08-1763 (SIGN) Title 24TITLE 24 REPORT
Title 24 Report for:
Corporate Centre Professional Plaza -Bldg 2
79-245 Corporate Centre Drive
La Quinta, Ca 92253
Project Designer:
Robert Pitchford, Architect
74-835 Fox Hills
Palm Desert, Ca 92260
(760) 346-8776
Report Prepared By:
Tim Scott
Scott Design & Title 24
77085 Michigan Dr.
Palm Desert, CA 92211
(760) 200-4780
Job Number:
Date:
1/11/2007
ti TV
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.2 by EnergySoft Job Number: User Number: 6712 1
L TABLE OF CONTENTS I
Cover Page
Table of Contents
Nonresidential Performance Title 24 Forms
Form ENV -MM Envelope Mandatory Measures
Form LTG -7-C Room Cavity Ratio Worksheet
Form OLTG-1-C Certificate of Compliance
Form OLTG-2-C Lighting Compliance Summary
Form OLTG-3-C Illuminated Area Calculation Worksheet
Form LTG -MM Lighting Mandatory Measures
Form MECH-MM Mechanical Mandatory Measures
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
Room Cooling Coil Loads
1
2
3
17
18
19
21
23
25
26
28
34
40
46
52
EnergyPro 4.2 by EnergySoft Job Number: User Number: 6712 1
,PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1
PROJECT NAME
1, Parts 1 and 6 of the
DATE
Corporate Centre Professional Plaza -Bldg 2
m documents is
ations submitted with this
i sections 110, 116,
professions Code to
the State of
ions Code Section
that I am a licensed
this document
is and Professions
Code are printed in
1/11/2007
PROJECT ADDRESS
HOTELIMOTEL GUEST ROOM
PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ADDITION
79-245 Corporate Centre Drive La Quinta
PRINCIPAL DESIGNER - ENVELOPE
TELEPHONE
Building Permit #
Robert Pitchford, Architect
(760) 346-8776
- -
DOCUMENTATION AUTHOR
TELEPHONE
Checked by/Date
Scott Design & Title 24
(760) 200-4780
Enforcement Agency Use
GENERAL INFORMATION
1, Parts 1 and 6 of the
DATE OF PLANS
BUILDING CONDITIONED FLOOR AREA
5,614 Sq.Ft.
m documents is
ations submitted with this
i sections 110, 116,
professions Code to
the State of
ions Code Section
that I am a licensed
this document
is and Professions
Code are printed in
CLIMATE ZONE
15
BUILDING TYPE ® NONRESIDENTIAL Ej HIGH RISE RESIDENTIAL E]
HOTELIMOTEL GUEST ROOM
PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ADDITION
EXISTING + ADDITION/ALTERATION
Page:3 of 57
1, Parts 1 and 6 of the
DAT
( (I( D
m documents is
ations submitted with this
i sections 110, 116,
professions Code to
the State of
ions Code Section
that I am a licensed
this document
is and Professions
Code are printed in
DATE
DATE
1-3 MECH-5
DE
171 ( O
Page:3 of 57
[PERFORMANCE CERTIFICATE OF, COMPLIANCE , -Part 2 of 3 PE
PROJECT NAM E
I E Corporate Centre Professional Plaza-Bldq 2 1/11/2007�1
ANNUAL TDV ENERGY USE SUMMARY (kBtu/sqft- yr)
Standard Proposed Cornpliance
ENERGY COMPONENT
Design
Space Heating
Space Cooling
Indoor Fans
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Lighting
Receptacle
Process
1.48
563.41
129.59
0.00
0.00
73.93
216.28
168.27
0.00
TOTALS: 1,152.96
Percent better than Standard:
Design ,
(N) 0 deg
Margin
2.13
-0.65
590.57
-27.16
143.80
-14.21
0.00
0.00
0.00
0.00
74.70
-0.77
121.61
.94.67
168.27
0.00
0.00
0.00
1 101.08 51 88
4.5% 4.5% excluding process)
von
Building Orientation
Number of Stories
Number.of Systems
Number of Zones
(N) 0 deg
Conditioned Floor Area
Unconditioned Floor Area
Conditioned'Footprint Area
Fuel Type
5,614
sqft.
sqft.
sqft.
1
0
6
5,614
s
Natural Gas,
78
16.1%
Orientation
Front Elevation (N
Left Elevation
Rear Elevation (S)
Right Elevation (W)
Total
Roof
Gross Area
sqft.
sqft.
sqft.
sqft.
sqft.
sqft.
Glazing Area
Glazing
sqft.
sqft.
sqft.
sqft.
sqft.
sqft.
Ratio
1,265
549
43.4%
485
78
16.1%
1,265
0
0.0%
485
781
16.1%
3,500
7051
5,614
E:0.0%
Standard - Proposed
Lighting Power Density 1.500 W/sqft. 0.641,W/sqft.'
Prescriptive Env. Heat Loss 903 Btu/h. 1,022 MUM
Prescriptive Env. Heat Gain 92,561 Btu/'h-F 100,482 Btu/h-F
I Remarks:
Run Initiation Time: 01/11/07,10:55:10 Run Code: 116854,1710.
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: PageA of 57
]PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1
PROJECT NAME
Corporate Centre Professional Plaza -Bldg 2
DATE
1/11/2007
ZONE INFORMATION
System Name Zone Name
Occupancy Type
Floor
Area
(sgft.)
Inst.
LPD
(W/sf)1
Ctrl.Allowed LPD
Credits Area Tailored
(W/sf)2 W/s 3 (W/S4
Proc.
Loads
(W/sf)
HVAC -1 Zone 1
Comp Bldg Retail and Wholesale
655
0.75
HVAC -2 Zone 2
Comp Bldg Retail and Wholesale
1,006
0.74
HVAC -3 Zone 3
Comp Bldg Retail and Wholesale
1,006
0.37
HVAC -4 Zone 4
Comp Bldg Retail and Wholesale
1,006
0.74
HVAC -5 Zone 5
Comp Bldg Retail and Wholesale
1,006
0.74
HVAC -6 Zone 6
Comp Bldg Retail and Wholesale
935
0.53
Notes: 1. See LTG -2-C
(items marked with asterisk, see LTG -2 -C by others)
2. See LTG -4-C 3. See LTG -5-C
(by others)
4. See LTG -6-C
Items above require special documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
The HVAC System "Carrier 50JX0425" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement.
The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Sionature or Stam
1 EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Pane:5 of 57 1
]CERTIFICATE OF COMPLIANCE ENV -1-C
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
OPAQUE SURFACES
# Surface
Type
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Am.
Tilt
Cond.
Status
Joint Appendix
IV Reference
Location / Comments
1 Roof
655
0.036
R-30
R-0.0
0
0
New
02-A9
Zone 1
2 Wall
96
0.074
R-19
R-0.0
0
90
New
09-A5
Zone 1
3 Wall
135
0.074
R-19
R-0.0
180
90
New
09-A5
Zone 1
4 Wall
407
0.074
R-19
R-0.0
270
90
New
09-A5
Zone 1
5 IlRoof
1,006
0.036
R-30
R-0.0
0
0
New
02-A9
Zone 2
6 lWall
72
0.074
R-19
R-0.0
0
90
New
09-A5
Zone 2
7 lWall
. 210
0.074
R-19
R-0.0
180
90
New
09-A5
Zone 2
8 Roof
1,006
0.036
R-30
R40
0
0
New
02-A9
Zone 3
9 lWall
1 132
0.074
R-19
R-0.0
0
90
New
09-A5
Zone 3
10 lWall 1
210
0.074
R-19
R-0.0
180
90
New
09-A5
Zone 3
11 IRoof 1
1,006
0.036
R-30
R-0.0
0
0
New
02-A9
Zone 4
12 lWall 1
132
0.074
R-19
R-0.0
0 1
90
New
09-A5
Zone 4
13 lWall 1
210
0.074
R-19
R-0.0
180
90
New
09-A5
Zone 4
14 IlRoof 1
1,006
0.036
R-30
R-0.0
0
0
New
02-A9
Zone 5
15 lWall
1 132
0.074
R-19
R-0.0
0
90
New
09-A5
Zone 5
16 Wall
210
0.074
R-19
R-0.0
180
90
New
09-A5
Zone 5
Roof
935
0.036
R-30
R-0.0
0
0
New
02-A9
lZone 6
_17
18 Wall
152
0.074
R-19
R-0.0
0
90
New
09-A5
Zone 6
19 Wall
407
0.074
R-19
R-0.0
90
90
New
09-A5
Izone 6
20 Wall
290
0.074
R-19
R-0.0
180 1
90
1 New
09-A5
I Zone 6
N, E, A, R (New, Existing, Altered, Removed)
FENESTRATION SURFACES
❑More than or equal to 10,000 sq.ft, of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default 1.1 -factors from
Standards Table 116-A and B. Certificate shall be filed in the contractor's project office during construction and in the building manager's office after construction
#
IType
Area U -Fac'
SHGC2
Act.
Azm.
Cond.
Stat.
Glazing Type
Location/
Comments
1
lWindow
Front
N
39 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 1
2
Window
Right
W)
39 0.8701 NFRC
0.59 NFRC
270
New
Double Metal Tinted Default
Zone 1
3
Window
Right
W
39 0.870 NFRC
0.59 NFRC
270
New
Double Metal Tinted Default
Zone 1
4
Window
Front
N
39 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 2
5
Window
Front
N
42 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 2
6
Window
Front
N
18 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 2
7
Window
Front
N
39 0.870 NFRC1
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 2
8
Window
Front
N
39 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 3
9
Window
Front
N
39 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 3
10 Window
Front
N
39 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 4
11 Window
Front
N
39 0.870 NFRC
0.59 INFRCI
0
New
I Double Metal Tinted Default
Zone 4
12 Window
Front
N
39 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 5
13 Window
Front
N
39 0.870 NFRC
0.59 INFRC 1
0
New
I Double Metal Tinted Default
JZone 5
((1 U4actor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
(2; SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
#
Exterior Shade Type
SHGC
Window
Hgt. Wd.
Overhang Left Fin Right Fin
Len. Hc1t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
1
None
0.76
6.0 6.5
8.0
0.1
8.0
8.0
2
None
0.76
6.0 6.5
8.0
0.1
8.0
8.0
3
None
0.76
6.0 6.5
8.0
0.1
8.0
8.0
4
None
0.76
6.0 6.5
8.0
0.1
8.0
8.0
5
None
0.76
7.0 6.0
8.0
0.1
8.0
8.0
6
None
0.76
3.0 6.0
8.0
0.1
8.0
8.0
7
None
0.76
6.0 6.5
8.0
0.1
8.0
8.0
8
None
0.76
6.0 6.5
8.0
0.1
8.0
8.0
9
None
0.76
6.0 6.5
8.0
0.1
8.0
8.0
10
None
1 0.76
6.0 6.5
1 8.0
0.1
8.0
8.0
11
None
0.76
6.0 6.5
1 8.0
0.1
8.0
8.0
12
None
0.76
6.0 6.5
1 8.0
0.1
8.0
8.0
13
1 None
0.76 1
6.0 6.5
1 8.0
0.1
8.0
8.0
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
The proposed building contains an enclosed space with floor area greater than 25,000 sq.ft, a ceiling height greater than 15 feet and a LPD for general lighting of at least 0.5 W/sq.ft. If this
box Is checked, ENV41-C must be filled out when submitting under the Prescriptive Compliance Approach.
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:6 of 57 1
]CERTIFICATE OF COMPLIANCE ENV -1-C
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
OPAQUE SURFACES
# Surface Insulation Act. Cond. Joint Appendix
Type Area U -Fac. Cay. Cont. Am. Tilt Status IV Reference Location / Comments
N, E, A, R (New, Existing, Altered, Removed)
FENESTRATION SURFACES
FMore than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U -factors from
Standards Table 116-A and B. Certificate shall be filed in the contractor's project office during construction and in the building managers office after construction
# TvDe
Area U -Fac'
SHGC2
Act.
Am.
Cond.
Stat.
Glazing Type
Location/
Comments
14 Window
Front
N
39 0.8701 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 6
15 Window
Front
(N)
42 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 6
16 Window
Front
(N)
18 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 6
17 Window
Front
N
39 0.870 NFRC
0.59 NFRC
0
New
Double Metal Tinted Default
Zone 6
18 Window
Left
E
39 0.870 NFRC
0.59 NFRC
90
New
Double Metal Tinted Default
Zone 6
19 Window
Left
E)
39 0.870 NFRC
0.59 NFRC
90
New
Double Metal Tinted Default
Zone 6
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
( 1 Ll -facto, 2) SHGC Typee 116-6 Defau tDefault
Table from Standaards, COG Cene of Gla sa NFRC Labe ed Va ue ble from the ACM Manual Appendix, NFRC Labeled value.
EXTERIOR SHADING
# Exterior Shade Type
SHGC
Window
Hgt. Wd.
Overhang Left Fin Right Fin
Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
14 None
0.76
6.0 6.5
8.0 0.1 8.0
8.0
15 None
0.76
7.0 6.0
8.0 0.1 8.0
8.0
16 None
0.76
3.0 6.0
8.0 0.1 8.0
8.0
17 None
0.76
6.0 6.5
8.0 0.1 8.0
8.0
18 None
0.76
6.0 6.5
8.0 0.1 8.0
8.0
19 None
0.76
6.0 6.5
8.0 0.1 8.0
8.0
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
The proposed building contains an enclosed space with Floor area greater than 25,000sq.ft, a ceiling height greater than 15 feet and a LPD for general lighting of at least 0.5 W/sq.ft. If this
box Is checked, ENV4-C must be filled out when submitting under the Prescriptive Compliance Approach.
{ EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:7 of 57 1
CERTIFICATE OF COMPLIANCE (Part 1 of 3) LTG -1 -C
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -5-C) ALLOWED
❑ AREA CATEGORY METHOD (From LTG -5-C) WATTS
❑ TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER 3,596
ALTERNATE COMPLIANCE
❑X PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C) 0
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION
CONTROL
IDENTIFICATION
CONTROLTYPE
(Auto Time Switch, Dimming, etc.)
SPACE CONTROLLED
Check if
NOTE TO
FIELD
NOTES TO FIELD - For Building Department Use Only
Run Initiation Time: 01/11/07 10:55:10 Run Code: 1168541710
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:8 of 57
INSTALLED
WATTS
INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C)
3,596
PORTABLE LIGHTING (From LTG -3-C)
0
LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG4-C)
0
CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER
1 3,596
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -5-C) ALLOWED
❑ AREA CATEGORY METHOD (From LTG -5-C) WATTS
❑ TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER 3,596
ALTERNATE COMPLIANCE
❑X PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C) 0
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION
CONTROL
IDENTIFICATION
CONTROLTYPE
(Auto Time Switch, Dimming, etc.)
SPACE CONTROLLED
Check if
NOTE TO
FIELD
NOTES TO FIELD - For Building Department Use Only
Run Initiation Time: 01/11/07 10:55:10 Run Code: 1168541710
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:8 of 57
CERTIFICATE OF COMPLIANCE
(Part 3 of 3) LTG-1-C
PROJECT NAME
Corporate Centre Professional Plaza-Bldg 2
DATE
1/11/2007
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance
tests for lighting systems. The designer is required to check the boxes by all acceptance tests that
apply and list all equipment that require an acceptance test. If all equipment of a certain type requires
a test, list the equipment description and the number of systems to be tested in parentheses. The NJ
number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the
test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design
professional or an agent selected by the owner). Since this form will be part of the plans, completion
of this section will allow the responsible party to budget for the scope of work appropriately.
Building Departments:
Before an occupancy permit is granted for a newly constructed building or space, or a new lighting
system system serving a building or space is operated for normal use, all control devices serving the
building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building department
that:
A. Certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of§ 10-103(b) and Title 24 Part 6.
Test Description
Test Performed BY:
❑ LTG-2-A: Lighting Control Acceptance Document
- Occupancy Sensor Acceptance
- Manual Daylight Controls Acceptance
- Automatic Time Switch Control Acceptance
Equipment requiring acceptance testing
❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing
Page:9 of 57
]CERTIFICATE OF COMPLIANCE MECH-1-C
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1
1/11/2007
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Buildina Deoartments:
:e -conditioning system serving a
he Acceptance Requirements for
specifications, installation
Page:10 of 57
]INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG -2-C
PROJECT NAME
Centre Professional Plaza -Bldg 2
INSTALLED LIGHTING POWER FOR CONDITIONED SPACES
DATE
1/11/2007
Luminaire
Lamps/Ballasts
Installed Watts
C
D
E
F
G
H
I
J
Name
Type Description
�m
a3
CD
i c
333
�yC
`D `�
nriv�
3! �
y
c CO �
3.;v3
���
CD � °
C.0 �
Wim°
N
`DYPR
O
con
cm
•J
r
z
3• C
m�v
(D
H
G)��
x
v N CDd
(2) 4 ft Fluorescent T8 Elec
F32T8
2
32
1.0
62.0
X
4
248
(4) 4 ft Fluorescent T8 Elec
4
32
2.0
124.0
X
27
3,348
PAGE TOTAL 3 596
BUILDING TOTAL (sum of all pages) 3,596
PORTABLE LIGHTING (From LTG -3-C) D
CONTROL CREDIT (From LTG -4-C) O
ADJUSTED ACTUAL WATTS 3 596
EnergvPro 4.2 by EnergySoft User Number: 6712 Job Number: Paae:11 of 57 1
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
AIR SYSTEMS, Central or Single Zone
HVAC -1
HVAC -2
HVAC -3
1
1
1
Reference on Plans or Specification 1
112(a)
7.20 HSPF
7.20 HSPF
7.20 HSPF
112(a)
12.0 SEER / 10.5 EER
12.0 SEER / 9.6 EER
12.0 SEER / 9.6 EER
112(b)
Yes
Yes
Yes
112(c), 115(a)
n/a
n/a
n/a
121(b)
Yes
Yes
Yes
121 b
98 cfm
151 cfm
151 cfm
121 c
No
No
No
121(c)
No
No
No
121 c 122(e)
Pro rammable Switch
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Required
Heating & Cooling Required
122
Auto
Auto
Auto
122
n/a
n/a
n/a
123
124
R-4.2
R-4.2
R-4.2
144 a & b
n/a
n/a
n/a
144 a & b
25,607 btuh
35,601 btuh
35,601 btuh
144 a & b
n/a
n/a
n/a
144 a & b
25,899 btuh
37,373 btuh
37,313 btuh
144 c
Constant Volume
Constant Volume
Constant Volume
144 (c)
144 c
Yes
Yes
Yes
144 d
No
No
No
144 a
No Economizer
No Economizer
No Economizer
144
Constant Temp
Constant Temp
Constant Tem
144 (f)
Constant Temp
Constant Temp
Constant Temp
144 k)
No
No
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
Kun Initiation Time: 01/11/07 10:55:10 Run Code: 1168541710
EnergyPro 4.2 by Energy5oft User Number: 6712 Job Number: Pape:12 of 57
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11!2007
SYSTEM FEATURES 771
ITEM OR SYSTEM TAG(S)
Number of Systems
AIR SYSTEMS, Central or Single Zone
HVAC -4
HVAC -5
HVAC -6
1
1
1
T-24
MANDATORY MEASURES Section Reference on Plans or Specification 1
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
112(a)
7.20 HSPF
7.20 HSPF
7.20 HSPF
112(a)
12.0 SEER / 9.6 EER
12.0 SEER / 9.6 EER
12.0 SEER / 9.6 EER
112(b)
Yes
Yes
Yes
112(c), 115(a),n/a
37,334 btuh
n/a
n/a
121(b)
Yes
Yes
Yes
121 b
151 cfm
151 cfm
140 cfm
121 c
No
No
No
121 c
No
No
No
121 c 122(e)
Programmable Switch
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Required
Heating & Cooling Required
122
Auto
Auto
Auto
122
n/a
n/a
n/a
123
124
R-4.2
R-4.2
R-4.2
144 a & b
n/a
n/a
n/a
144 a & b
35,601 btuh
35,601 btuh
35,601 btuh
144 a & b
n/a
n/a
n/a
144 a & b
37,334 btuh
37,334 btuh
37,548 btuh
144 c
Constant Volume
Constant Volume
Constant Volume
144 c)
144 c
Yes
Yes
Yes
144 d
No
No
No
144 a
No Economizer
No Economizer
No Economizer
144
Constant Tem
Constant Temp
Constant Tem
144 (f)
Constant Temp
Constant Temp
Constant Temp
144 k
No
No
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
EnergvPro 4.2 by EnergvSoft User Number: 6712 Job Number: Page:13 of 57 1
WATER SIDE SYSTEM REQUIREMENTS Part 2 of 2 MECH-2-C
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
SYSTEM FEATURES
2 WATER SIDE SYSTEMS: Chillers, Towers, Boilers, H dronic Loops
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section Reference on Plans or Specification'
Equipment Efficiency 112(a)
Pipe Insulation 123
PRESCRIPTIVE MEASURES
Calculated Capacity
Proposed Capacity
Tower Fan Controls
Tower Flow Controls
Variable Flow System Design
Chiller and Boiler Isolation
CHW and HHW Reset Controls
WLHP Isolation Valves
VSD on CHW, CW & WLHP Pumps > 5
HP
DP Sensor Location
144 (a & b)
144 (a & b)
144 h
144 h
144 0)
144
144 0)
144
144
144
1: For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph
number where the required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Water side systems include wet side system using other liquids such as glycol or brine.
1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and
paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" ins the column.
I EnerovPro 4.2 by EnerovSoft User Number: 6712 Job Number: Page:14 of 57 1
Service Hot Water, Pool Heating
ITEM OR SYSTEM TAG(S)
DHW Heater
Number of Systems
2
MANDATORY MEASURES
Reference on Plans or Specification'
Water Heater Certification
113 (a)
AO SMITH ELJF-06"
Water Heater Efficiency
113 (b)
99%
Service Water Heating Installation
113 (c)
Pool and Spa Efficiency and Control
114 a
n/a
Pool and Spa Installation
114 b
n/a
Pool Heater - No Pilot Light
115 (c)
n/a
Spa Heater - No Pilot Light
115 d
n/a
1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and
paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" ins the column.
I EnerovPro 4.2 by EnerovSoft User Number: 6712 Job Number: Page:14 of 57 1
MECHANICAL VENTILATION MECH-3-C
PROJECT NAME
Corporate Centre Professio
DATE
PRESCRIPTIVE REHEAT
LIMITATION (Section 144(d))
MECHANICAL VENTILATION Section 121(b)21
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
1
J
K
L
M
N
ZONE/SYSTEM
n
D�
a
0)F
0
N
a
won
-n -n
°o
0
o3
W`��
x 0 -n
Iv 3
c
m3
oam
m°
mon
om3
cN
�`3
m0�
-nr
T 7 3
..
m
vo3iA
�Kv
<D
<
n��
-nc-acv
D
o
o�
nmo
w
� Q
n
T3`x�
no
x A
;K n
oc
w3c3i
oyx
T=
3 �
0
yy,
;:�
o3
P
D
-�
vi
A
D
Zone 1
655
0.22
144
144
98
46
HVAC -1
Total
144
98
Zone 2
1,006
0.22
221
221
151
70
HVAC -2
Total
221
151
Zone 3
1,006
0.22
221
221
151
70
HVAC -3
Total
221
151
Zone 4
1,006
0.22
221
221
151
70
HVAC -4
Total
221
151
Zone 5
1,006
0.22
221
221
151
70
HVAC -5
Total
221
151
Zone 6
935
0.221
206
206
140
65
HVAC -6
Total
206
140
rate per Section 121 Table 121-A
E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seatin .
H Required Ventilation Air REO'D V.A. is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G).
I Must be greater than orequal to H or use Transfer Air column N to make up the difference.
J Design fan supply cfm Fan CFM x 30%; or
K Condition area ft. s x 04 cfm/ft. sq. F or
L Maximum of Columns H, J, K, or 300 cfm
M IThis must be less than orequal to Column L and greater that orequal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column H) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or
equal to the difference between the Required Ventilation Air (column H) and the Design Minimum Air (column M), column H - M.
Ener Pro 4.2 by Ener Soft User Number: 6712 Job Number: Page: 15 of 57
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 J�-C]MECH
PROJECT NAME
Corporate Centre Professional Plaza -Bldg 2
DATE
1/11/2007
CHILLER AND TOWER SUMMARY
Efficiency
Tons
PUMPS
Equipment Name
Equipment Type
Qty.
Tot.
Qty
GPM
BHP
Motor
Eff.
Drive
Eff.
Pump
Control
CENTRAL SYSTEM RATINGS
HEATING
COOLING -
System Name
System pe
QtV
Out ut
Aux.
kW
Eff.
Out ut
Efficiency
Condition
Status
Economizer Type
Carrier 50JX0425
Packaged DX
1
41,000
0.0
7.20 HSPF
41,500
12.0 SEER / 10.5 EER
New
No Economizer
CARRIER 50JX0605
Packaged DX
5
57,000
0.0
7.20 HSPF
60,000
DHW / BOILER SUMMARY
New
Hot Water P mp
Control # HP Type
Hot Water Piping Len th ft
In Plenum Outside Buried
Add 1/2"
Insulation
CENTRAL SYSTEM RATINGS
HEATING
COOLING -
System Name
System pe
QtV
Out ut
Aux.
kW
Eff.
Out ut
Efficiency
Condition
Status
Economizer Type
Carrier 50JX0425
Packaged DX
1
41,000
0.0
7.20 HSPF
41,500
12.0 SEER / 10.5 EER
New
No Economizer
CARRIER 50JX0605
Packaged DX
5
57,000
0.0
7.20 HSPF
60,000
12.0 SEER / 9.6 EER
New
No Economizer
ENVELOPE MANDATORY MEASURES ENV -MM
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1 1/11/2007
DESCRIPTION
Designer
Enforcement
0
§118(,)
Installed Insulating Material shall have been certified by the manufacturer to comply
with the California Quality Standards for insulating material, Title 20, Chapter 4, Article
3.
X]
§118(,)
All Insulating Materials shall be installed in compliance with the flame spread rating
and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2.
X]
§ 117(a)
All Exterior Joints and openings in the building that are observable sources of air
leakage shall be caulked, gasketed, weatherstripped or otherwise sealed.
X]
§ 116(b)
Site Constructed Doors, Windows and Skylights shall be caulked between the unit
and the building, and shall be weatherstripped (except for unframed glass doors and
fire doors).
X❑
§ 116(a)1
Manufactured Doors and Windows installed shall have air infiltration rates not
exceeding those shown in Table Number 1-E. of the Standards. Manufactured
fenestration products must be labeled for U -value according to NFRC procedures.
§118(e)
Demising Walls in Nonresidential Buildings:
The opaque portions of framed demising walls in nonresidential buildings shall have
insulation with an installed R -value of no less than R-13 between framing members.
EnergyPro
By EnergySoft User Number: User Job Number: Page: 17 of 57 .
CERTIFICATE OF COMPLIANCE (Part 1 of 2) OLTG-1-C
PROJECT NAME
DATE
Corporate Centre Professional Plaza -Bldg 2
1/11/2007
PROJECT ADDRESS
79-245 Corporate Centre Drive La Quinta
Permit #
PRINCIPAL DESIGNER - LIGHTING
TELEPHONE
Building
DOCUMENTATION AUTHOR
TELEPHONE
Checked by/Date
Scott Design & Title 24
(760) 200-4780
Enforcement Agency Use
GENERAL INFORMATION
DATE OF PLANS
OUTDOOR LIGHTING ZONE
LZ1 LZ2 ❑X LZ3 LZ4
FUNCTION TYPE rX-] OUTDOOR LIGHTING F-] OUTDOOR SIGNS F-1 INDOOR SIGNS
PHASE OF CONSTRUCTION ® NEW CONSTRUCTION F-] ADDITION F-] ALTERATION
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the outdoor lighting system specifications need to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations.
This certificate applies only to building lighting requirements.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
SIGNATURE
DATE
Tim Scott
The Principal Lighting Designer hereby certifies that the proposed outdoor lighting and signs design represented in this set of
construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other
calculations submitted with this permit application. The proposed building has been designed to meet the lighting requirements
contained in Sections 110, 119, 130 through 132, and 146,and 149 of Title 24, Part 6.
Please Check One: (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.)
El I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this
document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer
or electrical engineer, or I am a licensed architect.
I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or
6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing
this work.
I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code
Sections 5537, 5538 and 6737.1.
PRINCIPAL LIGHTING DESIGNER - NAME
SIGNATURE
DATE
LIC. #
LIGHTING COMPLIANCE FORMS & WORKSHEETS Check box if worksheet is included
191OLTG-1-C: Certificate of Compliance. Required on plans for all submittals for outdoor lighting. Part 2 of 2 maybe incorporated in schedules on the p
Either LTG -1-C or OLTG-I-C may be used for signs as follows:
1. Use LTG -1-C if the project consists solely of indoor signs.
2. Use LTG -1-C if the project consists of indoor lighting, outdoor or indoor signs, but no other outdoor lighting.
3. Use OLTG-1-C if the consists solely of outdoor signs.
project
4. Use OLTG-I-C if the project consists of outdoor lighting, outdoor or indoor signs, but no other indoor lighting.
[x OLTG-2-C: LIGHTING COMPLIANCE SUMMARY. Applicable parts required for ALL outdoor lighting allowances (Except Signs).
®OLTG-3-C: AREA CALCULATIONS WORKSHEET. Applicable parts required for all outdoor area calculations.
®OLTG-4-C: SIGN LIGHTING COMPLIANCE. Required for all internally and externally illuminated signs, for both indoor and outdoor
signs.
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 19 of 57
ans.
CERTIFICATE OF COMPLIANCE (Part 2 of 2) OLTG -C
(PROJECT NAME I DATE
Corporate Centre Professional Plaza -Bldg 2
1/11/2007
Lighting Schedules on Plans Show that Outdoor Lighting Meets Allowed Li htin Power
❑X
Lighting power allowance for general site illumination on OLTG-2-C Part 1 of 4
Not Applicable
❑
RX
Lighting power allowance for local ordinances or for security multipliers on OLTG-2-C Part 2 of 4
Not Applicable
❑X
❑
Lighting power allowances for specific applications, other than vehicle service stations with canopies on OLTG-2-C Part 3 of 4
Not Applicable
ElLighting
FX
power allowances for vehicle service station canopies on OLTG-2-C part 4 of 4
Not Applicable
❑X
F]
Sign lighting compliance on OLTG-4-C
Not Applicable
Mandatory Me sures on Plans Show that Outdoor Lighting Meets Outdoor Lighting Controls n ui men .
❑X
Installed lighting power has been determined in accordance with Section 130(c)1
Not Applicable
FX
All permanently installed luminaires with lamps rated 100 Watts either have a lamp efficacy of at least 60 lumins per Watt or are
controlled by a motion sensor per Section 132(a)
Not Applicable
aX
❑
All Luminaires with lamps rated greater than 175 Watts in hardscape area, including parking lots, building entrances, canopies, and all
outdoor sales areas meet the Cutoff Requirements of Section 132(b)
Not Applicable
FX
All permanently installed outdoor lighting meets the control requirements of Section 132(c)1
Not Applicable
aX
Building facades, parking lots, garages, canopies, and outdoor sales areas meet the Multi -Level Lighting Requirements of Section 132(c
Not Applicable
MANDATORY AUTOMATIC
CONTROLS
NOTE TO
FIELD
CONTROL LOCATION
(Room #)
CONTROL
IDENTIFICATION
CONTROL TYPE
(Auto Time Switch, Dimming, etc.)
AREA CONTROLLED
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:20 of 57
LIGHTING COMPLIANCE SUMMARY (Part 1 of 4) OLTG-2-C
Project. Name Date
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
LIGHTING POWER ALLOWANCES - GENERAL
SITE ILLUMINATION - Table 147-A
Allotted Watts
Luminaire
Lamps/Ballasts
Installed Watts
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Lighting Application
Category
(Table 147-A)
o'er
n
T x
�D
o
?co
rNa
ma r
o o
D
o
x
Wm
xa
q
d
ti�i
c
CL
m
Description
�
y. n
�c c
�$
?; �
c
r
,� d
v3
(D"O
rm
r
3 3
�H
m, a
y m
3
'0,0
cd
3 y
��
a o
�o
r
3 m
LEM
co
—
n
m
n
v,5
0�-
c
-
eZ
3.3
-c
y°
N
rco
xa
z
v d
Parking Lot Lighting
10,41
0.15
1,563
A
400w High Pressure Sodium
X
HPS400
1
400
1.01
469.01
X X
1,40
Total Installed Watts 1,40
Page:21 of 57
LIGHTING COMPLIANCE SUMMARY (Part 3 of 4) OLTG-2-C
Project Name
Corporate Centre Professional Plaza -Bldg 2
Date
1/11/2007
LIGHTING POWER ALLOWANCE FOR SPECIFIC APPLICATIONS Table 147-13 - Other than Vehicle Station without Cano
ies
Allotted Watts
Luminaire
Lam s/Ballasts
Desi n Watts
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Lighting Application
Category
(Table 147-B)
7, N
r- a
x
�o
?x0
F- A O.
Tar
oo
D
o
0°�
x a
n
m
ri
c
G
m
Description
�c
7 �
p;
o
,gym
v 3
m y
ca
33
7 N
a v
*
m
30
o o
�
e�
3�
� 0
°'
m�
301
7
"�
�`,
m
c7
p��
cC
3.3
y°
>
r`z�^
x 0' 5`1
z Edi
v °
D
>o
o.m
va
o
1m
Bldg Fasade
3,02
0.35
1,058
D
(2) 22w Compact Fluorescent
X
2
22
2.0
54.0
X X
37
37
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:22 of 57 1
ILLUMINATED AREA CALCULATION WORKSHEET (Part 1 of 5) OLTG-3-C
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
Hardscape - Method (i)
A. Hardscape for automotive vehicular use, including parking lots, driveways and site roads.
A
B
C D
I E
I F
I G
H
Lighting Application
(Table 147-B)
Actual Paved Area + 5'
perimeter of adjacent
unpaved land. Includes
planters and land.
Includes planters and
landscaped areas less
than 10' wide that are
enclosed by hardscape
on at least 3 sides.
Actual Paved Area + 5' of
unpaved land on either
side of path of travel.
Shall include all
contiguous paved area
before including adjacent
grounds.
Areas (SF) to Subtract
from within
the Illuminated Area
the Illuminated Area
Illuminated Area
(B - G)
Area between
poles or
luminaires that
are > 6 times th
mounting height
distance
(If Applicable)
Overlapping
areas
of another
application or
luminaire
Building
Areas
Areas
obstructed
by signs or
other structures
Sub total of
areas
to subtract
(C + D + E + F)
Parkina Lot Liahting
10,418
0
0
0
0
0
10.418
B. Hardscape for pedestian use, including plazas, sidewalks, walkways and bikeways
A
B
C
D
E
F
G
H
Lighting Application
(Table 147-B)
Actual Paved Area + 5' of
unpaved land on either
side of path of travel.
Shall include all
contiguous paved area
before including adjacent
grounds.
Areas SF to Subtract
from within
the Illuminated Area
Illuminated Area
(B - G)
Area between
poles or
luminaires that
are > 6 times thE
mounting height
distance
(If Applicable)
Overlapping
areas
of another
application or
luminaire
Building
Areas
Areas
obstructed
by signs or
other structures
Sub total of
areas
to subtract
(C + D + E + F)
Checklist
❑ Section 147 (c)1 B - Each portion of all illuminated areas has been assigned only one lighting application, and the applications are consistent with actual use of the areas.
F] Section 147 (c)1 A - General Illumination areas includes only those illuminated areas that are in the bounds of the Application and are within a square pattern around a
luminaire that is six times the luminaire mounting height, with the luminaire in the middle of the patttern, less any areas that are within buildings, under canopies, beyond
property lines, or obstructed by signs or other structures.
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 23 of 57
ILLUMINATED AREA CALCULATION WORKSHEET (Part 3 of 5) OLTG-3-C
PROJECT NAME DATE
Corporate Centre Professional Plaza-Blda 2 1
1/11/2007
IA. Outdoor Sales Lot Frontage and Sales Lot Area I
A
B
I C I
D I
E
I F
G
H
Gross Illuminated Area
(sq. ft.)
If an Outdoor Sales
Frontage Allotment was
used, subtract that area
from the Gross Illuminated
Area
Overlapping
Areas of
Another
Application
Sales Lot Area
(A - F - G)
Mounting height of
Sales Frontage
Luminaires (feet)
3 x B
Distance (In plan
view)from the
frontagge
luminaire to froni
edge of Sales
Lot
Sales Lot
Frontage
Length (feet)
Sales Frontage
Area
(C - D) x E
(sq. ft.)
❑ Section 147 (c)1 B - Each portion of all illuminated areas has been assigned only one lighting application, and the applications are consistent with actual use of the areas.
❑ Section 147 (c)2 B - Measured in plan view, only illuminated sections of outdoor sales frontage areas that are immediately adjacent to the principle viewing location and
unobstructed viewing length, and are within 3 mounting heights of the frontage have been used. Luminaires qualifying for this allowance are located in plan view between the
principle viewing location and the frontage sales.
B. Building Facade Area
A
B
C
D
E F G
H
Designated Name
and Orientation
Length
Height
Gross Area
(B x C)
Areas (SF) to Subtract
from within the Illuminated
Area
Net Area
Available for
Facade
Ligghting
(D - G)
Areas covered
by signs
Area for which
Illumination is
Obstructed by
Other Objects
and Area Not
Illuminated
Sub total
(E + F)
Bldg Fasade
168
18
3,024
0
0
3,024
Checklist
❑ Section 147 (01 B - Each portion of all illuminated areas has been assigned only one lighting application, and the applications are consistent with actual use of the areas.
❑ Section 147 (c)2 A - Only facades areas that are illuminated without obstruction or interference, by one or more luminaires, have been used.
Page:24 of 57
LIGHTING MANDATORY MEASURES LTG-MM
PROJECT NAME
Centre Professional Plaza -B
DATE
1/11/2007
DESCRIPTION
Designer
Enforcement
❑X §131(d)1 For every floor, all interior lighting systems shall be equipped with a separate automatic
control to shut off the lighting. This automatic control shall meet the requirements of
Section 119 and may be an occupancy sensor, automatic time switch, or other device
capable of automatically shutting off the lighting.
XJ §131(d)2Override for Building Lighting Shut-off: The automatic building shut-off system is
provided with a manual, accessible override switch in sight of the lights. The area
of override is not to exceed 5,000 square feet.
R§119(h) Automatic Control Devices Certified: All automatic control devices specified are
certified, all alternate equipment shall be certified and installed_ as directed by the
manufacturer.
0 §111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for
the project are certified and listed in the Directory. All installed fixtures shall be
certified.
0 §132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three
lamp fluorescent fixtures are tandem wired with two lamp ballasts where required
by Standards Section 132; or all one and three lamp fluorescent fixtures are
specified with electronic high -frequency ballasts and are exempt from tandem
wiring requirements.
X] §131(a) Individual Room/Area Controls: Each room and area in this building is equipped
with a separate switch or occupancy sensor device for each area with floor -to -
ceiling walls.
a§131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100
square feet and more than 0.8 watts per square foot of lighting load shall be
controlled with bi-level switching for uniform reduction of lighting within the room.
❑ §131(c) Daylight Area Control: All rooms with windows and skylights that are greater than
250 square feet and that allow for the effective use of daylight in the area shall
have 50% of the lamps in each daylit area controlled by a separate switch; or the
effective use of daylight cannot be accomplished because the windows are
continuously shaded by a building on the adjacent lot. Diagram of shading during
different times of the year is included on plans.
§131(e) Display Lighting. Display lighting shall be separately switched on circuits that
are 20 amps or less.
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:25 of 57
MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
PROJECT NAME
to Centre Professional Plaza -B
DATE
1/11/2007
DESCRIPTION
Designer
Enforcement
Equipment and Systems Efficiencies
FX—] §111 Any appliance for which there is a California standard established in the Appliance
Efficiency Regulations will comply with the applicable standard.
§ 115(a) Fan type central furnaces shall not have a pilot light.
RI § 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
n § 124 Air handling duct systems shall be installed and insulated in compliance with
Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards.
Controls
§ 122(e) Each space conditioning system shall be installed with one of the following:
§ 122(e)1A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the requirements
of Section 112 (d)) shall be installed with an automatic time switch with an
accessible manual override that allows operation of the system during off -hours for
up to 4 hours. The time switch shall be capable of programming different
schedules for weekdays and weekends and have program backup capabilities that
prevent the loss of the device's program and time setting for at least 10 hours if
power is interrupted; or
§ 122(e)1 B An occupancy sensor to control the operating period of the system; or
§ 122(e)1 C A 4 -hour timer that can be manually operated to control the operating period of the
system.
§ 122(e)2 Each space conditioning system shall be installed with controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint.
❑ § 122(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with isolation
zones. Each zone: shall not exceed 25,000 square feet; shall be provided with
isolation devices, such as valves or dampers, that allow the supply of heating or
cooling to be setback or shut off independently of other isolation areas; and shall
be controlled by a time control device as described above.
® § 122(a&b) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the control
shall be adjustable up to 85 degrees F or higher. Where used for both heating and
cooling, the control shall be capable of providing a deadband of at least 5 degrees
F within which the supply of heating and cooling is shut off or reduced to a
minimum.
0 § 122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable
setpoint stops accessible only to authorized personnel.
§ 112(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
EnergyPro By EnergySoft User Number: User Job Number: Page: 26 of 57
MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM
NAME
Corporate Centre Professional Plaza -Bldg 2
DATE
1/11/2007
Description
Designer
Enforcement
Ventilation
FX]
§ 121(e)
Controls shall be provided to allow outside air dampers or devices to be operated at
the ventilation rates as specified on these plans.
§ 122(f)
Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air intakes and discharges of all space conditioning and
exhaust systems.
n§
122(f)
All gravity ventilating systems shall be provided with automatic or readily accessible
manually operated dampers in all openings to the outside, except for combustion air
openings.
X❑
§ 121(f)1
Air Balancing: The system shall be balanced in accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
Associated Air Balance Council (AABC) National Standards (1989); or
§ 121(f)2
Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the
installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the
person with overall responsibility for the design of the ventilation system; or
X❑
§ 121(f)3
Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
a§
121(f)4
Another method approved by the Commission.
Service
Water Heating Systems
❑
§ 113(b)2
If a circulating hot water system is installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water is not required.
o§
113(c)
Lavatories in restrooms of public facilities shall be equipped with controls to limit the
outlet temperature to 110 degrees F.
EnergyPro
By EnergySoft User Number: User Job Number: Page: 27 of 57
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
SYSTEM NAME FLOOR AREA
HVAC -1 655
Number of Systems
1
Heating System
Output per System
41,000
Total Output (Btuh)
41,000
Output (Btuh/sgft)
62.6
Cooling System
Output per System
41,500
Total Output (Btuh)
41,500
Total Output (Tons)
3.5
Total Output (Btuh/sgft)
63.4
Total Output (sgft/Ton)
189.4
Air System
CFM per System
1,400
Airflow (cfm)
1,400
Airflow (cfm/sgft)
2.14
Airflow (cfm/Ton)
404.8
Outside Air (%)
7.0
Outside Air (cfm/sgft)
0.15
Note: values above aiven at ARI conditions
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensiblel
Latent
I CFM
I Sensible
1,073
15,896
2,996
893
12,623
0
795
631
0
0
98
3,562
1,015
98
4,556
0
0
795
631
21 048 4 01
HVAC EQUIPMENT SELECTION
Carrier 50JX0425 25,899 11,961
Total Adjusted System Output 25,899 11,961
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 5 pm
25,607
25,607
Jan 12 am
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0 OF 66.5 OF 83.7 OF 83.7 OF
OSupply Air Ducts
Outside Air
98 cfm 83.3 °F
Heating Coil Supply Fan
1400 cfm ROOMS
70.0 OF
69.6 OF i
�% Return Air Ducts `S
(COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Coolina Peak) I
08.6 / 77.0 OF 76.9 / 65.6 OF . 59.5 / 58.6 OF 59.5 / 58.6 OF
Outside Air
98 cfm
74.5/64.5 °F
Cooling Coil
O Supply Air Ducts
Supply Fan 60.1/58 . 8 OF
1400 cfm 59.7% R.H. ROOMS
74.0 / 64.3 OF
Return Air Ducts I
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:28 of 57
. HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
SYSTEM NAME FLOOR AREA
HVAC -2 1,006
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
11COILHTG.PEAK
CFM
I Sensiblel
Latent
I I CFM
I Sensible
1,254
18,484
4,592
958
13,069
0
924
653
0
0
15
6,033
1,475
151
7,017
0
0
924
653
26,366F 6,0671
21 392
CARRIER 50JX0605 37,373 16,642 35,601
Total Adjusted System Output 37,373 16,642 35,601
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 3 pm Jan 12 am
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0 OF 66.4 OF 83.10F 83.1°F
O Supply Air Ducts
Outside Air
151 cfm 82 8 °F
Heating Coil Supply Fan
2000 cfm ROOMS
70.0 OF
69.7 OF
h Return Air Ducts '4
(COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Coolina Peak) I
12.0 / 77.9 OF
Outside
��
151 cfm
74.4 / 64.6 °F
77.3/65.80F M 59.7/58.80F
Cooling Coil
0
Supply Fan
2000 cfm
59.7 / 58.8 of
Supply Air Ducts
60.1 / 59.0 of
60.2% R.H. ROOMS
74.0 / 64.5 OF
h Return Air Ducts `S
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:29 of 57 1
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
SYSTEM NAME FLOOR AREA
HVAC -3 1,006
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems
1
Heating System
Output per System
57,000
Total Output (Btuh)
57,000
Output (Btuh/sgft)
56.7
Cooling System
Output per System
60,000
Total Output (Btuh)
60,000
Total Output (Tons)
5.0
Total Output (Btuh/sqft)
59.6
Total Output (sgft/Ton)
201.2
Air System
CFM per System
2,000
Airflow (cfm)
2,000
Airflow (cfm/sqft)
1.99
Airflow (cfm/Ton)
400.0
Outside Air (%)
7.5
Outside Air (cfm/sgft)
0.15
Note: values above given at ARI conditions
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensiblel
Latent
CFM
I Sensible
989
14,726
4,592
798
10,967
0
736
548
0
0
15
6,047
1,488
151
7,025
0
0
736
548
22,253T 6 080 19 089
CARRIER 50JX0605 37,313 16,660 35,601
Total Adjusted System Output 37,313 16,660 35,60
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 3 pm an 12 am
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0 of 66.4 of 83.2 of 83.2 of
e O Supply Air Ducts
Outside Air
151 cfm
Heating Coil Supply Fan 82.9 OF
2000 cfm ROOMS
69.7 of 70.0 of
iL 0-41 — A:. n.. —4— E I
(COOLING SYSTEM PSYCHROMETRICS (Airstream Temueratures at Time of Cooling Peakl I
12.0 / 77.9 OF 77.2 / 65.5 of 59.7 / 58.8 of
Outside Air
151 cfm
74.3/64.50F
Cooling Coil
Supply Fan
2000 cfm
59.7 / 58.8 of
Supply Air Ducts
60.0 / 58.9 of
60.1% R.H. ROOMS
74.0 / 64.4 of
h Return Air Ducts 'I
EnergyPro 4.2 by Energysoft User Number: 6712 Job Number: Page:30 of 57
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
SYSTEM NAME FLOOR AREA
HVAC -4 1,006
ENGINEERING CHECKS SYSTEM LOAD11 1 11
Number of Systems 1
Heating System
Output per System 57,000
Total Output(Btuh) 57,000
Output (Stuh/sgft) 56.7
Cooling System
Output per System 60,000
Total Output (Btuh) 60,000
Total Output (Tons) 5.0
Total Output (Btuh/sgft) 59.6
Total Output (sgft/Ton) 201.2
Air System
CFM per System 2,000
Airflow (Cfm) 2,000
Airflow (cfm/sgft) 1.99
Airflow (cfm/Ton) 400.0
Outside Air N 7.5
Outside Air (cfm/sgft) 0.15
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
AK
4,592
798
10,967
0
800
548
0
0
15
6,042
1,484
151
7,025
0
0
800
548
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK COIL HTG. PE
CFM I Sensible Latent CFM Sensible
1,078
AK
4,592
798
10,967
0
1,078
15,994
4,592
798
10,967
0
800
548
0
0
15
6,042
1,484
151
7,025
0
0
800
548
23,644 6,076 F 19 089
CARRIER 50JX0605 37,334 16,654 35,601
Total Adjusted System Output 37,334 16,654 35,60
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 3 pm I Jan 12 am
Note: values above given at ARI conditions
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0 of 66.4 of 83.2 of 83.2 of
.ovO Supply Air Ducts
Outside Air
151 cfm 82 9 of
Heating Coil Supply Fan
2000 cfm ROOMS
69.7 of 70.0 of
Return Air Ducts < I
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112.0 / 77.9 of 77.2 / 65.8 of 59.7 / 58.8 of 59.7 / 58.8 of
&:% Supply Air Ducts
Outside Air
151 cfm Cooling Coil Supply Fan 60.1 / 58.9 of
2000 cfm 60.2% R.H. ROOMS
74.4/64.6 o f 74.0 64.4 OF
Return Air Ducts
EnergyPro 4.2 by Energysoft User Number: 6712 Job Number: Page:31 of 57
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
SYSTEM NAME FLOOR AREA
HVAC -5 1,006
ENGINEERING CHECKS 11SYSTEM LOAD
Number of Systems
1
Heating System
Output per System
57,000
Total Output (Btuh)
57,000
Output (Btuh/sqft)
56.7
Cooling System
Output per System
60,000
Total Output (Btuh)
60,000
Total Output (Tons)
5.0
Total Output (Btuh/sqft)
59.6
Total Output (sgft/Ton)
201.2
Air System
CFM per System
2,000
Airflow (cfm)
2,000
Airflow (cfm/sgft)
1.99
Airflow (cfm/Ton)
400.0
Outside Air (%)
7.5
Outside Air (cfm/sgft)
0.15
Note: values above
JEATING SYSTE
26.0 OF
Outside Air
151 cfm
69.7 OF
at ARI conditions
66.4 OF
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
Latent
CFM
I Sensible
1,078
15,994
4,592
798
10,967
0
800
548
0
0
15
6,042
1,484
151
7,025
0
0
800
548
23,641477;,0;6 19,0891
HVAC EQUIPMENT SELECTION
CARRIER 50JX0605 37,334 16,654 35,60
Total Adjusted System Output 37,334 16,654 35,601
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 3 am Jan 12 am
ream Temperatures at Time of Heating Peak
83.2 OF 83.2 OF
O Supply Air Ducts
Supply Fan 82.9 OF
2000 cfm ROOMS
70.0 OF
Heating Coil
COOLING SYSTEM PSYCHROMETRICS (Airstream T
112.0 / 77.9 OF 77.2 / 65.8 OF
Outside Air
151 rfm
74.4/64.6 °F
K Return Air Ducts `i
59.7 / 58.8 OF 59.7 / 58.8 OF
O>S Supply Air Ducts
Supply Fan 60.1 / 58.9 OF
2000 cfm 60.2% R.H. ROOMS
74.0 / 64.4 OF
Return Air Ducts I
Cooling Coil
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Paoe:32 of 57
,HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
SYSTEM NAME FLOOR AREA
HVAC -6 935
METRI
26.0 OF 66.5 OF
Outside Air
140 cfm
69.5 OF
COOLING S
112.0 / 77.9 OF
Outside Air
140 cfm
74.5/64.5 OF
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
Latent
CFM
I Sensible
1,525
22,638
4,268
Li,4E
19,953
0
1,132
998
0
0
140
5,592
1,448
140
6,497
0
0
1,132
998
30 494 5 716
CARRIER 50JX0605 37,548 16,291
Total Adjusted System Output 37,548 16,291
(Adjusted for Peak Design Conditions)
Heating Coil
TIME OF SYSTEM PEAK L Jul 3 pm
im Tei
83.2 OF
28,4415
35,601
35,901
Jan 12 am
83.2 of
Supply Air Ducts
Supply Fan 82.7 °F
2000 cfm ROOMS
70.0 OF
Return Air Ducts I
m Temperatures at Time of
77.2 / 65.6 OF i 59.5 / 58.6 OF
Supply Fa
2000 cfm
59.5 / 58.6 of
Supply Air Ducts
Fan
Cooling Coil
60.1 / 58.8 of
59.6% R.H. ROOMS
74.0 / 64.3 OF
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 33 of 57
ROOM LOAD SUMMARY
PROJECT NAME DATE
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
SYSTEM NAME FLOOR AREA
HVAC -1 655
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 1
Zone 1
1
1,073
15,896
2,996
1,073
15,896
2,996
893
12,623
EnergyPro By EnergySoft User Number: User Job Number: Page:34 of 57
ROOM LOAD SUMMARY
PROJECT NAME
Corporate Centre Professional Plaza -Bldg 2
DATE
1/11/2007
SYSTEM NAME
HVAC -2
FLOOR AREA
1,006
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 2
Zone 2
1
1,254
18,494
4,595
1,254
18,484
4,592
958
13,069
PAGE TOTAL 1 1,254 18,484 4,592 958 13,069
TOTAL 1 1,254 18,484 4,59211 958 13,069
EnergyPro By EnergySoft User Number: User Job Number: Page: 35 of 57
ROOM LOAD SUMMARY
PROJECT NAME
Corporate Centre Professional Plaza -Bldg 2
DATE
1/11/2007
SYSTEM NAME
HVAC -3
FLOOR AREA
1,006
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 3
Zone 3
1
994
14,810
4,595
989
14,726
4,592
798
10,967
PAGE TOTAL 1 989 14,726 4,592 798 10,967
TOTAL 989 14,726 4,592 798 10,967
EnergyPro By EnergySoft User Number: User Job Number: Page:36 of 57
ROOM LOAD SUMMARY
PROJECT NAME
Corporate Centre Professional Plaza -Bldg 2
DATE
1/11/2007
SYSTEM NAME
HVAC -4
FLOOR AREA
1,006
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 4
Zone 4
1
1,083
16,078
4,595
1,078
15,994
4,592
798
10,967
PAGE TOTAL 1 1,078 15,994 4,592 798 10,967
TOTAL 1 1,078 15,994 4,59211 798 10,967
EnergyPro By EnergySoft User Number: User Job Number: Page: 37 of 57
ROOM LOAD SUMMARY
PROJECT NAME
Corporate Centre Professional Plaza -Bldg 2
DATE
1/11/2007
SYSTEM NAME
HVAC -5
FLOOR AREA
1,006
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 5
Zone 5
1
1,083
16,078
4,595
1,078
15,994
4,592
798
10,967
PAGE TOTAL 1 1,078 15,994 4,592 798 10,967
TOTAL 1 1,078 15,994 4,592 798 10,967
Page:38 of 57
ROOM LOAD SUMMARY
PROJECT NAME
Corporate Centre Professional Plaza -Bldg 2
DATE
1/11/2007
SYSTEM NAME
HVAC -6
FLOOR AREA
935
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 6
Zone 6
1
1,525
22,638
4,268
1,525
22,638
4,268
1,472
19,953
PAGE TOTAL 1 1,525 22,638 4,268 1,472 19,953
TOTAL 1 1,525 22,638 1 4,268 1,472 19,953
EnergyPro By EnergySoft User Number: User Job Number: Page: 39 of 57
ROOM HEATING PEAK LOADS
Project Title Date
Corporate Centre Professional Plaza-Bld 2 1/11/2007
Room Information Desi n Conditions
Room Name zone 1 Time of Peak Jan 12 am
Floor Area 655 Outdoor Dry Bulb Temperature 26°F
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT of Btu/hr
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 1 O 067
Infiltration: 1 1.00 X 1.064 X 655 X 10.00 X 0.500 / 6] X � = 2 556
chedule Air Sensible Area Ceiling Height ACH pT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 12,623
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:40 of 57
655.0
X
x
X
X
X
x
X
x
x
X
x
x
x
X
X
X
X
x
X
X
X
X
X
x
x
x
X
X
X
x
X
X
X
X
X
x
X
x
X
0.0360
X
X
X
X
X
X
x
X
X
X
x
x
X
X
X
X
X
X
X
X
X
X
X
X
X
x
x
X
X
X
X
X
x
X
X
X
X
X
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
1,038
96.0
0.0740
44
313
39.0
0.8700
44
1,493
135.0
0.0740
44
440
407.0
0.0740
44
1,325
39.0
0.8700
44
1,493
39.0
0.8700
44
1,493
perimeter = 77.0
0.7300
44
2,473
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 1 O 067
Infiltration: 1 1.00 X 1.064 X 655 X 10.00 X 0.500 / 6] X � = 2 556
chedule Air Sensible Area Ceiling Height ACH pT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 12,623
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:40 of 57
ROOM HEATING PEAK LOADS
Project Title Date
Corporate Centre Professional Plaza -Bldg 2 11/11/2007
Room Information Desi n Conditions
Room Name zone 2 Time of Peak Jan 12 am
Floor Area 1,006 Outdoor Dry Bulb Temperature 26 OF
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT of Btu/hr
IDouble Metal Tinted Default I
1006.0
x
x
x
x
x
x
X
x
x
x
x
X
X
x
x
X
x
x
x
X
x
x
X
x
x
x
x
X
X
x
x
x
x
x
x
x
x
X
X
0.0360
X
X
x
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
X
X
x
X
x
x
X
x
x
x
X
X
x
x
X
X
x
x
X
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
1,594
72.0
0.0740
44
234
39.0
0.8700
44
1,493
42.0
0.8700
44
1,608
18.0
0.8700
44
689
39.0
0.8700
44
1,493
210.0
0.0740
44
684
perimeter = 42.0
0.7300
44
1,349
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 9,143
Infiltration: 1 1.001 x 1.064 x 1 006 x 10.00 x 0.500 / 6] x &T = 3 926
chedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 13,069
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 41 of 57
RnnM HFATING PEAK l_nAnS
Project Title Date
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
Room Information Design Conditions
Room Name zone 3 Time of Peak Jan 12 am
Floor Area 1,006 Outdoor Dry Bulb Temperature 26OF
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT of Btu/hr
Items shown with an asterisk (•) denote conduction through an interior surface to another room. Page Total: 7 042
Infiltration: r 1.00 x 1.osa x 1 oos x 10.0o x o.500 / 60� x as = 3 92s
schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 10,967
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 42 of 57
1006.0
X
X
X
x
X
X
X
x
x
x
x
x
X
x
x
x
X
x
X
X
x
x
x
x
X
X
X
x
X
x
x
X
x
X
x
X
X
x
x
0.0360
X
X
X
x
X
X
x
X
x
x
x
X
X
X
X
X
X
X
X
X
x
X
x
x
x
x
x
X
x
x
X
x
X
X
x
X
X
X
X
44
=
=
=
=
—
—
=
=
—
=
=
=
—
—
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
—
=
=
=
1,594
132.0
0.0740
44
430
39.0
0.8700
44
1,493
39.0
0.8700
44
1,493
210.0
0.0740
44
684
perimeter = 42.0
0.7300
44
1,349
Items shown with an asterisk (•) denote conduction through an interior surface to another room. Page Total: 7 042
Infiltration: r 1.00 x 1.osa x 1 oos x 10.0o x o.500 / 60� x as = 3 92s
schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 10,967
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 42 of 57
ROOM HEATING PEAK LOADS
Project Title Date
Corporate Centre Professional Plaza -Bldg 2 11/11/2007
Room Information Desi n Conditions
Room Name zone Time of Peak Jan 12 am
Floor Area 1,006 Outdoor Dry Bulb Temperature 26OF
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT of Btu/hr
Metal
1006.0
X
X
x
X
x
x
X
x
x
X
x
X
X
X
X
X
X
X
X
x
X
x
x
x
X
X
X
x
X
X
x
X
X
X
X
X
X
X
X
0.0360
X
x
X
x
X
X
X
X
X
x
x
x
X
X
x
x
X
X
x
x
x
X
X
X
X
X
X
X
x
X
X
x
X
X
x
X
x
x
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
1,594
132.0
0.0740
44
430
39.0
0.8700
44
1,493
39.0
0.8700
44
1,493
210.0
0.0740
44
684
perimeter = 42.0
0.7300
44
1,349
Items shown with an asterisk (•) denote conduction through an interior surface to another room. Page Total: 7,042
Infiltration: 1 1.001X 1.064 X 1 006 X 10.00 x 0.500 / 6] X 0 = 3 926
chedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 10,967
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page:43 of 57
.1 ROOM HEATING PEAK LOADS
Project Title Date
Corporate Centre Professional Plaza-Bldg2 1/11/2007
Room Information Desi n Conditions
Room Name zone 5 Time of Peak Jan 12 am
Floor Area 1,006 Outdoor Dry Bulb Temperature 26OF
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT of Btu/hr
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 7 042
Infiltration: r 1.001 X 1.064 X 1 006 X 10.00 X 0.500 / 6] X 44 = 3 926
schedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 10,967
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 44 of 57
1006.0
X
X
X
x
X
X
X
X
X
X
x
X
X
X
X
X
X
X
X
X
X
X
X
x
X
X
X
x
x
X
x
X
X
X
X
x
X
X
X
0.0360
X
x
X
x
X
X
X
X
X
X
x
X
X
X
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
1,594
132.0
0.0740
44
430
39.0
0.8700
44
1,493
39.0
0.8700
44
1,493
210.0
0.0740
44
684
perimeter = 42.0
0.7300
44
1,349
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 7 042
Infiltration: r 1.001 X 1.064 X 1 006 X 10.00 X 0.500 / 6] X 44 = 3 926
schedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 10,967
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 44 of 57
.1 ROOM HEATING PEAK LOADS
Project Title Date
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
Room Information Desi n Conditions
Room Name zone 6 Time of Peak Jan 12 am
Floor Area 935 Outdoor Dry Bulb Temperature 260F
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT of Btu/hr
Items shown with an asterisk ('r) denote conduction through an interior surface to another room. Page Total: 16 304
Infiltration: .001 x 1.064 x 935 x 10.00 x 0.500 / 6] x &T = 3648
chedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 19,953
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 45 of 57
935.0
X
X
x
X
X
x
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0.0360
X
X
x
X
X
x
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
-
=
-
=
=
=
-
=
-
=
-
=
=
=
=
=
=
=
-
=
=
=
=
1,481
495
152.0
0.0740
44
39.0
0.8700
44
1,493
42.0
0.8700
44
1,608
18.0
0.8700
44
689
39.0
0.8700
44
1,493
407.0
0.0740
44
1,325
39.0
0.8700
44
1,493
39.0
0,8700.
44
1,493
290.0
0.0740
44
944
erimeter = 118.0
0.7300
44=3
790
Items shown with an asterisk ('r) denote conduction through an interior surface to another room. Page Total: 16 304
Infiltration: .001 x 1.064 x 935 x 10.00 x 0.500 / 6] x &T = 3648
chedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 19,953
EnergyPro 4.2 by EnergySoft User Number: 6712 Job Number: Page: 45 of 57
ROOM COOLING PEAK LOADS
Project Title Date
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
ROOM INFORMATION DESIGN CONDITIONS
Room Name zone 1 Time of Peak Jul 5 pm
Floor Area 655 Outdoor Dry Bulb Temperature 109 OF
Indoor Dry Bulb Temperature 74`l= Outdoor Wet Bulb Temperature 77 `F
Conduction
30 Roof
19 Metal Stud Wall
Double Metal Tinted Default
Area
X
X
X
X
X
X
X
X
X
U -Value
655.0
0.0360
96.0
0.0740
117.0
0.8700
135.0
0.0740
407.0
0.0740
0.795
(W)
39.0
134
0.657
0.438
(W)
39.0
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
ow
DETD 1
X
X
X
X
X
X
X
X
X
52.7
=
=
=
=
=
=
=
=
=
38.3
25.1
35.8
56.9
Factor
=
=
=
=
=
U
39.0
Page Total
Orientation
Area
X
X
x
X
X
X
x
X
X
X
SGF
X
x
X
X
X
x
X
X
X
X
SC
Weighting
X
X
X
X
X
x
x
X
x
X
Factor
=
=
=
=
=
U
39.0
43
0.657
0.795
(W)
39.0
134
0.657
0.438
(W)
39.0
134
0.657
0.438
Page Total
Btu/hr
1,243
272
2,553
358
1,714
6 139
Btu/hr
875
1,509
1,509
3 893
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
fights 1.0c X 655 x 0.757 Watts/sqft X 3.41 Btuh/Watt X 0.999 = 1,692
ccu ants 1.0 X 655 x 300 Btuh/OCC. / 10C sgft/occ. X 1.00 = 1,965
Receptacle 1.0 x 655 X 0.000 Watts/sgft x 3.41 Btuh/Watt X 1.00 = 0
rocess 1.0 X 655 X 0.000 Watts/sqft x 3.41 Btuh[Watt X 1.00 = 0
Infiltration: 1.00 X 1.064 X 655 X 10.00 X 0.50 /601 X 38 = 2 207
-Schedule Air Sensible Area Ceiling Height ACH QT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 15,896
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 x 655 x 3001 Btuh/OCC. / 100 sqft/occ. = 1 965
Receptacle 1.00 x x a 000 Watts/sgft x 3 41 a I Btuh/watt =
Process 1.00 X 655 X 0.000 Watts/sgft x 1 3.413 Btuhfwatt = 0
Infiltration: x a 71 x x x � / 6] x � = 1031
chedule Air Latent Area Ceiling Height ACH pyy
ROOM COOLING PEAK LOADS
(Project Title Date
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
ROOM INFORMATION DESIGN CONDITIONS
Room Name zone Time of Peak Jul 2pm
Floor Area 1,006 Outdoor Dry Bulb Temperature 111 OF
Indoor Dry Bulb Temperature 74cl: Outdoor Wet Bulb Temperature 78 cl�
Conduction
Roof
Metal
Area
X
X
X
X
X
X
X
X
X
U -Value
1,006.0
0.0360
72.0
0.0740
78.0
0.8700
42.0
0.8700
18.0
0.8700
210.0
0.0740
42.0
46
0.657
0.702
(N)
18.0
t. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
DETD 1
X
X
X
X
X
X
X
X
X
76.6
=
=
=
=
=
=
=
=
=
36.5
25.0
25.0
25.0
42.2
=
=
=
=
=
=
(N)
39.0
Page Total
Orientation
Area
X
X
X
X
x
x
X
X
x
X
SGF
X
X
X
X
X
X
X
X
X
X
Sc
Weighting
X
x
X
x
X
x
X
X
X
X
Factor
=
=
=
=
=
=
(N)
39.0
46
0.657
0.700
(N)
42.0
46
0.657
0.702
(N)
18.0
46
0.657
0.700
(N)
39.0
46
0.657
0.700
Page Total
Btu/hr
2,773
194
1,699
915
392
656
6 629
Btu/hr
825
890
381
825
2 920
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
i hts 1.00 x 1,006 X 0.740 Watts/sqft x 3.41 Btuh/Watt X 0.999 = 2,537
ccu ants 1.0 x 1,006 X 300 Btuh/OCC. / 10 sgft/OCc. X 1.00 = 3,018
Receptacle 1.0 X 1,006 X 0.000 Wafts/sqft x 3.41 BtuhlWatt x 1.00 = 0
rocess 1.0c x 1,006 x 0.000 Watts/sgft x 3.41 Btuh[Watt x 1.00 = 0
Infiltration: 1.00 x 1.064 x 1 006 x 10.00 x 0.50 /601 x 38 = 3 390
chedule Air Sensible Area Ceiling Height ACH &T
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 18,494
Sched. Btulhr
Latent Gain Frac. Area Heat Gain
ccu ants 1.00 X 1,0061 X 300 Btuh/OCC. / 100 sgft/occ. = 3 018
Receptacle 1.00 x x 0000 Watts/sgft x 3 413 Btuh/Watt =
Process 1.00 x 1,006 x 0.000 Watts/sqft x 3.413 Btuh/Watt = 0
Infiltration: x x 1,006 x x 0p / 6] x � = 1 577
chedule Air Latent Area Ceiling Height ACH pyy
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 4 595
EnergyPro By EnergySoft User Number: User Page: 47 of 57
ROOM COOLING PEAK LOADS
Project Title
Corporate Centre Professional Plaza -Bldg 2
Date
1/11/2007
ROOM INFORMATION
DESIGN CONDITIONS
X
X
X
X
X
X
x
X
X
X
Room Name
zone 3
Time of Peak
Jul 2 pm
Floor Area
1,006
Outdoor Dry Bulb Temperature
111 OF
Indoor Dry Bulb Temperature
74 c1
Outdoor Wet Bulb Temperature
78 9F
Conduction
-30 Roof
-19 Metal Stud Wall
Double Metal Tinted Default
Area
21
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
U -Value
0.0360
0.0740
DETD 1
76.6 =
36.5 =
25.0 =
42.2 =
Page Total
Orientation
Area
X
x
x
X
X
x
X
X
X
X
SGF
X
X
X
X
X
X
x
X
X
X
SC
Weighting
X
X
x
X
X
X
X
X
X
X
Factor
=
=
=
=
=
=
=
(N)
39.0
46
0.657
0.700
U
39.0
46
0.657
0.700
Page Total
Btu/hr
2,773
356
1,699
656
5 484
Btu/hr
825
825
1649
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
i hts 1.0c X 1,006 X 0.370 Watts/sgft X 3.41 Btuh[Watt X 0.999 = 1,268
ccu ants 1.0c X 1,006 X 300 Btuh/OCC. / 10C sgft/occ. X 1.00 = 3,018
Receptacle 1.0c x 1,006 X 0.000 Watts/sgft x 3.41 Btuh/Watt X 1.00 = 0
rocess 1.0c x 1,006 x 0.000 Watts/sqft X 3.41 Btuh/Watt x 1.00 = 0
Infiltration: 1.00 x 1.064 x 1 006 x 10.00 x 0.50 /601 x 38 = 3 390
chedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 14,810
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 X 1,0061 X 300 Btuh/occ. / 1 100 sgft/occ. = 3 018
Receptacle 1 00 x 1,an x 0 000 Watts/sgft x I 3.4i3l BtuhlWatt =
Process 1.00 X 1,006 X 0.000 Watts/sgft xi 3.413 Btuh[Watt = 0
Infiltration: x ant x � x x � / 6] x � _
chedule Air Latent Area Ceiling Height ACH pyy
ROOM COOLING PEAK LOADS
Project Title
Corporate Centre Professional Plaza -Bldg 2
Date
1/11/2007
ROOM INFORMATION
DESIGN CONDITIONS
X
X
X
X
X
X
X
X
X
X
Room Name
zone 4
Time of Peak
Jul 2 pm
Floor Area
1,006
Outdoor Dry Bulb Temperature
111 °k
Indoor Dry Bulb Temperature
74 OF
Outdoor Wet Bulb Temperature
78 CIF
Conduction
Roof
LTlynI
Area
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
U -Value
0.0360
0.0740
DETD 1
76.6 =
36.5 =
25.0 =
42.2 =
Page Total
Orientation
Area
X
X
X
X
X
X
X
X
X
X
SGF
X
X
X
X
X
X
X
X
X
X
SC
Weighting
X
X
x
X
X
X
X
X
X
X
Factor
=
=
=
=
(N)
39.0
46
0.657
0.700
U
39.0
46
0.657
0.700
r
Page Total
Btu/hr
2,773
356
1,699
656
5 484
Btu/hr
825
825
1649
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
fights 1.0c X 1,006 X 0.740 Watts/sgft X 3.41 Btuh/Watt X 0.999 = 2,537
ccu ants 1.0c X 1,006 X 300 Btuh/OCC. / 10 sgft/OCc. X 1.00 = 3,018
Receptacle 1.0c x 1,006 X 0.000 Watts/sqft x 3.41 Btuh/Watt X 1.00 = 0
rocess 1.0c x 1,006 X 0.000 Watts/sgft x 3.41 Btuh/Watt x 1.00 = 0
Infiltration: FE�1.00 x 1.064 x 1 006 x 10.00 x 0.50 /601 x 38 = 3 390
"`Schedule Air Sensible Area Ceiling Height ACH i�sT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 16,078
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 X1006 X 3001 Btuh/OCC. / 100 sgft/occ. = 3018
Receptacle 1.00 x x Watts/sgft x Btuh/Watt =
Process 1.00 X 1,006 X 0.000 Watts/sgft x 3.413 Btuh/Watt = 0
Infiltration: x 4 771 x 1,006 x x � / 60] x �
chedule Air Latent Area Ceiling Height ACH pyy
ROOM COOLING PEAK LOADS
Project Title
Corporate Centre Professional Plaza -Bldg 2
Date
1/11/2007
ROOM INFORMATION
DESIGN CONDITIONS
X
X
X
x
x
X
X
X
X
x
Room Name
zone 5
Time of Peak
Jul 2 pm
Floor Area
1,006
Outdoor Dry Bulb Temperature
1119F
Indoor Dry Bulb Temperature
74 OF
Outdoor Wet Bulb Temperature
78 C�
Conduction
19
M
Area
21
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
U -Value
DETD 1
76.6 =
36.5 =
25.0 =
42.2 =
Page Total
Orientation
Area
X
X
X
x
x
X
X
X
X
X
SGF
X
X
X
x
x
X
X
X
X
x
SC
Weighting
X
X
X
X
X
X
X
X
X
X
Factor
=
=
=
=
=
=
(N)
39.0
46
0.657
0.700
(N)
39.0
46
0.657
0.700
Page Total
Btu/hr
2,773
356
1,699
656
5 484
Btu/hr
825
825
1649
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
fights 1.0 x 1,006 x 0.740 Watts/sgft x 3.41 Btuh/Watt x 0.999 = 2,537
ccu ants 1.0 X 1,006 X 300 Btuh/OCC. / 10 sgft/occ. X 1.00 = 3,018
Receptacle 1.0c x 1,006 X 0.000 Watts/sqft x 3.41 Btuh/Watt X 1.00 = 0
Process 1.0c X 1,006 X 0.000 Watts/sqft X 3.41 Btuh/Watt X 1.00 = 0
Infiltration: 1.00 x 1.064 x 1 006 x 10.00 x 0.50 /601 x 38 = 3 390
chedule Air Sensible Area Ceiling Height ACH Z�,T
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 16,078
Sched. Btu/hr
Latent Gain Frac. Area Heat Gain
ccu ants1.00 X 1 006 X 300 Btuh/OCC. / 100 Sgft/OCC. = 3 018
Receptacle 1.00 x 1 1111716 x 0000 Watts/sgft x Btuh/Watt =
Process 1.00 X 1,006 X 0.000 Watts/sgft X 1 3.413 Btuh/Watt = 0
Infiltration:� x� x 1 n�6 x x � / 6] x 000394 = 5Z
chedule Air Latent Area Ceiling Height ACH pyy
I
ROOM COOLING PEAK LOADS
Project Title
Corporate Centre Professional Plaza -Bldg 2
Date
1/11/2007
ROOM INFORMATION
DESIGN CONDITIONS
935.0
Room Name
zone 6
Time of Peak
Jul 3 pm
Floor Area
935
Outdoor Dry Bulb Temperature
112 C '
Indoor Dry Bulb Temperature
74 OF
Outdoor Wet Bulb Temperature
78 cl�
Conduction
Roof
Stud Wall
Area
X
X
X
X
X
X
X
X
X
U -Value
X
X
X
X
X
X
X
X
X
935.0
0.0360
152.0
0.0740
216.0
0.8700
407.0
0.0740
290.0
0.0740
(N)
42.0
41
0.657
0.798
(N)
18.0
41
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (`) denote conduction through an interior surface to another room.
Solar Gain
DETD '
71.8 =
37.8 =
26.2 =
40.2 =
40.3 =
Page Total
Orientation
Area
X
X
x
X
X
X
x
X
X
X
SGF
X
X
x
X
X
X
x
X
X
X
SC
Weighting
X
X
X
X
x
X
x
x
X
X
Factor
=
=
=
=
=
=
=
(N)
39.0
41
0.657
0.797
(N)
42.0
41
0.657
0.798
(N)
18.0
41
0.657
0.797
(N)
39.0
41
0.657
0.797
U
39.0
41
0.657
1.040
(E)
39.0
41
0.657
1.040
Page Total
Btu/hr
2,417
426
4,928
1,210
865
9 845
Btu/hr
837
903
386
837
1,092
1,092
5 146
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
fights 1.0c X 935 X 0.530 Watts/sqft X 3.41 BtuhfWatt x 0.999 = 1,691
ccu ants 11.0c X 935 x 300 Btuh/OCC. / 10 sqft/occ. x 1.00 = 2,805
Receptacle 1.0 x 935 x 0.000 Watts/sgft x 3.41 Btuh/Watt x 1.00 = 0
rocess 1.0 X 935 X 0.000 Watts/sqft X 3.41 Btuh[Watt X 1.00 = 0
Infiltration: 1.00 X 1.064 X 935 X 10.00 x 0.50 /601 X 38 = 3 151
chedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 22,638
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
ccu ants 1.00 x 935 X 3001 Btuh/OCC. / 100 sgft/occ. = 2 805
Receptacle 1.nn x x 0 Ono Watts/sgft x 1 3 4131 Btuh[Watt =
Process 1.00 x 935 x 0.000 Watts/sgft x 1 3.4131 BtuhfWatt = 0
Infiltration: oo xx x x � / 6] x zSpW = 1g
chedule Air Latent Area Ceiling Height ACH yy
ROOM COOLING COIL LOADS
Project Title
Corporate Centre Professional Plaza -Bldg 2
Date
1/11/2007
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
zone 1
Time of Peak
Jul 5 pm
Floor Area
655
Outdoor Dry Bulb Temperature
log tk
Indoor Dry Bulb Temperature
74`F
Outdoor Wet Bulb Temperature
77 OF
Conduction
Roof
Wall
Area
655.0
96.0
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
Orientation Area
(N) 39.0
(W) 39.0
(W) 39.0
U -Value
0.0360
0.0740
X 0.657
x 0.657
x 0.657
x
x
X
X
X
X
x
DETD 1
52.7 =
38.3 =
25.1 =
35.8 =
56.9 =
Page Total
Weighting
Factor
x 0.795 =
x 0.438 =
x 0.438 =
x =
X
X
x
x
x =
x =
Page Total
Btu/hr
1,243
272
2,553
358
1,714
6 139
Btu/hr
875
1,509
1,509
3 893
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
fights 1.0c x 655 x 0.757 Watts/sgft x 3.41 Btuh/Watt X 0.999 = 1,692
ccu ants 1.0c x 655 x 300 Btuh/OCC. / loc sgft/occ. x 1.00 = 1,965
Receptacle 1.0c x 655 x 0.000 Watts/sgft x 3.41 Btuh/Watt X 1.00 = 0
rocess 1.0 x 655 X 0.000 Watts/sqft X 3.41 Btuh[Watt x 1.00 = 0
Infiltration:1.00 X 1.064 X 655 X 10.00 x 0.50 /601 X 38 =
2 207
Ledule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 15,896
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 x 655 x 300 Btuhlocc. / 100 sgft/occ. = 1965
Receptacle 1.00 x x 0 Ono Watts/sgft x 3 413 Btuh/Watt =
Process 1.00 x 655 x 0.000 Watts/sqft x 3.413 Btuh/Watt = o
Infiltration: DOJ x 4 771 x x x 6] x o oo3s� = pg
chedule Air Latent Area Ceiling Height ACH pyy
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2 996
Energ pro By EnergySoft User Number: User Page: 52 of 57
ROOM COOLING COIL LOADS
Project Title
Corporate Centre Professional Plaza -Bldg 2
Date
1/11/2007
ROOM INFORMATION
DESIGN CONDITIONS
1,006.0
Room Name
zone 2
Time of Peak
Jul 3 pm
Floor Area
1,006
Outdoor Dry Bulb Temperature
112 OF
Indoor Dry Bulb Temperature
74`l�
Outdoor Wet Bulb Temperature
78 OF
Conduction
Roof
Double Metal Tinted Default I
Area
X
X
X
X
X
X
X
X
X
U -Value
X
X
X
X
X
X
X
X
X
1,006.0
0.0360
72.0
0.0740
138.0
0.8700
210.0
0.0740
0.657
0.797
(N)
42.0
41
0.657
0.798
(N)
18.0
41
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
DETD 1
71.8 =
37.8 =
26.2 =
40.3 =
Page Total
Orientation
Area
X
X
X
X
x
x
X
X
X
X
SGF
x
X
X
x
x
x
X
X
Xx
X
SC
Weighting
X
x
x
X
x
x
X
X
x
Factor
=
=
=
=
=
=
(N)
39.0
41
0.657
0.797
(N)
42.0
41
0.657
0.798
(N)
18.0
41
0.657
0.797
(N)
39.0
41
0.657
0.797
Page Total
Btu/hr
2,600
202
3,149
626
6 577
Btu/hr
837
903
386
837
2 962
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
i hts 1.0c x 1,006 x 0.740 Watts/sgft x 3.41 Btuh[Watt x 0.999 = 2,537
ccu ants 1.0c X 1,006 X 300 Btuh/OCC. / 10C sgft/occ. x 1.00 = 3,018
Receptacle 1.0c X 1,006 X 0.000 Watts/sgft x 3.41 Btuh/Watt x 1.00 = 0
rocess 1.0c X 1,006 x 0.000 Watts/sqft X 3.41 Btuh/Watt x 1.00 = 0
Infiltration: F 1.00 x 1.064 x 1006 x 10.00 x 0.50 /6] x 38 = 3390
"Schedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 18,484
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 x 1,0061 X 300 Btuh/OCC. / 100 sgft/occ. = 3 018
Receptacle 1.00 x x 0.000 Wafts/ sgft x I a4ul Btuh/Watt =
Process 1.00 X 1,006 x 0.000 Watts/sgft X 1 3.413 Btuh/Watt = o
Infiltration: x Latent
x � x x 6] x �
chedule Air Latent Area Ceiling Height ACH pyy
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 4 592
EnergyPro By EnergySoft User Number: User Page:53 of 57
ROOM COOLING COIL LOADS
(Project Title Date
Corporate Centre Professional Plaza -Bldg 2 1/11/2007
ROOM INFORMATION DESIGN CONDITIONS
Room Name zone 3 Time of Peak Jul 3 pm
Floor Area 1,006 Outdoor Dry Bulb Temperature 112 9F
Indoor Dry Bulb Temperature 74`F Outdoor Wet Bulb Temperature 78 `k
Conduction
Roof
Wall
Area
X
X
X
X
X
X
X
X
X
U -Value
1,006.0
0.0360
132.0
0.0740
78.0
0.8700'.
210.0
0.07401
41
0.657
0.797
(N)
39.0
41
0.657
0.797
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
DETD 1
X
X
X
X
X
X
X
X
X
71.8
=
=
=
=
=
=
=
=
=
37.8
26.2
40.3
Weighting
X
X
X
X
x
X
X
X
X
X
Factor
=
=
=
=
(M
39.0
Page Total
Orientation
Area
X
X
X
X
X
X
X
X
X
X
SGF
X
X
X
X
X
X
X
X
X
X
SC
Weighting
X
X
X
X
x
X
X
X
X
X
Factor
=
=
=
=
(M
39.0
41
0.657
0.797
(N)
39.0
41
0.657
0.797
Page Total
Btu/hr
2,600
370
1,780
626
5 376
Btu/hr
837
837
1 673
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
i hts 1.0 x 1,006 x 0.370 Watts/sqft xg3.41"
Btuh/Watt x 0.999 = 1,268
ccu ants 1.0 x 1,006 X 300 Btuh/OCC. / stgft/OCc. X 1.00 = 3,018
Receptacle 1.0 X 1,006 X 0.000 Watts/sqft XBtuh/Watt X 1.00 = 0
rocess 1.0 x 1,006 X 0.000 Watts/sgft X Btuh[Watt x 1.00 = 0
Infiltration: I 1.00 x 1.064 x 1 006 x 10.00 x 0.50 /601 x 38 = 3 390
—Schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 14,726
Sched. Btu/hr
Latent Gain Frac. Area Heat Gain
Occupants 1.00 X 1,0061 x 300 Btuh/OCC. / F 100 sgft/occ. = 3018
.Receptacle 1.00 x x 0 000 Watts/sgft x 1 3.4131 Btuh[Watt =
Process 1.00 X 1,006 X 0.000 Watts/sgft X 3.413 Btuh/Watt = 0
Infiltration: � x 4 771 x 1 1'00sJ x x/ 6] x= 1,574
chedule Air Latent Area Ceiling Height ACH pyy
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 4 592
EnergyPro By EnergySoft User Number: User Page: 54 of 57
ROOM COOLING COIL LOADS
Project Title
Corporate Centre Professional Plaza -Bldg 2
Date
1/11/2007
ROOM INFORMATION
DESIGN CONDITIONS
37.8
Room Name
Zone
Time of Peak
Jul 3pm
Floor Area
1,006
Outdoor Dry Bulb Temperature
112 �:
Indoor Dry Bulb Temperature
74`l:
Outdoor Wet Bulb Temperature
78 clZ
Conduction
Roof
Wall
Area
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
U -Value
1 0.03601
X
X
X
X
X
X
X
X
X
DETD 1
=
=
=
=
=
=
=
=
=
71.8
37.8
26.2
40.3
Factor
=
=
=
(N)
39.0
41
Page Total
Orientation
Area
X
X
X
X
X
X
X
X
X
X
SGF
X
X
X
X
X
X
X
X
X
X
SC
Weighting
X
X
x
x
X
X
X
X
X
X
Factor
=
=
=
(N)
39.0
41
0.657
0.797
(N)
39.0
41
0.657
0.797
Page Total
Btu/hr
2,600
370
1,780
626
5 376
Btu/hr
837
837
1,673
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
fights 1.0 X 1,006 x 0.740 Watts/sqft x 3.41 Btuh/Watt x 0.999 = 2,537
ccu ants 1.0 X 1,006 x 300 Btuh/OCC. / 10 sgft/OCc. X 1.00 = 3,018
eceptacle 1.0 x 1,006 x 0.000 Watts/sqft x 3.41 Btuh/Watt X 1.00 = 0
rocess 1.0 x 1,006 x 0.000 Watts/sqft X 3.41 Btuh/Watt x 1.00 = 0
Infiltration: F 1.00 x 1.064 x 1 006 x 10.00 x 0.50 / 6] x 38 = 3 390
chedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 15,994
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 X 1,0061 x 300 Btuh/occ. / 100 sgft/OCc. = 3 018
Receptacle 1.00 x x 0000 Watts/sgft xi 3 4 131 Btuh/Watt =
Process 1.00 X 1,006 X 0.000 Watts/sgft x 1 3.4131 Btuh/Watt = o
Infiltration: x Latent
x � x x � / 6] x egg = 11574
chedule Air Latent Area Ceiling Height ACH pyy
N
h
ROOM COOLING COIL LOADS
Project Title
Corporate Centre Professional Plaza -Bldg 2
Date
1/11/2007
ROOM INFORMATION
DESIGN CONDITIONS
X
X
x
X
X
X
X
X
x
x
Room Name
zone 5
Time of Peak
Jul 3 pm
Floor Area
1,006
Outdoor Dry Bulb Temperature
112 9F
Indoor Dry Bulb Temperature
74`F
Outdoor Wet Bulb Temperature
78 OF
Conduction
30 Roof
19 Metal
Area
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
U -Value
0.0360
0.0740
DETD '
71.8 =
37.8 =
26.2 =
40.3 =
Page Total
Orientation
Area
X
X
x
x
X
x
x
X
x
X
SGF
X
X
x
X
X
X
X
X
x
x
SC
Weighting
X
X
x
x
X
X
x
X
X
X
Factor
=
=
=
=
=
(N)
39.0
41
0.657
0.797
(N)
39.0
41
0.657
0.797
Page Total
Btu/hr
2,600
370
1,780
626
5 376
Btu/hr
837
837
1 673
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
i hts 1.0 x 1,006 x 0.740 Watts/sgft x 3.41 Btuh/Watt x 0.999 = 2,537
ccu ants 1.0c x 1,006 x 300 Btuh/OCC. / 10 sgft/occ. x 1.00 = 3,018
Receptacle 1.0c x 1,006 x 0.000 Watts/sqft x 3.41 Btuh/Watt X 1.00 = 0
rocess 1.0c x 1,006 X 0.000 Watts/sqft X 3.41 Btuh/Watt X 1.00 = 0
Infiltration: F 1.00 x 1.064 x 1 006 x 10.00 x 0.50 / 6 ] x 38 = 3 390
chedule Air Sensible Area Ceiling Height ACH QT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 15,994
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 x1006 I x 3001 Btuh/occ. / 100 sgft/occ. = 3018
Receptacle 1.00 x x Watts/sgft x Btuh/Watt =
Process 1.00 X 1,006 x 0.000 Watts/sgft X 1 3.413 Btuh/Watt = 0
Infiltration: ��� x x x x / 60] x 000394 = 5z4
schedule Air Latent Area Ceiling Height ACH pyy
t
ROOM COOLING COIL LOADS
Project Title
Corporate Centre Professional Plaza -Bldg 2
--]
Date
1/11/2007
ROOM INFORMATION
DESIGN CONDITIONS
935.0
Room Name
zone 6
Time of Peak
Jul 3 pm
Floor Area
935
Outdoor Dry Bulb Temperature
112 cl�
Indoor Dry Bulb Temperature
74`F
Outdoor Wet Bulb Temperature
78 OF
Conduction
30 Roof
19 Metal
Area
X
X
X
X
X
X
X
X
X
U -Value
X
X
X
X
X
X
X
X
X
935.0
0.0360
152.0
0.0740
216.0
0.8700
407.0
0.0740
290.0
0.0740
39.0
(E)
39.0
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
Orientation Area
(N)
39.0
(N)
42.0
(N)
18.0
(N)
39.0
(E)
39.0
(E)
39.0
SGF
SC
x 0.657
x 0.657
x 0.657
x 0.657
x 0.657
x 0.657
x
x
x
x
DETD 1
71.8 =
37.8 =
26.2 =
40.2 =
40.3 =
Page Total
Weighting
Factor
x 0.797 =
x 0.798 =
x 0.797 =
x 0.797 =
X 1.040 =
x 1.040 =
X
x =
x
X
Page Total
Btu/hr
2,417
426
4,928
1,210
865
9 845
Btu/hr
837
903
386
837
1,092
1,092
5 146
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
i hts 1.0 x 935 X 0.530 Watts/sgft x 3.41 Btuh[Watt x 0.999 = 1,691
ccu ants 1.0 x 935 x 300 Btuh/occ. / 10C sgft/occ. x 1.00 = 2,805
Receptacle 1.0 x 935 x 0.000 Watts/sqft x 3.41 Btuh/Watt x 1.00 = 0
rocess 1.0c x 935 x 0.000 Watts/sgft x 3.41 Btuh[Watt x 1.00 = 0
Infiltration: 1.00 x 1.064 x 935 x 10.00 x 0.50 / 60] x 38 = F 3 151
-Schedule Air Sensible Area Ceiling Height ACH Z1
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 7722,6738
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 x 935 x 3001 Btuh/OCC. /100 sgft/occ. = 2 805
Receptacle 1.0o x x Watts/sgft x 3.413 Btuh[Watt =
Process 1.00 x 935 x 0.000 Watts/sqft x 3.413 Btuh/Watt = o
Infiltration: x 7nt x � x x � / 6] x � _ 14
chedule Air Latent Area Ceiling Height ACH pyy
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 4726781
EnergyPro By EnergySoft User Number: User Page: 57 of 57 771