Loading...
07-2766 (AMUS) Title 24TITLE 24 REPORT • Title. 24 Report for: ' La Quinta Country Club 77-750 Avenue 50 La Quinta,.,CA 92247 i Project Designer: ` }Lee & Sakahara Architects AIA 16842 Von Karman Avenue, Suite 300 Irvine, CA 92606 a , �- 949-261-1`100 , Report Prepared By:. Y Matthew Arzt FDG Consulting Engineers 17701 Cowan; Suite 230A QUINTA . Irvine, CA 92614 SAFETY DEPT. y, (949) 253 9630 OVED STRUCTION LB . AP Job Number: D 07-082 ` MAR 2 7 268 Date: IBy 3/10/2008 The EnergyPro computer program has been used to perform the calculations summarized in this Compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC - www.energysoft.com. EnergyPro 4.4 by EnergySoft Job Number: 07-082 User Number: 5670 1 - EnergyPro 4.4 t • .r c PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 - PERF-1 PROJECT NAME DATE La Quinta Count Club 3/10/2008; PROJECT ADDRESS w'-=•-`—~~ ~g `° fi•`9 77-750 Avenue_ 50. La Quinta.�.,7 PRINCIPAL DESIGNER - ENVELOPE TELEPHONE RB*ui n9 'PeaK Lee & Sakahara Architects AIA 949-261-1100 DOCUMENTATION AUTHOR TELEPHONE Checked by/Date rii ym i FDG Consulting Engineers ,(949) 253 9630 is eriforcemet nfAgencyil5e�?�, GENERAL INFORMATION DATE OF PLANS 9/27/2007 BUILDING CONDITIONED FLOOR AREA 30,907Sq.Ft. CLIMATE ZONE. 15 BUILDING TYPE ® NONRESIDENTIAL HIGH RISE RESIDENTIAL HOTEUMOTEL GUEST ROOM' PHASE OF CONSTRUCTION NEW CONSTRUCTION . ADDITION . EXISTING + ADDITION/ALTERATION STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and complete. DOCUMENTATION AUTHOR SIGNATU DATE Matthew Arzt- 3 —1 us The Principal Designer hereby certifys that the proposed building de ' presented in this set of construction documents is consistent with the other compliance forms and worksheets, with pecifications,•and with any other calculations submitted with this permit application. The proposed building as designed meets energy efficiency requirements contained in sections 110, 116,. through 118, and 140, 142, 143 or 149 of Title 24, Part 6. , ENV. LTG. MECH. 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to LeN,sign this document as the person responsible for its preparation; and that I am licensed in the State of r California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect. ❑ a o ❑ 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions,Code Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed) ' ' .contractor performing this work. - r - 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign.this document a because it pertains to a structure ortype type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) _ ` ENVELOPE COMPLIANCE ` Indicate location on plans of Note Block for Mandatory Measures - ENV-1 - Required Forms PRINCIPAL ENVELOPE DESIGNER - NAME ."'Lee & Sakahara Architects AIA SIG NATU LIC. NO. DATE LIGHTING COMPLIANCE_ ' Indicate location on plans of Note Block for Mandatory Measures Lighting Compliance Not In The Scope Of S�Q Required Forms PRINCIPAL LIGHTING DESIGNER - NAME SIGNATURE LIC. NO. DATE MECHANICAL COMPLIANCE ` Indicate location on plans of Note Block for Mandatory Measures y MECH-1 'MECH-2 MECH-3 MECH-5 ' Required Forms PRINCIPAL MECHANICAL DESIGNER -NAME SIGNATU NO. DATE FDG Consulting En ineers Inc. ILIC. ` Run Initiation Time: 02/27/08 16:41:28 Run Code: 120415� EnergyPro 4.4 by EnergySoft - User Number. 5670 Job Number. 07-082 r • d PROJECT NAME DATE " La;Quinta.Count Club 3/1:0/2008' ANNUAL TDV.ENERGY. USE SUMMARY kBfu/s ft- r Standard Proposed Compliance. °.- `ENERGY. COMPONENT Design" Design -Margin [100sarw�d . Space Heating'-' 2.21 -1.48 3.69 ..Space Cooling _ .258.12 209.00 Indoor Fans 58.70 .' "• , .10233 -43.63 IMarF �" y 3 Heat Rejection 0.00 0.00 0.00-71 Pumps & Misc. 0.00 -. '0.00. 0.00 'Dornestic Hot -Water 0.00 f 0.00 0.00 . Lighting .;:. 67.65 '." '"'. s�s5... o:oli ,Receptacle 41.58 41.58 Process o.00 o.00 . o.00 • •• . ,. .. .. - TOTALS: '428.26. 419:07 9.19 -1 19 39 .59 7999 �119 139 159 179 199-219 239. wsgn-yr- -,,Percent better than..Staridartl;=; 2.1%. ( '2:1% excluding process) :. -BUILDING COMPLIES GENERAL INFORMATION Building Orientation Number of.Stories,.: Number of,Systems Number of Zones NE •45 deg 1 30 -60 Conditioned Floor Area'--, 30s07 sgft ' UncOnditione' d Floor Area 622 sgft Conditioned:Footprint Area 18,192 sgft Fuel Type_ Naturai Gas r s Orientation Gross Area Glazing Area Glazing Ratio, Front Elevation. , •„ • ,.. (NE) '• ' : 2,494 sgft. •;554 sgft. _22.2% a. Left 'ElevatiOn (SE 3,512 sqft. 415 sgft: 11.8% Rear Elevation SW 2,567 syft. 288 syn: 11.2% Elevation Total 4,618 13,191 sgft,- sgft., 2,553 snRight . sgft.,, 28.10/( 19.4% Roof F :. 14,006 sgft:,; ' . 230 sgft. 1.6% • standard Proposed-. a ' ..Lighting Power -Density 0.980 Wisgft. 0.947 W'/sgft. ' Prescriptive* Env,: HeatLoss 4,080Btu/n 2,846 Btum Prescriptive Env. Heat•Gain 406,039 Btuin-F 365,240 Btu/hJF n Remarks:. Run Initiation Time: 02/27/08 16:41:28 Run Code: 1204169288 '.. EnergyPro 4.4' by EnergySoft ': User.Number. 5670, ','.Job Number.' 01-682 Page;4 a PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 Of 3 PERF-1 PROJECT NAME DATE La Quinta Country Club 3/10/2008 LVrvt INrvKIVIA 1 lur . System Name Zone Name Occupancy Type Floor Area (sgfL) Inst. LPD (W/sf)1 HP-1 Priv Dining Entry 233 Lobby, Main Entry 141 *1.50 Hallway 234 Corridor/Restroom/Support 456 *0.60 Private Dining 235 Dining 1,125 *1.10 ' HP-2 _ Office Office 91 *1.20 Hall239 Corridor/Restroom/Support 173 *0.60 Storage Corridor/Restroom/Su ort 458 *0.60 Kitchen Kitchen, Food Preparation 1,642 *1.60 HP-3 4 Storage Corridor/Restroom/Su rt 216 *0.60 Mixed Grille 225 Dining • 1,724 *1.10 ' Hall 227 Cortidor/ResUoom/Su ort 346 *0.60 HP-6 Bar 204 Bar, Cocktail Lounge, Casino 274 *1.10 Storage 206 Corridor/Restroom/Support 36 *0.60 Lounge 202 Lounge, Recreation 1,154 *1.10 HP-5,7 Lobby 201 Lobby, Main Entry 1,286 *1.50 Hallway Corridor/RestroonVSupport 1,178 *0.60 HP-8 Boardroom 207 Convention/Conference/Meeting 616 *1.40 1. HP-9 General Manager Office 631 *1.20 HP-10 Workroom 215 _ Office �162 *1.20 Storage 214 Corridor/Restroom/Su ort 63 *0.60 Hall216 Corridor/Restroom/Su ort 326 *0.60 Notes: 1. See LTG-2-C 2. See LTG-4-C 3. See LTG-5-C 4. See LTG-6-C (items marked with asterisk, see LTG-2 -C by others) (by others) rCtrl. Allowed LPD' _ ; Proc. Area Tailored .Credits` 'Loads . (Wlsf)2,: 1 1s 3 -�4 (W/Sf)i ,e �' �4 ;iF ��_u, yf�' 3. ! tie ,�;e•. � "aril Gu€'4 x t: - u; Items above require special documentation . EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The HVAC System "CARRIER 25HBR360-60" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. The HVAC System "CARRIER 25HBR336-60" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. The.HVAC System "Carrier 50HJQ012" includes Demand Control Ventilation per Standards Section 121. The HVAC System "Carrier 50HJQ007" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJQ005" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier.50HJQ005" is design ated as 3 Phase or is Exempted from the NAECA 13 SEER re. uirement. The HVAC System "Carrier 50HJ0005" includes Demand Control Ventilation per Standards Section 121. The HVAC System "Carrier 50HJQ004" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. , The HVAC System "Carrier 50HJQ004" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. 1 no exceptional features Iistea in this perrormance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant. Authorized Signature or Stamp Run Initiation Time: 02/27/08 16:41:28 Run Code: 1204159288 EnergyPro 4.4 by EnergySoft . User Number. 5670 Job Number. 07-082 Page:5 of 30 a PERFORMANCE CERTIFICATE OF COMPLIANCE Part3 of 3 PERF-1 PROJECT NAME_ DATE La Quinta Country Club 3/10/2008 ZONE INFORMATION System Name Zone Name Occupancy Type Floor Area (sgft) Inst. LPD ' (W/sf)1 HP-11 Secretary Waiting 220 Waiting Area 158 *1.10 F&B Manager 218 Office 461 *1.20 FC-1 Maintenance Office 120 *1.20 Storage Corridor/Restroom/Support 57 *0.60 ' Locker Room Locker/Dressing Room 137 *0.80 Corridor/Restroom Corridor/Restroom/Su ort 622 *0.60 FC-2 Corridor Corridor/Restroom/Su ort 318 *0.60 Storage Conidor/Restroom/Su ort 433 *0.60 • . Employee Lounge Lounge, Recreation 342 *1.10 FC-3 Corridor 176/3 Corridor/Restroom/Su ort 221 •*0.60 Snack Bar Storage 167 Corridor/Restroom/Sup ort 122 *0.60 Cook and Dish Up Kitchen, Food Preparation 301 *1.60 Snack Bar 165 Dining 348 *1.10 FC-4, 5 Bar.152 Bar, Cocktail Lounge, Casino 151 *1.10 • Men's Card Room Lounge, Recreation _ 1,364 *1.10 FC-6, 7 Restroom Corridor/Restroom/Support 1,573 0.00 1 Corridor 157/6,7 Corridor/Restroom/Su ort 616 *0.60 Attendant Corridor/Restroom/Su ort 283 *0.60 Laundry Laundry - 108 *0.90 .L Men's Locker Room Locker/Dressing Room 1 1,447 *0.80 Notes: 1. See LTG-2-C 2. See LTG-4-C 3. See LTG-5-C 4. See LTG-6-C (items marked with asterisk, see LTG-2 -C by others) (by others) ; Ctrl . Allowed LPD=' Proc: d, Credits'' -Area:- Tailored Loads (YVIsfJ?f /s 3 : Is 4 (W/sf) L.� iS•�..M-. S. f. �>w. 7'. is .$}.'.,k�' ,,4�r;;; ems.• -a:. �.,��. V rs!r r1`,h• .'fir ,=`/ .�'. � §`x'° {Y x ak;'e 1, t Items above requireapecial documentation x,r A ..; - EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of i no exceptional features usteu in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant , Authorized Signature or Stamp Run Initiation Time: 02/27/08 16:41:28 Run Code: 1204159288 EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:6 of 30 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF-1 T NAME La Quinta Country Club NFORMATION System Name Zone Name Occupancy Type Floor Area (sgft.) Inst. LPD (W/sf) FC-8, 9 Pro Office 134 Office 116 *1.201 Pro Shop Storage 135 Corridor/Restroom/Support 143 *0.601 ~ Pro Shop 133 Retail Sales, Wholesale 1,090 *1.701 FC-10 Dressing Locker/Dressing Room 26 . *0.801 + Barber Shop Barber and Beauty Shop 272 *1.001 - Restroom Corridor/Restroom/Su ort 342 ' *0.601 FC-11, 12, 13, 14- Storage 105 Corridor/Restroom/Su ort 132 *0.601 Fitness Center Exercise Gymnasium 2,714 *1.001 FC-15 Elevator Lobby Corridor/Restroom/Su ort 199 *0.601 Gallery/Trophy Case Corridor/Restroom/Su ort 361 *0.601 Concourse Corridor/Restroom/Sup ort 551 *0.601 FC-16 Pedicure/Manicure 129 Barber and Beauty Shop 290 *1.001 Hallway 131 Corridor/Restroom/Support - 133 0.001 FC-17, 18 r Ladies Card Room 115 Lounge, Recreation 1,288 *1.101 Office Office 132 *1.201 } FC-19 Ladies Locker Room Locker/Dressing Room 717 *0.801 Hall Corridor/Restroom/Su ort 1,091 *0.601 Attendant 114 Corridor/Restroom/Su ort 286 • *0.601 Storage Corridor/Restroom/Su• rt 263 *0.601 Laundry 112 Laundry .103 *0.901 DATE 3/10/2006 Ctrl -,'; ,Credits, '; Mi/sf)? ` Allowed Area"' f /s 3 LBD, -' Tailored ' /s 4 4Pr6c•,I ,Loads- .• .(IN/sf). , Fom t �t � , 1 Y ' rt Y4 , t Items above require special documentation` ItMotl' 1 IUNAL R:UNUI 1 IUNS WIIRVLIANGt_ t,;MtGKLl51 I The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation ' submitted. . iptional features listed in this performance approach application have specifically been reviewed. Adequate written justification station for their use have been provided by the applicant., Authorized Signature or Stamp Run nitiation'Time: 02/27/08 16.41:28 Run Code: 1204159288 EnergyPro 4.4 by EnergySoft User Number. 5670 , Job Number. 07-082 Page:7 of 30 CERTIFICATE OF COMPLIANCE ENV-1-C La Quinta Country Club = 3/10/2008 OPAQUE SURFACES # Surface T Area U-Fac. Insulation Cay. Cont. Act. Am. A. Tilt` Cond' Status Joint Appendix IV Reference Location / Comments 1 Roof 14 0.032 R-30 •R-0.0 '0 0 New 01-A17 Priv Dining Ent 233 2 Wall 7 '0.074 R-19 R-0.0 180• 90 New 09=A5 Priv Dining Entry 233 3 . Wall 9 0.074 R-19 R-0.0 90 90 New 09-A5 ' Priv Dining Entry 233 4 Roof 456,0.032 R-30 R-0.0 - 0 0 New 01-A17 Hallway 234 5 Wall 2 0.074 R-19 ' R-0.0 270 90' New. 09-A5 Hallway 234 . 6' Roof 1,12$ 0.032 R-30 R-0.0 ' 0 0 ' New 01-A17 Private Dining 235 7 ; Wall 261 0.074 R-19 R-0.0 90 90 New 09-A5 Private Dining 235 8 Wall. 7C 0.074 •R-19 R-0.0 270 90 ` New ` 09-A5 Private Dining 235 9 Wall 367 ' 0.074 R-19 R-0.0 180 90 New 09-A5 Private Dining 235 10 IRoof 9 0.032 R-30 . R-0.0 0 0 New 01-A17 Office c 11 Roof 173 0.032 R-30 R-0.0 0 0 New 01 -Al 7 Hall239 12 Wall 70 0.074 R-19 R-0.0.270 90 New 09-A5 Hall239 13 Wall 135 0.074 R-19 R-0.0 '180 90 New 09-A5 Hall239 14 Roof 120 0.032 - R-30 R-0.0 0 ' -0 'New 01-A17 Storage 15 Roof 77 0.032 •' R-30 R-0.0 0 0 New 01-A17 Storage ' 16 Roof 56 0.032 R-30 R-0.0 0 0 New 01-A17 Storage 17 Wall' ' 75 0.074 R-19 R-0.0 270 90 New' 09-A5 - Storage 18 Roof 5 0.032 R-30 R-0.0 ' 0 0 New 01-A17 Storage 19 Wall ` 6 0.074 R-19 R-0.0 270 90 New 09-A5 Stora e - 20 Roof ' 15 0.032 R-30 R-0.0 0 0 New 01-A17 Stora a •' rv, t, A, K trvew, r�asung, Auerea, Kemoveo) FENESTRATION SURFACES ' More than or equal to 10,000 sq.R of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default LI-factors from . Standards Table 116-A and B. Certificate shall be filed In the contractor's project office during construction and in the building manager's office after construction # T e Area U-Fac' SHGC2 Act. Am. Cond. Stat. Glazin T e Location/ Comments .1 ' Indow -'Left S 20 0.580 116-A 0.53 116-B 180 New Double Non Metal Tinted Priv Dining Ent 233' '2� Window Front (E) 52 0.580 .116-A 0.53 116-B 90 New Double Non Metal Tinted Priv Dining Ent 233 3- Window Rear '52 0.580 116-A 0.53 116-B 270 New Double Non Metal Tinted Hallway 234 . 4 Window. Left S • 52 0.580 116-A 0.53 116-B 180 New Double Non Metal Tinted Private Dining235 - 5 Window Left S 32 0.580 11frA 0.53 116-B 180 New Double Non Metal Tinted Private Dining235 6 Window Left (S) 32 0.580 "116-A 0.53 116-B 180 New Double Non Metal Tinted Private Dining 235 7, Window Left (S 52 0.580 .116-A 0.53 116-B 180 New Double Non Metal Tinted Private Dining 235" 8 Window Rear 48 0.580 116-A 0.53 116-B 270 New Double Non Metal Tinted Mixed Grille 225 9 Window Rear 60 0.580 116-A 0.53 116-B 270 New Double Non Metal Tinted Mixed Grille 225 10 Window Rear (W) 48 0.580 116-A 0.53 116-B 270 New Double Non Metal Tinted Mixed Grille 225 11 Window Right (N 1 48 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Mixed Grille 225 12 Window Right N 60 0.580 116 A 0.53 116 B - 0 .. New Double Non Metal Tinted * Mixed Grille 225 13 Window Right (N 60 0.580 116 A 0.53 116 B 0 New Double Non Metal Tinted Mixed Grille 225 (1) U-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. 2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value' I EXTERIOR SHADING R # Exterior Shade Type SHGC Window Hgt. Wd. • Overhang Left Fin ° Right Fin Len. H t. LExt.RExt.:- Dist. Len. H t. Dist. Len.•H t: 1 • None 0.76 + 2 None 0.76 3 . None. 0.76 4 . None 0.76 <: .5 None 0.76 6 - None 0.76 7 None 0.76 ' 8 None 0.76 + 9 None 0.76 10 None 0.76 11, None 0.76 12 None 0.76 13 None 0.76 - MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES - • 4• f The proposed building Is In climate zones 2 through 15 and contains an enclosed space with Floor area greater than 26,000 112, a ceiling height greater than 15 feet, and an LPD for general lighting of at least 0.5 W)ft2. See Section 143(c). If this box Is checked, ENV-4-C must be filled out when submitting under the Prescriptive Compliance Approach. ' Run Initiation' Time: 02/27/08 16:41:28- Run Code: 1204159288 EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:8 of 30 s CERTIFICATE OF COMPLIANCE ENV-1=C PROJECT NAME ' ' DATE 'La Quinta Country Club • . 3/10/2008 OPAQUE SURFACES s- # Surface Type Area U-Fac. Insulation Cay. Cont. Act. Am. Tilt Cond' Status Joint Appendix 'IV Reference R , Location / Comments 21 Roof 327 0.032 R-30 R-0.0 0 0 New 01-A17 Kitchen r 22 Wall - .1320 0.074 . R-19 R-0.0 270 -90 New 09-A5 Kitchen 23 Roof 1.31 0.032 R-30 R-0.0 " 0 0 New 01-A17 Kitchen 24 Roof 151 0.032 R-30 R-0.0 0 0 New 01-A17 +. Storage 25 Roof 6 0.032 R-30 R-0.0 0 0 New 01-A17 .• Storage 26 Roof 1,724 0.032 R-30 R-0.0 .0 0 New 01-A17 Mixed Grille 225 27, Wall - 180 0.074 R-19 R-0.0 270 90 New 09-A5 Mixed Grille 225 28 Wall 38 0.074 . R-19 ' R-0.0 0 90 New 09-A5 Mixed Grille 225 29 Roof. 3 0.032 R-30 ' R-0.0 0 0 New 01-A17 Hall 227 30 Roof 31 0.032 R-30 R-0.0 0 0 New 01-A17 Hall 227 31 lWall 9 0.074 R-19 R-0.0 .0 90 New 09-A5 Hall 227 32 Door - 2 0.500 None R-0.0 0 90 New 28-A4 Hall 227 + 33 Roof 5f 0.032 R-30 R-0.0 0 0 New 01-A17 - Bar 204 34 Wall 7 0.074 R-19 R-0.0 '0 90 ' New 09-A5 • ".. Bar 204 35 Roof _ 210 0.032 R-30 R-0.0 40 0- - New 01-A171 Bar 204 36 Wall 44 0.074 R-19 R-0.0 90 • 90 New 09-A5 Bar 204 t... 37. Roof 3 0.032 'R-30 R-0.0 . 0 0 New 01=A17 Storage 206 38 Roof 1,1 0.032 R-30 -R-0.01 0 0 New 01-A17 Lounge 202 39 lWall '211 0.074 RA9 R-0.0 ' 0 90 New 09-A5 Lounge 202 40 lRoof ' 1,09Q 0.032 R-30 R-0.01 10 1 0 1 New 01-A17 Lobbv 201 N, E, A. R (New, Existing, Altered, Removed) f FENESTRATION SURFACES More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default LI-factors from i Standards Table 116-A and B. Certificate shall be filed In the contractor's project office during construction and in the building managers office after construction 4 (1) LI-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. , 2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value # Type Area U-Fac' Act. Am. A. Cond. .Stat. Glazing Type Location/ Comments 14 Window . Right N 481 0.580 116-A 0.53 116-B 01 New Double Non Metal Tinted Mixed Grille 225 15 Window Right (N) 23 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Bar 204 16 Window Right (N) 52.0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Lounge 202 f 17 Window Right N 92 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Lounge 202 18 Window Right N 52 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Lounge 202 19 Skylight Right N 196 0.390 NFRC 0.37 NFRC 0 New Milgard Classic Low-E Vinyl Lobby 201 < 20 Window Right (N) 7 0.580 116-A 0.53 116-BI 0 New Double Non Metal Tinted 'Lobby 201 21 Window Right N 7 0.580 116-A 0.53 116-BI 0 New Double Non Metal Tinted Lobby 201 22 Window. Right N 7 0.580 116-A 0.53 116-B 0 New: Double Non Metal Tinted Lobby 201 23 Window Left (S) 7 0.580 116-A 0.53 116-B 180 New Double Non Metal Tinted Lobby 201 24 Window Left (S) 7 0.580 116-A 0.53 116-B 1801 New I Double Non Metal Tinted I Lobby 201 25 26 Window Left ' S Window Left (S) 7 32 0.580 0.580 116-A 116 A 0.53 0.53 116 B 116-B 180 180 .. New New Double Non Metal Tinted Double Non Metal Tinted Lobby 201 t Lobby 201 EXTERIOR SHADING ' # Exterior Shade Type SHGC Window -, Hgt. Wd. Overhang Left Fin Right Fin Len. H t. LExt.RExt. Dist. Len. H t. Dist: Len. H t. - 14 None '• 0.76 ' 15 None 0.76. 16 • None 0.76 . 17. None 0.76 18 None 0.76 19 None i 1.00 - 20 None 0.76 21. None 0.76 i 22' None . 0.76 23 None 0.76 24; None 10.76 25 None •0.76 26 1 None 10.76 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES Ld„� y.uyea uonamg ,s ar umnam zones a mrougn io aria contains an enciosea space wrm noon area greater than 25,000 ttZ, a ceiling height greater than 15 feet, and an LPD for general Ilghtl'n o'sf at least 0.ii Wtft2. See Section M(c). If this box Is checked, ENV-" must be filled out. when submitting under the Prescriptive Compliance Approach. Run Initiation Time: 02/27/08 16:41:28 Run Code: 1204159288 EnergyPro 4.4 by EnergySoft -User Number. 5670 ' Job Number. 07-082 Page:9 0f 30 ! .. r CERTIFICATE OF COMPLIANCE ENV-1'-C PROJECT NAME DATE ' ' La'Quinta Count Club', - 3/10/2008 4 OPAQUE SURFACES # Surface Type Area U-Fac. Insulation Cay.. Cont. Act. Azm. Tilt Cond' Status Joint Appendix IV Reference Location / Comments 41 Wall 32S 0.074 R-19 R-0.0 0 90 New 09-A5 - Lobby 201' 42 Wall 23 .-0.074 R-19 R-0.0 90. 90 New 09-A5 Lobby 201 43 Wall 24 0.074 • R-19 R-0.0 270 90 New 09-A5 Lobby 201 44 Wall 591 0.074 R-19 R-0.0 180 90 New 09-A5 Lobby 201 1 45 Roof .300 0.032 R-30 R-0.0 _ 0 0 New 01-A17 Hallway 46 Wall 200 0.074 - R-19 R-0.0 90 90 _ New 09-A5' Hallway 47 Roof 20 0.032 R-30 R-0.0 •0 0 New 01-A17 - Hallway 48 Roof 19 - 0.032 R-30 R-0.0 0 0 New 01=A17 Hallway? 49 Roof 191 0.032 - R-30 R-0.0 0 0 New • • 01-A17 Hallway 50 Roof 2A 0.032 R-30 R-0.0 0 0 'New 01-A17 i .• Hallway, 51. Roof 211 0.032 R-30 R-0.01 0. 0 New 01-A17 . Hallway 52 Wall 2 0.074 R-19 R-0.0 -0 90. New' 09-A5 . Hallway 53 Roof 61 '0.032 R-30 R-0.0 0 0 "' New 01-A17 Boardroom207 54 Wall 23$ 0.074 R-19 R-0.0 0 90 .-New 09-A5 Boardroom 207 55 Wall 12 - '0.074 R-19 R-0.0 90 90 '. New • 09-A5 Boardroom 207 56 Roof 16C 0.032 R-30 R-0.0 0 0 New 01-A17 - General Manager 57 Wall 97 0.074 R-19 R-0.0 90 90 New 09-A5 General Manager 58 Wall 13C 0.074 R-19 R-0.0 . 0 J 90 . - New 09-A5 General Manager 59 Roof 202 0.032 R-30 R-0.0 0 . 0 _ New 01-A17 General Manager 60 Wall 11 0.074 R-19 R-0.0 901 90 " New 09-A5 General Manager N, E. A, R (New, Existing, Altered, Removed) r - FENESTRATION SURFACES ' More than or equal to 10.000 sq.ft of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U-factors from '. a. Standards Table 116-A and B. Certificate shall be filed in the contractors project office during construction and in the building manager's office after construction 4 .# •. Type Area. U-Fac' SHGC2 Act. Azm. Cond. Stat. Glazing Tyiple Location/ Comments 27 Window Left S ' +' 32 0.580 116-A 0.53 116-B 180 : New Double Non Metal Tinted LoRb-y 201, 28 Window Left (S) 52 0.580 116-A 0.53 116-B 180 New Double Non Metal Tinted Lobby 201 29 Window Front (E) 37 0.580 116-A '0.53 116-B 90 New Double Non Metal Tinted Hallway 30 Window Front E 66 0.580 116-A 0.53 116-B 90 New Double Non Metal Tinted Hallway 31 Window Front E 37 0.580 116-A ' 0.53 116-B 90 New Double Non Metal Tinted Hallway 32 Skylight Right N) 23 0.390 NFRC 0.37 NFRC -0 New °. Milgard Classic Low-E Vinyl Hallway 33 Skylight Right (N) , 11 0.390 NFRC 0.37 INFRC 0 New " Milgard Classic Low-E Vinyl Hallway 34 Window Right N 23 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted.. ` Hallway 35 Window Right N 23 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted • Boardroom 207 36 Window Right N 39 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted _ Boardroom 207 37 Window Right (N) 39 0.580 116-A 0.53 116-B 01 New Double Non Metal Tinted Boardroom 207 38 lWindow Front E 26 0.580 116-A 0.53 116-B1 901 New Double Non Metal Tinted Boardroom 207 39 Window • Front E) 52 0.580 116-Al 0.53 116-B 1.:'" 901 New I Double Non Metal Tinted lBoardroorn207 i u-�a l ypu: i io uafaun i aoie nom Jtanoaros, i aDle NI-1 ueraUll 1 8DI8 nom me AI;M Manual Appendlx, NhKG Labeled value. - 2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value _ EXTERIOR SHADING ## Exterior Shade Type SHGC Window ' ' Hgt: Wd. Overhang :. Left Firi - Right Fin Len. H t. LExt.RExt. Dist. Len. H t. - Dist. Len.-H t. 27 None 0.76 28 None 0.76 ;. 29 t None t . 0.76 _ >• 30: None 0.76 t 31 None 0.76 32 None 1.00 x , 33 None 1.00 34 None 0.76 35 None 0.76 36 None 0.76 37, None 0.76 38 None 0.76 39 _ None 0.76 MINIMUM SKYLIGHT AREA'FOR LARGE ENCLOSED SPACES - ' The proposed building Is In climate zones 2 through 16 and contains an enclosed space with floor area greater than 26,000 11:2, a telling height greater than 15 feet, and an LPD for general lighting of at least 0.5 W/R2. See Section Wic). If this box Is checked, ENV-" must be filled out when submitting under the Prescriptive Compliance Approach. Run Initiation Time`. 02/27/08 16:41:28 - Run Code: 1204159288 EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page: 10 of 30 i t 4 CERTIFICATE OF: COMPLIANCE ENV-1-C PROJECT NAME DATE La Quinta Country Club 3/10/2008; OPAQUE SURFACES . # Surface Type r Area U-Fac. Insulation Cay. Cont. Act. Am'. t ' Tilt Cond* Status Joint Appendix IV Reference Location / Comments 61 Roof 26 0.032 R-30 R-0.0 0 0 New 01-A17 General Mann er 62 Wall 20C 0.074 R-19 R-0.0 ' 90 90 ' New 09-A5 General Manager 63 Wall c 15 . 0.074 R-19 'R-0.01 180 90 New 09-A5 General Manager 64 Roof 5 0.032 R-30 R-0.0 • 0 0 New 01-A17 Workroom 215 65 Roof 10 0.032 R-30 ' R-0.0 '0 0 New 01-A17 Workroom 215 66 Roof 6 ' `•0.032 R-30 R-0.0 0 0 New 01-A17 Storage 214 67. Roof - 32 - 0.032 R-30 R-0.0 0 0 New . 01-A17 Hall 216 - 68 Roof 15 0.032 R-30 R-0.0 0. 0 New 01-A17 Secretary Waiting 220 h 69 Wall t ,9 0.074 R=19 . R-0.0 270 90 New 09-A5 Secretary Waiting 220 w 70 Wall 36 0.074 R-19 R-0.0 180 90 New 09-A5 Secretary Waiting 220 71 Roof 197 0.032 R-30 R-0.0 0 0 New 01-A17 F&B Manager 218 ! 72 Wall. 136 0.074 - R-19 R-0.0 • 180 90 New 09-A5 F&B Manager 218 73 Roof . 119 0.032 R-30 R-0.0 0 0. New 01-A17 F&B Manager 218 74 Wall 93 0.074 R-19 R-0.0 .270 90 New 09-A5 F&B Manager 218 ' 75 Wall 103 0.074 • R-19 R-0.0 180 90 New 09-A5 F&B Manager 218 76 Roof 14 0.032 . R-30 R-0.0 . 0 0 New 01-A17 F&B Manager 218 77 Wall 10 0.074 R-19 R-0.0 180. 90 New 09-A5 F&B Manager 218 78 Wall 4 0.081 None R-13.0 : 0 90 New 12-A9 Maintenance , 79 Wall 12 . 0.081 None R-13.0 270 90 New 12-A9 r Maintenance., 80 Wa11BG 26 0.152 ' None R-5.0 0 90 New 13-J5 ' Corridor ' N, E, A. R (New, Existing, Altered, Removed) FENESTRATION SURFACES More than or equal to 10,000 sq.fL of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U-factors from Standards Table 116-A and B. Certificate shall be filed in the contractors project office during construction and in the building managers office after construction 'A I # Type • Area U-Fac' t SHGC2 Act., Azm. Cond. Stat. r • . • - • Glazing Type" Location/ ` . , Comments 40 Window - Front E 26 0.580 116-Al 0.53 116-B 90. New Double Non Metal Tinted Boardroom 207 41 Window Front -(E) 23 0.580 116-A 0.53 116-B ' 90 New' Double Non Metal Tinted • General Manager 42 Window. Front (E) 16 0.580 116-A 0.53 116-B 90 New Double Non Metal Tinted General Manager 43 Window Front E 16 0.580 116-A 0.53 116-B 90 New Double Non Metal Tinted General Manager 44 Window Front. E 40 0.580 116-A 0.53 116-B 90 New Double Non Metal Tinted General Manager, 45 Window Rear 22 0.580 116-A 0.53 116-B 270 New Double Non Metal Tinted Secretary Waiting 220 46 Window Left (S) 34 0.580 116-A 0.53 116-B 180 • New Double Non Metal Tinted F&B Manager 218 - 47 Window Rear c, 22 0.580 116-A 0.53 116-B 270 New Double Non Metal Tinted F&B Manager 218 48 Window Left S 20 0.580 116-A 0.53 116-B 180 New' - Double Non Metal Tinted F&B Manager 218' ' 49 Indow Rear (W) 16 0.580 116-A 0.53 116-B 270 New Double Non Metal Tinted Maintenance 50 lWindow Right . (N) 21 0.580 1.16-A 0.53 116-B 0 ' New I Double Non Metal Tinted I Snack Bar 165 51 indow Right . N 33 0.580 116-A 0.53 116-BI 01, New I Double Non Metal Tinted Snack Bar 165 (1) U-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. (2) SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value Snack Bar 165 . 0 EXTERIOR SHADING ' - # ' Exterior Shade Type SHGC Window Hgt. Wd. Overhang Left Fin Right Fin - Len. H t. LExt.RExt. , Dist. Len. H t. Dist. Len. H t. 40 None 0.76 ' 41, None 0.76 42, None 0.76 43 1 None 0.76 44 None 0.76 45 None 0.76 +. ` 46 None 0.76 t 47 None 0.76 48 ' None 0.76 49 ' None 0.76 50 None a 0.76 s 51 1 None 0.76; ! 52 1 None 0.76 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES The proposed building Is In climate zones 2 through 16 and contains an enclosed space with floor area greater than 25,000 ft2, a telling height greater than 16 feet, and an LPD for general . lighting of at least 0.5 WIR2. See Section 143(c). If this box Is checked, ENV41-C must be filled ouL when submitting under the Prescriptive Compliance Approach. Run Initiation Time: 02/27/08 16:41:28 Run Code,• 1204159288 EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 • Page:11 of 30 ' CERTIFICATE OF COMPLIANCE ENV-1"-C PROJECT NAME ' DATE La Quinta Count Club 3/10/2008' OPAQUE SURFACES " # Surface Type Area U-Fac. Insulation' Cay. Cont. Act. Azm. Tilt Cond' Status Joint Appendix IV Reference: Location / Comments 81 WallBG, 18 0.152 None R-5.0 ., 0 90 New 13-J5 Storage - 0" dee 82 WallBG 18 0.152 None R-5.0 0 90 New 13-J5 Employee Lounge - 0" deep 83 WallBG 12 0.152 None R-5.0 0 90 New 13-J5 '. Employee Loun e = 0" deep 84 Wall - 2 0.074 " R-19 R-0.0 0 90 New . 09-A5 Corridor 176/3., 85 Door ' 21 0.500 None R-0.0 0 90 New. 28-A4 Corridor 176/3 86 Wall 16 0.074 R-19 R-0.0 0 90 New 09-A5 • Snack Bar 165 h 87 Door .2 0.500 None R-0.0 0 90: New 28-A4 Snack Bar 165 88 Wall 26 ' 0.074 -R-19 R-0.0 0 , 90 New 09-A5 Men's Card Room 89 Wall 56 0.081 None R-13.0 135 90 New 12-A9 Restroom _ 90 Wall 532 0.081 None R-13.0 225 90 New • 12-A9 Restroom 91 WallBG ­432 0.152 None R-5.0 0 90 New 13-J5 Corridor 157/6,7 - 0" deep, 92 Wall 70 0.074 R-19 R-0.0 0 90 New 09-A5 Pro Office 134 93 Wall 40 0.074 R-19 R-0.0 270 - 90 New 09-A5 Pro Office 134 94 Wall 49 0.074 R-19 R-0.0 90 90 New 09-A5 Pro Shop 133 95 Wall 40 0.074 R-19 R-0.0 270 90 New 09-A5 Pro Shop 133 96 Wall 170 0.074 R-19 R-0.0 0 90 New 09-A5 Pro Shop 133 97, WallBG 36 .0.152 . None R-5.01 0 1 90 New 13-J5 Restroom - 0" deep 98 WallBG 23 0.1521 None . R-5.0 - 0 90 New 13-J5 + ' Restroom - 0" deep .. 99 Wall 6 0.153 None R-5.0 90 90 New 112-A9 - Storage 105 •. 100 Wall 16 0.1531 None K-5.01 90 New 112-A9 Storage 105 -. IN, c, A, M pvew, uiaung, n tarao, memoveaf - FENESTRATION SURFACES ❑More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U-factors from Standards Table 116-A and B. Certificate shall be filed in the contractors project office during construction and in the building manager's office after construction r .4 a # Type r Area U-Fat'. SHGC2 Act. A. zm Cond. ' Stat.. - Glazing Type Location/ Comments 53 Window -Right N 48 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Men's Card Room 54 Window Right (N) 25 0.580 116-A 0.53 116-B .0 New Double Non Metal Tinted Men's Card Room 55 Window Right N) 25 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Men's Card Room 56 Window Right , N '36 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Men's Card Room 57 Window Right N 36 0.580 116-A 0.53 116-B . 0 .,New Double Non Metal Tinted Men's Card Room 58 Window Right N) .,21 0.580 116-A 0.53 116-B .. 0 New Double Non Metal Tinted Pro Office 134 ° 59 Window, Front E 20 0.580 116-A 0.53 116-B z 90 New Double Non Metal Tinted Pro Shop 133 60 Window Rear . W 20 0.580 116-A 0.53 116-B 270 New Double Non Metal Tinted Pro Shop 133 61 Window Right N ~42 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Pro Shop 133= 62 Window Right (N) 48 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted • Pro Shop 133 63I in ow Right (N) 42 0.580 116-A 0.53 116-B b0 New Double Non Metal Tinted Fitness Center 64 indow Ri ht N 70 0.580 116-A ' 0.53 116 B "0 New Double Non Metal Tinted Fitness Center 65 Window Right (N) 70 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Fitness Center 4 (1) Ll-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. 2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING .• _ # Exterior Shade Type, '•, SHGC Window Hgt. Wd. Overhang Left Fin' Right Fin Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. 53. None 0.76 54 None _- 0.76 55 None 0.76 . 56 None 0.76 _ + 57 None 0.76 58 None 0.76. 59 None 0.76 60 None 0.76 61 None 0.76 62 , None 0.76 + . 63 None 0.76 64 1 None 0.76 65 1 None 0.76 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES + ElThe proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a telling hi lighting of at least 0.5 WHM See Section 143(c). If this box Is checked, ENV-4-C must be filled out when submitting under the Prescriptive Run Initiation Time: 02/27/08 16:41:28 ' Run Code: 120 EnergyPno 4.4 by EnergySoft -User Number. 5670 Job Number. 07-082 , . . than 16 feet, and an LPD for general Approach. Page:12 of 30 T t CERTIFICATE OF COMPLIANCE - "ENV-I,C .�_�. • La Quinta Country Club ` � - - 3/10/2008 ' OPAQUE SURFACES J - -# . Surface Type A+rea U-Fac. Insulation Cay. Cont. Act. Azm. � Tilt Cond' Status Joint Appendix ]V Reference , Location /Comments 101 Wall 25 0.153 None R-5.0 0 90 New 12-A9 Fitness Center 102 Wall 6 0.074 - R-19 R-0.0 90 '90 New 09-A5 Fitness Center 103 Wall 2 0.074 R-19 R-0.0 270 90' New 09-A5 Fitness Center 104 Wall 11 23 0.074 R-19 R-0.0 0 90. New 09-A5 Fitness Center 105 Wa11BG 38 0.152 None R-5.0 0 .90 New 13-J5 ' • Gallery/Tr phy Case - 0" deep 106 Wall 3 0.074 R-19 R-0.0 0 -90 New 09-A5 Concourse 107 Wal1BG 10 0.152 None R-5.0 0 90 New 13-J5 Pedicure/Manicure 129 - 0" deep 108 WallBG -. 10 0.152 'None R-5.0 0 90 New 13-J5 Pedicure/Manicure 129 - 0" deep 109 WallBG 3 0.152 None R-5.0 0 90 New 13-J5 Hallway 131 = 0" deep 110 Wal1BG 4 0.152 None . R-5.0 0 90 New 13-J5 Hallway 131 - 0" deep 111 Roof 1,28 0.032 R-30 R-0.0 0 0 New 01-A17 . Ladies Card Room 115 112 Wall 274 0.074 R-19 R-0.0 180 90 _ New 09-A5 Ladies Card Room 115 113 Wall -190 0.074 - R-19 R-0.0 90 90 New ' 09-A5 Ladies Card Room 115. 114 Wall - 33 0.074 R-19 R-0.0 0 90 New 09-A5 Ladies Card Room 115 ' 115 Wall. "` 11$ 0.074 R-19 R-0.0 180 90 New . 09-A5 Office 116 Wall. 7 - 0.074 R-19 ' R-0.0 90 90 New 09-A5 Office 117 Wall, 273 0.081 - None R-13.0 225 90 New 12-A9 Ladies Locker Room - 118 Wall 147 0.081 None R-13.0 135 90 New 12-A9 Ladies Locker Room 119 Wall 14C 0.081 None R-13.0 135 1-90 New 12-A9 Stora e 120 Wall 126 0.081 None R-13.0 45 1 90 New 12-A9 Stora e' N. E. A, R (New, Existing, Altered, Removed) ", FENESTRATION SURFACES Morethan or equal to 10,000 sq.fL of sitebuilt fenestratlon area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U-factors from "Y Standards Table 116-A and B. Certificate shall be filed in the contractor's project office during construction and in the building managers office after construction - #' • • , • T e Area U-Fac' ` SHGC2 Act. Azm. Cond. Stat. I . GlazingType Location/ , Comments' 66 Window Right N 42 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Concourse 67 Window Left S) 18 0.580 116-A 0.53 116-B 180 New Double Non Metal Tinted Ladies Card Room 115 68 Window Left S) a y18 0.580 116-A 0.53 116-B 180 New Double Non Metal Tinted Ladies Card Room 115 69 Window Front E 40 0.580 116-A 0.53 116-B 90 New Double Non Metal Tinted Ladies Card Room 115 70 Window . Front E 40 0.580 116-A 0.53 116-B 90 - New Double Non Metal Tinted + Ladies Card Room 115 71. Window Front (E) 40 0.580 116-A 0.53 116-B 90 New Double Non Metal Tinted Ladies Card Room 115 72 Window Right (N 4 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Ladies Card Room 115 73 Window Right N 42 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted • Ladies Card Room 115 74 Window Right N 4 0.580 116-A 0.53 116-B 0 New Double Non Metal Tinted Ladies Card Room 115 75 Window Front E) 23 0.580 116 A 0.53 116-B 90 -tNew . Double Non Metal Tinted Office + (1) U-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. 2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value V EXTERIOR SHADING " # Exterior Shade Type ` SHGC Window Hgt. Wd. Overhang ' Left Fin ;,:Right Fin Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. ' 66 None 0.76 - 67 None 0.76 68 None . 0.76 69 None 0.76 70 None 0.76 71 None 0.76 72; None r 0.76 73 None 0.76 74, None•. 0.76 75 None • - 0.76 += MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES - ' The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a telling height greater than 15 feet, and an LPD for general lighting of at least 0.5 Wfft2. See Section 143(c). If this box Is checked, ENV-" must be filled out when submitting under the Prescriptive Compliance Approach. Run Initiation Time: 02/27/08 16:41.28 Run Code' 1204159288 EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page: 13 of 30 CERTIFICATE OF COMPLIANCE ENV-1-C PROJECT NAME DATE La Quinta Country Club 3/10/2008 OPAQUE SURFACES • N, E, A, R (New, Existing, Altered, Removed) FENESTRATION SURFACES More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either Issued by NFRC or provide a CEC Default Label Certificate using the default U-factors from Standards Table 116-A and B. Certificate shall be filed in the contractor's project office during construction and in the building managers office after construction # IType Area U-Fac' SHGC2 Act. Aim. Cond. Stat. IGIazinqType Location/ Comments (1) Ll-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix NFRC Labeled value. 2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING # Exterior Shade Type SHGC Window Hgt. Wd. Overhang Left Fin Right Fin Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES The proposed building is in climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a ceiling height greater than 15 feet, and an LPD for general lighting of at least 0.5 W/R2. See Section 143(c). If this box is checked, ENV-" must be filled ouL when submitting under the Prescriptive Compliance Approach. EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Pace:14 of 30 CERTIFICATE OF COMPLIANCE MECH-1-C PROJECT NAME DATE La Quinta Country Club 8/10/2008 Designer: This form is to be used by the designer'and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work. appropriately. Building Departments: SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or.space, or a new space -conditioning system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation certificates and operating and maintenance information meet the requirements of Section 10-103 b and Title 24 Part 6. STATEMENT OF COMPLIANCE ❑ MECH-2-A: Ventilation System Acceptance Document -Variable Air Volume Systems Outdoor Air Acceptance -Constant Air Volume Systems Outdoor Air Acceptance Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ❑ MECH-3-A: Packaged HVAC Systems Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ❑ MECH-4-A: Air -Side Economizer Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the commission do not require equipment testing but do require construction inspection. ❑ MECH-5-A: Air Distribution Acceptance Document Equipment requiring acceptance testing This test required If the unit serves 5,000 B2 of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace duds or replace the packaged unit. ❑ MECH-6-A: Demand Control Ventilation Acceptance Document Equipment requiring acceptance testing All new DCV controls installed on new or existing packaged systems must be tested. ❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document } Equipment requiring acceptance testing All new VA fan volume controls installed on new or existing systems must be tested ❑ MECH-8-A: -Hydronic System Control Acceptance Document -Variable Flow Controls Applies to chilled and hot water systems. -Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header. -Supply Water Temperature Reset Controls Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Btulhr. r -Water-loop Heat Pump Controls Applies to all new watedoop heat pump systems where the combined loop pumps are greater than 5 hp. -Variable Frequency Controls Applies to all new distribution pumps on new variable Bow chilled, hydronic heat pump or condenser water systems where the pumps motors are greater than 5 hp. Equipment requiring acceptance testing EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:15 of 30 IR SYSTEM REQUIREMENTS Part'1 of 2 MECH-2-C .. PROJECT NAME La Quinta Count 'Club 3/10/200& SYSTEM FEATURES ITEM OR SYSTEM TAG(S)'` Number of Systems AIR SYSTEMS, Central or Single Zone HP-1 HP-2 HP-3, 4 1 1 2 T-24 • MANDATORY MEASURES Section., Reference on Plans or Specification' , Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls ' Natural Ventilation' Minimum Ventilation +. VAV Minimum Position Control Demand Control Ventilation r. Time Control Setback and Setup Control • Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation l r } r f PRESCRIPTIVE MEASURES Calculated Heating Capacity'x 1.43 2 . „ Proposed Heating Capacity 2 ' Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 . n , Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance 112(a) : 3.30 COP - 3.20 COP 3.30 COP- 112 a 10.3 EER 9.8 EER 10.3 EER 112 b Yes Yes Yes ' 112(c), 115(a).n/a• n/a n/a 121(b) Yes Yes Yes 121(b) '652 cfm 355 cfm 946 cfm ' 121 c No No ` No 121(c) Yes No Yes - 121 c 122 a Pro rarnmable`Switch Programmable Switch. • Programmable Switch . 122 a Heating &Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122( n/a n/a ' n/a 123� t 124 ` 1 R-8.0 R-4.2 R-4.2 i 144 a & b n/a n/a n/a. 144 a & b 127,516 btuh 84,942 btuh " 255,032 btuh 144 a & b n/a :. n/a n/a 144 a & b 89,861 btuh 96,640 btuh 154,573 btuh 144 c Constant Volume Constant Volume Constant Volume 144 c ' 144 c Yes -' Yes Yes 144 d No No No 144 a Diff. Enth Inte rated Diff. Enth (Integrated) Diff. Enth (Integrated) 144 • Constant Temli Constant Temp Constant Temp 144 (1) Constant Temp' Constant Temp Constant Temp 144 (k) No _. - No No 1 :' For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. i + r 3: Enter Yes if System is: 'Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, 'see PERF-1 for performance method duct sealing requirements. A 'SIR SYSTEM REQUIREMENTS Part 1-of 2 MECH-2`-C PROJECT NAME DATE • La Quinta Count Club 3/10/2008 T SYSTEM FEATURES ITEM OR SYSTEM TAG(S) ' ,:Number of Systems , AIR SYSTEMS, Central or Single Zone HP-6 HP-5,7 • HP-8 1 2 T-24 MANDATORY MEASURES Section Reference on Plans or Specification 1 Heating Equipment Efficiency, Cooling Equipment Efficiency Heat Pump Thermostat ` Furnace Controls - c Natural Ventilation , Minimum Ventilation ` VAV Minimum Position Control Demand Control Ventilation • + Time Control . F Setback and.Setup Control • Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation ' 112(a) ' 3.30 COP 3.40 COP ` 7.80 HSPF 112(a). 10.3 EER, 10.5 EER • -13.0 SEER / 13.0 EER 112(b) Yes Yes . Yes yr 112(c), 115(a) � , 'n/a n/a n/a . . 121(b) Yes Yes Yes 121(b) 719 cfm ". 370 cfm 308 cfm' 121 c No No No 121(c) Yes No Yes 121 c ' 122 a Programmable Switch Programmable Switch Programmable Switch 122 a Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122 g n/a n/a n/a 123 x 124 R-8.0 R-8.0 R-8.0 PRESCRIPTIVE MEASURES ` Calculated Heating Capacity is i.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control v DP Sensor Location a Supply Pressure Reset (DDC only) Simultaneous Heat/Cool , • Economizer Heating Air Supply Reset , Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance . ti• 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification •section and paragraph number where the required features are documented. If a requirement is not applicable; put "N/A" in the column. f �2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, - see.PERF-1 for performance method duct sealing requirements. NOTES O FIELD- For Buildina DeoartmentUse Only Run Initiation Time: 02/27/0816:41:28 Run Code: 1204159288• , EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:17 of 30 144 a & b n/ate n/a n/a 144 a & b 127,516 btuh 127,147 btuh 48,584 btuh �. 144 a & b n/a n/a n/a 144r a & b 81,196 btuh 107,156 btuh 33,183 btuh 144 c Constant Volume' Constant Volume Constant Volume 144 (c)i 144 c Yes Yes Yes - 144 d No V i No No 144 a Diff. Enth (Integrated) , Diff. Enth. (Integrated) Diff. Enth (Integrated) 144 Constant Temp Constant Temp Constant Temp Constant Temp Constant Temp Constant Temp - 144 k No Now No �iR SYSTEM REQUIREMENTS ' ' Part 1 of 2 MECH-2-C PROJECT NAME DATE La-Quinta Country Club 3/10/2008 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems AIR SYSTEMS, Central or Single Zone HP-9 - HP-10 HP-11 T-24 .. ` MANDATORY MEASURES . Section Reference on Plans or Specification 1. Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation ' Minimum Ventilation = VAV Minimum Position Control Demand Control Ventilation Time Control M Setback and Setup Control - Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation 112(a) 7.70 HSPF 7.70 HSPF 7.70 HSPF 112 a 13.1 SEER / 13.1 EER •'13.1.SEER / 13.1 EER 13.1 SEER / 13.1 EER 112(b) . Yes' Yes Yes ' 112(c), 115(a) n/a ;, n/a n/a 121(b) Yes Yes Yes 121(b) 95 cfm 74 cfm - 93 cfm 121 c No - No No 121(c) No No, No 121 c 122 a Programmable Switch .,Programmable Switch F Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122(g) n/a n/a n/a 124 " R-8.0,. R-8.0 R-8.0 r� 1.1 For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the ; • required features are documented. If a requirement is not applicable, put "N/A' in the column. , 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, ti , see PERF-1 for performance method duct sealing requirements. - f f h . . PRESCRIPTIVE MEASURES '• I Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) • Simultaneous Heat/Cool' Economizer R' , Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance 144 a & b . • - n/a n/a n/a 144 a & b'- 42,213 btuh 42,213 btuh . 42,213 btuh F 144 a & b n/a -' ` I n/a n/a 144 a & b 27,028 btuh 26,250 btuh 27,442 btuh' • . 144 c Constant Volume Constant Volume Constant Volume 144 (c) 144 c Yes t P Yes Yes 144 d No . P No No 144 a Diff. Enth Inte •rated) Diff. Enth (integrated) Diff. Enth (Integrated) 144 Constant Temp Constant Temp Constant Temp 144 (f) ` Constant Temp Constant Temp 4 Constant Temp 144 (k) No i P No - No IR SYSTEM REQUIREMENTS Part 1 of 2 `MECH=2-C PROJECT NAME DATE - La Quinta Couintry Club • J. 3%10/2008 SYSTEM FEATURES r ITEM OR SYSTEM TAG(S) Number of Systems , AIR SYSTEMS, Central or Single Zone FC-1 , FC-2 FC-3 1 } 1. a 112(a) . 0.80 HSPF 0.80 HSPF 0.80 HSPF 112 a ' 14.0 SEER / 14.0 EER 14.0 SEER / 14.0 EER 14.0 SEER / 14.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a l n/a n/a 121(b) Yes Yes Yes 121(b) 47 cfm. 284 cfm 271 cfm 121 c _ No No No- 121(c) . No . 1 No ' No 121 c 122 a -Programmable Switch Programmable Switch Pro rammable Switch' 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122(g) n/a n/a n/a ^. 123 d. .. a .. 124 R-4.2 R-8.0 R-4.2 PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible_ Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) • - Simultaneous Heat/Cool • Economizer } . Heating Air Supply Reset Cooling Air Supply Reset t Duct Sealing for Prescriptive Compliance 144 a & b n/a n/a n/a _ 144 a & b 71,292 btuh 71,292 btuh 71,292 btuh 144 a & b ` n/a n/a n/a ' 144 a & b 31,050 btuh 35,603 btuh 34,767 btuh 144 c Constant Volume i Constant Volume Constant Volume 144 (c)w 144 c Yes... Yes Yes 144 d No ._ No No • ' 144 e - No Economizer : No Economizer.` No Economizer 144 Constant Temp Constant Temp Constant Temp 144 (o Constant Temp Constant Temp Constant Temp 144 (k) No T No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A", in the column.- 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. - 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct -sealing is required for Prescriptive Compliance, see PERF-1 for performance method duct sealing requirements. - + NOTES • O FIELD- For Buildina DepartmentUse Only �• Run Initiation Time: 02/27/08 16:41:28• Run Code: 1204159288 EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:19 of 30 . r IR-SYSTEM REQUIREMENTS Part 1 Of 2, MECH-2-C PROJECT NAME DATE La Quinta Country Club - 3/10/2008 t SYSTEM FEATURES ITEM OR SYSTEM TAG(S) ~, Number of Systems AIR SYSTEMS, Central or Single Zone FC-4, 5 FC-6, 7. F6-8, 9 2 2 e 2 . T-24 MANDATORY MEASURES Section . , Reference on Plans or Specification 1 Heating Equipment Efficiency' ,. Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural .Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control • Isolation Zones Pipe Insulation Duct Insulation , 112(a) 0.80 HSPF 0.80 HSPF 0.80 HSPF. 112 a 14.0 SEER / 14.0 EER 14.0 SEER / 14.0 EER " '14.0 SEER / 14.0 EER 112(b)� Yes • Yes Yes 112(c), 115(a) _ n/a n/a n/a 121(b) Yes Yes _ Yes _ 121(b) 758 cfm -_ 604 cfm 311 cfm .: 121 c No No No 121(c) No No No- 121 c 122 a Programmable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122(g r n/a _ n/a n/a 124 - R-4.2 +' R-4.2 R-4.2 PRESCRIPTIVE MEASURES .. Calculated Heating Capacity x 1.43 2 Proposed Heatind Capacity 2, Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 . Fan Control , DP Sensor Location - Supply Pressure Reset (DDC only) Simultaneous HeaVCool Economizer Heating Air Supply Reset . - Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance 144 a & b n/a n/a n/a . 144 a & b 142,584 btuh 142,584 btuh 142,584 btuh 144 a & b - n/a n/a n/a 144 a & b :69,324 btuh 70,832 btuh 63,384 btuh ! 144 c Constant Volume Constant Volume Constant Volume 144 (c) 144 c Yes Yes Yes 144 d No No No 144 a No Economizer No Economizer No Economizer. Constant Tem Constant Tim Constant TemConstant E44(0 Temp Constant Temp Constant Tempk) No No. No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the , required features are documented. If a requirement is not applicable, put "N/K in the column. , 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. , 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF-1 for performance method duct sealing requirements. ti INOTES O FIELD- e e Use Only Run InitiationTime: 02/27 0816:41.28 'Run Code: 1204159288 EnergyPro 4.4 by EnergySoft User Number. 5670 - • Job Number. 07-082 Page:20 of 30 IR Part 1 of 2 MECH- SYSTEM REQUIREMENTS ' .t. 2-C PROJECT NAME DATE La Quinta Country Club - 3/10/2008 SYSTEM FEATURES ITEM OR SYSTEM,TAG(S) ' Number of Systems AIR SYSTEMS, Central or Single Zone FC-10 ,. i 9C-11, 12, 13, 14 ' FC-15 1•' 4 1 , T-24 • • MANDATORY MEASURES Section' Reference on Plans or Specification 1 Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation, 'Time Control • Setback and Setup Control Outdoor Damper Control * Isolation Zones • ; Pipe Insulation . Duct Insulation 112(a) 0.80 HSPF 0.80 HSPF 0.80 HSPF 112 a 14.0 SEER / 14.0 EER, 14.0 SEER / 14.0 EER 14.0 SEER / 14.0 EER 112 b Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121 b) 164 cfm 427 cfm 167 cfm 121(c) No No • No 121 c No No : No 121 c 122 a Pro rainmable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122(g). . -- n/a n/a 'n/a 123 ' 124 ' } R-4.2. R-4.2 R-4.2 a PRESCRIPTIVE MEASURES; ' Calculated Heating Capacity x 1.43 2 ! Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 ` Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) • : Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance r� 144 a & b n/a - n/a n/a 144 a & b 71,292 btuh 285,168 btuh 71,292 btuh 144 a & b - n/a,*.. n/a n/a 144 a & b •' '33,737 btuh 102,257 btuh 32,254 btuh 144 c Constant Volume Constant Volume Constant Volume ` 144 "(c 144 c Yes Yes Yes 144 d No S. No - No • 144 a No Economizer . ' ' No Economizer No Economizer 144 Constant Tem p 'Constant Temp Constant Temp_ 144 (f) Constant Temp" Constant Temp Constant Temp 144 (k) No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put •'N/A•• in the column.: ' t` ' t 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. ' 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF-1 for performance method duct sealing requirements. NOTES O FIELD- For Buildina DenartmentUse OnIV 1 u y"� '3'f-s- Z r Aerg.: ,'q rd. 1 .i�: j t:z • _` i '" a.'s •.1, § -e a T ,.,°" un'InitiationTime: 02/27/0816:41:28 - Run Code: 1204159288 = - EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:21 of 30 f i _ �iRSYSTEWREQUIIkEMENTS- E ' Partl & 2 - MECH-2-C PROJECT NAME r' DATE - La.Quinta Country Club , 3/10/2008.' SYSTEM FEATURES " ITEM OR SYSTEM TAG(S) Number of Systems AIR SYSTEMS, Central or Single Zone . FC-16 . FC-17, 18 FC-19 2 T-24 ' .MANDATORY MEASURES Section ' ' ' Refere6ce on Plans or Specification 1 Heating Equipment Efficiency w Cooling Equipment Efficiency y . Heat Pump Thermostat. Furnace Controls • Natural Ventilation • . + Minimum Ventilation r VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control ' Outdoor Damper Control Isolation Zones Pipe Insulation Ductlnsulation 112(a) 0.80 HSPF 0.80 HSPF 0.80 HSPF 112 a ' •- 14.0 SEER /.14.0 EER 14.0 SEER / 14.0 EER 14.0 SEER / 14.0 EER 112(b) Yes Yes - Yes . . 112(c), 115(a) n/a' n/a n/a ' 121(b) Yes. ' Yes Yes "�- 121(b) 136 cfm • 664 cfm 369 cfrrt 121 c No No - No 121(c) No Y• No - w No 121 c 122(gl Pro rammable Switch Programmable Switch Programmable Switch 122 a Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122(g) /a n/a n/a 123 124 R-4.2 R-4.2 R-4.2 PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43.2 , I ` 2 I " Proposed Heating Capacity - Calculated Sensible Cooling Capacity z 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location . Supply Pressure Reset (DDC only) , Simultaneous Heat/Cool Economizer, Heating Air Supply Reset f r Cooling Air Supply Reset ' Duct Sealing for Prescriptive Compliance 144 a & b n/a t n/a n/a 144 a & b 39,175 btuh a ' 142,584 btuh 71,292 btuh ' 144 a & b n/a n/a n/a 144 a & b 19,791 btuh 66,842 btuh 36,444 btuh " 144 c . Constant Volume Constant Volume Constant Volume 144 (c) 144 c Yes • Yes Yes 144 d No No No 144 e + No Economizer No Economizer No Economizer 144 Constant Tem • Constant Temp Constant Temp .144(o Constant Temp Constant Temp Constant Temp` 144 (k) • No No No ' 1: For each central and single zone air systems (or group of similar units).fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement'is not applicable, put "NIX in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. T 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space.' Duct sealing is required for Prescriptive.Compliance,. ,. see PERF-1 for performance method duct sealing requirements. e 4 ' MECHANICAL VENTILATION MECH-3-C PROJECT NAME DATE La Quinta Country Club I 3/10/2008 PRESCRIPTIVE REHEAT LIMITATION Section 144(d)) MECHANICAL VENTILATION Section 121 b 2 AREA BASIS OCCUPANCY BASIS VAV MINIMUM A B C D E F G H I J K L M N ZONEISYSTEM o yam Tma o 3 co c 'W.a0 ®®'n �g c 'ts3 W 3 X DA Ada roc .3 CQ v_m CD" v m.a0 f�l mT c +3 3 Cr 03 m0 XCf cn �?� o3m yA OX v —D A v 0>to T»N 3• D� fVo �' OtDO �I UI gcv 9y-0 CD 3 'tW 3 X 00 xa 7C0 c 3 w3d O a TX— � fro •O 3 o3 �3 1 3 W u D Priv Dining Entry 233 14 0.15 21 21 21 Hallway 234 45E 0.15 68 68 68 Private Dining 235 1,12E 0.50 562 562 562 HP-1 Total 652 652 Office 9 0.151 14 14 14 Hall239 17 0.15 26 26 26 Storage 45E 0.15 69 69 69 Kitchen 1,64 0.15 246 246 246 HP-2 Total 355 355 Storage 21E 0.15 32 32 32 Mixed Grille 225 1,724 0.50 •862 862 862 Ha11227 34E 0.15 52 52 52 HP-3, 4 Total 946 946 Bar 204 274 0.50 137 137 137 Storage 206 3E 0.15 5 5 5 Lounge 202 1,154 0.50 577 577 577 HP-6 Total 719 719 Lobby 201 1,286 0.151 193 193 193 Hallway 1,178 0.15 177 177 177 HP-5,7 Total 370 370 Boardroom 207 61E 0.50 308 308 308 HP-8 Total 308 308 General Manager 631 0.15 95 95 95 HP-9 Total 95 95, Workroom 215 16 0.15 24 24 16 8 C Minimum ventilation rate r Section 121 Table 121-A E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seating. H Required Ventilation Air REQ'D V.A. Is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS (column D or G). I Must be greater than orequal to H, or use Transfer Air column N to make u the difference. J Design fan supply dm (Fan CFM x 30%; or K Condition area (fL sq.) x 04 dmtfl. sq.; or L Maximum of columns H. J, K or 300 dm M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N. N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:23 of 30 MECHANICAL VENTILATION MECH-3-C PROJECT NAME DATE La Quinta Country Club I 3/10/2008 PRESCRIPTIVE REHEAT LIMITATION Section 144d MECHANICAL VENTILATION Section 121 b 2 AREA BASIS OCCUPANCY BASIS VAV MINIMUM A B C D E F G H I J K L M N ZONE/SYSTEM 0 o D� v�a o a 15 don p�3 -n Qom` W�3 xDn A m •n °' 3 Z -U c CD 0� ° -0 A.,0 0�3 � 3 m�O5 xcn '1v '� `. _ � rn 01JR � 0 G) o< "' D < 13 ()3m icr- D 3 o� o nmo 3c17 v 1D ? n .n 3� �r M A xo o c w3d oyx o -n ` � CD %° 3 o3 ' D d ai 0 D Storage 214 63 0.15 9 9 9 Hall216 326 0.15 49 49 49 HP-10 Total 83 74 Secretary Waiting 220 158 0.15 24 24 24 F&B Manager 218 46 0.15 69 69 69 HP-11 Total 93 93 Maintenance 120 0.15 18 18 18 Storage 57 0.15 9 9 9 Locker Room 137 0.15 21 21 21 F6-1 Total 47 47 Corridor 316 0.15 48 48 48 Storage 433 0.15 65 1 65 65 Employee Lounge 342 0.50 171 171 171 FC-2 - Total 284 284 Corridor 176/3 22 0.15 33 33 33 Snack Bar Storage 167 122 0.15 18 18 18 Cook and Dish Up 30 0.15 45 45 45 Hack Bar 165 348 0.501 174 174 174 FC-3 Total 271 271 Bar 152 15 0.50 76 76 76 Men's Card Room 1,364 0.50 682 682 682 FC-4, 5 Total 758 758 Restroom 1,573 0.15 236 236 236 Corridor 157/6,7 616 0.15 92 1 92 92 Attendant 28 0.151 42 1 1 1 42 42 C Minimum ventilation rate per Section 121 Table 121-A E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occu ant load foregress purposes fors aces without fixed seating. H Required Ventilation Air REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS (column D or G). I Must be greater than orequal to H, or use Transfer Air column N to make up the difference. J Design fan supply cfm Fan CFM) x 30%; or K Condition area ft sq.) x 04 cfm/fi. sq.; or L Maximum of Columns H, J. K or 300 cfm M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N. N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 - Page: 24 of 30 MECHANICAL VENTILATION MECH-3-C PROJECT NAME DATE La Quinta Country Club I 3/10/2008 PRESCRIPTIVE REHEAT LIMITATION Section 144(d) MECHANICAL VENTILATION Section 121 b 2 AREA BASIS OCCUPANCY BASIS VAV MINIMUM A B C D E F G H I J K L I M N ZONE/SYSTEM O D0 N� �Ima o o 0 C y n �9 mmT C ° a3 X Dn 0)3 C m3 mQ vm ID 1j m.�n q�i m� o�g 3 rr � 3 O— fnO XC'f cn vd3 03 m 0) OX v 60°,< D < my A3m -n 3 m L3 N o cito 0. "n 3co vy T v 3 X yo .cA x 7C n 01 C 3 w3 Gl O o3X �_0 3` A (ny mo -3 o3 »� D @ 3 0 m � D Laundry 106 0.151 16 1 16 16 Men's Locker Room 1,447 0.15 217 217 217 FC-6, 7 Total 604 604 Pro Office 134 116 0.15 17 17 17 Pro Shop Storage 135 143 0.151 21 21 21 Pro Shop 133 1,0910 0.25 272 272 272 FC-8, 9 Total 311 311 Dressing 26 0.15 4 4 4 Barber Shop 272 0.401 109 109 109 Restroom 342 0.15 51 51 51 FC-10 Total 164 164 Storage 105 132 0.15 20 20 20 Fitness Center 2,714 0.151 407 407 407 FC-11, 12, 13, 14 Total 427 427 Elevator Lobby 199 0.15 30 30 30 Gallery/Trophy Case 36 0.15 54 54 54 Concourse 55 0.15 83 83 83 FC-15 Total 167 167 Pedicure/Manicure 129 29C 0.40 116 116 116 Hallway 131 133 0.15 20 20 20 FC-16 Total 136 136 Ladies Card Room 115 1,286 0.50 644 644 644 Office 132 0.151 20 20 20 FC-17, 18 Total 664 664 Ladies Locker Room 717 0.15 108 108 108 C Minimum ventilation rate per Section 121 Table 121-A E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load for actress purposes fors aces without fixed seating. H Required ventilation Air (REQ'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G . I Must be greater than orequal to H or use Transfer Air column N to make up the difference. J Design fan supply cfm Fan CFM x 30%; or K Condition area R sq. x 04 cfm/R. sq.; or L Maximum of Columns H, J, K, or 300 cfm M This must be less than orequal to Column L and greater that or equal to the sum of Columns H + N. N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:25 of 30 MECHANICAL VENTILATION MECH-3-C PROJECT NAME DATE La Quinta Country Club 3/10/2008 PRESCRIPTIVE REHEAT LIMITATION Section 144(d)) MECHANICAL VENTILATION Section 121 b 2 AREA BASIS OCCUPANCY BASIS VAV MINIMUM A B C D E F G H I I J K L M N ` ZONEISYSTEM o a� may» C 3 to c d a m03 T 0 o c3 W'�3 xDn n tD �I `� °' 3 vc 03 �� -� 0 v c®3 O Q 3 m03 x00'xp .T.'O T m vto ci 0, G �' D 0®� 3r. D 7 N wp 0' 0®0 3co 'O 0 '0 �' T 300 a A 7C n ° c w3c�i CD x y 0 -n ='" Ny o3_ »' d 3 m D Hall 1,09 0.15 164 164 164 ttendant 114 28E 0.15 43 43 43 Storage 262 0.15 39 39 39 Laundry 112 102 0.151 15 15 15 FC-19 Total 369 369 C Minimum ventilation rate per Section 121 Table 121-A E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load fore ress purposes fors aces without fixed seating. H Required Ventilation Air REO'D V.A. is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G . I Must be greater than orequal to H or use Transfer Air column N to make up the difference. J Design fan supply cfm (Fan CFM) x 30%; or K Condition area ft sq. x 04 chn ft. sq.; or L Maximum of Columns H, J. K, or 300 cfm M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N. ' N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:26 of 30 MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-5-C PROJECT NAME La Quinta Count Club DATE3/10/2OOH CHILLER AND TOWER SUMMARY Efficiency Tons PUMPS Equipment Name Equipment Type City. Tot Qty GPM BHP Motor Eff. Drive Eff. Pump Control D BOILER SUMMARY Energy Standby TANK INSUL. Rated Vol. Condition Factor Loss or Ext. System Name System Type Distribution Type Qty Input (Gals.) I Status I or RE Pilot I R-Val. Hot Water Hot Water Add 1/2" Control # HP Type In Plenum Outside Buried Insulation Motor Drive Motor Drive System Name Fan:[ype Motor Location CFM BHP Eff. Eff. CFM BHP Eff. Eff. Carrier 50HJQ012 Constant Volume Draw -Through 4,000 3.70 86.5% 97.0% none Carrier 50HJQ014 Constant Volume Draw -Through 4,500 4.25 86.5% 97.0% none Carrier 50HJQ007 Constant Volume Draw -Through 2,400 2.40 84.0%1 97.0% none Carrier 50HJQ005 Constant Volume Draw -Through 1,600 1.20 82.5% 97.0% none Carrier 50HJQ004 Constant Volume Draw -Through 1,200 1.20 82.5% 97.0% none CARRIER 25HBR360-60 Constant Volume Draw -Through 1,750 0.30 64.0% 97.0% none CARRIER 25HBR336-60 Constant Volume Draw -Through 1,050 0.20 60.0%1 97.0% none ENVELOPE MANDATORY MEASURES.". ENV-MM PROJECT NAME DATE La'Quinta Country Club 3/10/2008 DESCRIPTION Designer Enforcement a § 118(a) Installed Insulating Material shall have been certified by the manufacturer to _ comply•with the California Quality Standards for insulating material, Title 20, . Chapter 4, Article 3. r , a § 118(c) AII'Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. ' X❑ § f17(a) 411 Exterior Joints and openings in the building that are observable sources of air , leakage shall be caulked, gasketed, weatherstripped or otherwise sealed:' X❑ § 116(b) Site Constructed Doors, Windows and Skylights shall be'caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). X❑ § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards. Manufactured fenestration products must be labeled for U-value according to NFRC procedures. § 118(e) Demising Walls in Nonresidential Buildings: -The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R-value of no less than R-13 between framing - " members. ' 'r r , { u EnergyPro 4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:28 MECHANICAL MANDATORY MEASURES . Part 1 of 2 MECH-MM PROJECT NAME DATE r La Quinta Count `Club 3/10/2008 DESCRIPTION Designer Enforcement' Equipment and Systems Efficiencies 0 g 11 Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply with the applicable standard. F§115(a) Fan type central furnaces shall not have a pilot light. X] §123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be insulated in accordance with Standards Section 123. §124 Air handling duct systems shall be installed and insulated in compliance'with Sections 601,+602, 603, 604, and 605 of the2001 CIVIC Standards. ` Controls §122(e) Each space conditioning system shadbe installed with one of the following: X §122(e)1A Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the - requirements of Section 112 (d)) shall be installed with an automatic time switch r with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch shall be capable of programming different schedules for weekdays and weekends and have program back-up capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or ❑ §122(e)1 B An occupancy sensor to control the operating period of the system; or §122(e)1C A 4-hour timer that can be manually operated to control the operating period of the system. r • t XI §122(e)2 Each space conditioning system shall be installed with controls that temporarily .restart and temporarily operate the system as required to maintain a setback = r heating and/or a setup cooling thermostat setpoint. a §122(g) Each space conditioning system, serving multiple zones with a combined conditioned floor area more.than 25,000 square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided with isolation devices, such as valves or dampers, that allow the supply - of heating or cooling to be setback or shut off independently of other isolation areas; and shall be controlled by a time control device as described above. ® §122(a&b) Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or reduced to a minimum. n §122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to authorized personnel. 0 §112(b). Heat pumps shall be installed with controls to prevent electric resistance ' supplementary heater -operation when the heating load can be met by the heat pump alone. EnergyPro 4.4 by EnergySoft User Number. 6670 Job Number. 07-082 Page:29 of 30 • MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM v PROJECT NAME La Quinta Country Club DATE 3/10/2008 Description Designer Enforcement Ventilation ❑X • §121(e) Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified on these plans. a§122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be provided on the outside air intakes and discharges of all space conditioning and exhaust systems. X] §122(f) All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all openings to the outside, except for 'combustion air openings. ' Air Balancing: The system shall be balanced in accordance with the National Environmental Balancing Bureau (�NEBB) Procedural Standards (1983), or - Associated Air Balance Council (AABC) National Standards (1989); or X] §121(f)2 Outside Air Certification: The system shall provide the minimum outside air as shown on the mechanical drawings, and shall be measured and certified by the installing licensed C-20 mechanical contractor and certified by (1) the design mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the person with overall responsibility for the design of the ventilation system; or t X §1Y1(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous basis and displaying that quantity on a readily accessible display divice; or . §121(f)4 Another method approved by the Commission. Service Water Heating Systems §113(b)2 , If a circulating hot water system is installed, it shall have a control capable of automatically turning off the circulating pump(s) when hot water is not required. §113(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit the outlet temperature to 1,10 degrees F. i EnergyPro4.4 by EnergySoft User Number. 5670 Job Number. 07-082 Page:30 of 30 CERTIFICATE OF COMPLIANCE (Part 1 of 2) OLTG-1-C PROJECT NAME LA QUINTA COUNTRY CLUB - CLUBHOUSE DATE January 23, 2008 PROJECT ADDRESS 77-750 AVENUE 50, LA QUINTA, CALIFORNIA Building Permit Checked by/Date Enforcement Agency Use PRINCIPAL DESIGNER -LIGHTING JEFFREY C. OVERMYER TELEPHONE (949) 753-1553 DOCUMENTATION AUTHOR VICTOR BECERRA TELEPHONE (949) 753-1553 GENERAL INFORMATION DATE OF PLANS . January23, 2008 JOUTDOOR LIGHTING ZONE( V One) ❑ LZ1 EJ LZ2 2] LZ3 ❑ LZ4 FUNCTION TYPE ❑� OUTDOOR LIGHTING ❑ OUTDOOR SIGNS ❑ INDOOR SIGNS PHASE OF CONSTRUCTION ❑ NEW CONSTRUCTION ❑ ADDITIONS ❑ ALTERATIONS STATEMENT OF COMPLIANCE This Certificate of Compliance lists outdoor lighting system specifications need Janornplete. ly with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building lighting requirements. The documentation preparer hereby certifies that the documentation is accur DOCUMENTATION AUTHOR S GNATURE DATE VICTOR BECERRA I January 23, 2008 The Principal Lighting Designer hereby certifies that the proposed outdoor lighting an signs design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the sp cifications, and with any other calculations submitted with calculations submitted with this permit application. The proposed building has be n designed to meet the lighting requirements contained in the applicable parts of Sections 110, 119, 130 through 132, 146, and 149 of Title 24, Part 6. Please ,'One: El I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer or electrical engineer, or I am a licensed architect. ❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. ❑ I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 553, 5538 and 6737.1. (These sections of the Business and Profe§,s�,pns Code are printed in full in the Nonresidential Manual.) LIGHTING DESIGNER -NAME SIGNATU E!;Z DATE LIC. # 7PRINCIPAL EFFREY C. OVERMYER January 23, 2008 E8964 INSTRUCTIONS TO APPLICANT OUTDOOR LIGHTING COMPLIANCE & WORKS EETS (✓ box if worksheet is included) For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the SIWAIIN Manual published by the California Energy Commission. ��V OLTG-I-C Certificate of Compliance. Required on plans for all submittals for outdoo p Part O 2 of 2 may be incorporated in schedules on the plans. SPF� Either LTG-1-C or OLTG-1-C may be used for signs as follows: BU,�Q Pp�O J V,- 1. Use LTG-1-C if the project consists solely of indoor signs A 2. Use LTG-1-C if the project consists of indoor lighting, and outdoor or in oor sign 1�uE S9 014 utdoor lighti 3. Use OLTG-1-C if the project consists solely of outdoor signs Utz 4. Use OLTG-1-C if the project consists of outdoor lighting, and indoor or o door signs aY but no other indoor lighting. yy OLTG-2-C LIGHTING COMPLIANCE SUMMARY. Applicable parts required for ALL outowances (Except for signs). OLTG-3-C AREA CALCULATIONS WORKSHEETS. Applicable parts required for all outdoor area calculations. ❑ OLTG-4-C SIGN LIGHTING COMPLIANCE. Required for all internally and externally illuminated ' for both indoor and outdoor signs. u / _ �� L!n u UJ IS 2005 Nonresidential Compliance Forms K JAN 2 S 2008 is offm Y�DD CERTIFICATE OF COMPLIANCE (Part 2 of 2) OLTG-1-C PROJECT NAME LA QUINTA COUNTRY CLUB - CLUBHOUSE Lighting schedules on Plans Show that Outdoor Lighting Meets Allowed Lighting Power El ❑ Lighting power allowances for general.site illumination on OLTG-2-C Part 1 of 4 Not Applicable ❑ 0 Lighting power allowances for local ordinances or for security multipliers on OLTG-2-C Part 2 of 4 Not Applicable ❑ Lighting power allowances for specific applications, other than vehicle service stations with canopies on OLTG-2-C Part 3 of 4 Not Applicable ` ❑ Lighting power allowances for vehicle service station canopies on OLTG-2-C Part 4 of 4 Not Applicable ❑ 0 Sign lighting compliance on OLTG-4-C Not Applicable Mandatory Measures on Plans Show that Outdoor Lighting Meets Outdoor Lighting Controls and Equipment Indicate location on plans of Note Block for Mandatory Measure ✓ ❑ Installed lighting power has been determined in accordance with § 130(c)1 : Not Applicable El ❑ All permanently installed luminaries with lamps rated over 100 watts either have a lamp efficacy of at least 60 lumens per watt or are controlled by a motion sensor § 132(a) Not Applicable E21 ❑ All Luminaries with lamps rated greater than 175 watts in hardscape areas, including parking lots, building entrances, canopies, and all outdoor sales areas meet the Cutoff Requirements of § 132(b) Not Applicable D ❑ All permanently installed outdoor lighting meets the Control Requirements of § 132(c)1 Not Applicable 0 ❑ Building facades, parking lots, garages, canopies, and outdoor sales areas meet the Multi -Level Lighting Requirements of § 132(c)2 Not Applicable MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION CONTROL IDENTIFICATION CONTROL TYPE Auto Time SwitchlPhotosensor, etc AREA CONTROLLED NOTE TO FIELD ELECTRICAL ROOM LCP Timeclock/Photocell ALL EXTERIOR LTS 2005 Nonresidential Compliance Forms LIGHTING COMPLIANCE SUMMARY (Part 1 of 4) OLTG-2-C PROJECT NAME LA QUINTA COUNTRY CLUB - CLUBHOUSE DATE January 23, 2008 LIGHTING POWER ALLOWANCES - GENERAL SITE ILLUMINATION - (TABLE 147-A) Allotted Watts Luminaire Lamps/Ballasts Installed Watts A B C D E F G H 1 J K L M N O Lighting Applications Category (Table 147-A) m D �' )$ �y x No Q �r T p D 0 W a x� n y. r o ,��m CD o Description P y co vc_ o r °� m rnri c gym m m o °' ��' 3 v ry c �, 3 �'.�� m m o r� v �'in m ✓ o n�in c m .. C r r c -. 3 w.m y o -. y X�;y zCD a, n Hardscape for automotive vehicular use, including parking lots, driveways and site roads 1031000 0.15 15,450 S1A DECORATIVE Full -Cutoff H.I.D. 1 400 1 461 ✓ 7 3,227 - - - S16 DECORATIVE Full -Cutoff H.I.D. 1 400 1 461 ✓ 9 4,149 - - - S1C DECORATIVE Full -Cutoff H.I.D. 1 175 1 203 ✓ 3 609 - - - S2A DECORATIVE Full -Cutoff H.I.D. 2 400 2 922 ✓ 8 7,376 Total Allotted Watts 15,450 Total Installed Watts 15,361 2005 Nonresidential Compliance Forms ILLUMINATED AREA CALCULATION WORKSHEET (Part 1 of 5) OLTG-3-C PROJECT NAME LA QUINTA COUNTRY CLUB - CLUBHOUSE DATE January 23, 2008 Hardscape - Method ( i ) A. Hardscape for automotive vehicular use, including parking lots, driveways and site roads A B C r D E F G H List Specific Application . (Table 147-A) Actual Paved Area plus 5' perimeter adjacent unpaved land. Includes planters and landscaped areas less than 10' wide that are enclosed by hardscape on at least 3 sides Areas (ft) to Subtract from within Illuminated Area Illuminated Area (B - G) Areas between poles or luminaires that are greater than 6 mounting height distance (if applicable) Overlapping Areas of Another Application or Luminaire Building Areas Areas Obstructed By Sign or Other Structure Sub Total of areas to Subtract (C + D + E + F) Hardscape for automotive vehicular use, including parking lots, driveways and site roads 103,000 - 103,000 B. Hardscape for pedestrian use, including plazas, sidewalks, walkways and bikeways A B C I D E F - G H List Specific Application (Table 147-A) Actual Paved Area plus 5' of unpaved land on either side of path of travel. Shall include all contiguous paved area before including adjacent grounds. Areas (fe) to Subtract from within Illuminated Area Illuminated Area (B - G) Areas between poles or luminaires that are greater than 6 mounting height distance (if applicable) Overlapping Areas of Another Application or Luminaire Building Areas Areas Obstructed By Sign or Other Structure Sub Total of areas to Subtract (C + D + E + F) Checklist 0 § 147(c)1 B - Each portion of all illuminated areas has been assigned only one lighting application, and the applications are consistent with the actual use of the areas. . § 147(c)1 A - General illumination areas includes.only those illuminated areas that are in the bounds of the Application and are within a square pattern around a luminaire that is six times the luminaire mounting height, with the luminaire in the middle of the pattern, less any areas that are within buildings, under canopies, beyond property lines, or obstructed by signs or other structures. 2005 Nonresidential Compliance Forms CERTIFICATE OF COMPLIANCE (Part 1 of 4) LTG-1 -C I PROJECT NAME DATE La Quinta CountrV Club 10/12/2007 PROJECT ADDRESS 77-750 AVENUE 50 LA QUINTA Building Permit # PRINCIPAL DESIGNER - LIGHTING TELEPHONE JEFFREY C. OVERMYER 949.753.1553 Checked by/Date DOCUMENTATION AUTHOR OMB Electrical Engineers, Inc. TELEPHONE 949) 753-1553 Enforcement Agenc Use GENERAL INFORMATION DATE OF PLANS CONDITIONED FLOOR AREA CLIMATE ZONE 10.13.2007 JBUILDING � 38,650 sq.Ft. 15 BUILDING TYPE © NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM ® CONDITIONED SPACES ❑ UNCONDITIONED SPACES ❑ INDOOR & OUTDOOR SIGNS PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION METHOD OF LIGHTING ® COMPLETE BUILDING ❑ AREA CATEGORY ❑ TAILORED ❑ PERFORMANCE COMPLIANCE ❑ COMMON LIGHTING STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifi tions i I eded to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificqte applies only t buildir lighting requirements. The documentation preparer hereby certifies that the document ton is te. DOCUMENTATION AUTHOR SIGNA URE DATE VICTOR BECERRA \c>.-1 The Principal Lighting Designer hereby certifies that the proposed uilding sign r pres t d in this set of constr c ' ocuments is consistent with the other compliance forms and worksheets, with t cifications a ca c it u itted with this permit application. The proposed building has been designed to meet the I �tt ' i o S110,119, tir& 130 -132, 146, 148 & 149 of Title 24, Part 6. SAFETY DEPT. The plans & specifications meet the requirements of Part 6 (Sections 10-103a). BUILDING O �D Y ❑ The installation certificates meet the requirements of Part 6 (10-103a 3). AP P R -rfj�N ❑ The operation & maintenance information meet the requirements of Part 6 (10.103c). FOR CONSTRUC Please Check One: (These sections of the Business and Professions Code are Tinted in full in t e Nonres' t I 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and P fe Is docu docu n responsible for its preparation; and that I am licensed in the State of California as a civil gineer, or I am a licensed architect. ❑ 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. ❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Busine an Professions Code Sections 5537, 5538 and 6737.1. PRINCIPAL LIGHTING DESIGNER - NAME SI DATE L)C. # JEFFREY C. OVERMYER -4- LIGHTING MANDATORY MEASURES Indicate location on plans of Note Block for Mandatory Measures LIGHTING COMPLIANCE FORMS & WORKSHEETS Check box if Worksheet is Included ® LTG-1-C, Parts 1 of 4 and 2 of 4: Certificate of Compliance. Part 1 of 4 and 2 of 4 are required for all submittals Gil LTG-1-C, Part 3 of 4: Certificate of Compliance. Part 3 of 4 submittal is required only if Control Credits are claimed ®LTG-1-C, Part 4 of 4: Certificate of Compliance. Part 4 of 4 submittal is required when lighting controls are installed 1ZLTG-2-C: Indoor Lighting Schedule ❑LTG-3-C: Portable Lighting Worksheet ®LTG-4-C: Lighting Controls Credit Worksheet®LTG-5-C: Indoor Lighting Power Allowance ❑LTG-6-C: Tailored Method Worksheet 29 2008 rJAN ❑LTG-7-C: Room Cavity Ratio Worksheet ❑LTG-8-C: Common Lighting Systems Method Worksheet 0LTG-9-C: Line Voltage Track Lighting Worksheet EnergyPro 4.4 by EnergySoff User Number. 6861 Job Number. 70072 Page:1 of 1 D ''OEF/tom" 2'% CERTIFICATE OF COMPLIANCE (Part 2 of 4) LTG-1-C PROJECT NAME DATE - La Quinta Country Club 10/12/2007 INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES ' INSTALLED WATTS INSTALLED LIGHTING, CONDITIONED SPACES (From LTG-2-C) 54,247 PORTABLE LIGHTING (From LTG-3-C) 0 LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG-4-C) 4,541 CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 1 49,706 INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG-2-C) • 0 ' LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG4-C) 0 + UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0 ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES X❑ COMPLETE BUILDING METHOD (From LTG-5-C) ALLOWED ❑ AREA CATEGORY METHOD (From LTG-5-C) WATTS, ❑ - TAILORED METHOD (From LTG-5-C) ALLOWED LIGHTING POWER 50,245 t ALTERNATE COMPLIANCE ❑ PERFORMANCE METHOD COMMMON LIGHTING SYSTEM (From LTG-8-C) ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG-5-C 0 MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL IDENTIFICATION CONTROLTYPE (Auto Time Switch, Dimming, etc.) 4.4 by EnergySoft User Number: 6861 Check If SPACE CONTROLLED Daylighting CERTIFICATE OF COMPLIANCE (Part 3 of 4) LTG-1-C PROJECT NAME DATE La Quinta Country Club 10/12/2007 CONTROLS FOR CREDIT IN CONDITIONED AND UNCONDITIONED SPACES CONTROL LOCATION (Room # or Dwg. #) Lower Level Lower Level Lower Level Lower Level Lower Level Lower Level Lower Level Lower Level Lower Level Upper Level Upper Level Upper Level Upper Level Upper Level Upper Level Upper Level Upper Level Upper Level Upper Level CONTROL IDENTIFICATION CONTROLTYPE (Occupant, Daylight, Dimming, etc.) Dimming - Multi -scene Dimming - Multi -scene Dimming - Multi -scene Dimming - Multi -scene Dimming - Multi -scene Occ Sensor - — 250 s ft Dimming - Multi -scene Dimming - Multi -scene Dimming - Multi -scene Dimming - Multl-scene Dimmin - Multi -scene Dimmin - Multi -scene Dimming - Multi -scene Occ Sensor - — 250 s ft Dimming - Multi -scene Dimming - Multi -scene Dimming Multi -scene Dimming - Multi -scene nimminn - hm iiF,ann CONTROLLED TYPE A OF LUMINAIRES Q 50 15 1 114 2 115 1 EE3 63 X 23 C2 62 ME ' 38 B 59 Q 9 15 1 118 3 119 1 X 38 C2 49 ME 15 E 33 B 46 A 8 NOTE TO FIELD EnergyPro 4.4 by EnergySDft User Number. 6861 Job Number. 70072 Page:3 of 10 ]CERTIFICATE OF COMPLIANCE (Part 4 of 4) LTG-1-C PROJECT NAME La Quinta Country Club DATE ' 10/12/2007 Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for lighting systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that require an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that'describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments:., Before an occupancy permit is granted for a newly constructed building or space, or a new lighting system system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for. Code Compliance. In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building department that: A. Certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of§ 10-103(b) and Title 24 Part 6. Test Description I Test Performed UV: ❑ LTG-2-A: Lighting Control Acceptance Document - Occupancy Sensor Acceptance - Manual Daylight Controls Acceptance - Automatic Time Switch Control Acceptance Equipment requiring acceptance testing ❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document Equipment requiring acceptance testing EnergyPro 4A by EnergySoft User Number. 6861 Job Number: 70072 Page:4 of 10 INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG-2-C PROJECT NAME DATE La Quinta Country Club 10/12/2007 INSTALLED LIGHTING POWER FOR CONDITIONED SPACES Luminaire Lamps/Ballasts Installed Watts C D I E F G H I J 'ir ��3 �i�r2 3d3 3a f°0 r c Z�'y, N b N U) _,.� '�O M N y 'N'" fgD _,� �. �� C imi __ y O� _ X�� y M Name Type Description fD `�° o m 1D '' mCL v` A 75w - Q75 -Par 38 (1) 1 75 75.0 X 16 1.200 B 50w Surface Mount incandescent (1) 50 50 0 05 5,250 BB 30OW CHANDELIER (1) (1) 0OW 4 75 300.0 X 1 300 C2 50w Surface Mount Incandescent (1) aw 1 50 50.0 X 111 5.5501 D (2) 4 R Fluorescent T8 Rapid Start Elec 3 1.0, 62.0 X 14868 E 37w Low Voltage Halogen Mag 0 3 0 X 49 1,813 EE1 Architectural Cathod Lighting 8 18.0 X 29 522 EE2 Architectural Cathod Lighting 18.0 x 47 846 EE3 Architectural Cathod Lighting 8 18.0 X 63 1 134 EE4 Architectural Cathod Lighting 18 18.0 X 1 124 2,232 F 37w Low Voltage Halogen Mag 371 1.0 37 0 37 G (3) 4 ft Fluorescent T8 Rapid Start Elec 0 93.0 X 45 4.185 GE (3) 4 ft Fluorescent T8 Rapid Start Elec 3 3 0 93.0 651 H (2) 4 ft Fluorescent T8 Rapid Start Elec 0 6 HE (2) 4 ft Fluorescent T8 Rapid Start Elec 2 0 62.0 X 2 44 11 Sconce nw 1 40 40.0 X 2 80 110 225W CHANDELIER (1) 5 3 7 225.0 X 1 225 111 4Ow Wall Mount Incandescent 1 40 40.0 X 4 160 112 40w Wall Mount Incandescent 4 40.0 X 2 80 113 60w Wall Mount Incandescent 60.0 X 1 60 114 36OW CHANDELIER 6 g 360.0 X 2 720 115 40w Wall Mount Incandescent 4OW1 0 40 O X 1 0 116 120W CHANDELIER (1) 4OW Lamp 3 0 120.0 � 1 120 117 120W CHANDELIER (1) OW Lam 3 40 120.61 X 7 840 PAGE TOTAL 29 269 BUILDING TOTAL (sum of all pages) 54,247 PORTABLE LIGHTING (From LTG-3-C) CONTROL CREDIT (From LTG-4•C) 4 541 ADJUSTED ACTUAL WATTS 49 7O6 I EnergyPro 4.4 by EnergySoft User Number. 6861 Job Number. 70072 Page:5 of 1 D I INDOOR LIGHTING SCHEDULE (Part 1 of 2) ' LTG-2-C PROJECT NAME DATE La Quinta Country Club 10/12/2007 INSTALLED LIGHTING POWER FOR CONDITIONED SPACES Luminaire Lam s/Ballasts Installed Watts C D E F G H 1 J cdr �.�o comic 1.m3 c 3.om o wm r z �'03 3 .gym 'p ..0 'C7 y y _CD so a ' '�wm .: q CD Name Type Description ° fD CD ° m Y07No y O. 118 50w Recessed Incandescent (1) 50W 50 50.0 X 3 150 119 120W CHANDELIER (1) MIAM 3 40- 120.0 X 1 120 12 30OW CHANDELIER (1) (1) 30OW 4 75 300.0 X 4 1,200 120 40w Wall Mount Incandescent 40W 1 40 40.0 X 4 160 121 40w Wall Mount Incandescent 1 0 40.0 X 2 80 122 120W CHANDELIER (1) 3 0 3 360 123 40w Wall Mount Incandescent 1 0 40 0 6 240 13 40w Wall Mount Incandescent 1 0 $ 320 14 40w Wall Mount Incandescent 0 40.0 X 2 80 15 120W CHANDELIER (1) 3 40 120.0 X 2 240 16 40w Wall Mount Incandescent 1 40 40.0 X 16 640 17 40w Wall Mount Incandescent 18 40w Wall Mount Incandescent 1 4040,0X 80 19 40w Wall Mount Incandescent 0 40.0 4Q J (( Compact Fluorescent Triple 4 Pin Elec2w 3 1,0 35.0 X 4 140 K (2) 4 ft Fluorescent T8 Rapid Start Elec 2 32 1.0 62.0 X 22 1.364 KE (2) O ft Fluorescent T8 Rapid Start Elec 3 2 32 1.0)62 0 X. 7 434 LE (2) 4 ft Fluorescent T8 Rapid Start Elec 2 32 0 62.0 X 5 310 M (1) 32w Compact Fluorescent Triple 4 Pin Elec 3 1 3 0 35.0 210 7.350 ME (1) 32w Compact Fluorescent Triple 4 Pin Elec O 35,OX 53 1 855 N 50w Low Voltage Halogen Mag 50-Wall Lamp 11 50 1.01 55.0 X ' 5 275 Q. 45w per ft Track Light 5 45 0) 59 2 655 S (2) 26w Compact Fluorescent Triple 4 Pin Elec s 2 26 1.0 55.0 X 9 495 SE (2) 26w Compact Fluorescent Triple 4 Pin Elec 2 26 1.0 55.0 X 1 55 PAGE TOTAL 19 083 BUILDING TOTAL (sum of all pages) 54,247 PORTABLE LIGHTING (From LTG-3-C) CONTROL CREDIT (From LTG-4-C) 4 541 ADJUSTED ACTUAL WATTS 49 706 EnergyPro 4.4 by EnergySoft User Number. 6861 Job Number. 70072 Page:6 of 10 1 INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG-2-C PROJECT NAME DATE La Quinta Country Club 10/12/2007 INSTALLED LIGHTING POWER FOR CONDITIONED SPACES Luminaire Lamps/Ballasts Installed Watts C D E F G H I J Name Type Description `nor c d Z Cr '" `; o m r W Z g'yv '~° M E r md v wm N. r Z 503 S L� � a T 50w Low Voltage Halogen 50 Watt Lamp 1 50 1.0 54.0 X 10 540 V3 (1) 3 fi Fluorescent T8 Elec 1 25 1 0 2 0 X 9 323 V4 (1) 4 ft Fluorescent TS Rapid Start Elec 32T8 1 32 -1.0 32.0 X 22 704 X (2) 24w Linear Fluorescent T5 HO Elec F25T5HO 2 24 1.0 52.0 X 61 3.172 XE (2) 24w Linear Fluorescent T5 HO Elec 2 24 1.0 52.0 X 3 156 PAGE TOTAL 5 895 BUILDING TOTAL (sum of all pages) 54,247 PORTABLE LIGHTING (From LTG-3-C) J CONTROL CREDIT (From LTG-4-C) 4 541 ADJUSTED ACTUAL WATTS 49 7O6 EnergyPro 4.4 by EnergySoft User Number. 6851 Job Number. 70072 Paae:7 of 10 1 LIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG-4-C CONTROL CREDITS FOR CONDITIONED SPACES PROJECT NAME DATE La Quinta Country Club 10/12/2007 A B C D E I F I G H I J ROOM # ZONE ID CONDITIONED AREAS LIGHTING CONTROL DESCRIPTION PLAN REF. ROOM AREA (SF) DAYLIGHTING WATTS OF CONTROL LIGHTING LIGHTING ADJUST. FACTOR' CONTROL CREDIT WATTS (H X 1) WINDOW WALL RATIO GLAZING VLT SKYLIGHT EFFECTIVE APERTURE' Lower Level Dimming - Multi -scene Q 22,6501 2,250 0.20 450 Lower Level Dimming - Multi -scene 15 22,650 120 0.20 24 Lower Level Dimming - Multi -scene 114 22,650 720 0.20 144 Lower Level Dimming - Multi -scene 115 22,650 40 0.20 8 Lower Level Dimming - Multi -scene EE3 22,650 1,134 0.20 227 Lower Level Occ Sensor ft- <= 250 X 22,650 1,196 0.20 239 Lower Level Dimming - Multi -scene C2 22,650, 3,100 0.20 620 Lower Level Dimming - Multi -scene ME 22,6501 1,3301 0.20 266 Lower Level Dimming - Multi -scene g 22,6501 2 950 0.20 590 Upper Level Dimming - Multi -scene Q 16 OOo 405 0.20 81 Upper Level Dimming - Multi -scene 15 16,000 120 0.20 24 Upper Level Dimming - Multi -scene 118 16.000 150 0.20 30 Upper Level Dimming - Multi -scene 119 16,000 120 0.20 24 Upper Level occ sans ft- <= 250 X 16,000 1,9761 0.20 395 Upper Level Dimming - Multi -scene C2 16,000 2 450 0.20 490 Upper eve mm ng - u Pscene ME 16,000 525 0.20 105 Upper eve Dimming g - Multi -scene E 16,000 1,221 0.20 244 Upper Level Dimming - Multi -scene g 16,0001 2.300 0.20 460 Upper Level Dimming - Multi -scene A 16,0001 600 1' 0.20 120 1 From Equation 146-A 2 From Table 146-A PAGE TOTAL 4 541 BUILDING TOTAL 4 541 Enter In LTG-2-C: Lighting Control Credit EnergyPro 4.4 by EnergySoR User Number. 6851 - Job Number. 70072 Page:8 of 10 I INDOOR LIGHTING POWER ALLOWANCE LTG-5-C PROJECT NAME La Quinta Country Club DATE 10/12/2007 ALLOWED LIGHTING POWER Choose One Method COMPLETE BUILDING METHOD - CONDITIONED SPACES WATTS PER SF COMPLETE BLDG. AREA ALLOWED WATTS BUILDING CATEGORY (From Section 146 Table 146-B) Comp Bldg Convention Centers 1.30 38,650 50,245 AREA CATEGORY METHOD - CONDITIONED SPACES WATTS PER SF AREA (SF) AREA CATEGORY (From Section 146 Table 146-C) ALLOWED WATTS PAGE TOTAL BUILDING TOTAL AREA WATTS TAILORED METHOD - CON DITIONEDSPACES TOTAL ALLOWED WATTS (From LTG-6-C or from computer run.) UNCONDITIONED SPACES Complete Building and Area Catagory Methods Category (From Section 146 Table 146-B&C) WATTS PER SF AREA (SF) ALLOWED WATTS PAGE TOTAL BUILDING TOTAL WATTS AREA TAILORED METHOD - UNCONDITIONED SPACES TOTAL UNCONDITIONED SPACES ALLOWED WATTS (From LTG-5-C and LTG-6-C) EnergyPro 4.4 by EnergySoft User Number. 6861 Job Number. 70072 Page:9 of 10 ILIGHTING MANDATORY MEASURES LTG-MM� ,IPROJECT NAME ' DATE La Quinta Country Club 10/12/2007 DESCRIPTION Designer Enforcement a§131(d)1 For every floor, all interior lighting systems shall be equipped with a separate automatic control to shut off the lighting. This automatic control shall meet the requirements of Section 119 and may be an occupancy sensor, automatic time switch, or other device capable of automatically shutting off the lighting. §131(d)2Override for Building Lighting Shut-off: The automatic bullding shut-off system Is provided with a manual, accessible override switch in sight of the lights. The area of override is not to exceed 5,000 square feet F§119(h) Automatic Control Devices Certified: All automatic control devices specified are certified, all alternate equipment shall be certified and Installed as directed by the manufacturer. a§111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for the project are certified and listed in the Directory'. All installed fixtures shall be certified. §132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: ,All one and three lamp fluorescent fixtures are tandem wired with two lamp ballasts where required by Standards Section 132; or all one and three lamp fluorescent fixtures are specified with electronic high -frequency ballasts and are exempt from tandem wiring requirements. 0 §131(a) Individual Room/Area Controls: Each room and area in this building is equipped with a separate switch or occupancy sensor device for each area with floor -to - ceiling walls. F§131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 square feet and more than 0.8 watts per square foot of lighting load shall be controlled with bi-level switching for uniform reduction of lighting within the room. 0 §131(c) Daylight Area Control: All rooms with windows and skylights that are greater than " 250 square feet and that allow for the effective use of daylight in the area shall have 50% of the lamps in each daylit area controlled by a separate switch; or the effective use of daylight cannot be accomplished because the windows are continuously shaded by a building on the adjacent lot. Diagram of shading during different times of the year is included on plans.' §131(e) Display Lighting. Display lighting shall be separately switched on circuits that are 20 amps or less. y EnergyPro4.4 by EnergySoft User Number. 6861 Job Number. 70072 Page:10 of 10 ICERTIFICATE OF COMPLIANCE . (Part 1 of4) LTG-1-Cl rPROJECT NAME DATE La Quirlta Country Club 11/13t2008 PfiQIEC T AMPESS _ 77-750 AVENUE 50 LA QUINTA._......_............................__._...... PRINOPAL DESIGNER - LIGHTING TELEPH0NE 6uildhg Ponnit JEFFREY C. OVERNiYER 949.753.1553 DOCUI ENfATiONAUTHOR 1 OMB Electrical Engineers, Inc. TEIEPHOW (949) 753-15M Checked-byDate . trfbrcnma1A GENERAL INFORMATION IDATEOFPLANS BUILDIW7CONDMOW-DFLOOR AREA 'CUMATEZOW- j 10.13.2007j ._. __...._........ 38,650 sgFt 15 BUILDING TYPE 21 NONRESIDENTIAL HIGH RISE RESgEN1TAt HOTELJMOTELGUEST ROOM _CONDITIONED SPACES C UNCONDMONFD SPACES INDOOR & OUTDOORSIGNS (PHASE OFCONSTfd1CT1ON NEINCONSTRU'TION r AMMON ❑ ALTERATION I METHOD OF tJGHT1NG %X{ COMPLETE BUILDING J_ AREACATEGORY TAILORED C PERFORMANCE __._......_......, COPAPLIANC! i� COMMONLIGHTiNG STATEMENTOF COMPLIANCE This Certificate ofCoaplanoelists the building features aid performance specffi dins needed tocompiywithTlle24, Parts 1 and tiofthe Calfomia Code Regulations. This certificate apples only jlding lighting requirerrents. ;The documentation prep@rer hereby certifies that the documentation isaccurate t urate rrplea l DOCUMENTATION AUTHOR SIGNATUR DATE ;The Prndpal Lighting Designer harebycertifiesthat the proposadbuilcingdesignrjpr� anted in titsseto catsirLctiondocurients is consisteniwih the other ocmpiance forms and Aorksheets, with the specifications, anti with arty otttar calculations sLbmilted fifth il:this permt application. The proposed builcrrg has beers designed to meet the ligWig reT' irements contained in Spedions 110,119, 130-132,146, 148 & 149 ofTilie24, Part & 5The plans & speci<icaibnsrneat the requbmsnts of Pa•t6 (Seclms 10-1034 Thai inst dletkxi certificates meet the requi errents of Part 6 {10-1039 3). C The oprrat on & nnaMi erranoe infomxton meet therequ�rerents of Pat 6 Ill 0-1 03a). Please Check One: (These sections of the BLIsInes5 and Profess ions Code are pri-ited in full in the Nonraswential Manual.) r I herettyailirmthatl an db)beunde•the p-wrtiions ofOMsa -i 3 ofthe ELyiessandPr fessbrs Cade tosign, Ills dooirrent as thepersm Iu'pulsicwiu xsprewillor6arooL'rakr an'osnsecinTie 57atewuauanaasaGm] enynaerorejectriCElenquiec�,orIamal► ns' -da"cnr4.-L t l I atfirmthat I amellgble Lnderthepro/l5ons ofDvWon 3of tie Buslress and F7obssms Cede by Section 5537.2 or6737.3 to sign th(sd=rne" as fie pason respomble for Ispreparatbn;and hat Iamalbeiisedoontracbrpa~Iormhgih"s v, rc. l Iaffirm IlIadame!gblernderthe ecempiontoDivikn3oftre •"nessanditfesslowCodvtosgrithtsdowmertbacatseApatanstoa stnrdure or type of veakdosaibed as mmptpursttant b B n Prds edbns 553Z 5538 and6737.1. PRINCIPAL UC+MNG DESIGNER- NAME ; S JEFFREY C. OVERMYER ' JDATE l uC. # R- Vf -ce i E Cl j LIGHTIN G MANDATORYM EASUI RES Indicate location on pans of Note Block for Mand ures LIGHTING COMPLIANCE FORMS & WORKSHEETS Check boxft-mtsheat is indida X91TG1-C, Parisi of4 avid 2of4: Certificate of Compliance. Part i of and 2 of4 are required for all submittals X!LTG-1-C, Part 3 of 4: X LTG-1-C, Part4 of 4- kLTCr2 C: �iLTG3•C: XiLTG-4-C: RLTG-5•C: OLTG•G-C: -OLTG7--C: LTG-S-C: OLTG-9•C: Ceitificate of Cbmplance. Part 3of 4 sub miitaI is required only if Control Credits are claimed Certtica's of Compiarc a Part 4of4 sub rrittaI Is required W-en I Mng coriircls are installed Indoor Ll ftng Schedule Portable Ughting Warksheet Lighting Controls- Credit Worksheet Indoor Lighting Power Alovrance CITY OF LA QUINTA Tailored Whod Worksh t Roan Cavdy Ratio Wotksheet BUILDING & SAFETY DEPT. Comron LighliN Systems Method Vdork t APPROVED Line Votageirack lialttina Worksheat UserNumber,5WI CERTIFICATE OF CONPLIANCE (Part 2 of 4) LTG1-C ROJBCT NAME DATE La Qui r>ta Country q ub 11 /132008 IINSTALLED INDOOR LIGHTING POWERFCR CCNDITIONEDAND UNCCNDITIONEDSPACES INSTALLED WATTS INSTALLED LGHTINGs CONDITIONED SPACES (From LTG-2-C) 57770 PORTABLE LIGHTING (From LTG-3�C) 0 LIGHTING CONTROL CREDIT, CONDITIONEDSPPCES (From LTG-4-C) CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 49,475 INSTALLEDLIGHTING, UNCONDITIONED SPACES (From LTG 2-C) 0 LIGHTING CONTROL CREDIT, UNCONDITICNED SPACES (From LTG-4-C) 0 ` UNCONDITIONED SPACE ADJUSTED INSTALL EDLGHTINGPOWER 0 ALLOWED INDOOR LIGHTING POWER FOR CONDI-nONEDSPACES ❑X COMPLETE 13ULONG METHOD (From LTCr5-C) ALLOWED ❑ AREA CATEGORY METHOD (From LTG-5-C) WATT$ ❑ TAILCRED METHOD (From LTGb-C) ALLOIAED LIGHTING POVIAER F 50,244 ❑ PmmRMNVCE METHOD ❑ COMMMONLIGHTING SYSTEM (From LTG$-C) ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG-5 o CONTROL LOCATION CONTROL CONTROL TYPE Check I NOTE TO (Room#) IDENTIFICATION (Auto Time Switch, Dirmvng,etc.) SPACECONTROLLED Dafthting FIELD SEE PLANS DIMMER SWITCH SEE PLANS SEE PLANS ® OR M OCCUPANCY SENSORS SEE PLANS r EnergyPro4.4 byEnergySoft UserNumber.6861 Job Number.70072 Pege:2of24 �ERTI FICATE OF COMPLIANCE (Part 3 of 44) LTC-C T NAME DATE La Qui rrta Cou >Itry q ub 11 / 1320( (CONTROLS F CONTROL DENTIFlCATION / Ladies Massa a 128. Wbn's Massage 140 M'n's Ma ssa a 140 Boardroom i07lVbn's-rvbssage 140 Boardroom 207 Work Room 215/Stor.21 ® OR m ' Work Room 215/Stor. 21'® OR m .i Woman Ertp. 168JToiet EMI m CCNTRCL TYPE (Occupant, Daylight, Dimming, etc.) Dimming - Mult-scene Dimnirp - Mil&scene Dimrrin -Mufti-scene Dimni - Mil&scene Dirrmi - Mil&scene Dimni - Mil&scene Dirrmi - Mjlti•scene Dirrmi - Mil&scene Dirrmi - Mi4scEne Dinmi - MA&scene Dinmi - W l&scene Dirrmi - M16scene Dimni - Mil&scene Dimni - Mjlt�scene Dinmi - Mi6scene Dirrmi - Mjlt�scene Dimni - Mibscene Dirrmi - Miltfwene Dimri - Mil&scene Dirrmi - Mi4scene Dinmi - Mil&scene Dimni - Milt scene Ooc Senses - 250 sqft Ooc Sensor - 250 sqft Ooc Sensor - 250 §gft WMNAIRM D LLMINAIRES C2 9 C1 7 LT18 2 , C1 6 B 18 EE1 14 LT 18 2 J 2 J - 3 J 4 E E1 3 X 12 ME 15 E E1 2 X 4 LT2 3 2 LT25 2 EE1 8 LT25 1 EE1 8 LT25 3 ME 1 EEI 8 2 Q 8 H 2 D 1 HE 1 NOTE TO FELD �ERTIFICATEOFCOIVPLIANCE (Part 3 of 4) LTG-1-lc PROJECT NAIVE " DATE _ La Quinta CoLntry dub 11/132008 CONTROL LOCATION (Room # or Dv4 #) Women Emp 168/Toilet Nbn Errplo ee 170To0e 11 kbn ErTolo7vee 170To0e Lades Zs1bwm236 Lades Resbwm236 Lades Restroom236 Lades Restroom236 Concourse232 Conaourse232 Lades Restroom231 Lad es Reshwm231 Lad es Restroom 231. Wn's Restroom 230 Nbn's Restroom 230 Nbn's Restroom 230 Nbn's Rectroom 237 Nbn's Restroom 237 Nbn's Restnpom 237 Lades Restroom 172 Lades Restroom 172 Nbn's Restroom 173 Nbfis Restroom 173 Restroom 119 Lng 5 ' Ie PrivateW 235. Pd\rateDnn 235 Private Din ing 235 PrivateDh ing 235 CONTROLTYPE (Oceupard, Daylight, Dimming, etc.) Oec Sensor - — 250 sgft Ox Sense - <= 250 sgft Oec Sensor - <= 250s ft Ox Sensa.--250 sqft Ox Sense - r 250 sqft Ox Sense - — 250 sqft OX Sensa - — 250 sqft ` Dirrmi - Mjlti scene Dimni - NUlt�sceie Ox Sensa - <= 250 q ft <_. Ooc senscr - <= 250 sqft Ox Sense -<= 250 sqft Ox Sense - r 250 sqft Ox Sense - <= 250 sqft OX Sena - <= 250 sqft Ox Sensor - <= 250 sqft - Ox Senscr Ox Senscr 250 sqft — 250 mft Ooc Sensa - <= 250 sqft Ox Sensor - <= 250 sqft Ox Sensor - <= 250 sqft Ooc Sensa - <= 250 ft Ox Senscr -- 250 sqft Dinmi - IVUbsceie Dimni - M.i6sceie Dirrmi - Idibscere . Dirrmi - Nb6sceie LUMNAIRES CONTROLLED N(ME 2 M,NE 2 H HE 1 J 1 IT 15 4 E E1 2 ME` 8 LT24 1 ME 6 ME 12 LT 15 2 ME 12 J 2 LT 15 2 J 2 IT15 2 . 2 M J 2 ME 8 J 1 ME 7 ME 11 2 18 IT 1 6 B C2 7 C2 2 C2 5 C1 2 CERTIFICATE OF COMPLIANCE (Part 3 of 4) LTG'1-C PROJECT NAME La Qui rta Country a ub DATE 11/132008 CONTROL TYPE (Occupant, Daylight, Dimming, etc.) Dimmng - Mull -scene Dimnirg - MjltFscere Diming -MuM-scene Dimni - MiWscene Dimni - Mjlt�scete Dirrmi - Malt�sccne Dimni - Mjlti-scene Dimni - MiWscme Dimni - MiWscene Dinmi - Mjlt�scene Dirrmi - MjltHscwe Dimni - Milt�sceie Dimni - MiWscEne Ooc Sense - - 250 sqft 00c Sensor - - 250 sqft O0c Sensor - r_ 250 sqft Dirmi - MiltFscene Dimni - Mi6scere Dirrmi - NI 6scene Dirrmi - Mi6scene Dinmi - W6I scene - r_ 250 sqft Ooc Sensor - - 250 sqft Ooc Sensa - <-- 250 sq ft Dimming - MJlti-scere Dimnirr7 - MJltFscene CERTIFICATE OF COMPLIANCE (Part 3 of 4) LTG1-C 3ROJMT NAME • DATE LaQui nta Country a ub 11/132008 �CERTIFICATE OF COMPLIANCE (Part 3 of 4) LTG1-C T NANE La Quirta CountryClub DATE 11113f101 UNOONDI110N ISPACES CONTROLTYPE NOTE TO Sant, Daylio,Diffm etc.) FELD �WnFICATE OF CONPLIANCE (Part 4 of 4) LTG1-C MOJECT NAME La Qui r>ta Country a ub DATE 11 /132008 Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for lighting systems. The designer is fequi red to check the boxes by al I acceptance bests that apply and list all equipment that require'an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendixof the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments: Before an occupancy permit is granted for a newly constructed building or space, or anew lighting system system serving a building or space is operated for normal use, ail control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building department that: A. Certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of§ 10-103(b) and Title 24 Part 6. Test Dewription jest Perfonned ❑ LTG-2-A: Lighting Control Acceptance Document - Occupancy Sensor Acceptance - Manual Daylight Controls Acceptance - Automatic Time Switch Control Acceptance_ Equipment requiring acceptance testing ❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document Equipment requiring acceptance testing ErergyPro4.4 byErergySoft UserNumber6861 Job Number.70072 Page8of24 INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG 2-C PROJECT NAME DATE La Qui r>ta Country a ub 11/132008 INSTALLED LIGHTING POWER FOR CONDITIONED SPACES Luminaine Lamps/Ballasts Installed Watts C D E F G H I J Name Type Description � 3 33 �� f�l � 0 dv 0 ��.. y m 3 �S4a f� � C:I. 3v ��� @ N m� c n J Y N 3 503 N ��� xAlo a A 75w Recessed hcand escent B 50w Recessed hcand escent (1) 1 50 50.0 X 2 100 B 50w SJrface Nbunt Incandescent 1 50 50.0 X 138 6,900 C1 75w Recessed hcandesoent C2 50w Recessed hcand escent (1) C3 75w Recessed Incandescent 75W 1 6 450 D (2) 4ft Fluorescent T8 Rapid Start Bec E,E1 37w Lav Voltage Halogen Maq EE1 (2) 4ft Fluorescent T8 Rapid Start Bec 3 I.0 62.0 X 44 2,728 F 37w Lmv Voltage Halogen Mag37 Watt Lamp' 1 37 1.0 37.0 X 39 1443 G,GE (3) 4ft FluorescentT8 Rapid Start Bec H (2) 4ft FkioresoentT8 Rapid Start Bec H,HE (2) 4ft FkioresoentT8 Rapid Start Bec HE (2) 4ft Fluorescent T8 Rapid Start Bec J Elec 6N Compact Ruorescent Tripe 4 Rn K (1) 4ft FluorescentT8 Rapid Start Bec 1 32 1. '32.0 X1 20 640 KKE (1) 4ft FkjorescentT8 Rapid Start Bec I,LE (2) 4ft FkjoresoentT8 Rapid Start Bec IT 360W Abmnoe IT11 100W Albmnoe IT13 180W A lomence IT15 4ow SJrface Nbunt Incandescent ET11sowPlbvance 1 160 160.0 X 6 960 240w abHance 1 . 2401 240.01 X 4 960 PAGETOTAL 37,808 BUILDING TOTAL (sum of all pages) 57 770 PORTABLE UGH71NG (From LTG3C) OONTROL CREDIT (From LTG4-C) 8 295 ADJUSTED ACTUAL WATTS 49,475 I EnergyPro4.4 byEnergySdt tkerNumber:6861 Job Nwber. 70072 PaoE9or24 1 INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG 2-C PROJECT NMAE DATE La Quinta Count Club 11/132008 INSTALLED LIGHTING POWER FOR CONDITIONED SPACES, Luminaire Lamps/Ballasts Installed Watts C D E F G H I J r �m R9Y 91F p Nv CrC ,n 03 x— R�1y C-am Name Type Description m y o Yes No LT19 120W allowance LT2 12OW Alowenoe 120 120.0 X. 3 360 LT20 40w Surface Nbunt Incandescent 1 40 40.0 X 10 LT21 12OW Allowance _400 LT22 16OW Alowenoe LT23 40w Surface Mourt Incandesoent low 1 4 160 LT24 24OW Allowance LT25 40w Allowance LT3 40OW Allowance 1 400 400.0 X 2 800 LT4 12OW alowenae .20 1 120 120.0 X 7 840 LT5 80W Allowance LT6. 24OW Allov%enoe M (1)26NCompactRwrescentTd0e4Pn Elec MME (1) 2EW Compact Rwresceit Tribe 4 Pin Elec ME p 2&vCompact RwresceitTdoe 4 Rn Q 45w pe' ft Track Lift rack L nts 1 45 45.0 X 32 1 440 $SE E226ry Compact Rwrescett Trifle 4 Pin T 50w Lav Voltage Habgen V1 (1) 4ft Fluorescent T8 Rapid Start Bec V2 (1) 311 Fluorescent T8 Elec X (2) 24w Linear Fwresce t T5 HO Bec .XXE (2) 24w Linear Fluorescent T5 HO Bec PAGETOTAL 19,962 WILDING TOTAL (sum of all pages) 57, 770 'PORTABLE LIGHTING (From LTG3-C) ODNTROL CREDIT (From LTG4-C) 8 295 t ADJusT® ACTUAL WATTS 49,475 �Er�gypro 4.4 by EnergySdt LberNunber. 6861 Joy Number. 70072 p e;10of24 SLIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG-4-C OL CREDITS FOR CONDITIONED SPACES PRQIEC T NAME La QUI Ilia Coultry ) Ub CATE 11 /13/2008 A B C D E F G H I .l ROOM # ZONE ID CONDITIONED LIGHTING CONTROL PLAN ROOM AREA WATTS OF CONTROL LIGHTING ADJUST. OONTROL CREPT WATTS WINDOW WALL GLA23NG SKYLIGHT EFFECTIVE AREAS CESCHPTION REF. (SF) RATD VLT APERTURE' LIGWNG FACTOR' (HXI) Ladies Card Roan 115 Dimming- Milti-scene 90 Ladies Card Roan 115 D'mrring -Multi-scene C2 1490 450 0.20 105 C1 1490 525 0.20 Ladies Card Roan 115 Dinning - Mutii-scene LT18 1 490 480 0.20 96 Ladies Card Roan 115 Dinning -Multi-scene -Roan � 1 490 450 0.20 90 Ladies Card 115 Dinrnng -Multi-scene 180 B 1,490 900 0.20 Ladies Card Roan 115 Dinning - Multi -scene EE1 1,490 Men's (ardRoom 151 Dinrnng- Multi -scene 868 0.20 174 LT18 1,590 480 0.20 96 Men's Card Room 151 Dinning - Multi�oene J 1,590 Men's Card Room 151 Dinming - Multi -scene 56 020 11 Men's Card Room 151 Dunning - Multi -scene J 1,590 84 0.20 171 1590 112 0.20 22 Men's Card Room 151 Dinning -Multi-scene J 1,590 Men's Card Room 151 Dinrnng- Multi -scene 56 0.20 11 Men's Card Room 151 Dinming- Mutiiacene E E1 1590 111 0.20 22 Men's Card Room 151 Dimming - Multi -scene X 1590 624 0.20 125 M ME 1 590 420 0.20 84 Barber Shop139 Dimming - Multi -scene E E1 140 BarberShop139 Dinning -Multi -scene 74 0.20 15 WneCellar 229 Diming- MUti-scene X 140 208 0.20 42 LT2 140 360 0.20 72 Were Cellar 229 Dinning -Multi-scene Pediare'Manicure 129 Dunning - Mufti -scene E E1 140 74 0.20 15 Pediare'Maniare 129 Dimming -Multi-scene LT25 172 80 0.20 16 EE1 172 496 0.20 99 Lades Massage 128 Dinning - Multi -scene LT25 172 40 0.20 8 Lades Massage 128 Dinrnng - Multi -scene KFen's Massage 140 Dinning - Multi -scene EE1 172 496 0.20 99 Man's Massage 140 Dinrnng - Multi -scene LT25 193 120 0.20 24 M ME 193 28 0.20 6 Man's Massage 140 Dinning - Multi -scene EE1 193 Boardroan 207 Dinning - Multi -scene 496 0.20 99 LT11 580 200 0.20 40 Boardroan 207 Dinning - Mutti-scene F 590.629 Boardroan 207 D'mrnng - Multi�cene � 0.20 126 Work Roan 215Stor. Occ Sensor - <= 250 580 360 0.20 72 Fi 162 1241 0.201.25 F2) ) From Equation 146,A From Table 146,A PAGETOTAL 1 880 BUILDING TOTAL 8 295 Enter in LTG-2-0 Lighting Control O'edit 4.4 by EnergySdt tkerNunber. 6861 Job Number. 7017/2 11of24 .ILIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG-4-C CONTROL CREDITS FOR CONDITIONED SPACES PROJECT NAME Cl ub DOTE 11 i1 _1nnnq A B C D E F G RJOM #0DNrROL ZCNEID CONDITICNED LIGHTING CONTRCL PLAN ROOM AREA :CONTR70L LIGHTING ADJUST. CRECIT WATTS wNDOW WALL GLAaNG SKYLGHT EFFECTIVE AREAS Work Roan 215fStor. CESCRPTiCN Occ Sensor - — 250 REF. (SF) RATID VLT APERTURE' FACTOR' (HXI) 214 p 162 62 0.20 12 WomenE 6 68—rr t Occ ens r - <= 250 HE 126 62 0.20 12 Women E 9168rroi let Occ Sensor - <= 250 M, ME 126 _ 56 0.20 11 Men Errpl1yee 170lroi1 Occ Sens r-<=250 M ME 115 56 0.20 11 Man Errpl 1)r 170rroil 7711 Occ Sensor - <= 250 H, H E 115 62 0.20 12 Ladies FLstroom236 Occ Sensor J 226 ft-<=250 28 0.20 6 Ladies F2stroom236 Occ Sensor LT15 226 ft-<=250 160 0.20 32 Ladies Festroom236 Occ Sensor <-250 ft E,E1 226 74 020 15 Ladies Festroom236 Occ Sensor- <= 250 M ME 226 224 0.20 45 Concourse 232 Dimrring - Multi -scene LT24 290 240 0.20 48 Concourse 232 Dimmng - Multi -scene M ME 290 168 0.20 34 Ladies Fl stroom231 Occ Sensor -<=250sqft M ME 190 336 0.20 67 Ladies F9stm=231 Occ Sensor - <= 250 Ladies Fs?stroom231 ft OccSans J 190 84 0.20 17 n-<=250 LT15 190 80 0.20 16 Ntrn's Restrcom 230 Occ Sens r - <- 250 sqft M ME 190 336 0.20 67 AFn's Restrcom 230 Occ Sensor <= 250 Nfrn's Restroom 230 ft- Occ Sense - <= 250 J 190 56 0.20 11 sgft LT15 190 80 0.20 16 Imn's Restrcom 237 Occ Sensor - <= 250 Nnn's Restrcom 237 sqft56 Occ Sensor - <=sqft 250 J 2D6 0.20 11 LT15 206 80 0.20 16 Nl�n's Restroom 237 Occ Sensor - <= 250 ft E, E1 206 74 0.20 15 Ken's Restroom 237 Occ Sensor - <= 250 Ladies Fesboom 172 Occ Sensor - <= 250 M ME 206 196 0.20 39 Ladies F�stroom 172 ft Occ Sensor - — 250 J 172 56 0.20 11 Nfrn's Restrcom 173 Occ Sensor - — 250 M ME 172 224 0.20 45 ft J 148 28 0.20 6 Nbn's Restrcom 173 Occ Sensor - <= 250 sqft196 M ME 148 0.20 39 Restroom 119 Occ Sensor - <= 250 M ME 230 308 0.20 62 Lng 202JSS03/Grille Dimning - Multi -scene C2 3,850 900 0.20 180 Lng 2021SS 203�Grille Dimming - Mufti scene LT1 3 850 2160 0.20 432 Lng 2021SS 203/Grille Dimrring -Mufti-scene B 3 850 2,950 0.20 590 1) From Equation 146-A 2) From Table 146-A PAGETOTAL Da BUILDING TOTAL 8 295 Enter in LTG-2-0 Lighting Control Credit 4.4 by EnergySdt LkerNunber. 6861 Jab Nunber. 70072 12of24 SLIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG-4-C (CONTROL CREDITS FOR CONDITIONED SPACES PROJEC T NAME DOTE La Qui rrta Country a ub i 111-innnR A► B C D E F G H 1 Jv RDOM # ZONE ID CONDITIONED UGHi1NG CONTROL PLAN ROOM AREA WAT15 OF CONTROL UGHTING ADJUST. ODNTROL CREDIT WATTS WINDOW WALL GLA23NG SKYLIGHT EFFECTIVE AREAS Private Dining 235 DESCRIPTION Dimning- Milli-scen REF. (SF) RATIO VLT APERTURE' UGHTNG FACTOR' (H XI) Private Dining 235 Dinning - Mind -scene C2 1459 350 0.20 70 C2 1,459 100 0.20 20 Private Dining 235 Dirnning - Mind -scene C2 1,459 250 0.20 50 Private Dining 235 Dirnning - Multi -scene C1 1,459 150 0.20 30 Private Dining 235 Denning -Multi-scene LT5 1 459 320 0.20 64 Private Dining 235 Dinning -Mufti-scene LT6 1,459 720 0.20 144 Private Dining 235 Dinning - Multi -scene E,E1 1,459 259 0.20 52 Private Dining 235 Denning -Multi-scene B 1,456 1,250 020 250 Private Dining Entry 23 Dirnning -Multi-scene 172 250 0.20 50 Fitness 103 Denning6 -Multi-scene E E1 2,528 259 0.20 52 Fitness 103 Dimning- Multi -scene M ME 2,528 756 0.20 151 Fitness 103 Dinrririg -Multi-scene X 2,528 Training Studio 104 Denning - Multi -scene 832 0.20 166 M ME 980 448 ' 0.20 90 Training studio 104 Dinrring - Multi -scene X 980 468 0.20 94 Ba 204, Storage 206 Dhrring - Multi -scene F 190 Bar 152 Dinrring -Multi-scene 185 0.20 37 Bar152 Dinning- Multi -scene F 94 1.11 0.20 22 E,E1 94 222 0.20 44 Service Station 153 D'mrring -Multi-scene service Bar 257 Occ Sensor <= 250 B 49 100 0.20 20 ft- M ME 244 196 0.20 39 Laundry 155 Occ Sensoft- � 250 H 129 62 0.20 12 Laundry 112 Occ sensor - <= 250 H 125 Lades Locker Rm. En sqft Dinning - Multi -scene 124 0.20 25 106 E E1 70 37 0.20 7 Hallway2081216/219 Occ Sensor -<=250 sqft H HE 660 372 0.20 74 Lobby201/Reoeption Dinning - Multi -scene C3 1615 225 0.20 45 Lobby 20 1 /Reception Dinning - Multi -scene C3 1,615 Lobby 201/Reception Dirnrring - Mufti -scene LT4 1 615 225 0.20 45 840 0.20 168 Lobby 201/Reception D'mni ng - Multi -scene LT3 1,615 800 0.20 160 Lobby201/Reception Dinning -Multi -scene A 1 615 Elevator Lobby 101 Dunning -Multi-scene 900 0.20 180 LT19 203 120 0.20 24 1) From Equation 146,A 2) From Table 145-A PAGE TOTAL 2186 BUILDING TOTAL 8 295 Enter in LTG 21: Ughting Control O•ecit 4.4 by EnergySaft UserNumber. 6861 Job Nunber. 70072 Paae•13of24 (LIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG4-CI CONTROL CREDITS FOR CONDITIONED SPACES �PRQIECT NWE I DATE La Quinta Country Club 11/13/2008 A B C D E I F G H I J RDCM # ZONEID LIGHTING ROOM DAYLIUMN WATTS OF LIGHTING OONrROL CREPT WNDOW SKYLIGHT CONDITIONED CONTROL PLAN AREA WALL GLAaNG EFFECTIVE CONTROL ADJUST. WATTS AREAS CESCRIPTICN REF. (SF) RATIO VLT APERTURE' UGHrNG FACTOR' (HXI) VeAjbule127 Occ Sensor - — 250 sgft M,ME 471 28 0.20 6 Steam Fbcm143 Ccc Sensor-<=250saft T. 125 216 0.20 43 Show 126 Occ Sensor - <= 250sqft -r 86 108 0.20 22 Show 145 Occ Sensor - <= 250sqft T 324 216 0.20 43 Attendant 154 Dimming - Mufti -scene B 280 300 0.20 60 Attendant 114 Dimming-Muftiscene B 290 450 0.20 90 Dressirg 136 Occ Sensor --250saft M,ME 521 28. 0.20 6 Men's Locker 1% Dimming-Muftiscene t_T17 1,5651 960 020 192 Men's Lccker 1% Dimming - Muftiscene V1 1,565 992 0.20 198 Men's Lccker 156 Dimmi ng - Multiscene V2 1,565 1621 0.20 32 Men's Locker 156 Dimming -Multi scene M,ME 1,565 532 0.20 106 Ladies Locker Fbornn-1 117 Dimming- Mufti scene J 4821 84 0.20 17 Ladies Locker Fbom-1 117 Dimming - Mufti -scene V1 4821 352 0.20 70 Ladies Locker (mom-1 Dimming -Mufti-scene V2 4$2 270 0.20 54 Ladies LockerRbom-1 Dimming-Multisoene117 M,ME 482 112 0.20 22 Ladies Locke117r Fborn>- Dimmng- ultrscene LT22 482 480 0.20 96 dies Lo Lac Or Fbom-2 Dimning- Mtltiscene V21 227 81 0.20 16 Ladies Locker Furor-2 110 Dimming-Muftiscene V1 227 160 0.20 32dies Locker Fmom-2 110 Dimming - Muftisoene M ME 227 56 0.20 11 Ladies Locker Fmom-2 Dimming-Muftiscene110 LTA 227 160 0.20 32 Chef s Office245 occ Sensor- — 250 H 90 124 0.20 25 Computer Room 210 Occ Sens ft- <= 250 p 63 62 0.20 12 Pro Office 134 Occ Sensor - <= 250sqft H 1381 124 0.20 25 Controller 211 Occ Sensor ft- <= 250 H 1981186 0.20 37 Accounting 212 Occ Sensorr - <= 250sQft H 251 186 0.20 37 F&B Manager 218 Occ Sensor- <= 250sqft H 180 186 0.20 37 Office 116 Occ Sensor - <= 250sqft H 146 124 0.20 25 Pro Sbp 133 Dimming - Muftisoene Cl 1408 1 125 0.20 225 Pro Sbp 133 Dunning - Muftisaene C2 1,408 1501 020 30 1) From Equation 146-A Tj From Table 146-A PAGE TOTAL 1 603 BUILDINGTOTAL 8 295 Enter in LTG 2-Q Lightng Control Credit ErergyPro4.4 byErerg7Soft UserNunber.6861 Job Nwftr..70CY72 PaA P,14of24 LIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG4-C CONTROL CREDITS FOR CONDITIONED SPACES PRQJECT NAME DATE A B C D E F G H I J RDOM # ZONEID AREAS LIGHTIPG CONTROL DESCRIPTICN RAN REF. ROOM AREA (SF) WATT50F CCNTROL LIGHrNG LIGHTING ADJUST. FACTOR' ODNrRCL CREDITCONDITICNED WATTS (HXI) WINDOW WALL RATID GLA2IN3 VLT SKYLIGHT EFFECTIVE APERTURE' Pro Stop 133 Dimning- Miltiscene B 1,4081 800 0.20 160 roSbp 33 DUrmmng - u -saene Q 1,408 1,080 0.20 216 Storage 105 Occ Sensor - — 250sqft H 126 124 0.20 25 Storage 259 Occ Sensor - — 250sqft K 186 64 0.20 13 Storage 260 occ Sensor <= 250 K 1491 64 0.20 13 Mectenical Room 180 Occ Sensor - — 250sqft K 240 96 0.20 19 Snack Bar Storage 167 Occ Sensor- <= 250sqft H 180 1861 0.20 37 Dry Storage237 Occ Sensor -<=25osqft H 152 124 020 25 Janitor 159 Occ Sensor - <= 250sqft D 61 62 0.20 12 Closet 107 Occ Sensor - — 250sqft p 120 124 0.20 25 Janitor 123 Occ Sensor - <= 250 47 32 0.20 6 Janitor 255 Occ Sensor - <= 250 46 32 0.20 6 Bevator Equip. 130 Occ Sensor - <= 250 73 32 0.20 6 Elevator Equipment l8D Occ Sensor -<=250 65 1 32 0.20 6 Janitor 209 Occ Sensor - <— 250 KE 425 32 0.20 6 BU k Storage16 DimmngwOoc Sensor D 250 186 0.25 46 Liquor Sora77e 162 Dim-nirg w/occ D 90 62 0.25 16 Mairt. Shop174 Occ Sensor --25osqft H 110 124 0.20 25 Maint. Storage 175 Dimningw/Occ Sensor D 56 62 0.25 16 F i e Storage 158 Occ Sensor - — 250 sqftPro D 72 62 0.20 12 Shop Storage 135 Occ Sensor - — 250ft H 123 186 0.20 37 Storage 111 Occ Sens r - — 250soft H 122 62 0.20 12 Storage 125 Occ Sensor - <= 250sqft KE 27 32 0.20 6 1) From Equation 146-A Z) From Table 146-A PAGETCITAL 748 BUILDIN3TOTAL 8 295 Enter in LTG 2-Q Ugt tng Control O'edt Erergyft4.4 byErnergySoft UserNunber..6861 Jab Nmftr..70072 pana•15of24-- INDOOR LIGHTING POWER ALLOWANCE LTG- 5- PROJECT NAME DATE La Qui rya Country Club 11 /132008 WffTS BUILDING CATEGORY(FromSectbn 146 Table 146-B) COMPLETE ALLOWED PER SF BLDG. AREA WATTS Comp Bldg Convention Centers 1.30 38 650 50 244 UNCONDITIONED SPACES Complete BdlcGngandArea Catagory Methods Category (From Section 146Table 146-B&C) WATTS PER SF AREA (SF) ALLOWED WATTS PAGE TOTAL BUILDINGTOTAL AREA WATTS THOD - UNCONDITIONED SPACES TOTAL UNCONDITIONED SPACES ALLOWED WATTS (From LTG-5-C and LTG-6.C) . 4.4 by ErergySoft L)serNumber. 6861 Job Number. 70D72 Page I6of24 CERTIFICATE OF COMPLIANCE (Part 1 of 2) OLTG -1-C PROJECT NAME DATE La Quinta Country Club 10/21/2008 PROJECT ADD RESS 77-750 AVENUE 50 LA QUINTA PRINCIPAL DESIGNER - LIGHTING TELEPHONE Building Permit # JEFFREY C. OVERMYER 949.753.1553 DOCUMENTATION AUTHOR OMB Electrical Engineers, Inc. TELEPHONE (949) 753-1553 Checked by/Date Enforcement Agency Use GENERAL INFORMATION DATE OF PLANS OUTDOOR LIGHTING ZONE 10.13.2007 LZ1 EJ LZ2 [X] LZ3 ❑ LZ4 FUNCTIONTYPE ® OUTDOORLIGHTING ❑ OUTDOORSIGNS ❑ INDOOR SIGNS PHASE OF CONSTRUCTIONJ NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION STATEMENT OF COMPLIANCE This Certificate of Compliance lists the outdoor lighting system specifications need to complywith Title 24, Parts 1 and 6 of the Califomia Code of Regulations. This certificate applies only to building lighting requirements. The documentation preparer hereby certifies that the documentation is accurate and complete. DOCUMENTATION AUTHOR SIGNATURE U«�-CgT'M-� DATE 1 VICTOR BECERRA 10-22-08 The Principal Lighting Designer hereby certifies that the proposed outdoor lighting and signs design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building has been designed to meet the lighting requirements contained in Sections 110, 119, 130 through 132, and 146,and 149 of Title 24, Part 6. Please Check One: (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this ' document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer or electrical engineer, or I am a licensed architect. ❑ 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. ❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538 and 6737.1. PRINCIPAL LIGHTING DESIGNER- NAME SI RE DATE E8964 JEFFREY C. OVERMYER 10-22-08 c LIGHTING COMPLIANCE FORMS & WORKSH S Check box if worksheet is include I p OLTG- I-C: Certificate of Compliance. Required on plans for all submittals for outdoor light ng. Part 2 of 2 may be incorporated in ules on the plat Either LTG-1-C or OLTG-I-C may be used for signs as follows: Q ^ 1. Use LTG-1 -C if the project consists solely of indoor sons. /V'N 2 Use LTG-1-Cif the project consists d indoor lighting, outdoor or indoor signs, but no other outdoor lighting. 3. Use OLTG-1-C if the prgect consists solely of outdoor signs. 4. Use OLTG-1-C if the prged consists of outdoor lighting, outdoor or indoor signs, but no other indoor lig g. 2 � ® OLTG-2-C: LIGHTING COMPLIANCE SUMMARY. Applicable parts required for ALL outdoor lighting allowances (Except Sig INOLTG-3-C: AREA CALCULATIONS WORKSHEET. Applicable parts-required-for-all'outdoor-area-calcolations. D OLTG-4-C: SIGN LIGHTING COMPLIANCE. Required for all irdernally`and elite r Ily illuminated signs "far both i ndoor and outdoor 'lJ ! r I tJ' 1� e._I"k � r t! 4 t Vi i x1 signs. I EnergyPro4.4 by EnergySoft User Number.68611 BUIL0INJ Nn r. U 7 DEPTPage:17 of 24 A to P"11-511 1,911 . FOR CONSTRUCTION fi' AMIt-,1t V vi CERTIFICATE OF COMPLIANCE - (Part 2 of 2) OLTG -1-C PROJECT NAME DATE La Quinta Country Club 10/21/2008 Li-ghting Schedules on Plans Show that Outdoor Lighting Meets Allowed Lighting Power ❑ X❑ Lighting power allowance forgeneral site illumination on OLTG-2-C Part 1 of 4 Not Applicable X ❑ . Lighting power allowance for local ordinances or for security multipliers on OLTG-2-C Part 2 of 4 Not Applicable x] ❑ Lighting power allowances for specific applications, other than vehicle service stations with canopies on OLTG-2-C Part 3 of 4 Not Applicable ❑ X❑ Lighting power allowances for vehicle service station canopies on OLTG-2-C part 4 of 4 Not Applicable ❑ X❑ Sign lighting compliance on OLTG-4-C Not Applicable + rM an datory Measures on Plans Show that Outdoor Lighting Meets Outdoor Lighting Controls And E ui ment XD ❑ Installed lighting power has been determined in accordance with Section 130(c)1 Not Applicable X❑ ❑ All permanently installed luminaireswith lamps rated over 100 Watts either have a lamp efficacy of at least 60 lumins perWatt or are controlled by a motion sensorper Section 132(a) Not Applicable RI ❑ AllLuminaireswith lamps rated greater than 175 Watts in hardscape area, including parking lots, building entrances, canopies, and all outdoor sales areas meet the Cutoff Requirements of Section 132(b) Not Applicable RI ❑ All permanently installed outdoor lighting meets the control requirements of Section 132(c)1 Not Applicable X❑ ❑ Building facades, parking lots, garages, canopies, and outdoor sales areas meet the Multi -Level Lighting Requirements ofSection 132(c) Not Applicable MANDATORY AUTOMATIC CONTROLS NOTETO FIELD CONTROL LOCATION (Room 4) CONTROL IDENTIFICATION CONTROLTYPE (Auto Time Switch, Dimming, etc.) AREA CONTROLLED MAIN ELECT. LCPS AUTO TIME SWITCH EXTERIOR UPPER LVL ELEC LCP2M, LCP2S AUTO TIME SWITCH EXTERIOR EnergyPro4.4 by EnergySoft User Number.6861 Job Number: 70072 Page: 18 of24 LIGHTING COMPLIANCE SUMMARY (Part 2 of 4) OLTG-2-C Project Name Date La Quinta Country Club 10/21/2008 LIGHTING POWER ALLOWANCES-LOCALORD IN ANCE TABLE 147-C OR SECURITY MULTIPLIERS TABLE 147-D Allotted Watts I Luminaire Lamps/Ballasts Installed Watts A B C D E F G H I J K L M N O P LightingApplication Category Table 147�► ( ) N — . ?gym r N C. ma r o C, erg 'O C �' W 0 xm L7 a x I, or p Description , rac 7 g ,d 0 •. •cm 3 Av r 3 3 7 N L � 7d m' m 3 y �� m r W 3 d 7 „� Cl � m' r 3Ft ° y A ro ) n l7 m c c z c �3 y c A w o F- ID x a z " � rn PARKING LOT _ 114,36 0.07 8,006S1A 150w Hgh Pressure Sodium - S150 1 150 1.0 173.0 X 7 1,211 150wHghPressure Sodium S150 1 150 1.0 173.0 X 8, 1,384 S2 150wHgh Pressure Sodium S150 1 150 1.0 173.0 X 8 1,384 S31 150wHgh Pressure Sodium S150 1 1 1501 1.0 173.0 X 5 865 Checklist ❑ EXCEPTION 1 TO SECTION 147(C )1 8 -There's a law through aIocal ordinance rquring specific light levels, and therefore, the power alowancein Table 147-C were used. EnergyPro4.4 by EnergySoft User Number.6861 Job Number: 70072 Page:19 of24 LIGHTING COMPLIANCE SUMMARY (Part 3 of 4)-- OLTG-2-C flame La Quinta Cc Date 10/21 /2008 LIGHTING POWER ALLOWANCE FOR SPECIFIC APPLICATIONS Table 147-13 - Other than Vehicle Stationwithout Cano jes Allotted Watts I Luminaire Lamps/Ballasts Design Watts A B C D E F G H I J K L M' N O P Lighting Application Category (Table 147. ) a -n �p pia r o D �� XG n� ` m q n is Description 0 T. n 7� a o ' �r 3 m'o c 3 7U) d,o 'm r 3m v o obi ID 2 0 ,� (D c z m o A m m — .. r 3 c 7lT H ° ? > xa) zy — v 3D 5.0 CL , a °obi O m UPPER COV'D TERRACE 16,287 0.501 8,144 AAJ 70w Metal Halide Mag M70 1 70 1.0 92C X 19 1,748 8,013 (2) 26wCompact Fluorescent dple4-Ein_Elec 2 26 1.0 55.0 X 109 5,995 N 50w Lo+v Voltage Halogen 50 Watt 1 50 1.0 54.0 X 5 270 LO\AER COVD TERRACE 4,63. 0.50 Z319 (2) 26wCompact Fluorescent Triple_4-Pin_Elec Lamp 2 26 1.0 55.0 X 36 1,980 2,250, N 50w Lora Voltage Halogen 50 Watt 1 50 1.0 54.0 X 5 270 SERVICE YARD 138 0.50 �0 DStad-F]ec (2) 4 ft Fluorescent T8 Rapid LF32TanA 8 2 32 1.0 620 X 4 248 248 BUILDING FACADE 31,200 0.35 1Q920 (1) 26wCompact Fluorescent B1Triple4P_in_Elec 1 26 1.0 28.0 X 35 980 3,030. B2175N Metal Halide Mag M175 1 175I 1.0 205.0 X 10 2,050 1 EnergyPro4.4 by Energy5 User Number. 6861 Job Number: 70072 Fage:20 of 24 7 ILLUMINATED AREA CALCULATION WORKSHEET (Part 1 of 5) OLT6-3-C PROJECT NAME DATE La Quinta Country Club 10/21/2008 ' Hardscape -Method (i) A. Hardscape for automotive vehicular use. includina oarkina lots. driveways and site roads. A B- C I D E F I G H Lighting Application (fable 147-13) Actual Paved Area +5' perimeter of a d ace rd unpavedland. Includes planmrs and land. In eludes plan 'rs and Landscaped areas less man 1o'wde that are ancbsed byhardscapa on at least 3 sides. Areas (SF) to Subtract fromwfthin the Illuminated Area IlNminatedArea (B - G) Area between poles or luminaires that are > 6 times the mounting height distance + (If Applicable) - Overlapping areas of another application or luminaire, Building Areas Areas obstructed by signs or other structures Subtotal of areas to subtract (C + D + E + F) PARKING LOT 114,357 0 0 0 0 0 1147367 B. Hardscape for pedestian use, including plazas, sidewalks, walkways and bikeways A B C D E F G H L•ghtingApplication (Table 147-B) . Actual Paved Area +5'of unpaved land on either side ofpath oftravel. Shall include at contiguous pavederea before including adlacent grounds, Areas (SF) to Subtract fromwithin the Illuminated Area _ IllumulatedArea (B - G) Area between poles or luminaires that are > 6 tunes the mounting height distance (If Applicable) Overlapping areas of another application or luminaire Building Areas Areas obstructed by signs or other structures Sub total of areas to subtract (C + D + E + F) Checklist ❑ Section 147(c)l B- Each portion of all iIuninated areas has been ass gned only one fighting application, and the applications are consistent with actual use of the areas. Section 1 47(c)t A- General IIumhation arms includes only those illuminated areas that are in the bou rids of the Application and are within a square pattern around a luminaire that is sb( times the lumina ire mounting height, with the luninaire in the middle of the pattern, less any areas that are with buildings, under caropies, beyond property lines, orcbstructed bysign sorother struc_bires. t EnergyPro4.4 by EnergySoft User Number. 6861 Job Number: 70072 Page:21 of24 ILLUMINATED AREA CALCULATION WORKSHEET (Part 3 of 5) OLTG-3-C PROJECT NAME DATE La Quinta Country Club 10/21/2008 Outdoor Sales LotFrontaae and Sales Lot Area A B I C D I E I F G H Gross II Nm mated Area (sq. R) Ifan Ou tloor Sales Frontage Allotment was used, subtract that area from the Cross IWm inated Area Overlapping Areas of Another Application - Sales Lot Area (A - F - G) Mounting heightof Sales Frontage Lumhaees (feet) 3 x B Distance (In plan view) from the frontage luminaire to front edge of Sales Lot Sales Lot Frontage Length (feet) Sales Frontage Area (C- D) x E (sq. t.) Section 147(c)l B- Each portion of all ilumnated areas has bee nassign ad only one lighting application, and the applications are corsisten t with actual use of the areas. ❑ Section 147 (c)2 B- Measured in pan view, only illuminated sections of outdoor sales fronta go areas that are immediately adjacent to the principle viewing location and unobstructed viewing length, and are within 3 mounting heights of the frontage have been used,, tL mnaires qualifying for this albve nce are located in plan view between the principle viewing location and the frontage sales. B. Building Facade Area A B C D E F G H ' Designated Name and Orientation Length Height Gross Area (B x C) Areas (SF) to Su btra cl from within the I ll um era ted A rea Net Area Availablefor Facade Lighting (D - G) Areas covered by signs Area for which Illumination is Obstructed by Other Objects and Area Not Illuminated Sub total (E + F) BUILDINGFACADE 1,040 30 31,200 0 0 31,200 Checklist ❑ Section 1 47(c)l B- Eachportbn ofal illuminated areashas beenassgned only one fighting application, and the applications are consistent with actual use of the areas. ❑ Section 147(c)2 A- Orly facadesareas that are illuminated without obstruction orinterference, by one ormore luminaires, have been used. EnergyPro4.4 by EnergySoft User Number. 6861 . Job Number: 70072 Fage:22 of 24 1 _UMINATED AREA CALCULATION WORKSHEET (Part4 of 5) OLTG-3 PROJECT NAME DATE La Quinta Country Club 10/21/2008` Ornamental Lighting, Canopies, Vehicle Service Station Hardsca a and Outdoor Dining A B C I D I E F G Li!irn§q Apppplication (Tat51e147-B) Gross Illuminated Area of f cation SF Areas SF to Subtract from within the Illuminated Area Illuminated Area B- Area between pdes or luminaires that are > 6 tmes the mounting height distance Overl pi areas onotlier application or luminaire Areas obstructed by signs or other structures Sub total of areas to subtract C+D+E Non-sales Canopy 16 287 0 0 0 0 16 287 Non -sales Canopy 4,638 0 0 0 0 4,638 Non -sales Canopy 1.381 0 0 0 0 1.381 Checld iSt ❑ Section 147 (c)1 B -Each portion of al illuminated areas has been assigned only one lighting application, and the applications are consistent with actual use of the areas. ❑ Section 147 (c)1 C -The area of ornamental lighting includes no more than the total area of, the site a)demalto building. Luminaires used forornamental lighting employ lam rated 100 wafts orless, and are not used to determine LPDforgeneral illumination. ❑ Section 147 (c)2 D -Measured in plan view, the areas of illuminated canopies include the horimnta I projection of the canopies. ❑ Section 147 (c)l F - The area of vehicle service station hardscape includes only iluminated hardsrape areas beyond the horizontal projecton of the canopy in plan view. ❑ Section 147 (c)1 I - The area of outdoord'ning area includes only iluminated hardscape areas used to serve and consume food and beverages. EnergyPro4.4 by EnergySoft User Number. 6861 Job Number. 70072 Page:23 of 24 JUGHTING-MANDAT.ORY MEASURES - LTG-MM PROJECT NAME La Quinta,Count ' Club DATE 10/21 /2008 DESCRIPTION. Designer Enforcement a§ 131(d)1 Forevery floor, all interior lighting systems shall be equippedwith aseparate automatic control to shutoffthe lighting. This automatic control shall.meetthe requirementsof Section 119 and may be an occupancy'sensor, automatic time•switch, or other device capable ofautomatically shutting off the lighting. § 131(d)2 Override for Building Lighting Shut-off: The automatic building shut-off system is provided with a manual, accessible override switch in sight ofthe lights. The area of override is not to exceed 5,000 square feet. a119(h) Automatic Control Devices Certified: All automatic control devices specified are certified, all alternate equipment shall becertified and installed.as directed by the 'inanufacturer: ` X❑ § 111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified forthe ' project are certified and listed in the Directory. All installed fixtures shall be certified. § "131(a) Irid ividuaIRoom/Area. Controls: Each room and area in this building is equipped with a separateswitch or occupancy sensor device foreach area with floor -to -ceiling r walls. § 131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 . square feet and more than 0.8 watts per squarefoot of lighting load shall be controlled with bi-level switching foruniform reduction of lighting within the room. a •. , R § 131(c) 'Daylight Area Control: All rooms with windows and skylights that are greater than 250 squarefeet and that allow for theeffective use of daylight in the area shall'have 50°/u of theaamps in each daylit area controlled by a separate switch; orthe effective i use of daylight cannot'be accomplished because the windows are continuously shaded bya building on the adjacent lot. Diagram of shading during differenttimes of the year is included on plans. L,nj§ 131(e) Display Lighting. Display lighting shall be separately switched on circuits that are 20 amps or l ess. ' Energypro4.4 by EnergySoft User Number. 6861 Job Number: 70072 Page:24 of24 L ' , - TITLE 24, REPORT • Title ,24 Report for: La Quinta Country'Club Clubhouse - 77-750 Avenue 50, r La Quinta, Ca. 92253 Project DDesigher: Linthicum 20789 N. Pima Rd: Suite 250 Scottsdale, , Az. 85225 1. (760) 567-5351 'Report Prepared By:. Ric Krown Desert Energy Services, LLC F P.O. Box 6251 k La Quinta, CA 92248 - (760) 250-2084 t 'Job Number: a 0803-1 Y JUL 2 5 2008 Date By - 2/20/2008. The EnergyPro computer program. has been used to perform.the calculations summarized in this compliance report. This.program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards., This program developed by EnergySoft, LLC - www..energysoft.com. EnergyPro 4.4 by EnergySoft Job Number. 0803-1 : User Number. 2366 EnergyPro 4.4. by EnergySoft Job Number 0803-1 User Number. 2366 4-0 PERFORMANCE CERTIFICATE .OF COMPLIANCE Part 1 of 3 PERF-1 NAME La Quinta Country Club Clubhouse ADDRESS 77-750 Avenue 50 La Quinta LDESIGNER -ENVELOPE Linthicum ITATION AUTHOR Desert Energy Services, LLC TELEPHONE (760) 567-5351 250-2084 DATE 2/20/2008 Building Permit # Checked by/Date GENERAL INFORMATION DATE OF PLANS f/15/oa BUILDING CONDITIONED FLOOR AREA 31,922 sq.Ft CLIMATE ZONE 15 BUILDING TYPE ® NONRESIDENTIAL HIGH RISE RESIDENTIAL HOTELIMOTEL GUEST ROOM PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ❑ ADDITION EXISTING + ADDITIONIALTERATION STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using t e performance compliance approach. The documentation preparer hereby certifies that the documentation is accu t nd co pl Ften DOCUMENTATION AUTHOR Ric Krown SIGNATURE DATE 2/Zo o S The Principal Designer hereby certiys that the proposed building d si n re resented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116, through 118, and 140, 142, 143 or 149 of Title 24, Part 6. ENV. LTG. MECH. ❑ 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect. 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) ENVELOPE COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures ENV-1 Required Forms PRINCIPAL ENVELOPE DESIGNER - NAME SIGNATURE LIC. NO. DATE Linthicum LIGHTING COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures Required Forms Lighting Compliance Not In The Scope Of This -Submittal PRINCIPAL LIGHTING DESIGNER - NAME SIGNATURE LIC. NO. DATE MECHANICAL COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures MECH-1 MECH-2 MECH-3 MECH-S Required s PRINCIPAL MECHANICAL DESIGNER - NAME Polar Barr Air Conditioning SIG U LIC. NO. 1-722'zo I DAT EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:3 of 52 r PO E-RFORMANCE CERTIFICATE OF COMPLIANCE Part'2 of 3 PERF- s PROJECT NAME DATE La Quinta'Count Club -Clubhouse 2/20/2008 Building Orientation Number of Stories Number of Systems Number of Zones r S 180 deg 2 28 fit Conditioned Floor Area 31,922 sqft. Unconditioned Floor Area 8,086 sqft r Conditioned Footprint Area 20,333 sqft. Fuel Type k Natural Gas Orientation Gross Area Glazing Area Glazing Ratio . Front Elevation (S) 3,341 sqft. 461 sqft- 13.8% - Left Elevation (W) 2,975 sgft.. 384 sqft. 12.9% Rear Elevation (N) 5,899 sgft. 1,266 sqft. 21.5% Right Elevation Total Roof - : ' (E) x 4,116 16,331 19,863 sqft sqft. sgft. 529 2,640 230 sgfL sqft. sqft. 12.9% 1.2% ; ' Standard Proposed Lighting Power Density 1.001 w/sgft. " 1.001 wisgft. Prescriptive Env. Heat Loss 4,988 Btuih k 3,472 Btum Prescriptive Env. Heat Gain 454,936 Bhdth F 437,004 atum-F , Remarks: • Standard Building (Compliance) " Run Initiation Time: 02/20/08 10:08:47 Run Code: 121 EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 L - Page:4 of 52 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF-'1 PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008 ZONE INFORMATION System Name Zone Name Occupancy Type Floor Area (sgft) Inst LPD (W/sf)1 Ctrl. Credits (W/sf)2 Allowed LPD Proc. Loads (V/sf) Area IS3 Tailored /s 4 Packaged Heat Pump-1 Dining Dining 1,125 "1.10 Entry Lobby, Main Entry 141 '1.50 Halfway Corridor/Restroom/Su port 456 '0.60 Unconditioned All Others 2,138 -0.60 Packaged Heat Pump-2 Kitchen Kitchen, Food Preparation 1,642 -1.60 4.000 Office Office 91 '1.20 Hall Corridor/Restroom/Su ort 173 '0.60 Storage Commercial, Industrial Storage 458 '0.60 Unconditioned All Others 405 '0.60 Packa ed Heat Pumps-3 & 4 Storage Commercial, Industrial Storage 216 '0.60 Dining Dining 1,724 •1.10 Hall Corridor/Restroom/Support 346 "0.60 Packaged Heat Pumps 5 & 6 Lobby Lobby, Main Entry 1,286 -1.50 Support Corridor/Restroom/Support 1,178 -0.60 Packaged Heat Pump-7 Storage Commercial, Industrial Storage 36 `0.60 Bar Bar, Cocktail Lounge, Casino 274 '1.10 Lounge Lounge, Recreation 1,154 '1.10 Packaged Heat Pump-8 Meeting Room Convention/Conference/Meeting 616 '1.40 Packaged Heat Pump-9 Offices Office 461 '1.20 Wafting Area Waiting Area 158 '1.10 Notes: 1. See LTG2-C 2. See LTG4-C 3. See LTG-C 4. See LTG-" (items marked with asterisk, see LTG-2 -C by others) (by others) Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the Items specified In this checklist These items require special written justincation and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted_ The exceptional features listed In this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant or EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 . Page:5 of 52 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF-1 PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008. ZONE INFORMATION System Name Zone Name Occupancy Type Floor Area (sgft) Inst. LPD (W/sf)l Ctrl. Credits (W/sf)z Allowed LPD Proc. Loads (W/sf) Area /s 3 Tailored /s 4 Support Corridor/Restroom/Support 389 '0.60 Office Office 162 `1.20 Offices Office 631 '1.20 Split Heat Pump-1 Work Shop Industrial Work, Low Bay 120 '1.00 Storage Retail Sales, Wholesale 57 '1.70 Lockers Locker/Dressing Room 137 '0.80 Support Conidor/Restroom/Su ort 1,016 -0.60 Unconditioned All Others 2,543 0.00 Split Heat Pump-2 Lounge Lounge, Recreation 342 '1.10 Storage Commercial, Industrial Storage 433 '0.60 Support CoMdor/Restroom/Su rt 318 '0.60 Split Heat Pump-3 Snack Bar Dining 348 '1.10 Kitchen 10tchen, Food Preparation 301 '1.60 Storage Commercial, Industrial Storage 122 '0.60 Hallway Corridor/Restroom/Support 221 '0.60 Split Heat Pumps 4 & 5 Lounge Lounge, Recreation 1,364 -1.10 Bar Bar, Cocktail Lounge, Casino 151 '1.10 Split Heat Pumps 6, 7 & 8 Laundry Laundry 108 -0.90 Attendant Corridor/Restroom/Su ort 283 '0.60 Locker Locker/Dressing Room 1,447 -0.80 Notes: 1. See LTG-2-C 2. See LTGA-C 3. See LTG-5-C 4. See LTG-6-C (items marked with asterisk, see LTG-2 -C by others) (by others) I Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified In this checklist These Items require special written justification . and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant Authorized Signature or Stamp Run Initiation Ti 20/ 1 •0 7 Run Code: 1203530927 EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:6 of 52 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF-1 PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008 ZONE INFORMATION System Name Zone Name Occupancy Type Floor Area (sgft) Inst LPD (W/sf)l Ctrl. Credits (W/sf)2 Allowed LPD Proc. . Loads (W/sf) Area Is 3 Tallored Is 4 Restrooms Corridor/Restroom/Support 1,573 '0.60 Hallway Corridor/Restroom/Support 616 '0.60 Split Heat Pumps 9 & 10 Retail Sales Retail Sales,, Wholesale 1,090 -1.70C 1.500 Office Office 116 '1.20 Storage Commercial, Industrial Storage 143 '0.60 Split Heat Pum 11 Retail Zone Retail Sales, Wholesale 272 -1.70 Dressing Locker/Dressing Room 26 '0.80 Hallway Corridor/Restroom/Su ort 342 '0.60 Split Heat Pumps 12, 13 & 14 Exercize Exercise, G nasium 2.714 '1.00C 1.500 Storage Commercial, Industrial Storage 132 '0.60 Split Heat Pump-15 Lobby Lobby, Main Entry 199 '1.50 Gallery Corridor/Restroom/Support 361 '0.60 Hallway Convention/Conference/Meeting 551 '1.40 Split Heat Pumps 16 & 17 Recreation Lounge, Recreation 1,288 '1.10 Office Office 132 -1.2001 Split Heat Pumps 18 & 19 Retail Zone Retail Sales, Wholesale 290 -1.70 Retail Retail Sales, Wholesale 133 '1.70 HallwayCorridor/Restroom/Su rt 717 '0.60 Storage Commercial Industrial Storage 263 .'0.60 LaundryLaundry103 '0.90 Notes' 1. See LTG-2-C 2. See LTG-4-C 3. See LTG-5-C 4. See LTG-6-C Items above require special documentation (items marked with asterisk, see LTG-2 -C by others) (by others) EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checKust I nese nems require speerar wnaen rusaawuvn and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation The exceptional features listed In this performance approach application have specifically been reviewed. Adequate written justification ano documentation for their use have been provided by the applicant or EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0603.1 Page:7 of 52 FPE�R7FORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF-'I PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008 ZONE INFORMATION System Name Zone Name Occupancy Type Floor Area (sgft) Inst LPD ' (Wlsf)1 Ctri. Credits (W/sf)2 Allowed LPD Proc. Loads (W/sf) Area /s 3 Tailored /s 4 Support Corridor/Restroom/Support 286 '0.60 Restrooms Corridor/Restmom/Support 1;090 '0.60 Notes: 1. See LTG-2-C 2. See LTG-4-C 3. See LTG5-C 4. See LTG-" (items marked with asterisk, see LTG-2 -C by others) (by others) Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist These -items require special written justification and documentation, and special verification to be used with the performance approach. The -local enforcement agency determines the adequacy of . the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant EnergyPro 4.4 by EnergySoft User Number. 2366 'Job Number. 0803-1 Page:8 of 52 1 4e CERTIFICATE OF•COMPLIANCE ENV-1-C PROJECT NAME DATE ' La Quinta Count Club Clubhouse 2/20/2008 OPAQUE SURFACES i .Surface Type, Area U-Fac. Insulation Cay. Cont: Act. Am. Tilt Cond. Status Joint Appendix IV Reference Location I Comments ' V Roof 1,125 0.035 R-30 R-0.0 0 0 New 02-A10 Dinin 2 Wall 50 0.074 R-19 R-0.0 168 ' 90 New 09-A5 Dining 3 Wall 9 0.074 R-19 R-0.0 258 90 New 09-A5 Dining 4 Wall • 2 0.074 R-19 R-0.0 348 90 _ New 09-A5 Dining 5 Wall 27 0.074 R-19 R-0.0 78 90 New 09-A5 ? Dining 6 Demising22 0.074 R-19 • R-0.0 0 90 New 09-A5 Diningfaces Storage/Restrooms) 7 Roof .14 0.035 R-30 R-0.0 0 .0 New 02-A10 Entry 8 Wall 11 0.074 R-19 R-0.0 168 - 90 New 09-A5 Entry 9 Wall 2 0.074 R-19 R-0.0 .348 '90 New 09-A5 Entry 10 Wall , 9 0.074 R-19 R-0.0 78 90 New 09-A5 Entry 11 Roof ' 45 0.035 R-30 R-0.0 0 0 New 02-A10 Hallway 12 Wall 5 0.074 R-19 R-0.0 258 90 New 09-A5 Hallwa 13 Demising 9 0.074 R-19 R-0.0 0 90 New 09-A5 Hallway faces Storage/Restrooms) 14 Roof 1,64 0.035 R-30 R-0.0 0 0 New 02-A10 * Kitchen 15 Wall 9 0.074 'R-19 R-0.0 168 90 New 09-A5 Kitchen 16 Wall 32 0.074 R-19 R-0.0 258 90 New 09-A5 Kitchen 17 Demising 48 0.074 R-19 R-0.0 0 .-90 New 09-A5 - Kitchen (faces Storage/Restrooms) 18 19 Roof Roof 9 17 0.035 0.035 R-30 R-30 R-0.0 R-0.0 0 0 0 0 New New 02-Al0 02-A10 Office - Hall ' 20 Wall 4 0.074 R-19 R=0.0 258 90 New 09-A5 Hall • N, E. A. I (New, Existing, Altered, Removed) FENESTRATION SURFACES nMore than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U-factors from -... -.. ---. _,_-__r__.__ _.,._,_.,_._----.___.___,_���..._----__ .,____a,-.._...,i.,--_----�..��---n -i- , # T e Area U-Fac' SHGC2 Act: Am. Cond. Stat. Glazing Irype Location/ Comments 1 Window Front S • 104 0.500 116-A 0.50 NFRC 168 New Nonres Double Non Metal Low E Dining 2 Window. Front (S) 64 0.500 116-A 0.50 NFRC 168 New Nonres Double Non Metal Low E Dining ' 3 Window Front (S) . 20 0.500 116-A 0.50 NFRC 168 New Nonres Double Non Metal Low E Entry 4 Window Right E 104 0.500 116-A 0.50 NFRC 78 New Nonres Double Non Metal Low E Entry 5 Window Left CM 52 0.500 116-A 0.50 NFRC • .258 New Nonres Double Non Metal Low E Hallway 6 Window Left 96 0.500 116-A 0.50 NFRC 258 New Nonres Double Non Metal Low E Kitchen 7 Window Left 96 0.500 116-A 0.50 NFRC 258 New Nonres Double Non Metal Low E Dining 8 Window Left 60 0.500 116-A 0.50 NFRC 258 New Nonres Double Non Metal Low E Dining 9 Window Rear N 96 0.500 116=A 6.50 NFRC 348 . New Nonres Double Non Metal Low E. Dining 10 Window Rear N) 120 0.500 '116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Dining 11. indow Rear N) 21 0.500 116-A 0.50 NFRC 348: New Nonres Double Non Metal Low E I Hall ' 12 ISkylight Rear N 196 0.500 116 A 0.50' NFRC 0 New Nonres Double Non Metal Low E IlLobby 13 lWindow Front S) 21 0.500 116-Al 0.50 INFRC 1 168 New I Nonres Double Non Metal Low. E, I Lobby. (1) U-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. - 72) SHGC Tvoe: 116-B Default Table from Standards. COG Center of Glass. NFRC Labeled Value EXTERIOR SHADING . - # ' Exterior Shade Type SHGC Window Hgt. Wd. Overhang Left Fin Right Fin Len. Hot. LExt.RExt: Dist. Len. H t. Dist. Len. H t. 1 None 0.76 2 None 0.76 ' 3 • None 0.76 4 None 0.76 T 5 None 0.76 6 None 0.76 7 • None 0.76 8.0 6.0 26.0 3.5 26.0 " 26.0 8 None 0.76 7.5 8.0 26.0 3.5 26.0 26.0 - 9 None 0.76 8.0 6.0 19.0 3.5 19.0 19.0 10 None 10.76 1 6.3 -9.5 19.0 • 3.5 19.0 19.0 11 None 10.76 1 7.5 8.0 26.0 3.5.26.0 26.0 12 None 11.00 13 • None 10.76 1` MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES The proposed building Is In climate zones 2 through 16 and contains an enclosed space with floor area greater than 25,000 ft2, a ceiling height greater than 16 feet, and an LPD for general lighting of at least 0.6 WI112. See Section 143(c). B this box Is checked, ENV-" must be filled out when submitting under the PreWripthre Compltance Approach. Run Initiation Time- 02/2 / 8 1 •47 C 2 3 3 92 EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. • 0803-1' Page:9 of 52 - ICERTiFICATE-OF COMPLIANCE ENV - PROJECT NAME La Quinta Country Club Clubhouse - DATE2/20/2008 OPAQUE SURFACES #: Surface Type Area U-Fac. Insulation Cay. Cont. Act. • A. Tilt Cond: Status Joint Appendix IV Reference • Location / Comments 21 Door 4 0.500 Insul R-0.0 258 90 New 28-A3 , Had, 22 Roof 45 0.035 R-30 R-0.0 0 0 New 02-A10 • Storage 23 Roof 21 0.035 R-30 R-0.0 0 0 New 02-A10 Storage 24 Roof 1,72 0.035 R-30 R-0.0 0 0 New 02-A10 Dining 25 Wall 26 0.074 R-19 R-0.0 258 90 New 09-A5 Dining 26 Wall 50 0.074 R-19 R-0.0 348 90 New 09-A5 Dining 27 Roof 34 0.035 R-30 R-0.0 0 0 New. 02-A10 Hall 28 Wall 22 0.074 R-19 R-0.0 348 90 New 09-A5 Hall 29 Demising 10 0.074 R-19 R-0.0 0 90 New 09-A5 Hall faces Storage/Restrooms 30 Roof 1,09 0.035 R-30 R-0.0 0 _ 0 New 02-A10 Lobby 31 Wall 64 0.074 R-19 R-0.0 168 90 New 09-A5 Lobby 32 Wall 24 0.074 R-19 R-0.0 258 90 New 09-A5 _Lobby 33 Wall 28 0.074 R-19 R-0.0 348 -90 New 09-A5 Lobby 34 Wall 20 40.074 R-19 R-0.0 78 90 New 09-A5 ' Lobby 35 Roof 1,1 -0.035 R-30 R-0.0 0 0 New 02-A10 Support 36 Wall 32 0.074 R-19 R-0.0 78 90 .' New 09-A5 Support 37 Roof 3 0.035 R-30 R-0.0 0 _ 0 New 02-A10 Storage Roof 27 0.035 • R-30 - R-0.0 0 0 New 02-A10 Bar ' 10 0.074 R-19 R-0.0 348 90 New 09-A5 - Bar 40 W38 all •a 14 0.074 R-19 R-0.0 78 � 90 New 09=A5 Bar 39 Wall • N. E, A, R (New, Existing, Altered, Removed) FENESTRATION SURFACES n More than or equal to 10,000 sq.fL of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certficate using the default U-factors from # Type Area . U-Fac' SHGC2 Act.. Am. Cond. Stat. " Glazing Type Location/ Comments . 14 Window Front S 52 0.500 116-A 0.50 NFRC 168 New Nonres Double Non Metal Low E Lobb • 15 Window Front (S)• 64 0.500 116-A 0.50 NFRC - 168 New Nonres Double Non Metal Low E Lobby 16 Window Rear (N) 21 0.500 116-A 0.50 NFRC 348 ' New . Nonres Double Non Metal Low E • Lobby 17 Window Rear N 21 0.500 116-A 0.50 NFRC - 348 New Nonres Double Non Metal Low E Lobby 18 ISkylight Rear N 34 0.500 116-A 0.50 NFRC 01 New Nonres Double Non Metal Low E Support 19 Window Right (E) 37 0.500 116•A 0.50 NFRC 78 New Nonres Double Non Metal Low E Support 20 Window Right (E) 66 0.500 116-A 0.50 NFRC 78 New Nonres Double Non Metal Low E Support 21 Window . Rear N 21 0.500 116-A 0.50 NFRC 348 . New Nonres Double Non Metal Low E Bar 22 Window Rear . N 92 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Lounge 23 Window Rear (N) 104 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Lounge 24 Window Rear (N) 23 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Meeting Room - 25 Window •Rear N 781 0.500 116-A 0.50 NFRC 1 348 , New Nonres Double Non Metal Low E Meeting Room 26 Wi dow Right (E) 521 0.5001116-Al 0.50 NFRC 1. 78 New I Nonres Double Non Metal Low E Meeting Room (1) U•factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. (2) SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING i # Exterior Shade Type SHGC Window Hgt. Wd. Overhang Left Fin Right Fin Len. H t. LExt.RExt. Dist. Len. H-t. Dist. Len. H t.. 14 None 0.76 15 None 0.76 16 None 0.76 17 None 0.76 18 None 1.00 19 None 0.76 20 None 0.76 21 None 0.76 7.0 3.0 21.0 •3.5 21.0 21.0 22 None 0.76 6.2 -14.8 - 21.0 3.5 21.0 21.0 23 1 None 0.76 24 1 None 0.76 7.0 .3.0 8.0 3.5 16.0 16.0 25 1 None 0.76 5.7 6.7 8.0 3.5 16.0 16.0 ` 26 1 None 0.76 8.0 6.0 16.0 3.5 -16.0 16.0' ` MINIM M SKYLIGHT AREA FOR LARGE ENCLOSED SPACES The proposed building Is In climate zones 2 through 16 and contains an enclosed space with floor area greater than 25,000 ft2, a cellinl fighting of at least 0.5 WM. See Section 149(ct. if this box Is checked, ENV-" must be filled out when submitting under the Prescript Run Initiation Time: 02/20/08 10:M47 Run Code: 1: EnergyPro 4.4 by EnergySoft User Number. M6' Job Number. 0803-1 greater man is reel, ana an u•u Tor generar rpliande Approach. 30927 " • ' Page: 10 of 52 t CERTIFICATE OF COMPLIANCE ENV-1-C PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 OPAQUE SURFACES # Surface Type Area U-Fac. Insulation Cay. Cont. Act. Azm. Tilt Cond: Status Joint Appendix IV Reference Location / Comments 411 Roof 1,154 0.035 R-30 R-0.0 0 0 New 02-A10 Lounge 42 lWall 1 305 0.074 R-19 R-0.0 348 90 New 09-A5 Lounge 43 lRoof 1 616 0.035 R-30 R-0.0 0 0 New 02-A10 Meeting Room 44 lWall 1 30Z 0.074 R-19 R-0.0 348 90 New 09-A5 Meeting Room 45 lWall 1 18 0.074 R-19 R-0.0 78 1 90 New 09-A5 Meeting Room 46 lRoof 461 0.035 R-30 R-0.0 0 0 New 02-A10 Offices 47 lWall 34 0.074 R-19 R-0.0 168 90 New 09-A5 Offices 48 lWall 120 0.074 R-19 R-0.0 258 90 New 09-A5 Offices 49 Roof 150 0.035 R-30 R-0.0 0 0 New 02-A10 Wafting Area 50 Wall 3 0.074 R-19 R-0.0 168 90 New 09-A5 Waiting Area 51 Wall 134 0.074 R-19 R-0.0 258 90 New 09-A5 Waiting Area 52 Roof 389 0.035 R-30 R-0.0 0 0 New 02-A10 Support 53 Roof 162 0.035 R-30 R-0.0 0 0 New 02-A10 Office 54 Roof 631 0.035 R-30 R-0.0 0 0 New 02-A10 Offices 55 Wall 182 0.074 R-19 R-0.0 168 90 New 09-A5 Offices 56 Wall 182 0.074 R-19 R-0.0 348 90 New 09-A5 Offices 57 Wall 54 0.074 R-19 R-0.0 78 90 New 09-A5 Offices 58 Roof 12 0.053 6 in. R-30.0 0 1 0 1 New 06-A8 Work Shop 59 Wall 19 0.144 None R-7.5 258 1 90 1 New 1121F5 Work Shop 60 Wall I 7N 0.144 None R-7.5 348 1 90 1 New 13-1`5 Work Shop FIr�'�I More than or equal to 10.000 sq.R. of site -built fenestration area must include a label certificate either Issued by NFRC or provide a CEC Default Label Certificate using the default LI-factors from I 1 --A T..w1.. 4 4a A a.,A o PWA nale Shell he fl-i in rho rnMn nnre nmtwn of m dirtinn mnetnuJlnn and In the huildinn manaaefs office after construction # IType Area U-Fac' SHGC2 Act. Am. Cond. Stat. Glazing Type Location/ Comments 27 Window Right E 52 0.500 116-A 0.50 NFRC 78 New Nonres Double Non Metal Low E Meeting Room 28 lWindow Front (S) 54 0.500 116-A 0.50 NFRC 168 New Nonres Double Non Metal Low E Offices 29 lWindow Left 22 0.500 116-A 0.50 NFRC 258 New Nonres Double Non Metal Low E Offices 30 Window Left 22 0.500 116-A 0.50 NFRC 258 New Nonres Double Non Metal Low E Waiting Area 31 Window Right E 95 0.500 116-A 0.50 NFRC 781 New Nonres Double Non Metal Low E Offices 32 Window Left 16 0.500 116-A 0.50 NFRC 258 New Nonres Double Non Metal Low E Work Shop 33 Window Rear N 66 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Snack Bar 34 Window Rear N 21 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Snack Bar 35 Window Rear N 21 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Hallway 36 Window Rear (N) 50 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Lounge 37 Window Rear N 72 0.500 116-A 0.50 NFRC 348 New I Nonres Double Non Metal Low E Lounge 38 Window Rear N 48 0.500 116-A 0.50 NFRC 1 3481 New I Nonres Double Non Metal Low E Lounge 39 Window Left 20 0.500 116-Al 0.50.NFRCI 2581 New I Nonres Double Non Metal Low E I Retail Sales �1 U-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. 2; SHGC Type: 116-8 Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING # Exterior Shade Type SHGC Window Hgt. Wd. Overhang_ Left Fin Right Fin Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. 27 None 0.76 8.0 3.0 16.0 3.5 16.0 16.0 28 None 0.76 29 None 0.76 30 None 0.76 31 None 0.76 32 None 0.76 33 None 0.76 34 None 0.76 35 None 0.76 36 None 0.76 37 1 None 10.76 38 1 None 10.76 39 1 None 10.76 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES The proposed buMng Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a telling height greater than Ili feet, and an LPD for general Ilghting of at least 0.6 Wffl2 See Section 147(c). If this box Is checked, E14114-C must be filled out when submitting under the Prescriptive Compliance Approach. I EnefavPro 4.4 by EnemvSoft User Number. 2366 Job Number. 0803-1 Pane:11 of 52 1 �4,rCR 1 IrlV�i 1. G .�Jt' VVIYIiLI/11YVG.. &-IN v - I -%0I PROJECT NAAAE DATE La Quinta Country Club Clubhouse 2/20/2008 OPAQUE SURFACES # Surface Type Area U-Fac. Insulation Cay. Cont. Act. Am. Tilt . Cond: Status Joint Appendix IV Reference s Location / Comments 61 Dernisinq 14 0.074 R-19 R-0.0 •0 90 New ' 09-A5 Work Sho faces Restrooms/Storabe/etc: 62 lRoof 57 0.053 bin. R-30.0 0 0 New' 06-A8 Storage 63 Demisin 91 0.074 R-19 ' R-0.0 0 90 New 09-A5 Storage faces Restrooms/Storabe/etc. 64 lRoof 13 0.053 6 in: R-30.01 0 0 New 06-A8 - Lockers 65 IDemising 91 0.074 R-19 R-0.01 0 90. New 09-A5 Lockers faces Restrooms/Storabe/etc. 66 Wall 264 0.144 None • R-7.5 258 90 New 113-F5 Support 67 Door 21 0.500 '. None R-0.0 258 90 New 28-A4 . Support 68 Wall 24A 0.074 R-19 R-0.0 348 90 New 09-A5 Support ' 69 Wall 704 0.144 None R-7.5 78 90 New 13-1`5 Support 70 Door_ 21 0.500 None • R-0.0 78 • .. 90 New 28-A4 Support 71 lRoof 39 0.053 6 in. R-30.0 0 0 New 06-A8 Support 72 lRoof 62 0.053 6 in. R-30.0 -,45 0' New 06-AS Support 73 Wall 32 0.144 None R-7.5 .168 90 New 13-F5 Support 74 IDoor 3 0.500 Insul R-0.0 168 90 New 28-A3 Support 75 Wall 100 0.144 None R-7.5 258 90 New 13-F5 3 - Support . 76 Door 40 0.500 Insul R-0.0 258' 90 New 28-A3 Support 77 Wall 2 0.144 None . R-7.5 348 90 : New 13-F5 Support 78 Wall . -2 -0.144 None R-7.5 78 90 New 13-F5 Support 79 Wall 29 0.144 None R-7.5 258 90 New 113-F5 Lounge ' 80 FloorBG ' 341 0.730 None R-0.0 -0 180 1 New 26-A1 Lounge • N. E. A, R (New, Existing, Altered, Removed) FENESTRATION SURFACES ' n More than or equal to 10.000 sq.fL of site -built fenestration area must include a label certificate either Issued by NFRC or provide a CEC Default Label Certificate using the default 11-factors from :4dTMe tArea U-Fac' SHGC' Act. Am. Cond. Stat. Glazing lrype Location/ Comments 40 lwiqdow Rear N 48'0.500 116-A 0.50 NFRC 348 .New Nonres Double Non Metal Low E Retail Sales 41 Window Rear (N) 42 0.500 116-A 0.50 NFRC 348 + New Nonres Double Non Metal Low E Retail Sales 42 Window . Right (E) 20 0.500 116-A 0.50 NFRC 78 New Nonres Double Non Metal Low E Retail Sales 43 lWindow Rear- N 52 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Office 44 Window Rear N 521 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Exercize 45 Window Rear (N) 21 -0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Exercize 46 Window Rear N) 52 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Hallway 47 Window Front S 42 0.500 116-A 0.50 NFRC 168 New Nonres Double Non Metal Low E Recreation 48 Window Rear N 42 0.500 116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Recreation 49 Window Rear N) 82.0.500116-A 0.50 NFRC 348 New Nonres Double Non Metal Low E Recreation 50 Window - Right NE) 40 0.50 NFRC 60 New Nonres Double Non Metal Low E Recreation51• indow Ri ht E 40 0.50 NFRC 78 New Nonres Double Non Metal Low E Recreation 52 Window. Front (SE) 40� 0.50 NFRC 146 New Nonres Double Non Metal Low E Recreation ((1)) LI-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manuel Appendix, NFRC Labeled value. (2) SHGC Type: 116-8 Default Table from Standards, COG Center of Glass, NFRC Labeled Value MINIMUM SKYLIGHT 'AREA FOR LARGE ENCLOSED SPACES The proposed building Is In climate tones 2 through 16 and contains an enclosed space with floor area greater than 25,000 tt2, a ceiling height greater than 16 feet, and an LPD for general lighting of at least 0.6 WMI See Section 143(c). If this box Is checked, ENV-" must be filled out when submitting under the Prescriptive Compliance Approach. -R un Initiationim 2/ 0l 8 •08.4 Code: 1203 30927 EnergyPr04.4 by EnergySoft• User Number. 2366 Job Number. 0803-1 + Page:12 of 52 3 CERTIFICATE OF COMPLIANCE ENV-1-C PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 OPAQUE SURFACES # Surface T e Area U-Fac. Insulation Cay. Cont. Act. Azm. Tilt Cond: Status Joint Appendix IV Reference Location / Comments 81 WallBG 19 0.139 None R-7.5 0 90 New 13-J5 Lounge - 156" deer) 82 FloorBG 43 0.730 None R-0.0 0 180 New 26-A1 Storage 83 Roof 43 0.053 6 in. R-30.0 0 0 New 06-A8 Storage 84 WaIIBG 26 0.139 None R-7.5 0 90 New 13-J5 Storage -156" deep 85 FloorBG 31 0.730 None R-0.0 0 180 New 26-A1 Su ort 86 Roof 26 0.053 6 in. R-30.0 0 0 New 06-A8 Support 87 WallBG 27 0.139 None R-7.5 0 90 New 13J5 Support - 0" deep 88 Roof 34 0.053 6 in. R-30.0 0 0 New 06-A8 Snack Bar 89 Wall Demising 29 13 0.074 0.074 R-19 R-19 R-0.0 R-0.0 348 0 90 90 New New 09-A5 09-A5 Snack Bar Snack Bar faces Restrooms/StorabeMc. f 30 0.053 6 in. R-30.0 0 0 New 06-A8 Kitchen isin 16 0.074 R-19 R-0.0 0 90 New 09-A5 Kitchen faces Restrooms/StorabeMc. f 12 0.053 6 in. R-30.0 0 0 New 06-A8 Storage f 22 0.053 6 in. R-30.0 0 0 New 06-A8 Hallway ll [Wall 5 0.074 R-19 R-0.0 348 90 New 09-A5 Hallwaf 86 0.053 6 in. R-30.0 0 0 New 06-A8 Loun e ll 26 0.139 None R-7.5 258 90 New 13J5 Lounge ll 4 0.074 R-19 R-0.0 348 90 New 09-A5 Loun e orBG 10 0.730 None R-0.0 0 180 New 26-A1 -aundry orBG 283 0.730 I None R-0.0 0 180 New 26 Al Attendant N. E. A, IR (New, Existing, Altered, nore Mthan or equal to 10,000 sq.iL of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Labal Certificate using the default U-factors from U [;[T Standards Table 116-A and B. Certificate e shall be filed Area in the contractors U-Fac' roiect once aunng SHGC2 consoucuon Act. Azm. ana in ure o Cond.. Stat. uuffig nrurra ei . umw -.1 w11- ."vI . Glazinq Type Location/ Comments 53 Window Right E 231 0.500 116-A 0.50 NFRC 78 New Nonres Double Non Metal Low E Office S11 U-tailor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. Starr Tvoe 116-B Default Table from Standards. COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING # Exterior Shade Type SHGC Window Hgt. Wd. Overhang 'Left Fin Right Fin Len. Hgt. LExt.RExt. Dist. Len. H t. Dist. Len. H t. 53 None 0.76 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES The proposed building Is In climate zones 2 through 16 and contains an enclosed space wlth floor area greater than 26,000 ft2, a ceiling height greater than 16 feet, and an LPD for general lighting of at least 0.6 WNt2. See Section 143(c). It this box Is checked, ENVA-C must be filled out when submitting under the Prescriptive Compliance Approach. EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:13 of 52 CERTIFICATE OF COMPLIANCE ENVA -C PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 C•T RFACES # Surface Type Area U-Fac. Insulation Cay. Cont. Act. Am. Tilt Cond: Status Joint Appendix IV Reference Location / Comments 101 FloorBG 144 0.730 None F R-0.0 0 180 New 26-A1 Locker 102 FloorBG 1,573 0.730 None R-0.0 0 180 New 26-A1 Restrooms 103 FloorBG 616 0.730 None R-0.0 0 180 New 26-A1 Hallway 104 Wa1IBG 1,46 0.139 None R-7.5 0 90 New 13-J5 Hallway - 0" deep 105 Roof 33 0.053 6 in. R-30.01 0 0 New 06-A8 Retail Sales 106 Wall 61 0.074 R-19 R-0.01 258 90 New 09-A5 Retail Sales 107 Wall 271 0.074 R-19 R-0.01 348 90 New 09-A5 Retail Sales 108 Wall 70 0.074 R-19 R-0.0 78 90 New 09-A5 Retail Sales 109 Roof 471 0.053 6 in. R-30.0 0 0 New 06-A8 Office 110 Wall 8N 0.074 R-19 R-0.0 348 90 New 09-A5 Office 111 FloorBG 274 0.730 None R-0.0 0 180 New 26-A1 Retail Zone 112 FloorBG 20 0.730 None R-0.0 0 1 180 New 26-A1 Dressing 113 FloorBG 34 0.730 None R-0.0 0 1 180 New 26-A1 Hallwa' 114 WallBG 520 0.139 None R-7.5 0 90 New 13- J5 ' Hallway - 156" deep 115 Roof 2941 0.053 6 in. R-30.0 0 0 New 06-A8 Exercize, 116 Wall 5 0.074 R-19 R-0.0 348 90 New 09-A5 Exercize 117 Wall 31 0.144 None R-7.5 348 90 ew 13-F5 Exercize 118 Wall 8 0.074 R-19 R-0.0 78 90 ew 09-A5 Exercize 119 Roof 13 0.053 6 in. R-30.0 0 0 ew IN 06-AS Stora e 120 Wall 2 0.144 None R-7.5 348 90 ew 13-175 Stora e . 'N.E.A.R r--i Mare than or eaual to 10.000 soft of site -built fenestration area must include a label certificate either Issued by NFRC or provide a CEC Default Label Certificate using the default U-factors from U # Standards Table 116-A and B. Certificate FTjVype shall be filed Area in the contractors U-Fac' roect omce aunn SHGC2 consuucuon Act. Azm. enu in me u Cond. Stat. auiny mmrdgm s umw due w1 w" Glazin T e Location/ Comments (1) U factor Type: I i6-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRL; Labelea value. 2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING Window Overhang Left Fin Right Fin ## Exterior Shade Type SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 26,000 1111:2, a ceiling height greater than 15 feet, and an LPD for general lighting of at least 0.6 WINZ See Section 143(c). If this box Is checked, ENV- -C must be filled out. when submitting under the Prescriptive Compliance Approach. s..— r _:a:..a:..., r:—,-. nHi-snino 4n.nO.w7 113— t`i A-- 4AA4C4A097 EnemvPro 4.4 by EnemvSoft User Number. 2366 Job Number. 0803-1 Page:14 of 52 1 CERTIFICATE OF COMPLIANCE ENVA -C PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008. OPAQUE SURFACES # Surface Type Area U-Fac. Insulation Cay. Cont. Act. Azm. Tilt Cond: Status Joint Appendix IV Reference Location I Comments 121 122 Wall FloorBG 9 19 0.144 0.730 None None R-7.5 R-0.0 78 0 90 180 New New 13-F5 26-A1 Storage Lobby 123 WallBG 3 0.144 None R-7.5 0 90 New 13-F5 Lobby -156" deep FloorBG 36 0.730 None R-0.0 0 180 New 26-A1 Gallery WallBG 40 0.139 one R-7.5 0 90 New 13-J5 Galls -156' dee Roof 4 0.053 6 in. R-30.0 0 0 New 06-A8 Hallway Wall 5 0.074 R-19 R-0.0 348 90 New 09-A5 Hallway Roof 1,28 0.035 R-30 R-0.0 0 0 New 02-A10 Recreation [24 Wall 27 0.074 R-19 R-0.0 168 90 New 09-A5Recreation Wall 37 0.074 R-19 R-0.0 348 90 New 09-A5 Recreation Wall 11 0.074 R-19 R-0.0 60 90 New 09-A5 Recreation Wall 20 0.074 R-19 R-0.0 78 90 New 09-A5 Recreation Wall 11 0.074 R-19 R-0.0 146 90 New 09-A5 Recreation Roof 13 0.035 R-30 R-0.0 0 0 New 02-A10 Office 135 Wall 13 0.074 R-19 R-0.0 168 90 New I Office 136 Wall 8 0.074 R-19 R-0.0 78 90 New 09-A5 Office 137 138 FloorBG WallBG 29 32 0.730 0.139 None None R-0.0 R-7.5 0 0 180 90 New New 26-A1 13-J5 Retail Zone Retail Zone -156"deep 139 FloorBG 13 0.730 None R-0.0 0 180 N w 26-A1 Retail 140 WallBG 3771 0.1441 None I R-7.51 0 1 90 1 New 13-F5 Retail - 0" deep - N, E, A, R (New, E)isting, Altered, More than or equal to 10.000 sq.R. Of site -built fenestration area must include a label certificate either Issued by NFRC or provide a CEC Default Label Certificate using the default LI-factors LJ # Standards Table 116-A and B. Certificate Type shall be filed Area in the contractors U-Fac' proeciornos ounng SHGC' x onsoucuon Act. Azm. and m me uunuu,y Cond. Stat. mane m e u,,,ca r co GlazingType Location/ Comments (1 U-factor Type:116-A Default Table from Standards, Table NIA Default Table from the ACM Manual Appendix, NI-M; LaoelBd value. (2; SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING Window OverhangLeft Fin Right Fin # Exterior Shade Type SHGC Hgt. Wd. Len. Hgt. LExt.RExt. Dist. Len. H t. Dist. Len. H t. MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES The proposed building Is In climate zones 2 through 16 and contains an enclosed space with floor area greater than 26,000 14:2, a ceiling height greater than 16 feet, and an LPD for general Ilnhtinn of at least 0.5 WN12. See Section 143(c). if this box Is checked, ENVA-C must be filled out when submitting under the Prescriptive Compliance Approach, EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:15 of 52 CERTIFICATE OF COMPLIANCE ENV-1-C PROJECT NAME DATEZ/ZO/ZOOH La Quints Country Club Clubhouse OPAQUE SURFACES # Surface Type Area U-Fac. Insulation Cay. Cont. Act. Azm. Tilt Cond: Status Joint Appendix IV Reference Location 1 Comments 141 142 FloorBG Roof 717 34C 0.730 0.053 None 6 in. R-0.0 R-30.0 0 0 180 0 New New 26-A1 06-A8 Hallway Hallway 143 Wall 9 0.144 None R-7.5 168 90 New 13-F5 Hallway 144 Wall 124,0.144 None R-7.5 78 90 New 13-F5 Hallway 145 WallBG 32 0.139 None R-7.5 0 90 New 13-J5 Hallway-156" deep 146 Roof 26 0.053 6 in. R-30.0 0 0 New 06-A8 Storage 147 Wall 11 0.144 None R-7.5 348 90 New 13-F5 Storage 148 Wall 13 0.144 None R-7.5 78 90 New 13-F5 Story e 149 Roof 10 0.053 6 in. R-30.0 0 0 New 06-A8 Laundry 150 Wall 14 0.144 None R-7.5 78 90 New 13-F5 Laund 151 Roof 19 0.053 6 in. R-30.0 0 0 New 06-A8 Su port 152 FloorBG 1,09 0.730 None R-0.0 0 180 New 26-Al Restrooms 153 154 Roof WallBG 9 44 0.053 0.139 6 in. None R-30.0 R-7.5 0 0 0 90 New New 06-A8 13-J5 Restrooms Restrooms -156" deep N, E, A. R (New, Exisfing, Altered, Removed) FENESTRATION SURFACES n More than or equal to 10,000 sq.fL of site -built fenestration area must include a label ceNficate either issued by NFRC or provide a CEC Default Label Certificate using the default ll-factors from _f # Standards Table 116-A and B. Certificate Type shall be filed Area in the contractors U-Fac' projed otnce dung SHGC2 conswcuon Act. Azm. and m me uuwmmb Cond. Stat. ma, w Glazincjype Location/ Comments �1 U-factor Type: 116-A Default Table from Standards, Table NI-1 Default Table from the ACM Manual Appendix, NFRC Labeled value. 2; SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING Window Overhang Left Fin Right Fin # Exterior Shade Type SHGC Hgt. Wd. Len. Hgt. LExt.RExt. Dist. Len. H t. Dist. Len. H t. MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES El The proposed building Is In climate zones 2 through 16 and contains an enclosed space with floor area greater than 26.000 fl2, a telling height greater than 15 feet, and an LPD for general lighting of at least 0.6 Wf a See Section 143(c). If this box is checked, ENV�4-C must be filled out when submitting under the Prescriptive Compliance Approach. Run Initiation Time: 02 •08. 7 Run Code: 1203630927 EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:16 of 52 CERTIFICATE OF COMPLIANCE IVIECH-I-C PROJECT NAME DATE La Quints Country _Club Clubhouse 2/20/2008 j .Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. , Building Departments: SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance,, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation „s 0__4;__ 4n.'InQIK% .nil Tiff. 9d Part A certificates and operating and maintenance rntormauon MUM Lilt: 10 uucnlcnw- STATEMENT OF COMPLIANCE MECH-2-A: Ventilation System Acceptance Document -Variable Air Volume Systems Outdoor Air Acceptance -Constant Air Volume Systems Outdoor Air Acceptance Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit MECH-3-A: Packaged HVAC Systems Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit ❑ MECH-A: Air -Side Economizer Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. units with economizers that are installed at the factory and certified with the commission do not require equipment testing but do require construction inspection. ❑ MECH-5-A: Air Distribution Acceptance Document Equipment requiring acceptance testing This test required If the unit serves 5,000112 of space or less and 25% or more of the duds are in noncondiboned or semiconditioned space like an alfic. New systems that meet the above requirements. Retmfit systems that meet the above requirements and eitherextend ducts, replace ducts or r replace the packaged unit. ❑ MECH-6-A: Demand Control Ventilation Acceptance Document Equipment requiring acceptance testing All new DCV controls installed on new or existing packaged systems must be tested. ❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document Equipment requiring acceptance testing All new VA fan volume controls installed on new or existing systems must be tested ❑ MECH-8-A:-Hydronic System Control Acceptance Document f -Variable Flow Controls Applies to chilled and hot water systems. -Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header. -Supply Water Temperature Reset"Controls .Applies to new constant flow chiller/ and hot water systems that have a design capacity greater than or equal to 500,000 BhAr. -Water-loop Heat Pump Controls Applies to all new watertoop heat pump systems where the combined loop pumps are greater than 5 hp. -Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilled, hydronic heat pump orcondenser water systems where the pumps motors are greater than 5 hp. Equipment requiring acceptance testing EnergyPro 4.4 by EnergySoft User Number. 2366 - Job Number. 0803-1 Page:17 of 52 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation ; VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control isolation Zones Pipe Insulation Duct Insulation AIR SYSTEMS, Central or Single Zone Packaged Heat Pump-1 Packaged Heat Pump-2 Packaged Heat Pumps-3 & 1 1 2 Reference on Plans or Specification 112(a) 2.20 COP 2.10 COP 2.20 COP 112 a 10.3 EER 9.8 EER 11.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121 b 652 cfm 908 cfm 946 cfm 121 c No No No 121 c) No No No 121 c 122 a Procirammable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Re uired Heating & Cooling Require Heating .& Cooling Required 122 Gravity Gravitv Gravity 122 n/a n/a n/a 123 124 R-4.2 R-4.2 R-4.2 PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2` Fan Control .DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Seating for Prescriptive Compliance 144 a & b n/a n/a n/a 144 a & b 69,203 btuh 86,191 btuh 86,191 btuh 144 a & b n/a _ n/a n/a 144 a & b 82,461 btuh 103,163 btuh 106,189 btuh 144 c Constant Volume Constant Volume Constant Volume 144 (c) 144 c No No No 144 d No No No 144 a No Economizer No Economizer No Economizer 144 Constant Temp Constant Temp Constant Tern 144 (f) Constant Temp Constant Temp Constant Temp 144 k) No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. if a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons pet footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% dud in unconditioned space. Duct seating is required for Prescriptive Compliance, see PERF-1 for performance method dud sealing requirements. Run Initiation Time: 02/20/0810.08.47 RunCode• 1203530927 EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:18 of 52 �IR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 ITEM OR SYSTEM TAG(S) Number of Systems MANDATORY MEASURES Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance T-24 Section AIR SYSTEMS, Central or Single Zone Packaged Heat Pumps 5 & 6 Packaged Heat Pump-7 Packaged Heat Pump-8 2 1 1 Reference on Plans or Specification 1 112(a) 2.20 COP 2.20 COP 7.80 HSPF 112 a 11.0 EER 10.3 EER 13.0 SEER / 11.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a We n/a 121(b) Yes Yes Yes 121(b) 370 cfm 719 cfm 308 din 121 c No No No 121(c) No No No 121 c 122 a Programmable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Re uired Heating & Cooling Require 122 Gravitv Gravity Gravity 122() n/a n/a n/a 123 124 R-4.2 R-4.2 R-4.2 144 a & b n/a n/a n/a 144 a & b 86,191 btuh 69,203 btuh 29,043 btuh 144 a & b n/a n/a n/a 144 a & b 119,064 btuh 81,323 btuh 34,290 btuh 144 c Constant Volume Constant Volume Constant Volume 144 (c 144 c No No No 144 d No No No 144 a No Economizer No Economizer No Economizer 144 Constant Temp Constant Temp Constant Temp 144 (f) Constant Temp Constant Temp Constant Temp 144 (k No . No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF-1 for performance method duct sealing requirements. WR SYSTEM REQUIREMENTS Part 1 of 2 MECW-2-C PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 ITEM OR SYSTEM TAG(S) Plumber of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity - x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone Packaged Heat Pump-9 Split Heat Pump-1 Split Heat Pump-2 1 1 1 Reference on Plans or Specification 1 112(a) 2.20 COP 7.70 HSPF 7.70 HSPF 112 a 10.5 EER 13.0 SEER / 11.0 EER 13.0 SEER / 11.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121(b) 270 cfm 205 cfm 284 efm 121 c No No No 121 c) No No No 121 c 122 a Programmable Switch Programmable Switch -Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Re uired Heating & Cooling Required 122 Gravity Gravity Gravity 122(g) n/a n/a n/a 123 124 � R-4.2 R- .2 R-4.2 144 a & b n/a n/a n/a 144 a & b " 54,650 btuh 34,789 btuh 28,481 btuh 144 a & b n/a n/a n/a 144 a & b 67,491 btuh 45,458 btuh 35,589 btuh 144 c Constant Volume Constant Volume Constant Volume 144 c 144 c No No No 144 d No No No 144 a No Economizer No Economizer No Economizer 144 Constant Temp Constant Temp Constant Temp 144 (f) Constant Temp Constant Temp Constant Temp 144 k) No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement Is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF-1 for performance method duct sealing requirements. EnergyPro 4.4 by EnergySoft User Number. 2366 Job Nurnbet 0803-1 Page:20 of 52 AIR SYSTEM REQUIREMENTS Partl of 2 MECH-2-C PROJECT NAME DATE La Quinta Country Club Clubhouse I 2/20/2008 ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone Split Heat Pump-3 Split Heat Pumps 4 & 5 Split Heat Pumps 6, 7 & 8 1 2 3 Reference on Plans or Specification 112(a) 7.70 HSPF 7.70 HSPF 7.70 HSPF 112 a 13.0 SEER / 11:0 EER 13.0 SEER / 11.0 EER 13.0 SEER 111.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121(b) 271 afm 758 cfm 1868 cfm 121 c No No No 121(c) No No No 121 c 122 a Program able Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Gravity Gravity Gravity 122(g), n/a n/a n/a 123 124 R-4.2 R-4.2 R-4.2 144 a & b n/a n/a n/a 144 a & b 34,789 btuh 69,577 btuh 104,366 btuh 144 a & b n/a n/a n/a 144 a & b 39,246 btuh 76,750 btuh 136,823 btuh 144 c . Constant Volume Constant Volume Constant Volume 144 (c) 144 c No No No 144 d No No No 144 a No Economizer No Economizer No Economizer 144 Constant Temp Constant Temp Constant Temp 144 (o Constant Temp Constant Temp Constant Temp 144 k) No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "NW in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct seating is required for Prescriptive Compliance, see PERF-1 for performance method dud sealing requirements. AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE La Quintal Country Club Clubhouse 2/20/2008 SYSTEM FEATURES* ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES AIR SYSTEMS, Central or Single one Split Heat Pumps 9 & 10 Split Heat Pump-11 Split Heat Pumps 12, 13 & 2 1 14 3 Reference on Plans or Specification t 112(a) 7.70 HSPF 7.70 HSPF 7.70 HSPF 112 a ' 13.0 SEER / 11.0 EER 13.0 SEER / 11.0 EER 13.0 SEER / 11.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121(b) 311 cfm 123 cfm 427 cfm 121 c No No No 121 c) No No No 121 c .122 a Programmable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Gravity Gravity Gravity 122(g) n/a n/a n/a 123 124 RA.2 R-4.2 R4.2 Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance 144 a & b n/a n/a n/a 144 a & b 56,961 btuh 15,427 btuh 85,442 btuh 144 a & b n/a n/a n/a 144 a & b 71,350 btuh 17,525 btuh 82,713 btuh 144 c Constant Volume Constant Volume Constant Volume 144 c) 144 c No No No. 144 d No No No 144 a No Economizer No Economizer No Economizer 144(0 Constant Temp Constant Temp Constant Temp 144 0) Constant Temp Constant Temp Constant Temp 144 (k) No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" In the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5.000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF-1 for performance method duct sealing requirements. UR SYSTEM REQUIREMENTS Part 1 of 2 MECIH-2-C PROJECT NAME 16�2/20/2008 La Quinta Count Club Clubhouse RYSTFM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems MANDATORY MEASURES Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DOC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone Split Heat Pump-15 Split Heat Pumps 16 & 17 Split Heat Pumps 18 & 19 1 2 2 T-24 Section Reference on Plans or Specification 1 112(a) 7.70 HSPF 7.70 HSPF 7.70 HSPF 112 a 13.0 SEER 111.0 EER 13.0 SEER / 11.0 EER 13.0 SEER / 11.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121 b) 360 cfm 664 cfm 1311 cfm 121 c No No No 121(c) No No No 121 c 122 a Programmable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Gravity Gravity Gravity 122(g) n/a n/a n/a 123 124 R-4.2 R-4.2 R-4.2 144 a & b n/a n/a n/a 144 a & b 34,789 btuh 69,577 btuh 69,577 btuh 144 a & b n/a n/a n/a 144 a & b 40,827 btuh 76,742 btuh 94,150 btuh 144 c Constant Volume Constant Volume Constant Volume 144 c) 144 c No No No 144 d No No No 144 a No Economizer No Economizer No Economizer 144 Constant Temp Constant Temp Constant Temp 144 (f) Constant Temp Constant Temp Constant Temp 144 k) No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF-1 for performance method duct sealing requirements. EneravPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:23 of 52 WATER SIDE SYSTEM REQUIREMENTS Part 2 of 2 MECH-2-C PROJECT NAME DATE La Quinta Country Club Clubhouse _ 2/20/2008 - 2 WATER SIDE SYSTEMS: Chillers, Tc ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Reference on Plans or Specification' Equipment Efficiency 112(a) Pipe Insulation 123 Calculated Capacity Proposed Capacity Tower Fan Controls Tower Flow Controls Variable Flow System Design Chiller and Boiler Isolation CHW and HHW Reset Controls WLHP Isolation Valves VSD on CHW, CW & WLHP Pumps > 5 HP DP Sensor Location 1: For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/X in the column. - 2: Water side systems Include wet side system using other liquids such as glycol or brine. ITEM OR SYSTEM TAG(S) Number of Systems MANDATORY MEASURES Water Heater Certification 113 (a) Water Heater Efficiency 113 b Service Water Heating Installation 113 (c) Pool and Spa Efficiency and Control 114 a Pool and Spa Installation 114 b Pool Heater - No Pilot Light 115 (c) Spa Heater - No Pilot Light 115 d Service Hot Water, Pool Heating DHW Heater 3 1 L Reference on Plans or Specification' A.O. SMITH FPS-75-230 76% n/a " n/a n/a n/a 1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and ' paragraph number where the required features are documented. If a requirement is not applicable, put "NIA" Ins the column. NOTES TO FIELD - For Buildffing Del2artment Use Only Run Initiation Time: 02/20/08 10: 8:47 Run Code: 1203530927 EnergyPro 4.4 ' by EnergySoft User Number. 2366 Job Number. 0803-1 Page:24 of 52 F��E7CHANICAL VENTILATION MECH-3-C PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008 PRESCRIPTIVE. REHEAT LIMITATION Section 144(d) MECHANICAL VENTILATION Section 121 b 2 AREA BASIS OCCUPANCY BASIS VAV MINIMUM A ZONEISYSTEM B D02 10 arm— -- d= C m 1,0 mm 3 0 D @'<3 x D t7 n m rt v +y 3 E I z m3 0Cr vm m -, 0, F I rawM a 3 G tT 3 mOg xA Cn �tv 'r .. 0 2. H m v30 O � C °, < D I 0;S -n CA 3 m D.� J No ° c)mo„ 71 f✓! 3c6 v m � o K �� y 0 A r� L �n o wo3o3i 7x om -n °� M m m 9� o3 3 N y Dining 1,12E 0.50 562 562 562 Entry 14 0.15 21 21 21 Hallway 45E 0.15 68 68 68 Packaged Heat Pump-1 Total 652 652 Kitchen 1,642 0.15 246 246 800 Office 91 0.15 14 14 14 Hall 173 0.15 26 26 26 Storage 456 0.15 69 69 69 Packaged Heat Pump-2 Total 355 908 Storage 216 0.15 32 32 32 Dining 1,72. 0.50 862 862 862 Hall 34E 0.1552 52 52 Packaged Heat Pumps-3 & 4 Total 946 946 Lobby 1,286 0.15 193 193 193 upport 1,17E 0.15 177 177 177 Packaged Heat Pumps 5 & 6 Total 370 370 Storage 3E 0.15 5 5 5 Bar 274 0.60 137 137 137 Lounge 1,154 0.50 .577 577 577 Packaged Heat Pump-7 I Total 719 719 Meeting Room 61E 0.50 308 308 308 Packaged Heat Pump-8 Total 308 308 Offices 46 0.15 69 1 69 69 Waiting Area 158 0.15 24 24 24 Support .389 0.15 58 58 58 C Minimum ventilation rate per Section 121 Table 121-A E Based on fixed seat or the greater of the ex ected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seatin . H Required Ventilation Air REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G). I Must be areater than orequal to H or use Transfer Air column N to make up the difference. J Design fan supply cfm (Fan CFM) x 30%; or K Condition area (R sq.) x 04 &n/fL sq.; or L Maximum of Columns H, J, K, or 300 cfm M This must be less than orequal to Column L and areater that orequal to the sum of Columns H + N. N Transfer air must be provided where the Required Ventilation Air (column 1) Is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:25 of 52 FOMECHANICAL VENTILATION MECH-3-C PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008 PRESCRIPTIVE REHEAT LIMITATION Section 144 d MECHANICAL VENTILATION Section 121 b 2 AREA BASIS OCCUPANCY BASIS VAV MINIMUM A ZONE/SYSTEM B a� u1-.a C d9C) ®m n n 'o°. D W�3 xD n 8, � .. E Z m3 otS m � ° F I m�w7 '3a-n � ' � G m�3 xo w7 T� 'PI .. » H 111 �mA �x0 � �. L V D I c>;® -n ! � D 7 J o, nmO, -neC 3� 0 1 � K n T 3x° o � J► L oo � C IS3� oy (i = + -n M y o3_ 3 7 D N fe m ' D Office 162 0.15 24 24 24 Offices 631 0.15 95 95 95 Packaged Heat Pump-9 Total 270 270 ork Shop 120 0.151 18 18 18 Storage 57 0.25T 14 14 Lockers 13 0.15 Support 1,01 0.15 Split Heat Pump-1 Total Lounge 34 0.50 171 f4848 Storage 43 0.15 65 Support 31 0.15 48 Split Heat Pump-2 Total 284 284 Hack Bar 34E 0.50 174 174 174 Kitchen 30 0.15 45 .45 45 torage 12 0.15 18 18 18 Hallway 22 0.15 33 33 33 Split Heat Pump-3 Total 271 271 Lounge 1,364 0.50 682 682 682 Bar 151 0.50 76 76 76 Split*Heat Pumps 4 & 5 Total 758 758 Laundry 108 0.15 16 16 16 ttendant 283 0.15 42 42 42 Locker 1,447 0.15 217 217 217 Restrooms 1,57 0.15 236 236 1,500 Hallway 61 0.15 92 92 92 C Minimum ventilation rate per Section 121. Table 121-A E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load fore ress purposes fors aces without fixed seating. H Required Ventilation Air REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G). i Must be greater than orequal to H or use Transfer Air column N to make up the difference. J Design fan supply cfm (Fan CFM) x 30%; or K Condition area (ft. s .) x 04 dm/fL sq.; or L Maximum of Columns H. J, K or 300 cfm M This must be less than orequal to Column L and greater that orequal to the sum of Columns H . N. N Transfer air must be provided where the Required Ventilation Air (column I) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:26 of 52 flIIECHANICAL VENTILATION MECH-3-C PROJECT NAME I nr tints o rntry Club Clubhouse2/20/2008 I VG viGIM - DATE L_ PRESCRIPTIVE REHEAT LIMITATION Section 144 d VAV MINIMUM MECHANICAL VENTILATION Section 121 N21 AREA BASIS OCCUPANCY BASIS A ZONEfSYSTEM B �nT C Al d v .pp. D 4-3 3 E m3 vmo� °� F. vn G '� 3 mom xc H m vo3ip x ° v D I c>>.m " arm J p �No3dv 3c0o ,� a rK L pZ0 p—�D� wxKDn poD T=� 3` M »7 D N Split Heat Pumps 6,7 & 8 Total 604 1,868 Retail Sales 1,09C 0.25 272 272 272 Offer 11E 0.15 17 17 17 Storage Split Heat Pumps 9 & 10 143 0.15 21 Total 21 311 21 311 , Retail Zone 272 0.25 68 68 68 Dressing 26 0.15 4 4 4 Hallway 34 0.15 51 51 51 Split Heat Pump-11 Total 123 123 Exercize 2,714 0.15 407 407 407 r Storage 132 0.15 20 20 20 Split Heat Pumps 12, 13 & 14 Total 427 427 Lobby 19 0.15 30 30 30 Gallery 36EO.50 54 54 54 Hallway 55 276 276 276 Split Heat Pump-15 Total 360 360 Recreation 1,288 0.50 644 644 644 Office 132 0.15 20 1 20 20 Split Heat Pumps 16 & 17 Total 664 664 Retail Zone 29C 0.25 72 72 72 11 Retail 13 0.25 33 33 33 Hallway 717 0.15 108 108 108 Storage 263 0.15 39 39 39 Laundry10 0.15 15 15 15 Support 28 0.15 43 1 1 43 43 C Minimum ventilation rate per Section 121 Table 121-A E Based on fixed seat or the cireater of the expected number of occupants and 50% of the CBC occupant load for egress ourooses fors aces without fixed seating. H Required Ventilation Air (REQ'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS (column D or G). I Must be greater than orequal to H or use Transfer Air column N to make up the difference. J Design fan supply dm Fan CFM) x 30%; or K Condition area ft. sq. x 04 &n ff. sq.; or L Maximum of Columns H, J. K, or 300 cfrn M This must be less than orequal to Column L and waster that orequal to the sum of Columns H + N. N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air'(column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0603-1 Page:27 of 52 fOftECHANICAL VENTILATION MECH-3-C PROJECT NAME La Quinta C . ountry, Club Clubhouse DATE 2/20/2008 PRESCRIPTIVE REHEAT LIMITATION Section 144 d MECHANICAL VENTILATION Section 121 b 2 AREA BASIS OCCUPANCY BASIS VAV MINIMUM A ZONEISYSTEM B D� mod_ C N o�i a mm�1 q�3 0 D ��3 >K Dn t7m n .. 3 E Z m3 og P. F I m9n rim n 0' 3 G Cr 4C m�� xm n �v n » 3 H m °dO oxo �:< I c>>m 11rm 3D� J °� nmO, �r�0 3°y K n �� m o aA L °° (43�3, � ofA M N� v' 0 3 N d y B Restrooms 1-'090 0. J 164 1,000 Split Heat Pumps 18 & 19 Total 1 475 1,311 c r C Minimum ventilation rate per Section 121, Table 121-A E Based on fixed seat or the reater'of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seating. H Required Ventilation Air (REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS (column D or G). I Must be greater than orequal to H or use Transfer Air column N to make up the difference. J Design fan supply cfin Fan CFM x 30%; or K Condition area R sq. x 04 cfmft sq.; or L Maximum of Columns H. J. K, or 300 chn M This must be less than or equal to Column L and greater that orequal to the sum of Columns H + N. N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. ' EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:28 of 52 L�MIECHANICAL EQUIPMENT DETAILS Part 1 of 2 . MECH-S-C� PROJECT NAME DATE,,,,,—,, --. 10 FEtFiclency Tons PUMPS Equipment Name Equipment Type Qty. Tot Qty GPM BHP Motor Eff. Drive Eff. Pump Control Energy Standby IAN! iNauL. Rated Vol. Condition Factor Loss or Ext. Svstem Name System Type Distribution Type Qty Input (Gals.) Status or RE Pilot R-Val. System Name Fan Type Motor Location CFM BHP Motor Eff. I Drive Eff. CFM BHP yMotor Eff. Drive Eff. Carrier 38QRRR024-3 w/ FX4CO24 Constant Volume Blow -Through 800 0.25 64.0% 100.0% none MECHANICAL. EQUIPMENT DETAILS Part 2 of 2 MECH-S-C� q ENVELOPE MANDATORY. MEASURES ENV-IVIM PROJECT NAME i DATE La Quinta Count Club Clubhouse 2/20/2008 _ DESCRIPTION - -� Designer Enforcement FRI§ 118(a) Installed Insulating Material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20, , Y Chapter 4, Article 3. 0 ' § 118(c) . All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. , a § 117(a) All Exterior Joints and openings in the building that are observable sources of air ' leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. FX]§ 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit. ' and the building, and shall be weatherstripped (except for unframed glass doors r and fire doors). r 0 §.116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards: Manufactured fenestration products must be labeled for U-value according to NFRC procedures: R § 118(e) Demising Walls in,Nonresidential Buildings: • ' The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed_ R-value of no less than R-13 between framing members. e 3 EnergyPro 4.4 by EnergySoft . User Number. 2366 Job Number. 0803-1 Page:32 of 52 MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM ROJECT NAME La Quinta Country Club Clubhouse DESCRIPTION Equipment and Systems Efficiencies 0 @ 11 Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply with the applicable standard. §115(a) Fan type central furnaces shall not have a pilot light. . §A23 Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be insulated in accordance with Standards Section 123. 024 Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards. Controls _ §122(e) Each space conditioning system shall be installed with one of the following: FX§122(e)1A Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The'time switch shall be capable of programming different schedules for weekdays and weekends and have program backup ` capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or ❑ §122(e)1B An occupancy sensor to control the operating period of the system; or §122(e)1C A 4-hour timer that can be manually operated to control the operating period of the system. a §122(e)2 Each space conditioning system shall be installedwith controls that temporarily restart and temporarily operate the system as required to maintain a setback . heating and/or a setup cooling thermostat setpoint. §122(g) Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000 square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided with isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be setback or shut off independently of other isolation areas; and shall be controlled by a time control device as described above. DATE 2/20/2U08 w Enforcement ® " §122(a&b) Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the zone: Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or reduced to a minimum. X §122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to authorized personnel. " 12(b) Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the heating load can be met by the heat pump alone. EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:33 of 52 MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM PROJECT NAME 'La Quinta Country Club Clubhouse y - - DATE 2/20/2008 Description Designer Enforcement ion Ventilation §121(e) Controls shall be provided to allow outside air dampers or devices,to be operated at the ventilation rates as specified on these plans. 0 §122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be provided on the outside air intakes and discharges of all space conditioning and exhaust systems. - XJ §122(0 All gravity ventilating systems shall be'provided with automatic or readily. accessible manually operated dampers in all openings to the outside, except for combustion air. openings. ❑-§121(fj1 Air Balancing: ,The system shall be balanced in accordance with the National I Environmental Balancing Bureau (HEBB) Procedural Standards (1983), or , Associated Air Balance Council (AABC) National Standards (1989); or a§i21(f)2 Outside Air Certification: The system shall provide the minimum outside'air as , shown on the mechanical drawings, and shall be measured and certified by the installing licensed C-20.mechanical contractor and certified by'.(1) the design mechanical engineer, (2) the installing licenced C-20 mechanical contractor,Aor.(3) • . the person with overall responsibility for the design of the ventilation system; or . §121(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous basis4nd displaying that quantity on a readily accessible display divice;`or = , §121(f)4 Another method approved by the Commission. A Service WAter Heating Systems ., I FXJ g 12l(b)2 If a circulating hot water system is installed, it shall have a control capable of automatically turning off the circulating pump(s) when hot water Is not required. 6113(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit ' the outlet temperature to 110 degrees F. , J EnergyPro 4.4 by EnergySoft. User Number. 2366 Job Number. 0803-1 Paae:34 of 52, JHVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Packaged Heat Pum -1 1,722 (Number of Systems I lI Output per System 110,800 Total Output (Btuh) 110,800 Output (Btuh/sgft) 64.3 Output per System 119,400 Total Output (Btuh) 119,400 Total Output (Tons) 9.9 Total Output (Btuh/sgft) 69.2 Total Output (sgft/Ton) 173.' Air System Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM I Sensible .Latent CFM I Sensible 5,053 58,187 22,221 1,685 17,583 0 2,909 879 0 0 652 25,895 2,193 L 652 30,389 4,687 -4,687 2,909 879 98,5801 24.4131 45 043 " CFM per System 4,000 Carrier 50HJ00012-5/6 82,461 30,185 69,203 Airflow (cfm) 4,000 Airflow (cfm/sgft) 2.32 Airflow (cf nfTon) 402.0 Total Adjusted System Output (Adjusted for Peak Design Conditions) 82,461 30,185 TIME OF SYSTEM PEAK Aug 2 pm 69,203 Outside Air % ( ) 16.3 Outside Air (cfm/sgft) 0.38 Jan 12 am Note: values above given at ARI conditions (EATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) 26.0 of 62.7 of Outside Air 652 cfm 69.8 of 12.0 / 77.9 of 30 Outside - 652 cfm 74.7 / 66.6 of 78.9 of Heating Coil 80.8 J 68.6 of Supply Fan 4000 cfm 80.0 of Supply Air Ducts 79.8 of ROOMS 70.0 of k Return Air Ducts y 61.4 / 60.4 of Cooling Coil Supply Fa 4000 cfm 62.5 / 60.8 of Supply Air Ducts n 63.2/61.1oF 67.5% R.H. ROOMS 74.0/66.3OF >% Return Air Ducts'4 EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0603-1 Page:35 of 52 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Packaaed Heat Pump-2 2,364 (Number of Svstems I 111 Total Output (Btuh) Output (Btuh/sgft) Cooling System Output per System Total Output (Btuh) Total Output (Tons) Total Output (Btuh/sgft) Total Output (sgft/Ton) Air System CFM per System Airflow (cf n) Airflow (cfmisgft) Airflow (cfmrTon) Outside Air (%) Outside Air (cfm/sgft) Note: values above given at ARI conditions (EATING SYSTEM PSYCHROMETRI 26.0OF 61.9OF 78.1oF Outside Air 908 cfm Heating Coil 69.9 of 12.0 / 77.9 of Outside —�—� 908 drn 74.5 / 66.5 of 4.4 '000 Total Room Loads Return Vented Lighting Retum Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts ,000 58.4 ,000 ,000 12.211 61�I I TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM I Sensible 5,120 57,837 21,979 1,015 9,636 0 2,892 482 0 0 908 36,207 3,239 908 42,444 4,687 -4,687 2,892 482 109 618 25 218 48 357 5,000 5,000 Carrier 50HJQ0014-5/6 103,163 34,903 86,191 2.12 411.0 18 2 Total Adjusted System Output 1 103,163 34,903 86,191 (Adjusted for Peak Design Conditions) 0.38 TIME OF SYSTEM PEAK Aug 3 pm Jan 12 am 79.0 of O Supply Air Ducts Supply Fan 78.9 OF 5000 cfm ROOMS 70.0 of Return Air Ducts I 81.3/68.80F fC1 62.0/61.OoF 62.8/61.3OF O Supply Air Ducts Cooling Coil Supply Fan 63.4 / 61.5 of 5000 cfm 67.3% R.H. ROOMS 74.0/66.3OF Number. 2366 Return Air Ducts Job Number. 0803-1 36 of 52 FHV7AC_ SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Packaged Heat Pum s-3, & 4 2,286 Number of Systems 2 Heating System Output per System 69,000 Total Output(Btuh) 138,000 Output (Btuhlsgft) 60.4 Cooling System Output per System 76,000 Total Output(Btuh) 152,000 Total Output (Tons) 12.7 Total Output (Btuh/sgft) 66.5 Total Output (sgfUron) 180.5 Air System CFM per System 2,400 Airflow Wrn) 4,800 Airflow (cfm/sgft) 2.10 Airflow (cfm/Ton) 378.9 Outside Air (°/h) 19.7 Outside Air (cfmisgft) 0.41 Note: values above given at ARI conditions 26.0 OF Outside --� 946 cfm 69.8 OF 61.2 OF Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD Heating Coil COIL COOLING PEAK COIL HTG. PEAK CFM I Sensible Latent I CFM I Sensible 5,635 66,679 32,938 1,652 15,689 0. 3,334 784 0 0 946 37,611 2,382 946 44,156 5,113 3,334 121,5 35 319 -5,113 784 56 301 r 50HJQ007-5/6 106,189 38,611 86,191 Total Adjusted System Output 1106189 38,611 86,191 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Jul 3 pm Jan 12 am im Tel 78.1 OF -�@J Supply Fan 4800 cfm 79.1 OF -30Supply Air Ducts 78.9 OF ROOMS 70.0 OF I �_�; I � Retum Air Ducts `S COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 112.0 / 77.9 OF 82.0 / 69.2 OF IQ 61.2 / 60.2 OF 62.2 / 60.6 OF O Supply Air Ducts Outside Air 946 cfm 62.9 / 60.8 of Cooling Coil Supply Fan 4800 drn 68.4% R.H. ROOMS 74.7 / 66.8 °F 74.0 / 66.6 of Return Air Ducts E I EneravPro 4.4 by EnerovSoft User Number. 2366 Job Number. 0803-1 Page:37 of 52_J 1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Packaged Heat Pumps 5 & 6 2,464 NGINEERING Number of Systems 2 Heating System Output per System 69,000 Total Output (Stuh) 138,000 Output (Stuh/sgft) 56.0 Cooling System Output per System 76,000 Total Output (Btuh) 152,000 Total Output (Tons) 12.7 Total Output (Btuh/sgft) 61.7 Total Output (sgftrron) 194.5 Air System CFM per System 2,400 Airflow (cfm) 4,800 Airflow (cfm/sgft) 1.95 Airflow (cfm/Ton) 378.9 Outside Air (%) 7.7 Outside Air (cfm/sgft) 0.15 Note: values above given at ARI conditions (EATING SYSTEM PSYCHROMETRICS 26.0 OF 66.4 OF Outside Air 370 cfm 69.8 OF 111.0 / 77.6 OF Outside 1 - 370 cfm 74.7 / 61.2 °F 4.4 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK , COIL HTG. PEAK CFM I Sensible Latent CFM Sensible 3,818 73,443 6,160 1,350 20,262 0 3,672 1,013 0 0 370 14,263 7,745 370 17,229 5,113 -5,113 3,672 1,013 103 042 13 905 34 404 irrier 50HJQ007-5/6 119,064 11,850 86,191 Total Adjusted System Output 119,0641 11,850 86,191 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Jul 2 1 Jan 12 am im Temperatures at Time of Heating Peak) 83.3 OF 84.3 OF `O Su I Air Ducts Heating Coil 0 PP Y -1 ` W Supply Fan 84.1 OF 4800 drn ROOMS 70.0 OF I k Retum Air, Ducts 4 77.5 / 62.8 OF 54.2 / 53.0 OF 55.2 / 53.4 OF O Supply Air Ducts Cooling Coil Supply Fan 55.9 / 53.7 OF 4800 drn 47.6% R.H. ROOMS 74.0 / 61.0 OF User Number. 2366 Retum Air Ducts Job Number. 0803-1 of 52 1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Packaged Heat Pump-7 - 1 464 ;NGINEERING CH Number of Systei Output per System 110,800 Total Output (Btuh) 110,800 Output (Btuh/sgft) 75.7 Cooling System output per System 119,400 Total Output (Btuh) 119,400 Total Output (Tons) 9.9 Total Output (Btuhlsgft) 81.6 Total Output (sgftlron) 147.1 Air System CFM per System 4,000 Airflow (cfm) 4,000 Airflow (cfmisgft) 2.73 Airflow (cfm/Ton) 402.0 Outside Air (%) 18.0 Outside Air (cfm/sgR) 0.49 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS (Airs 26.0 OF 62.0 OF Outside Air 719 dm 69.9 OF 112.0 / 77.9 OF Outside Air er-y 719 cfm 74.6 / 67.3 °F 4.4 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM I Sensiblel Latent CFM I Sensible 4,595 49,445 26,362 898 8.842 0 2,472 442 0 0 719 28,648 443L 719 33,607 4,687 -4,687 2,472 442 91 974 26,8051 38 646 r 50HJ00012-5/6 81,323 32,824 69,203 Total Adjusted System Output 81,323 32,824 69,203 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK I Jul 3 pm I Jan 12 am im Tel 78.3 OF Heating Coil -�@-1 Supply Fan 4000 cfm 79.4 OF )� Supply Air Ducts 79.3 OF ROOMS 70.0 OF Return Air Ducts 81.3/69.4OF F .2/61.3°F 63.3/61.7OF O Supply Air Ducts Cooling Coil Supply Fan 63.9 / 61.9 OF 4000 dm 70.6% R.H. ROOMS 74.0 / 67.1 OF User Number. 2366 Return Air Ducts Job Number. 0803-1 of 52 1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008 SYSTEM NAME FLOOR AREA 616 Packaged Heat Pump-8 ENGINEERING CHECKS SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK 1 Number of Systems CFM Sensible Latent CFM FSensible Heating System Total Room Loads 2,293 25,515 6,397 716 Return Vented Lighting 0 Return Air Ducts 1,276 Return Fan o Ventilation 308 12,210 1,385 308 Supply Fan 1,727 Supply Air Ducts 1,2761 TOTAL SYSTEM LOAD 43,8 7,762 7,035 352 0 14,355 -1,727 352 20 366 Output per System 46,500 Total Output (Btuh) 46,500 Output(Btuhlsgft) 75.5 Cooling System Output per System 46,300 Total Output (Btuh) 46,300 Total Output (Tons) 3.9 Total Output (Btuh/sgft) 75.2 Total Output (sgftrron) 159.7 Air System HVAC EQUIPMENT SELECTION CFM per System 1,600 Carrier 50HJ0005-3/5/6 34,290 9,471 29,043 Airflow (cfm) 1,600 Total Adjusted System Output 290 9 471 29,043 Airflow (cfm/sgft) 2.60 Airflow (cfmrron) 414.7 19 2 Outside Air (%) (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK F77 Jul 3 pm Jan 12 am Outside Air (cfm/sgft) 0.50 Note: values above given at ARI conditions EATING SYSTEM PSYCHROMETRICS Airstream Temperatures -at Time of Heating Peak 26.0OF 61.4OF 78.4OF 79.4OF Supply Air Ducts O Outside Air 79.2 OF 308 cfm Heating Coil Supply Fan ROOMS 1600 cfm 70.0 of 69.8 of Retum Air Ducts DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 112.0/77.9OF 81.9l68.8OF 61.8/60.7OF 62.8/61.1OF Supply Air Ducts • O Outside Air of 308 cfm Cooling Coil Supply Fan 63.5 / 61.3 1600 cfm ROOMS 66.2% R.H. 74.0/66.0°F 74.7 / 66.3 OF* ' i Retum Air Ducts EnergyPro 4 4 by EnergySoft User Number 2366 Job Number. 0803-1 Page:40 of 52 1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008 SYSTEM NAME Packaged Heat Pump-9 FLOOR AREA 1,801 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 Heating System COIL COOLING PEAK COIL HTG. PEAK CFM ISensiblel Latent CFM Sensible Total Room Loads 2,299 38,127 3,796 824 12,089 Return Vented Lighting 0 Return Air Ducts 1,906 604 Return Fan 0 0 Ventilation 270 10,753 4,458 270 12,596 Supply Fan 3,182 -3,182 Supply Air Ducts 1,906 604 TOTAL SYSTEM LOAD 57,8311 81254 22 712 Output per System 87,500 Total output (stun) 87,500 Output (Btuh/sgft) 48.61 Cooling System Output per System 91,300 Total Output (Btuh) 91,300 Total Output (Tons) 7.6 Total Output (Btuh/sgft) 50.7 Total Output (sgfflron) 236.7 Air System HVAC EQUIPMENT SELECTION CFM per System 3,000 54,650 Carrier 50HJQ008-5/6 67,491 12,621 Airflow (cfin) 3,000 Airflow (cfm/sgft) 1.67 Airflow (cfmfTon) 394.3 Total Adjusted System Output 67,491 12,621 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Jul 3 pm 54,650 Outside Air (%) 9 0 Outside Air (cfm/sgft) 0.15 Jan 12 am Note: values above given at ARI conditions EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26.0OF 65.9OF 83.O°F 84.0OF O Supply Air Ducts Outside Air 270 din . 83.8 of Heating Coil Supply Fan 3000 cfm ROOMS 70.0 of 69.8 OF Return Air Ducts DOLING SYSTEM PSYCHROMETRICS Airstream Tempe tures at Time of Cooling Peak 112.0 / 77.9 OF Outside Air 270 din 74.6 / 62.6 of 78.0 / 64.2 of 56.8 / 55.7 of 57.8 / 56.1 of O Supply Air Ducts Cooling Coil Supply Fan 58.4 / 56.3 of 3000 cfm 52.6% R.H. ROOMS 74.0 / 62.4 OF Retum Air Ducts EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:41 of 52 AC SYSTEM HEATING AND COOLING LOADS SUMMARY ECT NAME DATE . La Quinta Country Club Clubhouse 2/20/2008 EM NAME FLOOR AREA Split Heat Pump-1 1.330 Number of Systems 1 Heating System Output per System 55,700 Total Output (Btuh) 55,700 Output (Btuh/sgft) 41.9 Cooling System Output per System 57,200 Total Output (Btuh) 57,200 Total Output (Tons) 4.8 Total Output (Btuh/sgft) 43.0 Total Output (sgft/Ton) 279.0 Air System CFM per System 2,000 Airflow (cfm) 2,000 Airflow (cfm/sgft) 1.50 Airflow (cfm/Ton) 419.6 Outside Air (%) 10.3 Outside Air (cfm/sgft) 0.15 Note: values above given at AR] conditions Total Room Loads Return Vented Lighting Return Air Ducts Return Fan. Ventilation Supply Fan Supply Air Ducts TOTAL.SYSTEM LOAD COIL COOLING PEAK I COIL HTG. PEAK CFM Sensible Latent CFM I Sensible 1,479 29,912 4,788 759 20,191 0 1,496 1,010 0 0 205 8,145 3,820L 205 9,505 1,675 -1,675 1,4961 1,010 44,1171 8,6081 30 041 Carrier 38QRRRO60-3 w/ FX4C060 45,458 4,667 34,789 Total Adjusted System Output 45,458 4,667 34,789 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAKAug 3 pm Jan 12 am SEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) 26.0 of 65.1 of 65.8 OF 95.0 of O Supply Air Ducts Outside Air 205 cfm 94.5 °F Supply Fan Heating Coil 2000 cfm ROOMS 69.5 of 70.0 of Return Air Ducts I 1000LING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 112.0 / 77.9 of Outside �� 205 cfm 74.7/62.0 of 78.5 / 63.8 of 79.3 / 64.2 OF =1 55.0 / 53.8 of 0 Supply Fan 2000 cfm Cooling Coil h Retum Air Ducts. 4 Supply Air Ducts 55.7 / 54.1 of 50.2% R.H. ROOMS 74.0 / 61.7 of i EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number: 0803-1 Pane:42 of 52 IHVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008 SYSTEM NAME FLOOR AREA 1,093 Split Heat Pump-2 ENGINEERING CHECKS SYSTEM LOAD COIL COOLING PEAK I COIL HTG. PEAK Number of Systems 1 FCFM]Sensiblel Latent I I CFM I Sensible Heating System Output per System 45,600 Total Room Loads 1,285 17,071 7,713 5,478 43,084 Total Output (Btuh) 45,600 Return Vented Lighting 0 Output (Btuh/sgft) 41.7 Return Air Ducts 854 2,154 Cooling System Return Fan 0 0 Output per System 49,000 Ventilation 284 11,320 1,469 284 12,900 Total Output (Btuh) 49,000 Supply Fan 1,313 -1,313 Total Output (Tons) 4.1 Supply Air Ducts 8541 2,154 Total Output (Btuh/sgft) 44.8 TOTAL SYSTEM LOAD 1 33,0001 9183 58 980 Total Output (sgft Ton) 267.7 Air System HVAC EQUIPMENT SELECTION CFM per System 1,600 Carrier 38QRRR048-3 w/ FX4C048 35,589 10,592 28,481 Airflow (cfm) 1,600 Airflow (cfm/sgft) 1.46 Airflow (cfm/Ton) 391.8 177 Total Adjusted System Output 35,589 10,592 28,481 Outside Air ( %) (Adjusted for Peak Design Conditions) Outside Air (cfmisgft) 0.26 TIME OF SYSTEM PEAK Aug 2 pm Jan 12 am Note: values above given at ARI conditions EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26.00F 61.20F 61.9OF 78.70E Supply Air Ducts O4 Outside Air 284 cfm 77.4 OF Supply Fan Heating Coil ROOMS 1600 cfm 70.0 OF 68.7 OF Retum Air Ducts DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Coolin Peak • 112.0/77.9OF 81.1 /68.3OF 81.9/68.6OF 61.0/60.00dow F Supply Air Ducts O Outside Air 284 Cfm Supply Fan Cooling Coil 61.5 / 60.1 OF 1600 cfm ROOMS 65.4% R.H. 74.0/65.8OF 74.5/66.0OF Retum Air Ducts EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:43 of 52 1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY - �. PROJECT NAME La Quints Country Club Clubhouse DATE 2/20/2008 SYSTEM NAME FLOOR AREA 992 Split Heat Pump-3 ENGINEERING CHECKS SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK Number of Systems 1 CFM Sensiblel Latent CFM Sensible Heating System Total Room Loads 1,747 21,512 7,853 596 6,897 Return Vented Lighting 0 Return Air Ducts 1,076 345 Return Fan 0 0 Ventilation 271 10,798 1,074 271 12,624 Supply Fan .1,675 -1,675 Supply Air Ducts 1,076 345 TOTAL SYSTEM LOAD F 37,740 8,927 18 536 Output per System 55,700 Total Output (Btuh) 55,700 Output (Btuh/sgft) 56.1 Cooling System Output per System 57,200 Total Output (Btuh) 57,200 Total Output (Tons) 4.8 Total Output (Btuh/sgft) 57.7 Total Output (sgftlron) 208.1 Air System HVAC EQUIPMENT SELECTION CFM per System 2,OD0 Carrier 38QRRRO60-3 w/ FX4C060 39,246 14,462 34,789 Airflow (cfm) 2,000 Total Adjusted System Output gg 246 14,462 34,789 Airflow. (cfm/sgft) 2.02 Airflow (cfm/ron) 419.E 135 Outside Air% ( ) (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Jul 2 pm Jan 12 am Outside Air (cfm/sgft) 0.27 Note: values above given at ARI conditions EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26.0°F 63.9°F 64.7,°F 81.0°F Supply Air Ducts 17 • O Outside Air 271 cfm 80.9 OF Supply Fan Heating Coil ROOMS 2000 cfm 70.0 OF 69.8 OF Return Air Ducts DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 112.0 / 77.9 OF 79.6 168.0 OF 80.4 / 68.4 OF 61.9 / 61.0 °F Supply Air Ducts 311 lot O Outside Air 271 cfm Supply Fan 2000 Cooling Coil 62.4 / 61.1 OF ROOMS cfm 66.8% R.H. 74.0/66.2OF 74.5 / 66.3 °F ' Retum Air Ducts EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:44 of 52 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE La Quinta Country, Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Split Heat Pumps 4 & 5 1,515 Number of Systems 2 Heating System Output per System 55,700 Total Output (Btuh) 111,400 Output (Btuh/sgft) 73.5 Cooling System Output per System 57,200 Total Output (Btuh) 114.400 Total Output (Tons) 9.5 Total Output (Stuh/sgfl) 75.5 Total Output (sgft/ron) 158.9 Air System CFM per System 2,000 Airflow (cfm) 4,000 Airflow (cfm/sgft) 2•64 Airflow (cfm/Ton) 419.6 Outside Air (%) 18.9 Outside Air (cfm/sgft) 0.50 Note: values above given at ARi conditions 26.0 of 61.6 of Outside Air �- 758 cfm Supply Fan 4000 drn 69.9 of 12.0 / 77.9 of Out._.�� side Air 758 cfm 74.6/68.70F Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM ISensiblel Latent I I CFM I Sensible 5,327 50,823 27,914 1,204 10,972 0 2,541 549 0 0 758 30,152 -3,425 758 35,367 3350 -3,350 2,541 549 93 676 24 489 44 085 Carrier 38QRRR060-3 w/ FX4C060 76,750 35,307 69,577 Total Adjusted System Output 76,750 35,307 69,577 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Jul 3 pm Jan 12 am ream Temneratures at Time of Heatina Peak) 62.40F -n 78.70F Heating Coil k Retum Air Ducts 4 81.7 / 70.6 of 82.5 / 70.9 of M. 64.4 / 63.5 of Supply Fan 4000 cfm Cooling Coil Cooli �% Return Air Ducts `i Supply Air Ducts 78.6 of ROOMS 70.0 of Supply Air Ducts 65.0/63.7OF 76.4% R.H. ROOMS 74.0 / 68.6 of Enem vPro 4.4 by EnerwSoft User Number. 2366 Job Number. 0803-1 Page:45 of 52 1 1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME La Quinta Country Club Clubhouse DATE 2/20/2008 SYSTEM NAME FLOOR AREA 4,027 Split Heat Pumps 6 7& 8 ENGINEERING CHECKS SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK Number of Systems 3 CFM Sensible Latent CFM Sensible Heating System Total Room Loads 3,168 28,437 20,196 L81,045 138,304 Return Vented Lighting 0 Return Air Ducts 1,422 6,915 Return Fan 0 0 Ventilation 1,868 75,104 -3,055 1,868 85,322 Supply Fan 5,025 -5,025 Supply Air Ducts 1,422 6,915 TOTAL SYSTEM LOAD 120 629 17,141 232 431 Output per System 55,700 Total Output (Btuh) 167,100 Output (Btuh/sgft) 41.5 Cooling System Output per System 57,200 Total Output (Btuh) 171,600 Total Output (Tons) 14.3 Total Output (Stuh/sgft) 42.6 Total Output (sgftfTon) 281.6 Air System HVAC EQUIPMENT SELECTION CFM per System 2,000 Carrier 38ORRRO60-3 w/ FX4C060 136,823 32,754 104,366 Airflow (cim) 6,000 Total Adjusted System Output 136,823 32.7541 104,366 Airflow (cfm/sgft) 1.49 Airflow (cf niTon) 419.6 31 1 Outside Air % ( ) (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Feb 11 pm Jan 12 am Outside Air (cfm/sgft) 0.46 Note: values above given at ARi conditions EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26.0OF 55.6OF 56.3OF 72.7OF Supply Air Ducts O4,S Outside Air 1868 cfm 71.6 of Supply Fan Heating Coil ROOMS 6000 cfm 70.0 of 68.9 of Return Air Ducts DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 112.0/77.9OF 86.0/71.2OF 86.8/71.4OF' 65.3/64.00 Supply Air Ducts O Outside Air 1868 cfm Supply Fan Cooling Coil 65.6 / 64.1 of 6000 cfm ROOMS 73.1% R.H. of 74.0 / 67.8 of 74.2 / 67.8 Return Air Ducts --� EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:46 of 52 1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Split Heat Pumps 9 & 10 1 349' ENGINEERING CH Number of Systems 2 Heating System Output per System 45,600 Total Output (Btuh) 91,200 Output (Stuh/sgft) 67.6 Cooling System Output per System 49,000 Total Output (Btuh) 98,000 Total Output (Tons) 8.2 Total Output (Btuh/sgft) 72.6 Total Output (sgftrron) 165.2 Air System CFM per System 1,600 Airflow (cfm) 3,200 Airflow (cfm/sgft) 2.37 Airflow (cf nrron) 391.8 Outside Air (%) 9.7 Outside Air (cfm/sgft) 0.23 Note: values above given at ARI conditions (EATING SYSTEM PSYCHROMETRICS 26.0OF 65.6OF 66.40F Outside Air 311 cfm Supply Fan 3200 cfm 69.9 OF Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD Heating Coil COIL COOLING PEAK COIL HTG. PEAK CFM I Sensiblel Latent I CFM I Sensible 2,193 36,110 11,350 703 9,692 0 1,805 485 0 0 311 12,415 3,736 311 14,532 2,626 -2,626 1,805 485 56,808 15,086 22 567 r 380RRRO48-3 w/ FX4C048 71,350 16,868 56,961 Total Adjusted System Output 71,35U 16,868 56,961 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Jul 3 pm Jan 12 am Temoeratures at Time of Heating Peak) �% Return Air Ducts M Supply Air Ducts 82.9 of ROOMS 70.0 of DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 112.0/77.9OF 78.2/65.5OF 78.9/65.8OF 58.0/57.00 Supply Air Ducts O Outside Air 311 Cfm Supply Fan Cooling Coil 58.5 / 57.2 of 3200cfm ROOMS 57.7% R.H. 74.0/63.8OF 74.5/64.00F �Retum Air Ducts I EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Page:47 of 52 C SYSTEM HEATING AND COOLING LOADS SUMMARY r NAME La Quinta Country Club Clubhouse DATE 2/20/2008 NAME FLOOR AREA Split Heat Pump-11 n A A Number of Systems 1 Heating System Output per System 24,700 Total Output (Btuh) 24,700 Output (Btuh/sgft) 38.6 Cooling System Output per System 24,000 Total Output (Btuh) 24,000 Total Output (Tons) 2.0 Total Output (Btuh/sgft) 37.5 Total Output (sgff/Ton) 320.0 Air System CFM per System 800 Airflow (cfm) 800 Airflow (cfm/sgft) 1.25 Airflow (cfmfTon) 400.0 Outside Air (%) 15.4 Outside Air (cfm/sgft) 0.19 . Note: values above given at ARI conditions SEATING SYSTEM PSYCHROME 26.0 of 62.0 of Outside_ Air 123 cfm Supply Fan 800 cfm 68.6 of 112.0 / 77.9 of �y Outside Air 123 cfm 74.4/65.4 of 63.2 of Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM FSensible. 497 6,787 2,897 2,245 23,740 0 339 1,187 0 0 123 4,930 851 123 5,586 995 -995 339 1,187 14 124 3 748 30 706 Carrier 38QRRRO24-3 w/ FX4CO24 17,525 4,868 15,427 Total Adjusted System Output 17,525 4,868 15,427 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Feb 11 pm Jan 12 am Heating Coil h Return Air Ducts 4 80.2/67.6OF 81.4/68.OoF M 60.8/59.70F Supply Fan 800 dm Cooling Coil Return Air Ducts Supply Air. Ducts W 79.9 of ROOMS 70.0 OF , Supply Air Ducts 61.2 / 59.8 OF 63.5% R.H. ROOMS 74.0 / 65.30F.- I EnergyPro 4.4 by EnergySoft User Number. 2366 Job Number. 0803-1 Pane:48 of 52 A 1HVAC SYSTEM HEATING.AND COOLING LOADS SUMMARY PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Split Heat Pumps 12 13 & 14 2,846 Number of Systems Heating System Output per System 4! 'Total Output (Btuh) 131 Output (Btuh/sgft) Cooling System Output per System 4' Total Output (Btuh) 14• Total Output (Tons) Total Output (Btuh/sgft) Total Output (sgiUTon) Air System CFM per System Airflow (cfm) Airflow (cfm/sgft) Airflow (cfmITon) Outside Air (°k) Outside Air (cfm/sgft) Note: values above given at ARI conditions iEATING SYSTEM PSYCHROMETRICS 26.0 OF 66.0 of 66.8 of Outside Air Q 427 cfm Supply Fan 4800 cfm 69.9 of 3 ,600 Total Room Loads ,800 Return Vented Lighting 48.1 Return Air Ducts Return Fan ,000 Ventilation ,000 Supply Fan 12.2 Supply Air Ducts 51.7 TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM ISensiblel Latent CFM I Sensible 78 852 54.2681 26 708 1,600 4,800 Carrier 38QRRRO48-3 w/ FX4C048 82,713 59,970 85,442 1.69 391.8 89 Total Adjusted System Output g2,713 59.970 85,442 (Adjusted for Peak Design Conditions) 0.15 TIME OF SYSTEM PEAK Jul 3 pm Jan 12 am 83.5 OF Heating Coil k Return Air Ducts ',J Supply Air Ducts 83.4 of ROOMS 70.0 of I DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 112.0/77.9OF 77.8/70.0OF 78.6/70.3OF 62.4/61.8OF O Supply Air Ducts Outside Air 427 cfm Supply Fan Cooling Coil 62.9 / 62.0 of 4800 cfm 78.3% R.H. ROOMS 74.5/69.20F 74.0/69.0OF 4.4 User Number. 2366 Return Air Ducts Job Number. 0803-1 of 52 FHVkC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME I DATE La Quinta Count Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Split Heat Pum =15 1 111 Number of Systems 1 Heating System Output per System 55,700 Total Output (Btuh) 55,700 Output (Stuh/sgft) 50.1 Cooling System Output per System 57,200 Total Output (Btuh) 57,200 Total Output (Tons) 4.8 Total Output (Btuh/sgft) 51.5 Total Output (sqf rron) 233.1 Air System CFM per System 2,000 Airflow (cfm) 2,000 Airflow (cirri/sgft) 1.80 Airflow (cfm/Ton) 419.6 Outside Air (%) 18.0 Outside Air (cfm/sgft) 0.32 Note: values above given at ARI conditions 26.0OF 61.7OF Outside Air 360 cfm Supply Fan 2000 cfm 69.5 of Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK I COIL HTG. PEAK CFM ISensiblel Latent CFM I Sensible 1,693 19,341 7,122 2,542 22,364 0 967 1,118 0 0 360 14,364 1,006 L 360 16,633 1,675 -1,675 967 1,118 39,3061 F 39,5591 r 380RRRO60-3 w/ FX4C060 40,827 13,591 34,789 Total Adjusted System Output 40,827 13,591 34,789 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK Jun 5 pm Jan 12 am 62.4OF arm 78.8OF Heating Coil k Return Air Ducts 4 Supply Air Ducts 78.3 of ROOMS 70.0 of I OGLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 112.0 / 77.9 of 81.2/68.9 of 82.0 / 69.1 of 62.8 / 61.8 of O Supply Air Ducts Outside Air 360 cfm Supply Fan Cooling Coil 63.3 / 61.9 of 2000 cfm 68.1% R.H. ROOMS 74.5/66.60F 74.0/66.5OF 4.4 User Number. 2366 Retum Air Ducts Job Number. 0803-1 of 52 'W".. .j 1HV C SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Split Heat Pumps 16 & 17 1,420 - Of Output per System 55,700 Total Output (Btuh) 111,400 Output (Btuh/saft) 78.5 Cooling System Output per System 57,200 Total Output(Btuh) 114,400 Total Output (Tons) 9.5 Total output (Btuh/sgft) 80.6 Total Output (sgft/Ton) 149.0 Air Syr tem CFM per System 2,000 Airflow (cfm) 4,000 'Airflow (cfm/sgft) 2.82 Airflow (cfm/Ton) 419.6 Outside Air (%,) 16.6 outside Air (cfm/sgft) 0.47 Note: values above given at ARI conditions (EATING SYSTEM PSYCHROMETRICS (p 26.0 of 62.5 of 63.3 of Outside Air 664 drn Supply Fan 4000 cfm 69.8 of 12.0 / 77.9 of Outside 664 cfrn 74.6168.0 of 4.4 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK 11COILHTG.PEAK CFM Sensible Latent 11CFM1 Sensible 5,297 54,970 23,995 1,727 17,377 0 2,748 869 0 0 664 26,388 -1,151 664 30,939 3,350 -3,350 2,748 869 94,087 22,844 46 703 r 38QRRRO60-3 w/ FX4C060 76,742 33,770 69,577 Total Adjusted System Output 76,742 33,770 69,577 (Adjusted for Peak Oesign Conditions) TIME OF SYSTEM PEAK Jul 2 pm Jan 12 am 79.7 of Heating Coil h Retum Air Ducts '*I ROMETRICS (Airstream Temperatures at 80.8 / 69.8 of 81.6 / 70.1 of 63.6 / 62.7 of 0 Supply Fan Cooling Coil 4000 cfm User Number. 2366 Return Air Ducts Job Number. 0803-1 Supply Air Ducts W 79.5 of ROOMS 70.0 of I . Supply Air Ducts 64.2/62.9OF 73.2% R.H. ROOMS 74.0/67.8OF of 52 1e .1' RV 'C SYSTEM HEATING AND COOLING LOADS. SUMMARY PROJECT NAME DATE La Quinta Country Club Clubhouse 2/20/2008 SYSTEM NAME FLOOR AREA Split Heat Pumps 18 & 19 2,882 Number of Systems 2 Heating System Output per System 55,700 Total Output (Btuh) 111,400 Output (Btuh/sgft) 38.7 Cooling System Output per System 57,200 Total Output (Btuh) 114,400 Total Output (Tons) 9.5 Total Output (Btuh/sgft) 39.7 Total Output (sqf rron) 302.3 Air System CFM per System 2,000 Airflow (cfm) 4,000 Airflow (cfm/sgft) 1.39 Airflow (cfmrron) 419.6 Outside Air (%) 32.8 Outside Air (cfm/sgft) 0.45 Note: values above given at ARI conditions 26.0 of Outside 1311 cfm 69.0 of 12.0 / 77.9 of out—�' 1 side Air 1311 afm 74.3 / 67.5 of 4.4 by Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD 54.9 of 55.7 of Supply Fan Heating Coil 4000 cfm COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM Sensible 3,156 27,964 8,657 82,865 87,460 0 1,398 4,373 0 0 1,311 52,563 -228 1,311 59,960 3,350 -3,350 1,398 4,373 93,1798 428 152 816 r 38QRRRO60-3 w/ FX4C060 94,150 18,760 69,577 Total Adjusted System Output �� 150 18,7so 69,577 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Jul 2 pm Jan 12 am k Return Air Ducts ',1 86.7/71.1OF 87.5/71.3OF 65.3/64.00 0 Supply Fan Cooling Coil 4000 cfm User Number. 2366 Return Air Ducts Job Number. 0803-1 Supply Air Ducts 71.0 of ROOMS 70.0 of I Supply Air Ducts 65.7164.1 OF 71.5% R.H. ROOMS 74.0/67.4OF of 52