13-1390 (AR) Title 24
BUILDING ENERGY ANALYSIS REPORT PROJECT: Ave La Fonda 78500 Ave La Fonda La Quinta, CA 92253 Project Designer: Sipovac Construction Inc. 72-651 Theodora Lane Palm Desert, CA 92260 760-360-9700 Report Prepared by: Sipovac Construction ECEIVED Job Number: 090513 CITY OF LA QUiNTA BUILDING & SAFETY DEPT. APPR1RUCTIONED JAN 2,2 2014 Date: FOR CONS CITY OF LA QUINTA IMUNITY DEVELOPMENT 1/22/2014 DATE Z I [(t_ The EnergyPro computer program has been used to perform the calculations summarized in this compliance repel . This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC — www.energysoft.com. Energ Pro 5.1 by Energ Soft User Number 5289 RunCode: 2014-01-22709:38:50 ID: 09051 TABLE OF CONTENTS Cover Page Table of Contents Form CF -1 R Certificate of Compliance Form MF -1 R Mandatory Measures Summary HVAC System Heating and Cooling Loads Summary Room Load Summary Room Heating Peak Loads Room Cooling Peak Loads S EnergyPro 5.1 by EnergySoft Job Number: ID: 090513 User Number: 5289 p 1 2 3 9 12 14 16 18 PERFORMANCE CERTIFICATE: Residential Part 1 of 5 CF-1 R Project Name Ave La Fonda Building Type 2 Single Family ❑ Addition Alone ❑ Multi Family ® Existing+ Addition/Alteration Date 1/22/2014 Project Address 78500 Ave La Fonda La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 2,715 Addition 1,175 # of Stories 1 FIELD INSPECTION ENERGY CHECKLIST ❑ Yes © No HERS Measures -- If Yes, A CF-4R must be provided per Part 2 of 5 of this form. ❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details. INSULATION Construction Type Area Special Cavity ftp Features see Part 2 of 5 Status Wall Wood Framed R-11 863 Existing Door Opaque Door None 39 Existing Wall Wood Framed R-13 93 Existing Slab Unheated Slab-on-Grade None 1,540 Perim = 0' Existing Roof Wood Framed Attic R-19 1,324 Existing Wall Wood Framed R-19 823 New Roof Wood Framed Rafter R-38 1,166 New Slab Unheated Slab-on-Grade None 1,175 Perim = 0' New FENESTRATION U- Exterior Orientation Area Factor SHGC Overhang Sidef ins Shades Status Front (S) 62.3 0.770 0.73 none none Bug Screen Removed Front (S) 45.0 0.390 0.37 none none Bug Screen New Left (W) 76.1 0.770 0.73 none none Bug Screen Removed Left (W) 156.8 0.390 0.37 none none Bug Screen New Rear (N) 114.6 0.770 0.73 none none Bug Screen Removed Right (E) 19.5 0.770 0.73 none none Bug Screen Removed Right (E) 19.5 0.390 0.37 none none Bug Screen New Skylight 14.3 0.390 0.30 none none None New Rear (N) 16.1 0.390 0.37 none none Bug Screen New Skylight 9.0 0.550 0.67 none none None New HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 Electric 3.50 HSPF Split Air Conditioner 13.0 SEER Setback Existing 1 Electric 3.50 HSPF Split Air Conditioner 13.0 SEER Setback New HVAC DISTRIBUTIONN Location HeatingCoolingDuct CITY OF U),mEMIN I A Locat 001DING & SR,-,Value0EFStatus HVAC System Ducted Ducted Attic, Ceiling Ins, ventedA P P R PA/F n New New 4 tons Ducted Ducted Attic, Ceiling Ins, vented-'OR CONS 8RUCTION New WATER HEATING N DATE BY Qty. Type Gallons Min. Eff Distribution Stats 1 Instant Gas 0 0.94 Kitchen Pipe Ins New EnergyPro 5.1 by EnergySoft User Number: 5289 RunCode: 2014-01-22709:38:50 ID: 090513 Page 3 of 19 PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF-1 R Project Name Ave La Fonda Building Type ® Single Family ❑ Addition Alone ❑ Multi Family ® Existing+ Addition/Alteration Date 1/22/2014 SPECIAL FEATURES INSPECTION CHECKLIST The enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a completed CF-4R form for each of the measures listed below for final to be given. L 11( F �U bN d r— o� C.LIFF:TY PT- PPROVED FOR CONSTRUCTION DATE BY- EnergyPro 5.1 by Ener Soft User Number: 5289 RunCode: 201401-22T09:38:50 /D: 090513 Pa e 4 of 19 PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF -1 R Project Name Building Type 53 Single Family ❑ Addition Alone Date Ave La Fonda ❑ Multi Family 53 Existing+ Addition/Alteration 1/22/2014 ANNUAL ENERGY USE SUMMARY Standard Proposed Margin TDV kBtu/ft2- r Space Heating 6.82 4.63 2.18 Space Cooling 94.71 90.62 4.09 Fans 19.98 19.63 0.35 Domestic Hot Water 23.76 18.02 5.73 Pumps 0.00 0.00 0.00 Totals 145.26 132.90 12.35 Percent Better Than Standard: 8.5 BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED Fenestration Building Front Orientation: (S) 180 deg Ext. Walls/Roof Wall Area Area Number of Dwelling Units: 1.00 (S) 512 45 Fuel Available at Site: 7ectric (No Natural Gas Available (M 562 157 Raised Floor Area: 0 (N) 587 16 Slab on Grade Area: 2,715 (E) 394 20 Average Ceiling Height: 8.9 Roof 2,514 23 Fenestration Average U -Factor: 0.39 TOTAL: 261 Average SHGC: 0.37 Fenestration/CFA Ratio: 9.6 REMARKS STATEMENT OF COMPLIANCE This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the Efficiency Standards of the California Code of Regulations. The documentation author hereby certifies that the documentation is accurate and complete. Documentation Author Company Sipovac Construction Address Name C F A` p i U I NT22/�20 I City/State/Zip Phone BUi rS ► -'l & SAFETY DEFUte I The individual with overall design responsibility hereby certifies that the ding?desig f'r�e in tis proposedibui presented set of construction documents is consistent with the other compliance forms a d workO,eegOk; ith-thi'�L�pecOpgtions, and with any other calculations submitted with this permit application, and recognizes that compliance using duct desi 3n, duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require installer testing and certification and field verification by an approved HER 3 �Jt�f. BY Designer or Owner (per Business & Professions Code) Company Sipovac Construction Inc. Address 72-651 Theodora Lane Name Bob Sipovac &I City/State/Zip Palm Desert, CA 92260 Phone 760-360-9700 Signed License # Date EnergyPro 5.1 by EnerqvSoft User Number: 5289 RunCode: 2014-01-22709:38:50 /D: 090513 Pa e 5 of 19 CERTIFICATE OF COMPLIANCE: Residential Part 4 of5 CF -1 R Project Name Ave La Fonda Building Type 0 Single Family ❑ Addition Alone ❑ Multi Family m Existing+ Addition/Alteration Date 1/22/2014 OPAQUE SURFACE DETAILS Surface Type Area U- Insulation Joint Appendix I Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Wall 167 0.110 R-11 180 90 Existing 4.3.1-A2 Existing House Door 20 0.500 None 180 90 Existin 4.5.1-A4 Existing House Wall 68 0.110 R-11 90 90 Existing 4.3.1-A2 Existing House Wall 223 0.110 R-11 180 90 Existin 4.3.1-A2 Existing House Wall 93 0.102 R-13 1 270 90 Existing 4.3.1-A3 Existing House Wall 351 0.110 R-11 0 90 Removec 4.3.1-A2 Existing House Wall 73 0.110 R-11 270 90 Removec 4.3.1-A2 Existing House Wall 81 0.110 R-11 180 90 Removec 4.3.1-A2 Existing House Wall 88 0.110 R-11 01 90 Removec 4.3.1-A2 Existing House Wall 57 0.110 R-11 0 90 Removec 4.3.1-A2 Existing House Wall 54 0.110 R-11 90 90 Existing 4.3.1-A2 Existing House Door 191 0.500 None 90 90 Existing 4.5.1-A4 Existing House Wall 164 0.110 R-11 0 90 Existing 4.3.1-A2 lExisting House Wall 187 0.110 R-11 90 90 Existing4.3.1-A2 ExistingHouse Slab 1,540 0.730 1 None 0 180 Existing 4.4.7-A 1 --dExistin House Roof 1,324 0.049 R-19 0 i Misting 4.2.1-A4 I Existing House FENESTRATION SURFACE DETAILS ID Type Area U -Factor SHGC Azm Status Glazing Type Location/Comments 1 Window 19.5 0.770 Default 0.73 Default 180 Removed Double Metal Clear Existing House 2 Window 19.5 0.390 NFRC 0.37 NFRC 180 New Milgard Classic Low -E Vinyl Existing House 3 Window 8.5 0.770 Default 0.73 Default 180 Removed Double Metal Clear Existing House 4 Window 8.5 0.390 NFRC 0.37 NFRC 180 New Milgard Classic Low -E Vinyl Existing House 5 Window 1 8.5 0.770 Default 0.73 Default 1801 Removed Double Metal Clear Existing House 6 Window 8.5 0.390 NFRC 0.37 NFRC 180 New Milgard Classic Low -E Vinyl Existing House 7 Window 8.5 0.770 Default 0.73 1 Default 180 Removed Double Metal Clear Existing House 8 Window 8.5 0.390 NFRC 0.37 NFRC 180 New Milgard Classic Low -E Vinyl Existing House 9 Window 19.5 0.770 Default 0.73 Default 270 Removed Double Metal Clear Existing House 10 Window 19.5 0.390 NFRC 0.37 NFRC 270 New 1 Milgard Classic Low -E Vinyl Existing House 11 Window 62.7 0.770 Default 0.73 Default 0 Removed Double Metal Clear Existing House 12 Window 13.3 0.770 1 Default 0.73 Default 270 Removed Double Metal Clear Existing House 13 Window 43.3 0.770 Default 0.73 Default 270 Removed Double Metal Clear Existing House 14 Window 17.3 0.770 Default 0.73 Default 180 Removed Double Metal Clear Existing House 15 Window 17.3 0.770 Default . 1Default 0 1 Removed Double Metal Clear Existing House 16 Window 17.3 0.770 Default 0.73 1 Default 0 1 Removed I Double Metal Clear Existing House (1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value 2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS ID Exterior Shade Type SHGC Window H t Wd Ove hang Left Fin Len H M LExt RExt Dist Len Right Fin H t Dist Len H t 1 Bug Screen 0.76 2 Bug Screen 0.76 3 Bug Screen 0.76 4 Bug Screen 0.76----- _ 5 Bug Screen 0.76 r . �'i -u r-: I , X r) I LN 6 Bug Screen 0.76, A ^r ,�r-r �T 7 Bug Screen 0.76 Li I i _U 11 V' 13 -r �.. P �'.. 8 Bug Screen 0.76 A 0-o m? 1\ TP 9 Bug Screen 0.76 ` "y = '" 10 Bug Screen0.76 11 Bug Screen 0.76 12 Bug Screen 0.76 V 13 Bug Screen 0.76 14 Bug Screen 0.76 15 IBug Screen 0.76 16 JBug Screen 0.76 Ener Pro 5.1 by EnergySoft User Number: 5289 RunCode: 2014-01-22709:38:50 ID: 090513 Page 6 of 19 CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R Project Name Ave La Fonda Building Type 10 Single Family ❑ Addition Alone 1 ❑ Multi Family 2 Existing+ Addition/Alteration Date 1/22/2014 OPAQUE SURFACE DETAILS Surface Type Area U- Insulation Joint Appendix Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Roof 202 0.049 R-19 0 0 Removea 4.2.1-A4 Existing House Wall 46 0.074 R-19 90 90 New 4.3.1-A5 New Living Area Wall 406 0.074 R-19 0 90 New 4.3.1-A5 New Living Area Wall 119 0.074 R-19 1 270 90 1 New 4.3.1-A5 New Living Area Wall 58 0.074 R-19 1 180 90 New 4.3.1-A5 New Living Area Wall 194 0.074 R-19 270 90 New 4.3.1-A5 New Living Area Roof 1,166 0.028 R-38 0 0 New 4.2.2-A 19 New Living Area Slab 1,175 0.730 None 0 180 New 4.4.7-A 1 New Living Area FENESTRATION SURFACE DETAILS ID Type Area LI -Factor' SHGC Azm Status Glazing Type Location/Comments 17 Window 17.3 0.770 Default 0.73 Default 0 Removed Double Metal Clear Existing House 18 Window 19.5 0.770 Default 0.73 Default 90 Removed Double Metal Clear Existing House 19 Window 19.5 0.390 NFRC 0.37 NFRC 90 New Milgard Classic Low -E Vinyl Existing House 20 Skylight 14.3 0.390 NFRC 0.30 NFRC 0 New Marvin Clad Casemaster Low E Existing House 21 Window 13.0 0.390 NFRC 0.37 NFRC 0 New Milgard Classic Low -E Vinyl New Living Area 22 Window 3.1 0.390 NFRC 0.37 NFRC 0 New Milgard Classic Low -E Vinyl New Living Area 23 Window 41.3 0.390 NFRC 0.37 NFRC 270 New Milgard Classic Low -E Vinyl New Living Area 24 Window 96.0 0.390 NFRC 0.37 NFRC 270 New Milgard Classic Low -E Vinyl New Living Area 25 Skylight 9.0 0.550 Default 0.67 Default 0 New Double Non Metal Clear New Living Area (1) LI -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value 2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS ID Window Exterior Shade Type SHGC H t Wd Ove hanq Left Fin Len H t LExt I RExt Dist Len Ri ht Fin H t Dist Len H t 17 Bug Screen 0.76 18 Bug Screen 0.76 19 Bug Screen 0.76 20 None 1.00 A � r � I -r 21 Bug Screen 0.76 , I I U r"1 � i s Y 1-1 22 Bug Screen 0.76 M R I I I N(-, 81 SAFETY 23 Bug Screen 0.76 -, r-' 7 r f I 24 Bug Screen 0.76 r IF'yk-.ov `it OL._ 25 None 1.00 011 C(j i" I V 1 I l 114 DF TE --BY— Ener Pro 5.1 by Ener Soft User Number.- 5289 RunCode: 2014-01-22T09:38:50 ID: 090513 Page 7 of 19 CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5 CF -1 R Project Name Ave La Fonda Building Type 2 Single Family ❑ Addition Alone ❑ Multi Family 2 Existing+ Addition/Alteration Date 1112212014 BUILDING ZONE INFORMATION System Name Floor Area Zone Name New Existinq Altered Removed Volume Year Built HVAC System Existing House 1,540 12,320 1991 New 4 tons New Living Room + Bed Room 1,175 11,750 Totals 1,1751 0 1,540 0 HVAC SYSTEMS System Name Qty. Heating Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status HVAC System 1 Electric 3.50 HSPF Split Air Conditioner 13.0 SEER Setback Existing New 4 tons 1 Electric 3.50 HSPF Split Air Conditioner 13.0 SEER Setback New HVAC DISTRIBUTION System Name Duct Heating Cooling Duct Location R -Value Ducts Tested? Status HVAC System Ducted Ducted Attic, Ceiling Ins, vented 8.0 ❑ New New 4 tons Ducted Ducted Attic, Ceiling Ins, vented 8.0 ❑ New WATER HEATING SYSTEMS S stem Name Qty. Type Distribution Rated Tank Input Cap. (Btu h) al Energy Standby Factor Loss or or RE Pilot Ext. Tank Insul. R- Value Status 50 Gallon Electric 1 Small Elec. Kitchen Pipe Ins 15,359 50 0.93 n/a n/a Removed Rheem RTGH-84DVN 1 Instant Gas Kitchen Pipe Ins 157,000 0 0.94 n/a n/a New MULTI -FAMILY WATER HEATING DETAILS I HYDRONIGaHEAT=_ING SYSTEMV Control Hot Water Piping Length ff o BUILDING & SAFETY DEPT. APPROVED FOR CONS F%1 eTIONPipe System ame Length Diameter Insul. Thick. Qty. HP Plenum Outside Buried ❑ ❑ I DATE BY Ener Pro 5.1 by Ener Soft User Number., 5289 RunCode: 2014-01-22709:38:50 0: 090513 Page 8 of 19 MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R Project Name Ave La Fonda Date 1/22/2014 NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF - 1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated into the permit documents, and the applicable features shall be considered by all parties as minimum component performance specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R Form with plans. Building Envelope Measures: 116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. §116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a). 117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed. 118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form. §118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(1) when the installation of a Cool Roof is specified on the CF -1 R Form. *§1 50 a : Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor. 150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value. *§1 50 c : Minimum R-13 insulation in wood -frame wall orequivalent LI -factor. *§1 50 d : Minimum R-13 insulation in raised wood -frame floor orequivalent U -factor. 150(f): Air retarding wrap is tested, labeled and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form. 150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16. §150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration. Fireplaces, Decorative Gas Appliances and Gas Log Measures: 150 e 1 A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox. §150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device. §150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited. Space Conditioning, Water Heating and Plumbing System Measures: §110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy Commission. §113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5. §115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and spa heaters. 150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA. 150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c). §1500)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped with insulation having an installed thermal resistance of R-12 or greater. §1500)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank. §1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, nongecirculating=systems ana o,Igngth o recirculatingsections of hot water pipes are insulated per Standards Table 150-8. rtTV ��: CA I §1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping nsulated betwee h ating�sP(cE)6 i dir ct hot water tank shall be insulated to Table 150-B and Equation 150-A. BUILDIINU fir'Al §1500)2: Pipe insulation for steam hydronic heating systems or hot water systemPs >15 psi,. rneetssthe �quir rnent of Standtrds Table 123-A. i\9 W T TION 150(j)3A: Insulation is protected from damage, including that due to sunlight, mo sture, a ui ment maintenance, and wind. §1 500)3A: Insulation for chilled water piping and refrigerant suction lines includesvapor retardant or is enclosed entirely in a conditioned space. BY 150(j)4: Solar water -heating systems and/or collectors are certified by the Solar Ratie--and-Gertthca ion Cor oration. EnergyPro 5.1 by EnergySoft User Number: 5289 RunCode: 2014-01-22T09:38:50 /D: 090513 Page 9 of 19 MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF-1 R Project Name Date Ave La Fonda 1/22/2014 §150(m)1: All air-distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections 601, 602, 603, 604, 605 and Standard 6-5; supply-air and return-air ducts and plenums are insulated to a minimum installed level of R- 4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct-closure system that meets the applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used §150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. §150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. 150(m)7: Exhaust fans stems have back draft or automatic dampers. §150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers. §150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. 150 m 10: Flexible ducts cannot have porous inner cores. §150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in Section 4 of that Standard. Pool and Spa Heating Systems and Equipment Measures: §114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating ora pilot light. §114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction and return lines, or built-up connections for future solar heating. 114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover. §114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or programmed to run only during off-peak electric demand periods. 150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 Residential Lighting Measures: §150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2. 150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d). §150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. §150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line-voltage socket or line- voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a medium screw-base socket. 150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k). 150(k)7: All switching devices and controls shall meet the requirements of §150(k)7. §150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting=in*itchens-shaf'bee�iigh efficacy. EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2or 00-watts ffor)dwel�gaun is largeNr that 2500 ft2 may be exempt from the 50% high efficacy requirement when: all low efficacy luminalres�unrthe kitchen are controlled by fmanual on occupant C° tr n r � A AA Yr I SJ@1 sensor, dimmer, energy management system (EMCS), or a multi-scene progpm�rrr1aa¢feEc7dhtrol system, and allpermanently installed luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility room aYrre`nigh a fWca`cy�an, controllL d by a manual-on occupant sensor. ' � .�Tr,. �� i §150(k)9: Permanently installed lighting that is internal to cabinets shall use no morefit an ODM ff df'po er per linear foot of illuminated cabinet. DATE __BY EnergyPro 5.1 by EnergySoft User Number: 5289 RunCode: 2014-01-22T09:38:50 to: 090513 Page 10 of 19 MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF-1 R Project Name Date Ave La Fonda 1/22/2014 §150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms shall be high efficacy. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual-on occupant sensor certified to comply with the applicable requirements of §119. EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a manual-on occupancy sensor. §150(k)11: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual- on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site is not required to comply with §150 k 11. §150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between the luminaire housing and ceiling. §150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor, and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor luminaires used to comply with Exceptions to §150(k)13 may be controlled by a temporary override switch which bypasses the motion sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not be high efficacy luminaires. §150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw-base socket, and consume no more than five watts of power as determined according to §130(d). §150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable requirements of Sections 130, 131, 134, and 146. §150(k)16: Permanently installed lighting in the enclosed, non-dwelling spaces of low-rise residential buildings with four or more dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119. CITY OF LA. QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION DATE BY EnergyPro 5.1 by EnergySoft User Number: 5289 RunCode: 201401-22709:38:50 /D: 090513 Page 11 of 19 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Ave La Fonda Date 1/22/2014 System Name HVAC System Floor Area 1,540 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL CFM Total Room Loads 827 Return Vented Lighting Return Air Ducts Return Fan Ventilation 0 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK COIL HTG. PEAK Heating System Sensible Latent CFM Sensible Output per System 0 16,565 2,327 351 13,520 Total Output Btuh 0 0 Output Btuh/s ft 0.0 956 664 Cooling System 0 0 Output per System 35,000 0 0 0 0 Total Output Btuh 35,000 0 2,327 0 Total Output Tons 2.9 956 664 Total Output Btuh/s ft 22.7 Total Output s ft/Ton 528.0 1 18,478 14,849 Air System CFM per System 0 HVAC EQUIPMENT SELECTION Airflow cfm 0 Goodman GSX130361B* 28,185 1,846 0 Airflow cfm/s ft 0.00 Airflow cfm/Ton 0.0 Outside Air % 0.0% Total Adjusted System Output 28,185 1,846 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK Aug 3 PM 0 Outside Air cfm/s ft 0.00 Note: values above given at ARI conditions Jan 1 AM HEATING SYSTEM PSYCHROMETRICS jAirstream Temperatures at Time of Heating Peak 26 OF Outside Air 0 cfm 67 OF 67 OF 105 OF Heating Coil 104 OF ROOM 68 OF if\ R 1 A Ile A'I(" ,i1. COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak - bk V! v f 5 � A 112178 °F Outside Air Ar 0 cfm 76 / 63 OF 76 / 63 °F 55 / 54 °F BUILDING & SAFE -I Y UEH I - - APP O ED O C N T �'.�� Cooling Coil DATE By_56 / 54 OF 1.6% ;ROOM 75 / 62 OF I EnergyPro 5.1 by EnergySoft User Number: 5289 RunCode: 201401-22T09:38:50 ID: 090513 Page 12 of 19 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Ave La Fonda Date 1/22/2014 System Name New 4 tons Floor Area 1,175 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING CFM Sensible Total Room Loads 690 13,760 Return Vented Lighting 0 Return Air Ducts 794 Return Fan 0 Ventilation 0 0 Supply Fan 0 Supply Air Ducts 794 TOTAL SYSTEM LOAD 1 15,348 PEAK COIL HTG. PEAK Heating System Latent CFM Sensible Output perSystem 01 1,365 251 9,692 Total Output Btuh 0 Output Btuh/s ft 0.0 476 Cooling System 0 Output perSystem 35,000 0 0 0 Total Output Btuh 35,000 1,365 0 Total Output Tons 2.9 476 Total Output Btuh/s ft 29.8 Total Output s ft/Ton 402.9 10,644 Air System CFM perSystem 0 HVAC EQUIPMENT SELECTION Airflow cfm 0 Goodman GSX130361B* 28,431 1,495 0 Airflow cfm/s ft 0.00 Airflow cfm/Ton 0.0 Outside Air % 0.0% Total Adjusted System Output (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 1 28,431 1,495 1 0 Outside Air cfm/s ft 0.00 Note: values above given at ARI conditions Aug 3 PM Jan 1 AM HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF Outside Air 0 cfm 67 OF 67 OF 105 OF Heating Coil _ 104 OF ROOM i 68 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Tim of Cpoling Peak A A I I � I�- M 112 / 78 OF Outside Air 0 cfm 76163 OF nasiI 'V I Y—i * , I ... .. 76 / 63 °F 55 / 54 °F BUILDING & SAFETY DEPT. c - TR C TR TION Cooling Coil 56154 OF DATE BY i 75 / 62 OF I EnergyPro 5.1 by EnergySoft User Number: 5289 RunCode: 2014-01-22709:38:50 ID: 090513 Page 13 of 19 ROOM LOAD SUMMARY Date Ave La Fonda 1/22/2014 System Name Floor Area HVAC System 1,540 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult. I CFM I Sensible I Latent CFM I Sensible I Latent CFM I Sensible Existing House Existing House 1 1 827 16,565 2,327 8271 16,5651 2,327 3511 13,520 BUILL 01NCU !F bAt- p.pR:>,(_)1 FC R CO vSYR DATE — BY. PAGE TOTAL TOTAL" I ' Total includes ventilation load for zonal 827 16,565 2,327 351 13,520 827 16,565 2,3271 351 13,5201 EnergyPro 5.1 by EnergySoR User Number: 5289 RunCode: 201401-22709:38:50 /D: 090513 Page 14 of 19 ROOM LOAD SUMMARY 13,7601 1,3651 251 Project Name Ave La Fonda 690 Date 1/22/2014 System Name New 4 tons Floor Area 1,175 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK Zone Name Room Name Mult. CFM Sensible I Latent CFM I Sensible I Latent I CFM Sensible New Living Area New Living Room + Bed F 1 690 13,7601 1,365 6901 13,7601 1,3651 2511 9, 692 PAGE TOTAL TOTAL* I * Total includes ventilation load for zonal 0W 690 13,7601 1,3651 251 9,692 690 13,7601 1,3651 251 9,6921 EnergyPro 5.1 by EnergySoft User Number: 5289 RunCode: 201401-22709:38:50 ID: 090513 Page 15 of 19 1 ROOM HEATING PEAK LOADS Project Name Ave La Fonda 771122/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Existing House Floor Area 1,540.0 ft2 Indoor Dry Bulb Temperature 68 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X XR to U -Value AT °F X 42 = = = = = = = = = = = = = = = = = = = = = = = = = = = Btu/hr Default Wall 1978 to 1991 862.6 0.1100 3,985 Milgard Classic Low -E Vinyl 84.0 0.3900 X 42 1,376 Wood Door 38.9 0.5000 X 42 X 42 X 42 X 42 817 R-13 Wall 92.5 0.1020 396 Default Roof 1978 to Present 1,324.2 0.0490 2,725 Marvin Clad Casemaster Low E 14.3 0.3900 234 X X X X X X X X X X X X X X X X X X X X X U1I�r- F— E Co age otal g—X- PT. 42 ��N��LX.� i� 1J FOR'- anot er room 8� �( �—y Heig Items shown with an asterisk (') denote conduction Infiltration: 1.00 X 1.064 Schedule Air Sensible Fraction through an interior surface X 1,540 X Area 9,534 3,986 Ceiling TOTAL HOURLY HEAT LOSS FOR ROOM 13,520 EnergyPro 5.1 by EnergySoft User Number: 5289 RunCode. 2014-01-22709:38:50 ID: 090513 Page 16 of 19 ROOM HEATING PEAK LOADS Project Name Ave La Fonda Date 1 1/22/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name New Living Room + Bed Room Floor Area 1,175.0 ft2 Indoor Dry Bulb Temperature 68 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area X X X X X X X X X X X X X X X X X X X X X X X X X X--- x x x x x to Ceiling U -Value X X X X X X X X X X X X X X X X X X X X X X X X X X RI �R CXR x AT *F = = = = = = = = = ' 0 ID I� Btu/hr R-19 Wall 823.2 0.0740 42 2,559 Milgard Classic Low -E Vinyl 153.4 0.3900 42 2,513 R-38 Roof Cathedral 1,166.0 0.0280 42 1,371 Double Non Metal Clear 9.0 0.5500 42 208 OF LAW.1�1T BUI VG & SAFE T R . Q CONSTRU i another r oPATE ______ 10.00 X 0.347 Height ACH Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.064 Schedule Air Sensible Fraction through an interior surface X 1,175 X Area image Total /60] X AT 6,650 42 = 3,041 TOTAL HOURLY. HEAT LOSS FOR ROOM 9,692 EnergyPro 5.1 by EnergySoft User Number., 5289 RunCode: 2014-01-22709:38:50 ID: 090513 Page 17 of 19 RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Ave La Fonda 1/22/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name Existing House Outdoor Dry Bulb Temperature 112 OF Floor Area 1,540.0 ft2 Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature 75 OF Outdoor Daily Range: 34 OF Opaque Surfaces Orientation Area U -Factor CLTD' Btu/hr Default Wall 1978 to 1991 (S) 389.0 X 0.1100 X 26.0 = 1,113 Wood Door (S) 20.0 X 0.5000 X 26.0 = 260 Default Wall 1978 to 1991 (E) 309.6 X 0.1100 X 33.0 = 1,124 R-13 Wall (lM 92.5 X 0.1020 X 33.0 = 311 Wood Door (E) 18.9 X 0.5000 X 33.0 = 312 Default Wall 1978 to 1991 (N) 164.0 X 0.1100 X 23.0 = 415 Default Roof 1978 to Present (N) 1,324.2 X 0.0490 X 56.0 = 3,634 X X = X X = Page Total 7,168 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr New Window (S) 0.0 X 21.5 + 19.5 X 21.6 = 422 New Window (S) 0.0 X 21.5 + 8.5 X 21.6 = 184 New Window (S) 0.0 X 21.5 + 8.5 X 21.6 = 184 New Window (S) 0.0 X 21.5 + 8.5 X 21.6 = 184 New Window (W) 0.0 X 21.5 + 19.5 X 43.5 = 848 New Window (E) 0.0 X 21.5 + 19.5 X 43.5 = 848 Skylight (N) 0.0 X 19.3 + 14.3 X 59.9 = 857 X + X - X + X - Page Total 3,526 Internal Gain Btu/hr Occupants 4.0 Occupants X _?30 Btuh/occ. ^`d� 920 Equipment 1.0 Dwelling Unit X�"j`f,6001�t� Q�I'V /- 1,600 �,. . & SAFETY DEPT. �.'JILDING Infiltration: 1.064 X 0.89 X 95.36 X � 37 ���®��® 3,351 Air Sensible CFM ELA °T FOR CONSTRUCTION TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 16,565 DATE �- Latent Gain Btu/hr Occupants 4.0 Occupants X 200 Btuh/occ. = 800 Infiltration: 4,771 X 0.89 X 95.36 X 0.00376 = 11527 Air Sensible CFM ELA AW TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2,327 Ener Pro 5.1 by Ener Soft User Number: 5289 RunCode: 2014-01-22T09:38:50 ID: 090513 Pae 18 of 19 RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Ave La Fonda 1/22/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name New Living Room + Bed Room Outdoor Dry Bulb Temperature 112 OF Floor Area 1,175.0 ft2 Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb,Tem erature 75 OF, Outdoor Daily Range: 34 OF s Opaque Surfaces Orientation Area U -Factor CLTD' Btu/hr R-19 Wall (E) 45.8 X 0.0740 X 33.0 = 112 R-19 Wall (N) 406.4 X 0.0740 X 23.0 = 692 R-19 Wall (W) 312.7 X 0.0740 X 33.0 = 764 R-19 Wall (S) 58.3 X 0.0740 X 26.0 = 112 R-38 Roof Cathedral (N) 1,166.0 X 0.0280 X 56.0 = 1,828 X X = X X = X X = X X = Page Total 3,508 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr New Window (N) 0.0 X 21.5 + 13.0 X 21.5 = 280 New Window (round) (N) 0.0 X 21.5 + 3.1 X 21.5 = 67 New door (W) 0.0 X 21.5 + 41.3 X 43.5 = 1,796 New door (W) 0.0 X 21.5 + 96.0 X 43.5 = 4,176 Skylight (N) 0.0 X 36.7 + 9.0 X 127.4 = 1,146 X + X - X + X - X + X - X + X - Page Total 7,465 Internal Gain Btu/hr 1.0 Occupants Occupants X 30 -Btub/o = Equipment 0.0 Dwelling Unit X Iy Wo htA QU�l�1 230 0 I G & SAFETY DEPT. r-� Infiltration: 1.064 X 0.89 X 72.76 X 37 = T' PROVED 2,557 Air Sensible CFM ELA T OR CONSTRUCTION TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 13,760 byLatent Gain Btu/hr Occupants 1.0 Occupants X 200 Btuh/occ. = 200 Infiltration: 4, 771 X 0.89 X 72.76 X 0.00376 = 1,165 Air Sensible CFM ELA AW TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 1,365 Ener Pro 5.1 by Ener Soft User Number 5289 RunCode: 2014-01-22709:38:50 ID: 090513 Pae 19 of 19