Loading...
06-3805 (CSCS) Title 24TITLE 24 REPORT Title 24 Report for: DUNES SHOP 3 DUNES RETAIL CENTER HIGHWAY 111 LA QUINTA, CA 92253 Project Designer: KKE ARCHITECTS 525 EAST COLORADO BLVD PASADENA, CA 91101 626.796.8230 Report Prepared By. S.Y. Lee S.Y. Lee Associates 1 Glendale Ave., Suite #205 GL NDALE, CA 91208 818) 244-4337 Let I** CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED J b Number: FOR CONSTRUCTION 5383 DATBYffg* 00 - lf3,93 Date: 4/2/2007 QRpFESS1pNA No. 16927 s Exp:��—b \;11'1 �FCTRIGP� OF C A0F APR- 0 6 2007 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC - www.energysoft.com. EnergyPro 4.3 by EnergySoft Job Number: 5383 User Number. 3193 G'7c,1*710 owl fit a TABLE -OF CONTENTS Cover Page Table of Contents Nonresidential Performance Title 24 Forms Form ENV -MM Envelope Mandatory Measures Form MECH-MM Mechanical Mandatory, Measures 1 2 3 17 18 EnergyPro 4.3 by EnergySoft Job Number: 5383 User Number: 3193 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1 PROJECT NAME DUNES SHOP 3 PROJECT ADDRESS DUNES RETAIL CENTER HIGHWAY 111 LA QUINTA PRINCIPAL DESIGNER - ENVELOPE TELEPHONE KKE ARCHITECTS 626.796.8230 DOCUMENTATION AUTHOR TELEPHONE S.Y. Lee Associates (818) 244-4337 DATE 4/2/2007 GENERAL INFORMATION This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and om lete. DOCUMENTATION AUTHOR DATE OF PLANS DVJE BUILDING CONDITIONED FLOOR AREA 9, 528 Sq.Ft. CLIMATE ZONE 1 15 BUILDING TYPE ® NONRESIDENTIAL HIGH RISE RESIDENTIAL HOTEUMOTEL GUEST ROOM PHASE OF CONSTRUCTION ® NEW CONSTRUCTION [:j ADDITION E] EXISTING + ADDITION/ALTERATION STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and om lete. DOCUMENTATION AUTHOR SIGNATURE DVJE S.Y. Lee o -->16 The Principal Designer hereby certifys that the proposed building dese/6preXented in this set of construction docum nts is consistent with the other compliance forms and worksheets, with the specific ions, and with any other calculations submitted with this permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116, through 118, and 140, 142, 143 or 149 of Title 24, Part 6. ENV. LTG. MECH. 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to YN sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, mechanical engineer, or I am a licensed architect. D F� 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. F] F� 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) ENVELOPE COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures ENVA Required Forms PRINCIPAL ENVELOPE DESIGNER - NAME SIGNATURE LIC. NO. DATE KKE ARCHITECTS LIGHTING COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures Lighting Compliance Not In The Scope Of Th'Ia Required Forms PRINCIPAL LIGHTING DESIGNER - NAME SIGNATURE LIC. NO. DATE MECHANICAL COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures MECH-1 MECH-2 MECH-3 MECH-5 Required Forms PRINCIPAL MECHANICAL DESIGNER - NAME SIGNATURE NO. DA S.Y. Lee Associates JLIQ. Z i • 1/ t EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number. 5383 Page:3 of 19 1 RFORMANCE .CERTIFICATE OF COMPLIANCE, Part 2 of 3 PERF PROJECT NAME DATE DUNES SHOP 3 I 4/2/2007 ANNUAL TDV ENERGY USE'SUMMARY kBtu/s ft- r Standard Proposed ENERGY COMPONENT Design Design Space Heating ; 0.39 0.00 SpaCe_:000ling 401.03 261.73 Indoor Fans 143.68 164.15 Heat Rejection 0.00 0.00 Pumps&Mise. 0.00 0.00 Domestic Hot Water 0.00 0.00 rLighting . 165.26 - 165.26 -.Receptacle. 82.18 82.18 Process o:oo o.00 " TOTALS: 792.55 673.32 Percent better than Standard: 15.0% Compliance Margin 0.39 139.30 '. s� a = Y k � a , MOM � i- e � IB , 2 0 , -0,30` 1?a.ia,80 2274.300 33 360 390'. kB17sa"n` process) -20.46 o.00���xt; 0.00 0.00 0.00 0.00 o.00 119.23 ( 15.0% excluding BUILDING COMPLIES GENERAL INFORMATION Building Orientation N O'deg Conditioned Floor Area 9,528 sgft. . Number of Stories 1, Unconditioned Floor Area o sqft. ' Number of Systems 9 Conditioned Footprint Area 0 sgft- Number of Zones 9 'Fuel Type Natural Gas Orientation Gross Area Glazing Area Glazing Ratio Front Elevation N 872 sgft. 215 sgft 24.7% Left Elevation (E) 2,289 sqft. 107 sgft. 4.7% Rear Elevations 998 sgft. 202 sgft. 20.2% Right Elevation - (W 2,699 sgft. 1,120 sgft. 41.5% Total 6,858 sgft. 1,644 sgft. Roof 9,528 sgft.sgft. 0.0% Standard Proposed Lighting -Power Density 1.500 wisgft. 1.500 W/sgn. Prescriptive,.Env. Heat Loss 1,776 Btu/h 1,206 Btum Prescriptive Env. Heat Gain 196,607 Btu/h-F 182,272 Brom-F Remarks: Run Initiation Time: 02/25/07'18:06:12 Run Code: 1172455572 EnergyPro 4.3. by EnergySoft User Number: 3193 Job Number: 5383 PageA of 19 [PERFORMANCE CERTIFICATE OF COMPLIANCE' Part 3 of 3 PERF -1 PROJECT NAME DATE DUNES SHOP 3 4/2/2007 ZONE INFORMATION h�.. 1 I C Floor Inst Ctrl'. Allowed LPD P�oc " Area LPD Credits sArea Tailo edi o - SYstem Name Zone Name Occupancy Type (sgft) (W/sf)1 AC -1-12 TENANT H Comp Bldg Retail and Wholesale 707 1.50 -AC-H1 TENANT H Comp Bldg Retail and Wholesale 707 *1.50, fr, AC-G TENANT Comp Bldg Retail and Wholesale 1,146 *1.50 AC -F TENANT F Comp Bldg Retail and Wholesale 1,146 *1.50 AC -E TENANT E Comp Bldg Retail and Wholesale 1,146 '1.50 k ' AC -D TENANT D - Com Bldg Retail and Wholesale 1,146 *1.50 AC -C TENANT Como Bldg Retail and Wholesale 1,146 '1.50 AC TENANT B Com Bld Retail and Wholesale 1 146 *1.50 AC -A '• TENANT A Com Bldg.Retail and Wholesale 1,238 *1.50 X � . �gn the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation The HVAC System "Carrier 50HJ0007" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJQ007" includes Demand Control Ventilation per Standards Section 121. The HVAC System "Carrier 50HJQ007: Premium Eff' 2.23 BHP Supply Fan Motor has been specified. The HVAC System "Carrier 50HJQ006" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJQ006" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. The HVAC System "Carrier 50HJQ006!' includes Demand Control Ventilation per Standards Section 121. The HVAC System "Carrier 50HJ0006: Premium Eff' 1.54 BHP Supply Fan Motor has been specified. The HVAC System "Carrier 50HJQ005" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJ0005" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. The HVAC System "Carrier 50HJQ005" includes Demand Control Ventilation per Standards Section 121. The HVAC System "Carrier 50HJQ005: Premium Efr' 1.08 BHP Supply Fan Motor has been specified. The HVAC System "Carrier 50HJQ004" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJQ004" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant Authorized Signature or Stam Run Initiation Time: 02/25/07 18:06:12 Run Code: 1172455572 EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number: 5383 Page:5 of 19 h�.. 1 I C 4 4 T._ '' '1 ri aC G Notes: 1. See LTG -2-C. 2. See LTG -4-C 3. See LTG -5-C 4. See LTG 6-C Items above regwre special documentahon s (hems marked with asterisk, see LTG -2 -C by others), (by others) EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation The HVAC System "Carrier 50HJ0007" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJQ007" includes Demand Control Ventilation per Standards Section 121. The HVAC System "Carrier 50HJQ007: Premium Eff' 2.23 BHP Supply Fan Motor has been specified. The HVAC System "Carrier 50HJQ006" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJQ006" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. The HVAC System "Carrier 50HJQ006!' includes Demand Control Ventilation per Standards Section 121. The HVAC System "Carrier 50HJ0006: Premium Eff' 1.54 BHP Supply Fan Motor has been specified. The HVAC System "Carrier 50HJQ005" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJ0005" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. The HVAC System "Carrier 50HJQ005" includes Demand Control Ventilation per Standards Section 121. The HVAC System "Carrier 50HJQ005: Premium Efr' 1.08 BHP Supply Fan Motor has been specified. The HVAC System "Carrier 50HJQ004" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500. The HVAC System "Carrier 50HJQ004" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant Authorized Signature or Stam Run Initiation Time: 02/25/07 18:06:12 Run Code: 1172455572 EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number: 5383 Page:5 of 19 PERFORMANCE CERTIFICATE OF COMPLIANCE Part3 of 3 PER Notes: 1. See LTG -2-C 2. See LTG -4-C'3. See LTG -5-C 4. See LTG -6-C Items above regwrespeaal documentagonRk dems marked with -asterisk, see LTG -2 -C b others (' y ) (by others) EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The HVAC System "Carrier 50HJQ004" includes Demand Control Ventilation per Standards Section 121. The HVAC System "Carrier 50HJQ004: Premium Eff 0.67 BHP Supply Fan Motor has been specified. I The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant Authorized Signature or Stam Run Initiation Time: 02/25/07 18:06:12 Ruh Code: 1172455572 EnergyPro 4.3 by. EnergySoft User Number. 3193 Job Number. 5383 Page:6 of 19 CERTIFICATE OF COMPLIANCE ENV-1-Cj PROJECT NAME DATE DUNES SHOP 3 4/2/2007 OPAQUE SURFACES # Surface Type I Area U -Fac. Insulation Cay. Cont. Act. Am. Tilt Cond' Status Joint Appendix I IV Reference I Location / Comments 1 Roof 1 707 0.036 R-30 R-0.0 0 0 New 02-A9 TENANT H 2 Wall 1571 0.074 R-19 R-0.0 270 90 New 09-A5 TENANT H 3 Wall 4041 0.074 R-19 R-0.0 180 1 90 New 09-A5 TENANT H 4 Roof 70 0.036 R-30 R-0.0 0 0 New 02-A9 TENANT H 5 Wall 190 0.074 R-19 R-0.0 90 90 New 09-A5 TENANT H 6 Wall 392 0.074 R-19 R-0.0 180 90 New 09-A5 TENANT H 7 Roof 1,146 0.036 R-30 R-0.0 0 0 New 02-A9 TENANT G 8 Wall 1921 0.074 R-19 R-0.01 270 90 New 09-A5 ITENANT G 9 Wall 33 0.074 R-19 R-0.0 90 90 New 09-A5 ITENANT G 10 Roof 1,146, 0.036 R-30 R-0.01 0 1 0 New 02-A9 ITENANT F 11 lWall 192, 0.074 R-19 R-0.0 270 1 90New Window 09-A5 ITENANT F 12 Wall 33 0.074 R-19 R-0.0 90 90 New 09-A5 TENANT F 13 Roof 1,14 0.036 R-30 R-0.0 0 0 New 02-A9 TENANT E 14 Wall 19 0.074 R-19 R-0.0 270 90 New 09-A5 TENANT E 15 Wall 33 0.074 R-19 R-0.0 90 90 New 09-A5 TENANT E 16 Roof 1,146, 0.036 R-30 R-0.0 0 0 New 02-A9 TENANT D 17 Wall 19 0.074 R-19 R-0.0 270 90 New 09-A5 TENANT D 18 lWall 33 - 0.074 R-19 R-0.0 90 90 New 09-A5 TENANT D 19 Roof 1,14 0.036 R-30 R-0.0 0 0 New 02-A9 TENANT C 20 lWall 19 0.074 R-19 R-0.0 270 1 90 1 New 09-A5 TENANT C N, E, A, R (New, Existing. Altered, Removed) FENESTRATION SURFACES IMore than or equal to 10,000 sq.fL of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U -factors from Standards Table 116A and B. Certificate shall be filed in the contractor's project office dudnq construction and in the building manaoefs office after construction # T e # Exterior Shade Type Window Overhang Left Fin Right Fin SHGC Hgt. Wd. ' Len. H t. LExt.RExt. Dist. Len. H I. Dist. Len. Hot U-Fac.t SHGC2 Act. Azm. Cond. Stat. Glazing Type 0.76 Location/ Comments 1 Window Right 6 None [Area 140 0.290 NI -1 0.37 COG 270 New PPG SOLARBAN 60 2 Clear TENANT H 2 Window Rear S 95 0.290 NI -1 0.37 COG 180 New PPG SOLARBAN 60 2 Clear TENANT H 3 Window Left E 107 0.290 NI -1 0.37 COG 90 New PPG SOLARBAN 60 2 Clear TENANT H 4 Window Rear S 107 0.290 NI -11 0.37 COG 180 New PPG SOLARBAN 60 2 Clear TENANT H 5 Window Right 140 0.290 NI -1 0.37 COG 270 New PPG SOLARBAN 60 2 Clear TENANT G 6 Window Right 140 0.290 NI -1 0.37 COG 270 New PPG SOLARBAN 60 2 Clear TENANT F 7 Window Right 140 0.290 NI -1 0.37 COG 270 New PPG SOLARBAN 60 2 Clear TENANT E 8 lWindow Right 140 0.290 NI -1 0.371 COG 270 New PPG SOLARBAN 60 2 Clear TENANT D 9 Window Right 140 0.290 NI -1 0.37 COG 270 New PPG SOLARBAN 60 2 Clear TENANT C 10 Window Right 140 0.290 NI -1 0.37 COG 270 New PPG SOLARBAN 60 2 Clear TENANT B 11 Window Front N 75 0.290 NI -1 0.37 COG 0ENew w SOLARBAN 60 2 Clear TENANT A 12 Window Front N 140 0.290 NI -1 0.37 COG 0w SOLARBAN 60 2 RG Clear TENANTA 13 Window Right 140 0.290 NI -1 0.37 COG 270 SOLARBAN 60 2 Clear ITFNANT A (1)U -factor Type: 116A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value. (2) SHGC Type: 1168 Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING # Exterior Shade Type Window Overhang Left Fin Right Fin SHGC Hgt. Wd. ' Len. H t. LExt.RExt. Dist. Len. H I. Dist. Len. Hot 1 None 0.76 2 None 0.76 3 None 0.76 4 None 0.76 5 None 0.76 6 None 0.76 7 None 0.76 8 None 0.76 9 None 0.76 10 None 0.76 11 None 0.76 12 None 0.76 13 None 0.76 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 fit, a ceiling height greater than 15 feet, and an LPD for general lighting of at least 0.5 W/fl2. See Section 143(c). If this box Is checked, ENV-" must be filled out when submitting under the Prescriptive Compliance Approach. EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number: 5383 Pace:7 of-, 9 CERTIFICATE OF COMPLIANCE ENV -1-C PROJECT NAME DATE DUNES SHOP 3 4/2/2007 OPAQUE SURFACES # Surface Type Area U -Fac. Insulation Cay. Cont. Act. Azm. Tilt Cond' Status Joint Appendix IV Reference Location / Comments 21 Wall 332. 0.074 R-19 R-0.0 90 90 New 09-A5 TENANT C 22 Roof 1146. 0.036 R-30 R-0.0 0 0 New 02-A9 TENANT B 23 Wall 19. 0.074 R-19 R-0.0 270 90 New 09-A5 TENANT B 24 Wall 33 0.074 R-19 R-0.0 90 90 New 09-A5 TENANT B 25 Roof 1,2381 0.036 R-30 R-0.0 0 0 New 02-A9 TENANT 26 Wall 657 0.074 R-19 R-0.01 0 90 New 09-A5 TENANT A 27 Wall 270 0.074 R-19 R-0.0 270 90 New 09-A5 TENANT A I FENESTRATION SURFACES More than or equal to 10,000 sq.fL of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default 1.11 -factors from Standards Table 116-A and B. Certificate shall be filed in the contractors Droiect office durina construction and in the building manacers office after construction Act. # lTvpe Area U-Fac.1 SHGC2 Am. Cond. Stat. Glazing TVpe Location/ Comments (1U -tactor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value. (2; SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING Window Overhang Left Fin Right Fin ## Exterior Shade Type SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. Hat. Dist. Len. H t. The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 1111:2, a ceiling height greater than 15 feet, and an LPD for general lighting of at least 0.5 Wfft2. See Section 143(c). If this box Is checked, ENV -4-C must be filled out when submitting under the Prescriptive Compliance Approach. I EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number. 5383 Page:8 of 19 1 CERTIFICATE OF COMPLIANCE MECH-1-C PROJECT NAME DATE DUNES SHOP 3 4/2/2007 Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments: SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation certificates and operatinq and maintenance information meet the requirements of Section 10-103(b) and Title 24 Part 6. STATEMENT OF COMPLIANCE ❑ MECH-2-A: Ventilation System Acceptance Document -Variable Air Volume Systems Outdoor Air Acceptance -Constant Air Volume Systems Outdoor Air Acceptance Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ❑ MECH-3-A: Packaged HVAC Systems Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ' ❑ MECH-4-A: Air -Side Economizer Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the commission do not require equipment testing but do require construction inspection. ❑ MECH-5-A: Air Distribution Acceptance Document Equipment requiring acceptance testing This test required If the unit serves 5,000 n2 of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend duds, replace ducts or replace the packaged unit. ❑ MECH-6-A: Demand Control Ventilation Acceptance Document Equipment requiring acceptance testing All new DCV controls installed on new or existing packaged systems must be tested. ❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document Equipment requiring acceptance testing All new VA fan volume controls installed on new or existing systems must be tested ❑ MECH-8-A: -Hydronic System Control Acceptance Document -Variable Flow Controls Applies to chilled and hot water systems. -Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header. -Supply Water. Temperature Reset Controls Applies to new constant flow drilled and hot water systems that have a design capacity greater than or equal to 500,000 B1Whr. -Water-loop Heat Pump Controls Applies to all new waterioop heat pump systems where the combined loop pumps are greater than 5 hp. -Variable Frequency Controls Applies to all new distribution pumps on new variable now chilled, hydronic heat pump or condenser water systems where the pumps motors are greater than 5 hp. Equipment requirin acceptance testing EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number: 5383 Page:9 of 19 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE DUNES SHOP 3 4/2/2007 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Contrbl Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone AC -1-12 AC -H1 AC-G 1 1 1 Reference on Plans or Specification 1 112(a) 0.77 HSPF 0.78 HSPF 0.77 HSPF 112(a) 13.0 SEER / 11.2 EER 13.0 SEER / 11.1 EER 13.0 SEER / 11.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121 b 177 cfm 177 cfm 286 cfm 121 c No No No 121 c Yes Yes Yes 121(c), 122(e) Programmable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Require Heating & Cooling Required 122 Auto Auto Auto 122(g) n/a n/a n/a 123 124 R-19.0 R-19.0 R-19.0 144 a & b n/a n/a n/a 144 a & b 21,735 btuh 28,106 btuh 34,352 btuh 144 a & b n/a n/a n/a 144 a & b 30,099 btuh 36,664 btuh 51,561 btuh 144 c Constant Volume Constant Volume Constant Volume 144 c 144 c Yes Yes Yes 144 d No No No 144 a Diff. Tem (integrated) Diff. Tem (Integrated) Diff. Temp (In te rated 144 Constant Temp Constant Temp Constant Tem 144 (f) Constant Temp Constant Temp Constant Temp 144 k No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/K in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes 9 System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF -1 for performance method duct sealing requirements. IYV 1 CJ 1 V rICLu - rur ou11U111 ue drunenl. use LJm I EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number. 5383 Page:10 of 19 1 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C (PROJECT NAME DATE DUNES SHOP 3 4/2/2007 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone AC -F AC -E AC -D 1 1 1 Reference on Plans or Specification 1 112(a) 0.77 HSPF 0.77 HSPF 0.77 HSPF 112(a) 13.0 SEER / 11.0 EER 13.0 SEER / 11.0 EER 13.0 SEER / 11.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121 b 286 cfm 286 cfm 286 cfm 121 c No No No 121 c Yes Yes Yes 121(c), 122(e) Programmable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122 n/a n/a n/a 123 124 R-19.0 R-19.0 R-19.0 144 a & b n/a n/a n/a 144 a & b 34,352 btuh 34,352 btuh. 34,352 btuh 144 a & b n/a n/a n/a 144 a & b 51,561 btuh 51,561 btuh 51,561 btuh 144 c Constant Volume Constant Volume Constant Volume 144 c 144 c Yes Yes Yes 144 d No No No 144 a Diff. Tem (Integrated) Diff. Tem (integrated) Diff. Tem (Integrated) 144 Constant Temp Constant Temp Constant Tem 144(f) Constant Temp Constant Temp Constant Temp 144 k No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Dud sealing is required for Prescriptive Compliance, see PERF -1 for performance method dud sealing requirements. , EnergyPro 4.3 by EnergySoft User Number. 3193 Job Number. 5383 Page: 11 of 19 1 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE DUNES SHOP 3 4/2/2007 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone AC -C I AC -B AC -A 1 1 1 Reference on Plans or Specification 1 112(a) 0.77 HSPF 0.77 HSPF 3.40 COP 112(a) 13.0 SEER / 11.0 EER 13.0 SEER / 11.0 EER 10.5 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121 b 286 cfm 286 cfm 310 cfm 121 c No No No 121 c Yes Yes Yes 121(c), 122(e) Programmable Switch Programmable Switch Pro rammable Switch 122(e) Heating & Cooling Required Heating & Cooling Require Heating & Cooling Required 122 Auto Auto Auto 122(g) n/a n/a n/a 123 124 R-19.0 R-19.0 R-19.0 144 a & b n/a n/a n/a 144 a & b 34,352 btuh 34,352 btuh 43,096 btuh 144 a & b n/a n/a n/a 144 a & b 51,561 btuh 51,561 btuh 66,073 btuh 144 c Constant Volume Constant Volume Constant Volume 144 (c 144 c Yes Yes Yes 144 d No No No 144 a Diff. Tem (Integrated) Diff. Tem (Integrated) Diff. Tem (integrated) 144 Constant Temp Constant Temp Constant Tem 144 (f) Constant Temp Constant Temp Constant Temp 144 (k) No No No 1: For each. central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes ff System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF -1 for performance method duct sealing requirements. �w 1 LVy r ILLy - r -V1 L71111U1114 VC4JQ1 411cnl UJ W Will EnergyPro 4.3 by EnergySoft User Number: 3193 Job Number: 5383 Page:12 of 19 1 MECHANICAL VENTILATION MECH-3-C PROJECT NAME DUNES SHOP 3 DATE 4/2/2007 PRESCRIPTIVE REHEAT I LIMITATION (Section 144(d)) MECHANICAL VENTILATION Section 121(b)2) AREA BASIS OCCUPANCY BASIS VAV MINIMUM A B C D E F G H I J K L M N ZONE/SYSTEM o yDa T ID' X V 0) N c �ac� ID m� T 3 0 a3 �'�� X> 0 0@ -A 3 �c ®� � a ID' 0 v � a0 N c 7' 3 a 3 A x 0 -n -n '� 3 m �yA O X 0 ai�< D < 0 'n .. N 3D7 Np on -r1 N �''p m v �' T 3W y X Q A x A0 O c w3c3i CD = 0y p T? m yv' »3 ^� D m' �. m D TENANT H 707 0.22 156 11.8 15.0 177 177 177 AC -H2 I Total 177 177 TENANT H 707 156 11.8 15.0 177 177 177 AC -H1 I Total 177 177 TENANT G 1,146 0.22 252 19.1 15.0 286 286 286 AC-G Total 286 286 TENANT F 1,146 0.22 252 19.1 15.0 286 286 286 AC -F Total 286 286 TENANT E 1,14E 0.22 252 19.1 15.0 286 286 286 AC -E Total 286 286 TEN ANT D 1,146 0.22 252 19.1 15.0 286 286 286 AC -D Total 286 286 TENANT C 1,146 0.22 252 19.1 15.0 286 286 286 AC -C Total 286 286 ENANT B 1,146 0.22 252 19.1 15.0 286 286 286 AC -13 Total 286 286 TENANT A 1,238 0.22 272 20.6 15.0 310 310 310 AC -A Total 310 310 C Minimum ventilation rate perSection 121 Table 121-A E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load for egress purposes fors aces without fixed seating. H Required Ventilation Air (REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G). I Must be greater than orequal to H or use Transfer Air column N to make up the difference. J Design fan supply ctm Fan CFM x 30%; or K Condition area (ft. sq.) x 04 cfm/ft. sq.; or L Maximum of Columns K J, K, or 300 cfm M This must be less than or equal to Column L and greater that orequal to the sum of Columns H + N. N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.3 by EnergySoft User Number: 3193 Job Number. 5383 Page: 13 of 19 MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-S-C PROJECT NAME DUNES SHOP 3 DATE 4/2/200� CHILLER AND TOWER SUMMARY System Type Distribution Type Efficiency Tons PUMPS Condition Status Ext. R -Val. Equipment Name Equipment Type Qty. Tot Qty GPM BHP Motor Eff. Drive Eff. Pump Control DHW / BOILER SUMMARY System Name Energy Factor or RE Standby Loss or Pilot TANK INSUL. System Name System Type Distribution Type Qty Rated Input Vol. (Gals.) Condition Status Ext. R -Val. System Name Fan Type Carrier 50HJ0004 Constant Volume Carrier 50HJQ005 Constant Volume Carrier 50HJ0006 Constant Volume Carrier 50HJQ007 Constant Volume none none Motor I Drive EnergyPro 4.3 by EnergySoft User Number: 3193 Job Number. 5383 Page: 14 of 19 1 MECHANICAL EQUIPMENT DETAILS Part 2 of 2 MECH-S-C MECHANICAL EQUIPMENT DETAILS Part 2 of 2 MECH-5-CI ENVELOPE MANDATORY MEASURES ENV -MM PROJECT NAME DATE DUNES SHOP 3 4/2/2007 DESCRIPTION Designer lEnforcement a§118(a) Installed Insulating Material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20, Chapter 4, Article 3. §118(c) All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. XJ §117(a) All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. F § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). FXI § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards. Manufactured fenestration products must be labeled for U -value according to NFRC procedures. X §118(e) Demising Walls in Nonresidential Buildings: The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value of no less than R713 between framing members. i. EnergyPro By EnergySoft User Number. User Job Number. 5383 Page: 17 of 19 1 MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM ROJECT NAME DUNES SHOP 3 DATE 4/2/2007 DESCRIPTION Designer Enforcement Equipment and Systems Efficiencies ❑X §111 Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply with the applicable standard. ❑ §11-5(a) Fan type central furnaces shall not have a pilot light FXI § 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be insulated in accordance with Standards Section 123. § 124 Air handling duct systems shall be installed and insulated in compliance with , Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards. Controls § 122(e) Each space conditioning system shall be installed with one of the following: ❑ § 122(e)1A Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch shall be capable of programming different schedules for weekdays and weekends and have program backup capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or § 122(e)1B An occupancy sensor to control the operating period of the system; or § 122(e)1C A 4 -hour timer that can be manually operated to control the operating period of the system. X❑ § 122(e)2 Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the system as required to maintain a setback heating and/or a setup cooling thermostat setpoint § 122(8) Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000 square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided with isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be setback or shut off independently of other isolation areas; and shall be controlled by a time control device as described above. ® § 122(a&b) Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or reduced to a minimum. R§ 122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to authorized personnel. § 112(b) Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the heating load can be met by the heat pump alone. EnergyPro By EnergySoft User Number: User Job Number: 5383 Page: 18 of 19 MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM NAME DUNES SHOP 3 DATE 4/2/2007 Description Designer Enforcement Ventilation FX§ 121(e) Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified on these plans. § 122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be provided on the outside air intakes and discharges of all space conditioning and exhaust systems. § 122(f) All gravity ventilating systems shall be provided with automatic or readily accessible ' manually operated dampers in all openings to the outside, except for combustion air openings. FXJ § 121(f)1 Air Balancing: The system shall be balanced in accordance with the National Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or Associated Air Balance Council (AABC) National Standards (1989); or JAI § 121(f)2 _ Outside Air Certification: The system shall provide the minimum outside air as shown on the mechanical drawings, and shall be measured and certified by the installing licensed C-20 mechanical contractor and certified by (1) the design mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the person with overall responsibility for the design of the ventilation system; or § 121(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous basis and displaying that quantity on a readily accessible display divice; or § 121(f)4 Another method approved by the Commission. Service Water Heating Systems § 113(b)2 If a circulating hot water system is installed, it shall have a control capable of automatically turning off the circulating pump(s) when hot water is not required. ❑ § 113(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit the outlet temperature to 110 degrees F. EnergyPro By EnergySoft User Number: User Job Number. 5383 Page: 19 of 19 CERTIFICATE OF COMPLIANCE (Part 1 of 4) LTG -1 -CI PROJECT NAME RETAIL 3 BUILDING DATE 10/20/2006 PROJECT ADDRESS LA QUI NTA Building Permit # PRINCIPAL DESIGNER - LIGHTING TELEPHONE SOTHOLROEUNG Checked by/Date DOCUMENTATION AUTHOR S.Y. Lee Associates TELEPHONE 818 244-4337 Enforcement Agency Use GENERAL INFORMATION DATE OF PLANS BUILDING CONDITIONED FLOOR AREA 10/19/06 10,200 sq.Ft. T�ONE15 BUILDING TYPE ® NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTELIMOTEL GUEST ROOM ® CONDITIONED SPACES ❑ UNCONDITIONED SPACES ❑ INDOOR & OUTDOOR SIGNS PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION METHOD OF LIGHTING ® COMPLETE BUILDING ❑ AREA CATEGORY ❑ TAILORED ❑ PERFORMANCE COMPLIANCE ❑ COMMON LIGHTING STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building lighting requirements. The documentation preparer hereby certifies that the documentation is accurate and complete. DOCUMENTATION AUTHORSIGNATURE D E SOTHOLROEUNG i The Principal Lighting Designer hereby certifies that the proposed building design represented it this set of construction d to is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitte this permit application. The proposed building has been designed to meet the lighting requirements contained in Sections 110, 130 - 132, 146, 148 & 149 of Title 24, Part 6. ❑ The plans & specifications meet the requirements of Part 6 (Sections 10-103a). ❑ The installation certificates meet the requirements of Part 6 (10-103a 3). ❑ The operation & maintenance information meet the requirements of Part 6 (10-103c). Please Check One: (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer or electrical engineer, or I am a licensed archite ❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this docum as the person responsible for its preparation; and that I am a licensed contractor performing this work. ❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538 and 6737.1. PRINCIPAL LIGHTING DESIGNER - NAME SIGNATURE JDAYE SOTHOL ROEUNG !- 4 % 1 02 - LIGHTING MANDATORY MEASURES Indicate location on plans of Note Block for Mandatory Measure LIGHTING COMPLIANCE FORMS & WORKSHEET Check box if worksheet is included ®LTG -1-C, Parts 1 of 4 and 2 of 4Certificate of Compliance. Part 1 of 4 and 2 of 4 are required for all submittals 0LTG-1-C, Part 3 of 4: Certificate of Compliance. Part 3 of 4 submittal is required only if Control Credits are claimed ®LTG -1-C, Part 4 of 4: Certificate of Compliance. Part 4 of 4 submittal is required when lighting controls are installe ®LTG -2-C: Indoor Lighting Schedule ❑LTG -3-C: Portable Lighting Worksheet ❑LTG -4-C: Lighting Controls Credit Worksheet ®LTG -5-C: Indoor Lighting Power Allowance ❑LTG -6-C: Tailored Method Worksheet ❑LTG -7-C: Room Cavity Ratio Worksheet []LTG -8-C: Common Lighting Systems Method Worksheet ❑LTG -9-C: Line Voltage Track Lighting Worksheet EnergyPro 4.2 by EnergySoft User Number. 3193 Job Number. Pagel of 6 ents I with 119, CERTIFICATE OF COMPLIANCE (Part 2 of 4) LTGA dj PROJECT NAME RETAIL 3 BUILDING DATE 10/20/2006 INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES INSTALLED WATTS INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C) —8,834 PORTABLE LIGHTING (From LTG -3-C) 0 LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG -4-C) 0 CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 8,834 INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0 LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0 UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0 ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES ❑X COMPLETE BUILDING METHOD (From LTG -5-C) ❑ AREA CATEGORY METHOD (From LTG -5-C) ❑ TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER ALTERNATE COMPLIANCE ❑ PERFORMANCE METHOD ❑ COMMMON LIGHTING SYSTEM (From LTG -8-C) ALLOWED WATTS 15,300 ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C) o IMANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS CONTROL LOCATIOI (Room #) I CONTROL IDENTIFICATION EnergyPro 4.2 by EnergySoft NOTE T FIELD CONTROL TYPE (Auto Time Switch, Dimming, etc.) SPACE CONTROLLED Check if DaylightinG NOTES TO FIELD - For Building Department Use Only EnergyPro 4.2 by EnergySoft User Number. 3193 Job Number. Paget of 6 CERTIFICATE OF COMPLIANCE (Part 4 of 4) LTG-1- PROJECT NAMERETAIL 3 BUILDING ri0/20/2006 Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptan tests for lighting systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that require an acceptance test. If all equipment of a certain type requir a test, list the equipment description and the number of systems to be tested in parentheses. The N number designates the Section in the Appendix of the Nonresidential ACM Manual that describes th test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, desi professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments: Before an occupancy permit is granted for a newly constructed building or space, or a new lighting system system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building departme that: A. Certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of 10-103(b) and Title 24 Part 6. Test Description Test Performed By: ❑ LTG-2-A: Lighting Control Acceptance Document - Occupancy Sensor Acceptance - Manual Daylight Controls Acceptance - Automatic Time Switch Control Acceptance Equipment requiring acceptance testing ❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document Equipment requiring acceptance testing i EnergyPro 4.2 by EnergySoft User Number. 3193 Job Number. Page3 of 6 JINDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG -2 -CI 1PROJECT NAME RETAIL 3 BUILDING DATE 10/20/2006 INSTALLED LIGHTING POWER FOR CONDITIONED SPACES Lurninaire Lamps/Ballasts Installed Wafts pe Descdpfion PAGE TOTAL 8 834 BUILDING TOTAL (sum of all pages) 8,834 PORTABLE LIGHTING (From LTG.3-C)� CONTROL CREDIT (From LTG -4-C) ADJUSTED ACTUAL WATTS 8 834 EnergyPro 4.2 by EnergySoft User Number. 3193 Job Number. Pace:4 of 6 1 INDOOR LIGHTING POWER ALLOWANCE I LTG -5 - PROJECT NAME RETAIL 3 BUILDING rDATE I 10/20/2006 BUILDING CATEGORY (From Section 146 Table 146-13) WATTS COMPLETE ALLOWED PER SF BLDG. AREA WATTS Com BldgRetail and Wholesale 1.50 10 200 15 300 AREA CATEGORY METHOD - CONDITIONED SPACES AREA CATEGORY (From Section 146 Table 146-0) WATTS AREA ALLOWED PER SF (SF) WATTS PAGE TOTAL BUILDING TOTAL D AREA WATTS TAILORED METHOD - CONDITIONED SPACES TOTAL ALLOWED WATTS (From LTG -6-C or from computer run. UNCONDITIONED SPACES Complete Building and Area Catagory Methods Category (From Section 146 Table 146 -B&C) WATTS PER SF AREA (SF) ALLOWED WATTS PAGE TOTAL BUILDING TOTAL AREA WATTS TAILORED METHOD - UNCONDITIONED SPACES TOTAL UNCONDITIONED SPACES ALLOWED WA (From LTG -5-C and LTG -6-C) EnergyPro 4.2 by EnergySoft User Number. 3193 Job Number. Pages of 6 IGHTING MANDATORY MEASURES LTG -M PROJECT NAME RETAIL 3 BUILDING DATE 10/20/2006 DESCRIPTION Designer Enforcement 131(d)iFor every floor, all interior lighting systems shall be equipped with a separate automatic control to shut off the lighting. This automatic control shall meet the requirements Section 119 and may be an occupancy sensor, automatic time switch, or other devi e capable of automatically shutting off the lighting. 0 131(d)20verride for Building Lighting Shut-off. The automatic building shut-off system is provided with a manual, accessible override switch in sight of the lights. The area of override Is not to exceed 5,000 square feet 0 119(h) Automatic Control Devices Certified: All automatic control devices specified are certified, all alternate equipment shall be certified and installed as directed by the manufacturer. 0 111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for the project are certified and listed in the Directory. All Installed fixtures shall be certified. 132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three lamp fluorescent fixtures are tandem wired with two lamp ballasts where required by Standards Section 132; or all one and three lamp fluorescent fixtures are specified with electronic high -frequency ballasts and are exempt from tandem wiring requirements. 131(a) Individual Room/Area Controls: Each room and area in this building is equipped with a separate switch or occupancy sensor device for each area with floor -to - ceiling walls. 0 131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 square feet and more than 0.8 watts per square foot of lighting load shall be controlled with bl-level switching for uniform reduction of lighting within the room. rVI 131(c) Daylight Area Control: All rooms with windows and skylights that are greater than 250 square feet and that allow for the effective use of daylight in the area shall have 50% of the lamps in each daylit area controlled by a separate switch; or the effective use of daylight cannot be accomplished because the windows are continuously shaded by a building on the adjacent lot. Diagram of shading during different times of the year is included on plans. 131(e) Display Lighting. Display lighting shall be separately switched on circuits that .are 20 amps or less. EnergyPro 4.2 by EnergySoft User Number. 3193 Job Number. Pages of 6 [CERTIFICATE OF COMPLIANCE (Part 1 of 2) OLTG-1-d PROJECT NAME DATE BLDG 3 RETIAL BLDG 1/11/2007 PROJECT ADDRESS LA QUINTA Building Permit # PRINCIPAL DESIGNER - LIGHTING TELEPHONE SOTHOLROEUNG Checked by/Date DOCUMENTATION AUTHOR S.Y. Lee Associates TELEPHONE (818)2 44337 Enforcement Agency Use GENERAL INFORMATION DATE OF PLANS LIGHTING ZONE 10/19/06 rUTDOOR ❑ LZ1 ❑ LZ2 ® LZ3 ❑ LZ4 FUNCTION TYPE ® OUTDOOR LIGHTING ❑ OUTDOOR SIGNS ❑ INDOOR SIGNS PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION STATEMENT OF COMPLIANCE This Certificate of Compliance lists the outdoor lighting system specifications need to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building lighting requirements. The documentation preparer hereby certifies that the documentation is accurate and complete. DOCUMENTATION AUTHOR SIGNATURE DAT SOTHOLROEUNG1-1VW07 The Principal Lighting Designer hereby certifies that the proposed outdoor lighting and signs design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building has been designed to meet the lighting requirements contained in Sections 110, 119, 130 through 132, and 146,and 149 of Title 24, Part 6. Please Check One: (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) (A I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this "document as the person responsible for its and that I licensed in the State California preparation; am of as a civil engineer or electrical engineer, or I am a licensed architect. ❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. ❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538 and 6737.1. PRINCIPAL LIGHTING DESIGNER -NAME SIGNATURE LIC.# SOTHOLROEUNG JDAz�% LIGHTING COMPLIANCE FORMS & WORKSHEET Check box if worksheet is included ®OLTG-1-C: Certificate of Compliance. Required on plans for all submittals for outdoor lighting. Part 2 of 2 may be incorporated in schedules or tt Either LTG -1 -C or OLTG-1-C may be used for signs as follows: 1. Use LTG -1 -C if the project consists solely of indoor signs. 2. Use LTG -1 -C ifthe project consists of indoor lighting, outdoor or indoor signs, but no other outdoor lighting. 3. Use OLTG-I-C if the project consists solely of outdoor signs. 4. Use OLTG-1-C if the project consists of outdoor lighting, outdoor or indoor signs, but no other indoor lighting. ®OLTG-2-C: LIGHTING COMPLIANCE SUMMARY. Applicable parts required for ALL outdoor lighting allowances (Except Signs). 99OLTG-3-C: AREA CALCULATIONS WORKSHEET. Applicable parts required for all outdoor area calculations. ❑OLTG-4-C: SIGN LIGHTING COMPLIANCE. Required for all internally and externally illuminated signs, for both indoor and outdoor signs. EnergyPro 4.2 by EnergySoft User Number. 3193 Job Number. Pages of 10 e plans. CERTIFICATE OF COMPLIANCE (Part 2 of 2) OLTG-1-0 PROJECT NAME DATE BLDG 3 RETIAL BLDG 1 1/11/2007 1-1-ghting Schedules on Plans Show that Outdoor Lighting Meets Allowed Li-ghting Power 0 Lighting power allowance for general site illumination on OLTG-2-C Part 1 of 4 Not Applicable Q Lighting power allowance for local ordinances or for security multipliers on OLTG-2-C Part 2 of 4 Not Applicable 0 Lighting power allowances for specific applications, other than vehicle service stations with canopies on OLTG-2-C Part 3 of 4 Not Applicable Q Lighting power allowances for vehicle service station canopies on OLTG-2-C part 4 of 4 Not Applicable QX Sign lighting compliance on OLTG-4-C Not Applicable Mandatory Measures on Plans Show that Outdoor Licihtin-q Meets Outdoor Lightinct Controls And Eauloment Q Installed lighting power has been determined in accordance with Section 130(c)1 Not Applicable Q All permanently installed luminaires with lamps rated 100 Watts either have a lamp efficacy of at least 60 lumins per Watt or are controlled by a motion sensor per Section 132(a) Not Applicable Q All Luminaires with lamps rated greater than 175 Watts in hardscape area, including parking lots, building entrances, canopies, a outdoor sales areas meet the Cutoff Requirements of Section 132(b) Not Applicable Q F] All permanently installed outdoor lighting meets the control requirements of Section 132(c)1 Not Applicable Q Building facades, parking lots, garages, canopies, and outdoor sales areas meet the Multi -Level Lighting Requirements of Sectio Not Applicable MANDATORY AUTOMATIC CONTROLS CONTROL LOCATIOI I CONTROL CONTROL TYPE NOTETO (Room #) IDENTIFICATION (Auto Time Switch, Dimming, etc.) AREA CONTROLLED FIELD EnergyPro 4.2 by EnergySoft User Number. 3193 Job Number. Page.7 of 10 d all 132(c) SLIGHTING COMPLIANCE SUMMARY (Part 1 of 4) OLTG-2-a Project Name Date BLDG 3 RETIAL BLDG 1/11/2007 LIGHTING POWER ALLOWANCES - GENERAL SITE ILLUMINATION - able 147-A Allotted Watts Luminaire Lamps/Ballasts Installed Watts A B C D E F G H I J K L IM I N O Lighting Application Category (Table 147•A) 71 mo��g i'� � A o� v D_ o WW na m o a Description w me m' ° c ��m m"o csi 33 m �� d01 ff v 0 cd 3d 0» �m r 3°1 m �� �° ' n n v e� 33 m e �o �' �' m x a Z� 01 SIDEWALK 52 4.00 2,100 D (1 ) 42w Compact Fluorescen n /Quad 4 in Elec 11 42 1.0 46.01 X 11 59 E 50w Metal Halide M50 1 50 1.0 58.0 X 1 1, 04 Total Allotted Watts 2,100 Total Installed Watts 1,64 EnergyPro 4.2 by Energysoft User Number. 3193 Job Number. Page•8 of 10 JILLUMINATED AREA CALCULATION WORKSHE$Tart 2 of 5) OLTq771 PROJECT NAME DATE BLDG 3 RETIAL BLDG 1/11/2007 A. Hardsca a Method ii Hardsca a for driveways, site roads sidewalks walkways and bikeways A B List Specific Application able 147-A Lengt o 25 wide pat incorporating much ,f25' f he paved area as ossible. SIDEWALK 525 Checklist ❑ Section 147 (c)1 B - Each portion of all illuminated areas has been assigned only one lighting application, and the applications are consistent with actual use of the C:] Section 147 (c)1 B Method ii - General illumination areas for site roadway, driveway, sidewalk, walkway, or bikeway includes only those illuminated areas that are in bounds of the Application and includes a 25 foot wide area rennin alon the axis of the path of travel and much of the paved area as possible. B. Buildinq Entrances without Cano lies A B C Width of Door plus 3 feet on each side Sma er o 8 ft or distance tot e edge of th property line Area sf) (A x ) Checklist ' Section 147 (c)1 B - Each portion of all illuminated areas has been assigned only one lighting application, and the applications are consistent with the actual use of areas. Section 147 (c)1 A - General illumination areas includes only those illuminated areas that in the bounds of the Application and are with a square pattern around a luminaire that is six times the luminaire mounting height, with the luminaire in the middle of the pattern, less any areas that are within buildings, under canopies, bey property lines, or obstructed by a signs or other structures. I EnergyPro 4.2 by EnergySoft User Number. 3193 Job Number. Page9 of 10 reas. the nd