9923 (DEMO) Title 24TITLE 24 REPORT FOR:
ETHOS OFFICE ADDITION
79-791 OLYMPIA FIELDS
LA QUINTA, CA.
PROJECT DESIGNER:
STEWART WOODARD, ARCHITECT
79-791 OLYMPIA FIELDS
LA QUINTA, CA.
(760) 564-4418
REPORT PREPARED BY:
R Krown CEPE NR-96-1001
KROWN MECHANICAL DESIGN
P.O.BOX 1761
LA QUINTA, CA 92253
( 760 ) 773-2623
Job Number: 98055
Date: 6/14/1998
The COMPLY 24 computer program has been used to perform the calculations
summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the
Residential and Nonresidential Building Energy Efficiency Standards.
This program developed by Gabel Dodd/EnergySoft, llc (415) 883-5900.
Table Of Contents for Title 24 Report
-------------------------------------
Cover Page.......................................................... 1
Table
of Contents ...................................................
2
Form
ENV-1
Envelope Certificate of Compliance .......................
3
Form
ENV-2
Prescriptive Envelope Summary ............................
5
Form
LTG-1
Lighting Certificate of Compliance .......................
9
Form
LTG-2
Prescriptive Lighting Compliance Summary .................
11
Form
MECH-1
Mechanical Certificate of Compliance ....................
12
Form
MECH-2
Prescriptive Mechanical Summary .........................
15
Form
MECH-3
Mechanical Equipment Summary ............................
16
Form
MECH-4
Mechanical Ventilation ..................................
17
HVAC
System
Loads Summary ...........................................
18
L < <
,CERTIFICATE OF COMPLIANCE - Envelope (part 1 of 2) ENV-1 page 3 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Address: 79-791 OLYMPIA FIELDS
LA QUINTA, CA. ;Building Permit No
Envelope
Designer: STEWART WOODARD, ARCHITECT
Checked by / Date
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
GENERAL INFORMATION
Date of Plans: Building Conditioned Floor Area: 115 sf
Building Type: Nonresidential Climate Zone: 15
Phase of Construction: 0 New Construction 0 Addition 0 Alteration
Method of Envelope Compliance: Prescriptive - Overall Envelope
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the Building features and performance
specifications needed to comply with Title 24, Parts 1 and 6 of the Calif-
ornia Code of Regulations. This certificate applies only to building
envelope requirements.
The documentation preparer hereby certifies that the documentation is
accurate and complete.
DOCUMENTATION AUTHOR
R Krown CEPE NR-96-1001 G ��
(760) 773-2623 Signa ure ) (bate)
The Principal Envelope Designer hereby certifies that the proposed build-
ing design represented in this set of construction documents is consistent
with the other compliance forms and worksheets, with the specifications,
and with any other calculations submitted with this permit application.
The proposed building has been designed to meet the envelope requirements
contained in sections 110, 116 through 118, and 140, 142, 143 or 149 of
Title 24, Part 6, Chapter 1.
Please check one:
0 I hereby affirm that I am eligible under the provisions of Division 3
of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am a civil engineer
or architect.
0 I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section 5537.2 of the Business and
Professions Code to sign this document as the person responsible for
its preparation; and that I am a licensed contractor preparing docu-
ments -for work that I have contracted to perform.
0 I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section of the
Code to sign this document as the person responsible for its
preparation; and for the following reason: /
PRINCIPAL ENVELOPE DESIGNER
STEWART WOODARD, ARCHITECT
(760) 564-4418 (Signature) ' (Lie. # ) (Date)
ENVELOPE MANDATORY MEASURES
Indicate location on plans of
to Bloc
or Mandatory Measures:
CERTIFICATE OF COMPLIANCE - Envelope (part 2 of 2) ENV-1 page 4 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
OPAQUE SURFACES Const Note to
Assembly Name Type Location/Comments Field
----------------------- ---------------------------------------------
R-19 Wall ( W .19 .2x6 .16 ) Wood G)(JSJ1ws
� Built-up/RIGID/PLY Wood rVw r Lbt7 av or
FENESTRATION Frame
Orient Panes Type Exterior Shade OH Glazing Type
-------- ----- ---------------------------- -- -----------------------
Front ( W ) - 2 Wood None Y Double Clear Default(N )
� � t
OVERALL ENVELOPE METHOD (part 1 of 4) ENV-2 page 5 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
WINDOW AREA TEST
A. Display Perimeter
B. Gross Exterior Wall Area
C. Gross Exterior Wall Area
D. Enter Larger of A or B
E. Enter Proposed Window Area
0.0 ft X 6 ft =
136.0 sf X 0.40 =
136.0 sf X 0.10 =
0.0 sf Display Area
54.4 sf 40% Area
13.6 sf Min Std Area
54.4 sf Max Std Area
33.3 sf Proposed Area
If E is greater than D or less than C, proceed to the next calculation
for window area adjustment. If not, go to part,2 of 4.
1. If E is greater than D:
Window
D. Maximum Standard Area E. Proposed Area Adjustment Factor
------------------------ ---------------- -----------------
N/A / N/A - N/A
2. If E is less than C:
Window
C. Minimum Standard Area E. Proposed Area Adjustment Factor
------------------------ ---------------- -----------------
N/A / N/A - N/A
SKYLIGHT AREA TEST
Atrium Height
-------------
0.0 ft
If Height < 55 fit If Height >= 55 ft
Standard = 5%----------+---------- Standard = 10%
V
A. Gross Exterior Roof Area 115.0 sf X 0.05 = 5.8 sf Standard Area
B. Enter Proposed Skylight Area 0.0 sf Proposed Area
If the Proposed Skylight Area is greater than the Standard Skylight Area,
proceed to the next calculation for the skylight area adjustment. If not
got to part 2 of 4.
1. If Proposed Skylight Area > Standard Skylight Area:
Skylight
Standard Skylight Area Proposed Skylight Area Adjustment Factor
---------------------- ---------------------- -----------------
N/A / N/A - N/A
OVERALL ENVELOPE METHOD (part 2 of 4) ENV-2 page 6 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
OVERALL HEAT LOSS
PROPOSED
Adj.
STANDARD
Assembly Name
Area
HC
U-Val
UxA
Area
U-Val
-----
UxA
------
-----------------------
R-19 Wall (W.19.2x6.16)
------
34.7
----
3.2
-----
0.065
------
2.3
------
34.7
0.084
2.9
R-19 Wall (W.19.2x6.16)
68.0
3.2
0.065
4.5
68.0
0.084
5.7
Built-up/RIGID/PLY
115.0
1.5
0.046
5.3
115.0
0.057
6.6
Double Clear Default(N)
33.3
N/A
0.550
18.3
33.3
0.720
24.0
Total
30.3
Total
39.2
** OVERALL HEAT LOSS COMPLIES
PROPOSED
UA <=
STANDARD
UA **
OVERALL ENVELOPE METHOD (part 3 of 4) ENV-2 page 7 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN 'COMPLY 24 User 2366
---------------------------------------------------------------------------
OVERALL HEAT GAIN
PROPOSED STANDARD
Glazing WF Area SC H V OHF Total Area RSHG Total'
-------------- ---- ------ ---- ---- ---- ---- ------ ------ ---- -------
West 1.13 33.3 0.88 5.0 6.8 0.51 16.9 33.3 0.57 21.4
Total 16.9 Total 21.4
** OVERALL HEAT GAIN COMPLIES PROPOSED HG <= STANDARD HG **
OVERALL ENVELOPE METHOD (part 4 of 4) ENV-2 page 8 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
Window Area Adjustment Calculations
Adjusted
Gross
Door Window
Adjust
Window Wall
Wall Name Dir
Area
Area Area
Factor
------
Area Area
----------------------- ---
Front Wall W
-----
68.0
------ ------
33.3
1.0000
------ ------
33.3 34.7
Rear Wall E
68.0
0.0
1.0000
0.0 68.0
------
TOTALS
-----
136.0
------ ------
0.0 33.3
------
33.3 102.7
Skylight Area Adjustment Calculations
Gross
Roof Name Dir Area
----------------------- --- -----
Flat Roof/Ceiling H 115.0
TOTALS 115.0
Adjusted
Skylt
Adjust Skylt
Roof
Area
------
Factor Area
------ ------
Area
------
0.0
------
0.0000 0.0
------
115.0
------
0.0
0.0
115.0
CERTIFICATE OF COMPLIANCE - Lighting (part 1 of 2) LTG-1 page 9 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Address: 79-791 OLYMPIA FIELDS
LA QUINTA, CA. ;Building Permit No
Lighting
Designer: STEWART WOODARD, ARCHITECT
Checked by / Date
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
GENERAL INFORMATION
Date of Plans: Building Conditioned Floor Area: 115 sf
Building Type: Nonresidential Climate Zone: 15
Phase of Construction: 0 New Construction 0 Addition 0 Alteration
Method of Lighting Compliance: Prescriptive
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the Building features and performance
specifications needed to comply with Title 24, Parts 1 and 6 of the Calif-
ornia Code of Regulations. This certificate applies only to building
lighting requirements.
The documentation preparer hereby certifies that the documentation is
accurate and complete.
DOCUMENTATION AUTHOR
R Krown CEPE NR-96-1001 9
(760) 773-2623 ignature ( Date )
The Principal Lighting Designer hereby certifies that the proposed build-
ing design represented in this set of construction documents is consistent
with the other compliance forms and worksheets, with the specifications,
and with any other calculations submitted with this permit application.
The proposed building has been designed to meet the lighting requirements
contained in sections 110, 119, 130 through 132 and 146 or 149.
Please check one:
0 I hereby affirm that I am eligible under the provisions of Division 3
of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am a civil engineer
electrical engineer or architect.
0 I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section 5537.2 of the Business and
Professions Code to sign this document as the person responsible for
its preparation; and that I am a licensed contractor preparing docu-
ments for work that I have contracted to perform.
0 I affirm that L am eligible under the exemption to Division 3 of the
Business and Professions Code by Section of the
Code to sign this document as the person responsible for its
preparation; and for the following reason:
PRINCIPAL LIGHTING DESIGNER
STEWART WOODARD, ARCHITECT f
(760) 564-4418 n re ) ( Lic . # ) ,(D�te )
LIGHTING MANDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures:
CERTIFICATE OF COMPLIANCE - Lighting (part 2 of 2) LTG-1 page 10 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION :Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
INSTALLED LIGHTING SCHEDULE
No of Watts/ Ballast Ballasts/ No of Note to
Name Lamp Type Lamps Lamp Type Luminaire Fixt. Field
----------------- ------ ------------------------- ----- -------
Incandescent 1 60 n/a n/a 2
MANDATORY AUTOMATIC CONTROLS
Control
Control Location ID Control Type Zone Controlled
------------------------------------------------------------
CONTROLS FOR CREDIT
Control
Control Location ID
Control Type Zone Controlled
--------------- ----------------------
Note to
Field
Note to
Field
LIGHTING COMPLIANCE
SUMMARY
LTG-2
page 11 of 18
---------------------------------------------------------------------------
Project Name: ETHOS
OFFICE ADDITION
;Date:
6/14/1998
Documentation: KROWN
---------------------------------------------------------------------------
MECHANICAL DESIGN
;COMPLY
24 User 2366
ACTUAL LIGHTING POWER
No of Watts Total
Name Description Lumin Jper Default Watts
---------------------------------------------- ----- ------------ -----
60w Surface Mount Incandescent 2 60.0 120.0
SubTotal 120
Less Control Credits (LTG-3) 0
Total Proposed Watts 120
* If not CEC Default value, please provide supporting documentation.
ALLOWED LIGHTING POWER BY ZONE Allowed
Floor LPD Total Tailored
Zone Name Occupancy Area (w/sf) ( watts) (watts)
--------------------------------------------- ----- ------ ------- -------
OFFICE Office 115 1.600 184 0
----- ------ ------- -------
TOTALS 115 1.600 184 0
* Note: Tailored Allotment requires supporting documentation on form LTG-4.
tCERTIFICATE OF COMPLIANCE - Mechanical (part 1 of 3) MECH-1 page 12 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Address= 79-791 OLYMPIA FIELDS
LA QUINTA, CA. ;Building Permit No
Mechanical
Designer: STEWART WOODARD, ARCHITECT
Checked by / Date
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
GENERAL INFORMATION
Date of Plans: Building Conditioned Floor Area: 115 sf
Building Type: Nonresidential Climate Zone: 15
Phase of Construction: 0 New Construction 0 Addition 0 Alteration
Method of Mechanical Compliance: Prescriptive
Proof of Envelope Compliance: 0 Previous Permit 0 Compliance Attached
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the Building features and performance
specifications needed to comply with Title 24, Parts 1 and 6 of the Calif-
ornia Code of Regulations. This certificate applies only to building
mechanical requirements.
The documentation preparer hereby certifies that the documentation is
accurate and complete.
DOCUMENTATION AUTHOR /
R Krown CEPE NR-96-1001
(760) 773-2623 ( ignature ( Date )
The Principal Mechanical Designer hereby certifies that the proposed build-
ing design represented in this set of construction documents is consistent
with the other compliance forms and worksheets, with the specifications,
and with any other calculations submitted with this permit application.
The proposed Building has been designed to meet the mechanical requirements
contained in sections 110 through 115, 120 through 124, 140 through 142,
144 and 145.
Please check one:
C� I hereby affirm that I am eligible under the provisions of Division 3
of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am a civil engineer
mechanical engineer or architect.
0. I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section 5537.2 of the Business and
Professions Code to sign this document as the person responsible for
its preparation; and that I am a licensed contractor preparing docu-
ments for work that I have contracted to perform.
0 I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section of the
Code to sign this document as the person responsible for its
preparation; and for the following reason:
PRINCIPAL MECHANICAL DESIGNER
STEWART WOODARD, ARCHITECT Y r
(760) 654-4418 ure ) ( Lic . # ) (D to )
`CERTIFICATE OF
---------------------------------------------------------------------------
COMPLIANCE - Mechanical (part 2 of 3)
MECH-1
page 13 of 18
Project Name:
ETHOS OFFICE ADDITION
;Date:
6/14/1998
Documentation':
---------------------------------------------------------------------------
KROWN MECHANICAL DESIGN
;COMPLY
24 User 2366
SYSTEM FEATURES
Zone Name
FURN/AC-1
Time Control
�_�Alslr
Setback Control
Setback
#of Isolation Zones
n/a
HP Thermostat
n/a
Electric Heat
n/a
Fan Control
Constant Volume
VAV Min Position
n/a
Simul. Heat/Cool
n/a
Heat Supply Reset
Constant Temp
Cool Supply Reset
Constant Temp
Ventilation
L'YlU T
OA Damper Control
ev/ST
Economizer Type
No Economizer
Outdoor Air CFM
17
Heat Equip Type
Gas Furnace
Make & Model No.
Part of Exist. Furn.
Cool Equip Type
DX
Make and Model
Part of Exist. Split
Code Tables
Time Control Ventilation OA Damper
S:Prog Switch B:Air Balance A=Auto
O:Occ Sensor C:OA Cert. G:Gravity
M:Man Timer M:OA Measure
D:Demand Cont
N:Natural
Note to
Field
`CERTIFICATE OF COMPLIANCE - Mechanical (part 3 of 3) MECH-1 page-14 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
DUCT INSULATION Duct Tape Insul Note to
System Name Type Duct Location Allowed R-Val Field
----------------------- ------- ---------_-_-_ OY
---- ------------
Part of Exist. Furn. Heating Ducts in Attic / N 4.2
Cooling Ducts in .Attic / N 4.2
PIPE INSULATION Insul Note to
System Name Pipe Type Required Field
----------------------- ----------- -------- -------
Domestic Hot Water Nz)' Y / N
Part of Exist. Furn. WIA Y / N
NOTES TO FIELD - For Building Department Use Only
---------------------------------------------------------------------------
MECHANICAL SIZING AND .FAN POWER MECH-2 page 15 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
SIZING AND EQUIPMENT SELECTION
HVAC System Name:
Heating System Name:
Cooling System Name:
System Multiplier:
Peak Load Method:
Relative Humidity:
1. DESIGN CONDITIONS FOR Palm Desert
2. SIZING
ZONES SERVED BY SYSTEM PEAK
----------------------- ----
OFFICE ( Jan 12am )
TOTAL ZONE LOAD
Duct Gains & Losses:
Ventilation: ( 17 CFM)
Return Air Lighting Gain
Supply/Return Fan Gain:
TOTAL SYSTEM LOAD
3. SELECTION
A. Safety/Warmup Factor
B. Maximum Adjusted Load
C. Installed Equipment Capacity
If Line 3-C > Line 3-B, Explain:
FAN POWER CONSUMPTION
FURN/AC-1
Part of Exist. Furn.
Part of Exist. Split
1
COINCIDENT
50 %
COOLING
HEATING SENSIBLE LATENT
------- -------- ------
32 F 112 F 78 F
Btu/hr PEAK Btu/hr Btu/hr
------- ------------ ------
1151 ( Aug 5pm ) 4050- 293
--------------- ------
1151 4050 293
115 405
703 ( 17 CFM ) 566 204
0
0 0
--------------- ------
1969 5021 497
1.43
1.21
2815
6075
6000
506.2 453
No. Efficiency Peak Conv Peak Supply
Fan Description Sys BHP Motor Drive HP Fact Watts CFM
--------------------- --- ----- ----- ----- ----- ---- ----- ------
Supply Fan 1 x 0.10 / [0.49 x 1.001 = 0.20 x 746 = 152 200
----- ----- ------
Totals 0.20 152 200
FAN POWER DEMAND 152 watts / 200 cfm = 0.761 watts/cfm
MECHANICAL EQUIPMENT SUMMARY MECH-3 page 16 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
CENTRAL SYSTEM SUMMARY
Sys No
No System Name System Type Sys Economizer Type
---------------------------------------- --- ---------------------------
1 Part of Exist. Furn. Split FAU-A/C 1 No Economizer
CENTRAL SYSTEM RATINGS
Sys ------- Heating ------------------ ---------------- Cooling ------
No Type Output Aux KW EFF Type Output Sensible EER SEER
--------------------- ------ -------------------------- ----- -----
1 Gas Furnace 6000 n/a 0.78 DX 6000 5000 8.00 8.90
CENTRAL FAN SUMMARY ------------ Supply Fan ----------- ---- Return Fan ---
Sys Mtr Dry Mtr Dry
No Fan Type Motor Location CFM BHP Eff Eff CFM BHP Eff Eff
-------------------------------- ----- ------ --- --- ----- ----- --- ---
1 Constant Volume Draw -Through 200 0.10 49 100 None
ZONAL FAN SUMMARY --------- Zonal Fan ------------ Exhaust Fan -----
Mtr Dry Mtr Dry
Zone Name No CFM BHP Eff Eff No CFM BHP Eff Eff
None
t
MECHANICAL VENTILATION MECH-4 page 17 of 18
--------------------------------------- 7-----------------------------------
Project Name: ETHOS OFFICE ADDITION :Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
VENTILATION SUMMARY BY ZONE Tran
Floor sqft CFM Dsg Min sfer
Zone Name T Occupancy Area /Occ /Occ CFM CFM CFM
----------------------- -------------- ----- ---- ---- ---- ------ ----
OFFICE * Office 115 100 15.0 17 17
TOTALS 17 17
Tailored OA (T=*) requires supporting documentation on MECH-5, Tailored
Ventilation and Process Loads Worksheet
a
.. .
HVAC SYSTEM HEATING & COOLING LOAD SUMMARY page 18 of 18
---------------------------------------------------------------------------
Project Name: ETHOS OFFICE ADDITION ;Date: 6/14/1998
Documentation: KROWN MECHANICAL DESIGN ;COMPLY 24 User 2366
---------------------------------------------------------------------------
HVAC SYSTEM DESCRIPTION
HVAC System Name:
Heating System Name:
Cooling System Name:
System Multiplier:
Fan Schedule:
Peak Load Method:
Relative Humidity:
ZONES ON THIS SYSTEM PEAK
----------------------- ----
OFFICE ( Jan 12am )
TOTAL ZONE LOAD
Duct Gains & Losses:
Ventilation: ( 17 CFM)
Return Air Lighting Gain
Supply/Return Fan Gain:
TOTAL SYSTEM LOAD
SYSTEM OUTPUT AT DESIGN CONDITIONS
MAIN HEATING & COOLING SYSTEM
TOTAL SYSTEM OUTPUT
HEATING
1151
1151
115
703
0
1969
6000
6000
FURN/AC-1
Part of Exist. Furn.
Part of Exist. Split
1
CA Daytime Fans
COINCIDENT
50 %
COOLING
PEAK SENSIBLE LATENT
------------ ------
( Aug 5pm ) 4050 293
-------- ------
4050 293
405
17 CFM) 566 204
0
0
-------- ------
5021 497
5062 453
-------- ------
5062 453
NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment
which will heat or cool this zone during the design conditions indicated.
These numbers include no safety factor, and the HVAC contractor should
oversize by a reasonable margin to account for variations in weather
conditions and the pick-up capacity required to bring the zone to temper-
ature as a result of a setback thermostat. Those responsible for final
equipment selection should note that Sensible and Latent Cooling Loads are
indicated to allow for accurate comparison with manufacturer's output data.