0
17.2
3.8
17.3
0.01
1 17.2
3.8
Page Total
Btu/hr
0
Btu/hr
344
1,399
670
670
142
66
66
66
66
3,488
Internal Gain Btu/hr
Occupants 2.0 Occupants X 230 Btuh/occ.
Equipment 1.0 Dwelling Unit X 1,600 Btu
Infiltration: 1.064 X 1.24 X 115.46 X 40 = L
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 9. nw7
Latent Gain Btu/hr
Occupants 2.0 Occupants X 200Btuh/occ. = 400
Infiltration: 4,771 X 1.24 X 115.46 X 0.00467 = 31192
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM q Sggl
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
"Colonial"
2/27/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great Room/Kitchen
Outdoor Dry Bulb Temperature
112 OF
Floor Area 2,110.0 ft2
.Outdoor Wet Bulb Temperature
78 OF
Indoor D Bulb Temperature 72 °F
Outdoor Dail Range:
34 OF
Opaque Surfaces Orientation Area U -Factor CLTD'
_
Btu/hr
X X
-
X X
_
X X
=
X X
-
X X
_
X X
_
X X
_
X X
_
X X
_.
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestration Orientation Area GLF Area GLF
Btu/hr
FxdWdw (116/B)(S) O.O.. Xi 17.2 . + 3.8.: X'
17.3•
_ 66
FxdWdw (116/C) (S) 0 0_ X 17 2 + 3.8 X
17.3
= 66
SGD (1.17/1) w (S) 216.0. X ; 17.2 + 0.0 X •
17.3 '
_ . ; _ 3,713
SGD(11411) (S) 72.0'X 17.2'+ 0.0'X
17.3'=.
1,238
,
FxdWdw (117/F) 0.0 X, 17.2; + . 3.8; X
33.8
= 128
FxdWdw (117/G) (l� 0.0 X' , 17.2 ` + 3.8 X
33.8
0 128
FxdWdw (103/C) (SW) 0.0 X 17.2, ' + 6.01 ' X
23.6
c 142
X. + X
—
Xi- .._ +: X •..
c ..
Page Total
5,481
Internal Gain
:Btu/hr
Occupants 2.0 Occupants X 230' ` Btuh/occ.
=
460
Equipment 1.0 Dwelling Unit X 1,600 Btu
=
1,600
Infiltration: 1.064 X 1.24, X _ 115.46 X. 40 =
6,097
Air Sensible CFM` ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM:
25,667
Latent Gain
Btu/hr
Occupants 2.0 Occupants' X _ 200], Btuh/occ.
c
400
Infiltration: 4,771 X 1.24 X 115.46 X 0.00467: =
3,192
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
3 592
Ener Pro 5.1 bv Ener Soft User Number: 3665 RunCode: 2012-02-27713:56:06 ID:
Page 38 of 41
J
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
"Colonial" 2/27/2012
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
Indoor Dry Bulb
Opaque Surfaces
R-38 Roof - Icynene
R-19 Wall
R-19 Wall
R-19 Wall
R-19 Wall
SIdWdDr (204/1)
Upstairs Casita Outdoor Dry Bulb Temperature
942.0 ft2 Outdoor Wet Bulb Temperature
72 °F Outdoor Daily Ranqe:
Orientation
(E) I
Area
° X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
c
=
=
=
=
=
=
=
=
942.0
0.0290
56.0
166.0
0.0740
23.0
352.4'
0.0740
33.0
152.0
0.0740
26.0
212.0
0.0740
33.0
24.0
1.4500
33.0
0.0.X
17.2
11.3
33.8
0.0'X
17.2'+
11.3
33.8
0.0
17.2
10.0'X
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
FxdWdw (203/8)
FxdWdw (203/C)
FxdWdw (203/D)
Operable Wdw (203/E)
Operable Wdw (201/8)
Operable Wdw (201/A)
OperablelMdw (203/A)
FxdWdw (103/D)
FxdWdw (201/C)
Oriantatinn
(N)
(N)
(N)
(N)
(E)
(E)
(E)
(E)
(S)
Shaded Unshaded
Area
X
X:-
X
X
X
X°
GLF
+
+
+.
+
+
+
+
Area
X
X
X
X
X
X
X
GLF
=
=
=
-
c
=
c
=
=
0-0[X
17.2'+
14.0
17.2
0.0
. 17.2
14.0
17.2
0.0
17.2
14.0
17.2
0.0.
17.2
14.0'X,
17.2
0.0.X
17.2
11.3
33.8
0.0'X
17.2'+
11.3
33.8
0.0
17.2
10.0'X
33.8
0.0,
17.2
5.0,
33.8
0.0
17.2
20.01
1 17.3
Page Total
112 OF
78 OF
34 OF
Btu/hr
1,530
283
861
292
518
1,148
4, 631
Btu/hr
241
241
241
241
382
382
338
169
345
2,579
Internal Gain Btu/hr
Occupants 1.0 Occupants X 230 Btuh/occ. = 230
Equipment 0.0 Dwelling Unit X 1,600 Btu = 0
Infiltration: 1.064 X 1.24 X 51.55 X 40 = 2,722
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 11,674
Latent Gain Btu/hr
Occupants 1.0 Occupants X 200. Btuh/occ. = 200
Infiltration: 4,771 X 1.24 X 51.55. X 0.00467 ' = 1,425
Air Sensible CFM ELA AW
TOTAL HOUR
RESIDENTIAL ROOM COOLING LOAD SUMMARY.
Project Name Date
pit- I /„
v- -
.,17.2
2/27/2072
ROOM INFORMATION :
X i
X
X;
X
X:
X
X.
DESIGN CONDITIONS
_
c
. '
-
_
—
-
Room Name
Upstairs Casita
Outdoor Dry Bulb Temperature
112 OF
Floor Area
942.0 ftZ
Outdoor Wet Bulb Temperature,
78 °F
Indoor Dr Bulb Temperature
72 °F
Outdoor Dail Range:
34 OF
Opaque Surfaces
Orientation Area
U -Factor CLTD'
Page Total 0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded. Unshaded
Fenestration Orientation Area " = GLF Area GLF Btu/hr
SwngGlsDr (20112)
FxdWdw (201/D)
OperableWdw (203/Ff
0.0
X
X
V
X'
X
XT
X.
X'
X'
.,17.2
+'
+
+,
+
+_
+
+:
48.0
X i
X
X;
X
X:
X
X.
.17.3
_
c
. '
-
_
—
-
828
0.0
' 17.2
20.0'X:
17.3
345
0.01
17.2!
10.0
33.8
:' 338
Page Total 1,512
Internal. Gain Btu/hr
Occupants 1.0 Occupants X 230 Btuh/occ. - 230
Equipment 0.0 Dwelling Unit X 1,600 Btu 0
Ell
Infiltration: 1.064, X 1.24 X. 7- 51.55 X 40 c 2,722
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN_ FOR ROOM 11,674
Latent Gain'
Occupants' ,, 1.0Occupants:
- B � .
to/h
. Occupants ` X 200 ; Btuh/occ. = 200
Infiltration: 4,771. X 1.24 X 51.55. X 0.00467_. = 1,425
Air Sensible CFM ELA • AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 1 625
Ener Pro 5.1 by EnerqySoft User Number: 3665 RunCode: 2012-02-27T13:56:06 ID: Pa e.40 of 41
I-ESIDENTIAL ROOM COOLING LOAD SUMMARY
P�oj'ect Name
Date
"Colonial"
2/27/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Casita
Outdoor Dry Bulb Temperature
112 OF
Floor Area 515.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 72 °F
Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof - Icynene (N) 515.0: X 0.0290
X
56.0 =
836
R-19 Wall (N) 265.0 X 0.0740
X
23.0 =
451
R-19 Wall (E) 193.0. X 0.0740
X
33.0 ' =
471
R-19 Wall(S) 55.0 ; X 0.0740
X
26.0 =
106
R-19 Wall (W) 243.0 X 0.0740-
X
33.0 c
593
X
X
=
X
X
-
X
X
_
X
X
=
Page Total
2,458
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
OperableWdw (134/A) (N) 0.0 X 17.2; ' + '
15.0 ? :X:
. 17.2
= 258
OperableWdw (134/8) (N) 0.0 X 17.2 +
15.0
X 17.2
= 258
OperableWdw (137/A) (E) 0.0 X 17.2; +
8.0 '
X 33.8
= 271
SwngGlsDr (134/1) (E) 39.0 X 17.2 +
0.0
X 33.8
= 670
FxdWdw (135/A) (W) 2.2 X 17.2; +
2.31
X 33.8
= 115
X +
X
-
X +
X
-
X +
1 El
X_
-
X' +
X
o
Page Total
1,571
Internal Gain
Btu/hr
Occupants 1.0 Occupants X 230.
Btuh/occ.
=
230
Equipment 0.0 Dwelling Unit X 1,600.
Btu
=
0
Infiltration: 1.064; X ` 1.24. -X 28.18 X 40 , =
1,488
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
5,747
Latent Gain
Btu/hr
Occupants 1 o Occupants X 200;
Btuh/occ.
=
200
Infiltration: 4,771; X 1.24: X 28.18 X ' 0,00467 1, =
779
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
979
Ener Pro 5.1 by Ener Soft User Number. 3665 RunCode: 2012-02-27713:56:06 ID:
Page 41 of 41