07-2554 (CONR) Revision 1 Title 24}
pproved
OFFICE COPY
REVISION No. I
IITE.TT07.2554,
#07 255,5
77"-75.0 Avenue 50
La Q uinta C.C.
Maint. Bldg &Cart Barn
0
r - TITLE.24 REPORT
Title 24 Report for:
La Quinta Country Club Maintenan:ce,Bldg
. 77-750 Avenue 50
La Quinta, Ca. 92253� �
Project Designer:
Linthicum
20789 N. Pima Rd. Suite 250
Scottsdale, , Az. 85225
(760) 567-5351:
Report Prepared By:
Ric Krown
Desert Energy Services, LLC
P.O. Box 6251 Rev.
La Quinta, CA 92248 CITY OF LA Ql1IRITq
(760) 250-2084 BUILDING & SAFETY DEPT.
APPROVED
FOR C NSTRUCTION
DATE JrY
Job Number:
0803-3
Efocomputer
0 9 2008
Date:
2/26/2008
TheEnerprogram has been used to.perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.4 by EnergySoft Job Number. 0803-3 User Number. 2366
�f
TABLE OF CONTENTS
Cover 'Page 1
Table of Contents 2
Nonresidential Performance Title 24 Forms f 3
Form ENV-MM Envelope Mandatory Measures , _ 13
Form MECH-MM Mechanical Mandatory Measures 14
HVAC System Heating and Cooling Loads Summary 16
EnergyPro 4.4 by EnergySoft Job Number. 080" User Number. 2366
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF-1
PROJECT NAME
La Quinta Country Club Maintenance Bld
PROJECT ADDRESS
77-750 Avenue 50 La Quinta
PRINCIPAL DESIGNER - ENVELOPE
Linthicum
DOCUMENTATION AUTHOR
Desert Energy Services, LLC
TELEPHONE
(760) 567-5351
TELEPHONE
(760) 250-2084
DATE
2/26/2008
Building Permit #
Checked by/Date
Enforcement Agency Use
NERAL INFORMATION
TE OF PLANS
1/15/08
BUILDING CONDITIONED FLOOR AREA
2,118 Sq.Ft
CLIMATE ZONE
15
BUILDING TYPE
® NONRESIDENTIAL HIGH RISE RESIDENTIAL
HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION
® NEW CONSTRUCTION ADDITION
EXISTING + ADDITION/ALTERATION
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accurate d mpl
DOCUMENTATION AUTHOR
SIGNATURE
DAT 01
Ric Krown
The Principal Designer hereby certifys that the proposed building design re resented in this set of construction documents is
consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this
permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
❑ ❑ 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
❑El❑ 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
❑ 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in
full in the Nonresidential Manual.)
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
ENV-1
Required Forms
PRINCIPAL ENVELOPE DESIGNER - NAME
SIGNATURE
LIC. NO.
DATE
Linthicum
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Lighting Compliance Not In The Scope Of
Required Forms
PRINCIPAL LIGHTING DESIGNER - NAME
SIGNATURE
LIC. NO. —7DATE
MECHANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
ME -1 MECH-2 MECH-3 MECH-5
Required Fo s
PRINCIPAL MECHANICAL DESIGNER - NAME I
SIGN E
LIC. NO.
D7)-o
Polar Barr Air Conditionin
-z,-z ,
/0 A
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Page:3 of 19 1
PERFORMANCE CERTIFICATE OF COMPLIANCE Part2 of 3 PERF-
PROJECT NAME DATE
La Quinta Country Club Maintenance Bldg 2/26/2008
ANNUAL TDV ENERGY USE SUMMARY kBtu/s ft- r
Standard
Proposed
Compliance
ENERGY COMPONENT Design _
Design
Margin
pmposad
4.98
sso
` 4
Space Heating 14.78
219.57
-
53.72t
� p�..b-i�y,a.r.ar..wa�. i+tN"frrir�`.r.W��r53f' •c^ :,� z .ins" -A
Space Cooling 273.29
Indoor Fans 96.04
Heat Rejection 0.00
Pumps & Misc. 0.00
Domestic Hot Water 11.59
Lighting 62.87
i
.77-
k �!, THY" t • c, , .
ntv,.n.p 4'
76.79
19.25
0.00
0.00
0.00
0.00
12.58
-0.99
62.87
Receptacle 52.67
Process 0.00
TOTALS: 511.23
y
zi ° a M 1-v ' ; r
0 20 40 80 , 80 100 120 140 160 180200 220 240 280
•.$ �= + sgR yr. ;�,.
52.67
0.00
0.00
429.45
81.78
16.0%
( 16.0% excluding
Percent better.than Standard:
process)
Q1111 111A1f`_ f"^RA0I.I11=0
Building Orientation
Number of Stories
Number of Systems
Number of Zones
N 0 deg
Conditioned Floor Area
Unconditioned Floor Area
Conditioned Footprint Area
Fuel Type
2,118
sgft
sgR
sgft
1
1,000
4
2,118
61
1 Natural Gas
Orientation Gross Area Glazing Area Glazing Ratio
Front Elevation
(N)
595
sgfL
60
sgft
10.1%
Left Elevation
(E)
289
sgft
15
sgft.
5.2%
Rear Elevation
S
703
sgft
54
sgft.
7.7%
Right Elevation
Total
Roof
M
1 7 8s7
2,454
a,62s
sgft
sgft
sgft
421
171
E=:�
sgft.
sgft
syft,
4.80%
7.0%
0.0%
Standard Proposed
Lighting Power Density 0.948 wisgft 0.948 wisgft
Prescriptive Env. Heat Loss 1,227 awm 602 Btum
Prescriptive Env. Heat Gain 78,595 Btum-F 55,472 Btdm-F
Remarks:
Standard Building (Compliance)
a EnergyPro 4.4
ime: uzie
Number. 2366
Run Code
Jab Number. 0803-3
i
Of 19
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF-1
PROJECT NAME
La Quinta Country Club Maintenance Bldg
DATE
2/26/2008
ZONE INFORMATION
System Name
Zone Name
Occupancy Type
Floor
Area
(sgft)
Inst.
LPD
(W/sf),
Ctrl.
Credits
(W/sf)2
Allowed LPD
Proc.
Loads
(W/sf)
Area
/s 3
Tailored
/5 4
FC-1
Lounge
Lounge, Recreation
544
*1.10
Warehouse/Shop
All Others
1,000
*0.60
FC-2
Locker
Locker/Dressing Room
279
*0.80
Support
Comdor/Resbcom/Support
614
*0.60
FC-3
Office
Office
485
*1.20
Wall Unit 1
Office
Office
196
*1.20
Notes: 1. See LTG-2-C 2. See LTG-4C 3. See LTG5-C 4. See LTG-"
(items marked with asterisk, see LTG-2 -C by others) (by others)
Items above require special. documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
The local enforcement agency should pay special attention to the items specified In this checklist These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
me exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant
Authorized Signature or
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Pane:5 of 19 1
CERTIFICATE OF COMPLIANCE ENV-1-C
PROJECT NAME DATE
La Quinta Country Club Maintenance Bldg,2/26/2008
OPAQUE SURFACES
#
Surface
Type
Area
U-Fac.
Insulation
Cay. Cont.
Act.
Azm.
Tilt
Cond.
Status
Joint Appendix
IV Reference
Location / Comments
1
Roof
544
0.036
R-30
R-0.0
0
0
New
02-A9
Lounge
2
Wall
484
0.157
None
R-5.0
0
90
New
13-F5
Lounge
3
Wall
253
0.157
None
R-5.0
90
90
New
13-F5
Lounge
4
Door
21
1.450
None
R-0.0
90
90
New
28-A1
Loun e
5
Wall
0.157
None
R-5.01
270
90
New
13-F5
Loun e
6
Roof
2,790
0.036
R-30
R-0.0
0
.0
New
02-A9
Locker
7
8
Demising
Roof
36
614
0.157
0.036
None
R-30
R-5.0
R-0.0
0
0
90
0
New
New
13-F5
02-A9
Locker faces Unconditioned Space
Support
9
Wall
51
0.157
None
R-5.0
180
90
New
13-F5
Support
10
Wall
31
0.157
None
R-5.0
270
90
New
13-F5
Support
11
Door
21
1.450
None
R-0.0
270
90
New
28-A1
Support
12
Demising
16
0.157
None
R-5.01
0
90
New
13-F5
Su ort faces Unconditioned Space)
13
Roof
48
0.036
R-30
R-0.01
0
0
New
02-A9
Office
14
Wall
51
0-1571
None
R-5.0
0
'90
New
13-F5
Office
15
Wall
571
0.1.57
None
R-5.01
180
90
New
13-F5
Office
16
Door
21
1.450
None
R-0.0
180
90
New
28-A1
Office
17
Wall
18
0.157
None
R-5.0
270
90
New
Office
18
Roof
19
0.036
R-30
R-0.0
0
0
New
fl-H
Office
19
Wall
26
0.157
None
R-5.0
270
90
New
Office
20
Demising
68
• 0.157
None
R-5.0
0 1
90,
New
13-175
Office faces Unconditioned Space)
FENESTRATION SURFACES
More than or equal to 10,000 sq.fL of sfta-buih fenestration area must include a label certificate either Issued by NFRC
Standards Table 116-A and B. Certificate shall be filed In the contractors project office during construction and in the
r
a CEC Default label Certificate using the default U-factors from
#
Type
Area
U-Fac?
SHGC2
Act.
Am.
Cond.
Stat.
GlazingT e
Location/
Comments
1
Window Front N
60
0.500
NI-1
0.50
NFRC
0
New
Nonres Double Non Metal Low E
Lounge
2
Window Left E
15
0.500
NI-1
0.50
NFRC
90
New
Nonres Double Non Metal Low E
Lounge
3
Window Rear S
54
0.500
NI-1
0.50
NFRC
180
New
Nonres Double Non Metal Low E
Office
4
lWindow Right
27
0.500
NI-1
0.50
NFRC
270
New
Nonres Double Non Metal Low E
Office
5
Window Right
15
0.500
NI-1
0.50
NFRCI
270
New
I Nonres Double Non Metal Low E
Office
1 U-factor type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix NFRC Labeled value.
2 SHGC Type:.116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR
SHADING
#
Exterior Shade Type
SHGC
Window
Hgt. Wd.
Overhang
Left Fin
Right Fin
Len. H t. LExt.RExt.
Dist. Len. H t.
Dist. Len. H t.
1
None
0.76
2
None
0.76
3
None
0.76
4
None
0.76
5
None
0.76
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
r-,%- .... -w A - - m ugn jo ana coursers an encrosea space wan poor area greater than 26,ow ft2, a ceiling height greater than 16 feet, and an LPD for general
lighting of at least ti.6 WIRL See Section 149(c). V this box Is checked, ENVdC must be ffifed ouL when submittin
g under the Prescriptive Compliance Approach.
Run Initiation Time: 02/ /08 15:53:28 Run Code: 1 040 000
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Paoe:6 of 19
CERTIFICATE OF COMPLIANCE MECH-I-C
PROJECT NAME DATE La Quinta Country Club Maintenance Bldg 2/26/2008
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates, and Weratino and maintenance information meet the requirements of Section 10-1031hl and Title 24 Part B
STATEMENT OF COMPLIANCE
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Censbucon and RetrofiL
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Conshucibn and Retrofit Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do require oonshucuon inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required If the and serves 5,000112 of space or less and 25% or more of the ducts are in nonconc tinned or semicondidoned space like an
attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit
❑ MECH-rA: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA tan volume controls installed on new or existing systems must be tested
❑ MECH-B-A:-Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Bhuhr.
-Water-loop Heat Pump Controls
Applies to all new watedoop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilled, hyttronic heat pump
or condenser water systems where the pumps motors are greater than 5 hp.
Equipment requiring acceptance testing
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Page:7 of 19
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
PROJECT NAME DATE
La Quinta Country Club Maintenance Bldg 2/26/2008
YSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
AIR SYSTEMS, Central or Single Zone
FC-1
FC-2
FC-3
1
1
1
Reference on Plans or Specification 1
112(a)
7.70 HSPF
7.70 HSPF
7.70 HSPF
112 a
13.0 SEER 111.0 EER
13.0 SEER / 11.0 EER
13.0 SEER / 11.0 EER
112(b)
Yes
Yes
Yes
112(c), 115 a
n/a
n/a
n/a
121(b)
Yes
Yes
Yes
121(b)
272 cfm
134 cfm
73 cfm
121 c
No
No
No
121 c
No
No
No
121 c 122 a
Programmable Switch
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Required
Heating & Cooling Required
122
Gravitv
Gravity
Gravity
122(g)
n/a
n/a
n/a
123
124
R-4.2
R-4.2
R-4.2
144 a & b
n/a
n/a
n/a
144 a & b
28,106 btuh
34,789 btuh
19,487 btuh
144 a & b
n/a
n/a
n/a
144 a & b
29,238 btuh
42,223 btuh
26,194 btuh
144 c
Constant Volume
Constant Volume
Constant Volume
144 c
144 c
No
No
No
144 d
No
No
No
144 a
No Economizer
No Economizer
No Economizer
144
Constant Terri
Constant Temp
Constant Temp
144 (f)
Constant Temp
Constant Temp
Constant Temp
144 )
No
No
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement Is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificetons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5.000 sqf , Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF-1 for performance method duct sealing requirements.
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Pane:8 of 19 1
AIR SYSTEM REQUIREMENTS Part 1 of 2. MECH-2-C
PROJECT NAME DATE
La Quinta Country Club Maintenance Bldg2/26/2008
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat(Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
AIR SYSTEMS, Central or Sin le Zone
Wall Unit 1
1
Reference on Plans or Specification 1
112(a)
6.59 HSPF
112 a
9.2 EER
112(b)
Yes
112c,115a)
n/a
121(b)
Yes
121 b
29 cfm
121 c
No
121 c
No
121 c 122 a
Programmable Switch
122(e)
Heating & Cooling Required
122
Gravity
122 g
n/a
123
124
n/a
144 a & b
n/a
144 a & b
9,431 btuh
144 a & b
n/a
144 a & b
13,615 btuh
144 c
Constant Volume
144 c
144 c
No
144 d
No
144 a
No Economizer
144
Constant Temp
144 (f)
Constant Temp
144 k
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "WA" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF-1 for performance method duct sealing requirements.
WATER SIDE SYSTEM REQUIREMENTS Part 2 of 2 MECH-2-C
PROJECT NAME DATE
La Quinta Count Club Maintenance Bldg2/26/2008
ITEM OR SYSTEM TAG(S)
Number of Systems
MANDATORY MEASURES
Equipment Efficiency
Pipe Insulation
PRESCRIPTIVE MEASURES
Calculated Capacity
Proposed Capacity
Tower Fan Controls
Tower Flow Controls
Variable Flow System Design
Chiller and Boiler Isolation
CHW and HHW Reset Controls
WLHP Isolation Valves
VSD on CHW, CW & WLHP Pumps > 5
HP
DP Sensor Location
T-24
Section Reference on Plans or Specification'
112(a)
123
1: For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph
number where the required features are documented. If a requirement is not applicable, put "WA" in the column.
2: Water side systems include wet side system using other liquids such as glycol or brine.
ITEM OR SYSTEM TAG(S)
Number of Systems
MANDATORY MEASURES
Water Heater Certification
Water Heater Efficiency
Service Water Heating Installation
Pool and Spa Efficiency and Control
Pool and Spa Installation
Pool Heater - No Pilot Light
Spa Heater - No Pilot Light
113 (a)
113 b
113 (c)
114 a
114 b
115 (c)
115 d
DHW Heater
Service Hot Water, Pool Heating
Reference on Plans or Specification'
Standard Gas 50 gal or Less
78%
n/a
n/a
n/a
1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and
paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" ins the column.
Run Initiation Time: 02/26/08 15:53:28 Run Code: 1204070008
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Page:10 of 19
MECHANICAL VENTILATION MECM-3-C
PROJECT NAME DATE
La Quinta Country Club Maintenance Blda 9i9FignnR
PRESCRIPTIVE REHEAT
LIMITATION Section 144 d
MECHANICAL VENTILATION
Section 121 b 2
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
ZONEISYSTEM
n
D a
ca
n
m�3
°o
ts3
ao`� g
xDn
n �' 3
�c
m 3
.om
m °,
v
m.a n
om3
3
m 3
x=n
.. In z
m
v m 10
Oxt7
� D
<
c� m m
3�Cc m
D
ca
, 8e
c� m o
3cv
CD
'c
n
W
fAo
i.
o°
4, 3
3m
o�x
S
3
w
m to
-��
o3
» ?
D
m
D
Lounge
544
0.50
272
272
272
FC-1
Total
272
272
Locker
279
0.15
42
42
42
Support
614
0.15
92
92
92
FC-2
Total
134
134
Ice
481
0.15
73
73
73
FC-3
Total
73
73
Ice
196
0.15
29
29
29
Wall Unit 1
Total
29
29
C
Minimum ventilation rate per Section 121
Table 121-A
E
Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load for egress purposes fors aces without fixed seating.
H
Required Ventilation Air REO'D VA) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G).
I
Must be greater than orequal to H or use Transfer Air column N to make up the difference.
J
Design fan supply dm Fan CFM x 30%; or
K
Condition area ft sq.) x 04 chnAt sq.; or
L
Maximum of Columns H. J. K or 300 dm
M
This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal
to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M.
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Page:11 of 19
IMECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-S-C
PROJECT NAME -I
La Quinta Country Club Maintenance Bldg2/26/2008
DATE
CHILLER AND TOWER SUMMARY
Efficiency
Tons
PUMPS
�.
Equipment Name
Equipment Type
Qty.
[T�ot
GPM
BHP
Motor
Elf.
Drive
Elf.
ControlIDHW/
BOILER SUMMARY
Energy
Factor
or RE
Standby
Loss or
Pilot
TANK INSUL.
System Name
System Type
Distribution Type
Qty
Rated
Input
Vol.
(Gals.)
Condition
Status
Ext.
R-Val.
Standard Gas 50 gal or
Less
Small Gas ,
No Pipe Insulation
1
40,000
• 50
New
0.53
n/a
n/a
MULTI -FAMILY CENTRAL WATER HEATING DI
f
Hot Water Pum
Control # . HP
Hot Water Pi it
In Plenum Outsi
Add 1/2"
Buried Insulation
CENTRAL SYSTEM RATINGS f
HEATING
COOLING'
System Name
System LTe
Qtv
Outout
Aux.
kW
Eff.
Output
Efficiencv
Condition
Status
Economizer Type
i Carrier 38QRR048-3/5/6
0QAE048
Split DX
1
45,000
` 0.0
7.70 HSPF
45,00013.0
SEER / 11.0 EE
•• New
No Economizer
Carrier 38QRRRO60-3 w/
FM060
Split DX
1
55,700
0.07.70HSPFI
57,20013.0
SEER / 11.0 EER
New
No Economizer
', Carrier 38QRRRO36-3 w/
FX4C036
Split DX
1
31,200
0.0
7.70 HSPF
35,10013.0
SEER / 11.0 EER
New
No Economizer
CARRIER 51QGB3183
Room PTAC
1
15,100
0.0
6.59 HSPF
17,500
9.2 EER
New
No Economizer
r`
CENTRAL SYSTEM FAN SUMMARY
ENVELOPE MANDATORY MEASURES ENV-MM
PROJECT NAME DATE
La Quinta Country Club Maintenance Bldg2/26/2008
DESCRIPTION
Designer
Enforcement
§ 118(a) Installed Insulating Material shall have been certified by the manufacturer to
comply with the California Quality Standards for insulating material, Title 20,
Chapter 4, Article 3.
X❑ § 118(c) All Insulating Materials shall be installed in compliance with the flame spread rating
and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2.
. 0 § 117(a) All Exterior Joints and openings in the building that are observable sources of air
leakage shall be caulked, gasketed, weatherstripped or otherwise sealed.
0 § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit
and the building, and shall be weatherstripped (except for unframed glass doors
and fire doors).
§ 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not
exceeding those shown in Table Number 1-E. of the Standards. Manufactured
fenestration products must be labeled for U-value according to NFRC procedures.
§ 118(e) Demising Walls in Nonresidential Buildings:
The opaque portions of framed demising walls in nonresidential buildings shall
have insulation with an installed R-value of no less than R-13 between framing
members.
}
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Page.13 of 19
MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
PROJECT NAME DATE
La Quinta Country Club Maintenance Bldg I
2/26/2008
DESCRIPTION
Designer
Enforcement
Equipment and Systems Efficiencies
0 § 11 Any appliance for which there is a California standard established in the
Appliance Efficiency Regulations will comply with the applicable standard.
l y�
§115(a) Fan type central furnaces shall not have a pilot light.
0 §123 Piping, except that conveying fluids at temperatures between 60 and 106 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
X❑ §424 Air handling duct systems shall be installed and insulated in compliance with
Sections 601, 602, 6.03, 604, and 605 of the 2001 CIVIC Standards.
A L
Controls
§122(e) Each space conditioning system shall be installed with one of the following:
0 §122(e)1A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the
I
requirements of Section 112 (d)) shall be installed with an automatic time switch
with an accessible manual override that allows operation of the system during
off -hours for up to 4 hours. The time switch shall be capable of programming
different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's program and time setting for at
least 10 hours if power is interrupted; or
§122(e)1B An occupancy sensor to control the operating period of the system; or
§122(e)1 C A 4-hour timer that can be manually operated to control the operating period of
the system.
X §122(e)2 Each space conditioning system shall be installed with controls that temporarily
p
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint
§122(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with
isolation zones. Each zone: shall not exceed 25,000 square feet; shall be
provided with isolation devices, such as valves or dampers, that allow the supply
of heating or cooling to be setback or shut off independently of other isolation
areas; and shall be controlled by a time control device as described above.
® §122(a8b) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
�8
control shall be adjustable down to 55 degrees F or lower. For cooling, the
control shall be adjustable up to 85 degrees F or higher. Where used for both
heating and cooling, the control shall be capable of providing a deadband of at
L
least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
0 §122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and
adjustable setpoint stops accessible only to authorized personnel.
§412(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Page.14 of 19
MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM
PROJECT NAME 16���212612�008
La Quinta Country Club Maintenance Bld
Description
Designer
Enforcement
Ventilation
a921(e) Controls shall be provided to allow outside air dampers or devices to be operated
at the ventilation rates as specified on these plans.
P
g A
/
0 §122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air intakes and discharges of all space conditioning and
exhaust systems.
X] §122(f) All gravity ventilating systems shall be provided with automatic or readily
accessible manually operated dampers in all openings to the outside, except for
combustion air openings.
§121(f)1 Air Balancing: The system shall be balanced in accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
Associated Air Balance Council (AABC) National Standards (1989); or
F§121(f)2 Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the
installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3)
the person with overall responsibility for the design of the ventilation system; or
❑ §121(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
❑ §121(f)4 Another method approved by the Commission.
Service Water Heating Systems
§113(b)2 If a circulating hot water system is installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water is not required.
X❑ §113(c) . Lavatories in restrooms of public facilities shall be equipped with controls to limit
the outlet temperature to 110 degrees F.
�r
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Page:15 of 19
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE '
La Quinta Count Club Maintenance Bldg2/26/2008
SYSTEM NAME FLOOR AREA
FC-1 1 544
Number of Systems
1
Heating System
Output per System
45,000
Total Output (Btuh)
45,000
Output (Btuh/sgft)
82.7
Cooling System
Output per System
45,000
Total Output (Stuh)
45,000
Total Output (Tons)
3.8
Total Output (Btuh/sgft)
82.7
Total Output (sgftfron)
145.1
Air System
CFM per System
1,600
Airflow (cfm)
1,600
Airflow (cfm/sgft)
2.94
Airflow (cfmfTon)
426.7
Outside Air (%)
17.0
Outside Air (cfm/sgft)
0.50
Note: values above given at ARI conditions
26.0 OF
Outside Air
272 cfm
69.7 OF
12.0 / 77.9 OF
Outside Air
272 cfm
74.7 / 68.3 °F
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
Latent
CFM
Sensible
2,553
23,998
10,023
1,127
10,831
0
1,200
542
0
0
272
10,796
-754
272
12,645
1,002
-1,002
1,200
542
39,7671 9,2691
23 557
Carrier 38QRR048-3/5/6 40QAE048 29,238 14,277 28,106
Total Adjusted System Output 2s 238 1a,277 28,1os
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 3 pm Jan 12 am
62.3 OF n 78.8 OF
� t,! ----
Heating Coil
0
Supply Fan
1600 cfm
79.4 OF
Supply Air Ducts
79.0 OF
ROOMS
70.0 OF
N Retum Air Ducts `i
Temoeratures at
81.0 / 70.1 OF ill 63.9 / 63.0 OF
Cooling Coil
0
Supply Fan
1600 cfm
64.5 / 63.2 OF
Supply Air Ducts
65.2 / 63.4 OF
74.4% R.H. ROOMS
74.0 / 68.1 OF
h Retum Air Ducts `i
I EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Page:16 of 19 1
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY �
PROJECT NAME DATE
La Quinta Country Club Maintenance Bldg 2/26/2008
SYSTEM NAME FLOOR AREA
FC-2 893
Number of Systems
1
Heating System
Output per System
55,700
Total Output (Btuh)
55,700
Output (Btuh/sgft)
62.4
Cooling System
Output per System
57,200
Total Output (Btuh)
57,200
Total Output (Tons)
4.8
Total Output (Btuh/sgft)
64.1
Total Output (sqf fTon)
187.3
Air System
CFM per System
1,916
Airflow (cfm)
1,916
Airflow (cfm/sgft)
2.15
Airflow (cf nfTon)
402.0
Outside Air (%)
7.0
Outside Air (cfm/sgft)
0.15
Note: values above given at ARI conditions
26.0 of 66.6 of
Outside Air 0
134 cfrn
Supply Fan
1916 clm
69.7 of
112.0 / 77.9 of
Outside Air
134 cfm
74.6 / 63.4 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
ICOILHTG.PEAK
CFM
Sensible
Latent
�JCFMJSensible
1,382
23,100
4,186
853
13,271
0
-1,155
664
0
0
134
5,336
1,869
134
6,226
2,557
-2,557
1,155
1 664
1 34,380 6,054 18 268
Carrier 38QRRRO60-3 w/ FX4C060 42,223 8,601 34,789
Total Adjusted System Output a2,223 8,so1 34,78s
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 2 pm Jan 12 am
67.9OF itl n 84.9OF
�
Heating Coil
k Return Air Ducts `S
77.2 / 64.5 of 78.4 / 65.0 of 57.7 / 56.7 of
--�Tt
Supply Fan
1916 cfm
Cooling Coil
h Retum Air Ducts 4
Supply Air Ducts
84.6 of
ROOMS
70.0 of
Supply Air Ducts
58.3/56.9OF
55.5% R.H. ROOMS
74.0/63.2OF
I EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Page: 17 of 19 1
IHV,AC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
La Quinta Country Club Maintenance Bldg 2/26/2008
SYSTEM NAME FLOOR AREA
FC-3 485
NGINEERING CHECKS ISYSTEM LOAD
Number of Systems
1
Heating System
Output per System
31,200
Total Output (Btuh)
31,200
Output (Stuh/sgft)
64.3
Cooling System
Output per System
35,100
Total Output (Btuh)
35,100
Total Output (Tons)
2.9
Total Output (Btuh/sgft)
72.4
Total Output (sgft/Ton)
165.8
Air System
CFM per System
1,257
Airflow (cfm)
1,257
Airflow (cfm/sgft)
2.59
Airflow (cfm/Ton)
429.7
Outside Air (%)
5.8
Outside Air (cfim/sgft)
0.15
Note: values above given at AR! conditions
26.0 OF 67.1 OF
— ., --* -10—&
Outside Air
73 cfm
Supply Fan
1257 cfm
69.6 OF
SYSTEM
06.0 / 73.4 OF
to I
Outside
73 cfm
74.7/63.30F
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
CFM
11 Sensible
1,239
19,790
970
839
11,167
0
990
558
0
0
73
2,419
163
73
3,374
1,727
-1,727
990
558
26,5241 1 133 13 931
Carrier 38QRRRO36-3 w/ FX4C036 26,194 , 5,642 19,487
Total Adjusted System Output 26,194 5,sa2 19,487
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Sep 2 pm Jan 12 am
68.4 °F n 82.9°F
Heating Coil
h Return Air Ducts'4
76.5 / 63.9 OF 77.8 164.4 OF 58.3 157.2 OF
Supply Fan
1257 cfm
Cooling Coil
k Return Air Ducts 4
Supply Air Ducts
82.5 OF
ROOMS
70.0 OF
Supply Air Ducts
59.0157.4 OF
54.8% R.H. ROOMS
74.0/63.0OF
EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-3 Pane:18 of 19 1
_ .IHVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
La Quinta Count Club Maintenance Bldg2/26/2008
SYSTEM NAME FLOOR AREA
Wall Unit 1 196
Number of Systems
1
Heating System
Output per System
15,100
Total Output (Btuh)
15,100
output (Btuh/sgft)
77.0
Cooling System
Output per System
17,500
Total Output (Btuh)
17,500
Total Output (Tons)
1.5
Total Output (Btuh/sgft)
89.3
Total Output (sqf rTon)
134.4
Air System
CFM per System
300
Airflow (cfm)
300
Airflow (cfm/sgft)
1.53'
Airflow (cfm/Ton)
205 77
Outside Air (%)
9.8
Outside Air (cfm/sgft)
0.15
Note: values above given at ARI conditions
26.0 of 65.7 of
Outside Air 0
29 cfm
Supply Fan
300 cfm
70.0 of
111.0 / 77.6 of
Outside Air
29 cfm
74.0 / 53.1 of
65.7 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
CFM
Sensible
261
10,841
392
264
7,075
0
0
0
0
0
29
1,157
1,269
29
1,377
0
0
0
0
1 11,998 1,661 8 451
CARRIER 51QGB3183 13,615 0 9,431
Total Adjusted System Output 13,615 —� 9,431
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 4 pm Jan 12 am
Heating Coil
95.2 of
h Return Air Ducts 4
77.6 / 56.1 of 77.6 / 56.2 of 35.0 / 33.3 of
Supply Fan Cooling Coil
300 cfm
h Retum Air Ducts 4
Supply Air Ducts
95.2 of
ROOMS
70.0 of
Supply Air Ducts
35.0 / 33.3 of
22.0% R.H. ROOMS
74.0/53.1OF
I EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number 0803-3 Page:19 of 19
CERTIFICATE OF COMPLIANCE (Part 1 of 2)
OLTG-1-C
PROJECT NAME
LA QUINTA COUNTRY CLUB -.MAINTENANCE BUILDING
DATE
November 6, 2007
PROJECT ADDRESS
77-750 AVENUE 50, LA QUINTA, CALIFORNIA
Gheotcsd:bylDate:Erifo[cerrtent:
.............................
::::::.4..
PRINCIPAL DESIGNER-LIGHTIN(
JEFFREY C. OVERMYER
TELEPHONE
(949) 753-1553
DOCUMENTATION AUTHOR
VICTOR BECERRA
TELEPHONE
(949) 753-1553
GENERAL INFORMATION
DATE OF PLANS November 6, 2007
OUTDOOR LIGHTING ZONE( v' One) ❑ LZ1 ❑ LZ2 ❑✓ LZ3 ❑ LZ4
FUNCTION TYPE ❑✓ OUTDOOR LIGHTING ❑ OUTDOOR SIGNS ❑ INDOOR SIGNS
PHASE OF CONSTRUCTION ❑ NEW CONSTRUCTION ❑ ADDITIONS ❑ ALTERATIONS
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists outdoor lighting system specifications need t co ply with Title 24, Parts 1 and 6 of the California Code of
Regulations. This certificate applies only to building lighting requirements.
The documentation preparer hereby certifies that the documentation is accurate complete.
DOCUMENTATION DOCUMENTATION AUTHOR
IGNATUR
DATEVICTOR
BECERRACNovember
[�..
6, 2007
v
The Principal Lighting Designer hereby certifies that the proposed outdoor lightinTdsigned
esign represented in this set of construction
documents is consistent with the other compliance forms and worksheets, with thons, and with any other calculations submitted with
calculations submitted with this permit application. The proposed building has beto meet the lighting requirements contained in the
applicable parts of Sections 110, 119, 130 through 132, 146, and 149 of Title 24, Part 6.
Please ✓ One:
❑' I hereby affirm that 1 am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am licensed in the State of California as a civil engineer or electrical engineer, or I am a
licensed architect.
❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3.to sign this
document as the person responsible for its preparation; and that I am a licensed contractor performing this work.
❑ I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or
type of work described as exempt pursuant to Business and Professions Code Sections 553, 5538 and 6737.1.
(These sections of the Business and Professions Co rinted in full in the Nonresidential Manual.)
NCIPAL LIGHTING DESIGNER -NAME
PRINCIPAL
TURE
DATE
LIC. #
rC. OVERMYER
November 6, 2007
E8964
INSTRUCTIONS TO APPLICANT OUT GHTING COMPLIANCE & WORKSHEETS (✓ box if worksheet is included)
For detailed instructions on the use of this and all Energy Efficiency Standards compliance form , plea g r o e
Manual published by the California Energy Commission. l� f� ii F I A QA & r
ElOLTG-I-C
Certificate of Compliance. Required on plans for all submittals for outdoor li ht w IN '
SAFETY
Part 2 of 2 may be incorporated in schedules on the plans. A�'1& �EP1',
Either LTG-1-C or OLTG-1-C may be used for signs as follows:
FOR CONSTRUCTION
1. Use LTG-1-C if the project consists solely of indoor signs
2. Use LTG-1 -C if the project consists of indoor lighting, and outdoor or ind or signs, but no ther outdoor lighting.
3. Use OLTG-1-C if the project consists solely of outdoor signs DA BY t/C
4. Use OLTG-I-C if the project consists of outdoor lighting, and indoor or o
but no other indoor lighting.
❑ OLTG-2-C
LIGHTING COMPLIANCE SUMMARY. Applicable parts required for ALL outdoor lighting M
— �
T
(Except for signs). U
n, .
❑ OLTG-3-C
AREA CALCULATIONS WORKSHEETS. Applicable parts required for all outdoor area c' a ions.
❑ OLTG-4-C
SIGN LIGHTING COMPLIANCE. Required for all internally and externally illuminated sign MAY
for both indoor and outdoor signs.
2005 Nonresidential Compliance Forms
leGV/5iok1
CERTIFICATE OF COMPLIANCE (Part 2 of 2) OLTG -1-C
PROJECT NAME
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING
Lighting schedules on Plans Show that Outdoor Lighting Meets Allowed Lighting Power
0
❑
Lighting power allowances for general site illumination on OLTG-2-C Part 1 of 4
Not Applicable
❑
El
Lighting power allowances for local ordinances or for security multipliers on OLTG-2-C Part 2 of 4
Not Applicable
❑
0
Lighting power allowances for specific applications, other than vehicle service stations with canopies on OLTG-2-C Part 3 of 4
Not Applicable
❑
Lighting power allowances for vehicle service station canopies on OLTG-2-C Part 4 of 4
Not Applicable
❑
0
Sign lighting compliance on OLTG-4-C
Not Applicable
Mandatory Measures on Plans Show that Outdoor Lighting Meets Outdoor Lighting Controls and Equipment
Indicate location on plans of Note Block for Mandatory Measure
❑
Installed lighting power has been determined in accordance with § 130(c)1
Not Applicable
❑
All permanently installed luminaries with lamps rated over 100 watts either have a lamp efficacy of at least
60 lumens per watt or are controlled by a motion sensor § 132(a)
Not Applicable
❑
All Luminaries with lamps rated greater than 175 watts in hardscape areas, including parking lots,
building entrances, canopies, and all outdoor sales areas meet the Cutoff Requirements of § 132(b)
Not Applicable
❑
All permanently installed outdoor lighting meets the Control Requirements of § 132(c)1
Not Applicable
0
❑
Building facades, parking lots, garages, canopies, and outdoor sales areas meet the Multi -Level Lighting Requirements of § 132(c)2
Not Applicable
MANDATORY AUTOMATIC CONTROLS
CONTROL LOCATION
CONTROL
IDENTIFICATION
CONTROL TYPE
Auto Time Switch/Photosensor, etc
AREA CONTROLLED
NOTE TO
FIELD
ELECTRICAL ROOM
LCP
Timeclock/Photocell
ALL EXTERIOR LTS
2005 Nonresidential Compliance Forms
LIGHTING COMPLIANCE SUMMARY (Part 1 of 4) OLTG-2-C
PROJECT NAME
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING .
DATE
November 6, 2007
LIGHTING POWER ALLOWANCES - GENERAL SITE ILLUMINATION - (TABLE 147-A)
Allotted Watts
Luminaire
Lamps/Ballasts
Installed Watts
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O'
Lighting Applications
Category
(Table 147-A)
r D
`n °'
�^
v$
D
° n
r
-n o
- D
O
CL
W
x
n�
o
3 0
cC
o
Description
-�
nY c
3
C c
3 3
5 W
�' m o
on `
m
iv"3
_' m
�' m o
3
5 ti
�' m
✓
_
�
c n
3 3
m m
CD
o
_
z y (D.-
CL
Hardscape for pedestrian
use, including plazas,
sidewalks, walkways and
bikeways
4,085
0.17
694
B1
Vertical Burn
Full -Cutoff
Fluor.
1
42
1
48"
✓
1
4g
-
-
-
B2
Vertical Burn
Full -Cutoff
Fluor.
1
26
1
28
✓
17
476
Total Allotted Watts
694
Total Installed Watts
524
2005 Nonresidential Compliance Forms
;..
LIGHTING COMPLIANCE SUMMARY (Part 3 of 4) OLTG-2-C
PROJECT NAME
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING
DATE
November 6, 2007
Lighting Power Allowance for Specific Applications (TABLE 147-B) - Other Than Vehicle Service Station without Canopies
A
B I C D
E I F I G
H I I J K
L M I N O P
Lighting Application
Table 147-B
Allotted Watts
Luminaire Description
Lamps/Ballasts
Design Watts
r D
ti
D
No
0
? r
D
oCD
CD
Co
x �,
n in
3 0
�' o
Description
p
�
Cn.r
n
'� c
o
v
`c
3 3 3
°i
m o
°:
r m
"
m
3 d 3
Q
T) `�
c� o
3 °1
in
m
c�
✓
p_
m
0
n
rZ
�'
m
y o
p
T.
r
x
Z y
D
0
�
o c
3
00 Cn
Non -sales canopies
687
0.50
344
Al
Horizontal Burn
Full -Cutoff
Fluor.
2
26
2
56
✓
9
504
344
2005 Nonresidential Compliance Forms
line IIAMNILAA-��-
i11-11-uIvitivHI IMU AMr-A UALUULAUION WORKSHEET (Part 1 of 5) OLTG-3-C
PROJECT NAME
DATE
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING November 6, 2007
Hardscape -Method (i )
A. Hardscape for automotive vehicular use,
including parking lots,
driveways and site roads
C I D E F G
Areas (ft) to Subtract from within Illuminated Area
A
B
H
List Specific Application
(Table 147-A)
Actual Paved Area plus 5'
perimeter adjacent unpaved land.
Includes planters and landscaped
areas less than 10' wide that are
enclosed by hardscape on at
least 3 sides
Illuminated Area
(B - G)
Areas between poles
or luminaires that are
greater than 6
mounting height
distance (if applicable)
Overlapping
Areas of
Another
Application or
Luminaire
Building
Areas
Areas
Obstructed
By Sign or
Other
Structure
Sub Total of
areas to
Subtract
(C + D +
E + F)
B. Hardscape for pedestrian use, including plazas, sidewalks, walkways and bikeways
A
B
_
C I D E F G
H
List Specific Application (Table 147-A)
Actual Paved Area plus 5' of
unpaved land on either side of
path of travel. Shall include all
contiguous paved area before
including adjacent grounds.
Areas (ft) to Subtract from within Illuminated Area
Illuminated Area
(B - G)
Areas between poles
or luminaires that are
greater than 6
mounting height
distance (if applicable)
Overlapping
Areas of
Another
Application or
Luminaire
Building
Areas
Areas
Obstructed
By Sign or
Other
Structure
Sub Total of
areas to
Subtract
(C + D +
E + F)
Hardscape for pedestrian use, including plazas,
sidewalks, walkways and bikeways
4,085
-
4,085
Checklist
E] § 147(c)1 B - Each portion of all illuminated areas has been assigned only one lighting application, and the applications are consistent with the actual use of the areas.
§ 147(c)1 A - General illumination areas includes- only those illuminated areas that are in the bounds of the Application and are within a square pattern around
a luminaire that is six times the luminaire mounting height, with the luminaire in the middle of the pattern, less any areas that are within buildings,
under canopies, beyond property lines, or obstructed by signs or other structures.
2005 Nonresidential Compliance Forms
11 1 1 IMAI\I. ATrlw w�
11-1-vinli'4/► I CU AKr_A UALUULATION WORKSHEET (Part 4 of 5) OLTG-3-C
PROJECT NAME
DATE
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING November 6, 2007
Ornamental Lighting, Canopies, Vehicle Service Station Hardscape, and Outdoor Dining
A
B
C _'D E F
Areas (ft) to Subtract from within Illuminated Area
G
Illuminated Area
(B - F)
Lighting Application
(Table 147-B)
Non -sales canopies
Gross Illuminated
Area of Application
(ft2)I
687
Areas between poles or
luminaires that are greater
than 6 mounting height
distance (if Applicable)
Overlapping Areas
of Another
Application or
Luminaire
Areas Obstructed
By Sign or Other
Structure
Sub Total of
areas to Subtract
(C + D + E)
-
687
Checklist
§ 147(c)l B - Each portion of all illuminated areas has been assigned only one lighting application, and the applications are consistent with the actual use of the areas.
EJ § 147(c) 2 C - The area of ornamental lighting includes no more than the total area of the site external to buildings. Luminaires used for ornamental lighting
employ lamps rated 100 wafts or less, and are not used to determine LPD for general illumination.
§ 147(c) 2 D - Measured in plan view, the areas of illuminated canopies include the horizontal projection of the canopies.
❑ § 147(c) 2 F - The area of vehicle service station hardscape includes only illuminated hardscape areas beyond the horizontal projection of the canopy in plan view.
❑ § 147(c) 2 1 - The area of outdoor dining area includes only illuminated hardscape areas used to serve and consume food and beverages.
2005 Nonresidential Compliance Forms
CERTIFICATE OF COMPLIANCE (Part 1 of 4)
LTG-1-C
PROJECT NAME
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING
DATE
September 17, 2007
PROJECT ADDRESS
77-750 AVENUE 50, LA QUINTA, CALIFORNIA
PRINCIPAL DESIGNER -LIGHTING
JEFFREY C. OVERMYER
TELEPHONE
(949) 753-1553
BtlddidiiR4itiiit tt
DOCUMENTATION AUTHOR
METHOD OF COMPLIANCE VICTOR BECERRA
TELEPHONE
(949) 753-1553
Cti66k d:b. /De14;61ifiirc ...6Fit'
A9n�Y':U:s
GENERAL INFORMATION
DATE OF PLANS I September 17,20071 BUILDING CONDITIONED FLOOR AREA 1 2,105 SOFT.
CLIMATE ZONE 15
BUILDING TYPE
0 NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL
❑ HOTEUMOTEL GUEST
❑ CONDITIONED SPACES
0 UNCONDITIONED SPACES ❑ INDOOR / OUTDOOR SIGNS
PHASE OF CONSTRUCTION
[21 NEW ❑ ADDITION ❑ ALTERATION
METHOD OF COMPLIANCE
❑ PERFORMANCE ❑ COMPLETE BUILDING [0 AREA CATEGORY ❑ TAILORED ❑ COMMON LIGHTING
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specificati
of the California Code of Regulations. This certificate applies only to building lighting
to comply with Title 24, Parts 1 and 6
The documentation preparer hereby certifies that the docurrldntation is accur
DOCUMENTATION AUTHOR ATURE DATE
VICTOR BECERRA IGN1 September 17, 2007
The Principal Lighting Designer hereby certifies that the propose u� design r6preke
consistent with the other compliance forms and worksheets, with the specifications, and w
submitted with this permit application. The proposed building has been designed to meet
parts of Sections 110, 119, 130-132, 146, 148, & 149 of Title 24, Part 6.
The plans & specifications meet the requirements of Part 6 (Sections 10-103a).
the requirements of Part 6 (10-103a 3).
❑ The operation & maintenance information meet the requirements of Part 6 (10-103c).
Please check one: (These sections of the Business and Professions Code are printed in ft
❑� 4 I hereby affirm that I am eligible under the provisions of Division 3 of the Business an
person responsible for its preparation; and that I am licensed in the State of California
licensed architect
din ttis ae of construction documents is
any other calculations submitted with calculations
ents con-tainedd in the applicable
CI ��13 To tall tt c r c t�fleeA
Al1�VCa & SAFETY DEPT.
in the Nb�ii�si�e rPROVED
CTION
3rofessions od to sign this document as the
sDAi9Lk &�gjZan electrical engineer, orj
❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 553 . or esign tb�s
document as the person responsible for its preparation; and that I am a licensed contractor performing this work.. 2�
❑ I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or
type of work described as exempt p to Business and Pro ions Code Sections 553, 5538 and 6737.1. ��%��i.SOY
PRINCIPAL LIGHTING DESIGNER -NAME SIGN URE DATE LIC: #
JEFFREY C. OVERMYER September 17, 2007 E8964
-IGHTING MANDATORY MEASUR
✓ R1 Indicate location on ple4s of Vie Block for mandatkmeasure THIS SHEET
LIGHTING COMPLIANCE FORMS & WORKSHEETS (check box if worksheet is included)
LTG-1-C, Parts 1 of 4 and 2 of 4
Certificate of Compliance. Part 1 of 4 and 2 of 4 are required for all submittals
❑
LTG-1-C, Part 3 of 4
Certificate of Compliance. Part 3 of 4 submittal is required only if Control Credits are claimed
❑
LTG-1-C, Part 4 of 4
Certificate of Compliance. Part 4 of 4 submittal is required when lighting controls are installed
❑,r
LTG-2-C
Interior Lighting Schedule
❑
LTG-3-C
Portable Lighting Worksheet
❑
LTG4-C
Lighting Controls Credit Worksheet
❑
LTG-5-C
Interior Lighting Power Allowance ()
❑
LTG-6-C
Tailored Method Worksheet
❑
LTG-7-C
Room Cavity Ratio Worksheet
❑
LTG-8-C
Common Lighting Systems Method Worksheet IRV
❑
LTG-9-C
Line Voltage Track Lighting Worksheet
❑
OLTG4-C
Signs (See OLTG4-C Sign Worksheet in Chapter 6, Outdoor Lighting & Signs Chapter)
2005 Nonresidential Compliance Forms
LTG-1
CERTIFICATE OF COMPLIANCE (Part 2 of 4) LTG -1-C
PROJECT NAME DATE
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING
tuber 17, 2007
JINSTALLED INTERIOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES i
INSTALLED
WATTS
INSTALLED LIGHTING, CONDITIONED SPACES (From LTG-2-C)
2,559
PORTABLE LIGHTING (From LTG-3-C)
+ -
LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG-4-C)
-. 444
CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER
= 2,115
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG-2-C)
6,734
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG-4-C)
- 182
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER
= 6,552
ALLOWED INTERIOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (from LTG-5-C)
0 AREA CATEGORY METHOD (from LTG-5-C)
❑ TAILORED METHOD (from LTG-5-C) ALLOWED
WATTS
ALLOWED LIGHTING POWER 2,005
ALTERNATE COMPLIANCE
I
❑ PERFORMANCE METHOD
❑ COMMON LIGHTING SYSTEM (from LTG-8-C)
ALLOWED INTERIOR LIGHTING POWER FOR UNCONDITIONED SPACES (From LTG-5-C) 6,790 Watts
'MANDATORY LIGHTING MEASURES FOR INTERIOR LIGHTING AND DAYLIT AREAS
MANDATORY INTERIOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROLTYPE
(Auto Time Switch,
Dimming,
Photosensor, etc.)
If Control is
for
Daylighting
NOTE TO
FIELD
CONTROL LOCATION
(Room #, Area #, or
Description)
CONTROL
IDENTIFICATION
SPACE CONTROLLED
Lists the location of
controlled lights
2005 Nonresidential Compliance Forms
LTG-2
CERTIFICATE OF COMPLIANCE (Part 3 of 4) LTG-1-C
PROJECT NAME DATE
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING September 17, 2007
CONTROLS FOR CREDIT IN CONDITIONED AND UNCONDITIONED SPACES
LUMINARIES CONTROLLED
CONTROL LOCATION CONTROL CONTROL TYPE # OF NOTE TO
(Room # or Dwg #). IDENTIFICATION (Occ Sensor, Daylight, Dimming, etc) TYPE LUMINAIRES FIELD
Occupant sensor with "manual ON" or bi
level F1,F2,F3,F4, EM9.1 SEE SYMBOL LIST automatic ON combined with multi -level 51
circuitry F5,A2,A3
and switching ,
2005 _Nonresidential Compliance Forms
LTG-3
CERTIFICATE OF COMPLIANCE (Part 4 of 4) LTG -C
PROJECT NAME
DATE
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING
September 17, 2007
Designer:
e
This form is to be used by the designer and attached to the plans. Listed below. are all the acceptance tests for lighting systems. ,
The designer is required to check the boxes by all acceptance tests that apply and list all equipment that require an acceptance
test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in
parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual -that describes the test. '
Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected
by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budgeffor the
scope of work appropriately. , H
Building Departments: • ` -
System Acceptance. Before an occupancy permit is granted for a newly constructed building or space, or a new space -
conditioning system serving a building or space is operated for. normal use',' all control device`s serving the building or space shall be
certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, MECH-1-A, Forms
shall be submitted to the building department that`. r
A. Certifies plans, specifications,'installation certificates, and operating and maintenance information meets the `
requirements of §10-103(b) and Title 24 Part 6. ,.
Test Description
Test Performed By:
❑ LTG-2-A: Lighting Control Acceptance Document
• Occupancy Sensor Acceptance Document
• Manual Daylight Controls Acceptance
• .. Automatic Time Switch Control Acceptance
Equipment requiring acceptance testing
.
'
r
❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing -
INTERIOR LIGHTING SCHEDULE (Part 1 of 2)
PROJECT NAME
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING
INSTALLED LIGHTING POWER FOR CONDITIONED SPACES
LTG-2-C
DATE
September 17, 2007
Luminaire
Lamps/Ballasts
Installed Watts
A
B
C
D
E
F
G
H
I
J
Name
Type Description
r
�
m
c
3
�.3.
�
���
m CD
��
3v,
c CO M c
��'
33
�'CQ'
m o
c
3
S'v,
m
✓
Cn
n
r-
C c
3.3
:3 CT
N o
ni
r. v,
x a
A2
RECESSED DOWNLIGHT
CFL
1
32
1
36
✓
13
468
A3
RECESSED DOWNLIGHT
CFL
1
26
1
28
✓
1
28
F3
1'X4' WRAPAROUND
FLUOR
2
32
1
62
✓
4
248
F4
2'X4' PARABOLIC
FLUOR
3
32
1
93
✓
10
930
F5
2'X4' LENSED
FLUOR
2
32
1
62
✓
10
620
F6
2'X2' LENSED
FLUOR
3
17
1
53
✓
5
265
PAGE TOTAL 2,559
BUILDING TOTAL (sum of all pages) + 2,559
PORTABLE LIGHTING (from LTG-3-C) + -
CONTROL CREDIT (from LTG-4-C) - 444
ADJUSTED TOTAL WATTS = 2,115
2005 Nonresidential Compliance Forms LTG-5
INTERIOR LIGHTING SCHEDULE (Part 2 of 2) LTG-2-C.
PROJECT NAME DATE
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING September 17, 2007
INSTALLED LIGHTING POWER FOR UNCONDITIONED SPACES
Luminaire
Lamps/Ballasts
Installed Watts
A
B
C
D
E
F
G
H
I
J
Name
Type Description
0)
O
co
r- r, c
�Nv
�p CD O
r�
3cn
o v
m
c 0W) c
��� CD
). �
CD CD 0
-^
c
v
I 7y
�.
fD Cl)
00
iv m =
C n
=
C c
�c
�'•
fD p
N —
0)) �
��
G) m
X a
--
Fl
8' STRIPLIGHT
FLUOR
4
32
1
114
✓
52
5,928
F2
4' STRIPLIGHT
FLUOR
2
•32
1
62
- ✓
13
806
s
BUILDING TOTAL (sum of all pages) + r 6,734
CONTROL CREDIT (fromLTG-4-C) - 182
ADJUSTED TOTAL WATTS = 6,552
2005 Nonresidential Compliance Forms I LTG-6
LIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG-4-C
CONTROL CREDITS FOR CONDITIONED SPACES
PROJECT NAME
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING
DATE
September 17, 2007
A B C D
E I F G
H 1
J
DAYLIGHTING
ROOM #,
ZONE ID
CONDITIONED
AREAS
LIGHTING
CONTROL
DESCRIPTION
PLAN
REFERENCE
ROOM
AREA
(ft`)
WINDOW
WALL
RATIO'
GLAZING
VLT
SKYLIGHT
EFFECTIVE
APERTURE'
WATTS
CONTROL
LIGHTING
LIGHTING
ADJUSTMENT
FACTOR`
CONTROL
CREDIT
WATTS
(H X 1)
3 OFFICES
Occupant sensor with "manual
ON" or bi-level
automatic ON combined with
multi -level circuitry
and switching
EM9.1
685
930
0.20
186
LUNCH
Occupant sensor with "manual
ON" or bi-level
automatic ON combined with
multi -level circuitry
and switching
EM9.1
9985
620
0.20
124
RR/LOCKER
Occupant sensor with "manual
ON" or bi-level
automatic ON combined with
multi -level circuitry
and switching
EM9.1
640
672
0.20
134
1) From Equation 146-A.
2) From Table 146-A
PAGE TOTAL
BUILDING TOTAL
444
444
LIUN I LNG CONTROLS CREDIT WORKSHEET (Part 2 of 2) LTG-4-C
CONTROL CREDITS FOR UNCONDITIONED SPACES
PROJECT NAME
LA QUINTA COUNTRY CLUB -.MAINTENANCE BUILDING
DATE
September 17, 2007
A B C D
E F G
H I
DAYLIGHTING
ROOM #,
ZONE ID
UNCONDITIONED
AREAS
REEL
GROUND.
LIGHTING
CONTROL
DESCRIPTION
Occupant sensor with "manual
ON" or bi-level
automatic ON combined with
multi -level circuitry
and switching
PLAN
REFERENCE
EM9.1
ROOM
AREA
(ft`)
390
WINDOW
WALL
RATIO'
GLAZING
VLT
SKYLIGHT
EFFECTIVE
APERTURE'
WATTS
CONTROL
LIGHTING
372
LIGHTING
ADJUSTMENT
FACTOR`
0.20
CONTROL
CREDIT
WATTS
(H X 1)
74
MISC
STORAGE
SPACES
Occupant sensor with "manual
ON" or bi-level
automatic ON combined with
multi -level circuitry
and switching
EM9.1
580
538
0.20
108
1) From Equation 146-A
2) From Table 146-A
PAGE TOTAL
182
182
BUILDING TOTAL
Enter in LTG-2-C: Lighting Control Credit
1111 r-MIUM LIUM I INU VUVVF:R ALLOWANCE LTG-5-C
PROJECT NAME
DATE
LA QUINTA COUNTRY CLUB - MAINTENANCE BUILDING September 17, 2007
ALLOWED LIGHTING POWER (Choose One Method)
COMPLETE BUILDING METHOD - CONDITIONED SPACES
BUILDING CATEGORY From § 146 Table 146-B
WATTS PER
(ft2)
COMPLETE
BLDG. AREA
ALLOWED
WATTS
AREA.CATEGORY METHOD - CONDITIONED SPACES
B
p
AREA CATEGORY From 146 Table 146-C
Office
WATTS PER
(ftz)
1.2
AREA (fe)
ALLOWED
WATTS
685
822
Lounge/recreation
1.1
550
605
Locker/dressing room
0.8
280
224
Corridors, restrooms, stairs and support areas
0.6
590
354
2,005
2,105
TAILORED METHOD - CONDITIONED SPACES
UNCONDITIONED SPACES
A
Complete Building and Area Category Methods
CATEGORY (From § 146 Table 146-B)
Commercial and industrial storage
Auto Repair
TAILORED METHOD - UNCONDITIONED SPACES
V I MLa AKtA WATTS
TOTAL ALLOWED WATTS
(From LTG-6-C)
WATTS PER
O
AREA (ft)
ALLOWED
WATTS
0.6
3,580
2,148
1.1
4,220
4,642
7,800 6,790
TOTALS AREA WATTS
TOTAL UNCONDITIONED SPACES ALLOWED WATTS
(From LTG-5-C and LTG-6-C)
2005 Nonresidential Compliance Forms
LTG-10