10-1383 (SFD) Title 24' BUILDING ENERGY ANALYSIS REPORT
PROJECT:
ADAMS RESIDENCE
77153 CASA DEL SOL
LA QUI NTA, CA 92253
Project Designer:.
GLS Architecture Group Inc.
74491 Joni Dr. Suite # 9
Palm Desert, Ca 92260
760 34.0.35.28
,Report Prepared by:
Armando Chavez
GLS Architecture Group
74491 Joni Dr. suite # 9
Palm Desert, Ca 92260_._, cam,
760 340.35.28 CITY OF
LA C�VINTq
BUILDING & SAFETY DEPT.
LAPPROVED
FOR CONSTRUCTION
DA Iz i t BY
Job Number:
MAR 1
i; . 11
Date:
3/9/2011
The. EnergyProcomputer program has been.used to perform the calcutations!summarized in.this compliance report This program has approval and is
authorized by the California Energy Commission for use with both,the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www,.energysoft.com.
EnergyPro 5.1 by EnergySoff User Number. 5553 RunCode. 2011-03,09710:54915 ID.
z
'TABLE OF CONTENTS
Cover Page
Table of Contents
Form CF -1 R Certificate of Compliance
Form MF -1 R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
EnergyPro 5.1 by EnergySoft Job.Number. ID: User Number: 5553
1
2
3
12
15
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
ADAMS RESIDENCE
Building Type ® single Family Q Addition Alone
❑ Multi Family 0 Existing+ Addition/Alteratlon
Date
M12011
Project Address
77153 CASA DEL SOL LA QUINTA
California Energy Climate Zone
. CA Climate Zone 15
Total Cond. Floor Area
2907
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
El Yes ❑, No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes El' No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavi ( Features see Part 2. of 5
Status
Wal! Wood Framed R-19 2437
New
Door Opaque Door None 96
New
Roof Wood Framed Attic R-38 Z150
New
Slab Unheated Slab -on -Grade None 2907 Perim = 311'
New
Roof Wood Framed Ratter R-30 757
New
FENESTRATION U- Exterior
Orientation Area(ft) Factor SHGC Overhang Sidefins Shades
Status
Rear (NE) 78.0 0.400
0.35 2.0 none Bug Screen
New
Rear (NE) 16.0 0.400
0.35 10:0 none Bug Screen
New
Left, (NKI 8.0 0.400
0.35 2.0 none Bug Screen
New
Left (Alm 4.0 0.400.
0.35 2.0 none Bug Screen
New
Left (AfM 21.0 0.400
0.35 2.0 none Bug Screen
New
Front (SW) 25.0 0.400
0.35 2.0. none Bug Screen
New
Right (SE) 20.0 0.400
0.35 2.0 none Bug°Screen
New
Left (NKK 7.'0 0:400
0.35 2.0 none Bug Screen
New
Front (SW) 70 0.400
0.35 2.0 none Bug Screen
New
Right (SE) 5.0 0.400
0.35 2.0 none Bug Screen
New
Rear (NE) 120 0.400
a35 4.0 none. Bug Screen
New
HVAC SYSTEMS
Ot . Heating Min. Eff
Cooling Min. Eff Thermostat
Status
2 Central Furnace 80%AFUE
Split Air Conditioner 13.0 SEER Selback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value
Status
HAVC-NEW Ducted
Ducled Attic, Ceiling Ins; vented a0
New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution
Status
1 Small Gas 50
0.58 Kitchen Pipe Ins
New
�VnargyPro 5.1 by EnergySoft User Number. 5553
RunCode. 2011-03-09110:54:15 ID:
Page 3 of 15
PERFORMANCE CERTIFICATE: Residential ' (Part 1 of 5
CF -1 R
Project Name
ADAMS RESIDENCE
Building Type ® Single Family 0 Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
"12011
Project Address
77153 CASA DEL SOL LA QUINTA
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
2,907
Addition
fva
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
Q Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes El No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavi ft) Features see Part 2 of 5
Status
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades
Status
Rear (NE) 48.0 0.400. 0.35 4.0 none Bug Screen
New
Rear (NE) 48.0 0.400 0:35 4.0 none- Bug Smen
New
Rear (NE) 12.0 0.400, 0:35 4..0 none Bug Screen
New
Front.(SKI 160.0 0.400 0;35 10.0 none Bug Screen
New
Rear (NE) 3.0 0.400 0:35 4.0 none Bug Screen
New
Rear (NE) 3:0 0.400 0.35 4.0 none Bug Screen
New
Rear (NE) 3.0 0.400 "0:35 4:0 none Bug Screen
New
Rear(NE) 10.0 0.650 0.48 4.0 none Bug Screen
New
Front(SK9 48.0 0.400 0.35 2.0 none Bug. Speen
New
Right (SE) 6.0 0.400 0.35 2.0 none Bug Speen
New
Right (SE) 10.0 0.650 a48 2.0 none Bug Speen
New
HVAC SYSTEMS
Qty. Heating Min. Eff Cooling Min. Eff Thermostat
Status
HVAC DISTRIBUTION Duct
Location/ Heating Cooking Duct..Location R -Value
Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution
Status
rEn-ergyPro,5.1 by,EnergySoft User Number. 5553 RunCode: 2011.03-09T10s4.15 ID:
Page 4 of 15
PERFORMANCE CERTIFICATE-: - Residential Part 1 of 5
CF -1R
Project Name
ADAMS RESIDENCE
Building Type 0 Single Family 0 Addition Alone
0 Multi Family 0 Existing+ Addition/Alteration
Date
")2011
Project Address
77153 CASA DEL SOL LA QUINTA
California Energy Climate Zone,
CA Climate Zone 15
Total Cond. Floor Area
2,907
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
F7 Yes ❑ No HERS Measures— If Yes, A -CF -413 must be provided per Part 2 of 5 of this form.
❑ Yes EINo Special Features --If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction. Type Cavity ( Features see Part 2 of 5 Status
FENESTRATION U- Exterior
Orientation Area(fl Factor SHGC Overhang Sidefins Shades Status
Right (SE) 4.0 0.400 0.35 2.0 none Bug Screen New
RightfSE) 4:0 0.400 0.35 2:0 none Bug Screen New
Right (SE) 8.0 0:400 0.35 2.0 none Bug Screen New
Right (SE) 8.0 6.400 0:35 2.0 none Bug Screen New
Rear (E) 6.0 0:400 0.35 2.0 none Bug Screen New
Front (VII 18.3 0.400 0.35 2.0 none Bug Screen New
Front (W) 18.3 0.400 0.35 2.0 none Bug Screen New
Right'(S) 350 0.400 0.35 2.0 none Bug Screen New
Right (S) 6.0 0.400 0.35 2.0 none Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
EnergyPro 5.1 by EnergySoft User Number., 5553 RunCode. 2011.0349T10r54:15 ID:
Page 5 of 15
PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF-1 R
Project Name
ADAMS RESIDENCE
Building Type 0 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
3/5/2011
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special, attention to the items specified in this checklist. These iterins require special written
justification and documentation, and special` verification to be used with the performance approachThe enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF-4R form for each of the measures listed below for final to be given.
The Cooling System YorkCZB36.PS8816N80.1200chn includes credit for a 11.5 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System HAVC-NEW incorporates HERS Verfied Refrigerant Charg&ora Charge Indicator Display.
HAVC-NEW'includes verified duchsystems that have air leakage to outside conditions equal to or less than, 25 cfm. HERS field verification for ducts in
conditioned space and duct leakage is required.
EnerayPro 5:1 by Ene Soft User Number. 5553 RunCode: 2011-03-09Ty0:54r15 1D: Peae 6 of 15
PERFORMANCE CERTIFICATE: Residential Part 3 of 5) CF-1 R
Project Name
Building Type 10 Single Family 13 Addition Alone
Date
ADAMS RESIDENCE
1 0 Multi Family 0 Existing+ Addition/Alteration
3/9/2011
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV kBtu/ft?
Space Heating 4.65 3.88 0.77
Space Cooling 56:96 53,94 3.01
Fans 11.79 14.76 -2.97
Domestic Hot Water 12.55 12.43 0.11
Pumps 0.00 0.00 0.00
Totals 85.95 85.02 0:93
Percent Better Than Standard: 1.1 %
BUILDING COMPLIES - HERS VERIFICATION REQUIRED
Fenestration
Building. Front Orientation: (SI49 225 deg Ext. Walls/Roof Wali Area Area
Number of Dwelling Units: 1.00 (SW 841 277
Fuel Available at Site: Natural Gas (NK9 656 40
Raised Floor Area: 0 (NE) 945 239
Slab on Grade Area: 2.907 (SE) 753 106
Average Ceiling Height: 10.4 Roof 2,907 0
Fenestration Average U-Factor: 0.41 TOTAL: 662
Avera a SHGC: 0.35 Fenestration/CFA Ratio: 22.8%
REMARKS
s
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
`
The documentation author hereby certifies thatthe documentation is accurate and complete
Documentation Author
Company GLS Ard►itectun9 Group
39/2011
Address 74491 Joni Dr. suite #`9 Name -Armando Chavez
Ci ip Palm Desert, Ce 92260Phone 760 340.35.28 ionif Date
The individual with overall design responsibility hereby certifies that the pr ed building design represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and
with any other calculations submitted with this permit application, and recognizes that compliance using duct design,
duct sealing, verification of refrigerant charge, insulation installation quality,. and building envelope sealing require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company GLS Architecture Group Inc.
Address 74491Joni Dr. Suite #9 Name Name
City/State2p Palm Desert, Ca 92260 Phone 760 340.35.28 Signed License # Date
EnemyPro 5.1 by Eire Soft User Number: 5553 RunCode: 20 1-03-09T10:54:15 /D: Page 7 of 15
CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF -1 R.
Project Name
ADAMS RESIDENCE
Building Type ® SingleFamily ❑ Addition Alone
❑ Multi, Family ❑ Existing+ Addition/Alteration
Date
3/912011
OPAQUE SURFACE DETAILS
Surface
Type Area'
U- Insulation
Factor Cavity Exterior Frame Interior Frame Azm
Joint Appendix
Tilt Status 4 Location/Comments
Wall
178
0.074 R-19
45
90 New 4.3.1 A5
NEW
Door
24
0.500 None
45
90 New 4:5.1-A4
NEW
Wall
330
0.074 R-19
315
90 New 4.3.1-A5
NEW
Wall
238
0.074 R-19
225
90 New 4.3.1=A5
NEW
Door
24
a500 None
225
90 'New 4:5.1-A4
NEW
Wall
87
.0.074 R-19
135
90 New 4:3.1-M
NEW
Door
20
0.500 None
135
90 New 4.5.1-A4
NEW
Roof
828
0.025 R�8
0
5 New 4.2:1 A21
NEW
Slab
828
0:730 None
01
180 New 4:4.7 Al
NEW
Wall
24
0.074 R-19
45
90 New 4.3.17A5
NEW
Wall
13
0.074 Wig
315
90 New 4.3:1-A5
NEW
Wall
171
0:074 R-19
225
90 New 4:3:1-A5
NEW
Wall
15
0:074 R-19
135
90 New 4.3.1-A5
NEW
Roof
475
0.033 R-30
0
.5 'New 4.2:2-A41
NEW
Slab
475
[ 0.730 None
01
180 New 4.4:7-A1
NEW
Wall
901
OA74 R-19
1 451
90 New 4.3.IA5
INEW
FENESTRATION SURFACE DETAILS
ID
Type
Area U -Factor
SHGC
Azm Status Glazing Type
Location/Comments
1
Window
54.0 0:400 NFRC
0.35 NFRC 45 New
2008 PRESCR. MWZ-15
NEW
2
Window
16.0 0.400 NFRC
0.35 NFRC 45 New
2008 PRESCR. WDWZ=15
NEW
3
Window
4.0 0.400 NFRC
a35' NFRC 315 New
2008 PRESCR. WDWZ-15
NEW
4
Window
40 a400 NFRC
0.35 NFRC 315 New
2008 PRESCR. 14DWZ--15
NEW
5
Window
21'.0 0.400 NFRC
0.35 NFRC 315 New
2008 PRESCR. WDW Z-15
NEW
6
Window
25.0 0.400 NFRC
0.35 NFRC 225 New
2008 PRESCR. WDW Z-15
NEW
7
Window
20.0 a400 NFRC
0.35 NFRC. 135 New
12008 PRESCR:. WDWZ,15
NEW
8
Window
TO 0.400 NFRC
0.35 NFRC 315 New
2008 PRESCR. WDW Z 15
NEW
9
Window
TO 0:400 NFRC
a35 NFRC 225 New
2008 PRESCR. WDWZ-15
NEW
10
Window
5.0 0.400 NFRC
0.35 NFRC 135 New
2008'PRESCR. WDW Z-15
NEW
11
Window
12.0 0:400 NFRC.
0.35,, NFRC 45 New
2008 PRESCR. WDWZ-15
NEW
12
Window
48.0 0:400 NFRC
'0.35' NFRC 45 New
2008 PRESCR. WDW Z-15
NEW
13
Window
48.0 0.400 NFRC
0.35' NFRC. 45 New.
12008 PRESCR: WDW Z-15
NEW
14
Window
12:0 0.400 NFRC
0.35' NFRC 45 New
2008 PRESCR. V10 Z-15
NEW
15
1Mhdow
160.0 0:400 NFRC
0.35 NFRC 225, New
2008 PRESCR. WDW Z-15
NEW
16
lWi7dow
3.01 0.400 NFRC
0.35 NFRC 45 New
2008 PRESCR. WDW Z-15
INEW
(1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGGT e: 116-6 = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
Hat Wd
Ove hana Left Fin
Len H t LExt1 RExt Dist I Len I
Right Fin
Hat • Dist Len H t
1
Bug Screen
0.76
5.5 8.5 2.0 0.1
2.'01 2.0
2
Bug Screen
0:76
3.5 3:5 10.0 0..1
10.0 10:0
3
Bug Screen
0.76
1.5 1.5 2.0 0,1
2;0 2.0
4
Bug Screen
0.76
1.5' 1.5 2.0 0.1
2:0 2.0
5
Bug Screen
0.76
6.51 2:5 201 0..1
2.0 2.0
6
Bug Screen
0.76
.6.5 2.5 2:0 a i
2:0 2.0
7
Bug Screen
0.76
6.5 2.5 2.0 0.1
2.0 2:0
8
Lug Screen
0:76
1.0 6.5 2.0 0.1
2.01 2:0,
9
Bug Screen
0.76
1.0 6.5 2.0 0:1
201 2:0
10
Bug Screen
0.76
1.6 4.5 2.0 a i
2.01 2:0
11
Bug Screen
0.76
1.5 5.5 4.0 0.1
4:0 4:0
12
Bug Screen
0.76
6.5 5.5 4.0 0:1
4.0 4.0
13
Bu Screen
0.76
6.5 5.5 4.0 0.1
4:0 4.0
14,
Bug Screen
0.76
1.5 5:5 4.0 0.1
4.0 4:0
15Bu
Screen
0.76
9.5 15.5 10.0 0.1
10.0 10:0
16
]Bug Screen
A 76
1.0 1.5 4.0 0.1
4.0 4.01 1
Fn
-&MY% 5.1 by EnergySoft. User Number. • 5553
RunCode: 2011-03-09710:54:15 ID:
Pow 8 of 15
CERTIFICATE OF COMPLIANCE: Residential. (Part 4 of 5) CFA R
Project Name
ADAMS RESIDENCE
I Building Type ®Single Family. Q AddibiDn Alone
13 Multi Family ❑ Existing+ Addition%Alteration
I Date
3/9/2011
OPAQUE SURFACE DETAILS
Surface
Type Area
U- Insulation
Factor Cavity Exterior Frame Interior Frame Azm
Joint Appendix
.Tilt Status 4 Location/Comments
Wall
35
0.074. R-19
225
90 New 4.3..1-A5
NEW
Wall
305
0.074'R-19
45
90 New 4.3.1_A5
NEW
Wall
2731
0.074 R-19
315
90, New 4.3.1-A5
NEW
Wall
93
0.074 R-19
225
90 New 4.3.1-A5
NEW
Door
280.500
None
225
90 New 4.5.1 A4
NEW
Wall
368
0.074 R-19
135
90 New 4.3.1-A5
NEW
Roof
1,322
0.025 R-38
0
5 New 4.2.1 A21
NEW
Slab
1,604'
0.730 None
0
180 New 4.4.7A1
NEW
Wall
85
0.074 R-19
90
90 New 4.3.1 A5
NEW
Wall
129
0.074 R-19
270
90 New 4.3:1-A5
NEW
Wall'
157
0.074 R-19
180
90 New 4.3:1-A5
NEW
Roof
282
0.033 R-30
0
5 New 4.2.2-A41
NEW
FENESTRATION SURFACE DETAILS
ID
Type
Area U -Factor
SHGC
Azm Status
Glazing Type
Location/Comments
17
Window
3.0 0.400 NFRC
0.35 NFRC 45 New
2008 PRESCR. MW Z-15
NEW
18
Window
3.0 a400 NFRC
a35 NFRC 45 New
.2008 PRESCR. WDWZ--15
NEW
19
Window
10.0 0.650 NFRC
0.48 NFRC 45 New
WECK, GLASS BLOCKr 8x8x4
NEW
20
Window
24.0 0.400. NFRC
0.35 NFRC 45 New
2008 PRESCR.. WDWZ-15
NEW
21
Window 1
4.0 0.400 NFRC
0.35 NFRC 1 315 New
12008PRESCR. WDWZ-15
NEW
22
Window
48.0 0.400 NFRC
0.35' NFRC 225 New
12008 PRESCR. KVW Z-15
NEW
23
Window
6.0 0.400 NFRC
0.35 NFRC 135 New
2008'PRESCR. WDWZ-15
NEW
24
Wcndow
10.0 0.650 NFRC
0.48 NFRC 135 New
WECK GLASS BLOCK 8x8x4
NEW
25
Window
4.0 0.400 NFRC
0.35 NFRC 135 New
2008'PRESCR. WDW Z-15 '
NEW
26
Window
4.0 0.400 NFRC
0. 35,1 NFRC 135 New
2008 PRESCR. WDW Z-15
NEW
27
lMndow
8.0 0.400 NFRC
0.35 NFRC 135 New
2008PRESCR. WDW Z45
NEW
28
Window
8.0 0.400 NFRC
0.35 NFRC 135 New
2008'PRESCR. WDWZ-15
NLEIV
29
Window
6.0 0.400 NFRC
0.35 NFRC 90 New
2008 PRESCR: WDW Z-15
NEW
30
Window
18.3 0.400 NFRC
0.35 NFRC 270 New
2008 PRESCR. MWZ-15
NEW
31
Window
18.3; 0.400 NFRC
0.35 NFRC 270 New
2008 PRESCR. WOW Z-15
NEW
32
Window
X01 0.400 1 NFRC
I 0.35 NFRC 180 'New
'2008 PRESCR. WDW Z-15
INEW
(1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC T 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS'
ID
Exterior Shade Type SHGC
Window
Hat Wd
Ove hana Left Fin Ri ht in
Len H t LExt I REA Dist Len I H t Dist Len H t
17
Bug Screen.
0.76
1.0 1.5 4.6 0.1
4.01 4.0
18
Bug Screen
0:76
1.0 1.5 4.0 0.1
4.01 4.0
19
Bug Screen
0.76
1.0 1.5 4.0 0.1
4:0 4.0
20
Bug Screen
0.76
3.5 5.5 2.0- 0.1
2.0 2.0
21'
Bug Screen
0.76
1.5 1111::1.5 2.01 0.1
2 0 2.0
22
Bug Screen
0.76
7.5 5.5 2;01 0.1
2.0 2.0
23
Bug Screen
0.76
1.5 2.5 2.01 a 1
2.0 2.0
24
Bug Screen
0.76
3.5 2.0 2.0 0.1
20 2;0
25
Bug Screen
a76
1.5. 1.5 2.0 0.1
2.0 2:0
26
Bug Screen
0.76
1.5 1.5 2.0' 0.1
2.0 2:0
27
Bu Screen
0:76
3.5 1:5 2.0 0.1
2.0 2.0
28
Bug Screen
0.76
3.5 1.5 2.0 0'1
20 2.0
29
Screen
0.76
3.5 2.0 2.0 0.1
2.0 2.0
30
_Bug
Bug Screen
0.76
4.5 3.5 2.0 0:1
2:0 2.0
31
ISug Screen
0.76
45 3.5 zol 0.11
2.01 2.01 1
32
IBug Screen
1 76
4:5 6.5 201 0.11
2.01 201 1
Ewe
Pro 5.1 by EnergySoff User Number. 5553
RunCode. 2011-03-09710:54:15 /D:
Page 9 of 15
I •
•MIMMEMEM
. I RESIDENCE
ADAMS
0 Multi Family
13 Existing+Addition/Alteration
. I
OPAQUE DETAILS
Insulation Joint Appendix
511 ®R: M N ff 4 Locabon/Comments
FENESTRATION SURFACE DETAILS
2008 PRESCR.
EXTERIOR SHADINDETAILS
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5
CF -1 R
Project Name
ADAMS RESIDENCE
Building Type 0 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
3/5/2011
BUILDING ZONE INFORMATION
System Name
Floor Area
Zone Name New Existina Altered Removed Volume Year Built
HAVC-NEW
ZONE 828 828
8,280
ZONE 475 475
5,938
ZONE 1604 1,604
16,040
Totals 2,907 0 01 0
HVAC SYSTEMS
System Name
Qty. Heating Type 'Min. Eff: Cooling Type Min. Eff. Thermostat Type Status
HAVC-NEW
2 Central Furnace 80% AFUE Split Air Conditioner 1 3. 0 SEER Setback
New
HVAC DISTRIBUTION
System Name
Duct
Heating Cooling Duct Location R -Value
Ducts
Tested? Status
HAVC-NEW
Ducted Ducted Attic, Ceiling Ins, vented8.0
0 New
13
13
1
13
WATER HEATING SYSTEMS
S stem Name
Oty.
Type
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy Standby
Factor Loss or
or RE Pilot.
Ext.
Tank
Insul. R-
Value
Status
Standard Gas 50.gal or Le
1
Small Gas
i ftchen.Pipe Ins
40,000
50
0.58 n/a
Na
New
MULTI -FAMILY WATER
HEATING
DETAILS
I HYDRONIC
HEATING SYSTEM
PIPING
Control
Hot Water Piping Length
ft
C
0
0 ,�
Q _
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
HP
Plenum Outside
Buried
13
13
13
Ene Pro. 5.1 by Energy,%ft.
User Number: 5553 RunCode: 2011-03-09T10:54 15 ID:
Pae 1.1 of. 15
MANDATORY MEASURES SUMMARY: Residential (Pagel of 3 MF -IR
Project Name
ADAMS RESIDENCE
Date
3/9/2011
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate, of Compliance. (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory. Measures Summary shall be incorporated'
into the permit documents, and theapplicablefeatures shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with Plan&
Building Envelope Measures:
116(a)l: Doors -and. windows between conditioned and unconditioned spaces aremanufactured to limit air leakage.
§11.6(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111'(a).
117: Exterior doors and windows are weather -stn d; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type.and include on CF -6R Form.
§1180): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
150(a): Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor.
150(b): Loose°fill insulation shall conform with manufacturer's installed design labeled R -Value.
150(c): Minimum R-13 insulation in wood -frame wall orequivalent U -factor.
150(d): Minimum R-13 insulation in raised wood -frame floor or equivalent U -factor.
150(f): Air retarding wrap is tested, labeled, and installed. according to ASTM E1.677-95 2000 when specified on the CF -1 R Form.
150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(1): Water absorption rate for slab edge insulation material. alone without facings is no greater than 0.3%; water vapor permeance
rate is no: reaterthan 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 e 1 A:. Masonry orfactory-built fireplaces have a closable metal or glass door covering the entire opening of"the firebox.
§150(e)l B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at'least six square inches in area and'is
equipped with.a with a readily accessible, operable, and tight -fitting damper and or a combustion-aircontrol.device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a`firebox jacket, when that indoor air is vented to the
outside of the. building,are prohibited.
Space Conditioning, Water Heatin nd Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the:Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple: dwelling units and High. =Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or RCCA.
§1500): Heating systems are equipped with thermostats that -meet the setback. requirements of Section 112(c).
§1500)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
With insulation, having an installed thermal resistance of R-12 or greater.
§1500)113' Unfired storage tanks, such as storage tanks or backup tanks for solarwater=heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internaHnsulation where the internal insulation R -value is indicated on the exterior of the
tank.
§1500)2: First 5 feet of hot and cold water pipes closest to water heater tank,non-recirculating systems, and entire length of
recirculating sections of bot water pipes are insulated per Standards Table.150-B.
§1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot_
watertank shall be insulated to Table 150-B and Equation 150-A.
§1500)2: Pipe insulation for steam hydronic heating systems or hot'water systems >15 psi, meets the requirements of Standards Table
123-A.
§1,500)3A: Insulation is protected from damage, includin .that due to sunlight, moisture equipment maintenance and wind.
§1500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely -in
conditioned space.
1NOW Solar water-heatin . systems and/or collectors are certified by the Solar Rating and Certification Corporation.
EnergyPro 5.1 by EnergySoR User Number. • 5553 RunCode: 2011-03-09T10:54:15 ID: Page. 12 of 15
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -IR
Project Name
Date
ADAMS RESIDENCE
3/9%2011
§150(m)1; All air -distribution system ducts and plenums installed, are sealed and insulated to meet the, requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and retum-air ducts and, plenums are insulated to a. minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL'181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 Inch, the combination of mastic and either mesh or tape shall be used
§150(m)1:: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shallnot be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of'the ducts. .
§150(m)2D: Joints and seams of duct systems and their components shall,not.be sealed with cloth back rubber adhesive duct tapes
unless such t e is used in combination with mastic and draw bands.
150 m 7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have eitherautomatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that duetosunlight, moisture, equipment maintenance, and wind.
Cellular foaminsulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause: de radation of the material..
150 m 10: Flexible ducts cannot have porous inner cores..
§150(o):.All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not.a permissible method of providing the. Whole Building Ventilation
required in Section 4 of that Standard.
Pool and Spa Heating Systems rand Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with,operating instructions; and
shall not use electric resistance heating ora pilot light.
§114(b)l : Any pool or spa heating equipment shall.be installed with at least.36" of pipe betweenJilter and heater, or dedicated,suction
and return lines, or built-up connections for future solar heating.
174(b)2. Outdoor pools or spas that have a heatpum or gas heater shall have a cover.
§1'14(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch thatwill allow all pumps.to be set or
programmed to run only during off -peak -electric demand periods.
150 : Residential pool -systems or equipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 .
Residential Lighting Measures:
§150(k)1: High efficacyduminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is nota low efficacy luminaire asspecified by §150(k)2,.
§1,50(k)3: The watts e..of permanently installed luminaires..shall be determined as specified by §130(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in. Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
150(k)6: Lighting integral to exhaust fans, in rooms other -than kitchens, shall meet theapplicable requirements of §150 k
§150(k)7: All switching devices and controls shall meet the requirements of 150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50%high efficacy _requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (.EMCS), or a multi -scene programmable control system; and all permanently installed
luminaries In.garages, laundry rooms, closets greater than 70 -square feet,. and utility rooms are high efficacy, and controlled by a
manual -on occupant, sensor.
§150(k)9: Permanently installed lighting that is internal to. cabinets shall use no more than 20 watts iof power, per linearfoot of
illuminated cabinet.
EnergyPro 5:1 by EnergySoft User Number: 5553 RunCode: 2011-03-09710:54:15 IDr Page 13 of 15
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 M.F-1R
Project Name
Date
ADAMS RESIDENCE
"/2011
§150(k)l0: Permanently installed; luminaires in bathrooms,attached. and detached garages, laundry'rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed'low efficacy luminaires In closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)11`- Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms,, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled byeither a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTIONZ Lighting in detached storage building less
than 1000.s uare feet located on a residential site is not required to comply with §150 k 11.
§150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory,;' and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies; and porches, which are permanently mounted to axesidential building or to other buildings on the
same lot shall'be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that.
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not�having an override or'bypass.switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptions to §150(k)13 may controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3:' Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the -California. Electric Code need not
be high efficacy luminaires.
§1.50(k)1.4: Internally illuminated address signs shall comply With Section 148; OR not contairn a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)15: Lighting for parking lots and carportsvith a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132,134, and 147. Lighting for parking garages for 8 or more vehicles.shall comply with the applicable
requirements of Sections 130, 131- ,134, and'146.,
§150(k)l6: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be, allowed provided
that thev are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
EnergyPro 5.1 by.EnergySoft User Number. 5553 RunCode: 2011,03-09T10:54:15 /D: Page 14 of 15
HVAC'SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name.
ADAMS RESIDENCE
Date
3/9/2011
System Name
HAVC-NEW
Floor Area
2,907
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
COIL
CFM
Total Room Loads 2,094
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK
Sensible
42,896
0
0
0
0
0
0
1 42,896
COIL HTG.
Latent CFM
4,502 '817
0 0
4,502
PEAK
Heating System
Sensible
Output OrSystem 64,000
43,574
Total Output Stuh 128,000
Output Btuh/ 44.0
0
Cooling System
0
output per System 35;000
0
Total Output Btuh 70,000
0
Total Output ons 5.8
0
Total Output Btuh/ 24.1
Total Output s on 498:3
43,574
Air System
CFM per System
1,200
HVAC EQUIPMENT SELECTION
Airflow (cfm)
2,400
YorkCZB36.PS8B16N80.1200dm
49,155
13,070
128,000
128,000
Jan 1 AM
Airflow clm/ 0.83
Airflow cfm/Ton) 411.4
Outside Air % 0.0%
Total Adjusted System Output 4P,1551
(Adjusted foe Peak Design conditions)
TIME OF SYSTEM PEAK
13,070
Aug 3 PM
Outside Air chW 0;00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF 70 OF
Outside Air
0 dm Supply Fan
2,400 dm
'
70'OF70
70 OF 120 OF.
Heating Coil
-TT.A �
-
120 OF
_..___...---..._._......__—,
ROOM
OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperaturesst Time of Cooling Peak
112 / 78 OF 78165 OF 78 / 65 OF 59 / 58 OF
Outside Air
0 dm Su Fan
Supply Cooling Coil
2,400 dm
78 / 65 OF
LJEnergyPro
50.1%
O
,, 59 / 58 F
( R OM
�— 78 / 65'OF
5.1 by EnergySoR. User Number. • 5553 RunCode. °2011-63-09710:54:15
ID: -
Page 15 of 15