BRES2015-0391 Title 24 Revision 1BUILDING ENERGY ANALYSIS REPORT
cjp(e /(Opv
PROJECT:
Madison Club 23B
81-382 Amundson Ave.
La Quinta, CA 92253:'
Project Designer:
Kristi Hanson Architects, Inc.
72-185 Painters Path STE A
Palm Desert, CA 92260
(760) 776-4068
Report Prepared by:
Jon Scott
Scott Design and Title 24, Inc,
77-085 Michigan Drive
Palm Desert, CA 9 2��
(760) 200-478 BUILD of CUNTA
TNG & SAFETY A
�EpT
FO � CONs
"2-
E83
NSUCTION
�A7-E
Job Number:
RE6.EIVED
Date: APR 11 2016,
4/7/2016 CITY OF LA QUINTA
COMMUNITY DEVELOPMENT
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
I iEnergyPro 6.7 by EnergySoft User Number: 6712 ID: of400
v
TABLE OF CONTENTS
Cover Page
Table of Contents
Form CF -1 R -PRF -01-E Certificate of Compliance
Form RMS -1 Residential Measures Summary
Form MF -1 R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
EnergyPro 6.7 by EnergySoft Job Number: ID: User Number: 6712
1
2
3
19
21
25
30
35
40
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CFi R -MF -01
Page 1 of 16
GENERAL INFORMATION
01
Building Complies with Computer Performance
01
Project Name Madison Club 23B
03
This building Incorporates one or,more Speclal Features shown below .•� * /� _ .-.
02
Calculation Description Title 24 Analysis
08
Energy Use (kTDV/ft2-yr)
03
Project Location 81-382 Amundson Ave.
Compliance Margin
Percent Improvement
04
City La Quinta
05
Standards Version Compliance 2015
06
Zip Code 92253
07
Compliance Manager Version BEMCmpMgr 2013-4 (744)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.6
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 135
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (ft2) 8044
15
Number of Zones 5
16
Slab Area (ft2) 6474
17
Number of Stories 2
18
Addition Cond. Floor Area N/A
19
Natural Gas Available Yes
20
Addition Slab Area (ff) N/A
21
Glazing Percentage (%) 40.7%
COMPLIANCE RESULTS _
01
Building Complies with Computer Performance
02
This building Incorporates features that require field testing and/or verification by a certified HERS iater'under' the supervision of a CEC-approved HERS provider.
03
This building Incorporates one or,more Speclal Features shown below .•� * /� _ .-.
06
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF113-03092016-744 Report Generated at: 2016-04-07 11:45:48
ENERGY USE SUMMARY
04
05
06
07
08
Energy Use (kTDV/ft2-yr)
Standard Design
Proposed Design
Compliance Margin
Percent Improvement
Space Heating
3.98
5.44
-1.46
-36.7%
Space Cooling
110.01
105.93
4.08
3.7%
IAQ Ventilation
1.11
1.11
0.00
0.0%
Water Heating
3.19
4.25
-1.06
-33.2%
Photovoltaic Offset
----
0.00
0.00
----
Compliance Energy Total
118.29
116.73
1.56
1.3%
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF113-03092016-744 Report Generated at: 2016-04-07 11:45:48
{
CERTIFICATE OF COMPLIANCE- RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-IAF-01
Project Name: Madison Club 2313 Calculation Date/Time: 11:43, Thu, Apr 07, 2016 - Page 2 of 16•
Calculation Description: -Title 24 Analysis Input File Name: Madison Club 2313-Kristi Hanson-15.xml - • - *r - - -
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for, this computer analysis.
Window overhangs and/or fins
HERS FEATURE SUMMARY ;
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below. -
Building -level Verifications: '
High Quality Insulation Installation (QII)-
IAO mechanical ventilation
Cooling System Verifications: ,
Minimum Airflow -
Verified EER w
Verified SEER • }
Refrigerant Charge -
Fan Efficacy Watts/CFM }
HVAC Distribution System Verifications: j
Duct Sealing _!J
Domestic Hot Water System Veriflcatlons:
None-- �� �'�i" '• r� N. F
ENERGY DESIGN RATING ! / f U . 40�� II A( h ` j1 � K 11 `� 3
This is the sum of the annual TDV energy consumption for energy use`cornponentsincluded in the p&iformance compliance approach for the Standard Design Building (Energy Budget) and the annual .
TDV energy consumption for lighting and components not regulated by Title 24, Part.6 (such as domestic appliances and consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system. r y T i.. �� •� 91 1 1 i.J .tz - Eti
- Reference Energy Use
Energy Design Rating
Margin Percent Improvement
Total Energy (kTDVtf2-yr)' 152.56
151.00
1.56 1.0%
includes calculated Appliances and Miscellaneous Energy Use (AMEU)
BUILDING -FEATURES INFORMATION - - •
= 01
02
03
04
05
06
07
Project Name •
Conditioned Floor Area (ft2)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones'
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Madison Club 23B
8044
1
15
5
5
1
Registration Number: 215-1\16343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25
CA Building Energy Efficiency Standards 2013 Residential Compliance Report Version - CF1R-03092016-744
R r
HERS Provider: CaICERTS inc.
Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE- RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis Input File Name: Madison Club 236-Kristi Hanson-15.xml
CF1 R-fiF-01
Page 3 of 16
ZONE INFORMATION
01
02
03
04
05
06
07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1
Water Heating System 2
off nook dining
Conditioned
HVAC 1 off kit nookl
1621
9
DHW Sys 1
great entry
Conditioned
HVAC 2 grt enry2
1659
9
DHW Sys 1
masterguest
Conditioned
HVAC 3 mstr gest3
1781
9
DHW Sys 1
guest living
Conditioned
HVAC 4 gest liv4
1413
9
DHW Sys 1
2nd master
Conditioned
HVAC 5 2nd5
1570
9
DHW Sys 1
�j i 1l 0 V f
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF113-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 23B-Kristi Hanson-15.xml
CF1 R -PAF -01
Page 4 of 16
OPAQUE SURFACES
01
02
03
04
05
06
07
08
Name
Zone
Construction
Azimuth
Orientation
Gross Area (ft2)
Window & Door Area (ft)
Tilt (deg)
NE Wall
off nook dining
R-21 Wall (W.21.2x6.16)
45
Right
832
339
90
SE Wall
off nook dining
R-21 Wall (W.21.2x6.16)
135
Front
464
129.1
90
SW Wall
off nook dining
R-21 Wall (W.21.2x6.16)
225
Left
1616
467.313
90
NW Wall
off nook dining
R-21 Wall (W.21.2x6.16)
315
Back
400
238.8
90
Roof
off nook dining
R-38 Roof Attic
522
NE Wall 2
great entry
R-21 Wall (W.21.2x6.16)
45
Right
684
120
90
SE Wall 2
great entry
R-21 Wall (W.21.2x6.16)
135
Front
416
260.536
90
SW Wall 2
great entry
R-21 Wall (W.21.2x6.16)
225
Left
684
90
NW Wall 2
great entry
R-21 Wall (W.21.2x6.16)
315
Back
455
378.5
90
Roof 2
great entry
R-38 Roof Attic
1659
NE Wall 3
masterguest
R-21 Wall (W.21.2x6.16)
45
Right
657
142.4
90
SE Wall 3
masterguest
R-21 Wall (W.21.2x6.16)
135
Front
576
104.2
90
SW Wall
masterguest
R-21 Wall (W.21.2x6.16)1
/225
Left
200
21.5
90
NW Wall 3
masterguest
R-21 Wall (W.21.2x6.16) Y
315
Back 1
480
146.4
90
Roof 3
masterguest
R-38 Roof Attic
-
1781
NE Wall 4
guest living
R-21 Wall (W.21.2x6.16)
45
-�,+ Right
907
203
90
SE Wall 4
guest living
R-21 Wall (W.21.2x6.16)
135
Front
619
70.6
90
SW Wall 4
guest living
R-21 Wall (W.21.2x6.16)
225
Left
907
199.6
90
NW Wall 4
guest living
R-21 Wall (W.21.2x6.16)
315
Back
619
129.6
90
Roof 4
guest living
R-38 Roof Attic
1413
NE Wall 5
2nd master
R-21 Wall (W.21.2x6.16)
45
Right
780
126
90
SE Wall 5
2nd master
R-21 Wail (W.21.2x6.16)
135
Front
350
27
90
SW Wall 5
2nd master
R-21 Wall (W.21.2x6.16)
225
Left
780
174.9
90
NW Wall 5
2nd master
R-21 Wall (W.21.2x6.16)
315
Back
350
17.8
90
Roof 5
2nd master
R-38 Roof Attic
1570
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis Input File Name: Madison Club 236-Kristi Hanson-15.xml
CF1 R -PRF -01
Page 5 of 16
ATTIC
01
02
03
04
05
06
07
08
Name
Construction
Type
Roof Rise
Roof Reflectance
Roof Emittance
Radiant Barrier
Cool Roof
Attic off nook dining
Attic Roofoff nook dining
Ventilated
3
0.1
0.85
No
No
Attic great entry
Attic Roofgreat entry
Ventilated
3
0.1
0.85
No
No
Attic masterguest
Attic Roofmasterguest
Ventilated
3
0.1
0.85
No
No
Attic guest living
Attic Roofguest living
Ventilated
3
0.1
0.85
No
No
Attic 2nd master
Attic Roof2nd master
Ventilated
3
0.1
0.85
No
No
QRS PR, 0 i
E R
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 23B-Kristi Hanson-15.xml
CF1 R-PhF-01 1
Page 6 of 16
WINDOWS
01
02
03
04
05
06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Width (ft)
Height (ft)
Multipll
er
Area
(ft)
1.11 -factor
SHGC
Exterior Shading
K3
Window
NE Wall (Right -45)
11.0
10.0
1
110.0
0.28
0.18
Insect Screen (default)
17
Window
NE Wall (Right -45)
11.6
10.0
1
116.0
0.32
0.24
Insect Screen (default)
K2
Window
NE Wali (Right -45)
11.3
10.0
1
113.0
0.28
0.18
Insect Screen (default)
12
Window
SE Wall (Front -135)
10.9
10.0
1
109.0
0.28
0.18
Insect Screen (default)
K3 2
Window
SW Wall (Left -225)
11.0
10.0
1
110.0
0.28
0.18
Insect Screen (default)
11
Window
SW Wall (Left -225)
12.1
10.0
1
121.0
0.32
0.24
Insect Screen (default)
J2
Window
SW Wall (Left -225)
2.0
8.0
1
16.0
0.28
0.18
Insect Screen (default)
J1
Window
SW Wall (Left -225)
2.0
8.0
1
16.0
0.28
0.18
Insect Screen (default)
H1
Window
SW Wall (Left -225)
5.3
4.0
1
21.2
0.28
0.18
Insect Screen (default)
10
Window
SW Wall (Left -225)
11.0
10.0
1
110.0
0.32
0.24
Insect Screen (default)
G2
Window
SW Wall (Left -225)
6.3
6.9
1.001
43.5
0.28
0.18
Insect Screen (default)
G3
Window
SW Wall (Left -225)
2.8
2.0
1
5.6
0.28
0.18
Insect Screen (default)
08
Window
SW Wall (Left -225)
3.0
8.0
1
24.0
0.32
0.24
Insect Screen (default)
07
Window
NW Wall (Back -315)
19.9
10.0
1
199.0
0.32
0.24
Insect Screen (default)
G1
Window
NW Wall (Back -315)
19.9
2.0
1
39.8
0.28
0.18
Insect Screen (default)
F3
Window
NE Wall 2 (Right -45)
----
----
1
60.0
0.28
0.18
Insect Screen (default)
F2
Window
NE Wall 2 (Right -45)
----
----
1
60.0
0.28
0.18
Insect Screen (default)
61
Window
SE Wall 2 (Front -135)
1.5
5.5
1.006
8.3
0.28
0.18
Insect Screen (default)
A4
Window
SE Wall 2 (Front -135)
2.9
12.2
1.001
35.4
0.28
0.18
Insect Screen (default)
A5
Window
SE Wall 2 (Front -135)
2.8
3.3
0.996
9.2
0.28
0.18
Insect Screen (default)
01
Window
SE Wall 2 (Front -135)
8.5
10.0
1
85.0
0.32
0.24
Insect Screen (default)
A3
Window
SE Wall 2 (Front -135)
5.3
3.3
1.001
17.5
0.28
0.18
Insect Screen (default)
Al
Window
SE Wall 2 (Front -135)
2.9
12.2
1.001
35.4
0.28
0.18
Insect Screen (default)
A2
Window
SE Wall 2 (Front -135)
2.8
3.3
1.006
9.3
0.28
0.18
Insect Screen (default)
M1
Window
SE Wall 2 (Front -135)
----
----
1
60.4
0.28
0.18
Insect Screen (default)
F5
Window
NW Wall 2 (Back -315)
5.8
9.5
1
55.1
0.28
0.18
Insect Screen (default)
F6
Window
NW Wall 2 (Back -315)
5.8
3.0
1
17.4
0.28
0.18
Insect Screen (default)
06
Window
NW Wall 2 (Back -315)
17.0
12.0
=
204.0
0.32
0.24
Insect Screen (default)
F4
Window
NW Wall 2 (Back -315)
17.0
3.0 1
1 1
51.0
0.28
0.18
Insect Screen (default)
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 23B-Kristi Hanson-15.xmi
CF1 R -PAF -01 '
Page 7 of 16
F1
Window
NW Wall 2 (Back -315)
5.1
10.0
1
51.0
0.28
0.18
Insect Screen (default)
E1
Window
NE Wall 3 (Right -45)
----
----
1
96.0
0.28
0.18
Insect Screen (default)
E2
Window
NE Wall 3 (Right -45)
----
----
1
19.2
0.28
0.18
Insect Screen (default)
D3
Window
NE Wall 3 (Right -45)
----
----
1
5.6
0.28
0.18
Insect Screen (default)
D2
Window
NE Wall 3 (Right -45)
----
----
1
21.6
0.28
0.18
Insect Screen (default)
D1
Window
SE Wall 3 (Front -135)
----
----
1
19.2
0.28
0.18
Insect Screen (default)
02
Window
SE Wall 3 (Front -135)
----
----
1
85.0
0.32
0.24
Insect Screen (default)
C1
Window
SW Wall 3 (Left -225)
----
----
1
21.5
0.28
0.18
Insect Screen (default)
05
Window
NW Wall 3 (Back -315)
----
----
1
78.0
0.32
0.24
Insect Screen (default)
E5
Window
NW Wall 3 (Back -315)
----
----
1
15.6
0.28
0.18
Insect Screen (default)
E3
Window
NW Wall 3 (Back -315)
----
----
1
44.0
0.28
0.18
Insect Screen (default)
E4
Window
NW Wall 3 (Back -315)
----
----
1
8.8
0.28
0.18
Insect Screen (default)
21
Window
NE Wall 4 (Right -45)
10.0
9.0
1
90.0
0.32
0.24
Insect Screen (default)
R2
Window
NE Wall 4 (Right -45)
2.0
8.0
1
16.0
0.28
0.18
Insect Screen (default)
R1
Window
NE Wall 4 (Right -45)
2.0
8.0
1
16.0
0.28
0.18
Insect Screen (default)
19
Window
NE Wall 4 (Right -45)
9.0
9.0
1
81.0
0.32
0.24
Insect Screen (default)
01
Window
SE Wall 4 (Front -135)
- 6.3
2.0
1
12.6
0.28
0.18
Insect Screen (default)
P3
Window
SE Wall 4 (Front -135)
2.0
9.0
1
18.0
0.28
0.18
Insect Screen (default)
N4
Window
SE Wall 4 (Front -135)
4.0
10.0
1
40.0
0.28
0.18
Insect Screen (default)
P2
Window
SW Wall 4 (Left -225)
2.0
9.0
1
18.0
0.28
0.18
Insect Screen (default)
P1
Window
SW Wall 4 (Left -225)
2.0
9.0
1
18.0
0.28
0.18
Insect Screen (default)
N3
Window
SW Wall 4 (Left -225)
6.2
10.0
1
62.0
0.28
0.18
insect Screen (default)
N2
Window
SW Wall 4 (Left -225)
6.2
10.0
1
62.0
0.28
0.18
Insect Screen (default)
S2
Window
SW Wall 4 (Left -225)
4.4
9.0
1
39.6
0.28
0.18
Insect Screen (default)
N1
Window
NW Wall 4 (Back -315)
4.0
10.0
1
40.0
0.28
0.18
Insect Screen (default)
18
Window
NW Wall 4 (Back -315)
7.7
10.0
1
77.0
0.32
0.24
Insect Screen (default)
S1
Window
NW Wall 4 (Back -315)
6.3
2.0
1
12.6
0.28
0.18
insect Screen (default)
122
Window
NE Wall 5 (Right -45)
4.0
9.0
1
36.0
0.28
0.18
Insect Screen (default)
22
Window
NE Wall 5 (Right -45)
10.0
9.0
1
90.0
0.32
0.24
Insect Screen (default)
M1 2
Window
SE Wall 5 (Front -135)
7.2
2.0
1
14.4
0.28
0.18
Insect Screen (default)
V1
Window
SE Wall 5 (Front -135)
6.3
2.0
1
12.6
0.28
0.18
Insect Screen (default)
W2
Window
SW Wall 5 (Left -225)
4.9
3.0
1
14.7
0.28
0.18
Insect Screen (default)
W1
Window
SW Wall 5 (Left -225)
6.0
3.0
1
18.0
0.28 1
0.18
Insect Screen (default)
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: -Title 24 Analysis Input File Name: Madison Club 23B-Kristi Hanson-15.xml
CF1 R-P§F-01
Page 8 of 16
23
Window
SW Wall 5 (Left -225)
10.8
9.0
1 97.2
0.32
0.24
Insect Screen (default)
U2
Window
SW Wall 5 (Left -225)
8.7
3.0
1 26.1
0.28
0.18
Insect Screen (default)
U1
Window
SW Wall 5 (Left -225)
6.3
3.0
1 18.9
0.28
0.18
Insect Screen (default)
Ti
Window
NW Wall 5 (Back -315)
8.9
2.0
1 17.8
0.28
0.18
Insect Screen (default)
DOORS
01
02
03
04
Name
Side of Building
Area (ft)
U -factor
26
SE Wall
20.1
0.50
'R 0 V
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 236-Kristi Hanson-15.xml
CF1 R -PRF -01
Page 9 of 16
OVERHANGS AND FINS
01
02
03
04
05
06
07
08
09
10
11
12
13
14
Overhang
Left Fin
Right Fin
Window
Depth
Dist Up
Left
Extent
Right
Extent
Flap Ht.
Depth
Top Up
DistL
Bot Up
Depth
Top Up
Dist R
Bot Up
K3
10
0.1
10
10
0
0
0
0
0
0
0
0
0
17
10
0.1
10
10
0
0
0
0
0
0
0
0
0
K2
10
0.1
10
10
0
0
0
0
0
0
0
0
0
12
10
0.1
10
10
0
0
0
0
0
0
0
0
0
K32
10
0.1
10
10
0
0
0
0
0
0
0
0
0
11
10
0.1
10
10
0
0
0
0
0
0
0
0
0
J2
10
0.1
10
10
0
0
0
0
0
0
0
0
0
11
10
0.1
10
10
0
0
0
0
0
0
0
0
0
H1
10
0.1
10
10
0
0
0
0
0
0
0
0
0
10
10
0.1
10
10
0
0
0
0
0
0
0
0
0
G2
10
0.1
�_ 10
,. 10 r
_.50 ,_
0 _
01,
0
0
0
0
0
0
G3
10
- .�0.1
10-
X10
- 0
0'� `
0
0
0
0
0
0
08
,1 0,
< " `0.1
�.'� _ 10 ,1
10-_
0 .
Or,
„ 0
i 0:--j
0
0
0
0
0
07
18
`,`0.,1
i. 18 -
---jt18 t-
a 0 ":
f-0 lk J
l- 0'-,
0r2
0
0
0
0
0
G1
18
0"!
18
F18—
' 0
"0
0—
w 0`
0
0
0
0
0
B1
10
0.1
10
10
0
0
0
0
0
0
0
0
0
A4
10
0.1
10
10
0
0
0
0
0
0
0
0
0
A5
10
0.1
10
10
0
0
0
0
0
0
0
0
0
01
10
0.1
10
10
0
0
0
0
0
0
0
0
0
A3
10
0.1
10
10
0
0
0
0
0
0
0
0
0
Al
10
0.1
10
10
0
0
0
0
0
0
0
0
0
A2
10
0.1
10
10
0
0
0
0
0
0
0
0
0
F5
18
0.1
18
18
0
0
0
0
0
0
0
0
0
F6
18
0.1
18
18
0
0
0
0
0
0
0
0
0
06
18
0.1
18
18
0
0
0
0
0
0
0
0
0
F4
18
0.1
18
18
0
0
0
0
0
0
0
0
0
F1
18
0.1
18
18
0
0
0
0
0
0
0
0
0
21
100.1
10
10.
0
0
0
0
0
0
0
0
0
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation DateMme: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 236-Kristi Hanson-15.xm1
CF1 R-P1RF-01 '
Page 10 of 16
Registration Number: 215-N6343967C-000000000.0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
����0000�0�00
0�00000000�00
Registration Number: 215-N6343967C-000000000.0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 236-Kristi Hansbn-15.xm1
CF1 R -PRF -01
Page 11 of 16
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
02
03
04
05
Total Cavity
Winter Design
Name
Construction Name
Surface Type
Construction Type
Framing
R -value
U -value
Assembly Layers
off nook dining
1621
206
None
0.8
No
• Cavity/Frame: no insul. /2x4 Top Chrd
great entry
1659
106
2x4 Top Chord of Roof Truss @ 24
0.8
No
Roof Deck: Wood Siding/sheathing/decking
Attic Roofoff nook dining
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
guest living
1413
190
None
0.8
No
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/ Frame: R-9.1 /2x4
R-38 Roof Attic
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 38
0.025
Over Floor Joists: R-28.9 insul.
• Inside Finish: Gypsum Board
• Cavity / Frame: R-21 / 2x6
• Exterior Finish: Wood
R-21 Wall (W.21.2x6.16)
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.066
Siding/sheathing/decking
• Cavity/Frame: no insul. /2x4 Top Chrd
Roofgreat
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic entry
Attic Roofs/, ,
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
Cavity / Frame: no insul. / 2x4 Top Chrd
-
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofmasterguest
Attic Roofs
_
Wood Framed Ceiling
fin: O.0 -:z� r= ,--:i rr
z,� none,
0.644
Roofing: Light Roof (Asphalt Shingle)
2x4 Top Chord Roof Truss @24
J
Cavity/Frame: no insul. /2x4 Top Chrd
Roof Deck:
of
it �`-' `in. L' 4
i �� ,
l
Wood Siding/sheathing/decking
Attic Roofguest living
Attic Roofs
,Wood Framed Ceiling'
O.C: `'
Pnone
0.644
Roofing: Light Roof (Asphalt Shingle)
�.J
V I U),
z i i
Cavity/ Frame: no insul. / 2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roof2nd master
Attic Roofs
Wood Framed Ceiling I
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
SLAB FLOORS
01
02
03
04
05
06
07
Name
Zone
Area (ft)
Perimeter (ft)
Edge Insul. R -value & Depth
Carpeted Fraction
Heated
Covered Slab
off nook dining
1621
206
None
0.8
No
Covered Slab 2
great entry
1659
106
None
0.8
No
Covered Slab 3
masterguest
1781
115
None
0.8
No
Covered Slab 4
guest living
1413
190
None
0.8
No
BUILDING ENVELOPE - HERS VERIFICATION
Ot 02 03 04
Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50
Required Not Required Not Required
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis Input File Name: Madison Club 23B-Kristi Hanson-15.xml
CF1 R-P14F-01
Page 12 of 16
WATER HEATING SYSTEMS
01
02
01
02 03
04 05 06
Name
System Type Distribution Type
Water Heater Number of Heaters Solar Fraction (%)
DHW Sys 1 - 1/3
DHW Pipe Insulation, All Lines
DHW Heater 1 3 .0%
WATER HEATERS
01
02
03
04
05
06
07
08
Name
Heater Element Type
Tank Type
Tank Volume
(gal)
Energy Factor or
Efficiency
Input Rating
Tank Exterior
Insulation
R -value
Standby Loss
(Fraction)
DHW Heater 1
Natural Gas
Small Storage
50
0.66
40000-Btu/hr
0
0
WATER HEATING - HERS VERIFICATION
01
02
03
04
05
06
07
Name
1
Pipe Insulation f.
Parallel Piping- -
Compact Distribution
Point -of Use
Recirculation
Control
Central DHW
Distribution
DHW Sys 1 - 1/3
f
HVAC Fan 1
Air Distribution System 1
Distribution System 1:HVAC Fan 1:1
---
---
SPACE CONDITIONING SYSTEMS
i ` '' �'^ ial✓f ''� T3
01
02
- 03 -
04
05
06
SC Sys Name
System Type
Heating Unit Name
Cooling Unit Name
Fan Name
Distribution Name
Cooling Component 1:Heating Component 1:Air
Other Heating and Cooling
Heating Component 1
Cooling Component 1
HVAC Fan 1
Air Distribution System 1
Distribution System 1:HVAC Fan 1:1
System
Cooling Component 2:Heating Component 2:Air
Other Heating and Cooling
Heating Component 2
Cooling Component 2
HVAC Fan 2
Air Distribution System 2
Distribution System 2:HVAC Fan 2:1
System
Cooling Component 3:Heating Component 3:Air
Other Heating and Cooling
Heating Component 3
Cooling Component 3
HVAC Fan 3
Air Distribution System 3
Distribution System 3:HVAC Fan 3:1
System
Cooling Component 4:Heating Component 4:Air
Other Heating and Cooling
Heating Component 4
Cooling Component 4
HVAC Fan 4
Air Distribution System 4
Distribution System 4:HVAC Fan 4:1
System
Cooling Component 5:Heating Component 5:Air
Other Heating and Cooling
Heating Component 5
Cooling Component 5
HVAC Fan 5
Air Distribution System 5
Distribution System 5:HVAC Fan 5:1
System
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CFI R-P'hF-01 '
Page 13 of 16
HVAC - HEATING UNIT TYPES
01
02
01
02
03
Name
Type
Efficiency
Heating Component 1
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 2
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 3
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 4
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 5
CntrlFurnace - Fuel -fired central furnace
80 AFUE
HVAC - COOLING UNIT TYPES
01
02
03 04
05
06
07
Name
Verified Airflow
Efficlency
Verified EER
Multi -speed
Verified Refrigerant
Charge
Name
System Type
EER SEER
Zonally Controlled
Compressor
HERS Verification
Cooling Component 1
SplitAirCond
13
16.5
Not Zonal
Single Speed
Cooling Component
Required
350
Required
Required
Required
Cooling Component 4 -hers -cool
1 -hers -cool
Cooling Component 2
SplitAirCond f
{ 13-- ,- -
.- 16.5 —
f
- Not Zonal
Single Speed
Cooling Component
2 -hers -cool
Required
Required
Required
Cooling Component 3
%
SplitAirCond
f. i 13
=� I `
16.5
�•
Not Zonal
Single Speed
Cooling Component
,
3 -hers -cool
Cooling Component 4
SplitAirCond. i y
' +� f:
'6.5°
Not Zonate
Single Speed
Cooling Component
` _13
;
-
4 -hers -cool
Cooling Component 5
SplitAirCond
13
16.5
Not Zonal
Single Speed
Cooling Component
5 -hers -cool
HVAC COOLING - HERS VERIFICATION
01
02
03
04
05
06
Name
Verified Airflow
Airflow Target
Verified EER
Verified SEER
Verified Refrigerant
Charge
Cooling Component 1 -hers -cool
Required
350
Required
Required
Required
Cooling Component 2 -hers -cool
Required
350
Required
Required
Required
Cooling Component 3 -hers -cool
Required
350
Required
Required
Required
Cooling Component 4 -hers -cool
Required
350
Required
Required
Required
Cooling Component 5 -hers -cool
Required
350
Required
Required
Required
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 236-Kristi Hanson-15.xml
CF1 R-PIIF-01
Page 14 of 16
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
Name
Type
Duct Leakage
Insulation R -value
Duct Location
Bypass Duct
HERS Verification
Air Distribution System 1
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
'Not Required
Not Required
---
Air Distribution System 2 -hers -dist
' Required
6.0 `
1 -hers -dist
Air Distribution System 2
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
Not Requimcl ""
" NotRequiredl
_:Not Required
Not Required
-
Air Distribution System 4 -hers -dist
2 -hers -dist
Air Distribution System 3
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
Required
6.0
Not Required
Not Required
Not Required
Not Required
3 -hers -dist
Air Distribution System 4
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
4 -hers -dist
Air Distribution System 5
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
5 -hers -dist
HVAC DISTRIBUTION - HERS VERIFICATION
01
02
03
04
05
06
07
08
Name
Duct Leakage
. Verification
Duct Leakage
Target (%)<
Verified Duct
Location
Verified Duct
Design
Buried
Ducts
Deeply Buried
Ducts
Low -leakage
Air Handier
Air Distribution System 1 -hers -dist
Required
'6.0
Not Required
Not Required
'Not Required
Not Required
---
Air Distribution System 2 -hers -dist
' Required
6.0 `
Not Required .
�_NotRequired
Not Required
Not Required
---
Air Distribution System 3 -hers -dist
Required
- 6.0-' =-
Not Requimcl ""
" NotRequiredl
_:Not Required
Not Required
-
Air Distribution System 4 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
---
Air Distribution System 5 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
---
HVAC - FAN SYSTEMS
01
02
03
04
Name
Type
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
HVAC Fan 1 -hers -fan
HVAC Fan 2
Single Speed PSC Furnace Fan
0.58
HVAC Fan 2 -hers -fan
HVAC Fan 3
Single Speed PSC Furnace Fan
0.58
HVAC Fan 3 -hers -fan
HVAC Fan 4
Single Speed PSC Furnace Fan
0.58
HVAC Fan 4 -hers -fan
HVAC Fan 5
Single Speed PSC Furnace Fan
0.58
HVAC Fan 5 -hers -fan
HVAC FAN SYSTEMS - HERS VERIFICATION
01 02 03
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 - Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE -METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis _ Input File Name: Madison Club 2313-Kristi Hanson- 15.xml
CF1 R -PRF -01
Page 15 of 16
Name
Verified Fan Waft Draw
Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan
Required
0.58
HVAC Fan 2 -hers -fan
Required
0.58
HVAC Fan 3 -hers -fan"
Required
0.58
HVAC Fan 4 -hers -fan
Required
0.58
HVAC Fan 5 -hers -fan
Required
0.58
IAQ (Indoor Air Quality) FANS
01
02
03
04
05
06
Dwelling Unit
IAQ CFM
IAQ Watts/CFM
IAQ Fan Type
IAQ Recovery
Effectiveness(%)
HERS Verification
SFam IAQVentRpt
.200.44
0.25
Default
0
Required
COOLING VENTILATION
,' i� ,
01
_ �.
02
03
04
05
Name
Cooling Vent CFM
Cooling Vent Watts/CFM
Total Watts
Number of Fans
WH Fan 1
61 �^'
i' � -'
, n)'0.52459( ��
32
1
WH Fan 2
+
�61 �r
j
l� i l� 0.52459 --'�) ': 1
C i s 32
1
WH Fan 3
61. '-r . es L
-� ,� `i 0.52459;—`
WH Fan 4
r
61,j—� ; y
f S
11 0.524,59 V j L I•
17- j�j 32
1
WH Fan 5
61
0.52459
32
1
PROJECT NOTES
The Madison Club 23B
Registration Number: 215-N6343967C-000000000-0000 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03092016-744 Report Generated at: 2016-04-07 11:45:48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Madison Club 23B Calculation Date/Time: 11:43, Thu, Apr 07, 2016
Calculation Description: Title 24 Analysis Input File Name: Madison Club 236=Kristi Hanson-15.xml
CF1 R -PRF -01
Page 16 of 16
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Tim Scott
Company:
Signature Date:
Scott Design and Title 24, Inc.
2016-04-07 11:58:25
Address:
CEA/HERS Certification Identification (If applicable):
77085 Michigan Drive
City/State/Zip:
Phone:
Palm Desert, CA 92211
760-200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify•that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations. `
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name: - (:{ i
Responsible Designer Signature: -, T
Tim Scott
Company: ` ,� 9 --- r
Date Signed:
Scott Design and Title 24, Inc.
2016-04-07 11:58:25
Address:
License:
77085 Michigan Drive
NA
City/State/Zip:
Phone:
Palm Desert, CA 92211
760-200-4780
Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document and in noway implies Registration Provider responsibility for the accuracy of the
information.
Registration Number: 215-N6343967C-000000000-0006 Registration Date/Time: 2016-04-07 11:58:25 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF113-03092016-744 Report Generated at: 2016-04-07 11:45:48
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Madison Club 23B
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
4/7/2016
Project Address
81-382 Amundson Ave. La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
8,044
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity (ft)
Special Features
Status
Roof Wood Framed Attic
R 38 6,945
New
Wall Wood Framed
R 21 9,480
New
Door Opaque Door
no insulation 20
New
Slab Unheated Slab -on -Grade
no insulation 6,474
Perim = 617'
New
Demising Wood Framed
R 13 3,280
New
FENESTRATION
Orientation Area ft2
I Total Area: 3,276 Glazing Percentage: 40.7 %
U -Fac SHGC Overhang Sidefins
New/Altered Average U -Factor:
Exterior Shades
0.30
Status
Right (NE) 255.0
0.280
0.18 10.0
none
Bug Screen
New
Right (NE) 287.0
0.320
0.24 10.0
none
Bug Screen
New
Front (SE) 309.1
0.280
0.18 10.0
none
Bug Screen
New
Left (SW) 411.9
0.280
0.18 10.0
none
Bug Screen
New
Left (SW) 255.0
0.320
0.24 10.0
none
Bug Screen
New
Rear (NM 403.0
0.320
0.24 18.0
none
Bug Screen
New
Rear (NW) 214.3
0.280
0.18 18.0
none
Bug Screen
New
Right (NE) 262.4
0.280
0.18 none
none
Bug Screen
New
Front (SE) 85.0
0.320
0.24 10.0
none
Bug Screen
New
Front (SE) 92.2
0.280
0.18 none
none
Bug Screen
New
Front (SE) 85.0
0.320
0.24 none
none
Bug Screen
New
Left (SW) 21.5
0.280
0.18 none
none
Bug Screen
New
Rear (NW) 78.0
0.320
0.24 none
none
Bug Screen
New
Rear (NM 68.4
0.280
0.18 none
none
Bug Screen
New
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling
Min. Eff
Thermostat
Status
1 Central Furnace
80% AFUE
Split Air Conditioner
16.5 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner
16.5 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner
16.5 SEER
Setback
New
HVAC DISTRIBUTION
Location Heating
Cooling Duct Location
Duct
R -Value
Status
HVAC 1 off kit nook Ducted
Ducted Attic
8.0
New
HVAC 2 grt enry Ducted
Ducted Attic
8.0
New
HVAC 3 mstr gest Ducted
Ducted Attic
8.0
New
WATER HEATING
Qty. Type
Gallons Min. Eff
Distribution
Status
3 Small Storage Gas
50
0.66
All Pipes Ins
New
Ener Pro 6.7 by Ener Soft User Number: 6712
RunCode: 2016-04-07711:47:24
/D:
Pae 19 of 49
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Madison Club 23B
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
4/7/2016
Project Address
81-382 Amundson Ave. La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
8,044
Addition
n/a
# of Units
Fl
INSULATION
Construction Type
Area
Cavity (ft) Special Features
Status
FENESTRATION Total Area: 3,276 Glazing Percentage: 40.7 % New/Altered Average U -Factor:
Orientation Area(ft) U -Fac SHGC Overhang Sidefins Exterior Shades
0.30
Status
Rear (NM 70.4 0.280
0.18 10.0 none Bug Screen
New
Rear (NIA 77.0 0.320
0.24 10.0 none Bug Screen
New
Right (NE) 36.0 0.280
0.18 6.0 none Bug Screen
New
Right (NE) 90.0 0.320
0.24 none none Bug Screen
New
Left (Sly 77.7 0.280
0.18 6.0 none Bug Screen
New
Left (St9 97.2 0.320
0.24 6.0 none Bug Screen
New
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling Min. Eff Thermostat
Status
1 Central Furnace 80% AFUE
Split Air Conditioner 16.5 SEER Setback
New
1 Central Furnace 80% AFUE
Split Air Conditioner 16.5 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value
Status
HVAC 4 gest liv Ducted
Ducted Attic 8.0
New
HVAC 5 2nd Ducted
Ducted Attic 8.0
New
WATER HEATING
Qty. Type Gallons Min. Eff Distribution
Status
Ener Pro 6.7 by Ener Soft User Number: 6712
RunCode: 2016-04-07T11:47:24 ID:
Page 20 of 49
2013 Low -Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the
compliance approach used. Exceptions may apply. Review the respective code section for more information.
Building Envelope Measures:
§110.6(a)1:
Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§ 110.6(a)5:
Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of § 10-111 (a).
§ 110.7:
Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed.
§ 110.8(a):
Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R.
§ 110.8(i):
The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of § 110.8(i) when the
installation of a cool roof is specified on the CF1R.
§ 110.80):
A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CFIR.
Minimum R-30 insulation in wood -frame ceiling; or the weighted average U -factor shall not exceed 0.031. Minimum R-19 in a
§ 150.0(a):
rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The
attic access shall be gasketed to prevent air leakage.
§ 150.0(b):
Loose fill insulation shall conform with manufacturer's installed design labeled R -value.
§ 150.0(c):
Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U -
factor).
§ 150.0(d):
Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U -factor.
In Climate Zones 14 and 16 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior
§ 150.0(g)1:
walls, vented attics and unvented attics with air -permeable insulation.
In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class II
§ 150.0(g)2:
vapor retarder.
In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of
§ 150.0(g)3:
the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section
150.0(d).
§ 150.0(1):
Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%;
have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration;
and when installed as part of a heated slab floor meets the requirements of § 110.8
150.0
§ (q)'
Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U-
factor of 0.58; or the weighted average U -factor of all fenestration shall not exceed 0.58.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
§ 150.0(e)IA:
Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1B:
Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
e ui ed with a readily accessible, operable, and tight -fitting damper or a combustion -air control device.
§150.0(e)1C:
Masonry or factory -built fireplaces have a flue damper with a readily accessible control.
§150.0(e)2:
Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside
of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§ 110.0-§ 110.3:
HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission.
§ 110.3(c)5:
Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation
valve, and recirculation loop connection requirements of § 1 10.3(c)5.
Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli-
§110.5:
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool
ands a heaters.
§ 150.0(h) 1:
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified
in § 150.0(h)2.
§ 150.0(h)3A:
Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any
dryer vent.
§ 150.0(i):
Heating systems are equipped with thermostats that meet the setback requirements of § 110.2(c).
§150.00)1 A:
Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§150.00)1B:
Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R- 12 external
insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank.
For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage
tank, all piping with a nominal diameter of 3/4 inch or larger, all piping associated with a domestic hot water recirculation system
§ 150.00)2A:
regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and
all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3-
A.
§ 150.0(j)2B:
All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable casing or sleeve
that allows for installation, removal, and replacement of the enclosed pipe and insulation.
2013 Low -Rise Residential Mandatory Measures Summary
150.00)2C:
Pipe for cooling system lines shall be insulated as specified in § 150.00)2A. Piping insulation for steam and hydronic heating
systems or hot waters stems with pressure > 15 psig shall meet the requirements in TABLE 120.3-A.
§ 150.00)3:
Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For
§ 150.00)3A:
example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or
painted with coating that is water retardant and provides shielding from solar radiation that degrades the material.
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I
§ 150.00)3B:
or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor
retarder.
Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3
feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the
§ 150.0(n)1:
space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000
Btu/hr.
§ 150.0(n)2:
Recirculating loops serving multiple dwelling units shall meet the requirements of § 110.3(c)5.
§150.0(n)3:
Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC)
or by a testing agency approved by the Executive Director.
Ducts and Fans Measures:
All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0,
§603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition.
Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC
§605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed
§150.0(m)1:
with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B or
aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than '/< inch, the
combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums
defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying
conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms
shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints
§ 150.0(m)2:
and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is
used in combination with mastic and draw bands.
§ 150.0(m)3-6:
Field -Fabricated Duct Systems shall comply with requirements for: pressure -sensitive tapes, mastics, sealants, and other
re uirements specified for duct construction; duct insulation R -value ratings; duct insulation thickness; and duct labeling.
§150.0(m)7:
All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic
dampers.
§150.0(m)8:
Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers
except combustion inlet and outlet air openings and elevator shaft vents.
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not
§ 150.0(m)9:
limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum,
sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is
water retardant and provides shielding from solar radiation.
§150.0(m)10:
Flexible ducts cannot have porous inner cores.
When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be
§ 150.0(m)11:
sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference
Residential Appendix RA3.
Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§150.0(m)12:
conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of
§150.0 m 12.
Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the
placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The
§ 150.0(m)13:
space conditioning system must also demonstrate airflow >_ 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic testing, in
accordance with Reference Residential Appendix RA3.
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode,
§ 150.0(m)15:
an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of> 350 CFM per ton of nominal cooling
capacity, and operating at an air -handling unit fan efficacy of:5 0.58 W/CFM as confirmed by field verification and diagnostic
testing, in accordance with Reference Residential Appendix RA3.
All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of
§ 150.0(o):
central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the
Whole Building Ventilation.
§150.0(o)lA:
Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.
Pool and Spa Heating Systems and Equipment Measures:
Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
§ 110.4(a):
Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat
setting; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating.
2013 ,Low -Rise Residential Mandatory Measures Summary
110.4(b)1:
Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction
and return lines, or built-up connections for future solar heating.
§ 110.4(b)2:
Outdoor pools or spas that have a heat pump or gas heater shall have a cover.
§ 110.4(b)3:
Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro-
grammed to run only during off-peak electric demand periods.
§ 110.5:
Natural gas pool and spa heaters shall not have a continuous burning pilot light.
§ I50.0(p):
Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements.
Lighting Measures:
§ 110.9:
All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of § 110.9.
§ 150.0(k)IA:
Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with § 150.0(k) in accordance with TABLE
150.0-A or TABLE 150.0-13, as applicable.
§150.0(k)IB:
When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply
with the applicable provisions of § 150.0(k).
The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with
§150.0(k)IC:
§ 130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has
been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180
watts of low efficacy lighting er electrical box.
§150.0(k)1D:
Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz.
Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no
§150.0(k)IE:
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with § 130.0(c). Night lights do not need to
be controlled by vacancy sensors.
§150.0(k)IF:
Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable
requirements of § 150.0(k).
§ 150.0(k)2A:
High efficacy luminaires must be switched separately from low efficacy luminaires.
§ 150.0(k)2B:
Exhaust fans shall be switched separately from lighting systems.
§ 150.0(k)2C:
Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF.
§ 150.0(k)2D:
Controls and equipment are installed in accordance with manufacturer's instructions.
§ 150.0(k)2E:
No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with § 150.0(k).
§ 150.0(k)2F:
Lighting controls comply with applicable requirements of § 110.9.
An Energy Management Control System (FMCS) may be used to comply with dimmer requirements if: it functions as a dimmer
§ 150.0(k)2G:
according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other
requirements in § 150.0(k)2.
An Energy Management Control System (FMCS) may be used to comply with vacancy sensor requirements of § 150.0(k) if: it
§ 150.0(k)2H:
functions as a vacancy sensor according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements
of § 130.5; and all other requirements in § 150.0(k)2.
§ 150.0(k)2I:
A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the
functionality of a dimmer according to § 110.9, and complies with all other applicable requirements in § 150.0(k)2.
§ 150.0(k)3A:
A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only
§ I50.0(k)3B:
the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are
considered kitchen lighting if they are not separately switched from kitchen lighting.
§ 150.0(k)4:
Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.
§ 150.0(k)5:
A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom
shall be high efficacy or controlled by vacancy sensors.
§ 150.0(k)6:
Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§ I50.0(k)7:
Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high
efficacy, or shall be controlled by either dimmers or vacancy sensors.
Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other
nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0
CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing
§ 150.0(k)8:
and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and
allow ballast maintenance and replacement without requiring cutting holes in the ceiling.
For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with § 150.0(k), the ballasts
shall be certified to the Energy Commission to comply with the applicable requirements in § 110.9.
For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the
same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and
§ 150.0(k)9A:
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically
reactivates the motion sensor within 6 hours; and
iii. Controlled by one of the following methods:
2013 ,Low -Rise Residential Mandatory Measures Summary
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is
programmed to automatically tum the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of
an astronomical time clock in accordance with § 110.9; meets the Installation Certification requirements in §130.4; meets the
requirements for an EMCS in § 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically tum the outdoor lighting OFF during daylight hours.
For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor
lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
§ 150.0(k)9B:
following requirements:
i. Shall comply with § 150.0(k)9A; or
ii. Shall comply with the applicable requirements in §110.9, §130.0, § 130.2, § 130.4, § 140.7 and §141.0.
§ 150.0(k)9C:
For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by § 150.0(k)9B or 150.0(k)9D
shall comply with the applicable requirements in § 110.9, § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0.
§ 150.0(k)9D:
Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply
with the applicable requirements in § 110.9, § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0.
§150.0(k)10:
Internally illuminated address signs shall comply with § 140.8; or shall consume no more than 5 watts of power as determined
according to § 13 0.0(c).
§150.0(k)11:
Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for
nonresidential garages in § 110.9, § 130.0, § 130. 1, § 130.4, § 140.6, and § 141.0.
In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of
§ 150.0(k)12A:
the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20
percent of the floor area, permanently installed lighting in that building shall:
§ 150.0(k)1213:
i. Comply with the applicable requirements in § 110.9, § 130.0, § 130. 1, § 140.6 and § 141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
ingress and egress.
Solar Ready Buildings:
Single family residences located in subdivisions with ten or more single family residences and where the application for a
§ 110.10(a)1:
tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014,
shall comply with the requirements of § 110.10 through § 110.10 e .
§ 110.10(a)2:
Low-rise multi -family buildings shall comply with the requirements of § 110.10(b) through § 110.10(d).
The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a
local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than
80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for
§ 110.10(b)1:
buildings with roof areas greater than 10,000 square feet.
For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less
than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or
on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the
building project and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area.
§ 110.10(b)2:
All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north.
§ 110.10(b)3A:
No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be
located in the solar zone.
Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice
§ 110.10(b)3B:
the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the
horizontal projection of the nearest point of the solar zone, measured in the vertical plane.
§ 110.10(b)4:
For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly
indicated on the construction documents.
The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit
§ l 10.10(c):
from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating
system.
§ 110.10(d):
A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c)
shall be provided to the occupant.
§ 110.10(e)1:
The main electrical service panel shall have a minimum busbar rating of 200 amps.
The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a
§110.10(e)2:
future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or
main circuit location, and permanently marked as "For Future Solar Electric".
d-IVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Madison Club 23B
Date
4/7/2016
System Name
HVAC 1 off kit nook
Floor Area
1,621
ENGINEERING CHECKS
SYSTEM LOAD
Number of System
1
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL
CFM
3,115
243
COOLING PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 110,000
33,156
2,867 721
35,004
Total Output Btuh 110,000
0
Output Btuh/s ft 67.9
1,562
1,336
Cooling System
.01
0
Output per System 58,000
10,678
2,750 243
11,741
Total Output Btuh 58,000
1,489
1,562
1 48,448
5,617
-1,489
Total Output ons 4.8
1,336
Total Output Btuh/s ft 35.8
Total Output s ft/Ton 335.4
47,928
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
carrier 24ANB760/58MVB110-
36,577
15,187
110,000
Airflow cfm/s ft
1.23
110,000
Jan 1 AM
Airflow cfm/Ton 413.8
Outside Air % 12.2 %
Total Adjusted System Output 36,577
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
15,187
Aug 3 PM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
jAirstream Temperatures at Time of Heating Peak
26 OF 66 OF
Outside Air
243 cfm Supply Fan
2,000 cfm
71 OF
67 OF 118 OF
Heating Coil
ti•-.i-�..�
118 OF
"OO,M
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 76/65°F 76/65°F 59/58°F
Outside Air O
243 cfm Supply Fan Cooling Coil
2,000 cfm
71 /63°F
60 / 59 OF
Q
67.0% ROOM
70/63°F
EnergyPro 6.7 by EnergySoft User Number. 6712 RunCode: 2016-04-07T11:47:24 ID:
Page 25 of 49
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Madison Club 23B
Date
4/7/2016
System Name
HVAC 2 grt enry
Floor Area
1,659
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL
CFM
2,180
249
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Out ut per System 110,000
27,144
2,934 512
24,951
Total Output Btuh 110,000
0
Output Btuh/s ft 66.3
1,279
952
Cooling System
0
Output per System 58,000
10,964
3,550 249
12,064
Total Output Btuh 58,000
1,489
6,484
-1,489
Total Output Tons 4.8
1,279
952
Total Output Btuhls ft 35.0
Total Output s ft/Ton 343.2
1 42,155
37,430
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24ANB760/58MVB110
39,916 11,204
110,000
Airflow cfm/s ft 1.21
Airflow cfm/Ton
413.8
110,000
Jan 1 AM
Outside Air % 12.4%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
1 39,916 11,204
Aug 3 PM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 66 OF
Outside Air Ar
249 cfm Supply Fan
2,000 cfm
72 OF
67 OF 118 OF
Heating Coil
��_...�
118 `F
ROOM
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 76/64°F 76/65°F 58/57°F -
Outside Air Ar Im
249 cfm Supply Fan Cooling Coil
2,000 cfm
71 /62°F
_I
58 / 57 OF
p
63.1 % ROOM
70/62°F
I .
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-04-07T11:47:24 ID: Page 26 of 49
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Madison Club 23B
Date
4/7/2016
System Name
HVAC 3 mstr gest
Floor Area
1,781
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL
CFM
1,819
267
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output per System 110,000
22,257
3,150
436
21,112
Total Output Btuh 110,000
0
Output Btuh/s ft 61.8
1,049
806
Cooling System
0
0
Output per System 58,000
11,801
3,633 267
12,970
Total Output Btuh 58,000
1,489
6,783
-1,489
Total Output Tons 4.8
1,049
806
Total Output Btuh/s ft 32.6
Total Output s ftiTon 368.5
1 37,644
34,205
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24ANB760/58MVB110
39,853
11,521
110,000
110,000
Jan 1 AM
Airflow cfm/s ft 1.12
Airflow cfmrron 413.8
Outside Alr % 13-4%
Total Adjusted System Output 39,853
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
11,521
Aug 3 PM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 66 OF 66 OF 118 OF
Ct
Outside Air
267 cfm . Supply Fan Heating Coil
2,000 cfm
72 OF
.—.. �....
118 OF
I,RQOM
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 76/65°F 77/65°F 58/57°F
0'
Outside Air Ar
267 cfm Supply Fan Cooling Coil
2,000 cfm
70/62°F
59 / 57 OF
64.0% ROOM
70/62°F
EnergyPro 6.7 by EnergySoft
User Number., 6712 RunCode: 2016-04-07T11:47:24 ID:
Page 27 of 49
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Madison Club 23B
Date
4/7/2016
System Name
HVAC 4 gest liv
Floor Area
1,413
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,828
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 212
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output per System
110,000
24,476
2,499
561
27,813
Total Output Btuh
110,000
0
Output Btuh/s ft
77.8
1,153
1,062
Cooling System
0
0
Output per System 58,000
9,351
3,369 212
10,263
Total Output Btuh 58,000
1,489
1,153
1 37,623
5,868
-1,489
Total Output Tons 4.8
1,062
Total Output Btuh/s ft 41.0
Total Output s ft/Ton 292.3
38,711
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24ANB760/58MVB110 39,927
10,543
110,000
Airflow cfm/s ft
1.42
Airflow cfm/Ton
413.8
Outside Air %
10.6 %
Total Adjusted System Output 39,927
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
10,543
Aug 3 PM
110,000
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions I
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 67 OF 67 OF 119 OF
Outside Air
212 cfm Supply Fan Heating Coil
2,000 cfm
72 OF
119 OF
ROOM In
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 75/63°F 76/64°F 57/56°F
a -
.�., _._.
Outside Air -4 r O �I�Ip
212 cfm Supply Fan Cooling Coil 57 / 56 OF
2,000 cfm
61.0% ROOM
71 / 61 OF 70 / 61 OF
EnergyPro 6.7 by EnergySoft
User Number: 6712 RunCode: 2016-04-07711:47:24 ID:
Page 28 of 49
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Madison Club 23B
Date
4/7/2016
System Name
HVAC 5 2nd
Floor Area
1,570
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,507
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 236
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output per System 110,000
19,641
2,777
343
16,916
Total Output Btuh 110,000
0
Output Btuh/s ft 70.1
925
646
Cooling System
0
0
Output per System 58,000
10,417
3,528
236
11,453
Total Output Btuh 58,000
1,489
925
33,398 6,305
-1,489
Total Output Tons 4.8
646
Total Output Btuh/s ft 36.9
Total Output s ft/Ton 324.8
E28172
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24ANB760/58MVB110 39,816 11,009
110,000
Airflow cfm/s ft 1.27
Airflow cfmfron 413.8
Outside Air %
11.8%
Total Adjusted System Output 39,816 11,009
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK Aug 3 PM
110,000
Jan 1 AM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 66 OF
Outside Air
236 cfm Supply Fan
2,000 cfm
72 OF
67 OF 119 OF
�,....1�
Heating Coil 118 ,F
Ft00M
72 OF
L!
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time ofPeak
.Cooling
112/78°F 75/64°F 76/64°F 57/56°F
Ct ��Outside Air Ar
236 cfm Supply Fan Cooling Coil 58 / 57 OF
2,000 cfm
62.2% ROOM Fa
70/62°F 70/61 OF
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-04-07T11:47:24 ID: Page 29 of 49
ROOM LOAD SUMMARY
Project Name Date
Madison Club 238 4/7/2016
System Name Floor Area
HVAC 1 off kit nook 1,621
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible I Latent CFM Sensible I Latent CFM I Sensible
off nook dining Office Kitchen Nook & Di 1 1 3,1151 33,1561 Z 867 3,1151 33,1561 2,867 7211 35,004
PAGE TOTAL
TOTAL*
3,115
33,156
2,8671
721
35,004
3,115
33,156
2,8671
721
35,0041
* Total includes ventilation load for zonal systems.
EnergyPro 6.7 by Ener Soft User Number: 6712 RunCode: 2016-04-07T11:47:24 ID: Page 30 of 49
ROOM LOAD SUMMARY
Project Name Date
Madison Club 238 4/7/2016
System Name Floor Area
HVAC 2 grt enry 1,659
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible I Latent CFM Sensible Latent I CFM I Sensible
great entry Great Room and Entry 1 1 1 2,1801 27,1441 2,934 2,1801 27,1441 2,9341 5121 24,951
PAGE TOTAL
TOTAL*
2,180
27,144
2,9341
512
24,951
F2,18OF
27,144
2,9341
512
24,951
* Total includes ventilation load for zonal systems.
EnetigyPro 6.7 by Eneng Soft User Number: 6712 RunCode: 2016-04-07711:47:24 ID: Page 31 of 49
ROOM LOAD SUMMARY
Project Name Date
Madison Club 238 4/7/2016
HVAC 3 mstr gest 1,781
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible I Latent CFM I Sensible I Latent CFM I Sensible
masterguest Guest Master Bedroom I 1 1 1,8191 22,2571 3,150 1,8191 22,2571 3,150 4361 21,112
PAGE TOTAL
TOTAL *
1,819
22,257
3,150
436
21,112
1,819
22,257
3,150
436
21,112
* Total includes ventilation load for zonal systems.
Ener Pro 6.7 by Ener Soft User Number. 6712 RunCode: 2016-04-07T11:47:24 ID: Page 32 of 49
ROOM LOAD SUMMARY
Project Name Date
Madison Club 238 4/7/2016
System Name Floor Area
HVAC 4 gest liv 1,413
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name I Mult. I CFM I Sensible I Latent CFM I Sensible I Latent CFM I Sensible
guest living I Guest Living Area I 1 1 1,8281 24,4761 2,4991 1,8281 24,4761 2,499 5611 27,813
PAGE TOTAL
TOTAL`
1,828
24,476
2,499
561
27,813
1,828
24,476
2,499
561
27,813
Total includes ventilation load for zonal systems.
Ener Pro 6.7 by Ener Soft User Number: 6712 RunCode: 2016-04-07711:47:24 ID: Page 33 of 49
ROOM LOAD SUMMARY
Project Name Date
Madison Club 238 4/7/2016
System Name Floor Area
HVAC 5 2nd 1,570
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. I CFM Sensible I Latent CFM I Sensible Latent CFM Sensible
2nd master 2nd Floor Master Bedrood 1 1,507 19,641 2,777 1,507 19,641 2,777 3431 16,916
PAGE TOTAL
TOTAL*
1,507
19,641
2,777
343
16,916
1,5071
19,6411
2,7771
343
16,916
* Total includes ventilation load for zonal systems.
Ener Pro 6.7 by Ener Soft User Number. 6712 RunCode: 2016-04-07711:47:24 ID: Page 34 of 49
ROOM HEATING PEAK LOADS
Project Name
Madison Club 23B
Date
4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Office Kitchen Nook & Dining
Floor Area 1,621.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area U-Value
522.0 X 0.0260
2,137.8 X 0.0690
584.1 X 0.2800
570.0 X 0.3200
20.1 X 0.5000
perim = 206.0 X 0.7300
856.0 X 0.1020
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
through an interior surface to another room
X 1,621 X 9.00 X 0.361
Area Ceiling Height ACH
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT °F
=
c
=
=
0
=
0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
46
624
R-21 Wall (W.21.2x6.16)
46
6,785
FIX door window slider. 28.18
46
7,523
OPP window door slider .32.24
46
8,390
Wood Door
46
462
Slab-On-Grade
46
6,917
'R-13 Wall
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
Page Total
/60] X
AT
30,703
= 4,301
TOTAL HOURLY HEAT LOSS FOR ROOM 35,004
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-04-07T11:47:24 ID: Page 35 of 49
ROOM HEATING PEAK LOADS
Project Name
Madison Club 238
Date
4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great Room and Entry
Floor Area 1,659.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U-Value AT OF
X 0.0260 X 46
X 0.0690 X 46
X 0.2800 X 46
X 0.3200 X 46
X 0.7300 X 46
X 0.1020 X 0
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
to another room Page Total
9.00 X 0.361 /60] X
Ceiling Height ACH AT
Btu/hr
= 1,984
= 4,698
= 6,054
= 4,254
= 3,559
= 0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
20,549
46 = 4,402
R-38 Roof Attic
1,659.0
R-21 Wall (W.21.2x6.16)
1,480.0
FIX door window slider. 28.18
470.0
OPP window door slider .32.24
289.0
Slab-On-Grade
perim = 106.0
'R-13 Wall
511.0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,659 X
Area
TOTAL HOURLY HEAT LOSS FOR ROOM 24,951
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-04-07T11:47:24 ID: Page 36 of 49
ROOM HEATING PEAK LOADS
Project Name
Madison Club 23B
Date
4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Master Bedroom
Floor Area 1,781.0 ftZ
Indoor Dry Bulb Tem erature 72 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction Area
R-38 Roof Attic 1,781.0
R-21 Wall (W.21.2x6.16) 1,498.5
FIX door window slider. 28.18 251.5
OPP window door slider .32.24 163.0
Slab -On -Grade perim = 115.0
*R-13 Wall 712.0
Items shown with an asterisk (') denote conduction through an interior surface
Infiltration:[ 1.00 X 1.064 X 1,781 X
Schedule Air Sensible Area
Fraction
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value AT'F
0.0260 X 46 =
0.0690 X 46 =
0.2800 X 46 c
0.3200 X 46 =
0.7300 X 46 =
0.1020 X 0 =
X =
X =
X =
X =
X =
X =
X =
X =
X
X =
X =
X =
X =
X =
X =
X =
X =
X
X =
X =
X =
X =
X =
X =
X =
another room Page Total
9.00 X 0.361 /60] X 46
Height ACH AT
Btu/hr
2,130
4,756
3,239
Z399
3,862
0
16,387
= 4,725
TOTAL HOURLY HEAT LOSS FOR ROOM 21,112
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-04-07T11:47:24 ID: Page 37 of 49
ROOM HEATING PEAK LOADS
Project Name
Madison Club 23B
Date
4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Living Area
Floor Area 1,413.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
0.0260 X
0.0690 X
0.3200 X
0.2800 X
0.7300 X
0.1020 X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
another room
9.00 X 0.361
Height ACH
AT °F
c
=
=
c
0
0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
1,413.0
46
1,690
R-21 Wall (W.21.2x6.16)
Z449.2
46
7,774
OPP window door slider .32.24
248.0
46
3,651
FIX door window slider. 28.18
354.8
46
4,570
Slab -On -Grade
perim = 190.0
46
6,380
*R-13 Wall
745.0
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,413 X
Area
Page Total
/60] X
AT
24,064
= 3,749
TOTAL HOURLY HEAT LOSS FOR ROOM 27,813
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-04-07T11:47:24 ID: Page 38 of 49
ROOM HEATING PEAK LOADS
Project Name
Madison Club 23B
Date
4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name 2nd Floor Master Bedroom
Floor Area 1,570.0 ft2
Indoor Dry Bulb Temperature 72 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction Area
R-38 Roof Attic 1,570.0 X
R-21 Wall (W.21.2x6.16) 1,914.3 X
FIX door window slider. 28.18 158.5 X
OPP window door slider .32.24 187.2 X
'R-13 Wall 456.0 X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Items shown with an asterisk (') denote conduction through an interior surface to
Infiltration:[ 1.00 X 1.064 X 1,570 X
Schedule Air Sensible Area Ceiling
Fraction
U-Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT °F
46 c
46 =
Btu/hr
0.0260
1,878
0.0690
6,076
0.2800
46
=
2,041
0.3200
46
=
2,756
0.1020
0
=
0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
another room
9.00 X 0.361
Height ACH
Page Total
/60] X 46
AT
12,751
= 4,166
TOTAL HOURLY HEAT LOSS FOR ROOM 16,916
EnergyPro 6.7 by EnergySoft User Number. 6712 RunCode: 2016-04-07T11:47:24 ID: Page 39 of 49
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Madison Club 23B
ROOM INFORMATION
Room Name
Floor Area
Indoor Dry Bulb Tem en
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
Wood Door
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
*R-13 Wall
DESIGN CONDITIONS
Office Kitchen Nook & Dining Outdoor Dry Bulb Temperature
1,621.0 ft2 Outdoor Wet Bulb Temperature
70 °F Outdoor Dailv Ranee:
Orientation
(NE)
(SE)
(SE)
(SW)
(NW)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
522.0
0.0260
56.0
493.0
0.0690
29.0
334.9
0.0690
31.0
20.1
0.5000
31.0
1,148.7
0.0690
31.0
161.2
0.0690
30.2
856.0
0.1020
0.0
16.4
121.0
15.3
0.0
20.8
16.0
12.3
0.0
Page Total
Items shown with an asterisk (*) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
K3
17
K2
12
K3
11
J2
J1
H1
Orientation
(NE)
(NE)
(NE)
(SE)
(SW)
(SW)
(S W)
(SW)
(S W)
Shaded Unshaded
4/7/2016
112 OF
78 OF
34 OF
Btu/hr
986
716
312
1 3361
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
c
=
=
=
=
=
=
=
=
0.0
12.3
110.0
18.1
0.0
15.3
116.0
23.0
0.0
12.3
113.0
18.1
109.0
12.3
0.0
16.4
110.0
12.3
0.0
16.4
121.0
15.3
0.0
20.8
16.0
12.3
0.0
16.4
16.0
12.3
0.0
16.4
21.2
12.3
0.0
16.4
Page Total
Btu/hr
1,987
2,671
2,042
1,338
1,351
1,852
196
1 1961
11,
Internal Gain Btu/hr
Occupants 4 9 Occupants X 245 Btuh/occ. = 1,191
Equipment 1,621 Floor Area X 0.50 w/sgff = 2,766
Infiltration: 1.064 X 1.27 X 66.86 X 42 = 3,782
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 33,1561
Latent Gain Btu/hr
Occupants 4 9 Occupants X 155 Btuh/occ. = 754
Infiltration: 4,771 X 1.27 X 66.86 X 0.00523 = 2,113
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 7541
I EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-04-07711:47:24 ID: Page 40 of 49 1
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 238
1 4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Office Kitchen Nook & Dining
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1, 621.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (*)
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
10
(SM 110.0 X 15.3 +
0.0 X
20.8 =
1,684
G2
(SI49 43.5 X 12.3 +
0.0 X
16.4 =
534
G3
(s 149 5.6 X 12.3 +
0.0 X
16.4 =
69
08
IS 149 24.0 X 15.3 +
0.0 X
20.8 =
367
07
(NIA 0.0 X 15.3 +
199.0 X
23.0 =
4,582
G1
(NIAq 0.0 X 12.3 +
39.8 X
18.1 =
719
X +
X
=
X +
X
=
X +
X
=
Page Total
7,95
Internal Gain
Btu/hr
Occupants
49 Occupants X 245
Btuh/occ.
=
1,191
Equipment
1,621 Floor Area X 0.50
w/sgft
=
2,766
Infiltration: 1.064
X 1.27 X 66.86 X
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
33,156
Latent Gain
Btu/hr
Occupants
4 9 Occupants X 155
Btuh/occ.
=
754
Infiltration: 4,771
X 1.27 X 66.86 X
F
2,113
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
754
Ener Pro 6.7 by EnetiqySoft
User Number: 6712 RunCode: 2016-04-07T11:47:24 ID:
Page 41 of 49
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Madison Club 238 1 4/7/2016
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Great Room and Entry
Outdoor Dry Bulb Temperature
112 °F
Floor Area
1,659.0 ft2
Outdoor Wet Bulb Temperature
78 °F
Indoor Dry Bulb Temperature
70 OF
Outdoor Dailv Ranae:
34 OF
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W 21.2x6.16)
R-21 Wall (W.21.2x6.16)
*R-13 Wall
Orientation
(M
(NE)
(SE)
(SW)
(NM
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
c
=
=
=
=
=
=
1,659.0
0.0260
56.0
564.0
0.0690
29.0
155.5
0.0690
31.0
684.0
0.0690
31.0
76.5
0.0690
30.2
511.0
0.1020
0.0
9.2
12.3
0.0
16.4
85.0
15.3
0.0
20.8
17.5
12.3
0.0
Page Total
Items shown with an asterisk (*) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
F3
F2
B1
A4
A5
01
A3
Al .
A2
CAriPntatinn
(NE)
(NE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
0.0
12.3
60.0
18.1
0.0
12.3
60.0
18.1
8.3
12.3
0.0
16.4
35.4
12.3
0.0
16.4
9.2
12.3
0.0
16.4
85.0
15.3
0.0
20.8
17.5
12.3
0.0
16.4
35.4
12.3
0.0
16.4
9.3
12.3
0.0
Page Total
1
5,499
Btu/hr
1,084
1,084
102
435
113
1,301
215
435
11
4,8831
Internal Gain Btu/hr
Occupants 5 0 Occupants X 245 Btuh/occ. = 1,219
Equipment 1,659 Floor Area X 0.50 w/sgft
Infiltration: 1.0e X 1.27 X 68.43 X 42 = C
Air Sensible CFM ELA AT
1 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 27,1441
Latent Gain Btu/hr
Occupants 5 0 Occupants X 155 Btuh/occ. = 771
Infiltration: 4, 771 X 1.27 X 68.43 X 0.00523 = 2,163
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 7711
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 238
4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Great Room and Entry
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,659.0 ft-
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 °F
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area GLF
Btu/hr
M1
(SE) 0.01 X 12.3 +
60.4 X
16.4 =
992
F5
(NKq 0.0 X 12.3 +
55.1 X
18.1 =
996
F6
(NM 0.0 X 12.3 +
17.4 X
18.1 =
314
06
(NM 0.0 X 15.3 +
204.0 X
23.0 =
4,697
F4
(NIM 0.0 X 12.3 +
51.0 X
18.1 =
921
F1
(NM 0.0 X 12.3 +
51.0 X
18.1 =
921
X +
X
=
X +
X
=
X +
X
=
Page Total
8,842
Internal Gain
Btu/hr
Occupants
50 Occupants X 245
Btuh/occ.
=
1,219
Equipment
1.659 Floor Area X 0.50
w/sgft
=
2,831
Infiltration: 1.064
X 1.27 X 68.43 X 42 =
3,870
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
27,144
Latent Gain
Btu/hr
Occupants
5.0 Occupants X 155
Btuh/occ.
=
771
Infiltration: 4,771
X 1.27 X 68.43 X
F7
2,163
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
771
Ener Pro 6.7 by Ener Soft
User Number. 6712 RunCode: 2016-04-07T11:47:24 ID:
Page 43 of 49
c
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Madison Club 238 4/7/2016
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Guest Master Bedroom
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1, 781.0 ft-
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
*R-13 Wall
Orientation
I'm
(NE)
(SE)
(SIM
(NM
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,781.0
0.0260
56.0
514.6
0.0690
29.0
471.8
0.0690
31.0
178.5
0.0690
31.0
333.6
0.0690
30.2
712.0
0.1020
0.0
0.0
12.3
19.2
16.4
0.0
15.3
85.0
20.8
0.0
12.3
21.5
Page Total
Items shown with an asterisk (*) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
I Fanastratinn
E1
E2
D3
D2
D1
02
C1
05
E5
Orientation
(NE)
(NE)
(NE)
(NE)
(SE)
(SE)
(SW)
(NW)
(NM
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
12.3
96.0
18.1
0.0
12.3
19.2
18.1
0.0
12.3
5.6
18.1
0.0
12.3
21.6
18.1
0.0
12.3
19.2
16.4
0.0
15.3
85.0
20.8
0.0
12.3
21.5
16.4
0.0
15.3
78.0
23.0
0.0
12.3
15.6
18.1
Page Total
Btu/hr
2,5931
1,030
1,009
382
5,710
Btu/hr
1,735
347
101
390
315
1,771
353
1,796
28
7,0901
Internal Gain Btu/hr
Occupants 5 3 Occupants X 245 Btuh/occ. = 1,�
Equipment 1.781 Floor Area X 0.50 w/sqn = 3,1
Infiltration: 1.064 X 1.27 X 73.46 X 42 = ,
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 22,257
Latent Gain Btu/hr
Occupants 5 3 Occupants X 155 Btuh/occ. = 828
Infiltration: 4,771 X 1.27 X 73.46 X 0.00523 = 2,322
Air Sensible CFM ELA AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 828
IEnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-04-07T11:47:24 ID: Page 44 of 49 1
A
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 23B
4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest Master Bedroom
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,781.0 ft-
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
E3
(NtM 0.0 X 12.3 +
44.0
X 18.1
= 795
E4
(NK9 0.0 X 12.3 +
8.8
X 18.1
= 159
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
Page Total
954
Internal Gain
Btu/hr
Occupants
53 Occupants X 245
Btuh/occ.=L
1,309
Equipment
1,781 Floor Area X 0.50
w/sgft
=
3,039
Infiltration: 1.064
X 1.27 X 73.46 X 42 =
4,155
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
22,257
Latent Gain
Btu/hr
Occupants
5 3 Occupants X 155
Btuh/occ.
=
828
Infiltration: 4,771
X 1.27 X 73.46 X 0.00523 =
2,322
Air Sensible
CFM ELA OW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
828
Ener Pro 6.7 by Ener Soft
User Number. 6712 RunCode: 2016-04-07711:47:24 ID:
Page 45 of 49
.f
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Madison Club 236 4/7/2016
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Guest Living Area
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,413.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
70 OF
Outdoor Daily Ranqe:
34 OF
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
*R-13 Wall
Orientation
(M
(NE)
(SE)
(SW)
(NM
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,413.0
0.0260
56.0
704.0
0.0690
29.0
548.4
0.0690
31.0
707.4
0.0690
31.0
489.4
0.0690
30.2
745.0
0.1020
0.0
221
40.0
0.0
491
18.0
0.0
221
18.0
0.0
221
Page Total
Items shown with an asterisk (*) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
21
R2
R1
19
Q1
P3
N4
P2
P1
Orientation
(NE)
(NE)
(NE)
(NE)
(SE)
(SE)
(SE)
(S W)
(SIM
Btu/hr
1,409
1,173
1,513
1,021
1 7,1731
Shaded
Area
X
X
X
X
X
X
X
X
GLF
15.3 +
12.3 +
12.3 +
15.3 +
12.3+
12.3 +
12.3 +
12.3 +
12.3 +
Unshaded
Area
X
X
X
X
X
X
X
X
GLF
23.0 =
18.1 =
18.1 =
23.0 =
16.4=
16.4 =
16.4 =
16.4 =
16.4 =
Page Total
Btu/hr
0.01
90.0
2,072
0.0
16.0
289
0.0
16.0
289
0.0
81.0
1,865
12.6X
0.0X
155
18.0
0.0
221
40.0
0.0
491
18.0
0.0
221
18.0
0.0
221
5,824
Internal Gain Btu/hr
Occupants 4 2 Occupants X 245 Btuh/occ. = 1,039
Equipment 1,413 Floor Area X 0.50 w/sgft = 2,411
Infiltration: 1.064 X 1.27 X 58.28 X 42 = 3,297
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 24,4761
Latent Gain Btu/hr
Occupants 4 2 Occupants X 155 Btuh/occ. = 657
Infiltration: 4,771 X 1.27 X 58.28 X 0.00523 = 1,842
Air Sensible CFM ELA AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 6571
r -J
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 238
4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest Living Area
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,413.0 ft--
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 T
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
N3
(SM 62.0 X 12.3 +
0.0
X 16.4 =
761
N2
(SIAL 62.0 X 12.3 +
0.0
X 16.4 =
761
S2
(SKq 39.6 X 12.3 +
0.0
X 16.4 =
486
N1
(NK9 0.0 X 12.3 +
40.0
X 18.1 =
723
18
(NKK 0.0 X 15.3 +
77.0
X 23.0 =
1,773
51
(NM 0.0 X 12.3 +
12.6
X 18.1 =
228
X +
X =
X+
X =
X +
X =
Page Total
4, 732
Internal Gain
Btu/hr
Occupants
4 2 Occupants X 245
Btuh/occ.
=
1,039
Equipment
1,413 Floor Area X 0.50
w/sgft
=
2,411
Infiltration: 1.064
X 1.27 X 58.28 X 42 =
3,297
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
24,476
Latent Gain
Btu/hr
Occupants
4 2 Occupants X 155
Btuh/occ.
=
657
Infiltration: 4,771
X 1.27 X 58.28 X 0.00523 =
11842
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT
HEAT GAIN FOR ROOM
657
Ener Pro 6.7 by Ener Soft
User Number: 6712 RunCode: 2016-04-07711:47:24 ID:
Page 47 of 49
_ti
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Madison Club 23B 4/7/2016
ROOM INFORMATION DESIGN CONDITIONS
Room Name 2nd Floor Master Bedroom Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,570.0 ft-- Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF 1 Outdoor Dailv Ranae: 34 OF
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
'R-13 Wall
Orientation
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,570.0
0.0260
56.0
654.0
0.0690
29.0
323.0
0.0690
31.0
605.1
0.0690
31.0
332.2
0.0690
30.2
456.0
0.1020
0.0
14.7
12.3
0.0
16.4
18.0
12.3
0.0
16.4
96.8
15.3
0.4
Page Total
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
12
22
M1
V1
W2
W1
23
U2
U1
Orientation
(NE)
(NE)
(SE)
(SE)
(SW)
(S W)
(S W)
(S W)
(SIM
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
0.0
12.3
36.0
18.1
0.0x
15.3+
90.0x
23.0=
14.4
12.3
0.0
16.4
0.0
12.3
12.6
16.4
14.7
12.3
0.0
16.4
18.0
12.3
0.0
16.4
96.8
15.3
0.4
20.8
26.1
12.3
0.0
16.4
18.9
12.3
0.0
Page Total
Btu/hr
2,286
1,309
691
1,2941
6,2731
Btu/hr
650
2,072
177
207
181
221
1,490
320
Internal Gain Btu/hr
Occupants 4 7 Occupants X 245 Btuh/occ. = 1,1
Equipment 1,570 Floor Area X 0.50 w/sgft = 2,6
Infiltration: 1.064 X 1.27 X 64.76 X 42 =
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,6411
Latent Gain Btu/hr
Occupants 4 7 Occupants X 155 Btuh/occ. _
Infiltration: 4,771 X 1.27 X 64.76 X 0.00523 = C
Air Sensible CFM ELA AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 7301
I EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-04-07711:47:24 ID: Pape 48 of 49 1
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 23B
4/7/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
2nd Floor Master Bedroom
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1, 570.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (*)
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
TI
(NVt9 0.0 X 12.3 +
17.8
X 18.1
c 322
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X. +
X
=
Page Total
322
Internal Gain
Btu/hr
Occupants
4 7 Occupants X 245
Btuh/occ.
=
1,154
Equipment
1,570 Floor Area X 0.50
w/sgft
=
2,679
Infiltration: 1.064
X 1.27 X 64.76 X 42 =
3,663
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
19,641
Latent Gain
Btu/hr
Occupants
4 7 Occupants X 155
Btuh/occ.
=
730
Infiltration: 4,771
X 1.27 X 64.76 X 0.00523 =
2,047
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
730
Ener Pro 6.7 by EnerjqySoft
User Number: 6712 RunCode: 2016-04-07711:47:24 ID:
Page 49 of 49