Loading...
BCOM2014-1041 Title 24COPY. - BUILDING ENERGY ANALYSIS REPORT PROJECT: State Farm Insurance 79-440 Corporate Center Drive. La Quinta, CA 92253 Project Designer: Robert Ricciardi Architects 75-400 Gerald -Ford STE 115 Palm Desert, CA 92211 (760) 408-1208 Report Prepared by: Jon Scott Scott Design and Title 24, Inc, 77-085 Michigan Drive Palm Desert, CA 92211 (760) 200-4780 cf Job Number: Date: 12/23/2014 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC — www.energysoft.com. f EnergyPro 6.3 by EnergySoft User Number.' 6712 ID: 1 I TABLE OF CONTENTS Cover Page . Table of Contents Form ENV -MM Envelope Mandatory Measures Form LTI-01-E Indoor Lighting Form LTI-02-E Lighting Controls Form LTI-03-E Indoor Lighting Power Allowance Form MCH -01-E Mechanical Systems Form MCH -02-E HVAC System Requirements Form MCH -03-E Mechanical Ventilation and Reheat EnergyPro 6.3 by EnergySoft Job Number: ID: User Number: 6712 1 2 3 4 10 14 17 20 22 ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV -MM Project Name Date State Farm Insurance 12/23/2014 DESCRIPTION Building Envelope Measures: §110.8(a): Installed insulating material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20 Chapter 4, Article 3. §110.8(c): All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. §110.8(f): The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value of no less than R-13 between framing members. §110.7(a): All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.z of §110.6(a): window area, 0.3 cfm/ft.Z of door area for residential doors, 0.3 cfm/ft.Z of door area for nonresidential single doors (swinging and sliding), and 1.0 cfm/ft.2 for nonresidential double doors (swinging). §110.6(a): Fenestration U -factor shall be rated in accordance with NFRC 100, or the applicable default LI -factor. §110.6(a) Fenestratiori SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the applicable default SHGC. §110.6(b): Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). Ener Pro 6.3 by Energ Soft User Number: 6712 RunCode: 2014-12-23712:37:44 ID: Page 3 of 23 CALIFORNIA ENERGY COMMISSION SER INSTRUCTIONS NRCC-LTI-01-E (Page 1 of 5)' ;gDate Prepared: 12/23/2014 )ned Floor Area: 1,980 this and all Energy Efficiency Standards compliance documents, refer to the Nonresidential Manual published by the California Energy Commission. )RM TITLE t& -LIT -01-E itioned Floor Area : 0 tCC-LIT-02-E Lighting Controls, Certificate of Compliance, and PAF Calculation. All Pages required on plans for all submittals. tCC-LIT-03-E Indoor Lighting Power Allowance tCC-LIT-04-E Tailored Method Worksheets tCC-LIT-05-E Line Voltage Track Lighting Worksheets NRCC-LTI-01-E, page 4 ® Nonresidential ❑ Relocatable Public Schools ❑ ❑ High -Rise Residential Conditioned Spaces ❑ ❑ Hotel/Motel Unconditioned Spaces ❑ New Construction ❑ Addition ❑ Alteration ❑ Complete Building ❑ Area Category ❑ Tailored (select yes for each document included) this and all Energy Efficiency Standards compliance documents, refer to the Nonresidential Manual published by the California Energy Commission. )RM TITLE t& -LIT -01-E Certificate of Compliance. All Pages required on plans for all submittals. tCC-LIT-02-E Lighting Controls, Certificate of Compliance, and PAF Calculation. All Pages required on plans for all submittals. tCC-LIT-03-E Indoor Lighting Power Allowance tCC-LIT-04-E Tailored Method Worksheets tCC-LIT-05-E Line Voltage Track Lighting Worksheets ig Power ;pace Lighting must not be combined for compliance sting Power for Conditioned Spaces Indoor Lighting Power for Unconditioned Spaces Watts Watts Installed Lighting Installed Lighting 1 0 1 NRCC-LTI-01-E, page 4 + ,446 NRCC-LTI-01-E, page 4 + PORTABLE ONLY FOR OFFICES NRCC-LTI-01-E, page 3 Minus Lighting Control Credits 0 Minus Lighting Control Credits 0 NRCC-LTI-02-E, page 2 NRCC-LTI-02-E, page 2 Adjusted Installed Lighting Power _ 1,446 Adjusted Installed Lighting Power � _ 0 (row 1 plus row 2 minus row 3 ) (row 1 minus row 3) . Is - 2013 Nonresidential Compliance June 2014 CALI SER INSTRUCTIONS NRCC-LTI-01-E (Page 2 of 5) ice I Date Prepared: 12/23/201.4 I Complies ONLY if Installed <_ Allowed Complies ONLY if Installed <_ Allowed ed Lighting Power 1 NRCC-LTI-03-E, page 1 1.980 Allowed Lighting Power Unconditioned.NRCC-LTI-03-E, page 1 0 on Certificates — Declare by selecting yes for all Installation Certificates that will be submitted. (Retain copies and verify forms are -E - Must be submitted for all buildings ❑ Field Inspector -E - Must be submitted for a lighting control system, or for an Energy Management Control System (EMCS), sized for compliance. ❑ Field Inspector -E - Must be submitted for a line -voltage track lighting integral current limiter, or for a supplementary protection panel used to energize only line -voltage track lighting, to be recognized for compliance. ❑ Field Inspector -E - Must be submitted for two interlocked systems serving an auditorium, a convention center, a room, a multipurpose room, or a theater to be recognized for compliance. ❑ Field Inspector -E -'Must be submitted for a Power Adjustment Factor (PAF) to be recognized for compliance. ❑ Field Inspector -E - Must be submitted for additional wattage installed 'in a video conferencing studio to be recognized for ❑ Field Inspector ies of Acceptance — Declare by checking all of the Certificates of Acceptance that will be submitted. (Retain copies and verify forms are 2-A - Must be submitted for occupancy sensors and automatic time switch controls. ❑ Field Inspector 3-A - Must be submitted for automatic daylight controls. ❑ Field Inspector 4-A - Must be submitted for demand responsive lighting controls. ❑ Field Inspector Js - 2013 Nonresidential Compliance June 2014 CALIFORNIA ENERGY COMMISSION " SER INSTRUCTIONS NRCC-LTI-01-E (Page 3 of 5) ce Date Prepared: 12/23/2014 ;t Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule. is only for: ❑ UNCONDITIONED SPACE :DULE and FIELD INSPECTION ENERGY CHECKLIST ever listed on this page and on the next page includes all installed permanent and planned portable lighting systems. :hod is used for compliance, list each different type of luminaire on separate lines. or Tailored Method is used for compliance, list each different type of luminaire by each different function area on separate lines ;chedule, and submit the track lighting compliance form (NRCC-LTI-05-E) when line -voltage track lighting is installed. aires in Offices — Exception to Section 140.6(a) ONLY for portable luminaires in offices (As defined in §100.1). All other planned portable luminaires shall be documented on next page of ine if greater than 0.3 watts of portable lighting is planned for any office h different office. Small offices that are typical (having the same general and portable lighting) may be grouped together. This allowance offices having different lighting systems. re Office Installed Portable luminaire Watts Per Square Office Location Field Foot Inspector B C D E F G H I J Installed Z portable L+ Watts If F 5 0.3, Identify Office area in which 3 3 luminaire a iv per enter zero; -n 3 a -(D " watts in this ° — square E x G these portable luminaires are �+ _ ounied .Watts per ° office o foot if F > 0.3, installed Luminaire (B x C) (D / E) (F-0.3) ❑ ❑ ❑ ❑ ❑ ❑ Enter sum total of all pages into NRCC- -table luminaire watts that are greater than 0.3 watts per square foot per office: LTI-01-E; Page 1 Is - 2013 Nonresidential Compliance June 2014 CALIFORNIA ENERGY COMMISSIONj#� SER INSTRUCTIONS NRCC-LTI-01-E (Page 3 of 5) Ce Date Prepared: 1.2/23/2014 ;t Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule is only for: m UNCONDITIONED SPACE :DULE and FIELD INSPECTION ENERGY CHECKLIST rarer listed on this page and on the next page includes all installed permanent and planned portable lighting systems. :hod is used for compliance, list each different type of luminaire on separate lines. or Tailored Method is used for compliance, list each different type of luminaire by each different function area on separate lines schedule, and submit the track lighting compliance form (NRCC-LTI-05-E) when line -voltage track lighting is installed. aires in Offices — Exception to Section 140.6(a) ONLY for portable luminaires in offices (As defined in §100.1). All other planned portable luminaires shall be documented on next page of ine if greater than 0.3 watts of portable lighting is planned for any office h different office. Small offices that are typical (having the same general and portable lighting) may be grouped together. This allowance offices having different lighting systems. re Office Installed Portable Luminaire Watts Per Square Office Location Field Foot Inspector B C D E F G H I J Installed z portable Watts If 1`5 0.3,, Identify Office area in which 3 3 luminaire N a �; per enter zero; E x G these portable luminaires arecu - ,n watts in this ° — squarerD installed _ ounted Watts per ° office :; foot if F > 0.3, Luminaire (B x C) (D / E) (F-0.3) ❑ ❑ ❑ ❑ ❑ ❑ Enter sum total of all pages into NRCC- -table luminaire watts that are greater than 0.3 watts per square foot per office: LTI-01-E; Page 1 Is - 2013 Nonresidential Compliance June 2014 CALIFORNIA ENERGY COMMISSION `4rz' SER INSTRUCTIONS NRCC-LTI-01-E (Page 4 of 5) Ice I Date Prepared: 12/23/2014 I 'Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule is only for: I ] UNCONDITIONED SPACE DULE and FIELD INSPECTION ENERGY CHECKLIST hedule Installed Watts Location Field Inspector 1 B C D E F G H How wattage was determined : o iinaire Description r n �D'+ o ^ ° c 35. z 3 d s uorescent troffer, 3 10Da LU CL Z �; o •w x °' Primary Function area in which ble electronic ballast) m `�00= `� a a these luminaires are installed Pass Fail 8 ElecRO . 27:0 ® ❑ 2 54 Office <= 250 sqft ❑ ❑ '8 ElecRO 48.0 ® ❑ 13 624 Office <= 250 sqft ❑ ❑ '8 ElecRO 48.0 ® ❑ 16 768 Office <= 250 sqft ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ INSTALLED WATTS PAGE TOTAL: 1,446 Enter sum total of all pages into NRCC-LTI-01-E; Page 2 Is - 2013 Nonresidential Compliance June 2014 SER INSTRUCTIONS NRCC-LTI-01-E (Page 5 of 5) ,e I Date Prepared: 12/23/2014 RATION STATEMENT )mpliance documentation is accurate and complete. Documentation Author Signature: gn and Title 24, Inc, signature Date: 12/23/2014 ' Jon d. Scott ;hlgan Drive CEA/ HERS Certification Identification (if applicable): !rt, CA 92211 Phone: (760) 200-4780 )N STATEMENT alty of perjury, under the laws of the State of California: s Certificate of Compliance is true and correct. the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance nance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of drements of Title 24, Part 1 and Part 6 of the California Code of Regulations. .ystem design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance tions, plans and specifications submitted to the enforcement agency for approval with this building permit application. ;ned copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the cable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the Dwner at occupancy. :iardi Responsible Designer Signature: :iardi Architects Date Signed: ald Ford STE 115 License: 1, CA 92211 Phone: (760) 408-1208 is - 2013 Nonresidential Compliance June 2014 HTING CONTROLS CALIFORNIA ENERGY COMMISSION N RCC-LTI-02-E (Page 1 of 3 Date Prepared: 12/23/2014 Ised to document all mandatory and prescriptive lighting controls that are applicable to the project. Declaration Statements (Indicate if the measure applies by checking yes or no below:) ments controlled by self-contained lighting control devices which are certified to the Energy Commission according to the Title 20 Appliance itions in accordance with Section 110.9. controlled by a lighting control a system or energy management control system in accordance with §110.9. An Installation Certificate �d in accordance with Section 130.4(b). ick Lighting Integral Current Limiters shall be installed which have been certified to the Energy Commission in accordance with §110.9 and pally, an Installation Certificate shall be submitted in accordance with Section 130.4(b). Supplementary Overcurrent Protection Panel shall be installed in accordance with Section 110.9 and Section 130.0. Additionally, an fic•ate shall be installed in accordance with Section 130.4(b). ols and equipment shall comply with the applicable requirements in §110.9 and shall be installed in accordance with the manufacturer's :cordance with Section 130.1. all be functionally controlled with manually switched ON and OFF lighting controls in accordance with Section 130.1(a). shall be separately controlled from all other lighting systems in an area. Floor and wall display, window display, case display, ornamental, As lighting shall each be separately controlled on circuits that are 20 amps or less. When track lighting is used, general, display, I special effects lighting shall each be separately controlled; in accordance with Section 130.1(a)4. Jng of any enclosed area 100 square feet or larger, with a connected lighting load that exceeds 0.5 watts per square foot shall meet the ng control requirements in accordance with Section 130.1(b). for lighting shall be equipped with controls that meet the applicable Shut -OFF control requirements in Section 130.1(c). ylit Zones shall be controlled in accordance with the requirements in Section 130.1(d) and daylit zones are shown on the plans. n buildings larger than 10,000 square feet shall be capable of being automatically reduced in response to a Demand Responsive Signal in Section 130.1(e). ancy permit is granted for a newly constructed building or area, or a new lighting system serving a building, area, or site is operated for )or lighting controls serving the building, area, or site shall be certified as meeting the Acceptance Requirements for Code Compliance in Section 130.4.(a). The controls required to meet the Acceptance Requirements include automatic daylight controls, automatic shut -OFF mand responsive controls. - 2013 Nonresidential Compliance June 2014 HTING CONTROLS.� CALIFORNIA ENERGY COMMISSION �"'X NRCC-LTI-02-E 2of3) Date Prepared: 12/23/2014 )e filled out for Conditioned and Unconditioned Spaces. This page is used only for the following: ❑ UNCONDITIONED SPACES PTIVE INDOOR LIGHTING CONTROL SCHEDULE, PAF CALCULATION, and FIELD INSPECTION CHECKLIST PAF Credit Calculation 2 ` T rl f m �+ D C. Standards Complying With 1 O 04 Or s o (l '� n rD CU N a `° :ontrol Schedule (✓ all that apply, or enter if Exempted) opo a -n = ° a ° 6 C D E F G H I I J K L M N O ype/ Description of Lighting mtrol (i.e.: occupancy sensor, # 01 `40M to, a; L40M Q' '4' automatic time switch, of o 0 0 0 0 o a Jimmer, automatic daylight, Units c+ 0- F 2L v °' n N etc... ) ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Control Credit PAGE TOTAL (Sum of Column M): p MULTIPLE PAGES ARE USED, ENTER SUM TOTAL OF Control Credit for all pages HERE (Sum of all Column M): 0 Enter Control Credit total into NRCC-LTI-01-E; Page 1. -Is; §130.0(b) = Multi Level, • §130.1(c) = Auto Shut -Off; §130.1(d) = Mandatory Daylight, §130.1(e) = Demand Responsive; §140.6(d) _ ?d to earn a PAF, • §140.6(d) = Prescriptive Secondary Sidelit Daylight Controls. Factor. PAFs shall not be traded between conditioned and unconditioned spaces. As a condition to earn a PAF, an Installation Certificate is ?d, and submitted. ; - 2013 Nonresidential Compliance June 2014 HTING'CONTROLS CALIFORNIA ENERGY COMMISSION rlk- NRCC-LTI-02-E 2 of 12/23/2014 )e filled out for Conditioned and Unconditioned Spaces. This page is used only for the following: Z UNCONDITIONED SPACES PTIVE INDOOR LIGHTING CONTROL SCHEDULE, PAF CALCULATION, and FIELD INSPECTION CHECKLIST PAF Credit Calculation Z t _T n r n * rl ., ^ n a Standards Complying With 1 ? o ? �. :ontrol Schedule (✓ all that apply, or enter 'E' if Exempted) w a T = o B C D E F G H I J K L M N O ype/ Description of Lighting mtrol (i.e.: occupancy sensor, # Q71 a; '4' °' ;°; p automatic time switch, of o 0 0 0 0 o W v Dimmer, automatic daylight, Units N o, -o a v a a o, a etc...) ❑ ❑ ❑ ❑ ❑ ❑ 1:1 . ❑ Control Credit PAGE TOTAL (Sum of Column M): 0 MULTIPLE PAGES ARE USED, ENTER SUM TOTAL OF Control Credit for all pages HERE (Sum of all Column M): 0 Enter Control Credit total into NRCC-LTI-01-E; Page 1. ,Is §130.0(b) = Multi Level; §130.1(c) = Auto Shut -Off; §130.1(d) = Mandatory Daylight; §130.1(e) = Demand Responsive, §140.6(d) _ ?d to earn a PAF; §140.6(d) = Prescriptive Secondary Sidelit Daylight Controls. Factor. PAFs shall not be traded between conditioned and unconditioned spaces. As a condition to earn a PAF an Installation Certificate is !d, and submitted. c 2013 Nonresidential Compliance June 2014 HTING'CONTROLS Date Prepared: 12/23/2014 N RCC-LTI-02-E (Page 3 of 3) 2ATION STATEMENT ,mpliance documentation is accurate and complete. Documentation Author Signature: ]n -and Title 24, Inc,- signature Date: 12/23/2014 Jon d. Scott CEA/ HERS Certification Identification (if applicable): • .higan Drive !rt, CA 92211 Phone' (760)200-4780 )N STATEMENT alty of perjury, under the laws of the State of California: Certificate of Compliance is true and correct. :he Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance lance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of irements of Title 24, Part 1 and Part 6 of the California Code of Regulations. ystem design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance :ions, plans and specifications submitted to the enforcement agency for approval with this building permit application. ;ned copy of this Certificate of Compliance shall be made available with the building per (s ssued for the building, and made available to the cable inspections. I understand that a completed signed copy of this Certificate of Com ii n is required to be included with the documentation the )wner at occupancy. :iardi Responsible Designer gn re: .iardi Architects Date Signed: O n �c ald Ford STE 115 License: t, CA 92211 Phone: (760) 408- 208 ; - 2013 Nonresidential Compliance June 2014 ER ALLOWANCE CALIFORNIA ENERGY COMMISSION N RCC-LTI-03-E Lighting Power Allowance (Page 1 of 4), Date Prepared: 12/23/2014 for Conditioned and Unconditioned Spaces. This page is only for: ❑ UNCONDITIONED spaces .IGHTING POWER ALLOWANCES thod for compliance, use only the total in column (a) as total allowed building watts. I, Tailored Method, or a combination of Area Category and Tailored Method for compliance, use only the total in column (b) as the total (a) (b) ved Watts. Documented in section B of NRCC-LTI-03-E (below on this page) Watts. Documented in section C-1 of NRCC-LTI-03-E (below on this page) 1,980 Documented in section A of NRCC-LTI-04-E 0 NG WATTS. Enter,number into correct cell on NRCC-LTI-01, Page 2, Row 1 1,980 both conditioned and unconditioned areas. :THOD LIGHTING POWER ALLOWANCE A B 1,980 C 0 D ,F BUILDING (From §140.6 Table 140.6-B) WATTS PER (ft) X COMPLETE BLDG. AREA = ALLOWED WATTS Total Area: Total Watts. Enter Total Watts into section A, row 1 (Above on this page) HOD TOTAL LIGHTING POWER ALLOWANCES (C-2 plus C-3) Watts Total from section C-2 1,980 Total from section C-3 0 Total Watts. Enter Total Watts into section A, row 2 (Above on this page) 1,980 I ; -2013 Nonresidential Compliance June 2014 ER ALLOWANCE CALIFORNIA ENERGY COMMISSION NRCC-LTI-03-E Lighting Power Allowance (Page 2 of 4) Date Prepared: 12/23/2014 It for Conditioned and Unconditioned Spaces. This page is only for: ❑ UNCONDITIONED spaces M GENERAL LIGHTING POWER ALLOWANCE ig for offices. Portable lighting for offices shall be documented only in section B of NRCC-LTI-01-E. n primary function area as defined in §100.1 of the Standards. A. B C D ,TEGORY (From §140.6 Table 140.6-C) WATTS ALLOWED g Primary Function Area per Table 140.6-C PER (ft) X AREA (ft) = WATTS Office <= 250 sqft 1.00 1,980 1,980 TOTALS 1,980 Enter sum total Area Category allowed watts into section C-1 of NRCC-LTI-03-E (this compliance form) 1,980 WATTS 2013 Nonresidential Compliance June 2014 ER ALLOWANCE CALI 0� COMMISSION N RCC-LTI-03-E Lighting Power Allowance (Page 4 of 4) Date Prepared: 1-2/23/2014 2ATION STATEMENT impliance documentation is accurate and complete. Documentation Author Signature: ;ign and Title 24, Inc, Signature Date: 1'2/23/2014 ichigan Drive CEA/ HERS Certification Identification (if applicable): ion a. Scott ;ert, CA 92211 Phone: (760) 200-4780 )N STATEMENT alty of perjury, under the laws of the State of California: ; Certificate of Compliance is true and correct. :he Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance lance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of irements of Title 24, Part 1 and Part 6 of the California Code of Regulations. . ystem design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance :ions, plans and specifications submitted to the enforcement agency for approval with this building permit application. ;ned copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the cable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the )wner at occupancy. :iardi Responsible Designer Signature: :iardi Architects Date Signed: ald Ford STE 115 License: 1, CA 92211 Phone: (760) 408-1208 ; - 2013 Nonresidential Compliance June 2014 Em NRCC-MCH-01-E (Page 1 of 3) Date Prepared: 12/23/2014 IORKSHEETS (check box if worksheet is included) s and all Energy Efficiency Standards compliance forms, refer to the 2013 Nonresidential Manual fire all forms to be incorporated onto the building plans. t Title 'art 1 of 3) Certificate of Compliance, Declaration. Required on plans for all submittals. 'art 2 of 3) Certificate of Compliance, Required Acceptance Tests (MCH -02A to 11A). Required on plans for all submittals. 'art 3 of 3) Certificate of Compliance, Required Acceptance Tests (MCH -12A to 18A). Required on plans where applicable. 'art 1 of 2) Mechanical Dry Equipment Summary is required for all submittals with Central Air Systems. It is optional on plans. 'art 2 of 2) Mechanical Wet Equipment Summary is required for all submittals with chilled water, hot water or condenser water systems. It is optional on plans. MCH -10A Mechanical Ventilation and Reheat is required for all submittals with multiple zone heating and cooling systems. It is optional on plans. MS (check box for required forms) ,ttached to the plans. Listed below are all the acceptance tests for HVAC systems. The designer is required to check the applicable boxes for all ,ment that requires an acceptance test. All equipment of the same type that requires a test list the equipment description and the number of systems. is responsible to either conduct the acceptance test them self or have a qualified entity run the test for them. If more than one person has -h person shall sign and submit the Certificate of Acceptance applicable to the portion of the construction or installation for which they are responsible. considered a completed form and is not to be accepted by the building department unless the correct boxes are checked. ed all newly installed process systems must be tested to ensure proper operations. MCH -03A MCH -04A MCH -05A MCH -06A MCH -07A MCH -08A MCH -09A MCH -10A MCH -11A Single Zone Air Economizer Demand Supply Fan Valve Leakage Supply Water Hydronic Automatic Unitary Distribution Controls Control VAV Test Temp. Reset System Demand Shed Ducts Ventilation Variable Flow Control (DCV) Control ❑ .❑ ❑ ❑. ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ .❑ ❑ ❑ ❑ ❑ B Nonresidential Compliance June 2014 NRCC-MCH-01-E (Page 2 of 3) Date Prepared: 12/23/2014 VIS (check box for required forms) ,ttached to the plans. Listed below are all the acceptance tests for HVAC systems. The designer is required to check the applicable boxes for all -"Ment that requires an acceptance test. All equipment of the same type that requires a test, list the equipment description and the number of systems. is responsible to either conduct the acceptance test them self or have a qualified entity run the test for them. If more than one person has :h person shall sign and submit the Certificate of Acceptance applicable to the portion of the construction or installation for which they are responsible. considered a completed form and is not to be accepted by the building department unless the correct boxes are checked, ed all newly installed process systems must be tested to ensure proper operations. ?A MCH -13A MCH -14A MCH -15A MCH -16A MCH -17A MCH -18A tion & for.DX Automatic Fault Detection & Diagnostics for Air & Zone Distributed Energy Storage DX AC . Systems Thermal Energy Storage (TES) Systems Supply Air Temperature Reset Controls Condenser Water Reset Controls ECMS ❑ ❑ ❑ ❑ ❑ ❑ ❑. ❑ ❑ ❑ ❑ ❑ ❑' ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ .❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 13 Nonresidential Compliance June 2014 CALIFORNIA ENERGY COMMISSION NRCC-MCH-01-E (Page 3 of 3) Date Prepared: 12/23/2014 V STATEMENT ice documentation is accurate and complete. tl 13 Nonresidential Compliance June 2014 Documentation Author Signature: id Title 24, Inc, Signature Date: 12/23/2014 Jon d. Scott In Drive CEA/ HERS Certification Identification (if applicable): A 92211 Phone: (760) 200-4780 .TEMENT perjury, under the laws of the State of California: icate of Compliance is true and correct. ;iness and Professions Code to accept responsibility for the building design or system design identified on Lhis Certificate of Compliance (responsible ;pecifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance 1, Part,1 and Part 6 of the California Code of Regulations. design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, !cifications submitted to the enforcement agency for approval with this building permit application. )py of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement understand that a completed signed copy of this Certificate of Compliance is required to be included with the do mentation the builder provides to the Responsible Designer Signature: Id Title 24, Inc. Date Signed: Jon d. Scott n Drive License: 12-23-14 Phone: (760) 200-4780 a 92211 13 Nonresidential Compliance June 2014 J I H I t UI' UHLWUKIMIH HVAC SYSTEM REQUIREMENTS, GEC-NRCC-MCH-02-E (Revised 06/14) CALIFORNIA ENERGY COMMISSION - CERTIFICATE OF COMPLIANCE NRCC-MCH-02-E HVAC Dry System Requirements (Page 1 of 3) Project Name: State Farm Insurance Date Prepared: 12/23/2014 ., Equipment Tags and System Description' HVAC 1 MANDATORY MEASURES Heating Equipment Efficiency3 Cooling Equipment Efficiency3 HVAC or Heat Pump Thermostats Furnace Standby Loss Control Low leakage AHLls Ventilation Demand Control Ventilations Occupant Sensor Ventilation Control6 Shutoff and Reset Controls' Outdoor Air and Exhaust Damper Control Isolation Zones Automatic Demand Shed Controls Economizer FDD Duct Insulation PRESCRIPTIVE'MEASURES T-24 Sections Reference to the Requirements in the Contract Documenm2 110.1 or 110.2(a) 110.1 or 110.2(a) 110.2(b), 110.2(c) 110.2(d) 110.2(f) 120.1(b) 120.1(c)4 120.1(c)5, 120.2(e)3 120.2(e) 120.2(f) 120.2(g) 120.2(h) 120.2(i) 120.4 Equipment is sized in conformance with 140.4(a & b) Y 140.4(a&b) Supply Fan Pressure Control 140.4(c) Simultaneous Heat/Coo18 140.4(d) Economizer 140.4(e) Heat and Cool Air Supply Reset 140.4(f) Electric Resistance Heating9 140.4(g) Duct Leakage Sealing and Testing.10 140.4(1) Notes: 1. Provide equipment tags (e.g. AHU 1 to 10) and system description (e.g. Single Duct VAV reheat) as appropriate. Multiple units with common requirements can be grouped together. 2. Provide references to plans (i.e. Drawing Sheet Numbers) and/or specifications (including Section name/number and relevant paragraphs) where each requirement is specified. Enter "N/A" if the requirement is not applicable to this system. 3. The referenced plans and specifications must include all of the following information: equipment tag, equipment nominal capacity, Title 24 minimum efficiency requirements, and actual rated equipment efficiencies. Where multiple efficiency requirements are applicable (e.g. full- and part -load) include all. Where appliance standards apply (110.1), identify where equipment is required to be listed per Title 201601 et seq. 4. Identify where the ventilation requirements are documented for each central HVAC system. Include references to both central unit schedules and sequences of operation. If one or more space is naturally ventilated identify where this is documented in the plans and specifications. Multiple zone central air systems must also provide a MCH -03-E form. 5. If one or more space has demand controlled ventilation identify where it is specified including the sensor specifications and the sequence of operation. 6. - If. one or more space has occupant sensor ventilation control identify where it is specified including the sensor specifications and the sequence of operation 7. If the system is DDC identify the sequences for the system start/stop, optimal start, setback (if required) and setup (if required). For all systems identify the specification for the thermostats and time clocks (if applicable). 8. Identify where the heating, cooling and deadband airflows are scheduled for this system. Include a reference to the specification of the zone controls. Provide a MCH -03-E form. 9. Enter N/A if there is no electric heating. If the system has electric heating indicate which exception to 140.4(g) applies. 10. If duct leakage sealing and testing is required, a MCH -04-A form must be submitted. CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA HVAC SYSTEM REQUIREMENTS Ra, ,EC-NRCC-MCH-02•E (Revised 06/13) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-02-E HVAC Wet System Requirements (Page 3 of 3) Project Name: State Farm Insurance Date Prepared: 12/23/2014 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Jon Scott Documentation Author Signature: Company: Scott Design and Title 24, Inc, signature Date: 12/23/2014 Address: 77-085 Michigan Drive CEA/HERS Certification Identification(ifapplicable): Pon d. Scott City/State/zip: Palm Desert, CA 92211 Phone' (760) 200-4780 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials', components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a mpI ted sig copy of this Certificate of Compliance is required to be* included with the documentation the builder provides to t!]P bui •ng own at o upa Responsible Designer Name: Jon Scott Responsible Designer Signature: Company: Scott Design and Title 24, Inc. Date Signed: Jon d. Scott. Address: 77-085 Michigan Drive . License: 12-23-14 Phone: (760) 200-4780 City/State/Zip: Palm Desert, Ca 92211 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 AND REHEAT, CALIFORNIA ENERGY COMMISSION N RCC -MCH -03-E (Page 1 of 2) Date Prepared: 12/23/2014 raining cells are protected and automatic died by the terminal unit when it's operating in the cooling mode. pplied by the terminal unit in the deadband mode. died by the terminal unit when it's operating in the heating mode. DDC controls, or non -DDC controls. Each control category ha•s different reheat limitations in code. tequired Ventilation Airflow (Column M) is greater than the Design Primary Deadband Airflow (Column C). §120.1. Table 120.1-A. applicable or the greater of the expected number of occupants and 50% of the CBC occupant load for egress purposes for spaces without fixed seating. !ntilation Airflow) is the larger of the ventilation rates calculated on an AREA BASIS or OCCUPANCY BASIS (Column I or L) the Design Primary Deadband Airflow complies or not. It compares the value in column M to the value in column C and column F. - for DDC, Design Primary Cooling Airflow * 0.30 for Non -DDC. If the Design Primary Cooling Airflow is less than 300 cfm, then this is not applicable. . I. If the Design Primary Cooling Airflow is 300 cfm or less, then this is not applicable. the Design Primary Reheat Airflow at the zone level, complies or not. It compares the value in column P to the value in column D. for DDC. Not applicable for Non -DDC zones or zones where Design Primary Cooling Airflow is is 300 cfm or less. . Not applicable if the Design Primary Cooling Airflow is 300 cfm or less. the Design Primary Deadband Airflow at the zone level, complies or not. It compares the value in column S to the value in column C. 3 Nonresidential Compliance June 2014 VAV Reheated Primary Air VAV Deadband AREA BASIS OCCUPANCY BASIS MINIMUM CFM Primary Air CFM E F G H I 1 K L M N O P Q R %S T 0 Z Z C 3 3 Z 33 m r� 0 3 x n Z o ? pc n < D z n T 0 Z D T O v '^ T k D n z p O 3 p o D r3 Z z 3 O^ C O p oe ('1 Z p D ru 3 C, O �� �rOr .._. xD� m -< �< �OO< — 30051 O O 0X3 p o n "r) 3 .... Z r M 00 m A Z A m M M O O Z m ,^ w O m m O n Z N n m O A mD y m 0 Z n r0 m D Z D O . A 1,980 jO.15 j297 j19.8 j 15.0 j 297 j 594 jY Total 1594 raining cells are protected and automatic died by the terminal unit when it's operating in the cooling mode. pplied by the terminal unit in the deadband mode. died by the terminal unit when it's operating in the heating mode. DDC controls, or non -DDC controls. Each control category ha•s different reheat limitations in code. tequired Ventilation Airflow (Column M) is greater than the Design Primary Deadband Airflow (Column C). §120.1. Table 120.1-A. applicable or the greater of the expected number of occupants and 50% of the CBC occupant load for egress purposes for spaces without fixed seating. !ntilation Airflow) is the larger of the ventilation rates calculated on an AREA BASIS or OCCUPANCY BASIS (Column I or L) the Design Primary Deadband Airflow complies or not. It compares the value in column M to the value in column C and column F. - for DDC, Design Primary Cooling Airflow * 0.30 for Non -DDC. If the Design Primary Cooling Airflow is less than 300 cfm, then this is not applicable. . I. If the Design Primary Cooling Airflow is 300 cfm or less, then this is not applicable. the Design Primary Reheat Airflow at the zone level, complies or not. It compares the value in column P to the value in column D. for DDC. Not applicable for Non -DDC zones or zones where Design Primary Cooling Airflow is is 300 cfm or less. . Not applicable if the Design Primary Cooling Airflow is 300 cfm or less. the Design Primary Deadband Airflow at the zone level, complies or not. It compares the value in column S to the value in column C. 3 Nonresidential Compliance June 2014 AND REHEAT Prepared: 12/23/2014 NRCC-MCH-03-E (Page 2 of 2) V STATEMENT ice documentation is accurate and complete. Documentation Author Signature: Signature Date: 12/23/2014 ]J�d.Scott and Title 24, Inc, Ian Drive CEA/ HERS Certification Identification (if applicable): CA 92211 Phone: (760) 200-4780 .TEMENT perjury, under the laws of the State of California: icate of Compliance is true and correct. >iness and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible >pecifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance t, Part 1 and Part 6 of the California Code of Regulations. . design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, !cifications submitted to the enforcement agency for approval with this building permit application. )py of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and m e available he enforcement ter inderstand that a completed signed copy of this Certificate of Compliance is required to be included with the d cumen tion the ui provides to the Responsible Designer Signature:. nd Title 24, Inc. Date Signed: license: Jon U. Scott in Drive 12-23-14 ?none: (760) 200-4780 L I, :a 92211 3 Nonresidential Compliance June 2014