06-3804 (CSCS) Title 24IL i Y, o, ,4 TITLE 24 REPORT Title 24 Report for: DUNES SHOP 2 DUNES RETAIL CENTER HIGHWAY 111 LA Q U 1 NTA, CA 92253 Project Designer: KKE ARCHITECTS 525 EAST COLORADO BLVD PASADENA, CA 91101 626.796.8230 Report Prepared By: S.Y. Lee S.Y. Lee Associates 14 S. Glendale Ave., Suite #205 DALE, CA 91208 ( 18) 244-4337 CIT OF LA QUINTA 13UILDAPPROVED ING & SAFETY® PT. ~P/ED FOR CONSTRUCTION DATES BY L *0(o Jdb Number: 5383 Date: 4/2/2007 �ppFESS/;�`�� e Not. ROF Exp:=�o o TRIGP� 9TFOF CALIF n[�C��Od�n APR 062007 IUI (07vi7t� q%M rte i�►CF- The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC - www.energysoft.com. EnergyPro 4.3 by EnergySoft Job Number: 5383 user Number. 3193 " . c PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3' PERF -1 PROJECT NAME DUNES SHOP 2 This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the DATE 4/2/2007 PROJECT ADDRESS=-----> DUNES RETAIL CENTER HIGHWAY 111 LA QUINTA ��..,. PRINCIPAL DESIGNER -ENVELOPE KKE ARCHITECTS BUILDING CONDITIONED FLOOR AREA TELEPHONE 626.796.8230 Bwlding Permit # ui DOCUMENTATION AUTHOR S.Y. Lee Associates ® TELEPHONE 1 (818) 244-4337 Checked by/Date ` EnforcemertAgen •use..:: GENERAL INFORMATION This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and c m tete. DOCUMENTATION AUTHOR DATE OF PLANS S.Y. LeeA BUILDING CONDITIONED FLOOR AREA 4,443 Sq.Ft CLIMATE ZONE 15 BUILDING TYPE ® NONRESIDENTIAL HIGH RISE RESIDENTIAL HOTEL/MOTEL GUEST ROOM PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ADDITION 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed EXISTING + ADDITION/ALTERATION STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and c m tete. DOCUMENTATION AUTHOR SIGNATURE D T S.Y. LeeA 2—(-6-7 The Principal Designer hereby certifys that the proposed building desig rep es ted in this set of construction documents is consistent with the other compliance forms and worksheets, with the specificatidfis, and with any other calculations submitted with this permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116, through 118, and 140, 142, 143 or 149 of Title 24, Part 6. ENV. LTG. MECH. ❑(p� 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to i sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, mechanical engineer, or I am a licensed architect. Ej ❑ 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. ❑ F� F� 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) ENVELOPE COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures ENV -1 Required Forms PRINCIPAL ENVELOPE DESIGNER - NAME SIGNATURE LIC. NO. DATE KKE ARCHITECTS LIGHTING COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures Lighting Compliance Not In The Scope Of T —Suib 11 Required Forms PRINCIPAL LIGHTING DESIGNER - NAME SIGNATURE LIC. NO. DATE MECHANICAL COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures ECH-1, MECH-2 MECH-3 MECH-5 Required Forms PRINCIPAL MECHANICAL DESIGNER - NAME SIGNATVOP 11,1C. NO. D T. S.Y. Lee Associates �/ L 6 2-10 7 I v It %-- I — EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number. 5383 Paoe:3 of 13 1 fk-RFORMANCE CERTIFICATE OF .COMPLIANCE Part 2 of 3 PER [PROJECT NAME DATE DUNES SHOP 2' I 4/2/2007 Building Orientation Number of Stories " Number of Systems Number of Zones. N 0 dtg ANNUAL TDV ENERGY USE SUMMARY kBtu/s ft- r --.. - . Standard Proposed ENERGY COMPONENT. °. Design Design Space_Heating 2.41 -0.17 _ ,Space:Cooling 288.00 178.31 V' -'indoor Fans 102.50 112.64 Heat Rejection } 0.00 0.00 Pumps & Misc. 0.00 0.00 Domestic Hot Water 0.00 0.00 Lighting •72.98 Receptacle 81.78 81.78 Process o.00 o.00 TOTALS: ' 547.66 445.54 'Percent better than Standard: 18.6% • ..; Compliance Margin 4 o 2.58 VAN 109.68 ' PAN ;AN P -10.14 0.00 0.00 L _ 0.00 (E) 0.00` process) o.00 102. t2 ( 18.6% excluding 23.6% BUILDING COMPLIES Rear Elevation _ GENERAL INFORMATION Building Orientation Number of Stories " Number of Systems Number of Zones. N 0 dtg Conditioned Floor Area Unconditioned Floor Area Conditioned Footprint Area Fuel Type 4,443 sgft. sgft sgft. 1 0 4 o 11 Natural Gas 1,310 sgft. - awnuaru rrupubeu Lighting Power Density 1.100 wisgft. 1.100 wisgft. Prescriptive Env. Heat Loss 1,084 Btu/h 741 Muth Prescriptive Env. Heat Gain 106,675 Btnm-F . 91,810 Btu/h-F Remarks: Run Initiation Time: 02/25/07 17:40:04 -Run Co EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number: 5383 4of13 Orientation Gross Area Glazing Area Glazing Ratio Front Elevation (N 1,310 sgft. 319 sgft. 24.4% Left Elevation " (E) 1,421 sgft. 335 sgft. 23.6% " Rear Elevation _ S 1,386 sgft. 42 sgft 3.09% " Right Elevation, Total •Roof4,443 (W) 1,386 sgft: sgft. sgft. 1 109 sgft sgft. sgft. 7.9% 5,503 805 14.6% 0.0% - awnuaru rrupubeu Lighting Power Density 1.100 wisgft. 1.100 wisgft. Prescriptive Env. Heat Loss 1,084 Btu/h 741 Muth Prescriptive Env. Heat Gain 106,675 Btnm-F . 91,810 Btu/h-F Remarks: Run Initiation Time: 02/25/07 17:40:04 -Run Co EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number: 5383 4of13 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF- PROJECT NAME DATE DUNES SHOP 2' 4/2/2007 1 1EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. i The HVAC System "Carrier 50HJQ006" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJQ006" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. The HVAC System "Carrier 50HJQ006" includes Demand Control Ventilation per Standards Section 121. The HVAC. System "Carrier 50HJQ006: Premium Efr' 1.54 BHP Supply Fan Motor has been specified. 4 The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant Authorized Si nature or Stam Run Initiation Time: 02/25/07 17:40:04 Run Code: 1172454004 EnergyPro 4.3 by Energysoft User Number. 3193 Job Number. 5383 Page:5 of 13 CERTIFICATE OF COMPLIANCE ENV -1-C PROJECT NAME DATE DUNES SHOP 2 4/2/2007 OPAQUE SURFACES # Surface Tvpe I Area U -Fac. I Insulation Cay. Cont. Act. Am. Tilt Cond' Status Joint Appendix I IV Reference I Location/ Comments 1 Wall 1 99 0.074 R-19 R-0.0 0 90 1 New 109-A5 I TENANT A 2 Wall 1,08 0.074 R-19 R-0.0 90 90 New 109-A5 TENANT A -3 Roof 444 0.036 R-30 R-0.0 0 0 New 02-A9 ITENANTA 4 Wall 1,277 0.074 R-19 R-0.0 270 90 New 09-A5 TENANT A 5 Wall 1,344 0.074 R-19 R-0.0 180 90 New 09-A5 I TENANT N. E. A. R (New, Existing, Altered, Removed) FENESTRATION SURFACES FMore than or equal to 10,000 sq.fL of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default LI -factors from Standards Table 116-A and B. Certificate shall be filed in the contractors project office during construction and in the building manager's office after construction # Ilype ## Exterior Shade Type Area U -Fac' SHGC2 Act. Am. Cond. Stat Glazing Type 3 None Location/ Comments 1 Window Front N 319 0.290 NI -1 0.37 COG 01 New PPG SOLARBAN 60 2 Clear TENANT 2 Window Left E 335 0.290 NI -1 0.37 COG 901 New PPG SOLARBAN 60 2 Clear TENANT A 3 Window Right 109 0.290 NI -1 0.37 COG 2701 New PPG SOLARBAN 60 2 Clear TENANT A 4 Window Rear S 42 0.290 NI -1 0.37 COG 180 New PPG SOLARBAN 60 2 Clear TENANT A �1 U -factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value. 23 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING ## Exterior Shade Type Window Overhang Left Fin Right Fin SHGC Hgt. Wd. Len. Hat. LExt.RExt. Dist. Len. Hot. Dist. Len. Hot. 1 None 0.76 2 None 0.76 3 None 0.76 4 None 0.76 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES The proposed building is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a ceiling height greater than 15 feet, and an LPD for general lighting of at least 0.5 W/11:2. See Section W(c). If this box Is checked, ENV4-C must be filled out. when submitting under the Prescriptive Compliance Approach. EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number. 5383 Page:6 of 13 1 CERTIFICATE OF COMPLIANCE MECH-1-C NAME DUNES SHOP DATE 4/2/2007 Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments: SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of Section 10-103(b) and Title 24 Part 6. STATEMENT OF COMPLIANCE ❑ MECH-2-A: Ventilation System Acceptance Document -Variable Air Volume Systems Outdoor Air Acceptance -Constant Air Volume Systems Outdoor Air Acceptance Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ❑ MECH-3-A: Packaged HVAC Systems Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ❑ MECH-4-A: Air -Side Economizer Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the commission do not require equipment testing but do require construction inspection. ❑ MECH-5-A: Air Distribution Acceptance Document Equipment requiring acceptance testing This test required If the unit serves 5,000112 of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or replace the packaged unit. ❑ MECH-6-A: Demand Control Ventilation Acceptance Document Equipment requiring acceptance testing All new DCV controls installed on new or existing packaged systems must be tested. ❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document Equipment requiring acceptance testing All new VA fan volume controls installed on new or existing systems must be tested ❑ MECH-8-A: -Hydronic System Control Acceptance Document -Variable Flow Controls Applies to chilled and hot water systems. -Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header. -Supply Water Temperature Reset Controls Applies to new constant Bow chilled and hot water systems that have a design capacity greater than or equal to 500,000 BIWhr. -Water-loop Heat Pump Controls Applies to all new watedoop heat pump systems where the combined loop pumps are greater than 5 hp. -Variable Frequency Controls Applies to all new distribution pumps on new variable Bow chilled, hydronic heat pump or condenser water systems where the pumps motors are greater than 5 hp. Equipment requiring acceptance testing EnergyPro 4.3 by Energysoft User Number. 3193 Job Number. 5383 Page:7 of 13 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C (PROJECT NAME DATE DUNES SHOP 2 4/2/2007 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone AC -A1 THRU A4 4 Reference on Plans or Specification 1 112(a) 0.77 HSPF 112(a) 13.0 SEER / 11.0 EER 112(b) Yes 112(c), 115(a), n/a 121(b) Yes 121(b) 1111 cfm 121 c No 121 c Yes 121(c), 122(e) Programmable Switch 122(e) Heating & Cooling Required 122 Auto 122(g) n/a 123 124 R-19.0 144 a & b n/a 144 a & b 137,406 btuh 144 a & b n/a 144 a & b 206,379 btuh 144 c Constant Volume 144 c 144 c Yes 144 d No 144 a Diff. Tem Integrated) 144 Constant Tem 144 (f) Constant Temp 144 k No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/K in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes 9 System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has >.25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF -1 for performance method duct sealing requirements. EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number. 5383 Paoe:8 of 13 1 U M U W ►7 z O F- J_ W J U_ Z 2 U W 2 (V a- 0�/� 'U) v/ W z Z Transfer Air v Design Min. AI _�2 ° S � _ Setpoint 8 ; m a o Max of i Columns H, J, m >� Z K or 300 CFM _z Bx0.4 a > Y CFM/sq. ft. 5 _� 30% of Design -� Zone Supply o CFM 3 Design o — Vent. Air v CFM N REQ'D V.A $ = Max ofcn _ E CD (D or G) m Min CFM m d z a n U5 by Occupant � o a m (Ex F) �� E$ a CFM 9 -' U Z LL per ; Z vi E Q+ a Person o w _ $ D Q UNumber W of 'r E $ E p People s m ; o 'o Min CFM m E c o by Area co d m = o N (BXC) d E s �$ rn d a CFM o Z = U mU per Square Foot o o d a E N a m Q Condition V ¢ E �sQ 12>a c" v H Cm Area v te a; a c D U (SF) mu"� $ o �; m c w S L� Oo> _% 0 o U O o L N m 0 m w U m Y= 3: Er v m O 4 J a ZH z c°. E c '6 d m c aa) N o N .. a a s W QT N c d c N m cj d E a % > d c m o n .� m M a Z Q ; co m �' o; y o V N cc- Z w= a r c N C � a Q < a: 20 U ZFo O = Z Q -� W W U w= — Y Z W Q MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-5-C PROJECT NAME DUNES SHOP 2 DATE 4/2/2007 CHILLER AND TOWER SUMMARY HP Type Efficiency Tons PUMPS Add 1/2" Insulation Equipment Name Equipment Type Qty. Tot. Qty GPM BHP Motor Eff. Drive Eff. Pump Control CENTRAL SYSTEM RATINGS HEATING I COOLING I System Name System Type CLty Output Aux. kW Eff. Out ut Efficiencv Condition Status Economizer Type Carrier 50HJ0006 Packaged DX 4 tl 0.0 0.77 HSPF 63,800 13.0 SEER / 11.0 EER New DHW / BOILER SUMMARY Energy Standby TANK INSUL. Rated Vol. Condition Factor Loss or Ext System Name System Type Distribution Type QtyInput (Gals.) Status or RE Pilot R -Val. Hot Water P mp Hot Water Piping Leng ith ft Control # HP Type In Plenum Outside Buried Add 1/2" Insulation CENTRAL SYSTEM RATINGS HEATING I COOLING I System Name System Type CLty Output Aux. kW Eff. Out ut Efficiencv Condition Status Economizer Type Carrier 50HJ0006 Packaged DX 4 55,000 0.0 0.77 HSPF 63,800 13.0 SEER / 11.0 EER New Diff. Temp (Integrated) ENVELOPE MANDATORY MEASURES ENV -MM NAME DUNES SHOP 2 DATE 4/2/2007 DESCRIPTION Designer Enforcement 0 §118(,) Installed Insulating Material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20, Chapter 4, Article 3. F§118(c) All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. s XJ §117(a) All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. 0 § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards. Manufactured fenestration products must be labeled for U -value according to NFRC procedures. 0 §118(e) Demising Walls in Nonresidential Buildings: The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value of no less than R-13 between framing members. EnergyPro By EnergySoft User Number. User Job Number. 5383 Page: 11 of 13 MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM PROJECT NAME DATE DUNES SHOP 2 1 4/2/2007 DESCRIPTION Desi ner Enforcement Equipment and Systems Efficiencies FX] §111 Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply with the applicable standard. ❑ § 115(a) Fan type central furnaces shall not have a pilot light X] § 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be insulated in accordance with Standards Section 123. X] � § 124 Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards. Controls § 122(e) Each space conditioning system shall be installed with one of the following: ❑ § 122(e)1A Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the requirements r•r�?r :r•n of Section 112 (d)) shall be installed with an automatic time switch with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch shall be capable of programming different schedules for weekdays and weekends and have program backup capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or § 122(e)1B An occupancy sensor to control the operating period of the system; or F§ 122(e)1C A 4 -hour timer that can be manually operated -to control the operating period of the system. X❑ § 122(e)2 Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the system as required to maintain a setback heating and/or a setup cooling thermostat setpoint F§ 122(g) Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000 square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided with isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be setback or shut off independently of other isolation areas; and shall be controlled by a time control device as described above. ® § 122(a&b) Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or reduced to a minimum. 0 • § 122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to authorized personnel. X] § 112(b) Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the heating load can be met by the heat pump alone. EnergyPro By EnergySoft User Number: User. Job Number. 5383 Page: 12 of 13 VIECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM PROJECT NAME DATE DUNES SHOP 2 4/2/2007 X] § 121(f)1 Description Designer Enforcement Associated Air Balance Council (AABC) National Standards (1989); or Ventilation Outside Air Certification: The system shall provide the minimum outside air as shown on the mechanical drawings, and shall be measured and certified by the § 121(e) Controls shall be provided to allow outside air dampers or devices to be operated at mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the person with overall responsibility for the design of the ventilation system; or the ventilation rates as specified on these plans. Outside Air Measurement: The system shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous ❑ § 122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be Another method approved by the Commission. provided on the outside air intakes and discharges of all space conditioning and exhaust systems. 0 §'122(f) All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all openings to the outside, except for combustion air openings. X] § 121(f)1 Air Balancing: The system shall be balanced in accordance with the National Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or Associated Air Balance Council (AABC) National Standards (1989); or X] § 121(02 Outside Air Certification: The system shall provide the minimum outside air as shown on the mechanical drawings, and shall be measured and certified by the installing licensed C-20 mechanical contractor and certified by (1) the design mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the person with overall responsibility for the design of the ventilation system; or ❑ § 121(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous basis and displaying that quantity on a readily accessible display divice; or ❑ § 121(f)4 Another method approved by the Commission. Service Walter Heating Systems ❑ § 113(b)2 If a circulating hot water system is installed, it shall have a control capable of automatically turning off the circulating pump(s) when hot water is not required. ❑ § 113(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit the outlet temperature to 110 degrees F. 4 EnergyPro By EnergySoft User Number: User Job Number. 5383 Pape: 13 of 13 1