06-3646 (SFD) Title 24I TITLE 24 REPORT I Title 24 Report for: Faherty Residence 53-390 Del Gato Drive, the Traditions La Quinta, CA 92253 Project Designer: Prest Vuksic Architects 44-530 San Pablo, Suite 200 Palm Desert, CA 92260 (760) 779-5393 Report Prepared By: Tim Scott Scott Design & Title 24 77085 Michigan Dr. Palm Desert, CA 92211 (760) 200-4780 Job Number: Date: 1/5/2007 CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION DATEIJ!��BY�Jw 0& - .3lo 440 EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is orized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC - www.energysoft.com. I EnergyPro 4.2 by EnergySoft Job Number: User Number: 6712 1 Y 4 1 -k TABLE OF CONTENTS Cover Page 1 Table of Contents 2 Form CF -1 R Certificate of Compliance 3 Form MF -1 R Mandatory Measures Summary 11 Form WS -5R Residential Kitchen Lighting 13 HVAC System Heating and Cooling Loads Summary 14 Room Load Summary 18 Room Heating Peak Loads 22 Room Cooling Peak Loads 26 EnergyPro 4.2 by EnergySoft Job Number: User Number: 6712 Certificate Of Compliance : Residential (Part 1 of 4) CF -1 R -r-qhprtv Residence 1/5/2007 ject Ti le Date Project Address Building Permit # Design & Title 24 (760) 200-4780 sScott Documentation Author Telephone Plan Check/Date FneraVPro 15 Field Check/Date Compli ce Method Climate Zone TDV Standard Proposed Compliance (kBtu/sf-yr) Design Design Margin Space Heating 1.72 1.30 0.43 Space Cooling 56.87 49.94 6.93 Fans 8.55 8.65 -0.10 Domestic Hot Water 3.84 6.17 -2.33 Pumps 0.00 0.08 -0.08 Totals Percent better than Standard: 70.99 66.14 Building Type: [X-) Single Family ❑ Multi Family Building Front Orientation: Fuel Type: Fenestration: Area: 1,523 ft2 Ratio: 22.8% ❑ Addition ❑ Existing + Add/Alt (W) 280 deg Natural Gas Avg. U: Avg. SHGC: q'LDING ZONE INFORMATION e Name 0.39 0.37 Floor Area Volume HVAC' -1 137 _ 15 4 HVAC, -2, 3 & 4 3,457 41.8 HVAC -5 478 5 - HVAC -6 -HVAC -6 1,371 16.3 OPAQUE SURFACES Insulation Act. Type Frame Area U -Fac. Cay. Cont. Azm. Tilt Rnnf Wnnd 1 371 ()()?4 R-38 R_7 0 _� n Wall Wood 175 0 069 R_21 R-0.0 if) 90 Wall Wood 12 0 069 R-21 R-0.0 90 _90 Wall Wnnd 127 n n69_ R_91 R_0 0 100 9Il Wall Wood 349 0.069 R-21 R-0.0 180 90 Wall Wood 237 0069 R -91 R-0 0 ign go Wall Wnnd 1R0 _0069_ -91R-0 n 97n gn Rnnf Wnnd 3 453 0094 R_38 R_7 n -0 2n Wall Wnnd 74 0.069 R-21 _R-0p_0_gn Wall Wood 148 _006,9_-21X0.0_1Q90 Wall Wnod 322 n 069 R_91 R_0 n inn gn Wall Wnnd 1R n n69 R-21 R_0 0 270_ gn Wall Wood 179 0 069 R_91 R-0 0 180 9Q noor None 24 1.450 None R-0.0 _180_0 Wall Wnnd 60 0.069 R_21 _B_p 0 190 90 Wall Wnnd 96 0069 R-21 R-0.0 _9260 Wall Wnnd 244 o n6g _$21 R -n fl_ AZO A0 Wall Wnod 42 n n69 R_91 R -n n 31.5 q() Rnnf Wnnd 474 n n24 R_38 R-7 n n 9n Wall Wood 363 0069 R_21 R-0.0 10 90 Wall Wood 88 00.69 R21R-0 0 X00_90 Wall Wood 63 0.069 R_21 R-0.0 _28.0 9n Amlhnnf Wood 1,367 0024 -38 - 0-0 90 Wnnd 146 n nF;9_ R_91 _R-0 D_ i m gn Wall Wnnd 145 n 069 R21R-0J11Sin gIl MDR Total Conditioned Floor Area: Existing Floor Area: Raised Floor Area: Slab on Grade Area: Average Ceiling Height: Number of Dwelling Units: Number of Stories: # of Thermostat Units Zone Type Type 091 Sleeping SleepingS-tat ��Z Living evingStat 0"07 Conditioned Setback 0.21 Sleeping Sleepin Sg tat 6,677 ft2 n/a ft2 0 ft2 6,677 ft2 11.8 ft 1.00 Vent Hgt. Area -2 n/a n/a n/a -2 n/a Gains Condition Y / N Status JA IV Reference Location / Comments EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:3 of 31 1 Certificate Of Compliance : Residential ft2 (Part 1 of 4) CF -1 R ject Ti le ft2 Raised Floor Area: 0 1/5/2007 Date Slab on Grade Area: 6,677 ft2 Average Ceiling Height: 11.8 Project Address Number of Dwelling Units: 1.00 Building Permit # s, ott Design & Title 24 (760) 200-4780 Documentation Author Telephone Plan Check/Date FneraVPro Compli nce Method 15 Climate Zone Field Check/Date TDV Standard Proposed Compliance (kBtu/sf-yr) Design Design Margin Space Heating 1.72 1.30 0.43 Space Cooling 56.87 49.94 6.93 Fans 8.55 8.65 -0.10 Domestic Hot Water 3.84 6.17 -2.33 Pumps 0.00 0.08 -0.08 Totals 70.99 66.14 4.85 Building Type: W Single Family ❑ Multi Family Building Front Orientation: Fuel Type: Fenestration: ❑ Addition ❑ Existing + Add/Alt (W) 280 deg Natural Gas Area: 1,523 ft2 Avg. U: 0.39 Ratio: 22.8% Avg. SHGC: 0.37 � 'LDING ZONE INFORMATION one Name Floor Area Volume OPAQUE SURFACES Insulation Act. Type Frame Area U -Fac. Cay. Cont. Azm. Tilt Wall Wnnd 4R7 n nsg R_91 R -n n 195 90 Wall Wood 241 0.069 R-21 R-0 0 985_ 90 Wall Wood 504 0 069 R-21 R-0 0 is gn Wall Wnnd 0 n n6g R_91 R-0 0 n go r Total Conditioned Floor Area: 6,677 ft2 Existing Floor Area: n/a ft2 Raised Floor Area: 0 ft2 Slab on Grade Area: 6,677 ft2 Average Ceiling Height: 11.8 ft Number of Dwelling Units: 1.00 Number of Stories: 1 # of Thermostat Vent Units Zone Type Type Hgt. Area Gains Condition Y / N Status JA IV Reference Location / Comments Run Initiation Time: 01/05/07 16:10:56 Run Code: 1168042256 EnergyPro 4.2 by Energysoft User Number: 6712 Job Number: Page:4 of 31 1 0 1 k. Certificate Of Compliance : Residential (Part 2 of 4) CF -1 R herty Residence 1/5/2007 ject Title Date FENESTRATION SURFACES True Cond. Location/ # Type Area U -Factor' SHGC2 Azm. Tilt Stat. Glazing Type Comments _1_ Window Left (N)56 0 _ 039 NERC 0_37 NERC 10_ qQ New Sierra Pacific Windows & Doors Master Suite 2 Window Rear (E) 148.0 0.390 NFRC 0.37 NFRC 100 90 New Sierra Pacific Windows & Doors Master Suite 3 Window Right (S) 11.0 0.390 NFRC 0_37 NFRC 180 90 New Sierra Pacific Windows & Doors Master Suite 4 Window Right (S) 11.0 0.390 NFRC 0.37 NFRC 180 90 New Sierra Pacific Windows & Doors Master Suite 5 Window Right (S) 8.0 0.390 NFRC 0_37 NFRC 180 90 New Sierra Pacific Windows & Doors Master Suite 6 Window Right (S) 11.0 0.390 NFRC 0_37 NFRC 180 90 New Sierra Pacific Windows & Doors Master Suite L Window Right (S) 51.0 0_390 NFRC 0_37 NFRC 180 90 New Sierra Pacific Windows & Doors Master Suite 8 Window Right (S) 11.0 0.390 NFRC 0.37 NFRC 180 90 New Sierra Pacific Windows & Doors Master Suite 6 Skylight Left (N) 4.0 0_800 NFRC 0_39 NFRC 0 20 New Double Metal Tinted Great/KiUBreak/Din/Den 1Q Window Left (N) 46.5 0_390 NFRC 0_37 NFRC 0 . 90 New Sierra Pacific Windows & Doors Great/Kot/Break/DM/Den 11 Window Left (N) 11.0 0.390 NFRC 0_37 NFRC 0 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den 12 Window Left (N) 21.0 0.390 NFRC 0_37 NFRC 10 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den _U Window Left (N) 52.0. 0_390 NFRC 0_37 NFRC 10 _y_Q New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den 14 Window Left (N) 3.0 0.390 NFRC 0_37 NFRC 10 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den 15 Window Left (N) 3.0 0.390 NFRC 0.37 NFRC 10 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den 16 Window Rear (E) 66.0 0.390 NFRC 0.37 NFRC 100 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den 17 Window Rear (E) 288.0 0.390 NFRC 0_37 NFRC 100 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den 18 Window Front (W) 22.0 0.390 NFRC 0.37 NFRC 270 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den --ta Window Right (SW) 22.0 0_390 NFRC 0_37 NFRC _ 225 90 New Sierra Pacific Windows & Doors _Great/KiUBreak/Din/Den 1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 11613. INTERIOR AND EXTERIOR SHADING Window Overhang Left Fin Right Fin # Exterior Shade Type SHGC Hgt. Wd. Len. Hgt. LExt. RExt. Dist. Len. Hgt. Dist. Len. Hgt. 1 Bug Screen 0.76 9.3 6.0 8.0 0.1 8.0 8.0 2 Bug Screen 0.76 9.3 16.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 Bug Screen 0.76 Bug Screen 0.76 _ Bug Screen 0.76 6 Bug Screen 0.76 7 Bug Screen 0.76 8 Bug Screen 0.76 9 None 1.00 10 Bug Screen 0.76 7.8 6.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 11 Bug Screen 0.76 1.8 6.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 12 Bug Screen 0.76 6.3 3.3 8.0 0.1 8.0 8.0 0.0 0.0 0 0.1 4.0 0 13 Bug Screen 0.76 6.5 8.0 10.0 0.1 10.0 10.0 14 Bug Screen 0.76 15 Bug Screen 0.76 16 Bug Screen 0.76 6.2 10.5 10.0 0.1 10.0 10.0 17 Bug Screen 0.76 12.0 24.0 10.0 0.1 10.0 10.0 18 Bug Screen 0.76 19 Bug Screen 0.76 THERMAL MASS FOR HIGH MASS DESIGN Area Thick. Heat Inside Condition Location/ Type (sq (in.) Cap. Cond. R -Val. JA IV Reference Status Comments Concrete, Heavyweight 960 4.00 28 0_98 2 26-A1 New Master Suite / Slab on Grade Concrete, Heavyweight 411 4.00 28 0.98 0 26-A1 New Master Suite / Slab on Grade Concrete, Heavyweight 468 4.00 28 0.98 2 26-A1 New Great/Kit/Break/Din/Den / Slab on Concrete, Heavyweight 2,989 4.00 28 0.98 0 26-A1 New FO ®Kit/Break/Din/Den / Slab on Concrete, Heavyweight 322 4.00 28 0.98 2 26-A1 New m 18 /Slab on Grade PERIMETER LOSSES Insulation Condition Location/ Type Length R -Val. Location JA IV Reference Status Comments Slab Perimeter 105 None No Insulation 26-A1 New Master Suite Slab Perimeter 29 None No Insulation 26-A1 New Master Suite Aoftb Perimeter 37 None No Insulation 26-A1 New Great/Kit/Break/Din/Den Perimeter 147 None No Insulation 26-A1 New Great/Kit/Break/Din/Den EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:5 of 31 1 Certificate Of Compliance : Residential (Part 2 of 4) CF -1 R 1/5/2007 Date FENESTRATION SURFACES # Type Area U-Factorl SHGC2 True Cond. Azm. Tilt Stat. Glazing Type Location/ Comments 2Q 21 Window Window Right Front (SWl (W) _220_ 0-390 NERC 0_37 NERC ?9_5_ _9Q New Sierra Pacific Windows & Doors 46.5 0.390 NFRC 0.37 NFRC 270 90 New Sierra Pacific Windows & Doors Creat/Kit/break/Din/Den Great/Kit/Break/Din/Den 22 Window Front (W) 11.0 0.390 NFRC 0_37 NFRC 270 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den 23 Window Front (NW) 46.5 0.390 NFRC 0.37 NFRC 315 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den 24 Window Front (NW) 11.0 0.390 NFRC 0_37 NFRC 315 90 New Sierra Pacific Windows & Doors Great/Kit/Break/Din/Den 25 Skylight Left (N) 4.0 0.800 NFRC 0_39 NFRC 0 20 New Double Metal Tinted Bedroom 18 2E Window Left (N) 7.0 0_390 NFRC 0_37 NFRC �10 90 New Sierra Pacific Windows & Doors Bedroom 18 27 Window Left (N) 3.0 0.390 NFRC 0.37 NFRC 10 90 New Sierra Pacific Windows & Doors Bedroom 18 2$ Window Rear (E) 76.0 0_390 NFRC 0_37 NFRC 100 90 New Sierra Pacific Windows & Doors Bedroom 18 2a Skylight Left (N) 4.0 0_800 NFRC 0_39 NFRC 0 20 New Double Metal Tinted Guest Suite M Window Right (SE) 30.0 0.390 NFRC 0_37 NFRC 150 90 New Sierra Pacific Windows & Doors Guest Suite 31 Window Right (S) 46.5 0.390 NFRC 0_37 NFRC 195 90 New Sierra Pacific Windows & Doors Guest Suite ,2 Window Right (S) 10.0 0_390 NFRC JIN NFRC 195 qQ New Sierra Pacific Windows & Doors Guest Suite 33 Window Right (S) 34.0 0.390 NFRC 0_37 NFRC 195 90 New Sierra Pacific Windows & Doors Guest Suite 34 Window Right (S) 27.1 0.390 NFRC 0.37 NFRC 195 90 New Sierra Pacific Windows & Doors Guest Suite 35 Window Right (S) 46.5 0.390 NFRC 0_37 NFRC 195 90 New Sierra Pacific Windows & Doors Guest Suite 36 Window Right (S) 54.0 0.390 NFRC 0_37 NFgc,, 195 90 New Sierra Pacific Windows & Doors Guest Suite 37 Window Front (W) 27.0 0.390 NFRC 0_37 NFRC 285 90 New Sierra Pacific Windows & Doors Guest Suite -M Window Front (W) 8.0 _ 0.390 NFRC 0_37 NFRC 285 90 New Sierra Pacific Windows & Doors Guest Suite 1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 1166. INTERIOR AND EXTERIOR SHADING Area Thick. Heat Inside Condition Location/ Type (sf) (in.) Cap. Cond. R -Val. JA IV Reference Status Comments Concrete, Heavyweight 156 Window 28 Overhang 26-A1 New Left Fin Concrete, Heavyweight Right Fin 28 # Exterior Shade Type SHGC Hgt. Wd. Len. Hgt. LExt. REA Dist. Len. Hgt. Dist. Len. Hgt. 20 Bug Screen 0.76 21 Bug Screen 0.76 7.8 6.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 Bug Screen 0.76 1.8 3.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 4iBug Screen 0.76 7.8 6.0 2. 0,_1 2.0 2.0 0.1 _2.0 0 0.1 2.0 0 _ Bug Screen 0.76 1.8 6.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 25 None 1.00 26 Bug Screen 0.76 27 Bug Screen 0.76 28 Bug Screen 0.76 9.3 8.2 6.0 0.1 6.0 6.0 29 None 1.00 30 Bug Screen 0.76 31 Bug Screen 0.76 32 Bug Screen 0.76 33 Bug Screen 0.76 34 Bug Screen 0.76 7.8 3.5 2.0 0.1 2.0 2.0 35 Bug Screen 0.76 7.8 6.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 36 Bug Screen 0.76 5.4 10.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 37 Bug Screen 0.76 4.8 6.0 2.0 0.1 2.0 2.0 0.1 2.0 0 0.1 2.0 0 38 Bug Screen 0.76 THERMAL MASS FOR HIGH MASS DESIGN PERIMETER LOSSES Area Thick. Heat Inside Condition Location/ Type (sf) (in.) Cap. Cond. R -Val. JA IV Reference Status Comments Concrete, Heavyweight 156 4.00 28 0.98 0 26-A1 New Bedroom 18 / Slab on Grade Concrete, Heavyweight 823 4.00 28 0_98 2 26-A1 New Guest Suite / Slab on Grade Concrete, Heavyweight 548 4.00 28 0.98 0 26-A1 New Guest Suite / Slab on Grade PERIMETER LOSSES Insulation Condition Location/ Type Length R -Val. Location JA IV Reference Status Comments Slab Perimeter 11 None No Insulation 26-A1 New Bedroom 18 Slab Perimeter 94 None No Insulation 26-A1 New Guest Suite Afteb Perimeter 91 None No Insulation 26-A1 New Guest Suite Run Initiation Time: 01/05/07 16:10:56 Run Code: 1168042256 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:6 of 31 Certificate Of Compliance : Residential (Part 2 of 4) CF -1 R 1/5/2007 Date True Cond. Location/ # Type Area U-Factorl SHGC2 Azm. Tilt Stat. Glazinq Tvge Comments 3R Window Front (gyp() 140 0_390 NFRC J= NFR •285 A0_ New Sierra Pacific Windows & noorc Guest Suite 40 Window Front (W) 5.0 0.390 NFRC 0.37 NFRC 285 90 New Sierra Pacific Windows & Doors Guest Suite 41 Window Left (N) 58.0 0.390 NFRC 0_37 NFRC 15 90 New Sierra Pacific Windows & Doors Guest Suite 42 Window Left (N) 86.2 0.390 NFRC 0_37 NFRC 0 90 New Sierra Pacific Windows & Doors Guest Suite 1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 116B. INTERIOR AND EXTERIOR SHADING Window Overhang Left Fin Right Fin # Exterior Shade Type SHGC Hgt. Wd. Len. Hgt. LExt. RExt. Dist. Len. Hgt. Dist. Len. Hgt. 39 Bug Screen 0.76 40 Bug Screen 0.76 Bug Screen 0.76 Bug Screen 0.76 THERMAL MASS FOR HIGH MASS DESIGN Area Thick.Heat Inside Condition Location/ Type (sf) (in.) Cap. Cond. R -Val. JA IV Reference Status Comments PERIMETER LOSSES Insulation Type Length R -Val. Location Condition Location/ JA IV Reference Status Comments Run Initiation Time: 01/05/07 16:10:56 Run Code: 1168042256 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:7 of 31 Certificate Of Compliance : Residential (Part 3 of 4) CF -1 R Wlect Title HVAC SYSTEMS 1/5/2007 Date Location Heating Type Minimum Eff Cooling Type Minimum _ Eff Condition Status Thermostat Type HVAC -1 Central Furnace 80% AFUE Split Air Conditioner 14.0 SEER New Setback HVAC -2, 3 & 4 Central Furnace 80% AFUE Split Air Conditioner 14.0 SEER New Setback HVAC -5 Central Furnace 80% AFUE Split Air Conditioner 14.0 SEER New Setback HVAC DISTRIBUTION Location Heating Cooling Duct Location HVAC -1 Ducted Ducted Attic HVAC -2, 3 & 4 Ducted Ducted Attic HVAC -5 Ducted Ducted Attic Hydronic Piping Pipe Pipe Insul. System Name Length Diameter Thick. Duct Condition Ducts R -Value Status Tested? 4.2 New No 4.2 New No 4.2 New No WATER HEATING SYSTEMS Water Heater System Name Type Distribution Rated # in Input Syst. (Btu/hr) Tank Cap. (gal) Energy Condition Factor Status or RE Tank Insul. Standby R -Value Loss (%) Ext. American G32 -75T75 -4N0"` Large Gas Recirc/Time+Temp 2 75,100 75 New 0.80 2.53% 0.0 Multi -Family Central Water Heating Details Hot Water Pump Control # HP Type Hot Water Piping Length (ft) In Plenum Outside Buried Add 1/2" Insulation COMPLIANCE STATEMENT This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall design responsibility. The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insulation installation quality, and building envelope sealing require installer testing and certification and field verification by an approved HERS rater. Designer or Owner (per Business & Professions Code) Documentation Author Name: Name: Tim Scott Title/Firm: Prest Vuksic Architects Address: 44-530 San Pablo, Suite 200 Palm DesertCA 92260 Telephone: 760 779 393 Lic. #: G Z O ' •S•o (signature) (date) Enforcement Ag Name: Title/Firm: Address: Telephone: nature) (date) Title/Firm: Scott Design & Title 24 Address: 77085 Michigan Dr. Palln DesertA 92211 Telephonel(74)_200-47 0 (signature) — I (date) Certificate Of Compliance : Residential (Part 3 of 4) CF -1 R Title 1/5/2007 Date Heating Minimum Cooling Minimum Condition Thermostat Location Type Eff Type Eff Status Type HVAC -6 Central Furnace 80% AFUE Split Air Conditioner 14.0 SEER New Setback HVAC DISTRIBUTION Duct Location Heatina Coolina Location HVAC -6 Ducted Ducted Attic Hydronic Piping Pipe Pipe Insul. System Name Length Diameter Thick. Duct Condition Ducts R -Value Status Tested? 4.2 New No WATER HEATING SYSTEMS Rated Tank Energy Tank Insul. Water Heater # in Input Cap. Condition Factor Standby R -Value System Name Type Distribution Syst. (Btu/hr) (gal) Status or RE Loss (%) Ext. Multi -Family Central Water Heating Details Hot Water Pump Hot Water Piping Length (ft) Add 1/2" Control # HP Type In Plenum Outside Buried Insulation REMARKS COMPLIANCE STATEMENT This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall design responsibility. The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insulation installation quality, and building envelope sealing require installer testing and certification and field verification by an approved HERS rater. Designer or Owner (per Business & Professions Code) Name: Title/Firm: Prest Vuksic Architects Address: 44-530 San Pablo, Suite 200 Palm DesertCA 92260 Telephone: 760 779 3 Lic. #: C_ - 'L ,G'J•0 (signature) (date) Enforcement Ag cy Name: Title/Firm: Address: Telephone: • gnature) (date) Documentation Author Name: Tim Scott . Title/Firm: Scott Design & Title 24 Address: 77085 Michigan Dr. Pal Desert92211 Telephong, 200-478 / 0 (signature (date) Certificate Of Compliance : Residential (Part 4 of 4) CF -1 R Title 11512007 Date Special Features and Modeling Assumptions The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. I Plan I Field The DHW System "American G32 -75T75 -4N0**— is a Large Gas water heater with Pilot Loss = 0 btuh. The Roof "R-38 Roof(R.30.2x14.16)" includes credit for a Radiant Barrier installed per Section 3.3.3 of the Residential Manual. The HVAC System "HVAC -1" must meet all CEC Criteria for a Zonally Controlled system serving only Sleeping Areas. HIGH MASS Design - Verify Thermal Mass: 960 sqft Covered Slab Floor, 4.00" thick at Master Suite HIGH MASS Design - Verify Thermal Mass: 411 sqft Exposed Slab Floor, 4.00" thick at Master Suite The HVAC System "HVAC -2, 3 8, 4" must meet all CEC Criteria for a Zonally Controlled system serving only Living Areas. HIGH MASS Design - Verify Thermal Mass: 468 sqft Covered Slab Floor, 4.00" thick at Great/Kit/Break/Din/Den HIGH MASS Design - Verify Thermal Mass: 2989 sqft Exposed Slab Floor, 4.00" thick at GreaUKit/Break/Din/Den HIGH MASS Design - Verify Thermal Mass: 322 sqft Covered Slab Floor, 4.00" thick at Bedroom 18 HIGH MASS Design - Verify Thermal Mass: 156 sqft Exposed Slab Floor, 4.00" thick at Bedroom 18 The HVAC System "HVAC -6" must meet all CEC Criteria for a Zonally Controlled system serving only Sleeping Areas. HIGH MASS Design - Verify Thermal Mass: 823 sqft Covered Slab Floor, 4.00" thick at Guest Suite HIGH MASS Design - Verify Thermal Mass: 548 sqft Exposed Slab Floor, 4.00" thick at Guest Suite HERS Required Verification Items in this section require field testing and/or verification by a certified home energy rater under the supervision of a CEC- approved HERS provider using CEC approved testing and/or verification methods and must be reported on the CF -4R Plan Field installation certificate. e HVAC System "HVAC -1" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve. I The Cooling System "Carrier 38TXA060/58DLX110" includes credit for a 11.1 EER Condenser. A certified HERS rater must field verify the installation of the correct Condenser. The HVAC System "HVAC -2, 3 & 4" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve. The Cooling System "Carrier 38TXA048/58DLX090" includes credit for a 11.5 EER Condenser. A certified HERS rater must field verify the installation of the correct Condenser. The HVAC System "HVAC -5" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve. The Cooling System "Carrier 38TXA024/58DLX045 includes credit for a 11.2 EER Condenser. A certified HERS rater must field verify the installation of the correct Condenser. The HVAC System "HVAC -6" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve. The Cooling System "Carrier 38TXA060/58DLX110" includes credit for a 11.1 EER Condenser. A certified HERS rater must field verify the installation of the correct Condenser. 6— EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 10 of 31 1 Mandatory Measures Summary: Residential (Page 1 of 2) MF -1 R NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent compliance • requirements from the Certificate of Compliance supercede the items marked with an asterisk (*) below. When this checklist is incorporated into the permit documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether they are shown elsewhere in the documents or on this checklist only. • • DESCRIPTION Check or initial applicable boxes or check NA if not applicable and included with the ENFORCE - permit application documentation. N/A DESIGNER MENT Building Envelope Measures 150(a): Minimum R-19 in wood ceiling insulation or equivalent U -factor in metal frame ceiling. § 150(b): Loose fill insulation manufacturer's labeled R -Value: 150(c): Minimum R-13 wall insulation in wood framed walls or equivalent U -factor in metal frame walls (does not apply to exterior mass walls). ❑ O ❑ ❑ ❑ ❑ ❑ ❑X ❑ *§ 150(d): Minimum R-13 raised floor insulation in framed floors or equivalent U -factor. ❑ 0 ❑ § 150(e): Installation of Fireplaces, Decorative Gas Appliances and Gas Logs. ❑ ❑X ❑ 1. Masonry and factory -built fireplaces have: ❑ ❑X ❑ a. closable metal or glass door covering the entire opening of the firebox ❑ ❑ ❑ b. outside air intake with damper and control, flue damper and control ❑ ❑ ❑ 2. No continuous burning gas pilot lights allowed. ❑ ❑ ❑ § 150(f): Air retarding wrap installed to comply with §151 meets requirements specified in the ACM Residential Manual. ❑ ❑ ❑ § 150(g): Vapor barriers mandatory in Climate Zones 14 and 16 only. ❑ ❑ ❑ § 150(1): Slab edge insulation - water absorption rate for the insulation alone without facings no greater than 0.3%, water vapor ❑ ❑ ❑ permeance rate no greater than 2.0 perm/inch. ❑ ❑X ❑ § 118: Insulation specified or installed meets insulation installation quality standards. Indicate type and include ❑ a ❑ CF -6R Form: ❑ ❑X ❑ § 116-17: Fenestration Products, Exterior Doors, and Infiltration/Exfiltration Controls. 1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage. ❑ ❑X ❑ 2. Fenestration products (except field fabricated) have label with certified U -Factor, certified Solar Heat Gain ❑ N ❑ Coefficient (SHGC), and infiltration certification. 3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed. ❑ ❑ ❑ Space Conditioning, Water Heating and Plumbing System Measures § 110-13: HVAC equipment, water heaters, showerheads and faucets certified by the Energy Commission. ❑ ❑X ❑ § 150(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA or ACCA. ❑ ❑X ❑ § 150(i): Setback thermostat on all applicable heating and/or cooling systems. ❑ ❑X ❑ § 1500): Water system pipe and tank insulation and cooling systems line insulation. 1. Storage gas water heaters rated with an Energy Factor less than 0.58 must be externally wrapped with insulation ❑ ❑ ❑ having an installed thermal resistance of R-12 or greater. 2. Back-up tanks for solar systems, unfired storage tanks, or other indirect hot water tanks have R-12 external ❑ ❑ ❑ insulation or R-16 internal insulation and indicated on the exterior of the tank showing the R -value. 3. The following piping is insulated according to Table 150-A/B or Equation 150-A Insulation Thickness: 1. First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire ❑ ❑X ❑ length of recirculating sections of hot water pipes shall be insulated to Table 1508. 2. Cooling system piping (suction, chilled water, or brine lines), piping insulated between heating source and ❑ ❑X ❑ indirect hot water tank shall be insulated to Table 150-B and Equation 150-A. 4. Steam hydronic heating systems or hot water systems > 15 psi, meet requirements of Table 123-A. ❑ ❑ ❑ 5. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, ❑ ❑ ❑ and wind. 6. Insulation for chilled water piping and refrigerant suction piping includes a vapor retardant or is enclosed ❑ ❑ ❑ entirely in conditioned space. 7. Solar water -heating systems/collectors are certified by the Solar Rating and Certification Corporation. ❑ ❑ ❑ EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 11 of 31 Mandatory Measures Summarv: Residential (Page 2 of 2) MF -1 R NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent • compliance requirements from the Certificate of Compliance supercede the items marked with an asterisk (*) below. When this checklist is incorporated into the permit documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether they are shown elsewhere in the documents or on this checklist only. • • DESCRIPTION Instructions: Check or initial applicable boxes when completed or check N/A if not ENFORCE - applicable. N/A DESIGNER MENT Space Conditioning, Water Heating and Plumbing System Measures: (continued) § 150(m): Ducts and Fans 1. All ducts and plenums installed, sealed and insulated to meet the requirements of the CMC Sections 601, 602, 603, 604, ❑ 0 ❑ 605, and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minumum installed level of - R-4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used. 2. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than ❑ X❑ ❑ sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and a. At least 36" of pipe between filter and heater for future solar heating. ❑ ❑ ❑ support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause ❑ ❑ ❑ 3. Pool system has directional inlets and a circulation pump time switch. ❑ ❑ ❑ reductions in the cross-sectional area of the ducts. ❑ 2 ❑ burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr) 3. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive ❑ ® ❑ duct tapes unless such tape is used in combination with mastic and draw bands. ❑ ® ❑ 150-C, and do not contain a medium screw base socket (E24/E26). Ballasts for lamps 13 Watts or greater are 4. Exhaust fan systems have back draft or automatic dampers. ❑ ❑ ❑ 5. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operating ❑ ❑ ❑ dampers. provided that these luminaires are controlled by switches separate from those controlling the high efficacy luminaires. 6. Protection of Insulation. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment ❑ ® ❑ maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water ❑ X❑ ❑ controlled by an occupant sensor that complies with Section 1) 9(d) that does not turn on automatically or have an retardant and provides shielding from solar radiation that can cause degradation of the material. ❑ ❑X ❑ certified to ASTM E283 and labeled as air tight (AT) to less than 2.0 CFM at 75 Pascals. 7. Flexible ducts cannot have porous inner cores. ❑ ® ❑ § 114: Pool and Spa Heating Systems and Equipment 1. A thermal efficiency that complies with the Appliance Efficiency Regulations, on-off switch mounted outside of the ❑ ❑ ❑ heater, weatherproof operating instructions, no electric resistance heating and no pilot light. 2. System is installed with: a. At least 36" of pipe between filter and heater for future solar heating. ❑ ❑ ❑ b. Cover for outdoor pools or outdoor spas. ❑ ❑ ❑ 3. Pool system has directional inlets and a circulation pump time switch. ❑ ❑ ❑ § 115: Gas fired fan -type central furnaces, pool heaters, spa heaters or household cooking appliances have no continuously ❑ 2 ❑ burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr) § 118 (i): Cool Roof material meets specified criteria ❑ ❑ ❑ Lighting Measures § 150(k)l: HIGH EFFICACY LUMINAIRES OTHER THAN OUTDOOR HID: contain only high efficacy lamps as outlined in Table ❑ ® ❑ 150-C, and do not contain a medium screw base socket (E24/E26). Ballasts for lamps 13 Watts or greater are electric and have an output frequency no less than 20 kHz. § 150(k)l: HIGH EFFICACY LUMINAIRES - OUTDOOR HID: contain only high efficacy lamps as outlined in Table 150-C, ❑ ❑ ❑ luminaire has factory installed HID ballast. § 150(k)2: Permanently installed luminaires in kitchens shall be high efficacy luminaires. Up to 50% of the Wattage, as determined ❑ ❑X ❑ in Section 130(c), of permanently installed luminaires in kitchens may be in luminaires that are not high efficacy luminaires, provided that these luminaires are controlled by switches separate from those controlling the high efficacy luminaires. § 150(k)3: Permanently installed luminaires in bathrooms, garages, laundry rooms, utility rooms shall be high efficacy luminaires. ❑ ❑X ❑ OR are controlled by an occupant sensor(s) certfied to comply with Section 119(d). § 150(k)4: Permanently installed luminaires located other than in kichens, bathrooms,garages, laundry rooms, and utility rooms shall be high efficacy luminaires (except closets less than 70 ft) OR are confrolled by a dimmer switch OR are ❑ X❑ ❑ controlled by an occupant sensor that complies with Section 1) 9(d) that does not turn on automatically or have an always on option. § 150(k)5: Luminaires that are recessed into insulated ceilings are approved for zero clearance insulation cover (IC) and are ❑ ❑X ❑ certified to ASTM E283 and labeled as air tight (AT) to less than 2.0 CFM at 75 Pascals. § 150(k)6: Luminaires providing outdoor lighting and permanently mounted to a residential building or to other buildings on the ❑ ❑ ❑ same lot shall be high efficacy luminaires (not including lighting around swimming pools/water features or other Article 680 locations) OR are controlled by occupant sensors with integral photo control certified to comply with Section 119(d). § 150(k)7: Lighting for parking lots for 8 or more vehicles shall have lighting that complies with Sections 130, 132, and 147. ❑ ❑ ❑ Lighting for parking garages for 8 or more vehicles shall have lighting that complies with Section 130, 131, and 146. § 150(k)8: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more ❑ ❑ ❑ dwelling units shall be high efficacy luminaires OR are controlled by occupant sensor(s) certified to comply with Section 119(d). EnergyPro 4.2 by EnergySoft User Number. 6712 Job Number: Page: 12 of 31 Residential Kitchen Lighting Worksheet WS -5R -aherty Residence 1/5/2007 ject Title Date At least 50% of the total rated wattage of permanently installed luminaires in kitchens must be in luminaires that are high efficacy luminaires as defined in Table 150-C. Luminaires that are not high efficacy must be switched separately. Kitchen Lighting Schedule. Provide the following information for all luminaires to be installed in kitchens. High Efficacy Luminaire Type High Efficacy? Watts Quantity Watts Other Watts (2) 26w Compact Fluorescent Triple 4 Pin Yes X No 74.0 x 13 = 962 or Yes No x = or Yes No x or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Yes No x = or Total A:, 962 B: 0 COMPLIES IF A;-* B YES ® NO ❑ is I EneravPro 4.2 by EnergvSoft User Number: 6712 Job Number: Paoe:13 of 31 1 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE Faherty Residence 1/5/2007 TEM NAME FLOOR AREA HVAC -1 1,371 26.0 of 68.8 of Outside Air 0 cfm Supply Fan 2025 cfm 68.8 of 68.8 of Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM I Sensible Latent I CFM I Sensible 900 19,148 82 528 19,685 0 2,977 2,526 0 0 0 0 0 0 0 0 0 2,977 2,526 25.102F77777;2 24 736 Carrier 38TXA060/58DLX110 42,607 7,733 89,000 Total Adjusted System Output a2,6o7 7,733 89,000 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Aug 2 pm Jan 12 am 105.0 of Heating Coil e of Heatina Pea Supply Air Ducts 103.8 of ROOMS 70.0 of Return Air Ducts `5 COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 110.0/72.5OF 76.4/61.8OF 76.4/61.8OF 55.0/53.8OF O Outside Air Supply Air Ducts 0 cfm Supply Fan Cooling Coil 56.4 / 54.4 of 2025 cfm 45.9% R.H. ROOMS 76.4/61.80F 75.0/61.3OF Return Air Ducts I EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 14 of 31 i HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY 71 PROJECT NAME DATE Faherty Residence 1/5/2007 STEM NAME FLOOR AREA HVAC -2 3 & 4 3,457 Number of Systems 31 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD Heating System Output per System 71,000 Total Output (Btuh) 213,000 Output (Btuh/sgft) 61.6 Cooling System Output per System 46,500 Total Output (Btuh) 139,500 Total Output (Tons) 11.6 Total Output (Btuh/sgft) 40.4 Total Output (sgft/Ton) 297.4 CFM per System Airflow (cfm) Airflow (cfm/sgft) Airflow (cfm/Ton) ' Outside Air (%) Outside Air (cfm/sgft) Note: values above given at ARI conditions EATING SYSTEM PSYCHROMETRICS 26.0 of 69.10F Outside Air 0 cfm 69.1 of HVAC E UI 1,720 5,160 1.49 443.9 2000 COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM I Sensible 2,246 37,097 -20 Lj,n 39,93 0 5,768 5,123 0 0 0 0 0 0 0 0 0 5,7681 5,123 48,633 -20 Carrier 38TXA048/58DLX090 96,749 22,720 Total Adjusted System Output 86,749 22,720 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Aug 2 pm am Tel 107.9 of Heating Coil Supply Fan 5160 cfm 213,000 213,000 Jan 12 am 107.9 of 30Supply Air Ducts 106.9 of ROOMS 70.0 of Return Air Ducts `5 :OGLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 10.0 / 72.5 of 76.1 / 62.1OF 58.4 / 55.6 of 58.4 / 55.6 of Supply Air Ducts Outside Air O 0 cfm Cooling Coil Supply Fan 59.5 / 56.0 of 5160 cfm 47.1% R.H. ROOMS 76.1 / 62.0 of 75.0 / 61.7 of Return Air Ducts I EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 15 of 31 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE Faherty Residence 1/5/2007 STEM NAME FLOOR AREA HVAC -5 478 26.0 of 68.9 of Outside Air 0 0 cfm Supply Fan 800 cfm 68.9 of Total Room Loads 2eturn Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM I Sensiblel Latent I I CFM I Sensible 356 8,123 508 173 7,163 at Time of Cooling 0 10.0 / 72.5 of 79.5 / 62.9 of 79.5 / 63.0 of 1,263 919 0 0 0 0 0 0 0 0 Supply Fan Cooling Coil 0 1,263 919 10,649 508 9 00 Carrier 38TXA024/58DLX045 20,761 86 35,000 Total Adjusted System Output 20,761 86 35,000 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Aug 2 pm Jan 12m 'earn Temperatures at Time of Heatina. Peak) 68.9 °F%� 110.0 °F Heating Coil Supply Air Ducts 109.0 of ROOMS 70.0 of IE IE Return Air Ducts :DOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 10.0 / 72.5 of 79.5 / 62.9 of 79.5 / 63.0 of 55.1 / 53.7 of O Supply Air Ducts Outside Air 0 cfm Supply Fan Cooling Coil 56.6 / 54.3 of 800 cfm ROOMS 41.8% R.H. 78.0/62.4OF 79.5/62.90F Return Air Ducts I 1 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Paae:16 of 31 1 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE Faherty Residence 1/5/2007 STEM NAME FLOOR AREA HVAC -6 1,371 EATING S 26.0 of Outside �� 0 cfm 68.5 of Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM I Sensible Latent CFM I Sensible 1,148 22,241 -36 613 25,015 0 3,458 3,209 0 0 0 0 0 0 0 0 0 3,458 3,209 29157 -36 1 31434 Carrier 38TXA060/58DLX110 46,159 5,330 89,000 Total Adjusted System Output 46,159 5,330 89,000 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK- Aug 2 pm Jan 12 am M PSYCHROMETRICS (Airstream Temperatures at Time of Heatina Peak) 68.5 of 68.5 of 109.8 of 0 Supply Fan Heating Coil 2025 cfm Return Air nits Supply Air Ducts 108.3 of ROOMS 70.0 of COOLING SYSTEM PSYCHROMETRICS Airstream. Temperatures at Time of Coolin Peak 110.0/72.50F 79.6 63.2 of 79.6 / 63.3 of 58.2 / 55.5 of Supply Air Ducts Outside Air O W 0 cfm Supply Fan Cooling Coil 59.8 / 56.1 of 2025 cfm 42.6% R.H. ROOMS 79.6/63.2 of 78.0 / 62.7 of h Return Air Ducts "I EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 17 of 31 1 ROOM LOAD SUMMARY PROJECT NAME Faherty Residence DATE 1/5/2007 STEM NAME HVAC -1 FLOOR AREA 1,371 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK ZONE NAME ROOM NAME Ault. CFM SENSIBLE LATENT CFM SENSIBLE LATENT CFM SENSIBLE Master Suite Master Suite 1 900 19,148 82 900 19,148 82 528 19,685 IL I PAGE TOTAL 1 900 19,148 82 528 1 19,685 TOTAL 1 900 19,148 82 528 19,685 EnergyPro By EnergySoft User Number: User Job Number: Page: 18 of 31 ROOM LOAD SUMMARY PROJECT NAME DATE Faherty Residence 1/5/2007 TEM NAME FLOOR AREA HVAC -2, 3 & 4 3,457 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK ZONE NAME ROOM NAME Mult. CFM SENSIBLE LATENT CFM SENSIBLE LATENT CFM SENSIBLE Great/Kit/Break/Din/Den Great/Kit/Break/Din/Den 1 2,246 37,097 -201 2,246 37,097 -201 1,016 39,931 PAGE TOTAL 1 2,246 37,097 -201 1,016 39,931 TOTAL 1 2,246 37,097 -201 1,016 39,931 EnergyPro By EnergySoft User Number: User Job Number: Page: 19 of 31 ROOM LOAD SUMMARY PROJECT NAME Faherty Residence DATE 1/5/2007 TEM NAME HVAC -5 FLOOR AREA 478 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK ZONE NAME ROOM NAME Mult. CFM SENSIBLE LATENT CFM SENSIBLE LATENT CFM SENSIBLE Bedroom 18 Bedroom 18 1 356 8,123 508 356 8,123 508 173 7,163 PAGE TOTAL 1 356 8,123 508 173 7,163 TOTAL 1 356 8,123 508 173 7,163 11 EnergyPro By EnergySoft User Number: User Job Number: Page:20 of 31 ROOM LOAD SUMMARY PROJECT NAME Faherty Residence DATE 1/5/2007 TEM NAME HVAC -6 FLOOR AREA 1,371 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK ZONE NAME ROOM NAME Mult. CFM SENSIBLE LATENT CFM SENSIBLE LATENT CFM SENSIBLE Guest Suite Guest Suite 1 1,148 22,241 -36 1,148 22,241 -36 613 25,015 PAGE TOTAL 1 1,148 22,241 -36 613 25,015 TOTAL 1 1,148 22,241 -36 613 25,015 li EnergyPro By EnergySoft User Number: User Job Number: Page:21 of 31 4 ROOM HEATING PEAK LOADS roject Title Date herty Residence 11/5/2007 Room Information Desi n Conditions Room Name Master Suite Time of Peak Jan 12 am Floor Area 1,371 Outdoor Dry Bulb Temperature 26°F Indoor Dry Bulb Temperature 70 OF Conduction Area U -Value QT of Btu/hr 1 1 1371.0 X X x X X X X x X X x X x X X X x x x X X X X x X X x X X X X X X X X X X x X 0.0240 X x x x X x x X X X x X X X X X X x x X X X x X X x x X X X X x X x X x X x X 44 = = = = = = = = = = = = = = = = = = = 1,450 175.0 0.0690 44 531 56.0 0.3900 44 961 11.5 0.0690 44 35 127.0 0.0690 44 386 148.0 0.3900 44 2,540 349.0 0.0690 44 1,060 11.0 0.3900 44 189 0,3900 44 189 8.0 0.3900 44 137 11.0 0.3900 44=igg 51.0 0.3900 44 875 11.0 0.3900 44 189 237.0 0.0690 44= 720 180.0 0.0690 44=54 erimeter = 105.0 0.7300 44 3,373 perimeter -29.0 44 931 nems snown wnn an asrerisK k-) aenoce conauction inrougn an mrenor surrace to anomer room. Page Total: 14,299 Infiltration: r 1.00 X 1.064 X 1 371 X 11.30 X 0.445 / 6 ] x 44 = 5 386 schedule Air Sensible Area Ceiling Height ACH DT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 19,685 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 22 of 31 i ROOM HEATING PEAK LOADS roject Title Date hertResidence 11/5/2007 Room Information Desi n Conditions Room Name Time of Peak Jan 12 am Floor Area 3,457 Outdoor Dry Bulb Temperature 26°F Indoor Dry Bulb Temperature 70 OF Conduction ISierra Pacific Windows & Doors I Area 3,453.0 4.0 74.5 46.5 11.0 148.3 21.0 52.0 3.0 322.0 66.0 288.0 18.0 22.0 179.0 60.0 96.0 22.0 244.5 46.5 11.0 41.5 46.5 11.0 perimeter = 37.0 perimeter = 147 n- U -Value OT OF Btu/hr 3,651 141 226 798 189 450 360 892 51 51 978 1,133 4.942 55 37A 543 291 378 742 798 moi] Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 26 350 Infiltration: 1 1.00 X 1.064 X 3 457 X 12.10 x 0.416 / 6] X 44 = 13 581 chedule Air Sensible Area Ceiling Height ACH OT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 39,931 EnergyPro 4.2 by Energysoft User Number: 6712 Job Number: Page: 23 of 31 f i ! 9 11 �. ROOM HEATING PEAK LOADS roject TitleDate hert Residence 1 /5/2007 Room Information Desi n Conditions Room Name Bedroom 18 Time of Peak Jan 12 am Floor Area 478 Outdoor Dry Bulb Temperature 26OF Indoor Dry Bulb Temperature 70 OF Conduction Area U -Value AT of Btu/hr Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 5 348 Infiltration: r 1.00 x 1.064 x a7s x 11.30 x o.a3o / 6] x ® = 1 s14 schedule Air Sensible Area Ceiling Height ACH OT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 7,163 EnergyPro 4.2 by EnergySoft . User Number: 6712 Job Number: Page: 24 of 31 474.0 x x X x x X X X x x x x x x x x x x x x X X x x x x x X x x x x x x X x X x X 0.0240 X X X x X X X X X X x x X x x x x x x x x x x x x x x X x x x x x X x x X X X 44 = = = = = = = = = = = = = = = = = = = = = = = 501 4.0 0.8000 44 141 363.0 0.0690 44 1,102 7.0 0.3900 44 120 3.0 0.3900 44 51 88.0 0.0690 441 267 76.0 0.3900 44 1,304 63.0 0.0690 44 191 perimeter — 0,7300 44 1,317 perimeter = 11.0 0.7300 44 353 Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 5 348 Infiltration: r 1.00 x 1.064 x a7s x 11.30 x o.a3o / 6] x ® = 1 s14 schedule Air Sensible Area Ceiling Height ACH OT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 7,163 EnergyPro 4.2 by EnergySoft . User Number: 6712 Job Number: Page: 24 of 31 ! r!9 ROOM HEATING PEAK LOADS roject Title Date hertResidence 1 /5/2007 Room Information Desi n Conditions Room Name Guest suite Time of Peak Jan 12 am Floor Area 1,371 Outdoor Dry Bulb Temperature 26°F Indoor Dry Bulb Temperature 70°F Conduction Area U -Value AT of Btu/hr IR -21 Wall (W.19.2x6.16) 1367.0 x x X x x X x X X X X X x x X X X X X x x X x x x x x x x x x x x x x x x x x 0.0240 X X X X X X X X X X X X x x X X X X X X x X x x x x x x x x x x x x x x x x x 44 = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = 1,445 4.0 0.8000 44 141 146.0 0.0690 44 443 145.0 0.0690 44 440 30.0 0.3900 44 515 486.9 0.0690 44 1,478 46.5 0.3900 44 798 10.0 0.3900 44 172 34.0 0,3900 44 583 27.1 0.3900 44= 465 46.5 0.3900 44=798 54.0 0.3900 44 927 241.0 0.0690 44 732 27.0 0.3900 44= 463 8.0 0.3900 44c137 14.0 0.3900 44 240 01900 44 86 504.0 0.0690 44=1,530 58.0 0.3900 44 995 86.2 0.3900 44 1,480 perimeter = 0,7300 44=3019 perimeter = 91.0 0.7300 44 2,923 Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 19 811 Infiltration: 1 1.001 X 1.064 X 1 371 X 11.90 X 0.409 / 6] X � = 5 204 chedule Air Sensible Area Ceiling Height ACH DT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 25,015 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 25 of 31 t I 1 0 .• 41 RESIDENTIAL ROOM COOLING LOAD SUMMARY roject Title Date hert Residence 11/5/2007 Room Information Desicin Conditions Room Name: Master Suite Outdoor Dry Bulb Temperature: 111OF Floor Area: 1,371 sf Outdoor Web Bulb Temperature: 730F Indoor Dry Bulb Temperature: 750F Outdoor Daily Range: 340F Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr R-38 Roof R.30.2x14.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.24.16 R-21 Wall (W.19.24.16) 0.0690 33.0 E 127.0 0.0690 32.6 S 349.0 0.0690 26.0 N 1,371.0 x X X X X X X x X X X X 0.0166 X X X X X X X x X X X X 56.0 N 175.0 0.0690 24.3 E 11.5 0.0690 33.0 E 127.0 0.0690 32.6 S 349.0 0.0690 26.0 S 237.0 0.0690 27.1 (W) 180.0 0.0690 33.0 0.0 21.6 8.0 21.7 S 0.0 21.6 11.0 21.7 S 0.0 21.6 51.0 21.7 S 0.0 21.6 11.0 21.7 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestration n Page Total Orientation Shaded Area X X x x x x x X+ X GLF + + + + + + + + Unshaded Area X X X x X x X X X GLF N 0.0x 21.6+ 56.0x 24.3 E 28.9X 21.6+ 119.1x 42.8 S 0.0 21.6 11.0 21.7 S 0.0 21.6 11.0 21.7 S 0.0 21.6 8.0 21.7 S 0.0 21.6 11.0 21.7 S 0.0 21.6 51.0 21.7 S 0.0 21.6 11.0 21.7 Page Total 1,276 294 26 285 626 443 410 3 361 Btu/hr Internal Gain Btu/hr Occu ants 2 X Occupants X 230 Btuh/oCC. = 460 P P E ui ment 1 X Dwelling Units x 1 1,6001 Watts/sqft = 1,6001 Infiltration: 1.064 X 1.19 X 96.74 X = 440 Air Sensible CFM ELA DT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,148 Latent Gain Btu/hr Occu ants 0 X Occupants x 200 Btuh/oCC. = 400 Infiltration: 4 771 X 1.19 X 96.74 X 0.00058 = 318 Air Latent CFM ELA AW • TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 82 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:26 of 31 Ah RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Title Date hert Residence 1/5/2007 Room Information Desicin Conditions Room Name: Great/Kit/Break/Din/Den Outdoor Dry Bulb Temperature: 1110F Floor Area: 3,457 sf Outdoor Web Bulb Temperature: 730F Indoor Dry Bulb Temperature: 75OFOutdoor Daily Range: 340F Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr • R-38 Roof R.30.2x14.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.2x6.16 Solid Wood Door R-21 Wall (W.19.2x6.16) R-21 Wall W.19.2x6.16 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestration Skylight 5 K Y W BB cc X V G x 0.0166 X x 0.0690 X x 0.0690 X x 0.0690 X x 0.0690 X x 0.0690 X x 1.4500 X X 0.0690 X x 0.0690 X X 238 X X 21.6 X X 510 X 3,213 118 249 723 41 - 321 - 905 - 112 = 205 Page Total i 5.889 Orientation Shaded Area X X X x x X x+ GLF + + + + + + Unshaded Area X X X X x x x X GLF = = = = = = = Btu/hr (Sky) 0.0 30.7 4.0 83.5 334 N 0.0 21.6 46.5 21.6 1,006 N 0.0x 21.6+ 11.0x 21.6= 238 N 0.0 21.6 21.0 24.3 510 N 0.0 21.6 52.0 24.3 1,263 N 0.0x 21.6+ 3.0X 24.3= 73 N 0.0X 21.6+ 3.0X 24.3= 73 E 66.0 6 21F1.6 0.0 42.8 1 428 E 227.5 60.5 42. 7 514 W 0.0 22.0 43.6X+ Page Total 13 399 Internal Gain Btu/hr Occupants 3 X Occupants X 1 230 Btuh/occ. = 690 E ui ment 0 X Dwelling Units X 1 1,6001 Watts/sqft = 01 Infiltration: 1.064 x 1.19 x 243.93 x = 11111 Air Sensible CFM ELA Z�sT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 37,097 Latent Gain Btu/hr Occu ants X Occupants X 200 Btuh/occ. = 600 Infiltration: 4 771 x 1.19 x 243.93 x 0.00058 = -801 Air Latent CFM ELA pW • TOTAL HOURLY LATENT HEAT GAIN FOR ROOM -201 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:27 of 31 RESIDENTIAL ROOM COOLING LOAD SUMMARY roject Title Date herty Residence 1/5/2007 Room Information Desi n Conditions Room Name: Great/Kit/Break/Din/Den Outdoor Dry Bulb Temperature: 111OF Floor Area: 3,457 sf Outdoor Web Bulb Temperature: 730F Indoor Dry Bulb Temperature: 75 of Outdoor Daily Range: 340F • ue surraces 1 1 Orientation Area U -Factor CLTD 1 Btu/hr W 244.5 X 0.0690 X 33.0 = 557 NW 41.5 X 0.0690 X 30.2 = 87 x X = x x x X = X x x x X X X X x X = x x X r X Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestration 7 Page i otal 1 6431 Orientation Shaded Area x x x X X x X X GLF + + + + + + Unshaded Area x x X X X X Page GLF = = = SW 21.6+ 22.0x 30.2= SW -0.0 0.0x 21.6+ 22.0X 30.2= 8.9X 21.6+ 37.6x 43.6= W 9.2 21.6 1.8 43.6 NW 0.0X 21.6+ 46.5X 33.5= NW 21.6+ 11.0x 33.5= -0.0 Total Btu/hr Internal Gain Btu/hr Occu ants 3 X Occupants X 230 Btuh/oCC. = 690 P P E ui ment 0 x Dwelling Units X 1,6001 Watts/sgft = 1 0 Infiltration: 1.064 X 1.19 x 243.93 X = 11111 Air Sensible CFM ELA Z�T TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 37,097 Latent Gain Btu/hr Occu ants F 31 x Occupants X 200 Btuh/oCC. = 600 Infiltration: 4 771 x 1.19 x 243.93 X -0.00058 = -801 Air Latent CFM ELA QW ID TOTAL HOURLY LATENT HEAT GAIN FOR ROOM -201 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:28 of 31 f . #)-A) • RESIDENTIAL ROOM COOLING LOAD SUMMARY roject Title Date herty Residence 1/5/2007 Room Information Desi n Conditions Room Name: Bedroom 18 Outdoor Dry Bulb Temperature: 1110F Floor Area: 478 sf Outdoor Web Bulb Temperature: 730F Indoor Dry Bulb Temperature: 78OFOutdoor Daily Range: 340F Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr IR -21 Wall (W.19.2x6.16) I D N 474.0 X X X X X X X X X x X X 0.0166 X X X X X X X X X X X X 56.0 N 363.0 0.0690 24.3 E 88.0 0.0690 32.6 W 63.0 0.0690 32.4 24.3 N 0.0x 21.6+ 3.0X 24.3 E 46.1 21.6 29.9 42.8 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestration • rage I otal Orientation Shaded Area x X X x X X X X X X GLF + + + + + + + + + Unshaded Area X X x X X X X X X GLF (Sky) 30.7+ 4.OX 83.5 N -0.0 0.0 21.6 7.0 24.3 N 0.0x 21.6+ 3.0X 24.3 E 46.1 21.6 29.9 42.8 Page Total 441 609 198 141 1 389 Btu/hr Internal Gain Btu/hr Occu ants 4 X Occupants X 230 Btuh/OCC. = 920 P P E ui ment 1 X Dwelling Units X 1,6001 Watts/sgft = 1,6001 Infiltration: 1.064 X 1.15 X 33.73 X = 1361 Air Sensible CFM ELA DT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 8,123 Latent Gain Btu/hr Occu ants F4 X Occupants X 1 2001 Btuh/OCC. = 800 Infiltration: 4 771 x 1.15 x 33.73 x 0.00158 = 292 Air Latent CFM ELA pW • TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 508 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:29 of 31 A RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Title Date pert Residence 1/5/2007 oom Information Desi n Conditions Room Name: Guest Suite Outdoor Dry Bulb Temperature: 111OF Floor Area: 1,371 sf Outdoor Web Bulb Temperature: 730F Indoor Dry Bulb Temperature: 78 of Outdoor Daily Range: 340F Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr is R-38 Roof R.30.2x14.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.2x6.16 R-21 Wall W.19.24.16 R-21 Wall W.19.24.16 SE 145.0 0.0690 29.3 S 486.9 0.0690 27.7 21.6 241.0 0.0690 32.1 N 1,367.0 x X X X X X x x x x x x 0.0166 X X X X X X x x X X X x 56.0 = = = = = = = = E 146.0 0.0690 32.3 SE 145.0 0.0690 29.3 S 486.9 0.0690 27.7 21.6 241.0 0.0690 32.1 N 504.0 0.0690 25.0 24.5 1,141 S 0.0x 21.6+ 10.0x 24.5= 245 S 0.0 21.6 34.0 24.5 834 S 23.0 21.6 4.1 24.5 598 S 39.4 21.6 7.1 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestration Skylight F 3 E D 2 1 C B A Page Total Orientation Shaded Area x x X X X X X, X GLF + + + + + + + Unshaded Area X X X X X X x GLF = = = = = = Btu/hr (Sky) 0.0x 30.7+ 4.Ox 83.5= 334 (SE) 0.0 21.6 30.0 27.4 821 S 0.0 21.6 46.5 24.5 1,141 S 0.0x 21.6+ 10.0x 24.5= 245 S 0.0 21.6 34.0 24.5 834 S 23.0 21.6 4.1 24.5 598 S 39.4 21.6 7.1 24.5 1,027 S 54.0X 21.6+ 0.0x 24.5= 1,169 W 5.4 21.6 21.6 40. 986 W 0.01 21.6+ 8.0x 40.3= 322 Page Total I 7,477 Internal Gain Btu/hr Occu ants 4 x Occupants x 230 Btuh/occ. = 920 P P E ui ment 1 x Dwelling Units x 1,6001 Watts/sgft = 1,600 Infiltration: 1.064 x 1.15 x 96.74 x F 3-9031 Air Sensible CFM ELA DT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 22,241 Latent Gain Occu ants 0 x Occupants x 200 BtUh/oCC. Btu/hr 800 Infiltration: 4 77 x 1.15 x 96.74 x 0.00158 = -836 Air Latent CFM ELA pW iTOTAL HOURLY LATENT HEAT GAIN FOR ROOM -36 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 30 of 31 RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Title Date herty Residence �1/5/2007 oom Information Desicin Conditions Room Name: Guest Suite Outdoor Dry Bulb Temperature: 111OF Floor Area: 1,371 sf Outdoor Web Bulb Temperature: 730F Indoor Dry Bulb Temperature: 78OFOutdoor Daily Range: 340F Opaque Surfaces Orientation Area U -Factor CLTD 1 Btu/hr • Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestration x x x GLF x x x X x X X x X 1 X x x 0.0x x x 40.3 x x 21.6 x x N x x 58.0X x x 0.0 x x 21.6 x x x x x Page Total Orientation Shaded Area X X x X X X XF� X1 X GLF + + + + + +X + + + Unshaded Area x X x X X x X 1 X GLF W 0.0x 21.6+ 14.0x 40.3 W 0.0 21.6 5.0 40.3 N 0.0x 21.6+ 58.0X 25.6 N 0.0 21.6 86.2 21.6 1 Page Total Btu/hr Internal Gain Btu/hr Occu ants 4 X Occupants X 230 Btuh/oCC. = 920 P P E ui ment 1 X Dwelling Units x 1,6001 Watts/sqft = 1,6001 Infiltration: 1.064 X 1.15 X 96.74 X = 3903 Air Sensible CFM ELA DT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 22,2411 Latent Gain Btu/hr Occu ants F4 X Occupants X 200 Btuh/oCC. = 800 Infiltration: 4 771 X 1.15 X 96.74 X F 836 Air Latent CFM ELA pw TOTAL HOURLY LATENT HEAT GAIN FOR ROOM -36 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:31 of 31