06-3646 (SFD) Title 24I TITLE 24 REPORT I
Title 24 Report for:
Faherty Residence
53-390 Del Gato Drive, the Traditions
La Quinta, CA 92253
Project Designer:
Prest Vuksic Architects
44-530 San Pablo, Suite 200
Palm Desert, CA 92260
(760) 779-5393
Report Prepared By:
Tim Scott
Scott Design & Title 24
77085 Michigan Dr.
Palm Desert, CA 92211
(760) 200-4780
Job Number:
Date:
1/5/2007
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
DATEIJ!��BY�Jw
0& - .3lo 440
EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
orized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
I EnergyPro 4.2 by EnergySoft Job Number: User Number: 6712 1
Y 4 1 -k
TABLE OF CONTENTS
Cover Page
1
Table of Contents
2
Form CF -1 R Certificate of Compliance
3
Form MF -1 R Mandatory Measures Summary
11
Form WS -5R Residential Kitchen Lighting
13
HVAC System Heating and Cooling Loads Summary
14
Room Load Summary
18
Room Heating Peak Loads
22
Room Cooling Peak Loads
26
EnergyPro 4.2 by EnergySoft Job Number: User Number: 6712
Certificate Of Compliance : Residential (Part 1 of 4) CF -1 R
-r-qhprtv Residence
1/5/2007
ject Ti le
Date
Project Address
Building Permit #
Design & Title 24
(760) 200-4780
sScott
Documentation Author
Telephone
Plan Check/Date
FneraVPro
15
Field Check/Date
Compli ce Method
Climate Zone
TDV
Standard
Proposed
Compliance
(kBtu/sf-yr)
Design
Design
Margin
Space Heating
1.72
1.30
0.43
Space Cooling
56.87
49.94
6.93
Fans
8.55
8.65
-0.10
Domestic Hot Water
3.84
6.17
-2.33
Pumps
0.00
0.08
-0.08
Totals
Percent better than Standard:
70.99 66.14
Building Type: [X-) Single Family
❑ Multi Family
Building Front Orientation:
Fuel Type:
Fenestration:
Area: 1,523 ft2
Ratio: 22.8%
❑ Addition
❑ Existing + Add/Alt
(W) 280 deg
Natural Gas
Avg. U:
Avg. SHGC:
q'LDING
ZONE INFORMATION
e Name
0.39
0.37
Floor Area Volume
HVAC' -1 137 _ 15 4
HVAC, -2, 3 & 4 3,457 41.8
HVAC -5 478 5 -
HVAC -6
-HVAC -6 1,371 16.3
OPAQUE SURFACES Insulation Act.
Type Frame Area U -Fac. Cay. Cont. Azm. Tilt
Rnnf Wnnd 1 371 ()()?4 R-38 R_7 0 _� n
Wall Wood 175 0 069 R_21 R-0.0 if) 90
Wall Wood 12 0 069 R-21 R-0.0 90 _90
Wall Wnnd 127 n n69_ R_91 R_0 0 100 9Il
Wall Wood 349 0.069 R-21 R-0.0 180 90
Wall Wood 237 0069 R -91 R-0 0 ign go
Wall Wnnd 1R0 _0069_ -91R-0 n 97n gn
Rnnf Wnnd 3 453 0094 R_38 R_7 n -0 2n
Wall Wnnd 74 0.069 R-21 _R-0p_0_gn
Wall Wood 148 _006,9_-21X0.0_1Q90
Wall Wnod 322 n 069 R_91 R_0 n inn gn
Wall Wnnd 1R n n69 R-21 R_0 0 270_ gn
Wall Wood 179 0 069 R_91 R-0 0 180 9Q
noor None 24 1.450 None R-0.0 _180_0
Wall Wnnd 60 0.069 R_21 _B_p 0 190 90
Wall Wnnd 96 0069 R-21 R-0.0 _9260
Wall Wnnd 244 o n6g _$21 R -n fl_ AZO A0
Wall Wnod 42 n n69 R_91 R -n n 31.5 q()
Rnnf Wnnd 474 n n24 R_38 R-7 n n 9n
Wall Wood 363 0069 R_21 R-0.0 10 90
Wall Wood 88 00.69 R21R-0 0 X00_90
Wall Wood 63 0.069 R_21 R-0.0 _28.0 9n
Amlhnnf Wood 1,367 0024 -38 - 0-0 90
Wnnd 146 n nF;9_ R_91 _R-0 D_ i m gn
Wall Wnnd 145 n 069 R21R-0J11Sin gIl
MDR
Total Conditioned Floor Area:
Existing Floor Area:
Raised Floor Area:
Slab on Grade Area:
Average Ceiling Height:
Number of Dwelling Units:
Number of Stories:
# of Thermostat
Units Zone Type Type
091 Sleeping SleepingS-tat
��Z Living evingStat
0"07 Conditioned Setback
0.21 Sleeping Sleepin Sg tat
6,677 ft2
n/a ft2
0 ft2
6,677 ft2
11.8 ft
1.00
Vent
Hgt. Area
-2 n/a
n/a
n/a
-2 n/a
Gains Condition
Y / N Status JA IV Reference Location / Comments
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:3 of 31 1
Certificate Of Compliance :
Residential
ft2
(Part 1 of 4) CF -1 R
ject Ti le
ft2
Raised Floor Area:
0
1/5/2007
Date
Slab on Grade Area:
6,677
ft2
Average Ceiling Height:
11.8
Project Address
Number of Dwelling Units:
1.00
Building Permit #
s, ott Design & Title 24
(760) 200-4780
Documentation Author
Telephone
Plan Check/Date
FneraVPro
Compli nce Method
15
Climate Zone
Field Check/Date
TDV
Standard
Proposed Compliance
(kBtu/sf-yr)
Design
Design
Margin
Space Heating
1.72
1.30
0.43
Space Cooling
56.87
49.94
6.93
Fans
8.55
8.65
-0.10
Domestic Hot Water
3.84
6.17
-2.33
Pumps
0.00
0.08
-0.08
Totals
70.99
66.14
4.85
Building Type: W Single Family
❑ Multi Family
Building Front Orientation:
Fuel Type:
Fenestration:
❑ Addition
❑ Existing + Add/Alt
(W) 280 deg
Natural Gas
Area: 1,523 ft2 Avg. U: 0.39
Ratio: 22.8% Avg. SHGC: 0.37
�
'LDING ZONE INFORMATION
one Name Floor Area Volume
OPAQUE SURFACES Insulation Act.
Type Frame Area U -Fac. Cay. Cont. Azm. Tilt
Wall Wnnd 4R7 n nsg R_91 R -n n 195 90
Wall Wood 241 0.069 R-21 R-0 0 985_ 90
Wall Wood 504 0 069 R-21 R-0 0 is gn
Wall Wnnd 0 n n6g R_91 R-0 0 n go
r
Total Conditioned Floor Area:
6,677
ft2
Existing Floor Area:
n/a
ft2
Raised Floor Area:
0
ft2
Slab on Grade Area:
6,677
ft2
Average Ceiling Height:
11.8
ft
Number of Dwelling Units:
1.00
Number of Stories: 1
# of Thermostat Vent
Units Zone Type Type Hgt. Area
Gains Condition
Y / N Status JA IV Reference Location / Comments
Run Initiation Time: 01/05/07 16:10:56 Run Code: 1168042256
EnergyPro 4.2 by Energysoft User Number: 6712 Job Number: Page:4 of 31
1 0 1 k.
Certificate Of Compliance : Residential (Part 2 of 4) CF -1 R
herty Residence
1/5/2007
ject Title
Date
FENESTRATION SURFACES
True Cond. Location/
# Type
Area U -Factor' SHGC2
Azm. Tilt Stat. Glazing Type Comments
_1_ Window Left (N)56
0 _ 039 NERC 0_37 NERC 10_ qQ New Sierra Pacific Windows & Doors Master Suite
2 Window Rear (E)
148.0 0.390 NFRC 0.37 NFRC
100 90 New Sierra Pacific Windows & Doors Master Suite
3 Window Right (S)
11.0 0.390 NFRC 0_37 NFRC
180 90 New Sierra Pacific Windows & Doors Master Suite
4 Window Right (S)
11.0 0.390 NFRC 0.37 NFRC
180 90 New Sierra Pacific Windows & Doors Master Suite
5 Window Right (S)
8.0 0.390 NFRC 0_37 NFRC
180 90 New Sierra Pacific Windows & Doors Master Suite
6 Window Right (S)
11.0 0.390 NFRC 0_37 NFRC
180 90 New Sierra Pacific Windows & Doors Master Suite
L Window Right (S)
51.0 0_390 NFRC 0_37 NFRC 180 90 New Sierra Pacific Windows & Doors Master Suite
8 Window Right (S)
11.0 0.390 NFRC 0.37 NFRC
180 90 New Sierra Pacific Windows & Doors Master Suite
6 Skylight Left (N)
4.0 0_800 NFRC 0_39 NFRC 0 20 New Double Metal Tinted Great/KiUBreak/Din/Den
1Q Window Left (N)
46.5 0_390 NFRC 0_37 NFRC 0 . 90 New Sierra Pacific Windows & Doors Great/Kot/Break/DM/Den
11 Window Left (N)
11.0 0.390 NFRC 0_37 NFRC
0 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den
12 Window Left (N)
21.0 0.390 NFRC 0_37 NFRC
10 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den
_U Window Left (N)
52.0. 0_390 NFRC 0_37 NFRC 10 _y_Q New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den
14 Window Left (N)
3.0 0.390 NFRC 0_37 NFRC
10 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den
15 Window Left (N)
3.0 0.390 NFRC 0.37 NFRC
10 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den
16 Window Rear (E)
66.0 0.390 NFRC 0.37 NFRC
100 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den
17 Window Rear (E)
288.0 0.390 NFRC 0_37 NFRC
100 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den
18 Window Front (W)
22.0 0.390 NFRC 0.37 NFRC
270 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den
--ta Window Right (SW)
22.0 0_390 NFRC 0_37 NFRC _ 225 90 New Sierra Pacific Windows & Doors _Great/KiUBreak/Din/Den
1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 11613.
INTERIOR AND EXTERIOR SHADING
Window
Overhang Left Fin Right Fin
# Exterior Shade Type
SHGC Hgt. Wd.
Len. Hgt. LExt. RExt. Dist. Len. Hgt. Dist. Len. Hgt.
1 Bug Screen
0.76 9.3 6.0
8.0 0.1 8.0 8.0
2 Bug Screen
0.76 9.3 16.0
2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0
Bug Screen
0.76
Bug Screen
0.76
_ Bug Screen
0.76
6 Bug Screen
0.76
7 Bug Screen
0.76
8 Bug Screen
0.76
9 None
1.00
10 Bug Screen
0.76 7.8 6.0
2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0
11 Bug Screen
0.76 1.8 6.0
2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0
12 Bug Screen
0.76 6.3 3.3
8.0 0.1 8.0 8.0 0.0 0.0 0 0.1 4.0 0
13 Bug Screen
0.76 6.5 8.0
10.0 0.1 10.0 10.0
14 Bug Screen
0.76
15 Bug Screen
0.76
16 Bug Screen
0.76 6.2 10.5
10.0 0.1 10.0 10.0
17 Bug Screen
0.76 12.0 24.0
10.0 0.1 10.0 10.0
18 Bug Screen
0.76
19 Bug Screen
0.76
THERMAL MASS FOR
HIGH MASS DESIGN
Area Thick. Heat Inside
Condition Location/
Type
(sq (in.) Cap. Cond. R -Val.
JA IV Reference Status Comments
Concrete, Heavyweight
960 4.00 28 0_98 2
26-A1 New Master Suite / Slab on Grade
Concrete, Heavyweight
411 4.00 28 0.98 0
26-A1 New Master Suite / Slab on Grade
Concrete, Heavyweight
468 4.00 28 0.98 2
26-A1 New Great/Kit/Break/Din/Den / Slab on
Concrete, Heavyweight
2,989 4.00 28 0.98 0
26-A1 New FO ®Kit/Break/Din/Den / Slab on
Concrete, Heavyweight
322 4.00 28 0.98 2
26-A1 New m 18 /Slab on Grade
PERIMETER LOSSES
Insulation
Condition Location/
Type Length R -Val. Location
JA IV Reference Status Comments
Slab Perimeter
105 None No Insulation
26-A1 New Master Suite
Slab Perimeter
29 None No Insulation
26-A1 New Master Suite
Aoftb Perimeter
37 None No Insulation
26-A1 New Great/Kit/Break/Din/Den
Perimeter
147 None No Insulation
26-A1 New Great/Kit/Break/Din/Den
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:5 of 31 1
Certificate Of Compliance : Residential (Part 2 of 4) CF -1 R
1/5/2007
Date
FENESTRATION SURFACES
# Type Area U-Factorl SHGC2
True Cond.
Azm. Tilt Stat. Glazing Type
Location/
Comments
2Q
21
Window
Window
Right
Front
(SWl
(W)
_220_ 0-390 NERC 0_37 NERC ?9_5_ _9Q New Sierra Pacific Windows & Doors
46.5 0.390 NFRC 0.37 NFRC 270 90 New Sierra Pacific Windows & Doors
Creat/Kit/break/Din/Den
Great/Kit/Break/Din/Den
22
Window
Front
(W)
11.0 0.390 NFRC 0_37 NFRC
270 90 New Sierra Pacific Windows & Doors
Great/Kit/Break/Din/Den
23
Window
Front
(NW)
46.5 0.390 NFRC 0.37 NFRC
315 90 New Sierra Pacific Windows & Doors
Great/Kit/Break/Din/Den
24
Window
Front
(NW)
11.0 0.390 NFRC 0_37 NFRC
315 90 New Sierra Pacific Windows & Doors
Great/Kit/Break/Din/Den
25
Skylight
Left
(N)
4.0 0.800 NFRC 0_39 NFRC
0 20 New Double Metal Tinted
Bedroom 18
2E
Window
Left
(N)
7.0 0_390 NFRC 0_37 NFRC �10 90 New Sierra Pacific Windows & Doors
Bedroom 18
27
Window
Left
(N)
3.0 0.390 NFRC 0.37 NFRC
10 90 New Sierra Pacific Windows & Doors
Bedroom 18
2$
Window
Rear
(E)
76.0 0_390 NFRC 0_37 NFRC 100 90 New Sierra Pacific Windows & Doors
Bedroom 18
2a
Skylight
Left
(N)
4.0 0_800 NFRC 0_39 NFRC 0 20 New Double Metal Tinted
Guest Suite
M
Window
Right
(SE)
30.0 0.390 NFRC 0_37 NFRC
150 90 New Sierra Pacific Windows & Doors
Guest Suite
31
Window
Right
(S)
46.5 0.390 NFRC 0_37 NFRC
195 90 New Sierra Pacific Windows & Doors
Guest Suite
,2
Window
Right
(S)
10.0 0_390 NFRC JIN NFRC 195 qQ New Sierra Pacific Windows & Doors
Guest Suite
33
Window
Right
(S)
34.0 0.390 NFRC 0_37 NFRC
195 90 New Sierra Pacific Windows & Doors
Guest Suite
34
Window
Right
(S)
27.1 0.390 NFRC 0.37 NFRC
195 90 New Sierra Pacific Windows & Doors
Guest Suite
35
Window
Right
(S)
46.5 0.390 NFRC 0_37 NFRC
195 90 New Sierra Pacific Windows & Doors
Guest Suite
36
Window
Right
(S)
54.0 0.390 NFRC 0_37 NFgc,,
195 90 New Sierra Pacific Windows & Doors
Guest Suite
37
Window
Front
(W)
27.0 0.390 NFRC 0_37 NFRC
285 90 New Sierra Pacific Windows & Doors
Guest Suite
-M
Window
Front
(W)
8.0 _ 0.390 NFRC 0_37 NFRC 285 90 New Sierra Pacific Windows & Doors
Guest Suite
1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 1166.
INTERIOR AND EXTERIOR SHADING
Area Thick. Heat
Inside
Condition
Location/
Type
(sf)
(in.)
Cap.
Cond. R -Val.
JA IV Reference
Status
Comments
Concrete, Heavyweight
156
Window
28
Overhang
26-A1
New
Left Fin
Concrete, Heavyweight
Right
Fin
28
#
Exterior Shade Type
SHGC
Hgt.
Wd.
Len.
Hgt.
LExt.
REA
Dist.
Len.
Hgt.
Dist.
Len.
Hgt.
20
Bug Screen
0.76
21
Bug Screen
0.76
7.8
6.0
2.0
0.1
2.0
2.0
0.1
2.0
0
0.1
2.0
0
Bug Screen
0.76
1.8
3.0
2.0
0.1
2.0
2.0
0.1
2.0
0
0.1
2.0
0
4iBug
Screen
0.76
7.8
6.0
2.
0,_1
2.0
2.0
0.1
_2.0
0
0.1
2.0
0
_
Bug Screen
0.76
1.8
6.0
2.0
0.1
2.0
2.0
0.1
2.0
0
0.1
2.0
0
25
None
1.00
26
Bug Screen
0.76
27
Bug Screen
0.76
28
Bug Screen
0.76
9.3
8.2
6.0
0.1
6.0
6.0
29
None
1.00
30
Bug Screen
0.76
31
Bug Screen
0.76
32
Bug Screen
0.76
33
Bug Screen
0.76
34
Bug Screen
0.76
7.8
3.5
2.0
0.1
2.0
2.0
35
Bug Screen
0.76
7.8
6.0
2.0
0.1
2.0
2.0
0.1
2.0
0
0.1
2.0
0
36
Bug Screen
0.76
5.4
10.0
2.0
0.1
2.0
2.0
0.1
2.0
0
0.1
2.0
0
37
Bug Screen
0.76
4.8
6.0
2.0
0.1
2.0
2.0
0.1
2.0
0
0.1
2.0
0
38
Bug Screen
0.76
THERMAL MASS FOR HIGH MASS DESIGN
PERIMETER LOSSES
Area Thick. Heat
Inside
Condition
Location/
Type
(sf)
(in.)
Cap.
Cond. R -Val.
JA IV Reference
Status
Comments
Concrete, Heavyweight
156
4.00
28
0.98 0
26-A1
New
Bedroom 18 / Slab on Grade
Concrete, Heavyweight
823
4.00
28
0_98 2
26-A1
New
Guest Suite / Slab on Grade
Concrete, Heavyweight
548
4.00
28
0.98 0
26-A1
New
Guest Suite / Slab on Grade
PERIMETER LOSSES
Insulation
Condition
Location/
Type
Length
R -Val. Location
JA IV Reference
Status
Comments
Slab Perimeter
11
None No Insulation
26-A1
New
Bedroom 18
Slab Perimeter
94
None No Insulation
26-A1
New
Guest Suite
Afteb Perimeter
91
None No Insulation
26-A1
New
Guest Suite
Run Initiation Time: 01/05/07 16:10:56 Run Code: 1168042256
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:6 of 31
Certificate Of Compliance : Residential (Part 2 of 4) CF -1 R
1/5/2007
Date
True Cond. Location/
# Type Area U-Factorl SHGC2 Azm. Tilt Stat. Glazinq Tvge Comments
3R Window Front (gyp() 140 0_390 NFRC J= NFR •285 A0_ New Sierra Pacific Windows & noorc Guest Suite
40 Window Front (W) 5.0 0.390 NFRC 0.37 NFRC 285 90 New Sierra Pacific Windows & Doors Guest Suite
41 Window Left (N) 58.0 0.390 NFRC 0_37 NFRC 15 90 New Sierra Pacific Windows & Doors Guest Suite
42 Window Left (N) 86.2 0.390 NFRC 0_37 NFRC 0 90 New Sierra Pacific Windows & Doors Guest Suite
1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 116B.
INTERIOR AND EXTERIOR SHADING Window Overhang Left Fin Right Fin
# Exterior Shade Type SHGC Hgt. Wd. Len. Hgt. LExt. RExt. Dist. Len. Hgt. Dist. Len. Hgt.
39 Bug Screen 0.76
40 Bug Screen 0.76
Bug Screen 0.76
Bug Screen 0.76
THERMAL MASS FOR HIGH MASS DESIGN
Area Thick.Heat Inside Condition Location/
Type (sf) (in.) Cap. Cond. R -Val. JA IV Reference Status Comments
PERIMETER LOSSES Insulation
Type Length R -Val. Location
Condition Location/
JA IV Reference Status Comments
Run Initiation Time: 01/05/07 16:10:56 Run Code: 1168042256
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:7 of 31
Certificate Of Compliance : Residential (Part 3 of 4) CF -1 R
Wlect Title
HVAC SYSTEMS
1/5/2007
Date
Location
Heating
Type
Minimum
Eff
Cooling
Type
Minimum _
Eff
Condition
Status
Thermostat
Type
HVAC -1
Central Furnace
80% AFUE
Split Air Conditioner
14.0 SEER
New
Setback
HVAC -2, 3 & 4
Central Furnace
80% AFUE
Split Air Conditioner
14.0 SEER
New
Setback
HVAC -5
Central Furnace
80% AFUE
Split Air Conditioner
14.0 SEER
New
Setback
HVAC DISTRIBUTION
Location
Heating
Cooling
Duct
Location
HVAC -1
Ducted
Ducted
Attic
HVAC -2, 3 & 4
Ducted
Ducted
Attic
HVAC -5
Ducted
Ducted
Attic
Hydronic Piping Pipe Pipe Insul.
System Name Length Diameter Thick.
Duct
Condition
Ducts
R -Value Status
Tested?
4.2
New
No
4.2
New
No
4.2
New
No
WATER HEATING SYSTEMS
Water Heater
System Name Type Distribution
Rated
# in Input
Syst. (Btu/hr)
Tank
Cap.
(gal)
Energy
Condition Factor
Status or RE
Tank Insul.
Standby R -Value
Loss (%) Ext.
American G32 -75T75 -4N0"` Large Gas Recirc/Time+Temp
2 75,100
75
New
0.80
2.53% 0.0
Multi -Family Central Water Heating Details
Hot Water Pump
Control # HP Type
Hot Water Piping Length (ft)
In Plenum Outside Buried
Add 1/2"
Insulation
COMPLIANCE STATEMENT
This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of
Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall design responsibility.
The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insulation installation quality,
and building envelope sealing require installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code) Documentation Author
Name: Name: Tim Scott
Title/Firm: Prest Vuksic Architects
Address: 44-530 San Pablo, Suite 200
Palm DesertCA 92260
Telephone: 760 779 393 Lic. #: G Z O
' •S•o
(signature) (date)
Enforcement Ag
Name:
Title/Firm:
Address:
Telephone:
nature) (date)
Title/Firm: Scott Design & Title 24
Address: 77085 Michigan Dr.
Palln DesertA 92211
Telephonel(74)_200-47 0
(signature) — I (date)
Certificate Of Compliance : Residential (Part 3 of 4) CF -1 R
Title
1/5/2007
Date
Heating Minimum Cooling Minimum Condition Thermostat
Location Type Eff Type Eff Status Type
HVAC -6 Central Furnace 80% AFUE Split Air Conditioner 14.0 SEER New Setback
HVAC DISTRIBUTION
Duct
Location Heatina Coolina Location
HVAC -6 Ducted Ducted Attic
Hydronic Piping Pipe Pipe Insul.
System Name Length Diameter Thick.
Duct Condition Ducts
R -Value Status Tested?
4.2 New No
WATER HEATING SYSTEMS Rated Tank Energy Tank Insul.
Water Heater # in Input Cap. Condition Factor Standby R -Value
System Name Type Distribution Syst. (Btu/hr) (gal) Status or RE Loss (%) Ext.
Multi -Family Central Water Heating Details
Hot Water Pump Hot Water Piping Length (ft) Add 1/2"
Control # HP Type In Plenum Outside Buried Insulation
REMARKS
COMPLIANCE STATEMENT
This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of
Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall design responsibility.
The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insulation installation quality,
and building envelope sealing require installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Name:
Title/Firm: Prest Vuksic Architects
Address: 44-530 San Pablo, Suite 200
Palm DesertCA 92260
Telephone: 760 779 3 Lic. #: C_ - 'L
,G'J•0
(signature) (date)
Enforcement Ag cy
Name:
Title/Firm:
Address:
Telephone:
•
gnature) (date)
Documentation Author
Name: Tim Scott .
Title/Firm: Scott Design & Title 24
Address: 77085 Michigan Dr.
Pal Desert92211
Telephong, 200-478
/ 0
(signature (date)
Certificate Of Compliance : Residential (Part 4 of 4) CF -1 R
Title
11512007
Date
Special Features and Modeling Assumptions
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special
written justification and documentation, and special verification to be used with the performance approach. The local enforcement
agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the
adequacy of the special justification and documentation submitted. I Plan I Field
The DHW System "American G32 -75T75 -4N0**— is a Large Gas water heater with Pilot Loss = 0 btuh.
The Roof "R-38 Roof(R.30.2x14.16)" includes credit for a Radiant Barrier installed per Section 3.3.3 of the Residential Manual.
The HVAC System "HVAC -1" must meet all CEC Criteria for a Zonally Controlled system serving only Sleeping Areas.
HIGH MASS Design - Verify Thermal Mass: 960 sqft Covered Slab Floor, 4.00" thick at Master Suite
HIGH MASS Design - Verify Thermal Mass: 411 sqft Exposed Slab Floor, 4.00" thick at Master Suite
The HVAC System "HVAC -2, 3 8, 4" must meet all CEC Criteria for a Zonally Controlled system serving only Living Areas.
HIGH MASS Design - Verify Thermal Mass: 468 sqft Covered Slab Floor, 4.00" thick at Great/Kit/Break/Din/Den
HIGH MASS Design - Verify Thermal Mass: 2989 sqft Exposed Slab Floor, 4.00" thick at GreaUKit/Break/Din/Den
HIGH MASS Design - Verify Thermal Mass: 322 sqft Covered Slab Floor, 4.00" thick at Bedroom 18
HIGH MASS Design - Verify Thermal Mass: 156 sqft Exposed Slab Floor, 4.00" thick at Bedroom 18
The HVAC System "HVAC -6" must meet all CEC Criteria for a Zonally Controlled system serving only Sleeping Areas.
HIGH MASS Design - Verify Thermal Mass: 823 sqft Covered Slab Floor, 4.00" thick at Guest Suite
HIGH MASS Design - Verify Thermal Mass: 548 sqft Exposed Slab Floor, 4.00" thick at Guest Suite
HERS Required Verification
Items in this section require field testing and/or verification by a certified home energy rater under the supervision of a CEC-
approved HERS provider using CEC approved testing and/or verification methods and must be reported on the CF -4R Plan Field
installation certificate.
e HVAC System "HVAC -1" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve.
I
The Cooling System "Carrier 38TXA060/58DLX110" includes credit for a 11.1 EER Condenser. A certified HERS rater must field
verify the installation of the correct Condenser.
The HVAC System "HVAC -2, 3 & 4" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion
Valve.
The Cooling System "Carrier 38TXA048/58DLX090" includes credit for a 11.5 EER Condenser. A certified HERS rater must field
verify the installation of the correct Condenser.
The HVAC System "HVAC -5" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve.
The Cooling System "Carrier 38TXA024/58DLX045 includes credit for a 11.2 EER Condenser. A certified HERS rater must field
verify the installation of the correct Condenser.
The HVAC System "HVAC -6" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve.
The Cooling System "Carrier 38TXA060/58DLX110" includes credit for a 11.1 EER Condenser. A certified HERS rater must field
verify the installation of the correct Condenser.
6—
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 10 of 31 1
Mandatory Measures Summary: Residential (Page 1 of 2) MF -1 R
NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent compliance
• requirements from the Certificate of Compliance supercede the items marked with an asterisk (*) below. When this checklist is incorporated into the permit
documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether
they are shown elsewhere in the documents or on this checklist only.
•
•
DESCRIPTION Check or initial applicable boxes or check NA if not applicable and included with the ENFORCE -
permit application documentation. N/A DESIGNER MENT
Building Envelope Measures
150(a): Minimum R-19 in wood ceiling insulation or equivalent U -factor in metal frame ceiling.
§ 150(b): Loose fill insulation manufacturer's labeled R -Value:
150(c): Minimum R-13 wall insulation in wood framed walls or equivalent U -factor in metal frame walls (does not
apply to exterior mass walls).
❑
O
❑
❑
❑
❑
❑
❑X
❑
*§ 150(d): Minimum R-13 raised floor insulation in framed floors or equivalent U -factor.
❑
0
❑
§ 150(e): Installation of Fireplaces, Decorative Gas Appliances and Gas Logs.
❑
❑X
❑
1. Masonry and factory -built fireplaces have:
❑
❑X
❑
a. closable metal or glass door covering the entire opening of the firebox
❑
❑
❑
b. outside air intake with damper and control, flue damper and control
❑
❑
❑
2. No continuous burning gas pilot lights allowed.
❑
❑
❑
§ 150(f): Air retarding wrap installed to comply with §151 meets requirements specified in the ACM Residential Manual.
❑
❑
❑
§ 150(g): Vapor barriers mandatory in Climate Zones 14 and 16 only.
❑
❑
❑
§ 150(1): Slab edge insulation - water absorption rate for the insulation alone without facings no greater than 0.3%, water vapor
❑
❑
❑
permeance rate no greater than 2.0 perm/inch.
❑
❑X
❑
§ 118: Insulation specified or installed meets insulation installation quality standards. Indicate type and include
❑
a
❑
CF -6R Form:
❑
❑X
❑
§ 116-17: Fenestration Products, Exterior Doors, and Infiltration/Exfiltration Controls.
1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage.
❑
❑X
❑
2. Fenestration products (except field fabricated) have label with certified U -Factor, certified Solar Heat Gain
❑
N
❑
Coefficient (SHGC), and infiltration certification.
3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed.
❑
❑
❑
Space Conditioning, Water Heating and Plumbing System Measures
§ 110-13: HVAC equipment, water heaters, showerheads and faucets certified by the Energy Commission.
❑
❑X
❑
§ 150(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA or ACCA.
❑
❑X
❑
§ 150(i): Setback thermostat on all applicable heating and/or cooling systems.
❑
❑X
❑
§ 1500): Water system pipe and tank insulation and cooling systems line insulation.
1. Storage gas water heaters rated with an Energy Factor less than 0.58 must be externally wrapped with insulation
❑
❑
❑
having an installed thermal resistance of R-12 or greater.
2. Back-up tanks for solar systems, unfired storage tanks, or other indirect hot water tanks have R-12 external
❑
❑
❑
insulation or R-16 internal insulation and indicated on the exterior of the tank showing the R -value.
3. The following piping is insulated according to Table 150-A/B or Equation 150-A Insulation Thickness:
1. First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire
❑
❑X
❑
length of recirculating sections of hot water pipes shall be insulated to Table 1508.
2. Cooling system piping (suction, chilled water, or brine lines), piping insulated between heating source and
❑
❑X
❑
indirect hot water tank shall be insulated to Table 150-B and Equation 150-A.
4. Steam hydronic heating systems or hot water systems > 15 psi, meet requirements of Table 123-A.
❑
❑
❑
5. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance,
❑
❑
❑
and wind.
6. Insulation for chilled water piping and refrigerant suction piping includes a vapor retardant or is enclosed
❑
❑
❑
entirely in conditioned space.
7. Solar water -heating systems/collectors are certified by the Solar Rating and Certification Corporation.
❑
❑
❑
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number:
Page: 11 of 31
Mandatory Measures Summarv: Residential (Page 2 of 2) MF -1 R
NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent
• compliance requirements from the Certificate of Compliance supercede the items marked with an asterisk (*) below. When this checklist is incorporated
into the permit documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory
measures whether they are shown elsewhere in the documents or on this checklist only.
•
•
DESCRIPTION Instructions: Check or initial applicable boxes when completed or check N/A if not ENFORCE -
applicable. N/A DESIGNER MENT
Space Conditioning, Water Heating and Plumbing System Measures: (continued)
§ 150(m): Ducts and Fans
1. All ducts and plenums installed, sealed and insulated to meet the requirements of the CMC Sections 601, 602, 603, 604, ❑ 0 ❑
605, and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minumum installed level of -
R-4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system
that meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol sealant that meets the requirements
of UL 723. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh
or tape shall be used.
2. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than
❑
X❑
❑
sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and
a. At least 36" of pipe between filter and heater for future solar heating.
❑ ❑ ❑
support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause
❑ ❑ ❑
3. Pool system has directional inlets and a circulation pump time switch.
❑ ❑ ❑
reductions in the cross-sectional area of the ducts.
❑ 2 ❑
burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr)
3. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive
❑
®
❑
duct tapes unless such tape is used in combination with mastic and draw bands.
❑ ® ❑
150-C, and do not contain a medium screw base socket (E24/E26). Ballasts for lamps 13 Watts or greater are
4. Exhaust fan systems have back draft or automatic dampers.
❑
❑
❑
5. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operating
❑
❑
❑
dampers.
provided that these luminaires are controlled by switches separate from those controlling the high efficacy luminaires.
6. Protection of Insulation. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment
❑
®
❑
maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water
❑ X❑ ❑
controlled by an occupant sensor that complies with Section 1) 9(d) that does not turn on automatically or have an
retardant and provides shielding from solar radiation that can cause degradation of the material.
❑ ❑X ❑
certified to ASTM E283 and labeled as air tight (AT) to less than 2.0 CFM at 75 Pascals.
7. Flexible ducts cannot have porous inner cores.
❑
®
❑
§ 114: Pool and Spa Heating Systems and Equipment
1. A thermal efficiency that complies with the Appliance Efficiency Regulations, on-off switch mounted outside of the
❑ ❑ ❑
heater, weatherproof operating instructions, no electric resistance heating and no pilot light.
2. System is installed with:
a. At least 36" of pipe between filter and heater for future solar heating.
❑ ❑ ❑
b. Cover for outdoor pools or outdoor spas.
❑ ❑ ❑
3. Pool system has directional inlets and a circulation pump time switch.
❑ ❑ ❑
§ 115: Gas fired fan -type central furnaces, pool heaters, spa heaters or household cooking appliances have no continuously
❑ 2 ❑
burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr)
§ 118 (i): Cool Roof material meets specified criteria
❑ ❑ ❑
Lighting Measures
§ 150(k)l: HIGH EFFICACY LUMINAIRES OTHER THAN OUTDOOR HID: contain only high efficacy lamps as outlined in Table
❑ ® ❑
150-C, and do not contain a medium screw base socket (E24/E26). Ballasts for lamps 13 Watts or greater are
electric and have an output frequency no less than 20 kHz.
§ 150(k)l: HIGH EFFICACY LUMINAIRES - OUTDOOR HID: contain only high efficacy lamps as outlined in Table 150-C,
❑ ❑ ❑
luminaire has factory installed HID ballast.
§ 150(k)2: Permanently installed luminaires in kitchens shall be high efficacy luminaires. Up to 50% of the Wattage, as determined
❑ ❑X ❑
in Section 130(c), of permanently installed luminaires in kitchens may be in luminaires that are not high efficacy luminaires,
provided that these luminaires are controlled by switches separate from those controlling the high efficacy luminaires.
§ 150(k)3: Permanently installed luminaires in bathrooms, garages, laundry rooms, utility rooms shall be high efficacy luminaires.
❑ ❑X ❑
OR are controlled by an occupant sensor(s) certfied to comply with Section 119(d).
§ 150(k)4: Permanently installed luminaires located other than in kichens, bathrooms,garages, laundry rooms, and utility rooms
shall be high efficacy luminaires (except closets less than 70 ft) OR are confrolled by a dimmer switch OR are
❑ X❑ ❑
controlled by an occupant sensor that complies with Section 1) 9(d) that does not turn on automatically or have an
always on option.
§ 150(k)5: Luminaires that are recessed into insulated ceilings are approved for zero clearance insulation cover (IC) and are
❑ ❑X ❑
certified to ASTM E283 and labeled as air tight (AT) to less than 2.0 CFM at 75 Pascals.
§ 150(k)6: Luminaires providing outdoor lighting and permanently mounted to a residential building or to other buildings on the
❑ ❑ ❑
same lot shall be high efficacy luminaires (not including lighting around swimming pools/water features or other Article
680 locations) OR are controlled by occupant sensors with integral photo control certified to comply with Section 119(d).
§ 150(k)7: Lighting for parking lots for 8 or more vehicles shall have lighting that complies with Sections 130, 132, and 147.
❑ ❑ ❑
Lighting for parking garages for 8 or more vehicles shall have lighting that complies with Section 130, 131, and 146.
§ 150(k)8: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
❑ ❑ ❑
dwelling units shall be high efficacy luminaires OR are controlled by occupant sensor(s) certified to comply with Section
119(d).
EnergyPro 4.2 by EnergySoft User Number. 6712 Job Number:
Page: 12 of 31
Residential Kitchen Lighting Worksheet WS -5R
-aherty Residence 1/5/2007
ject Title Date
At least 50% of the total rated wattage of permanently installed luminaires in kitchens must be in luminaires that are high efficacy luminaires
as defined in Table 150-C. Luminaires that are not high efficacy must be switched separately.
Kitchen Lighting Schedule. Provide the following information for all luminaires to be installed in kitchens.
High Efficacy
Luminaire Type High Efficacy? Watts Quantity Watts Other Watts
(2) 26w Compact Fluorescent Triple 4 Pin Yes X No 74.0 x 13 = 962 or
Yes No x = or
Yes No x or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Total A:, 962 B: 0
COMPLIES IF A;-* B YES ® NO ❑
is
I EneravPro 4.2 by EnergvSoft User Number: 6712 Job Number: Paoe:13 of 31 1
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Faherty Residence 1/5/2007
TEM NAME FLOOR AREA
HVAC -1 1,371
26.0 of 68.8 of
Outside Air
0 cfm
Supply Fan
2025 cfm
68.8 of
68.8 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
Latent
I CFM
I Sensible
900
19,148
82
528
19,685
0
2,977
2,526
0
0
0
0
0
0
0
0
0
2,977
2,526
25.102F77777;2 24 736
Carrier 38TXA060/58DLX110 42,607 7,733 89,000
Total Adjusted System Output a2,6o7 7,733 89,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 pm Jan 12 am
105.0 of
Heating Coil
e of Heatina Pea
Supply Air Ducts
103.8 of
ROOMS
70.0 of
Return Air Ducts `5
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
110.0/72.5OF 76.4/61.8OF 76.4/61.8OF 55.0/53.8OF
O
Outside Air Supply Air Ducts
0 cfm Supply Fan Cooling Coil 56.4 / 54.4 of
2025 cfm 45.9% R.H. ROOMS
76.4/61.80F 75.0/61.3OF
Return Air Ducts I
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 14 of 31
i
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY 71
PROJECT NAME DATE
Faherty Residence 1/5/2007
STEM NAME FLOOR AREA
HVAC -2 3 & 4 3,457
Number of Systems
31
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
Heating System
Output per System
71,000
Total Output (Btuh)
213,000
Output (Btuh/sgft)
61.6
Cooling System
Output per System
46,500
Total Output (Btuh)
139,500
Total Output (Tons)
11.6
Total Output (Btuh/sgft)
40.4
Total Output (sgft/Ton)
297.4
CFM per System
Airflow (cfm)
Airflow (cfm/sgft)
Airflow (cfm/Ton)
' Outside Air (%)
Outside Air (cfm/sgft)
Note: values above given at ARI conditions
EATING SYSTEM PSYCHROMETRICS
26.0 of 69.10F
Outside Air
0 cfm
69.1 of
HVAC E UI
1,720
5,160
1.49
443.9
2000
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
CFM
I Sensible
2,246
37,097
-20
Lj,n
39,93
0
5,768
5,123
0
0
0
0
0
0
0
0
0
5,7681
5,123
48,633 -20
Carrier 38TXA048/58DLX090
96,749
22,720
Total Adjusted System Output 86,749 22,720
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 pm
am Tel
107.9 of
Heating Coil
Supply Fan
5160 cfm
213,000
213,000
Jan 12 am
107.9 of
30Supply Air Ducts
106.9 of
ROOMS
70.0 of
Return Air Ducts `5
:OGLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
10.0 / 72.5 of 76.1 / 62.1OF 58.4 / 55.6 of 58.4 / 55.6 of
Supply Air Ducts
Outside Air O
0 cfm Cooling Coil Supply Fan 59.5 / 56.0 of
5160 cfm 47.1% R.H. ROOMS
76.1 / 62.0 of 75.0 / 61.7 of
Return Air Ducts I
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 15 of 31
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Faherty Residence 1/5/2007
STEM NAME FLOOR AREA
HVAC -5 478
26.0 of 68.9 of
Outside Air 0
0 cfm
Supply Fan
800 cfm
68.9 of
Total Room Loads
2eturn Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensiblel
Latent
I I CFM
I Sensible
356
8,123
508
173
7,163
at Time of Cooling
0
10.0 / 72.5 of
79.5 / 62.9 of 79.5 / 63.0 of
1,263
919
0
0
0
0
0
0
0
0
Supply Fan Cooling Coil
0
1,263
919
10,649 508 9 00
Carrier 38TXA024/58DLX045 20,761 86 35,000
Total Adjusted System Output 20,761 86 35,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 pm Jan 12m
'earn Temperatures at Time of Heatina. Peak)
68.9 °F%� 110.0 °F
Heating Coil
Supply Air Ducts
109.0 of
ROOMS
70.0 of
IE
IE
Return Air Ducts
:DOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures
at Time of Cooling
Peak)
10.0 / 72.5 of
79.5 / 62.9 of 79.5 / 63.0 of
55.1 / 53.7 of
O
Supply Air Ducts
Outside Air
0 cfm
Supply Fan Cooling Coil
56.6 / 54.3 of
800 cfm
ROOMS
41.8% R.H.
78.0/62.4OF
79.5/62.90F
Return Air Ducts
I
1 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Paae:16 of 31 1
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Faherty Residence 1/5/2007
STEM NAME FLOOR AREA
HVAC -6 1,371
EATING S
26.0 of
Outside
��
0 cfm
68.5 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
Latent
CFM
I Sensible
1,148
22,241
-36
613
25,015
0
3,458
3,209
0
0
0
0
0
0
0
0
0
3,458
3,209
29157 -36 1 31434
Carrier 38TXA060/58DLX110 46,159 5,330 89,000
Total Adjusted System Output 46,159 5,330 89,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK- Aug 2 pm Jan 12 am
M PSYCHROMETRICS (Airstream Temperatures at Time of Heatina Peak)
68.5 of 68.5 of 109.8 of
0
Supply Fan Heating Coil
2025 cfm
Return Air nits
Supply Air Ducts
108.3 of
ROOMS
70.0 of
COOLING SYSTEM PSYCHROMETRICS Airstream. Temperatures at Time of Coolin Peak
110.0/72.50F 79.6 63.2 of 79.6 / 63.3 of 58.2 / 55.5 of
Supply Air Ducts
Outside Air
O W
0 cfm Supply Fan Cooling Coil 59.8 / 56.1 of
2025 cfm 42.6% R.H. ROOMS
79.6/63.2 of 78.0 / 62.7 of
h Return Air Ducts "I
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 17 of 31 1
ROOM LOAD SUMMARY
PROJECT NAME
Faherty Residence
DATE
1/5/2007
STEM NAME
HVAC -1
FLOOR AREA
1,371
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Ault.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Master Suite
Master Suite
1
900
19,148
82
900
19,148
82
528
19,685
IL
I
PAGE TOTAL 1 900 19,148 82 528 1 19,685
TOTAL 1 900 19,148 82 528 19,685
EnergyPro By EnergySoft User Number: User Job Number: Page: 18 of 31
ROOM LOAD SUMMARY
PROJECT NAME DATE
Faherty Residence 1/5/2007
TEM NAME FLOOR AREA
HVAC -2, 3 & 4 3,457
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Great/Kit/Break/Din/Den
Great/Kit/Break/Din/Den
1
2,246
37,097
-201
2,246
37,097
-201
1,016
39,931
PAGE TOTAL 1 2,246 37,097 -201 1,016 39,931
TOTAL 1 2,246 37,097 -201 1,016 39,931
EnergyPro By EnergySoft User Number: User Job Number: Page: 19 of 31
ROOM LOAD SUMMARY
PROJECT NAME
Faherty Residence
DATE
1/5/2007
TEM NAME
HVAC -5
FLOOR AREA
478
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Bedroom 18
Bedroom 18
1
356
8,123
508
356
8,123
508
173
7,163
PAGE TOTAL 1 356 8,123 508 173 7,163
TOTAL 1 356 8,123 508 173 7,163
11 EnergyPro By EnergySoft User Number: User Job Number: Page:20 of 31
ROOM LOAD SUMMARY
PROJECT NAME
Faherty Residence
DATE
1/5/2007
TEM NAME
HVAC -6
FLOOR AREA
1,371
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Guest Suite
Guest Suite
1
1,148
22,241
-36
1,148
22,241
-36
613
25,015
PAGE TOTAL 1 1,148 22,241 -36 613 25,015
TOTAL 1 1,148 22,241 -36 613 25,015 li
EnergyPro By EnergySoft User Number: User Job Number: Page:21 of 31
4
ROOM HEATING PEAK LOADS
roject Title Date
herty Residence 11/5/2007
Room Information Desi n Conditions
Room Name Master Suite Time of Peak Jan 12 am
Floor Area 1,371 Outdoor Dry Bulb Temperature 26°F
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value QT of Btu/hr
1
1
1371.0
X
X
x
X
X
X
X
x
X
X
x
X
x
X
X
X
x
x
x
X
X
X
X
x
X
X
x
X
X
X
X
X
X
X
X
X
X
x
X
0.0240
X
x
x
x
X
x
x
X
X
X
x
X
X
X
X
X
X
x
x
X
X
X
x
X
X
x
x
X
X
X
X
x
X
x
X
x
X
x
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
1,450
175.0
0.0690
44
531
56.0
0.3900
44
961
11.5
0.0690
44
35
127.0
0.0690
44
386
148.0
0.3900
44
2,540
349.0
0.0690
44
1,060
11.0
0.3900
44
189
0,3900
44
189
8.0
0.3900
44
137
11.0
0.3900
44=igg
51.0
0.3900
44
875
11.0
0.3900
44
189
237.0
0.0690
44=
720
180.0
0.0690
44=54
erimeter = 105.0
0.7300
44
3,373
perimeter -29.0
44
931
nems snown wnn an asrerisK k-) aenoce conauction inrougn an mrenor surrace to anomer room. Page Total: 14,299
Infiltration: r 1.00 X 1.064 X 1 371 X 11.30 X 0.445 / 6 ] x 44 = 5 386
schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 19,685
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 22 of 31
i
ROOM HEATING PEAK LOADS
roject Title Date
hertResidence 11/5/2007
Room Information Desi n Conditions
Room Name Time of Peak Jan 12 am
Floor Area 3,457 Outdoor Dry Bulb Temperature 26°F
Indoor Dry Bulb Temperature 70 OF
Conduction
ISierra Pacific Windows & Doors I
Area
3,453.0
4.0
74.5
46.5
11.0
148.3
21.0
52.0
3.0
322.0
66.0
288.0
18.0
22.0
179.0
60.0
96.0
22.0
244.5
46.5
11.0
41.5
46.5
11.0
perimeter = 37.0
perimeter = 147 n-
U -Value
OT OF
Btu/hr
3,651
141
226
798
189
450
360
892
51
51
978
1,133
4.942
55
37A
543
291
378
742
798
moi]
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 26 350
Infiltration: 1 1.00 X 1.064 X 3 457 X 12.10 x 0.416 / 6] X 44 = 13 581
chedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 39,931
EnergyPro 4.2 by Energysoft User Number: 6712 Job Number: Page: 23 of 31
f i ! 9 11 �.
ROOM HEATING PEAK LOADS
roject TitleDate
hert Residence 1 /5/2007
Room Information Desi n Conditions
Room Name Bedroom 18 Time of Peak Jan 12 am
Floor Area 478 Outdoor Dry Bulb Temperature 26OF
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT of Btu/hr
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 5 348
Infiltration: r 1.00 x 1.064 x a7s x 11.30 x o.a3o / 6] x ® = 1 s14
schedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 7,163
EnergyPro 4.2 by EnergySoft . User Number: 6712 Job Number: Page: 24 of 31
474.0
x
x
X
x
x
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
X
X
x
x
x
x
x
X
x
x
x
x
x
x
X
x
X
x
X
0.0240
X
X
X
x
X
X
X
X
X
X
x
x
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
X
x
x
x
x
x
X
x
x
X
X
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
501
4.0
0.8000
44
141
363.0
0.0690
44
1,102
7.0
0.3900
44
120
3.0
0.3900
44
51
88.0
0.0690
441
267
76.0
0.3900
44
1,304
63.0
0.0690
44
191
perimeter —
0,7300
44
1,317
perimeter = 11.0
0.7300
44
353
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 5 348
Infiltration: r 1.00 x 1.064 x a7s x 11.30 x o.a3o / 6] x ® = 1 s14
schedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 7,163
EnergyPro 4.2 by EnergySoft . User Number: 6712 Job Number: Page: 24 of 31
! r!9
ROOM HEATING PEAK LOADS
roject Title Date
hertResidence 1 /5/2007
Room Information Desi n Conditions
Room Name Guest suite Time of Peak Jan 12 am
Floor Area 1,371 Outdoor Dry Bulb Temperature 26°F
Indoor Dry Bulb Temperature 70°F
Conduction Area U -Value AT of Btu/hr
IR -21 Wall (W.19.2x6.16)
1367.0
x
x
X
x
x
X
x
X
X
X
X
X
x
x
X
X
X
X
X
x
x
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0.0240
X
X
X
X
X
X
X
X
X
X
X
X
x
x
X
X
X
X
X
X
x
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
1,445
4.0
0.8000
44
141
146.0
0.0690
44
443
145.0
0.0690
44
440
30.0
0.3900
44
515
486.9
0.0690
44
1,478
46.5
0.3900
44
798
10.0
0.3900
44
172
34.0
0,3900
44
583
27.1
0.3900
44=
465
46.5
0.3900
44=798
54.0
0.3900
44
927
241.0
0.0690
44
732
27.0
0.3900
44=
463
8.0
0.3900
44c137
14.0
0.3900
44
240
01900
44
86
504.0
0.0690
44=1,530
58.0
0.3900
44
995
86.2
0.3900
44
1,480
perimeter =
0,7300
44=3019
perimeter = 91.0
0.7300
44
2,923
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 19 811
Infiltration: 1 1.001 X 1.064 X 1 371 X 11.90 X 0.409 / 6] X � = 5 204
chedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 25,015
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 25 of 31
t I 1 0 .•
41
RESIDENTIAL ROOM COOLING LOAD SUMMARY
roject Title Date
hert Residence 11/5/2007
Room Information Desicin Conditions
Room Name: Master Suite Outdoor Dry Bulb Temperature: 111OF
Floor Area: 1,371 sf Outdoor Web Bulb Temperature: 730F
Indoor Dry Bulb Temperature: 750F Outdoor Daily Range: 340F
Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr
R-38 Roof R.30.2x14.16
R-21 Wall
W.19.2x6.16
R-21 Wall
W.19.2x6.16
R-21 Wall
W.19.2x6.16
R-21 Wall
W.19.2x6.16
R-21 Wall
W.19.24.16
R-21 Wall (W.19.24.16)
0.0690
33.0
E
127.0
0.0690
32.6
S
349.0
0.0690
26.0
N
1,371.0
x
X
X
X
X
X
X
x
X
X
X
X
0.0166
X
X
X
X
X
X
X
x
X
X
X
X
56.0
N
175.0
0.0690
24.3
E
11.5
0.0690
33.0
E
127.0
0.0690
32.6
S
349.0
0.0690
26.0
S
237.0
0.0690
27.1
(W)
180.0
0.0690
33.0
0.0
21.6
8.0
21.7
S
0.0
21.6
11.0
21.7
S
0.0
21.6
51.0
21.7
S
0.0
21.6
11.0
21.7
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
n
Page Total
Orientation
Shaded
Area
X
X
x
x
x
x
x
X+
X
GLF
+
+
+
+
+
+
+
+
Unshaded
Area
X
X
X
x
X
x
X
X
X
GLF
N
0.0x
21.6+
56.0x
24.3
E
28.9X
21.6+
119.1x
42.8
S
0.0
21.6
11.0
21.7
S
0.0
21.6
11.0
21.7
S
0.0
21.6
8.0
21.7
S
0.0
21.6
11.0
21.7
S
0.0
21.6
51.0
21.7
S
0.0
21.6
11.0
21.7
Page Total
1,276
294
26
285
626
443
410
3 361
Btu/hr
Internal Gain Btu/hr
Occu ants 2 X Occupants X 230 Btuh/oCC. = 460
P P
E ui ment 1 X Dwelling Units x 1 1,6001 Watts/sqft = 1,6001
Infiltration: 1.064 X 1.19 X 96.74 X = 440
Air Sensible CFM ELA DT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,148
Latent Gain Btu/hr
Occu ants 0 X Occupants x 200 Btuh/oCC. = 400
Infiltration: 4 771 X 1.19 X 96.74 X 0.00058 = 318
Air Latent CFM ELA AW
• TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 82
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:26 of 31
Ah
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Title Date
hert Residence 1/5/2007
Room Information Desicin Conditions
Room Name: Great/Kit/Break/Din/Den Outdoor Dry Bulb Temperature: 1110F
Floor Area: 3,457 sf Outdoor Web Bulb Temperature: 730F
Indoor Dry Bulb Temperature: 75OFOutdoor Daily Range: 340F
Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr
•
R-38 Roof R.30.2x14.16
R-21 Wall W.19.2x6.16
R-21 Wall W.19.2x6.16
R-21 Wall W.19.2x6.16
R-21 Wall W.19.2x6.16
R-21 Wall W.19.2x6.16
Solid Wood Door
R-21 Wall (W.19.2x6.16)
R-21 Wall W.19.2x6.16
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Skylight
5
K
Y
W
BB
cc
X
V
G
x
0.0166
X
x
0.0690
X
x
0.0690
X
x
0.0690
X
x
0.0690
X
x
0.0690
X
x
1.4500
X
X
0.0690
X
x
0.0690
X
X
238
X
X
21.6
X
X
510
X
3,213
118
249
723
41
- 321
- 905
- 112
= 205
Page Total i 5.889
Orientation
Shaded
Area
X
X
X
x
x
X
x+
GLF
+
+
+
+
+
+
Unshaded
Area
X
X
X
X
x
x
x
X
GLF
=
=
=
=
=
=
=
Btu/hr
(Sky)
0.0
30.7
4.0
83.5
334
N
0.0
21.6
46.5
21.6
1,006
N
0.0x
21.6+
11.0x
21.6=
238
N
0.0
21.6
21.0
24.3
510
N
0.0
21.6
52.0
24.3
1,263
N
0.0x
21.6+
3.0X
24.3=
73
N
0.0X
21.6+
3.0X
24.3=
73
E
66.0
6
21F1.6
0.0
42.8
1 428
E
227.5
60.5
42.
7 514
W
0.0
22.0
43.6X+
Page Total 13 399
Internal Gain Btu/hr
Occupants 3 X Occupants X 1 230 Btuh/occ. = 690
E ui ment 0 X Dwelling Units X 1 1,6001 Watts/sqft = 01
Infiltration: 1.064 x 1.19 x 243.93 x = 11111
Air Sensible CFM ELA Z�sT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 37,097
Latent Gain Btu/hr
Occu ants X Occupants X 200 Btuh/occ. = 600
Infiltration: 4 771 x 1.19 x 243.93 x 0.00058 = -801
Air Latent CFM ELA pW
• TOTAL HOURLY LATENT HEAT GAIN FOR ROOM -201
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:27 of 31
RESIDENTIAL ROOM COOLING LOAD SUMMARY
roject Title Date
herty Residence 1/5/2007
Room Information Desi n Conditions
Room Name: Great/Kit/Break/Din/Den Outdoor Dry Bulb Temperature: 111OF
Floor Area: 3,457 sf Outdoor Web Bulb Temperature: 730F
Indoor Dry Bulb Temperature: 75 of Outdoor Daily Range: 340F
•
ue surraces
1
1
Orientation Area U -Factor CLTD 1 Btu/hr
W 244.5 X 0.0690 X 33.0 = 557
NW 41.5 X 0.0690 X 30.2 = 87
x X =
x x
x X =
X x
x x
X X
X X
x X =
x x
X r X
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
7
Page i otal 1 6431
Orientation
Shaded
Area
x
x
x
X
X
x
X
X
GLF
+
+
+
+
+
+
Unshaded
Area
x
x
X
X
X
X
Page
GLF
=
=
=
SW
21.6+
22.0x
30.2=
SW
-0.0
0.0x
21.6+
22.0X
30.2=
8.9X
21.6+
37.6x
43.6=
W
9.2
21.6
1.8
43.6
NW
0.0X
21.6+
46.5X
33.5=
NW
21.6+
11.0x
33.5=
-0.0
Total
Btu/hr
Internal Gain Btu/hr
Occu ants 3 X Occupants X 230 Btuh/oCC. = 690
P P
E ui ment 0 x Dwelling Units X 1,6001 Watts/sgft = 1 0
Infiltration: 1.064 X 1.19 x 243.93 X = 11111
Air Sensible CFM ELA Z�T
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 37,097
Latent Gain Btu/hr
Occu ants F 31 x Occupants X 200 Btuh/oCC. = 600
Infiltration: 4 771 x 1.19 x 243.93 X -0.00058 = -801
Air Latent CFM ELA QW
ID TOTAL HOURLY LATENT HEAT GAIN FOR ROOM -201
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:28 of 31
f . #)-A) •
RESIDENTIAL ROOM COOLING LOAD SUMMARY
roject Title Date
herty Residence 1/5/2007
Room Information Desi n Conditions
Room Name: Bedroom 18 Outdoor Dry Bulb Temperature: 1110F
Floor Area: 478 sf Outdoor Web Bulb Temperature: 730F
Indoor Dry Bulb Temperature: 78OFOutdoor Daily Range: 340F
Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr
IR -21 Wall (W.19.2x6.16) I
D
N
474.0
X
X
X
X
X
X
X
X
X
x
X
X
0.0166
X
X
X
X
X
X
X
X
X
X
X
X
56.0
N
363.0
0.0690
24.3
E
88.0
0.0690
32.6
W
63.0
0.0690
32.4
24.3
N
0.0x
21.6+
3.0X
24.3
E
46.1
21.6
29.9
42.8
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
•
rage I otal
Orientation
Shaded
Area
x
X
X
x
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Unshaded
Area
X
X
x
X
X
X
X
X
X
GLF
(Sky)
30.7+
4.OX
83.5
N
-0.0
0.0
21.6
7.0
24.3
N
0.0x
21.6+
3.0X
24.3
E
46.1
21.6
29.9
42.8
Page Total
441
609
198
141
1 389
Btu/hr
Internal Gain Btu/hr
Occu ants 4 X Occupants X 230 Btuh/OCC. = 920
P P
E ui ment 1 X Dwelling Units X 1,6001 Watts/sgft = 1,6001
Infiltration: 1.064 X 1.15 X 33.73 X = 1361
Air Sensible CFM ELA DT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 8,123
Latent Gain Btu/hr
Occu ants F4 X Occupants X 1 2001 Btuh/OCC. = 800
Infiltration: 4 771 x 1.15 x 33.73 x 0.00158 = 292
Air Latent CFM ELA pW
• TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 508
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:29 of 31
A
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Title Date
pert Residence 1/5/2007
oom Information Desi n Conditions
Room Name: Guest Suite Outdoor Dry Bulb Temperature: 111OF
Floor Area: 1,371 sf Outdoor Web Bulb Temperature: 730F
Indoor Dry Bulb Temperature: 78 of Outdoor Daily Range: 340F
Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr
is
R-38 Roof R.30.2x14.16
R-21 Wall
W.19.2x6.16
R-21 Wall
W.19.2x6.16
R-21 Wall
W.19.2x6.16
R-21 Wall
W.19.24.16
R-21 Wall
W.19.24.16
SE
145.0
0.0690
29.3
S
486.9
0.0690
27.7
21.6
241.0
0.0690
32.1
N
1,367.0
x
X
X
X
X
X
x
x
x
x
x
x
0.0166
X
X
X
X
X
X
x
x
X
X
X
x
56.0
=
=
=
=
=
=
=
=
E
146.0
0.0690
32.3
SE
145.0
0.0690
29.3
S
486.9
0.0690
27.7
21.6
241.0
0.0690
32.1
N
504.0
0.0690
25.0
24.5
1,141
S
0.0x
21.6+
10.0x
24.5=
245
S
0.0
21.6
34.0
24.5
834
S
23.0
21.6
4.1
24.5
598
S
39.4
21.6
7.1
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Skylight
F
3
E
D
2
1
C
B
A
Page Total
Orientation
Shaded
Area
x
x
X
X
X
X
X,
X
GLF
+
+
+
+
+
+
+
Unshaded
Area
X
X
X
X
X
X
x
GLF
=
=
=
=
=
=
Btu/hr
(Sky)
0.0x
30.7+
4.Ox
83.5=
334
(SE)
0.0
21.6
30.0
27.4
821
S
0.0
21.6
46.5
24.5
1,141
S
0.0x
21.6+
10.0x
24.5=
245
S
0.0
21.6
34.0
24.5
834
S
23.0
21.6
4.1
24.5
598
S
39.4
21.6
7.1
24.5
1,027
S
54.0X
21.6+
0.0x
24.5=
1,169
W
5.4
21.6
21.6
40.
986
W
0.01
21.6+
8.0x
40.3=
322
Page Total I 7,477
Internal Gain Btu/hr
Occu ants 4 x Occupants x 230 Btuh/occ. = 920
P P
E ui ment 1 x Dwelling Units x 1,6001 Watts/sgft = 1,600
Infiltration: 1.064 x 1.15 x 96.74 x F 3-9031
Air Sensible CFM ELA DT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 22,241
Latent Gain
Occu ants 0 x Occupants x 200 BtUh/oCC.
Btu/hr
800
Infiltration: 4 77 x 1.15 x 96.74 x 0.00158 = -836
Air Latent CFM ELA pW
iTOTAL HOURLY LATENT HEAT GAIN FOR ROOM -36
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 30 of 31
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Title Date
herty Residence �1/5/2007
oom Information Desicin Conditions
Room Name: Guest Suite Outdoor Dry Bulb Temperature: 111OF
Floor Area: 1,371 sf Outdoor Web Bulb Temperature: 730F
Indoor Dry Bulb Temperature: 78OFOutdoor Daily Range: 340F
Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr
•
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
x
x
x
GLF
x
x
x
X
x
X
X
x
X
1 X
x
x
0.0x
x
x
40.3
x
x
21.6
x
x
N
x
x
58.0X
x
x
0.0
x
x
21.6
x
x
x
x
x
Page Total
Orientation
Shaded
Area
X
X
x
X
X
X
XF�
X1
X
GLF
+
+
+
+
+
+X
+
+
+
Unshaded
Area
x
X
x
X
X
x
X
1 X
GLF
W
0.0x
21.6+
14.0x
40.3
W
0.0
21.6
5.0
40.3
N
0.0x
21.6+
58.0X
25.6
N
0.0
21.6
86.2
21.6
1
Page Total
Btu/hr
Internal Gain Btu/hr
Occu ants 4 X Occupants X 230 Btuh/oCC. = 920
P P
E ui ment 1 X Dwelling Units x 1,6001 Watts/sqft = 1,6001
Infiltration: 1.064 X 1.15 X 96.74 X = 3903
Air Sensible CFM ELA DT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 22,2411
Latent Gain Btu/hr
Occu ants F4 X Occupants X 200 Btuh/oCC. = 800
Infiltration: 4 771 X 1.15 X 96.74 X F 836
Air Latent CFM ELA pw
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM -36
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:31 of 31