September 13, 2004
Ficcadenti & Waggoner
16969 Von Karmen, Ste 240
Irvine, CA 92714
Re: "Non -Structural Building Plan Review
LAQ=04-BPAI / L.Q. Valley Plaza — Bldg. 6
720 wy' 11
Fire Department personnel have reviewed and approved the plans you submitted for the above
referenced project. Please be advised the following conditions apply as a part of the conditions for the
issuance of a building permit.
1) These conditions are for a shell building and will receive a shell final only. No fire and life safety
clearance will be issued for a tenant space until the specific occupancy classification has been
established and tenant improvement plans have been reviewed and conditioned by the Riverside
County Fire Department.
2) Fire Department approval is based upon the 2001 CBC requirements for Group B/M occupancies. It
is prohibited to use, process or store any materials in the occupancy that would classify it as a Group
H occupancy per Sec. 307 of the 2001 CBC.
3) The Fire Department is required to set a minimum fire flow for the remodel or construction of all
commercial buildings using the procedure established in the 2001 CFC. A fire flow of 1500 gpm for
a 2 -hour duration at 20 psi residual operating pressure must be available before any combustible
material is placed on the job site.
4) The required fire flow shall be available from a Super hydrant(s) (6" x4" x21/2" x 21/2') located not
less than 25' or more than 165' from any portion of the building(s) as measured along approved
vehicular travel ways.
5) Install a complete fire sprinkler system per NFPA 13. The post indicator valve and fire department
connection shall be located to the front within 25' to 50' of a hydrant, and a minimum of 25' from the
building. System plans must be submitted to the Fire Department for review, along with a
plan/inspection fee. The approved plans, with Fire Department Job card must be at the job site for
all inspections.
6) Install a monitoring system designed in accordance with NFPA 72, which must include a water flow
monitor, control valve tamper and continuous monitoring service. System plans must be submitted
to the Fire Department for review, along with a plan check/inspection fee.
7) Install Knox Key Lock box, Model 3200, mounted per recommended standard of the Knox
Company. If the building/facility is protected with a fire alarm system or burglar alarm system, the
lock boxes will require "tamper" monitoring. Special forms are available from this office for the
ordering of the Key Switch, this form must be authorized and signed by this office for the correctly
coded system to be purchased.
8) All egress doors shall comply with CBC Sec. 1003.3.1.8 for proper door hardware.
EMERGENCY SERVICES DIVISION • PLANNING SECTION • INDIO OFFICE
82.675 Highway 111, 2nd FI., Indio, CA 92201 • (760) 863-8886 • Fax (760) 863-7072
9) Install portable fire extinguishers per Title 19, but not less than 2A1 OBC in rating. Contact certified
extinguisher company for proper placement of equipment.
10) Approved building address shall be placed in such a position as to be plainly visible and legible from the street
and rear access if applicable. Building address numbers shall be a minimum of 12" for building(s) up to 25' in
height, and 24" in height for building(s) exceeding 25' in height. In multi -tenant buildings, businesses shall
post the business name and suite number on back doors as well as the front. Suite numbers or letters must
be a minimum of 6' in height. All addressing must be legible and of a contrasting color with the background.
11) Electrical room door shall be posted "ELECTRICAL ROOM" on the outside of door.
Please contact the Fire. Department Planning & Engineering staff for final inspection prior to occupancy.
All questions regarding. the meaning of these conditions should be referred to the Fire Department Planning &
Engineering staff at (760) 863-8886.
Sincerely,
FRANK KAWASAKI
Chief Fire Department Planner
By
Walter Brandes
Fire Safety Specialist