11-0898 (SFD) General SpecificationsMarch 14, 2008
Sprinkler 41a
MicrofastHP® QUICK
D A A :,SPRINKLERS
ESPONSE PENDENT I KJ:N::G* I I I I
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
DESCRIPTION
Viking Microfast® and MicrofastHP 1 Quick Response Pendent Sprinklers are small,
thermosensitive, glass -bulb spray sprinklers available in several different finishes and
temperature ratings and K -Factors to meet design requirements. The special Polyester
and Teflon® coatings can be used in decorative applications where colors are desired.
In addition, these coatings have been investigated for installation in corrosive at-
mospheres and are cULus listed as corrosion resistant as indicated in the Approval
Chart. (Note: FM Global has no approval classification for Teflon® and Polyester coat-
ings as corrosion resistant.)
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV -
FM Approved: Class 2020
NYC Approved: Calendar Number 219 -76 -SA and MEA 89-92-E, Volume 16
ABS Certified: Certificate 04-HS407984C-PDA
VdS Approved: Certificate G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021
LPC Approved: Ref. No. 096e/03 and 096e/04
CE Certified: Standard EN 12259-1, EC -certificate of conformity 0832 -CPD -2001, 0832 -CPD -2003, 0786 -CPD -40130, and
0786 -CPD -40170
MED Certified: Standard EN 12259-1, EC -certificate of conformity 0832 -MED -1003 and 0832 -MED -1008
NOTE: Other International approval certificates are available upon request.
Refer to the Approval Chart on page 41d and Design Criteria on page 41e for cULus and FM approval requirements that must be
followed.
3. TECHNICAL DATA
Specifications:
Available since 1987.
Minimum Operating Pressure: 7 psi (0.5 bar)
Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for
use with water working pressures ranging from the minimum 7 psi
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-
sure (HP) sprinklers can be identified by locating "250" stamped on
the deflector. All other Part Nos. not mentioned above are rated to a
maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: Refer to the Approval Chart
Nominal K -Factor: Refer to the Approval Chart
Glass -bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: Refer to the Approval Chart
Viking Technical Data may be found on
The Viking Corporation's Web site at
http://www.vikinggroupinc.com.
The Web site may Include a more recent
edition of this Technical Data Page.
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 06662B, 066668, 06765B, and 12104. Copper
UNS-C19500 for Sprinkler 12282. Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Pip Cap Attachment: Brass UNS-C36000
Ejector Spring (for Sprinkler 12104): Stainless Steel
Form No. F_081296 Replaces page 41a -f, dated October 12, 2007. (Added LPCB Approval and updated CE
Approval for Sprinkler 06666B, Added Dry System note in approval chart for Small Orifice.)
Sprinkler 41 b
March 14, 2008
-MICROFASTO AND
MicrofastHP® QUICK
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
For Teflon® Coated Sprinklers: Belleville Spring -Exposed, Screw -Nickel Plated, Pip Cap -Teflon® Coated
For Polyester Coated Sprinklers: Belleville Spring -Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Microfast® and MicrofastHP® Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler fin-
ish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M -/W, Black Polyester = M -/B, and Black Teflon® = N
Temperature Suffix (°F/°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G
For example, sprinkler VK302 with a 1/2" thread, Brass finish and a 155 *F/68 *C temperature rating = Part No. 06662BAB
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 10896W/B (available since 2000).
B. Wrench for coated and/or recessed sprinklers: Part No. 12144W/B** (available since 2003)
NOTE: RECESSED PENDENT SPRINKLERS WITH PROTECTIVE CAPS MUST USE WRENCH 12144W/B.
**A Y." ratchet is required (not available from Viking).
Sprinkler Cabinets:
A. Six -head capacity: Part No. 01724A (available since 1971)
B. Twelve -head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat -sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® and MicrofastHP® Quick Response Pendent
Sprinklers are available through a network of domestic and
international distributors. See The Viking Corporation web site for
the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule
or contact Viking directly.
Wrench
Flats
Protective
Sprinkler
Cap
10896 m
Figure 1:
Standard Sprinkler Wrench 10896W/B
March 14, 2008
Sprinkler 41 c
MICROFASTOAND
MicrofastHP® QUICK
NIKJ:N7G:4AA A RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI.49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
TABLE
Sprinkler Temperature
Sprinkler Nominal
Maximum Ambient
Bulb Qatar
CkassBication
Temperature Elating'
Ceiling Temperature'
Ordinary
135 'F (57 °C)
100 'F (38 °C)
Orange
Ordinary
155'F (68 °C)
100'F (38 °C)
Red
Intermediate
175'F (79 °C)
150'F (65 °C)
Yellow
Intermediate
200'F (93 °C)
150'F (65 °C)
Green
High
286'F (141 °C)
225'F (107 °C)
Blue
Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®
Corrosion -Resistant Coatings°: White Polyester, Black Polyester, and Black Teflon®
Footnotes
The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
9 The corrosion -resistant coatings have passed the standard corrosion test required by the approving agencies indicated on
pages 41d. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through
the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the
coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester and Teflon® coatings.
— Sprinkler Wrench
12144W/B)K)K for
installing coated
and/or recessed
pendent sprinklers
with protective caps.
N Carefully slide the
_________; wrench sideways
-""- around the protective
cap, ensuring engage-
`------`' Ment with the sprinkler
*A 1/2' ratchet is required wrench flats.
(not available from Viking),
Sprinkler 41 d
March 14, 2008
MicrofastHP® QUICK
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
Approval Chart ___Taue KEY
Microfast" and MicrofastHP0Quick Response Pendent Sprinklers r'"is`
p p A�Jt �— Esaichea� tlt applk'&ble}
Maximum 175 PSI (12 bar) WWP
Sprinkler
Thread Size
Nominal
Overall
Listings and Approvals'
Base
SIN
K -Factor
Length
(Refer also to Design Criteria on page 41e.)
Part No.1
NPT
BSP
U.S.
metria
Inches
mm
cULus°
FMS
NYCE
VdS
LPCB
E
Standard Orifice
06662B
VK302
1/2"
15 mm
5.6
80.6
2-1/4"
58
1 AIX, B•1Y
I A3X, 133Y
I AIX, B1Y
A3 A3X, 63Y
C3X, E3Y13
C3X, E3Y15
Large Odfice
06666B
VK352
3/4"
20 mm
8.0
115.2
2-3/8"
60
AIX, 131Y
A2X, 132Y
AIX, B1Y
—
A3X
C313
--
12104
VK352
3/4"
20 mm
8.0
115.2
2-1/4"
58
--
—
—
G3
—
—
--
06765B
VK352
1/2"
15 mm
8.0
115.2
2-3/8"
60
AIX, B'1Y
—
AIX, B1Y
A3
—
—
--
Small Orifice"
067181310
VK329
1/2"
15 mm
2.8
40.3
2-3/16"
56
AIX, B1Y
A2X
AIX, B1Y
--
--
—
--
06720B10
VK331
1/2"
15 mm
4.2
60.5
2-1/4"
58
AIX, B1Y
--
AIX, BIY
--
--
—
--
06932B
VK331
--
10 mm
4.2
60.5
2-3/8"
60
--
--
—
A3
--
G214
--
Maximum 250 PSI (17 bar) WWP
Standard Orifice
Sprinkler
Thread Size
Nominal
Overall
Listings and Approvals'
Base
SIN
K -Factor
Length
(Refer also to Design Criteria on page 41e.)
Part No'
NPT
BSP
U.S.
metric'
Inches
mm
cULu54
FM
NYC"
VdS
LPCB
E
12282
VK317
1/2"
15 mm
5.6
80.6
2-1/4"
58
AIX, Ely
— I
AIX
—
--
--
--
Maximum 250 PSI (17 bar) WWP
Small OrlfIce"
1229010
VK342
1/2"
1 15 mm
2.8 1
40.3
2-3/16"
56
AIX, E1Y
—
AIX
--
--
--
--
Approved Temperature Ratings
Approved Escutcheons
A- 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C),
Approved Finishes
X - Standard surface -mounted escutcheon or
and 286 °F 141 °C
B - 135 °F (57 °C), 155 ° (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
1 - Brass, Chrome-Enloy®, White Poly-
the Viking Microfase Model F-1 Adjustable
C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F
ester' ", Black Pol ester' ", and Black
y
Escutcheon 12
(141 °C)
Teflon'"
Y - Standard surface -mounted escutcheon or
D - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 286 °F
2 - Brass and Chrome-Enloy®
the Viking Microfase Model F-1 Adjustable
(141 °C
3- Brass, Chrome-Enloy®,White Polyester",
Escutcheon12 or recessed with the Viking
E - 155 °F 68 -C), 175 °F (79 °C), and 200 °F (93 °C)
F - 155 °F (68 C), 175 °F (79 °C), and 286 °F (141 °C)
and Black Polyester8
MicromatiO Model E-1 or E-2 Recessed
G-155°F(68°C)
Escutcheon
Footnotes
1 Base part number is shown. For complete part number, refer to Viking's currern price schedule.
2 Metric K -factor measurement shown is when pressure is measured in Bar. When peessure is measured in kPa, divide the metric K -factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Ch eck with the manufacturer for any additional approvals.
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
S FM Approved for use only in wet -pipe sprinkler systems (or preaction systems qualifying as wet systems) for protection of occupancies described in the Factory
Mutual Engineering and Research Loss Prevention Data Sheets and Technical Advisory Bulletins.
"Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219 -76 -SA.
cULus Listed as corrosion resistant.
8 Other colors are available on request with the same Listings and Approvals as the standard colors.
"Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems
only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized.
10The sprinkler orifice is bushed.
"Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 16.
12The Viking Microfas Model F-1 Adjustable Escutcheon is considered a surface -mounted escutcheon because it does not allow the fusible element of the
sprinkler to be recessed behind the face of the wall or ceiling.
13 pE Certified, Standard EN 12259-1, EC 0832 0832
-certificate of conformity -CPD -2001 and -CPD -2003.
14 C.E Certified, Standard EN 12259-1, EC -certificate of conformity 0786 -CPD -40130 and 0786 -CPD -40170.
15 MED Certified, Standard EN 12259-1, EC -certificate of conformity 0832 -MED -1003 and 0832 -MED -1008.
1.
March 14, 2008
Sprinkler 41 e
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
DESIGN CRITERIA
(Also refer to the Approval Chart on page 41d)
cULus Listing Requirements:
Microfas& and MicrofastHP® Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with
the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by
the installation standards being applied, with hydraulically calculated wet systems only).
• The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
FM Aoproval Reauirements:
For installation in accordance with the latest applicable FM Loss Prevention Data Sheets (including 2-8N) and Technical Advisory Bulletins. FM Global
Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements,
hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
ORI -3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
1/2'
(15 mm) �\
NPT
15cID►�tBlb\
2-1/4'
1-5/8'
(58 mm)
(4
Pendent Sprinkler
06662B (VK302)
Ceiling Opening Sizei
2-5/16' (58.7 MM) Minimum 2-1/8'
2-1/2' (63.5 mm) maximum (54 Mrs)
1-31/4' r N NI'L
(44.5 mm) 2' 1-1/2' (38.1 mm)
(Maxi um Minimum
MQXII`'1u1`'1
Installed with a
standard 1/8' surface -
mounted escutcheon, Installed with a Microfast
Model F-1 Adjustable Escutcheon
Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon
Sprinkler 41 f
March 14, 2008
MICROFASTO AND
MicrofastHP® QUICK
RESPONSE PENDENT I KJ 7N:G4]
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
2-1/8'
(54 mm)
Ceiling Opening Size: 2-1/8'
2-5/16' (58.7 mm) minimum (54 mm)
2-1/2' (63.5 mm) -maximum
1-3/4'
(44,5 mm)
Maximum
1-1/8' (28,6 mm)
Minimum
t
2-
(50.8 mm)
Maximum
1-1/8'. (28.6 mm)
Minimum
f
Installed with a Micromatic
Model. E-1 Recessed Escutcheon Installed with a thread on
Model E-2 Recessed Escutcheon
Figure 4: Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons
Form No. F_081296 Replaces page 41a -f, dated October 12, 2007. (Added LPCB Approval and updated CE
Approval for Sprinkler 0666613, Added Dry System note in approval chart for Small Orifice.)
January 6, 2010
Sprinkler 145h
FREEDOM® RESIDENTIAL
NJ1KJ7W74J A A A FLUSH PENDENT
SPRINKLER VK476 (K4.9)
The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Freedom® Residential Flush Pendent Sprinkler VK476 is a small high -sensi-
tivity fusible element residential sprinkler designed for installation on concealed pipe
systems where the appearance of a smooth ceiling is desired. The orifice design, with
a K -Factor of 4.9 (70.6 metric*), allows the sprinkler's efficient use of available water
supplies for the hydraulically designed fire -protection system. The fast response
operating element and special deflector combine speed of operation and areas of
coverage to meet residential sprinkler standards.
The two-piece design of the sprinkler and ceiling ring allows installation and testing of
the sprinkler prior to ceiling installation. The ceiling ring allows for up to 5/8" (16 mm)
of vertical adjustment and can be removed and re -installed, allowing access above
removable ceiling panels without shutting down the sprinkler system and removing
the sprinkler.
2. LISTINGS AND APPROVALS
cULus Listed: Category VKKW
Refer to the Approval Chart and Design Criteria on pages 145j -k for cULus Listing requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2009. Viking Technical Data may be found on
Minimum Operating Pressure: Refer to the Approval Chart. The Viking Corporation's Web site at
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically http://www.vikinggroupinc.com.
to 500 psi (34.5 bar). The Web site may include a more recent
Thread size: 1/2" (15 mm) NPT edition of this Technical Data Page.
Nominal K -Factor: 4.9 U.S. (70.6 metric*)
*Metric Mactor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0.
Overall Length: 2-1/8" (54 mm)
Material Standards:
Sprinkler Body and Inlet: QM Brass
Deflector Assembly: Copper UNS-C51000 and Brass UNS-C36000
Pin Assembly: Stainless Steel UNS-S30200 and C23000
Seat Assembly: Brass UNS-C31400 or UNS-C31600
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Fusible Element Assembly: Beryllium Nickel and Eutectic Solder
Element Cover: Copper UNS-C11000
Lever Bar Assembly: Copper Alloy UNS-C72500 and Brass UNS-C36000
Lever Arm: Stainless Steel UNS-S31600
Element Assembly: Copper UNS-C11000 and Nickel Alloy
Ceiling Ring: Cold Rolled Steel UNS-Gl0080
Ordering Information: (Also refer to the current Viking price list.)
Viking Freedom® Residential Flush Pendent Sprinkler VK476 and Ceiling Ring:
Part No. 15630MC/- (includes a 165 *F (74 °C) rated sprinkler with a protective plastic cap covering the unit, and a ceiling ring).
Specify finish of the sprinkler and ceiling ring by adding the appropriate suffix for the finish to the base part number:
Finish Suffix: Wood Beam Finish = G, Painted White = W, Painted Black = B
For example, sprinkler VK476 with a Wood Beam Finish = 15630MC/G.
Available Finishes And Temperature Ratings:
Refer to Table 1
Form No. F120608 Replaces page 145h -m, dated Sept. 3, 2009.
— (Revised sloped ceiling listings.)
Sprinkler 145i January 6, 2010
FREEDOM® RESIDENTIAL
• FLUSH PENDENT
SPRINKLER VK476 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrench": Heavy Duty Wrench Part No. 15209W/R (available since 2009)
-Requires a Y.' ratchet (not available from Viking).
Sprinkler Cabinet: Part No. 01731A, Capacity: five (5) sprinklers (available since 1971)
Replacement Ceiling Ring (3" diameter): Base Part No. 15618M/ -
Specify finish of the ceiling ring by adding the appropriate suffix for the finish to the base part number:
Finish Suffix: Wood Beam Finish = G, Painted White = W, Painted Black = B
For example, ceiling ring 15618 with a Wood Beam Finish = 15618M/G.
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the fusible element reach-
es its operating temperature, the element cover, fusible
element and lever assembly fall away. The deflector is
suspended below the ceiling. Water flowing through
the sprinkler orifice strikes the deflector, forming a
uniform spray pattern over a specific area of coverage
determined by the water supply pressure at the sprin-
kler to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Mainte-
nance requirements.
7. AVAILABILITY
Viking Sprinkler VK476 is available through a network
of domestic and international distributors. See The
Viking Corporation web site for the closest distributor
or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list
price schedule or contact Viking directly.
1-1/2' (38 mm)
Diameter Ceiling -\e\
Opening Required I_
Flush Pendent
VK476 Sprinkler Body
with Protective Cap
Sprinkler Wrench
15209W/Raa must be
used for installing
Sprinkler VK476
■*A 1/2' ratchet Is
required <not avallable
from Viking.)
Step 1t Slide the wrench
over the sprinkler
and protective cap.
Sprinkler
Wrench Flats
Step 2: Carefully press
the wrench upward and
turn slightly to ensure
engagement with the
sprinkler wrench flats.
Figure 1: Sprinkler Installation and Correct Use of Wrench
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambient Ceiling Ring
Classification Temperature Rating' Calling Temperature2 Bass Part Number'
Ordinary 165 'F (74 °C) 100 °F (38 °C) 15618
Finishes: Wood Beam Finish, Painted White, or Painted Black
Footnotes
' The sprinkler temperature rating is stamped on the sprinkler inlet.
s Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the
Authority Having Jurisdiction. Refer to specific installation standards.
3 Part number shown is the base part number for replacement ceiling rings. For complete part number, refer to current Viking price list schedule.
January 6, 2010 Sprinkler 145j
FREEDOM® RESIDENTIAL
NIKJNG* • FLUSH PENDENT
SPRINKLER VK476 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart sprinkterTernw -
Residential Flush Pendent Sprinkler VK476 Cow PlaAsTemperaturaRatMg
For system designed to NFPA 13R or NFPA 13R. re ' K EY
'
For systems designed to NFPA 13, refer to the design arteria on page 145k.
Sprinkler Base
NPT Thread Size Nominal K -Factor
Maximum Water
Overall Length
Part Number'
SIN
Working Pressure
Inches
mm U.S. T
metric'
Inches mm
15630
VK476
1/2
15 4.9
70.6
175 psi (12 bar)
2-1/8" 54
Listings and Approvals3,1
Maximum Areas of Coverages
Minimum Water Supply Requirements
(Refer also to Design Criteria on page 145k.)
cULus° INYC NSF
Installed below smooth, flat, horizontal ceilings and horizontal ceilings with beams. Includes ceilings with slopes up to and including 2/12 (9.5°).
16 ft. x 16 ft. (4.9 m x 4.9 m) 13 gpm @ 7.0 psi (49.2 Umin @ 0.48 bar) Al -- -
18ft. x18ft. (5.5mx5.5m) 17 gpm@ 12 psi (64.4 Umin @ 0.83 bar) Al -- -
20 ft. x 20 ft. (6.1 m x 6.1 m) 21 gpm @ 18.4 psi (79.5 Umin @ 1.27 bar) Al -- --
Installed below ceilings with slopes' up to and including a 4/12 (18.4°) pitch. Refer to Figure 5 on page 145m.
UL NYC NSF
16 ft. x 16 ft. (4.9 m x 4.9 m) 18 gpm @ 13.5 psi (68.1 Umin @ 0.93 bar) Al -- -
18 ft. x 18 ft. (5.5 m x 5.5 m) 20 gpm @ 16.7 psi (75.7 Umin @ 1.15 bar) Al -- -
20 ft. x 20 ft. (6.1 m x 6.1 m) 24 gpm @ 24 psi (90.8 Umin @ 1.65 bar) Al -- -
Sprinkler Temperature Rating
Finishes
1
A - 165 -F (74 'C)
1 - Wood Beam Finish, Painted White, and Painted Blacks
Footnotes
' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K -factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0.
3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any
additional approvals.
Listed by Underwriter's Laboratories for use in the U.S. and Canada.
5 Listings are for residential occupancies with smooth, flat, horizontal ceilings or horizontal ceilings with beams. Includes ceilings with slopes up to and
including a 2/12 (9.5°) pitch. (For beam ceiling design criteria, refer to Beam Ceiling Guidelines and Figures 3 through 4D on pages 1451-m).
s For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement' for the next larger area listed. Flows and pressures listed
are per sprinkler. The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the "Minimum Water Supply
Requirement' used.
' Areas under sloped ceilings must be measured along the ceiling slope. Actual floor coverage in the horizontal plane under sloped ceilings will be less
than the listed area of coverage.
s Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label on the sprinkler body.
1/2'
(15 mm�
NPT 1-5/8'
(41 mm)
Maximum 1
:::.
=" 1
2 5/8' C16 m'1) C25.4 mm)
2-1/8' (12.7 mm) Vertical Adjustment _ __ M um
(54 mm)
3'
(76,2 mm) 1
(28.5 mm)
NOTEi Upon sprinkler activatlon, the deflector descends
to approximately 1/2' (12 mm) below the sprinkler body.
Figure 2: Sprinkler Dimensions and Ceiling Ring Installation
Sprinkler 145k January � � rY 6, 2010
FREEDOM® RESIDENTIAL
IK
• • FLUSH PENDENT - .JN
SPRINKLER VK476 (K4:9) .
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone :'269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
_ ��� CRITERIA
r
(Ads o refer -W the Approval ;Chart on paw 1459.) `
cULus Listing Reauirements: _
When using Viking Residential Flush Pendent Sprinkler VK476 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of coverage
and minimum water supply requirements showrnin' the Approval Chart on page 145j.` '
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum
required discharge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in the Approval Charfon data page 145j for NFPA 13D and NFPA 13R applications for each listed area of coverage, o
• Calculated based on a'minimum discharge of 0.1 gpm/sq. ft. over the "design area" in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
•. Minimum distance between residential sprinklers: 8 ft. (2.4 m).
BEAM CEILING,GUIDELINES
cULas Llsted for Installation In residential occdpancfes-with beam ceilings (W#h horizc rital ceilings only),
Refer to,the rovat Chart for rtinkler' areas of coven and li` drau c design.
Sprinkler Locatlon: Locate sprinklers on the underside of the beams (not in the bays or pockets formed by the beams). Refer to Figure 3. The vertical
distance from the sprinkler deflector to the bottom of the primary beam must be between 1/2 and 1-1/8" (12.7 to 28.5 mm). The horizontal distance from
the centerline of the sprinkler to the primary beam cannot be more than 2" (51 mm) (Figure•3).
NOTE: Consult with a structural engineer before drilling beams to allow the installation of sprinkler drops. Where drilling is not permitted, sprinkler posi-
tion requirements allow for the sprinkler drop to be placed adjacent to the primary beam.
Beam Position: Directly attached to the underside of a combustible or non-combustible smooth ceiling of any height.
Beam Size and Shape (Cross section): .
• Depth: Maximum 14" (355 mm) for primary beams. Secondary beam depth cannot be greater than the primary beam.
Width: Unlimited. -
Beam Shape: Rectangular to circular. -
Beam Types: Combustible or non-combustible; solid surface, solid or hollow core.
Beam Spacing:
t
A. For primary beams, the distance from the wall to the center of the nearest primary beam must be at least 3'-4" (1.0 m), and not more than one-half
the listed sprinkler spacing. Note: Sprinklers may not be required to be located in the first beam nearest_ the wall. Center -to -center distance between
primary beams is to be a maximum of 20'-0" (6.1 m). Refer to Figure 4A.
B. When beam pockets created by the primary beams exceed 20'-0" (6.1 m) in length, secondary beams are required as follows (also refer to Figure 4B):
1. Secondary beam depth must be equal to primary beam depth.
2. Secondary beams must be placed so that the bays formed by the primary beams do not exceed 20'-0" (6,1 m) in length.
C. When primary beam spans do not exceed 20'-0" (6.1 m), secondary beams (not required) may have any distance from wall to nearest secondary
'- beam and any distance center to center between secondary beams. Refer to Figure 4C.
Lintels: Must be present over doorways exiting the compartment. Lintel height must be at least 8" (203 mm), or at least the depth of the primary beams,
whichever is greater.
Beam and Soffit Arrangements: If a soffit is installed, beams may be arranged within the soffit. The cross section of the soffit may be any size, pro-
vided it does not create an obstruction to water distribution per the obstruction rules of NFPA 13 for residential sprinklers. Where there is a soffit, beam
spacing from the wall is to be measured from the face of the soffit rather than the wall. Refer to Figure 4D. NOTE: The sprinkler area of coverage is to
be measured from the wall.
Definitions: r '
• • Primary beams: The main beams that run primarily in one direction.
• Secondary beams: The beams that run perpendicular to the main beams.
IMPORTANT: Always refer toIBulletin Form No. F 091699 - Care and Handling of Sprinklers. Also refer to pages
RES1-17 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition•of Viking technical data, the appropriate standards of NFPA and any other similar
Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained
from the Authorities Having Jurisdiction.
January 6, 2010 Sprinkler 1451
FREEDOM® RESIDENTIAL
FLUSH PENDENT
SPRINKLER VK476 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
..............
....... .......
.............. ....... .......
....... .......
1/2' (12,mm) Min. ........
Srinkler
1-1/8' 12e,5 mm) Max.
p Maximum 1/2 Beam Sprinkler
VK476 Width Plus 2' (50.8 mm) VK476
Figure 3: Sprinkler Positioniig Under Primary Beams
Cellinc
We
imary
eam
Prima
Beai
All dimensions are measured to wall
faces and to centerlines of beams.
A = Distance from wall to nearest primary beam
Minimum 3 ft 4 In (1.0 m).
Maxlmumi No more than 1/2 listed sprinkler spacing,
B = Spacing between primary beams, 20 ft (6,1 m) maximum,
C = Beam depth, 14' (355 mm) maximum.
D = Beam spam 20 f t (6.1 m) maximum.
Figure 4A: Primary Beam Spans up to 20'-0" (6.1 m)
idary
Xm
All dimensions are measured to wall
faces and to centerlines of beams.
A = Distance from wall to nearest primary beam+
Minimum 3 ft 4 In (1.0 m).
Maximum, No more than 1/2 listed sprinkler spacing.
B = Spacing between primary beams: 20 ft (6.1 m) maximum,
= Beam depths 14' (355 mm) maximum.
D = 20 ft (6.1 m) maximum for secondary beams that
are to be equal in depth to primary beams and
that are required so that primary beam pockets
do not exceed 20 ft (6.1 m).
Figure 4113: Primary Beam Spans over 20'-0" (6.1 m)
L,
Sprinkler 145m
January 6, 2010
FREEDOM® RESIDENTIAL
FLUSH PENDENT
SPRINKLER VK476 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
W
ondary Beare
ary Beam* Celllnc
All dimensions are measured to wall
faces and to centerlines of beams,
Com partme,,.
Walls
A = Distance from wall to nearest primary beams
Minimum 3 f t 4 In M0 m).
Maximums No more than 112 listed sprinkler spacing.
B = Spacing between primary beamst 20 ft (61 m) maximum,
C = Beam depths 14' (355 mm) maximum. Note, Secondary beam
depth cannot be greater than the primary beam.
D = Any distance for secondary beams, unless primary
. beam spans exceed 20 ft y6,1 m).
x Refer to Figure 4B for primary beam
spans exceeding 20 ft (61 m).
Figure 4C: Combination of Primary and Secondary Beams
Maxims
ceilini
slope = �
(18.4°
Refer to the Apprc
Chart for listed
areas of coverag
Beare
Secondary
Beam
Face of Soffit
Bottom of Soffit
D = Dimensions shown In Figures 4A, 4B, and 4C,
except measurements are taken from the face
of the soffit Instead of from the wall surface,
NOTE: The sprinkler area of coverage Is to be
measured from the wall.
Figure 4D: Beam and Soffit Arrangements
Note 1 below.
Notes:
1. Listed areas of coverage correspond to areas measured
along ceiling slope. (For sloped ceiling installations, ac-
tual floor coverage in the horizontal plane under sloped
ceilings will be less than the listed area.)
2. Actual installations may require multiple sprinklers.
A single sprinkler installation has been shown for clarity.
3. For"cathedral" ceiling applications, install sprinklers in a
symmetrical mirror-image of Figure 5.
Figure 5: Installation Instructions - Sloped Ceilings
Form No. F120608 Replaces page 145h -m, dated Sept. 3, 2009.
(Revised sloped ceiling listings.)
Technical Features
• Sizes Available (Nominal): 3/4" (DN20) through 3" (DN80) pipe diameters,
c @us
with a Standard Dimension Ratio (SDR) of 13.5 as specified in ASTM F442.
LISTED
• Environmental Specifications: Indoor use only.
FM
Maximum Ambient Temperature: 150°F (65°U
inch metric
inch mm.
APPROVED
• Hazen -Williams C Value: 150
NSF
• Pressure Data: Working Pressure: 175 PSI (12.1 bar) at 150°F (65°0
• Specifications: • Meets NFPA 13R and 13D standards for residential occupancies as well as
DN20
NFPA 13 standards for light hazard occupancies.
0.874 / 22,199
• Pipe meets or exceeds ASTM F442.
15/4,6
• Certified by NSF International for potable water services.
34PIPE
• CPVC pipe from Viking Plastics use compound cell class 23547
DN25
(demonstrated highest structural properties).
1.101 / 27,965
• cULus Listed, FM Approved, New York City (MEA) Approved, LPCB Approved.
15/4,6
CPVC Pipe Physical Data
1 PIPE
Nominal Pipe Size
Actual Outside Diameter
Average I D
Weight per 15' (4.6m) :
Length
Approvals
Part Number E
inch metric
inch mm.
(inch / mm)
- length Ob dkg)
_.
(ft / m)
3/4"
DN20
1.050 26,670
0.874 / 22,199
2.52 / 1,14
15/4,6
cULus, FM,
34PIPE
I"
DN25
1.315 33,401
1.101 / 27,965
3.93/ 1,78
15/4,6
NSF
1 PIPE
1 1/4'
DN32
1.660 42,164
1.394 / 35,408
6.27/2,84
15/4,6
114PIPE
1 12"
DN40
1.900 48,260
1.598 / 40,589
8.22/3,73
15/4,6
112PIPE
2"
DN50
2.375 60,325
2.003 / 50,876
12.89/5.85
15/4,6
2PIPE
212"
DN65
2.875 73,000
2.423 / 61,500
18.86/8,55
15/4,6
212PIPE
3'
DN80
3.500 88,900
2.950 / 74,900
28.01 / 12,71
15/4,6
3PIPE
Nominal Pipe Size
Actual Outside Diameter
Average I.D.
Weight per 10' (3.05ni)
Length
Approvals
Part Number
j inch metric
Ind( mm
Unc / mm)
length (Ib /kg)
(ft / m)
34"
DN20
1.050
26,670
0.874 / 22,199
1.68/0,76
10/3,05
cULus, FM,
34PIPEIO
1"
DN25
1.315
33,401
1.101 / 27,965
2.62/1,19
1013,05
NSF
1 PIPE10
1 1/4"
DN32
1.660
42,164
1.394 / 35,408
4.18/1,90
10/3,05
114PIPEIO
1 12"
DN40
1.900
48,260
1.598 / 40,589
5.48/2,49
10/3,05
112PIPE10
2'
DN50
2.375
60,325
2.003 / 50,876
8.59/3,90
10/3,05
2PIPE10
2 12'
DN65
2.875
73,000
2.423 / 61,500
12.57/5,70
10/3,05
212PIPEIO
3'
DN80
3.500
88,900
2.950 / 74,900
18.67/8,47
10/3,05
3PIPE10
NOTE: CPVC Pipe is produced in SDR 13.5 Dimensions in accordance with ASTM F442. Standard Dimension Ratio is the ratio of the outside pipe diameter to the wall thickness of the pipe.
IMPORTANT: Installers should receive thorough hands-on training in the proper methods of assembly and installation of CPVC products.
Specifications subject to change without notice.
81aseMaster® is a registered trademark of Lubrizol.
Trusted above aII.Tm N I KJ W4j 0
CPVC Pipe Product Specifications
Corrosion resistant CPUC fire sprinkler pipe, when installed in strict accordance with the manufacturers design and installation instructions,
is UL and c -UL Listed by Underwriters Laboratories for use in the following:
• Meets NFPA 13R and 13D standards for residential occupancies as well as NFPA 13 standards for light hazard occupancies.
• Residential occupancies up to and including four stories in height as defined by NFPA 13R.
• Residential occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings, NFPAI3D.
• Installation of private fire service mains and their appurtenances, NFPA 24.
CPVC fire sprinkler pipe from Viking Plastics shall be employed in wet pipe systems only and are not listed for outdoor use. CPVC pipe must
never be used in a system using compressed air or other gases.
CPVC pipe from Viking Plastics also carries the following
enhanced listings and approvals:
• According to UL Listing
• Can be Flush at return air plenums
• Mechanical cut -in tee & crosses concealed with
Grinnell figure 730 fittings
• Mechanical cut -in tee & crosses exposed with
Grinnell figure 730 fittings
• Exposed system risers NFPA 13D, 13R
• Exposed basement NFPA 13D (solid wood joist)
• Extended coverage (exposed)
• 20' spacing on pendent in lieu of 15'
• 18' spacing on sidewall in lieu of 14'
• Use with combustible concealed sprinklers
• Tyco attic sprinkler head (to protect the floor below)
• Tyco attic sprinkler head with wet system piping
(feed main and ridge installation)
New and enhanced listings and approvals are being pursued. Always check with
the appropriate Listing and Approval agency for details on current listing parameters.
CPVC pipe also meets all applicable standards for pressure rated application as
required in ANSI -NSF Standard 14 and complies with ANSI -NSF Standard 61
for health effects and are marked with the NSF-pw end use marking.
All CPVC fire sprinkler pipe shall be Listed by Underwriters Laboratories for wet
pipe systems, and shall carry a rated working pressure of 175 psi @ 150°F (12 bar
@ 65.5°0. The FM Approval is limited to use in wet pipe fire protection sprinkler
systems for light hazard occupancies in both concealed and exposed applications
with certain restrictions.
Piping must always be installed in strict accordance to the manufacturer's DESIGN
AND INSTALLATION GUIDE, including product storage and handling, joining
methods, supporting and bracing, expansion and contraction allowance and testing,
etc National Fire Protection Association (NFPA) Standards 13, 13D, and 13R must
be referenced for design and installation requirements in conjunction with the
installation instructions.
Specifications subject to change without notice.
• Exposed sidewall sprinkler listing for exposed pipe & fittings
• 24' extended coverage sidewall sprinkler, 12" drop,
155T sprinkler head
• 18' extended coverage sidewall sprinkler, 12" drop,
165T sprinkler head
• 16' extended coverage sidewall sprinkler, 12" drop,
175°F sprinkler head
• 14' standard coverage sidewall sprinkler, 12" drop,
200T sprinkler head
• Factory Mutual Approved'
• Factory Mutual Approval exposed
• Factory Mutual Approval above drop-in ceilings
• Factory Mutual Approval exposed w/Soffa-Steel soffjting
covering system
All CPVC fire sprinkler pipe from Viking Plastics is manufactured in the USA. All CPVC
pipe shall be packaged immediately after its manufacture to prevent damage and shall
be stored indoors after production, at the manufacturing site, until shipped from the
factory. The pipe shall bear the logo of the listing agencies, and shall carry the National
Sanitation Foundation (NSF) seal of approval for potable water applications.
CPVC products are intended for use in areas where the maximum ambient
temperature does not exceed 150°F (65.5.0. If the ambient temperature is expected
to exceed this limitation, refer to the manufacturers DESIGN AND INSTALLATION
GUIDE for additional information on methods to reduce the pipe exposure
temperatures. CPVC pipe is not intended to be installed in outdoor applications.
CPVC pipe is intended to be used in wet pipe systems only and have not been
investigated for use in dry pipe systems. Special installation and design criteria relative
to pipe hanger spacings, piping and sprinkler restraint, sprinkler temperature rating,
piping locations, testing procedures and friction loss characteristics are specified in
the manufacturers installation instructions provided with the pipe. The manufacturers
installation instructions should be reviewed and the Authority Having Jurisdiction
consulted before installation.
Trusted above all."m VIKING®
August 13, 2009
Sprinkler 147u
FREEDOM® RESIDENTIAL
• • • CONCEALED PENDENT
SPRINKLER VK457 (K4.9)
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
DESCRIPTION
Viking Freedom® Residential Concealed Pendent Sprinkler VK457 is a small high -
sensitivity solder link and lever residential sprinkler designed for installation on con-
cealed pipe systems where the appearance of a smooth ceiling is desired. The orifice
design, with a K -Factor of 4.9 (70.6 metric*), allows the sprinkler's efficient use of
available water supplies for the hydraulically designed fire -protection system. The
fast response operating element and special deflector combine speed of operation
and areas of coverage to meet residential sprinkler standards.
The sprinkler is pre -assembled with a threaded adapter for installation with a low -
profile small -diameter cover assembly installed flush to the ceiling. The two-piece
design allows installation and testing of the sprinkler prior to installation of the cover
plate. The "push -on", "thread -off" design of the concealed cover plate assembly allows
easy installation of the cover plate after the system has been tested and the ceiling
finish has been applied, while also providing up to Yi' (12.7 mm) of vertical adjustment.
The cover assembly can be removed and reinstalled, allowing temporary removal of
ceiling panels without taking the sprinkler system out of service or removing the sprinkler.
2. LISTINGS AND APPROVALS
cULus Listed: Category VKKW
Refer to the Approval Chart on page 147w and Design Criteria on page 147x for cULus Listing requirements that must be followed.
3. TECHNICAL DATA
Specifications: Viking Technical Data may be found on
Available since 2008. The Viking Corporation's Web site at
Minimum Operating Pressure: Refer to the Approval Chart.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically hteb site may include aimore r.
to 500 psi (34.5 bar). The Web site may include a more recent
Thread size: 1/2" (15 mm) NPT edition of this Technical Data Page.
Nominal K -Factor: 4.9 U.S. (70.6 metric`)
*Metric K -factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400
Deflector: Copper UNS-C51000
Deflector Pins: Stainless Steel UNS-S30200
Button: Brass UNS-C36000
Seat Assembly: Brass UNS-C31600
Compression Screw: Brass UNS-C36000
Fusible Element Assembly: Beryllium Nickel, coated with black acrylic paint
Levers: Stainless Steel UNS-S31600
Lever Bar: Copper Alloy UNS-C72500
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Shipping Cap: Polyethylene
Cover Plate Materials:
Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800
Spring: Beryllium Nickel
Solder: Eutectic
Form No. F_072607 Replaces page 147u -z, issued October 31, 2008. (Revised
minimum and maximum dimensions in Figure 2.)
Sprinkler 147v August 13, 2009
FREEDOM® RESIDENTIAL
• CONCEALED PENDENT
SPRINKLER VK457 (K4.9)
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
Ordering Information: (Also refer to the current Viking price list.)
Viking Freedom® Residential Concealed Pendent Sprinkler VK457 and Cover Plate Assembly must be ordered separately:
Sprinkler: Part No. 14694AC (includes a 165 °F (74 °C) rated sprinkler with a protective plastic cap covering the unit).
Cover Plate Assembly: Base Part No. 13750 (2-3/4" diameter), Base Part No. 14934 (3-5/16" diameter), or Base
Part No. 15394 (square cover plate, 3-5/16" diameter)
Specify finish and temperature rating of the cover plate assembly by first adding the appropriate suffix for the finish and then the
appropriate suffix for the cover temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Painted White = M-/SW1004, Painted Ivory = M-/SW1634, Painted Black = M-/SW1007
Temperature Suffix (°F/°C): 135°/57° =A
For example, cover 13750 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13750FA.
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches":
A. Heavy Duty Part No. 13623W/B (available since 2006), or
B. Head Cabinet Wrench Part No. 13619*** (available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007)
D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007)
**Requires a 'W ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A, Capacity: five (5) sprinklers (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
releasing the deflector. Continued heating of the exposed sprinkler causes the fusible element to disengage releasing the sealing
assembly. Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern over a specific area of
coverage determined by the water supply pressure at the sprinkler to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK457 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Spt1»It r illaximurtr Umpersture Rollittg, $444Ir Govt r
Amblent etNnp of the C Clow IP100 Cover Plate,Pisibi Ili Pont
TemperatureTen�eratiue RatMg' Part Numbee base Pout Numbers
Classlfication Temperature' Assembly (Required) Number'
Ordinary 165 °F (74 °C) 100 °F (38 °C) 135 °F (57 °C) 13750 14934 15394
Cover Plate Finishes: Polished Chrome, Painted White, Painted Ivory, or Painted Black
Footnotes
' The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the
Authority Having Jurisdiction. Refer to specific installation standards.
3 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
August 13, 2009
Sprinkler 147w
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK457 (K4.9)
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
_--- __ Approval Chart
itpslderttlai Concealed Pendent Sprinkler VK457 m�
For system designed to NFPA 130 or NFPA 13R.
For systems designed to NFPA 13, refer to the design criteria on page 147x.
Sprinkler Base
NPT Thread Size
Nominal K -Factor
Maximum Water
Part Number'
SIN
Working Pressure
Inches
mm
U.S.
metria
14694A
VK457
1/2
15
4.9
70.6
175 psi (12 bar)
Listings and Approvals'
Maximum Areas of Coverages
Minimum Water Supply Requirements'
(Refer also to Design Criteria on page 147x.)
cULus° NYC NSP
Installed below smooth, flat, horizontal ceilings, including ceilings* with slopes up to and Including 2/12 (9.5°).
12 ft. x12ft. (3.7mx3.7m) 13 gpm@ 7.0 psi (49.2 Umin @ 0.48 bar) AX1 -- AX1
14 ft. x 14 ft. (4.3 m x 4.3 m) 13 gpm@ 7.0 psi (49.2 Umin @ 0.48 bar) AXI -- AX1
16 ft. x 16 ft. (4.9 m x 4.9 m) 13 gpm@ 7.0 psi (49.2 Umin @ 0.48 bar) AX1 -- AXI
18 ft. x 18 ft. (5.5 m x 5.5 m) 17 gpm @ 12.0 psi (64.4 Umin @ 0.83 bar) AX1 -- AXI
20 ft. x 20 ft. (6.1 m x 6.1 m) 20 gpm @ 16.7 psi (75.7 Umin @ 1.15 bar) AX1 -- AX1
Installed below ceilings with slopese up to and Including a 8/12 (33.7°) pitch. Refer to Figure 5 on page 147z.
UL NYC NSP
16 ft. x 16 ft. (4.9 m x 4.9 m) 26 gpm @ 28.2 psi (98.4 Umin @ 1.94 bar)
AX1 -- AX1
18 ft. x 18 ft. (5.5 m x 5.5 m) 31 gpm @ 40.0 psi (117.3 Umin @ 2.76 bar)
AX1 -- AXI
20 ft. x 20 ft. (6.1 m x 6.1 m) 31 gpm @ 40.0 psi (117.3 L/min @ 2.76 bar)
AX1 -- AXI
Cover Temperature Rating
Cover Plate Finishes
Sprinkler Temperature Rating
X - 135 °F (57 °C) cover 137501, 14934' (large diameter),
1 - Polished Chrome, Painted White, Painted Ivory,
A - 165 °F (74 °C)
or 15394 (square cover plate)
and Painted Black8
Footnotes
' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K -factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0.
3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any
additional approvals.
° Listed by Underwriter's Laboratories for use in the U.S. and Canada.
s For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement" for the next larger area listed. Flows and pressures listed
are per sprinkler. The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum Water Supply
Requirement' used.
8 Areas under sloped ceilings must be measured along the ceiling slope. Actual floor coverage in the horizontal plane under sloped ceilings will be less
than the listed area of coverage.
' Tested and Certified by NSF (National Sanitation Foundation) to NSF/ANSI Standard 61, Drinking Water System Components.
8 Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer.
Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3.
Sprinkler 147x August 13, 2009
FREEDOM® RESIDENTIAL
• CONCEALED PENDENT
SPRINKLER VK457 (K4.9)
-NlKjw4j
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
DESIGN CRITERIA
(Also refer to the Approval Chad on page 147w.)
cULus Listing Requirements:
When using Viking Residential Concealed Pendent Sprinkler VK457 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-
age and minimum water supply requirements shown in the Approval Chart on page 147w.
For systems designed to NFPA 13 The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum
required discharge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in the Approval Chart on data page 147w for NFPA 13D and NFPA 13R applications for each listed area of coverage,
2E
• Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the "design area" in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
• Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE: Concealed sprinklers must be Installed In neutral or negative pressure plenums only.
IMPORTANT. Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to pages
RES1-17 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar
Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained
from the Authorities Having Jurisdiction.
Sprinkler and
Adapter Assembly
(Protective Cap
is removed for
installation --use
Wrench 13619)9)K)
Step 11 Carefully sl
wrench sideways a
the deflector anc
)KeA 1/2' ratchet is required
(not available from Viking),
M
2-1/4' (57.2 mm)
diameter opening
Is required In
the ceiling, —
Sprinkler
Wrench
(Part No.
13623W/Bw*
Is shown)
Step 2: Carefully press the wrench
upward and turn slightly to ensure
engagement with sprinkler wrench flats,
Figure 1: Sprinkler Installation and Correct Use of Wrenches
August 13, 2009
Sprinkler 147y
FREEDOM® RESIDENTIAL
• CONCEALED PENDENT
SPRINKLER VK457 (K4.9)
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
1/2'
(15 mm)
NPT
2-1/8'
'(54 mm)
Note: Upon sprinkler activation, the deflector descends
to approximately 13/16' (20.6 mm) below the sprinkler body,
2-1/16'
(52 mm)
Minimum
Figure 2: Sprinkler Dimensions and Cover Installation
CUSTp�\
Q rZ
v
o;
o
r— o
v
VIKING
Identification of .Custom Paint Color:
All custom color painted cover plates will
have an identifying label affixed to the
inside of the cover that indicates custom
color and will have a representative sample
(a paint dot) of the paint on the label,
Figure 3: Identification of Custom Paint Color for Concealed Covers
2-3/4' (70 mm) or
3-5/16' (84,1 mm)
D❑ NOT PAINT
�3-5/16' (84.1 Mrs) ►�
Figure 4: Square Cover Assembly 15394
Sprinkler 147z August 13, 2009
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
MaximL
ceilinc
slope = F
(33.7
Refer to the Appro
Chart for listed
areas of coverag
Note 1 below.
Notes:
1. Listed areas of coverage corre-
spond to areas measured along
ceiling slope. (For sloped ceiling
installations, actual floor cover-
age in the horizontal plane under
sloped ceilings will be less than
% the listed area.)
2. Actual installations may require
multiple sprinklers. A single sprin-
kler installation has been shown
for clarity.
3. For "cathedral' ceiling applica-
tions, install sprinklers in a sym-
metrical mirror-image of Figure 5.
Figure 5:
Installation Instructions - Sloped Ceilings
Form No. F_072607 Replaces page 147u -z, issued October 31, 2008. (Revised
minimum and maximum dimensions in Figure 2.)
Rel-labila
Guidelines for Listed Residential Sprinkler
installations below Sloped Ceilings
The installation guidelines cover
Residential Sprinkler Models:
F1 Res 49 Pendent
F1 Res 49 Recessed Pendent/F2
F1 Res 58 Pendent
F1 Res 58 Recessed Pendent/172
F1 Res 44 HSW
F1 Res 44 Recessed HSW/F2
F1 Res 49 CCP
F1 Res 58 CCP
RFC 43 Flat Concealed
RFC 49 Flat Concealed
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
2. NYC MEA 258-93-E
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents: US Patent number 6,516,893
Model F1 Res 49
Product Description for F1 Res Sprinklers
Model F1 Res Pendent sprinklers are fast response
sprinklers combining excellent durability, high sensitivity
glass -bulb and low profile decorative design. The F1 Res
Horizontal Sidewall sprinklers are equally attractive when
above ceiling piping cannot be used.
The 3mm glass -bulb pendent sprinklers, with a K Factor
of 4.9 & 5.8 for pendent and 4.4 for horizontal sidewall,
permit the efficient use of residential water supplies for
sprinkler coverage in residential fire protection design.
The low flow F1 Res sprinklers are specially engineered
for fast thermal response to meet the sensitive fire protec-
tion application needs of the latest residential market stan-
dards (UL 1626 Standard *). Upon fire conditions, rising
heat causes a sprinkler's heat -sensitive glass -bulb to shat-
ter, releasing the waterway for water flow onto the deflec-
tor, evenly distributing the discharged water to control a
fire.
Bulletin 035 Rev. H
Residential Sprinkler
For Sloped Ceilings
F1 Res 49 & 58
Pendent
F1 Res 44
HSW
F1 Res 49 & 58 CCP
Pendent
mr-u 41j b& HrIL. 4y
* Effective date July 12, 2002
F1 Res 49 & 58
Recessed Pendent / F2
r I ries 44
Recessed HSW/F2
RFC 43 & RFC 49
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Product Description for RFC 43 & RFC 49
Model RFC43 & RFC49 Concealed Residential Sprin-
klers are fast response residential fusible solder link au-
tomatic sprinklers. Residential sprinklers differ from stan-
dard'sprinklers primarily in their response time and water
distribution patterns.
Model RFC43 & RFC49 sprinklers discharge water in a
hemispherical pattern below the sprinkler deflector. Resi-
dential distribution patterns are higher and generally con-
tain a finer droplet size than standard sprinkler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has dem-
onstrated, in fire testing, an ability for controlling residen-
tial fires, and thereby providing significant evacuation time
for occupants.
The RFC43 & RFC49 Sprinkler provides the best form
of fire protection by combining an attractive appearance
and 1/2" (13mm) of cover adjustment for ease of installa-
tion. The small diameter cover plate is easily and posi-
tively attached and blends into the ceiling, concealing the
most dependable fire protection available, an automatic
sprinkler system.
The RFC43 & RFC49 are UL Listed Residential Sprinkler
to be installed in the residential portions of any occupancy
in accordance with NFPA 13,13R, & 13D.
The RFC43 & RFC49 can reduce the need for precise
cutting of drop nipples. The threaded cover plate assem-
bly can be adjusted without tools to fit accurately against
the ceiling. The fire protection system need not be shut
down to adjust or remove the cover plate assembly.
2.
Technical Data (F1 Res Sprinklers):
e Thermal Sensor: Nominal 3mm glass -bulb
Sprinkler Frame: Brass Casting
• Sprinkler Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size : 1/2" NPT (R1/2)
• K Factor : 4.9 (Actual) - F1 Res 49 Pendent Sprinkler
4.4 (Actual) - F1 Res 44 HSW Sprinkler
5.8 (Actual) - F1 Res 58 Pendent Sprinkler
• Density : Minimum .05 gpm/ft2
,Technical Data (RFC 43 & RFC 49):
• Thermal Sensor: 165°F Fusible Link
• Sprinkler Frame: Brass Machined
• Sprinkler Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size : 1/2" NPT (RI/2)
• K Factor 4.3 (Actual) RFC43;
4.9 (Actual) RFC49
• Density Minimum .05 gpm/ft2
Application
Model F1 Res and RFC 43 & RFC 49 Sprinklers are used
for Residential Fire Protection according to UL 1626 Stan-
dard*. Be sure that orifice size, temperature rating, deflec-
tor style, cover plate and sprinkler type are in accordance
with the latest published standards of The National Fire
Protection Association or the approving Authority Having
Jurisdiction.
* Effective date July 12, 2002
METHOD OF CALCULATING THE CONVERSION
OF 'RISE -OVER -RUN' TO DEGREES OF AN ANGLE.
.mac
a (rise)
run C
1.4 A = TAN-' (a/b)
2. slope distance: c = I;r + b2
Example: a = 4
b = 12'
.¢A = TAN .' (a/b) slope distance: c = 4Z +122
.4A = TAN-' = (0:333) c = 1160
4A= 18.43' c= 12.65
1055_ROR A
N
Model F1 Res 49 Pendent & F1 Res 49 Recessed Pendent/F2 & F1 Res 49 CCP Pendent,
,Model F1 Res 58 Pendent & F1 Res 58 Recessed Pendent/F2 & F1 Res 58 CCP Pendent,
RFC 43 & RFC 49 Pendent Flat Concealed Sprinklers installed below Sloped Ceilings.
F1 Res 49 & 58
Pendent
F1 Res 49 & 58
Recessed Pendent / F2
RFC 43 & RFC 49
Note: F1 Res 49 CCP Pendent, RFC 43 and RFC 49
sprinklers are not suitable for installation in ceilings
which have positive pressure in the space above.
4
F1 Res 49 & 58 CCP
Pendent
mr-U 415 b& mr-U 4y
L/2
L L/2
A B
W
L/2
C , ' wQG
-' ELEVAT/ON - L
B
LISTED AREA OF COVERAGE
CORRESPONDS TO CEILING SLOPE _ L/2
L = THE MAXIMUM LISTED SPRINKLER - \NIN.
SPACING, LENGTH (8'-0" MINIMUM).
L/2 = ONE HALF THE MAXIMUM LISTED
SPRINKLER SPACING (0'-4" MINIMUM).
W THE MAXIMUM LISTED SPRINKLER
SPACING, WIDTH.
A 3'-0" MAXIMUM., F�ooa
B = RANGE: 2/12 (9.4') *< B S 8/12 (33.70).
C = 8'-0" MINIMUM.
035FGOI
5.
ELEVA
LISW AREA OF COYLWGE
CORRESMAOM IO CEILING
-+f
L = THE MAXIMUM LISTED SPRINKLER
SPACING. LENGTH (8'-0" MINIMUM).
L/2 = ONE HALF THE MAXIMUM LISTED
SPRINKLER SPACING (0'-4" MINIMUM).
W = THE MAXIMUM LISTED SPRINKLER
SPACING, WIDTH.
A = 3'-0" MAXIMUM.
8 = RANGE: 2/12 (9.4') < 8 S 8/12 (33.7*)
C = 8'-0" MINIMUM.
OJ5FW2
*--B
Sprinkler spacing below multiple sloped ceilings with a maximum slope of 8/12 (33.70) pitch.
r
6
Model F1 Res 49 Pendent & F1 Res 49 Recessed Pendent/F2 installed below Sloped Ceiling.
Technical Data
Table 1 - Application
Max.
Max.
Actual
Min. Flow Per Sprinkler Head
Pressure
Sprinkler
Thread
Pressure
Ambient
K Factor
Sprinkler
Escutcheon
Identification
Size
psi (bar)
Temp.em
(metric)
Length
(68°C)
Number (SIN)
Sprinkler mead gpm psi (bar)
Length
Number (SIN)
14 x 14 4,3 x 4,3
14 53
8.2 0,57
12 x 12 3,6 x 3,6
'/i' NPT (R'/2)
175 (12)
100 (38)
4.9 (69,94)
2.25" (57mm)
1/2" Adjustment)R3516
7.0 0,48
Table 1 - Application
Model F1 Res 49 CCP Pendent installed below Sloped Ceiling.
Technical Data
Max. Slope of 8hz
33.7° Pitch
Max. Slope of °hz 18.4° Pitch
Min. Flow Per Sprinkler Head
Pressure
Sprinkler Temp. Rating OF (°C)
Max. Sprinkler Spacing
Along Slope
gpm (Lpm)
psi (bar)
155 (68) & 175 (79)
Ambient
K
175°F
Min. Flow Per Pressure
(W) Width x ( L) Length it (m)155°F
OF (°C)
155-F (68-C) 175-F (790C)
(68°C)
(79°C)
Sprinkler mead gpm psi (bar)
Length
Number (SIN)
14 x 14 4,3 x 4,3
14 53
8.2 0,57
12 x 12 3,6 x 3,6
13 49 13 49
7.0 0,48
7.0 0,48
13 49 7.0(0,48
14 x 14 4,3 x 4,3
13 49 13 49
7.0 0,48
7.0 0,48
13 49 7.0 0,48
16 x 16 4,9 x 4,9
13 49 13 49
7.0 0,48
7.0 0,48
13 49 7.0 0,48
18 x 18 5,5 x 5,5
17 64,3 18 68,2
12.0 0,83
13.5 0,93
18 68,3 13.5 0,93
20 x 20 6,1 x 6,1
20 75,7 21 79,5
16.7. 1,15
18.4 1,28
20 75,7 16.7(l.15)
Model F1 Res 49 CCP Pendent installed below Sloped Ceiling.
Technical Data
Table 2 - Application
Max. Sprinkler Spacing
Sprinkler
CCP Assy.
Max.
Max.
Actual
Min. Flow
Sprinkler
Thread Size
Temp. Rating
Temp.
Pressure
Ambient
K
Sprinkler
Identification
100 (38)
OF (°C)
Rating
OF°C
psi (bar)
Temp.
Factor
Length
Number (SIN)
14 x 14 4,3 x 4,3
14 53
8.2 0,57
13 49
OF °C
metric
14 53
8.2 0,57
'/z" NPTR'/z
155 68
135 57
175 12
100 38
4.9 69,94
2.25" 57mm
R3516
Table 2 - Application
Max. Sprinkler Spacing
Max. Slope of 8hz 33.70Pitch
Max. Slo
of 4/1218.4° Pitch
Min. Flow
Pressure
Min. Flow
Pressure
Along Slope
(W) Width x (L) Length ft (m)
Per Sp
Sprinkler Head
psi (bar)
Per Sprinkler Head
(bar)
'/z" NPT (RI/2)
m (Lpm)
100 (38)
m(Lpm)psi
2.25" (57mm)1/2
12 x 12 3,6 x 3,6
14 53
8.2 0,57
13 49
7.0 0,48
14 x 14 4,3 x 4,3
14 53
8.2 0,57
13 49
7.0 0,48
16 x 16 4,9 x 4,9
14 53
8.2 0,57
14 53
8.2 0,56
18 x 18 5,5 x 5,5
23 87
22 1,52
20 75,7
17 1,17
20 x 20 6,1 x 6,1
23 87
22 1,52
21 75,7
17 1,17
Model F1 Res 58 Pendent & F1 Res 58 Recessed Pendent/F2 installed below Sloped Ceiling.
Technical Data
Thread
Max.
Pressure
Max.
Ambient Temp.
Actual
Sprinkler
Min. Flow
Sprinkler Identifica-
Size
sI bar
°F °C
K Factor (metric)
Length
Pressure
tion tion Number (SIN)
'/z" NPT (RI/2)
175 (12)
100 (38)
5.8 (83,38)
2.25" (57mm)1/2
AdF stment
R3513
Table 3 - Application
7.
Max. Slope of 8 33.7° Pitch
Max. Slope of °hz 18.4° Pitch
Min. Flow
Max. Sprinkler Spacing
Along Slope
Min. Flow Per Sprinkler Head
Pressure
Per Sprinkler
Pressure
(W) Width x ( L) Length ft (m)
gpm (Lpm)
psi (bar)
Head
psi (bar)
m (Lpm)
155°F 68°C 175°F 79°C
155°F 68°C 175°F 79°C
155°F 68°C
155°F 68°C
12 x 12 (3,6 x 3,6)
21 (79.5) 23 (87)
13.1 (0,9) 15.7 (1,1)
14 x 14 4,3 x 4,3
21 79.5 23 87
13.1 0,9 15.7 1,1
16 x 16 4,9 x 4,9
21 79.5 23 87
13.1 0,9 15.7 1,1
18 x 18 5,5 x 5,5
23 87
15.7 1,1
20 75,7
12 0,83
20 x 20 6,1 x 6,1
23 87
15.7 1,1
20(75,7)
12(0,83)
7.
Model F1 Res 58 CCP Pendent Installed below sloped Ceiling.
Technical Data
Table 4 - Aoolication
Max. Sprinkler Spacing Along Slope Max. Slope of °/12 18.40Pitch
(W) Width x ( L) Length ft (m) Min. Flow Per Sprinkler Head Pressure
m (Lpm) psi bar
18x18 55x55 20 75.7 12(0.83)
20 x 20 (6.1 x 6.1) 20 75.7 12(0.83)
Model RFC43 Pendent Flat Concealed installed below Sloped Ceiling.
Technical Data
Sprinkler Temp.
CCP Assy.
Max.
max.
ActualZ2557
Max
Sprinkler
Thread Size
Rating
Temp.
Pressure
Ambient
KIdentification
Identification
30(30.0)
of (°C)
Rating
psi (bar)
Twp'
Factor (metric)
Adjustment
Number (SIN)
1/z" NPT (RI/2)
165 74
F C
175 12
°F °C
4.3(61.4)
'/z" 13mm
RA0612
'/z" NPT R'/2
155 68
135 57
175 12
100 38
5.8 83,38
17.5 121
R3513
Table 4 - Aoolication
Max. Sprinkler Spacing Along Slope Max. Slope of °/12 18.40Pitch
(W) Width x ( L) Length ft (m) Min. Flow Per Sprinkler Head Pressure
m (Lpm) psi bar
18x18 55x55 20 75.7 12(0.83)
20 x 20 (6.1 x 6.1) 20 75.7 12(0.83)
Model RFC43 Pendent Flat Concealed installed below Sloped Ceiling.
Technical Data
Table 5 - Application
Sprinkler
Coverplate
Max.
Max.
Actual
Max
Sprinkler
Thread Size
Temp. Rating
Temp. Rating
Pressure
Ambient Temp.
K Factor
Max.
Identification
30(30.0)
°F °C
°F °C
psi bar
°F °C
metric
Adjustment
Number SIN
1/z" NPT (RI/2)
165 74
135 57
175 12
100 38
4.3(61.4)
'/z" 13mm
RA0612
Table 5 - Application
Model RFC 49 Pendent Flat Concealed installed below Sloped Ceiling.
Technical Data
Max. Slo of 8/12 (33.7*1 Pitch
Max. Slopeof
4/12 18.4° Pitch
Max. Sprinkler Spacing Along Slope
Min. Flow Per Sprinkler Head
Pressure
Min. Flow Per
Pressure
(W) Width x ( L) Length ft (m)
gpm (Lpm)
psi (bar)
Sprinkler mead
psi (bar)
Max.
Identification
30(30.0)
qpm
°F °C
12x12 36x36
18 68
17.5 121
13 49
9.1(0.63)
14 x 14 3x43
18 68
17.5 121
13 49
9.1(0.63)
16x16 49x49 1
18 68 1
17.5 121
13 49
9.1 063
18x18 55x55
24 91
31(2,14)
18 68
17.5 121
20 x 20 6,1 x 6,1
24 91
31 2,14
21 79
23.8 1,64
Model RFC 49 Pendent Flat Concealed installed below Sloped Ceiling.
Technical Data
Table 6 - Application
Max. Sprinkler Spacing Along Slope
(W) Width x (L) Length ft (m)
Sprinkler
Coverplate
Max.
Max.
Actual
23 193
Sprinkler
Thread Size
Temp. Rating
Temp. Rating
Pressure
Ambient Temp.
K Factor
Max.
Identification
30(30.0)
°F °C
°F °C
i bar
°F °C
metric
Adjustment
Number SIN
1/2" NPT(RI/2)
165 74
135 57
175 12
100 38
4.9(69,94)
Yz" 13mm
RA0616
Table 6 - Application
Max. Sprinkler Spacing Along Slope
(W) Width x (L) Length ft (m)
Max. Slo a of 8/12 33.7° Pitch
Max. Slope of 4/1208.41 Pitch
Min. Flow Per Sprinkler Head Pressure Min. Flow Per Sprinkler Head Pressure
m (Lpm) psi bar gpm (Lpm) psi bar
16x16 49x49
28 106
23 193
18 x 18 (5.5 x 5.5)
29 109.8
29(20.0)
18 68
13.5(0 93
20 x 20 (6.1 x 6 1
30 113.6
30(30.0)
1 23 87
220,52)
Installation Guidelines
1. For systems designed in accordance with NFPA 13,
13D and 13R, where specific UL Listed flows are not
required, consult with the local Authority Having Juris-
diction regarding the number of design sprinklers for
sloped ceilings having a pitch greater than (9.40).
2. Installation of UL Listed residential sprinklers under
sloped ceilings shall be limited to a type of unob-
structed construction consisting of smooth ceilings,
as defined by NFPA 13, having a maximum pitch of
4/12 (18.41) or 8/12 (33.7°).
3. Spacing of residential sprinklers under sloped ceil-
ings is measured along the slope when determining
the distance off of walls and between sprinklers.
4. Measure listed areas of coverage along the sloped
ceiling. The actual floor coverage area will be less
than the listed area.
5. For coverage areas less than the listed coverage area
shown in Tables 1 through 5, use the minimum flow
requirement for the next largest listed coverage area.
.:*
6. Minimum spacing between pendent type sprinklers is
8 ft. (2.4 m). Minimum distance from a pendent type
sprinkler and an adjacent wall is 4" (102 mm).
7. Residential sprinklers located closest to the peak of
the ceiling shall have the deflectors located not more
than 3 ft (1m) vertically down from the peak. Align de-
flectors parallel with the ceiling slope 1" to 4" (25mm
to 102mm) below the sloped ceiling.
8. Hydraulic Requirements:
a. For NFPA 13D Systems, the number of design
sprinklers shall include all sprinklers within a
compartment, up to a maximum of two sprinklers
(where specific UL Listed flows are required) that
requires the greatest hydraulic demand.
b. For NFPA 13R Systems, the number of design
sprinklers shall include all sprinklers within a com-
partment, up to a maximum of four (4) sprinklers
(where specific UL Listed flows are required), that
requires the greatest hydraulic demand.
c. For NFPA 13 systems, the design area shall be
the area that includes the four (4) hydraulically
most demanding sprinklers. The minimum re-
quired discharge from each of the four hydrauli-
cally demanding sprinklers shall be the greater of
the following:
(1) In accordance with the minimum flow rates in-
dicated by the individual listings (that already
will provide a minimum density of 0.1 gpm/ft2);
or
(2) A calculated value based on delivering a mini-
mum of 0.1 gpm/ft2 over the design area.
9. Because of the varied nature of residential construc-
tion features, there will be some compartment designs
which cannot be fully sprinklered in accordance with
NFPA 13, 13D, or 13R. In these instances, consult
the Authority Having Jurisdiction (AHJ) for guidance
and approval. This includes sloped ceilings having a
pitch greater than 8/12 (33.7).
10. Glass bulb sprinklers have orange bulb protectors
to minimize bulb damage during shipping, handling
and installation. REMOVE THIS PROTECTION AT THE
TIME THE SPRINKLER SYSTEM IS PLACE IN SER-
VICE FOR FIRE PROTECTION. Removal of the pro-
tectors before this time may leave the bulb vulnerable
to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PRO-
TECTORS BY UNDOING THE CLASP BY HAND. DO
NOT USE TOOLS TO REMOVE THE PROTECTORS.
Model F1 Res 44 and F1 Res 44 HSW/F2 installed below Sloped Ceiling.
F1 Res 44
HSW
F1 Hes 44
Recessed HSW/F2
Horizontal 5idewall bprinKler
(with discharge directed across the slope)
91
(with discharge directed down the slope)
- = LISTED AREA OF COVERAGE
A ;S B CORRESPONDS
TOP OF DEFLECTOR MUST BE LOCATL
C 4' TO 12' BELOW SLOPED CE/UNG.
THE TOP OF THE DEFLECTOR MUST I
PARALLEL WITH THE PLANE OF THE i
ELEVAT/ON DISCHARGE /S A THE SLOPE.
L = THE MAXIMUM LISTED SPRINKLER
SPACING, LENGTH.
W = THE MAXIMUM LISTED SPRINKLER
SPACING, WIDTH.
W/2 = ONE—HALF THE MAXIMUM LISTED SPRINKLER
SPACING, WIDTH (0'-4" MINIMUM).
A = 3'-0" MAXIMUM.
B = RANGE: 2/12 (9.4') < B s 8/12 (33.7'):
C = 8'-0" MINIMUM.
TOP OF DEFLECTOR MUST BE LOCATED
4' TO 12' BELOW SLOPED CEILING.
THE TOP OF 7H£ DEFLECTOR MUST BE
PARALLEL WITH THE PLANE OF THE COUNG.
DISCHARGE /S DOWN THE SLOPE.
035FGOJB
p,
D AREA OF COVERAGE
ESPONDS TO CEILING SLOPE
HSW sprinkler spacing below single sloped ceilings with a maximum slope of 9/12 (33.7°) pitch.
W
B
LEM AREA OF COVERAGE
oDRRESAavas ro c>:TLLMc SLOPE
Ci TOP OF DIEFLEL= MUST BE L.OGTED
4' ro B' BELOW SLOPm CMAC THE
EL /VA TOP OF THE QEFLECTOR MUST BE
PARALLEL MON THE PLANE OF THE CEUAA
DMWAGGE IS AQMS THE SLOPE
L = THE MAXIMUM LISTED SPRINKLER
SPACING. LENGTH.
W = THE MAXIMUM LISTED SPRINKLER
SPACING. WIDTH (0'-4' MINIMUM).
W/2 = ONE—HALF THE MAXIMUM LISTED SPRINKLER
SPACING. WIDTH (0'-4' MINIMUM).
A = 3'-0' MAXIMUM.
B = RANGE: 2/12 (9.4') < B s 8/12 (33.T).
C = 8'-0" MINIMUM.
OT5FG104
prinkler spacing below multiple sloped ceilings with a maximum
10. ;
Model F1 RES 44 HSW & F1 RES 44 HSW Recessed HSW/F2 installed below Sloped Ceiling.
Technical Data
Table 7 - Application
Sprinkler Temp.
Max.
Max.
Actual
Sprinkler
Discharge Directed Across the Slope
Sprinkler
Thread Size
Rating
Pressure
Ambient Temp.
K Factor
Len ht
g
Escutcheon
Identification
OF °C
i bar
OF °C
metric
16 60,5
13.3 (0,92)
Number SIN
'/2" NPT (R'/2)
155 (68)
175 (12)
100 (38)
4.4 (62,8)
2.45"
F2
R3531
13.3 0,92
175 79
15 1,04
18 x 18 4,9 x 5,5
18 68,1
62mm
1/2" Adjustment
20.7 1,43
Table 7 - Application
Table 8 - ADDlication
Max.
Max. Slope of 4/12 18.4° Pitch
Max. Sprinkler Spacing Along Slope
Discharge Directed Across the Slope
Discharge Directed Across the Slope
(W) Width x ( L) Length ft (m)
4" to 6" Deflector to Ceiling
6" to 12" Deflector to Ceilin
Down the Slope
6" to 12"
Deflector to Ceiling
Min. Flow gpm (Lpm)
Pressure psi (bar)
Min. Flow gpm (Lpm)
Pressure
mLm psi (bar)
mLm sibar
psi(bar)
12 x 12 3,6 x 3,6
16 60,5
13.3 (0,92)
17 64,3
15 1,04
14 x 14 4,3 x 4,3
16 60,5
13.3 0,92
17 64,3
15 1,04
16 x 16 4,9 x 4,9
16 60,5
13.3 0,92
17 64,3
15 1,04
18 x 18 4,9 x 5,5
18 68,1
16.8 1,16
20 75,6
20.7 1,43
20 x 20 (4,6 x 6,1)
23 68,1
27.4 1,89
23 68,1
27,4 1,89
Table 8 - ADDlication
(1) Minimum flow per sprinkler gpm (Lpm).
(2) Minimum 3 head design in a compartment.
(3) 155°F only.
Installation Guidelines
1. For systems designed in accordance with NFPA 13,
13D and 13R, where specific UL Listed flows are not
required, consult with the local Authority Having Juris-
diction regarding the number of design sprinklers for
sloped ceilings having pitch greater than (9.40).
2. Installation of UL Listed residential sprinklers under
sloped ceilings shall be limited to a type of unobstruct-
ed construction consisting of flat, smooth ceilings, as
defined by NFPA 13, having a maximum pitch of 4/12
(18.40) or 8/12 (33.70).
3. Where listed, install horizontal sidewall sprinklers
along the wall below the sloped ceiling when dis-
charge is directed across the slope, and install at
the peak below the sloped ceiling when discharge is
directed down the slope. Always align the sprinkler
deflector parallel with the direction of the sloped ceil-
ing.
4. Residential HSW sprinklers located closed to the peak
of the ceiling shall have the deflectors located not
more than 3 ft. (1m) vertically down from the peak.
5. Spacing of residential HSW sprinklers under sloped
ceilings is measured along the slope when determin-
ing the distance off of walls and between sprinklers.
11.
6. Measure listed areas of coverage along the sloped
ceiling. The actual floor coverage area will be less
than the listed area.
7. For coverage areas less than the listed coverage area
shown in Tables 1 through 6, use the minimum flow
requirement for next largest listed coverage area.
8. Minimum spacing between horizontal sidewall sprin-
klers is 8 ft. (2.4 m). Minimum distance from a hori-
zontal sidewall sprinkler and an adjacent wall is 4"
(102 mm).
9. Hydraulic Requirements:
a. For NFPA 13D Systems, the number of design
sprinklers shall include all sprinklers within a
compartment, up to a maximum of two sprinklers
(where specific UL Listed flows are required) that
requires the greatest hydraulic demand.
b. For NFPA 13R Systems, the number of design
sprinklers shall include all sprinklers within a com-
partment, up to a maximum of four (4) sprinklers
(where specific UL Listed flows are required), that
requires the greatest hydraulic demand.
Max.
Sloo of 8/12 33.70Pitch
Discharge Directed
Discharge Directed
(430ischarge Directed
Max. Sprinkler Spacing Along Slope
(W) Width x (L) Length ft (m)
Down the Slope
4" to 6"
Deflector to Ceilina
Down the Slope
6" to 12"
Deflector to Ceiling
Across the Slope
4" to 12"
Deflector to Ceiling
Min. Flow Pressure
Min. Flow Pressure
(1) Min. Flow Pressure
mLm psi (bar)
mLm sibar
gpm (Lpm) sibar
12x12 36x36
12(45.4) 7.5(0.52)
14(53.0) 10.2 071
16(60.6) 13.3 092
14x14 43x43
14(53.0) 10.2 071
16(60.6) 13.3 092
16(60.6) 13.3 092
16x16 49x49
16(60.6) 13.3 092
17(64.4) 150,04)
16(60.6) 13.3 092
18x18 49x55
18(68.1) 1 16.8 116
20(75.6) 20.7 143
20 x 20 4,6 x 6,1
23 72,0 27.4 1,89
23 87,1 27,4 1,89
(1) Minimum flow per sprinkler gpm (Lpm).
(2) Minimum 3 head design in a compartment.
(3) 155°F only.
Installation Guidelines
1. For systems designed in accordance with NFPA 13,
13D and 13R, where specific UL Listed flows are not
required, consult with the local Authority Having Juris-
diction regarding the number of design sprinklers for
sloped ceilings having pitch greater than (9.40).
2. Installation of UL Listed residential sprinklers under
sloped ceilings shall be limited to a type of unobstruct-
ed construction consisting of flat, smooth ceilings, as
defined by NFPA 13, having a maximum pitch of 4/12
(18.40) or 8/12 (33.70).
3. Where listed, install horizontal sidewall sprinklers
along the wall below the sloped ceiling when dis-
charge is directed across the slope, and install at
the peak below the sloped ceiling when discharge is
directed down the slope. Always align the sprinkler
deflector parallel with the direction of the sloped ceil-
ing.
4. Residential HSW sprinklers located closed to the peak
of the ceiling shall have the deflectors located not
more than 3 ft. (1m) vertically down from the peak.
5. Spacing of residential HSW sprinklers under sloped
ceilings is measured along the slope when determin-
ing the distance off of walls and between sprinklers.
11.
6. Measure listed areas of coverage along the sloped
ceiling. The actual floor coverage area will be less
than the listed area.
7. For coverage areas less than the listed coverage area
shown in Tables 1 through 6, use the minimum flow
requirement for next largest listed coverage area.
8. Minimum spacing between horizontal sidewall sprin-
klers is 8 ft. (2.4 m). Minimum distance from a hori-
zontal sidewall sprinkler and an adjacent wall is 4"
(102 mm).
9. Hydraulic Requirements:
a. For NFPA 13D Systems, the number of design
sprinklers shall include all sprinklers within a
compartment, up to a maximum of two sprinklers
(where specific UL Listed flows are required) that
requires the greatest hydraulic demand.
b. For NFPA 13R Systems, the number of design
sprinklers shall include all sprinklers within a com-
partment, up to a maximum of four (4) sprinklers
(where specific UL Listed flows are required), that
requires the greatest hydraulic demand.
For NFPA 13 systems, the design area shall be
the area that includes the four (4) hydraulically
most demanding sprinklers. The minimum re-
quired discharge from each of the four hydrauli-
cally demanding sprinklers shall be the greater of
the following:
(1) In accordance with the minimum flow rates in-
dicated by the individual listings (that already
will provide a minimum density of 0.1 gpm/ft2);
or
(2) A calculated value based on delivering a mini-
mum of 0.1 gpm/ft2 over the design area.
10. Because of the varied nature of residential construc-
tion features, there will be some compartment designs
which cannot be fully sprinklered in accordance with
NFPA 13, 13D, or 13R. In these instances, consult
the Authority Having Jurisdiction (AHJ) for guidance
and approval. This includes sloped ceilings having a
pitch greater than 8/12 (33.70).
11. Glass bulb sprinklers have orange bulb protectors
to minimize bulb damage during shipping, handling
and installation. REMOVE THIS PROTECTION AT THE
TIME THE SPRINKLER SYSTEM IS PLACE IN SER-
VICE FOR FIRE PROTECTION. Removal of the pro-
tectors before this time may leave the bulb vulnerable
to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PRO-
TECTORS BY UNDOING THE CLASP BY HAND. DO
NOT USE TOOLS TO REMOVE THE PROTECTORS.
Model F1 res 49 Pendent, F1 Recessed Pendent/F2, F1 Res 49 Concealed (CCP), RFC 49 and RFC 43 installed
below sloped ceiling with a maximun slope of 8/12 (33.7°) pitch.
Table 9 - Application
-*-B
L = THE MAXIMUM LISTED SPRINKLER
SPACING, LENGTH (8'-0' MINIMUM).
L/2 = ONE HALF THE MAXIMUM LISTED
SPRINKLER SPACING (0'-4' MINIMUM).
W = THE MAXIMUM LISTED SPRINKLER
SPACING, WIDTH.
A = 3'-0' MAXIMUM.
9 = RANGE: 2/12 (9.4') < 8 S 8/12 (33.71).
C = 8'-0' MINIMUM.
MULTI -SPRINKLER ARRAINGEMENT FOR SLOPED CEILINGS
auM7 WITH A MAXIMUM SLOPE OF 8/12 (33.71) PITCH.
Fig. 7
K - Factor
Max.
Min.
Sprinkler
Coverplate
Model
(metric)
Spacing
Flow/Pressure
Temperature Rating
Temperature
Ft. x Ft m x m
m I m / si bar
OF °C
Rated°F °C
F1 Res 49Pendent
4.9 69,94
10 x 10 3 x 3
13 49 / 7.0 0,48
155 68
-
F1 Res 49
Reccesed Pendent/F2
4.9 (69,94)
10 x 10 (3 x 3)
13(49) / 7.0(0,48)
155 (68)
F1 Res 49CCP Pendent
4.9 69,94
10 x 10 3 x 3
13 49 / 7.0 0,48
155 68
135 57
RFC49Pendent
4.9 69,94
10 x 10 3 x 3
14 53 / 8.2 0,57
165 74
135 57
RFC43Pendent
4.3(61,4)
10 x 10 3 x 3
18(68) /17.5(l.21)
165(74)
135 57
-*-B
L = THE MAXIMUM LISTED SPRINKLER
SPACING, LENGTH (8'-0' MINIMUM).
L/2 = ONE HALF THE MAXIMUM LISTED
SPRINKLER SPACING (0'-4' MINIMUM).
W = THE MAXIMUM LISTED SPRINKLER
SPACING, WIDTH.
A = 3'-0' MAXIMUM.
9 = RANGE: 2/12 (9.4') < 8 S 8/12 (33.71).
C = 8'-0' MINIMUM.
MULTI -SPRINKLER ARRAINGEMENT FOR SLOPED CEILINGS
auM7 WITH A MAXIMUM SLOPE OF 8/12 (33.71) PITCH.
Fig. 7
tLt
LISTED AREA OF COVERAGE
CORRESPONDS TO CEILING SLO
L = THE MAXIMUM LISTED SPRINKLER
SPACING, LENGTH (10'-0" MAXIMUM)
(8'-0" MINIMUM).
L/2 = ONE HALF THE MAXIMUM LISTED
SPRINKLER SPACING (5'-0" MAXIMUM)
(4'-0"MINIMUM)
W = THE MAXIMUM. LISTED SPRINKLER
SPACING, WIDTH (10'-0")..
A = 3'-0" MAXIMUM.
B = RANGE: ,2/12 (9.4') < B 5 8/12 (33.7').
C = 8'-0" MINIMUM.
035FG08
ELEVATION H2
Fig. 8
13.
L = B + C
D = 8' - 0" MINIMUM
A = 3' - 0" MAXIMUM
Cnstallation Guidelines per UL1626A
1. For systems designed in accordance with NFPA 13,
13D and 13R, where specific UL Listed flows are not
required, consult with the local Authority Having Juris-
diction regarding the number of design sprinklers for
sloped ceilings having pitch greater than (9.4°).
2. Installation of UL Listed residential sprinklers under
sloped ceilings shall be limited to a type of unob-
structed construction consisting of smooth ceilings,
as defined by NFPA 13, having a maximum pitch of
8/12 (33.7).
3. Spacing of residential sprinklers under sloped ceil-
ings is measured along the slope when determining
the distance off of walls and between sprinklers.
4. Measure listed areas of coverage along the sloped
ceiling. The actual floor coverage area will be less
than the listed area.
5. For coverage areas less than the listed coverage area
shown.in Tables 8, use the minimum flow requirement
listed.
6. Minimum spacing between pendent type sprinklers is
8 ft. (2.4 m). Minimum distance from a pendent type
sprinkler and an adjacent wall is 4" (102 mm).
7. Reidential sprinklers located closest to the peak of
the ceiling shall have the deflectors located not more
than 3 ft (1 m) vertically down from the peak. Align de-
flectors parallel with the ceiling slope 1" to 4" (25mm
to 102mm) below the slope ceiling.
8. Hydraulic Requirements:
a. For UL1626A, the number of design sprinklers
shall include up to a maximum of two sprinklers
that requires the greatest hydraulic demand.
9. Glass bulb sprinklers have orange bulb protectors
to minimize bulb damage during shipping, handling
and installation. REMOVE THIS PROTECTION AT THE
TIME THE SPRINKLER SYSTEM IS PLACE IN SER-
VICE FOR FIRE PROTECTION. Removal of the pro-
tectors before this time may leave the bulb vulnerable
to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PRO-
TECTORS BY UNDOING THE CLASP BY HAND. DO
NOT USE TOOLS TO REMOVE THE PROTECTORS.
10. -A maximum distance from the floor to the ceiling peak
of 24 ft.
11. A maximum of two sprinklers installed within 3 ft. verti-
cally of the peak.
12. Installation is for smooth, flat ceilings only that do not
extend into or serve as a ceiling for an upper level
floor in the structure.
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. ® Recycled
® (800) 431-1588 Sales Offices Paper
' (800) 848-6051 Sales Fax Revision lines indicate updated or new data.
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A 11/09 P/N 9999970245