08-1833 (AR) Title 24i TITLE 24 REPORT
� Nov o 7 zoos
Title 24 Report for:
THOMAS.& DIANE RICHARDS RESIDENCE
80-645 LA DOCENA TRAIL,
La Quinta, Ca 92253
Project Designer:
Ochoa Design Associates
73-626 Highway 111
Palm Desert, Ca 92260
760.773.6605
Report Prepared By:
SLO
Santiago Lopez-Ocampo
P.O. Box 1018
La Quinta, CA 92247
(760) 485-8927
Job Number:
Ig070808corr
Date:
11/2/2008
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
.07101610BY
ja
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.4 by EnergySoft Job Number: Ig070808corr User Number: 5732
N
TABLE OF CONTENTS
r
Cover Page 1
Table of Contents 2
Form CF -1 R Certificate of Compliance 3
Form MF -1 R Mandatory Measures Summary 12
Form WS -5R Residential Kitchen Lighting 14 .
HVAC System Heating and Cooling Loads Summary 15
n
J
EnergyPro 4.4 by EnergySoft Job Number: Ig070808corr User Number: 5732
Certificate Of Compliance:
Residential
(Part 1* of 4) CF -1 R
THOMAS R DIANE RI
Project Title
CARDS RESIDENCE
)
11/?/gn08
Date
8n-845 I A DOCENA
TRAIL, I a Qubta
Project Address
Building Permit #
,S,qntiano I nPP7-0_ramp.n
(760) 485-8927
DocumenYation Abthor
Telephone
Plan Check/Date
_FnPr vprn
Complin'ce Method
CA
CllmntP 7nne 1
Climate Zone
Field Check/Date
TDV
Standard
Proposed Compliance
(kBtu/sf-yr)
Design
Design
Margin
Space Heating
5.70
3.01
2.70
Space Cooling
109.44
82.10
27.34
Fans
14.70
11.24
3.45
Domestic Hot Water
6.52
6.52
0.00
Pumps
0.00
0.00
0.00
Totals
Building Type:
191:191•
Y Single Family
❑ Multi Family
Building Front Orientation:
Fuel Type:
Fenestration:
102.86
❑ Addition
[J Existing + Add/Alt
(N) 0 deg
Natural Gas
Area: 1,088 ft2 Avg. U: 0.35
Ratio: 20.6% Avg. SHGC: 0.27
BUILDING ZONE INFORMATION
Zone Name Floor Area Volume
HVAC Rystem - 7nne 1 Q9A 2
HVAC System - 7nne 9 1 393 171
HVAC System - 7one 3 1 X585 17 4
HVAC System - Zone 4 1448 15 99
OPAQUE SURFACES Insulation Act.
Type Frame Area U -Fac. Cay. Cont. Azm. Tilt
Roof Wood 46 Q 095 R_38 R_n n 0 i8
Wall Wnnd Q6 n ns4 R-71 R -n n _agp
Wall Wnnd 35 n nsa R-71 R -n n en gn
Wall Wood 95 n 069 R_21 R_n n 1 Rn A
Wall Wnnd QS n nsa R_21 R -n n 97n a
Rnnf Wnnd 879; n n49 R-19 R_n n _dam$
Wall Wood 65 _II102 X130110 -9D
Wall Wnnd 465 0102 X13 _ R -o 0 i0 A
Wall Wnnd 70 X02 R_13 R -n n 135 �0
Wall Wnnd 97 0109 R_13 R -n n 180 gn
Wall Wnnri 90 0102 R-13 _R=0 0 X25 An
Wall Wood 188 n 109 R_13 R_n n 27n _9n
Rnnf Wnnd sq _Qj)25_ R -IR R -nn n is
Wall Wnnd 64 n nsa R_91 R -n n C)n q
Wall Wnnd 18 n n5g R_21 R -n n 979; _g0
Wall Wood 54 n nfg R-71 R_n n 1Rn g0
Wall lAbnd 18 n 069 R_21 R_n n 995 _g0
Roof Wood 1954 n 049 _R-19 _RA 0 n-1
Wall Wood 418 0109 R_13 R_n n Q_0
Wall Wnnd qn5 n 1n9 R_13 R_n n go c)n
Wall Wnnd 147 n1Q2 R_13 R_n n 1Rn Qn
Wall Wnnd M3 _0 109 R_13 R -n n 970 �q0
Rnnf Wnnd ri53 n naa R-1 Q R_n n _0 1
Wall Wood 98 _n 099 —R-21 _R_0 0 135 —gn
Wall Wnnd 900 n 059 R_91 R -n n 1 Rn _9n
33.49
24.6%
Total Conditioned Floor Area
Existing Floor Area:
Raised Floor Area:
Slab on Grade Area:
Average Ceiling Height:
Number of Dwelling Units:
Number of Stories:
# of Thermostat
Units Zone Type Type
017 Conditioned Setback
n g5 Cnnditinnad SPthark
f) 30 Cnnditinned Sethack
n 27 Conditioned Sethack
5,278 ft2
4,315 ft2
0 ft2
5,278 ft2
11.3 ft
1.00
Vent
Hgt. Area
2 n/a
_2 n/a
_2 n/a
Gains Condition
Y / N Status JA IV Reference Location / Comments
1 EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: I070808corr Paae:3 of 18 1
Certificate Of Compliance:
Residential
Existing Floor Area:
(Part 1 of 4) CF -1 R
THOMAS R DIANE
Project Title
RICH SIDENCF
Slab on Grade Area:
5,278 ft2
11/9/gnn8
Date
-8n -H45 1 A DOCENA
TRAIL, La Quinta
1.00
Number of Stories:
1
Project Address
Building Permit #
_Santiann I 0nP7-0campp
(760) 485-8927
Documenlatlon A thor
Telephone
Plan Check/Date
FnPraVPrn
CompliaAce Method
CA
Climatp 7pne I
Climate Zone
Field Check/Date
TDV
Standard
Proposed Compliance
(kBtu/sf-yr)
Design
Design
Margin
Space Heating
5.70
3.01
2.70
Space Cooling
109.44
82.10
27.34
Fans
14.70
11.24
3.45
Domestic Hot Water
6.52
6.52
0.00
Pumps
0.00
0.00
0.00
Totals . -136.36
r than Standard:
Building Type: [k Single Family
❑ Multi Family
Building Front Orientation:
Fuel Type:
Fenestration:
102.86
❑ Addition
Q Existing + Add/Alt
(N) 0 deg
Natural Gas
Area: 1,088 ft2 Avg. U: 0.35
Ratio: 20.6% Avg. SHGC: 0.27
BUILDING ZONE INFORMATION
Zone Name Floor Area Volume
OPAQUE SURFACES Insulation Act.
Type Frame Area LI -Fac. Cay. Cont. Azm. Tilt
Wall Wood 9F n nsq _8:21 R_n n 975 —90
Wall Wond 170 n nsg R_91 R -n n 970 9Q
Rnnf Wnnd 1 n32 0049 R-19 R -n n _n I
Wall Wood 147 n 102 R_13 R_n n 0 9
Wall Wnnd 38 nin? R_13 R-na _g3_gp
Wall Wnnd 51 n 1 n9 R_1I R -n n 77n qp
Rnnf Wood 945 n 025 R-38 _B-0 n n 1 R
Wall Wnnd 771 n Q6g—&:21—RA 0 n q
nnnr Nnna 74 n 5nn NnnP R -n 0 _n gn
Wall Wand An n nFa R_?l R -n n gn A
Wall Wnnd 137 n nsa R-91 R_n n 1 an g0
Wall Wand 125 n,nea R_91 R_n n 270 _9n
Roof Wnnd 1 157 n 095 R_38 R -n n _n Is
Wall Wnnd 181 0102 R_13 R_n n An
Wall Wond 95 _a i n9 R_13 R -n n gn An
Wall Wond 76n n102 R_13 R_n n 770 A
33.49
24.6%
Total Conditioned Floor Area:
5,278 ft2
Existing Floor Area:
4,315 ft2
Raised Floor Area:
0 ft2
Slab on Grade Area:
5,278 ft2
Average Ceiling Height:
11.3 ft
Number of Dwelling Units:
1.00
Number of Stories:
1
# of Thermostat Vent
Units Zone Type Type Hgt. Area
Gains Condition
Y / N Status JA IV Reference Location / Comments
I EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: Ig070808corr Page:4 of 18 1
Certificate Of Compliance: Residential (Part 2 of 4) CF -1 R
THOMAS & DIANE RICHARDS RESIDENCE 11/2/2008
Project Title Date
FENESTRATION SURFACES
True Cond.
# Type Area U -Factor' SHGCZ Azm. Tilt Stat. Glazing Type
Location/
Comments
_t_
2
Windnw
Window
Front
Right
(p)
(1A11
144 C 150 NERC: n9 NFRC n __qo_ New Pn7A Windnwc
5.0 0.350 NFRC 0_29 NFRC 270 90 New Pozzi Windows
Jane 1
Zone 1
-3
Skylight
Front
U
0.5 0.480 NFRC 0.37 NFRC 0 18 New 10" Solatube Curved Prismatic
Zone 1
4
Window
Left
(E)
16.0 0.650 NFRC 0_48 NFRC 90 90 Existing WECK, GLASS BLOCK 8x8x4
Zone 1
5
Window .
Left
(E)
16.0 0.650 NFRC 0.48 NFRC 90 90 Existing WECK. GLASS BLOCK 8x8x4
Zone 1
_Q_
Window
Left
(SE)
20.0 0_350 NFRC 0 29 NFRC 135 90 Altered Pozzi Windows
Zone 1
Z
Existing
0.76
28
0.790 116_A 0.70 116-8 Double Metal Clear
pre -altered for above
8
Window
Rear
(S)
84.3 0.350 NFRC 0_29 NFRC 180 90 Altered Pozzi Windows
Zone 1
,q__
Fxisting
0
26-A1
0.790 116_A 0.70 116-B Double Metal Clear
pre -altered for above
10
11 --Existing
Window
Rear
(,S -W
200 0.350 NFRC J129 NFRC 225 __U Altered Pozzi Windows
0.790 116-A 0.70 116-B Double Metal Clear
Zone 1
pre -altered for above
112 _
Window
Right
(VaV
4.0 0.350 NFRC0 29 NFRC 270 90 New Pozzi Windows
Zone 1
13
Window
Rear
(SM
^ inn 0 350 NFRC _0.29 NFRC925 q0_ New Pozzi Windnws
7nne 2
14
Window
Rear
(S)
48.8 0.350 NFRC0 29 NFRC 180 90 New Pozzi Windows
Zone 2
15
Window
Rear
(SW)
10.0 0.350 NFRC 0_29 NFRC 225 90 New Pozzi Windows
Zone 2
16
Window
Front
(N)
60.0 0.320 NFRC 0.24 NFRC 0 90 Altered Pozzi Doors
Zone 2
17
Existing
10
Bug Screen
0.790 116-A 0_70 116 -R -R Double Metal Clear
pre -altered for above
18
Window
Front
(N)
32.3 0.350 NFRC 0_29 NFRC 0 90 Altered Pozzi Windows
Zone 2
J2
Fxisting
0.76
0.790 116-A 0.70 116.8 Double Metal Clear
ore -altered for above
1. Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 116B.
INTERIOR AND EXTERIOR SHADING
Area Thick. Heat Inside
(so (in.) Cap. Cond. R -Val.
JA IV Reference
Condition
Status
Location/
Comments
Concrete, Heavyweight
46
3.50
28
0_98
Window
26-A1
Overhang
Left Fin Right Fin
#
Exterior Shade Type
SHGC
Hgt.
Wd.
Len.
Hgt.
LEA
RExt. Dist. Len. Hgt. Dist. Len. Hgt.
1
Bug Screen
0.76
28
0_98
2
26-A1
Existing
Zone 1 / Slab on Grade
2
Buq Screen
0.76
28
0_98
0
26-A1
New
Zone 2 / Slab on Grade
3
None
1.00
28
0_98
0
26-A1
Existing
Zone 2 / Slab on Grade
4
Bug Screen
036
5
Bug Screen
0.76
6
Bug Screen
0.76
19
2.5
3 0
0 1
2.0
2.0
8
Bug Screen
0.76
8.0
9.5
3.0
0.1
2.0
2.0
10
Bug Screen
0.76
8.0
2.5
3.0
0.1
2.0
2.0
12
Bug Screen
0.76
13
Bug Screen
0.76
7.5
1.3
12.0
0.1
12.0
12.0
14
Bug Screen
0.76
7.5
6.5
12.0
0.1
12.0
12.0
15
Bug Screen
0.76
7.5
1.3
12.0
0.1
12.0
12.0
16
Bug Screen
0.76
18
0.76
Bug Screen
THERMAL MASS FOR HIGH MASS DESIGN
Type
Area Thick. Heat Inside
(so (in.) Cap. Cond. R -Val.
JA IV Reference
Condition
Status
Location/
Comments
Concrete, Heavyweight
46
3.50
28
0_98
0
26-A1
New
Zone 1 / Slab on Grade
Concrete, Heavyweight
186
3.50
28
0_98
0
26-A1
Existing
Zone 1 / Slab on Grade
Concrete, Heavyweight
690
3.50
28
0_98
2
26-A1
Existing
Zone 1 / Slab on Grade
Concrete, Heavyweight
69
3.50
28
0_98
0
26-A1
New
Zone 2 / Slab on Grade
Concrete, Heavyweight
213
3.50
28
0_98
0
26-A1
Existing
Zone 2 / Slab on Grade
PERIMETER LOSSES Insulation Condition Location/
TVDe Length R -Val. Location JA IV Reference Status Comments
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: Ig070808corr Page:5 of 18 1
Certificate Of Compliance: Residential (Part 2 of 4) CF -1 R
THOMAS &DIANE RICHARDS RESIDENCE 11/2/2008
Project Title Date
FENESTRATION SURFACES
True Cond. Location/
# Type Area U -Factor' SHGCZ Azm. Tilt Stat. Glazing Type Comments
2Il
21
Windnw
Existing
Frnnt
in n a �SnNFgc n �a Fgr �_ _90_ Altered Pn774 Wndnws
0.790 116-A 0470 116-B Double Metal Clear
7nnP
pre -altered for above
22
Window
Left
i 9.5 0.350 NFRC 0.29 NFRC 90 90 Altered Pozzi Windows
Zone 2
23
Existing
Left Fin Right Fin
0.790 116-A 0_70 116-B Double Metal Clear
pre -altered for above
24
Window
Rear
(S) 150.0 0.320 NFRC0 24 NFRC 180 90 AlteredPozzi Doors
Zone 2
28
Existing
Bug Screen
0_790 116-A 0=70 116-B Double Metal Clear
Ore -altered for above
2E
Window
Left
(,SF,) 175 �0 NFRC _0.29 NFRC 135 �Q New Pozzi Windows
Zone 3
27
Window
Rear
(S) 11.0 0.350 NFRC 0_29 NFRC 180 90 New Pozzi Windows
Zone 3
28.
29
_3.0
Window
Window
Window
Rear
Rear
Rear
(S) 48.0 0_320 NFRC J124 NFRC 180 __2Q New Pozzi Doorc
(_S) 15.4 0_350 NFRC 0_29 NFRC 180 qn New eozzi Windows
(S) 54.7 0_350 NFRC _QM NFRC 180 90 New Pozzi Windows
lone 3
7one 3
Zone 3
3
Window
Rear
(S) 11.0 0.350 NFRC 0_29 NFRC 180 90 New Pozzi Windows
Zone 3
22
33
Window
Window
Rear
Rear
(S.) 480 _039 NFRC J124 NFRC 180 _9Q -New Pn770Dnors
_(S) 22.5 0_320 NFRC 0_24 NFRC 180 90 New Pozzi Doors
7one3
Zone 3
34
Window
Rear
(S) 45.0 0.320 NFRC 0_24 NFRC 180 90 New Pozzi Doors
Zone 3
_a5
_Window
Rear
(U 2205 0_320 _NFRC 0_24 NFRC 180 90 New Pozzi Doors
Zone 3
36
Window
Rear
(SW) 17.5 0.350 NFRC 0_29 NFRC: 225 90 New Pozzi Windows
Zone 3
37
Window.
Front
(N) 44.9 0.350 NFRC 0_29 NFRC 0 90 Altered Pozzi Windows
Zone 3
2$
Existing
29
0_790 116_A 0_70 116-B Double Metal Clear
Ore -altered for above
Indicate source either from NFRC or Table 116A. 2. Indicate source either from NFRC or Table 116B.
INTERIOR AND EXTERIOR SHADING
Area Thick. Heat Inside
(so (in.) Cap. Cond. R -Val.
JA IV Reference
Condition
Status
Location/
Comments
Concrete, Heavyweight
1.041
3.50
28
Window
2
Overhang
Left Fin Right Fin
#
Exterior Shade Type
SHGC
Hgt.
Wd.
_
Len.
Hgt. LExt
RExt Dist Len Hgt Dist Len Hgt
20
Bug Screen
0.76
1.032
3.50
28
0_98
0
26-A1
22
Bug Screen
0.76
223
3.50
28
0_98
2
26-A1
24
Bug Screen
f 0.76
10.0
16.0
18.0
0.1 2.0
2.0
26-A1
26Bug
Screen
0.76
27
Bug Screen
0.76
1.8
6.0
14.0
0.1 4.0
4.0
28
Bug Screen
0.76
8.0
6.0
14.0
0.1 4.0
4.0
29
Bug Screen
0.76
1.8
8.4
14.0
0.1 4.0
4.0
30
Bug Screen
0.76
6.5
8.4
14.0
0.1 4.0
4.0
31
Bug Screen
0.76
1.8
6.0
14.0
0.1 4.0
4.0
32
Bug Screen
0.76
8.0
6.0
14.0
0.1 4.0
4.0
33
Bug Screen
0.76
34
Bug Screen
0.76
35
Bug Screen
0.76
36
Buq Screen
0.76
37
Bug Screen
0.76
THERMAL MASS FOR HIGH MASS DESIGN
Type
Area Thick. Heat Inside
(so (in.) Cap. Cond. R -Val.
JA IV Reference
Condition
Status
Location/
Comments
Concrete, Heavyweight
1.041
3.50
28
0_98
2
26-A1
Existing
Zone 2 / Slab on Grade
Concrete, Heavyweight
553
3.50
28
0_98
0
26-A1
New
Zone 3 / Slab on Grade
Concrete, Heavyweight
1.032
3.50
28
0_98
0
26-A1
Existing
Zone 3 / Slab on Grade
Concrete, Heavyweight
223
3.50
28
0_98
2
26-A1
New
Zone 4 / Slab on Grade
Concrete. Heavyweight
72
3.50
28
0_98
0
26-A1
New
Zone 4 / Slab on Grade
PERIMETER LOSSES Insulation Condition Location/
Type Length R -Val. Location JA IV Reference Status Comments
Run Initiation Time: 11/02/08 23.36.34 Run Code: 1225697794
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number Ig070808corr Page 6 of 18
Certificate Of Compliance: Residential (Part 2 of 4) CF -1 R
THOMAS & DIANE RICHARDS RESIDENCE 11/2/2008
Project Title Date
FENESTRATION SURFACES
True Cond.
# Type Area U -Factor' SHGC2 Azm. Tilt Stat. Glazing Type
Location/
Comments
M
40
Wndnw
Window
Front
Left
(N)
(E)
4S Q IS NFRC n 9a NERC n __qQ NPw Pnzzi Windows
24.0 0.320 NFRC 0_24 NFRC 90 90 New Pozzi Doors
7nnp 4
Zone 4
41
Window
Rear
(Sl
11.2 0.350 NFRC 0_29 NFRC 180 90 New Pozzi Windows
_Zone 4
42
Window
Rear
(S)
20.0 0.320 NFRC 0_24 NFRC 180 90 New Pozzi Doors
Zone 4
43
Window
Rear
(S)
40.0 0.320 NFRC 0.24 NFRC 180 90 New Pozzi Doors
Zone 4
A4
Window
Rear
(S)
20.0 0.320 NFRC 0.24 NFRC 180 90 New Pozzi Doors
Zone 4
45.
Window
Right
(Zo
33.0 0.350 NFRC )29 NFRC 270 9Q New Pozzi Windows
Zone 4
46
Skylight
Front
(N)
0.5 0.480 NFRC 0.37 NFRC 0 18 New 10" Solatube Curved Prismatic
Zone 4
4Z
Window
Front
(ILi)
10.5 0.350 NFRC 0.29 NFRC 0 9Q Altered Pozzi Windows
Zone 4
A8i�g
8.0 2.5
8 0 0 1 8.0 8.0
45
0.790 116_A 0.70 116.8 Double Metal Clear
pre -altered for above
AR
Window
Front
(I)
35.0 0.35 NFRC 0.29 NFRC 0 90 Altered Pozzi Windows
Zone 4
50
Existing
Buo Screen
0.76
0.790 116-A 0.70 116-B Double Metal Clear
pre -altered for above
49 Bug Screen 0.76
THERMAL MASS FOR HIGH MASS DESIGN
Area Thick. Heat Inside Condition Location/
Type (sf) (in.) Cap. Cond. R -Val. JA IV Reference Status Comments
Concrete, Heavyweight 673 3.50 28 0_98 2 26-A1 Existing Zone 4 / Slab on Grade
Concrete, Heavyweight 480 3.50 28 0_98 0 26-A1 Existing Zone 4 / Slab on Grade
PERIMETER LOSSES Insulation
Type Length R -Val. Location
Condition
JA IV Reference Status
Location/
Comments
Run Initiation Time: 11/02/08 23:36:34 Run Code: 1225697794
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: Ig070808corr Page:7 of 18
1. Indicate
source either from NFRC or Table
116A.
2. Indicate source either from NFRC or Table 1168.
INTERIOR
AND EXTERIOR SHADING
Window
Overhang Left Fin Right Fin
#
Exterior Shade Type
SHGC
Hgt. Wd.
Len. Hgt. LExt. RExt. Dist. Len. Hgt. Dist. Len. Hgt.
39
Bug Screen
0.76
40
Bug Screen
0.76
41
Bug Screen
0.76
42
Bug Screen
0.76
8 0 2 5
8.0 0.1 8.0 8.0
43
Bug Screen
0.76
8.0 5.0
8.0 0.1 8.0 8.0
44
Bug Screen
0.76
8.0 2.5
8 0 0 1 8.0 8.0
45
Bug Screen
0.76
46
None
1.00
47
Buo Screen
0.76
49 Bug Screen 0.76
THERMAL MASS FOR HIGH MASS DESIGN
Area Thick. Heat Inside Condition Location/
Type (sf) (in.) Cap. Cond. R -Val. JA IV Reference Status Comments
Concrete, Heavyweight 673 3.50 28 0_98 2 26-A1 Existing Zone 4 / Slab on Grade
Concrete, Heavyweight 480 3.50 28 0_98 0 26-A1 Existing Zone 4 / Slab on Grade
PERIMETER LOSSES Insulation
Type Length R -Val. Location
Condition
JA IV Reference Status
Location/
Comments
Run Initiation Time: 11/02/08 23:36:34 Run Code: 1225697794
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: Ig070808corr Page:7 of 18
Certificate Of Compliance : Residential
(Part 3 of 4)
CF -1 R
THOMAS & DIANE RICHARDS RESIDENCE
Water Heater # in Input
11/2/2008
Project Title
Standby R -Value
System Name Type Distribution Syst. (Btu/hr)
(gal)
Date
Loss (%) Ext.
HVAC SYSTEMS
50
Existing 0.57
n/a n/a
Heating
Minimum
Cooling
Minimum Condition
Thermostat
Location
Type
Eff
Type
Eff Status
Type
HVAC System - Zone 1
Central Furnace
78% AFUE
Split Air Conditioner
9.7 SEER Existing
Setback
HVAC System - Zone 2
Central Furnace
78% AFUE
Split Air Conditioner
9.7 SEER Existing
Setback
HVAC System - Zone 3
Central Furnace
80% AFUE
Split Air Conditioner
13.0 SEER Altered
Setback
HVAC DISTRIBUTION
Duct
Duct Condition
Ducts
Location
Heating
Cooling
Location
R -Value Status
Tested?
HVAC System - Zone 1
Ducted
Ducted
Attic
4.2 Existing
No
HVAC System - Zone 2
Ducted
Ducted
Attic
4.2 Existing
No
HVAC System - Zone 3
Ducted
Ducted
Attic
4.2 - Existing
No
Hydronic Piping
Pipe Pipe
Insul.
System Name
Length Diameter
Thick.
WATER HEATING SYSTEMS Rated
Tank
Energy
Tank Insul.
Water Heater # in Input
Cap.
Condition Factor
Standby R -Value
System Name Type Distribution Syst. (Btu/hr)
(gal)
Status or RE
Loss (%) Ext.
Standard Gas 50 gal or Less Small Gas No Pipe Insulation ' 2 40,000
50
Existing 0.57
n/a n/a
Multi -Family Central Water Heating Details
Hot Water Pump Hot Water Piping Length (ft) Add 1/2"
Control # HP Type In Plenum Outside Buried Insulation
REMARKS
This calculation supercedes all previous reports.
5LO.110208
COMPLIANCE STATEMENT
This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of
Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall design responsibility.
The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insulation installation quality,
and building envelope sealing require installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code) Documentation Author
Name: Name: SLO
Title/Firm: Ochoa2resian Associates Title/Firm: Santiago Lopez-Ocampo
Adffress73-6H ighway 111 Address: P.O. Box 1018
P DesertCa 92260 La Quinta. CA 92247
Telephone: 0.773.6609 Lic. #: Telephone: 760 485-8927
ag
(signs re) (date) (signature) (date)
Enforcement Agency
Name:
Title/Firm:
Address:
Telephone:
(signature) (date)
4.4 by EnergySoft User Number: 5732 Job Number: I070808corr Pace:8 of 18
Certificate_ Of Compliance: Residential (Part 3 of 4) CF -1 R
THOMAS & DIANE RICHARDS RESIDENCE
11/2/2008
Project Title
Date
HVAC SYSTEMS
Heating
Minimum
Cooling
Minimum
Condition Thermostat
Location
Type
Eff
Type
Eff
Status Type
pre -altered for above
Central Furnace
78% AFUE
Split Air Conditioner
9.7 SEER
Setback
HVAC System - Zone 4
Central Furnace
80% AFUE
Split Air Conditioner
13.0 SEER
Altered Setback
pre -altered for above
Central Furnace
78% AFUE
Split Air Conditioner
9.7 SEER
Setback
HVAC DISTRIBUTION
' Duct Duct Condition Ducts
Location Heating Cooling Location R -Value Status Tested?
HVAC System -Zone 4 Ducted Ducted Attic 4:2 Altered No
Hydronic Piping I Pipe Pipe Insul.
System Name Length Diameter Thick.
WATER HEATING SYSTEMS
Rated Tank Energy Tank Insul.
Water Heater # in Input Cap. Condition Factor Standby R -Value
System Name Type Distribution Syst. (Btu/hr) (gal) Status or RE Loss (%) Ext.
Multi -Family Central Water Heating Details
Hot Water Pump Hot Water Piping Length (ft) Add 1/2"
Control # HP Type In Plenum Outside Buried Insulation
REMARKS
This calculation supercedes all previous reports.
SLO.110208
COMPLIANCE STATEMENT
This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of
Regulations, and the administrative regulations to implement them.This certificate has been signed by the individual with overall design responsibility.
The undersigned recognizes that compliance using duct design, duct sealing, verification of refrigerant charge and TXVs, insulation installation quality,
and building envelope sealing require installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Name:
Title/Firm: Ochoa Design Associates
Address: 73-626 Highway 111
Palm Desert, Ca 92260
Telephone: 760.773.6605 Lic. #:_
(signature) (date)
Enforcement Agency
Name:
Title/Firm:
Address:
Telephone:
(signature) (date)
Documentation Author
Name: SLO
Title/Firm: Santiago Lopez-Ocampo
Address: P.O. Box 1018
La Quinta. CA 92247
Telephone: 760 485-8927
(signature) (date)
Certificate Of Compliance: Residential (Part 4 of 4) CF -1 R
THOMAS & DIANE RICHARDS RESIDENCE 11/2/2008
Project Title Date
Special Features and Modeling Assumptions
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special
written justification and documentation, and special verification to be used with the performance approach. The local
enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies
based on the adequacy of the special justification and documentation submitted. oI
The Roof "R-38 Roof Attic w/Radiant Barrier" includes credit for a Radiant Barrier installed per Section 3.3.3 of the Residential ManuE I.
The Roof "R-38 Roof w/Radiant Barrier' includes credit for a Radiant Barrier installed per Section 3.3.3 of the Residential Manual.
HIGH MASS Design - Verify Thermal Mass:
46 sqft Exposed Slab Floor, 3.50" thick at Zone 1 - Addition
HIGH MASS Design - Verify Thermal Mass:
186 sqft Exposed Slab Floor, 3.50" thick at Zone 1- Existing
HIGH MASS Design - Verify Thermal Mass:
690 sqft Covered Slab Floor, 3.50" thick at Zone 1- Existing
HIGH MASS Design - Verify Thermal Mass:
69 sqft Exposed Slab Floor, 3.50" thick at Zone 2 - Addition
HIGH MASS Design - Verify Thermal Mass:
213 sqft Exposed Slab Floor, 3.50" thick at Zone 2 - Existing
HIGH MASS Design - Verify Thermal Mass:
1041 sqft Covered Slab Floor, 3.50" thick at Zone 2 - Existing
HIGH MASS Design - Verify Thermal Mass:
553 sqft Exposed Slab Floor, 3.50" thick at Zone 3 - Addition
HIGH MASS Design - Verify Thermal Mass:
1032 sqft Exposed Slab Floor, 3.50" thick at Zone 3 - Existing
HIGH MASS Design - Verify Thermal Mass:
223 sqft Covered Slab Floor, 3.50" thick at Zone 4 - Addition
HIGH MASS Design - Verify Thermal Mass:
72 sqft Exposed Slab Floor, 3.50" thick at Zone 4 - Addition
HIGH MASS Design - Verify Thermal Mass:
673 sqft Covered Slab Floor, 3.50" thick at Zone 4 - Existing
HERS Required Verification
Items in this section require field testing and/or verification by a certified home energy rater under the supervision of a
_.._ r. ... tr rr. .. ...y
Plan I Field
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: Ig070808corr Page:10 of 18 1
Certificate Of Compliance: Residential (Part 4 of 4) CF -1 R
THOMAS& DIANE RICHARDS RESIDENCE 11/2/2008
Project Title Date
Special Features and Modeling Assumptions
The local enforcement agency should pay special attention to,the items specified in this checklist. These items require special
written justification and documentation, and special verification to be used with the performance approach. The local
enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies
rases on the aaequacy or ine special jusuncation ana aocumentation suomittea. Plan Field
HIGH MASS Design - Verify Thermal Mass: 480 sqft Exposed Slab Floor, 3.50" thick at Zone 4 - Existinq
HERS Required Verification
Items in this section require field testing and/or verification by a certified home energy rater under the supervision of a
Plan I Field
I EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: Ig070808corr Paae:11 of 18 1
Mandatory Measures Summary: Residential (Page 1 of 2) MF -1 R
NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent compliance
requirements from the Certificate of Compliance supercede the items marked with an asterisk (') below. When this checklist is incorporated into the permit
documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether
they are shown elsewhere in the documents or on this checklist only.
DESCRIPTION Check or initial applicable boxes or check NA if not applicable and included with the
permit application documentation.
N/A
DESIGNER
ENFORCE -
MENT
Building Envelope Measures
§ 150(e):
Installation of Fireplaces, Decorative Gas Appliances and Gas Logs.
❑
*§ 150(a): Minimum R-19 in wood ceiling insulation or equivalent U -factor in metal frame ceiling.
❑
❑X
❑
§ 150(b): Loose fill insulation manufacturers labeled R -Value:
❑
❑
❑
w§ 150(c): Minimum R-13 wall insulation in wood framed walls or equivalent U -factor in metal frame walls (does not
❑
❑X
❑
apply to exterior mass walls).
b, outside air intake with damper and control, flue damper and control
❑
❑X
�§ 150(d):
Minimum R-13 raised floor insulation in framed floors or equivalent U -factor.
❑
❑
❑
§ 150(e):
Installation of Fireplaces, Decorative Gas Appliances and Gas Logs.
❑
§ 150(i): Setback thermostat on all applicable heating and/or cooling systems.
❑
❑X
1. Masonry and factory -built fireplaces have:
§ 1500): Water system pipe and tank insulation and cooling systems line insulation.
a. closable metal or glass door covering the entire opening of the firebox
❑
❑X
❑
having an installed thermal resistance of R-12 or greater.
b, outside air intake with damper and control, flue damper and control
❑
❑X
❑
❑
2. No continuous burning gas pilot lights allowed.
❑
❑X
❑
§ 150(f):
Air retarding wrap installed to comply with §151 meets requirements specified in the ACM Residential Manual.
❑
❑X
❑
§ 150(g):
Vapor barriers mandatory in Climate Zones 14 and 16 only.
❑
❑
❑
§ 150(1):
Slab edge insulation - water absorption rate for the insulation alone without facings no greater than 0.3%, water vapor
❑
❑
❑
❑
permeance rate no greater than 2.0 permfinch.
❑
indirect hot water tank shall be insulated to Table 150-8 and Equation 150-A.
§ 118: Insulation specified or installed meets insulation installation quality standards. Indicate type and include
❑
❑X
❑
❑
CF -6R Form:
5. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance,
❑
❑
§ 116-17:
Fenestration Products, Exterior Doors, and Infiltration/Exfiltration Controls.
6. Insulation for chilled water piping and refrigerant suction piping includes a vapor retardant or is enclosed
1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage.
❑
❑X
❑
2. Fenestration products (except field fabricated) have label with certified U -Factor, certified Solar Heat Gain
Coefficient infiltration
❑
❑X
❑
❑
(SHGC), and certification.
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: lg07O8O8corr
Page: 12 of 18
3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed.
❑
❑X
❑
Space Conditioning, Water Heating and Plumbing System Measures
§ 110-13: HVAC equipment, water heaters, showerheads and faucets certified by the Energy Commission.
❑
❑X
❑
§ 150(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA or ACOA.
❑
❑X
❑
§ 150(i): Setback thermostat on all applicable heating and/or cooling systems.
❑
❑X
❑
§ 1500): Water system pipe and tank insulation and cooling systems line insulation.
1. Storage gas water heaters rated with an Energy Factor less than 0.58 must be externally wrapped with insulation
❑
❑
❑
having an installed thermal resistance of R-12 or greater.
2. Back-up tanks for solar systems, unfired storage tanks, or other indirect hot water tanks have R-12 external
❑
❑
❑
insulation or R-16 internal insulation and indicated on the exterior of the tank showing the R -value.
3. The following piping is insulated according to Table 150-A/B or Equation 150-A Insulation Thickness:
1. First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire
❑
❑
❑
length of recirculating sections of hot water pipes shall be insulated to Table 150B.
2. Cooling system piping (suction, chilled water, or brine lines), piping insulated between heating source and
❑
❑
❑
indirect hot water tank shall be insulated to Table 150-8 and Equation 150-A.
4. Steam hydronic heating systems or hot,water systems > 15 psi, meet requirements of Table 123-A.
❑
❑
❑
5. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance,
❑
❑
❑
and wind.
6. Insulation for chilled water piping and refrigerant suction piping includes a vapor retardant or is enclosed
❑
❑
❑
entirely in conditioned space.
7. Solar water -heating systems/collectors are certified by the Solar Rating and Certification Corporation.
❑
❑
❑
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: lg07O8O8corr
Page: 12 of 18
r
Mandatory Measures Summary: Residential (Page 2 of 2) MF -1 R
NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. More stringent compliance
requirements from the Certificate of Compliance supercede the items marked with an asterisk (•) below. When this checklist is incorporated into the permit
documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether
they are shown elsewhere in the documents or on this checklist only.
DESCRIPTION Instructions: Check or initial applicable boxes when completed or check N/A if not ENFORCE -
applicable. N/A DESIGNER MENT
Space Conditioning, Water Heating and Plumbing System Measures: (continued)
§ 150(m): Ducts and Fans
1. All ducts and plenums installed, sealed and insulated to meet the requirements of the CMC Sections 601, 602, 603, 604, ❑ Q ❑
605, and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minumum installed level of
R-4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system
that meets the applicable requirements of UL 181, UL 181 A, or UL 181B or aerosol sealant that meets the requirements
of UL 723. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or
tape shall be used.
2. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed ❑
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support
platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions
in the cross-sectional area of the ducts.
07
3. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive
❑
®
❑
duct tapes unless such tape is used in combination with mastic and draw bands.
❑
❑
❑
❑
❑
®
❑
4. Exhaust fan systems have back draft or automatic dampers.
5. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operating
❑
. ®
❑
dampers.
6. Protection of Insulation. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment
❑
®
❑
maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water
retardant and provides shielding from solar radiation that can cause degradation of the material.
7. Flexible ducts cannot have porous inner cores
§ 114: Pool and Spa Heating Systems and Equipment
1. A thermal efficiency that complies with the Appliance Efficiency Regulations, on-off switch mounted outside of the
heater, weatherproof operating instructions, no electric resistance heating and no pilot light.
2. System is installed with:
a. At least 36" of pipe between filter and heater for future solar heating.
b. Cover for outdoor pools or outdoor spas.
3. Pool system has directional inlets and a circulation pump time switch.
§ 115: Gas fired fan -type central furnaces, pool heaters, spa heaters or household cooking appliances have no continuously
burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr)
§ 118 (i): Cool Roof material meets specified criteria
Lighting Measures
§ 150(k)1: HIGH EFFICACY LUMINAIRES OTHER THAN OUTDOOR HID: contain only high efficacy lamps as outlined in Table
150-C, and do not contain a medium screw base socket (E24/E26). Ballasts for lamps 13 Wafts or greater are electric
and have an output frequency no less than 20 kHz.
§ 150(k)1: HIGH EFFICACY LUMINAIRES - OUTDOOR HID: contain only high efficacy lamps as outlined in Table 150-C,
luminaire has factory installed HID ballast.
§ 150(k)2: Permanently installed luminaires in kitchens shall be high efficacy luminaires. Up to 50% of the Wattage, as determined
in Section 130(c), of permanently installed luminaires in kitchens may be in luminaires that are not high efficacy luminaires,
provided that these luminaires are controlled by switches separate from those controlling the high efficacy luminaires.
§ 150(k)3: Permanently installed luminaires in bathrooms, garages, laundry rooms, utility rooms shall be high efficacy luminaires.
OR are controlled by an occupant sensor(s) certfied to comply with Section 119(d).
§ 150(k)4: Permanently installed luminaires located other than in kitchens, bathrooms,garages, laundry rooms, and utility rooms
shall be high efficacy luminaires (except closets less than 70 ft) OR are controlled by a dimmer switch OR are controlled
by an occupant sensor that complies with Section 119(d) that dries not turn on automatically or have an always on option.
§ 150(k)5: Luminaires that are recessed into insulated ceilings are approved for zero clearance insulation cover (IC) and are
certified to ASTM E283 and labeled as air tight (AT) to less than 2.0 CFM at 75 Pascals.
§ 150(k)6: Luminaires providing outdoor lighting and permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy luminaires (not including lighting around swimming poolstwater features or other Article 680
locations) OR are controlled by occupant sensors with integral photo control certified to comply with Section 119(d).
§ 150(k)7: Lighting for parking lots for 8 or more vehicles shall have lighting that complies with Sections 130, 132, and 147.
Lighting for parking garages for 8 or more vehicles shall have lighting that complies with Section 130, 131, and 146.
❑ ❑
❑ ❑
0
0
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
®
❑
0
■
0
❑ ❑ ❑
§ 150(k)8: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more ❑ ❑ ❑
dwelling units shall be high efficacy luminaires OR are controlled by occupant sensor(s) certified to comply with Section 119(d).
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: lg07O8O8corr Page: 13 of 18
Residential Kitchen Liqhtinq Worksheet WS -5R
THOMAS & DIANE RICHARDS RESIDENCE 11/2/2008
Project Title l Date
At least 50% of the total rated wattage of permanently installed luminaires in kitchens must be in luminaires that are high efficacy luminaires
as defined in Table 150-0. Luminaires that are not high efficacy must be switched separately.
a
Kitchen Lighting Schedule. Provide the following information for all luminaires to be installed in kitchens.
High Efficacy
Luminaire Type High Efficacy? Watts Quantity Watts Other Watts
(1) 2 ft U -Tube T8 Elec Yes No 39.0 x 8 = 312 or
(1) 42w Compact Fluorescent Trip/Quad 4pin Yes X No 46.0 x 9 = 414 or
pec Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Yes No x = or
Total A: 726 B: 0
COMPLIES IF A >_ B YES ® NO ❑
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: lg07O8O8corr Page: 14 of 18
FHVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
THOMAS & DIANE RICHARDS RESIDENCE 11/2/2008
SYSTEM NAME FLOOR AREA
HVAC System - Zone 1 922
Number of Systems
1
Heating System
Output per System
0
Total Output (Btuh)
0
Output (Btuh/sqft)
0.0
Cooling System
Output per System
1
Total Output (Btuh)
1
Total Output (Tons)
0.0
Total Output (Btuh/sgft)
0.0
Total Output (sgft/Ton) 11,064,000.0
0
Air System
CFM per System
0
Airflow (cfm)
0
Airflow (cfm/sqft)
0.00
Airflow (cfm/Ton)
• 0.0
Outside Air (%)
0.0
Outside Air (cfm/sqft)
0.00
Note: values above given at ARI conditions
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
CFM
Sensible
680
16,652
1,507
296
12,612
0
3,347
1,807
0
0
0
0
0
0
0
0
0
3,347
1,807
231346 1,507 16 225
Default FAU/AC 1992 - 2005 1 0 0
Total Adjusted System Output 1 0
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug2 m Jan 12 am
EATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time
26.0°F 70.0°F ® 110.0°F
Outside Air
0 cfm
Heating Coil
70.0 °F
k Return Air Ducts 4
;DOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of
11.0/77.6°F 78.0/62.30F . 55.0/53.7°F
Outside Air 0
0 cfm
Cooling Coil
78.0/62.2 ° F
h Return Air Ducts 4
Supply Air Ducts
110.0 °F
ROOMS
70.0 OF
Supply Air Ducts
55.0/53.7°F
41.2% R.H. ROOMS
78.0/62.2°F
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: Ig070808corr Page: 15 of 18 1
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
THOMAS & DIANE RICHARDS RESIDENCE 11/2/2008
SYSTEM NAME FLOOR AREA
HVAC System - Zone 2 1,323
Number of Systems
1
Heating System
Output per System
0
Total Output (Btuh)
0
Output (Btuh/sgft)
0.0
Cooling System
Output per System
1
Total Output (Btuh)
1
Total Output (Tons)
0.0
Total Output (Btuh/sgft)
0.0
Total Output (sgft/Ton) 1
,876,000.0
Air System '
CFM per System
0
Airflow (cfm)
0
Airflow (cfm/sqft)
0.00
Airflow (cfm/Ton)
0.0
Outside Air (%)
0.0
Outside Air (cfm/sqft)
0.00
Note: values above given at ARI conditions
EATING SYSTEM PSYCHROMETRICS
26.0 OF 70.0 OF
Outside Air
0 cfm
70.0 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensiblel
Latent
I CFM
I Sensible
775
18,980
1,815
380
16,171
0
3,815
2,316
0
0
0
0
Oil
0
0
0
0
3,815
2,316
26,6091 1,8151
20 803
HVAC EQUIPMENT SELECTION
Default FAU/AC 1992 - 2005 1 0 0
Total Adjusted System Output
1 0
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug2 m Jan 12 am
110.0 OF
Heating Coil
1% Return Air Ducts `S
Supply Air Ducts
110.0 OF
ROOMS
70.0 of
ICOOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Coolina Peak) I
111.0/ 77.60F
Outside Air
0 cfm
78.0/62.2 0 F
78.0/62.30F . 55.0/53.70F
Cooling Coil
h Return Air Ducts "I
Supply Air Ducts
55.0/53.7 OF
41.2% R.H. ROOMS
78.0/62.2OF
I EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: lg07O8O8corr Page:16 of 18 1
111VAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME ° DATE
THOMAS & DIANE RICHARDS RESIDENCE 11/2/2008
SYSTEM NAME FLOOR AREA
HVAC System - Zone 3 1,585
Number of Systems
1
Heating System
Output per System
80,000
Total Output (Btuh)
80,000
Output (Btuh/sqft)
50.5
Cooling System
Output per System
57,000
Total Output (Btuh)
57,000
Total Output (Tons)
4.8
Total Output (Btuh/sqft)
36.0
Total Output (sgft/Ton)
333.7
Air System
CFM per System
1,800
Airflow (cfm)
1,800
Airflow (cfm/sqft)
1.14
Airflow (cfm/Ton)
378.9
Outside Air (%)
0.0
Outside Air (cfm/sqft)
0.00
Note: values above given at ARI conditions
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
I CFM
I Sensible
968
19,738
2,016
388
16,242
0
80.1 /64.2OF 80.1 /64.2OF
56.8/55.5OF
3,967
2,327
0
0
0
0
0
0
0
(
0
0
3,967
2,327
27,6713 2 016
HVAC EQUIPMENT SELECTION
YorkCZB60.PS8CN100.2000cfm 44,631 5,610
Total Adjusted System Output 631 5,610
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug2 pm
EATING SYSTEM PSYCHROMETRICS (Airstream Temneratures at Time of Heatina Peakl
26.0 OF
Outside Air
0 cfm
68.8 OF
68.8 OF 68.8 OF
110.5 OF
Supply Fan Heating Coil
1800 cfm
�% Return Air Ducts 4
80,000
80,000
Jan 12 am
Supply Air Ducts
109.3 of
ROOMS
70.0 OF
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures
at Time of Cooling
Peak
111.0/77.6OF
80.1 /64.2OF 80.1 /64.2OF
56.8/55.5OF
Supply Air Ducts
Ji,Q
Outside Air
0 cfm
Supply Fan Cooling
Coil
58.8 / 56.3 OF
1800 cfm
ROOMS
45.1° R. H.
0
78.0/63.5 OF
80.1 / 64.2 F
Return Air Ducts
I
EnergyPro 4.4 by EnergySoft User Number: 5732 job Number: lg07O8O8corr Page:17 of 18
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY I
PROJECT NAME DATE
THOMAS & DIANE RICHARDS RESIDENCE 11/2/2008
SYSTEM NAMEFLOOR AREA
HVAC Svstem - Zone 4 1 AAR
EATING S
26.0 OF
�0
Outside Air
0 cfm
1 68.9 OF
M PSYCHROMETRICS
68.9°F 68.9°F
Q:
Supply Fan
1600 cfm
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
CFM
I Sensible
211600 2,111
YorkCZB48.PS8CN1 00.1 600cfm 39,816 2,715 80,000
Total Adjusted System Output39,816 2,715 80,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug2 m Jan 12 am
115.8°F
Heating Coil
res at Time of
�% Return Air Ducts 4
Supply Air Ducts
114.7 OF
ROOMS
70.0 OF
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
111.0/77.6°F 79.7/63.8°F 79.7/63.9°F 56.3/55.0°F
0 Supply Air Ducts
Outside Air
0 cfm Supply Fan Cooling Coil 57.9 / 55.6 OF
1600 cfm 44.6% R.H. ROOMS
79.7 / 63.8 F
° 78.0 / 63.3 ° F
h Return Air Ducts `i
EnergyPro 4.4 by EnergySoft User Number: 5732 Job Number: Ig070808corr Page:18 of 18 1