09-1314 (RC) Revision 1 Title 24is 6
TITLE 24 REPORT
Title 24 Report for:
Eisenhower Ambulatory Care Center - Einstein Cafe
45-280 Seeley Drive
La Quinta, CA
Project Designer:
Curtis Chong
1426 Pearl Street, Suite 300
Boulder, CO 80302
303.499.7795
. YBUILDING & OF LA QUINTA
SAFETY•
APPROVED
FOR CONSTRUCTION
..:�J
Report Prepared By:
Glynnis Cassan
JBA Consulting Engineers
36 Technology Drive, Suite 200
Irvine, CA 92618
(949) 419-3030
Job Number:
oyffie
Date:
1/14/2010
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.4 by EnergySoft Job Number: 07.0021 _ User Number: 5678
ICERTIFICATE OF COMPLIANCE (Part 1 of 4) LT
PROJECT NAME DATE
Eisenhower Ambulatory Care Center - Einstein Cafe 1/14/2010
PROJECT ADDRESS
45-280 Seeley Drive La Quinta
Building Permit #
PRINCIPAL DESIGNER - LIGHTING TELEPHONE
Magdy A. Francis 949-419-3030
TELEPPONE Checked by/Date
DOCUMENTATION AUTHOR ^
use
|CLIMATE Zowe |
---—'—'— 1��1A-0A�-------'—ED FLOOR427p"Ft | 15 �
BUILDING TYPE
X!, NONRESIDENTIAL HIGH RISE RESIDENTIAL
HOTELIMOTEL GUEST ROOM
X! CONDITIONED SPACES [-j UNCONDITIONED SPACES INDOOR & OUTDOOR SIGNS
PHASE OF CONSTRUCTION NEW CONSTRUCTION ADDITION F ALTERATION
1M ETHOD OF LIGHTING 17 COMPLETE BUILDING AREA CATEGORY [7 TAILORED PERFORMANCE
ICOMPLIANCE [] COMMON LIGHTING
ISTATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24,
Parts 1 and 6 of the California Code of Regulations. This certificate applies only to buildingjl"ing requirements.
The documentation preparer hereby certifies that the documentation is a�4ate,�nd co le
RE
DOCUMENTATION AUTHOR SIGNATURE DATE
The Principal Lighting Designer hereby certifies that the proposed bu ding esi Wepr sented in this set of construction documents
is consistent with the other compliance forms and worksheets, with the specific !ions, and with any other calculations submitted with
ithis permit application. The proposed building has been designed to meet the lighting requirements contained in Sections 110, 119,
K7 The plans & specifications meet the requirements of Part 6 (Sections 10-103a).
The installation certificates meet the requirements of Part 6 (10-103a 3).
The operation & maintenance information meet the requirements of Part 6 (10-103c).
Please Check One: (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.)
I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person
responsible for its preparation; and that I am licensed in the State of California as a civil engineer or electrical engineer, or I am a licensed architect.
I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document
as the person responsible for its preparation; and that I am a licensed contractor performing this work.
I affirm that I am eligible under the exemption to Division 3 of the Business and roN��Sns Code to sign this document because it pertains to a
structure or type of work described as exempt pursuant to Business 8�1
Sli - L�6
PRINCIPAL LIGHTING DESIGNER - NAME
Maqdv A. Francis A
LIGHTING MANDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures
!LIGHTING COMPLIANCE FORMS & WORKSHEETS (Check box if worksheet is included)
!IXILTG-1-C, Parts I of 4 and 2 of 4: Certificate of Compliance. Part 1 of 4 and 2 of 4 are required for all submittals
LILTG-1-C, Part 3 of 4: Certificate of Compliance. Part 3 of 4 submittal is required only if Control Credits are claimed
IxILTG-1-C, Part 4 of 4: Certificate of Compliance. Part 4 of 4 submittal is required when lighting controls are installed
llx;LTG-2-C: Indoor Lighting Schedule
ILTG-4-C: Lighting Controls Credit Worksheet
1 -'LTG-5-C: Indoor Lighting Power Allowance
!LTG-8-C: Common Lighting Systems Method Worksheet
1 1 LTG-9-C: Line Voltage Track Lighting Worksheet
Pagel of 6
CERTIFICATE OF COMPLIANCE (Part 2 of 4) LTG-1-C
PROJECT NAME -DATE
Eisenhower Ambulatory_ Care Center - Einstein Cafe 1 1 /14/2010
INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES
INSTALLED
WATTS
INSTALLED LIGHTING, CONDITIONED SPACES (From LTG-2-C) 532
PORTABLE LIGHTING (From LTG-3-C) 0
LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG-4-C) 0
CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 532
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG-2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG-4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG-S-C)
FX AREA CATEGORY METHOD (From LTG-5-C)
❑ TAILORED METHOD (From LTG-S-C) ALLOWED LIGHTING POWER
ALLOWED
WATTS
548
ALTERNATE COMPLIANCE
❑ PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG-8-C)
ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG-5-C
0
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
NOTE TO
FIELD
CONTROL LOCATION
(Room #)
CONTROL
IDENTIFICATION
CONTROL TYPE
(Auto Time Switch, Dimming, etc.)
SPACE CONTROLLED
Check if
Daylighting
i EnergyPro 4.4 by Enerqvsoft User Number: 5678 Job Number: 07.0021 Page:4 of 6 I
CERTIFICATE OF COMPLIANCE (Part 4 of 4) LTG-1-C�
PROJECT NAME ---DATE
Eisenhower Ambulator�r Care Center - Einstein Cafe ( 1/14/2010
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance
tests for lighting systems. The designer is required to check the boxes by all acceptance tests that
apply and list all equipment that require an acceptance test. If all equipment of a certain type requires
a test, list the equipment description and the number of systems to be tested in parentheses. The NJ
number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the
test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design
professional or an agent selected by the owner). Since this form will be part of the plans, completion
of this section will allow the responsible party to budget for the scope of work appropriately.
Building Departments:
Before an occupancy permit is granted for a newly constructed building or space, or a new lighting
system system serving a building or space is operated for normal use, all control devices serving the
building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building department
that:
A. Certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of§10-103(b) and Title 24 Part 6.
Test Description I
Test Performed By:
❑ LTG-2-A: Lighting Control Acceptance Document
- Occupancy Sensor Acceptance
- Manual Daylight Controls Acceptance
- Automatic Time Switch Control Acceptance
Equipment requiring acceptance testing
❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing
EnerovPro 4.4 by EnerovSoft User Number: 5678 Job Number: 07.0021 Page:5 of 6 1
INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG-2-C
PROJECT NAME DATE
Eisenhower Ambulatory Care Center - Einstein Cafe ! 1/14/2010
INSTALLED LIGHTING POWER FOR CONDITIONED SPACES
Name
Luminaire i
Type Description
35w Low Voltage Halogen
_ '35
Lamps/Ballasts
C
ter' i
-0
CDp
watt LamD
rr
cvc
3 3
dym
•0
11
ma `t'
3CD
C N
351
i
cdc
3 m 3 l
5 aQ
d. p
W °
9_.0i38.0
Installed
c
3-0
��
0
.0
ir
iurn
4i Ci9
X :_
Watts
r
c Z
'y°�
M
—�
14
3
m
.v N N
53.2
I
I
I
PAGE TOTAL
BUILDING TOTAL (sum of all pages) i 532;
PORTABLE LIGHTING (From LTG-3-C) j 0
CONTROL CREDIT (From LTG4-C) 0'
ADJUSTED ACTUAL WATTS �_ 532
EnergyPro 4.4 by EnergySoft User Number: 5678 Job Number: 07.0021 Page:6 of 6