BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Clearwater/Sparks Residence
53-540 Del Gato Drive, The Traditions
La Quinta, Ca 92253
Project Designer:
Fedderly and Associates
38-747 Nopales Road
. Palm Desert, Ca 92253
(760) 773-0875
Report Prepared by:
Tim Scott
Scott Design and Title 24, Inc;
77-085 Michigan Drive
Palm Desert, Ca 92211
60) 200-4780 I?ECEIVED
CI�OF��QUINTA
BUILDING & SAFETY DEPT
APPROVED MAY 17 2013
FOR CONSTRUCTION
qOM��NIN -p QUIIVTA
DATE '2 BY IL. 4� EVEL0pMENT
ob Number:
Date:
5/15/2013
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
EnergyPro 5.1 by EnergySoft User Number: 6712: RunCode: 2013-05-15713:32:46. ID:
•
0
TABLE OF CONTENTS
Cover Page
Table of Contents
Form CF -1 R Certificate of Compliance
Form MF -1 R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
IEnergyPro 5.1 by EnergySoft Job Number: ID: User Number: 6712
1
2
3
11
14
17
20
24
•
•
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type m Single Family 13 Addition Alone
❑ Multi Family O Existing+ Addition/Alteration
Date
5/15/2013
Project Address
53-540 Del Gato Drive, The Traditions
La
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,226
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity Features see Part 2 of 5 Status
Roof Wood Framed Attic
R-38 5,199 Radiant Barrier New
Wall Wood Framed
R-21 3,394 New
Slab Unheated Slab -on -Grade
None 5,226 Perim = 414' New
Door Opaque Door
None 24 New
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades Status
Left (N) 151.8 0.390
0.39 none none Bug Screen New
Rear (NE) 182.5 0.390
0.39 none none Bug Screen New
Right (SE) 112.1 0.390
0.39 none none Bug Screen New
Front (Stat 189.5 0.390
0.39 none none Bug Screen New
Skylight 9.0 0.800
0.39 none none None New
Skylight 9.0 0.800
0.39 none none None New
Skylight 9.0 0.800
0.39 none none None New
Rear (NE) 180.0 0.390
0.39 22.0 none Bug Screen New
Rear (NE) 30.6 0.390
0.39 18.0 none Bug Screen New
Rear (NE) 90.0 0.390
0.39 14.0 none Bug Screen New
Right (S) 160.9 0.390
0.39 none none Bug Screen New
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE
Split Air Conditioner 16.5 SEER Setback
New
1 Central Furnace 80% AFUE
Split Air Conditioner 16.5 SEER Setback
New
2 Central Furnace 80% AFUE
Split Air Conditioner 16.5 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
HVAC 1 Ducted
Ducted Attic, Ceiling Ins, vented 8.0 New
HVAC 2 Ducted
Ducted Attic, Ceiling Ins, vented 8.0 New
HVAC 3 8 4 Ducted
Ducted Attic, Ceiling Ins, vented 8.0 New
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
1 Large Gas 65
0.96 All Pipes Ins New
EnergyPro 5.1 by EnergySoft User Number: 6712
RunCode: 2013-05-15713:32:46 ID:
Pa e 3 of 30
•
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration 1511512013
Date
Project Address
53-540 Del Gato Drive, The Traditions La
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,226
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavity Features see Part 2 of 5 Status
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades Status
Front (K9 61.2 0.390 0.39 none none Bug Screen New
Left (NM 74.7 0.390 0.39 none none Bug Screen New
Left (NKK 36.0 1.040 0.38 none none Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
EnergrPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID:
Pe e 4 of 30
•
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type ® Single Family ❑ Addition Alone
1 ❑ Multi Family ❑ Existing+ Addition/Alteration
Date
5/15/2013
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special 'ustification and documentation submitted.
The DHW System Lochinvar #SNR126-065 is a non-NAECA large storage gas water heater. Verify DHW details.
The HVAC System HVAC 1 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Verify Thermal Mass: 970.0 ft2 Covered Slab Floor, 3.500" thick at Master Bedroom
HIGH MASS, Design - Verify Thermal Mass: 324.0 ft2 Exposed Slab Floor, 3.500" thick at Master Bedroom
The HVAC System HVAC 2 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow uirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Verify Thermal Mass: 566.0 ft2 Covered Slab Floor, 3.500" thick at Guest 1/ Office
HIGH MASS Design - Verify Thermal Mass: 203.0 ft2 Exposed Slab Floor, 3.500" thick at Guest 1/ Office
The HVAC System HVAC 3 & 4 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Verify Thermal Mass: 266.0 ft2 Covered Slab Floor, 3.500" thick at GreaWitchen/Dining/Gallery
HIGH MASS Design - Verify Thermal Mass: 2,511. 0 ft' Exposed Slab Floor, 3.500" thick at Great/Witchen/Dining/Gallery
HIGH MASS Design - Verify Thermal Mass: 327.0 ft2 Covered Slab Floor, 3.500" thick at Guest 2
HIGH MASS Design - Verify Thermal Mass: 59.0 112 Exposed Slab Floor, 3.500" thick at Guest 2
The Roof R-38 Roof(R.38.2x 12.16) includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in
Residential Appendix RA4.2.2.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
The Cooling System Carrier 24APA760/58PH•l 10 includes credit for a 13.0 EER Condenser. A certified HERS rater must field verify the installation of
the correct Condenser.
The HVAC System HVAC 1 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 1 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Carrier 24ACA736/58PH'090 includes credit for a 13.2 EER Condenser. A certified HERS rater must field verify the installation of
the correct Condenser
The HVAC System HVAC 2 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 2 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Carrier 24APA760/58PH'110 includes credit for a 13.0 EER Condenser. A certified HERS rater must field verify the installation of
the correct Condenser.
The HVAC System HVAC 3 & 4 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 3 & 4 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
Erre Pro 5.1 by Enem ySoft User Number.- 6712 RunCode: 2013-05-15713:32:46 ID: Page 5 of 30
•
•
PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF -1 R
Project Name
Building Type m Single Family ❑ Addition Alone
Date
Clearwater/Sparks Residence
❑ Multi Family ❑ Existing+ Addition/Alteration
5/15/2013
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV kBtu/ft2- r
Space Heating 3.57 3.02 0.56
Space Cooling 51.52 45.79 5.73
Fans 10.24 14.32 -4.08
Domestic Hot Water 6.98 3.91 3.07
Pumps 0.00 0.00 0.00
Totals 72.31 67.04 5.27
Percent Better Than Standard: 7.3%
BUILDING COMPLIES - HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (w) 270 deg Ext. Walls/Roof Wall Area Area
Number of Dwelling Units: 1.00 (K9 970 251
Fuel Available at Site: Natural Gas (N) 1,245 263
Raised Floor Area: 0 (E) 1,178 483
Slab on Grade Area: 5,226 (S) 1,295 273
Average Ceiling Height: 11.9 Roof 5,226 27
Fenestration Average U -Factor: 0.41 TOTAL: 1.296
Average SHGC: 0.39 Fenestration/CFA Ratio: 24.18%
REMARKS
7ot180-The Hideaway
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and comple
Documentation Author
Company Scott Design and Title 24, Inc,
5/15/7013
Address 77-085 Michigan Drive Name Tim Scott
City/State/ZipCity/State/Zip Palm Desert, Ca 92211 Phone (760) 200-4780 Signed Date
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and
with any other calculations submitted with this permit application, and,recognizes that compliance using duct design,
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company Fedderly and Associates
Address 38-747 Nopales Road Name Fedderly and Associates
City/State2jp Palm Desert, Ca 92253 Phone (760) 773-0875 Signed License # Date
EnemvPro 5.1 by EnemySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID: Page 6 of 30
•
0
•
CERTIFICATE OF COMPLIANCE: Residential
Part 4 of 5 CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
15/15/2013
OPAQUE SURFACE DETAILS
Surface
T e Area
U- Insulation Joint Appendix
Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Roof
1,294
0.026 R-38
270
0 New 4.2.1-A9
Master Bedroom
Wall
219
0.069 R-21
0
90 New 4.3.1-A6
Master Bedroom
Wall
184
0.069 R-21
60
90 New 4.3.1-A6
Master Bedroom
Wall
403
0.069 R-21
150
90 New 4.3.1-A6
Master Bedroom
Wall
187
0.069 R-21
330
90 New 4.3.1-A6
Master Bedroom
Slab
970
0.730 None
0
180 New 4.4.7-A1
Master Bedroom
Slab
324
0.730 None
0
180 New 4.4.7-A1
Master Bedroom
Roof
769
0.026 R-38
270
0 New 4.2.1 A9
Guest 1/0ffice
Wall
229
0.069 R-21
0
90 New 4.3.1-A6
Guest 1/0ffice
Wall
55
0.069 R-21
60
90 New 4.3.1-A6
Guest 1/0ffice
Wall
44
0.069 R-21
90
90 New 4.3.1-A6
Guest 1/Office
Wall
132
0.069 R-21
150
90 New 4.3.1-A6
Guest 1/Office
Wall
221
0.069 R-21
240
90 New 4.3.1-A6
Guest 1/Office
Wall
215
0.069 R-21
330
90 New 4.3.1-A6
Guest 1/Office
Slab
566
0.730 None
0
180 New 4.4.7-A1
Guest 1/Office
Slab
203
0.730 None
0
180 New 4.4.7-A1
IGuest 1/Office
FENESTRATION SURFACE DETAILS
ID
Type
Area LI -Factor'
SHGC
Azm Status
Glazing Type
Location/Comments
1
Window
37.8 0.390 NFRC
0.39 NFRC 0 New
Dual non Metal Tinted
Master Bedroom
2
Window
24.0 0.390 NFRC
0.39 NFRC 0 New
Dual non Metal Tinted
Master Bedroom
3
Window
4.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Master Bedroom
4
Window
88.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Master Bedroom
5
Window
3.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Master Bedroom
6
Window
3.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Master Bedroom
7
Window
3.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Master Bedroom
8
Window
30.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Master Bedroom
9
Window
15.0 0.390 NFRC
0.39 NFRC 150 New
Dual non Metal Tinted
Master Bedroom
10
Window
30.0 0.390 NFRC
0.39 NFRC 150 New
Dual non Metal Tinted
Master Bedroom
11
Window
4.0 0.390 NFRC
0.39 NFRC 0 New
Dual non Metal Tinted
Guest 1/0ffice
12
Window
64.0 0.390 NFRC
0.39 NFRC 0 New.
Dual non Metal Tinted
Guest 1/Office
13
Window
31.5 0.390 NFRC
0.39 NFRC 240 New
Dual non Metal Tinted
Guest 1/0f ice
14
Window
27.0 0.390 NFRC
0.39 NFRC 240 New
Dual non Metal Tinted
Guest 1/Office
15
Window
31.5 0.390 NFRC
0.39 NFRC 240 New
Dual non Metal Tinted
Guest 1/Office
16
Window
4.0 0.390 NFRC
0.39 NFRC 240 New
Dual non Metal Tinted
Guest 1/Office
(1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-13 = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
Hat I Wd
Ove hanq Left Fin
Len Hat LExt RExt Dist Len
Ri ht Fin
Hat Dist Len Hat
1
Bug Screen
0.76
2
Bug Screen
0.76
3
Bug Screen
0.76
4
Bug Screen
0.76
5
Bug Screen
0.76
6
Bug Screen
0.76
7
Bug Screen
0.76
8
Bug Screen
0.76
9
Bug Screen
0.76
10
Bug Screen
0.76
11
Bug Screen
0.76
12
Bug Screen
0.76
13
Bug Screen
0.76
14
Bug Screen
0.76
15
18ug Screen
0.76
16
JBug Screen
0.76
EnergyPro
5.1 by EnemySoft User Number: 6712
RunCode: 2013-05-15713:32:46 ID:
Pae 7 of 30
•
•
CERTIFICATE OF COMPLIANCE: Residential
Part 4 of 5L__ CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type m Single Family ❑ Addition Alone
[3 Multi Family ❑ Existing+ Addition/Alteration
Date
5/15/2013
OPAQUE SURFACE DETAILS
Surface
Type Area
U- Insulation Joint Appendix
Factor Cavi Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Roof
2,750
0.026 R-38
270
0 New 4.2.1-A9
Living Zone
Wall
78
0.069 R-21
0
90 New 4.3.1-A6
Living Zone
Wall
346
0.069 R-21
60
90 New 4.3.1-A6
Living Zone
Wall
175
0.069 R-21
150
90 New .4.3. I -A6
Living Zone
Wall
110
0.069 R-21
180
90 New 4.3.1-A6
Living Zone
Door
24
0.500 None
180
90 New 4.5.1-A4
Living Zone
Wall
77
0.069 1 R-21
240
90 New 4.3.1-A6
Living Zone
Wall
202
0.069 R-21
270
90 New 4.3.1-A6
Living Zone
Wall
54
0.069 R-21
330
90 New 4.3.1-A6
Living Zone
Slab
266
0.730 None
1
0
180 New 4.4.7-A1
Living Zone
Slab
2,511
0.730 None
1 01
180 1 New 4.4.7-A1
Living Zone
Roof
386
0.026 R-38
270
0 New 4.2.1-A9
Guest 2
Wall
64
0.069 R-21
90
90 New 4.3.1-A6
Guest 2
Wall
1781
0.069 1 R-21
180
90 New 4.3.1-A6
Guest 2
Wall
220
0.069 R-21
270
90 New 4.3.1-A6
Guest 2
Slab
3271
0.730 None I
1
0
180 1 New 4.4.7-A1
I Guest 2
FENESTRATION SURFACE DETAILS
ID
Type
Area LI -Factor'
SHGC
Azm Status
Glazing Type
Location/Comments
17
Window
4.0 0.390 NFRC
0.39 NFRC 240 New
Dual non Metal Tinted
Guest 1/Office
18
Skylight
9.0 0.800 NFRC
0.39 NFRC 270 New
Skylight
Living Zone
19
Skylight
9.0 0.800 NFRC
0.39 NFRC 270 New
Skylight
Livin Zone
20
Skylight
9.0 0.800 NFRC
0.39 NFRC 270 New
Skylight
Living Zone
21
Window
22.0 0.390 NFRC
0.39 NFRC 0 New
Dual non Metal Tinted
Living Zone
22
Window
180.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Living Zone
23
Window
30.6 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Living Zone
24
Window
90.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Living Zone
25
Window
45.5 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Living Zone
26
Window
3.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Living Zone
27
Window
3.0 0.390 NFRC
0.39 NFRC 60 New
Dual non Metal Tinted
Living Zone
28
Window
35.0 0.390 NFRC
0.39 NFRC 150 New
Dual non Metal Tinted
Living Zone
29
Window
23.1 0.390 NFRC
0.39 NFRC 150 New
Dual non Metal Tinted
Living Zone
30
Window
3.0 0.390 NFRC
0.39 NFRC 150 New
Dual non Metal Tinted
Living Zone
31
Window
3.0 0.390 NFRC
0.39 NFRC 150 New
Dual non Metal Tinted
Living Zone
32
Window 1
3.0 0.390 NFRC
0.39 NFRC 150 New
Dual non Metal Tinted
Living Zone
(1) LI -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
H t Wd
Ove hanq Left Fin
Len Hot LExt I RExt Dist I Len
Ri ht Fin
Hot Dist Len Hot
17
Bug Screen
0.76
18
None
1.00
19
None
1.00
20
None
1.00
21
Bug Screen
0.76
22
Bug Screen
0.76
10.0 18.0 22.0 0.1 22.0 22.0
23
Bug Screen
0.76
6.5 4.7 18.0 0.1 18.0 18.0
24
Bug Screen
0.76
10.0 9.0 14.0 0.1 14.0 14.0
25
Bug Screen
0.76
26
Bug Screen
0.76
27
Bug Screen
0.76
28
Bug Screen
0.76
29
Bug Screen
0.76
30
Bug Screen
0.76
31
JBug Screen
0.76
32
JBug Screen
0.76
EnergyPro
5.1 by Ene Soft User Number: 6712
RunCode: 2013-05-15713:32:46 ID:
Peg e 8 of 30
•
•
•
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1511512013
OPAQUE SURFACE DETAILS
Surface Ll-
Type Area Factor
Insulation Joint Appendix
Cavity Exterior I Frame Interiorl Frame Azm Tilt Status 4 Location/Comments
Slab
59 0.730 None
0 180 New 4.4.7-A1
Guest 2
FENESTRATION SURFACE DETAILS
ID
Type Area
LI -Factor SHGC
Azm Status Glazing Type
Location/Comments
33
Window 90.0
0.390 NFRC 0.39 NFRC 180 New Dual non Metal Tinted
Living Zone
34
Window 2.3
0.390 NFRC 0.39 NFRC 180 New Dual non Metal Tinted
Living Zone
35
Window 2.3
0.390 NFRC 0.39 NFRC 180 New Dual non Metal Tinted
Living Zone
36
Window 2.3
0.390 NFRC 0.39 NFRC 180 New Dual non Metal Tinted
Living Zone
37
Window 85.5
0.390 NFRC 0.39 NFRC 240 New Dual non Metal Tinted
Living Zone
38
Window 3.0
0.390 NFRC 0.39 NFRC 240 New Dual non Metal Tinted
Living Zone
39
Window 3.0
0.390 NFRC 0.39 NFRC 240 New Dual non Metal Tinted
Living Zone
40
Window 61.2
0.390 NFRC 0.39 NFRC 270 New Dual non Metal Tinted
Living Zone
41
Window 31.5
0.390 NFRC 0.39 NFRC 330 New Dual non Metal Tinted
Living Zone
42
Window 36.0
1.040 NFRC 0.38 NFRC 330 New Custom Door
Living Zone
43
Window 43.2
0.390 NFRC 0.39 NFRC 330 New Dual non Metal Tinted
Living Zone
44
Window 64.0
0.390 NFRC 0.39 NFRC 180 New Dual non Metal Tinted
Guest 2
(1) U -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
Window
SHGC -Hat Wd
Ove hanq Left Fin
Len Hat LExt I RExt Dist Len
Ri ht Fin
Hat Dist Len Hat
33
Bug Screen
0.76
34
Bug Screen
0.76
35
Bug Screen
0.76
36
Bug Screen
0.76
37
Bug Screen
0.76
38
Bug Screen
0.76
39
Bug Screen
0.76
40
Bug Screen
0.76
41
Bug Screen
0.76
42
Bug Screen
0.76
43
Bug Screen
0.76
44
Bug Screen
0.76
EnergyPro
5.1 by EnergySoft
User Number: 6712
RunCode: 2013-05.15713:32:46 ID:
Page 9 of 30
•
•
•
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5
CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1511512013
BUILDING ZONE INFORMATION
System Name Zone Name
Floor Area
New Existina I Altered Removed Volume
Year Built
HVAC 1 Master Bedroom
1,294
16,304
HVAC 2 Guest 1/ Office
769
8,151
HVAC 3 & 4 GreatXitchen/Dining/Gallery
2,777
33,602
Guest 2
386
4,246
Totals 5,2261 0 0 0
HVAC SYSTEMS
System Name Qty. Heating Type
Min. Eff. Coolina Type Min. Eff. Thermostat Type
Status
HVAC 1 1 Central Furnace
80% AFUE Split Air Conditioner 16.5 SEER Setback
New
HVAC 2 1 Central Furnace
80% AFUE S lit Air Conditioner 16.5 SEER Setback
New
HVAC 3 & 4 2 Central Furnace
80% AFUE Split Air Conditioner 16.5 SEER Setback
New
HVAC DISTRIBUTION
System Name Heating
Duct
Cooling Duct Location R -Value
Ducts
Tested? Status
HVAC 1 Ducted Ducted Attic, Ceiling Ins, vented 8.0
m
New
HVAC 2 Ducted Ducted Attic, Ceiling Ins, vented 8.0
m
New
HVAC 3 & 4 Ducted Ducted Attic, Ceiling Ins, vented 8.0
0
New
WATER HEATING SYSTEMS
S stem Name
Oty.
Ty e
Distribution
Rated
Input
(Btu h)
Tank
Cap.
al
Energy Standby
Factor Loss or
or RE Pilot
Ext.
Tank
Insul. R-
Value
Status
Lochinvar#SNR126-065
1
Large Gas
All Pipes Ins
126,000
65
0.96 0.00%
0.0
New
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
Control
Hot Water Piping Length
ft
o
y
a c
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
QtyTHP
Plenum Outside Buried
EnerqyPro 5.1 by EnergySoft User Number. 6712
RunCode: 2013-05-15713:32:46 ID:
Pae 10 of 30
•
0
•
MANDATORY MEASURES SUMMARY: Residential (Page 1 of 3 MF -1 R
Project Name
Clearwater/Sparks Residence
Date
5/15/2013
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form.
` §118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(1) when the
' installation of a Cool Roof is specified on the CF -1 R Form.
*§150(a): Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor.
150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
*§150(c): Minimum R-13 insulation in wood -frame wall orequivalent U -factor.
*§150(d): Minimum R-13 insulation in raised wood -frame floor orequivalent U -factor.
150(f): Air retarding wrap is tested labeled and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form.
§150(q): Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
-rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 e 1 A: Masonry or facto -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
`-equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
,outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
,1§150(h):
_§1500): Heatingsystems are equipped with thermostats that meet the setback requirements of Section 112(c).
�,§150(j)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
"with insulation having an installed thermal resistance of R-12 or greater.
§1500)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
&`tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
'§1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculatinq sections of hot water pipes are insulated per Standards Table 150-13.
§1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot
water tank shall be insulated to Table 150-B and Equation 150-A.
§1500)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
123-A.
1500)3A: Insulation is protected from damage, including that due to sunlight, moisture equipment maintenance and wind.
§1500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
- 150(j)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
�. EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID: Page 11 of 30
0
•
•
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
Clearwater/Sparks Residence
1511512013
§150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
-applicable requirements of UL 181, UL 181A, or UL 1818 or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
§150(m)7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
§150(m)10: Flexible ducts cannot have porous inner cores.
§150(0): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
-Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
,required in Section 4 of that Standard.
Pool and S a Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 .
Residential Lighting Measures:
§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low eff icacy luminaire asspecified by §150(k)2.
150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d).
"§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens shall meet the applicable requirements of §150(k).
150(k)7: All switching devices and controls shall meet the requirements of §150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
manual -on occupant sensor.
-•§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
EnergyPro 5.1 by EnergySoff User Number: 6712 RunCode: 2013-05-15713:32:46 ID: Page 12 of 30
0
•
•
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
Clearwater/Sparks Residence
5/15/2013
,§150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
.occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)l 1: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with 150 k 11.
§150(k)l2: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
-dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
..they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptionl to §150(k)l3 may be controlled by a temporary override switch which bypasses the motion
.sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130 131, 134, and 146.
§150(k)l6: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
.'that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
EnergyPro5.1 by EnergySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID: Page 13 of 30
C�
•
•
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Clearwater/Sparks Residence
Date
5/15/2013
System Name
HVAC 1
Floor Area
1,294
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING
CFM Sensible
Total Room Loads 815 18,261
Return Vented Lighting 0
Return Air Ducts 1,054
Return Fan 0
Ventilation F 0 0
Supply Fan 0
Supply Air Ducts 1,054
TOTAL SYSTEM LOAD 20,369
PEAK COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output perSystem 110,000
1,008 280
15,167
Total Output Btuh 110,000
Output Btuh/s ft 85.0
745
Cooling System
0
Output perSystem 59,000
0 0
0
Total Output Btuh 59,000
1,008
0
Total Output ons 4.9
745
Total Output Btuh/s ft 45.6
Total Output s ft/Ton 263.2
16,658
'Air System
CFM perSystem
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24APA760/58PH'110 46,928
Total Adjusted System Output 46,928
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
4,133 110,000
4,133 110,000
Aug 3 PM F Jan 1 AM
Alrflow cfm/s ft 1.55
Airflow cfm/Ton 406.8
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 70 OF
�.
Outside Air
0 cfm Supply Fan
2,000 cfrn
70 OF
70 OF 121 OF
10
10
Heating Coil
121 OF
FROOM r
70 OF
-COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 78!63°F
Outside Air
0 cfm
78/63°F
78/63°F 56/55°F
Supply I Fan
Cooling Coil57 / 55 OF
2,000 cfm _-..-............ .—
44.2% ROOM
78/63°F
r
EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2013-05-15713:32:46 ID:
Page 14 of 30
•
•
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Clearwater/Sparks Residence
Date
5/15/2013
System Name
HVAC 2
Floor Area
769
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 374
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation F 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Outout oerS stem 89,000
9,105
680 152
11,150
Total Output Btuh 89,000
0
Output Btuh/ ft 115.7
526
548
`Cooling System
0
0
Output perSystem 36,600
0
0 0
0
Total Output Btuh 36,600
0
526
1 10,157
680
0
Total Output ons 3.1
548
Total Output Btuh/s ft 47.6
Total Output s ft/Ton 252.1
12,246
Air System
CFM perSystem
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Carrier 24ACA736/58PH•090 30,261
941
89,000
Airflow cfm/s ft
1.56
Total Adjusted System Output 30,261
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
941 1 89,000
Aug 3 PM F Jan 1 AM
Airflow cfm/Ton 393.4
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 70 OF
Outside Air
0 elm Supply Fan
1,200 cfm
70 OF
70 OF 139 OF
Heating Coil
138 OF
••••••- ..
ROOM
70 OF
'.COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112 / 78 OF 78 162 OF 78 / 62 OF 55 / 53 OF
o
Outside Air
0 cfm Supply Fan Cooling Coil 55 / 54 OF
1,200 cfm
41.3% ROOM
78 162 OF 78 / 62 OF
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID:
Page 15 of 30
•
•
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Clearwater/Sparks Residence
Date
5/15/2013
System Name
HVAC 3 & 4
Floor Area
3,163
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
COIL
CFM
Total Room Loads 1,943
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 110,000
43,094
2,375 746
40,266
Total Output Btuh 220,000
0
Output Btuh/ ft 69.6
2,488
1,979
Coolin System
01
0
Output per System 59,000
0
0 0
0
Total Output Btuh 118,000
0
2.486
1 48,069
2,375
0
Total Output ons 9.8
1,979
Total Output Btuh/s ft 37.3
Total Output s ft/Ton 321.7
44,224
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Alrf low cfm
4,000
Carrier 24APA760/58PH'110 93,679
Total Adjusted System Output 93,679
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
8,654 220,000
8,654 220,000
Aug 3 PM I Jan 1 AM
Airflow cfm/s ft 1.26
Airflow cfmfron 406.8
Outside Air°io 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
-HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 70 OF
Outside Air
0 cfm Supply Fan
4,000 cfm
70 of
70 OF 121 OF
Heating Coil
121 OF
---
ROOM M
70 OF
,COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112 / 78 OF 79163
Outside Air
0 cfm
79 / 63 OF
OF 79 / 64 OF 57 / 55 OF
Supply Fan
Cooling Coil57156 OF
_...... _ _........... _..._..
a,000 cfm 44.5% ROOM
78 / 63 OF
EnergyPro 5.1 by EnergySoff
User Number: 6712 RunCode: 2013-05-15713:32:46 ID:
Page 16 of 30
•
•
•
ROOM LOAD SUMMARY
Project Name Date
Clearwater/Sparks Residence 5/15/2013
System Name Floor Area
HVAC 1 1,294
ROOM LOAD SUMMARY
ROOM COOLINNPEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM SensibleCFM Sensible Latent • CFM Sensible
Master8edroom Master Bedroom 1 815 18,261 8151 18,2611 1,008 2601 15,167
.m
6712
PAGE TOTAL
TOTAL'
815
18,261
1,008
280
15,167
815
18,261
1,008
280
15,167
•
•
ROOM LOAD SUMMARY
Project Name Date
Clearwater/Sparks Residence 5/15/2013
System Name Floor Area
HVAC 2 769
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible I Latent CFM Sensible Latent CFM I Sensible
Guest 1/Office Guest 1/ Office I 1 1 3741 9,1051 680 3741 9,1051 6801 1521 11,150
' Total i
Enemy,
PAGE TOTAL
TOTAL'
374
9,105
680
1,521
11,150
374
9,105
680
152
11,150
0
•
ROOM LOAD SUMMARY
Project Name Date
Clearwater/Sparks Residence 5/15/2013
System Name Floor Area
HVAC 3 & 4 3,163
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible I Latent CFM Sensible Latent CFM Sensible
Living Zone GreatXitchen/Dining/Gall 1 1,770 39,243 1,934 1,770 39,243 1,934 647 34,969
Guest Guest 1 1 1741 3,8511 441 174 3,851 4411 98 5,297
PAGE TOTAL 1,943 43,094 2,375 746 40,266
•TOTAL' 1,943 43,094 2,375 746 40,266
' Total includes ventilation load for zonal systems.
N
•
•
•
ROOM HEATING PEAK LOADS
Project Name75/15/2013
ate
Clearwater/Sparks Residence
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master Bedroom
Time of Peak Jan 1 AM
Floor Area 1,294.0 ft2
Outdoor Dry Bulb Temperature 26 OF
Indoor Dry Bulb Temperature 70 OF
Conduction Area
U -Value
AT OF Btu/hr
R-38 Roof(R.38.2x 12.16) 1,294.0
X
0.0260 X
44 = 1,480
R-21 Wall (W.21.2x6.16) 992.7
X
0.0690 X
44 = 3,014
Dual non Metal Tinted 237.8
X
0.3900 X
44 = 4,081
Slab -On -Grade perm = 107.0
X
0.7300 X
44 = 3,437
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
J=
Items shown with an asterisk (') denote conduction through an interior surface
to
another room
Page Total 12.012
Infiltration:[ 1.00 X 1.064 X 1,294 X
12.60 X 0.248
/60] X 44 0 3,156
Schedule Air Sensible Area
Ceiling
Height ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 15,167
EneTyPro 5.1 by Energ Soft User Number: 6712 RunCode: 2013-05-15T13:32:46 ID: Page 20 of 30
1 •
•
ROOM HEATING PEAK LOADS
Project Name Date
Clearwater/Sparks Residence 5/15/2013
ROOM INFORMATION DESIGN CONDITIONS
Room Name Guest I/ Office Time of Peak Jan 1 AM
Floor Area 769.0 ft' Outdoor Dry Bulb Temperature 26 OF
Indoor Dry Bulb Temperature 70 OF
Conduction Area
R-38 Roof(R.38.2x 12.16) 769.0
R-21 Wall (W.21.2x6.16) 896.0
Dual non Metal Tinted 166.0
Slab -On -Grade perim = 88.0
Items shown with an asterisk (`) denote conduction through an interior surface
Infiltration:[ 1.00 X 1.064 X 769 X
Schedule Air Sensible Area
Fraction
U -Value
X 0.0260
AT -F Btu/hr
X 44 = 880
X 44 = 2,720
X 44 = 2,849
X 44 = 2,827
X =
X =
X =
X =
X =
X =
X =
X =
X
X =
X
X
X
X
X
X =
X =
X
X
X =
X
X =
X
X _
X =
X
X
Page Total 9.275
/60] X 44 = 1,875
AT
X
X
X
X
X
X
0.0690
0.3900
0.7300
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to another room
10.60 X 0.295
Ceiling Height ACH
TOTAL HOURLY HEAT LOSS FOR ROOM 11.150
L]
•
•
ROOM HEATING PEAK LOADS
Project Name75/15/2013
Clearwater/Sparks Residence
ate
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great/Kitchen/Dining/Gallery
Floor Area 2,777.0 ft'
Indoor Dry Bulb Temperature 70 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction Area
R-38 Roof(R.38.2x 12.16) 2,750.0 X
Skylight 27.0 X
R-21 Wall (W.21.2x6.16) 1,043.5 X
Dual non Metal Tinted 765.5 X
Wood Door 24.0 X
Custom Door 36.0 X
Slab -On -Grade Perim = 175.0 X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Items shown with an asterisk (') denote conduction through an interior surface to
Infiltration:[ 1.00 X 1.064 X 2, 777 X
Schedule Air Sensible Area Ceiling
Fraction
U -Value
0.0260 X
0.6000 X
0.0690 X
0.3900 X
0.5000 X
1.0400 X
0.7300 X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
L X
another room
12.10 X 0.258
Height ACH
AT OF
Btu/hr
44
=
3,146
44
=
=
950
44
3,168
44
=
13,136
44
=
528
44
=
=
=
=
1,647
44
5,621
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Page Total
/60] X 44
AT
28,197
= 6,772
TOTAL HOURLY HEAT LOSS FOR ROOM 34,969
Energ Pro 5.1 by Energ Soft User Number: 6712 RunCode: 2013-05-15713:32:46 ID: Page 22 of 30
•
•
•
ROOM HEATING PEAK LOADS
Project Name
ClearwaterlSparks Residence
Date
5/15/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest 2
Floor Area 386.0 ft'
Indoor Dry Bulb Temperature 70 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area U -Value
386.0 X 0.0260 X
462.0 X 0.0690 X
64.0 X 0.3900 X
pan = 44.0 X 0.7300 X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
through an interior surface to another room
X 386 X 11.00 X 0.284
Area Ceiling Height ACH
AT °F Btu/hr
44 = 442
44 = 1,403
44 = 1,098
44 = 1,413
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Page Total 4,356
/ 60 1 X 44 = 941
AT
R-38 Roof(R.38.2x 12.16)
R-21 Wall (W.21.2x6.16)
Dual non Metal Tinted
Slab -On -Grade
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 5,297
Energ Pro 5.1 by Energ Soft User Number: 6712 RunCode: 2013-05-15713:32:46 ID: Page 23 of 30
•
•
0
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Clearwater/Sparks Residence 1 5/15/2013
ROOM INFORMATION DESIGN CONDITIONS
Room Name Master Bedroom Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,294.0 (tz Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 78 OF Outdoor Dailv Ranae: 34 OF
Opaque Surfaces Orientation
Area
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
R-38 Roof(R.38.2x 12.16) (lM
1,294.0
X
0.0260
X
77.0 =
R-21 Wall (W.21.2x6.16) (N)
219.2
X
0.0690
X
31.0 =
R-21 Wall (W.21.2x6.16) (NE)
184.0
X
0.0690
X
37.3 =
R-21 Wall (W.21.2x6.16) (SE)
403.0
X
0.0690
X
41.3 =
R-21 Wall (W.21.2x6.16) (NM
186.5
X
0.0690
X
45.8 =
(NE)
(SE)
0.0
X
30.0
X
=
27.1
15.0
X
X
=
X
X
=
X
J
X
=
Page Total
Items shown with an asterisk (') denote conduction through an
interior surface to
another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation
Area
GLF
Area
GLF
O
11
N
M
BB
BB
BB
L
K
Internal Gain
(N)
(N)
(NE)
0.0
X
X
X
X
X
X
X
X
X
27.1
+
+
+
+
+
+
+
+
+
37.8
X
X
X
X
X
X
X
X
X
27.1
=
=
=
=
=
=
=
=
=
0.0
27.1
24.0
27.1
0.0
27.1
4.0
48.3
(NE)
(NE)
(NE)
(NE)
0.0
27.1
88.0
48.3
0.0
27.1
3.0
48.3
0.0
27.1
3.0
48.3
0.0
27.1
3.0
48.3
(NE)
(SE)
0.0
27.1
30.0
48.3
0.0
27.1
15.0
56.4
Page Total
1.0 Occupants X 230 Btuh/occ.
0.0 Dwelling Unit X 1,2001 Btu =
I Infiltration: 1.064 X 0.87 X 70.81 X 34 =
Air Sensible CFM ELA AT
ll
Latent Gain
Occupants 1.0 Occupants X 200 Btuh/occ. _
Infiltration: 4,771 X 0.87 X 70.81 X 0.00276 =
Air Sensible CFM ELA AW
Btu/hr
2,591
469
474
1,149
589
2721
Btu/hr
1,024
650
193
4,252
145
145
145
1,450
2,218
18,261
Btu/hr
200
808
0
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Clearwater/Sparks Residence
1 5115/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master Bedroom
Outdoor Dry Bulb Temperature
112 OF
Floor Area 1,294.0 fie
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
X
X
X
X
X
X
=
X
X
=
X
X
X
X
X
X
=
X
X
X
X
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
10 (SE) 0.0 X 27.1 +
30.0 X 56.4
= 1,691
X +
X
X +
X
X +
X
-
X +
X
-
X +
X
-
X +
X
-
X +
X
-
X + I
X
-
Page Total
1,691
Internal Gain
Btu/hr
Occupants 1.0 Occupants X 230
Btuh/occ. =
230
Equipment 0.0 Dwelling Unit X 1,200
Btu
c
0
Infiltration: 1.064 )( 0.87 X 70.81 X 34 =
2,218
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
18,261
Latent Gain
Btu/hr
Occupants 1.0 Occupants X F 200
Btuh/occ. =
200
Infiltration: 4,771 X 0.87 X 70.81 X 0.00276 =
F7778-08
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,008
Ene-myPro, 5.1 by EnemySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID:
Pace 25 of 30
` f M
•
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Clearwater/Sparks Residence
1 5/15/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest I/ Office
Outdoor Dry Bulb Temperature
112 OF
Floor Area
769.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-36 Roof(R.38.2x 12.16)
(IM 769.0 X 0.0260
X 56.0 =
1,120
R-21 Wall (W.21.2x6.16)
(N) 229.0 X 0.0690
X 23.0 =
363
R-21 Wall (W.21.2x6.16)
(NE) 55.0 X 0.0690
X 30.3 =
115
R-21 Wall (W.21.2x6.16)
(E) 44.0 X 0.0690
X 33.0 =
100
R-21 Wall (W.21.2x6.16)
(SE) 132.0 X 0.0690
X 29.3 =
267
R-21 Wall (W.21.2x6.16)
(SIM 221.0 X 0.0690
X 31.7 =
483
R-21 Wall (W.21.2x6.16)
(NIM 215.0 X 0.0690
X 29.3 =
435
X
X =
X J
X I=
Page Total
2,883
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
P
(N) 0.0 X 22.3 +
4.0 X 22.3
= 69
7
(N) 0.0 X 22.3 +
64.0 X 22.3
= 1,425
S
(SW) 0.0 X 22.3 +
31.5 X 32.2
= 1,015
12
(SIM 0.0 X 22.3 +
27.0 X 32.2
= 870
S
(SW) 0.01 X 22.3 +
31.5 X 32.2
= 1,015
R
(SIM 0.0 X 22.3 +
4.0 X 32.2
= 129
Q
(SIM 0.0 X 22.3 +
4.0 X 32.2
= 129
X +
X
-
X +1
X
-
Page Total
4,674
Internal Gain
Btu/hr
Occupants
1.0 Occupants X 230
Btuh/occ. =
230
Equipment
0.0 Dwelling Unit X 1,600
Btu =
0
Infiltration: 1.064
X 0.87 X 42.08 X 34 =
1,318
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
9,105
Latent Gain
Btu/hr
Occupants
10 Occupants X 200
Btuh/occ. =
200
Infiltration: 4,771
X 0.87 X 42.08 X 0.00276 =
480
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
680
EnerovPrp 5.1 by Ene-mySoft
User Number: 6712 RunCode: 2013-05-15713:32:46 ID:
Page 26 of 30
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Clearwater/Sparks Residence
ROOM INFORMATION DESIGN CONDITIONS
Room Name GreaWitchen/Dining/Gallery Outdoor Dry Bulb Temperature
Floor Area Z777.0 ft2 Outdoor Wet Bulb Temperature
Indoor Dry Bulb Temperature 78 OF Outdoor Dailv Ranae:
nnan"P Rnrfar_Ps
R-38 Roof(R.38.2x 12.16)
R-21 Wall (1..21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
Wood Door
R-21 Wall (W.21.2x6.16)
R-21 Wall (W. 21.2x6.16)
R-21 Wall (W. 21.2x6.16)
(N)
(NE)
Date
5/15/2013
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
2, 750.0
0.0260
56.0
78.0
0.0690
23.0
347.9
0.0690
30.3
174.9
0.0690
29.3
110.1
0.0690
26.0
24.0
0.5000
26.0
76.5
0.0690
31.7
201.8
0.0690
33.0
54.3
0.06901
29.3
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
FPnPStrattnn
Skylight
Skylight
Skylight
C
9
J
8
G
BB
(N)
(NE)
Page Total
Shaded
Area
GLF
Unshaded
Area
+ 9.0
GLF
X 83.7
X 83.7
X 83.7
X 22.3
X 38.4
X 38.4
X 38.4
X 38.4
X 38.4
Page Total
=
=
=
=
=
=
=
=
=
0.0
X
30.9
0.0
X
X
30.9
+
+
+
+
+
+
9.0
0.0
30.9
9.0
0.0
X
X
X
X
22.3
22.0
103.8
22.3
76.2
22.1
22.3
8.5
32.7
22.3
57.3
0.0
X
22.3
+ 45.5
+1 3.0
0.0 X
22.3
112 OF
78 OF
34 OF
lu/hr
4,004
124
728
354
198
312
167
459
110
Btu/hr
754
754
754
490
5,234
818
2,926
1,745
115
13.589
Internal Gain Btu/hr
Occupants 1.0 Occupants X 230 Btuh/occ. = 230
Equipment 0.0 Dwelling Unit X 1,600 Btu = 0
Infiltration: 1.064 X 0.87 X 151.96 X 34 = 4,761
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 39,243
Latent Gain Btu/hr
Occupants 10 Occupants X 200 Btuh/occ. = 200
Infiltration: 4,771 X 0.87 X 151.96 X 0.00276 = 1,734
Air Sensible CFM ELA AW
• TOTAL HOURLY LAT
•
0
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Clearwater/Sparks Residence 1 5/15/2013
ROOM INFORMATION DESIGN CONDITIONS
Room Name GreabKitchen/Dining/Gallery Outdoor Dry Bulb Temperature 112 OF
Floor Area 2,777.0 ft' Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temaerature 78 OF Outdoor Dailv Ranoe: 34 OF
Area U -Factor CLTD'
X X =
X X =
X X _
X X =
X X =
X X =
X X =
X X =
X X =
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
FanPstratinn
BB
H
F
BB
BB
BB
E
AA
AA
Orientatinn
(NE)
(SE)
(SE)
(SE)
(SE)
(SE)
(S)
(S)
(S)
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
Btu/hr
0.0
22.3
3.0
38.4
115
0.0
22.3
35.0
28.3
990
0.0
22.3
23.1
28.3
653
0.0
22.3
3.0
28.3
85
0.0
22.3
3.0
28.3
85
0.01
22.3
3.0
28.3
85
0.0
22.3
90.0
22.4
2,013
0.0
22.3
2.3
22.4
51
0.0
22.3
2.3
22.4
51
Page Total
4,129
Internal Gain Btu/hr
Occupants 1.0 Occupants X 230 Btuh/occ. = 230
Equipment 0.0 Dwelling Unit X 1,600 Btu = 0
Infiltration: 1.064 X 0.87 X 151.96 X 34 = 4,761
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 39,2431
Latent Gain Btu/hr
Occupants 1.0 Occupants X 200 Btuh/occ. = 200
Infiltration: 4,771 X 0.87 X 151.96 X 0.00276 = 1,734
Air Sensible CFM ELA AW
J \1 4
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Clearwater/Sparks Residence
1 5/15/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Great/Kitchen/Dining/Gallery
Outdoor Dry Bulb Temperature
112 OF
Floor Area
2,777.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
AA
(S) 0.0 X 22.3 +
2.3
X 22.4 =
51
T
(S K9 0.0 X 22.3 +
85.5
X 32.2 =
2,756
88
(SIM 0.0 X 22.3 +
3.0
X 32.2 =
97
BB
(S K9 0.0 X 22.3 +
3.0
X 32.2 =
97
B
(lM 0.01 X 22.3 +
61.2
X 45.4 =
2,780
A
(NM 0.0 X 22.3 +
31.5
X 34.8 =
1,097
1
(NM 0.0 X 34.9 +
36.0
X 47.1 =
1,696
U
(NIM 0.0 X 22.3 +
43.2
X 34.8 =
1,504
X +1
1
X1 I =
Page Total
10,078
Internal Gain
Btu/hr
Occupants
1.0 Occupants X 230
Btuh/occ.
= �-10
Equipment
0.0 Dwelling Unit X 1,600
Btu
=
Infiltration: 1.064
x 0.87 X 151.96 X 34 =
4,761
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
39,243
Latent Gain
Btu/hr
Occupants
1.0 Occupants X 200
Btuh/occ.
=
200
Infiltration: 4.771
X 0.87 X 151.96 X 0.00276 =
1,734
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,934
EnemvPro 5.1 by EnemySoft
User Number: 6712 RunCode: 2013-05-15713:32:46 ID:
Pa a 29 of 30
0
0
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project NameDate
Clearwater/Sparks Residence
5/15/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest 2
Outdoor Dry Bulb Temperature
112 OF
Floor Area 386.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x 12.16) 386.0 X 0.0260
X 56.0 =
562
R-21 Wall (W. 21.2x6.16) . (E) 64.0 X 0.0690
X 33.0 =
146
R-21 Wall (W.21.2x6.16) (S) 178.0 X 0.0690
X 26.0 =
319
R-21 Wall (W.21.2x6.16) (IM 220.0 X 0.0690
X 33.0 =
501
X
X =
X
X =
X
X =
X
X =
X J
X =
Page Total
1,528
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area GLF
Btu/hr
7 (S) 0.0 X 22.3 +
64.0 X 22.4
= 1,431
X +
X
-
X +
X
-
X +
X
-
X +
X
-
X +
X
-
X +
X
-
X +
X
-
X +1
xi
-
Page Total
1,431
Internal Gain
. Btu/hr
Occupants 1.0 Occupants X 230
Btuh/occ. =
0
Equipment 0.0 Dwelling Unit X 1,600
Btu =
f0
Infiltration: 1.064 X 0.87 X 21.12 X 34 =
662
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
3,851
Latent Gain
Btu/hr
Occupants 1.0 Occupants X 200
Btuh/occ. =
200
Infiltration: 4,771 X 0.87 X 21.12 X 0.00276 =
241
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
441
Ene Pro 5.1 by Enemysoft User Number.* 6712 RunCode: 2013-05-15T13:32:46 ID:
Pa a 30 of 30
Electronically Filed by Tim Scott and Authenticated at CalCERTS.com - 5/15/2013
Electronically Signed at CalCERTS.com by Nicole Charon (Fedderly & Associates) 5/16/2013
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration 1511512013
Date
Project Address
53-540 Del Gato Drive, The Traditions La
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,226
Addition
n1a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
IZI Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavity Features art 2 of 5 Status
Roof Wood Framed Attic R-38 5,199 Radiant Barrier New
Wall Wood Framed R-21 3,394 New
Slab Unheated Slab -on -Grade None 5,226 Perim = 414' New
Door Opaque Door None 24
O I
(i F< 6(12
Q
..:F
FENESTRATION `` U. Exterior til�cN
Orientation Area 1 Factor SHGC Overhang Sidefins Shades T Status
Left, (N) 151.8 h 0.390 0.39 none none Bug Screen New
Rear`(NE) _ 182.5 �p .0:390 0.39- none .:.:_none_ Bug,Screen,; New
'� 39�r 0 39 " none ,; � ..none ,
Right (SE) : ° 112.1 T " (px� 6,:, - ""Bug Screen �� , New
Front (&lNJ- ; ,- 189 5 0:390 0 39 : ;none _ none ` Bug Screen; New
Skylight ` § 9.0 0.800 0139 =%noneee J none x _„,_; „� . .4NoneyNe`w
Skylight\,, `'.'" .1 „ ti 9 04 0 800 0 39 n ' \none,, „ ;; None
Skylight `: 9.0 ' r, 0.800 0 39.: -;:none none -" None New
Rear (NE) ,, m '� 180.0. ..0.390 0.39 22.0 none Bug Screen New
Rear (NE), 30.6 0.390 0.39 18.0 none Bug Screen New
Rear (NE) 90.0 0.390 0.39 14.0 none Bug Screen New
Right (S) 160.9'.,; . 0.390 0.39 none none Bug Screen New
HVAC SYSTEMS
City. Heating Min. Eff Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE Split Air Conditioner 16.5 SEER Setback New
1 Central Furnace 80% AFUE Split Air Conditioner 16.5 SEER Setback New
•. 2 Central Furnace 80% AFUE Split Air Conditioner 16.5 SEER Setback New
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
HVAC 1 Ducted Ducted Attic, Ceiling Ins, vented 8.0 New
HVAC 2 Ducted Ducted Attic, Ceiling Ins, vented 8.0 New
HVAC 3 & 4 Ducted Ducted Attic, Ceiling Ins, vented 8.0 New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
1 Large Gas 65 0.96 All Pipes Ins New
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID:
Pae 1 of 8
Reg: 213-N0016858C-000000000-0000 Registration Date/Time: 2013/03/20 12:36:20 HERS Provider: CalCERTS, Inc
Electronically Filed by Tim Scott and Authenticated at CalCERTS.com - 5/15/2013
Electronically Signed'at CalCERTS.com by Nicole Charon (Fedderly & Associates) 5/16/2013
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type 0 Single Family 0 Addition Alone
0 Multi Family 0 Existing+ Addition/Alteration
Date
5/15/2013
Project Address
53-540 Del Gato Drive, The Traditions La
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5, 226
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes. ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavity Features see Part 2 of 5 Status
FEN ESTRATION:,:r'' 'I1,U- Exterior
_.,._._Area ii; Factor SHGC Overhang Sidefins Shades Status
.Orientation
Font (IAS 61.2 ...,0.390 0.39 none none Bug Screen New
LeibVIO 74.70 390 0 39 none -- none Bug,Screen New
Left (Nl<1�?� r,.F- _ � 3R : 36.0Bug New
i
111A 's
Mill
x..
HVAC SYSTEMS
My. Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID:
Page 2 of 8
Reg: 213-N0016858C-000000000-0000 Registration Date/Time: 2013/03/20 12:36:20 HERS Provider: Ca10ERTS, Inc
Electronically Filed by Tim Scott and Authenticated at Ca10ERTS.com - 5/15/2013
Electronically Signed at CalCERTS.com by Nicole Charon (Fedderly &Associates) 5/16/2013
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name
Building Type ® Single Family 0 Addition Alone
Date
ClearwaterlSparks Residence
O Multi Family 13Existing+ Addition/Alteration
5/15/2013
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted. ,
The DHW System Lochinvar #SNR126-065 is a non-NAECA large storage gas water heater. Verity DHW details.
The HVAC System HVAC 1 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
se crate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential A endix RA3.3 must be met.
HIGH MASS Design - Verity Thermal Mass: 9 70. 0 ft2 Covered Slab Floor, 3.500" thick at Master Bedroom
HIGH MASS Design - Verify Thermal Mass: 324.0 ft' Exposed Slab Floor, 3.500" thick at Master Bedroom
The HVAC System HVAC 2 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
se crate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix R43.3 must be met.
HIGH MASS Design - Verify Thermal Mass: 566.0 ft' Covered Slab Floor, 3.500" thick at Guest 1/ Office
HIGH MASS Design - Verity Thermal Mass: 203.0 ft2 Exposed Slab Floor, 3.500" thick at Guest 1/ Office
The HVAC System HVAC 3 & 4 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the airflow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Verify Thema Wass: 266.0 ft2 Covered Slab Floor, 3.500" thick at Great/Kitchen/Dining/Gallery
,HIGH MASS Design - Verify Thermali!Mass: 2,511.0 ft' Exposed Slab Floor, 3.500" thick at Great/Kitchen/Dining/Gallery
::..... -....r .
HIGH MASS Design - Verity Thermal Mass;;. 327.0 ft' Covered Slab Floor, 3.500" thick at Guest 2
i €..
HIGHaMASS7�D✓esTgn Venjly Thermal, Mass 59--y0 - Exposed Sl6b Floor 3'500 lhickiat Guest 2
F�.i.i
The Roof R;38,Roof(Ri38 2 42 16) includes credit`for a Radiant Barrer that 1s�f,Continuous meeting
eligibildy and�installatlon cntena;as specified in
Residential -A endix _
HEFtSREQUIRED�1�/ERIFICATIONi
Items m section f a
field testing antl/or ver(f(cation bya certified HERS Rater"!The mspeetor
th(s regwre rnustreceive
coli leted CF;;4R form"for`each '0" 65measures'listed-below for final to be" Ivan:
The Cooling System.,.Carrier 24APA760/58PH'110 includes credit for a 13.0 EER Condenser. A certified HERS rater must field verity the installation of
-.;-
the correct Condenser
The HVAC`System HVAC 4,incorpoi ieiiHERS Verified Refrigerant Charge or a Charge Indicator Display.
is ),
The HVAC System HVAC 1 incorppiates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified cntena ::
The Cooling System Carrier 24ACA736/58PH•090 includes credit for a 13.2 EER Condenser. A certified HERS rater must field verify the installation of
the correct Condenser.
The HVAC System HVAC 2 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 2 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Carrier 24APA760/58PH'110 includes credit for a 13.0 EER Condenser. A certified HERS rater must field verity the installation of
the correct Condenser.
The HVAC System HVAC 3 & 4 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC.3 & 4 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
Erie Pro 5.1 by Ene Soft User Number: 6712 RunCode: 2013-05-15713:32:46 ID: Page 3 of 8
Reg: 213-N0016858C-000000000-0000 Registration Date/Time: 2013/03/20 12:36:20 HERS Provider: CalCERTS, Inc
Electronically Filed by Tim Scott and Authenticated at CalCERTS.com - 5/15/2013
Electronically Signed'at CalCERTS.com by Nicole Charon (Fedderly & Associates) 5/16/2013
PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF -1 R
Project Name
Building Type m Single Family ❑ Addition Alone
Date
Clearwater/Sparks Residence
❑ Multi Family ❑ Existing+ Addition/Alteration
5/15/2013
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV kgtu/ft2-
Space Heating 3.57 3.02 0.56
Space Cooling 51.52 45.79 5.73
Fans 10.24 14.32 -4.08
Domestic Hot Water 6.98 3.91 3.07
Pumps 0.00 0.00 0.00
Totals 72.31 67.04 5.27,
Percent Better Than Standard: 7.3%
BUILDING COMPLIES '- HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (►M 270 deg Ext. Walls/Roof Wall Area Area
Number of Dwelling Units: 1.00 (w) 970 251
Fuel Available at Site: Natural Gas (N) 1,245 263
Raised Floor Area: 0 (E) 1,178 483
Slab on Grade Area: i 5,226 (S) 1,295 273
Average Ceiling Height:...:....' €,: 11.9 Roof 5,226 27
ii;
Fenestration .Average U -Factor: 0.41 TOTAL: 1,296
Avera a SHGC� = . 0.39 Fenestration/CFA Ratio: 24.8
REM ARKS"`-= ;'' r
Lot 80 -The Hideaway
I
�g'"
1p(C
y 7
tl
f y�1 tt
y
.- 4 .....r. .....n: ... .' .........
. ...._ .:nn ... :: ....:.: :.....__ .. ......::.........
1. f.: .. ..
STATEMENT�OF COMPLIANCE
Th slcert to of compliance;i ists the building features and specifications needed
to comply with Title 24 .P�arts'1 the Administrative Regulations and Part 6 the
Efficiency Standards of'tl'e�.Cal.fornia Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
Company Scott Design and Title 24, Inc,
5/15/7013
Address 77-085 Michigan Drive Name Tim Scott
Ci /State/Zi ' Palm Desert, Ca 92211 Phone (760) 200-4780 Signed Date
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and
with any other calculations submitted with this permit application, and recognizes that compliance using duct design,
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company Fedderly and Associates
Address 38-747 Nopales Road Name Fedderly and Associates
City/State2ip Palm Desert Ca 92253 Phone (760) 773-0875 Signed License # Date
EnemvPro 5.1 by EnemySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID: Page 4 of 8
Reg: 213-N0016858C-000000000-0000 Registration'Date/Time: 2013/03/20 12:36:20 HERS Provider: CalCERTS, Inc
Electronically Filed by Tim Scott and Authenticated at Ca10ERTS.com - 5/15/2013
Electronically Signed at Ca10ERTS.com by Nicole Charon (Fedderly & Associates) 5/16/2013
CERTWICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1511512013
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Exterior Frame Interiorl Frame Azm Tilt Status 4 Location/Comments
Roof
-gAwX
1,294 0.026 R-38
270 0 New 4.2.1-A9
Master Bedroom
Wall
219 0.069 R-21
0 90 New 4.3.1-A6
Master Bedroom
Wall
184 0.069 R-21
60 90 New 4.3.1-A6
Master Bedroom
Wall
403 0.069 R-21
150 90 New 4.3.1-A6
Master Bedroom
Wall
187 0.0691R-21
330 90 New 4.3.1-A6
Master Bedroom
Slab
970 0.730 None
0 180 New 4.4.7-A 1
Master Bedroom
Slab
324 0.730 None
0 180 New 4.4.7-A1
Master Bedroom'
Roof
769 0.026 R-38
270 0 New 4.2.1-A9
Guest 1/0foe
Wall
229 0.069 R-21
0 90 New 4.3.1-A6
Guest 1/Office
Wall
55 0.069 R-21
60 90 New 4.3.1-A6
Guest i/Office
Wall
44 0.069 R-21
90 90 New 4.3.1-A6
Guest 1/Office
Wall
132 0.069 R-21
150 90 New 4.3.1-A6
Guest 1/Office
Wa11
221 0.069 R-21
240 90 New 4.3.1-A6
Guest 1/Office
Wall
215 0.069 R-21
330 90 New 4.3.1-A6
Guest 1/01fice
Slab
566 0.730 None
0 180 New 4.4.7-A1
Guest 1/0ffice
Slab
203 0.730 None
0 180 New 4.4.7-A1
Guest 1/Office
FENESTRATION SURFACE,DETAILS
ID
Type Area .' U -Factor SHGC
Azm Status Glazing Type
Location/Comments
1
Window 37.8. " 0.390 NFRC 0.39 NFRC
0 New Dual non Metal Tinted
Master Bedroom
2-_ Window 24.0 0.390 .NFRC 0.39 NFRC
0 New Dual non Metal Tinted
Master Bedroom
3
Window " +' 4.0 0.390 NFRC, 0.39 NFRC
60 New Dual non Metal Tinted
Master Bedroom
4;.
window 88.0 0.390 NFRC. 0.39 NFRC
60 New Dual non Metal Tinted
Master Bedroom
5 N Window, . 3.0 0.390 NFRC: ": 0.39_.NFRC
New�.� ,DuaLnon,MetalTinted_ _ -- .. ,Master Bedroom
6' ..'
Mf7dow':. 30 .0.390 NFRC;.; 0.39';NFRC "<`
^` f60 New ,: Dual;non A9etal:Tmted,.,
Master Bedroom
7
' lNindow 1"3.0 0:390 ,NFRC `,"A.39'NFRC :--
60 `New, Dua1non:Metal Tmtedi;- ' . _ ' Master Bedroom
8
window, 30 0; 0.390, NFRC ;- ", " .' 0.39 NFRC ';'
r " 60 New, " Dual non,iMetal:Tinted A,;
Master Bedioom - -
9
Window 1,5?0 ,10:390 NFRC 0.39 NFRC ,;
x';150 ,New `; Dual non MetafTinted : ; .
L- Master�aedrooMr, ,p .
10
Window#30:0, x".0.390'- NFRC 7 ;; 0.39! NFRC `r
' X150 Newer. '): Duals=non Metal Tinted ',
Master Bedroom
11 :: VlQndaw 1' X4.0 X0:390"NFRC - *-x-0.39 'NFRCLL ,':0 New k DuaA n MetaljTinted; ""
;,<'Gudst'110 6-"q b,
12'"
Window,.-IWndow,.-I 64 0 ':; )0"39.0, NFRC 0.39' NFRC_': ;
. 0 ,New ` =.- "Dual non MetafTinted
Guest 1/Office
13
Window _ 31.5 0.390 NFRC :: 0.39 NFRC
240 New Dual non Metal Tinted
Guest 1/Office
74.- Window " '27:0 0.390 NFRC 0.39 NFRC
240 New Dual non Metal Tinted
Guest 1/Office
15'..
Window n:: = 31'5 0.390 NFRC 0.39 NFRC
240 New Dual non Metal Tinted
Guest 1/Office
16
Window 4Q. 1,_0.390; NFRC 0.39 NFRC
240 New Dual non Metal Tinted
Guest 1/Office
(1) U -Factor Type: ;,1.16-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: P1'6-13 = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Window Ove hanq Left Fin
at Wd Len Hat LExt RExt Dist I Len
Exterior Shade Type SHGC Hc
Ri ht Fin
Hot I Dist Len H t
1
Bug Screen 0.76
2
Bug Screen 0.76
3
Bug Screen 0.76
4
Bug Screen 0.76
5
Bug Screen 0.76
6
Bug Screen 0.76
7
Bug Screen 0.76
8
Bug Screen 0.76
9
Bug Screen 0.76
10
Bug Screen 0.76
11
Bug Screen 0.76
12
Bu Screen 0.76
13
Bug Screen 0.76
14
Bug Screen 0.76
15
Bug Screen 0.76
16
IBug Screen 0.76
EnergyPro
5.1 by EnergySoft User Number: 6712 RunCode: 2013-05-15713:32:46 ID:
Page 5 of 8
Reg: 213-N0016858C-000000000-0000 Registration Date/Time: 2013/03/20 12:36:20 HERS Provider: Ca10ERTS, Inc
Electronically Filed by Tim Scott and Authenticated at CalCERTS.com - 5/15/2013
Electronically Signed at C'a10ERTS.com by Nicole Charon (Fedderly & Associates) 5/16/2013
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type O Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
5/15/2013
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Roof
2,750 0.026 R-38
270 0 New 4.2.1-A9
Living Zone
Wall
78 0.069 R-21
0 90 New 4.3.1-A6
Living Zone
Wall
348 0.069 R-21
60 90 New 4.3.1-A6
Living Zone
Wall
175 0.069 R-21
150 90 New 4.3.1-A6
Living Zone
Wall
110 0.069 R-21
180 90 1 New 4.3.1-A6
Living Zone
Door
24 0.500 None
180 90 New 4.5.1-A4
Living Zone
Wall
77 0.069 R-21
240 90 New 4.3.1-A6
Living Zone
Wall
202 0.069 R-21
270 90 New 4.3.1-A6
Living Zone
Wall
54 0.069 R-21
330 90 New 4.3.1-A6
Living Zone
Slab
266 0.730 1 None
0 180 New 4.4.7-A1
Living Zone
Slab
2,511 0.730 None
0 180 New 4.4.7-A1
Living Zone
Roof
386 0.026 R-38
270 0 New 4.2.1-A9
Guest 2
Wall
64 0.069 R-21
90 90 New 4.3.1-A6
Guest 2
Wall
178 0.069 R-21
160 90 New 4.3.1-A6
Guest 2
Wall
220 0.069 R-21
270 90 New 4.3.1-A6
Guest 2
Slabl
327 0.730 None
0 180 New 4.4.7-A 1
Guest 2
FENESTRATION SURFACE: DETAILS
ID
Type Area :0-17actor
SHGC Azm Status Glazing Type
Location/Comments
17
Window 4.0: 0.390 NERC
0.39 NFRC 240 New Dual non Metal Tinted
Guest 1/Office
18_,� Skylight 9.0 0.800 NFRC
0.39 NFRC 270 New Skylight
Living Zone
19
S li ht'* '' 9.0 0.800 ',NFRC
0.39 NFRC 270 New Skylight
Livin Zone
20.
Skylight 9.0 0.800 NFRC,
0.39 NFRC 270 New Skylight
Living Zone
2T: Window_----. 22.0 0.390 NFRC :" „0=39, NFRC..._.v 0 New...Dual:ngn Metale.Tinted,...,,_,., Living Zone
22
_L.
Window , 7' 1.80:0 0.390 'NFRC,;;; 0.39' NFRC 160 New �,, � Dual,{non Metal "Tinted,' (.
$,. Living Zone
23
lhrindow, X30:6 0 390 ,NFRC 'NFRC ; . "6Q :Naw ;4 '� Dual non; Metal `T hied'. _
� Living Zone
24
Window.' 90.0< ;0 390J NFRC
0.39 NFR_`C 60 New "� Duahnon YMetal Tinted )
Living one "-- -
25
Krindow 4,515 f0.390 ,NFRC .
;;;: 0.39 NFRC; lk,,'60 ,New ';; `. Dual norr"MetahTinted
Living;Zone,
26
Window 3.0, ;0 3901 NFRC ,
": 0.39" NFRC `°" r 60' ?New: A Dual'non Metal Tinted:
LivingrZone!. f `.
27 Windows l':.. 3.0 x;0'390; NFRC ,,
..
0 39;'NFRC x`60 New . , Duahnon Metal Tmtedw:.., '+'
L;iymg,Zone ' ., O
28'1
Window.,.. , :.35:0 ;039.0 NFRC'
':" 0.39 NFRC;, 15.o New .:' ' 'Duahnon MetahTinted:;
living Zone
29
Window " 23.1 0.390 NFRC
0:39 NFRC 150 New Dual non Metal Tinted
Livin Zone
x'30.- Window x.3.0 0.390 NFRC
0.39 NFRC 150 New Dual non Metal Tinted
Living Zone
31
:: Window 3:0 0.390 'NFRC
0.39 NFRC 150 New Dual non Metal Tinted
Living Zone
32
Window `3:0; 'x. 0.390, NFRC
0.39 NFRC 150 New Dual non Metal Tinted
Living Zone
(1) LI -Factor Type: `Q----` ] 16-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: ".f:16,B =: D'efauft Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window Ove hanq Left Fin
H t Wd Len H t LExt RExt Dist Len
Ri ht Fin
H t Dist Len H t
17
Bug Screen 0.76
18
None 1.00
19
None 1.00
20
None 1.00
21
Bug Screen 0.76
22
Bug Screen 0.76
10.0 18.0 22.01 0.1 22.0 22.0
23
Bug Screen 0.76
6.5 4.7 18.0 0.1 18.0 18.0
24
Bug Screen 0.76
10.0 9.0 14.0 0.1 14.0 14.0
25
Bug Screen 0.76
26
Bug Screen 0.76
27
Bug Screen 0.76
28
Bug Screen 0.76
29
Bug Screen 0.76
30
Bug Screen 0.76
31
JBug Screen 0.76
32
JBug Screen 0.76
EnargyPro
5.1 by EnergySoft User Number: 6712 RunCode: 2013-05-15T13:32:46 ID:
Page 6 of 8
Reg: 213-N0016858C-000000000-0000 Registration Date/Time: 2013/03/20 12:36:20 HERS Provider: CalCERTS, Inc
Electronically Filed by Tim Scott and Authenticated at Ca10ERTS.com - 5/15/2013
Electronically Signed at CalCERTS.com by Nicole Charon (Fedderly & Associates) 5/16/2013
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Clearwater/Sparks Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1511512013
OPAQUE SURFACE DETAILS
Surface U- Insulation -Joint Appendix
Type Area Factor Cavity Exterior Frame Interiorl Frame Azm Tilt Status 4 Location/Comments
Slab 59 0.730 None 0 180 New 4.4.7-A1 Guest 2
FENESTRATION SURFACE DETAILS
ID Type Area U -Factor SHGC Azm Status Glazing Type Location/Comments
33 Window 90.0.: 0.390 NFRC 0.39 1 NFRC 180 New Dual non Metal Tinted Living Zone
34::; Window 2.3 0.390 NFRC 0.39 NFRC 180 New Dual non Metal Tinted Living Zone
35 Wiridd1ty + 2.3 0.390 ',NFRC 0.39 NFRC 180 New Dual non Metal Tinted Living Zone
36 Window 2.3 0.390 NFRC. 0.39 NFRC 180 New Dual non Metal Tinted Living Zone
37:N lMndow, 85.5.0.390 NFRC' : _0:39. NFRC._._... _ .__2_4,0 New. ,,-,--.Dual RQn Metal_Tinted,-._Living Zone
_.
38... Window' ,' /3:0 0.390 'NFRC':',, "0.39';NFRG . 240 New : a Duafnon MetarTinted S ,'Living Zone
39 = Vtrindow :: 3.0 0:390 NFRC . _ 0:39 'NFRC :..:. 240 'New; f "� Living Zone
A Dual rion.Metal Tinted;,
46 endow: 61.2; ;;0.390 NFRC.-' " r`.' 0.39 NFRC . .276 New 'Dual nonYMetal,Tinted X. Living Zone
41 Window 3.1:x5 0.390 .NFRC 0.39 NFRC=".. . 330 ,New Dual non Metat7inted ;,tib Livirig,Zone,
42 ,Window ; 36:0, a "1.040 ,NFRC -;1 0.30;' NFRC.-;,, .. ;430: eNaw. 'J Custom Door f t ) Living Zone ` pl;
e1,`",
43 ;' Window f° 43.2' ; 0.390 NF_RCa' ' X0.39 NFRC_ X330 New; ` Dual°non Metal Tinted ; Lwing_ZoniC3
44r? Window, ,...:.,; ..64:0 0:390 NFRC' ' `'` 0.39' NFRC.:; ".:1:80, New .: 'Dual-non"Metaf Tinted.: ,, : Guest 2
_.
`3
(1) U -Factor Type: =: -:11.6 A = Default Table from Standards, NFRC =Labeled Value
2 SHGC Type: `:146-B=,Defauh Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
Window Ove hanq Left Fin Ri ht Fin
ID Exterior Shade Type SHGC Hat I Wd Len Hat LExt I RExt Dist Len Hat Dist Len I Hat
33 Bug Screen 0.76
34 Bug Screen 0.76
35 Bug Screen 0.76
36 Bug Screen 0.76
37 Bug Screen 0.76
38 Bug Screen 0.76
39 Bug Screen 0.76
40 Bug Screen 0.76
41 Bug Screen 0.76
42 jBug Screen 0.76
43 Bug Screen 0.76
44 Bug Screen 0.76
EnemyPfo 5.1 by EnefgySoft User Number., 6712 RunCode: 2013-05-15T13:32:46 /D: Pae 7 of 8
Reg: 213-N0016858C-000000000-0000 Registration Date/Time: 2013/03/20 12:36:20 HERS Provider: CalCERTS, Inc
Electronically Filed by Tim Scott andAuthenticated at CalCERTS.com - 5/15/2013
'Bl�_ctronically Signed at CalCERTS.com by Nicole Charon (Fedderly & Associates) 5/16/2013
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5 CF -1 R
Project NameType
ClearwaterlSparks Residence
Building ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
5/15/2013
BUILDING ZONE INFORMATION
Floor Area
System Name Zone Name New Existinq Altered Removed Volume Year Built
HVAC 1 Master Bedroom 1,294 16,304
HVAC 2 Guest 1/ Office 769 8,151
HVAC 3 & 4 GreaWitchen/Dining/Gallery 2,777 33,602
Guest 2 386 4,246
Totals 5,226o 0 0
HVAC SYSTEMS
- ` Heating Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status
HVAC 1 "- 1 lk Central Furnace 80%AFUE Split Air Conditioner 16.5 SEER Setback New
HVAC 2 1 `! ,Central Furnace 80% AFUE Split Air Conditioner 16.5 SEER Setback New
v
HVAC 3 8 4 -, ,; 2 Central;Fumace ; r80.%AFUE SplitAit Conditioner 16°5 SEER„ Sefback_,,:. New
� R S t �. f.' �;�f �@v,,;, ?'3"i
1 )I
d3."'y .,yif. s'�..;}f{�'� , _ r�s R;" ,I,�'..:. '.' �'�✓..:�t� ..:.'.*4 -.�, ; :.: .�ib'Y' ...
'. ""1171 . ' a ae..d�(€:i�'?"'l:t ,'
HVACDI$TRIBUTI O.N<�� An,::ARW
t - '> 1Duct '/ DiictsC;
S'stem::Name , Heating Coolin ._: .. Duct.L - Aon.... R..Value Tested? Status
.::
HVAC 1 Ducted Ducted Attic, Ceiling Ins, vented 8.0 m New
HVAC 2,',-': Ducted ti _' Ducted Attic, Ceiling Ins, vented 8.0 m New
HVA: ¢ Ducted (` Ducted Attic, Ceiling Ins, vented 8.0 d New
i..�_ ❑
WATER HEATING SYSTEM5t
S stem Name
at .
TvDe
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
Lochinvar #SNR126-065
1
Large Gas
All Pipes Ins
126,000
65
0.96
0.00 %
0.0
New
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING
SYSTEM
PIPING
Control
Hot Water Piping Length'
ft
C
0
76
v
a c
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
Qty.THP
Plenum Outside Buried
EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2013-05-15713:32:46 ID: Page 8 of 8
Reg: 213-N0016858C-000000000-0000 Registration Date/Time: 2013/03/20 12:36:20 HERS Provider: Ca10ERTS', Inc