11-1042 (SFD) Hydraulic Calcs
SOUTHLAND FIRE PROTECTION, INC. 4733 POINT LOMA AVENUE SAN DIEGO,CA 92107 HYDRAULIC CALCULATIONS FOR Santerra at La Quinta Lot 1 57-517 Barristo Circle La Quinta, CA 92253 ^FILE NUMBER: 11-133-1 DATE: OCT 26, 2011 -DESIGN DATA - OCCUPANCY CLASSIFICATION: R3 I r CITY OF LA QUjrJTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION DA 13 2e1L Q- lC942 DENSITY: .05 gpm/sq. ft. AREA OF APPLICATION: 2-Sprinklers COVERAGE PER SPRINKLER: 256 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 26.2 gpm TOTAL WATER REQUIRED (including hose): 31.2 gpm FLOW AND PRESSURE (@ BOR): 26.2 gpm @ 25.3 psi SPRINKLER ORIFICE SIZE: 7/16 inch NAME OF CONTRACTOR: Southland Fire Protection, Inc. DESIGN/LAYOUT BY: M. Lovely AUTHORITY HAVING JURISDICTION: Riverside County Fire CONTRACTOR CERTIFICATION NUMBER: C-16 611956 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 27091255 1 HRS SYSTEMS, INC. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 10/26/2011 H:\2011\11-133-1.SDF JOB TITLE: Santerra Lot 1 - 2-Sprinkler Calc. 16x16 Max. Spacing WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) 1 90.0 20.0 1100.0 89.9 31.2 52.5 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 31.2 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 5.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.2 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 0.0 SOURCE 52.5 31.2 2 0.0 - -- - - 46.5 - - - 3 0.0 ---- 33.5- 4 2.0 HOSE STREAM 25.3 5.0 5 5.0 - - - - 23.5 - -- - 6 10.0 -- - - - 18.7 - - - 7 10.0 -- -- - - 11.8 - - - 8 10.0 - - - - 9.7 - - - 9 10.0 -- - - 8.9 - - - 10 10.0 - - - - 7.3 - - - S1 10.0 K= 4.90 7.2 13.2 S2 10.0 K= 4.90 7.0 13.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 10/26/2011 H:\2011\11-133-1.SDF JOB TITLE: Santerra Lot 1 - 2-Sprinkler Calc. 16xl6 Max. Spacing PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 31.2 0.995 PL 15.00 PF 6.1 1 0.0 SRCE 52.5 (N/A) 12.9 150 FTG ETG PE 0.0 2 0.0 0.0 46.5 0.0 0.253 TL 24.00 PV Pipe: 2 FIXED PRESSURE LOSS DEVICE 2 0.0 0.0 46.5 0.0 13.0 psi, 31.2 gpm 3 0.0 0.0 33.5 0.0 Pipe: 3 31.2 0.995 PL 25.00 PF 7.3 3 0.0 0.0 33.5 0.0 12.9 150 FTG 2E PE -0.9 4 2.0 H.S. 25.3 5.0 0.253 TL 29.00 PV- Pipe: 4 26.2 1.025 PL 3.00 PF 0.5 4 2.0 H.S. 25.3 5.0 10.2 150 FTG ---- PE -1.3 5 5.0 0.0 23.5 0.0 0.158 TL 3.00 PV Pipe: 5 26.2 1.101 PL 5.00 PF 2.6 5 5.0 0.0 23.5 0.0 8.8 150 FTG 18.0 PE -2.2 6 10.0 0.0 18.7 0.0 0.112 TL 23.00 PV Pipe: 6 26.2 1.101 PL 30.00 PF 6.9 6 10.0 0.0 18.7 0.0 8.8 150 FTG 32.0 PE 0.0 7 10.0 0.0 11.8 0.0 0.112 TL 62.00 PV Pipe: 7 11.9 1.101 PL 53.00 PF 2.1 7 10.0 0.0 11.8 0.0 4.0 150 FTG 28.0 PE 0.0 8 10.0 0.0 9.7 0.0 0.026 TL 81.00 PV Pipe: 8 11.9 1.101 PL 22.00 PF 0.8 8 10.0 0.0 9.7 0.0 4.0 150 FTG 8.0 PE 0.0 9 10.0 0.0 8.9 0.0 0.026 TL 30.00 PV Pipe: 9 14.2 1.101 PL 60.00 PF 2.9 7 10.0 0.0 11.8 0.0 4.8 150 FTG 20.0 PE 0.0 9 10.0 0.0 8.9 0.0 0.036 TL 80.00 PV Pipe: 10 26.2 1.101 PL 9.00 PF 1.6 9 10.0 0.0 8.9 0.0 8.8 150 FTG 5.0 PE 0.0 10 10.0 0.0 7.3 0.0 0.112 TL 14.00 PV Pipe: 11 13.2 1.101 PL 2.00 PF 0.1 10 10.0 0.0 7.3 0.0 4.4 150 FTG 2.0 PE 0.0 Sl 10.0 4.9 7.2 13.2 0.031 TL 4.00 PV Pipe: 12 13.0 1.101 PL 8.00 PF 0.3 10 10.0 0.0 7.3 0.0 4.4 150 FTG 2.0 PE 0.0 S2 10.0 4.9 7.0 13.0 0.031 TL 10.00 PV TM SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 10/26/2011 H:\2011\11-133-1.SDF JOB TITLE: Santerra Lot 1 - 2-Sprinkler Calc. 16x16 Max. Spacing NOTES (HASS): (1) Calculations were performed by the HASS 8.2 computer program under license no. 27091255 granted by HRS Systems, Inc. 208 South Public Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.008 gpm and a maximum imbalance at any node of 0.087 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 12.9 ft/sec at pipe 1. (4) PIPE FITTINGS TABLE Pipe Table Name: STANDARD.PIP PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E L B R C S G 45 E1 BrT RunT Cplg SwCk Gate 1.101 1.00 5.00 5.00 1.00 1.00 8.00 2.00 PAGE: K MATERIAL: CT-K HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T F R C S G N Ell Tee 45-Ell TeeRun Couplg SwgChk GatVly NPTee 0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00 PAGE: L MATERIAL: CT-L HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T F R C S G N Ell Tee 45-Ell TeeRun Couplg SwgChk GatVly NPTee 1.025 3.00 7.00 1.00 2.00 0.00 7.00 0.00 7.00 tqco Fire Suppression & Building Products Technical Services 800-381-9312 1 +1-401-781-8220 www.tyco-fire.com Series TY-FRB — 2.8, 4.2.9 5.5, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent sprinklers Quick Response, Standard Coverage General Description The TYCO Series TY-FRB, 2.8, 4.2, 5.6, and 8.0 K-factor, Upright and Pendent Sprinklers described in this data sheet are quick response, standard coverage, decorative 3 mm glass bulb -type spray sprinklers designed for use in light or ordinary hazard, commercial occupan- cies such as banks, hotels, and shop- ping malls. The recessed version of the Series TY- FRB Pendent Sprinkler, where applica- ble, is intended for use in areas with a finished ceiling. This recessed pendent sprinkler uses one of the following, • A two-piece Style 10 (1/2 inch NPT) or Style 40 (3/4 inch NPT) Recessed Escutcheon with 1/2 inch (12,7 mm) of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment from the flush pendent position, or a • A two-piece Style 20 (1/2 inch NPT) or Style 30 (3/4 inch NPT) Recessed Escutcheon with 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Corrosion -resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo- spheres. Although corrosion -resistant coated sprinklers have passed the standard corrosion tests of the appli- cable approval agencies, the testing is not representative of all possible cor- rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit- ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. An intermediate level of the Series TY- FRB Pendent Sprinklers is detailed in Technical Data Sheet TFP356, and Sprinkler Guards are detailed in Tech- nical Data Sheet TFP780. EUM The Series TY-FRB Concealed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. Owners are responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manu- facturer should be contacted with any questions. fy=f=i f Model/Sprinkler Identification Number (SIN) TY1131: Upright 2.8K, 1/2-NPT TY1231: Pendent 2.8K, 1/2" NPT TY2131: Upright 4.2K, 1/2" NPT TY2231: Pendent 4.21K, 1/2-NPT TY3131: Upright 5.6K, 1/2" NPT TY3231: Pendent 5.6K, 1/2-NPT TY4131: Upright 8.01K, 3/4-NPT TY4231: Pendent 8.0K, 3/4-NPT TY4831: Upright* 8.0K, 1/2"NPT TY4931: Pendent* 8.0K, 1/2" NPT CITY C);,_ BUILDING LX �i,FLI Y DCPT. � n r--% rya. e r r— r—% FUH UL . DA Z` I3�2z 8Y _jEj Hernlsphere Safes Only Page 1 of 10 IJ- 1D42. TFP171 TFP171 Page 2 of 10 7/16" (11,1 mm) SSU * NOMINAL DEFLECTOR MAKE -IN I 5 7/16" } 4 (11,1 mm) NOMINAL 2 MAKE -IN -71 3 2-3/16" (55,6 mm) WRENC 1 ` $ l FLATS 7 1 1/2" NPT a* 5 4 2 3 1/2" NPT ESCUTCHEON PLATE SEATING SURFACE 2-1/4" (57,2 mm) -9/16" ),7 mm) T SSP DEFLECTOR* STYLE 10 or 20 RECESSED ESCUTCHEON 2-7/8"(73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly ' Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Compression 7 - Bushing orifice seat on frame. Screw FIGURE i QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K-FACTOR, 112 INCH NPT 7/16" (11,1 mm) SSU * NOMINAL DEFLECTOR MAKE -IN _ 1 1 i 7/16" (11,1 mm) NOMINAL MAKE -IN -3/16" ,6 mm) WRENCH FLATS 1/2" NPT 1/2" NPT ESCUTCHEON PLATE SEATING SURFACE C T t 2-3/16" } (55,6 mm) 1-1/2" (38,1 mm) SSP DEFLECTOR* STYLE 10 or 20 RECESSED ESCUTCHEON 2-7/8"(73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly 'Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Compression orifice seat on frame. Screw FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K-FACTOR, 112 INCH NPT TFP171 Page 3 of 10 a* 5 4 2 3 7/16" (11,1 mm) SSU * NOMINAL DEFLECTOR MAKE -IN 7/16" f (11,1 mm) T7 NOMINAL MAKE -IN -3/16" ,6 mm) WRENCH FLATS I +. 1/2" NPT 1/2" NPT I ESCUTCHEON PLATE SEATING SURFACE 2-3/16" (55,6 mm) SSP DEFLECTOR* STYLE 10 or 20 RECESSED ESCUTCHEON 2-7/8"(73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly "Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Compress on orifice seat on frame. Screw FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K-FACTOR, 112 INCH NPT SSU * DEFLECTOR 6* 5-- 1J/2 (12, 4 NO MA 2 ,2 m (57,2 mm) 3 1 �3/4" NPT 1/2" (12,7 mm) ESCUTCHEON STYLE 30 or 40 NOMINAL 3/4„ PLATE SEATING RECESSED MAKE -IN I NPT SURFACE ESCUTCHEON 2-5/16" (58,7 mm) l 1-9/16" (39,7 mm) JJ I SSP DEFLECTOR * -- 2-7/8" (73,0 mm) DIA. —� CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly "Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Compression orifice seat on frame. Screw FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K-FACTOR, 314 INCH NPT TFP171 Page 4 of 10 7/16" (11,1 mm) SSU* NOMINAL DEFLECTOR MAKE —IN 1/2" NPT 6 �— — 5 7/16"1,1 mm) 2-1/4" 4NOMINALd (57,2 mm) T"(55,6 MAKE —IN 2 2-3/16" 1 9/16" mm) WRENCH (39,7 mm) 3 FLATS } SSP *' 1/2 NPT DEFLECTOR CROSS SECTION UPRIGHT PENDENT 1 - Frame 3 - Sealing Assembly 4 - Bulb 6 - Deflector 'Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Compression orifice seat on frame. Screw FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K-FACTOR, 112 INCH NPT Technical Data Approvals UL and C-UL Listed FM, LPCB, and NYC Approved Refer to Table A and B for complete approval information including corrosion -resistant status. Maximum Working Pressure Refer to Table C. Discharge Coefficient K=2.8 GPM/psi1/2 (40,3 LPM/bar1/2) K=4.2 GPM/psi1/2 (60,5 LPM/bars/ K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2) K=8.0 GPM/psi1/2 (115,2 LPM/barlre) Temperature Rating Refer to Table A and B. Finishes Sprinkler: Refer to Table A and B. Recessed Escutcheon: White Coated, Chrome Plated, or Brass Plated. Physical Characteristics Frame ................... Bronze Button .............. Brass/Copper Sealing Assembly ......... Beryllium Nickel w/Teflont Bulb ......................Glass Compression Screw........ Bronze Deflector........... Copper/Bronze Bushing (K=2.8) ... _ ....... Bronze t Registered Trademark of Dupont Operation The glass Bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, allowing the sprinkler to activate and water to flow. Design Criteria The TYCO Series TY-FRB Pendent and Upright Sprinklers are intended for fire protection systems designed in accordance with the standard installa- tion rules recognized by the applicable Listing or Approval agency (such as, UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM's Loss Preven- tion Data Sheets). Only the Style 10, 20, 30, or 40 Recessed Escutcheon, as applicable, is to be used for recessed pendent installations. Installation The TYCO Series TY-FRB Sprinklers must be installed in accordance with the following instructions. Do not install any bulb -type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter of the air bubble is approximately 1116 inch (1,6 mm) for the 135°F/57°C and 3132 inch (2,4 mm) for the 2860F/141°C temperature ratings. Obtain a leak -tight 112 inch NPT sprin- kler joint by applying a minimum to maximum torque of 7 to 14 ft./bs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with con- sequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Escutch- eon Plate by under- or over -tightening the sprinkler. Re -adjust the position of the sprinkler fitting to suit. The Series TY-FRB Pendent and Upright Sprinklers must be installed in accordance with the following instructions. 1. Install Pendent sprinklers in the pendent position. Install upright sprinklers in the upright position. 2. With pipe -thread sealant applied to the pipe threads, hand -tighten the sprinkler into the sprinkler fitting. 3. Tighten the sprinkler into the sprin- kler fitting using only the W-Type 6 Sprinkler Wrench (Figure 14). With reference to Figures 1 through 5, apply the W-Type 6 Sprinkler Wrench to the sprinkler wrench flats. TFP171 Page 5 of 10 SPRINKLER FINISH (See Note 5) K FACTOR TYPE TEMPERATURE BULB LIQUID COLOR NATURAL CHROME BRASS PLATED WHITE*** POLYESTER 2.8 1/2" NPT PENDENT (TY1231) and UPRIGHT (TY1131) 135°F/57°C Orange 1, 2, 3, 4 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue RECESSED PENDENT (TY1231)* Figure 6 135°F/57°C Orange 1,2,4 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green RECESSED PENDENT (TY1231)** Figure 7 135°F/57°C Orange 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 4.2 1/2" NPT PENDENT (TY2231) and UPRIGHT (TY2131) 135°F/57°C Orange 1,2 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green 286°F/141°C Blue RECESSED PENDENT (TY2231)* Figure 8 135°F/57°C Orange 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green RECESSED PENDENT (TY2231)** Figure 9 135°F/57°C Orange 155°F/68°C Red 175°F/79°C Yellow 200°F/93°C Green NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion -Resistant Sprinklers. ` Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. *** Frame and Deflector only. Listings and approvals apply to color (Special Order). N/A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS TFP171 Page 6 of 10 SPRINKLER FINISH (See Note 8) K FACTOR TYPE TEMPERATURE BULB LIQUID COLOR NATURAL BRASS I CHROME PLATED I WHITE*-* POLYESTER LEAD COATED 5.6 1/2" NPT PENDENT (TY3231) and UPRIGHT (TY3131) 135'F/57'C Orange 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 155'F/68'C Red 175*F/79'C Yellow 200'F/93'C Green 286'F/141°C Blue RECESSED PENDENT (TY3231)* Figure 10 135'F/57'C Orange 1, 2, 4, 5 N/A 155°F/68'C Red 175'F/79'C Yellow 200'F/93'C Green 286*F/141'C Blue RECESSED PENDENT (TY3231)** Figure 11 135'F/57'C Orange 1, 2, 3, 4, 5 N/A 155'F/68'C Red 175'F/79'C Yellow 200'F/93'C Green 286'F/141°C Blue 8.0 3/4" NPT PENDENT (TY4231) and UPRIGHT (TY4131) 135'F/57*C Orange 1, 2, 3, 4, 5, 6, 7 1, 2, 5 155'F/68'C Red 175'F/79'C Yellow 200'F/93'C Green 286'F/141°C Blue RECESSED PENDENT (TY4231)' Figure 12 135'F/57*C Orange 1, 2, 5 N/A 155'F/68'C Red 175'F/79'C Yellow 200'F/93'C Green 286'F/141'C Blue RECESSED PENDENT (TY4231)'* Figure 13 135'F/57'C Orange 1, 2, 3, 5 N/A 155*F/68'C Red 175'F/79*C Yellow 200'F/93'C Green 286*F/141'C Blue 1/28 NPT PENDENT (TY4931) and UPRIGHT (TY4831) 135'F/57'C Orange 1, 2, 4, 5, 6 1, 2, 5 155*F/68'C Red 175'F/79°C Yellow 200'F/93°C Green 286'F/141'C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead -Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion -Resistant Sprinklers. Where Lead -Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion -Resistant Sprinklers. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. " Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. Frame and Deflector only. Listings and approvals apply to color (Special Order). N/A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD FACTOR BRASS PLATED POLYESTER COATED PENDENT (TY1231) and 2.8 UPRIGHT (TY1131) 1/2" NPT 75 PSI (12,1 BAR) N/A RECESSED PENDENT (TY1231) PENDENT (TY2231) and 4.2 UPRIGHT (TY2131) 1/2" NPT 175 PSI (12,1 BAR) N/A RECESSED PENDENT (TY2231) PENDENT (TY3231) 175 PSI 5.6 and UPRIGHT (TY3131) PSI 1B BAR) 1/2" NPT OR 1�5 PSI(12;BAR)(12,1 RECESSED (SEE NOTE 1) PENDENT (TY3231) N/A PENDENT (TY4231) 175 PSI 8.0 and UPRIGHT (TY4131) (12,1 BAR) 3/4" NPT 175 PSI (12,1 BAR) RECESSED N/A PENDENT (TY4231) 8.0 PENDENT (TY4931) 5 PSI 1/2" NPT and UPRIGHT (TY4831) 175 PSI (12,1 BAR) (121 BAR) NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York. The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor- dance with the following instructions. 1. After installing the Style 10, 20, 30, or 40 Mounting Plate, as applica- ble, over the sprinkler threads and with pipe -thread sealant applied to the pipe threads, hand -tighten the sprinkler into the sprinkler fitting. 2. Tighten the sprinkler into the sprin- kler fitting using only the W Type 7 Recessed Sprinkler Wrench (Fig- ure 15). With reference to Figures 1 to 4, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. 3. After ceiling installation and finish- ing, slide on the Style 10, 20, 30, or 40 Closure over the Series TY-FRB Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TABLE C MAXIMUM WORKING PRESSURE Care and Maintenance The TYCO Series TY-FRB must be maintained and serviced in accordance with the following instructions. MUM Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. Exercise care to avoid damage to sprinklers before, during, and after installation. Never paint, plate, coat, or otherwise alter automatic sprinklers after they leave the factory. Replace sprinklers that: • were modified or over -heated. • were damaged by dropping, striking, wrench twisting, wrench slippage, or the like. • are leaking or exhibiting visible signs of corrosion. • were exposed to corrosive products of combustion but have not oper- ated, if you cannot easily remove combustion by-products with a cloth. • have a cracked bulb or have lost liq- uid from the bulb. Refer to the Instal- lation section in this data sheet. TFP171 Page 8 of 10 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) - � r i MOUNTING 1 SURFACE CLOSURE / SERIES 1-5/16"(33,3mm) TY-FRB 13/16" (20,6 mm) FIGURE 6 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 2.8 K-FACTOR, 112 INCH NPT 2-7/8" DIA. (73,0 mm) 3/4" 19,1 mm (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) *W/ f MOUNTING SURFACE l CLOSURE SERIES 1-1/4" (31,8 mm) TY-FRB 3/4" (19,1 mm) FIGURE 8 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 4.2 K-FACTOR, 112 INCH NPT Initial and frequent visual inspections of random samples are recommended for corrosion -resistant sprinklers to verify the integrity of the corrosion -resistant material of construction. Thereafter, annual inspections per NFPA 25 should suffice. Inspections of corrosion -resistant sprinklers are recommended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprin- kler condition and the long-term integ- rity of the corrosion -resistant material, which can be affected by the corrosive conditions present. 1 /2±1 /8" (12,7±3,2 mm) FACE OF SPRINKLER FITTING MOUNTING SURFACE 2-7/8" DIA. (73,0 mm) 1/2" (12,7 mm) 2-1/4" DIA. 1/4" (6,4 mm) (57,2 mm) MOUNTING PLATE CLOSURE SERIES TY-FRB (3,2 mm) I T 1-5/16" (33,3 mm) 1-1/16" (27,0 mm) FIGURE 7 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 112 INCH NPT 1/2±1/8" (12,7±3,2 mm) FACE OF SPRINKLER FITTING }MOUNTING SURFACE 2-7/8" DIA. (73,0 mm) 1/2" (12,7 mm) 2-1/4" DIA. 1/4" (6,4 mm) (57,2 mm) MOUNTING PLATE CLOSURE SERIES TY-FRB 1 /1 (3,2 mm) 1-1/4"(31,8 mm) 1 " (25,4 mm) FIGURE 9 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 112 INCH NPT Responsibility lies with the owner for the inspection, testing, and mainte- nance of their fire protection system and devices in compliance with this document, as well as with the appli- cable standards of the National Fire Protection Association (for example, NFPA 25), in addition to the standards of any other authorities having jurisdic- tion. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. Care must be exercised to avoid dam- age to the sprinklers -before, during, and after installation. Sprinklers dam- aged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). Initial and frequent visual inspections of random samples are recommended for corrosion -resistant sprinklers to verify the integrity of the corrosion -resistant material of construction. Thereafter, annual inspections per NFPA 25 should suffice. TFP171 Page 9 of 10 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) MOUNTING SURFACE CLOSURE SERIES 1-1/4" (31,8 mm) TY-FRB 3/4" (19,1 mm) FIGURE 10 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5.6 K-FACTOR, 112 INCH NPT 2-7/8" DIA. 5/8+1/4" (73,0 mm) 3/4" (19,1 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) (57,2 mm) FACE OF MOUNTING SPRINKLER PLATE FITTING 1/8" (3,2 mm) r MOUNTING SURFACE r CLOSURE SERIES 1-5/16" (33,3 mm) TY-FRB 13/16" (20,6 mm) FIGURE 12 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON 8.0 K-FACTOR, 314 INCH NPT Inspections of corrosion -resistant sprinklers are recommended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprin- kler condition and the long-term integ- rity of the corrosion -resistant material, which can be affected by the corrosive conditions present. 2-7/8" DIA. " 12,7 mm 1/2t1/8" (73,0 mm) 1/2( ) (12,7t3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING (3,2 mm) f ' MOUNTING SURFACE 1 CLOSURE SERIES 1-1/4" (31,8 mm) TY-FRB 1 " (25,4 mm) FIGURE 11 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 112 INCH NPT 2-7/8" DIA. 1/2t1/8" (73,0 mm) 1/2" (12,7 mm) (12,7t3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING SPRINKLER _ PLATE FITTING ' (3,2 mm) MOUNTING SURFACE f CLOSURE SERIES TY-FRB i- 1-5/16" (33,3 inln) 1-1/16" (27,0 mm) FIGURE 13 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 314 INCH NPT WRENCH RECESS (END "A" USED FOR 1/2" NPT MODELS) WRENCH RECESS (END "B" USED FOR 3/4" NPT MODELS) FIGURE 14 W-TYPE 6 SPRINKLER WRENCH WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 15 W-TYPE 7 RECESSED SPRINKLER WRENCH TFP171 Page 10 of 10 P/N 57 - XXX - X - XXX MODEL/SIN 330 2.8K UPRIGHT (1/2"NPT) TY1131 331 2.8K PENDENT (1/2"NPT) TY1231 340 4.2K UPRIGHT (1/2"NPT) TY2131 341 4.2K PENDENT (1/2"NPT) TY2231 370 5.6K UPRIGHT (1/2"NPT) TY3131 371 5.6K PENDENT (1/2"NPT) TY3231 390 8.OK UPRIGHT (3/4"NPT) TY4131 391 8.OK PENDENT (3/4"NPT) TY4231 360 8.OK UPRIGHT (1/2"NPT) TY4831" 361 8.OK PENDENT (1/2"NPT) TY4931' Limited Warranty SPRINKLER TEMPERATURE FINISH RATINGS 1 NATURAL BRASS 135 135°F (57°C) 4 I WHITE POLYESTER I I 155 I 155°F (68°C) 3 WHITE (RAL9010)- 175 175°F (79°C) 9 CHROME PLATED 200 200°F (93°C) 7 I LEAD COATED I I 286 I 286°F (141°C) Eastern Hemisphere sales only. TABLE D PART NUMBER SELECTION SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS Products manufactured by Tyco Fire Suppression & Building Products (TFSBP) are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFSBP. No warranty is given for prod- ucts or components manufactured by companies not affiliated by ownership with TFSBP or for products and com- ponents which have been subject to misuse, improper installation, corro- sion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Associa- tion, and/or the standards of any other Authorities Having Jurisdiction. Mate- rials found by TFSBP to be defective shall be either repaired or replaced, at TFSBP's sole option. TFSBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFSBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete infor- mation supplied by Buyer or Buyer's representatives. In no event shall TFSBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFSBP was informed about the possibility of such damages, and in no event shall TFSBP's liability exceed an amount equal to the sales price. The foreaoing warrantv is made in lieu of any and all other warranties, express or implied. including_ warrantee_ s of_mer- chantabilit and fi ne fgr a 1particular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: (Specify Model/SIN), Quick Response, (specify K-factor), (specify temperature rating), Series TY-FRB (specify Pendent or Upright) Sprinkler with (specify type of finish or coating), P/N (specify from Table D). Recessed Escutcheon: Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify`) finish, P/N (specify'). Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387. Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. Refer to Technical Data Sheet TFP770. Copyright © 2007-2010 Tyco Fire Suppression & Building Products. All rights reserved. tqCU Fire & Building Products Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 B1azeMaster 11 CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Description Tyco® CPVC Pipe and Fittings pro- duced by Tyco Fire & Building Prod- ucts (TFBP) are designed exclusively for use in wet pipe automatic fire sprin- kler systems. The Tyco CPVC Pipe and Fittings are produced from Blaze - Master® CPVC compound that is a specially developed thermoplastic compound composed of post chlorin- ated polyvinyl chloride (CPVC) resin and state of the art additives. Tyco CPVC Pipe and Fittings are easier to install than traditional steel pipe sys- tems, and at the same time, provide superior heat resistance and strength as compared to traditional CPVC and PVC piping materials used in the plumbing trade. Various adapters are available to connect CPVC pipe to me- tallic piping. All female pipe thread adapters have brass inserts for dura- bility. Grooved adapters connect di- rectly to grooved end valves and me- tallic pipe, with flexible grooved end couplings. rvorrcE Tyco® CPVC Pipe and Fittings pro- duced with BlazeMaster® CPVC com- pound described herein must be in- stalled and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may im- pair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Technical Data Sizes 3/4" to 3" Maximum Working Pressure 175 psi Approvals UL, FM, C-UL, NSF, LPCB, MEA, and the City of Los Angeles. (Refer to In- stallation Handbook iH-1900 dated June 2008 for exact listing/approval information.) Manufacture Source U.S.A. Material 0 rapid response M HOME FIRE SPRINKLER SYSTEM • Pipe: ASTM F442, SDR 13.5 • Fittings: ASTM F438 (Sch. 40) and ASTM F439 (Sch. 80), ASTM F1970 Color •1 0 C Orange NJ L,')ING -l�r, I A-.l'�I �ED �STRUC_T BlazeMasterV is a registered trademark of The Lubrizol Corporation Page 1 of 2 JUNE, 2008 TFP1915 Page 2 of 2 TFP1915 Installation TYCO42' CPVC Pipe and Fittings pro- duced by Tyco Fire & Building Prod- ucts (TFBP) are to be installed in accordance with Installation Hand- book IH-1900 dated June 2008. Care and Maintenance The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stalling contractor or product manufac- turer should be contacted relative to any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accord- ance with local requirements and/or national codes. NQTlCE Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that rt controls, permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action Must be notified. After placing a fire protection. system in service, notify the proper authorities and advise those responsible formani- toring proprietary andlor central sta- tion alarms. Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com- ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP's sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of prod- ucts. TFBP shall not be responsible for sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer's repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP's liability exceed an amount equal to the sales price. T r oin a r t i ale in JlQu f ex- rranties �f mer�h�tabiliiy�tl�fitness for, ar- tiQular puUwag. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory, This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. © 2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 Reliably A Residential Flat Concealed Sprinkler engineered for a minimum design density of 0.05 gpmlfta with low GPM requirements. Features 1. Very low water flow requirements. 2. 1/2" (13mm) Total adjustment. 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Bulletin 006 Rev. F Model RFC30 (SIN RA0611) Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Residential Flat Concealed Sprinklers Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) 2. NYC MEA 258-93-E UL Listingti Cate ories �,�1L1711•1ta ov ED Residential Automatic FOR ONSTRUCTIO UL Guide Number VKKW n:: At ZA1'I--�Y 'RA Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- tial Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Model RFC30, RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler de- flector. Residential distribution patterns are higher and generally contain a finer droplet size than standard sprin- kler patterns. The combination of speed of operation and high dis- charge pattern required for residential sprinklers has dem- onstrated, in fire testing, an ability for controlling residen- tial fires, and thereby providing significant evacuation time for occupants. The RFC30, RFC43 and RFC49 Sprinklers provide the best form of fire protection by combining an attractive ap- pearance and'h" (13mm) of cover adjustment for ease of installation. The small diameter cover plate is easily and positively attached and blends into the ceiling, concealing the most dependable fire protection available, an automat- ic sprinkler system. The RFC30, RFC43 and RFC49 are UL Listed Residential Sprinklers to be installed in the residential portions of any occupancy in accordance with NFPA 13, 13R, & 13D. The RFC30, RFC43 and RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assembly can be adjusted without tools to fit accurately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly.. Application and Installation The RFC30, RFC43 and RFC49, for residential Installa- tions, use a 165°F (74°C) fusible solder link in a tuning fork style sprinkler frame with a drop -down deflector. This as- sembly Is recessed into the ceiling and concealed by a flat cover plate. The cover plate is attached to the skirt, using 1350F (57°C) ordinary temperature classification solder. When the ceiling temperature rises, the solder holding the cover plate releases the cover allowing the deflector to drop into position and exposing the sprinkler inside to CD 0 0 M The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 ceiling temperature. The subsequent operation of the sol- der link opens the waterway and causes the deflector to drop into position to distribute the discharging water in a hemispherical pattern below the sprinkler deflector. Any adjustment of thread engagement between the cover plate and cup will assure that the drop -down deflector is properly located below the ceiling. The residential distri- bution pattern contains a finer droplet size than a standard sprinkler, and the pattern produces significantly higher wall wetting. After a 25/8 inch diameter hole is cut in the ceiling, the sprinkler is to be installed with the Model FC Wrench. When installing a sprinkler, the wrench is first positioned into the sprinkler/cup assembly and around the hexagonal body of the sprinkler frame. The Wrench must bottom out against the cup in order to ensure proper, safe installation. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprinkler/cup assembly, care should be taken to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART Temperature Rating OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS MUST BE INSTALLED ONLY WITH 1350F RATED COVERS. Note: A leak tight'h" NPT (R1/2) sprinkler joint can be ob- tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. Cover assemblies provide up to '/2" (13mm) of adjust- ment. Turn the cover clockwise until the flange is in con- tact with the ceiling. For the push-on/thread-off option, the cover assembly is pushed onto the cup and final adjust- ment is made by turning the cover clockwise until the skirt flange makes full contact with the ceiling. Cover removal requires turning in the counter -clockwise direction. In ceilings that have a plenum space above the sprinkler, the plenum space may have neutral or negative pressur- ization but must not be positively pressurized. Inspect all sprinklers after installation to ensure that the gap between the cover plate and ceiling and the 4 slots in the cup are all open and free from any air flow impediment. Sprinkler Cover Plate Max. Ambient Temp. 165°F/74°C 135°F/57°C 100°F/38°C Installation Data: RFC30 (SIN RA0611) Thread Sprinkler Maximum Minimum Minimum Required Size K Factor Spacing Distance to Distance between Sprinkler Discharge Flow Press. inch (mm) ft. (m) Wall sprinklers I ft. (m) ft. (m) gpm (Lpm) psi (bar) 1/2" (15mm) 3.0 12 x 12 (3.6x3.6) 6(1.83) 8(2,43) 9(34.1) 9.0 (0.62) 1/2" (15mm) 3.0 14 x 14 (4.3x4.3) 7(2.13) 8(2.43) 10 (37.8) 11 (0.76) Note: 1 bar = 100 Kpa Installation Data: RFC43 (SIN RA0612) Thread Size inch (mm) K Factor Sprinkler Spacing ft. (m) Maximum Distance to Wall Minimum Distance between sprinklers Minimum Required Sprinkler Discharge Flow Press. ft. (m) ft. (m) gpm (Lpm) psi (bar) 1/2" (15mm) 4.3 12 x 12 (3.6x3.6) 6(1.83) 8(2.43) 12 (45) 7.8 (0.54) 1/2" (15mm) 4.3 14 x 14 (4.3x4.3) 7(2.13) 8(2.43) 13 (49) 9.1 (0.63) 112" (15mm) 4.3 16 x 16 (4.9x4.9) 8(2.43) 8(2.43) 13 (49) 9.1 (0.63) 112" (15mm) 4.3 18 x 18 (5.5x5.5) 9(2.74) 8(2.43) 18 (68) 17.5 (1.21) '/2" (15mm) 4.3 20 x 20 (6.Ox6.0) 10 (3,05) 8(2.43) 21 (79) 23.8 (1.64) Note: 1 bar = 100 Kpa Installation Data: RFC49 (RA0616) Thread Sprinkler Maximum Minimum Minimum Required Size K Factor Spacing Distance to Distance between Sprinkler Discharge inch (mm) ft. (m) Wall sprinklers Flow Press. ft. (m) ft. (m) gpm (Lpm) psi (bar) 1/2" (15mm) 4.9 12 x 12 (3.6x3.6) 6(1.83) 8(2.43) 13 (49) 7.0 (0.48) 1/2" (15mm) 4.9 14 x 14 (4.3x4.3) 7(2.13) 8(2.43) 13 (49) 7.0 (0.48) 1/2" (15mm) 4.9 16 x 16 (4.9x4.9) 8(2.43) 8(2.43) 13 (49) 7.0 (0.48) '/2" (15mm) 4.9 18 x 18 (5.5x5.5) 9(2.74) 8(2.43) 17 (64.3) 12.0 (0.83) 1/2" (15mm) 4.9 20 x 20 (6.Ox6.0) 10 (3.05) 8(2.43) 20 (75.7) 16.7 (1.14) Note: 1 bar = 100 Kpa FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035. 2. Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprinklers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gen- tle vacuuming. Remove any sprinkler cover plate assem- bly which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non -operation. Model RFC30, RFC43 and RFC49 Residential Concealed Sprinkler Specification Sprinklers shall be cULus Listed low flow residential con- cealed sprinklers with drop -down deflector and adjust- able flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a 112" NPT thread. Thermal element shall consist of an approved black -painted beryllium -nickel fusible solder link with symmetric lever mechanism, maintaining a Teflon -coated Belleville spring washer and machined brass cap water seal assembly containing no plastic parts. Sprinkler K-factor shall be nominal 3.0 (44), 4.3 (62.4), and 4.91 (70) having a 6/,6", 3/8" and 7/16" orifice. Temperature rating shall be Ordinary 165°F (74°C); cover plate temperature rating to be 1350F (57C). Cover plate assembly shall I" x 112" REDUCING TEE OR ELBOW ni 21J" [58.42mm1 DIA — CUP �L CEILING F 3 " [12.70-1 MAX. COVER ADJUSTMENT CCP COVER PLATE ASSEMBLY 3P6" [84.21mm] DIA. consist of a brass cover plate and copper alloy retainer flange allowing a'/2" cover plate adjustment. Any secure engagement between the cover plate and the cup will assure that the drop -down deflector is properly located below the ceiling. A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the drop -down sprinkler deflector from dam- age, which could occur during construction before the cover plate is installed. Standard cover finish: [Chrome] [White] [Specialty — specify]. Residential concealed sprinklers shall be Reliable Model RFC30, SIN RA0611 (Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616 (Bulletin 006). Ordering Information Cover Plate Finishes M Specify: Standard Finishes 1. Sprinkler Model 2. Cover Plate Finish Chrome White3. Thread -On or Special Application Finishes Bright Brass Black Plating Black Paint Off White Satin Chrome Push -On Feature 28 [6a55mmJ HOLE IN CEILING 2" [50.8mm] MAX. FACE OF FITTING TO FACE OF CEILING DIMENSION " [4.96mmJ Wfi=FA COVER PLATE- 112" [ 12. 7mm l ADJUSTMENT (') Other colors and finishes avail- able. Consult factory for details. Note: Paint or any other coatings applied over the factory finish will void all approvals and warran- ties. 3 J 90C 3, Reliable,,,For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision -made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Flush automatic sprinklers • Recessed automatic sprinklers • Concealed automatic sprinklers • Adjustable automatic sprinklers • Dry automatic sprinklers • Intermediate level sprinklers • Open sprinklers • Spray nozzles ■ Alarm valves • Retarding chambers • Dry pipe valves • Accelerators for dry pipe valves • Mechanical sprinkler alarms • Electrical sprinkler alarm switches • Water flow detectors • Deluge valves • Detector check valves • Check valves • Electrical system • Sprinkler emergency cabinets • Sprinkler wrenches • Sprinkler escutcheons and guards • Inspectors test connections • Sight drains • Ball drips and drum drips • Control valve seals ■ Air maintenance devices • Air compressors • Pressure gauges Identification signs • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Prod uctsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. � Recycled ® (800) 431-1588 Sales Offices Paper iabilm (800) 848-6051 Sales Fax Revision lines indicate updated or new data. Rel(914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG. Printed in U.S.A 02/11 PM 9999970261