Loading...
Malaga Estates (Plans 1-3) Title 24MALAGA ESTATES AT CORAL MOUNTAIN La Quinta, Ca Climate Zone # 15 F2005 Energy Code Compliancel BEG Project No.: 27031 REVISED: R.T. Hughes LLC Scheurer Architects Inc. lie CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION Heritage Energy Group, LLC -July 30, 2007 Title 24 Energy Calculations & Mechanical L Tel: (949) 789-7221 Fax: (949) 789-7222J flyf@�N 8 w AUG 0 1 200? CEATIFICA-TE OF COMPLIANCE: RESIDENTIAL C OMPUTER METHOD -lR Page 8 CF Project Title ........... Date..07/30/07 15:34:41 MICROPAS7 v7.10 File-2703lPl Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------ ------ REMARKS COMPLIANCE STATEMENT --------------------- This certi ficate of compliance lists the building f eatures and performance specifications needed to comply with Title-24,�Parts 1 and 6 of the California Code of Regulations, and the administrative regulations to implement them. This certificate has been signed by the individual with overall design responsibility. DESIGNER or OWNER DOCUMENTATION AUTHOR Name .... Name .... Sam Maimone Company. R.T. Hughes LLC Company. Heritage Energy Group, LLC Address. 78-900 Ave 47 #200 Address. 470 Wald La Quinta CA 92253 Irvine, CA 92618 Phone ... 760 771-8890 Phone ... 949-789-7221 License. Signed.. Signed.. (date) (date) Name .... Title ... Agency.. Phone ... Signed. . (date) 6 .2 CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD ---------- CF-lR Page 1 Project Title ....... * ... Plan 1A Date..07/30/07 15:34:41 Project Address ........ Malaga Estates.Coral Mtn --------------------- La quinta *v7.10* I I Documentation Author ... Sam Maimone I Building Permit # Heritage Energy Group, LLC 470 Wald I Plan Check Date Irvine, CA 92618 1 1 949-789-7221 1 Field Check/ Date Climate Zone ........... 15 ------------ Compliance Method ...... MICROPAS3 v7.10 for 2005 ---------- Standards by Enercomp, Inc. I MICROPAS7 v7.10 File-27O3lPl Wth-CTZ15SO5 Program -FORM CF -IR User#-MP0940 User -Heritage Energy ---------------------------------------------------------------------------- Group, LL Run- -------------------- MICROPAS7 ENERGY USE SUMMARY ------- - ----------------------------- Energy Use Standard Proposed Compliance (kTDV/sf-yr) ----------------------- ---------- Design ---------- Design Margin Space Heating .......... 2.60 1.94 --------- 0.66 Space Cooling .......... 70.16 70.94 -0.78 Water Heating .......... 8.02 -------- 6.42 1.60 North Total -------- 80.78 79.30 -------- 1.48 Space Heating .......... . 2.60 2.51 0.09 Space Cooling .......... 70.16 69.62 0.54 Water Heating .......... 8.02 --------- 6.42 1.60 East Total -------- 80.78 78.55 -------- 2.23 Space Heating .......... 2.60 2.44 0.16 Space,Cooling ............ 70.16 67.90 2.26 Water Heating ........ 8-.02 ---------- 6.42 1.60 South Total -------- �.80.78 76.76 --------- 4.02 = Space Heating .......... 2.60 1.93 0.67 = Space Cooling o ... 70.16 69.83 0.33 = Water*Hea ting ........... 8.-02 -------- 6.42 1.60 West Total -------- 80.78 78.18 -------- 2.60 Building complies with Computer Performance HERS Verification R6quired for Compliance CEI�TIFICgTE --------------- OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 2 --------- ---------- Project Title .......... Plan 1A Date..07/30/07 15:34:41 I MICROPAS7 v7.10 File -27031P1 Wth-CTZ15SO5 Program -FORM CF-lR ----------------------------------------------------- User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------- 19 GENERAL INFORMATION 258 ------------- HERS Verification ...... ... Req�ired Wood Conditioned Floor Area ..... 3014 sf 19 Building Type ......... ...... Single Family Detached 0.025 Construction Type ......... New 20 Fuel Type .................. . NaturalGas A18 Building Front Orientation. Cardinal - N,E,S,W No Number of Dwelling Units ... 1 Number of Building Stories. 2 Weather Data Type ............ FullYear Floor Construction Type .... Slab On Grade Number of Building Zones... 3 Conditioned Volume ......... 30850 cf Slab -On -Grade Area ......... 2587 sf Glazing Percentage ........ 17.8 % of floor area Average Glazing U -factor ... 0.37 Btu/hr-sf-F Average Glazing SHGC ....... 0.29 Average Ceiling Height ..... 10.2 ft BUILDING ZONE INFORMATION - - - - - - - - - - - - - Floor # of -# of - - - - - - - - - - Cond- Thermo- Vent Vent Verified Area Volume Dwell Peop7 it- stat Height Area Leakage or Zone Type -------------- (sf) (cf) Units le ----- ------ ----- ----- ioned Type (ft) (sf) Housewrap ----- -------- ----- LIV DIN ------- ---------- Residence 1350 14850 0.45 3.1 Yes Setback 8.0 Standard 3.8 SLA MBR BR2 Residende 1237 12370 0.41* 2.9 Yes Setback 8.0 Standard 3.8 SLA 2ND FLR Residence 427 3630 0.14 1.0 Yes Setback 8.0 Standard 3.8 SLA OPAQUE SURFACES --------------- U_ Sheath- Solar Appendix Frame Area fact- Cavity ing Act Gains IV Location/ Surface ------------ Type (sf) or R-val R-val ----- ---- ----- --- 7- ___7 Azm Tilt Reference Comments - --- ---- --- --------- -------------- LIV DIN 2 Wall. 3 Wall 4 Wall 5 Wall 6 Roof 7 Door MBR BR2 9 Wall Wood 169 0.074 19 Wood 83 0.074 19 Wood 258 0.074 19 Wood 379 0.074 19 Wood 1350 0.025 38 Wood 20 0.330 0 Wood 263 0.074 19 0 180 90 Yes IV.9 A5 0 270 90 Yes IV.9 A5 10 0 90 Yes IV.9 A5 0 90 90 Yes IV.9 A5 0 n/a 0 Yes-IV.1 A18 io 0 90 No None 0 180 90 Yes IV.9 A5 S. CERTIFICATE OF COMPLIANCE: RESIDiNTIAL COMPUTER METHOD CF -1R Page 3 Project Title .......... Plan 1A Date..07/30/07 15:34:41 MICROPAS7 v7.10 File-2703lPl Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User-Heritage'Energy Group, LL Run- I -------------------------------------------- --------- ------------------------- LIV DIN 1 SlabEdge 104 0.730 R-0 No IV.26 Al MBR BR2 8 SlabEdge 0.730 R-0 Nd IV.26 Al I Orientation LIV DIN 1 Door Back (S) 5 Door Right (W) 12 Door Front (N) 13 Wind Front (N) 15 Wind Left (E) 20 Door Front (N) MBR BR2 2 Wind Back (S) 3 Wind Back (S) 6 Wind Right (W) 7 Wind Right (W) 8 Door Right (W) 9 Door Right (W) 10 Wind Right (W) FENESTRATION SURFACES --------------------- Exterior Area U_ Act Shade (sf) factor SHGC Azm Tilt Type - ----- ------ ----- --- ---- -------- Location/Comments ------------------------ 128.0 0.350 0.280 180 90 Standard 1/wood,S.G.D.low-e 60.0 0.400 0.280 270 90 Standard 5/french door low -e 18.7 0.400 0.280 0 90 Standard 12/french door low -e 14.0 0.350 0.320 0 90 Standard 13/wood,operable low -e 6.0 0.350 0.320 90 90 Standard 15/wood,operable low -e 28.0 0.400 0.280 '0 90 Standard 20/french door low -e 45.0 0.350 0.320 180 90 OPAQUE SURFACES --------------- 0.350 0.320 180 90 3.0 0.350 U_ Sheath- 90 25.0 Solar Appendix 270 90 Frame Area fact- Cavity ing Act 0.400 Gains IV Location/ Surface ------------ Type ----- (sf) ---- or ----- R-val ----- R-val Azm Tilt Reference Comments 11 Wall Wood 390 0.074 19 ----- 0 -------- 270 90,Yes --- --------- -------------- IV.9 A5 13 Wall Wood 30 0.074 19 0 0 90' Yes IV.9 A5 15 Wall Wood 277 0.074 19 0 90 90 Yes IV.9 A5 17 Wall Wood 198 0.074 19 0 0 90 No IV.9 A5 18 Roof Wood 816 0.025 38 0 n/a 0 Yes IV.1 A18 2ND FLR 10 Wall Wood 183 0.074 19 0 180 90 Yes IV.9 A5 12 Wall Wood 161 0.074 19 0 270 90 Yes IV.9 A5 14 Wall Wood 169 0.074 19 0 0 90 Yes IV.9 A5 16 Wall Wood 131 0.074 19 0 90 90 Yes IV.9 A5 19 Roof Wood 427 0.025 38 0 n/a 0 Yes IV.1 A18 PERIMETER ---------------- LOSSES Appendix Length F2 'Insul Solar IV Location/ Surface ------------ 1(ft) ------ Factor -------- R-val ---- -- Gains ----- Reference ------- --- Comments ---------------------- LIV DIN 1 SlabEdge 104 0.730 R-0 No IV.26 Al MBR BR2 8 SlabEdge 0.730 R-0 Nd IV.26 Al I Orientation LIV DIN 1 Door Back (S) 5 Door Right (W) 12 Door Front (N) 13 Wind Front (N) 15 Wind Left (E) 20 Door Front (N) MBR BR2 2 Wind Back (S) 3 Wind Back (S) 6 Wind Right (W) 7 Wind Right (W) 8 Door Right (W) 9 Door Right (W) 10 Wind Right (W) FENESTRATION SURFACES --------------------- Exterior Area U_ Act Shade (sf) factor SHGC Azm Tilt Type - ----- ------ ----- --- ---- -------- Location/Comments ------------------------ 128.0 0.350 0.280 180 90 Standard 1/wood,S.G.D.low-e 60.0 0.400 0.280 270 90 Standard 5/french door low -e 18.7 0.400 0.280 0 90 Standard 12/french door low -e 14.0 0.350 0.320 0 90 Standard 13/wood,operable low -e 6.0 0.350 0.320 90 90 Standard 15/wood,operable low -e 28.0 0.400 0.280 '0 90 Standard 20/french door low -e 45.0 0.350 0.320 180 90 12.0 0.350 0.320 180 90 3.0 0.350 0.350 270, 90 25.0 0.350 0.320 270 90 40.0. 0.400 0.280 270 90 20.0 0.400 0.280 270 90 12.5 0.350 0.320 270 90 Standard 2/wood,operable low -e Standard 3/wood,operable low -e Standard 6/wood,fixed, low -e Standard 7/wood,operable low -e Standard 8/french door low -e Standard 9/french door low -e Standard 10/wood,operable low -e CEIMFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 4 Project Title .......... Plan 1A Date..07/30/07 i5:34:41 MICROPAS7 v7,.10 File-2703lPl Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- -------------------------------------------------------------------------- FENESTRATION SURFACES Exterior Area U_ Act Shade .Orientation (sf) factor SHGC Azm Tilt Type Location/Comments ------------------ ----- ----- ----- --- - -- -------- ------------------------ 16 Door Left (E) 48.0'0.400 0.280 90� 90 Standard 16/french door low -e 17 Wind Left (E) 5.3 0.350 0.320 90 90 Standard 17/wood,operable low -e 2ND FLR 4 Wind Back (S) 4.5 0.350 0.320-180 90 Standard 4/wood,operable low -e 11 Wind Right'(W) 9.0 0.350 0.320 270 90 Standard 11/wood,operable low -e 14 Wind Front (N) 18.0 0.350 0.350,- 0 90 Standard 14/wood,fixed, low -e 18 Wind Left (E) 4.5 0.350 0.320 90 90 Standard 18/wood,operable low -e 19 Door Left (E) 35.0 0.400 0.280 90 90 Standard 19/french door low -e OVERHANGS --- Window --- ----------- 70verhang ------------- Area Left Right Surface (sf) Width Height. Depth Height Extension Extension ----------- ----- ----- ------ ----- ------ --------- --------- LIV DIN. 1 Door 128.0 n/a 8 1 1 n/a n/a 5 Door 60.0 n/a 8 1.5 2 n/a n/a MBR BR2 16 Door 48.0 n/a 8 12 1 n/a n/a 2ND FLR 11 Window 9.0 n/a 6 1.5 1 n/a n/a 18 Window 4.5 n/a 3 4 1 n/a n/a 19 Door 35.0 n/a 7 4 1 n/a n/a SLAB SURFACES ------------- Area Slab Type (sf) ----------- 7 ---- ------ LIV DIN Standard Slab 1350 MBR BR2 Standard Slab 1237 0 CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF -1R Page 5 Project Title .......... *Plan 1A Date..07/30/07 15:34:41 I MICROPAS7 v7.10 File -27031P1 Wth-CTZ15SO5 Program -FORM CF -1R I User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------- ----------------------------------------------------- Orientation of Maximum ...... Front Facing 90 deg (E) Sizing Location ............. LA QUINTA Winter Outside Design ...... 26 F Winter Inside Design ..... :. 70 F Summer Outside Design.�,.... 111 F Summer Inside Design ......... 75 F Summer Range ............... 34 F kVAC SYSTEMS ------------ Verified Number Verified Verified Verified Verified Maximum System of Minimum Refrig Charg!12 Adequate,Fan Watt Cooling Type ------------ Systems ------- Efficiency ----------- EER or TXV Airflow . Draw Capacity LIV DIN ----- ------------- -------- - ------ -------- Furnace 1 0.800 AFUE n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No MBR BR2 Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No 2ND FLR Furnace 1 �0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No HVAC SIZING ----------- Verified Total Sensible Design Maximum Heating Cooling Cooling Cooling System Load Load Capacity Capacity Type ------------- (Btu/hr) ---------- (Btu/hr) ----------- ---------- (Btu/hr) (Btu/hr) LIV DIN ---------- Furnace 22030 n/a n/a' n/a ACSplit n/a 20312 25207 n/a. -MBR.BR2 - Furnace 21589 n/a n/a n/a ACSplit n/a 16446 20410 n/a 2ND FLR Furnace 71091 n/a n/a �/a ACSplit ------------- n/a ---------- 6645 ----- ;� 8246 n/a Total 50709 ------ ---------- 43403 53863 ----------- n/a Orientation of Maximum ...... Front Facing 90 deg (E) Sizing Location ............. LA QUINTA Winter Outside Design ...... 26 F Winter Inside Design ..... :. 70 F Summer Outside Design.�,.... 111 F Summer Inside Design ......... 75 F Summer Range ............... 34 F CEF�TIFICATE OF COMPLIANCE: -RESIDENTIAL COMPUTER METHOD CF -1R Page 6 Project Title .......... Plan 1A Date..07/30/07 15:34:41 MICROPAS7 v7.10 File -27031P1' Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ----------------- -------------------------------------------------------- DUCT SYSTEMS Verified Verified Verified System Duct Duct Duct Surface Buried Type Location., R -value Leakage Area Ducts ------------- ----------- ------- - 7 ----- -------- --------- LIV DIN Furnace Attic R-6 Yes No No ACSplit Attic R'-'6 Yes No No MBR BR2 Furnace Attic R-6 Yes No No ACSplit Attic R76 Yes, No No 2ND FLR Furnace Attic R-6 Yes No No ACSplit Attic R-6., Yes No No INFILTRATION TESTING DETAILS ------------------------ Blower Door Blower Door Leakage Target' Leakage Minimum (CFM50h/SLA) (CFM50h/SLA) -------------- --------------- LIV DIN 1343 3.8 530 1.5 MBR BR2� 1231 3.8 1.5 2ND FLR 425 3.8 1681 1.5 WATER HEATING SYSTEMS Number Tank External Heater in Energy Size Insulation Tank Type Type Distribution Type System' Factor (gal) R -value ---------------- ------- ------------------- ------ -------- ------ ---------- 1 Large Gas Standard n/a 75 R-12 WATER HEATING SYSTEMS DETAIL ------------ 7 --------------- Standby . Internal Tank Recovery Rated Loss- Insulation Pilot System Efficiency Input Fraction 'R -value Light' ------------ ------------ ------------ ---------- --------------- ------- 1 Large 0.76 n/a 0.0318 R-n/a 0 P CERTIFICATE OF COMPLIANCE: RESIDENTIALCOMPUTER METHOD CF-lR Page 7 Project Title .......... Plan 1A Date..07/�0/07 15,:34:41 MICROPAS7 v7.10 File-2703lPl Wth-CTZ15SO5 Program -FORM CF-lR User#-MP09-40 User -Heritage Energy Group, LL Run- -------------------------------- ---------------------------------------------- SPECIAL FEATURES AND MODELING ASSUMPTIONS -------------7----------- 7 --------------- Items in this section -should be documented on the plans, installed to manufacturer and CEC spec�cifications, and verified during plan check and field inspection. This building incorporates HERS verified Infiltration. The Homeowner's Manual must include instructions on how to operate the windows and/or mechanical ventilation to achieve adequate ventilation. .This building incorporates HERS verified Duct Leakage. This is a multiple orientation' building. This printout is for the front facing North. This building incorporates a non-standard Water Heating System. HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified home energy rater under the supervision of a CEC-approved HERS provider using CEC approved testing and/or verification methods and must be reported on the CF -4R installation certificate. This building incorporates HERS verified Infiltration. Target and Minimum CFM values measured at 50 pascals are shown in INFILTRATION TESTING DETAILS above. If the measured CFM50h is above the target, then corrective action must be taken to reduce the infiltration and then retest. Alternatively, the compliance calculations could be redone without infiltration testing. If the measured CFM50h is below the minimum, then the building must meet Uniform mechanical Code requirements for unusally tight construction and corrective action must be taken to either intentionally increase infiltration or provide for mechanical supply,ventilation adequate to maintain the residence at a pressure greater than -5 pascals relative to the outside average air'pressure with other continuous ventilation fans operating This building incorporates HERS'verified Duct Leakage. Target leakage is calculated and documented on the CF -4R. If the measured CFM is above the target, then corrective action must be taken to'reduce the duct leakage and then must be retested. Alternatively, the compliance calculations could be redone without duct testing. If ducts are not installed, then HERS verification is not necessary. CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 1 Project Title .......... Plan 1B 1C Date..07/30/07 15:35:39 Project Address ........ Malaga Estates'Coral Mtn --------------------- La quinta *v7.10*' I' . I I Documentation Author ... Sam Maimone I Building Permit # Energy -Group, LLC ,Heritage 470 Wald I Plan Check / Date Irvine, CA 92618 1 949-789-7221 1 Field Check/ Date Climate Zone ............ 15 --------------------- -Compliance Method ...... MICROPAS7 v7.10 for 2005 Standards by Enercomp, Inc. MICROPAS7 v7.10 File-2703lPlB Wth--=Z15S05 Program -FORM CF-lR Us.er#-MP0940 --------------------- ---------------------------------------------------------- User -Heritage Energy.Grloup, LL Run- ENERGY USE SUMMARY Energy Use ----------------------------- Standard Proposed Compliance (kTDV/sf-yr) ----------------------- ---------- Design ---------- Design Margin Space Heating ........... 2.60 1.95 ---------- 0.65 = Space Cooling .......... 70.20 70.93 -0.73 = Water Heating .......... 8.02 --------- 6.42 1.60 North Total -------- 80.82 79.30 -------- 1.52 = Space Heating .......... 2.60 2.50 0.10 = Space Cooling ........... 70.20 69.62 0.58' = Water Heating .......... 8.02 -------- 6.42 1.60. East Total -------- 80.82 78.54 --------- 2.28 = Space Heating .......... 2.60 2.44 0.16 = Space Cooling .......... 30.20 67.91 2.29 = Water Heating .......... 8.02 6.42 1.60 South Total -------- 80.82 - 76.77 -------- 4.05 = Space Heating ............ 2.60 1.93 0.67 = Space Cooling .......... 70.20 69.85 �0.35 = Water.Heating..; ....... 8.02 -------- 6.42 1.60 West Total -------- 80.82 78.20 -------- - 2.62 Building complies with Computer Performance HERS Verification Required.for Compliance CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD- CF-lR Page 2 Project Title .......... Plan 1B 1C Date..07'/30/07 15:35:39 MICROPAS7 v7.10 File-2703iPlB Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL -Run- --------------- : ------------------------------------------------------------ I ------ GENERAL INFORMATION HERS Verification .......... Required Conditioned Floor Area ..... 3016 sf B , uilding Type .............. Single Family Detached construction Type ......... New Fuel Type ................. NaturalGas Building Front Orientation. Cardinal - N,E,S,W Number of Dwelling Units.... 1 Number of Building Stories. 2 Weather Data Type ........... FullYear Floor Construction Type .... Slab On Grade Number of Building Zones... - 3 Conditioned Volume ......... 30857 cf Slab -On -Grade Area ......... 2583 sf Glazing Percentage .......... 17.8 % of floor area Average Glazing U -factor ... 0.37 Btu/hr-sf-F Average Glazing SHGC ........ 0.29 Average Ceiling Height ..... 10.2 ft BUILDING ZONE INFORMATION 'OPAQUE SURFACES Floor # of # of Cond- Thermo- Vent Vent Verified Area Volume Dwell Peop- it- stat Height Area *Leakage or Zone Type -------------- (sf) ----- (cf) ------ Units ----- le ----- ioned ----- Type - ------ (ft) (sf) Housewrap LIV DIN Reference Comments LIV DIN 7 ----- ------- ---------- Residence 1346 14806 0.45 3.1 Yes Setback 8.0 Standard 3.8 SLA MBR BR2 90 Yes IV.9 A5 3 Wall Wood 83 0.074 19 Residence 1237 1P70 0.41 2.9 Yes Setback 8.-0 Standard, 3.8 SLA 2ND FLR 0 0 90 Yes IV.9 A5 5 Wall Wood 379 Residence 433 3681 0.14 1.0 Yes Setback 8.0 Standard 3.8 SLA 'OPAQUE SURFACES U_ Sheath- Solar Appendix Frame Area fact- Cavity ing Act Gains IV Location/ Surface ------------ type ----- (sf) ---- or ----- R-val ----- R-val ----- Azm Tilt Reference Comments LIV DIN --- ---- --- --------- -------------- 2 Wall Wood 169 0.074 19-. 0 180 90 Yes IV.9 A5 3 Wall Wood 83 0.074 19 0 270 90 Yes IV.9 A5 4 Wall Wood 258 0.074 19 0 0 90 Yes IV.9 A5 5 Wall Wood 379 0.074 19 0 90 90 Yes IV.9 A5 6 Roof Wood 1346 0.025 38 0 n/a 0 Yes IV.1 A18 7 Door Wood* 20 0.330 0 .01 0 90 No None MBR BR2 9 Wall Wood 263 0.074 19, 0 180 90 Yes IV.9 A5 CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 3 Project Title .......... Plan 1B-lC Date..07/30/07 15:35:3� ---------- I MICROPAS7 v7.10 File-2703lPlB Wth-CTZ15SO5 Program-FOR'M CF-lR I User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- n FENESTRATION SURFACES Exterior Area U_ Act Shade Orientation (sf) factor SHGC Azm Tilt Type Location/Comments ------------------ ----- ----- ----- --- - 7 -- -------- ----------- ------------ LIV DIN 1 Door Back (S) 128.0 0.350 0.280 180 90 Standard 1/wood,S.G.D.low-.e 5 Door Right (W) 60.0 0.400 0.280 270 90 Standard 5/french door low -e 12 Door Front (N) 18.7 0.400 0.280 0 90 Standard 12/french door low -e 13 Wind Front (N) 14.0 0.350 0.320 0 90 Standard 13/wood,operable low -e 15 Wind Left (E) 6.0 0.350 0.320 90 90 Standard 15/wood,operable low -e 21 Door Front (N) 28.0 0.400 0.280 0 90 Standard 21/french door low -e MBR BR2 2 Wind Back (S) 45.0 0.350 0.320 180 90 Standard 2/wood,operable low -e 3 Wind Back (S) 12.0 0.350 0.320 180 90 Standard 3/wood,operable low -e 6 Wind Right (W) 3.0 0.350 0.350 270 90. Standard 6/wood,fixed, low -e 7 Wind Right (W) 25.0 0.350 0.320 270 90 Standard 7/wood,operable low -e 8 Door Right (W) 40.0 0.400 0.280.270 90 Standard 8/french door low -e 9 Door Right (W) 20.0 0.400 0.280 270 90 Standard 9/french door low -e 10 Wind Right (W) 12.5 0.350 0.320 270 90 Standard 10/wood,operable low -e OPAQUE SURFACES --------------- U_ Sheath- Solar Appendix Frame Area fact- Cavity ing Act Gains IV Location/ Surface --------- -- Type ----- (sf) ---- or - ----- R-val R-val Azm Tilt Reference Comments 7 11 Wall Wood 390 0.074 ----- 19 --------- 0. ---- 270 90 --- Yes --------- -------------- IV.9 A5 13 Wall Wood 30 0.074 19 0 0 90 Yes IV.9 A5 15 Wall Wood 277 0.074 19 0 90 90 Yes IV.9 A5 17 Wall Wood 198 0.074 19 0 0 90 No IV.9 A5 18 Roof Wood 816 0.025 38 0 n/a 0 Yes IV.1 A18 2ND FLR 10 Wall Wood 183 0.074 19 0 180 90 Yes IV.9 A5 12 Wall Wood 161 0.074 19 0 270 90 Yes IV.9 A5 14 Wall Wood 168 0.074 19 0 0 90 Yes IV.9 A5 16 Wall Wood 131 0.074 19 0 90 90 Yes IV.9 A5 19 Roof Wood 433 0.025 38 0 n/a 0 Yes IV.1 A18 PERIMETER ---------------- LOSSES Appendix Length F2 Insul Solar IV Location/ Surface ------------ (ft) ------ Factor -------- R-val Gains Reference Comments LIV DIN ------- ----- --------- ------- 7 -------------- 1 SlabEdge 104 0.730 R-0 No IV.26 Al MBR BR2 8 SlabEdge 137 0.730 R-0 No IV.26 Al FENESTRATION SURFACES Exterior Area U_ Act Shade Orientation (sf) factor SHGC Azm Tilt Type Location/Comments ------------------ ----- ----- ----- --- - 7 -- -------- ----------- ------------ LIV DIN 1 Door Back (S) 128.0 0.350 0.280 180 90 Standard 1/wood,S.G.D.low-.e 5 Door Right (W) 60.0 0.400 0.280 270 90 Standard 5/french door low -e 12 Door Front (N) 18.7 0.400 0.280 0 90 Standard 12/french door low -e 13 Wind Front (N) 14.0 0.350 0.320 0 90 Standard 13/wood,operable low -e 15 Wind Left (E) 6.0 0.350 0.320 90 90 Standard 15/wood,operable low -e 21 Door Front (N) 28.0 0.400 0.280 0 90 Standard 21/french door low -e MBR BR2 2 Wind Back (S) 45.0 0.350 0.320 180 90 Standard 2/wood,operable low -e 3 Wind Back (S) 12.0 0.350 0.320 180 90 Standard 3/wood,operable low -e 6 Wind Right (W) 3.0 0.350 0.350 270 90. Standard 6/wood,fixed, low -e 7 Wind Right (W) 25.0 0.350 0.320 270 90 Standard 7/wood,operable low -e 8 Door Right (W) 40.0 0.400 0.280.270 90 Standard 8/french door low -e 9 Door Right (W) 20.0 0.400 0.280 270 90 Standard 9/french door low -e 10 Wind Right (W) 12.5 0.350 0.320 270 90 Standard 10/wood,operable low -e CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 4 ---------- Project Title .......... Plan 1B 1C- Date..07/30/07 15:35:39 MICROPAS7 v7.10 File-2703lPlB Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------ FENESTRATION SURFACES 7 ----------------- Exterior Area U� Act Shade Orientation (sf) factor SHGC Azm Tilt Type Location/Comments ------------------ ----- ----- ----- --- ---- -------- --------- 7 -------------- 16 Door Left (E) 48.0 0.400 0.280 90 90 Standard 16/french door low -e 17 Wind Left (E) 5.3 0.350 0.320 90 90 Standard 17/wood,operable low -e 2ND FLR 4 Wind Back (S) 4.5 0.350 0.320 180 90 Standard 4/wood,operable low -e 11 Wind Right '(W) 9.0 0.350 0.320 270 90 Standard 11/wood.operable low -e 14 Wind Front (N) -10.5 0.350 0.350 0 90 Standard 14/wood.fixed, low -e 118 Wind Left (E) 4.5 0.350 0.320 90 90 Standard 18/wood.operable low -e 19 Door Left (E) 35.0 0.400 0 * 280 .90 90 Standard 19/french door low -e 20 Wind Front (N) 8'.8 0.350 0.320 0, 90 Standard 20/wood.operable low -e OVERHANGS --- Window --- ------------- Overhang ------------ Area Left Right Surface (sf) Width Height Depth Height Extension Extension ----------- ----- ----- ------ ----- ------ --------- --------- LIV DIN 1 Door 128.0 n/a 8 1 1 n/a n/a 5 Door 60.0 n/a 8 1.511 2 n/a n/a MBR BR2 16 Door 48.0 n/a 8 12 1 n/a n/a 2ND FLR 11 Window 9.0 n/a 6 1.5.1 1 n/a n1a 18 Window 4.5 n/a 3 4 1 n/a n/a 19 Door 35.0 n/a 7 4 1 n/a n/a SLAB SURFACES ------------- Area Slab Type (sf) ---------------- ------ LIV DIN Standard Slab 1346 MBR BR2 Standard Slab 1237 a CER�IFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 5 Project Title .......... Plan 1B 1C Date -.07/30/07 15:35:39 MICROPAS7 v7.10 File-2703lPlB Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- HVAC SYSTEMS ------------ HVAC SIZING ----------- Verified Total Sensible Verified Maximum Number Heating Verified Cooling Verified Verified Verified Maximum System - of Minimum 11 Refrig Charge Adequate Fan Watt Cooling Type Systems Efficiency EER or TXV Airflow Draw Capacity ------------ LIV DIN ------- ----------- 20292 ----- ------------- -------- -------- -------- Furnace 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No MBR BR2 n/a n/a n/a ACSplit n/a 6701 8317 n/a Furnace 1 0.806 AFUE n/a n/a n/a n/a n/a ACSplit 11 13.00 SEER No No No No No 2ND FLR Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit �l 13.00 SEER '.No No No No No HVAC SIZING ----------- Orientation of Maximum ..... Front Facing 90 deg (E) Sizing Location ............ LA QUINTA Winter Outside Design ...... 26 F winter Inside Design ....... 70 F Summer Outside Design ...... 111 F Summer Inside Design ....... 75 F Summer Range ............... 34 F Verified Total Sensible Design Maximum Heating Cooling Cooling Cooling System Load Load Capacity 'Capacity Type ------------- (Btu/hr) --------- (Btu/hr) ---------- (Btu/hr) ---------- (Btu/hr) ---------- LIV DIN. Furnace 22002 n/a n/a n/a ACSplit n/a 20292 25182 n/a MBR BR2 Furnace 21589 n/a In/a n/a ACSplit n/a 16446 20410 n/a 2ND FLR 1 Furnace 7149 n/a n/a n/a ACSplit n/a 6701 8317 n/a ------------- Total ---------- 50740 ---------- . 43440 , ---------- 53909 ---------- n/a Orientation of Maximum ..... Front Facing 90 deg (E) Sizing Location ............ LA QUINTA Winter Outside Design ...... 26 F winter Inside Design ....... 70 F Summer Outside Design ...... 111 F Summer Inside Design ....... 75 F Summer Range ............... 34 F CER�IFIC,�TE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR' Page 6 Project Title ....... :...Plan 1B 1C Date..07/30/07 --------------------------------------- 15:35:39 MICROPAS7 v7.10 File-2703lPlB Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -He ritage Energy Group, LL -------------------------------- ­ ----------- -------- I ------------------------- Run- DUCT SYSTEMS Verified Verified Verified System Duct Duct Duct Surface Buried Type ------------- Location R -value Leakage Area ------ ---- Ducts LIV DIN ------- ------- -------- --------- Furnace At*tic R'6 Yes No No ACSplit Attic R-6 Yes No No MBA BR2 Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No 2ND FLR Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No INFILTRATION TESTING DETAILS ---------------------------- Blower Door Blower Door Leakage Target Leakage -Minimum (CFM50h/SLA) (CFM50h/SLA) --------------- - ------------- LIV DIN 1339 3.8 529 1.5 MBR BR2 1231 3.8 486 1.5 2ND FLR 431 / 3.8 170 / 1.5 WATER HEATING SYSTEMS Number Tank External Heater in Energy' Size Insulation Tank Type Type Distribution Type System Factor (gal) R -value ---------------- -------- ------------------- ------ -------- ------ ---------- 1 Large Gas Standard 1 n/a 75 R-12 7 WATER HEATING SYSTEMS DETAIL Standby Internal Tank Recovery Rated Loss Insulation Pilot System Efficiency Input Fraction R -value Light ------------------------- ------------ ---------- --------------- 7 ------ 1 Large 0.76 - n/a 0.0318 R-n/a 0 CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 7 ---------- Project Title .......... Plan 1B 1C Date..07/30/07 15:35:39 MICROPAS7 v7.10 File-2703lPlB Wth-CTZ15SO5 Program -FORM CF -1R User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- SPECIAL FEATURES AND MODELING ASSUMPTIONS ----------------------------------------- Items in this section should be documented on the plans, installed to manufacturer and CEC specifications, and verified during plan check and field inspection. This building incorporates HERS verified Infiltration. The Homeowner's Manual must include instructions on how to operate the windows and/or mechanical ventilation to achieve adequate ventilation. This building incorporates HERS verified Duct Leakage. This is a multiple orientation building. This printout is for the front facing North. I I This building incorporates a non-standard Water Heating System. HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified home energy rater under the supervision of a CEC-&pproved HERS provider using CEC approved testing and/or verification methods and must be reported on the CF -4R installation certificate. This building incorporates HERS verified Infiltration. Target and Minimum CFM values measured at.50 pascals are shown in INFILTRATION TESTING DETAILS above. If the measured CFM50h is above the target, then corrective action must be taken to reduce the infiltration and then retest. Alternatively, the compliance calculations could be redone without infiltration testing. If the measured CFM50h is below the minimum, then the building must meet Uniform Mechanical Code requirements for unusally tight construction and corrective action must be taken to either intentionally increase infiltration or provide for mechanical supply ventilation adequate to maintain the residence at a pressure greater than -5 pascals relative to the outside average air pressure with other continuous ventilation fans operating This building incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the CF -4R. If the measured CFM is above,the target, then corrective action must be taken to reduce the duct leakage and then must be retested. Alternatively,�the compliance calculations could be redone without duct testing. If ducts are not installed, then HERS verification is not necessary. k CERiIFICATE OF COMPLIANCE: RESIDENTIAL.COMPUTER METHOD CF-�R Page 8 ---------- Project Title .......... Plan 1B Date..07/30/07 15:35:39 --------------- === MICROPAS7 v7.10 File-2703lPlB Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- --------------------------------------------------- --------------------------- REMARKS, COMPLIANCE STATEMENT -------------------- This certificate of compliance lists ' the building features and performance spec ifications needed to comply with Title -24, Parts 1 and � of the, California Code of Regulations, and the administrative regulations to implement them.. This certificate has�lbeen signed by the individual with overall design responsibility. DESIGNER or OWNER DOCUMENTATION AUTHOR Name .... Name .... Sam Maimone Company. R.T. Hughes LLC Company. Heritage Energy Group, LLC Address. 78-900 Ave 47 #200 Address. 470 Wald La Quinta CA 92253 Irvine, CA 92618 Phone ... 760 771-8890 Phone ... 949-789-7221 License. Signed.. Signed... (date) (date) ENFORCEMENT AGENCY Name .... Title ... Agency.. Phone... Signed.. (date) CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD -CF-lR Page 1 ----------- Project Title .......... Plan 2a 2c Date..07/30/07 16:02:04 Project Address ........ Malaga Estates Coral.Mtn --------------------- La quinta *v7.10*, Documentation Author ... Sam Maimone ******* I Building Permit # I Heritage Energy Group, LLC I I 470 Wald I Plan Check Date I Irvine, CA 92618 949-789-,7221 - Field Check/ Date Climate Zone ........... 15 --------------------- Compliance Method ...... MICROPAS7 v7.10 for 2 005 Standards by Enercomp, Inc. MICROP�S7 v7.10 File -27031P2 Wth-CTZ15SO5 Program -FORM CF-lR. User#-MP0940 User-Heritag� Energy Group, LL Run- --------------------------------- 7 --------------------------------------------- MICROPAS7 ---------- ENERGY USE SUMMARY -------------------- = Energy Use Standard Proposed Compliance = (kTDV/sf-yr) ----------------------- ---------- Design Design ---------- ----------- Margin Space Heating .......... 1-.91 1.64 0.'27 *Space Cooling ........... 70.17 69.66 0.51 Water Heating .......... 7.78 6.35 1.43 North Total -------- 79.86 -------- -------- 77.*65 2.21 Space Heating .......... 1.91 1.73 0.18 Space Cooling .......... 70.17 68.75 1.42 Water Heating .......... 7.78 6.35 1.43 East Total -------- 79.86 -------- -------- 76.83 3.03 = Space Heating .......... 1 91 1.98 -0.07 = Space Cooling .......... 70-.17 68.68 1.49 = Water Heating .......... 7.78 6.35 - 1.43 South Total -------- 79.86 -------- --------- 77.01 2.85 = Space Heating ............ 1.91 1.80 0'.11 = Space Cooling .......... . 70.17 67.33 2.84 = Water Heating ........... 7.78 6.35 1.43 West-Total --------- 79.86 -------- -------- 75.48 4.38 Building complies with Computer Performance HERS Verification Required for Compliance CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 2 Project Title .......... Plan 2a 2c Date..07/30/07 16:02:04 MICROPAS7 v7.10 File -27031P2 Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- GENERAL INFORMATION HERS Verification .......... Required Conditioned Floor Area ..... 3303 sf Building Type .............. Single Family Detached Construction Type ......... New I Fuel Type ................. NaturalGas Building Front Orientation. Cardinal - N,E,S,W Number of Dwelling Units ... 1 Number of Building Stories. 1 Weather Data Type ........... FullYear Floor Construction Type .... Slab On Grade Number of Building Zones ... 3 Thermo- Conditioned volume ......... 36072 cf Slab -On -Grade Area ......... 3303 sf Glazing Percentage ......... 20.9 % of floor area Average Glazing U -factor. *.. 0.39 Btu/hr-sf-F Average Glazing SHGC ....... 0.29 Type -------- Average Ceiling Height ..... 10.9 ft BUILDING ZONE INFORMATION OPAQUE SURFACES Floor # of # of Cond- Thermo- Vent Vent Verified Frame Area Volume Dwell Peop- it- stat Height Area Leakage or Zone Type ----------- (sf) -- ----- (cf) ------ Units ----- le ----- ioned ----- Type -------- (ft) ----- (sf) ------ Housewrap 7 GRT DIN --- ---- --- 7 ---------- Residence 1441 17292 0.44 3.1 Ye's Setback - 2.0 Standard 3.8 SLA MBR 485 0.074 19 0 270 90 Yes IV.9 A5 4 Wall Residence 800 8160 0.24 1.2 Yes Setback 2.0 Standard 3.8 SLA BRS LAU 144 0.074 19 0 90 90 Yes IV.9 A5 6 Roof Residence 1062 10620 0.32 1.6 Yes Setback 2.0 Standard 3.8 SLA OPAQUE SURFACES U_ Sheath- Solar Appendix Frame Area fact- Cavity ing Act Gains IV Location/ Surface ------------ Type ---- (sf) ---- or ----- R-val ----- R-val ---- Azm Tilt Reference Comments GRT DIN --- ---- --- --------- -------------- 2 Wall Wood 255 0.074 19 0 180 90 Yes IV.9 A5 3 Wall Wood 485 0.074 19 0 270 90 Yes IV.9 A5 4 Wall Wood 32 0.074 19 0 0 90 Yes IV.9 A5 5 Wall Wood 144 0.074 19 0 90 90 Yes IV.9 A5 6 Roof Wood 1441 0.025 38 0 n/a 0 Yes IV.1 A18 7 Door Wood 20 0.330 0 0 0 90 No None MBR 10 Wall Wood 118 0.074 19 0 180 90 Yes IV.9 A5 CER�IFI6AtE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD. CF-lR Page 3 Project.Ti,tle .......... Plan 2a 2c Date..07/30/07 16:02:04 MICROPAS7 ' v7.10 File -27031P2 Wth-CTZ15SO5 Program -FORM CF-lR 'User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------ ------------------------------------------------- OPAQUE SURFACES U_ Sheath- Solar Appendix Frame Area fact- Cavity ing �Act Gains TV Location/ Surface Type (sf) or R-val.R-val Azm Tilt Reference Comments- ------------ ----- ---- ----- ----------- --- ---- --- --------- -------------- 13 Wall Wood 146 0.074 19 0 90- 90 Yes IV.9 A5 17 Roof Wood 800 0.025 38 0 n/a 0 Yes IV.1 A18 BR§ LAU 11 wall Wood 150 0.074 19 0 270- 90 Yes IV.9A5 12 Wall Wood 260 0.074 19 0 0 90 Yes IV.9 A5 14 Wall Wood 275 0.074 19 0 90 90 Yes IV.9 A5 15 Wall Wood 140 0.074 19 0 0 90 No IV.9 A5 16 Wall Wood 170 0.074 19 0 270 90 No IV.9 A5 18 Roof Wood 1062 0.025 38 0 n/a 0 Yes IV.1 A18 PERIMETER LOSSES ---------------- Appendix Length F2 Insul Solar * IV Location/ Surface (ft) Factor R-val Gains Reference Comments --------- ------ -- ----- ------- ---- 7- ------- ---------------------- GRT DIN 1 SlabEdge 107 0.730 R-0 No IV.26 Al MBR 8 SlabEdge 44 0.730, R-0 No IV.26 Al BRS LAU 9 SlabEdge 112 0.730 R-0 No IV.26 Al FENESTRATION -SURFACES i --------------------- Exterior Area U_ Act Shade Orientation ------------------ (sf) ----- factor ----- SHGC ----- Azm --- Tilt ---- Type --- ---- Location/Comments ------------------------ GRT DIN 1 Door Back (S) 144.0 0.400 0.280 1&0 90 Standard 1/french door low -e 2 Wind Back (S) 9.0 0.350 0.350 180 90 Standard 2/wood,fixed,low-e 4 Wind Right (W) 6.0 0.350 0.350 2jO 90 Standard 4/wood,fixed,low-e 5 Wind Right (W) 5.3 0.350 0.320 270 90 Standard 5/wood,operable low -e 6 Door Right (W) 80.0 0.400 0.280 270 90 Standard 6/french door low -e 10 Door Left (E) 96.0 0.400 0.280 90 90 Standard 10/french door low -e 16 Door Front (N) 28.0 0.400 0.280 - 0 90 Standard 16/french door low -e MBR 3 Door Back (S) 96.0 0.400 0.280-180 90 Standard 3/french door low -e 11 Wind Left (E) 24.0 0.350 0.320 90 90 Standard 11/wood,operable low -e 12 Wind Left (E) 25.0 0.350 0.320 90 90 Standard 12/wood,operable low -e 13 Door Left (E) 40.0 0.400 0.280 90 90 Standard 13/french door low -e BRS LAU 7 Door Right (W) 20.0 0.400 0.280 270 90 Standard 7/french door low -e i CERTIFICA�E OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 4 -------------------- Project Title .......... Plan 2a 2c Date..07/30/07 16:02:04 MICROPAS7 v7.10 File -27031P2 Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run-- ------------------------------------------------------------ I ------------- FENESTRATION SURFACES OVERHANGS rb Number . Verified Verified --- Window --- --- I --------- Overhang ------------ Verified Maximum System Area Minimum Refrig Charge Exterior Fan Watt Left Right Surface Efficiency EER or TXV Area U_ Height Depth Act ------- Shade ----------- GRT Orientation ----- (sf) factor SHGC Azm — Tilt Type Location/Comments ------------------ 8 Wind Front'(N) 2 ----- 18.0 ----- 0.350 ----- 0.350 0 ---- 90 -------- Standard ------------------------ 8/wood ',fixed,low-e 9 Wind Front (N) 42.0 0.350 0.320 0 90 Standard 9/wood,operable low -e 14 Wind Left (E) 45.0 0.350 0.320 90 90 -Standard 14/wood,operable low -e 15 Wind Left (E) 10.5 0.350 0.320 90 90 Standard 15/wood,operable low -e OVERHANGS rb HVAC SYSTEMS ------------ verified Number . Verified Verified --- Window --- --- I --------- Overhang ------------ Verified Maximum System Area Minimum Refrig Charge Adequate Fan Watt Left Right Surface Efficiency EER or TXV (sf) Width Height Depth Height Extension ------- Extension ----------- GRT DIN ----- ----- ------ ----- ------ --------- n/a --------- 6 Door 80.0 n/a 8 1.5 2 n/a n/a 10 Door 96.0 n/a 8 12 1 n/a n/a MBR 3 Door 96.0 n/a 8 12 11 n/a n/a 11 Window 24.0 n/a 6' 1.5 l' n/a n/a 12 Window 25.0 n/a 5 1.5 1 n/a n/a. 13 Door 40.0 n/a 8 1.5 1 n/a n/a BRS LAU 8 Window 18.0 n/a 8 6 1 n/a n/a SLAB SURFACES - ------------- �Area Slab Type ----------------- (sf) ------ GRT DIN Standard Slab 1441 MBR Standard Slab 800 BRS LAU Standard Slab 1062 HVAC SYSTEMS ------------ verified Number . Verified Verified verified Verified Maximum System of Minimum Refrig Charge Adequate Fan Watt Cooling Type Systems Efficiency EER or TXV Airflow Draw Capacity ------------ GRT DIN ------- ----------- - 7 --- ------------- -------- -------- -------- Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No CER�IFICAtE OF COMPLIANCE: RESIDENT IAL COMPUTER METHOD CF-lR' Page 5 Project Title .......... Plan 2a 2c Date..07/30/07 16:02:04 MICROPAS7 v7.10 File -27031P2 Wth-CTZ15SO5 Program -FORM CF -IR User#-MP0940, User -Heritage Energy Group, LL Run- -------------------------------------------------------------------------------- EVAC SYSTEMS ------------ verified Number Verified Verified Verified Verified Maximum System of Minimum. . I . Refrig Charge Adequate Fan Watt Cooling Type Systems Efficiency EER or TXV Airflow Draw Capacity ------------ MBR ------- --- 7 ------- ----- ---- -------- -------- -------- -------- Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No BRS LAU Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No HVAC SIZING ----------- Verified Total Sensible Design Maximum Heating Cooling Cooling Cooling System, Load Load Capacity Capacity Type ------------- (Btu/hr) ---------- (Btu/hr) (Btu/hr) ---------- ---------- (Btu/hr) ---------- GRT DIN Furnace 24541 n/a n/a n/a ACSplit n/a 20936 �25981 n/a MBR Furnace 11282 n/a n/a n/a ACSplit n/a 15349 19048 n/a BRS LAU Furnace 17480 n/a n/a n/a ACSplit n/a 14296 17741 n/a ------------- Total, ---------- 53303 ---------- -- ------- 50580 62770 ---------- n/a Orientation of Maximum ...... Front Facing 180 deg (S) Sizing Location ............ LA QUINTA Winter Outside Design ...... 26 F Winter Inside Design ....... 70 F Summer Outside Design ...... 111 F Summer Inside Design ....... 75 F Summer Range ............... 34 F CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 6 Project Title ...... .... Plan 2a 2c Date..07/30/07 16:02:04 ------------------- ---------- MICROPAS7 v7.10 File -27031P2 Wth-CTZ15S05 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- N DUCT SYSTEMS ------------ Verified Verified Verified System Duct Duct Duct Surface Buried Type Location R -value Leakage- Area Ducts ------------- ----------- ------- ------- -------- ----------- GRT DIN Furnace Attic R-6 Yes No No ACSplit� Attic R-6 Yes. No No MBR Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No. No BRS LAU Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No INFILTRATION TESTING DETAILS ---------------------------- Blower Door Blower Door Leakage Target L;aakage Minimum (CFM50h/SLA) (CFM50h/SLA) --------------- --------------- GRT DIN 1434 3.8 566,/ 1.5 MBR 796 3.8 '314 1.5 BRS LAU 1057 3.8 417 1.5 WATER HEATING SYSTEMS -------------- Number Tank External Heater in Energy Size Insulation Tank Type Type Distribution Type -System Factor (gal) R -value --------------- - -------- ------------------- ------ --------------- ---------- 1 Large Gas Standard 1 n/a 75 R-12 WATER HEATING SYSTEMS DETAIL ------------------------------ Standby Internal Tank Recovery Rated Loss Insulation Pilot System Efficiency Input Fraction R-va*lue Light ------------ ------- ---- ------------ ---------- --------------- ------- 1 Large 0.76 n/a 0.0318 R-n/a 0 CER�IFICA:TE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 7 ---------- Project Title .......... Plan 2a �c Da-te..07/30/07 16:02:04 MICROPAS7 v7.10 File -27031P2 Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL, Run- ------------------------------------------------------------------- ----------- SPECIAL-FEATURES AND MODELING ASSUMPTIONS ----------------------------------------- Items in this section should be documented on the plans, installed to manufacturer and CEC specifications, and verified during plan check and field inspection. This building incorporates HERS verified Infiltration. The Homeowner's Manual must include instructions on how to operate the windows and/or mechanical'ventilation to achieve adequate ventilation. - This building incorporates HERS verified Duct Leakage. This is a multiple orientation building. This printout is for the front facing North. This building incorporates a non-standard Water Heating System. HERS REQUIRED VERIFICATION Items in this section require'field testing and/or verification by a certified home energy rater under. the supervision of a CEC-approved HERS provider using CEC approved testing and/or verification methods and must be reported on the CF -4R installation certificate. This building incorporates HERS verified Infiltration. Target and Minimum CFM values measured at 50 pascals are shown in INFILTRATION TESTING DETAILS above. If the measured CFM50h is above the target, then corrective action must be taken to reduce the infiltration and then retest. Alternatively, the compliance calculations could be redone without infiltration testing. If the measured CFM50h is below the minimum, then the building must meet Uniform Mechanical Code requirements for unusally tight construction and corrective action must be taken to either intentionally increase infiltration or provide for mechanical supply ventilation adequate to maintain the residence at a pressure greater than -5 pascals relative to the outside average air pressure with other continuous ventilation fans operating This building incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the CF -4R. If the measured CFM is above the target, then corrective action must be taken to reduce the duct leakage and then must be retested., Alternatively, the compliance calculations could be redone without duct testing. If ducts are not installed, then HERS verification is not necessary. CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF -1R Page 1 ---------- Project Title .......... Plan 2B Date..07/30/07 16:02:29 Project Address ........ Malaga Estates Coral Mtn --------------------- La quinta *v7.10* 1, 1 Documentation Author ... Sam Maimone ******* I Building Permit # Heritage Energy group, LLC, 470 Wald Plan Check Date Irvine, CA 92618 949-789-7221. Field Check/ Date Climate Zone ........... 15 --------------------- Compliance'Method ...... MICROPAS7 V7.10 for 2005 Standards by Enercomp, Inc. MICROPAS7 v7.10 File -27031P26 Wth-CTZ15SO5 Program -FORM CF -1R User#-MP0940 User-Her.itage Energy Group, LL Run- ------------------------------------------------------ ------------------------ MICROPAS7 ENERGY USE SUMMARY ----------------------------- Energy Use Standard Proposed Compliance (kTDV/sf-yr) ------------------------ ---- Design ----- Design ---------- ---------- Margin Space Heating .......... 1.91 1.64 0.27 = 'Space'Cooling ........... 70.19 .69.50 0.69 = Water Heating .......... 7.78 6.36 1.42 North Total 79.88 -------- -------- 77.50 2.38 = Space Heating .......... 1.91 1.73 0.18 = Space Cooling .......... 70.19 68.54 1.65 = Water Heating .......... 7.78 6.36 1.42 East Total -------- 79.88 -------- 76.63 3.25 = Space Heating..: ....... 1.91 1.97 -0.06 = Space Cooling .......... 70.19 68.61 1.58 = Water Heating .......... - 7.78. 6.36 1.42 South Total -------- 79.88 -------- -------- 76.94 2.94 = Space Heating ........... 1.91 1.81 0.10 = Space Cooling ............. 70.19 67.18 3.01 = Water Heating .......... 7.78. 6.36 1.42 West Total -------- - 79:88 -------- -------- 75.35 4.53 Building complies with Computer Performance HERS Verification Required for Com�liance CER�IFICAfE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 2 Project Title ........... Plan 2B Date..07/30/07 16:02:29 -------------------- MICROPAS7 v7.10 File-27031P2B Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ---------------------------------------------------------- 7 --------------------- GENERAL INFORMATION ------------------- HERS Verification ­­­ ­. Required Conditioned Floor Area.,.... 3300 sf Building Type .............. Single Family Detached Construction Type ......... New Fuel Type .................. NaturalGas Building Front'Orientatio'n. Cardinal - N,E,S,W Number of Dwelling Units ... 1 Number of Building Stories. 1 Weather Data Type .......... FullYear Floor Construction Type .... Number of Building Zones ... Conditioned Volume ......... Slab -On -Grade Area ......... Glazing Percentage ......... Average Glazing U -factor ... Average Glazing'SHGC ....... Average,Ceiling Height ..... Slab On Grade 3 36036 cf 3300, sf 20.7 % of -floor area 0.39 Btu/hr-sf-F 0.29 10.9 ft BUILDING ZONE INFORMATION OPAQUE SURFACES Floor - # of # of Cond- Thermo- Vent Vent Verified Area Volume Dwell Peop� it- stat Height Area Leakage,or Zone Type -------------- (sf) ----- (cf) ------ Units ----- le ----- ioned ----- Type -------- (ft) ----- (sf) Housewrap ------ ---------- GRT DIN Reference Comments' ------------ GRT DIN ----- ---- ----- ----- ----- 7 Residence 1438 17256 0.44 3.1 Yes Setback 2.0 Standard 3.8 SLA MBR '90 Yes IV.9 A5 3 Wall Wood 485 0.074 19 Residence 800 8160 0.24 1.2 Yes Setback 2.0 Standard 3.8 SLA BRS LAU 0 0 90 Yes IV.9 A5 5 Wall Wood 144 Residence 1062- 10620 .0.32 1.6 -Yes Setback 2.0 Standard 3.8 SLA OPAQUE SURFACES U_ Sheath- Solar Appendix Frame Area fact- Cavity ing. Act Gains IV Location/ Surface Type (sf) or R-val R-val Azm Tilt Reference Comments' ------------ GRT DIN ----- ---- ----- ----- ----- --- ---- --- --------- -------------- 2 Wall Wood 260 0.074 19 0 180 '90 Yes IV.9 A5 3 Wall Wood 485 0.074 19 0 270 90 Yes IV.9 A5 4 Wall Wood 32 0.074 19 0 0 90 Yes IV.9 A5 5 Wall Wood 144 0.074 f9 0 90 9Mes IV.9 A5 6 Roof Wood 1438 0.025 38 0 n/a 0 Yes IV.1 A18 7 Door Wood 20 0.330 0 V 90 No. None MBR 10 Wall Wood 118 0.074 19 0 180 90 Yes IV.9 A5 CER�IFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 3 ---------- Project Title ........... Plan 2B Date..07/30/07 16:02:29 I. MICROPAS7 v7.10 File-27031P2B Wth-CTZ15S05 Program -FORM CF-lR 1. User#-MP094.0 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- OPAQUE SURFACES PERIMETER LOSSES U_ Sheath- Length Solar Appendix Solar IV Location/ Frame Area iact- Cavity ing Act GRT DIN Gains IV Location/ Surface ----- Type (sf) or ;R-val R-val Azm Tilt MBR Reference Comments ------------ 13 Wall ----- Wood' ---- 146 ----- 0.074 ----- 19 ----- 0 --- 90 ---- 90 --- Yes --------- -------------- IV.9 A5 17 Roof Wood 800 0.025 38 0 n/a 0 Yes IV.1 A18 BRS LAU 11 Wall Wood, 150 0.074 19 0 270. 90 Yes IVA A5 12 Wall Wood 260 0.074 19 0 0 90 Yes IV.9 A5 14 Wall Wood 275 0.074 19 0 90 90 Yes IV.9 A5 15 Wall Wood 140 0.074 19 0 0 90 No IV.9 A5 16 Wall Wood 170 0.074 19 0 270 90 No IV.9 A5 18 Roof Wood 1062 0.025 38 0 n/a 0 Yes IV.1 A18 PERIMETER LOSSES FENESTRATION SURFACES Exterior Area - U- Act Shade Orientation (sf) factor SHGC Azm Tilt Type Location/Comments ------------------ ----- ----- ----- I --- ---- -------- ------------------- 7 GRT DIN 1 Door Back (S) 144.0 0.400 0.280 180 90 Standard 1/french door low -e 2 Wind Back (S) 4.5 0.350 0.350 180 90 Standard 2/wood,fixed,low-e 4 Wind Right (W) 6.0 0.350 0.350 270 90 Standard 4/wood,fixed,low-e 5 Wind Right (W) 5.3 0.350 0.320 270 90 Standard 5/wood,operable low -e 6 Door Right (W) 80.0 0.400 0.280 270 90 Standard 6/french door low -e 10 Door Left (E) 96.0 0.400 0.280 90 90 Standard 10/french door low -e 16 Door Front (N) 28.0 0.400 0.280 0 90 Standard 16/french door low -e MBR 3 Door Back (S) 96.0 0.400 0.280 180 90 Standard 3/french door low -e 11 Wind Left (E) 24.0 0.350 0.320 90 90 Standard 11/wood,operable low -e 12 Wind Left (E) 25.0 0.350 0.320 90 90 Standard 12/wood,operable low -e .13 Door Left (E) 40 0 0.400 0.280 90 90 Standard 13/french door low -e BRS LAU 7 Door Right (W) 20.0 0.400 0.280 270 '90 Standard 7/french door low -e Appendix Length F2 Insul Solar IV Location/ Surface ------------ (ft) Factor R-val Gains Reference Comments GRT DIN ------ -------- ------- ----- --------- ---------------------- 1 SlabEdge 107 0.730 R-0 No IV.26 Al MBR 8-SlabEdge 44 0.730 R-0 No IV.26 Al BRS LAU 9 SlabEdge 112 0.730 R-0 No IV.26 Al FENESTRATION SURFACES Exterior Area - U- Act Shade Orientation (sf) factor SHGC Azm Tilt Type Location/Comments ------------------ ----- ----- ----- I --- ---- -------- ------------------- 7 GRT DIN 1 Door Back (S) 144.0 0.400 0.280 180 90 Standard 1/french door low -e 2 Wind Back (S) 4.5 0.350 0.350 180 90 Standard 2/wood,fixed,low-e 4 Wind Right (W) 6.0 0.350 0.350 270 90 Standard 4/wood,fixed,low-e 5 Wind Right (W) 5.3 0.350 0.320 270 90 Standard 5/wood,operable low -e 6 Door Right (W) 80.0 0.400 0.280 270 90 Standard 6/french door low -e 10 Door Left (E) 96.0 0.400 0.280 90 90 Standard 10/french door low -e 16 Door Front (N) 28.0 0.400 0.280 0 90 Standard 16/french door low -e MBR 3 Door Back (S) 96.0 0.400 0.280 180 90 Standard 3/french door low -e 11 Wind Left (E) 24.0 0.350 0.320 90 90 Standard 11/wood,operable low -e 12 Wind Left (E) 25.0 0.350 0.320 90 90 Standard 12/wood,operable low -e .13 Door Left (E) 40 0 0.400 0.280 90 90 Standard 13/french door low -e BRS LAU 7 Door Right (W) 20.0 0.400 0.280 270 '90 Standard 7/french door low -e CERTIFICA!fE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 4 ---------------- Project Title .......... Plan 2B Date..07/30/07 16:02':29 MICROPAS7 v7.10 File-27031P2B W th-CTZ15S05 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ---------------------------------- L -------------------------------------------- OVERHANGS Number Verified Verified --- Window --- ------------ FENESTRATION SURFACES System of Area Adequate Fan Watt --------------------- . Left Right Surface ----------- Exterior (sf) ----- Width ----- Height Depth Height Area U_ GRT Act Furnace Shade ------ ----- Orientation ------------------ --------- (sf)-factor 6 SHGC Azm,.Tilt n/a Type Location/Comments 8 Wind'Front (N) ----- 18.0 ----- '0.350 ----- 0.350 --- - 0 ---- 90 -------- Standard ----------------------- 7 8/wood,fixed,low7e 9 Wind Front (N) 42.0 0.350 0.320 0 90 Standard 9/wood,operable low -e 14 Wind Left (E) 45.0 0.350 0.320 90 90 Standard 14/wood,operable low -e 15 Wind Left (E) 10.5 0.350 0!320 90 I 90 '-Standard 15/wood,operable low -e OVERHANGS HVAC SYSTEMS ------------ Verified Number Verified Verified --- Window --- ------------ Verified Overhang ------------ System of Area Adequate Fan Watt . . Left Right Surface ----------- Airflow (sf) ----- Width ----- Height Depth Height Ext�ension Extension GRT DIN Furnace 1 ------ ----- ------ --------- --------- 6 Door 80.0 n/a 8 1.5 2 n/a n/a 10 Door 96.0 n/a 8 12 1 n/a n/a MBR 3 Door 96.0 n/a 8 12 1 n/a n/a 11 Window 24.0 n/a 6 1.5 1 n/a n/a 12 Window 25.0 n/a 5 1.5 1 n/a n/a 13 Door 40.0 n/a 8 1.5 1 n/a n/a BRS LAU 8 Window 18.0 n/a 6 1 n/a n/a SLAB SURFACES ------------- Area Slab Type ---------------- (sf) ------ GRT DIN Standard Slab 1438 MBR Standard Slab 800 BRS LAU Standard Slab 1062 HVAC SYSTEMS ------------ Verified Number Verified Verified Verified Verified Maximum� System of Minimum Refrig Charge Adequate Fan Watt Cooling Type ------------ Systems Efficiency EER or TXV Airflow Draw Capacity GRT DIN ------- ----------- ----- ------------- -------- -------- -------- Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No CERiIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page' 5 ---------- Project Title ........... Plan 2B Date..07/30/07 16:02:29 MICROPAS7 v7.10 File-27031P2B Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- HVAC SYSTEMS - ------------ Verified Orientation of Maximum Front Facing'180 deg (S) Sizing Lo : cation ...... ...... LA QUINTA Winter Outside Design ...... 26 F Winter Inside Design ....... 70 F Summer Outside Design ...... 111 F Summer Inside Design ....... 75 F Summer Range ............... 34 F Number Verified Verified Verified Verified maximum System of Minimum Refrig Charge Adequate Fan Watt Cooling Type ------------ Systems ------- Efficiency EER or TXV Airflow braw Capacity MBR ----------- ----- ------------- -------- -------- -------- Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No- No No No No BRS LAU Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No' No No No No HVAC SIZING ----------- Verifi6d Total Sensible- Design Maximum Heating Cooling Cooling Cooling System Load Load Capacity Capacity Type ------------- (Btu/hr) ------- (B�u/hr) (Btu/hr) (Btu/hr) GRT�DIN ---- ---------- Furnace .24463 n/a n/a n/a ACSplit n/a 20829 25848 n/a MBR Furnace 11282 n/a n/a n/a ACSplit n/a 15349 19048 n/a BRS LAU Furnace 17480 n/a n/a n/a ACSplit ------------- �/a ---------- 14296 17741 n/a Total 53225 ---------- ---------- 50474 62638 ---------- n/a Orientation of Maximum Front Facing'180 deg (S) Sizing Lo : cation ...... ...... LA QUINTA Winter Outside Design ...... 26 F Winter Inside Design ....... 70 F Summer Outside Design ...... 111 F Summer Inside Design ....... 75 F Summer Range ............... 34 F CERtIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 6 Project Title .......... Plan 2B Date..07/3'0*/07 16:02:29 MICROPAS7 v7.10 File-2703iP2B Wth-CTZ15SO5 Pr'ogram-FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- --------------------------------------------------------------------- 7 --------- WATER HEATING SYSTEMS DETAIL Standby Internal Tank Recovery Rated Loss Insulation Pilot System Efficiency Input Fraction R -value -Light -------------------------- ------------ ---------- --------------- ------- 1 Large 0.76 n/a 0.0318 R-n/a 0 DUCT SYSTEMS ------------ Verified Verified Verified System Duct ..Duct Duct Surface Buried Type ------------- Location R -value Leakage ----------- ------- Area Ducts,' GRT DIN ------- -------- --------- Furnace Attic R-6 Yes NO No ACSplit Attic R-6- Yes No No MBR Furnace Attic R-6 Yes. No No ACSplit Attic R-6 Yes No No BRS LAU Furnace -Attic R-6 Yes No No �ACSplit Attic R-6 Yes No No INFILTRATION TESTING DETAILS ---------------------------- Blower Door Blower Door Leakage Target Leakage Minimum (CFM50h/SLA) (CFM50h/SLA) --------------- --------------- GRT DIN 1431 / 3.8 565 1.5 MBR 796 3.8 314 -1.5 BRS LAU 1057 3.8 417 1.5 WATER HEATING SYSTEMS --------------------- Number Tank External Heater in Energy size Insulation Tank.Type Type ---------------- -------- Distribution Type System -------------------- Factor (gal) R -value I.Large Gas ------ Standard I 1 1 -------- n/a ------ ---------- . 75 R-12 WATER HEATING SYSTEMS DETAIL Standby Internal Tank Recovery Rated Loss Insulation Pilot System Efficiency Input Fraction R -value -Light -------------------------- ------------ ---------- --------------- ------- 1 Large 0.76 n/a 0.0318 R-n/a 0 CER�IFICATE OF'COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 7 Project Title .......... Plan 2B Date..07/30/07 16:02:29 MICROPAS7 v7.10 File-27031P2B Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- SPECIAL FEATURES AND MODELING ASSUMPTIONS ----------------------------------------- Items in this section should be documented on the plans, installed to manufacturer and CEC specifications, and verified during plan check and field inspection. This building incorporates HERS verified Infiltration. The Homeowner's Manual must include instructions on how to operate the windows and/or mechanical ventilation to achieve adequate ventilation. This building incorporates HERS verified Duct Leakage. This is a multiple orientation building. This printout is for the front facing North. This building incorporates a non-standard Water Heating System. HERS REQUIRED VERIFICATION Items in this section require.field testing and/or verification by a certified home energy rater under the supervision of a CEC-approved HERS provider using CEC approved testing and/or verification methods and must be reported on the CF -4R installation certificate. This building incorporates HERS verified Infiltration. Target and Minimum CFM values measured at 50 pascals are shown in INFILTRATION TESTING DETAILS above. If the measured CFM50h is above the target, then corrective action must be taken to reduce the infiltration and then retest. Alternatively, the compliance calculations could be redone without infiltration testing. If the measured CFM50h is below the minimum, then the building must meet Uniform Mechanical Code requirements for unusally tight construction and corrective action must be taken to either intentionally increase infiltration or provide for mechanical'supply ventilation adequate to maintain the residence at a pressure greater than* -5 pascals relative to the outside average air pressure with other continuous ventilation fans operating This building incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the CF -4R. If the measured CFM is above the target, then corrective action must be taken to reduce the duct leakage and then must be retested. Alternatively, the compliance calculations could be redone without duct testing. If ducts are not installed, then HERS verification is not necessary. CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 1 Project Title .......... Plan 3A Date..07/30/07 15:00:23 Project Address ........ Malaga Estates Coral Mtn ___L ------------------- La quinta *v7.10* I Documentation Author ... Sam Maimone ******* I Building Permit # Heritage Energy Group, LLC 470 Wald Plan Check Date Irvine, CA 92618' 949-789-7221 Field Check/ Date Climate Zone ........... 15 --------------------- Compliance Method ...... MICROPAS7,v7.10 for 2005 Standards by Enercomp,'Inc. MICROPAS7 v7.10 File -27031P3 Wth-CTZ15SO5 Progr am -FORM CF -1R User#-MP0940 User -Heritage Energy Group, LL Run- ----------------------------------------------------------------- L ------------- MICROPAS7 ------------------------------ ENERGY USE SUMMARY = Energy ---------------------------- Use Standard Proposed' Compliance = (kTDV/sf"yr)' ------------------- ---- ---------- Design Design ---------- ---------- Margin Spa ce Heating .......... 2.95 2.43 0.52 Space Cooling ........... .71.18 71.32 -0.14 Water Heating......-..... 6'.43 5.15 1.28 North Total ---- 80.56 -------- -------- 78.90 1.66 Space Heating .......... 2.95 2.60 0.35 Space Cooling .......... 71.18 69.84 1.34 Water Heating..; ....... --------- 6.43 5.15 East Total 80.56 -------- -------- 77.59 2.97 Space Heating .......... 2.95 2.88 0.07 Space Cooling .......... 71.18 69.68 1.50 Water Heating .......... 6.43 5.15 1.28 South Total -------- 80.56 -------- -------- 77.71- 2.85, Space Heating .......... 2.95 2.52 0.43 Space Cooling .......... 71.18 68.27 2.91 Water Heating .......... 6.43 5.15 1.28 West Total -------- 80.56 -------- -------- 75.94 4.62 Building complies with Computer Performance HERS Verification Required for Compl I iance CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 2 ===== ---------- Project Title .......... Plan 3A Date..07/30/07 15:00:23 MICROPAS7 v7.10 File -27031P3 Wth-CTZ15SO5 Program -FORM CF-lR User*-MP0940 User-Heritagb Energy Group, LL Run- -------------------------------------------- ---------------------------------- GENERAL INFORMATION HERS Verification .......... Required Conditioned Floor Area ..... 3761 sf Building Type .............. Single Family Detached Construction Type ......... New Fuel Type .................. NaturalGas Building Front Orientation. Cardinal N,EfS,W Number of Dwelling Units ... 1 Number of Building Stories�. 2 Weather Data Type .......... FullYear Floor Construction Type .... Slab On Grade Number of Building Zones ... 3 Conditioned Volume ......... 39419 cf Slab -On -Grade Area ...... ... 2887 sf Glazing P ' ercentage ......... 18 % of floor area Average Glazing U -factor ... 0.38 Btu/hr-sf-F Average Glazing SHGC ... I .... 0.3 Average Ceiling Height ..... 10.5 ft BUILDING ZONE INFORMATION OPAQUE SURFACES Floor # of # of Cond- Thermo- Vent Vent Verified Area Volume Dwell Peop- it- stat Height Area Leakage or Zone Type -------------- (sf) ----- (cf) ------ Units ----- le ----- ioned ----- Type -------- (ft) ----- (sf) ------- Housewrap LIV ----- ---- ----- ----- ----- --- ---- --- ---------- Residence 1560 18720 0.41 2;9 Yes Setback 8.0 Standard 3.8 SLA MBR BR2 Wood 396 0.074 19 0 270 90 Yes IVA A5 Residence 1327 13270 0.35 2.5 Yes Setbick 8.0 Standard 3.8 SLA 2ND FLR Wood 281 0.074 19 0 90 *90 Yes IV.9 A5 Residence 874 7429 0.24 1.2 Yes Setback 8.0 Standard 3.8 SLA OPAQUE SURFACES i U_ Sheath- Solar Appendix Frame Area fact- Cavity ing Act Gains IV Location/ Surface ------------ Type (sf) or R-val R-val Azm Tilt Reference Comments LIV ----- ---- ----- ----- ----- --- ---- --- --------- -------------- 2 Wall Wood 313 0.074 19 0 180 90 Yes IVA A5 .3 Wall Wood 396 0.074 19 0 270 90 Yes IVA A5 4 Wall Wood 83 0.074 19 0 0. 90 Yes IV.9 A5 5 Wall Wood 281 0.074 19 0 90 *90 Yes IV.9 A5 6 Roof Wood 1560 0.025 38 0 n/a 0 Yes IV.1 A18 7 Door Wood 20 0.330 0 0 0 90 No None MBR BR2 9 Wall Wood 88 0.074 19 0 180 90 Yes IV.9 A5 i CERTIFICATE OF COMPLIANCE: RESIDENTIAL -COMPUTER METHOD Page 3 -------------------- Project Title .......... Plan 3A Date..07/30/07 15:00:23 MICROPAS7 v7.10 Fiie-27031P3 Wth-CTZ15SO5 Program -FORM CF-lR .-User#-MP0940 User -Heritage Energy.Group, LL Run- ------------------------------------------------------------------------------- OPAQUE SURFACES U.- Sheath- Solar Appendix Frame Area fact- Cavity ing Act Gains IV Location/ Sur.face Type (sf) or R-val R-val Azm Tilt - Reference Comments ------------ ----- ---- ----- ----- ----- --- ---- --- --------- -------------- 11 Wall Wood 404 0.074 19 0 270 90 Yes IV.9 A5 14 Wall Wood 461 0.074 19 0 90 90 Yes IV.9 A5 16 Wall Wood 369 0.074 19 0 270 90 No IV.9 A5 18 Roof Wood 900 0.025 38 0 n/a 0 Yes IV.1 A18 2ND FLR 10 Wall Wood 271 0.074 19 0 180 90 Yes IVA A5 12 Wall Wood 271 0.074 19 0 270 90 Yes IV.9 A5 13 Wall Wood 274 0.074 19 0 0 90 Yes IVA A5 15 Wall Wood 259 0.074 19 0 90 90 Yes IVA A5 17 FloorExt Wood 175 0.046 13 0 n/a 0 No IV.20 A3 19 Roof Wood 874 0.025 38 0 n/a 0 Yes IV.1 A18 PERIMETER LOSSES ---------------- Appendix Length F2 Insul Solar IV Location/ Surface (ft) Factor R-val Gains Reference Comments ------------ ------ -------- ------- ----- --------- ---------------------- LIV 1 SlabEdge 118 '0.730 R-0 No IV.26 Al MBR BR2 8 SlabEdge 158 0.730 R-0 No IV.26 Al FENESTRATION SURFACES --------------------- Exterior Area U_ Act Shade Orientation (sf) factor SHGC Azm Tilt Type Location/Comments ------------------ ----- - 7 --- ----- --- ---- -------- ------------------------ LIV /,"l Wind Back (S) 45.0 0.350 0.320 180 90 Standard l/wood,operable low -e Door Back (S) 80.0 0.400 0.280 180 90 Standard 2/french door low -e /,"3 Wind Back (S) 6.0 0.350 0.350 180 90 Standard 3/wood,fixed, low -e 8 Wind Right (W) 18.0 0.350 0.320 270 90 Standard 8/wood,operable low -e 9 Wind Right (W) -6.0 0.350 0.350 270 90 Standard 9/wood,fixed, low -e -16 Wind Front (N) 20.0 0.350 0.350 0 90 Standard 17/wood,fixed, low -e ----�17 Wind Front (N) 25.0 0.350 0.350 0 90 Standard 18/wood,fixed, low -e /20 Wind Left (E) 30.0 0.350 0.320 90 90 Standard 21/wood,operable low -e ,,�.21 Wind Left (E) 2.0 0.350 0.350 90 90 Standard 22/wood,fixed, low -e 22 Door Left (E) 72.0 0.400 0.280 90 90 Standard 23/french door low -e ,-23 Wind Left (E) 11.3 0.350 0.350 90 90 Standard 24/wood,fixed, low -e '--29 Door Front (N) 28.0 0.400 0.280 0 90 Standard 30/french door low -e MBR BR2 (/*4 Door Back (S) 20.0 0..400 0.280 180 90 Standard 4/french door low -e CERkFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 4 Project Title .......... Plan 3A Date..07/30/07 15:00:23� MICROPAS7 v7.10 File -27031P3 Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- --------------------------------------- --------------------------------------- FENESTRATION SURFACES OVERHANGS --- Window --- ------------ Overhang ------------ Area Left Right Surface ----------- Exterior Width ----- Height ------ Depth -- -- Height ------ Extension --------- Area U_ Act Shade Orientation (sf) factor SHGC Azm Tilt Type Location/Comments ----------- /5 Door 77 Back - --- (S) ----- 72.0 ----- 0.400 ----- 0.280 --- 180 ---- 90 -------- Standard ------------------------ 5/french door low -e /iO Door Right (W) 20.0 0.400 0.280 270 90 Standard 11/french door low -e . 11 Door Right (W) 20.0 0.400 ' 0.280 270 90 Standard 12/french door low. -e J /12 Wind Right (W) 30.0 0.350 0.350 270 90 Standard 13/wood,fixed, low -e /13 Wind Right (W) 6.0 0.350 0.320 270 90 Standard 14/wood,operable low -e ,,-24 Wind Left (E) 18.0 0.350 0.320 90 90 Standard 25/wood,operable low -e ,.,*25 wind Left (E) 27.0 0.350 0.320 90 90 Standard 26/wood,operable low -e 26 Wind Left (E) 4.5 0.350 0.320 90 90 Standard 27/wood,operable low -e 2ND FLR 18 Window 12.0 n/a 4 1.5 1 n/a n/a 19 Window 6 Wind Back (S) 3.0 0.350 0.320 180 90 Standard 6/wood,operable low -e /� Wind Back (S) 24.0 0A50 0.320 180 90 Standard 7/wood,operable low -e /,14 Wind Right (W) 15.0 0.350 0.320 270 90 Standard 15/wood,operable low -e /,* 1 5 Wind Right (W) 12.0 0.350 0.320 270 90 Standard 16/wood,operable low -e /18 Wind Front (N) 12.0 0.350 0.320 01 90 Standard 19/wood,operable low -e /L9 Wind Front (N) 12.0 0.350 0.320 � 0 90 Standard 20/wood,operable low -e 2�7 Wind Left (E) 6.0 0.350 0.320 90 90 Standard 28/wood,operable low -e /28 Door Left (E) 32.6 0.400 0.280 90 90 Standard 29/french door low -e OVERHANGS --- Window --- ------------ Overhang ------------ Area Left Right Surface ----------- (sf) ----- Width ----- Height ------ Depth -- -- Height ------ Extension --------- Extension --------- LIV 3 Window 6.0 n/a 2 1.5 1 n/a n/a 16 Window 20.0 n/a 5 6 1 n/a n/a 17 Window 25.0 n/a 5- 5 1 n/a n/a 22 Door 72.0 n/a 8 12 1 n/a n/a MBR BR2 4 Door 20.0 n/a 8 12 1 n/a n/a- 5 Door 72.0 n/a 8 12 1 n/a n/a 11 Door 20.0 n/a 8 1.5 1 n/a n/a 12 Window 30.0 n/a 6 1.5 1 n/a n/a 2ND FLR 6 Window 3.0 n/a 2 1.5 1 n/a n/a 7 Window 24.0 n/a 4 1.5 , 1 n/a n/a 18 Window 12.0 n/a 4 1.5 1 n/a n/a 19 Window 12.0 n/a 4 1.5 1 n/a n/a CER�IFICAtE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF -1R Page 5 ---------------- Project Title .......... Plan 3A Date..07/30/07 15:00:23 MICROPAS� v7.10 File -27031P3 Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- -------------------------------------------------------------------------------- SLAB SURFACES HVAC SIZING ------------ Area Total Sensible Design Maximum Slab Type ------------ (S I f) Cooling Cooling System Load Load Capacity LIV ------ (Btu/hr) ----------- (Btu/ht) ---------- (Btu/hr) (Btu/hr) LIV Stand ard Slab 1560 ---------- Furnace' 26518 n/a n/a n/a MBR BR2 n/a 21997 27298 n/a MBR BR2 'Standard Slab 1327 Furnace 23856 n/a. n/a n/a ACSplit HVAC SYSTEMS ------------ 119743 24501 n/a� 2ND FLR Furnace 13262 Verified n/a Number ACSplit ------------- Verified Verified Verified Verified Maximum System of Minimum Refrig Charge Adequate Fan.Watt Cooling Type ------------ Systems ------- Efficiency EER' or TXV Airflow. Draw Capacity LIV ----------- ----- ----------- - -------- -- ----- -------- Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No MBR BR2 Furnace 1 0.800 AFUE* n/a -,n/a n/a n/a ACSplit 1 13.0.0 SEER No No No No No 2ND FLR Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No 'No No No HVAC SIZING ------------ Orientation of Maximum ..... Front Facing 0 deg (N) Sizing Location ............ LA QUINTA Winter Outside Design ....... 26 F Verified Total Sensible Design Maximum Heating Cooling Cooling Cooling System Load Load Capacity Capacity Type ------------- (Btu/hr) ----------- (Btu/ht) ---------- (Btu/hr) (Btu/hr) LIV --- 7 ------ ---------- Furnace' 26518 n/a n/a n/a ACSplit n/a 21997 27298 n/a MBR BR2 Furnace 23856 n/a. n/a n/a ACSplit n/a 119743 24501 n/a� 2ND FLR Furnace 13262 n/a n/a n/a ACSplit ------------- n/a ---------- 12315 ---------- n/a Total 63636 54055 ---------- 67082 ---------- n/a Orientation of Maximum ..... Front Facing 0 deg (N) Sizing Location ............ LA QUINTA Winter Outside Design ....... 26 F CERTIFICA�E OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF -1R Page 6 ------------ ----------- --------- ---------- Project Title .......... Plan 3A Date..07/30/07 15:00:23 ---------- MICROPAS7 v7.10 File -27031P3 Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- Winter Inside Design ....... 70 F Summer Outside Design ...... 111 F Summer Inside Design ....... 75 F Summer Range ................ 34 F DUCT SYSTEMS ------------ Verified verffied Verified System Duct, Duct Duct Surface Buried Type Location R -value Leakage Area Ducts ------------- ------------ ------- ------- -------- - 7 ------- LIV Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No MBR BR2 Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No FLR Furnace Attic R-6 Yes No No �ACSplit Attic R-6 Yes No No INFIL TRATION TE STING DETAILS ---------------------------- Blower Door Blower Door Leakage Target Leakage Minimum .(CFM50h/SLA) (CFM50h/SLA) --------------- -------------- LIV 1552 3.8 613 1.5 MBR BR2 1320 3.8 521 1,.5 2ND FLR 870 3.8 .343 1.5 WATER HEATING SYSTEMS 7 ---------- Numbe.r Tank External Heater in Energy Size Insulation Tank Type Type Distribution Type System Factor (gal) R -value ------ -------- ------------------- ------ -------- ------ ---------- 1 Large Gas, Standard 1 n/a 75 R-12 CER�IFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 7 Project Title .......... Plan 3A Date..07/30/07 15:00:23 MICROPAS7 v7.10 File -2703 1P3 Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- WATER HEATING ---------------------------- SYSTEMS DETAIL Standby Internal Tank Recovery Rated Loss Insulation Pilot System Efficiency Input- ------------ ------------ ------------ Fraction R -value ---------- Light 1 Large 0.76 n/a --------------- 0.0318 R-n/a ------- 0 SPECIAL FEATURES AND -------------- MODELING ASSUMPTIONS -------------------------- Items in this section should be documented on the plans, installed to manufacturer and CEC specifications, and verified during plan check and field inspection. This building incorporates HERS verified Infiltration. The Homeowner's Manual must include instructions on how to' operate the windows and/or mechanical ventilation to achieve adequate ventilation. This building incorporates HERS verified Du ct Leakage. This is a multiple orientation building. T his printout is for the front facing North. This building incorporates a non-standard Water Heating System. HERS REQUIRED VERIFICATION Items in.thi-s section require field testing and/or verification by a certified home energy rater under the supervision of a CEC-approved HERS provider using CEC approved testing and/or verification methods and ***.must be reported on the CF -4R installation certificate. This building incorporates HERS verified Infiltration. Target and Minimum CFM values measured at 50 pascals are shown in INFILTRATION TESTING DETAILS above. If the measured CFM50h is above the target, then corrective action must be taken to reduce the infiltration and then retest. Alternatively, the compliance calculations could be redone without infiltration testing. If the measured CFM50h is below the minimum, then the building must meet Uniform Mechanical Code requirements for unusally tight construction and corrective action must be taken to either intentionally increase infiltration or provide for mechanical supply ventilation adequate to -maintain the residence at a pressure greater than -5 pascals relative to the outside average air pressure with other continuous ventilation fans operating This building incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the CF -4R. If the measured CFM is above the target, then corrective action must be taken to reduce the duct leakage and CERTIFICA�E OF COMPLIANCE: , RESIDENTIAL COMPUTER . METHOD CF-lR Page 8 ---------- Project Title .......... Plan 3A Date..07/30/07 15:00:23 ----------- MICROPAS7 v7.10 File-2703IP3 Wth-CTZ15S05 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- -------------------------------------------------------------------------- HERS REQUIRED VERIFICATION ------- 7 ------------------- then must be retested. Alternatively, the compliance calculations could be redone without duct testing. If ducts are,not installed, then HERS verification is not necessary. REMARKS COMPLIANCE STATEMENT This certificate of compliance lists the building features and.performanc'e specifications 'needed to comply with Title -24, Parts 1 and 6 of the California Code of Regulations, and the administrative* regulations to implement them. This ceriificate has been signed by the individual with overall design responsibility. ' I . DESIGNER or OWNER Name .... Company. R.T. Hughes LLC Address. 78-900 Ave 47 #200 La Quinta CA 92253 Phone ... 760 771-8890 License. Signed. . ENFORCEMENT AGENCY Name.... Title ... �gency.. Phone ... Signed. . (date) F (date) DOCUMENTATION AUTHOR Name .... Sam Maimone Company. Heritage Energy Group, LLC Address. 470 Wald Irvine, CA 92618 Phone ... 949-789-7221 Signed. . (date) k CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 1 Project Title .... * ...... Plan 3B Design ---------- Date..07/30/07 15:02:'30 Project Address ........ Malaga Estates Coral Mtn 2.96 --------------------- 0.53 La quinta *v7.10* 70.98 Documentation Author ... Sam Maimone Water Building Permit 4 6.49 -------- Heritage Energy Group, LLC 1.29 I North Total 470 Wald -------- -------- 79.10 Plan Check / Date Space Irvine, CA 92618 2.96 2.63 0.33 949-789-7221 Cooling .......... Field Check/ Date Climate Zone ........... 15 Water --------------------- Compliance Method ...... MICROPAS7 v7.10 for 2005 Standards by Enercomp, Inc. MICROPAS7 v7.10 File-27031P3B Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940. User' -Heritage Energy Group, LL Run- ---------------------------- 7 ----------------------------------- MICROPAS7 ENERGY USE SUMMARY Energy Use Standard Proposed Compliance (kTDV/sf-yr) ----------------------- ---------- Design Design ---------- Margin Space Heating .......... 2.96 ---------- 2.43 0.53 Space Cooling ........... 70.98 71.47 -0.49 Water Heating ........... 6.49 -------- 5.20 1.29 North Total 80.43 -------- -------- 79.10 1.33 Space Heating .......... 2.96 2.63 0.33 Space Cooling .......... 70.98 69.93 1.05 Water Heating .......... 6.49 -------- 5.20 1.29 East Total 80.43 -------- -------- 77.76 2.67 Space Heating .......... 2.96 2.92 0.04 Space Cooling .......... 70.98 69.84 1.14 Water Heating .......... 6.49 -------- 5.20 1.29 South Total 80.43 ------ -------- 77.96 2.47 Space Heating .......... 2.96 2.53 0.43 Space Cooling .......... 70.98. 68.28 2.70 Water Heating .......... 6.49 -------- 5.20 1.29 West Total 80.43 -------- -------- 76.01 4.42 Building complies with Computer Performance HERS Verification Required for Compliance CER�IFICA�E OF COMPLIANCE: RESIDENTIAL'COMPUTER METHOD CF-lR Page 2 Project Title .......... Plan 3B Date..07/30/07 15:02:30 MICROPAS7 v7.10 File-27031P3B Wth-CTZ15S05 Pro'gram-FORM CF-lR ------------------------------------------- User#-MP0940 User -Heritage Energy Group, LL Run- ------------------ ---------------- GENERAL INFORMATION ------------------- HERS Verification ........ 1. Required Conditioned Floor Area ..... 3725 sf Building Type .............. Single Family Detached Construction Type .......... New Fuel Type ................. NaturalGas Building Front Orientation. Ca I rdinal N,E,S,W Number of Dwelling Units ... 1 Number of Building Stories. 2' Weather Data Type ........... FullYear Floor Construction Type .... Slab On Grade Number of Building Zones.... 3 Conditioned Volume .......... 39013 cf Slab -On -Grade Area ......... 2851'sf Glazing Percentage ......... 17.7 % of floorar�a Average Glazing U -factor... 0.38 Btu/hr-sf-F Average Glazing SHGC ....... 0.3, Average Ceiling Height ..... 10-5 ft BUILDING ZONE ------------------------- INFORMATION Floor # of # of Cond- Thermo- Vent Vent Verified Area Volume Dwell Peop- it- stat Height Area Leakage or Zone Type -------------- (sf) (cf) Units le ioned ----- ------ ----- ----- ----- -Type- (ft) (sf) Housewrap -------- LIV ----- ------- ---------- Residence 1537 18444 0.41- 2.9 Yes. Setback 8.0 Standard 3.8 SLA MBR BR2 Residence 1314, 13140 0.35 2.5 Yes Setback 8.0 Standard 3.8 SLA 2ND FLR Residence 874 7429 0.24 1.2 Yes Setback' 8.0 Standard 3.8 SLA OPAQUE SURFACES --------------- U_ Sheath- Solar Appendix Frame Area fact- Cavity ing Act Gains IV Location/ Surface ------------ Type (sf) or R-val R-val ----- ---- ----- ----- ----- Azm Tilt I Reference Comments LIV --- ---- --- --------- -------------- 2 Wall Wood 311 0.074 19 0 180 90 Yes'IV.9 A5 3 Wall Wood 396 0.074 19 0 270 90 Yes IV.9 A5 4 Wall Wood 104 0.074 19 0 0 90 Yes IV.9 A5 5 Wall Wood 281 0.074 19 0 90 90 Yes IV.9 A5 6 Roof Wood 1537 0.025 38, 0 n/a 0 Yes IV.1 A18 7 Door wood 20 0.330 0 0 0 90 No None MBR BR2 - 9 Wall Wood 88 0.074 -19 0 180 90 Yes IV.9 A5 CERTIFICA�E OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 3 ---------- Project Title .......... Plan 3B Date..07/30/07 15:02i3O ---------- MICROPAS7 v7.10 File-27031P3B. Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run.- ----------------------------------- L ------------------------------- ------------ OPAQUE SURFACES PERIMETER -LOSSES U_ Appendix Sheath- Length F2 Solar Appendix IV Location,/ Surface ------------ Frame Area fact- Cavity ing Act Gains IV Location/ Surface --------- -------------------- Type (sf) or R-val R-val Azm Tilt Shade �eference Comments ------------ 11 Wall ----- Wood ---- 404 ----- 0.074 ----- 19 ----- 0 --- 270 ---- 90 --- Yes --------- -------------- IV.9 A5 14 Wall Wood 461 0.074 19 0 90 90 Yes IV.9 A5 16 Wall Wood 369 0.074 19 0 270 90 No IV.9 A5 18 Roof Wood 900 0.025 38 0 n/a 0 Yes IV.1 A18 2ND FLR 0.350 0.350 180 90 Standard 3/wood,fixed, low -e 8 Wind Right 10 Wall Wood 271 0.074 19, 0 180 90 Yes IV.9 A5 12 Wall Wood 271 0.074 19 0 270 90 Yes IVA A5 13 Wall Wood 273 0.074 19 0 0 90 Yes IVA A5 15 Wall Wood 259 0.074 19 0 90 90.Yes Wind IVA A5 17 FloorExt Wood 175 0.046 13 0 n/a 0 No IV.20 A3 19 Roof Wood 874 0.025 38 0 n/a '0 Yes IV.1 A18 PERIMETER -LOSSES FENESTRATION SURFACES . Appendix Length F2 Insul- Solar IV Location,/ Surface ------------ Aft) ------ Factor -------- R-val Gai�s Reference Comments LIV Exterior ------- - 71 --- --------- -------------------- 1 SlabEdge, 118 0.730 R-0 No IV.26 Al MBR BR2 Shade Orientation ------------------------ (sf) 8 SlabEdge 158 0.730 R-0 No IV.26 Al FENESTRATION SURFACES --------------------- Exterior Area U_ Act Shade Orientation ------------------------ (sf) factor ----- SHGC ----- Azm. --- Tilt ---- Type -------- Location/Comments -------------- LIV 7 --------- ,�-1 Wind Back' (S) 45.0 0.350 0.320 180 90 Standard l/wood,operable low -e "'-2 Door Back (S) 80.0 0.400 0.280 180 90 Standard 2/french door low -e ,,_3 Wind Back (S) 8.0 0.350 0.350 180 90 Standard 3/wood,fixed, low -e 8 Wind Right (W) 18.0 0.350 0.320 270 90 Standard 8/wbod,operable low -e 9 Wind Right (W) 6.0 0.350 0.350 270 90 Standard 9/wood,fixed, low -e 16 Wind Front (N) 24.0 0.350 0.350 0 90 Standard 18/wood,fixed, low -e 19 Wind Left (E) 30.0 0.350 0.320 90 90 Standard 21/w'ood,operable low -e 20 Wind Left (E) 2.0 0.350 0.350 90 90 Standard 22/wood,fixed, low -e 21 Door Left (E) 72.0 0.400 0.280 90 90 Standard 23/french door low -e 22 Wind Left (E) 11.3,0.350*0.350 90 90 Standard 24/wood,fixed, low -e 28 Door Front (N) 28.0 0.400 0.280 0 90 Standard 30/french door low -e MBR BR2 4 Door Back (S) 20.0 0.400 0.280 180 90 Standard 4/french door low -e 5 Door Back (S) 72.0 0.400 0.280 180 90 Standard 5/french door low -e CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 4 Project Title .......... Plan 3B Date..07/30/07 15:02:30 ---------- MICROPAS7 v7.10 File-27031P3B Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ---------------------------------------------- --------------------------------- FENESTRATION SURFACES --------------------- 'Exterior Area U_ Act Shade Orientation (sf) factor SHGC Azm Tilt Type Location/Comments ------------------------- ----- ----- --- ---- -------- ------------------------ 10 Door Right (W) 20.0 0.400 0.280 270 90 Standard 11/french door lov�-e 11 Door Right (W) 20.0 0.400 0.286 270 90 Standard 12/french door low -e 12 Wind Right (W) 30.0 0.350 0.350 270 90 Standard 13/wood,fixed, low -e 13 Wind Right (W) 6.0 0.350 0.320 270 90 Standard 14/wood,operable low -e 23 Wind Left (E) 18.0 0.350 0.320 90 90 Standard 25/wood,operable low -e 24 Wind Left (E) 27.0 0.350 0.320 90 90 Standard 26/wood,operable low -e 25 Wind Left (E) 4.5 0.350 0.320 90 90 Standard 27/wood,operable low -e 2ND FLR. 6 Wind Back (S) 3.0 0.350 0.'320 180 90 Standard 6/wood,operable low -e 7 Wind Back (S) 24.0 0.350 0.320 180 90 -Standard 7/wood,operable low -e 14 Wind Right (W) 15.0 0.350 0.320 270 90* Standard 15/wood,operable low -e 15 Wind Right (W) 12.0 0.350 0.320 270 90 Standard 16/wood,operable low -e 17 Wind Front (N) 12.0 0.350 0.320 0 90 Standard 19/wood,operable low -e 18 Wind Front (N) 13.5 0.35,0 0.320 0 90 Standard 20/wood,operable low -e 26 Wind Left (E) 6.0 0.350 0.320 90 '90 Standard 28/wood,operable low -e 27 Door Left (E) 32.6 0.400 0.280 90 90 Standard 29/french door low -e OVERHANGS --- Window --- ------------ Overhang ------------ Area . Left Right Surface (sf) Width Height Depth Height Extension Extension ----------- ----- ----- ------ ----- ------ -------- --------- LIV 3 Window 8.0 n/a 2 1.5 1 n/a n/a 16 Window 24.0 n/a 5 5 1 n/a n/a 21 Door 72.0 n/a 8 12 1 n/a n/a MBR BR2 4 Door 20.0 n/a 8 12 1 n/a n/a 5 Door 72.0 n/a 8 12 1 n/a n/a 11 Door 20.0 n/a 8 1.5 1 n/a n/a 12 Window 30.0 n/a 6 1.5 1 n/a n/a 2ND FLR 6 window 3.0 n/a 2 1.5 1 n/a n/a 7 Window 24.0 n/a 4 1.5, 1 n/a n/a 17 Window 12.0 n/a 4 1.5 1 n/a n/a 18 Window i3.5 n/a- 4 1.5 1 n/a n/a 1 0 CERTIFICATE OF COMPLIANCE: RESIDENTIAL. COMPUTER METHOD. ---------- CF-lR ---------- Page 5 Project Title .......... -------------------- Plan 3B Date..07/30/07 1,5:02:30 MICROPAS7 v7.10, File-27031P3B Wth-CTZ15SO5 Program -FORM CF-lR -------------------------- User#-MP0940 User-Heritage.Energy Group,,LL 7 ---------------------------------------------------- Run- SLAB SURFACES ------------- Area Slab Type (sf) ---------------- ------ LIV Standara Slab 1537 MBR BR2 Standard Slab 1314 'HVAC SYSTEMS ------------ Verified Number Verified Verified Verified Verifi ed Maximum System of Minimum . Refrig Charge Adequate Fan Watt Cooling Type ------------ Systems Efficiency iER � or TXV Airflow m Draw Capacity LIV ----------------- -- ----- ------------- -------- ---- --- -------- Furnace 1 0.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No. No No MBR BR2 Furnace 1 0,1800 AFUE n/a n/a n/a n/a. n/a ACSplit 1 13.00 SEER No No. No No No' 2ND FLR Furnace 1 6.800 AFUE n/a n/a n/a n/a n/a ACSplit 1 13.00 SEER No No No No No HVAC SIZING ----------- Verified Total Sensible Desi�n 9 Maximum Heating Cooling Cooling Cooling System Load Load Capacity Capacity Type --------- (Btu/hr) (Btu/hr) (Btu,/hr) ---------- ---------- ---------- (Btu/hr) ---------- Furnace 26111 n/a n/a n/a ACSplit n/a. 21493 26673 n/a MBR BR2 Furnace 23795 - n/a n/a n/a ACSplit n/a 19705. 24453 n/a 2ND FLR Furnace 13282 n/a n/a n/a ACSplit ------------- n/a. 12343 15318 ---- n/a Total ------- ---------- 63188 53541 66444 ---------- n/a Orientation of Maximum ..... Front Facing O'deg (N) ,Sizing Location ........ : ... LA QUINTA Winter Outside Design ...... 26 F I CERTIFICA�E OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 6 ---------- Project Title .......... Plan 3B Date..07/30/07 15:02:30 MICROPAS7 v7.10 File-27031P3B Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User-Heritage'Ene'rgy Group,'LL Run- ------------------------------------------------------------------------------- Winter Inside Design ....... 70 F Summer Outside Design 111 F Summer Inside Design ....... 75 F Summer Range .................. 34 F .DUCT SYSTEMS ------------ Verified Verified Verified System Duct Duct Duct Surface Buried Type ------------- Location R -value Leakage ----------- ------- Area Ducts LIV ------- -------- --------- Furnace Attic R-6 Yes No No' ACSplit Attic R-6 Yes No No MBR BR2 Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No 2ND FLR Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No INFILTRATION TESTING DETAILS -------------------------- 7 Blower Door Blower Door. - Leakage Target Leakage Minimum .(CFM50h/SLA) (CFM50h/SLA)"' --------- --------------- 7 LIV 1529 3.8 604 1.5 MBR BR2 1307 3.8 516 1.5 2ND FLR 870 3.8 343 1.5 WATER HEATING SYSTEMS --------------------- Number Tank External Heater in Energy Size Insulation - Tank Type Type ---------------- ---- w ---- Distribution Type' System ------------ Factor (gal) R -value 1 Large Gas 7 ------- ------ Standard -------- n/a ------ ---------- 75 R-12 CERTIFICA�E OF COMPLIANCE; RESIDENTIAL COMPUTER METHOD- CF-lR Page 7 ====== --------------- Project Title ........... Plan 3B Date. -.07/30/07 15:02:30 ---------- MICROPAS7 v7.10 File-27031P3B Wth-CTZ15SO5 Program -FORM CF -1R User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- WATER HEATING SYSTEMS DETAIL Standby Internal Tank Recovery Rated Loss Insulation Pilot System Efficiency Input Fraction R -value Light ------------ ------------ --------------------------------------- ------- 1 Large 0.76 n/a 0.0318 R-n/a 0 SPECIAL FEATURES AND�MODELING ASSUMPTIONS ----------------------------------------- Items in this section should be documented on the plans, installed to manufacturer and CEC specifications, and verified during plan check and field inspection. This building incorporates HERS verified Infiltration. The Homeowner's Manual must include instructions on how to op'�rate the windows and/or mechanical ventilation to achieve adequate ventilation. This building incorp6rates HERS verified Duct Leakage. This is a multiple orientation building. This printout is for the front facing North. This building incorporates a non-standard Water Heating System. HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified home energy rater under the supervision of a CEC-approved HERS provider using CEC approved testing and/or verification methods and ***,must be reported on the CF -4R installation certificate. This building incorporates HERS verified Infiltration. Target and Minimum CFM values measured at 50 pascals are shown in INFILTRATION TESTING DETAILS above. If the measured CFM50h is above the target, then corrective action must be taken to reduce the infiltration and then retest-. Alternatively, the compliance calculations could be redone without infiltration testing. If the measured CFM50h is below the minimum, then the building must meet Uniform Mechanical Code requirements for unusally tight construction and corrective action must be taken to either intentionally increase infiltration or provide for mechanical supply ventilation adequate to maintain the residence at a pressure greater than -5 pascals relative to the outside average air pressure with other continuous ventilation fans operating This building incorporates HER - S verified Duct Leakage. Target,leakage is calculated and documented on the CF -4R. If the measured CFM is above the target, then corrective action must be taken to reduce the duct leakage and CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 1 Project Title .......... Plan 3C Date..07/30/07 1'5:03:52 Project Address ......... Malaga Estates Coral Mtn *******. --------------------- I La quinta *v7.10* -1 1 Documentation Author ... Sam Maimone ******* I Building Permit # Heritage Energy Group, LLC I 470 Wald Plan Check / Date Irvine, CA 92618 949-789-7221 Field Check/ Date Climate Zone ........... 15 --------------------- Compliance Method ....... MICROPAS7 v7.10 for 2005 Standards by Enercomp, Inc MICROPAS7 v7.10 File-27031P3C Wth-CTZ15SO5- Program -FORM CF-lR User#-MP0940 ----------------------------------------------- User -Heritage Energy Group, LL 7 --------------------------- Run- MICROPAS7 ---------------------------- ENERGY USE SUMMARY Energy Use Standard Proposed Compliance (kTDV/sf-yr) ----------------------- ---------- Design ---------- Design Margin Space Heating .......... 3.00 2.50 ---------- 0.50 Space Cooling .......... 71.77 7'2.17 -0.40 Water -Heating ........... 6.47 -------- 5.18 1.29 North I Total -------- 81.24. 79.85 -------- 1.39 Space Heating ........... 3.00 2.67 0.33 Space Cooling .......... 71.77 70.86 0.91 Water Heating ........... 6.47 -------- 5.18 1.29 East Total -------- 81.24 78.71 -------- 2.53 Space Heating ........... 3.00 0.06 Space Cooling .......... 71.77 70.62 1.15 Water Heating .......... 6.47 -------- 5.18 1.29 South Total -------- 81.24� 78.74 --------- 2.50 Space Heating .......... 3.00 2.60 0.40 Space Cooling .......... 71.77 69.32 2.45 Water Heating ........... 6.47 -------- 5.18 1.29' West Total -------- 81.24 77.10 -------- 4.14 Building complies with Computer Performance HERS Verification Required for Compliance CERTIFICA�E OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 2 ---------- Project Title .......... Plan 3C Date..07/30/07 15:03:52 ------------ MICROPAS7 v7.10 File-270'31P3C Wth-CTZ15SO5 Program-FORM'CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------ ---------------------------------- m -------------- GENERAL INFORMATION HERS Verification .......... Required Conditioned Floor Area ...... 3737 sf Building Type ............... Single Family Detached Construction Type ......... New Fuel Type .................. �aturalGas Building Front Orientation. Cardinal N,E,S,W Number of Dwelling Units ... i Number of Building Stories. 2 Weather Data Type ..... i ...... FullYear Floor Construction Type .... Number of Building Z ' ones.-.. Conditioned Volume ......... Slab -On -Grade Area ......... Glazing Percentage ......... Average Glazing U -factor ... Average Glazing SHGC ....... Average Ceiling Height ..... Slab On Grade 3 39145 cf 2863 sf 18.2 % of floor area. 0.38 Btu/hr-sf-F 0.3 10.5 ft BUILDING ZONE INFORMATION Surface LIV 2 Wall 3 Wall 4 Wall 5 Wall 6 Roof 7 Door 8 Door MBR BR2 OPAQUE SURFACES --------------- U- Sheath-, Solar Appendix Frame Area fact- Cavity'ing Act Gains IV Location/ Type (sf) or R-val R-val Azm Tilt Reference Comments ----- ---- ----- ----- ----- --- ---- --- --------- -------------- Wood 310 0.074 i9 0 180 90 Yes IV.9 A5 Wood 396 0.074 19 0 270 90 Yes IV.9 A5 Wood 83 0.074 19 0 0 90 Yes IV.9 A5 Wood 281 0.074 19 0 90 90 Yes IV.9 A5 Wood -1543 0.025 38 0 n/a 0 Yes IV.1 A18 Wood 28 0.330 0 0 0 90 Yes None Wood 20 0.330 0 0 0 90 No None Floor # of # of Cond- Thermo- Vent Vent Verified Area Volume Dwell Peop- it- stat Height Area Leakage or Zone Type -------------- (sf) ----- (cf) ------ Units - --- le ----- ioned ----- Type -------- (ft) ----- (sf) Housewrap LIV 7 ------- ---------- Residence 1543 18516 0.41' 2.9 Yes Setback 8.0 Standard. 3.8 SLA MBR BR2 Residence 1320 13200 0.35 2.5 Yes 'Setb ack 8.0 Standard 3.8 SLA 2ND FLR Residence 874 7429 0.24 1.2 Yes Setback -8.0 Standard 3 8 SLA Surface LIV 2 Wall 3 Wall 4 Wall 5 Wall 6 Roof 7 Door 8 Door MBR BR2 OPAQUE SURFACES --------------- U- Sheath-, Solar Appendix Frame Area fact- Cavity'ing Act Gains IV Location/ Type (sf) or R-val R-val Azm Tilt Reference Comments ----- ---- ----- ----- ----- --- ---- --- --------- -------------- Wood 310 0.074 i9 0 180 90 Yes IV.9 A5 Wood 396 0.074 19 0 270 90 Yes IV.9 A5 Wood 83 0.074 19 0 0 90 Yes IV.9 A5 Wood 281 0.074 19 0 90 90 Yes IV.9 A5 Wood -1543 0.025 38 0 n/a 0 Yes IV.1 A18 Wood 28 0.330 0 0 0 90 Yes None Wood 20 0.330 0 0 0 90 No None CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 3 Project Title .......... Plan 3C Date..07/30/07 15:03:52 MICROPAS7 v7.10 File-27031P3C Wth-CTZ15SO5 Program -FORM CF-lR User*-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------ ------------------------ OPAQUE SURFACES PERIMETER LOSSES U_ Appendix Sheath- Length Solar Appendix Solar IV Location/ Frame Area fact- Cavity ing Act Gains IV Location/ Surface Type (sf) or R-val R-val Azm Tilt No Reference Comments ------------ 10 wall ----- Wood ---- 88 ----- 0.074 ----- 19 ----- 0 --- 180 ---- 90 --- Yes --------- -------------- IV.9 A5 12 wall Wood 404 0.074 19 0 270 90 Yes IV.9 A5 15 Wall Wood 461 0.074 19 0 90 90 Yes IV.9 A5 17 Wall Wood 369 0.074 19 0 �-270 180 90 No IVA A5 19 Roof Wood 900 0.025 38 0 n/a 0 Yes IV.1 A18 2ND FLR Wind Right (W) 6.0,0.350 0.350 270 90 Standard 9/wood,fixed, low -e 11 Wall Wood 271 0.074 19 0 180 90 Yes IVA A5 13 Wall Wood 271 0.074 19 0 270 90 Yes IV.9 A5 14 Wall Wood 274 0.074 19 0 0 90 Yes IVA A5 16 Wall Wood 259 0.074 19 0 90 90 Yes IVA A5 18 FloorExt Wood 175 0.046 13 0 n/a 0 No IV.20 A3 20 Roof Wood 874 0.025 .38 0 n/a 0 Yes IV.1 A18 PERIMETER LOSSES FENESTRATION SURFACES Appendix Length F2 Insul Solar IV Location/ Surface (ft) ------ Factor -------- R-val ------- Gains ----- Reference Comments -- ------ -------------- ------- ------------ LIV Shade Orientation 7 1 SlabEdge 118 0.730 R-0 No IV.26 Al MBR BR2 ------------------ LIV 9 SlabEdge 158 0.730 R-0 No IV.26 Al FENESTRATION SURFACES Exterior Area U_ Act Shade Orientation (sf) ----- factor ----- SHGC ----- Azm --- Tilt ---- Type -------- Location/Comments ------------------------ ------------------ LIV 1 Wind Back (S), 45.0 0.350 0.320 180 90 Standard l/wood,operable low -e 2 Door Back (S) 80.0 0.400 0.280 180 90 Standard 2/french door low -e 3 Wind Back (S) 6.0 0.350 0.350 180 90 Standard 3/wood,fixed, low -e 8 Wind Right (W) 18.0 0.350 0.320 270 90 Standard 8/wood,operable low -e 9 Wind Right (W) 6.0,0.350 0.350 270 90 Standard 9/wood,fixed, low -e 16 Wind Front (N) 20.0 0.350 0.350 0 90 Standard 17/wood,fixed, low -e 17 Wind Front (N) 25.0 0.350 0.350 0 90 Standard 18/wood,fixed, low -e 20 Wind Left (E) 30.0 0.350 0.320 90 90 Standard 21/wood,operable low -e 21 Wind Left (E) 2.0 0.350 0.350 90 90 Standard 22/wood,fixed, low -e 22 Door Left (E) 72.0 0.400 0.280 90 90 Standard 23/french door low -e 23 Wind Left (E) 11.3 0.350 0.350 90 90 Standard 24/wood,fixed, low -e 29 Wind Back (S) 3.0 0.350 0.350 180 90 Standard 30/wood,fixed, low -e 30 Door Front (N) 28.0 0.400 0.280 0 90 Standard 31/french door low -e CERTIFICA�E OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 4 Project Title..; ....... Plan 3C Date..07/30/07 15:03:52 MICROPAS7 v7.10 File-27031P3C Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- FENESTRATION SURFACES Exterior Area U_ Act Shade Orientation (sf) factor SHGC Azm Tilt- Type Location/Comments ------------------ ----- ----- ----- --- ---- -------- ------------------------ - MBR BR2 4 Door Back (S) 20.0 0.400 0.280 180 90 Standard 4Yfrench door low -e 5 Door Back (S) 72.0 0 * 400 0.280 186 90 Standard 5/french door low -e 10 Door Right (W) 20.0 0.400 0.280 270 90 Standard 11/french door -low-e 11 Door Right (W) 20.0 0.400 0.280 270 90 Standard 12/french door low -e 12 Wind Right (W) 30.0 0.350 0.350 270 9,0 Standard 13/wood,fixed, low -e 13 Wind Right (W) 6.0 0.350 0.320 270 90 Standard 14/wood,operable low -e 24 Wind Left (E) 18.0 0.350 0.320 90 90 Standard 25/wood,operable low -e 25 Wind Left (E) 27.0 0.350 0.320 90 90 Standard 26/wood,operable low -e 26 Wind Left (E) 4.5 0.350 0.320 90 90 Standard-27/wood,operable low -e 2ND FLR 6 Wind Back (S) 3.0 0.350 0.320 180 90 Standard 6/wood, operable low -e 7 Wind Back (S) 24.0 0.350 0.320 180 90 Standard 7/wood,operable low -e 14 Wind Right (W) 15.0 0.350 0.320 270 90 Standard 15/wood,opetable low -e 15 Wind Right (W) 12.0 0.350 ' 0.320 270 90 Standard 16/wood,operable low -e 18 Wind Front (N) 12.0 0.350 0.320 0 90 Standard 19/wood,operable low -e 19 Wind Front (N) 12.0 0.350 0.320 0 90 Standard 20/wood,operable low -e 27 Wind Left (E) 6.0 0.350 0.320- 90 90 Standard 28/wood,operable low -e 28 Door Left (E) 32.6 0.400 0.280 90 90 Standard 29/french door low -e OVERHANGS --- Window --- ------------ Overhang ------------ Area Left Right Surface (sf) Width Height Depth Height Extension Extension ----------- ----- ----- ------ ----- ------ --------- --------- LIV 3 Window 6.0 n/a 2 1.5 1 n/a n/a 16 Window 20.0 n/a 5 6 1 n/a n/a 17 Window 25.0 n/a 5 5 1 n/a n/a 22 Door 72.0 n/a 8 12 1 n/a n/6 MBR BR2 4 Door 20.0 n/a 8 12 1 n/a n/a 5 Door 72.0 n/a 8 12 1 n/a n/a, 11. Door 20.0 n/a 8 1.5 1 n/a n/a 12 Window 30.0 n/a 6 1.5 1 n/a n/a 2ND FLR 6 Window 3.0 n/a 2 1.5 1 n/a n/a 7 Window 24.0 n/a 4 1.5 1 n/a n/a 18 Window 12.0 n/a 4 1.5 1 n/a n/a 19 Window 12.0 n/a 4 1.5 1 n/a n/a I CERTIFICA�E OF COMPLIANCE: RESI'DENTIAL COMPUTER -METHOD CF-lR Page 5 Project Title .......... Plan 3C Date..07/30/07 15:03:52 I MICROPAS7 v7.10 File-27031�3C Wth-CTZ15SO5 Program -FORM CF-lR I User4-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- System Type ---------- LIV Furnace ACSplit MBR BR2 Furnace ACSplit 2ND FLR Furnace ACSplit SLAB SURFACES ---------- Area Slab Type (sf) -------------- LIV Standard Slab 1543 MBR-BR2 Standard Slab 1320 HVAC SYSTEMS ------------ Verified Number Verified Verified Verified Verified Maximum of Minimum I . I Refrig Charge Adequate Fan Watt Cooling Systems Efficiency EER or TXV Airflow Draw Capacity ------- ----------- ----- ------------- -------- -------- -------- 1 0.800 AFUE n/a n/a n/a n/a 1 13.00 SEER No No No No 1 0.800 AFUE n/a n/a n/a n/a 1 13.00 SEER No No No No 1 0.800 AFUE n/a n/a -n/a n/a 1 13.00 SEER No No No No HVAC SIZING n/a No ' n/a No n/a No Verified Total Sensible Design Maximum Heating Cooling Cooling Cooling System Load Load Capacity Capacity Type ------------- (Btu/hr) --------------------- (Btu/hr) (Btu/hr) ---------- (Btu/hr) LIV ---------- Furnace 26899 n/a n/a n/a ACSplit n/a 22224, 27580 n/a MBR BR2 Furnace 23823 n/a,. n/a n/a ACSplit n/a 19722 24476 n/a 2ND FLR Furnace n/a n/a n/a ACSplit ------------- ---------- n/a 12315 15282 n/a Total 6398.5 ----------- 54261 ---------- ---------- 67338 n/a Orientation of Maximum ..... Front Facing 0 deg (N) Sizing Location ............ LA QUINTA Winter Outside Design ...... 26 F n/a No ' n/a No n/a No CERTIFICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF -IR Page 6 Project Title .......... Pla n 3C Date..07/30/07 15:03:52 MICROPAS7 v7.10 File-2703iPiC Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- -------------------------------------------------------------------------------- Winter Inside Design ....... 70 F Summer Outside Design ...... 111 F Summer Inside Design ....... 75 F Summer Range ................. 34 F DUCT SYSTEMS ------------ Verified Verified Verified System Duct Duct Duct Surface Buried Type Location R -value Leakage Area Ducts -------------- ----------- ------- ------- -------- --------- LIV Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No MBR BR2 Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No 2ND FLR Furnace Attic R-6 Yes No No ACSplit Attic R-6 Yes No No INFILTRATION TESTING DETAILS ---------------------------- Blower Door' Blower Door Leakage Target - Leakage Minimum (CFM50h/SLA) (CFM50h/SLA) --------------- ------------- LIV 1535 3.8 606 1.5 MBR*BR2' 1313 3..8 518 1.5 2ND FLR 870 3.8 343 1.5 WATER HEATING SYSTEMS --------------------- Number Tank External Heater in Energy Size Insulation. Tank Type Type Distribution Type System Factor (gal) R -value ---------------- -------- ------------------- I ------ -------- ------ ---------- .1 Large Gas Standard 1 n/a 75 R-12 N a CERTIFICA�E OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 7 Project Title .......... Plan 3C Date..07/30/07 15:03:52 MICROPAS7 v7.10 File-27031P3C Wth-CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------ ------ WATER HEATING SYSTEMS DETAIL Standby Internal Tank Recovery Rated Loss Insulation Pilot System Efficiency Input� Fraction R -value Light ------------ ------------ ------- ----- ---------- --------------- ------- 1 Large 0.76 n/a 0.0318 R-n/a 0 SPECIAL FEATURES AND MODELING ASSUMPTIONS ----------------------------------------- Items in this section should be documented on the plans, installed to manufacturer and CEC specifications, and verified during plan check and field inspection. This building incorporates HERS verified Infiltration. The Homeowner's Manual must include instructions on how to operate the windows and/or mechanical ventilation to achieve adequate ventilation. This building incorporates HERS verified Duct Leakage. This is a multiple orientation building. This printout is for the front facing North. This building incorporates a non-standard Water Heating System. HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified home energy rater under the supervision of a CEC-approved HERS provider using CEC approved testing and/or verification methods and must be reported on the CF -4k installation certificate. This building incorporates HERS verified Infiltration. Target.and Minimum CFM values measured at 50 pascals are shown in INFILTRA ' TION TESTING DETAILS above. If the measured CFM50h is above the target, then corrective action must be taken to reduce the infiltration and then retest. Alternatively, the compliance calculations could be redone without infiltration testing. If the measured CFM50h is below the minimum, then the building must 'meet Uniform mechanical Code requirements for unusally tight construction and corrective action must be taken to either intentionally increase infiltration or provide for mechanical supply ventilation adequate to maintain the residence at a pressure greater than -5 pascals relative to the outside average air pressure with other continuous ventilation fans operating This building incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the CF -4R. If the measured CFM is above the target, then corrective action must be taken to reduce the duct leakage and CERTIPICATE OF COMPLIANCE: RESIDENTIAL COMPUTER METHOD CF-lR Page 8 ---------- Project Title .......... Plan 3C Date..07/30/07 15:03:52 MICROPAS7 v7.10 File-27031P3C Wth�CTZ15SO5 Program -FORM CF-lR User#-MP0940 User -Heritage Energy Group, LL Run- ------------------------------------------------------------------------------- HERS REQUIRED VERIFICATION -------------------------- then must be retested. Alternatively, the compliance calculation -s could be redone without duct. testing. If ducts are not installed, then HERS verification is not necessary. REMARKS COMPLIANCE STATEMENT This certificate of compliance lists the building features'and performance specifications needed to comply with Title -24, Parts 1 and 6 of the California Code of Regulations, and the administrative regulations to implement them. This certif ' icate has been signed by the individual with overall design responsibility. DESIGNER or OWNER DOCUMENTATION AUTHOR Name .... Name .... Sam Maimone Compan ' y. R.T. Hughes LLC Company. Heritage Energy Group, LLC Address. 78-900 Ave 47 #200 Address. 470 Wald La Quinta CA 92253 Irvine, CA 92618 Phone ... 760 771-8890 Phone ... 949-789-7221 License. Signed.. Signed.. (date) (date) ENFORCEMENT AGENCY Name.... Title ... Agency.. Phone ... Signed.. (date) ly a MANDATORY MEASURES SUMMARY: RESIDENTIAL (Page I of 2) MF -IR P Project Title Date Note: Low-rise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent compliance requirements from the Certificate ofCompliance supersede the items marked with an asterisk (*) below. When this checklist is incorporated into the pennit documents, the features noted shall be considered by all parties as minimum component perfon-nancc specifications for the mandatory measures whether they are shown elsewhere in the documents or on this checklist only. Instructions: Check or initial applicable boxes when completed or check NA if not applicable. DESCRIPTION NA Designer Enforce -ment Building Envelope Measures: • §150(a): Minimum R-19 in wood� frame ceiling insulation or eqluivalentU-factor in metal fi-ame ceiling. §150(b): Loose fill insulation manufacturer's labeled R -Value: 21 El 0 • §150(c): Minimum R-1 3 wall insulation in wood framed walls or equivalent U -factor in metal frame walls (does not apply to exterior mass walls). 11 • §150(d): Mnimum R-1 3 raLised floor insulation in framed floors or equivalent 11 -factor. 11 § I SO(e): Installation of Fireplaces, Decorative Gas Appliances and Gas Logs. 1. Masonry and factory -built fireplaces have: a. closeable metal or glass door covering the entire opening of the firebox El 21 0 b. out I side air intake with damper and control, flue damper and control 2. No continuous burning gas pilot lights allowed. §150(0: Air retardingwrap installed to comply with §151 meets requirements specified in the ACM Residential Manual. El 21 11 §1 50(g): Vapor barriers mandatory in.Cli.mate Zones 14 and 16 only. 11 21 0 § I SO(]) : Slab edge insulation - water absorption rate for the insulation material alone without facings no greater than 0.3%, water vapor peryneance rate no greater than 2.0 pernitinch. 21 El 11 §118: frisulation specified or installed meets insulation installation quality standards. 3ndicate type and include CF -6R . Fonn: 0 El 11 §116-17: Fenestration Products, Exterior Doors, and InfiltrationfFxfiltration Controls. 1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage. 1:1 2. Fenestration products (except field -fabricated) have label with certified U -factor, certified Solar Heat Gain Coefficient (SHGC), and infiltration certification. 11 3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed. El 21 11 Space Conditioning, Water Heating and Plumbing System Measures: §110-§113: HVAC equipmen� water heaters, showerheads and faucets certified by the Energy Commission. [21 11 §150(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA orACCA. 10 11 §150(i): Setback thermostat on all applicable heating and/or cooling systems. 0 0 § 1506): Water system pipe and tank insulation and cooling systems line insulation, 21 11 1. Storage gas water heaters rated with an Energy Factor less than 0.58 must be externally wrapped with insulation having an installed thermal resistance of R-12 or greater. [21 11 2. Back-up tanks for solar system, unfired storage tanks, or other indirect hot water tanks have R-12 external insulation or R-16 internal insulation and indicated on the exterior of the tank showing the R -value. 121 0 11 3. The following piping is insulated according to Table 150-A /B or Equation I 50-A Insulation Thickness: 1. First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of recirculating sections of hot water pipes shall be insulated to Table 150B. 2. Cooling system piping (suction, chilled water, or brine lines), piping insulated between heating source and indirect hot water tank shall be insulated to Table 150-B and Equation 150-A 4. Steam hydronic heating systems or hot water systems >1 5 psi, meet requirements of Table- I 23-A. El Residential Compliance Forms I March 2005 * MANDATORY MEASURES SUMMARY: RESIDENTIAL (Page 2 of 2) MF -71R Space Conditioning, Water Heating and Plumbing System Measures: (continued) NA Designer Enforce a. at least 36" ofpipe between filter and heater for future solar heating 0 -ment 5. insulation must be protected from damage, including that due to sunlight, moisture, equipment.maintenance, and wind. 11 21 El 6. Insulation for chilled water piping and refrigerant suction piping includes a vapor retardant or is enclosed entirely in 11 1 3. Pool system has directional inlets and a circulation pump time switch. conditioned space. El 7. Solar water -heating systems/collectors are certified by the Solar Rating and Certification Corporation. 0 El § I 50(m): Ducts and Fans burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr I. All ducts and plenums installed, scaled and insulated to meet the requirement of the CMC Sections 601, 602,603 ' 604 ' 605 11 §1 18(i): Cool Roofmaterial meets specified criteria and Standard 6-5; supply -air and retum-air ducts and plenums art insulated to a minimum installed level of"R4.2 or Residential Lighting Measures: enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets §150(k)l: HIGH EFFICACY LUMrNA1R.ES OTHER THAN 01JTDOOR HID: contain only high efficacy lamps as the applicable requirements of UL 181, UL 181 A, or I_rL 181 B or aerosol sealant that meets the requirements of UL 123. If 0 0 outlined in Table 150-C. and do not contain a medium screw base socket (E24IE26). Ballast for lamps 13 watts or mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used. greater are electronic and have an output frequency no less than 20 kHz 2. Building cavities, support platfortris for air handlers, and plenums defined or constructed with materials other than § 150(k)l: HIGH EFFICACY LUMINAIRES - OUTDOOR HID: contain only high efficacy lamps as outlined in Table scaled sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and 21 11 150-C, haTdwired ballasts and ifthe ballast is electromagnetic has a medium screw base socket. support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to §1 50(k)2: Permanently installed luminaires in kitchens shall be high efficacy luminaires. 'Up to 50 percent ofthe total cause reductions in the cToss-sectional area of the ducts. rated wattage of permanently installed luminaires (based on nominal rated wattage of high efficacy lamps) in kitchens 3. Joints and seams of duct systerns and their components shall not be scaled with cloth back rubber adhesive duct tapes may be in luminaires that are not high efficacy luminaires, provided that these luminaires are controlled by switches unless such tape is used in combination with mastic and draw bands. separate from those controlling the high efficacy luminaires. 4. Exhaust fan systems have back draft or automatic dampers. R1 El 5. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated El R1 11 dampers. automatically or have an always on option. 6. Protection of Insulation. Insulation shall be protected from damage, including that due to sunlight, moisture, § I 50(k)4: Permanently installed luminaires located other than in kitchens, batluooms, garages, laundry rooms, and utility equipment maintenance, and wind. Cellular.foam insulation shall be protected as above or painted with a coating that rooms shall be high efficacy luminaires (except closets less than 7W): OR are controlled by a dimmer switch OR are is water retardant and provides shielding from solar radiation that can cause degradation of the material. 0 E] controlled by an occupant sensor that complies with Section I 19(d) that does not turn on automatically or have an always 7. Flexible ducts cannot have porous inner cores. El R1 El §114: Pool and Spa Heating Systems and Equiemcnt. — 1. A thermal efficiency that complies with the Appliance Efficiency Regulations, on-off switch mounted outside of the -A -- -;1- ];�kt 0 2. System is installed with: a. at least 36" ofpipe between filter and heater for future solar heating 0 El b. cover for outdoor pools or outdoor spas 0 0 1 3. Pool system has directional inlets and a circulation pump time switch. 0 El § 115: Gas fired fan -type central furnaces, pool heaters, spa heaters or household cooking appliances have no continuously El burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr §1 18(i): Cool Roofmaterial meets specified criteria Residential Lighting Measures: §150(k)l: HIGH EFFICACY LUMrNA1R.ES OTHER THAN 01JTDOOR HID: contain only high efficacy lamps as 0 0 outlined in Table 150-C. and do not contain a medium screw base socket (E24IE26). Ballast for lamps 13 watts or El greater are electronic and have an output frequency no less than 20 kHz § 150(k)l: HIGH EFFICACY LUMINAIRES - OUTDOOR HID: contain only high efficacy lamps as outlined in Table El 21 11 150-C, haTdwired ballasts and ifthe ballast is electromagnetic has a medium screw base socket. §1 50(k)2: Permanently installed luminaires in kitchens shall be high efficacy luminaires. 'Up to 50 percent ofthe total rated wattage of permanently installed luminaires (based on nominal rated wattage of high efficacy lamps) in kitchens [3 may be in luminaires that are not high efficacy luminaires, provided that these luminaires are controlled by switches separate from those controlling the high efficacy luminaires. §1 50(k)3: Permanently installed luminaires in bathrooms, garages, laundry rooms utility rooms shall be high efficacy luminaires. OR are controlled by an occupant sensor(s) certified to comply with Section 119(d) that does not turn on automatically or have an always on option. § I 50(k)4: Permanently installed luminaires located other than in kitchens, batluooms, garages, laundry rooms, and utility rooms shall be high efficacy luminaires (except closets less than 7W): OR are controlled by a dimmer switch OR are El 0 E] controlled by an occupant sensor that complies with Section I 19(d) that does not turn on automatically or have an always on option. §150(k)S: Luminaires that are recessed into insulated ceilings are approved for zero clearance insulation cover OC) and are rated to ASTM E283 and labeled as air tight (AT) to less than 2.0 CFM at 75 Pascals. §1 50(k)6: Luminaires Providing outdoor lighting and permanently mounted to a residential building or to other buildings on the same lot shall be high efficacy luminaires (not including lighting around swinuriing pools/water features or other 0 R1 El Article 680 locations) OR are controlled by occupant sensors with integral photo control certified to comply,96th Section 119(d) §1 50(k)7: Lighting for parking lots for 9 or more vehicles shall have lighting that complies with See. 130, 132, and 147. 0 El 0 Lighting for parking garages for 8 or more vehicles shall have lighting that complies with Sec. 130, 131, and 146. §1 50(k)8: Permanently installed lighting in the enclosed, con -dwelling spaces oflow-rise residential buildings with ft��Uh more dwelling units shall be high efficacy lum�inaircs OR are controlled by occupant sensoqs) certified to comply wit Section 119(d). Residential Compliance Forms marcn zuu:) .