08-0401 (RC) Revision 1 Title 24TITLE 24 REPORT
Title 24 Report for:
Heavenly Hair Salon
79-710 Highway 111, Suite 105
La Quinta, Ca 92253
Project Designer:
McKinzie Electrical Contractors
79-607 Country Club Drive
Bermuda Dunes, Ca 92203
(760) 360-0728
Report Prepared ,Py
Tim Scott CITY OF �,q QUIIVT
Scott Design & Titl 2RUILDING & SAFETY DEPT,
77085 Michigan Dr. APP
Palm Desert, CA 92211 FOR Cp RAVED
(760) 200-4780 TIS
BY
Job Number:
Date:
3/13/2008
EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
orized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.4 by EnergySoft Job Number: User Number: 6712
TABLE OF CONTENTS
dh
Cover Page
Table of Contents
Form LTG -1-C Certificate of Compliance
Form LTG -2-C Indoor Lighting Schedule
Form LTG -3-C Portable Lighting Worksheet
Form LTG -4-C Lighting Controls Credit Worksheet
Form LTG -5-C. Indoor Lighting Power Allowance
Form LTG -7-C Room Cavity Ratio Worksheet
Form LTG -MM Lighting Mandatory Measures
1
2
3
7
8
9
10
11
12
EnergyPro 4.4 by EnergySoft Job Number: User Number: 6712
r
L
CERTIFICATE OF COMPLIANCE (Part 1 of 4) LTG -1 -C
PROJECT NAME
DATE
Heavenly Hair Salon
3/13/2008
ROJECT ADDRESS
79-710 Highway 111, Suite 105 La Quinta
_.
PRINCIPAL DESIGNER - LIGHTING
TELEPHONE
Building Permit #
McKinzie Electrical Contractors
(760) 360-0728
-
DOCUMENTATION AUTHOR
TELEPHONE
Checked by/Date
Scott Design & Title 24
(760) 200-4780
Enforcement Agency Use
GENERAL INFORMATION
DATE OF PLANS
BUILDING CONDITIONED FLOOR AREA
CLIMATE ZONE
1,200 Sq.Ft.
1 10
BUILDING TYPE 0 NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL F—] HOTEL/MOTEL GUEST ROOM
CONDITIONED SPACES ❑ UNCONDITIONED SPACES ❑ INDOOR & OUTDOOR SIGNS
PHASE OF CONSTRUCTION O NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION
METHOD OF LIGHTING F--1COMPLETEBUILDING a AREA CATEGORY F—] TAILORED ❑ PERFORMANCE
COMPLIANCE ❑ COMMON LIGHTING
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24,
Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building lighting requirements.
The documentation preparer hereby certifies that the documentation i accurate and complete.
DOCUMENTATION AUTHOR
SIGN TU
Tim Scott
TDAT'E
LI--!)
The Principal Lighting Designer hereby certifies that the proposed building design represented in this set of construction documents
is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with
this permit application. The proposed building has been designed to meet the lighting requirements contained in Sections 110, 119,
130 - 132, 146, 148 & 149 of Title 24, Part 6.
,efhe plans & specifications meet the requirements of Part 6 (Sections 10-103a).
4he installation certificates meet the requirements of Part 6 (10-103a 3).
F] -'The operation & maintenance information meet the requirements of Part 6 (10-103c).
Please Check One: (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.)
❑ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person
responsible for its preparation; and that I am licensed in the State of California as a civil engineer or electrical engineer, or I am a licensed architect.
❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document
as the person responsible for its preparation; and that I am a licensed contractor performi is rk.
0/1'affirm that I am eligible under the exemption to Division 3 of the Business an/Pressions de to sign this document because it pertains to a
structure or type of work described as exempt pursuant to Business and Pro Cc Sections 5537, 5538 and 6737.1.
PRINCIPAL LIGHTING DESIGNER - NAME
SIGNAT E
D
LIC. #
McKinzie Electrical Contractors
LIGHTING MANDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures
14
LIGHTING COMPLIANCE FORMS & WORKSHEETS Check box if worksheet is included
®LTG -1-C, Parts 1 of 4 and 2 of 4: Certificate of Compliance. Part 1 of 4 and 2 of 4 are required for all submittals
®LTG -1-C, Part 3 of 4: Certificate of Compliance. Part 3 of 4 submittal is required only if Control Credits are claimed
®LTG -1-C, Part 4 of 4: Certificate of Compliance. Part 4 of 4 submittal is required when lighting controls are installed
®LTG -2-C: Indoor Lighting Schedule
®LTG -3-C: Portable Lighting Worksheet
IR LTG -4-C: Lighting Controls Credit Worksheet
DO LTG -5-C: Indoor Lighting Power Allowance
LTG -6-C: Tailored Method Worksheet
LTG -7-C: Room Cavity Ratio Worksheet
LTG -8-C: Common Lighting Systems Method Worksheet
❑LTG -9-C: Line Voltage Track Lighting Worksheet
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:3 of 13
4
CERTIFICATE OF COMPLIANCE (Part 2 of 4) LTG -1 -C
PROJECT NAME
Heavenly Hair Salon
DATE
3/13/2008
INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C)
PORTABLE LIGHTING (From LTG -3-C)
LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG -4-C)
CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C)
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C)
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -6-C)
❑X AREA CATEGORY METHOD (From LTG -5-C)
❑ TAILORED METHOD (From.LTG-5-C)
PERFORMANCE METHOD
ALLOWED LIGHTING POWER
INSTALLED
WATTS
1,051
0
14
1,037
0
0
0
ALLOWED
WATTS
2,040
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C) 0
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION
(Room #)
V—
CONTROL
IDENTIFICATION
DC
CONTROLTYPE
Time Switch, Dimming, etc.)
5 &p4j
SPACE CONTROLLED
Check if
NOTE TO
FIELD
NOTES TO FIELD - For Building
Department Use Only
EnergyPro 4.4 by EnergySoft
User Number: 6712 Job Number:. Page:4 of 13
CERTIFICATE OF COMPLIANCE (Part 3 of 4) LTGT
PROJECT NAME
1111, Heavenly Hair Salon
CONTROL
IDENTIFICATION
CONTROLTYPE
(Occupant, Daylight, Dimming, etc.)
Occ Sensor - — 250 sqft
DATE
3/13/2008
1
NOTE TO
FIELD
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:5 of 13 1
4
4
CERTIFICATE OF COMPLIANCE (Part 4 of 4) LTG -1]-C
PROJECT NAME
Heavenly Hair Salon
DATE
3/13/2008
esigner:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance
tests for lighting systems. The designer is required to check the boxes by all acceptance tests that
apply and list all equipment that require an acceptance test. If all equipment of a certain type requires
a test, list the equipment description and the number of systems to be tested in parentheses. The NJ
number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the
test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design
professional or an agent selected by the owner). Since this form will be part of the plans, completion
of this section will allow the responsible party to budget for the scope of work appropriately.
Building Departments:
Before an occupancy permit is granted for a newly constructed building or space, or a new lighting
system system serving a building or space is operated for normal use, all control devices serving the
building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
In addition a Certificate of Acceptance, LTG -1-A, Forms shall be submitted to the building department
that:
A. Certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of§ 10-103(b) and Title 24 Part 6.
Test Description
Test Performed By:
❑ LTG -2-A: Lighting Control Acceptance Document
- Occupancy Sensor Acceptance
- Manual Daylight Controls Acceptance
- Automatic Time Switch Control Acceptance
Equipment requiring acceptance testing y7 E I? tc7e�
.� Y CLEC. &)-t l .
❑ LTG -3-A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:6 of 13 1
INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG -2-C
r
L_
NAME
Heavenlv Hair Salon
NSTALLED LIGHTING POWER FOR
DATE
3/13/2008
Luminaire
Lamps/Ballasts
Installed Watts
C
D
E
F
G
H
I
J
Name
Type Description
-+cri
-03
CD
--Z
333
�y�
-.�
`" m °
m��
3m
'O 1 N
c d c
3•x,3
��CD
-.�
o
c
3��
_ N
fD
v
�n
cn
-
r
C Z
3. c
LU
- fD
w
y
X m
- N M
a
(2) 4 ft Fluorescent T8 Rapid Start
F32T8
2
32
1.0
70.0
X
1
70
(3) 4 ft Fluorescent T8 Rapid Start
3
32
2.0
109.0
X
9
981
PAGE TOTAL 1 051
BUILDING TOTAL (sum of all pages) 1,051
PORTABLE LIGHTING (From LTG -3-C) D
CONTROL CREDIT (From LTG -4-C) 14
ADJUSTED ACTUAL WATTS 1 037
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:7 of 13 1
f
L
f
L
PORTABLE LIGHTING WORKSHEET LTG -3-C
PROJECT NAME
Heavenly Hair Salon
DATE
3/13/2008
TABLE 1 - PORTABLE LIGHTING NOT SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE FEET
A
B
C
D
ROOM #
OR ZONE ID
DEFAULT
W/s ft
AREA
SF
TOTAL WATTS
B X C
F
G
ROOM #
OR ZONE ID
PORTABLE LIGHTING
Description.
# OF
FIXT.
LUMIN. TASKTOTAL
WATTS PER AREAAREA
FIXTURE (SF)
(SF)
(D x E)
TOTAL
WATTS
(C x E)
Tenant Improvement
1 2001,200
TOTAL
0
0
ITABLE 2 - PORTABLE LIGHTING
SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE FEET
I
BUILDING TOTAL
1,200
0
A
B
C DEAREAS
F
G
ROOM #
OR ZONE ID
PORTABLE LIGHTING
Description.
# OF
FIXT.
LUMIN. TASKTOTAL
WATTS PER AREAAREA
FIXTURE (SF)
(SF)
(D x E)
TOTAL
WATTS
(C x E)
Tenant Improvement
1 2001,200
TOTAL
1,200
0
TABLE 3 - PLANS SHOW PORTABLE LIGHTING IS NOT REQUIRED FOR OFFICE AREAS > 250 SQUARE FEET
ROOM # TOTAL AREA
OR ZONE ID (SF)
TOTAL 0
BUILDING SUMMARY - PORTABLE LIGHTING
Designer needs to provide detailed documentation that the lighting
level provided by the overhead lighting meets the needs of the
space. The details include luminaire types and mounting locations
relative to work areas.
BUILDING SUMMARY
TOTAL AREA (SF)
(FROM TABLES 1+2+3)
TOTAL WATTS
BUILDING TOTAL
1,200
0
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:8 of 13
LIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG -4-C
CONTROL CREDITS FOR CONDITIONED SPACES
OJECT NAME DATE
Heavenly Hair Salon 3/13/2008
A
B
C
D
E F G
H
I
J
ROOM #
ZONE ID
CONDITIONED
AREAS
LIGHTING
CONTROL
DESCRIPTION
PLAN
REF.
ROOM
AREA
(SF)
DAYLIGHTING
WATTS OF
CONTROL
LIGHTING
LIGHTING
ADJUST.
FACTOR'
CONTROL
CREDIT
WATTS
(H X 1)
WINDOW
WALL
RATIO
GLAZING
VLT
SKYLIGHT
EFFECTIVE
APERTURE'
Tenant Improvement
Occ Sensor - <= 250
sqft
1200
70
0.20
14
1) From Equation 146-A
2) From Table 146-A
PAGE TOTAL
BUILDING TOTAL
Enter in LTG -2-C: Lighting Control Credit
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Paoe:9 of 13 1
]INDOOR LIGHTING POWER ALLOWANCE LTG -5-C
4
PROJECT NAME
Heavenly Hair Salon
DATE
3/13/2008
LLOWED LIGHTING POWER Choose One Method
COMPLETE BUILDING METHOD - CONDITIONED SPACES
ALLOWED
WATTS
WATTS
PER SF
COMPLETE
BLDG. AREA
ALLOWED
WATTS
BUILDING CATEGORY (From Section 146 Table 146-B)
AREA CATEGORY METHOD - CONDITIONED SPACES
AREA
(SF)
ALLOWED
WATTS
AREA CATEGORY (From Section 146 Table 146-C)
WATTS
PER SF
Retail Sales Wholesale
1.70
1,200
2,040
PAGE TOTAL
BUILDING TOTAL
D
D
D
AREA
D
WATTS
TAILORED METHOD - UNCONDITIONED SPACES
TOTAL UNCONDITIONED SPACES ALLOWED WATTS
(From LTG -5-C and LTG -6-C)
0
D
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 10 of 13
PAGE TOTAL
BUILDING TOTAL
1,200
2,040
1 ,200
AREA
2,040
WATTS
TAILORED METHOD - CONDITIONED SPACES
TOTAL ALLOWED WATTS D
(From LTG -6-C or from computer run.)
4
UNCONDITIONED SPACES
Complete Building and Area Catagory Methods
Category (From Section 146 Table 146 -B&C)
WATTS
PER SF
AREA
(SF)
ALLOWED
WATTS
PAGE TOTAL
BUILDING TOTAL
D
D
D
AREA
D
WATTS
TAILORED METHOD - UNCONDITIONED SPACES
TOTAL UNCONDITIONED SPACES ALLOWED WATTS
(From LTG -5-C and LTG -6-C)
0
D
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 10 of 13
ROOM CAVITY RATIO WORKSHEET (RCR>=3.5) LTG -7-C
PROJECT NAME Heavenly Hair Salon FOR ENFORCEMENT AGENCY USE ONLY
NTATION AUTHOR
DATE (PLAN CHECK BY IDATE
A
B
C
D
E
F
Room
Name
Task/Activity
Description
Room
Length (L)
ft
Room
Width (W)
ft)
Room Cavity
Height (H)
(ft)
Room Cay. Ratio
5xHx(L+W)
/(LxW)
A
B
C
D
E
F
Room
Name
Task/Activity
Description
Room
Area (A)
M
Room
Perimeter (P)
(ft)
Room Cavity
Height (H)
(ft)
Room Cay. Ratio
2.5 x H x P
/A
4.4 by EnergySoft User Number: 6712 Job Number: Page: 11 of 13
4
1
1
ILIGHTING MANDATORY MEASURES LTG -MM
PROJECT NAME
DATE
Heavenly Hair Salon
3/13/2008.
DESCRIPTION
Designer
Enforcement
§131(d)1 For every floor, all interior lighting systems shall be equipped with a separate automatic
control to shut off the lighting. This automatic control shall meet the requirements of
Section 119 and may be an occupancy sensor, automatic time switch, or other device
capable of automatically shutting off the lighting.
X] §131(d)20verride for Building Lighting Shut-off: The automatic building shut-off system is
provided with a manual, accessible override switch in sight of the lights. The area
of override is not to exceed 5,000 square feet.
X] §119(h) Automatic Control Devices Certified: All automatic control devices specified are
certified, all alternate equipment shall be certified and installed as directed by the
manufacturer.
X❑ §111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for
the project are certified and listed in the Directory. All installed fixtures shall be
certified.
X] §132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three -
lamp fluorescent fixtures are tandem wired with two lamp ballasts where required
by Standards Section 132; or all one and three lamp fluorescent fixtures are
specified with electronic high -frequency ballasts and are exempt from tandem
wiring requirements.
y
§131(a) Individual Room/Area Controls: Each room and area in this building is equipped
with a separate switch or occupancy sensor device for each area with floor -to -
ceiling walls.
RX §131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100
square feet and more than 0.8 watts per square foot of lighting load shall be
controlled with bi-level switching for uniform reduction of lighting within the room.
§131(c) Daylight Area Control: All rooms with windows and skylights that are greater than
250 square feet and that allow for the effective use of daylight in the area shall
have 50% of the lamps in each daylit area controlled by a separate switch; or the
effective use of daylight cannot be accomplished because the windows are
continuously shaded by a building on the adjacent lot. Diagram of shading during
different times of the year is included on plans.
® §131(e) Display Lighting. Display lighting shall be separately switched on circuits that
are 20 amps or less.
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 12 of 13
LIGHTING INSPECTION CHECKLIST LTG -
PROJECT NAME
Heavenlv Hair Salon
INSPECTION DATE
3/13/2008
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 13 of 13 1
FIXTURE
CODE
TYPE
DESCRIPTION
LAMP
TYPE
LAMP
QUANT.
NUMBER OF
FIXTURES
WATTS PER
FIXTURE
FIELD NOTES
2 4 ft Fluorescent T8 Rapid Start
F32T8
2
1
70.0
3 4 ft Fluorescent T8 Rapid Start
F32T8
3
9
109.0
Type DESCRIPTION
MH METAL HALIDE
INC INCANDESCENT
INC/LV INCANDESCENT LOW VOLTAGE
CFL COMPACT FLUORESCENT
FL FLUORESCENT
OTHER
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 13 of 13 1