08-1709 (AC) Title 24TITLE 24 REPORT
Title 24 Report for:
Desert Sage Restaurant (Skylight Addition)
78-065 Avenida Lafonda
La Quinta, CA 92253
B ITyOF
U1LDING & sA QUIN7-A
' DlEp-r
Pro'ect.Desi ner• F RPPR0VE
. J 9 CO D
71ON
Benjamin Hertz Archit
645 Oleander Road y
Palm Springs, CA 92264
(760) 320-1644
R
Report Prepared By:
C.J. McFadden
BREEZE AIR CONDITIONING
75-145 ST. CHARLES PLACE
PALM DESERT, CA 92211
(760) 346-0855
4
Job Number:
Date:
10/29/2008
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.4 by EnergySoft Job Number: User Number: 3665
I TABLE OF CONTENTS I
Cover Page
Table of Contents
z
Form ENV -1-C Certificate of Compliance
Form ENV -3-C Overall Envelope Method
Form ENV -MM Envelope Mandatory Measures
Form MECH=1-C Certificate of Compliance
Form MECH-3-C, Mechanical Ventilation
Form MECH-4-C HVAC Misc. Prescriptive Requirements
Form MECH-MM Mechanical Mandatory Measures
HVAC System Heating and Cooling Loads Summary
Zone Load Summary
Room Load Summary '
Room Heating Peak Loads
Room Cooling Peak Loads
Room Cooling Coil Loads
1
2
3
6
14
15
17
18
20
22
24
26
28
30
32
I EnergyPro 4.4 by EnergySoft Job Number. User Number: 3665
CERTIFICATE OF COMPLIANCE (Part 1 of 2) ENV -1-C
PROJECT NAME
DATE
Desert Sage Restaurant (Skylight Addition
10/29/2008
PROJECT ADDRESS
"–
78-065 Avenida Lafonda La Quintat
a
PRINCIPAL DESIGNER - ENVELOPE
TELEPHONE
?Butldmg'Fermit
Benjamin Hertz Architects
(760) 320-1644
DOCUMENTATION AUTHOR
TELEPHONE
Checked.by/Date
BREEZE AIR CONDITIONING
(760) 346-0855
Enforcement Agenc Use'
GENERAL INFORMATION
DATE OF PLANS
BUILDING CONDITIONED FLOOR AREA
CLIMATE ZONE
3,551 Sq.Ft.
1 15
BUILDING TYPE [—X] NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM
❑ RELOCATABLE- Indicate:❑ Specific Climate - list: , or ❑ All Climates
PHASE OF CONSTRUCTION ❑ NEW CONSTRUCTION ❑ ADDITIONX❑ ALTERATION ❑ UNCONDITIONED (File Affidavit)
METHOD OF ENVELOPE ❑ COMPONENT(ENV-2-C) ' r OVERALL ENVELOPE(ENV-3-C) ❑ PERFORMANCE
COMPLIANCE
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24,
Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building envelope requirements.
The documentation preparer hereby certifies that the document is accurate and complete.
DOCUMENTATION AUTHOR
SIGNATURE
DATE
C.J. McFadden
1 i01o .o
The Principal Envelope Designer hereby certifies that the proposeif build' g design represented in this set of construction
documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other
calculations submitted with this permit application. The proposed building has been designed to meet the envelope
requirements contained in Sections 110, 116 through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
Please check one:
❑ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this
document as the person responsible for its preparation; and that I am licensed in the state of California as a civil engineer
or mechanical engineer, or I am a licensed architect.
❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 or
6737.3 to sign this document as the person responsible for its preparation; and that I am a
licensed contractor performing this work.
❑ I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains
to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538, and
6737.1.
PRINCIPAL ENVELOPE DESIGNER - NAME
SIGNATURE
DATE
LIC. #
Benjamin Hertz Architects
ENVELOPE MANDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures
ENVELOPE COMPLIANCE FORMS & WORKSHEETS Check box if worksheet is included
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the Nonresidential Manual published bl.
the California Energy Commission.
®ENV -1-C: Certificate of Compliance. Required on plans for all submittals. Part 2 may be incorporated in schedules on plans.
❑ENV -2-C: Used Envelope Component compliance method
®ENV -3-C: Used with Overall Envelope Compliance method
DENV-4-C: Optional. Use for minimum skylight requirements for large enclosed spaces
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:3 of 33
CERTIFICATE OF COMPLIANCE (Part 2 of 2) ENV -1 -C
PROJECT NAME DATE
Desert Sage Restaurant (Skylight Addition) 10/29/2008
OPAQUE SURFACES
# Surface
Type
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Azm.
Tilt
Cond'
Status
Joint Appendix
IV Reference
Location / Comments
1 Roof
3.182
0.049
R-19
R-0.0
315
45
Existing_01-A4
(N)
Existina Restaurant
2 lWall
41
0.074
R-19
R-0.0
0
90
Existing
09-A5
Existing Restaurant
3 lWall
11
0.074
R-19
R-0.0
0
90
Removed
09-A5
Existing Restaurant
4 lWall
59
0.074
R-19
R-0.01
90
90
Existing
09-A5
Existing Restaurant
5 Wall
93
0.074
R-19
R-0.0
90
90
lRemoved
09-A5
Existing Restaurant
6 lWall
45
0.074
R-19
R-0.0
180
90
Existing
0.83
Existing Restaurant
7 lWall
1 84
0.074
R-19
R-0.0
180
90
-09-A5
Removed
09-A5
Existing Restaurant
8 1wall
1 59
0.074
R-19
R-0.0
270
90
Existing
09-A5
Existing Restaurant
9 lWall
1 57
0.074
R-19
R-0.0
270
90
Removed
09-A5
Existing Restaurant
10 IRoof
I 0
0.297
None
R-0.0
0
0
New
02 -Ai
New Dining Area
11 Wall
1 5
0.074.
R-19
R-0.01
0
90
New
09-A5
New Dining Area
12 Wall
54
0.074
R-19
R-0.0
90
90
New
09-A5
New Dining Area
13 Wall
51
0.074
R-19
R-0.0
180
90
New
09-A5
New Dining Area
14 Wall
54
0.074
R-19
R-0.0
270
90
New
09-A5
New Dining Area
- N, E, A. R (New, Existing, Altered, Removed)
FENESTRATION SURFACES
1FI
More than or equal to 10,000 sq.. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default Ll -factors from
I Slandards Tahle 116-A and R r lifimip shall he filed in the rnntmrtnrs nrniert nffice durina rnnstmrfinn and in the huildino manners office after construction
ye
illyTindow
##
Window Overhang Left Fin Right Fin
Exterior Shade Type SHGC Hgt. Wd. Len. Hgt. LExt.RExt. Dist. Len. Hgt. Dist. Len. Hgt_
Area U -Fac'
SHGC 2
Act. Cond.
Azm. Stat. Glazing Tye
Location/
Comments
7_1
Rear
(N)
48 1.250 116-A
0.80
116-B
0 Existing Existing French Door
Existing Restaurant
2 iWindow
Rear
(N)
40 1.250 116-A
0.80
116-B
0 Removed Existing French Door
Existing Restaurant
3 lWindow
Rear
(N)
1 40 1.250 116-A
0.80
116-B
0 Removed Existing French Door
Existing Restaurant
4 Window
Right
E
128 1.250 116-A
0.80
116-B
901 Removed Existing SGD
Existing Restaurant
5 lWinclow
Front
S
20 1.250 116-A
0.80
116-B
180 Removed I Existing French Door
Existing Restaurant
6 lWindow
Front
(S)
12 1.190 116-A
0.83
116-B
180 Removed Existing Fixed Window
Existing Restaurant
7 lWindow
Front
(S)
48 1.250 116-A
0.80
116-B 1
180 Removed Existing French Door
Existing Restaurant
8 lWindow
Front
S
12 1.1901 116-A
0.83
116-B1
180 Removed Existing Fixed Window
Existing Restaurant
9 (Window
Front
(S)
20 1.250 116-A
0.80
116 -BI
180 Removed Existing French Door
Existing Restaurant
10 Window
Left
(W)
12 1.190 116-A
0.83
116 -BI
270 Removed Existing Fixed Window
Existing Restaurant
11 lWindow
Left
(W)
40 1.250 116-A
0.80
116-B 1
2701 Removed Existing French Door
Existing Restaurant
12 lWindow
Left
(W)
12 1.190 116-A
0.83
116 -BI
2701 Removed Existing Fixed Window
I Existing Restaurant
13 iWindow
Left
(W)
12 1.190 116-A
0.83
116 -BI
2701 Removed Existing Fixed Window
I Existing Restaurant
(1)1.1 -factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
(2) SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
##
Window Overhang Left Fin Right Fin
Exterior Shade Type SHGC Hgt. Wd. Len. Hgt. LExt.RExt. Dist. Len. Hgt. Dist. Len. Hgt_
1
j None 0.76
2
None 0.76
7_1
None 0.76
4
None 0.76
5
None 0.76
6
None 0.76
7
None 0.76
8
None 0.76
9
None 0.76
10
None 0.76
11
None 0.76
12
1 None 1 0.76
13
lNone 10.76
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
The proposed building Is In climate zones 2 through 15 and contains an enclosed space with Floor area greater than 25,000 W, a ceiling height greater than 15 feet, and an LPD for general
lighting of at least 0.5 W/ft2. See Section 143(c). If this box Is checked, ENV -4-C must be filled out. when submitting under the Prescriptive Compliance Approach.
i EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:4 of 33 1
CERTIFICATE OF COMPLIANCE art 2 o ENV -1 -C1
PROJECT NAME DATE
Desert Sage Restaurant Skylight Addition 10/29/2008
OPAQUE SURFACES
# I Surface Insulation Act. Cond. lint Appendix
Tvne Area U -Fac. Cay. Cont. Azm. Tilt Status I IV Reference I Location/ Comments
N, E. A, R (New, Existing, Altered, Removed)
FENESTRATION SURFACES
FMore than or equal to 10,000 sq.fl. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default LI -factors from
Standards Table 116-A and B. Ceniftcate shall be filed in the contractor's oroiect office during construction and in the building managers office after construction
# Tye
Area U -Fac'
SHGC2
Act. Cond.
Azm. Stat. Glazing Type
Location/
Comments
14 iWindow Left W
48 1.250 116-A
0.80 116-B
2701 Removed Existing French Door
Existing Restaurant
15 lWindow Left (W)
40 1.250 116-A
0.80 116-B
270 Removed Existing French Door
Existing Restaurant
16 ISkylight Rear (N)
369 0.340 NFRC
0.27 NFRC
0 New Polycarb Skylight
New Dining Area
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
(1) U -factor Type:116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
(2) SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR
SHADING
##
Exterior Shade Type SHGC
Window Overhang Left Fin Right Fin
Hgt. Wd. Len. Hgt. LExt.RExt. Dist. Len. Hgt Dist. Len. Hgt.
14
None 0.76
15
None 0.76
16
None 1.00
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
f The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a ceiling height greater than 15 feet, and an LPD for general
U lighting of at least 0.5 W/ft2. See Section 143(c). If this box Is checked, ENV4-C must be filled out. when submitting under the Prescriptive Compliance Approach.
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:5 of 33 1
OVERALL ENVELOPE METHOD (Part 1 of 7) ENV -3-C
PROJECT NAME � DATE
Desert Saqe Restaurant (Skvlight Addition) 10/29/2008
WINDOW AREA CALCULATION
A. DISPLAY PERIMETER O ftx 6 ft =
Q ft' DISPLAY AREA
B. GROSS EXTERIOR WALL AREA 2,318 ftx 0.40 =
9271 W 40% GROSS WALL AREA
C. ENTER LARGER OF A OR B 2,318
927 W MAXIMUM STND. AREA
D. ENTER PROPOSED WINDOW AREA
481 W PROPOSED AREA
E. WINDOW WALL RATIO = Proposed Window Area Divided by Gross Exterior Wall Area
= 2.070/1,
F. WEST DISPLAY PERIMETER 0 ftx 6 ft =
Q w WEST DISPLAY AREA
G. WEST EXTERIOR WALL AREA 649 ftx 0.40 =
260 ft'40% WEST WALL AREA
H. ENTER THE LARGER OF F AND G 649
260 ftZ MAX. STND. WEST AREA
I. ENTER PROPOSED WEST WINDOW AREA
01 ftZ PROPOSED WEST AREA
J. WEST WINDOW WALL RATIO= Proposed West Window Area Divided by West Exterior Wall Area= 0.000/10
Combined Values for North, East and South Walls
K. N/EIS DISPLAY PERIMETER (A - F) 01 ftx 6 ft =
Q ft WEIS DISPLAY AREA
1, 6 6 91
6681 ft� 40% N/EIS AREA
L. N/EIS EXTERIOR WALL AREA (B - G) ftx 0.40 =
M. ENTER LARGER OF K OR L 1669
6681 ft MAX. STAND. WE/S AREA
N. PROPOSED N/E/S WINDOW AREA (D -1)
481 W PROPOSED N/E/S AREA
WINDOW ADJUSTMENT
O. IF D > C and/or if I > H, PROCEED TO CALCULATION STEPS 1 OR 2, AS APPROPRIATE, FOR THE WINDOW AREA ADJUSTMENT. IF NOT,
GO TO THE SKYLIGHT AREA TEST, ENV -3-C, PART 2 OF 7.
1. IF I < H: Use the calculated Window adjustment for all walls.
MAXIMUM STANDARD PROPOSED WINDOW
WINDOW
AREA (from C) AREA (from D)
ADJUSTMENT FACTOR
2. IF I > H: Calculate one window adjustment factor (WAF) for the West wall.
a. Calculate the WAF for the West wall.
MAX. STANDARD WEST PROPOSED WEST
WEST WINDOW
AREA (from H) AREA (from 1)
ADJUSTMENT FACTOR
b. If N > M: Calculate the WAF for the North, East and South walls.
MAX. STANDARD NIE/S PROPOSED N/E/S
N/E/S WINDOW
AREA from M) AREA (from N)
ADJUSTMENT FACTOR
GO TO PART 7 TO CALCULATE ADJUSTED AREAS.
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number:
Page:6 of 33
OVERALL ENVELOPE METHOD (Part 2 of 7) ENV -3-C
-r
PROJECT NAME DATE
Desert Sage Restaurant (Skylight Addition 10/29/2008
A. ATRIUM HEIGHT 14 ft
GROSS STANDARD ALLOWED
ROOF AREA SKYLIGHT AREA
B. IF <= 55 FT 3,551 ft'x 0.05 = 178 ft:
C. IF > 55 FT f'x 0.10 = ftZ
D. PROPOSED SKYLIGHT AREA 369 ft2
IF THE PROPOSED SKYLIGHT AREA IS GREATER THAN THE STANDARD SKYLIGHT AREA, PROCEED
TO THE NEXT CALCULATION FOR THE SKYLIGHT AREA ADJUSTMENT. IF NOT, GO TO PART 3 OF 7.
1. IF PROPOSED SKYLIGHT AREA >= STANDARD SKYLIGHT AREA:
PROPOSED SKYLIGHT AREA SKYLIGHT
STANDARD SKYLIGHT AREA (IF E = 0 ENTER 1) ADJUSTMENT FACTOR
1781 369 = 0.481
GO TO PART 7 TO CALCULATE ADJUSTED AREAS.
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:7 of 33
OVERALL ENVELOPE METHOD (Part 3 of 7) ENV -3-C
PROJECT NAME
A
ASSEMBLY NAME
(e.g. Wall -1, Floor -1)
Existing Roof
North Wall (Existing)
FrenchDr (6080) (E)
East Wall (Existing)
South Wall (Existing)
West Wall (Existing)
Polycarb Skylight (Plastic)
North Wall
East Wall
South Wall
I West Wall
B C D I I E
PROPOSED
AREA
HEAT
CAP.
U-
FACT'
ACM
J.A. IV Ref.
UA
(B X D)
3,182
162.3
0.049
01-A4
155.9
411
0.470
0.074
09-A5
30.4
48
4591
1.250
46.8
60.0
595
60.7
0.074
09-A5
44.0
4591
0.102
0.074
09-A5
34.0
595
51
0.074
09-A5
44.0
369
5.5
0.3401
125.5
51
0.074
09-A5
3.8
54
0.074
09-A5
4.0
51
0.074
09-A5
3.8
54
0.074
09-A5
4.0
DATE
F I G I H
STANDARD
AREA*
(Adjusted)
U-
FACT.
UA
(F X G)
3,182
0.051
162.3
411
0.102
41.9
48
0.470
22.6
595
0.102
60.7
4591
0.102
46.8
595
0.102
60.7
178
1.320
234.4
51
0.102
5.2
541
0.102
5.5
51
0.102
5.2
54
0.102
5.5
1) In climate zones 1 and 16 the insulating R -value of continuous *If Window and/or Skylight Area Adjustment is
insulation materials installed above the roof waterproof Required, use Adjusted Areas from Part 7 of 7. 509 This Page Total 65
membrane shall be multiplied times 0.8 before choosing the
table column for determining assebmly U -factor. See Footnotes, 509 Building Tota I 66
Tables IV.1 through IV.7 in the Joint Appendices.
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:8 of 33
OVERALL ENVELOPE METHOD (Part 4 of 7) ENV -3-C
PROJECT NAME DATE
Desert Sage Restaurant Sk li ht Addition 10/29/2008
VERALL HEAT GAIN FROM CONDUCTION
A
B C D E F
G H I I J
ASSEMBLY NAME
(e.g. Wall -1, Floor -1)
PROPOSED,
STANDARD
AREA
TF
HEAT
CAP.
U-
FACT.
ACM
J.A. IV Ref.
HEAT
GAIN
(BxCxE)
AREA*
(Adjusted)
U-
FACT.
TF
HEAT
GAIN
(GxHxl)
Existing Roof
3,182
55 1
0.049
01-A4
8,575
3,182
0.051
55
8,926
North Wall (Existing)
411
55
0.074
09-A5
1,673
411
0.102
55
2,306
FrenchDr (6080) (E)
48
55 1
1.250
3,300
48
0.470
55
1,241
East Wall (Existing)
595
55
0.074
09-A5
2,422
595
0.102
55
3,338
South Wall (Existing)
459
55
0.074
09-A5
1,868
459
0.102
55
2,575
West Wall (Existing)
595
55
0.074
09-A5
2,422
595
0.102
55
3,338
Polycarb Skylight (Plastic)
369
55
0.340
6,900
1781
1.320
55 1
12,890
North Wall
51
55
1
0.074
09-A5
208
51
0.102
55
286
East Wall
54
55
0.074
09-A5
220
54
0.102
55
303
South Wall
51
55
0.074
09-A5
208
51
0.102
55
286
West Wall
54
55
0.074
09-A5
220
54
0.102
55
303
1) In climate zones 1 and 16 the insulating R -value of continuous
insulation materials installed above the roof waterproof membrane
shall be multiplied times 0.8 before choosing the table column for
determining assembly U -factor. See footnotes, Tables IVA
through IV.7 in the Joint Appendices.
If Window and/or Skylight Area Adjustment is
Required, use Adjusted Areas from Part 6 of 7.
28,015 35,791
Subtotal Subtotal
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:9 of 33
(Part 5 of 7) ENV -3-C
PROJECT NAME DATE
Desert Saqe Restaurant (SkVlight Addition) I
10/29/2008.
ROOF ABSORPTANCE CALCULATION
R-0 Roof Cathedral
CHECK APPLICABLE BOXES
H I J K
Case 1 -Proposed YES NO
STANDARD
1. CRRC-1 Certified?
2. Is the thermal emittance > 0.75?
3. Enter the initial reflectance pwt value:
4. Calculate a o.", = 0.94 - 0.7 p m—P
AREA
Go to 2.
Go to 3.
X
Go to 8.
Go to 5.
Go to 4. Insert value in calculation.
Enter calculated value in Column F below.
Absorp
HEAT GAIN
(BxCxDxExF)
Pm.o,00 =
a a", =
Absorp
Case 2 - CRRC-1 Tested
Existing Roof
5. Enter initial reflectance & emittance values from CRRC-1
6. Calculate pR.o,", = - 0.448 + 1.121 pw,+ 0.524 Ewt
7. Calculate a P. , = 0.94 - 0.7 p Rto,�
123
Ewe = Go to 6. Insert values in calculation.
Go to 7. Insert value in calculation.
Enter calculated value in Column F below.
pw, =
pRkPWP =
a ".p =
3 182
8. Not CRRC-1 Tested
0.73
13.406
For nonresidential low -sloped roofs:
For all other roofs:
a ,., = 0.87 Enter default value in Column F below.
a Pac = 0.73 Enter default value in Column F below.
Standard absorptance values for Column J are either
For nonresidential low -sloped roofs:
For all other roofs:
a.. = 0.45 Enter standard value in Column J below.
a.. = 0.73 Enter standard value in Column J below.
(OVERALL HEAT GAIN FROM RADIATION OPAQUE SURFACES I
A0
;x
i
o y
B C D E F G
H I J K
PROPOSED
STANDARD
ASSEMBLY NAME
(e.g. Roof -1)
AREA
SF
WF
U-
FACTOR
Absorp
HEAT GAIN
(BxCxDxExF)
AREA'
(ADJUSTED)
U -Factor
Absorp
HEAT GAIN
(CxDxHxlxJ)
Existing Roof
3,182
123
0.92
0.049
0.73
12.880
3 182
0.051
0.73
13.406
12 88 Subtotals are entered under "Subtotal" 13 406
SUBTOTAL in COLUMNS I and M of ENV -3-C, Part SUBTOTAL
6of7.
EnerovPro 4.4 by EnergvSoft User Number: 3665 Job Number: Page: 10 of 33
(Part 5 of 7) ENV -3-C
PROJECT NAME DATE
Desert Saae Restaurant (Skvlight Addition) I
10/29/2008
ROOF ABSORPTANCE CALCULATION
Default Roof 1978 to Present
CHECK APPLICABLE BOXES
F�
0—
B C D E F G
Case 1 -Proposed YES NO
STANDARD
1. CRRC-1 Certified?
2. Is the thermal emittance > 0.75?
3. Enter the initial reflectance p pit value:
4. Calculate a,.,p = 0.94 - 0.7 p Ri-,p
AREA
Go to 2.
Go to 3.
X
Go to 8.
Go to 5.
Go to 4. Insert value in calculation.
Enter calculated value in Column F below.
Absorp
HEAT GAIN
(BxCxDxExF)
pR.P.P =
a ,,., =
Absorp
Case 2 - CRRC-1 Tested
5. Enter initial reflectance & emittance values from CRRC-1
6. Calculate pm -.p = - 0.448 + 1.121 pw, + 0.524 Ew.
7. Calculate a,..p = 0.94 - 0.7 p Ri.p p
Ew = Go to 6. Insert values in calculation.
Go to 7. Insert value in calculation.
Enter calculated value in Column F below.
pm =
pR.,,., =
a,,.p =
8. Not CRRC-1 Tested
For nonresidential low -sloped roofs:
For all other roofs:
a pm = 0.87 Enter default value in Column F below.
a w.p = 0.73 Enter default value in Column F below.
Standard absorptance values for Column J are either
For nonresidential low -sloped roofs:
For all other roofs:
a .e = 0.45 Enter standard value in Column J below.
a.a = 0.73 Enter standard value in Column J below.
OVERALL HEAT GAIN FROM RADIATION OPAQUE SURFACES
a o'
o �
A
F�
0—
B C D E F G
H I J K
STANDARD
ASSEMBLY NAME
(e.g. Roof -1)
AREA
SF
WF
U-
FACTOR
Absorp
HEAT GAIN
(BxCxDxExF)
AREA'
(ADJUSTED)
U -Factor
Absorp
HEAT GAIN
(CxDxHxlxJ)
L� Subtotals are entered under "Subtotal"
SUBTOTAL in COLUMNS I and M of ENV -3-C, Part SUBTOTAL
6of7.
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 11 of 33
a o'
o �
PROPOSED
STANDARD
ASSEMBLY NAME
(e.g. Roof -1)
AREA
SF
WF
U-
FACTOR
Absorp
HEAT GAIN
(BxCxDxExF)
AREA'
(ADJUSTED)
U -Factor
Absorp
HEAT GAIN
(CxDxHxlxJ)
OVERALL ENVELOPE METHOD (Part 6 of 7) ENV -3-C'
PROJECT NAME DATE
Desert Sage Restaurant (Skylight Addition) 1 10/29/2008
OVERALL HEAT GAIN FROM RADIATION FENESTRATION SURFACES
A
B
C D E I I
J K I L M
.WINDOW/SKYLIGHT NAME
(e.g. Wind -1, Sky -1) ORIENT.
WEIGHTING
FACTOR
PROPOSED
STANDARD
AREA
SF
1
SHGC
OVERHANG
HEAT GAIN?
(BxCxDxExH)
AREA 3
(ADJUSTED)
RSHG 4
or SHGC
SF
HEAT GAIN
(BxJxKxL)
H
V
H[V
OHF
FrenchDr6( 080) Q N
0.61
48
123
0.80
Part 6 Subtotal
from Part 6 of 7.
2,881
48
0.61
123
2197
Polycarb Skylight H
2.29
369
123
0.27
EnergyPro 4.4 by EnergySoft User Number: 3665
Job Number:
Page:12 of 33
28.063
178
0.58
123
29,006
1. From Fenestration Surfaces ENV -1-C, Part 2, Column G, or when Column
Part 4 Subtotal 28,015
Part 4 Subtotal
36,328
H has a "C identifier, calculate using the center of glass value SHGCc in
SHGCfen =.08 + (0.86xSHGCc) and enter value.
12 880
Part 5 Subtotal
13,903
2. Proposed Heat Gain, Column I may be no greater than Standard Heat
Part 5 Subtotal
Gain Column M.
30,944
31,203
3. If Window and/or Skylight Area Adjustment is required, use adjusted area
Part 6 Subtotal
Part 6 Subtotal
from Part 6 of 7.
4. Only SHGC is used for Skylights
71,839
Total Heat Gain
81,434
EnergyPro 4.4 by EnergySoft User Number: 3665
Job Number:
Page:12 of 33
OVERALL ENVELOPE METHOD Part 7 of 7 ENV -3-C
PROJECT NAME DATE
Desert Saqe Restaurant (Skylight Addition) 1 10/29/2008
WINDOW AREA ADJUSTMENT CALCULATIONS
X❑ CHECK IF NOT APPLICABLE (See
Part 1 of 7)
ORIENTATION
D
E
E
F
G
WINDOW
ADJUST.
OR
(From Peart 1)
ADJUSTED
WINDOW
AREA
(D X E)
ADJUSTED
WALL
B A(F +AC)
A
B
C
D
WALL NAME
(e.g. Wall -1, Wall -2)
GROSS
AREA
DOOR
AREA
WINDOW
AREA
N I E I S JW
❑ ❑ ❑ ❑
❑ ❑ ❑ ❑
❑ ❑ ❑ ❑
❑ ❑ ❑ ❑
❑ ❑ ❑ ❑
❑ ❑ ❑ ❑
❑❑❑❑
❑❑❑❑
❑❑❑❑
❑❑❑❑
❑❑o❑
❑❑❑❑
❑❑❑❑
❑❑❑❑
❑❑❑❑
❑❑❑❑
❑❑❑❑
❑❑❑❑
3,182
TOTALS
3,182
01
N/Al
01
3,182
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:13 of 33
TOTALS
N/A
SKYLIGHT AREA ADJUSTME T CALCULATION
❑ CHECK IF NOT APPLICABLE (See Part 2 of 7)
D
E
F
SKYLIGHT
ADJUST.
FACTOR
(From Part 1)
ADJUSTED
SKYLIGHT
AREA
(C X D)
ADJUSTED
ROOF
AREA
(B - E)
A
B
C
ROOF NAME
(e.g. Roof -1, Roof -2)
GROSS
AREA
SKYLIGHT
AREA
Existing Roof
3,182
00.481
0
3,182
TOTALS
3,182
01
N/Al
01
3,182
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:13 of 33
ENVELOPE MANDATORY MEASURES ENV -MM
PROJECT NAME DATE
Desert Sage Restaurant (Skylight Addition) 10/29/2008
DESCRIPTION
Designer
Enforcement
§118(a) Installed Insulating Material shall have been certified by the manufacturer to
comply with the California Quality Standards for insulating material, Title 20,
Chapter 4, Article 3.
X] § 118(c) All Insulating Materials shall be installed in compliance with the flame spread rating
and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2.
X § 117(a) All Exterior Joints and openings in the building that are observable sources of air
leakage shall be caulked, gasketed, weatherstripped or otherwise sealed.
§ 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit
and the building, and shall be weatherstripped (except for unframed glass doors
and fire doors).
X❑ § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not
exceeding those shown in Table Number 1-E. of the Standards. Manufactured
fenestration products must be labeled for U -value according to NFRC procedures.
X❑ .§118(e) Demising Walls in Nonresidential Buildings:
The opaque portions of framed demising walls in nonresidential buildings shall
have insulation with an installed R -value of no less than R-13 between framing
members.
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 14 of 33
[CERTIFICATE OF COMPLIANCE (Part 1 of 2) MECH-1-C
PROJECT NAME
Desert Sage Restaurant (Skylight Addition)
DATE OF PLANS
DATE
10/29/2008
PROJECT ADDRESS
31551sq.Ft.
78-065 Avenida Lafonda La Quinta
BUILDING TYPE a NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION ❑ NEW CONSTRUCTION ❑ ADDITION a ALTERATION ❑ UNCONDITIONED (File Affidavit)
Building Permit#'
PRINCIPAL DESIGNER - MECHANICAL
Breeze Air Conditioning
TELEPHONE
(760) 346-0855
,
DOCUMENTATION AUTHOR
BREEZE AIR CONDITIONING
TELEPHONEChecked'by/Date.,
(760) 346-0855
jiEnforcementAgency:
GENERAL INFORMATION
DATE OF PLANS
BUILDING CONDITIONED FLOOR AREA
CLIMATE ZONE
15
31551sq.Ft.
BUILDING TYPE a NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION ❑ NEW CONSTRUCTION ❑ ADDITION a ALTERATION ❑ UNCONDITIONED (File Affidavit)
METHOD OF MECHANICAL PRESCRIPTIVE ❑ PERFORMANCE
COMPLIANCE
PROOF OF ENVELOPE COMPLIANCE ❑ PREVIOUS ENVELOPE PERMIT ❑ ENVELOPE COMPLIANCE ATTACHED
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24,
Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building mechanical requirements.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
SIGNATURE
DATE
1
C.J. McFadden
1
I ---,° 1 °6
The Principal Mechanical Designer hereby certifies that the prop( sluitld*g�design represented in this set of construction
documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other
calculations submitted with this permit application. The proposed building has been designed to meet the mechanical
requirements contained in the applicable parts of Sections 100, 101, 102, 110 through115, 120 through 125, 142, 144, and 145.
❑ The plans & specifications meet the requirements of Part 1 (Sections 10-103a).
❑ The installation certificates meet the requirements of Part 1 (10-103a 3).
The operation & maintenance information meets the requirements of Part 1 (10-103c).
Please check one: (These sectionsof the Business and Professions Code are printed in full in the Nonresidential Manual.)
❑ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, or mechanical engineer or I
am a licensed architect.
❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign
this document as the person responsible for its preparation; and that I am a licensed contractor performing this work.
❑ 1 affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a
structure or type of work described pursuant to Business and Professions Code sections 5537, 5538, and 6737.1.
PRINCIPAL MECHANICAL DESIGNER - NAME SIGNATURE DATE LIC. #
0 ,16 A►e354
Breeze Air Conditioning
INSTRUCTIONS TO APPLICANT
M MECH-1-C: Certificate of Compliance. Part 1, 2, 3 of 3 are required on plans for all submittals.
Air/Water/Service/Water Pools Requirements. Part 1 of 3, 2 of 3, 3 of 3 are required for all submittals, but may be on
❑ MECH-2-C: plans.
0 MECH-3-C: Mechanical Ventilation and Reheat is required for all submittals with mechanical ventilation, but may be on plans.
fN MECH-4-C: HVAC Misc. Prescriptive Requirements is required for all prescriptive submittals, but may be on plans.
❑ MECH-5-C: Mechanical Equipment Details are required for all performance submittals.
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 15 of 33
CERTIFICATE OF COMPLIANCE (Part 2 of 2) MECH-1-C
PROJECT NAME DATE
Desert Sage Restaurant S( kylight Addition) 10/29/2008
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
_____.:__ __� __:_.......---;_4:_......#;. ---f 0'.ren iiromcnfc of Rprtinn in-10.1thl and Title 24 Part 6.
uumucates, and U ciatui alio nianncnai we unv�n,mw„,��..... .. ... ... ..��......,..._,.._---
STATEMENT OF COMPLIANCE
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. i
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do require construction inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required If the unit serves 5,000 R2 of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an
attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA fan volume controls installed on new or existing systems must be tested
MECH-8-A:-Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Btu/hr.
-Water-loop Heat Pump Controls
Applies to all new waterfoop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilled, hydronic heat pump
or condenser water systems where the pumps motors are greater than 5 hp.
Equipment requiring acceptance testing
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 16 of 33
MECHANICAL VENTILATION MECH-3-C
PROJECT NAME
Desert Sage Restaurant (Skylight Addition)
DATE
10/29/2008
PRESCRIPTIVE REHEAT
LIMITATION (Section 144(d))
L=
MECHANICAL VENTILATION (Section
121(b)2)
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM —, --+
ZONE/SYSTEM
B
o�a
C
W.0
�
0
D
Cr
'�(D
D
nm3
E
c
3
o
F
n
�v3m
G
is
p
i�
H
m
vim
L°�3
a
I
m
n0n
3D39T
J
No
no,
U)
E
K
-nW
3
o
L
n
2.
ow33
W
3o
�c
O
�
M
o3x
DI—
F3
N
—I
n
D
Existing Restaurant
3,182
0.38
1,209
1,209
191
1,018
Existing A/C
Total
1,209
191
New Dining Area
36
0.50
184
184
22
162
New Fijitsu Mini Split
Total
184
22
C Minimum ventilation rate per Section 121, Table 121-A
E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seating.
H Required Ventilation Air (REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS (column D or G).
I Must be greater than orequal to H, or use Transfer Air column N to make up the difference.
J Design fan supply cfm (Fan CFM) x 30%; or
K 1condition area (ft. sq.) x 04 cfm/ft. sq.; or
L I Maximum of Columns H, J. K, or 300 cfm
M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal
to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M.
EnergyPro 4.4 by EnergySoft User Number 3665 Job Number: Page: 17 of 33
MECHANICAL SIZING AND FAN POWER MECH-4-C
3ROJECT NAME I DATE
Desert Sage Restaurant (Skylight Addition) 10/29/2008
SYSTEM NAME FLOOR AREA
Existing A/C 3,182
FAN POWER CONSUMPTION I
B C D E F
DESIGN EFFICIENCY NUMBER PEAK WATTS
BRAKE HP MOTOR DRIVE OF FANS B x E x 746 / (C X D)
0.750 77.0% 97.0% 2.0 1,498
1. TOTAL FAN SYSTEM POWER INDEX or ADJUSTED FAN POWER INDEX must not exceed 0.8 W/cfm for Constant Volume systems or 1.25 W/cfm for VAV systems.
ITEM or SYSTEM TAG(S)
Total Adjustments
FILTER PRESSURE ADJUSTMENT EQUATION
144-A
A) If filter pressure drop is greater than 1 inch W.C. enter
filter pressure drop. SPa on line 4 and Total Fan pressure
SPf on Line 5.
B) Calculate Fan Adjustment and enter on Line 6.
C) Calculate Adjusted Fan Power Index and enter on Line 7.
1 TOTAL FAN SYSTEM POWER Watts, Sum Column F
1,498
2) SUPPLY DESIGN AIRFLOW (CFM)
4,000
3 TOTAL FAN SYSTEM POWER INDEX Row 1/Row 2)1
4 SPa
144 (h)
5 SPf
6) Fan Adjustment =1-(SPa -1)/SPf
144 (i)
7) ADJUSTED FAN POWER INDEX (Line 3 x Line 6)1
1 0.375
1. TOTAL FAN SYSTEM POWER INDEX or ADJUSTED FAN POWER INDEX must not exceed 0.8 W/cfm for Constant Volume systems or 1.25 W/cfm for VAV systems.
ITEM or SYSTEM TAG(S)
PRESCRIPTIVE MEASURES
Electric Resistance Heating 1
Heat Rejection System 2
Air Cooled Chiller Limitation 3
T-24
Section
Capacity
Exception
Notes
144 (g)
144 (h)
144 (i)
1. Total installed capacity (MBtu/hr) of all electric heat on this project exclusive of electric auxiliary heat for heat pumps. If electric heat is used, explain which exception(s) to Section(g) apply.
2. Are centrifugal fan cooling towers used on this project? (Enter "Yes" or "No") If centrifugal fan cooling tower are used, explain which exception(s) to Section 144(h) apply.
3. Total installed capacity (tons) of all water and air cooled chillers under this permit. If there are more than 100 tons of air-cooled chiller capacity being installed, explain which exception(s) to Section
144(i) apply. -
I
�l EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:18 of 33
f
a
i t
MECHANICALSIZING AND FAN POWER MECH-4-C
PROJECT NAME
DATE
Desert Sage Restaurant (Skylight Addition
10/29/2008
SYSTEM NAME
New Fijitsu Mini Split
FLOOR AREA
369
FAN POWER CONSUMPTION
FAN DESCRIPTION
Supply Fan
Return Fan
B
DESIGN
BRAKE HP
0.500
0.750
C I D
EFFICIENCY
FILTER PRESSURE ADJUSTMENT EQUATION
MOTOR
DRIVE
76.0%
100.0%
77.0%
100.0%
SPf on Line 5.
4 SPa
E
NUMBER
OF FANS
2.0
2.0
PEAK WATTS
B x E x 746 / (C X D)
982
1.453
1. TOTAL FAN SYSTEM POWER INDEX or ADJUSTED FAN POWER INDEX must not exceed 0.8 W/cfm for Conslan! Volume systems or 1.25 W/cfm for VAV systems.
ITEM or SYSTEM TAG(S)
Total Adjustments
FILTER PRESSURE ADJUSTMENT EQUATION
1 TOTAL FAN SYSTEM POWER Watts, Sum Column F
982
144-A
A) If filter pressure drop is greater than 1 inch W.C. enter
filter pressure drop. SPa on line 4 and Total Fan pressure
2) SUPPLY DESIGN AIRFLOW (CFM)
800
3 TOTAL FAN SYSTEM POWER INDEX Row 1/Row 2 1
SPf on Line 5.
4 SPa
B) Calculate Fan Adjustment and enter on Line 6.
5 SPf
6) Fan Adjustment=14SPa -1)/SPf
C) Calculate Adjusted Fan Power Index and enter on Line 7.
7) ADJUSTED FAN POWER INDEX Line 3 x Line 6 1
1 .227
1. TOTAL FAN SYSTEM POWER INDEX or ADJUSTED FAN POWER INDEX must not exceed 0.8 W/cfm for Conslan! Volume systems or 1.25 W/cfm for VAV systems.
ITEM or SYSTEM TAG(S)
PRESCRIPTIVE MEASURES
Electric Resistance Heating '
Heat Rejection System 2
Air Cooled Chiller Limitation 3
T-24
Section
Capacity
Exception
Notes
144 g)
144 (h)
144 i
1. Total installed capacity (MBIu/hr) of all electric heal on this project exclusive of electric auxiliary heat for heal pumps. If electric heat is used, explain which exception(s) to Section(g) apply.
2. Are centrifugal fan cooling lowers used on this project? (Enter "Yes" or "No") If centrifugal fan cooling tower are used, explain which exception(s) to Section 144(h) apply.
3. Total installed capacity (tons) of all water and air cooled chillers under this permit. If there are more than 100 tons of air-cooled chiller capacity being installed, explain which exception(s) to Section
144(i) apply.
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:19 of 33
MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
PROJECT NAME DATE
Desert Sage Restaurant (Skylight Addition) 1 10/29/2008
DESCRIPTION
Designer
Enforcement
Equipment and Systems Efficiencies
a11 Any appliance for which there is a California standard established in the
Appliance Efficiency Regulations will comply with the applicable standard.
❑ §115(a) Fan type central furnaces shall not have a pilot light.
a§123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
FX] §124 Air handling duct systems shall be installed and insulated in compliance with
Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards.
Controls
§122(e) Each space conditioning system shall be installed with one of the following:
r§122(e)1A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the
requirements of Section 112 (d)) shall be installed with an automatic time switch
with an accessible manual override that allows operation of the system during
off -hours for up to 4 hours. The time switch shall be capable of programming
different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's program and time setting for at
least 10 hours if power is interrupted; or
X❑ §122(e)1 B An occupancy sensor to control the operating period of the system; or
FX] §122(e)1C A 4 -hour timer that can be manually operated to control the operating period of
the system.
XJ §122(e)2 Each space conditioning system shall be installed with controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint.
§I22(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with
isolation zones. Each zone: shall not exceed 25,000 square feet; shall be
provided with isolation devices, such as valves or dampers, that allow the supply
of heating or cooling to be setback or shut off independently of other isolation
areas; and shall be controlled by a time control device as described above.
o§122(a&b) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the
control shall be adjustable up to 85 degrees F or higher. Where used for both
heating and cooling, the control shall be capable of providing a deadband of at
least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
X❑ §122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and
adjustable setpoint stops accessible only to authorized personnel.
a§1 12(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:20 of 33
MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM
DATE
PROJECT NAME
Desert Sage Restaurant (Skylight Addition) 10/29/2008
Description Designer Enforcers
Ventilation
§121(e) Controls shall be provided to allow outside air dampers or devices to be operated
at the ventilation rates as specified on these plans.
F] §122(f)
Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air intakes and discharges of all space conditioning and
exhaust systems.
§122(f)
All gravity ventilating systems shall be provided with automatic or readily
for
accessible manually operated dampers in all openings to the outside, except
§l21(f)3
combustion air openings.
§121(f)1
Air Balancing: The system shall be balanced in accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
§121(f)4
Associated Air Balance Council (AABC) National Standards (1989); or
F] §121(f)2
Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the
installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3)
the person with overall responsibility for the design of the ventilation system; or
§l21(f)3
Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
§121(f)4
Another method approved by the Commission.
Service Water Heating Systems
§113(b)2 If a circulating hot water system is installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water is not required.
§113(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit
the outlet temperature to 110 degrees F.
EneravPro 4.4 by EnergySoft User Number: 3665 Job Number Page:21 of 33 1
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME
Desert Sage Restaurant (Skylight Addition
DATE
10/29/2008
SYSTEM NAME
Existin A/C
FLOOR AREA
3,182
ENGINEERING CHECKS
SYSTEM LOAD
COIL COOLING PEAK COIL HTG.
CFM Sensible Latent CFM I
Total Room Loads 5,246 40,5301,973 1,649
Return Vented Lighting 0
Return Air Ducts 2,027
Return Fan 0
Ventilation 19 6,604 249191
Supply Fan 0
Supply Air Ducts 2,027
TOTAL SYSTEM LOAD F 51,188 1,723
PEAK
Number of Systems
2
Sensible
Heating System
Output per System
56,000
24,174
Total Output (Btuh)
112,000
Output (Btuh/sqft)
35.2
1,209
0
Cooling System
Output per System
35,000
8,882
Total Output (Btuh)
70,000
0
1,209
Total Output (Tons)
5.8
35,473
Total Output (Btuh/sgft)
22'0
Total Output (sgft/Ton)
545.5
Air System
HVAC EQUIPMENT SELECTION
CFM per System
2,000
69,952
69,952
Existing Packaged Air Conditioner
41,563
25,846
Airflow (cfm)
4,000
Airflow (cfm/sqft)
1.26
Airflow (cfm/Ton)
685.7
Total Adjusted System Output 41,563 25,846
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 2 pm
Outside Air %
t )
48
Outside Air (cfm/sqft)
0.06
Jan 12 am
Note: values above given at ARI conditions
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0 OF 67.6 OF 84.1 OF 84.1 OF
Supply Air Ducts
Outside Air
�, UF11
191 cfm 83.8 of
Heating Coil Supply Fan
4000 cfm ROOMS
70.0 of
69.7 of
Return Air Ducts
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
111.0 / 77.6 OF
Outside Air
191 cfm
78.5/69.0 of
80.0 / 69.6 OF 70.3166.4 OF 70.3 / 66.4 OF
Supply Air Ducts
Cooling Coil Supply Fan 70.7 / 66.6 OF
4000 cfm 63.7% R.H. ROOMS
78.0 / 68.9 OF
Return Air Ducts
EnergyPro 4.4 by EnergySoft
User Number 3665 Job Number: Page:22 of 33
w
PROJECT NAME DATE
Desert Sa a Restaurant Sk Int Addition 10/29/2008
SYSTEM NAME FLOORAREA
New Fi'itsu Mini Split 369
Total Output (Tons)
5.1
Total Output (Btuh/sqft)
166.4
Total Output (sgft/Ton)
72.1
Air System
CFM per System
400
Airflow (cfm)
800
Airflow (cfm/sgft)
2.17
Airflow (cfm/Ton)
156.4
Outside Air N
2.8
Outside Air (cfm/sgft)
0.06
Note: values above given at ARI conditions
EATING SYSTEM PSYCHROMETRICS
26.0 OF 74.4 of
Outside Air
22 cfm
75.8 of
OOLING SYSTEM PSYCHROM
109.0 / 75.1 of
Outside Air
22 cfm
83.8/63.9 ° F
i
EnergyPro 4.4 by EnergySoft
EM
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible Latent CFM Sensible
36 53 ;
,280 L�
HVAC EQUIPMENT SELECTION
Fijitsu Mini Split System (14 SEER) 53,734 1,012 30,542
Total Adjusted System Output53,734 1,012 30,542
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jun 3 pm Jan 12 am
Heating Coil
►irstream 1
84.5164.3 of
User Number: 3665
s at Time of Heating Peak)
108.9 of
J Supply Air Ducts
108.9 of
Supply Fan
800 cfm ROOMS
70.0 of
k Return Air Ducts ',I
eratures at Time of Cooling Peak)
55.0 / 53.3 of 58.9 / 54.9 OF
j Olr�a
Supply Air Ducts
Supply Fan 58.9 / 54.9 of
800 cfm 40.4% R.H. ROOMS
78.0 / 62.0 of
Return Air Ducts I
Cooling Coil
Job Number:
:23 of 33
ZONE LOAD SUMMARY
PROJECT NAME
Desert Sage Restaurant (Skylight Addition
DATE
10/29/2008
SYSTEM NAME
Existing A/C
FLOOR AREA
3,182
ZONE LOAD SUMMARY
ZONAL SYSTEM
COOLING PEAK
HEATING PEAK
ZONE NAME
SYSTEM NAME
Mult.
CFM
Cooling
Latent
Heating
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Existing Restaurant
1.0
5,246
47,231
4,370
1,649
33,113
Values include ventilation load
COINCIDENT TOTAL 1 47,231 4,370 33,113
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:24 of 33
ZONE LOAD SUMMARY
PROJECT NAME
Desert Sage Restaurant (Skylight Addition
DATE
10/29/2008
SYSTEM NAME
New Fi'itsu Mini Split
FLOOR AREA
369
ZONE LOAD SUMMARY
ZONAL SYSTEM
COOLING PEAK
HEATING
PEAK
ZONE NAME
SYSTEM NAME
Mult.
CFM
Cooling
Latent
Heating
CFM I
SENSIBLE
LATENT
CFM
SENSIBLE
New Dining Area
1.0
1,118
28,107
319
167
7,241
Values include ventilation load
COINCIDENT TOTAL 1 28,107 319 7,241
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page:25 of 33
ROOM LOAD SUMMARY
PROJECT NAME DATE
Desert Sa e Restaurant Skylight Addition 10/29/2008
SYSTEM NAME FLOOR AREA
Existing A/C 3,182
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Existing Restaurant
Existing Restaurant
1
5,246
40,530
1,973
5,246
40,530
1,973
1,649
24,174
PAGE TOTAL 1 5,246 40,530 1,973 17649 24,174
TOTAL 1 5,246 40,530 1,973 1,649 24,174
EnergyPro 4.4 by EnergySoft ' User Number: 3665 Job Number: Page: 26 of 33
ROOM LOAD SUMMARY
PROJECT NAME
Desert Sage Restaurant (.§ i ht Addition
DATE
10/29/2008
SYSTEM NAME
New Fi'itsu Mini Split
FLOOR AREA
369
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG.
PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
New Dining Area
New Conditioned Dining Are
1
1,118
27,377
229
1,118
27,377
229
167
6,204
PAGE TOTAL 1,118 27,377 229 167 6,204
TOTAL 1,118 27,377 229 IF 167 6,204
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 27 of 33
ROOM HEATING PEAK LOADS
Project Title Date
Desert Sa a Restaurant (Skylight Addition) 10/29/2008
Room Information Design Conditions
Room Name Existing Restaurant Time of Peak Jan 12 am
Floor Area 3,182 Outdoor Dry Bulb Temperature 260E
Indoor Dry Bulb Temperature 70°F
Conduction Area U -Value AT of Btu/hr
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 24 1741
Infiltration: [ 1.00 x 1.064 x 3 182 x 10.50 x 0.000 16] X
Schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 24,174
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 28 of 33
3.182.0
x
X
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
0.0490
x
X
x
X
x
x
x
X
X
X
x
x
x
x
x
x
x
x
X
x
x
x
x
X
x
x
x
X
X
x
x
X
x
x
x
X
X
X
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
_
=
=
=
6,860
411.0
0.0740
44
1,338
48.0
1.2500
44
2,640
595.0
0.0740
44
1,937
459.0
0.0740
44
1,495
595.0
0.0740
44
1,937
perimeter = 248.0
0.7300
44
7,966
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 24 1741
Infiltration: [ 1.00 x 1.064 x 3 182 x 10.50 x 0.000 16] X
Schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 24,174
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 28 of 33
t
ROOM HEATING PEAK LOADS
Project Title Date
Desert Sage Restaurant (Skylight Addition) 110/29/2008
Room Information Desi n Conditions
Room Name New Conditioned Time of Peak Jan 12 am
Floor Area Dining "'0 Outdoor Dry Bulb Temperature 260F
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT of Btu/hr
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 6 204
Infiltration: [ 1.00 x 1.064 x 369 x 14.00 x 0.000 16] x
Schedule Air Sensible Area Ceiling Height ACH ILT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 6,204
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 29 of 33
369.0
X
x
x
X
x
X
X
x
x
x
x
x
x
x
x
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
X
x
X
0.3400
x
x
X
x
X
X
x
x
x
x
x
x
x
x
x
x
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
5,520
51.0
0.0740
44
166
54.0
0.0740
44
176
51.0
0.0740
44
166
54.0
0.0740
44
176
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 6 204
Infiltration: [ 1.00 x 1.064 x 369 x 14.00 x 0.000 16] x
Schedule Air Sensible Area Ceiling Height ACH ILT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 6,204
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 29 of 33
, .: 0,,
ROOM COOLING PEAK LOADS
Title
Desert Sage Restaurant
MATION
Room Name
Floor Area
Indoor Dry Bulb Temperature
Conduction
Default Roof 1978 to Present
R-19 Wall
19
t Addition
Existing Restaurant I Time of Peak
3,182 1 Outdoor Dry Bulb Temperature
780F Outdoor Wet Bulb Temperature
Area
3,182.0
411.0
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
U -Value
1.2500
0.0740
Date
10/29/2008
X
X
X
X
X
X
X
X
X
DETD
=
=
=
=
=
=
=
=
=
66.7
32.5
20.3
35.1
38.3
48.2
Page Total
Weighting
Orientation Area SGF SC Factor
(N) 48.0 X 46 X 0.856 X 0.735 =
X X x =
x X X =
x X X
X x X =
X x x
x X x =
X x X
X X X
_ X X x =
Page Total
Jul 2 pm
111 OF
78 OF
Btu/hr
10,399
988
1,217
1,547
1 300
2 123
17 575
Btu/hr
1,389
1 389
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
Lights —1.0-0, X 3,182 X 1.200 Watts/sgft X 3.413 Btuh/Watt x 0.999 = 13,018
Occupants 1.01 x 3,182 X 245 Btuh/occ. 1 25 sqft/occ. X 1.00 = 3,118
Receptacle — 1.00 X 3,182 X 0.500 Watts/sqft x 3.41 Btuh/Watt X 1.00 = 5,430
Process 1.00 X 3,182 X 0.000 Watts/sqft X 3.41 Btuh[Vllatt X 1.00 = 0
Infiltration: [ 1.00 x 1.064 x 3 182 x 10.50 x 0.00 /6 ] x
Schedule Air Sensible Area Ceiling Height ACH QT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 40,530
Schied. Btu/hr
Latent Gain Frac. Area Heat Gain
Occu ants 1.00 x 3,182 x 155 Btuh/OCC. / 250 sqft/occ. = 1 973
Receptacle x,_00 x 3,18 x 0.900 Watts/sqft x 3413 Btuh/Watt =
!Process r 1.00 X 3,182 X 0.000 Watts/sqft x 3.413 BtuhfWatt = �0�
Infiltration: L 1�0 x 4Z71 x g,18 x 1.0.50 x 0_0.0 / 6] x 0_OOQ00 = L --OJ
Schedule Air Latent Area Ceiling Height ACH InW
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 1,9731
EnergyPro 4.4 by EnergySoft User Number 3665 Job Number Page: 30 of 33
ROOM COOLING PEAK LOADS
Title
ROOM INFO
Room Name
Desert Sage Restaurant (Skylight Addition
VIATION DE:
:Ioor Area
ndoor Dry Bulb Temperature
Conduction
New Conditioned Dining Area I Time of Peak
369 (Outdoor Dry Bulb Temperature
780F Outdoor Wet Bulb Temperature
Area
54.0
51.0
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
Orientation Area
(Skv) 369.0
x
x
x
x
U -Value
0.3400
0.0740
Date
10/29/2008
X
X
X
X
X
X
X
X
X
DETD 1
=
=
=
=
=
=
=
=
=
17.8
31.0
33.3
31.6
51.4
0.828
Page Total
SGF
x
x
x
x
x
x
x
x
x
x
Sc
Weighting
Factor
=
=
=
=
=
=
=
=
=
=
234
0.310
0.828
X
x
x
X
Page Total
Jun 3 pm
109
75
Btulhr
2,233
117
133
119
205
2 Sol
Btu/hr
22,194
22 194
Sched. Weighting Btulhr
Internal Gain Frac. Area Heat Gain Factor
r— 1Lights 1.00 x 369 X 1.100 Watts/sgft X 3.413 Btuh/Vllatt X 0.999 = 1,384
Occl— u ants 1 00 x 369 x 245 Btuh/occ. I 25 sgft/occ. X 1.00 = 362
Receptacle 1 00 X 369 x 0.500 Watts/sgft x 3.413 BtuhlWatt x 1.00 = 630
Process 1 00 x 369 x 0.000 Watts/sgft x 3.41 BtuhlWatt x 1.00 = 001
L Infiltration: [ 1.00 x 1.064 x 369 x 14.00 x 0.00 l6] x
Schedule Air Sensible Area Ceiling Height ACH
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 27,377
Sched. Btu/hr
Latent Gain Frac. Area Heat Gain
O cupants 1.00 x 369 X 155 Btuh/occ. / 250 sqft/OCC. = 229
Receptacle �i*OQ x 36 x 0.999 Watts/sgft x Btuh/Watt = 0
(Process 1.00 x 369 x 0.000 Wattslsgft x 3.413 BtuhlWatt = 00I
Infiltration: [ 1_.0.0 x 4,77 x 369 x 1_4.09 x 0 0.0 / 6] x X000.00 = L—OJ
Schedule Air Latent Area Ceiling Height ACH DW
Fra
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 229
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 31 of 33
ROOM COOLING COIL LOADS
Project Title
Desert
ROOM INFORMATION
Room Name
Floor Area
e Restaurant (Skylight Addition
oor Dry Bulb Temperature
Conduction
Default Roof 1978 to Present
R-19 Wall
:7
Existing Restaurant I Time of Peak
31182 I Outdoor Dry Bulb Temperature
78cl' Outdoor Wet Bulb Temperature
Area
3,182.0
411.0
48.0
595.0
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
U -Value
X
0.0490
X
X
0.0740
X
X
1.2500
X
X
0.0740
X
X
0.0740
X
X
0.0740
X
X
X
X
X
X
X
Date
10/29/2008
DETD 1
66.7 =
32.5 =
20.3 =
35.1 =
38.3 =
48.21 =
Page Total
Weighting
Orientation Area SGF SC Factor
(N) 48.0 X 46 X 0.856 X 0.735 =
X x X
X X X
X X X =
X X X =
X X X =
X X X =
X X X =
X X X =
X I X X =
Page Total
Jul 2 pm
111 9F
78 c�
Btu/hr
10,399
988
1,217
1,547
1,300
2,123
17 575
Btu/hr
1,389
1 389
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
Lights 1.00 x 3,182 x 1.200 Watts/sgft x 3.413 Btuh[Watt x 0.999 = 13,018
�Occupants 00{ x 3,182 x 245 Btuh/occ. / 25 sgft/occ. x 1.00 = 3,118
'Receptacle 1.00 x 3,182 x 0.500 Watts/sgft X 3.413 Btuh/Watt x 1.00 = 5,430
Process 1.017 x 3,182 x 0.000 Watts/sgft x 3.41 Btuh/Watt x 1.00 = 0
Infiltration: [ 1.00 x 1.064 x 3 182 x 10.50 x 0.00 /6 0] x 34 = LJ
Schedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 40,530
Sched. Btu/hr
Latent Gain Frac. Area Heat Gain
Occ
upants 1.00 x 3182 x 155 Btuh/OCC. I 250 SgftlocC.
Receptacle �_QQ X 3,18 x 0009 Wattslsgft x 3 BtuhlWatt =
,Process ess 1.00 x 3,182 x 0.000 Watts/sqft x 3.413 Btuh[Watt = 0
Infiltration: [ 1_ Q x 477 x 3 �_g x 10.50 x 0 Q / 60] x Q.Q000_
Schedule Air Latent Area Ceiling Height ACH Z�lw
Fraction -
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM '1,973
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 32 of 33
t . "
ROOM COOLING COIL LOADS
Title
Desert Saae Restaurant (Skylight Addition
)M INFO!
m Name
r Area
or Dry Bulb Temperature
Conduction
19 Wall
DESIGN CON
New Conditioned Dining Area I Time of Peak
NS
369 Outdoor Dry Bulb Temperature
789k Outdoor Wet Bulb Temperature
Area
51
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
U -Value
0.3400
0.0740
Date
10/29/2008
DETD 1
17.8 =
31.0 =
33.3 =
31.6 =
51.4 =
Page Total
Weighting
Orientation Area SGF SC Factor
(�) 369.0 x 234 X 0.310 x 0.828
x x x =
X X X =
X X X
X x X
x X X
X X X =
X X X
X X X =
X X x
Page Total
Jun 3 pm
109 OF
75 OF
Btu/hr
2,233
117
133
119
205
2 807
Btu/hr
22,194
22 194
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
fights 1.00{ X 369 X 1.100 Watts/sqft x 3.413 Btuh/Watt X 0.999 = 1,384
O�pants 1.0 I X.— 369 X 245 Btuhlocc. 1 25( sgft/OCc. X 1.00 = 362
Receptacle 1.00 x 369 x 0.500 Wattslsgft x 3.413 Btuh/Watt x 1.00 = 630
Process 01 x 369 x 0.000 Wattslsgft x 3.413 Btuh/Watt x 1.00 = 0
Infiltration: [ 1.00 x 1.064 x 369 x 14.00 x 0.00 /6 01 x
Schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 27,377
Sched. Btu/hr
Latent Gain Frac. Area Heat Gain
OL ccupa its 1.00 x9 x 155 Btuhlocc. 1 250 sgftlocc. = 229
Receptacle x_00 xF7719- x 0900 Wattslsgft x 3413 Btuh/V11att = 0
iProcess 1.00 x 369 x 0.000 Wattslsgft x 3.413 Btuh/Watt = 0
Infiltration: [ 1.00 X 4,77_1 X 3.6.9 x '_4..000 X 0.00 / 60� x 000000 = I o
Schedule Air Latent Area Ceiling Height ACH Z�lw
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 229
EnergyPro 4.4 by EnergySoft User Number: 3665 Job Number: Page: 33 of 33
*wl.jw * m * * * A * A a & A A A&A^
GLAZING SPECIFICATIONS
15EE: Nex4 pa Je -foc egvCA+,0(N to eoc%vec} 5G -ta 51AGC. ,
6MM
8MM
LU
0
4
C7
10MM
16M M
* U -values calculated by ASTM C-236. ASHRAE standard 15 mph (winter) and 7.5 mph (summer) winds assumed.
* 112' dead air space between each glazing_
Single Glazed
[tt�ttt�ttl•��
Double Glazed
TRANSMISSIONLIGHT • SHADING -COEFFICIENTS
01
CAN + a TO MEET DESIRED SPECIFICATIONS
Light Transmittance
Shading Coefficient
U -Values (Winter)
U -Values (Summer)
Glazing
Color
Single
Double;
Single
Double
Single
Double
Single
Double
Glazed
Glazed
Glazed
Glazed
Glazed
Glazed
Glazed
Grazed
(same color)
same color)
(same color)
.(same color)
Clear
83%
$9%
0.98
0.85
0.61
0.29
0.61
0.29
L1. Bronze
50%
25%
0.70
0.49
0.61
0.29
0.70
0.35
Dk. Bronze
25%
13%
0.61
0.40
0.61
0.29
0.74
0.37
Opal
40%
19%
0.66
0.47
0.61
0.29
0.72
0.32
White
20%
- 10%
0.53
0.32
0.61
0.29
0.71
0.38
Clear
82%
67%
0.96
0.82
0.56
Or27
0.58
0.28
Lt. Bronze
50%
25%
0.70
0.49
0.56
0.27
0.68
0.34
Dk_ Bronze
25%
13%
0.61
0.40
0.56
0.27
0.70
0.35
Opal
40%
19%
0.66
0.47
0.56
0.27
0.70
0.30
White
2001a
10%
0.53
0.32
0.56
0.27
0.67
0.36
Clear
80%
64% 10.89
0.72
0.53
0.25
0.56
0.28
Lt. Bronze
50%
25%
0.70
0.49
0.53
0.25
0.66
0.32
Dk. Bronze
25%
13%
0.61
0.40
0.53
0.25
0.68
0.34
Opal
40%
19%
0.66
0.47
0.53
0.25
0.69
0.29
White
20%
10%
0.53.
0.53
.-�2a
0.64
-6.34,
Clear
74%
55%
0.87
0.69
0.48
0.22
0.51
0.27
Lt. Bronze
50%
25%
0.70
0.49
0.48
0.22
0.52
0.30
Dk. Bronze
25%
13%
0.61
0.40
0.48
0.22
0.61
0.31
Opal
40%
19%
0.66
0.47.
0.48
0.22
0,54
0.28
White
20%
10%
0.53
0.32
0.48
0.22
0.58
0.31
* U -values calculated by ASTM C-236. ASHRAE standard 15 mph (winter) and 7.5 mph (summer) winds assumed.
* 112' dead air space between each glazing_
Single Glazed
[tt�ttt�ttl•��
Double Glazed
TRANSMISSIONLIGHT • SHADING -COEFFICIENTS
01
CAN + a TO MEET DESIRED SPECIFICATIONS
11
any int e ral ,le--tv-t or thewilldbw syster.fl that red'u-cesthe floe
Orsola.v- lira -L sud'i as, layers.; reflective creat-
is'Ir.d.h.terwed-
lay all the scmic fi,,ictors aslheSC lout since lturin.beaplied,.to
p
t.he ei'Alre vvindavv assembly. 7; ilie SFIGC is also affected by
sly adi,ng r ons the rrarne a:,4*- vvoall- as the ratio orglaxing alid,
fr-aime.'F'or arty gJazing Alie SITGC Is
fryou riti,d:tiii..o:ldetif,,nfortii.at4,ioii. source wiLh.SC values, ardy,
ofn:make ersi, . on . to. - S110 C 4 104. theli
&m`:ng1s y I V tae SC vatue by.0,87..Total windovv
S'f,iG,,C Ls ttsed thlrough.oul ffils booR.- and, Is round 1 0 n th'.e INFRC
latiels.
MGC C: = 5 C =-AO - (Y7
C).2-7 = c), 2> �L /',1- O. � 7
t> `A &'C. = 0..,-7