07-3066 (RC) Revision 2 Certificate of Compliance.. i
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1
PROJECT NAME ------------ — �-
-----i--
—
DATE -- —
Komar _Desert _C_ enter - Bld_g H_— _
—__
Sq.Ft.
12/4/2007
PROJECT ADDRESS
NONRESIDENTIAL HIGH RISE RESIDENTIAL
NEW CONSTRUCTION L7 ADDITION lJ
HOTEUMOTEL GUEST ROOM
EXISTING + ADDITION/ALTERATION
consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this
Hway 111 and Jefferson CA
1. 1 hereby affirm that I am eligible under the provisions of Division I ahMl INIG "A sE)ERTq
sign this document as the person responsible for its preparation; ar d that I a li
_L_a_Q_u_inta,
!PRINCIPAL DESIGNER - ENVELOPE
_
!TELEPHONE
i,
J u 2. I affirm that I am eligible under the provisions of Division 3 of the Business and rofessions ode ec ion
Building Permit #
SGPA Architecture Planning
i 619.297.0131
Code Sections 5537, 5538, and 6737.1. (These sections of the Business an Profs Cod are printed in
full in the Nonresidential Manual.) ---
00CUMENTATION AUTHOR
ITELEPHONE
Required F
Checked by/Date
LSW Engineers California, Inc. _
(858) 268_3224
Indicate location on plans of Note Block for Manda ory Measures 'Lig- ing Compliance Not In The Scope Of
1 Enforcement Agency Use
GENERAL INFORMATION
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DATE OF PLANS
—---------
IBUILDING CONDITIONED FLOOR AREA
— i — — -----10,194
Sq.Ft.
(CLIMATE ZONE
15
BUILDING TYPE �iC�
PHASE OF CONSTRUCTION
NONRESIDENTIAL HIGH RISE RESIDENTIAL
NEW CONSTRUCTION L7 ADDITION lJ
HOTEUMOTEL GUEST ROOM
EXISTING + ADDITION/ALTERATION
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
SI J—
DATE
Chris French
/-2 vy oy
_ — _ — —
The Principal Designer hereby certifys that the proposedi ding design represented in this set of construction documents is
consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this
permit application. The proposed building as designed meets the energy efficiency re(0 116
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH. CITY i OF LA QUINTA
1. 1 hereby affirm that I am eligible under the provisions of Division I ahMl INIG "A sE)ERTq
sign this document as the person responsible for its preparation; ar d that I a li
California as a civil engineer, mechanical engineer, electrical engin w, or I is n 7� J
FOR 9ONSTRYCTI�f�.
i,
J u 2. I affirm that I am eligible under the provisions of Division 3 of the Business and rofessions ode ec ion
5537.2 or 6737.3 to sign this document as the person responsible f r its pre ra ion; and that I am a lic ns d
contractor performing this work. DATE! By m —
1[-J ❑ 01 3. 1 affirm that I am eligible under Division 3 of the Business and Pro a io
because it pertains to a structure or type of work described as exec ain= nc.
Code Sections 5537, 5538, and 6737.1. (These sections of the Business an Profs Cod are printed in
full in the Nonresidential Manual.) ---
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Required F
PRINCIPAL ENVELOPE DESIGNER - NAME I SIGNATU I -LI NO. TDAT
�/l
1 SGPA Architecture Plannin
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Manda ory Measures 'Lig- ing Compliance Not In The Scope Of
--
Required Forms 1Sub-mittat-----
—
PRINCIPAL LIGHTING DESIGNER - NAME 'SIGNATURE RE :LIC. NO. DATE ------I I
I !
MECHANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
rms ; CH -1 MECH-2 MECH-3 MECH-5
Bquired
iPRINCIPAL MECHANICAL DESIGNER - NAME I U LIC. NO. I DATE
L Devin A. Abellon,_ P.E.- LSW Engineers, _ _�_Z_ 131 /YR ;12. y� •J7
4.4
User Number: 3137
?,7 - 715- /// - P='I'4 ;7�1 -
Job Number:
F`"ryZi AND JOB CARD ARE NOT ON
THE SITE FOR A SCHEDULED
INSPECTION.
NO EXCEPTIONS!
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF-'
PROJECT NAME
r Desert Center - Blida H
Standard Proposed Compliance
ENERGY COMPONENT_ _Design Design Margin _
Space Heating 1.59 _ 0.83
Space Cooling 323.69 _ _ 255.40 68.28
Indoor Fans 105.56 151.13 -45.561
Heat Rejection F 0.00 0.00 -2-04
Pumps & Misc. I 0.00 0.00 0.00
Domestic Hot Water 13.79 13.79 0.00
Lighting I 164.07 164.07 0.001
Receptacle 81.51 ; - 81.51 0.00
Process L- 0.00 0.00 I 0.00
TOTALS: 690.21 666.72 23.49
Percent better than Standard: 3.4% ( 3.4% excl
(DATE
12/4/2007
£ r
r:vq g1�y X74
ixkn fxa' :�ic� •:,zy: ,�
iMM lkJo-"kn � 4 ,� R�•� �
P: NW 6zi
•... _ F
•ON r�i yK` .�
W1.1..
AC f
z
n.--firIN
v zn aC;so eo+t+p+zoiaoieo+abxoozeq<go�eaensboazo
F Building Orientation I E 90 de
Conditioned Floor Area
10,194
sqn.
Number of Stories 1
Unconditioned Floor Area
- o
sqn.
Number of Systems �_ 7
Conditioned Footprint Area
10,194
soft.
jI
Number of Zones_ - -- aI
M
Fuel Type ---
L Natural Gas
Orientation Gross Area Glazing Area Glazing Ratio
Front Elevation (E) 1,065 sqn. 4351 sqn. 40.8i°
Left Elevation _(S)I _ 2,33a sqn. o sgrt. 0.0%
I Rear Elevation (wHjj 1,624 sgn. ojsgn, o.0°i°
-1 i
Right Elevation (N)� 1,973 sqn. 1 1.2231sgn. _62.0%!
1 Total -_ 6,996 sgft. I 1,6581sgrt. 23.7%J
Roof 10,194 g .C -o qrt. l o
o.o%
i Standard_ Proposed
Lighting Power Density t.asi wrsgn.i.a911 W/sqn.
Prescriptive Env. Heat Loss 1, 5'Btuih I 2,7291Btuwh
Prescriptive Env. Heat Gain r Btu/h-F 191,145I8tu/h-F 283,1121
i -
Remarks:
i EnergyPro 4.4 by EnergySoft _ _ User Number: 3137 Job Number: 2006796.000 Page:2 of 9 1
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -11
PROJECT NAME
Komar Desert Center - Bldg H _ _ _ 12/_4/2007
ZONE INFORMATION
--- System Name _�-
Zone Name
i Occupancy Type
Floor
Area
1 (sgft.)
Inst.
LPD
( (W/sf)1
Ctrl.
Credits
(W/sf)2
Allowed LPD
Area I Tailored
M-1-02 w1s�4
Proc.
Loads
(W/sf)
RTU H-6 &RTU H-7
Lease Space
I Comp Bldg Retail and Wholesale
� _2,524
'1.50
- --
—_
;The Zone 'Lease Space' has a North/East/South Displa rL erimeter Credit of 87 ft. -
--RTU H-1 - RTU H.5
r —�
Lease Space
-
Comp Bldg Retail and Wholesale
__
I
7,5731
–�----
'1.50
----
----I
----
I Restrm_--__
Corridor/Restroom/Support
491
'0.60
--_--_
---
Restrm -_
Corridor/Restroom/Suppon
49
-0.60
__--
—
-
-
I
Notes: 1. See LT -2-C 2. See LTG -4-C 3. See LTG -5-C 4. See LTG -6-C
(items marked with asterisk, see LTG -2 -C by others) (by others)
Items above require special documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
The local enforcement agency snoulo pay special attention to the items specified in this checklist. These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
s;uhmittpd-
IrThe Roof Roof R-30 is a CRRC Certified Roof with Reflectance = 0.30, Emittance = 0.75.
_
The HVAC System 'Carrier 50HJQ006-5 w/ DCV" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500.
iThe HVAC Siem "Carrier 50HJQ006-5 w/ DCV" is designated as 3 Phase, or is Exempted from the NAEC_A 13 SEER reguireme_nt.
_
The HVAC System "Carrier 50HJQ006-5 w/ DCV" includes Demand Control Ventilation per Standards Section 121.
The HVAC System "Carrier 50HJ0007-5 w/ DCV" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2_500.
The HVAC System "Carrier 50HJ0007-5 w/ DCV" includes Demand Control Ventilation per Standards Section 121_
— -- - --
—
�The Zone "Lease Space" has a North/East/South Display Perimeter Credit of 87 ft.
— _ — ---
The Zone 'Lease Space' has a West Display Perimeter Credit of 14 ft.
—_
;The Zone 'Lease Space' has a North/East/South Displa rL erimeter Credit of 87 ft. -
- -_ - -- - ---
The Zone "lease Space" has a West Dispj�yferimeter Credit of 14 ft. -----
The exceptional features Iisteo in this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Sianature or
EnergyPro 4.4 by EnergySoft User Number: 3137 Job Number: 2006796.000 Paoe:3 of 9 1
CERTIFICATE OF COMPLIANCE ENV -1 -Cl
7PROJECT NAME--_-_-----.-�---------- - ----- DATE
-_ Komar Desert Center - Bldg _ _ _ 12/4/2007
OPAQUE SURFACES
#
Surface I Insulation Act. I Cond:
TY_ee-I Area ' U -Fac. 1 Cay. Cont. �mmmmmmmmmmm. Tilt Status
Joint Appendix - -j
( IV Reference Location / Comments
1_
2
Wall _ �- 81 _0.074 _ R -19R-0.0 270 90 New _1!-09--A5
Roof 2,5_ _ 2 0.036 R-30 R-0_0 0 0 New
0� 2-A9
Space
_ Lease Space
3 ]Wall
I_ 81 0.0741 R-19 R-0.0 2790 New 09 -AS Lease Space
4
S
'Roof_ rt 7,573. 0.036 R-30 R-0.0 0 0 New 102 A9
Wall 75 0.074_! __ R-191 R-0.0`_0 90 New 709 -A5
-
Lease Space__
Space
6
Wall 63d 0.074_ R -19-T _R-0.0 9-00 990
_ � New
109-A5
--Lease
ILease Space
7
8
9
10
�.
Wall _ _2_1_3 0074_)--R-19 R-0.0 180 90 New --,
Door_ 2 0.700 None R-0.01 180 90 New
Door 0.700 None _ R 0.01 180 90 ; New
Door 2 0.7001 None i R-0.01 180 90 ; New
�09_A5
'28-A2
128-A2
Lease Space
_ Lease Space _
- Lease Space--- -
Lease Space
111
12
13
_ _28-A2
Door 2 , 0.700 Noner R-0.01 180 90 ! New 28-A2
Wall _ 110-0.074 R_19 R-0.0 180 90 i New 09 A5rRestrm
Roof 4 0.036 R-30 R-0.01 0 0i I New 02-A9
_
-ILease Space _
-_
!Restrm
14
Roof 4 0.036 R-30 R-0.0 0 New
02-A9
-
Restrm
None
None
_ _0
,
----�
--- -
_--�---- -- -
1.2 3.8 0 1.2-5.0 0
---i -- ---- -- - -1 -
Window
Rih9 t (N)
;- 177 1.190 116-A
0.83116_BB�- 01
NewlStorefront -----!Lease
Space -_--j
8
Window
Front E
47 1. 1901, 116-A
0.83 116-B I 90101
New I Storefront
I Lease Space
9
�10
Window
Front E)
135 1.190116-A0.83
116 -BBQ 90
N. E. A, R (New, Existing, Altered.
IF More than or equal to 10,000 sq.lt. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U -factors from
I Standards Table 116-A and B. Certificate shall be filed in the contractor's rimlect office dudnn constmctinn and in thn mdidinn ma oe, nefco arra, nnn�t�,nrnn
#
ITyj�e
Act. I Cond Location/
Area U -Fac' SHGC2 Azm.[Stat, Glazing Type 'Comments
r1
IWindow_
Right
177 1.190 116-A
Overhang -
I
I Left Fin.- I _Right Fin
1 2
Window
(N) --1
R�ht N)_
127 1.190 116-A
0.83 116-B 01 New I Storefront - ---
0.83 116 -BI 0 New Storefront
_.ILease Space -
ILease space
_4 3
_ -_--
_ indow Right (N) 223 1.190 116 -Al 0.83 116-B _0 New Storefront__
W
(indow R!ght(N) 177 1.190 116-A 0.83 116-B 0 New Storefront
Lease Space _
Lease Space
L5
6
rWindow
lWindow
Right (N)_ 89 1.190 116-A
Ri hg N) 253 1.1901 116-A
0.83 116-B 0
116-6 01
New Storefront _
New Storefront
_ Lease Space _
lease Space
5
6
None
None
1 0.76_ 1 10.0 6.3
0.76 1 10.0 25.3
_0.83
-_
_--�---- -- -
1.2 3.8 0 1.2-5.0 0
7
Window
Rih9 t (N)
;- 177 1.190 116-A
0.83116_BB�- 01
NewlStorefront -----!Lease
Space -_--j
8
Window
Front E
47 1. 1901, 116-A
0.83 116-B I 90101
New I Storefront
I Lease Space
9
�10
Window
Front E)
135 1.190116-A0.83
116 -BBQ 90
New _ tor
Sefront
,Storefront
LeaseSpaace
6.8
Window
Front (E) _-
_25311.190116 -A116
-B1 90
New
ILease Space ------iii
-�
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
1 u -tactor type: n b -A uetaun table from standards, ]able NI -1 uelault Table from the AGM Manual Appendix, NFRC Labeled value.
2 SHGC Type: 116-B Default Table from Standards. COG Center of Glass. NFRC Labeled Value
EXTERIOR
SHADING
#
Exterior Shade
Window
Type 1SHGC1 Hgt. Wd.
Overhang -
I
I Left Fin.- I _Right Fin
Len.
Hgt. LExt.RExt.
Dist. Len. Hgt.- Dist. Len. Hgt._
U
3
None
None
None
0.776�-_ 10.0 1_2.7 ; _ 6.0
10.76 10.0 12.7 7.0
1 0.76 I 10.0 22.3 1 7.0
0.1 20.0 20.0
0.1 10.8 15.0
0.1 10.0-
I
4
None
10.76 10.0 12.7 1
6.0
0.1 11.0 7.0
5
6
None
None
1 0.76_ 1 10.0 6.3
0.76 1 10.0 25.3
8.0
11.0
0.1 3.3 21.0
0.1 32.0 32.0
_--�---- -- -
1.2 3.8 0 1.2-5.0 0
7
None ----
-T ---'---F-
( 0.76 10.0 12.7
-- - - -- --- -
9.4 _
0.1 _7.3 _ 3_0.0 --
-- - ------ - -- ;-- - - ---
8
9
None
'None
10.76 10.0 3.3 ;
-! 0.76_ 10.0
28.0
0.1 0.0 6.7
�-
_ 9.7 _
6.8
0.1 20.0 10_0
110
___
None -_-_-
- 10.76 11 10.0 25.3
6.8
0.1 0.1 20.0
-- -
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
II The proposed building is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 tt2, a telling height greater than 15 feet, and an LPD for general
-
lighting of at least 0.5 W/tt2. See Section 143(c). If this box is checked, ENV -4-C must be filled out. when submitting under the Prescriptive Compliance Approach.
1-_-_EnergyPro 4.4 by EnergySoft User Number: 3137 Job Number: 2006796.000 Page:4 of 9 1
CERTIFICATE OF COMPLIANCE MECH-I-C
PROJECT NAME i DATE
Komar Desert Center - Bldg H _— i 12/4/2007
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Forth shall be submitted to the building department that certifies plans, specifications, installation
certificates, and operating and maintenance information meet the reauirements of Section 10-103(b) and Title 24 Part 6.
STATEMENT OF COMPLIANCE
MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing _—
i
Test required on all New systems both New Construction and Retrofit.
[� MECH-3-A: Packaged HVAC Systems Acceptance Document ---�
Equipment requiring acceptance testing
--
Test required on all New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing-_— —
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do require construction inspection.
MECH-5-A: Air Distribution Acceptance Document
!
Equipment requiring acceptance testing —
This test required If the unit serves 5, 000 h2 of space or loss and 25% or more of the ducts are in nonconditioned or semiconditioned space like an
attic. New systems that moot the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
1 11 MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
Ll MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
i
Equipment requiring acceptance testing
All new VAV fan volume controls installed on newer existing systems must be tested---
❑ MECH-8-A:-Hydronic System Control Acceptance Document
—I
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to now boilers and chillers and the primary pumps are connected to a common header.
I
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500.000 Btu/hr.
-Water-loop Heat Pump Controls
I
Applies to all new watedoop host pump systems where the combined loop pumps ate greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable flow chillotl, hydropic neat purnp
i
orcondensor water systems where the pumps motors are greater than 5 hp.
Equipment requiring acceptance testing__ _
j EnergyPro 4.4 by EnergySoft _—_ User Number: 3137 Job Number 2006796.000 __ Page:5 of 9
IAIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-CI
('PROJECT NAME rDATE
�— _ -Komar Desert Center =Bldg H_— __— I 12/4/2.007 _
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
MANDATORY MEASURES
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous HeattCool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
I AIR SYSTEMS, Central or Single Zone —
RTU H-6 & RTU H-7 _ RTU H-1 - RTU H-5
--- — 2 -- — --- -- 5
T-24
Section Reference on Plans or Specification t
F-
144
144 a & b
I n/a
—_-�
1112(l) 7.70 HSPF_—_
2.20 COP
-�
--------
_-I _
11 12(a)13.0 SEER / 11.0 EER
_
j 11.0 EER-
----
� 112(b) j Yes
Yes
�
112(c), 115 a i n/a---I__
n/a
I _
121(b) _ Yes
Yes _
_ ---
121 b) 555 cfm —_
1866 cfm__-
121 c No
I No
—1
--
I
I
121(c) Yes
Yes
--J{
121 c 122(e) Programmable Switch
Proarammable Switch
122(e) Heating & Coolin _Required
Heating &Cooling Re uired
122(f) Auto —�
Auto
I--
t 122_— n/a
---- n/a
- ----
123
{-
-
124-- R-8.0
; R-0.0
F-
144
144 a & b
I n/a
144 (a & b)
144 ja ice-__
_— 70,202 btuh ( 215,478 btuh —T
-- n/a — - - n/a --
-�
--------
144 a &b)
87,417 btuh—� - 277,969 btuh
_
144 c
X144 (c)
Constant Volume I Constant Volume
�
I
I
144 (c)
( Yes { Yes -----I
I _
144jdj—
No I No
_ ---
124 a
Diff. Enth Integrated I Diff. Temp�ntegrated�
144 (1)�
Constant Temp Constant Temp
—1
144(o —i----
Constant Temp j Constant Temp
--; ----No
I
144 (k)
No
--J{
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A' in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes it System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has -- 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
EnergyPro 4.4 by EnergySoft User Number: 3137 Job Number: 2006796.000 Paae:6 of 9 1
IMECHANICAL VENTILATION MECH-3-CI
PROJECT NAME DATE
Komar Desert Center - Bldg H 12/4/2007
_.]
PRESCRIPTIVE REHEAT
LIMITATION Section 144(d))
MECHANICAL VENTILATION Section 121(b)2)
AREA
BASIS
1
BASIS
VAV MINIMUM
- A
B
o
a�
�M CIL
i C
I cn
Ic
mvn
IABD 71
D
Cr3
31
SI
xDn
_OCCUPANCY
I E
�c
m3
I F
m n
yf�p-n
G
I Cr
�
mO�
xFf
H
'a m
o'K
I
! �
nfD�(c>�o
-A
J w
N O
3e
T(n -"
K -�
m
x
L_
�
°c
�,
07M
I_ My
�
�y
fD`O
'fl0
N
m
o
y
ZONE/SYSTEM
O
0
(�A TI
—
3
V�
A
M0
0
O-+�
7
n
C T
��
3
f7
O
�a5
•- D
�• 1D
D
- 3
�CQ
V
p_ m
I O
I x A
IOy0
T=•
O
5
e;
D
—
Lease Space
I 2,5242
i 0.22
555
73.2
— —7.6
555
555
555
—
I
�^
RTU H-6 & RTU H-7
—_
.4
I
I _
�_
Total
555
555
-�
I
Lease Space _
Restrm_
Restrm
7,57
_ 4
49j
0.22j
0.151
0.15(17�
1,666
7
219_6
- 7.6
1,666
1,6_66
j 7
1,666
100
-- - -
RTU H-1 RTU
-I-7
I
�-
100
- H-5
-----
I---
I---i----'—�—_
I
Total
—'—
1,681
1,8661
—7-'—
--
I
i
I
I
�
!
I
I
1
L... C ;Minimum ventllaton rate Per Section 121,
j—_ E— �Basod on flzed stator the
Table t21 -A
ccupant
load tore
r0gLe4Toses
fobs aces
without lixod
seating.
--
H I Required Ventilation Air.( is the Larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G). —_-- — 1
I ._'Must be greater than or equal to H, or use Transler Air column H to make uD the dilference. _ ---- -- — _ --
— --__—
J _ De> n tan sup ty cfm (Fan CFM x 30%: or
I K I Condition area it. sq.) x 04 cfm/ft. sq.:
j--'-t — -- --
L Maximum of Columns H. J. K. or 300 cfm
I M (This must be less than or gual to Column L and greater that or equal to the sum of Columns H + N_ _ ---- —__ —_ ------ — —
FN Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal
1 to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M.
I
EnergyPro 4A by EnergySoft User Number: 3137 Job Number: 2006796.000 Page:7 of 9 I
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-S-C
PROJECT NAME—
Komar_Desert Center -_Bid E
g _
I
DATE �___ 12/4/2007 J
H LLER AND TOWER SUMMARY
I_—_.—.-------_
Equipment Name
------
Equipment Type
city.
— --�-- --- —.-�--
1 I Tot. i ;
Eff Iclency Tons Oty GPM BHP
I I i
PUMPS
Motor
_Dr
Eff.
ve
Eff.
r.—--
L--Pumpi
Control
,DHW / BOILER SUMMARY
_. Energy Standby TANK INSUL.
Rated Vol. — Condition I Factor Loss or Ext.
System Name I System Type Distribution Type IOty Input (Gals.) ( Status { or RE Pilot 1 R -Val.
CENTRAL SYSTEM RATINGS
HEATING I COOLING
ITAux. I Condition
System Name System Type — Qty OutDut kW I Eff.i� Output Efficiency --_ Status Economizer T e
Carrier 50HJ0006-5 w/ — i T--
DCV Packaged DX 2 56,200 0.a 7.70 HSPF 61,000113.0 SEER / 11_0 EER -- New Diff_Enth (integrated)
Carrier 50HJ0007-5 w/ I`
DCV !Packaged DX 1 5 69,000 0.0 2.20 COP 76,000!11.0 EER New (Diff. Temp (Integrated)
i