11-0898 (SFD) General SpecificationsMarch 14, 2008 Sprinkler 41a MicrofastHP® QUICK D A A :,SPRINKLERS ESPONSE PENDENT I KJ:N::G* I I I I The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com DESCRIPTION Viking Microfast® and MicrofastHP 1 Quick Response Pendent Sprinklers are small, thermosensitive, glass -bulb spray sprinklers available in several different finishes and temperature ratings and K -Factors to meet design requirements. The special Polyester and Teflon® coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive at- mospheres and are cULus listed as corrosion resistant as indicated in the Approval Chart. (Note: FM Global has no approval classification for Teflon® and Polyester coat- ings as corrosion resistant.) 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV - FM Approved: Class 2020 NYC Approved: Calendar Number 219 -76 -SA and MEA 89-92-E, Volume 16 ABS Certified: Certificate 04-HS407984C-PDA VdS Approved: Certificate G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021 LPC Approved: Ref. No. 096e/03 and 096e/04 CE Certified: Standard EN 12259-1, EC -certificate of conformity 0832 -CPD -2001, 0832 -CPD -2003, 0786 -CPD -40130, and 0786 -CPD -40170 MED Certified: Standard EN 12259-1, EC -certificate of conformity 0832 -MED -1003 and 0832 -MED -1008 NOTE: Other International approval certificates are available upon request. Refer to the Approval Chart on page 41d and Design Criteria on page 41e for cULus and FM approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1987. Minimum Operating Pressure: 7 psi (0.5 bar) Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres- sure (HP) sprinklers can be identified by locating "250" stamped on the deflector. All other Part Nos. not mentioned above are rated to a maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Chart Nominal K -Factor: Refer to the Approval Chart Glass -bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: Refer to the Approval Chart Viking Technical Data may be found on The Viking Corporation's Web site at http://www.vikinggroupinc.com. The Web site may Include a more recent edition of this Technical Data Page. Material Standards: Frame Casting: Brass UNS-C84400 Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 06662B, 066668, 06765B, and 12104. Copper UNS-C19500 for Sprinkler 12282. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Pip Cap Attachment: Brass UNS-C36000 Ejector Spring (for Sprinkler 12104): Stainless Steel Form No. F_081296 Replaces page 41a -f, dated October 12, 2007. (Added LPCB Approval and updated CE Approval for Sprinkler 06666B, Added Dry System note in approval chart for Small Orifice.) Sprinkler 41 b March 14, 2008 -MICROFASTO AND MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com For Teflon® Coated Sprinklers: Belleville Spring -Exposed, Screw -Nickel Plated, Pip Cap -Teflon® Coated For Polyester Coated Sprinklers: Belleville Spring -Exposed Ordering Information: (Also refer to the current Viking price list.) Order Microfast® and MicrofastHP® Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler fin- ish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M -/W, Black Polyester = M -/B, and Black Teflon® = N Temperature Suffix (°F/°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK302 with a 1/2" thread, Brass finish and a 155 *F/68 *C temperature rating = Part No. 06662BAB Available Finishes And Temperature Ratings: Refer to Table 1 Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for coated and/or recessed sprinklers: Part No. 12144W/B** (available since 2003) NOTE: RECESSED PENDENT SPRINKLERS WITH PROTECTIVE CAPS MUST USE WRENCH 12144W/B. **A Y." ratchet is required (not available from Viking). Sprinkler Cabinets: A. Six -head capacity: Part No. 01724A (available since 1971) B. Twelve -head capacity: Part No. 01725A (available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat -sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Microfast® and MicrofastHP® Quick Response Pendent Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. Wrench Flats Protective Sprinkler Cap 10896 m Figure 1: Standard Sprinkler Wrench 10896W/B March 14, 2008 Sprinkler 41 c MICROFASTOAND MicrofastHP® QUICK NIKJ:N7G:4AA A RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI.49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com TABLE Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Qatar CkassBication Temperature Elating' Ceiling Temperature' Ordinary 135 'F (57 °C) 100 'F (38 °C) Orange Ordinary 155'F (68 °C) 100'F (38 °C) Red Intermediate 175'F (79 °C) 150'F (65 °C) Yellow Intermediate 200'F (93 °C) 150'F (65 °C) Green High 286'F (141 °C) 225'F (107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon® Corrosion -Resistant Coatings°: White Polyester, Black Polyester, and Black Teflon® Footnotes The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 9 The corrosion -resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 41d. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and Teflon® coatings. — Sprinkler Wrench 12144W/B)K)K for installing coated and/or recessed pendent sprinklers with protective caps. N Carefully slide the _________; wrench sideways -""- around the protective cap, ensuring engage- `------`' Ment with the sprinkler *A 1/2' ratchet is required wrench flats. (not available from Viking), Sprinkler 41 d March 14, 2008 MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com Approval Chart ___Taue KEY Microfast" and MicrofastHP0Quick Response Pendent Sprinklers r'"is` p p A�Jt �— Esaichea� tlt applk'&ble} Maximum 175 PSI (12 bar) WWP Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K -Factor Length (Refer also to Design Criteria on page 41e.) Part No.1 NPT BSP U.S. metria Inches mm cULus° FMS NYCE VdS LPCB E Standard Orifice 06662B VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 1 AIX, B•1Y I A3X, 133Y I AIX, B1Y A3 A3X, 63Y C3X, E3Y13 C3X, E3Y15 Large Odfice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 AIX, 131Y A2X, 132Y AIX, B1Y — A3X C313 -- 12104 VK352 3/4" 20 mm 8.0 115.2 2-1/4" 58 -- — — G3 — — -- 06765B VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 AIX, B'1Y — AIX, B1Y A3 — — -- Small Orifice" 067181310 VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 AIX, B1Y A2X AIX, B1Y -- -- — -- 06720B10 VK331 1/2" 15 mm 4.2 60.5 2-1/4" 58 AIX, B1Y -- AIX, BIY -- -- — -- 06932B VK331 -- 10 mm 4.2 60.5 2-3/8" 60 -- -- — A3 -- G214 -- Maximum 250 PSI (17 bar) WWP Standard Orifice Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K -Factor Length (Refer also to Design Criteria on page 41e.) Part No' NPT BSP U.S. metric' Inches mm cULu54 FM NYC" VdS LPCB E 12282 VK317 1/2" 15 mm 5.6 80.6 2-1/4" 58 AIX, Ely — I AIX — -- -- -- Maximum 250 PSI (17 bar) WWP Small OrlfIce" 1229010 VK342 1/2" 1 15 mm 2.8 1 40.3 2-3/16" 56 AIX, E1Y — AIX -- -- -- -- Approved Temperature Ratings Approved Escutcheons A- 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), Approved Finishes X - Standard surface -mounted escutcheon or and 286 °F 141 °C B - 135 °F (57 °C), 155 ° (68 °C), 175 °F (79 °C), and 200 °F (93 °C) 1 - Brass, Chrome-Enloy®, White Poly- the Viking Microfase Model F-1 Adjustable C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F ester' ", Black Pol ester' ", and Black y Escutcheon 12 (141 °C) Teflon'" Y - Standard surface -mounted escutcheon or D - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 286 °F 2 - Brass and Chrome-Enloy® the Viking Microfase Model F-1 Adjustable (141 °C 3- Brass, Chrome-Enloy®,White Polyester", Escutcheon12 or recessed with the Viking E - 155 °F 68 -C), 175 °F (79 °C), and 200 °F (93 °C) F - 155 °F (68 C), 175 °F (79 °C), and 286 °F (141 °C) and Black Polyester8 MicromatiO Model E-1 or E-2 Recessed G-155°F(68°C) Escutcheon Footnotes 1 Base part number is shown. For complete part number, refer to Viking's currern price schedule. 2 Metric K -factor measurement shown is when pressure is measured in Bar. When peessure is measured in kPa, divide the metric K -factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Ch eck with the manufacturer for any additional approvals. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. S FM Approved for use only in wet -pipe sprinkler systems (or preaction systems qualifying as wet systems) for protection of occupancies described in the Factory Mutual Engineering and Research Loss Prevention Data Sheets and Technical Advisory Bulletins. "Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219 -76 -SA. cULus Listed as corrosion resistant. 8 Other colors are available on request with the same Listings and Approvals as the standard colors. "Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. 10The sprinkler orifice is bushed. "Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 16. 12The Viking Microfas Model F-1 Adjustable Escutcheon is considered a surface -mounted escutcheon because it does not allow the fusible element of the sprinkler to be recessed behind the face of the wall or ceiling. 13 pE Certified, Standard EN 12259-1, EC 0832 0832 -certificate of conformity -CPD -2001 and -CPD -2003. 14 C.E Certified, Standard EN 12259-1, EC -certificate of conformity 0786 -CPD -40130 and 0786 -CPD -40170. 15 MED Certified, Standard EN 12259-1, EC -certificate of conformity 0832 -MED -1003 and 0832 -MED -1008. 1. March 14, 2008 Sprinkler 41 e The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com DESIGN CRITERIA (Also refer to the Approval Chart on page 41d) cULus Listing Requirements: Microfas& and MicrofastHP® Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. FM Aoproval Reauirements: For installation in accordance with the latest applicable FM Loss Prevention Data Sheets (including 2-8N) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page ORI -3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. 1/2' (15 mm) �\ NPT 15cID►�tBlb\ 2-1/4' 1-5/8' (58 mm) (4 Pendent Sprinkler 06662B (VK302) Ceiling Opening Sizei 2-5/16' (58.7 MM) Minimum 2-1/8' 2-1/2' (63.5 mm) maximum (54 Mrs) 1-31/4' r N NI'L (44.5 mm) 2' 1-1/2' (38.1 mm) (Maxi um Minimum MQXII`'1u1`'1 Installed with a standard 1/8' surface - mounted escutcheon, Installed with a Microfast Model F-1 Adjustable Escutcheon Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon Sprinkler 41 f March 14, 2008 MICROFASTO AND MicrofastHP® QUICK RESPONSE PENDENT I KJ 7N:G4] SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com 2-1/8' (54 mm) Ceiling Opening Size: 2-1/8' 2-5/16' (58.7 mm) minimum (54 mm) 2-1/2' (63.5 mm) -maximum 1-3/4' (44,5 mm) Maximum 1-1/8' (28,6 mm) Minimum t 2- (50.8 mm) Maximum 1-1/8'. (28.6 mm) Minimum f Installed with a Micromatic Model. E-1 Recessed Escutcheon Installed with a thread on Model E-2 Recessed Escutcheon Figure 4: Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons Form No. F_081296 Replaces page 41a -f, dated October 12, 2007. (Added LPCB Approval and updated CE Approval for Sprinkler 0666613, Added Dry System note in approval chart for Small Orifice.) January 6, 2010 Sprinkler 145h FREEDOM® RESIDENTIAL NJ1KJ7W74J A A A FLUSH PENDENT SPRINKLER VK476 (K4.9) The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Freedom® Residential Flush Pendent Sprinkler VK476 is a small high -sensi- tivity fusible element residential sprinkler designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired. The orifice design, with a K -Factor of 4.9 (70.6 metric*), allows the sprinkler's efficient use of available water supplies for the hydraulically designed fire -protection system. The fast response operating element and special deflector combine speed of operation and areas of coverage to meet residential sprinkler standards. The two-piece design of the sprinkler and ceiling ring allows installation and testing of the sprinkler prior to ceiling installation. The ceiling ring allows for up to 5/8" (16 mm) of vertical adjustment and can be removed and re -installed, allowing access above removable ceiling panels without shutting down the sprinkler system and removing the sprinkler. 2. LISTINGS AND APPROVALS cULus Listed: Category VKKW Refer to the Approval Chart and Design Criteria on pages 145j -k for cULus Listing requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 2009. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart. The Viking Corporation's Web site at Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically http://www.vikinggroupinc.com. to 500 psi (34.5 bar). The Web site may include a more recent Thread size: 1/2" (15 mm) NPT edition of this Technical Data Page. Nominal K -Factor: 4.9 U.S. (70.6 metric*) *Metric Mactor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0. Overall Length: 2-1/8" (54 mm) Material Standards: Sprinkler Body and Inlet: QM Brass Deflector Assembly: Copper UNS-C51000 and Brass UNS-C36000 Pin Assembly: Stainless Steel UNS-S30200 and C23000 Seat Assembly: Brass UNS-C31400 or UNS-C31600 Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Fusible Element Assembly: Beryllium Nickel and Eutectic Solder Element Cover: Copper UNS-C11000 Lever Bar Assembly: Copper Alloy UNS-C72500 and Brass UNS-C36000 Lever Arm: Stainless Steel UNS-S31600 Element Assembly: Copper UNS-C11000 and Nickel Alloy Ceiling Ring: Cold Rolled Steel UNS-Gl0080 Ordering Information: (Also refer to the current Viking price list.) Viking Freedom® Residential Flush Pendent Sprinkler VK476 and Ceiling Ring: Part No. 15630MC/- (includes a 165 *F (74 °C) rated sprinkler with a protective plastic cap covering the unit, and a ceiling ring). Specify finish of the sprinkler and ceiling ring by adding the appropriate suffix for the finish to the base part number: Finish Suffix: Wood Beam Finish = G, Painted White = W, Painted Black = B For example, sprinkler VK476 with a Wood Beam Finish = 15630MC/G. Available Finishes And Temperature Ratings: Refer to Table 1 Form No. F120608 Replaces page 145h -m, dated Sept. 3, 2009. — (Revised sloped ceiling listings.) Sprinkler 145i January 6, 2010 FREEDOM® RESIDENTIAL • FLUSH PENDENT SPRINKLER VK476 (K4.9) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrench": Heavy Duty Wrench Part No. 15209W/R (available since 2009) -Requires a Y.' ratchet (not available from Viking). Sprinkler Cabinet: Part No. 01731A, Capacity: five (5) sprinklers (available since 1971) Replacement Ceiling Ring (3" diameter): Base Part No. 15618M/ - Specify finish of the ceiling ring by adding the appropriate suffix for the finish to the base part number: Finish Suffix: Wood Beam Finish = G, Painted White = W, Painted Black = B For example, ceiling ring 15618 with a Wood Beam Finish = 15618M/G. 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, when the fusible element reach- es its operating temperature, the element cover, fusible element and lever assembly fall away. The deflector is suspended below the ceiling. Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pressure at the sprin- kler to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Mainte- nance requirements. 7. AVAILABILITY Viking Sprinkler VK476 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. 1-1/2' (38 mm) Diameter Ceiling -\e\ Opening Required I_ Flush Pendent VK476 Sprinkler Body with Protective Cap Sprinkler Wrench 15209W/Raa must be used for installing Sprinkler VK476 ■*A 1/2' ratchet Is required <not avallable from Viking.) Step 1t Slide the wrench over the sprinkler and protective cap. Sprinkler Wrench Flats Step 2: Carefully press the wrench upward and turn slightly to ensure engagement with the sprinkler wrench flats. Figure 1: Sprinkler Installation and Correct Use of Wrench TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Ceiling Ring Classification Temperature Rating' Calling Temperature2 Bass Part Number' Ordinary 165 'F (74 °C) 100 °F (38 °C) 15618 Finishes: Wood Beam Finish, Painted White, or Painted Black Footnotes ' The sprinkler temperature rating is stamped on the sprinkler inlet. s Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 Part number shown is the base part number for replacement ceiling rings. For complete part number, refer to current Viking price list schedule. January 6, 2010 Sprinkler 145j FREEDOM® RESIDENTIAL NIKJNG* • FLUSH PENDENT SPRINKLER VK476 (K4.9) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval Chart sprinkterTernw - Residential Flush Pendent Sprinkler VK476 Cow PlaAsTemperaturaRatMg For system designed to NFPA 13R or NFPA 13R. re ' K EY ' For systems designed to NFPA 13, refer to the design arteria on page 145k. Sprinkler Base NPT Thread Size Nominal K -Factor Maximum Water Overall Length Part Number' SIN Working Pressure Inches mm U.S. T metric' Inches mm 15630 VK476 1/2 15 4.9 70.6 175 psi (12 bar) 2-1/8" 54 Listings and Approvals3,1 Maximum Areas of Coverages Minimum Water Supply Requirements (Refer also to Design Criteria on page 145k.) cULus° INYC NSF Installed below smooth, flat, horizontal ceilings and horizontal ceilings with beams. Includes ceilings with slopes up to and including 2/12 (9.5°). 16 ft. x 16 ft. (4.9 m x 4.9 m) 13 gpm @ 7.0 psi (49.2 Umin @ 0.48 bar) Al -- - 18ft. x18ft. (5.5mx5.5m) 17 gpm@ 12 psi (64.4 Umin @ 0.83 bar) Al -- - 20 ft. x 20 ft. (6.1 m x 6.1 m) 21 gpm @ 18.4 psi (79.5 Umin @ 1.27 bar) Al -- -- Installed below ceilings with slopes' up to and including a 4/12 (18.4°) pitch. Refer to Figure 5 on page 145m. UL NYC NSF 16 ft. x 16 ft. (4.9 m x 4.9 m) 18 gpm @ 13.5 psi (68.1 Umin @ 0.93 bar) Al -- - 18 ft. x 18 ft. (5.5 m x 5.5 m) 20 gpm @ 16.7 psi (75.7 Umin @ 1.15 bar) Al -- - 20 ft. x 20 ft. (6.1 m x 6.1 m) 24 gpm @ 24 psi (90.8 Umin @ 1.65 bar) Al -- - Sprinkler Temperature Rating Finishes 1 A - 165 -F (74 'C) 1 - Wood Beam Finish, Painted White, and Painted Blacks Footnotes ' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K -factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0. 3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. Listed by Underwriter's Laboratories for use in the U.S. and Canada. 5 Listings are for residential occupancies with smooth, flat, horizontal ceilings or horizontal ceilings with beams. Includes ceilings with slopes up to and including a 2/12 (9.5°) pitch. (For beam ceiling design criteria, refer to Beam Ceiling Guidelines and Figures 3 through 4D on pages 1451-m). s For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement' for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the "Minimum Water Supply Requirement' used. ' Areas under sloped ceilings must be measured along the ceiling slope. Actual floor coverage in the horizontal plane under sloped ceilings will be less than the listed area of coverage. s Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. NOTE: Custom colors are indicated on a label on the sprinkler body. 1/2' (15 mm� NPT 1-5/8' (41 mm) Maximum 1 :::. =" 1 2 5/8' C16 m'1) C25.4 mm) 2-1/8' (12.7 mm) Vertical Adjustment _ __ M um (54 mm) 3' (76,2 mm) 1 (28.5 mm) NOTEi Upon sprinkler activatlon, the deflector descends to approximately 1/2' (12 mm) below the sprinkler body. Figure 2: Sprinkler Dimensions and Ceiling Ring Installation Sprinkler 145k January � � rY 6, 2010 FREEDOM® RESIDENTIAL IK • • FLUSH PENDENT - .JN SPRINKLER VK476 (K4:9) . The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone :'269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com _ ��� CRITERIA r (Ads o refer -W the Approval ;Chart on paw 1459.) ` cULus Listing Reauirements: _ When using Viking Residential Flush Pendent Sprinkler VK476 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of coverage and minimum water supply requirements showrnin' the Approval Chart on page 145j.` ' For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in the Approval Charfon data page 145j for NFPA 13D and NFPA 13R applications for each listed area of coverage, o • Calculated based on a'minimum discharge of 0.1 gpm/sq. ft. over the "design area" in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13. •. Minimum distance between residential sprinklers: 8 ft. (2.4 m). BEAM CEILING,GUIDELINES cULas Llsted for Installation In residential occdpancfes-with beam ceilings (W#h horizc rital ceilings only), Refer to,the rovat Chart for rtinkler' areas of coven and li` drau c design. Sprinkler Locatlon: Locate sprinklers on the underside of the beams (not in the bays or pockets formed by the beams). Refer to Figure 3. The vertical distance from the sprinkler deflector to the bottom of the primary beam must be between 1/2 and 1-1/8" (12.7 to 28.5 mm). The horizontal distance from the centerline of the sprinkler to the primary beam cannot be more than 2" (51 mm) (Figure•3). NOTE: Consult with a structural engineer before drilling beams to allow the installation of sprinkler drops. Where drilling is not permitted, sprinkler posi- tion requirements allow for the sprinkler drop to be placed adjacent to the primary beam. Beam Position: Directly attached to the underside of a combustible or non-combustible smooth ceiling of any height. Beam Size and Shape (Cross section): . • Depth: Maximum 14" (355 mm) for primary beams. Secondary beam depth cannot be greater than the primary beam. Width: Unlimited. - Beam Shape: Rectangular to circular. - Beam Types: Combustible or non-combustible; solid surface, solid or hollow core. Beam Spacing: t A. For primary beams, the distance from the wall to the center of the nearest primary beam must be at least 3'-4" (1.0 m), and not more than one-half the listed sprinkler spacing. Note: Sprinklers may not be required to be located in the first beam nearest_ the wall. Center -to -center distance between primary beams is to be a maximum of 20'-0" (6.1 m). Refer to Figure 4A. B. When beam pockets created by the primary beams exceed 20'-0" (6.1 m) in length, secondary beams are required as follows (also refer to Figure 4B): 1. Secondary beam depth must be equal to primary beam depth. 2. Secondary beams must be placed so that the bays formed by the primary beams do not exceed 20'-0" (6,1 m) in length. C. When primary beam spans do not exceed 20'-0" (6.1 m), secondary beams (not required) may have any distance from wall to nearest secondary '- beam and any distance center to center between secondary beams. Refer to Figure 4C. Lintels: Must be present over doorways exiting the compartment. Lintel height must be at least 8" (203 mm), or at least the depth of the primary beams, whichever is greater. Beam and Soffit Arrangements: If a soffit is installed, beams may be arranged within the soffit. The cross section of the soffit may be any size, pro- vided it does not create an obstruction to water distribution per the obstruction rules of NFPA 13 for residential sprinklers. Where there is a soffit, beam spacing from the wall is to be measured from the face of the soffit rather than the wall. Refer to Figure 4D. NOTE: The sprinkler area of coverage is to be measured from the wall. Definitions: r ' • • Primary beams: The main beams that run primarily in one direction. • Secondary beams: The beams that run perpendicular to the main beams. IMPORTANT: Always refer toIBulletin Form No. F 091699 - Care and Handling of Sprinklers. Also refer to pages RES1-17 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition•of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction. January 6, 2010 Sprinkler 1451 FREEDOM® RESIDENTIAL FLUSH PENDENT SPRINKLER VK476 (K4.9) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com .............. ....... ....... .............. ....... ....... ....... ....... 1/2' (12,mm) Min. ........ Srinkler 1-1/8' 12e,5 mm) Max. p Maximum 1/2 Beam Sprinkler VK476 Width Plus 2' (50.8 mm) VK476 Figure 3: Sprinkler Positioniig Under Primary Beams Cellinc We imary eam Prima Beai All dimensions are measured to wall faces and to centerlines of beams. A = Distance from wall to nearest primary beam Minimum 3 ft 4 In (1.0 m). Maxlmumi No more than 1/2 listed sprinkler spacing, B = Spacing between primary beams, 20 ft (6,1 m) maximum, C = Beam depth, 14' (355 mm) maximum. D = Beam spam 20 f t (6.1 m) maximum. Figure 4A: Primary Beam Spans up to 20'-0" (6.1 m) idary Xm All dimensions are measured to wall faces and to centerlines of beams. A = Distance from wall to nearest primary beam+ Minimum 3 ft 4 In (1.0 m). Maximum, No more than 1/2 listed sprinkler spacing. B = Spacing between primary beams: 20 ft (6.1 m) maximum, = Beam depths 14' (355 mm) maximum. D = 20 ft (6.1 m) maximum for secondary beams that are to be equal in depth to primary beams and that are required so that primary beam pockets do not exceed 20 ft (6.1 m). Figure 4113: Primary Beam Spans over 20'-0" (6.1 m) L, Sprinkler 145m January 6, 2010 FREEDOM® RESIDENTIAL FLUSH PENDENT SPRINKLER VK476 (K4.9) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com W ondary Beare ary Beam* Celllnc All dimensions are measured to wall faces and to centerlines of beams, Com partme,,. Walls A = Distance from wall to nearest primary beams Minimum 3 f t 4 In M0 m). Maximums No more than 112 listed sprinkler spacing. B = Spacing between primary beamst 20 ft (61 m) maximum, C = Beam depths 14' (355 mm) maximum. Note, Secondary beam depth cannot be greater than the primary beam. D = Any distance for secondary beams, unless primary . beam spans exceed 20 ft y6,1 m). x Refer to Figure 4B for primary beam spans exceeding 20 ft (61 m). Figure 4C: Combination of Primary and Secondary Beams Maxims ceilini slope = � (18.4° Refer to the Apprc Chart for listed areas of coverag Beare Secondary Beam Face of Soffit Bottom of Soffit D = Dimensions shown In Figures 4A, 4B, and 4C, except measurements are taken from the face of the soffit Instead of from the wall surface, NOTE: The sprinkler area of coverage Is to be measured from the wall. Figure 4D: Beam and Soffit Arrangements Note 1 below. Notes: 1. Listed areas of coverage correspond to areas measured along ceiling slope. (For sloped ceiling installations, ac- tual floor coverage in the horizontal plane under sloped ceilings will be less than the listed area.) 2. Actual installations may require multiple sprinklers. A single sprinkler installation has been shown for clarity. 3. For"cathedral" ceiling applications, install sprinklers in a symmetrical mirror-image of Figure 5. Figure 5: Installation Instructions - Sloped Ceilings Form No. F120608 Replaces page 145h -m, dated Sept. 3, 2009. (Revised sloped ceiling listings.) Technical Features • Sizes Available (Nominal): 3/4" (DN20) through 3" (DN80) pipe diameters, c @us with a Standard Dimension Ratio (SDR) of 13.5 as specified in ASTM F442. LISTED • Environmental Specifications: Indoor use only. FM Maximum Ambient Temperature: 150°F (65°U inch metric inch mm. APPROVED • Hazen -Williams C Value: 150 NSF • Pressure Data: Working Pressure: 175 PSI (12.1 bar) at 150°F (65°0 • Specifications: • Meets NFPA 13R and 13D standards for residential occupancies as well as DN20 NFPA 13 standards for light hazard occupancies. 0.874 / 22,199 • Pipe meets or exceeds ASTM F442. 15/4,6 • Certified by NSF International for potable water services. 34PIPE • CPVC pipe from Viking Plastics use compound cell class 23547 DN25 (demonstrated highest structural properties). 1.101 / 27,965 • cULus Listed, FM Approved, New York City (MEA) Approved, LPCB Approved. 15/4,6 CPVC Pipe Physical Data 1 PIPE Nominal Pipe Size Actual Outside Diameter Average I D Weight per 15' (4.6m) : Length Approvals Part Number E inch metric inch mm. (inch / mm) - length Ob dkg) _. (ft / m) 3/4" DN20 1.050 26,670 0.874 / 22,199 2.52 / 1,14 15/4,6 cULus, FM, 34PIPE I" DN25 1.315 33,401 1.101 / 27,965 3.93/ 1,78 15/4,6 NSF 1 PIPE 1 1/4' DN32 1.660 42,164 1.394 / 35,408 6.27/2,84 15/4,6 114PIPE 1 12" DN40 1.900 48,260 1.598 / 40,589 8.22/3,73 15/4,6 112PIPE 2" DN50 2.375 60,325 2.003 / 50,876 12.89/5.85 15/4,6 2PIPE 212" DN65 2.875 73,000 2.423 / 61,500 18.86/8,55 15/4,6 212PIPE 3' DN80 3.500 88,900 2.950 / 74,900 28.01 / 12,71 15/4,6 3PIPE Nominal Pipe Size Actual Outside Diameter Average I.D. Weight per 10' (3.05ni) Length Approvals Part Number j inch metric Ind( mm Unc / mm) length (Ib /kg) (ft / m) 34" DN20 1.050 26,670 0.874 / 22,199 1.68/0,76 10/3,05 cULus, FM, 34PIPEIO 1" DN25 1.315 33,401 1.101 / 27,965 2.62/1,19 1013,05 NSF 1 PIPE10 1 1/4" DN32 1.660 42,164 1.394 / 35,408 4.18/1,90 10/3,05 114PIPEIO 1 12" DN40 1.900 48,260 1.598 / 40,589 5.48/2,49 10/3,05 112PIPE10 2' DN50 2.375 60,325 2.003 / 50,876 8.59/3,90 10/3,05 2PIPE10 2 12' DN65 2.875 73,000 2.423 / 61,500 12.57/5,70 10/3,05 212PIPEIO 3' DN80 3.500 88,900 2.950 / 74,900 18.67/8,47 10/3,05 3PIPE10 NOTE: CPVC Pipe is produced in SDR 13.5 Dimensions in accordance with ASTM F442. Standard Dimension Ratio is the ratio of the outside pipe diameter to the wall thickness of the pipe. IMPORTANT: Installers should receive thorough hands-on training in the proper methods of assembly and installation of CPVC products. Specifications subject to change without notice. 81aseMaster® is a registered trademark of Lubrizol. Trusted above aII.Tm N I KJ W4j 0 CPVC Pipe Product Specifications Corrosion resistant CPUC fire sprinkler pipe, when installed in strict accordance with the manufacturers design and installation instructions, is UL and c -UL Listed by Underwriters Laboratories for use in the following: • Meets NFPA 13R and 13D standards for residential occupancies as well as NFPA 13 standards for light hazard occupancies. • Residential occupancies up to and including four stories in height as defined by NFPA 13R. • Residential occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings, NFPAI3D. • Installation of private fire service mains and their appurtenances, NFPA 24. CPVC fire sprinkler pipe from Viking Plastics shall be employed in wet pipe systems only and are not listed for outdoor use. CPVC pipe must never be used in a system using compressed air or other gases. CPVC pipe from Viking Plastics also carries the following enhanced listings and approvals: • According to UL Listing • Can be Flush at return air plenums • Mechanical cut -in tee & crosses concealed with Grinnell figure 730 fittings • Mechanical cut -in tee & crosses exposed with Grinnell figure 730 fittings • Exposed system risers NFPA 13D, 13R • Exposed basement NFPA 13D (solid wood joist) • Extended coverage (exposed) • 20' spacing on pendent in lieu of 15' • 18' spacing on sidewall in lieu of 14' • Use with combustible concealed sprinklers • Tyco attic sprinkler head (to protect the floor below) • Tyco attic sprinkler head with wet system piping (feed main and ridge installation) New and enhanced listings and approvals are being pursued. Always check with the appropriate Listing and Approval agency for details on current listing parameters. CPVC pipe also meets all applicable standards for pressure rated application as required in ANSI -NSF Standard 14 and complies with ANSI -NSF Standard 61 for health effects and are marked with the NSF-pw end use marking. All CPVC fire sprinkler pipe shall be Listed by Underwriters Laboratories for wet pipe systems, and shall carry a rated working pressure of 175 psi @ 150°F (12 bar @ 65.5°0. The FM Approval is limited to use in wet pipe fire protection sprinkler systems for light hazard occupancies in both concealed and exposed applications with certain restrictions. Piping must always be installed in strict accordance to the manufacturer's DESIGN AND INSTALLATION GUIDE, including product storage and handling, joining methods, supporting and bracing, expansion and contraction allowance and testing, etc National Fire Protection Association (NFPA) Standards 13, 13D, and 13R must be referenced for design and installation requirements in conjunction with the installation instructions. Specifications subject to change without notice. • Exposed sidewall sprinkler listing for exposed pipe & fittings • 24' extended coverage sidewall sprinkler, 12" drop, 155T sprinkler head • 18' extended coverage sidewall sprinkler, 12" drop, 165T sprinkler head • 16' extended coverage sidewall sprinkler, 12" drop, 175°F sprinkler head • 14' standard coverage sidewall sprinkler, 12" drop, 200T sprinkler head • Factory Mutual Approved' • Factory Mutual Approval exposed • Factory Mutual Approval above drop-in ceilings • Factory Mutual Approval exposed w/Soffa-Steel soffjting covering system All CPVC fire sprinkler pipe from Viking Plastics is manufactured in the USA. All CPVC pipe shall be packaged immediately after its manufacture to prevent damage and shall be stored indoors after production, at the manufacturing site, until shipped from the factory. The pipe shall bear the logo of the listing agencies, and shall carry the National Sanitation Foundation (NSF) seal of approval for potable water applications. CPVC products are intended for use in areas where the maximum ambient temperature does not exceed 150°F (65.5.0. If the ambient temperature is expected to exceed this limitation, refer to the manufacturers DESIGN AND INSTALLATION GUIDE for additional information on methods to reduce the pipe exposure temperatures. CPVC pipe is not intended to be installed in outdoor applications. CPVC pipe is intended to be used in wet pipe systems only and have not been investigated for use in dry pipe systems. Special installation and design criteria relative to pipe hanger spacings, piping and sprinkler restraint, sprinkler temperature rating, piping locations, testing procedures and friction loss characteristics are specified in the manufacturers installation instructions provided with the pipe. The manufacturers installation instructions should be reviewed and the Authority Having Jurisdiction consulted before installation. Trusted above all."m VIKING® August 13, 2009 Sprinkler 147u FREEDOM® RESIDENTIAL • • • CONCEALED PENDENT SPRINKLER VK457 (K4.9) The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com DESCRIPTION Viking Freedom® Residential Concealed Pendent Sprinkler VK457 is a small high - sensitivity solder link and lever residential sprinkler designed for installation on con- cealed pipe systems where the appearance of a smooth ceiling is desired. The orifice design, with a K -Factor of 4.9 (70.6 metric*), allows the sprinkler's efficient use of available water supplies for the hydraulically designed fire -protection system. The fast response operating element and special deflector combine speed of operation and areas of coverage to meet residential sprinkler standards. The sprinkler is pre -assembled with a threaded adapter for installation with a low - profile small -diameter cover assembly installed flush to the ceiling. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The "push -on", "thread -off" design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied, while also providing up to Yi' (12.7 mm) of vertical adjustment. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. 2. LISTINGS AND APPROVALS cULus Listed: Category VKKW Refer to the Approval Chart on page 147w and Design Criteria on page 147x for cULus Listing requirements that must be followed. 3. TECHNICAL DATA Specifications: Viking Technical Data may be found on Available since 2008. The Viking Corporation's Web site at Minimum Operating Pressure: Refer to the Approval Chart. Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically hteb site may include aimore r. to 500 psi (34.5 bar). The Web site may include a more recent Thread size: 1/2" (15 mm) NPT edition of this Technical Data Page. Nominal K -Factor: 4.9 U.S. (70.6 metric`) *Metric K -factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0. Material Standards: Sprinkler Body: Brass UNS-C84400 Deflector: Copper UNS-C51000 Deflector Pins: Stainless Steel UNS-S30200 Button: Brass UNS-C36000 Seat Assembly: Brass UNS-C31600 Compression Screw: Brass UNS-C36000 Fusible Element Assembly: Beryllium Nickel, coated with black acrylic paint Levers: Stainless Steel UNS-S31600 Lever Bar: Copper Alloy UNS-C72500 Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating Shipping Cap: Polyethylene Cover Plate Materials: Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800 Spring: Beryllium Nickel Solder: Eutectic Form No. F_072607 Replaces page 147u -z, issued October 31, 2008. (Revised minimum and maximum dimensions in Figure 2.) Sprinkler 147v August 13, 2009 FREEDOM® RESIDENTIAL • CONCEALED PENDENT SPRINKLER VK457 (K4.9) The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com Ordering Information: (Also refer to the current Viking price list.) Viking Freedom® Residential Concealed Pendent Sprinkler VK457 and Cover Plate Assembly must be ordered separately: Sprinkler: Part No. 14694AC (includes a 165 °F (74 °C) rated sprinkler with a protective plastic cap covering the unit). Cover Plate Assembly: Base Part No. 13750 (2-3/4" diameter), Base Part No. 14934 (3-5/16" diameter), or Base Part No. 15394 (square cover plate, 3-5/16" diameter) Specify finish and temperature rating of the cover plate assembly by first adding the appropriate suffix for the finish and then the appropriate suffix for the cover temperature rating to the base part number: Finish Suffix: Polished Chrome = F, Painted White = M-/SW1004, Painted Ivory = M-/SW1634, Painted Black = M-/SW1007 Temperature Suffix (°F/°C): 135°/57° =A For example, cover 13750 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13750FA. Available Finishes And Temperature Ratings: Refer to Table 1 Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches": A. Heavy Duty Part No. 13623W/B (available since 2006), or B. Head Cabinet Wrench Part No. 13619*** (available since 2006) C. Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007) D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007) **Requires a 'W ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets. Sprinkler Cabinet: Part No. 01731A, Capacity: five (5) sprinklers (available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches, releasing the deflector. Continued heating of the exposed sprinkler causes the fusible element to disengage releasing the sealing assembly. Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pressure at the sprinkler to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Sprinkler Model VK457 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Spt1»It r illaximurtr Umpersture Rollittg, $444Ir Govt r Amblent etNnp of the C Clow IP100 Cover Plate,Pisibi Ili Pont TemperatureTen�eratiue RatMg' Part Numbee base Pout Numbers Classlfication Temperature' Assembly (Required) Number' Ordinary 165 °F (74 °C) 100 °F (38 °C) 135 °F (57 °C) 13750 14934 15394 Cover Plate Finishes: Polished Chrome, Painted White, Painted Ivory, or Painted Black Footnotes ' The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. August 13, 2009 Sprinkler 147w FREEDOM® RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com _--- __ Approval Chart itpslderttlai Concealed Pendent Sprinkler VK457 m� For system designed to NFPA 130 or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria on page 147x. Sprinkler Base NPT Thread Size Nominal K -Factor Maximum Water Part Number' SIN Working Pressure Inches mm U.S. metria 14694A VK457 1/2 15 4.9 70.6 175 psi (12 bar) Listings and Approvals' Maximum Areas of Coverages Minimum Water Supply Requirements' (Refer also to Design Criteria on page 147x.) cULus° NYC NSP Installed below smooth, flat, horizontal ceilings, including ceilings* with slopes up to and Including 2/12 (9.5°). 12 ft. x12ft. (3.7mx3.7m) 13 gpm@ 7.0 psi (49.2 Umin @ 0.48 bar) AX1 -- AX1 14 ft. x 14 ft. (4.3 m x 4.3 m) 13 gpm@ 7.0 psi (49.2 Umin @ 0.48 bar) AXI -- AX1 16 ft. x 16 ft. (4.9 m x 4.9 m) 13 gpm@ 7.0 psi (49.2 Umin @ 0.48 bar) AX1 -- AXI 18 ft. x 18 ft. (5.5 m x 5.5 m) 17 gpm @ 12.0 psi (64.4 Umin @ 0.83 bar) AX1 -- AXI 20 ft. x 20 ft. (6.1 m x 6.1 m) 20 gpm @ 16.7 psi (75.7 Umin @ 1.15 bar) AX1 -- AX1 Installed below ceilings with slopese up to and Including a 8/12 (33.7°) pitch. Refer to Figure 5 on page 147z. UL NYC NSP 16 ft. x 16 ft. (4.9 m x 4.9 m) 26 gpm @ 28.2 psi (98.4 Umin @ 1.94 bar) AX1 -- AX1 18 ft. x 18 ft. (5.5 m x 5.5 m) 31 gpm @ 40.0 psi (117.3 Umin @ 2.76 bar) AX1 -- AXI 20 ft. x 20 ft. (6.1 m x 6.1 m) 31 gpm @ 40.0 psi (117.3 L/min @ 2.76 bar) AX1 -- AXI Cover Temperature Rating Cover Plate Finishes Sprinkler Temperature Rating X - 135 °F (57 °C) cover 137501, 14934' (large diameter), 1 - Polished Chrome, Painted White, Painted Ivory, A - 165 °F (74 °C) or 15394 (square cover plate) and Painted Black8 Footnotes ' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K -factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K -factor shown by 10.0. 3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. ° Listed by Underwriter's Laboratories for use in the U.S. and Canada. s For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement" for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum Water Supply Requirement' used. 8 Areas under sloped ceilings must be measured along the ceiling slope. Actual floor coverage in the horizontal plane under sloped ceilings will be less than the listed area of coverage. ' Tested and Certified by NSF (National Sanitation Foundation) to NSF/ANSI Standard 61, Drinking Water System Components. 8 Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3. Sprinkler 147x August 13, 2009 FREEDOM® RESIDENTIAL • CONCEALED PENDENT SPRINKLER VK457 (K4.9) -NlKjw4j The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com DESIGN CRITERIA (Also refer to the Approval Chad on page 147w.) cULus Listing Requirements: When using Viking Residential Concealed Pendent Sprinkler VK457 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover- age and minimum water supply requirements shown in the Approval Chart on page 147w. For systems designed to NFPA 13 The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in the Approval Chart on data page 147w for NFPA 13D and NFPA 13R applications for each listed area of coverage, 2E • Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the "design area" in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13. • Minimum distance between residential sprinklers: 8 ft. (2.4 m). NOTE: Concealed sprinklers must be Installed In neutral or negative pressure plenums only. IMPORTANT. Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to pages RES1-17 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction. Sprinkler and Adapter Assembly (Protective Cap is removed for installation --use Wrench 13619)9)K) Step 11 Carefully sl wrench sideways a the deflector anc )KeA 1/2' ratchet is required (not available from Viking), M 2-1/4' (57.2 mm) diameter opening Is required In the ceiling, — Sprinkler Wrench (Part No. 13623W/Bw* Is shown) Step 2: Carefully press the wrench upward and turn slightly to ensure engagement with sprinkler wrench flats, Figure 1: Sprinkler Installation and Correct Use of Wrenches August 13, 2009 Sprinkler 147y FREEDOM® RESIDENTIAL • CONCEALED PENDENT SPRINKLER VK457 (K4.9) The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com 1/2' (15 mm) NPT 2-1/8' '(54 mm) Note: Upon sprinkler activation, the deflector descends to approximately 13/16' (20.6 mm) below the sprinkler body, 2-1/16' (52 mm) Minimum Figure 2: Sprinkler Dimensions and Cover Installation CUSTp�\ Q rZ v o; o r— o v VIKING Identification of .Custom Paint Color: All custom color painted cover plates will have an identifying label affixed to the inside of the cover that indicates custom color and will have a representative sample (a paint dot) of the paint on the label, Figure 3: Identification of Custom Paint Color for Concealed Covers 2-3/4' (70 mm) or 3-5/16' (84,1 mm) D❑ NOT PAINT �3-5/16' (84.1 Mrs) ►� Figure 4: Square Cover Assembly 15394 Sprinkler 147z August 13, 2009 The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com MaximL ceilinc slope = F (33.7 Refer to the Appro Chart for listed areas of coverag Note 1 below. Notes: 1. Listed areas of coverage corre- spond to areas measured along ceiling slope. (For sloped ceiling installations, actual floor cover- age in the horizontal plane under sloped ceilings will be less than % the listed area.) 2. Actual installations may require multiple sprinklers. A single sprin- kler installation has been shown for clarity. 3. For "cathedral' ceiling applica- tions, install sprinklers in a sym- metrical mirror-image of Figure 5. Figure 5: Installation Instructions - Sloped Ceilings Form No. F_072607 Replaces page 147u -z, issued October 31, 2008. (Revised minimum and maximum dimensions in Figure 2.) Rel-labila Guidelines for Listed Residential Sprinkler installations below Sloped Ceilings The installation guidelines cover Residential Sprinkler Models: F1 Res 49 Pendent F1 Res 49 Recessed Pendent/F2 F1 Res 58 Pendent F1 Res 58 Recessed Pendent/172 F1 Res 44 HSW F1 Res 44 Recessed HSW/F2 F1 Res 49 CCP F1 Res 58 CCP RFC 43 Flat Concealed RFC 49 Flat Concealed Listings & Approvals 1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) 2. NYC MEA 258-93-E UL Listing Category Residential Automatic Sprinkler UL Guide Number VKKW Patents: US Patent number 6,516,893 Model F1 Res 49 Product Description for F1 Res Sprinklers Model F1 Res Pendent sprinklers are fast response sprinklers combining excellent durability, high sensitivity glass -bulb and low profile decorative design. The F1 Res Horizontal Sidewall sprinklers are equally attractive when above ceiling piping cannot be used. The 3mm glass -bulb pendent sprinklers, with a K Factor of 4.9 & 5.8 for pendent and 4.4 for horizontal sidewall, permit the efficient use of residential water supplies for sprinkler coverage in residential fire protection design. The low flow F1 Res sprinklers are specially engineered for fast thermal response to meet the sensitive fire protec- tion application needs of the latest residential market stan- dards (UL 1626 Standard *). Upon fire conditions, rising heat causes a sprinkler's heat -sensitive glass -bulb to shat- ter, releasing the waterway for water flow onto the deflec- tor, evenly distributing the discharged water to control a fire. Bulletin 035 Rev. H Residential Sprinkler For Sloped Ceilings F1 Res 49 & 58 Pendent F1 Res 44 HSW F1 Res 49 & 58 CCP Pendent mr-u 41j b& HrIL. 4y * Effective date July 12, 2002 F1 Res 49 & 58 Recessed Pendent / F2 r I ries 44 Recessed HSW/F2 RFC 43 & RFC 49 The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Product Description for RFC 43 & RFC 49 Model RFC43 & RFC49 Concealed Residential Sprin- klers are fast response residential fusible solder link au- tomatic sprinklers. Residential sprinklers differ from stan- dard'sprinklers primarily in their response time and water distribution patterns. Model RFC43 & RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler deflector. Resi- dential distribution patterns are higher and generally con- tain a finer droplet size than standard sprinkler patterns. The combination of speed of operation and high dis- charge pattern required for residential sprinklers has dem- onstrated, in fire testing, an ability for controlling residen- tial fires, and thereby providing significant evacuation time for occupants. The RFC43 & RFC49 Sprinkler provides the best form of fire protection by combining an attractive appearance and 1/2" (13mm) of cover adjustment for ease of installa- tion. The small diameter cover plate is easily and posi- tively attached and blends into the ceiling, concealing the most dependable fire protection available, an automatic sprinkler system. The RFC43 & RFC49 are UL Listed Residential Sprinkler to be installed in the residential portions of any occupancy in accordance with NFPA 13,13R, & 13D. The RFC43 & RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assem- bly can be adjusted without tools to fit accurately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly. 2. Technical Data (F1 Res Sprinklers): e Thermal Sensor: Nominal 3mm glass -bulb Sprinkler Frame: Brass Casting • Sprinkler Pressure Rating : 175 psi Factory Hydrostatically Tested to 500 psi • Thread Size : 1/2" NPT (R1/2) • K Factor : 4.9 (Actual) - F1 Res 49 Pendent Sprinkler 4.4 (Actual) - F1 Res 44 HSW Sprinkler 5.8 (Actual) - F1 Res 58 Pendent Sprinkler • Density : Minimum .05 gpm/ft2 ,Technical Data (RFC 43 & RFC 49): • Thermal Sensor: 165°F Fusible Link • Sprinkler Frame: Brass Machined • Sprinkler Pressure Rating : 175 psi Factory Hydrostatically Tested to 500 psi • Thread Size : 1/2" NPT (RI/2) • K Factor 4.3 (Actual) RFC43; 4.9 (Actual) RFC49 • Density Minimum .05 gpm/ft2 Application Model F1 Res and RFC 43 & RFC 49 Sprinklers are used for Residential Fire Protection according to UL 1626 Stan- dard*. Be sure that orifice size, temperature rating, deflec- tor style, cover plate and sprinkler type are in accordance with the latest published standards of The National Fire Protection Association or the approving Authority Having Jurisdiction. * Effective date July 12, 2002 METHOD OF CALCULATING THE CONVERSION OF 'RISE -OVER -RUN' TO DEGREES OF AN ANGLE. .mac a (rise) run C 1.4 A = TAN-' (a/b) 2. slope distance: c = I;r + b2 Example: a = 4 b = 12' .¢A = TAN .' (a/b) slope distance: c = 4Z +122 .4A = TAN-' = (0:333) c = 1160 4A= 18.43' c= 12.65 1055_ROR A N Model F1 Res 49 Pendent & F1 Res 49 Recessed Pendent/F2 & F1 Res 49 CCP Pendent, ,Model F1 Res 58 Pendent & F1 Res 58 Recessed Pendent/F2 & F1 Res 58 CCP Pendent, RFC 43 & RFC 49 Pendent Flat Concealed Sprinklers installed below Sloped Ceilings. F1 Res 49 & 58 Pendent F1 Res 49 & 58 Recessed Pendent / F2 RFC 43 & RFC 49 Note: F1 Res 49 CCP Pendent, RFC 43 and RFC 49 sprinklers are not suitable for installation in ceilings which have positive pressure in the space above. 4 F1 Res 49 & 58 CCP Pendent mr-U 415 b& mr-U 4y L/2 L L/2 A B W L/2 C , ' wQG -' ELEVAT/ON - L B LISTED AREA OF COVERAGE CORRESPONDS TO CEILING SLOPE _ L/2 L = THE MAXIMUM LISTED SPRINKLER - \NIN. SPACING, LENGTH (8'-0" MINIMUM). L/2 = ONE HALF THE MAXIMUM LISTED SPRINKLER SPACING (0'-4" MINIMUM). W THE MAXIMUM LISTED SPRINKLER SPACING, WIDTH. A 3'-0" MAXIMUM., F�ooa B = RANGE: 2/12 (9.4') *< B S 8/12 (33.70). C = 8'-0" MINIMUM. 035FGOI 5. ELEVA LISW AREA OF COYLWGE CORRESMAOM IO CEILING -+f L = THE MAXIMUM LISTED SPRINKLER SPACING. LENGTH (8'-0" MINIMUM). L/2 = ONE HALF THE MAXIMUM LISTED SPRINKLER SPACING (0'-4" MINIMUM). W = THE MAXIMUM LISTED SPRINKLER SPACING, WIDTH. A = 3'-0" MAXIMUM. 8 = RANGE: 2/12 (9.4') < 8 S 8/12 (33.7*) C = 8'-0" MINIMUM. OJ5FW2 *--B Sprinkler spacing below multiple sloped ceilings with a maximum slope of 8/12 (33.70) pitch. r 6 Model F1 Res 49 Pendent & F1 Res 49 Recessed Pendent/F2 installed below Sloped Ceiling. Technical Data Table 1 - Application Max. Max. Actual Min. Flow Per Sprinkler Head Pressure Sprinkler Thread Pressure Ambient K Factor Sprinkler Escutcheon Identification Size psi (bar) Temp.em (metric) Length (68°C) Number (SIN) Sprinkler mead gpm psi (bar) Length Number (SIN) 14 x 14 4,3 x 4,3 14 53 8.2 0,57 12 x 12 3,6 x 3,6 '/i' NPT (R'/2) 175 (12) 100 (38) 4.9 (69,94) 2.25" (57mm) 1/2" Adjustment)R3516 7.0 0,48 Table 1 - Application Model F1 Res 49 CCP Pendent installed below Sloped Ceiling. Technical Data Max. Slope of 8hz 33.7° Pitch Max. Slope of °hz 18.4° Pitch Min. Flow Per Sprinkler Head Pressure Sprinkler Temp. Rating OF (°C) Max. Sprinkler Spacing Along Slope gpm (Lpm) psi (bar) 155 (68) & 175 (79) Ambient K 175°F Min. Flow Per Pressure (W) Width x ( L) Length it (m)155°F OF (°C) 155-F (68-C) 175-F (790C) (68°C) (79°C) Sprinkler mead gpm psi (bar) Length Number (SIN) 14 x 14 4,3 x 4,3 14 53 8.2 0,57 12 x 12 3,6 x 3,6 13 49 13 49 7.0 0,48 7.0 0,48 13 49 7.0(0,48 14 x 14 4,3 x 4,3 13 49 13 49 7.0 0,48 7.0 0,48 13 49 7.0 0,48 16 x 16 4,9 x 4,9 13 49 13 49 7.0 0,48 7.0 0,48 13 49 7.0 0,48 18 x 18 5,5 x 5,5 17 64,3 18 68,2 12.0 0,83 13.5 0,93 18 68,3 13.5 0,93 20 x 20 6,1 x 6,1 20 75,7 21 79,5 16.7. 1,15 18.4 1,28 20 75,7 16.7(l.15) Model F1 Res 49 CCP Pendent installed below Sloped Ceiling. Technical Data Table 2 - Application Max. Sprinkler Spacing Sprinkler CCP Assy. Max. Max. Actual Min. Flow Sprinkler Thread Size Temp. Rating Temp. Pressure Ambient K Sprinkler Identification 100 (38) OF (°C) Rating OF°C psi (bar) Temp. Factor Length Number (SIN) 14 x 14 4,3 x 4,3 14 53 8.2 0,57 13 49 OF °C metric 14 53 8.2 0,57 '/z" NPTR'/z 155 68 135 57 175 12 100 38 4.9 69,94 2.25" 57mm R3516 Table 2 - Application Max. Sprinkler Spacing Max. Slope of 8hz 33.70Pitch Max. Slo of 4/1218.4° Pitch Min. Flow Pressure Min. Flow Pressure Along Slope (W) Width x (L) Length ft (m) Per Sp Sprinkler Head psi (bar) Per Sprinkler Head (bar) '/z" NPT (RI/2) m (Lpm) 100 (38) m(Lpm)psi 2.25" (57mm)1/2 12 x 12 3,6 x 3,6 14 53 8.2 0,57 13 49 7.0 0,48 14 x 14 4,3 x 4,3 14 53 8.2 0,57 13 49 7.0 0,48 16 x 16 4,9 x 4,9 14 53 8.2 0,57 14 53 8.2 0,56 18 x 18 5,5 x 5,5 23 87 22 1,52 20 75,7 17 1,17 20 x 20 6,1 x 6,1 23 87 22 1,52 21 75,7 17 1,17 Model F1 Res 58 Pendent & F1 Res 58 Recessed Pendent/F2 installed below Sloped Ceiling. Technical Data Thread Max. Pressure Max. Ambient Temp. Actual Sprinkler Min. Flow Sprinkler Identifica- Size sI bar °F °C K Factor (metric) Length Pressure tion tion Number (SIN) '/z" NPT (RI/2) 175 (12) 100 (38) 5.8 (83,38) 2.25" (57mm)1/2 AdF stment R3513 Table 3 - Application 7. Max. Slope of 8 33.7° Pitch Max. Slope of °hz 18.4° Pitch Min. Flow Max. Sprinkler Spacing Along Slope Min. Flow Per Sprinkler Head Pressure Per Sprinkler Pressure (W) Width x ( L) Length ft (m) gpm (Lpm) psi (bar) Head psi (bar) m (Lpm) 155°F 68°C 175°F 79°C 155°F 68°C 175°F 79°C 155°F 68°C 155°F 68°C 12 x 12 (3,6 x 3,6) 21 (79.5) 23 (87) 13.1 (0,9) 15.7 (1,1) 14 x 14 4,3 x 4,3 21 79.5 23 87 13.1 0,9 15.7 1,1 16 x 16 4,9 x 4,9 21 79.5 23 87 13.1 0,9 15.7 1,1 18 x 18 5,5 x 5,5 23 87 15.7 1,1 20 75,7 12 0,83 20 x 20 6,1 x 6,1 23 87 15.7 1,1 20(75,7) 12(0,83) 7. Model F1 Res 58 CCP Pendent Installed below sloped Ceiling. Technical Data Table 4 - Aoolication Max. Sprinkler Spacing Along Slope Max. Slope of °/12 18.40Pitch (W) Width x ( L) Length ft (m) Min. Flow Per Sprinkler Head Pressure m (Lpm) psi bar 18x18 55x55 20 75.7 12(0.83) 20 x 20 (6.1 x 6.1) 20 75.7 12(0.83) Model RFC43 Pendent Flat Concealed installed below Sloped Ceiling. Technical Data Sprinkler Temp. CCP Assy. Max. max. ActualZ2557 Max Sprinkler Thread Size Rating Temp. Pressure Ambient KIdentification Identification 30(30.0) of (°C) Rating psi (bar) Twp' Factor (metric) Adjustment Number (SIN) 1/z" NPT (RI/2) 165 74 F C 175 12 °F °C 4.3(61.4) '/z" 13mm RA0612 '/z" NPT R'/2 155 68 135 57 175 12 100 38 5.8 83,38 17.5 121 R3513 Table 4 - Aoolication Max. Sprinkler Spacing Along Slope Max. Slope of °/12 18.40Pitch (W) Width x ( L) Length ft (m) Min. Flow Per Sprinkler Head Pressure m (Lpm) psi bar 18x18 55x55 20 75.7 12(0.83) 20 x 20 (6.1 x 6.1) 20 75.7 12(0.83) Model RFC43 Pendent Flat Concealed installed below Sloped Ceiling. Technical Data Table 5 - Application Sprinkler Coverplate Max. Max. Actual Max Sprinkler Thread Size Temp. Rating Temp. Rating Pressure Ambient Temp. K Factor Max. Identification 30(30.0) °F °C °F °C psi bar °F °C metric Adjustment Number SIN 1/z" NPT (RI/2) 165 74 135 57 175 12 100 38 4.3(61.4) '/z" 13mm RA0612 Table 5 - Application Model RFC 49 Pendent Flat Concealed installed below Sloped Ceiling. Technical Data Max. Slo of 8/12 (33.7*1 Pitch Max. Slopeof 4/12 18.4° Pitch Max. Sprinkler Spacing Along Slope Min. Flow Per Sprinkler Head Pressure Min. Flow Per Pressure (W) Width x ( L) Length ft (m) gpm (Lpm) psi (bar) Sprinkler mead psi (bar) Max. Identification 30(30.0) qpm °F °C 12x12 36x36 18 68 17.5 121 13 49 9.1(0.63) 14 x 14 3x43 18 68 17.5 121 13 49 9.1(0.63) 16x16 49x49 1 18 68 1 17.5 121 13 49 9.1 063 18x18 55x55 24 91 31(2,14) 18 68 17.5 121 20 x 20 6,1 x 6,1 24 91 31 2,14 21 79 23.8 1,64 Model RFC 49 Pendent Flat Concealed installed below Sloped Ceiling. Technical Data Table 6 - Application Max. Sprinkler Spacing Along Slope (W) Width x (L) Length ft (m) Sprinkler Coverplate Max. Max. Actual 23 193 Sprinkler Thread Size Temp. Rating Temp. Rating Pressure Ambient Temp. K Factor Max. Identification 30(30.0) °F °C °F °C i bar °F °C metric Adjustment Number SIN 1/2" NPT(RI/2) 165 74 135 57 175 12 100 38 4.9(69,94) Yz" 13mm RA0616 Table 6 - Application Max. Sprinkler Spacing Along Slope (W) Width x (L) Length ft (m) Max. Slo a of 8/12 33.7° Pitch Max. Slope of 4/1208.41 Pitch Min. Flow Per Sprinkler Head Pressure Min. Flow Per Sprinkler Head Pressure m (Lpm) psi bar gpm (Lpm) psi bar 16x16 49x49 28 106 23 193 18 x 18 (5.5 x 5.5) 29 109.8 29(20.0) 18 68 13.5(0 93 20 x 20 (6.1 x 6 1 30 113.6 30(30.0) 1 23 87 220,52) Installation Guidelines 1. For systems designed in accordance with NFPA 13, 13D and 13R, where specific UL Listed flows are not required, consult with the local Authority Having Juris- diction regarding the number of design sprinklers for sloped ceilings having a pitch greater than (9.40). 2. Installation of UL Listed residential sprinklers under sloped ceilings shall be limited to a type of unob- structed construction consisting of smooth ceilings, as defined by NFPA 13, having a maximum pitch of 4/12 (18.41) or 8/12 (33.7°). 3. Spacing of residential sprinklers under sloped ceil- ings is measured along the slope when determining the distance off of walls and between sprinklers. 4. Measure listed areas of coverage along the sloped ceiling. The actual floor coverage area will be less than the listed area. 5. For coverage areas less than the listed coverage area shown in Tables 1 through 5, use the minimum flow requirement for the next largest listed coverage area. .:* 6. Minimum spacing between pendent type sprinklers is 8 ft. (2.4 m). Minimum distance from a pendent type sprinkler and an adjacent wall is 4" (102 mm). 7. Residential sprinklers located closest to the peak of the ceiling shall have the deflectors located not more than 3 ft (1m) vertically down from the peak. Align de- flectors parallel with the ceiling slope 1" to 4" (25mm to 102mm) below the sloped ceiling. 8. Hydraulic Requirements: a. For NFPA 13D Systems, the number of design sprinklers shall include all sprinklers within a compartment, up to a maximum of two sprinklers (where specific UL Listed flows are required) that requires the greatest hydraulic demand. b. For NFPA 13R Systems, the number of design sprinklers shall include all sprinklers within a com- partment, up to a maximum of four (4) sprinklers (where specific UL Listed flows are required), that requires the greatest hydraulic demand. c. For NFPA 13 systems, the design area shall be the area that includes the four (4) hydraulically most demanding sprinklers. The minimum re- quired discharge from each of the four hydrauli- cally demanding sprinklers shall be the greater of the following: (1) In accordance with the minimum flow rates in- dicated by the individual listings (that already will provide a minimum density of 0.1 gpm/ft2); or (2) A calculated value based on delivering a mini- mum of 0.1 gpm/ft2 over the design area. 9. Because of the varied nature of residential construc- tion features, there will be some compartment designs which cannot be fully sprinklered in accordance with NFPA 13, 13D, or 13R. In these instances, consult the Authority Having Jurisdiction (AHJ) for guidance and approval. This includes sloped ceilings having a pitch greater than 8/12 (33.7). 10. Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACE IN SER- VICE FOR FIRE PROTECTION. Removal of the pro- tectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PRO- TECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. Model F1 Res 44 and F1 Res 44 HSW/F2 installed below Sloped Ceiling. F1 Res 44 HSW F1 Hes 44 Recessed HSW/F2 Horizontal 5idewall bprinKler (with discharge directed across the slope) 91 (with discharge directed down the slope) - = LISTED AREA OF COVERAGE A ;S B CORRESPONDS TOP OF DEFLECTOR MUST BE LOCATL C 4' TO 12' BELOW SLOPED CE/UNG. THE TOP OF THE DEFLECTOR MUST I PARALLEL WITH THE PLANE OF THE i ELEVAT/ON DISCHARGE /S A THE SLOPE. L = THE MAXIMUM LISTED SPRINKLER SPACING, LENGTH. W = THE MAXIMUM LISTED SPRINKLER SPACING, WIDTH. W/2 = ONE—HALF THE MAXIMUM LISTED SPRINKLER SPACING, WIDTH (0'-4" MINIMUM). A = 3'-0" MAXIMUM. B = RANGE: 2/12 (9.4') < B s 8/12 (33.7'): C = 8'-0" MINIMUM. TOP OF DEFLECTOR MUST BE LOCATED 4' TO 12' BELOW SLOPED CEILING. THE TOP OF 7H£ DEFLECTOR MUST BE PARALLEL WITH THE PLANE OF THE COUNG. DISCHARGE /S DOWN THE SLOPE. 035FGOJB p, D AREA OF COVERAGE ESPONDS TO CEILING SLOPE HSW sprinkler spacing below single sloped ceilings with a maximum slope of 9/12 (33.7°) pitch. W B LEM AREA OF COVERAGE oDRRESAavas ro c>:TLLMc SLOPE Ci TOP OF DIEFLEL= MUST BE L.OGTED 4' ro B' BELOW SLOPm CMAC THE EL /VA TOP OF THE QEFLECTOR MUST BE PARALLEL MON THE PLANE OF THE CEUAA DMWAGGE IS AQMS THE SLOPE L = THE MAXIMUM LISTED SPRINKLER SPACING. LENGTH. W = THE MAXIMUM LISTED SPRINKLER SPACING. WIDTH (0'-4' MINIMUM). W/2 = ONE—HALF THE MAXIMUM LISTED SPRINKLER SPACING. WIDTH (0'-4' MINIMUM). A = 3'-0' MAXIMUM. B = RANGE: 2/12 (9.4') < B s 8/12 (33.T). C = 8'-0" MINIMUM. OT5FG104 prinkler spacing below multiple sloped ceilings with a maximum 10. ; Model F1 RES 44 HSW & F1 RES 44 HSW Recessed HSW/F2 installed below Sloped Ceiling. Technical Data Table 7 - Application Sprinkler Temp. Max. Max. Actual Sprinkler Discharge Directed Across the Slope Sprinkler Thread Size Rating Pressure Ambient Temp. K Factor Len ht g Escutcheon Identification OF °C i bar OF °C metric 16 60,5 13.3 (0,92) Number SIN '/2" NPT (R'/2) 155 (68) 175 (12) 100 (38) 4.4 (62,8) 2.45" F2 R3531 13.3 0,92 175 79 15 1,04 18 x 18 4,9 x 5,5 18 68,1 62mm 1/2" Adjustment 20.7 1,43 Table 7 - Application Table 8 - ADDlication Max. Max. Slope of 4/12 18.4° Pitch Max. Sprinkler Spacing Along Slope Discharge Directed Across the Slope Discharge Directed Across the Slope (W) Width x ( L) Length ft (m) 4" to 6" Deflector to Ceiling 6" to 12" Deflector to Ceilin Down the Slope 6" to 12" Deflector to Ceiling Min. Flow gpm (Lpm) Pressure psi (bar) Min. Flow gpm (Lpm) Pressure mLm psi (bar) mLm sibar psi(bar) 12 x 12 3,6 x 3,6 16 60,5 13.3 (0,92) 17 64,3 15 1,04 14 x 14 4,3 x 4,3 16 60,5 13.3 0,92 17 64,3 15 1,04 16 x 16 4,9 x 4,9 16 60,5 13.3 0,92 17 64,3 15 1,04 18 x 18 4,9 x 5,5 18 68,1 16.8 1,16 20 75,6 20.7 1,43 20 x 20 (4,6 x 6,1) 23 68,1 27.4 1,89 23 68,1 27,4 1,89 Table 8 - ADDlication (1) Minimum flow per sprinkler gpm (Lpm). (2) Minimum 3 head design in a compartment. (3) 155°F only. Installation Guidelines 1. For systems designed in accordance with NFPA 13, 13D and 13R, where specific UL Listed flows are not required, consult with the local Authority Having Juris- diction regarding the number of design sprinklers for sloped ceilings having pitch greater than (9.40). 2. Installation of UL Listed residential sprinklers under sloped ceilings shall be limited to a type of unobstruct- ed construction consisting of flat, smooth ceilings, as defined by NFPA 13, having a maximum pitch of 4/12 (18.40) or 8/12 (33.70). 3. Where listed, install horizontal sidewall sprinklers along the wall below the sloped ceiling when dis- charge is directed across the slope, and install at the peak below the sloped ceiling when discharge is directed down the slope. Always align the sprinkler deflector parallel with the direction of the sloped ceil- ing. 4. Residential HSW sprinklers located closed to the peak of the ceiling shall have the deflectors located not more than 3 ft. (1m) vertically down from the peak. 5. Spacing of residential HSW sprinklers under sloped ceilings is measured along the slope when determin- ing the distance off of walls and between sprinklers. 11. 6. Measure listed areas of coverage along the sloped ceiling. The actual floor coverage area will be less than the listed area. 7. For coverage areas less than the listed coverage area shown in Tables 1 through 6, use the minimum flow requirement for next largest listed coverage area. 8. Minimum spacing between horizontal sidewall sprin- klers is 8 ft. (2.4 m). Minimum distance from a hori- zontal sidewall sprinkler and an adjacent wall is 4" (102 mm). 9. Hydraulic Requirements: a. For NFPA 13D Systems, the number of design sprinklers shall include all sprinklers within a compartment, up to a maximum of two sprinklers (where specific UL Listed flows are required) that requires the greatest hydraulic demand. b. For NFPA 13R Systems, the number of design sprinklers shall include all sprinklers within a com- partment, up to a maximum of four (4) sprinklers (where specific UL Listed flows are required), that requires the greatest hydraulic demand. Max. Sloo of 8/12 33.70Pitch Discharge Directed Discharge Directed (430ischarge Directed Max. Sprinkler Spacing Along Slope (W) Width x (L) Length ft (m) Down the Slope 4" to 6" Deflector to Ceilina Down the Slope 6" to 12" Deflector to Ceiling Across the Slope 4" to 12" Deflector to Ceiling Min. Flow Pressure Min. Flow Pressure (1) Min. Flow Pressure mLm psi (bar) mLm sibar gpm (Lpm) sibar 12x12 36x36 12(45.4) 7.5(0.52) 14(53.0) 10.2 071 16(60.6) 13.3 092 14x14 43x43 14(53.0) 10.2 071 16(60.6) 13.3 092 16(60.6) 13.3 092 16x16 49x49 16(60.6) 13.3 092 17(64.4) 150,04) 16(60.6) 13.3 092 18x18 49x55 18(68.1) 1 16.8 116 20(75.6) 20.7 143 20 x 20 4,6 x 6,1 23 72,0 27.4 1,89 23 87,1 27,4 1,89 (1) Minimum flow per sprinkler gpm (Lpm). (2) Minimum 3 head design in a compartment. (3) 155°F only. Installation Guidelines 1. For systems designed in accordance with NFPA 13, 13D and 13R, where specific UL Listed flows are not required, consult with the local Authority Having Juris- diction regarding the number of design sprinklers for sloped ceilings having pitch greater than (9.40). 2. Installation of UL Listed residential sprinklers under sloped ceilings shall be limited to a type of unobstruct- ed construction consisting of flat, smooth ceilings, as defined by NFPA 13, having a maximum pitch of 4/12 (18.40) or 8/12 (33.70). 3. Where listed, install horizontal sidewall sprinklers along the wall below the sloped ceiling when dis- charge is directed across the slope, and install at the peak below the sloped ceiling when discharge is directed down the slope. Always align the sprinkler deflector parallel with the direction of the sloped ceil- ing. 4. Residential HSW sprinklers located closed to the peak of the ceiling shall have the deflectors located not more than 3 ft. (1m) vertically down from the peak. 5. Spacing of residential HSW sprinklers under sloped ceilings is measured along the slope when determin- ing the distance off of walls and between sprinklers. 11. 6. Measure listed areas of coverage along the sloped ceiling. The actual floor coverage area will be less than the listed area. 7. For coverage areas less than the listed coverage area shown in Tables 1 through 6, use the minimum flow requirement for next largest listed coverage area. 8. Minimum spacing between horizontal sidewall sprin- klers is 8 ft. (2.4 m). Minimum distance from a hori- zontal sidewall sprinkler and an adjacent wall is 4" (102 mm). 9. Hydraulic Requirements: a. For NFPA 13D Systems, the number of design sprinklers shall include all sprinklers within a compartment, up to a maximum of two sprinklers (where specific UL Listed flows are required) that requires the greatest hydraulic demand. b. For NFPA 13R Systems, the number of design sprinklers shall include all sprinklers within a com- partment, up to a maximum of four (4) sprinklers (where specific UL Listed flows are required), that requires the greatest hydraulic demand. For NFPA 13 systems, the design area shall be the area that includes the four (4) hydraulically most demanding sprinklers. The minimum re- quired discharge from each of the four hydrauli- cally demanding sprinklers shall be the greater of the following: (1) In accordance with the minimum flow rates in- dicated by the individual listings (that already will provide a minimum density of 0.1 gpm/ft2); or (2) A calculated value based on delivering a mini- mum of 0.1 gpm/ft2 over the design area. 10. Because of the varied nature of residential construc- tion features, there will be some compartment designs which cannot be fully sprinklered in accordance with NFPA 13, 13D, or 13R. In these instances, consult the Authority Having Jurisdiction (AHJ) for guidance and approval. This includes sloped ceilings having a pitch greater than 8/12 (33.70). 11. Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACE IN SER- VICE FOR FIRE PROTECTION. Removal of the pro- tectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PRO- TECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. Model F1 res 49 Pendent, F1 Recessed Pendent/F2, F1 Res 49 Concealed (CCP), RFC 49 and RFC 43 installed below sloped ceiling with a maximun slope of 8/12 (33.7°) pitch. Table 9 - Application -*-B L = THE MAXIMUM LISTED SPRINKLER SPACING, LENGTH (8'-0' MINIMUM). L/2 = ONE HALF THE MAXIMUM LISTED SPRINKLER SPACING (0'-4' MINIMUM). W = THE MAXIMUM LISTED SPRINKLER SPACING, WIDTH. A = 3'-0' MAXIMUM. 9 = RANGE: 2/12 (9.4') < 8 S 8/12 (33.71). C = 8'-0' MINIMUM. MULTI -SPRINKLER ARRAINGEMENT FOR SLOPED CEILINGS auM7 WITH A MAXIMUM SLOPE OF 8/12 (33.71) PITCH. Fig. 7 K - Factor Max. Min. Sprinkler Coverplate Model (metric) Spacing Flow/Pressure Temperature Rating Temperature Ft. x Ft m x m m I m / si bar OF °C Rated°F °C F1 Res 49Pendent 4.9 69,94 10 x 10 3 x 3 13 49 / 7.0 0,48 155 68 - F1 Res 49 Reccesed Pendent/F2 4.9 (69,94) 10 x 10 (3 x 3) 13(49) / 7.0(0,48) 155 (68) F1 Res 49CCP Pendent 4.9 69,94 10 x 10 3 x 3 13 49 / 7.0 0,48 155 68 135 57 RFC49Pendent 4.9 69,94 10 x 10 3 x 3 14 53 / 8.2 0,57 165 74 135 57 RFC43Pendent 4.3(61,4) 10 x 10 3 x 3 18(68) /17.5(l.21) 165(74) 135 57 -*-B L = THE MAXIMUM LISTED SPRINKLER SPACING, LENGTH (8'-0' MINIMUM). L/2 = ONE HALF THE MAXIMUM LISTED SPRINKLER SPACING (0'-4' MINIMUM). W = THE MAXIMUM LISTED SPRINKLER SPACING, WIDTH. A = 3'-0' MAXIMUM. 9 = RANGE: 2/12 (9.4') < 8 S 8/12 (33.71). C = 8'-0' MINIMUM. MULTI -SPRINKLER ARRAINGEMENT FOR SLOPED CEILINGS auM7 WITH A MAXIMUM SLOPE OF 8/12 (33.71) PITCH. Fig. 7 tLt LISTED AREA OF COVERAGE CORRESPONDS TO CEILING SLO L = THE MAXIMUM LISTED SPRINKLER SPACING, LENGTH (10'-0" MAXIMUM) (8'-0" MINIMUM). L/2 = ONE HALF THE MAXIMUM LISTED SPRINKLER SPACING (5'-0" MAXIMUM) (4'-0"MINIMUM) W = THE MAXIMUM. LISTED SPRINKLER SPACING, WIDTH (10'-0").. A = 3'-0" MAXIMUM. B = RANGE: ,2/12 (9.4') < B 5 8/12 (33.7'). C = 8'-0" MINIMUM. 035FG08 ELEVATION H2 Fig. 8 13. L = B + C D = 8' - 0" MINIMUM A = 3' - 0" MAXIMUM Cnstallation Guidelines per UL1626A 1. For systems designed in accordance with NFPA 13, 13D and 13R, where specific UL Listed flows are not required, consult with the local Authority Having Juris- diction regarding the number of design sprinklers for sloped ceilings having pitch greater than (9.4°). 2. Installation of UL Listed residential sprinklers under sloped ceilings shall be limited to a type of unob- structed construction consisting of smooth ceilings, as defined by NFPA 13, having a maximum pitch of 8/12 (33.7). 3. Spacing of residential sprinklers under sloped ceil- ings is measured along the slope when determining the distance off of walls and between sprinklers. 4. Measure listed areas of coverage along the sloped ceiling. The actual floor coverage area will be less than the listed area. 5. For coverage areas less than the listed coverage area shown.in Tables 8, use the minimum flow requirement listed. 6. Minimum spacing between pendent type sprinklers is 8 ft. (2.4 m). Minimum distance from a pendent type sprinkler and an adjacent wall is 4" (102 mm). 7. Reidential sprinklers located closest to the peak of the ceiling shall have the deflectors located not more than 3 ft (1 m) vertically down from the peak. Align de- flectors parallel with the ceiling slope 1" to 4" (25mm to 102mm) below the slope ceiling. 8. Hydraulic Requirements: a. For UL1626A, the number of design sprinklers shall include up to a maximum of two sprinklers that requires the greatest hydraulic demand. 9. Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACE IN SER- VICE FOR FIRE PROTECTION. Removal of the pro- tectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PRO- TECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. 10. -A maximum distance from the floor to the ceiling peak of 24 ft. 11. A maximum of two sprinklers installed within 3 ft. verti- cally of the peak. 12. Installation is for smooth, flat ceilings only that do not extend into or serve as a ceiling for an upper level floor in the structure. The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. ® Recycled ® (800) 431-1588 Sales Offices Paper ' (800) 848-6051 Sales Fax Revision lines indicate updated or new data. (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG. Printed in U.S.A 11/09 P/N 9999970245