BRES2014-1097 Title 24COPy BUILDING ENERGY ANALYSIS REPORT
\. 1
PROJECT:
Mattison Floyd Residence
53-005 Latrobe Lane
La Quinta, CA 92253
Project Designer:
JMA Architecture and Engineering
73-995 EI Paseo Suite 203
Palm Desert, CA 92260
(760) 346-6155
Job Number:RECOMVED
OCT 202014
CM OF LA ZUINTA
Date: COMMUHrrY DEVELOPMfIff,"
4
10/3/2014
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
• authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
? This program developed by EnergySoft, LLC — www.energysoft.com.
�--• -
tnergyPro 6.3 by Ene Sof User Number: 6712 ID:
Report Prepared by:
Jon Scott
Scott Design and Title 24,,
77-085 Michigan Driv CITY OF LA QUINTA
Palm Desert, CA 9221 BUILDING & SAFETY DEPT.
(760) 200-4780 APPROVE D
FOR CONSTRUCTION
DA 2) BY
•
Job Number:RECOMVED
OCT 202014
CM OF LA ZUINTA
Date: COMMUHrrY DEVELOPMfIff,"
4
10/3/2014
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
• authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
? This program developed by EnergySoft, LLC — www.energysoft.com.
�--• -
tnergyPro 6.3 by Ene Sof User Number: 6712 ID:
CERTIFOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD.
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Mattison Floyd-JMA-14.xml
CF*F-0f
Page 1 of 13
ra
GENERAL INFORMATION
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing ancl//or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features shown below
01
Project Name Mattison Floyd Residence
05
06
07
02
Calculation Description Title 24 Analysis
Standard7'
Des gn
Proposed
Design
Compliance
Margin
03
'Project Location 53-005 Latrobe Lane
�6 07
6.46
-0.39
04
A City La Quinta
05
Standards Version Compliance 2015
06
Zip code 92253
07
Compliance Manager Version
BEMCmpMgr 2013-3 (650)
08
Climate Zone CZ15
09
Software Version
EnergyPro 6.3
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 15
12
Project Scope Newly Constructed
13 R5*
Number of Dwelling Units
1
• 14
Total Cond. Floor Area (FT2) 5230
15 A
Number of Zones
4
16
Slab Area (FT2) 5230
17
Number of Stories
1
18
Addition Cond. Floor Area NA
*19'9'`
Natural Gas Available
Yes
20
Addition Slab Area (FT2) NA
# 2�1
Glazing Percentage (%)
28.7%
AW
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing ancl//or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features shown below
.49ENERGY USE SUMMARY
04
05
06
07
08
Energy Use
(kTDV/ft)
Standard7'
Des gn
Proposed
Design
Compliance
Margin
Percent
Improvement
Space Heating
�6 07
6.46
-0.39
-6.4%
Space Cooling
OM1,36.40
110.44
25.96
19.0%
IAQ Ventilation
1.28
1.28
0.00
0.0%
Water Heating
4.91
4.27
0.64
13.0%
Photovoltaic Offset
`r --
0.00
0.00
--
Compliance Energy Total
148.66
122.45
26.21
17.6%
.®�9
Registration Number: ,��
CA Building Energy Efficiency Standards�- 2013 Residential Compliance
------------
CITY OF LA QUINTA
BUILDING & SAFETY U EpT.
APPROVED
FOR CONSTRUCTION
Registration Date/Time: I pA-jE BY HERS
Report Version - CF1R-09042014-6v — —'—Re
erated at: 2014-10-03 09:53:12
CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OOD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Ducts with high level of insulation
• Cathedral Ceiling
• Window overhangs and/or fins
PROJECT HERS FEATURES
CF* F-011`
Page 2 of 13
The following are project -level features that must be field -verified as a condition for meeting the modeled energy performance for this computer analysis. These, plus any additional HERS features listed
in the building components tables below, requre field verification by a certified HERS Rater.
• IAQ mechanical ventilation w
ENERGY DESIGN RATING sc�
This is the sum of the annual TDV energy consumption for energy use components included in the perfor�m_"`nce compliance approach for the Standard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and components not regulated by Title 24, Part 6 (such as domestic,appliances and consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system. 4S.O
Reference Energy Use Energy Design Rating MarginPercent Improvement
Total Energy (kTDV/f2)` 185.46 159.25 26.21 14.1%
• includes calculated Appliances and Miscellaneous Energy Use (AMEU)
—Zi
BUILDING - FEATURES INFORMATION
01
02
03
04
05
06
07
Project Name
Conditioned Floor Area (sft)
Number of Dwelling
Uwmtt ,
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Mattison Floyd Residence
5230
1
12
4
4
1
.A
ZONE INFORMATION �v
01
02
03
04
05
06
07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1
Water Heating System 2
Kitchen Living Entry
Conditioned
HVAC 1 kit liv entyl
1564
18
DHW Sys 1
Living Exiercise
Conditioned
HVAC 2 liv exr2
940
18
DHW Sys 1
Master bedroom
Conditioned
HVAC 3 master3
1596
18
DHW Sys 1
Casita
Conditioned
HVAC 4 castia4
1130
18
DHW Sys 1
Registration Number:
CA Building Energy Efficiency Stands - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIFJOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE JOD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Mattison Floyd-JMA-14.xml
CF*F-01"
Page 3 of 13
-j
OPAQUE SURFACES
01
02
03
04
05
06
07
08
Name
Zone
Construction
Azimuth
Orientation
Gross Area (ft2)
Window Area (ft2)
Tilt(deg)
15d Wall
Kitchen Living Entry
R-21 Wall (W21.2x6.16)
15
Front
940
182.5
90
105d Wall
Kitchen Living Entry
R-21 Wall (W.21.2x6.16)
105
Left
1220
229
90
195d Wall
Kitchen Living Entry
R-21 Wall (W.21.2x6.16)
195
Back
1188
255
90
285d Wall
Kitchen Living Entry
R-21 Wall (W.21.2x6.16)
28
- specify -
626
65
90
Roof 4
Kitchen Living Entry
R-38 Roof Attic
1532
15d Wall
Living Exiercise
R-21 Wall (W21.2x6.16)
`'b15
Front
560
0
90
60d Wall
Living Exiercise
R-21 Wall (W.21.2x6.16)
�� 60
- specify -
120
25.5
90
105d Wall 2
Living Exiercise
R-21 Wall (W.21.2x6.16) r.� 105
Left
840
200.1
90 y
150d Wall
Living Exiercise
R-21 Wall (W.21.2x6.16)�
150
- specify -
120
22.5
90 j
195d Wall 2
Living Exiercise
R-21 Wall (W21.2x6.ay6)�
195
Back
230
0
90
285d Wall 2
Living Exiercise
R-21 Wall (W.21.4x6'61"6)
28
- specify -
230
0
90
Roof 5
Living Exiercise
R-38 RooftAttic
936.8
15d Wall 3
Master bedroom
R-21 Wall (y 21 2x6.16)
15
Front
320
0
90 t
105d Wall 3
Master bedroom
R-21 Wall (W 21.2x6.16)
105
Left
320
0
90 p
150d Wall 2
Master bedroom
R-21 Wall'(W.21.2x6.16)
150
- specify -
120
22.5
90
195d Wall 3
Master bedroom
R-,11�1Nall (W21.2x6.16)
195
Back
460
97.5
90
240d Wall
Master bedroom
R 21'Wall (W.21.2x6.16)
240
- specify -
120
25.5
90
285d Wall 3
Master bedroom A%R-21 Wall (W21.2x6.16)
28
- specify -
1500
99.6
90
Roof 6
Master bedroom
R-38 Roof Attic
1596
15d Wall 4
Casita
R-21 Wall (W21.2x6.16)
15
Front
640
50.8
90
60d Wall 2
Casita 0
R-21 Wall (W.21.2x6.16)
60
specify -
400
27
90
105d Wall 4
Casita %%
R-21 Wall (W21.2x6.16)
105
Left
880
40.5
90
150d Wall 3
Casita
R-21 Wall (W.21.2x6.16)
150
specify -
120
0
90
195d Wall
Casita& v
R-21 Wall (W21.2x6.16)
195
Back
640
33.5
90
240d Wall 2
Cas�aaV
R-21 Wall (W.21.2x6.16)
240
specify -
240
24
90
285d Wall 4
^Casita
R-21 Wall (W21.2x6.16)
28
- specify -
880
64
90
Roof 7
Gasita
R-38 Roof Attic
1127.6
Registration Number:
CA Building Energy Efficiency Stands - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF111-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE IOD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml
CF*F-01`
Page 4 of 13
OPAQUE SURFACES — Cathedral Ceilings
01
02
03
04
05
06
07
08
09
10
11
Name
Zone
Type
Orientation
Area (ft2)
Roof Rise
(x in 12)
Roof
Pitch
Roof Tilt
(deg)
Roof
Reflectance
Roof
Emmittance
Framing
Factor
Roof
Kitchen Living Entry
R-38 Roof Attic1
specify -
32.1
3
0.25
14.04
0.1
0.85
0.1
Roof 2
Living Exiercise
R-38 Roof Attic1
- specify -
1 3.3
3
0.25
14.04
0.1
0.85
0.1
Roof 3
Casita
R-38 Roof Attic1
specify -
2.5
3
0.25
14.04
0.1
0.85
0.1
ATTIC
A
01 02 03 04'1 '05 06 07
Name Construction Roof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic Attic Roof Cons 3 %W0.1 0.85 Yes No
�®err
X41
Registration Number: p�►® Registration Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE I,OD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Mattison Floyd-JMA-14.xml
CF*F-01"'
Page 5 of 13
WINDOWS
01
02
03
04
05
06
07
08
09 10
Name
Type
Surface (Orientation -Azimuth)
Width(ft
)
Height
(ft)
Multiplier
Area
(ft)
U -factor
SHGC Exterior Shading
NEW A
Window
15d Wall (Front -15)
--
-
1
20.0
0.28
0.18
NEW 1
Window
15d Wall (Front -15)
-
-
1
40.0
0.28
0.18
NEW B
Window
15d Wall (Front -15)
-
--
1
20.0
0.28
0.18
NEW C
Window
15d Wall (Front -15)
--
--
1
22.5
0.28
0.18
NEW E
Window
15d Wall (Front -15)
--
�--
1
16.0
0.28
0.18
NEW 2
Window
15d Wall (Front -15)
---
1
48.0 1
0.28
0.18
NEW F
Window
15d Wall (Front -15)
1
16.0
0.28
0.18
NEW X
Window
105d Wall (Left -105)
A,�=�
--
1
3.0
0.28
0.18
NEW X 2
Window
105d Wall (Left -105)
1
3.0
0.28
0.18
NEW X 3
Window
105d Wall (1 -eft -105) r�--
--
1
3.0
0.28
0.18
NEW 11
Window
105d Wall (Left -105) M `'�
-
--
1
20.0
0.28
0.18
NEW 12
Window
105d Wall (Left -105) Q�
-
--
1
24.0
0.28
0.18
NEW 13
Window
105d Wall (Left -105)
16.0
11.0
1
176.0
0.24
0.18
NEW Z
Window
195d Wall (Back -195) #10
-
-
1
48.0
0.28
0.18
NEW 14
Window
195d Wall (Back -195)
17.0
11.0
1
187.0
0.24
0.18
NEW 2A
Window
195d Wall (Back -195)0
--
--
1
5.0
0.28
0.18
NEW 2A 2
Window
195d Wall (Back 95)
-
--
1
5.0
0.28
0.18
NEW 2A 3
Window
195d Wall (Baclv�195)
--
--
1
5.0
0.28
0.18
NEW 2A 4
Window
195d Wall (I ack-195)
-
--
1
5.0
0.28
0.18
NEW
Window
285d Walspecify -28)
-
--
1
65.0
0.28
0.18
Skylight
Skylight
Roof( pecify -285)
1
32.0
0.46
0.53
NEW 2R
Window
606"Wall (- specify --60)
-
--
1
25.5
0.28
0.18
NEW 2S
Window
f05d Wall 2 (Left -105)
--
--
1
59.5
0.28
0.18
NEW 2U
Window
%V105d Wall 2 (Left -105)
-
--
1
59.2
0.28
0.18
NEW 2V
Window
��' 105d Wall 2 (Left -105)
-
-
1
22.2
0.28
0.18
NEW 2W
Window
�`� 105d Wall 2 (Left -105)
-
--
1
59.2
0.28
0.18
NEW 2T
Window`'1
150d Wall (- specify --150)
--
--
1
22.5
0.28
0.18
Skylight 2
Skylight
iQ� Roof 2 (- specify --285)
1
1.6
0.30
0.30
Skylight 3
Skylight
Roof 2 (- specify --285)
1
1.6 1
0.30
0.30
#4114�
Registration Number: ��
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIF•E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Mattison Floyd-JMA-14.xml
CF*F-01`
Page 6 of 13
NEW 2B
Window
150d Wall 2 (- specify -150)
-- --
1
22.5
0.28
0.18
NEW 2C
Window
195d Wall 3 (Back -195)
-- --
1
25.5
0.28
0.18
NEW 2E
Window
195d Wall 3 (Back -195)
- --
1
12.0
0.28
0.18
NEW 15
Window
195d Wall 3 (Back -195)
-- --
1
48.0
0.28
0.18
NEW 2F
Window
195d Wall 3 (Back -195)
-- --
1
12.0
0.28
0.18
NEW 2D
Window
240d Wall (- specify --240)
-- --
1
25.5
0.28
0.18
NEW 2H
Window
285d Wall 3 ( specify -28)
-- --
1
13.8
0.28
0.18
NEW 2J
Window
285d Wall 3 (- specify -28)
-- --
1
13.8
0.28
0.18
NEW 2K
Window
285d Wall 3 (- specify -28)
-- -
1
6.0
0.28
0.18
NEW 2L
Window
285d Wall 3 (- specify -28)
-- ^f --
1
30.0
0.28
0.18
NEW 16
Window
285d Wall 3 (- specify -28)
1
20.0
0.28
0.18
NEW 2M
Window
285d Wall 3 (- specify -28)
--
1
6.0
0.28
0.18
NEW 2N
Window
285d Wall 3 (- specify -28)--
--
1
10.0
0.28
0.18
NEW K
Window
15d Wall 4 (Front -15) Al
,r -- --
1
19.3
0.28
0.18
NEW L
Window
15d Wall 4 (Front -15)`
1
4.5
0.28
0.18
NEW M
Window
15d Wall 4 (Front -15) Ov
- -
1
4.5
0.28
0.18
NEW P
Window
15d Wall 4 (Front -15) �
- --
1
22.5
0.28
0.18
NEW N
Window
60d Wall 2 (- specify -60)
1
4.5
0.28
0.18
NEW Q
Window
60d Wall 2 (- specify -60?D
-- --
1
22.5
0.28
0.18
NEW R
Window
105d Wall 4 (Left -106 v*
-- --
1
22.5
0.28
0.18
NEW S
Window
105d Wall 4 (Left;05)
-- --
1
3.0
0.28
0.18
NEW T
Window
105d Wall 4 ( e0105)
-- --
1
3.0
0.28
0.18
NEWT 2
Window
105d Wall(Lfeft-105)
-- --
1
3.0
0.28
0.18
NEWT 3
Window
105d WKII-4' (Left -105)
-- --
1
3.0
0.28
0.18
NEW U
Window
105dJWall 4 (Left -105)
-- --
1
3.0
0.28
0.18
NEW V
Window
105d.Wall 4 (Left -105)
-- --
1
3.0
0.28
0.18
NEW W
Window
�195d Wall 4 (Back -195)
-- --
1
6.0
0.28
0.18
NEW J
Window
195d Wall 4 (Back -195)
- --
1
27.5
0.28
0.18
NEW 4
Window
* 1W40d Wall 2 (- specify -240)
-- --
1
24.0
0.28
0.18
NEW G
Window
�� 285d Wall 4 (- specify -28)
-- --
1
12.0
0.28
0.18
NEW 3
Window`'
285d Wall 4 (-specify -28)
-- --
1
40.0
0.28
0.18
NEW H
Window
, ��'' 285d Wall 4 (- specify -28)
-- --
1
12.0
0.28
0.18
Skylight 4
Skylight
j,i Roof 3 (- specify --285)
1
1.2
0.30
0.30
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF111-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE IOD
Project Name: Mattison Floyd Residence Ca culation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input.File Name: Mattison Floyd-JMA-14.xml
Skylight 5 1 Skylight I Roof 3 (- specify –285) 1 1 1 1 1 1.2 1 0.30 1 0.30
CF*F-01-
Page 7 of -13
DOORS
01 02 03 04
Name Side of Building Area (ft2) U -factor
Door 45 15d Wall 2 28.0 0.50
OVERHANGS AND FINS
01 -
- --02 --- –
03
�� 04
05
06
Construction Name
Surface Type
Construction Type
`'� Framing
01
02
03
04
05
06
07-
08 09
10
11
12 13
14
Cavity/Frame: no insul. /2x4 Top Chrd
Overhang
Roof Truss @ 24 in.
Left Fin
Attic Roof Cons
Attic Roofs
Right Fin
O.C.
Window
Depth
Dist Up
Left
Extent
Right
Extent
Flap Ht.
��+!�+�+
Cliepth
Top Up DistL
Bot Up
Depth
Top Up Dist R
Bot Up
NEW 13
12
0.1
12
12
0 'j
;ll- 0
0 0
0
O.
G 0
0
NEW 14
12
0.1
12
12
0oi
0
0 0
0
0
0 0
0
.#W
OPAQUE SURFACE CONSTRUCTIONS►v
01 -
- --02 --- –
03
�� 04
05
06
Construction Name
Surface Type
Construction Type
`'� Framing
Total Cavity R -value
Assembly Layers
2x4 Top Chord of
Cavity/Frame: no insul. /2x4 Top Chrd
Roof Truss @ 24 in.
Roof Deck: Wood Siding/sheathing/decking
Attic Roof Cons
Attic Roofs
Wood Framed Ceiling
O.C.
none
Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
Cavity/Frame: R-9.1 /2x4
R-38 Roof Attic
Ceilings (below attic)
Wood FraiQ"d:Ceiling
2x4 @ 16 in. O.C.
R 38
Over Floor Joists: R-28.9 insul.
Inside Finish: Gypsum Board
• Cavity /Frame: R-38 / 2x4
A
Roof Deck: Wood Siding/sheathing/decking
R-38 Roof Atticl
Cathedral Ceilings
W Framed Ceiling
2x4 @ 16 in. O.C.
R 38
Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
O
• Cavity/Frame: R-21 /2x6
R-21 Wall (W.21.2x6.16)
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
Exterior Finish: Wood Siding/sheathing/decking
.may
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIF40E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Mattison Floyd-JMA-14.xml
CF*F-01`
Page 8 of 13
OPAQUE SURFACES— Cathedral Ceilings
01
02
03
04
05
06
07
08
09
10
11
Name
Zone
Type
Orientation
Area (ft)
Roof Rise
(x in 12)
Roof
Pitch
Roof Tilt
(deg)
Roof
Reflectance
Roof
Emmittance
Framing
Factor
Roof
Kitchen Living Entry
R-38 Roof Attic1
- specify -
32.1
3
0.25
14.04
0.1
0.85
0.1
Roof 2
Living Exiercise
R-38 Roof Attic1
- specify -
3.3
3
0.25
14.04
0.1
0.85
0.1
Roof 3
Casita
R-38 Roof Attic1
- specify -
2.5
3
0.25
14.04
0.1
0.85
0.1
SLAB FLOORS
01
01
02 03 04
Quality Insulation Installation (QII)
Quality Installation of Sp�ray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa
Not Required
01
02
03
JV04
05
06
07
Name
Zone
Area (ft2)
Perimeter (ft)
Edge Insul. R-value&_Depth
Carpeted Fraction
Heated
Covered Slab
Kitchen Living Entry
1564
y 270
None
0.8
No
Covered Slab 2
Living Exiercise
940
A��' 90
None
0.8
No
Covered Slab 3
- Master bedroom
1596
0% 115
None
0.8
No
Covered Slab 4
. Casita
11301.
V 1 185
None
0.8
No
BUILDING ENVELOPE - HERS VERIFICATION
01
01
02 03 04
Quality Insulation Installation (QII)
Quality Installation of Sp�ray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa
Not Required
Not Re}q fired Not Required --
fK
WATER HEATING SYSTEMS
01 �`'� 02 03 04
Name '01C�''Distribution Type Number of Heaters Solar Fraction (%)
DHW Sys 1 Ov Pipe Insulation, All Lines 1 0.0%
WATER HEATERS
01
02 03
04
05
06
07
08
Tank Volume
Energy Factor or
Tank Exterior
Standby Loss
Name
Heater Element T.y,pe Tank Type
(gal)
Efficiency
Input Rating
Insulation R -value
(Fraction)
DHW Heater 1
Natural.Ga`'ssO Small Storage
50
0.66
40000-Btu/hr
0
0
'ey
Registration Number:
CA Building Energy Efficiency Stan`da ds - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE JOD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Mattison Floyd-JMA-14.xml
CF*F-01-
Page 9 of 13
WATER HEATING - HERS VERIFICATION
01
02
03
04
05
06
07
Name
Pipe Insulation
Parallel Piping
Compact Distribution
Point -of Use
Recirculation with
Manual Control
Recirculation with
Sensor Control
DHW Sys 1-hers-dhw
n/a
n/a
n/a
n/a
80 AFUE
n/a
HVAC SYSTEMS
01
02
03
04
05
06
07
Efficiency
Heating Component 1
Heating System
Cooling System
Heating Component 2`
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 3
y ®` CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 4
Distribution
80 AFUE
Floor Area
Name
System Type
Name DucteB,
Name Ducted
System
Fan System
Served
HVAC 1 kit liv entyl
Other Heating and Cooling System
Heating Component 1
es
�
Component 1 Cooling
Yes
Air Distribution
System 1
HVAC Fan 1
1564
HVAC 2 liv exr2
Other Heating and Cooling System
Heating Component 2
�Yes
Cooling
Component 2
Yes
Air Distribution
System 2
HVAC Fan 2
940
HVAC 3 master3
Other Heating and Cooling System
Heating Componen�f3-
Yes
Cooling
Yes
Air Distribution
HVAC Fan 3
1596
Component 3
System 3
HVAC 4 castia4
Other Heating and Cooling System
Heating Component 4
Yes
CCooling omponent 4
Yes
System 4 Air Distribution
HVAC Fan 4
1130
f
01
HVAC - HEATING SYSTEMS
01
�`�'� 02
03
Name
��� Type
Efficiency
Heating Component 1
� CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 2`
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 3
y ®` CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 4
A. t �'# CntrlFurnace - Fuel -fired central furnace
80 AFUE
O�
'ems
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIF-0 OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE AOD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Mattison Floyd-JMA-14.xmi
CF*F-01-
Page 10 of 13
HVAC - COOLING SYSTEMS
01
02
03 04
05
06
07
Name
Verified Airflow
Efficiency
Verified EER
Multi -speed
Verified Refrigerant
Charge
Name
System Type
EER SEER
Zonally Controlled
Compressor
HERS Verification
Cooling Component 1
SplitAirCond - Split air conditioning
13
16.5
No
No
Cooling Component
Required
system
Required
Required
Required
Cooling Component 4 -hers -cool
1 -hers -cool
Cooling Component 2
SplitAirCond - Split air conditioning
13
16.5
No
No
Cooling Component
System 1 -hers -dist
system
Ducts located entirely in
2 -hers -cool
Cooling Component 3
SplitAirCond - Split air conditioning
13
16.5
No
No
Cooling Component
Conditioned Zone
system
System 2 -hers -dist
%I
Ducts located entirely in
3 -hers -cool
Cooling Component 4
SplitAirCond -Split air conditioning
13
16I
No
No
Cooling Component
8
system
Conditioned Zone
r
System 3 -hers -dist
Air Distribution System 4
4 -hers -cool
HVAC COOLING - HERS VERIFICATION
01
02
03 —
04
05
06
Name
Verified Airflow
2w
Airflowjlget
Verified EER
Verified SEER
Verified Refrigerant
Charge
Cooling Component 1 -hers -cool
Required
^350
Required
Required
Required
Cooling Component 2 -hers -cool
Required
`x350
Required
Required
Required
Cooling Component 3 -hers -cool
Required
350
Required
Required
Required
Cooling Component 4 -hers -cool
Required
�� 350
Required
Required
Required
HVAC - DISTRIBUTION SYSTEMS
01
02
03``'1
04
05
06
07
08
A`�
Supply Duct
Name
Type
Duct`Lre_akage
Insulation R -value
Location
Return Duct
Bypass Duct
HERS Verification
Air Distribution System 1
Ducts located entirely in
.�
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
conditioned space
A.
System 1 -hers -dist
Ducts located entirely in
Air Distribution
Air Distribution System 2
conditioned space _
Q'S aled and tested
8
Conditioned Zone
Conditioned Zone
None
System 2 -hers -dist
Ducts located entirely in
Air Distribution
Air Distribution System 3
A;
conditioned space �
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
System 3 -hers -dist
Air Distribution System 4
Ducts located entirely i6
Sealed and tested
8
Conditioned Zone
Conditioned Zone
None
Air Distribution
conditioned sp;i`'*
System 4 -hers -dist
.0
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Mattison Floyd-JMA-14.xml
CF*F-01-
Page 11 of 13
HVAC DISTRIBUTION - HERS VERIFICATION
01
02
03
04
05 06
Name
Duct Leakage Verification
Duct Leakage Target (%)
Verified Duct Location
Verified Duct Design
Return Supply
Air Distribution System 1 -hers -dist
Required
6.0
Not Required
Not Required Not Required
Air Distribution System 2 -hers -dist
Required
6.0
Not Required
Not Required Not Required
Air Distribution System 3 -hers -dist
Required
6.0
Not Required
Not Required Not Required
Air Distribution System 4 -hers -dist
Required
6.0
Not Required
Not Required Not Required
HVAC -FAN SYSTEMS
co
020`"
_
01
02 ,ll�
03
04 .
Name
Type ��►"
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
Required
HVAC Fan 2
Single Speed PSC Furnace Fan Q�.Y
0.58
Required
HVAC Fan 3
Single Speed PSC Furnace Fang
0.58
Required
HVAC Fan 4
Single Speed PSC Furnaceiran
_ 0.58
Required
HVAC FAN SYSTEMS - HERS VERIFICATION
co
020`"
_
01
l
02
03
Name
`W
VerifiedFanWatt Draw
Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan
S*
Required
0.58
HVAC Fan 2 -hers -fan
A'4�
Required
0.58
HVAC Fan 3 -hers -fan
—�v
Required
0.58
HVAC Fan 4 -hers -fan
4t�
Required
0.58
,p �40
IAQ (Indoor Air Quality) FANS A* *40
01
020`"
03
04
05
06
IAQ Recovery
Name
IAQ CFM
IAQ Watts/CFM
IAQ Fan Type
Effectiveness(%)
HERS Verification
SFam IAQVentRpt
149.8'r
0.25
Default
0
Required
Registration Number:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xm1
CF — F -01 -
Page 12 of 13
COOLING VENTILATION
01
02
03
04
05
Name
Cooling Vent CFM
Cooling Vent Watts/CFM
Number of Fans
HERS Verification
WH Fan 1
61
0.52459
1
Required
WH Fan 2
61
0.52459
1
Required
WH Fan 3
61
0.52459
1
Required
WH Fan 4
61,'
0.52459
1
Required
Registration Number: i® Registration Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE i *OD
Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Mattison Floyd-JMA-14.xml
CF*F-01-
Page 13 of 13
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Jon Scott
Documentation Author Sign
Company:
Signature Date:
Scott Design and Title 24, Inc,
10/3/2014
Address:
CEA/HERS Certification Identification (If applicable):
77-085 Michigan Drive
City/State:
Palm Desert, CA 92211
Phone: %1-
(7 0) 200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT�/-
I certify the following under penalty of perjury, under the laws of the State of California: .�
l�
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
1 Title Part
2. certify that the energy features and performance specifications identified on this Certificate, fj'C=ompliance conform to the requirements f 24, Part 1 and 6 of the California Code of
Regulations. vV
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the informatio pro ded on other applicable. compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency-Ywfo� approval with this building permit applic_ tion.
Responsible Designer Name:
Responsible Designer Signature:
JMA Architecture and Engineering .�I�
AI V
Company: W
Date Signed:
JMA Architecture and Engineering
Address: 4%—
License:
73-995 EI Paseo Suite 203 44�,�ZG%
City/State/Zip:
Phone:
Palm Desert, CA 92260 ,��
(760) 346-6155
14F
.,490
Registration Number: t�
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09042014-650
HERS Provider:
Report Generated at: 2014-10-03 09:53:12
L'
•
•
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Mattison Floyd Residence
Building Type
10 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
10/3/2014
Project Address
53-005 Latrobe Lane La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,230
Addition
n/a
# of Units
4
INSULATION
Construction Type
Cavity
Area
ftz) Special Features Status
Roof Wood Framed Attic
R38
5,192
New
Wall Wood Framed
R 21
11,222
New
Slab Unheated Slab -on -Grade
- no insulation
5,230 Perim = 660'
New
Demising Wood Framed
R 13
4,440
New
Door Opaque Door
no insulation
28
New
FENESTRATION
Orientation Area ft2
Total Area: 1,502 Glazin Percentage: 28.7%1New/Altered
U -Fac SHGC Overhang Sidefins
Average U -Factor: 0.27
Exterior Shades Status
Skylight 32.0
0.460
0.53 none
none
None New
Front (N) 233.3
0.280
0.18 none
none
Bug Screen New
Left (E) 293.6
0.280
0.18 none
none
Bug Screen New
Left (E) 176.0
0.240
0.18 12.0,
none
Bug Screen New
Rear (S) 199.0
0.280
0.18 none
none
Bug Screen New
Rear (S) 187.0
0.240
0.18 12.0
none
Bug Screen New
Front (NE) 228.6
0.280
0.18 none
none
Bug Screen New
Skylight 1.6
0.300
0.30 none
none
None New
Skylight 1.6
0.300
0.30 none
none
None New
Front (NE) 52.5
0.280
0.18 none
none
Bug Screen New
Left (SE) 45.0
0.280
0.18 none
none
Bug Screen New
Rear (SVIO 49.5
0.280
0.18 none
none
Bug Screen New
Skylight 1.2
0.300
0.30 none
none
None New
Skylight 1.2
0.300
0.30 none
none
None New
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling
Min. Eff
Thermostat Status
1 Central Furnace
80% AFUE
Split Air Conditioner 16.5 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner 16.5 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner 16.5 SEER
Setback
New
HVAC DISTRIBUTION
Location Heating
Cooling
Duct Location
Duct
R -Value Status
HVAC 1 kit liv enty Ducted
Ducted
Conditioned
8.0
New
HVAC 2 liv exr Ducted
Ducted
Conditioned
8.0
New
HVAC 3 master Ducted
Ducted
Conditioned
8.0
New
WATER HEATING
Qt . Type
Gallons Min. Eff Distribution Status
1 Small Storage Gas
50
0.66
All Pipes Ins
New
Ene Pro6.3 by EnemySoft User Number.' 6712
RunCode: 2014.10-03T09:59:22
ID:
Pae 16 of 41
•
.J
R SIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Mattison Floyd Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
10/3/2014
Project Address
53-005 Latrobe Lane La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,230
Addition
n/a
# of Units
4
INSULATION
Construction Type
Area
Cavity (ft) Special Features Status
FENESTRATION I Total Area: 1,5021 Glazing Percentage: 28.7 New/Altered Average U -Factor: 0.27
Orientation Area ft2 U -Fac SHGC Overhang Sidefins Exterior Shades Status
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE
Split Air Conditioner 16.5 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
HVAC 4 castia Ducted
Ducted Conditioned 8.0
New
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
EnemyPro 6.3 by EnemySoft User Number: 6712
RunCode: 201410-03T09:59:22 /D:
Pae 17 of 41
4
r
4
MANDATORY MEASURES SUMMARY: Residential (Page 1 of 3 MF -1 R
Project Name
Date
Mattison Floyd Residence
1101312014
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
110.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§110.6(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
110.7: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
110.8(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -2R Form.
§110.8(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §110.8(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§1 50.0 a : Minimum R-30 R-19 for Additions/Alterations insulation in wood -frame ceiling orequivalent U -factor.
150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
*§1 50.0 c : Minimum R-13 insulation in 2x4 wood -frame wall R-19 in 2x6 orequivalent U -factor.
*§1 50.0 d : Minimum R-19 insulation in raised wood -frame floor orequivalent U -factor.
150.0 : Air retarding wrap is tested labeled, and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form.
150.0 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150.0(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0 erm/inch and shall be protected from physical damage and UV light deterioration.
§150.0(q) Fenestration Products. Fenestration separating conditioned space from unconditioned space or outdoors shall meet the
requirements of either Item 1 or 2 below.-
elow:1.
1.Fenestration, including skylight products, must have a maximum U -factor of 0.58.
2. The weighted average U -factor of all fenestration, including skylight products, shall not exceed 0.58.
EXCEPTION to Section 150.0(q)1: Up to 10 square feet of fenestration area or 0.5 percent of the Conditioned Floor Area, whichever is
greater, is exempt from the maximum U -factor requirement.
150.0 r Solar Ready Buildings. Shall meet the requirements of Section 110.10 applicable to the building project.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150.0 a 1A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150.0(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§110.3(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve and recirculation loop connection requirements of §110.3(c)5
§110.5: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
§150.0(h): Heating and/or cooling loads are calculated in accordance with ASHRAE SMACNA or ACCA.
§150.00): Heating systems are equipped with thermostats that meet the setback requirements of Section 11 0.2 c .
§150.00)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally
wrapped with insulation having an installed thermal resistance of R-12 or greater.
§150.00)113: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
EnergyPro 6.3 by EnergySoft User Number: 6712 /D: Page 18 of 41
4
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
Mattison Floyd Residence
1101312014
§150.00)2A: All domestic hot water system piping conditions listed below, whether buried or unburied, must be insulated per TABLE
120.3-A.
i. The first 5 feet (1.5 meters) of hot and cold water pipes from the storage tank.
ii. All piping with a nominal diameter of 3/4 inch (19 millimeter) or larger.
iii. All piping associated with a domestic hot water recirculation system regardless of the pipe diameter.
iv. Piping from the heating source to storage tank or between tanks.
v. Piping buried below grade.
vi. All hot water pipes from the heating source to the kitchen fixtures.
§150.00)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards
Table 120.3-A.
150.0(j)3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§150.00)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
§150.0(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC
Sections 601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed
level of R-6 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that
meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic
or tape is used to seal o enin s greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150.0(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150.0(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150.0(m)7: Exhaust fans stems have back draft or automatic dampers.
§150.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150.0(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150.0 m 10: Flexible ducts cannot have porous inner cores.
§150.0(n)1: Systems using gas or propane water heaters, whether tank or on -demand, to serve individual dwelling units shall include
all the following components :
A. A 120V electrical receptacle that is within 3 feet from the water heater and accessible to the water heater with no obstructions;
B. A Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the space where the water
heater is installed;
C. A condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining
without pump assist,
D. A gas supply line with a capacity of at least 200,000 Btu/hr.
§150.0(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2 Ventilation and Acceptable Indoor Air Quality
in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in
Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§110.4(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines or built-up connections for future solar heating.
110.4(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150.0 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150.0
Residential Lighting Measures:
§150.0(k)1A: Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with Section 150.0(k) in accordance
with TABLE 150.0-A or TABLE 150.0-B as applicable.
150.0 k 1C: The wattage of permanently installed luminaires shall be determined asspecified by §130.0(c).
150.0 k 1 D: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency <= 20 kHz.
§150.0(k)1 E: Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume
no more than five watts of power per luminaire or exhaust fan as determined in accordance with Section 130.0(c). Night lights shall not
be required to be controlled by vacancy sensors.
EnergyPro 6.3 by EnergySoft User Number: 6712 /D: Page 19 of 41
•
C.
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1R
Project Name
Date
Mattison Floyd Residence
1101312014
150.0 k 1 F: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150.0(k).
150.0(k)2: All switching devices and controls shall meet the requirements of §150.0(k)2.
§150.0(k)3: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft' or 100 watts
for dwelling units larger than 2,500 ft2 may be exempt from the 50 percent high efficacy requirement when all
lighting in the kitchen is controlled in accordance with the applicable provisions in Section 150.0(k)2, and is also
controlled by vacancy sensors or dimmers.
§150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
§150.0(k)5: Lighting installed in bathrooms shall meet the following requirements:
A. A minimum of one high efficacy luminaire shall be installed in each bathroom; and
B. All other lightinq installed in each bathroom shall be high efficacy or controlled by vacancy sensors.
§150.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be
high efficacy, or shall be controlled by either dimmers or vacancy sensors.
EXCEPTION 1: Luminaires in closets less than 70 square feet.
EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site.
§150.0(k)8: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the luminaire is airtight with air
leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150.0(k)9A: For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on
the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of items
ii or iii below; and
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and
automatically reactivates the motion sensor within 6 hours
iii. Controlled by one of the following methods:
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and
which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements:
At a minimum provides the functionality of an astronomical time clock in accordance with Section 110.9;
meets the Installation Certification requirements in Section 130.4; meets the requirements for an EMCS in
Section 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
§150.0(k)9A: For low-rise multi -family residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and
outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
following requirements:
i. Shall comply with Section 150.0(k)9A; or
ii. Shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by Section 150.0(k)9B or
Section 150.0(k)9D shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall
comply with the applicable requirements in Sections 110.9 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)10: Internally illuminated address signs shall comply with Section 140.8; OR not contain a screw -base socket, and consume
no more than five watts of power as determined according to §130.0(d).
§150.0(k)11: Lighting for residential parking garages for eight or more
vehicles shall comply with the applicable requirements for nonresidential garages in Sections 110.9, 130.0, 130.1,
130.4, 140.6, and 141.0.
§150.0(k)12A. In a low-rise multi -family residential building where the total interior common area in a single building equals 20 percent
or less of the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
§150.0(k)12B. In a low-rise multi -family residential building where the total interior common area in a single building equals more than
20 percent of the floor area, permanently installed lighting in that building shall: .
i. Comply with the applicable requirements in Sections 110.9, 130.0, 130.1, 140.6, and 141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
ingress and egress.
EnergyPro 6.3 by EnergySoft User Number: 6712 /D: Page 20 of 41
r-
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
attison Floyd Residence
Date
10/3/2014
System Name
HVAC 1 kit liv enty
Floor Area
1,564
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING
CFM Sensible
Total Room Loads 4,024 38,494
Return Vented Lighting 0
Return Air Ducts 557
Return Fan 0
Ventilation 469 20,841
Supply Fan 0
Supply Air Ducts 557
TOTAL SYSTEM LOAD 1 60,450
PEAK COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output per System 110,000
3,741 852
36,735
Total Output Btuh 110,000
Output Btuh/s ft 70.3
437
Cooling System
0
Output per System 58,000
3,968 469
22,867
Total Output Btuh 58,000
7,708
0
Total Output Tons 4.8
437
Total Output Btuh/s ft 37.1
Total Output s ft/Ton 323.6
60,476
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
CARRIER 24ANB760-58MVB110 41,088
12,509
110,000
Airflow cfm/s ft
1.28
Airflow cfm/Ton
413.8
Outside Air %
23.5%
Total Adjusted System Output 41,088
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
12,509
Aug 3 PM
110,000
Outside Air cfm/s ft 0.30
Note: values above given at ARI conditions I1
I Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
469 cfm
72 OF
4
61 OF 113 OF 113 OF
0. f n.�
Pi
Heating Coil Supply Fan
2,000 cfm 113 °F
ROOM
72 OF
3 4
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air Arc
469 cfm
70/64°F
80/67°F 61/60°F 61/60°F
Cooling Coil Supply Fan 61 / 60 OF
2,000 cfm - - -
70.7 % ROOM
70/64°F
EnergyPro 6.3 by Energ Soft User Number: 6712 Run Code: 201410-03T09:59:22 /D:
Page 21 of 41.
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Date
Mattison Floyd Residence
10/3/2014
System Name
Floor Area
HVAC 2 liv exr
940
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING
PEAK COIL HTG.
PEAK
Heating System
CFM Sensible
Total Room Loads 1,532 20,328
Return Vented Lighting 0
Return Air Ducts 294
Return Fan 0
Ventilation 282 12,563
Supply Fan 0
Supply Air Ducts 294
TOTAL SYSTEM LOAD 1 33,4801
Latent CFM
Sensible
Output per System 110,000
2,248 365
17,490
Total Output Btuh 110,000
Output Btuh/s ft 117.0
208
Cooling System
0
Output per System 58,000
4,258 282
13,776
Total Output Btuh 58,000
6,506
0
Total Output Tons 4.8
208
Total Output Btuh/s ft 61.7
Total Output s ftrron 194.5
31,682
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
CARRIER 24AN8760-58MVB110 39,685
11,205
110,000
Airflow cfm/s ft
2.13
Airflow cfm/Ton
413.8
Outside Air %
14.1%
Total Adjusted System Output 39,685
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
11,205
Aug 3 PM
110,000
Outside Air cfm/s ft 0.30
Note: values above given at ARI conditions I
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
65 OF 117 OF 117 OF
Outside Air
f (ilk
282 cfm
Heating Coil Supply Fan
2,000 cfm
117 °F
ROOM
72 OF
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
76/64°F 57/56°F 57/56°F
0'
Outside Air
282 cfm
Cooling Coil Supply Fan
58 / 57 OF
2,000 cfm - -
62.0Bio ROOM
70/61 OF
70/61 OF
Energ Pro 6.3 by Energ Sok User Number: 6712 Run Code: 201410-03709:59:22 /D:
Page 22 of 41
4
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
attison Floyd Residence
Date
10/3/2014
System Name
HVAC 3 master
Floor Area
1,596
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 2.121
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 479
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 110,000
20,354
3,817 544
23,402
Total Output Btuh 110,000
0
Output Btuh/s ft 68.9
295
278
Cooling System
0
0
Output per System 58,0001
21,330
3,944 479
23,373
Total Output Btuh 58,000
0
7,761
0
Total Output Tons 4.8
295
278
Total Output Btuh/s ft 36.3
Total Output s ft/Ton 330.2
42,274
47,332
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
CARRIER 24ANB760-58MVB110 41,112
12,566
110,000
Airflow cfm/s ft
1.25
Airflow cfm/Ton
413.8
Outside Air %
23.9%
Total Adjusted System Output 41,112
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
12,566
Aug 3 PM
110,000
Outside Air cfm/s ft 0.30
Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heatin Peak
26 OF
Outside Air
479 cfm
72 OF
61 OF 113 OF 113 OF
f`•,�
Heating Coil Supply Fan
2,000 cfm 112 °F
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
479 cfm
70/64°F
80/67°F 61/60°F 61/60°F
Cooling Coil Supply Fan 61 / 60 OF
2,000 cfm — - -
71.0% ROOM
70/64°F
-A a I
Energ Pro 6.3 by Energ Soft User Number: 6712 Run Code: 201410-03709:59:22 /D:
Page 23 of 41
4
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
attison Floyd Residence
Date
10/3/2014
System Name
HVAC 4 castia
Floor Area
1,130
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,612
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 339
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output per System 110,000
19,524
2,703
569
26,400
Total Output Btuh 110,000
0
Output Btuh/s ft 97.3
283
314
Cooling System
0
0
Output per System 58,000
15,104
4,405 339
16,542
Total Output Btuh 58,000
0
7,108
0
Total Output Tons 4.8
283
314
Total Output Btuh/s ft 51.3
Total Output s ft/Ton 233.8
35,194
43,570
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
CARRIER 24ANB760-58MVB110 39,898
11,855
110,000
Airflow cfm/s ft
1.77
Airflow cfm/Ton
413.8
110,000
Jan 1 AM
Outside Air (%) 17.0%
Total Adjusted System Output 39,898
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
11,855
Aug 3P ml
Outside Air cfm/s ft 0.30
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
339 cfm
72 OF
64 OF 116 OF 116 OF
fC�lr�
Heating Coil Supply Fan o
2,000 cfm 116 F
ROOM
72 OF
4
COOLING SYSTEM PSYCHROMETICS Airstream.Tem eratures at Time of Cooling Peak
112/78°F
Outside Air Ar
339 cfm
70/62°F
77/65°F 58/58°F 58/58°F
c O
c
Cooling Coil Supply Fan 59 / 58 OF
2,000 cfm — - -
64.8% I ROOM
70/62°F
I
EnergyPro 6.3 by Energ Soft User Number: 6712 Run Code: 2014-10-03T09:59:22 /D:
Page 24 of 41
•
is
0
ROOM LOAD SUMMARY
Project Name Date
Mattison Floyd Residence 10/3/2014
System Name Floor Area
HVAC.1 kit liv enty 1,564
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name Room Name Mult. CFM 1,Sensible I Latent CFM Sensible Latent I CFMSensible
Kitchen Living Entry Kitchen Living Entry 1 41024 { 38,494 .3,741 4,0241 38,4941 3,7411 852 36735
PAGE TOTAL
TOTAL *
1 4,024
38,494
3,741
852
36,735
4,0241
38,4941
3,7411
852
36, 735
1.' Total includes ventilation load for zonal systems.
I EnergyPro 6.3 by EnemySoft User Number: 6712 RunCode: 201410-03T09:59:22 /D• Page 25 of 41
•
.7
•
ROOM LOAD SUMMARY
Project Name Date
Mattison Floyd Residence 10/3/2014
System Name Floor Area
HVAC 2 liv exr 940
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. I CFM Sensible Latent CFM Sensible Latent CFM Sensible
Living Exiercise Living Exiercise 1 1,532 20,328 2,248 1,5321 20,3281 2,248 3651 17,490
PAGE TOTAL
TOTAL'
1,5321
20, 328
2,2481
365 17,490
1, 532
20, 328
2, 248
365 17, 490
' Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnerqySoft User Number: 6712 Run Code: 201410-03709:59:22 /D: Page 26 of 41
i
•
•
ROOM LOAD SUMMARY
Project Name Date
Mattison Floyd Residence 101312014
System Name Floor Area
HVAC 3 master 1,596
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. I CFM I Sensible I Latent CFM I Sensible Latent CFM I Sensible
Master bedroom Master bedroom 1 1 2,1211 20,3541 3,817 2,1211 20,3541 3,817 5441 23,402
PAGE TOTAL
TOTAL*
2,121
20,3541
3,8171
544
23,41992
2,121
20, 354
3, 817
544
23, 402
* Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnemySoft User Number: 6712 Run Code: 201410-03T09:59:22 /D: Page 27 of 41
is
•
ROOM LOAD SUMMARY
Project Name Date
Mattison Floyd Residence 101312014
System Name Floor Area
HVAC 4 cash. 1,130
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name I Mult. I CFM I Sensible Latent CFM Sensible Latent CFM I Sensible
Casita Casita 1 1 1 1,6121 19,5241 2, 703 1,6121 19, 524 2,7031 5691 26,400
PAGE TOTAL
TOTAL*
1,6121
19,5241
2,7031
569
26,400
1,612
19,524
2,703
569
26,400
* Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnemySoft User Number. 6712 Run Code: 2014-10-03709:59:22 /D: Page 28 of 41
9
ROOM HEATING PEAK LOADS
Project Name
Mattison Floyd Residence
Date
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Kitchen Living Entry
Floor Area 1,564.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT 'F
=
_
=
=
_
=
c
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
1,532.0
X
0.0260
46
1,832
skylight
32.0
X
0.4600
46
677
R-21 Wall (W.21.2x6.16)
3,242.5
X
0.0690
46
10,292
Low -E Vinyl
368.5
X
0.2800
46
4,746
IivLow-E Vinyl
363.0
X
X
0.2400
46
4,008
Slab -On -Grade
perim = 270.0
0.7300
46
9,067
'R-13 Wall
1,364.0
X
0.1020
0
0
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,564 X
Area
to another room
18.00 X 0.266
Ceiling Height ACH
Page Total
/60] X
AT
30,621
_ 6,114
TOTAL HOURLY HEAT LOSS FOR ROOM 36,735
EnergyPro 6.3 by EnergySoft User Number- 6712 RunCode: 201410-03709:59:22 /D: Page 29 of 41.
0
0
•
ROOM HEATING PEAK LOADS
Project Name
Mattison. Floyd Residence.
Date
10/3/2014
°ROOM INFORMATION
DESIGN CONDITIONS
Room Name Living Exiercise
Floor Area 940.0 ft2
Incloor.Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
46 c
46 c
46 =
46 _
46 =
46 _
0 =
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Page Total
/60] X 46
AT
Btu/hr
R-38 Roof Attic
936.8
0.0260
1,120
st skylite
3.2
0.3000
44
R-21 Wall (W.21.2x6.16)
1,823.9
0.0690
5,789
Wood Door
28.0
0.5000
644
Low -E Vinyl
248.1
0.2800
3,196
Slab -On -Grade
perim = 90.0
0.7300
3,022
'R-13 Wall
740.0
0.1020
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 940 X
Area
another room
18.00 X 0.266
Height ACH
13,815
= 3,674
TOTAL HOURLY HEAT LOSS FOR ROOM 17,490
EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 2014.10-03709:59:22 /D: Page 30 of 41
•
ROOM HEATING PEAK LOADS
Project Name
Mattison,Floyd Residence
Date
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master bedroom
Floor Area 1,596.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
_
_
c
=
_
=
=
=
=
_
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
1,596.0
0.0260
46
1,909
R-21 Wall (W.21.2x6.16)
2,594.9
0.0690
46
8,236
Low -E Vinyl
245.1
0.2800
46
3,157
Slab -On -Grade
penim = 115.0
0.7300
46
3,862
'R-13 Wall
1,396.0
0.1020
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,596 X
Area
another room
18.00 X 0.266
Height ACH
Page Total
/60] X
AT
17,164
= 6,239
TOTAL HOURLY HEAT LOSS FOR ROOM 23,402
EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 2014-10-03709:59:22 /D: Page 31 of 41
•
ROOM HEATING PEAK LOADS
Project Name
Mattison Floyd Residence
Date
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Casita
Floor Area 1,130.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
=
=
=
c
=
c
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
1,127.6
0.0260
46
1,349
st skylite
2.4
0.3000
46
33
R-21 Wall (W.21.2x6.16)
3,560.2
0.0690
46
11,300
Low -E Vinyl
239.8.
0.2800
46
3,089
Slab -On -Grade
perim = 185.0
0.7300
46
6,212
'R-13 Wall
940.0
0.1020
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,130 X
Area
another room
18.00 X 0.266
Height ACH
Page Total
/60] X
AT
21.983
0 4,417
TOTAL HOURLY HEAT LOSS FOR ROOM 26,400
EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 201410-03T09:59:22 ID: Page 32 of 41
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Mattison Floyd Residence 10/3/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Kitchen Living Entry Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,564.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranoe: 34 OF
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
"R-13 Wall
Orientation
(tM
(N)
(E)
(S)
(NE)
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,532.0
0.0260
77.0
757.5
0.0690
32.0
991.0
0.0690
43.7
933.0
0.0690
42.7
561.0
0.0690
32.9
1,364.0
0.1020
0.0
0.0
14.5
22.5
16.7
0.0
14.5
16.0
16.7
0.0
14.5
48.0
Page Total
Fa_nPctratinn
Skylight
NEW A
NEW 1
NEW B
NEW C
NEW E
NEW 2
NEW F
NEW X
OriPntatinn
(W)
(N)
(N)
(N)
(N)
(N)
(N)
(N)
(E)
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
-
=
=
=
-
0.0
36.3
32.0
162.2
0.0
14.5
20.0
16.7
0.0
14.5
40.0
16.7
0.0
14.5
20.0
16.7
0.0
14.5
22.5
16.7
0.0
14.5
16.0
16.7
0.0
14.5
48.0
16.7
0.0
14.5
16.0
16.7
0.0
14.5
3.0
Page Total
3,067
1,673
2,986
2,747
1,272
11,
rstuinr
5,190
335
669
335
376
268
803
268
91
8,33
Internal Gain Btu/hr-
Occupants
tu/hrOccu ants 4 7 Occupants X 245 Btuh/occ. = 1,1
Equipment 1,564 Floor Area X 0.50 w/sqft = 6
Infiltration: 1.064 X 0.94 X 129.02 X
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 38494
.Latent Gain Btu/hr
Occupants 4 7 Occupants X 155 Btuh/occ. = 727
Infiltration: 4,771 X 0.94 X 129.02 X 0.00523 = 3,013
Air Sensible CFM ELA AW
• TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 797
2014-1
•
•
RE'SIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Mattison Floyd Residence 7 10/3/2014
ROOM. INFORMATION I DESIGN CONDITIONS
Room Name
Kitchen Living Entry
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,564.0 ftz
Outdoor Wet Bulb Temperature
78 OF
Indoor.Dry Bulb Temperature
70 OF
Outdoor Daily Ranqe:
34 OF
Surfaces
Orientation
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
GLF
=
=
=
=
=
=
=
=
0.0
14.5
3.0
30.4
0.0
14.5
3.0
30.4
0.0
14.5
20.0
30.4
0.0
14.5
24.0
30.4
'
13.7
0.0
29.6
0.0
14.5
48.0
22.0
187.0
13.7
0.0
Page Total
FP_nP_Ctrnfinn
NEW X
NEW X
NEW 11
NEW 12
NEW 13
NEW Z
NEW 14
NEW 2A
NEW 2A.
Gain
r)riontatinn
(E)
(E)
(E)
(E)
(E)
(S)
(S)
(S)
(S)
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
0.0
14.5
3.0
30.4
0.0
14.5
3.0
30.4
0.0
14.5
20.0
30.4
0.0
14.5
24.0
30.4
176.0
13.7
0.0
29.6
0.0
14.5
48.0
22.0
187.0
13.7
0.0
21.2
0.0
14.5
5.0
22.0
0.0
14.5
5.0
Page Total
4.7 Occupants X 245 Btuh/occ.
1,564 Floor Area X 0.50 w/sqft =
Infiltration: 1.064 X 0.94 X 129.02 X 42 =
Air Sensible CFM ELA AT
AL HOURLY SENSIBLE HEAT GAIN FOR ROOM
Latent Gain
4.7 Occupants X I Btuh/occ. _
Infiltration: 4,771 X 0.94 X 129.02 X 0.00523 =
Air Sensible CFM ELA AW
Btu/hr
Btu/hr
91
91
608
729
2,412
1,056
2,563
110
110
7,771
Btu/hr
1,150
2,669
5,393
38,494
Btulhr
727
3,013
727
1 EnemyPro 6.3 by EnergySoR User Number: 6712 RunCode: 2014-16-03T09:59:22 /D: Page 34 of 41
•
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Mattison Floyd Residence 1
710/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Kitchen Living Entry
Outdoor Dry Bulb Temperature
112 OF
Floor Area 1,564.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btulhr
X
X -
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF
Area GLF
Btu/hr
NEW 2A (S) 0.0 X 14.5 +
5.0 X 22.0 =
110
NEW 2A (S) 0.0 X 14.5 +
5.0 X 22.0 =
110
NEW (NE) 0.0 X 14.5 +
65.0 X 18.7 =
1,213
X +
X =
X +
X
X +
X =
X +
X -
X +
X =
X +
X =
Page Total
1,433
Internal Gain
Btu/hr
Occupants 4.7 Occupants X 245
Btuh/occ. =
1,150
Equipment 1,564 Floor Area • X 0.50
w/s4 ft =
2,669
Infiltration: 1.064 X 0.94 X 129.02 X 42
5,393
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
38,494
Latent Gain
Btu/hr
Occupants 4.7 Occupants X 155
Btuh/occ. =
727
Infiltration: 4,771 X 0.94 X 129.02 X 0.00523 =
3,013
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
727
EnergyPro 6.3 by Ene Soft User Number: 6712 Run Code: 201410-03709:59:22 /D:
Page 35 of 41
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Mattison Floyd Residence
ROOM INFORMATION DESIGN, CONDITIONS
Room Name Living Exiercise Outdoor Dry Bulb Temperature
Floor Area 940.0 ft2 Outdoor Wet Bulb Temperature
Indoor Dry Bulb Temperature 70 OF Outdoor Daily Range:
0nanup Surfacac
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
Wood Door
R-21 Wall (W.21.2x6.16)
R-21 Wall (W 21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
'R-13 Wall
Orientation
(N)
(N)
(NE)
(E)
(SE)
(S)
(NE)
Date
10/3/2014
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
x
CLTD'
=
=
=
=
=
=
=
=
=
936.8
0.0260
77.0
532.0
0.0690
32.0
28.0
0.5000
33.3
94.5
0.0690
37.3
639.9
0.0690
43.7
97.5
0.0690
41.3
230.0
0.0690
42.7
230.0
0.0690
32.9
740.0
0.1020
0.0
Items shown with an asterisk (`) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
•NEW
Skylight
Skylight
2R
NEW 2S
NEW 2U
NEW 2V
NEW 2W
NEW 2T
0.0
Internal Gain
0
Orientation
(tM
(IM
(NE)
(E)
(E)
(E)
(E)
(SE)
Page Total
Shaded Unshaded
Area
X
X
X
X
x
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
x
GLF
=
=
=
=
=
=
=
=
=
0.0
21.3
1.6
92.6
0.0
21.3
1.6
92.6
0.0
14.5
25.5
24.3
0.0
14.5
59.5
30.4
0.0
14.5
59.2
30.4
0.0
14.5
22.2
30.4
0.0
14.5
59.2
30.4
0.0
14.5
22.5
28.0
Page Total
2.8 Occupants X 245 Btuh/occ.
940 Floor Area X 0.50 w/sqft =
Infiltration: 1.064 X 0.94 X 77.54 X 42 =
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
,Latent Gain
2.8 Occupants X I Btuh/occ. _
Infiltration: 4,771 X 0.94 X 77.54 X 0.00523 =
Air Sensible CFM ELA AW
User
:59:22
112 OF
78 OF
34 OF
Btu/hr
1,875
1,175
467
243
1,928
278
677
522
0
7,165
Btu/hr
148
148
620
1,808
1,799
675
1, 799
630
7,627
Btu/hr
691
1,604
3,241
20,328
Btu/hr
437
1,811
437
e36of41
•
•
[ktSIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Mattison Floyd Residence 10/3/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Master bedroom Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,5960 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry.Bulb Temperature 70 OF Outdoor Daily Range: 34 OF
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
"R-13 Wall
Orientation
(►M
(N)
(E)
(SE)
(S)
(SM
(NE)
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,596.0
0.0260
56.0
320.0
0.0690
25.0
320.0
0.0690
32.3
97.5
0.0690
29.3
362.5
0.0690
27.7
94.5
0.0690
31.7
1,400.4
0.0690
26.7
1,396.0
0.1020
0.0
25.5
16.9
0.0
12.3
13.8
Page Total
Fpnoctratinn
NEW 2B
NEW 2C
NEW 2E
NEW 15
NEW 2F
NEW 2D
NEW 2H
NEW 2J
NEW 2K
nriantatinn
(SE)
(S)
(S)
(S)
(S)
(SVV)
(NE)
(NE)
(NE)
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
-
=
=
=
=
=
0.0
12.3
22.5
15.1
0.0
12.3
25.5
13.7
0.0
12.3
12.0
13.7
0.0
12.3
48.0
13.7
0.0
12.3
12.0
13.7
0.0
12.3
25.5
16.9
0.0
12.3
13.8
15.9
0.0
12.3
13.8
15.9
0.0
12.3
6.0
15.9
Page Total
Btu/hr
2,324
552
714
197
692
206
2,583
0
7,269
Btu/hr
339
349
164
657
164
430
219
219
Internal Gain Btu/hr
Occupants 4 8 Occupants X 245 Btuh/occ.
Equipment 1,596 Floor Area X 0.50 w/sqft =
Infiltration: 1.064 X 0.94 X 131.66 X
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 20,354
Latent Gain Btu/hr
Occupants 4 8 Occupants X 155 Btuh/occ. = 742
Infiltration: 4.771 X 0.94 X 131.66 X 0.00523 - 3,075
Air Sensible CFM ELA AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 742
I EnemyPro 6.3 by EnergySott User Number: 6712 Run Code: 2014-10-03709:59:22 /D: Page 37 of 41
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Mattison Floyd Residence
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master bedroom
Outdoor Dry Bulb Temperature
112 OF
Floor Area 1,596.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature _ 70 OF
Outdoor Daily Range:
34 OF
O a ue,Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
X
X =
X
X
X
X
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
Page Total
0
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area GLF
Btu/hr
NEW 2L (NE) 0.0 X 12.3 +
30.0 X 15.9 =
476
NEW 16 (NE) 0.0 X 12.3 +
20.0 X 15.9 =
318
NEW 2M (NE) 0.0 X 12.3 +
6.0 X 15.9 =
95
NEW 2N (NE) 0.0 X 12.3 +
10.0 X 15.9 =
159
X +
X =
X +
X =
X +
X =
X +
X =
X +
X =
Page Total
1,048
Internal Gain .
Btu/hr
Occupants 4 8 Occupants X d245
Btuh/occ. =L
1,173E
ui ment 1,596 Floor Area X
w/ggft =
2,724
Infiltration: 1.064 X 0.94 X 131.66 X 42 =
5,503
Air Sensible CFM ELA AT
.TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
20,354
Latent Gain
Btu/hr
Occupants 4 8 Occupants X 155
Btuh/occ. =
742
Infiltration: 4,771 X 0.94 X 131.66 X 0.00523 =
3,075
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
742
EnergyPro 6.3 by Ene Soft User Number: 6712 Run Code: 201410-03T09:59:22 ID:
Page 38 of 41
r
RESIDENTIAL ROOM COOLING LOAD SUMMARY
'Project Name . Date
Mattison Floyd Residence 10/3/2014
ROOM INFORMATION DESIGN CONDITIONS
17,
Room Name
Casita
Outdoor Dry Bulb Temperature
112°F
Floor Area
1,130.0 ft2
Outdoor Wet Bulb Temperature
78 °F
Indoor Dry Bulb Temperature
70 OF
Outdoor Daily Ranqe:
34 OF
Ooaaue Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W..21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
'R-13 Wall
Orientation
(1/10
(N)
(NE)
(E)
(SE)
(S)
(S K9
(NE)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,127.6
0.0260
56.0
589.2
0.0690
25.0
373.0
0.0690
30.3
839.5
0.0690
32.3
120.0
0.0690
29.3
606.5
0.0690
27.7
216.0
0.0690
31.7
816.0
0.0690
26.7
940.0
0.1020
0.0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestratinn
Skylight
Skylight
NEW K
NEW L
NEW M
NEW P
NEW N
NEW Q
NEW R
Internal Gain
Orientatinn
W
(tM
(N)
(N)
(N)
(N)
(NE)
(NE)
(E)
Page Total
Shaded Unshaded
Area
X
X
X
X
X
X
X
X12.3
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
17.5
1.2
58.1
0.0
17.5
1.2
58.1
0.0
12.3
19.3
14.2
0.0
12.3
4.5
14.2
0.0
12.3
4.5
14.2
0.0
12.3
22.5
14.2
0.0
12.3
4.5
19.7
0.0
22.5
19.7
0.0
12.3
22.5
22.4
Page Total
3.4 Occupants X 245 Btuh/occ. _
1,130 Floor Area X 0.50 w/sgft =
Infiltration: 1.064 X 0.94 X 93.21 X 42 =
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
Latent Gain
3.4 Occupants X 1 155 Btuh/occ. _
Infiltration: 4,771 X 0.94 X 93.21 X 0.00523 =
Air Sensible CFM ELA AW
401
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
6.3 by EnergySoft User Number: 6712 Run Code: 2014-1 0-03 70 9:59:22
Btu/hr
1,642
1,016
781
1,873
243
1,158
472
1,505_
0
8, 690
Btu/hr
70
70
274
64
64
320
89
443
1
Btu/hr
831
1, 928
19,524
Btu/hr
525
2,177
525
re 39 of 41
M
•
a
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Mattison Floyd Residence 10/3/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Casita Outdoor Dry Bulb Temperature 112°F
Floor Area 1,130.0 ft' Outdoor Wet Bulb Temperature 78 °F
Indoor Pry Bulb Temperature 70 OF Outdoor Daily Range: 34 OF
e Su
Orientation
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
-
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Btu/l
0.0
3.0
22.4
0.0
3.0
22.4
1,130
0.0
3.0
22.4
_
-
0.0
3.0
22.4
Infiltration:
0.0
3.0
22.4
3,896
0.0
3.0
22.4
AT
0.0
6.0
13.7
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1.. Cooling Load Temperature Difference (CLTD)
FanPCfrn inn
NEWS
NEW T
NEW T
NEW T
NEW U
NEW V
NEW W
NEW J
NEW 4
Orientation
(E)
(E)
(E) .
(E)
(E)
(E)
(S)
(S).
(SM
Btulhr
5haded
Area
GLF
X 12.3
X 12.3
X 12.3
X 12.3
X 12.3
X 12.3
X 12.3
X 12.3
X1 12.3
+
+
+
+
+
+
+
+
+
Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
Btu/l
0.0
3.0
22.4
0.0
3.0
22.4
1,130
0.0
3.0
22.4
_
-
0.0
3.0
22.4
Infiltration:
0.0
3.0
22.4
3,896
0.0
3.0
22.4
AT
0.0
6.0
13.7
0.0
27.5
13.7
0.0
24.0
Latent Gain
Page Total
F,
01
67
67
67
67
67
67
82
376
Internal Gain
Btulhr
Occupants
3.4
Occupants X
245
Btuh/occ.
831
Equipment
1,130
Floor Area X
0.50
w/s4 ft
_
-
1,928
Infiltration:
1.064
X 0.94 X 93.21
X 42 =
3,896
Air Sensible
CFM ELL
AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
19,524
Latent Gain
Btu/hr
Occupants
3 4 Occupants X 155 Btuh/occ.
= 525
Infiltration:
.4.771
X 0.94 X 93.21
X 0.00523 =
2,177
Air Sensible
CFM ELA
AW
I Enemy. Pro 6.3 by EneroySoft User Number: 6712 Run Code: 201410-03709:59.22 /D: Pape 40 of 41
r
•
C
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Mattison Floyd Residence
7
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Casita
Outdoor Dry Bulb Temperature
112 OF
Floor Area 1,130.0 ftz
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
X
X =
X
X =
X
X =
NTA I x
x =
Y U EPT. xx
=
x
x =
CONSTRUCTION x
x =
x
x =
BY x
x =
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area GLF
Btu/hr
NEW G (NE) 0.0 x 12.3 +
12.0 X 15.9 =
191
NEW 3 (NE) 0.0 X 12.3 +
40.0 X 15.9 =
635
NEW H (NE) 0.0 X 12.3 +
12.0 X 15.9 =
191
X +
X =
X +
X =
X +
X =
X +
X =
X +
X =
x
x =
Page Total
1,016
Internal Gain
Btu/hr
Occupants 3.4 Occupants X 245
Btuh/occ. =
831
Equipment 1,130 Floor Area X 0.50
w/sgft =
1928,
Infiltration: 1.064 X 0.94 X 93.21 X 42 =
3,896
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
19,524
Latent Gain
Btu/hr
Occupants 3.4 Occupants X 155
Btuh/occ. =
525
Infiltration: 4,771 X 0.94 X 93.21 X 0.00523 =
2,177
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
525
Ener,gyPro 6.3 by Ene Soft User Number: 6712 Run Code: 201410-03709:59:22 /D:
Page 41 of 41