BRES2014-1097 Title 24COPy BUILDING ENERGY ANALYSIS REPORT \. 1 PROJECT: Mattison Floyd Residence 53-005 Latrobe Lane La Quinta, CA 92253 Project Designer: JMA Architecture and Engineering 73-995 EI Paseo Suite 203 Palm Desert, CA 92260 (760) 346-6155 Job Number:RECOMVED OCT 202014 CM OF LA ZUINTA Date: COMMUHrrY DEVELOPMfIff," 4 10/3/2014 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is • authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards. ? This program developed by EnergySoft, LLC — www.energysoft.com. �--• - tnergyPro 6.3 by Ene Sof User Number: 6712 ID: Report Prepared by: Jon Scott Scott Design and Title 24,, 77-085 Michigan Driv CITY OF LA QUINTA Palm Desert, CA 9221 BUILDING & SAFETY DEPT. (760) 200-4780 APPROVE D FOR CONSTRUCTION DA 2) BY • Job Number:RECOMVED OCT 202014 CM OF LA ZUINTA Date: COMMUHrrY DEVELOPMfIff," 4 10/3/2014 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is • authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards. ? This program developed by EnergySoft, LLC — www.energysoft.com. �--• - tnergyPro 6.3 by Ene Sof User Number: 6712 ID: CERTIFOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD. Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml CF*F-0f Page 1 of 13 ra GENERAL INFORMATION 01 Building Complies with Computer Performance 02 This building incorporates features that require field testing ancl//or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider. 03 This building incorporates one or more Special Features shown below 01 Project Name Mattison Floyd Residence 05 06 07 02 Calculation Description Title 24 Analysis Standard7' Des gn Proposed Design Compliance Margin 03 'Project Location 53-005 Latrobe Lane �6 07 6.46 -0.39 04 A City La Quinta 05 Standards Version Compliance 2015 06 Zip code 92253 07 Compliance Manager Version BEMCmpMgr 2013-3 (650) 08 Climate Zone CZ15 09 Software Version EnergyPro 6.3 10 Building Type Single Family 11 Front Orientation (deg/Cardinal) 15 12 Project Scope Newly Constructed 13 R5* Number of Dwelling Units 1 • 14 Total Cond. Floor Area (FT2) 5230 15 A Number of Zones 4 16 Slab Area (FT2) 5230 17 Number of Stories 1 18 Addition Cond. Floor Area NA *19'9'` Natural Gas Available Yes 20 Addition Slab Area (FT2) NA # 2�1 Glazing Percentage (%) 28.7% AW COMPLIANCE RESULTS 01 Building Complies with Computer Performance 02 This building incorporates features that require field testing ancl//or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider. 03 This building incorporates one or more Special Features shown below .49ENERGY USE SUMMARY 04 05 06 07 08 Energy Use (kTDV/ft) Standard7' Des gn Proposed Design Compliance Margin Percent Improvement Space Heating �6 07 6.46 -0.39 -6.4% Space Cooling OM1,36.40 110.44 25.96 19.0% IAQ Ventilation 1.28 1.28 0.00 0.0% Water Heating 4.91 4.27 0.64 13.0% Photovoltaic Offset `r -- 0.00 0.00 -- Compliance Energy Total 148.66 122.45 26.21 17.6% .®�9 Registration Number: ,�� CA Building Energy Efficiency Standards�- 2013 Residential Compliance ------------ CITY OF LA QUINTA BUILDING & SAFETY U EpT. APPROVED FOR CONSTRUCTION Registration Date/Time: I pA-jE BY HERS Report Version - CF1R-09042014-6v — —'—Re erated at: 2014-10-03 09:53:12 CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OOD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml REQUIRED SPECIAL FEATURES The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis. • Ducts with high level of insulation • Cathedral Ceiling • Window overhangs and/or fins PROJECT HERS FEATURES CF* F-011` Page 2 of 13 The following are project -level features that must be field -verified as a condition for meeting the modeled energy performance for this computer analysis. These, plus any additional HERS features listed in the building components tables below, requre field verification by a certified HERS Rater. • IAQ mechanical ventilation w ENERGY DESIGN RATING sc� This is the sum of the annual TDV energy consumption for energy use components included in the perfor�m_"`nce compliance approach for the Standard Design Building (Energy Budget) and the annual TDV energy consumption for lighting and components not regulated by Title 24, Part 6 (such as domestic,appliances and consumer electronics) and accounting for the annual TDV energy offset by an on-site renewable energy system. 4S.O Reference Energy Use Energy Design Rating MarginPercent Improvement Total Energy (kTDV/f2)` 185.46 159.25 26.21 14.1% • includes calculated Appliances and Miscellaneous Energy Use (AMEU) —Zi BUILDING - FEATURES INFORMATION 01 02 03 04 05 06 07 Project Name Conditioned Floor Area (sft) Number of Dwelling Uwmtt , Number of Bedrooms Number of Zones Number of Ventilation Cooling Systems Number of Water Heating Systems Mattison Floyd Residence 5230 1 12 4 4 1 .A ZONE INFORMATION �v 01 02 03 04 05 06 07 Zone Name Zone Type HVAC System Name Zone Floor Area (ft2) Avg. Ceiling Height Water Heating System 1 Water Heating System 2 Kitchen Living Entry Conditioned HVAC 1 kit liv entyl 1564 18 DHW Sys 1 Living Exiercise Conditioned HVAC 2 liv exr2 940 18 DHW Sys 1 Master bedroom Conditioned HVAC 3 master3 1596 18 DHW Sys 1 Casita Conditioned HVAC 4 castia4 1130 18 DHW Sys 1 Registration Number: CA Building Energy Efficiency Stands - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIFJOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE JOD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml CF*F-01" Page 3 of 13 -j OPAQUE SURFACES 01 02 03 04 05 06 07 08 Name Zone Construction Azimuth Orientation Gross Area (ft2) Window Area (ft2) Tilt(deg) 15d Wall Kitchen Living Entry R-21 Wall (W21.2x6.16) 15 Front 940 182.5 90 105d Wall Kitchen Living Entry R-21 Wall (W.21.2x6.16) 105 Left 1220 229 90 195d Wall Kitchen Living Entry R-21 Wall (W.21.2x6.16) 195 Back 1188 255 90 285d Wall Kitchen Living Entry R-21 Wall (W.21.2x6.16) 28 - specify - 626 65 90 Roof 4 Kitchen Living Entry R-38 Roof Attic 1532 15d Wall Living Exiercise R-21 Wall (W21.2x6.16) `'b15 Front 560 0 90 60d Wall Living Exiercise R-21 Wall (W.21.2x6.16) �� 60 - specify - 120 25.5 90 105d Wall 2 Living Exiercise R-21 Wall (W.21.2x6.16) r.� 105 Left 840 200.1 90 y 150d Wall Living Exiercise R-21 Wall (W.21.2x6.16)� 150 - specify - 120 22.5 90 j 195d Wall 2 Living Exiercise R-21 Wall (W21.2x6.ay6)� 195 Back 230 0 90 285d Wall 2 Living Exiercise R-21 Wall (W.21.4x6'61"6) 28 - specify - 230 0 90 Roof 5 Living Exiercise R-38 RooftAttic 936.8 15d Wall 3 Master bedroom R-21 Wall (y 21 2x6.16) 15 Front 320 0 90 t 105d Wall 3 Master bedroom R-21 Wall (W 21.2x6.16) 105 Left 320 0 90 p 150d Wall 2 Master bedroom R-21 Wall'(W.21.2x6.16) 150 - specify - 120 22.5 90 195d Wall 3 Master bedroom R-,11�1Nall (W21.2x6.16) 195 Back 460 97.5 90 240d Wall Master bedroom R 21'Wall (W.21.2x6.16) 240 - specify - 120 25.5 90 285d Wall 3 Master bedroom A%R-21 Wall (W21.2x6.16) 28 - specify - 1500 99.6 90 Roof 6 Master bedroom R-38 Roof Attic 1596 15d Wall 4 Casita R-21 Wall (W21.2x6.16) 15 Front 640 50.8 90 60d Wall 2 Casita 0 R-21 Wall (W.21.2x6.16) 60 specify - 400 27 90 105d Wall 4 Casita %% R-21 Wall (W21.2x6.16) 105 Left 880 40.5 90 150d Wall 3 Casita R-21 Wall (W.21.2x6.16) 150 specify - 120 0 90 195d Wall Casita& v R-21 Wall (W21.2x6.16) 195 Back 640 33.5 90 240d Wall 2 Cas�aaV R-21 Wall (W.21.2x6.16) 240 specify - 240 24 90 285d Wall 4 ^Casita R-21 Wall (W21.2x6.16) 28 - specify - 880 64 90 Roof 7 Gasita R-38 Roof Attic 1127.6 Registration Number: CA Building Energy Efficiency Stands - 2013 Residential Compliance Registration Date/Time: Report Version - CF111-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE IOD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml CF*F-01` Page 4 of 13 OPAQUE SURFACES — Cathedral Ceilings 01 02 03 04 05 06 07 08 09 10 11 Name Zone Type Orientation Area (ft2) Roof Rise (x in 12) Roof Pitch Roof Tilt (deg) Roof Reflectance Roof Emmittance Framing Factor Roof Kitchen Living Entry R-38 Roof Attic1 specify - 32.1 3 0.25 14.04 0.1 0.85 0.1 Roof 2 Living Exiercise R-38 Roof Attic1 - specify - 1 3.3 3 0.25 14.04 0.1 0.85 0.1 Roof 3 Casita R-38 Roof Attic1 specify - 2.5 3 0.25 14.04 0.1 0.85 0.1 ATTIC A 01 02 03 04'1 '05 06 07 Name Construction Roof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof Attic Attic Roof Cons 3 %W0.1 0.85 Yes No �®err X41 Registration Number: p�►® Registration Date/Time: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE I,OD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml CF*F-01"' Page 5 of 13 WINDOWS 01 02 03 04 05 06 07 08 09 10 Name Type Surface (Orientation -Azimuth) Width(ft ) Height (ft) Multiplier Area (ft) U -factor SHGC Exterior Shading NEW A Window 15d Wall (Front -15) -- - 1 20.0 0.28 0.18 NEW 1 Window 15d Wall (Front -15) - - 1 40.0 0.28 0.18 NEW B Window 15d Wall (Front -15) - -- 1 20.0 0.28 0.18 NEW C Window 15d Wall (Front -15) -- -- 1 22.5 0.28 0.18 NEW E Window 15d Wall (Front -15) -- �-- 1 16.0 0.28 0.18 NEW 2 Window 15d Wall (Front -15) --- 1 48.0 1 0.28 0.18 NEW F Window 15d Wall (Front -15) 1 16.0 0.28 0.18 NEW X Window 105d Wall (Left -105) A,�=� -- 1 3.0 0.28 0.18 NEW X 2 Window 105d Wall (Left -105) 1 3.0 0.28 0.18 NEW X 3 Window 105d Wall (1 -eft -105) r�-- -- 1 3.0 0.28 0.18 NEW 11 Window 105d Wall (Left -105) M `'� - -- 1 20.0 0.28 0.18 NEW 12 Window 105d Wall (Left -105) Q� - -- 1 24.0 0.28 0.18 NEW 13 Window 105d Wall (Left -105) 16.0 11.0 1 176.0 0.24 0.18 NEW Z Window 195d Wall (Back -195) #10 - - 1 48.0 0.28 0.18 NEW 14 Window 195d Wall (Back -195) 17.0 11.0 1 187.0 0.24 0.18 NEW 2A Window 195d Wall (Back -195)0 -- -- 1 5.0 0.28 0.18 NEW 2A 2 Window 195d Wall (Back 95) - -- 1 5.0 0.28 0.18 NEW 2A 3 Window 195d Wall (Baclv�195) -- -- 1 5.0 0.28 0.18 NEW 2A 4 Window 195d Wall (I ack-195) - -- 1 5.0 0.28 0.18 NEW Window 285d Walspecify -28) - -- 1 65.0 0.28 0.18 Skylight Skylight Roof( pecify -285) 1 32.0 0.46 0.53 NEW 2R Window 606"Wall (- specify --60) - -- 1 25.5 0.28 0.18 NEW 2S Window f05d Wall 2 (Left -105) -- -- 1 59.5 0.28 0.18 NEW 2U Window %V105d Wall 2 (Left -105) - -- 1 59.2 0.28 0.18 NEW 2V Window ��' 105d Wall 2 (Left -105) - - 1 22.2 0.28 0.18 NEW 2W Window �`� 105d Wall 2 (Left -105) - -- 1 59.2 0.28 0.18 NEW 2T Window`'1 150d Wall (- specify --150) -- -- 1 22.5 0.28 0.18 Skylight 2 Skylight iQ� Roof 2 (- specify --285) 1 1.6 0.30 0.30 Skylight 3 Skylight Roof 2 (- specify --285) 1 1.6 1 0.30 0.30 #4114� Registration Number: �� CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIF•E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml CF*F-01` Page 6 of 13 NEW 2B Window 150d Wall 2 (- specify -150) -- -- 1 22.5 0.28 0.18 NEW 2C Window 195d Wall 3 (Back -195) -- -- 1 25.5 0.28 0.18 NEW 2E Window 195d Wall 3 (Back -195) - -- 1 12.0 0.28 0.18 NEW 15 Window 195d Wall 3 (Back -195) -- -- 1 48.0 0.28 0.18 NEW 2F Window 195d Wall 3 (Back -195) -- -- 1 12.0 0.28 0.18 NEW 2D Window 240d Wall (- specify --240) -- -- 1 25.5 0.28 0.18 NEW 2H Window 285d Wall 3 ( specify -28) -- -- 1 13.8 0.28 0.18 NEW 2J Window 285d Wall 3 (- specify -28) -- -- 1 13.8 0.28 0.18 NEW 2K Window 285d Wall 3 (- specify -28) -- - 1 6.0 0.28 0.18 NEW 2L Window 285d Wall 3 (- specify -28) -- ^f -- 1 30.0 0.28 0.18 NEW 16 Window 285d Wall 3 (- specify -28) 1 20.0 0.28 0.18 NEW 2M Window 285d Wall 3 (- specify -28) -- 1 6.0 0.28 0.18 NEW 2N Window 285d Wall 3 (- specify -28)-- -- 1 10.0 0.28 0.18 NEW K Window 15d Wall 4 (Front -15) Al ,r -- -- 1 19.3 0.28 0.18 NEW L Window 15d Wall 4 (Front -15)` 1 4.5 0.28 0.18 NEW M Window 15d Wall 4 (Front -15) Ov - - 1 4.5 0.28 0.18 NEW P Window 15d Wall 4 (Front -15) � - -- 1 22.5 0.28 0.18 NEW N Window 60d Wall 2 (- specify -60) 1 4.5 0.28 0.18 NEW Q Window 60d Wall 2 (- specify -60?D -- -- 1 22.5 0.28 0.18 NEW R Window 105d Wall 4 (Left -106 v* -- -- 1 22.5 0.28 0.18 NEW S Window 105d Wall 4 (Left;05) -- -- 1 3.0 0.28 0.18 NEW T Window 105d Wall 4 ( e0105) -- -- 1 3.0 0.28 0.18 NEWT 2 Window 105d Wall(Lfeft-105) -- -- 1 3.0 0.28 0.18 NEWT 3 Window 105d WKII-4' (Left -105) -- -- 1 3.0 0.28 0.18 NEW U Window 105dJWall 4 (Left -105) -- -- 1 3.0 0.28 0.18 NEW V Window 105d.Wall 4 (Left -105) -- -- 1 3.0 0.28 0.18 NEW W Window �195d Wall 4 (Back -195) -- -- 1 6.0 0.28 0.18 NEW J Window 195d Wall 4 (Back -195) - -- 1 27.5 0.28 0.18 NEW 4 Window * 1W40d Wall 2 (- specify -240) -- -- 1 24.0 0.28 0.18 NEW G Window �� 285d Wall 4 (- specify -28) -- -- 1 12.0 0.28 0.18 NEW 3 Window`' 285d Wall 4 (-specify -28) -- -- 1 40.0 0.28 0.18 NEW H Window , ��'' 285d Wall 4 (- specify -28) -- -- 1 12.0 0.28 0.18 Skylight 4 Skylight j,i Roof 3 (- specify --285) 1 1.2 0.30 0.30 Registration Number: CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: Report Version - CF111-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE IOD Project Name: Mattison Floyd Residence Ca culation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input.File Name: Mattison Floyd-JMA-14.xml Skylight 5 1 Skylight I Roof 3 (- specify –285) 1 1 1 1 1 1.2 1 0.30 1 0.30 CF*F-01- Page 7 of -13 DOORS 01 02 03 04 Name Side of Building Area (ft2) U -factor Door 45 15d Wall 2 28.0 0.50 OVERHANGS AND FINS 01 - - --02 --- – 03 �� 04 05 06 Construction Name Surface Type Construction Type `'� Framing 01 02 03 04 05 06 07- 08 09 10 11 12 13 14 Cavity/Frame: no insul. /2x4 Top Chrd Overhang Roof Truss @ 24 in. Left Fin Attic Roof Cons Attic Roofs Right Fin O.C. Window Depth Dist Up Left Extent Right Extent Flap Ht. ��+!�+�+ Cliepth Top Up DistL Bot Up Depth Top Up Dist R Bot Up NEW 13 12 0.1 12 12 0 'j ;ll- 0 0 0 0 O. G 0 0 NEW 14 12 0.1 12 12 0oi 0 0 0 0 0 0 0 0 .#W OPAQUE SURFACE CONSTRUCTIONS►v 01 - - --02 --- – 03 �� 04 05 06 Construction Name Surface Type Construction Type `'� Framing Total Cavity R -value Assembly Layers 2x4 Top Chord of Cavity/Frame: no insul. /2x4 Top Chrd Roof Truss @ 24 in. Roof Deck: Wood Siding/sheathing/decking Attic Roof Cons Attic Roofs Wood Framed Ceiling O.C. none Roofing: Light Roof (Asphalt Shingle) • Inside Finish: Gypsum Board Cavity/Frame: R-9.1 /2x4 R-38 Roof Attic Ceilings (below attic) Wood FraiQ"d:Ceiling 2x4 @ 16 in. O.C. R 38 Over Floor Joists: R-28.9 insul. Inside Finish: Gypsum Board • Cavity /Frame: R-38 / 2x4 A Roof Deck: Wood Siding/sheathing/decking R-38 Roof Atticl Cathedral Ceilings W Framed Ceiling 2x4 @ 16 in. O.C. R 38 Roofing: Light Roof (Asphalt Shingle) • Inside Finish: Gypsum Board O • Cavity/Frame: R-21 /2x6 R-21 Wall (W.21.2x6.16) Exterior Walls Wood Framed Wall 2x6 @ 16 in. O.C. R 21 Exterior Finish: Wood Siding/sheathing/decking .may Registration Number: CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIF40E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml CF*F-01` Page 8 of 13 OPAQUE SURFACES— Cathedral Ceilings 01 02 03 04 05 06 07 08 09 10 11 Name Zone Type Orientation Area (ft) Roof Rise (x in 12) Roof Pitch Roof Tilt (deg) Roof Reflectance Roof Emmittance Framing Factor Roof Kitchen Living Entry R-38 Roof Attic1 - specify - 32.1 3 0.25 14.04 0.1 0.85 0.1 Roof 2 Living Exiercise R-38 Roof Attic1 - specify - 3.3 3 0.25 14.04 0.1 0.85 0.1 Roof 3 Casita R-38 Roof Attic1 - specify - 2.5 3 0.25 14.04 0.1 0.85 0.1 SLAB FLOORS 01 01 02 03 04 Quality Insulation Installation (QII) Quality Installation of Sp�ray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa Not Required 01 02 03 JV04 05 06 07 Name Zone Area (ft2) Perimeter (ft) Edge Insul. R-value&_Depth Carpeted Fraction Heated Covered Slab Kitchen Living Entry 1564 y 270 None 0.8 No Covered Slab 2 Living Exiercise 940 A��' 90 None 0.8 No Covered Slab 3 - Master bedroom 1596 0% 115 None 0.8 No Covered Slab 4 . Casita 11301. V 1 185 None 0.8 No BUILDING ENVELOPE - HERS VERIFICATION 01 01 02 03 04 Quality Insulation Installation (QII) Quality Installation of Sp�ray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa Not Required Not Re}q fired Not Required -- fK WATER HEATING SYSTEMS 01 �`'� 02 03 04 Name '01C�''Distribution Type Number of Heaters Solar Fraction (%) DHW Sys 1 Ov Pipe Insulation, All Lines 1 0.0% WATER HEATERS 01 02 03 04 05 06 07 08 Tank Volume Energy Factor or Tank Exterior Standby Loss Name Heater Element T.y,pe Tank Type (gal) Efficiency Input Rating Insulation R -value (Fraction) DHW Heater 1 Natural.Ga`'ssO Small Storage 50 0.66 40000-Btu/hr 0 0 'ey Registration Number: CA Building Energy Efficiency Stan`da ds - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE JOD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml CF*F-01- Page 9 of 13 WATER HEATING - HERS VERIFICATION 01 02 03 04 05 06 07 Name Pipe Insulation Parallel Piping Compact Distribution Point -of Use Recirculation with Manual Control Recirculation with Sensor Control DHW Sys 1-hers-dhw n/a n/a n/a n/a 80 AFUE n/a HVAC SYSTEMS 01 02 03 04 05 06 07 Efficiency Heating Component 1 Heating System Cooling System Heating Component 2` CntrlFurnace - Fuel -fired central furnace 80 AFUE Heating Component 3 y ®` CntrlFurnace - Fuel -fired central furnace 80 AFUE Heating Component 4 Distribution 80 AFUE Floor Area Name System Type Name DucteB, Name Ducted System Fan System Served HVAC 1 kit liv entyl Other Heating and Cooling System Heating Component 1 es � Component 1 Cooling Yes Air Distribution System 1 HVAC Fan 1 1564 HVAC 2 liv exr2 Other Heating and Cooling System Heating Component 2 �Yes Cooling Component 2 Yes Air Distribution System 2 HVAC Fan 2 940 HVAC 3 master3 Other Heating and Cooling System Heating Componen�f3- Yes Cooling Yes Air Distribution HVAC Fan 3 1596 Component 3 System 3 HVAC 4 castia4 Other Heating and Cooling System Heating Component 4 Yes CCooling omponent 4 Yes System 4 Air Distribution HVAC Fan 4 1130 f 01 HVAC - HEATING SYSTEMS 01 �`�'� 02 03 Name ��� Type Efficiency Heating Component 1 � CntrlFurnace - Fuel -fired central furnace 80 AFUE Heating Component 2` CntrlFurnace - Fuel -fired central furnace 80 AFUE Heating Component 3 y ®` CntrlFurnace - Fuel -fired central furnace 80 AFUE Heating Component 4 A. t �'# CntrlFurnace - Fuel -fired central furnace 80 AFUE O� 'ems Registration Number: CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIF-0 OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE AOD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xmi CF*F-01- Page 10 of 13 HVAC - COOLING SYSTEMS 01 02 03 04 05 06 07 Name Verified Airflow Efficiency Verified EER Multi -speed Verified Refrigerant Charge Name System Type EER SEER Zonally Controlled Compressor HERS Verification Cooling Component 1 SplitAirCond - Split air conditioning 13 16.5 No No Cooling Component Required system Required Required Required Cooling Component 4 -hers -cool 1 -hers -cool Cooling Component 2 SplitAirCond - Split air conditioning 13 16.5 No No Cooling Component System 1 -hers -dist system Ducts located entirely in 2 -hers -cool Cooling Component 3 SplitAirCond - Split air conditioning 13 16.5 No No Cooling Component Conditioned Zone system System 2 -hers -dist %I Ducts located entirely in 3 -hers -cool Cooling Component 4 SplitAirCond -Split air conditioning 13 16I No No Cooling Component 8 system Conditioned Zone r System 3 -hers -dist Air Distribution System 4 4 -hers -cool HVAC COOLING - HERS VERIFICATION 01 02 03 — 04 05 06 Name Verified Airflow 2w Airflowjlget Verified EER Verified SEER Verified Refrigerant Charge Cooling Component 1 -hers -cool Required ^350 Required Required Required Cooling Component 2 -hers -cool Required `x350 Required Required Required Cooling Component 3 -hers -cool Required 350 Required Required Required Cooling Component 4 -hers -cool Required �� 350 Required Required Required HVAC - DISTRIBUTION SYSTEMS 01 02 03``'1 04 05 06 07 08 A`� Supply Duct Name Type Duct`Lre_akage Insulation R -value Location Return Duct Bypass Duct HERS Verification Air Distribution System 1 Ducts located entirely in .� Sealed and tested 8 Conditioned Zone Conditioned Zone None Air Distribution conditioned space A. System 1 -hers -dist Ducts located entirely in Air Distribution Air Distribution System 2 conditioned space _ Q'S aled and tested 8 Conditioned Zone Conditioned Zone None System 2 -hers -dist Ducts located entirely in Air Distribution Air Distribution System 3 A; conditioned space � Sealed and tested 8 Conditioned Zone Conditioned Zone None System 3 -hers -dist Air Distribution System 4 Ducts located entirely i6 Sealed and tested 8 Conditioned Zone Conditioned Zone None Air Distribution conditioned sp;i`'* System 4 -hers -dist .0 Registration Number: CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml CF*F-01- Page 11 of 13 HVAC DISTRIBUTION - HERS VERIFICATION 01 02 03 04 05 06 Name Duct Leakage Verification Duct Leakage Target (%) Verified Duct Location Verified Duct Design Return Supply Air Distribution System 1 -hers -dist Required 6.0 Not Required Not Required Not Required Air Distribution System 2 -hers -dist Required 6.0 Not Required Not Required Not Required Air Distribution System 3 -hers -dist Required 6.0 Not Required Not Required Not Required Air Distribution System 4 -hers -dist Required 6.0 Not Required Not Required Not Required HVAC -FAN SYSTEMS co 020`" _ 01 02 ,ll� 03 04 . Name Type ��►" Fan Power (Watts/CFM) HERS Verification HVAC Fan 1 Single Speed PSC Furnace Fan 0.58 Required HVAC Fan 2 Single Speed PSC Furnace Fan Q�.Y 0.58 Required HVAC Fan 3 Single Speed PSC Furnace Fang 0.58 Required HVAC Fan 4 Single Speed PSC Furnaceiran _ 0.58 Required HVAC FAN SYSTEMS - HERS VERIFICATION co 020`" _ 01 l 02 03 Name `W VerifiedFanWatt Draw Required Fan Efficiency (Watts/CFM) HVAC Fan 1 -hers -fan S* Required 0.58 HVAC Fan 2 -hers -fan A'4� Required 0.58 HVAC Fan 3 -hers -fan —�v Required 0.58 HVAC Fan 4 -hers -fan 4t� Required 0.58 ,p �40 IAQ (Indoor Air Quality) FANS A* *40 01 020`" 03 04 05 06 IAQ Recovery Name IAQ CFM IAQ Watts/CFM IAQ Fan Type Effectiveness(%) HERS Verification SFam IAQVentRpt 149.8'r 0.25 Default 0 Required Registration Number: CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIFO OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xm1 CF — F -01 - Page 12 of 13 COOLING VENTILATION 01 02 03 04 05 Name Cooling Vent CFM Cooling Vent Watts/CFM Number of Fans HERS Verification WH Fan 1 61 0.52459 1 Required WH Fan 2 61 0.52459 1 Required WH Fan 3 61 0.52459 1 Required WH Fan 4 61,' 0.52459 1 Required Registration Number: i® Registration Date/Time: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 CERTIF& OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE i *OD Project Name: Mattison Floyd Residence Calculation Date/Time: 09:49, Fri, Oct 03, 2014 Calculation Description: Title 24 Analysis Input File Name: Mattison Floyd-JMA-14.xml CF*F-01- Page 13 of 13 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Jon Scott Documentation Author Sign Company: Signature Date: Scott Design and Title 24, Inc, 10/3/2014 Address: CEA/HERS Certification Identification (If applicable): 77-085 Michigan Drive City/State: Palm Desert, CA 92211 Phone: %1- (7 0) 200-4780 RESPONSIBLE PERSON'S DECLARATION STATEMENT�/- I certify the following under penalty of perjury, under the laws of the State of California: .� l� 1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance. 1 Title Part 2. certify that the energy features and performance specifications identified on this Certificate, fj'C=ompliance conform to the requirements f 24, Part 1 and 6 of the California Code of Regulations. vV 3. The building design features or system design features identified on this Certificate of Compliance are consistent with the informatio pro ded on other applicable. compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency-Ywfo� approval with this building permit applic_ tion. Responsible Designer Name: Responsible Designer Signature: JMA Architecture and Engineering .�I� AI V Company: W Date Signed: JMA Architecture and Engineering Address: 4%— License: 73-995 EI Paseo Suite 203 44�,�ZG% City/State/Zip: Phone: Palm Desert, CA 92260 ,�� (760) 346-6155 14F .,490 Registration Number: t� CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-09042014-650 HERS Provider: Report Generated at: 2014-10-03 09:53:12 L' • • RESIDENTIAL MEASURES SUMMARY RMS -1 Project Name Mattison Floyd Residence Building Type 10 Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 10/3/2014 Project Address 53-005 Latrobe Lane La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 5,230 Addition n/a # of Units 4 INSULATION Construction Type Cavity Area ftz) Special Features Status Roof Wood Framed Attic R38 5,192 New Wall Wood Framed R 21 11,222 New Slab Unheated Slab -on -Grade - no insulation 5,230 Perim = 660' New Demising Wood Framed R 13 4,440 New Door Opaque Door no insulation 28 New FENESTRATION Orientation Area ft2 Total Area: 1,502 Glazin Percentage: 28.7%1New/Altered U -Fac SHGC Overhang Sidefins Average U -Factor: 0.27 Exterior Shades Status Skylight 32.0 0.460 0.53 none none None New Front (N) 233.3 0.280 0.18 none none Bug Screen New Left (E) 293.6 0.280 0.18 none none Bug Screen New Left (E) 176.0 0.240 0.18 12.0, none Bug Screen New Rear (S) 199.0 0.280 0.18 none none Bug Screen New Rear (S) 187.0 0.240 0.18 12.0 none Bug Screen New Front (NE) 228.6 0.280 0.18 none none Bug Screen New Skylight 1.6 0.300 0.30 none none None New Skylight 1.6 0.300 0.30 none none None New Front (NE) 52.5 0.280 0.18 none none Bug Screen New Left (SE) 45.0 0.280 0.18 none none Bug Screen New Rear (SVIO 49.5 0.280 0.18 none none Bug Screen New Skylight 1.2 0.300 0.30 none none None New Skylight 1.2 0.300 0.30 none none None New HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 Central Furnace 80% AFUE Split Air Conditioner 16.5 SEER Setback New 1 Central Furnace 80% AFUE Split Air Conditioner 16.5 SEER Setback New 1 Central Furnace 80% AFUE Split Air Conditioner 16.5 SEER Setback New HVAC DISTRIBUTION Location Heating Cooling Duct Location Duct R -Value Status HVAC 1 kit liv enty Ducted Ducted Conditioned 8.0 New HVAC 2 liv exr Ducted Ducted Conditioned 8.0 New HVAC 3 master Ducted Ducted Conditioned 8.0 New WATER HEATING Qt . Type Gallons Min. Eff Distribution Status 1 Small Storage Gas 50 0.66 All Pipes Ins New Ene Pro6.3 by EnemySoft User Number.' 6712 RunCode: 2014.10-03T09:59:22 ID: Pae 16 of 41 • .J R SIDENTIAL MEASURES SUMMARY RMS -1 Project Name Mattison Floyd Residence Building Type m Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 10/3/2014 Project Address 53-005 Latrobe Lane La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 5,230 Addition n/a # of Units 4 INSULATION Construction Type Area Cavity (ft) Special Features Status FENESTRATION I Total Area: 1,5021 Glazing Percentage: 28.7 New/Altered Average U -Factor: 0.27 Orientation Area ft2 U -Fac SHGC Overhang Sidefins Exterior Shades Status HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 Central Furnace 80% AFUE Split Air Conditioner 16.5 SEER Setback New HVAC DISTRIBUTION Location Heating Duct Cooling Duct Location R -Value Status HVAC 4 castia Ducted Ducted Conditioned 8.0 New WATER HEATING Qty. Type Gallons Min. Eff Distribution Status EnemyPro 6.3 by EnemySoft User Number: 6712 RunCode: 201410-03T09:59:22 /D: Pae 17 of 41 4 r 4 MANDATORY MEASURES SUMMARY: Residential (Page 1 of 3 MF -1 R Project Name Date Mattison Floyd Residence 1101312014 NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF - 1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated into the permit documents, and the applicable features shall be considered by all parties as minimum component performance specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R Form with plans. Building Envelope Measures: 110.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. §110.6(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a). 110.7: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed. 110.8(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -2R Form. §110.8(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §110.8(i) when the installation of a Cool Roof is specified on the CF -1 R Form. *§1 50.0 a : Minimum R-30 R-19 for Additions/Alterations insulation in wood -frame ceiling orequivalent U -factor. 150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value. *§1 50.0 c : Minimum R-13 insulation in 2x4 wood -frame wall R-19 in 2x6 orequivalent U -factor. *§1 50.0 d : Minimum R-19 insulation in raised wood -frame floor orequivalent U -factor. 150.0 : Air retarding wrap is tested labeled, and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form. 150.0 : Mandatory Vapor barrier installed in Climate Zones 14 or 16. §150.0(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance rate is no greater than 2.0 erm/inch and shall be protected from physical damage and UV light deterioration. §150.0(q) Fenestration Products. Fenestration separating conditioned space from unconditioned space or outdoors shall meet the requirements of either Item 1 or 2 below.- elow:1. 1.Fenestration, including skylight products, must have a maximum U -factor of 0.58. 2. The weighted average U -factor of all fenestration, including skylight products, shall not exceed 0.58. EXCEPTION to Section 150.0(q)1: Up to 10 square feet of fenestration area or 0.5 percent of the Conditioned Floor Area, whichever is greater, is exempt from the maximum U -factor requirement. 150.0 r Solar Ready Buildings. Shall meet the requirements of Section 110.10 applicable to the building project. Fireplaces, Decorative Gas Appliances and Gas Log Measures: 150.0 a 1A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox. §150.0(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device. §150.0(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited. Space Conditioning, Water Heating and Plumbing System Measures: §110.0-§110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy Commission. §110.3(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release valve, backflow prevention, pump isolation valve and recirculation loop connection requirements of §110.3(c)5 §110.5: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and spa heaters. §150.0(h): Heating and/or cooling loads are calculated in accordance with ASHRAE SMACNA or ACCA. §150.00): Heating systems are equipped with thermostats that meet the setback requirements of Section 11 0.2 c . §150.00)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped with insulation having an installed thermal resistance of R-12 or greater. §150.00)113: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank. EnergyPro 6.3 by EnergySoft User Number: 6712 /D: Page 18 of 41 4 MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R Project Name Date Mattison Floyd Residence 1101312014 §150.00)2A: All domestic hot water system piping conditions listed below, whether buried or unburied, must be insulated per TABLE 120.3-A. i. The first 5 feet (1.5 meters) of hot and cold water pipes from the storage tank. ii. All piping with a nominal diameter of 3/4 inch (19 millimeter) or larger. iii. All piping associated with a domestic hot water recirculation system regardless of the pipe diameter. iv. Piping from the heating source to storage tank or between tanks. v. Piping buried below grade. vi. All hot water pipes from the heating source to the kitchen fixtures. §150.00)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table 120.3-A. 150.0(j)3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. §150.00)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation. §150.0(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections 601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal o enin s greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used §150.0(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. §150.0(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. 150.0(m)7: Exhaust fans stems have back draft or automatic dampers. §150.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers. §150.0(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. 150.0 m 10: Flexible ducts cannot have porous inner cores. §150.0(n)1: Systems using gas or propane water heaters, whether tank or on -demand, to serve individual dwelling units shall include all the following components : A. A 120V electrical receptacle that is within 3 feet from the water heater and accessible to the water heater with no obstructions; B. A Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the space where the water heater is installed; C. A condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining without pump assist, D. A gas supply line with a capacity of at least 200,000 Btu/hr. §150.0(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2 Ventilation and Acceptable Indoor Air Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in Section 4 of that Standard. Pool and Spa Heating Systems and Equipment Measures: §110.4(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating ora pilot light. §110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction and return lines or built-up connections for future solar heating. 110.4(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover. §110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or programmed to run only during off-peak electric demand periods. 150.0 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150.0 Residential Lighting Measures: §150.0(k)1A: Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with Section 150.0(k) in accordance with TABLE 150.0-A or TABLE 150.0-B as applicable. 150.0 k 1C: The wattage of permanently installed luminaires shall be determined asspecified by §130.0(c). 150.0 k 1 D: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency <= 20 kHz. §150.0(k)1 E: Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no more than five watts of power per luminaire or exhaust fan as determined in accordance with Section 130.0(c). Night lights shall not be required to be controlled by vacancy sensors. EnergyPro 6.3 by EnergySoft User Number: 6712 /D: Page 19 of 41 • C. MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1R Project Name Date Mattison Floyd Residence 1101312014 150.0 k 1 F: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150.0(k). 150.0(k)2: All switching devices and controls shall meet the requirements of §150.0(k)2. §150.0(k)3: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy. EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft' or 100 watts for dwelling units larger than 2,500 ft2 may be exempt from the 50 percent high efficacy requirement when all lighting in the kitchen is controlled in accordance with the applicable provisions in Section 150.0(k)2, and is also controlled by vacancy sensors or dimmers. §150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated cabinet. §150.0(k)5: Lighting installed in bathrooms shall meet the following requirements: A. A minimum of one high efficacy luminaire shall be installed in each bathroom; and B. All other lightinq installed in each bathroom shall be high efficacy or controlled by vacancy sensors. §150.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and controlled by vacancy sensors. §150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high efficacy, or shall be controlled by either dimmers or vacancy sensors. EXCEPTION 1: Luminaires in closets less than 70 square feet. EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site. §150.0(k)8: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the luminaire is airtight with air leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between the luminaire housing and ceiling. §150.0(k)9A: For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements: i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of items ii or iii below; and ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically reactivates the motion sensor within 6 hours iii. Controlled by one of the following methods: a. Photocontrol not having an override or bypass switch that disables the photocontrol; or b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of an astronomical time clock in accordance with Section 110.9; meets the Installation Certification requirements in Section 130.4; meets the requirements for an EMCS in Section 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and, is programmed to automatically turn the outdoor lighting OFF during daylight hours. §150.0(k)9A: For low-rise multi -family residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the following requirements: i. Shall comply with Section 150.0(k)9A; or ii. Shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0. §150.0(k)9: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by Section 150.0(k)9B or Section 150.0(k)9D shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0. §150.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply with the applicable requirements in Sections 110.9 130.0, 130.2, 130.4, 140.7, and 141.0. §150.0(k)10: Internally illuminated address signs shall comply with Section 140.8; OR not contain a screw -base socket, and consume no more than five watts of power as determined according to §130.0(d). §150.0(k)11: Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for nonresidential garages in Sections 110.9, 130.0, 130.1, 130.4, 140.6, and 141.0. §150.0(k)12A. In a low-rise multi -family residential building where the total interior common area in a single building equals 20 percent or less of the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or controlled by an occupant sensor. §150.0(k)12B. In a low-rise multi -family residential building where the total interior common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building shall: . i. Comply with the applicable requirements in Sections 110.9, 130.0, 130.1, 140.6, and 141.0; and ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of ingress and egress. EnergyPro 6.3 by EnergySoft User Number: 6712 /D: Page 20 of 41 r- 4 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name attison Floyd Residence Date 10/3/2014 System Name HVAC 1 kit liv enty Floor Area 1,564 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING CFM Sensible Total Room Loads 4,024 38,494 Return Vented Lighting 0 Return Air Ducts 557 Return Fan 0 Ventilation 469 20,841 Supply Fan 0 Supply Air Ducts 557 TOTAL SYSTEM LOAD 1 60,450 PEAK COIL HTG. PEAK Heating System Latent CFM Sensible Output per System 110,000 3,741 852 36,735 Total Output Btuh 110,000 Output Btuh/s ft 70.3 437 Cooling System 0 Output per System 58,000 3,968 469 22,867 Total Output Btuh 58,000 7,708 0 Total Output Tons 4.8 437 Total Output Btuh/s ft 37.1 Total Output s ft/Ton 323.6 60,476 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow cfm 2,000 CARRIER 24ANB760-58MVB110 41,088 12,509 110,000 Airflow cfm/s ft 1.28 Airflow cfm/Ton 413.8 Outside Air % 23.5% Total Adjusted System Output 41,088 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 12,509 Aug 3 PM 110,000 Outside Air cfm/s ft 0.30 Note: values above given at ARI conditions I1 I Jan 1 AM HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF Outside Air 469 cfm 72 OF 4 61 OF 113 OF 113 OF 0. f n.� Pi Heating Coil Supply Fan 2,000 cfm 113 °F ROOM 72 OF 3 4 COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112/78°F Outside Air Arc 469 cfm 70/64°F 80/67°F 61/60°F 61/60°F Cooling Coil Supply Fan 61 / 60 OF 2,000 cfm - - - 70.7 % ROOM 70/64°F EnergyPro 6.3 by Energ Soft User Number: 6712 Run Code: 201410-03T09:59:22 /D: Page 21 of 41. 4 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Date Mattison Floyd Residence 10/3/2014 System Name Floor Area HVAC 2 liv exr 940 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING PEAK COIL HTG. PEAK Heating System CFM Sensible Total Room Loads 1,532 20,328 Return Vented Lighting 0 Return Air Ducts 294 Return Fan 0 Ventilation 282 12,563 Supply Fan 0 Supply Air Ducts 294 TOTAL SYSTEM LOAD 1 33,4801 Latent CFM Sensible Output per System 110,000 2,248 365 17,490 Total Output Btuh 110,000 Output Btuh/s ft 117.0 208 Cooling System 0 Output per System 58,000 4,258 282 13,776 Total Output Btuh 58,000 6,506 0 Total Output Tons 4.8 208 Total Output Btuh/s ft 61.7 Total Output s ftrron 194.5 31,682 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow cfm 2,000 CARRIER 24AN8760-58MVB110 39,685 11,205 110,000 Airflow cfm/s ft 2.13 Airflow cfm/Ton 413.8 Outside Air % 14.1% Total Adjusted System Output 39,685 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 11,205 Aug 3 PM 110,000 Outside Air cfm/s ft 0.30 Note: values above given at ARI conditions I Jan 1 AM HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF 65 OF 117 OF 117 OF Outside Air f (ilk 282 cfm Heating Coil Supply Fan 2,000 cfm 117 °F ROOM 72 OF 72 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112/78°F 76/64°F 57/56°F 57/56°F 0' Outside Air 282 cfm Cooling Coil Supply Fan 58 / 57 OF 2,000 cfm - - 62.0Bio ROOM 70/61 OF 70/61 OF Energ Pro 6.3 by Energ Sok User Number: 6712 Run Code: 201410-03709:59:22 /D: Page 22 of 41 4 4 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name attison Floyd Residence Date 10/3/2014 System Name HVAC 3 master Floor Area 1,596 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL CFM Total Room Loads 2.121 Return Vented Lighting Return Air Ducts Return Fan Ventilation 479 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK COIL HTG. PEAK Heating System Sensible Latent CFM Sensible Output per System 110,000 20,354 3,817 544 23,402 Total Output Btuh 110,000 0 Output Btuh/s ft 68.9 295 278 Cooling System 0 0 Output per System 58,0001 21,330 3,944 479 23,373 Total Output Btuh 58,000 0 7,761 0 Total Output Tons 4.8 295 278 Total Output Btuh/s ft 36.3 Total Output s ft/Ton 330.2 42,274 47,332 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow cfm 2,000 CARRIER 24ANB760-58MVB110 41,112 12,566 110,000 Airflow cfm/s ft 1.25 Airflow cfm/Ton 413.8 Outside Air % 23.9% Total Adjusted System Output 41,112 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 12,566 Aug 3 PM 110,000 Outside Air cfm/s ft 0.30 Note: values above given at ARI conditions Jan 1 AM HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heatin Peak 26 OF Outside Air 479 cfm 72 OF 61 OF 113 OF 113 OF f`•,� Heating Coil Supply Fan 2,000 cfm 112 °F ROOM 72 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112/78°F Outside Air 479 cfm 70/64°F 80/67°F 61/60°F 61/60°F Cooling Coil Supply Fan 61 / 60 OF 2,000 cfm — - - 71.0% ROOM 70/64°F -A a I Energ Pro 6.3 by Energ Soft User Number: 6712 Run Code: 201410-03709:59:22 /D: Page 23 of 41 4 4 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name attison Floyd Residence Date 10/3/2014 System Name HVAC 4 castia Floor Area 1,130 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL CFM Total Room Loads 1,612 Return Vented Lighting Return Air Ducts Return Fan Ventilation 339 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK COIL HTG. PEAK Heating System Sensible Latent CFM Sensible Output per System 110,000 19,524 2,703 569 26,400 Total Output Btuh 110,000 0 Output Btuh/s ft 97.3 283 314 Cooling System 0 0 Output per System 58,000 15,104 4,405 339 16,542 Total Output Btuh 58,000 0 7,108 0 Total Output Tons 4.8 283 314 Total Output Btuh/s ft 51.3 Total Output s ft/Ton 233.8 35,194 43,570 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow cfm 2,000 CARRIER 24ANB760-58MVB110 39,898 11,855 110,000 Airflow cfm/s ft 1.77 Airflow cfm/Ton 413.8 110,000 Jan 1 AM Outside Air (%) 17.0% Total Adjusted System Output 39,898 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 11,855 Aug 3P ml Outside Air cfm/s ft 0.30 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF Outside Air 339 cfm 72 OF 64 OF 116 OF 116 OF fC�lr� Heating Coil Supply Fan o 2,000 cfm 116 F ROOM 72 OF 4 COOLING SYSTEM PSYCHROMETICS Airstream.Tem eratures at Time of Cooling Peak 112/78°F Outside Air Ar 339 cfm 70/62°F 77/65°F 58/58°F 58/58°F c O c Cooling Coil Supply Fan 59 / 58 OF 2,000 cfm — - - 64.8% I ROOM 70/62°F I EnergyPro 6.3 by Energ Soft User Number: 6712 Run Code: 2014-10-03T09:59:22 /D: Page 24 of 41 • is 0 ROOM LOAD SUMMARY Project Name Date Mattison Floyd Residence 10/3/2014 System Name Floor Area HVAC.1 kit liv enty 1,564 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK Zone Name Room Name Mult. CFM 1,Sensible I Latent CFM Sensible Latent I CFMSensible Kitchen Living Entry Kitchen Living Entry 1 41024 { 38,494 .3,741 4,0241 38,4941 3,7411 852 36735 PAGE TOTAL TOTAL * 1 4,024 38,494 3,741 852 36,735 4,0241 38,4941 3,7411 852 36, 735 1.' Total includes ventilation load for zonal systems. I EnergyPro 6.3 by EnemySoft User Number: 6712 RunCode: 201410-03T09:59:22 /D• Page 25 of 41 • .7 • ROOM LOAD SUMMARY Project Name Date Mattison Floyd Residence 10/3/2014 System Name Floor Area HVAC 2 liv exr 940 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult. I CFM Sensible Latent CFM Sensible Latent CFM Sensible Living Exiercise Living Exiercise 1 1,532 20,328 2,248 1,5321 20,3281 2,248 3651 17,490 PAGE TOTAL TOTAL' 1,5321 20, 328 2,2481 365 17,490 1, 532 20, 328 2, 248 365 17, 490 ' Total includes ventilation load for zonal systems. EnergyPro 6.3 by EnerqySoft User Number: 6712 Run Code: 201410-03709:59:22 /D: Page 26 of 41 i • • ROOM LOAD SUMMARY Project Name Date Mattison Floyd Residence 101312014 System Name Floor Area HVAC 3 master 1,596 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult. I CFM I Sensible I Latent CFM I Sensible Latent CFM I Sensible Master bedroom Master bedroom 1 1 2,1211 20,3541 3,817 2,1211 20,3541 3,817 5441 23,402 PAGE TOTAL TOTAL* 2,121 20,3541 3,8171 544 23,41992 2,121 20, 354 3, 817 544 23, 402 * Total includes ventilation load for zonal systems. EnergyPro 6.3 by EnemySoft User Number: 6712 Run Code: 201410-03T09:59:22 /D: Page 27 of 41 is • ROOM LOAD SUMMARY Project Name Date Mattison Floyd Residence 101312014 System Name Floor Area HVAC 4 cash. 1,130 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name I Mult. I CFM I Sensible Latent CFM Sensible Latent CFM I Sensible Casita Casita 1 1 1 1,6121 19,5241 2, 703 1,6121 19, 524 2,7031 5691 26,400 PAGE TOTAL TOTAL* 1,6121 19,5241 2,7031 569 26,400 1,612 19,524 2,703 569 26,400 * Total includes ventilation load for zonal systems. EnergyPro 6.3 by EnemySoft User Number. 6712 Run Code: 2014-10-03709:59:22 /D: Page 28 of 41 9 ROOM HEATING PEAK LOADS Project Name Mattison Floyd Residence Date 10/3/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Kitchen Living Entry Floor Area 1,564.0 ft2 Indoor Dry Bulb Temperature 72 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area U -Value X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT 'F = _ = = _ = c = = = = = = = = = = = = = = = = = = = = = = = 46 Btu/hr R-38 Roof Attic 1,532.0 X 0.0260 46 1,832 skylight 32.0 X 0.4600 46 677 R-21 Wall (W.21.2x6.16) 3,242.5 X 0.0690 46 10,292 Low -E Vinyl 368.5 X 0.2800 46 4,746 IivLow-E Vinyl 363.0 X X 0.2400 46 4,008 Slab -On -Grade perim = 270.0 0.7300 46 9,067 'R-13 Wall 1,364.0 X 0.1020 0 0 X X X X X X X X X X X X X X X X X X X X X X X X Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.064 Schedule Air Sensible Fraction through an interior surface X 1,564 X Area to another room 18.00 X 0.266 Ceiling Height ACH Page Total /60] X AT 30,621 _ 6,114 TOTAL HOURLY HEAT LOSS FOR ROOM 36,735 EnergyPro 6.3 by EnergySoft User Number- 6712 RunCode: 201410-03709:59:22 /D: Page 29 of 41. 0 0 • ROOM HEATING PEAK LOADS Project Name Mattison. Floyd Residence. Date 10/3/2014 °ROOM INFORMATION DESIGN CONDITIONS Room Name Living Exiercise Floor Area 940.0 ft2 Incloor.Dry Bulb Temperature 72 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X to Ceiling U -Value X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT *F 46 c 46 c 46 = 46 _ 46 = 46 _ 0 = = = = = = = = = = = = = = = = = = = = = = = = = Page Total /60] X 46 AT Btu/hr R-38 Roof Attic 936.8 0.0260 1,120 st skylite 3.2 0.3000 44 R-21 Wall (W.21.2x6.16) 1,823.9 0.0690 5,789 Wood Door 28.0 0.5000 644 Low -E Vinyl 248.1 0.2800 3,196 Slab -On -Grade perim = 90.0 0.7300 3,022 'R-13 Wall 740.0 0.1020 0 Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.064 Schedule Air Sensible Fraction through an interior surface X 940 X Area another room 18.00 X 0.266 Height ACH 13,815 = 3,674 TOTAL HOURLY HEAT LOSS FOR ROOM 17,490 EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 2014.10-03709:59:22 /D: Page 30 of 41 • ROOM HEATING PEAK LOADS Project Name Mattison,Floyd Residence Date 10/3/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Master bedroom Floor Area 1,596.0 ft2 Indoor Dry Bulb Temperature 72 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X to Ceiling U -Value X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT OF _ _ c = _ = = = = _ = = = = = = = = = = = = = = = = = = = = = 46 Btu/hr R-38 Roof Attic 1,596.0 0.0260 46 1,909 R-21 Wall (W.21.2x6.16) 2,594.9 0.0690 46 8,236 Low -E Vinyl 245.1 0.2800 46 3,157 Slab -On -Grade penim = 115.0 0.7300 46 3,862 'R-13 Wall 1,396.0 0.1020 0 0 Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.064 Schedule Air Sensible Fraction through an interior surface X 1,596 X Area another room 18.00 X 0.266 Height ACH Page Total /60] X AT 17,164 = 6,239 TOTAL HOURLY HEAT LOSS FOR ROOM 23,402 EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 2014-10-03709:59:22 /D: Page 31 of 41 • ROOM HEATING PEAK LOADS Project Name Mattison Floyd Residence Date 10/3/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Casita Floor Area 1,130.0 ft2 Indoor Dry Bulb Temperature 72 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X to Ceiling U -Value X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT *F = = = c = c = = = = = = = = = = = = = = = = = = = = = = = 46 Btu/hr R-38 Roof Attic 1,127.6 0.0260 46 1,349 st skylite 2.4 0.3000 46 33 R-21 Wall (W.21.2x6.16) 3,560.2 0.0690 46 11,300 Low -E Vinyl 239.8. 0.2800 46 3,089 Slab -On -Grade perim = 185.0 0.7300 46 6,212 'R-13 Wall 940.0 0.1020 0 0 Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.064 Schedule Air Sensible Fraction through an interior surface X 1,130 X Area another room 18.00 X 0.266 Height ACH Page Total /60] X AT 21.983 0 4,417 TOTAL HOURLY HEAT LOSS FOR ROOM 26,400 EnergyPro 6.3 by EnergySoft User Number: 6712 Run Code: 201410-03T09:59:22 ID: Page 32 of 41 • RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Mattison Floyd Residence 10/3/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Kitchen Living Entry Outdoor Dry Bulb Temperature 112 OF Floor Area 1,564.0 ft2 Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranoe: 34 OF Opaque Surfaces R-38 Roof Attic R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) "R-13 Wall Orientation (tM (N) (E) (S) (NE) Items shown with an asterisk (") denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = = = = = = = = = 1,532.0 0.0260 77.0 757.5 0.0690 32.0 991.0 0.0690 43.7 933.0 0.0690 42.7 561.0 0.0690 32.9 1,364.0 0.1020 0.0 0.0 14.5 22.5 16.7 0.0 14.5 16.0 16.7 0.0 14.5 48.0 Page Total Fa_nPctratinn Skylight NEW A NEW 1 NEW B NEW C NEW E NEW 2 NEW F NEW X OriPntatinn (W) (N) (N) (N) (N) (N) (N) (N) (E) Shaded Unshaded Area X X X X X X X X X GLF + + + + + + + + + Area X X X X X X X X X GLF = = = = - = = = - 0.0 36.3 32.0 162.2 0.0 14.5 20.0 16.7 0.0 14.5 40.0 16.7 0.0 14.5 20.0 16.7 0.0 14.5 22.5 16.7 0.0 14.5 16.0 16.7 0.0 14.5 48.0 16.7 0.0 14.5 16.0 16.7 0.0 14.5 3.0 Page Total 3,067 1,673 2,986 2,747 1,272 11, rstuinr 5,190 335 669 335 376 268 803 268 91 8,33 Internal Gain Btu/hr- Occupants tu/hrOccu ants 4 7 Occupants X 245 Btuh/occ. = 1,1 Equipment 1,564 Floor Area X 0.50 w/sqft = 6 Infiltration: 1.064 X 0.94 X 129.02 X Air Sensible CFM ELA AT I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 38494 .Latent Gain Btu/hr Occupants 4 7 Occupants X 155 Btuh/occ. = 727 Infiltration: 4,771 X 0.94 X 129.02 X 0.00523 = 3,013 Air Sensible CFM ELA AW • TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 797 2014-1 • • RE'SIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Mattison Floyd Residence 7 10/3/2014 ROOM. INFORMATION I DESIGN CONDITIONS Room Name Kitchen Living Entry Outdoor Dry Bulb Temperature 112 OF Floor Area 1,564.0 ftz Outdoor Wet Bulb Temperature 78 OF Indoor.Dry Bulb Temperature 70 OF Outdoor Daily Ranqe: 34 OF Surfaces Orientation Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = = = = = = = = = GLF = = = = = = = = 0.0 14.5 3.0 30.4 0.0 14.5 3.0 30.4 0.0 14.5 20.0 30.4 0.0 14.5 24.0 30.4 ' 13.7 0.0 29.6 0.0 14.5 48.0 22.0 187.0 13.7 0.0 Page Total FP_nP_Ctrnfinn NEW X NEW X NEW 11 NEW 12 NEW 13 NEW Z NEW 14 NEW 2A NEW 2A. Gain r)riontatinn (E) (E) (E) (E) (E) (S) (S) (S) (S) Shaded Unshaded Area X X X X X X X X X GLF + + + + + + + + + Area X X X X X X X X X GLF = = = = = = = = 0.0 14.5 3.0 30.4 0.0 14.5 3.0 30.4 0.0 14.5 20.0 30.4 0.0 14.5 24.0 30.4 176.0 13.7 0.0 29.6 0.0 14.5 48.0 22.0 187.0 13.7 0.0 21.2 0.0 14.5 5.0 22.0 0.0 14.5 5.0 Page Total 4.7 Occupants X 245 Btuh/occ. 1,564 Floor Area X 0.50 w/sqft = Infiltration: 1.064 X 0.94 X 129.02 X 42 = Air Sensible CFM ELA AT AL HOURLY SENSIBLE HEAT GAIN FOR ROOM Latent Gain 4.7 Occupants X I Btuh/occ. _ Infiltration: 4,771 X 0.94 X 129.02 X 0.00523 = Air Sensible CFM ELA AW Btu/hr Btu/hr 91 91 608 729 2,412 1,056 2,563 110 110 7,771 Btu/hr 1,150 2,669 5,393 38,494 Btulhr 727 3,013 727 1 EnemyPro 6.3 by EnergySoR User Number: 6712 RunCode: 2014-16-03T09:59:22 /D: Page 34 of 41 • • • RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Mattison Floyd Residence 1 710/3/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Kitchen Living Entry Outdoor Dry Bulb Temperature 112 OF Floor Area 1,564.0 ft2 Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature 70 OF I Outdoor Daily Range: 34 OF Opaque Surfaces Orientation Area U -Factor CLTD' Btulhr X X - X X = X X = X X = X X = X X = X X = X X = X X = Page Total 0 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr NEW 2A (S) 0.0 X 14.5 + 5.0 X 22.0 = 110 NEW 2A (S) 0.0 X 14.5 + 5.0 X 22.0 = 110 NEW (NE) 0.0 X 14.5 + 65.0 X 18.7 = 1,213 X + X = X + X X + X = X + X - X + X = X + X = Page Total 1,433 Internal Gain Btu/hr Occupants 4.7 Occupants X 245 Btuh/occ. = 1,150 Equipment 1,564 Floor Area • X 0.50 w/s4 ft = 2,669 Infiltration: 1.064 X 0.94 X 129.02 X 42 5,393 Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 38,494 Latent Gain Btu/hr Occupants 4.7 Occupants X 155 Btuh/occ. = 727 Infiltration: 4,771 X 0.94 X 129.02 X 0.00523 = 3,013 Air Sensible CFM ELA AW TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 727 EnergyPro 6.3 by Ene Soft User Number: 6712 Run Code: 201410-03709:59:22 /D: Page 35 of 41 • RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Mattison Floyd Residence ROOM INFORMATION DESIGN, CONDITIONS Room Name Living Exiercise Outdoor Dry Bulb Temperature Floor Area 940.0 ft2 Outdoor Wet Bulb Temperature Indoor Dry Bulb Temperature 70 OF Outdoor Daily Range: 0nanup Surfacac R-38 Roof Attic R-21 Wall (W.21.2x6.16) Wood Door R-21 Wall (W.21.2x6.16) R-21 Wall (W 21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) 'R-13 Wall Orientation (N) (N) (NE) (E) (SE) (S) (NE) Date 10/3/2014 Area X X X X X X X X X U -Factor X X X X X X X X x CLTD' = = = = = = = = = 936.8 0.0260 77.0 532.0 0.0690 32.0 28.0 0.5000 33.3 94.5 0.0690 37.3 639.9 0.0690 43.7 97.5 0.0690 41.3 230.0 0.0690 42.7 230.0 0.0690 32.9 740.0 0.1020 0.0 Items shown with an asterisk (`) denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestration •NEW Skylight Skylight 2R NEW 2S NEW 2U NEW 2V NEW 2W NEW 2T 0.0 Internal Gain 0 Orientation (tM (IM (NE) (E) (E) (E) (E) (SE) Page Total Shaded Unshaded Area X X X X x X X X X GLF + + + + + + + + + Area X X X X X X X X x GLF = = = = = = = = = 0.0 21.3 1.6 92.6 0.0 21.3 1.6 92.6 0.0 14.5 25.5 24.3 0.0 14.5 59.5 30.4 0.0 14.5 59.2 30.4 0.0 14.5 22.2 30.4 0.0 14.5 59.2 30.4 0.0 14.5 22.5 28.0 Page Total 2.8 Occupants X 245 Btuh/occ. 940 Floor Area X 0.50 w/sqft = Infiltration: 1.064 X 0.94 X 77.54 X 42 = Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM ,Latent Gain 2.8 Occupants X I Btuh/occ. _ Infiltration: 4,771 X 0.94 X 77.54 X 0.00523 = Air Sensible CFM ELA AW User :59:22 112 OF 78 OF 34 OF Btu/hr 1,875 1,175 467 243 1,928 278 677 522 0 7,165 Btu/hr 148 148 620 1,808 1,799 675 1, 799 630 7,627 Btu/hr 691 1,604 3,241 20,328 Btu/hr 437 1,811 437 e36of41 • • [ktSIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Mattison Floyd Residence 10/3/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Master bedroom Outdoor Dry Bulb Temperature 112 OF Floor Area 1,5960 ft2 Outdoor Wet Bulb Temperature 78 OF Indoor Dry.Bulb Temperature 70 OF Outdoor Daily Range: 34 OF Opaque Surfaces R-38 Roof Attic R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) "R-13 Wall Orientation (►M (N) (E) (SE) (S) (SM (NE) Items shown with an asterisk (") denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = = = = = = = = = 1,596.0 0.0260 56.0 320.0 0.0690 25.0 320.0 0.0690 32.3 97.5 0.0690 29.3 362.5 0.0690 27.7 94.5 0.0690 31.7 1,400.4 0.0690 26.7 1,396.0 0.1020 0.0 25.5 16.9 0.0 12.3 13.8 Page Total Fpnoctratinn NEW 2B NEW 2C NEW 2E NEW 15 NEW 2F NEW 2D NEW 2H NEW 2J NEW 2K nriantatinn (SE) (S) (S) (S) (S) (SVV) (NE) (NE) (NE) Shaded Unshaded Area X X X X X X X X X GLF + + + + + + + + + Area X X X X X X X X X GLF = = = - = = = = = 0.0 12.3 22.5 15.1 0.0 12.3 25.5 13.7 0.0 12.3 12.0 13.7 0.0 12.3 48.0 13.7 0.0 12.3 12.0 13.7 0.0 12.3 25.5 16.9 0.0 12.3 13.8 15.9 0.0 12.3 13.8 15.9 0.0 12.3 6.0 15.9 Page Total Btu/hr 2,324 552 714 197 692 206 2,583 0 7,269 Btu/hr 339 349 164 657 164 430 219 219 Internal Gain Btu/hr Occupants 4 8 Occupants X 245 Btuh/occ. Equipment 1,596 Floor Area X 0.50 w/sqft = Infiltration: 1.064 X 0.94 X 131.66 X Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 20,354 Latent Gain Btu/hr Occupants 4 8 Occupants X 155 Btuh/occ. = 742 Infiltration: 4.771 X 0.94 X 131.66 X 0.00523 - 3,075 Air Sensible CFM ELA AW I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 742 I EnemyPro 6.3 by EnergySott User Number: 6712 Run Code: 2014-10-03709:59:22 /D: Page 37 of 41 • • RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Mattison Floyd Residence 10/3/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Master bedroom Outdoor Dry Bulb Temperature 112 OF Floor Area 1,596.0 ft2 Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature _ 70 OF Outdoor Daily Range: 34 OF O a ue,Surfaces Orientation Area U -Factor CLTD' Btu/hr X X = X X X X X X = X X = X X = X X = X X = X X = Page Total 0 Items shown with an asterisk (") denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr NEW 2L (NE) 0.0 X 12.3 + 30.0 X 15.9 = 476 NEW 16 (NE) 0.0 X 12.3 + 20.0 X 15.9 = 318 NEW 2M (NE) 0.0 X 12.3 + 6.0 X 15.9 = 95 NEW 2N (NE) 0.0 X 12.3 + 10.0 X 15.9 = 159 X + X = X + X = X + X = X + X = X + X = Page Total 1,048 Internal Gain . Btu/hr Occupants 4 8 Occupants X d245 Btuh/occ. =L 1,173E ui ment 1,596 Floor Area X w/ggft = 2,724 Infiltration: 1.064 X 0.94 X 131.66 X 42 = 5,503 Air Sensible CFM ELA AT .TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 20,354 Latent Gain Btu/hr Occupants 4 8 Occupants X 155 Btuh/occ. = 742 Infiltration: 4,771 X 0.94 X 131.66 X 0.00523 = 3,075 Air Sensible CFM ELA AW TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 742 EnergyPro 6.3 by Ene Soft User Number: 6712 Run Code: 201410-03T09:59:22 ID: Page 38 of 41 r RESIDENTIAL ROOM COOLING LOAD SUMMARY 'Project Name . Date Mattison Floyd Residence 10/3/2014 ROOM INFORMATION DESIGN CONDITIONS 17, Room Name Casita Outdoor Dry Bulb Temperature 112°F Floor Area 1,130.0 ft2 Outdoor Wet Bulb Temperature 78 °F Indoor Dry Bulb Temperature 70 OF Outdoor Daily Ranqe: 34 OF Ooaaue Surfaces R-38 Roof Attic R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W..21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) 'R-13 Wall Orientation (1/10 (N) (NE) (E) (SE) (S) (S K9 (NE) Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = = = = = = = = = 1,127.6 0.0260 56.0 589.2 0.0690 25.0 373.0 0.0690 30.3 839.5 0.0690 32.3 120.0 0.0690 29.3 606.5 0.0690 27.7 216.0 0.0690 31.7 816.0 0.0690 26.7 940.0 0.1020 0.0 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestratinn Skylight Skylight NEW K NEW L NEW M NEW P NEW N NEW Q NEW R Internal Gain Orientatinn W (tM (N) (N) (N) (N) (NE) (NE) (E) Page Total Shaded Unshaded Area X X X X X X X X12.3 X GLF + + + + + + + + + Area X X X X X X X X X GLF = = = = = = = = = 0.0 17.5 1.2 58.1 0.0 17.5 1.2 58.1 0.0 12.3 19.3 14.2 0.0 12.3 4.5 14.2 0.0 12.3 4.5 14.2 0.0 12.3 22.5 14.2 0.0 12.3 4.5 19.7 0.0 22.5 19.7 0.0 12.3 22.5 22.4 Page Total 3.4 Occupants X 245 Btuh/occ. _ 1,130 Floor Area X 0.50 w/sgft = Infiltration: 1.064 X 0.94 X 93.21 X 42 = Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM Latent Gain 3.4 Occupants X 1 155 Btuh/occ. _ Infiltration: 4,771 X 0.94 X 93.21 X 0.00523 = Air Sensible CFM ELA AW 401 TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 6.3 by EnergySoft User Number: 6712 Run Code: 2014-1 0-03 70 9:59:22 Btu/hr 1,642 1,016 781 1,873 243 1,158 472 1,505_ 0 8, 690 Btu/hr 70 70 274 64 64 320 89 443 1 Btu/hr 831 1, 928 19,524 Btu/hr 525 2,177 525 re 39 of 41 M • a RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Mattison Floyd Residence 10/3/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Casita Outdoor Dry Bulb Temperature 112°F Floor Area 1,130.0 ft' Outdoor Wet Bulb Temperature 78 °F Indoor Pry Bulb Temperature 70 OF Outdoor Daily Range: 34 OF e Su Orientation Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = - = = = = = = = = = = = = = = = Btu/l 0.0 3.0 22.4 0.0 3.0 22.4 1,130 0.0 3.0 22.4 _ - 0.0 3.0 22.4 Infiltration: 0.0 3.0 22.4 3,896 0.0 3.0 22.4 AT 0.0 6.0 13.7 Page Total Items shown with an asterisk (') denote conduction through an interior surface to another room. 1.. Cooling Load Temperature Difference (CLTD) FanPCfrn inn NEWS NEW T NEW T NEW T NEW U NEW V NEW W NEW J NEW 4 Orientation (E) (E) (E) . (E) (E) (E) (S) (S). (SM Btulhr 5haded Area GLF X 12.3 X 12.3 X 12.3 X 12.3 X 12.3 X 12.3 X 12.3 X 12.3 X1 12.3 + + + + + + + + + Unshaded Area X X X X X X X X X GLF = = = = = = = = Btu/l 0.0 3.0 22.4 0.0 3.0 22.4 1,130 0.0 3.0 22.4 _ - 0.0 3.0 22.4 Infiltration: 0.0 3.0 22.4 3,896 0.0 3.0 22.4 AT 0.0 6.0 13.7 0.0 27.5 13.7 0.0 24.0 Latent Gain Page Total F, 01 67 67 67 67 67 67 82 376 Internal Gain Btulhr Occupants 3.4 Occupants X 245 Btuh/occ. 831 Equipment 1,130 Floor Area X 0.50 w/s4 ft _ - 1,928 Infiltration: 1.064 X 0.94 X 93.21 X 42 = 3,896 Air Sensible CFM ELL AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,524 Latent Gain Btu/hr Occupants 3 4 Occupants X 155 Btuh/occ. = 525 Infiltration: .4.771 X 0.94 X 93.21 X 0.00523 = 2,177 Air Sensible CFM ELA AW I Enemy. Pro 6.3 by EneroySoft User Number: 6712 Run Code: 201410-03709:59.22 /D: Pape 40 of 41 r • C RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Mattison Floyd Residence 7 10/3/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Casita Outdoor Dry Bulb Temperature 112 OF Floor Area 1,130.0 ftz Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature 70 OF Outdoor Daily Range: 34 OF Opaque Surfaces Orientation Area U -Factor CLTD' Btu/hr X X = X X = X X = NTA I x x = Y U EPT. xx = x x = CONSTRUCTION x x = x x = BY x x = Page Total 0 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr NEW G (NE) 0.0 x 12.3 + 12.0 X 15.9 = 191 NEW 3 (NE) 0.0 X 12.3 + 40.0 X 15.9 = 635 NEW H (NE) 0.0 X 12.3 + 12.0 X 15.9 = 191 X + X = X + X = X + X = X + X = X + X = x x = Page Total 1,016 Internal Gain Btu/hr Occupants 3.4 Occupants X 245 Btuh/occ. = 831 Equipment 1,130 Floor Area X 0.50 w/sgft = 1928, Infiltration: 1.064 X 0.94 X 93.21 X 42 = 3,896 Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,524 Latent Gain Btu/hr Occupants 3.4 Occupants X 155 Btuh/occ. = 525 Infiltration: 4,771 X 0.94 X 93.21 X 0.00523 = 2,177 Air Sensible CFM ELA AW TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 525 Ener,gyPro 6.3 by Ene Soft User Number: 6712 Run Code: 201410-03709:59:22 /D: Page 41 of 41